NOV 1519
Docket No. 50-261
License No. DPR-23
Carolina Power and Light Company
ATTN: Mr. Lynn W. Eury
Executive Vice President
Power Supply
P. 0. Box 1551
Raleigh, NC 27602
Gentlemen:
SUBJECT:
ENFORCEMENT CONFERENCE SUMMARY
(NRC INSPECTION REPORT NO. 50-261/91-20)
This letter refers to the Enforcement Conference held at our request on
November 6, 1991.
This meeting concerned activities authorized for your H. B.
Robinson facility. The issues discussed at this conference were design control
measures related to the loss of coolant analyses and overtemperature delta
temperature modifications. A list of attendees and a copy of your handout are
enclosed.
We are continuing our review of these issues to determine the
appropriate enforcement action.
In accordance with Section 2.790 of the NRC's "Rules of Practice," Part 2,
Title 10,
Code of Federal
Regulations,
a copy of this letter and its
enclosures will be placed in the NRC Public Document Room.
Should you have any questions concerning this matter, please contact us.
Sincerely,
Original signed by:
Ellis W. Merschoff
Ellis W. Merschoff, Acting Director
Division of Reactor Projects
Enclosures:
1. List of Attendees
2. Licensee Handout
cc w/encls:
C. R. Dietz, Manager
Robinson Nuclear Project Department
H. B. Robinson Steam Electric Plant
P. 0. Box 790
Hartsville, SC 29550
(cc w/encls cont'd - See page 2)
9112030053 911115
PDR ADOCK 05000261
Q
Carolina Power and Light Company
2
NOV1 5 1991
(cc w/encls cont'd)
R. H. Chambers, Plant General Manager
H. B. Robinson Steam Electric Plant
P. 0. Box 790
Hartsville, SC 29550
Heyward G. Shealy, Chief
Bureau of Radiological Health
Dept. of Health and Environmental
Control
2600 Bull Street
Columbia, SC 29201
Dayne H. Brown, Director
Division of Radiation Protection
N. C. Department of Environment,
Health & Natural Resources
P. 0. Box 27687
Raleigh, NC 27611-7687
McCuen Morrell, Chairman
Darlington County Board of Supervisors
County Courthouse
Darlington, SC 29535
Mr. H. Ray Starling
Manager -
Legal Department
P. 0. Box 1551
Raleigh, NC
27602
H. A. Cole
Special Deputy Attorney General
State of North Carolina
P. 0. Box 629
Raleigh, NC 27602
Robert Gruber
Executive Director
Public Staff -
NCUC
P. 0. Box 29520
Raleigh, NC 27626-0520
J. D. Kloosterman, Director
Regulatory Compliance
H. B. Robinson Steam
Electric Plant
P. 0. Box 790
Hartsville, SC
29550
bcc w/encls: (See page 3)
Carolina Power and Light Company
3
NOV 1 51991
bcc w/encls:
Document Control Desk
H. Christensen, RII
R. Lo, NRR
NRC Resident Inspector
U.S. Nuclear Regulatory Commission
Route 5, Box 413
Hartsville, SC 29550
RIIDRP
RI
RI :DRP
RII:DRP
asn:tj
HChstensen
DVerrelli
JJo son
11/141/91
11/h/i
/9
11//T-g1
1
/91
ENCLOSURE 1
LIST OF ATTENDEES
Carolina Power and Light Company
R. A. Watson, Senior Vice President, Nuclear Operations
C. R. Dietz, Vice President, Robinson Nuclear Project
G. E. Vaughn, Vice President, Nuclear Services
R. H. Chambers, General Manager, Robinson Nuclear Plant
A. M. Lucas, Manager, Nuclear Engineering Department (NED)
R. W. Prunty, Jr., Manager, Nuclear Licensing - Robinson
T. Clements, Manager, Transient Analysis
J. M. Curley, Manager, Special Projects, NED
R. M. Parsons, Manager, Robinson Engineering Support
M. F. Page, Manager, Technical Support
Nuclear Regulatory Commission
J. L. Milhoan, Deputy Regional Administrator, Region II (RII)
E. W. Merschoff, Acting Director, Division of Reactor Projects (DRP), RII
. J. R. Johnson, Deputy Director, DRP, RII
S. D. Rubin, Deputy Director, Division of Reactor Safety (DRS), RH
E. G. Adensam, Director, Project Directorate II-1, Office of Nuclear Reactor
Regulation (NRR)
G. R. Jenkins, Director, Enforcement and Investigation Coordination Staff
(EICS), RH
D. M. Verrelli, Chief, Reactor Projects Branch 1, DRP, Rh
H. 0. Christensen, Chief, Reactor Projects Section 1A, DRP, Rh
R. E. Carroll, Project Engineer, DRP, RII
B. Uryc, Senior Enforcement Specialist, EICS, RH
R. Lo, Project Manager, NRR
M. Caruso, Section Chief, Reactor Systems, NRR
J. G. Luehman, Office of Enforcement
D. H. Dorman, Office of Enforcement
C. Evans, Regional Counsel, RH
M. Markley, Licensing Programs Evaluation Branch, NRR
ENCLOSURE 2
CAROLINA POWER AND LIGHT COMPANY
H. B. ROBINSON UNIT NO. 2
ENFORCEMENT CONFERENCE
ATLANTA, GEORGIA
NOVEMBER 6, 1991
INTRODUCTION
PURPOSE
TO RESPOND TO "RECENTLY IDENTIFIED EXAMPLES
OF INADEQUATE ENGINEERING DESIGN CONTROLS
AND INTERFACES"
APPARENT VIOLATION OF 10CFR50, APPENDIX B
NRC INSPECTION REPORT NO. 50-261/91-20
NOT TO RESPOND TO TECHNICAL ISSUES ASSOCIATED
WITH H. B. ROBINSON'S POST-LOCA RESPONSE AND
ITS RELATIONSHIP TO REQUIREMENTS OF
10CFR50.46(B)(5)
FOLLOWUP MEETING IS BEING SCHEDULED
91-2932(1)
INTRODUCTION
OBJECTIVES
TO PROVIDE INFORMATION FROM INTERNAL
INVESTIGATION
CAUSAL FACTORS CONTRIBUTIVE TO
PERFORMANCE
TO PROVIDE ASSURANCE THAT CP&L MANAGEMENT
CONSIDERS PERFORMANCE TO BE OF SIGNIFICANT
CONCERN
RESPONSE WAS TIMELY AND COMPREHENSIVE
ISSUES WERE NOT INDIVIDUALLY SAFETY
SIGNIFICANT, BUT REPRESENTED AN ADVERSE
PERFORMANCE TREND
TO PROVIDE INFORMATION THAT ILLUSTRATES
SUBSTANTIVE PROCESSES, INTERFACE, AND
TECHNICAL CAPABILITY WITHIN ALL ELEMENTS OF
CP&L'S ENGINEERING ORGANIZATIONS
ACKNOWLEDGED DEFICIENCIES VERSUS
"SIGNIFICANT DEFICIENCIES"
91-2932(2)
INTRODUCTION
AGENDA
OPENING REMARKS ..............
C. R. DIETZ
EVENTS REVIEW
OT DELTA T EVENT ............
M. F. PAGE
POST LOCA COOLING EVENT . ......
T. B. CLEMENTS
MANAGEMENT OVERVIEW/ExPECTATIONS .
.
.
.
.
R. H. CHAMBERS
ENGINEERING INITIATIVES
NUCLEAR FUELS ............
T. B. CLEMENTS
TECHNICAL SUPPORT... . .. . .
..
.
.
.
M. F. PAGE
NUCLEAR ENGINEERING .
.
.
.
.
.
.
.
.
R. M. PARSONS
CONCLUSION .
.
.
..............
C. R. DIETZ
91-2932(3)
MANAGEMENT OVERVIEW
CONCERNS
REPETITIVE PERFORMANCE ISSUES
FUEL ANALYSES
DESIGN CONTROLS
ISSUES
UNDETECTED SIMILAR DEFICIENCIES
ENGINEERING PROCESS, CAPABILITY, AND
CONTROL
TIMELINESS OF CORRECTIVE ACTIONS AND
IMPROVEMENTS
91-2932(4)
AGENDA
OPENING REMARKS
.............
C.
R. DIETZ
EVENTS REVIEW
OT DELTA T EVENT.
.
........... M. F. PAGE
POST LOCA COOLING EVENT . ......
T. B. CLEMENTS
MANAGEMENT OVERVIEw/EXPECTATIONS .
. .
. .
R. H. CHAMBERS
ENGINEERING INITIATIVES
NUCLEAR FUELS .
...........
T. B. CLEMENTS
TECHNICAL SUPPORT .
..M............
F. PAGE
NUCLEAR ENGINEERING . ........
R. M. PARSONS
CONCLUSION . ................
C. R. DIETZ
91-2932(5)
OTAT EVENT
CHRONOLOGY
VENDORS PROVIDE EXPERTISE FOR
1988/1990
REFUELING RTD RESPONSE TIME
TESTING
REACTOR ENGINEER RTD RESPONSE
AUG. 5-6, 1991
TIME TESTING TRAINING
REACTOR ENGINEER QUESTIONS
AUG. 14, 1991
PROCESS (SYSTEM ENGINEER
INVOLVED)
SYSTEM ENGINEER
AUG. 15, 1991
DISCOVERS/QUESTIONS FILTER
CAPACITORS
CONFIRMS FILTER CAPACITORS'
AUG. 16, 1991
POTENTIAL IMPACT ON SAFETY
ANALYSES
POTENTIAL UNANALYZED CONDITION -
AUG. 16, 1991
PLANT SHUTDOWN
REVIEW OF OTHER CIRCUITS
AUG. 17, 1991
COMPLETE
MODIFICATION REMOVED FILTER
AUG. 18, 1991
CAPACITORS
UNIT RETURNED TO POWER
AUG. 18, 1991
91-2932(6)
OTAT EVENT
INVESTIGATION
SITE SENIOR MANAGEMENT
CONCERN WITH POTENTIAL SIGNIFICANCE OF EVENT
CONCERN WITH PREVIOUS EVENTS
-
OTAT ISSUES
-
THREE PART INVESTIGATION
ROOT CAUSE/CORRECTIVE ACTIONS
DETERMINE LINKAGE WITH OTHER EVENTS
DETERMINE SAFETY SIGNIFICANCE
91-2932(7)
OTAT EVENT
INVESTIGATION
(CONTINUED)
TEAM MEMBERSHIP
NUCLEAR SERVICES DEPARTMENT (LEADER)
HARRIS PLANT - REACTOR ENGINEER
ROBINSON PLANT - REACTOR ENGINEER
ROBINSON PLANT - CORRECTIVE ACTION PROGRAM
REPRESENTATIVE
0
NUCLEAR ASSESSMENT DEPARTMENT - ONSITE
REPRESENTATIVE
NUCLEAR ASSESSMENT DEPARTMENT - HARRIS PLANT
REPRESENTATIVE
TEAM TRAINED IN ROOT CAUSE ANALYSIS
6 MAN-MONTH EFFORT
-
INTERVIEWS
-
DOCUMENT SEARCHES
-
PROCESS REVIEWS
-
ORGANIZATION REVIEWS
91-2932(8)
OTAT EVENT
RESULTS
NO DIRECT LINKAGE BETWEEN OTAT (CAPACITOR) EVENT
AND PREVIOUS OTAT EVENTS, ALTHOUGH CAUSAL FACTORS
SIMILAR
.
0
DETERMINED 2 ROOT CAUSES WITH SEVERAL SECONDARY
CAUSAL FACTORS
91-2932(9)
OTAT EVENT
ROOT CAUSES
VENDOR FAILED TO INCLUDE DESIGN BASIS REQUIREMENT
INTO FIELD DESIGN, INSTALLATION AND TESTING
DOCUMENTS
CP&L REVIEWS FAILED TO DETECT OMISSION
0
AREAS FOR IMPROVEMENT IDENTIFIED IN SYSTEM
ENGINEERING
LEVEL OF SPECIFIC SYSTEM/COMPONENT SKILL
COMPLEXITY OF SYSTEM
LEVEL OF SYSTEM TRAINING
MOD EXPEDITED - SOME REVIEWS WAIVED
LEVEL OF REVIEWS
91-2932(10)
OTAT EVENT
CORRECTIVE ACTIONS
PROVIDE EMPHASIS TO ASSURE IN-DEPTH/RIGOROUS
TECHNICAL REVIEWS (COMPLETE)
REINFORCE SUPERVISORY ASSIGNMENT OF PERSONNEL
COMMENSURATE WITH JOB FUNCTION OR JOB SKILL
(ONGOING)
.
0
PROVIDE A SYSTEM ENGINEER FOR RPS (COMPLETE)
DESIGNATE NED AS DESIGNER OF RECORD FOR RPS
(COMPLETE)
REQUIRE DBD FOR ALL RPS MODS (COMPLETE)
DEVELOP OTAT PROCESS/INSTRUMENTATION SCALING
CALCULATIONS (3/92)
TRAINING ON SCALING DOCUMENT (6/92)
91-2932(11)
OTAT EVENT
SAFETY SIGNIFICANCE
OTAT FUNCTION WOULD PROVIDE REACTOR TRIP TO MEET
MDNBR REQUIREMENTS
0
REANALYSIS OF CYCLES 13 AND 14 WITH LAG IN
CIRCUIT DEMONSTRATED PARAMETERS REMAINED WITHIN
APPLICABLE LIMITS
THE TWO SECOND LAG IN CIRCUIT RESULTED IN NO
SAFETY SIGNIFICANCE
91-2932(12)
AGENDA
OPENING REMARKS...
.
.
.
........
C.
R. DIETZ
EVENTS REVIEW
OT DELTA T EVENT ... ............M. F. PAGE
POST LOCA COOLING EVENT . ......
T. B. CLEMENTS
MANAGEMENT OVERVIEWEXPECTATIONS .
.
. .
.
R. H. CHAMBERS
ENGINEERING INITIATIVES
NUCLEAR FUELS .
...........
T. B. CLEMENTS
TECHNICAL SUPPORT.
.
......... .
M. F. PAGE
NUCLEAR ENGINEERING .
.
.
.
.
.
.
.
.
R. M. PARSONS
CONCLUSION .................
C. R. DIETZ
91-2932(13)
POST LOCA COOLING EVENT
CHRONOLOGY
WESTINGHOUSE CORRESPONDENCE
1987
SINGLE SI PUMP MODIFICATION
1988
19-CASE SBLOCA ANALYSES
1988
DESIGN ACTIVITY 89-0001
1989
(EPP-9 REV.)
1991
O *
IPE INQUIRY
MAY 8
ERROR CONFIRMED - POWER
MAY 14
REDUCTION INITIATED
INTERIM ANALYSIS - RETURN TO 90%
MAY 14
POWER (95% JUSTIFIED (ANS 1979)
WITH 7000F PCT LIMIT)
REANALYSIS - ANS 1971
MAY 16
(92.5% JUSTIFIED WITH 700OF PCT
LIMIT)
REANALYSIS/RETURN TO 100% POWER
MAY 29
91-2932(14)
POST LOCA COOLING EVENT
DEFICIENCY
INVESTIGATED BY MANAGEMENT INITIATED "ADVERSE
CONDITION REPORT" (ACR)
PERSONNEL ERROR -
FAILED TO CONSIDER ENTRAINMENT IN
DESIGN ANALYSIS 89-0001
CAUSES
LIMITED DOCUMENT SEARCH
PRIOR VENDOR CORRESPONDENCE OVERLOOKED
DESIGN BASIS DOCUMENT (DBD)
NOT INCORPORATED
INTO REVIEW
MISUNDERSTOOD USE OF TERM "NATURAL CIRCULATION"
INADEQUATE FOLLOW-UP WITH VENDOR
91-2932(15)
POST LOCA COOLING EVENT
CORRECTIVE ACTIONS
EVENT TRAINING (7/91)
-
ADEQUATE DOCUMENT SEARCH
-
USE OF DBDs
-
APPROPRIATE USE OF ANS DECAY HEAT
ELECTRONIC DATABASE SEARCH CAPABILITY (8/91)
91-2932(16)
POST LOCA COOLING EVENT
SAFETY SIGNIFICANCE
CORRECTIVE ANALYSES CONFIRMED ERROR RESULTED IN
NO SAFETY SIGNIFICANCE
.
0
ADDITIONAL ANALYSES PERFORMED TO ANSWER NRC
QUESTIONS CONFIRMED CP&L'S ENGINEERING JUDGEMENT
91-2932(17)
AGENDA
OPENING REMARKS
.*....*.
.
.
.
C. R. DIETZ
EVENTS REVIEW
OT DELTA T EVENT .M............
.. F. PAGE
POST LOCA COOLING EVENT .
.
.
. .
.
.
T. B. CLEMENTS
MANAGEMENT OVERVIEW/EXPECTATIONS .
.
.
.
.
R. H. CHAMBERS
ENGINEERING INITIATIVES
NUCLEAR FUELS . ...........
T. B. CLEMENTS
TECHNICAL SUPPORT .
.
.
.
.
M........
. F. PAGE
NUCLEAR ENGINEERING .
.
.
.
.
.
.
.
.
R. N. PARSONS
CONCLUSION . ...............
.
C. R. DIETZ
91-2932(18)
H. B. ROBINSON UNIT 2
ENGINEERING ORGANIZATIONS
NUCLEAR
GENERATION
NUCLEAR
NUCLEAR
ROBINSON
ENGINEERING
SERVICES
NUCLEAR
PROJECT
ROBINSON
NUCLEAR
TECHNICAL
ENGINEERING
FUELS
SUPPORT
SUPPORT
91-2932(19)
DESIGN CONTROL IMPLICATIONS OF EVENTS
LEVEL OF ASSIGNMENT COMMENSURATE WITH COMPLEXITY OF
TASK
RELIANCE ON EXPERTISE OF VENDORS...RESULTED IN LACK
OF RIGOROUS/INDEPTH IN-HOUSE REVIEWS
PERSONNEL RELUCTANT TO "RAISE FLAG" WHEN JOB
ASSIGNMENT MIGHT EXCEED WORK SKILLS OR PRESCRIBED
SCHEDULE
LEVEL OF TECHNICAL CAPABILITY/TOOLS
OTHER AREAS RECOGNIZED
-
NEED FOR ADDITIONAL TRAINING
-
MORE CRITICAL SELF-ASSESSMENT
-
IMPROVED COMMUNICATIONS
-
IMPROVED INTERFACE
CHRONOLOGY OF MAJOR EVENTS/CONTINUUM OF IMPROVEMENT
91-2932(20)
AGENDA
INTRODUCTION.......
.
.
.
.
.
.
.
.
.
C. R. DIETZ
OT DELTA T EVENT.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
1. F.
PAGE
POST LOCA COOLING EVENT .........
T. B. CLEMENTS
MANAGEMENT OVERVIEW ...........
R. H. CHAMBERS
ENGINEERING INITIATIVES
NUCLEAR FUELS . ...........
T. B. CLEMENTS
TECHNICAL SUPPORT . .M..........
N. F. PAGE
NUCLEAR ENGINEERING . ........
R. N. PARSONS
CONCLUSION .
.................
C. R. DIETZ
91-2932(21)
NUCLEAR FUELS
IMPROVEMENTS
DESIGN BASIS REFERENCE PROCEDURE
1988
ON DISTRIBUTION FOR KEY VENDOR
1989
DOCUMENTS
WOG ANALYSIS SUBCOMMITTEE
1989
.
PLANT PARAMETER LIST
1989
QUALIFIED SAFETY REVIEWER
1990
TRAINING
VERIFICATION RECORD PROCEDURE
1991
REVISION
NFS/NED INTERFACE AGREEMENT
1991
DESIGN BASIS DOCUMENTATION
ONGOING
ROTATIONAL ASSIGNMENTS
ONGOING
PLANT RECORDS DATABASE ACCESS
1992
91-2932(22)
NUCLEAR FUELS
IMPROVEMENTS
SUMMARY
DESIGN CONTROL PROCESS WORKS
HIGHLY QUALIFIED PERSONNEL
DESIGN PHILOSOPHY ENCOURAGES IMPROVEMENT/DEFICIENCY
IDENTIFICATION
CORRECTIVE ACTIONS PROMPTLY IMPLEMENTED UPON
DEFICIENCY IDENTIFICATION
PHILOSOPHY TO LEAVE MARGIN IN ANALYSIS
WITH THE CONTINUALLY IMPROVING PROCESS MISTAKES WILL
BE MINIMIZED
91-2932(23)
AGENDA
OPENING REMARKS.............
.
C. R. DIETZ
EVENTS REVIEW
OT DELTA T EVENT . . ..........
N. F. PAGE
POST LOCA COOLING EVENT . ......
T. B. CLEMENTS
MANAGEMENT OVERVIEW/ExPECTATIONS .
. .
.
.
R. H. CHAMBERS
ENGINEERING INITIATIVES
NUCLEAR FUELS
.
.
.....
T. B. CLEMENTS
TECHNICAL SUPPORT . . . ...
N. F. PAGE
NUCLEAR ENGINEERING .o.
.. .....
R. N. PARSONS
CONCLUSION ..............
.
.
C. R.DIETZ
91-2932(24)
TECHNICAL SUPPORT
IMPROVEMENTS
MISSION
PROVIDE TECHNICAL EXPERTISE AND MANAGEMENT TO ASSURE
THAT THE TECHNICAL SUPPORT NECESSARY FOR SAFE, RELIABLE
OPERATION OF H. B. ROBINSON UNIT 2 IS PROVIDED.
OUR MISSION IS ACCOMPLISHED THROUGH THE INTEGRATION OF
PROACTIVE SYSTEM ENGINEERING INTO DAY TO DAY SITE
ACTIVITIES; THE DEVELOPMENT, APPLICATION,
ADMINISTRATION, AND MAINTENANCE OF PLANT PROGRAMS; THE
APPLICATION OF COMPONENT AND TECHNICAL EXPERTISE; AND
EFFECTIVE UTILIZATION OF COMPANY WIDE RESOURCES.
91-2932(25)
TECHNICAL SUPPORT
IMPROVEMENTS
TECHNICAL SUPPORT FIRST/LAST LINE PLANT INTERFACE FOR
MANY ORGANIZATIONS
PROCUREMENT ENGINEERING
OUTAGE AND MODS
.
0
NUCLEAR FUELS
NUCLEAR ENGINEERING DEPARTMENT
NUCLEAR SERVICES DEPARTMENT
MATERIALS LAB
TRANSMISSION
NDE SERVICES
VENDORS
TECH REPS
91-2932(26)
TECHNICAL SUPPORT
IMPROVEMENTS
OBSERVATIONS PRIOR TO AUGUST 1989
UNDEFINED/AMBIGUOUS INTERFACES
INSUFFICIENT RESOURCES VS DEMANDS
SYSTEM ENGINEERS INEFFECTIVE
. *
HIGH PERSONNEL TURNOVER
INADEQUATE TRAINING ON SPECIFIC FUNCTIONAL
ACTIVITIES
LACK OF CULTIVATION OF DESIGN QUESTIONING ATTITUDES
ACCOUNTABILITIES/RESPONSIBILITIES/EXPECTATIONS NOT
EFFECTIVELY DELINEATED
REVIEW METHODS INCONSISTENT/UNDEFINED
91-2932(27)
TECHNICAL SUPPORT
IMPROVEMENTS
INCREASE AVAILABLE PERSONNEL RESOURCES
REALIGN RESOURCES TO FOCUS ON FUNCTIONS
DEFINE AND COMMUNICATE RESPONSIBILITIES
INITIATE PROGRAMS TO ASSURE CONSISTENCY IN
METHODOLOGY
PROVIDE DEVELOPMENT OF SYSTEM ENGINEERS; ALLOW
REMOVAL OF COLLATERAL DUTIES AND
SYSTEM/COMPONENT/FUNCTION SPECIFIC TRAINING
91-2932(28)
TECHNICAL SUPPORT
IMPROVEMENTS
CHANGES/CAPABILITIES
RESOURCES INCREASED:
34 FULL TIME (AUG. 1989)
50 FULL TIME (NOW)
25 NEW TO TECH SUPPORT SINCE AUG. 1989'
- 6 EXPECTED BY 1992
0
19 CONTRACTOR SUPPORT PERSONNEL
REALIGNED PERSONNEL:
MECHANICAL SYSTEMS
ELECTRICAL SYSTEMS
Rx ENG & BOP SYSTEMS
PROGRAMS
SUPPORT
OUTAGE COORDINATOR
91-2932(29)
TECHNICAL SUPPORT
IMPROVEMENTS
CHANGES/CAPABILITIES
(CONTINUED)
DEFINED, DOCUMENTED AND COMMUNICATED TECHNICAL SUPPORT
MISSION AND VISION
DEFINED, DOCUMENTED AND COMMUNICATED ACCOUNTABILITIES,
EXPECTATIONS, AND RESPONSIBILITIES IN A CONDUCT OF
- OPERATIONS DOCUMENT, THROUGH FORMAL TRAINING, AND ONE
ON-ONE COUNSELING
PROCEDURALIZED
-
CONDUCT OF OPERATION
-
REVIEW METHODOLOGY
-
SYSTEM ENGINEER PROGRAM
-
COMPONENT ENGINEER PROGRAM
-
PERSONNEL CERTIFICATION PROCESS
-
MOD WALKDOWNS/REVIEWS
91-2932(30)
TECHNICAL SUPPORT
IMPROVEMENTS
CHANGES/CAPABILITIES
(CONTINUED)
TRAINING PLANS DEVELOPED FOR EACH PERSON
ATTENTION TO FUNCTIONAL SPECIFIC TRAINING INCREASED
(8000 HOURS IN 1991)
3 CERTIFIED SYSTEM ENGINEERS
20 ACTIVE SYSTEM TEAMS
RESULTS HAVE DEMONSTRATED A SIGNIFICANT INCREASE IN
SYSTEM/COMPONENT OWNERSHIP, INTERFACE BETWEEN GROUPS,
TECHNICAL KNOWLEDGE OF PERSONNEL, ABILITY TO ASSIGN
WORK/REVIEWS TO QUALIFIED PERSONNEL, AND ABILITY TO
PERFORM REVIEWS.
91-2932(31)
- '
TECHNICAL SUPPORT
IMPROVEMENTS
SUMMARY
RESULTS OF OUR PROGRESS TO DATE IS PARTIALLY WHY WE
ARE HERE... CONTINUED PROGRESS IS WHY WE WON'T BE
BACK.
. *
PROBLEMS IDENTIFIED-REINFORCED THAT OUR CURRENT
IMPROVEMENT PLANS AND ACTIVITIES ARE APPROPRIATE.
CONTINUED ATTENTION TO INTERFACE DEVELOPMENT AND
ONGOING TRAINING MUST BE MAINTAINED.
DEMONSTRATION OF AN IMPROVING PROCESS INDICATES THE
BUILDING OF AN INFRASTRUCTURE WHERE MISTAKES WILL BE
MINIMIZED.
91-2932(32)
AGENDA
OPENING REMARKS ...............
C. R. DIETZ
EVENTS REVIEW
OT DELTA T EVENT
.
.
.
.
.
.
.
.
1. F. PAGE
POST LOCA COOLING EVENT .
.
. .
. .
.
T. B. CLEMENTS
MANAGEMENT OVERVIEW/EXPECTATIONS .
.
.
.
.
R. H. CHAMBERS
ENGINEERING INITIATIVES
NUCLEAR FUELS.... . . .
.
.
.
... T. B. CLEMENTS
TECHNICAL SUPPORT........ .. .
.
M. F. PAGE
NUCLEAR ENGINEERING . ........
R. M. PARSONS
CONCLUSION . ......
.......
.
C. R. DIETZ
91-2932(33)
e-
AASTAT
ENGINEERING IMPROVEMENTS
--
AFW ISSUES
MOD t016
OTTOTAT
OTAT
9MS
11
1990
1991
I
1992
MANAGEMENT INITIATIVES
COO-ENGINEER
OF RECORD
MORE FORMAL WALKDOWNS
INSTILL OWNERSHIP OF
REINFORCE OWNERSHIP OF
VENDOR PRODUCTS
VENDOR DES IGNS
ESTABLISHED GUIDELINE ON
STRICTER ADMIN.
CHECK LIST
ADDITIONAL DISCIPLINE TO
DEDICATED TO RNP
DURATIONS FOR MOD DESIGNS
ASSIGNING OF WORK
STRICTER REVIEWER
COO -
SPECIALIZED SUPPORT
CHECK LISTS
FUELS PLANT PARAMETERS
BEGAN ASSESSING
DOCUMENT
FIELD REVISIONS
ON -
SITE NED
MOOOTERITED
NED/FUELS
INTERFACE
DOCUMENT
ITOOLS
3 DBDe WRITTEN
5 DBDs WRITTEN
3 050s WRITTEN
2 D0 VALIDATIONS
3 OBD
WRITTEN
(4 VALIDATED)
(4 VALIDATED)
(4 VALIDATED)
PLUS CLOSEDUTS
CAD CAPABILITY
FUELS PLANT
ECCS SINGLE
EOG ELECTRICAL
DC ELECTRICAL
(INTERFERENCE CHECKS)
PARAMETERS
FAILURE ANALYSIS
CALCULATIONS
CALCULATIONS
STARTED PRA
4Ov VOLTAGE
DROP CALCULAT IONSBOP
050.
DESIGN GUIDE FOR CHECKING
PIPE DOCUMENTS
SUBMIT PRA
SURROGATE VIDEO TOUR
SKILLS.
NCSU I N-HOUSE CIVIL
PROFESSIONAL ENGINEER
ADDED 30
SYSTEMS TRAINING
SEISMIC TRAINING
PUSH (25 IN RESS)
INFRASTRUCTURE SLOTS
(16 ENGINEERS)
INSTITUTED REAL TIME
33,000 HOURS IN
TRAINING
TRAINING (YTO)
16,000 HOURS IN
TRAINING
L------------------------------------------------------------------------------
-
NUCLEAR ENGINEERING
IMPROVEMENTS
SUMMARY
EVENTS CITED SHOW THAT OUR EMPHASIS ON ENGINEERING
IMPROVEMENT IS APPROPRIATE. WE INTEND TO CONTINUE TO
IMPROVE THE TOOLS, SKILLS AND PROCESSES THAT SHAPE THE
DESIGN OUTPUTS.
ROBINSON ENGINEERING SUPPORT IS CONTINUING TO SEEK
OPPORTUNITIES TO IMPROVE OUR PRODUCTS BY:
REINFORCING OWNERSHIP OF VENDOR DESIGNS
ADDITIONAL DISCIPLINE TO THE PROCESS OF ASSIGNING
WORK
COMPLETING DBDs
ROBINSON SPECIFIC PRA
TRAINING (SYSTEMS, REAL TIME, TOPICAL)
CONTINUING IMPROVEMENT IS RESULTING, AND HAS RESULTED,
IN A MORE COMPETENT ENGINEERING STAFF WHERE MISTAKES
WILL BE MINIMIZED.
91-2932(35)
AGENDA
OPENING REMARKS
...............
C.
R.
DIETZ
EVENTS REVIEW
OT DELTA T EVENT.
.
........... M. F. PAGE
POST LOCA COOLING EVENT . ......
T. B. CLEMENTS
MANAGEMENT OVERVIEW/ExPECTATIONS .
.
.
. .
R. H. CHAMBERS
ENGINEERING INITIATIVES
NUCLEAR FUELS ............
T. B. CLEMENTS
TECHNICAL SUPPORT.......
.
.
.
.
.
M. F. PAGE
NUCLEAR ENGINEERING .
.
.......
R. M. PARSONS
CONCLUSION .
.
.
.
.
.
.
.
.
........
C. R. DIETZ
91-2932(36)
CONCLUSIONS
- SIGNIFICANCE
EVENTS,
WHEN ANALYZED,
REPRESENTED NO SAFETY
SIGNIFICANCE IN AND OF THEMSELVES
EVENTS,
IN AGGREGATE,
CAUSED SIGNIFICANT
MANAGEMENT CONCERN RELATED TO ABILITY TO
EFFECTIVELY CONTROL THE ROBINSON DESIGN BASIS
WITH THE ELEMENTS OF CONCERN FOCUSING ON:
DESIGN PROCESS AND RELATED TECHNICAL REVIEW
FUNCTION
TECHNICAL CAPABILITY OF VENDORS, STAFF, AND
TECHNICAL REVIEWERS
ADEQUACY AND TIMELINESS OF PERFORMANCE
IMPROVEMENTS
91-2932(37)
CONCLUSIONS
SUMMARY
DISCOVERY WAS PRODUCT OF PHILOSOPHY AND
MANAGEMENT PRINCIPLES THAT SERVE AS CORNERSTONE
OF ENGINEERING AND DESIGN ACCOUNTABILITIES.
THAT IS:
SELF-ASSESSMENT
-
SELF-DISCLOSURE
-
OPERATIONAL SKEPTICISM
CONSERVATIVE DECISIONS
-
PROTECT THE CORE
-
"WALK THE TALK"
91-2932(38)
CONCLUSIONS
THERE ARE NOT SIGNIFICANT DEFICIENCIES IN
H. B. ROBINSON'S DESIGN CONTROL PROCESS
DESIGN CONTROL RESULTED IN IDENTIFICATION OF
ERROR
ACTIONS WERE PROACTIVE, CONSERVATIVE, AND
COMPREHENSIVE TO ASSURE:
MINIMAL SAFETY SIGNIFICANCE
DESIGN BASIS FOR H. B. ROBINSON IS SOUND TODAY
EFFECTIVE INTER/INTRA-DEPARTMENTAL
COMMUNICATIONS
CAPABLE AND IMPROVING ENGINEERING
WELL STRUCTURED AND DISCIPLINED ENGINEERING
PROCESS
ESCALATED ENFORCEMENT IS NOT WARRANTED FOR THE
ISSUES DISCUSSED TODAY
SELF IDENTIFICATION
TIMELY AND CONSERVATIVE RESPONSE TO ISSUES
MINIMAL SAFETY SIGNIFICANCE