oq InRl REferTo UNITED STATES NUCLEAR REGULATORY COMMISSION REGION 11 101 MARIETTA ST., N.W., SUITE 3100c S ATLANTA, GEORGIA 30303 FEB 8 1980 In Reply Refer To:
RII:JPO 50-325, 50-324 50-400, 50-401 50r-402, 50-403 Carolina Power and Light Company ATTN:
J.
A. Jones Senior Executive Vice President 4
and Chief Operating Officer 411 FayMtteville Street Raleigh, North Carolina 27602 Gentlemen:
The enclosed IE Information Notice is forwarded to you for information. No written response to this Information Notice is required.
If you have any questions related to the subject, please contact this office.
Sincerely, ATT:James P. O'Reilly Director
Enclosures:
- 1.
IE Information Notice io. fo-05
- 2.
List of Recently Issued IE Information Notices 4
tc SincerelyO
FED 819g0 Carolina Power and Light Company
-2 cc w/encl:
A. C. Tollison, Jr.
Plant Manager Box 458 Southport, North Carolina 28461 R. Parsons, Site Manager.
Post Office Box 101 New Hill, North Carolina 27562 R. B. Starkey, Jr., Plant Manager Post Office Box 790 Hartsville, South Carolina 29550 4
SSINS No.:
6870 Accession No.:
UNITED STATES 7912190673 NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C. 20555 February 8, 1980 IE Information Notice No. 80-05 HLORIDE CONTAMINATION OF SAFETY RELATED PIPING AND COMPONENTS A Bechtel Power Corporation Study at the Wolf Creek Project has revealed that a fire retardent coating is potentially corrosive in contact with stainless steel.
Albi "Duraspray" is a fire retardent coating which contains magnesium oxychloride, and is used for fireproofing of exposed structural steel in some Nuclear Power Plants.
There appears to be no deleterious effect when it is applied over unprimed, inorganic zinc coated, or galvanized steel, however, it may be corrosive in contact with stainless steel, bare aluminum or copper. Droppings or overspray of this material cannot be properly removed with water. Diluted Nitric acid has been proven to be a useful cleanser, however, it presents a safety hazard.
Applicants and holders of construction permits and licensees of operating power reactors are advised to protect all stainless steel, copper and aluminum material from overspray and droppage of cementitious oxychloride materials and to remove accidently applied materials immediately and completely employing strict safety precautions during the process.
Special attention should be given to weld areas in any removal procedures.
No written response to this information notice is required. If you require additional information regarding this matter contact the Director of the appropriate NRC Regional Office.
IE Information Notice No. 80-05 Enclosure February 8, 1980 RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued To Notice No.
Issued 80-05 Chloride Contamination of 2/8/80 All holders of power Safety Related Piping and reactor OLs and CPs Components 80-04 BWR Fuel Exposure in 2/4/80 All BWR's holding a Excess of Limits power reactor OL or CP 80-03 Main Turbine Electro-1/31/80 All holders of power Hydraulic Control System reactor OLs aqd CPs 80-02 8X8R Water Rod Lower 1/25/80 All BWR Facilities End Plug Wear holder power reactor OLs or CPs 80-01 Fuel Handling Events 1/4/80 All holders of power reactor OLs and CPs 79-37 Cracking in Low Pressure 12/28/79 All power reactor OLs Turbine Discs and CPs 79-36 Computer Code Defect in 12/31/79 All power reactor OLs Stress Analysis of Piping and CPs Elbow 79-35 Control of Maintenance 12/31/79 All power reactor facilities and Essential Equipment with an OL or CP 79-34 Inadequate Design of 12/27/79 All holders of power reactor Safety-Related Heat Exchangers OLs and CPs 79-33 Improper Closure of Primary 12/21/79 All power reactor facilities Containment Access Hatches holding OLs and CPs 79-32 Separation of Electrical 12/21/79 All power reactor facilities Cables for HPCI and ADS holding OLs and CPs 79-31 Use of Incorrect Amplified 12/13/79 All holders of power reactor Response Spectra (ARS)
OLs and CPs 79-30 Reporting of Defects and 12/6/79 All power reactor facilities Noncompliance, 10 CFR Part 21.