Building Demolition Survey Packages Buffalo Materials Research Center Prepared for:

Universit amt Buffalo 193 The State nwersity of New York Buffalo Material Research Center Office of Environment, Health, and Safety Services Completed by:

OENERCON Excellence-Every project Every day 4490 Old William Penn Hwy Murrysville, PA 15668 May 16, 2014

Building Demolition Survey Packages Buffalo Materials Research Center Prepared for:

UNIVersity at muff.le 14&

The State Univeity of New York Buffalo Material Research Center Office of Environment, Health, and Safety Services Completed by:

OENERCON Excellence-Every project Every day 4490 Old William Penn Hwy Murrysville, PA 15668 May 16, 2014

OENERCON Table of Contents Survey Package Location Identification ID RCD-001 Control Deck North RCD-002 Control Deck South RGD-001 Gamma Deck North RGD-002 Gamma Deck South RND-001 Neutron Deck North RND-002 Neutron Deck South ADM-1OK-001 1 Ok Tank Room ADM-BR-001 Boiler Room ADM-100 First Floor of Administration Building ADM-115 Room 115 ADM-1K-001 1k Tank Room RBC-201 Control Deck Rooms ADM-000-4 N 16 Tank Room ADM-000-5 1k Tank Room Pit ADM-001-1 1 Ok Tank Room, Rooms N05, SN06, and N04; Upper Surfaces ADM-001-2 Room N02, N03, and N16; Upper Surfaces ADM-201 Second Floor of Administration Building RBC-200-1 P Chem Lab Lower Surfaces RBC-201-1 Room 202 (P Chem Lab) Upper Surfaces RBE-401 Reactor Building Exterior RBG-101 Gamma Deck Rooms 101, 101A, 103, 106, 108, and 109; Upper Surfaces RBN-000-1 Neutron Level Reactor Pit Lower Surfaces RBN-001 Neutron Deck Upper Surfaces RBN-001-1 Neutron Level Reactor Pit Upper Surfaces ADM-200 Administration Side of Control Deck ADM-101 Administration Side of the Gamma Deck RBR-301 Reactor Roof ADM-301 Administration Roof ADM-401 Administration Exterior

Enercon Services Inc.

Survey Package Building: Reactor Building I Survey Unit #: RCD-001 I Page 1 of 5 Classification:

Z Class 1 - Impacted El Class 2-Impacted E3 Class 3 - Impacted

[Survey Type:

EL Characterization Z Demolition E3 Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/100cm 2)

Investigation 3,750 (dpm/100cm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys Floors

[L' 10%

] 50% 0 100% El N/A Lower walls E3 10% E3 50% Z 100% [1 N/A E3 Upper walls E310% E150% 13100% 0 N/A E3 Ceilings E1 10% E150% 13100% Z N/A E3 Structures (Permanent Furnishings) Interior and Exterior Surfaces E3 10% 13 50% E] 100% [E N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

ZL-2360/43-93 Beta/Alpha 1 Minute 1 probe Tc-99 N/A 612 width/!sec Z L-3030/43-10-1 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Alpha - 10 Beta-120 z

A Planchet Counter shall be used for analysis of any required removal contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL, values have been selected based on the most limiting nuclides of concern for the survey unit.

RCD-O01 / Page 1 of 7

Enercon Services Inc.

Survey Package General Survey Instructions: RCD-001

[ Page2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3. Document all scan survey results on the applicable survey maps and data results sheets.
4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5. Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.
6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8. Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.
9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 RCD-001 / Page 2 of 7

Enercon Services Inc.

Survey Package Location Code Description RCD-001 I Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as FI, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "1" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (I character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By: C P C ro-Reviewed By:'?JXt

,LL Printed Name/Si-gnture Date:

Ll I. T~

Date: 11/

Date: Lh2,Og1 Print lk.Jarne/Signature Package Complete: Pl, "L

Qk

"* F &-trb.,.t Printed Name/Signature RCD-001 / Page 3 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RCD-001 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

Survey Technician(s):

C Crott Floor Survey - Completed in accordance with the survey package 0 N/A Step #1 0 Beta Scan Date Completed 3/26/2014 Initials CC El Alpha Scan Date Completed N/A Initials N/A Z Beta Static Date Completed 3/26/2014 Initials cc El Alpha Static Date Completed N/A Initials N/A ER Smears Date Completed 3/26/2014 Initials cc Lower Wall Survey - Completed in accordance with the survey package

[- N/A Step #2 0 Beta Scan Date Completed 3/26/2014 Initials CC E] Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/2014 Initials CC E] Alpha Static Date Completed N/A Initials N/A IE Smears I Date Completed 3/26/2014 Initials cc I

5. __________________
5.

.5 5.

Upper Wall Survey - Completed in accordance with the survey package

[D N/A Step #3 El Beta Scan Date Completed Initials El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials RCD-O01 / Page 4 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RCD-001 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package Step #4 0 N/A E] Beta Scan Date Completed

[] Alpha Scan Date Completed Li Beta Static Date Completed

[] Alpha Static Date Completed EL Smears Date Completed Initials Initials Initials Initials Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

Z N/A Step #5 Li Beta Scan Date Completed Initials Li Alpha Scan Date Completed Initials EL Beta Static Date Completed Initials L] Alpha Static Date Completed Initials EL Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey Dackage N/A RCD-001 / Page 5 of 7

RADJOLOGJRVE REPORT IIw d3 m

cio rnuS1.U4S 06 2WmA 01131 0&-

70

~

-167 4=

Now___10 3in4W1.1.UNo2 0

.?ADA 0

09 bmD

-07

____/__k_0_DA 25 IAMA I

MCn401-WU1 7____

__I_-___4___A

/A H/

336..420 4NDA 0

19

'DA

-*07 124___

inC4SlWT.414W 0

PAMD 0

0

ýMDA

-16710 bi 29MIN/MA 41V080 OmD 0

0 aimA

-107 loll RCD-001I/ Popg of 7

13 12 14E 15 10--,

S9 7 6 5x 4

2 RCD-001 NORTH RCD-001 / Page 7 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RCD-002 I Page 1 of 5 Classification:

Z Class I - Impacted El Class 2-Impacted El Class 3 - Impacted Survey Type:

El Characterization Z Demolition El Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/1 00cm 2)

Investigation 3,750 (dpm/100cm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys Z

Floors El10% [E150% ED100% EN/A Z

Lower walls El10% [E 50% Z 100% E] N/A El Upper walls El 10% El 50% El 100% ZN/A

[] Ceilings E] 10% E] 50% E] 100% Z N/A El Structures (Permanent Furnishings) Interior and Exterior Surfaces El 10% E] 50% E] 100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

ZL-2360/43-93 Bta/Alph Minute I probe Tc-99 N/A 612 L-649eta/Alpha 1 Minute width/ sec Z L-3030/43-10-1 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Alpha - 10 Beta - 120 A Planchet Counter shall be used for analysis of any required removal contamination measurements. See General Survey Instructions Item #7.

Since this inslrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL. values have been selected based on the most limiting nuclides of concern for the survey unit.

RCD-002 / Page 1 of 7

Enercon Services Inc.

Survey Package General Survey Instructions: RCD-002 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5.

Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.

6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8.

Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.

9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 RCD-002 / Page 2 of 7

Enercon Services Inc.

Survey Package Location Code Description RCD-002 Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as FI, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "1" (e.g., WI, F1, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (1 character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

CA Cco+-

cA- :s-ýc7 Prepared By:

Printed Name/Signature Date:

Date:

Reviewed By: Asc Piintgam/Siature Package Complete: F-r6, m.

Ai L*.-,A Q.

)Pr F A'v,*

Date:

4 -1(.o 14 Printed Name/Signature RCD-002 I Page 3 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RCD-002 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

Survey Technician(s):

C Crott Floor Survey - Completed in accordance with the survey package F1 N/A

[@ Beta Scan Date Completed 3126/2014 Initials CC Step #1 El Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/2014 Initials CC El Alpha Static Date Completed N/A Initials N/A 0 Smears Date Completed 3/26/2014 Initials cc Lower Wall Survey - Completed in accordance with the survey package ElN/A 0 Beta Scan Date Completed 3/26/2014 Initials CC Step #2 El Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/2014 Initials CC El Alpha Static Date Completed N/A Initials N/A 0 Smears Date Completed 3/26/2014 Initials CC Upper Wall Survey - Completed in accordance with the survey package O N/A El Beta Scan Date Completed Initials Step #3 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials RCD-002 / Page 4 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RCD-002 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package El N/A EJ Beta Scan Date Completed Initials Step #4

[1 Alpha Scan Date Completed Initials El Beta Static Date Completed Initials

[] Alpha Static Date Completed Initials D Smears Date Completed Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

ON/A El Beta Scan Date Completed Initials Step #5 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6 0 N/A E0 Smears Date Completed Initials RCD-002 I Page 5 of 7

RADIOLO4IJRVY REPORT pursm

  • ew""

pwmaionSWAW ftft

  • C4WI" Iom wob 29031214-00 mw----~

I

~

-omb-vo hob pia hAm. impa'l Zmaso Als" umA Maml Jj Sts Rfsahw

.Jjag pat 3/2512014 16011 3080 4LILI 130-is 1s 0

10%

10 SIS190%

1ie Tim 1000 Lub N

rf65 61LIJ2MM 424PS so..i.....

0G 30-ll5 5

2 100 I

I am/nltb DmU 353!it o3 JIM1 emmi o,

s3 Ai4" So sDoft. so" RCW6G".-U.0b a

ýMDA 0

0 SUam

-167 i10 Do23W/

IAJA RiCD04M"494101 0

'UDA 0

0

'UDA

-167 j

&';II J

I 3 W 3, 10

_A 3

mC4"1M 0_

_m 0_

_m 6

I, w18 2

2 I

I

/

MCD.041".u41ft 0

ýJADA 0

0

~

mm

-14671 N

9 MA1 I

0

'UD 0

0 bmD

-167 101 Iso

-m

-5 A

/A MI 3C0400-W4140 0

-FADA 0

0

.1m

-167 i

4m

-2 F/N/MI AU4"4~

0m 4m~m 0,

1m

-16

  • /Amuh lmeRi 4Mi m m -

l m m ~ m m di lo/

A N/

A~

a 10lo RCD-002 / Page 6 of 7

1412 15 13 RCD-002 SOUTH RCD-002 / Page 7 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RGD-001 I Page 1 of 5 Classification:

Z Class 1 - Impacted Ej Class 2-Impacted El Class 3 - Impacted Survey Type:

El Characterization Z Demolition El Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/100cm 2)

Investigation 3,750 (dpm/1OOcm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys Z

Floors E110% [:50% 0 100% IZN/A Z

Lower walls

[

10% LI 50% Z 100% []N/A El Upper walls E110% LI50% E] 100% Z N/A El Ceilings E]10% LI 50% E] 100% E N/A El Structures (Permanent Furnishings) Interior and Exterior Surfaces EI 10% LI 50% LI 100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

ZL-2360/43-93 Beta/Alpha 1 Minute 1 probe Tc-99 N/A 612

____L-2360/43-93_____

B pMwidth/sec Z L-3030/43-10-1 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Alpha - 10 Beta-120 Z

A Planchet Counter shall be used for analysis of any required removal contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL,. values have been selected based on the most limiting nuclides of concern for the survey unit.

RGD-001 / Page 1 of 7

Enercon Services Inc.

Survey Package General Survey Instructions: RGD-001 I Page 2 of 5 I. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).

2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5. Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.
6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8. Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.
9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO

.or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 RGD-001 I Page 2 of 7

Enercon Services Inc.

Survey Package Location Code Description RGD-001 h

Psge 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR = Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as F l, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "I" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (1 character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By: C A C ra4-CA, z(ý Printed Name/Signature Date:

I L 1.,

Date:

Reviewed By:

fN I rLi-Printedi'ame/Signatu Package Complete: F 0..

F-, 3 P.1M Date: "7"/7LO 14 Printed Name/Signature RGD-001 / Page 3of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit#: RGD-O01 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

C Crott Survey Technician(s):

R Shank Floor Survey - Completed in accordance with the survey package El N/A Step #1

[9 Beta Scan Date Completed 3/26/2014 Initials CC 0l Alpha Scan Date Completed N/A Initials N/A ED Beta Static Date Completed 3/26/2014 Initials cc El Alpha Static Date Completed N/A Initials N/A Z Smears Date Completed 1 3/26/2014 Initials cc Lower Wall Survey - Completed in accordance with the survey package Step #2 ElN/A 0 Beta Scan Date Completed 3/26/2014 Initials CC El Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/2014 Initials CC El Alpha Static Date Completed N/A Initials N/A Z Smears Date Completed 3126/2014 Initials cc Upper Wall Survey - Completed in accordance with the survey package G] N/A Step #3 E] Beta Scan Date Completed Initials El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials Dat Copee Inital El Smears I Date Completed Initials RGD-001 I Page 4 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RGD-001 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package 0N/A El Beta Scan Date Completed Initials Step #4 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

Z N/A El Beta Scan Date Completed Initials Step #5 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials

[j Alpha Static Date Completed Initials El Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6 EK N/A El Smears Date Completed Initials RGD-001 / Page 5 of 7

RADIOLcXREY RE)PORT

.. OM...

WOOM.

4113120I..43a..

3,41 10 0.0 Wj.

10 142 The 100D Von~-

100WW I

MOD4014W40401 0

-UDA 0

0 l4D

-161

ýqAa 4

I I

I 3400-CONW 0

A

_A0__DA_40MAI 3in4.l~~u.U411 54_____

a"_____

MIA___

MD-SI-F-44661 3

to 30 0

DA

-21 02 hm 42 MA IM AIn.001-E4 0

10D 1

0 0

.6m

-101 u

I 26W0.014-1U-010

_____ 10 10 0_m_61____"I____r 1

51 56 IAMA I

RUS01101.4W.U-0l 0_____

MD_03___9_ot___48_/ANA I

11020,001-W-4140 0

Mm 0

_____ 0

-DA

-11 9

mu 12 MA IAM YAMDDI-W1.?-U011 0

.&M 0

0

_MA_-11 11_548 549__A___MI 0S.-U1

'__m 0

2 27_7_1_46 4

V I

3111104n104100 JA 3

DA1U4101 lie___

g 624__

624________

a~

hE ale we I mamb umk otuoin met 49609"tM I op13u 0m ysg emesesi to MIA m co.nso y

1oi1 RGD-001 I Page 6 of 7

TRUCK DOOR 115 13 14 6

RGD-001 NORTH RGD-001 / Page 7 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RGD-002 I Page I of 5 Classification:

Z Class 1 - Impacted El Class 2-Impacted El Class 3 - Impacted Survey Type:

El Characterization Z Demolition E3 Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/100cm 2)

Investigation 3,750 (dpm/1OOcm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys Floors EL 10% EI 50% 0 100% [] N/A Lower walls

[-110% [1 50% Z 100% E] N/A El Upper walls E1 10% E1150% E] 100% Z N/A

[-

Ceilings E1 10% [1 50% El 100% Z N/A 13 Structures (Permanent Furnishings) Interior and Exterior Surfaces

[: 10% 03 50% Ei 100% N N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

ZL-2360/43-93 Beta/Gamma I Minute 1 probe Tc-99 N/A 612 width/ sec Z L-3030/43-10-1 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Alpha - 10 Beta-120

  • A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL. values have been selected based on the most limiting nuclides of concern for the survey unit.

RGD-002 / Page 1 of 7

Enercon Services Inc.

Survey Package General Survey Instructions: RGD-002 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5.

Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.

6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8.

Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.

9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 RGD-002 / Page 2 of 7

Enercon Services Inc..

Survey Package Location Code Description RGD-002 I Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

=

Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as Fl, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "1" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (I character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters) r A Nei+4-Qf\\- (~2-+

Prepared By:

Printed Name/Signature Reviewed By:'.

U £'Jc,,,J.-

Printed AmeSignature Date:

L1

~fL-Date:

Date:

Package Complete:

t--r

/rioff&/*Lk,

" A&...

Printed Name/Signature RGD-002 / Page 3 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building survey Unit #- RGD-oo0 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

C Crott Survey Technician(s):

R Shank Floor Survey - Completed in accordance with the survey package 1N/A Step #1 Z Beta Scan Date Completed 3/26/2014 Initials CC El Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/2014 Initials cc E] Alpha Static Date Completed N/A Initials N/A Z Smears Date Completed 3/26/2014 Initials cc Lower Wall Survey - Completed in accordance with the survey package

[I N/A Step #2 0D Beta Scan Date Completed 3/26/2014 Initials CC E3 Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/2014 Initials CC El Alpha Static Date Completed N/A Initials N/A Dat Copee I/621 I

ED Smears Date Completed 3/26/2014 Initials cc Upper Wall Survey - Completed in accordance with the survey package O N/A Step #3 El Beta Scan Date Completed Initials El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials RGD-002 / Page 4 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RGD-002 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package Z N/A El Beta Scan Date Completed Initials Step #4 C3 Alpha Scan Date Completed Initials 0l Beta Static Date Completed Initials El Alpha Static Date Completed Initials 0l Smears Date Completed Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

Z N/A E] Beta Scan Date Completed Initials Step #5 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6

[9 N/A El Smears Date Completed Initials 0

RGD-002 I Page 5 of 7

RADIO*

~RVKY REPORT pmsýor vmewsts wymm RO4" 1110/2044104 how-fm.~

Prb Fn"uL..

Am ho WA~du

... JL. -.

NW no" sme..amow.

pa 31=513014 2W 611_201

_ jSW LS_____

so______

S"__

___9______

_ ji mm

_______4 48__M 25___

1___

I"__

m.0.t30

__m um__

OmaIm____WI lli e

B"S

-w"

_cma 30M

_lomm lpsp O

q omm woe" c

0WM awSai rlp wR 0omwpi 01)___b_

10 MIlA MI 0

59 49MA I

/

30*408.-4140 0______3_m_3___PI VA 13 3

43MI IA P/

3G004W-41-W 0_

_DA 0_1_.m__MIAMI 1 com 47 471.3..

0~.

iDfl 0~s

36.

.64Mm Is am 4m 484

~

MIAMIA lI OI RGD-002/ Page 6 of 7

S w

TRUCK DOOR RD 2S R 0 4 a7

[-7 RGD-00 SOUT R 8-01Pae7o

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RND-001 I Page 1 of 5 Classification:

Z Class 1 - Impacted El Class 2-Impacted E3 Class 3 - Impacted

[Survey Type :

E Characterization Z Demolition E3 Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/1OOcm 2)

Investigation 3,750 (dpm/100cm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys 2

Floors E1 10% El 50% Z 100% El N/A Z Lower walls 1l 10% F 50% Z 100% E3N/A

[1 Upper walls 1l 10% [:150% E1 100% E N/A E3 Ceilings E1 10% [1 50% [:1100% ED N/A 13 Structures (Permanent Furnishings) Interior and Exterior Surfaces El 10% El 50% El 100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

ZL-2360/43-93 Beta/Gamma 1 Minute 1 probe Tc-99 N/A 612 L-2360/43-3_Beta/Gamm 1Minute_

width/sec Z L-3030/43-10-1 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Alpha - 10 Beta - 120 13 Z

A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL,. values have been selected based on the most limiting nuclides of concern for the survey unit.

RND-001 I Page 1 of 7

Enercon Services Inc.

Survey Package General Survey Instructions: RND-001 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5.

Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.

6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8.

Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.

9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-I 54; Ni-63 RND-001 / Page 2 of 7

Enercon Services Inc.

Survey Package Location Code Description RND-001 I Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as FI, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "1" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (I character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By: C A CiC.*4"L Reviewed By: ý.C *,'-

J rA-(ýýj Printed Name/Signature JIa~~K-Date:

L*/ 7 -

Date:

Date: 4-lb Loo Printet~ame/Signature Package Complete: rc* rJ{ ?,-t

./t A1-k Printed Name/Signature RND-001 / Page 3 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit M RND-001 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

C Crott Survey Technician(s):

R Shank Floor Survey - Completed in accordance with the survey package El N/A Step #1 0 Beta Scan Date Completed 3/26/2014 Initials CC El Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/2014 Initials cc El Alpha Static Date Completed N/A Initials N/A 0 Smears Date Completed 3/26/2014 Initials Icc Lower Wall Survey - Completed in accordance with the survey package

[] N/A Step #2 Z Beta Scan Date Completed 3/26/2014 Initials CC El Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/2014 Initials cc El Alpha Static Date Completed N/A Initials N/A Z Smears Date Completed 3/26/2014 Initials cc Upper Wall Survey - Completed in accordance with the survey package Step #3 ON/A El Beta Scan Date Completed Initials El Alpha Scan Date Completed Initials E] Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed IInitials RND-001 / Page 4 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RND-001 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package

[] N/A El Beta Scan Date Completed Initials Step #4 0l Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

ED N/A El Beta Scan Date Completed Initials Step #5 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6 Z N/A El Smears Date Completed Initials RND-001 / Page 5 of 7

RADIOL"xURVIEY RJEPOlrr JIn6mstrom Number DOW Prb.

PMA reskm s"

AD"m ftdwmnm ft~

s**.&.

Iamo.1 low" be" 111101me 1ma d

3.612812014 Lule 303 07 MOM 1312014 431-W is 1

0 30.4%

10 31.8 I

00

.la loco*

00 Lmh 16 726 5 6

1124 4801 2:1 i0 2

11.1%

74 72 3.02 merzr 1"0 Iflmesm F.6 M6 IA be7wi-2i0 aso..%m sot100e7,1 l

o m401.V.4A

-12D_

_A_

NN.0..460

~mDA 0

0

MDA

-167

= Ao-,u m

01ID 0

0 JA

-167 0

bm 0

0

-167

_____v_4 1425 619 619 MA Mt NUD.001-t-E013 0

UImA 0

48

'MDA

-16 IOLA-W I 11310,11".4194W__

UN401..0144___

~~~~~~~h 0m 48~

mm 265 14 81 819 ywIA.m121214 MIA.w

~55866,mA 6.664uh si

.m.s RXD4Wl~r~k66l 6

2D

'otl RND-OO1/ Page 5of 7

14-ON WALL UNDER STAIRS 19

-17 RND-001 NORTH RND-001 / Page 7 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building I Survey Unit #: RND-002 I Page 1 of 5 Classification:

2 Class 1 - Impacted E3 Class 2-Impacted El Class 3 - Impacted Survey Type:

E3 Characterization Z Demolition EL Final Status Survey Applicable. Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/1OOcm 2)

Investigation 3,750 (dpm/1OOcm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys 0

Floors

[L 10% [L 50% 0 100% E] N/A ED Lower walls EL 10% [-1-.50% Z 100% [L N/A EL Upper walls F1 10% [] 50% E] 100% Z N/A E] Ceilings

[1 10% [1 50% 1 o100%

EN/A E3 Structures (Permanent Furnishings) Interior and Exterior Surfaces E3 10% E3 50% E] 100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

ZL-2360/43-93 Beta/Alpha 1 Minute 1 probe Tc-99 N/A 612

__-36/3-3BeaAlh 1__Minute___

width/sec Z L-3030/43-10-1 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Alpha-10 Beta - 120 13 Z

A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL*, values have been selected based on the most limiting nuclides of concern for the survey unit.

RND-002 / Page 1 of 7

Enercon Services Inc.

Survey Package General Survey Instructions: RND-002 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5.

Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.

6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8.

Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.

9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-I 54; Ni-63 RND-002 / Page 2 of 7

Enercon Services Inc.

Survey Package Location Code Descriplion RND-002

[ Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as FI, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "1" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (I character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By:

C A Cvn4-OA (N Printed Name/Signature Reviewed By:ý--

C Date:

./1'Iq Date:

Date: L1 [2J,14 Package Complete: (-Ra4LJ i,--1 w t{

--*I(*

i, Printed Name/Signature RND-002/ Page 3of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RND-002 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

C Crott Survey Technician(s):

R Shank Floor Survey - Completed in accordance with the survey package El N/A Step #1 0 Beta Scan Date Completed 3/26/2014 Initials CC LI Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/2014 Initials cc El Alpha Static Date Completed N/A Initials N/A 0 Smears Date Completed 3/26/2014 Initials CC Lower Wall Survey - Completed in accordance with the survey package

[- N/A Step #2 0 Beta Scan Date Completed 3/26/2014 Initials CC El Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/2014 Initials CC El Alpha Static Date Completed N/A Initials N/A 0 Smears Date Completed 3/26/2014 Initials cc Upper Wall Survey - Completed in accordance with the survey package O N/A Step #3 El Beta Scan Date Completed Initials

[] Alpha Scan Date Completed Initials El Beta Static Date Completed Initials

[: Alpha Static Date Completed Initials El Smears Date Completed Initials RND-002 / Page 4 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RND-002 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package EN/A El Beta Scan Date Completed Initials Step #4 LI Alpha Scan Date Completed Initials El Beta Static Date Completed Initials LI Alpha Static Date Completed Initials El Smears Date Completed Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods) 2 N/A El Beta Scan Date Completed Initials Step #5 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials 0l Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package.

Step #6 0 N/A El Smears Date Completed Initials RND-002 / Page 5 of 7

RADIOLO4*URtVEY PWorn vwvýs o

OW Mmmsowwr ra-&Ofnbu IS20144006 gaey x~L mow__ "Mue bow.tký%~fs CA-C 4_CR zew 26697 "w"

  • i 20141 46101 16 10 0M 04%

I0

21.

2.0%

its Tim pC 2Mj~~

MU 61 11120141 48.6 12m 10 1

&.1%

668.6%

266 Down ANNs m0

-~~~ý Ow mow

ý I W

7Ofm no 9/

Mh.A us 924086-30ft 0

?MDA 0

0

'UDA

-107 NA wi 3784 82

/IIA H/

RED402.V-U.004 0____________

.)M 0

2 mNAii XJý

ý1A MNAPA IMUMM0-t4&M 3

to__3

_m_2 MA___

IA_,,

3 on inR

/

IIA EN3418.V.3006 0

JAM_________

0___

0 I

17 KK j

tA 14 60 60NAA NA inUP062.W.N.0 3

10 10 0

'MDA

-167 MI 13 109_02____TA

/

ma46.3u.16 0___

bm__

0_

0_'_-6_x_4_91_7_NAMI

/

100013 MW-U 2___

0 H1M

-4 I

V' KA 2

5 5

I 1ANA A,,.~~jk

'CIA 143 11 912 264W.i/Am.dwt ti I

.dgt Dua "464no owm 0

1 m

6 I,

I J

!.ogmbo"l 01 hm~t~

0 4m o

um

-146 l23 140mb4 140 t..R I oif RNU-02 / Page 6 of 7

A U

RND-002 SOUTH RND-002 / Page 7 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: ADM-1OK-001 Page 1 of 5 Classification:

0 Class 1 - Impacted El Class 2-Impacted n] Class.3 - Impacted Survey Type:

El Characterization 0 Demolition El Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/1OOcm 2)

Investigation 3,750 (dpm/100cm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys E

Floors El 10% []50% 0 100% [EN/A Z

Lower walls E] 10% [] 50% Z 100% E] N/A

[] Upper walls El 10°% [Z50% [: 100% Z N/A El Ceilings

[] 10% LI 50% EL 100% 0 N/A LI Structures (Permanent Furnishings) Interior and Exterior Surfaces El 10% E] 50% E] 100% 0 N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

DL-2360/43-93 Beta/Gamma 1 Minute 1 probe Tc-99 N/A 612 L-2360/43-93_Beta/Gamm 1_Minute_

width/sec L-3030/43-10-1 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Alpha-10 Beta - 120 El A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGLw values have been selected based on the most limiting nuclides of concern for the survey unit.

ADM-10K-001 / Page 1 of 8

Enercon Services Inc.

Survey Package General Survey Instructions: ADM-IOK-001 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5. Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.
6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8. Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.
9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 ADM-10K-001 / Page 2 of 8

Enercon Services Inc.

Survey Package Location Code Description ADM-IOK-001 Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as FI, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "1" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (I character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number I. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By:

ck-)2ri

ý

&S Reve B: Came/Signature Reviewed By: C A C*F-r CL.@-~

Date: 17 Date:

f

)

Date:

17W_____4 Printed Name/Signature I

Package Complete: Er WA-r j

Printed Name/Signature ADM-IOK-001 I Page 3 of 8

Enercon Services Inc.

Survey Package Building: Reactor Building ISurvey Unit #: ADM-10K-001 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

Survey Technician(s):

R Shank Floor Survey - Completed in accordance with the survey package El N/A

[

Beta Scan Date Completed 3/26/14 Initials RS Step #1 El Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/14 Initials RS E] Alpha Static Date Completed N/A Initials N/A

[

Smears Date Completed.

3/26/14 Initials RS Lower Wall Survey - Completed in accordance with the survey package EIN/A

[ Beta Scan Date Completed 3/26/14 Initials RS Step #2 E Alpha Scan Date Completed N/A Initials N/A

[ Beta Static Date Completed 3/26/14 Initials RS El Alpha Static Date Completed N/A Initials N/A

[ Smears Date Completed 3/26/14 Initials RS Upper Wall Survey - Completed in accordance with the survey package EN/A El Beta Scan Date Completed Initials Step #3 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials I

0 ADM-1OK-001 I Page 4 of 8

Enercon Services Inc.

Survey Package Building: Reactor Building 7 Survey Unit #: ADM-1OK-001 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package EN/A El Beta Scan Date Completed Initials Step #4 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

ED N/A El Beta Scan Date Completed Initials Step #5

[] Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6 0 N/A El Smears Date Completed Initials ADM-10K-001 / Page 5 of 8

  • SULOO RVZY RELMR 4&-6111S1 is~

30 0

  • a*

9 61 9A1%

Li 3 le a&"

it______

li WAA 0--4120 34 sm S

I

_____WIA an-4..

.U 0mpe

'KOAý,

0o 0m

'KIM~

-1671 mýfo F o a

ADU-134WW-W48U.

0

-liDA 0

4

-KMD

-346 6

m

-l AVm-34S1W-U-594f a

ONDA 0

0 UKIA

-16 s

b?

4 A*U-l6S01441.~4t0 0

Kmw 0

4

-Kmm

-3467 3

-D "1

  • ll-3UK.94MU41tB 0

wKm 0

0 aKm

-167 so hm 78 MI AMIN-1*,9,4R1F 4M3 0

'KIM 0

34

'KMD

-946 91 4NW__MI in-1K44.1-W341 0

OKm 0

0

'KMA

-167 7

e 5

I A=mO44StU4W4M 3

10 t0 23

-Kmm 39 3

m32 AN1 1=4040R 1M 0

4 m

16w ID 1

Ani-= MM14511 m

0 0

OWA

-17 6

-DA M

IW2 ADM-1OK-O01 I Page 6 of 8

O RADIOLOGICAL. SURVEY REPORT

)smsh.

D biWAM L.. Eh..0 o"ý njb I

361IOB/014-M tmk* wmw b

re sb f

s=

I~

h moohmm loo Mauim x

(62W sma...

dsaw29 0*136114

  • mow

&~I Abf BMW me no"u Timm O~diiri SAMl AOU-1406l.V4UU 0

mmD 0

0 AamD

.167

"/

A Xfý 74 44DA 250 N/A 40-100 N/A 2E2 ADM-IOK-001 / Page 7 of 8

S V

ADM-10K-001 ADM-10K-001 / Page 8 of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-BR-001 I Page 1 of 5 Classification:

0 Class 1 - Impacted El Class 2-Impacted El Class 3 - Impacted Survey Type:

El Characterization 0 Demolition EL Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/1 00cm 2)

Investigation 3,750 (dpm/l00cm2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys E

Floors

[L 10% [L 50% Z 100% [] N/A Z

Lower walls

[L 10% [L 50% M 100% E]'N/A El Upper walls El10% LI50% E] 100% Z N/A LI Ceilings

[_ 10% I ]50% El 100% Z N/A LI Structures (Permanent Furnishings) Interior and Exterior Surfaces El 10% [L 50% EI 100% [K N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

OL-2360/43-93 Beta/Gamma 1 Minute I probe Tc-99 N/A 612 width/sec Z L-3030/43-10-1 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Alpha-10

________Beta

- 120 z

A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL.. values have been selected based on the most limiting nuclides of concern for the survey unit.

ADM-BR-001 / Page 1 of 7

Enercon Services Inc.

Survey Package General Survey Instructions: ADM-BR-001 I. Perform scan surveys of the required surface area at the prescribed sc required, use professional judgment to select the areas scan surveyed to contain residual activity (i.e., areas of known radionuclide usage, crevices not easily cleaned, countertop workspaces, storage locations with a known history of contamination).

2.

If elevated activity is detected during the scan surveys, then establish area(s) and mark the affected area(s) and quantify the activity by taki area(s). Notify the Project Manager or designee of the type, amount,

3. Document all scan survey results on the applicable survey maps and
4.

The established number of static measurement locations needed for t is 14. However, due to statistical and geometrical considerations, thl this case, collect the actual locations provided on the survey map wh than 14

5. Locate and mark the required static measurements locations using thi sufficient detail to measure and locate all of these locations have beeJ
6.

Collect all required static measurements and document the results on Additional static measurements may be taken in suspect areas at the technician. However, these additional locations are not included in t.

7.

Removable contamination measurements (swipes) shall be performei and counted on a planchet counter accounting for alpha/beta contami

8. Notify the Project Manager or designee if elevated activity is detecte applicable removable contamination measurements.
9.

Ensure that all package information is completed and signed prior to or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 0

- Page 2 of 5 can rates. If less than a 100% scan is

t. Select areas with the highest probability floor traffic pathways, cracks and/or s, stained or water spotted areas, or areas the extent (size) of the contaminated ig static measurements of the affected and extent of any contamination.

data results sheets.

he statistical evaluation of this survey unit

- actual number of locations may vary. In ether this number is greater than or less e survey map(s). Survey maps with n provided.

the associated data results sheets.

discretion of the Project Manager or survey he analysis of the statistical sample set.

d at the established measurement locations nation.

d by any of the static measurements or turning in this Survey Package to the RSO ADM-BR-001 / Page 2 of 7

Enercon Services Inc.

Survey Package Location Code Description ADM-BR-001 Page 3 of p

A unique location code shall be assigned to each individual survey location to ensure proper date management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as Fl, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "I" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (1 character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prenared By: ~ 7 ~ ~ Cs StA Reviewed By:

ftPdndName/Sipiature CA CA4 Printed NamelSignature Date:.4/7,*

Date:

9 Package Complete:

J.

9 8

I,9-i b

Date:

i fi//7.'i iPnted Name/Signatr ADM-BR-001 I Page 3 of 7

Enercon Services Inc.

Survey Package Building: Administration PgSurvey Unit #: ADM-BR-001 P

4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

Survey Technician(s):

R Shank Floor Survey - Completed in accordance with the survey package E] N/A Z Beta Scan Date Completed 3/26/2014 Initials RS Step #1 E] Alpha Scan Date Completed N/A Initials N/A Z Beta Static Date Completed 3/26/2014 Initials RS El Alpha Static Date Completed N/A Initials N/A S smears Date Completed 3/26/2014 Initials RS Lower Wall Survey - Completed in accordance with the survey package UN/A 0 Beta Scan Date Completed 3/26/2014 Initials RS Step #2 E] Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/2014 Initials RS E] Alpha Static Date Completed N/A Initials N/A 0 Smears Date Completed 3/26/2014 Initials RS Upper Wall Survey - Completed in accordance with the survey package 0 N/A El Beta Scan Date Completed Initials Step #3 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials ADM-BR-001 / Page 4 of 7

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-BR-001 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package 0 N/A 13 Beta Scan Date Completed Initials Step #4 13 Alpha Scan Date Completed Initials El Beta Static Date Completed Initials 13 Alpha Static Date Completed Initials El Smears Date Completed Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

MN/A El Beta Scan Date Completed Initials Step #5 13 Alpha Scan Date Completed Initials El Beta Static Date Completed Initials 13 Alpha Static Date Completed Initials EI Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6 0 N/A El Smears Date Completed Initials ADM-BR-001 / Page 5 of 7

RADIOLWOGJVY REPORT twat!me wwb Our nz~

IA fk Au" pJbys L~~gin Mmsa Lmba UA WNWi kma Usot Uemmsh 4dl O

31261 2014 mom 11312014 WJ10-L is 10l

^4 10

-L 19.0%

its..j.....

1200 I-MOM.

41ULMI 4*-j 125 10 ILI i

0$A-246 2ý 100IQ 11VWn0

-60.1m0 cm!

~

0

-omwu AM a WUIs

/O A=MU.U.00-W4A4*

-0

ýMDA 0

0 MAm

-t167 t

OD 32 MA MI MA

  • 3U.3a-001-W4-U44 OM__

0__m_

16___MA HA 4

6 63 MAMI ADW4W400-W-U07

____A

__IA 341 W

4 to_

0 17 NN-:

ltw s

37 7

h-001.RW2--.0,4 0__

-MDR 0__m_

67_

s A.

fm-7 ID 2

MI I

ADWWOW-W41-U40 0_

PA_____

-6 M

IA 5

ýb 3

MA I

I ADU40401-W-N.11 0_____

___0___m_

67___;,/A 9

f 17 MI IA N

A9UUB.Um.0-W-N-12 0

-mmA 0

0 41"

-6 l-MA MAý-

7 MDA "2

MI 0A7I LUU.UR-001.F.E.1 0____

bm_0____6____7 11 04 XA

ý MI I

  • flU.=-01.V-N-14 0__Im_2_______7 9

3 MA MA I

ADhm 4WU41.F-U4 0_

1___m__71IM%

fm-IW VE 17 32 1

I J/

I I

ADSI-2201449441 0____

___b_1___13_10 10 IAMA A*W4NtM~U4s1&W3T 0____

bg__9.AM_20___MA69___s NAMI I

ADm4SlE-M.F419 3_

10 t_____16 t

b 37 NA t

I AhU4N4D401-1-3 0

4IDA 0

0 4.IDA

-167 A

MA MA ADUAR401.V-U.2 a_____

OA 0

0 DAXA IAXf 2

bm

-1 MA_

Li,.uAýmboh hwCm21*CmI" 1

om~

mS 32114.

Xx A*

eo dwadahsm I

feawotmiabo 1011 ADMBR-001 I Pop 6 of 7

V ADM-BR-001 ADM-BR-001 / Page 7 of 7 NOTES:

1-12 WALL SAMPLE POINTS 13-20 FLOOR SAMPLE POINTS

Enercon Services Inc.

Survey Package

[

Building: Administration I Survey Unit #: ADM-100 Page I of 5 Classification:

[] Class I - Impacted E3 Class 2-Impacted 0 Class 3 - Impacted

[Survey Type:

0l Characterization 0 Demolition El Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/1OOcm 2)

Investigation OOCM 2)

Lev-e!d 3,750 (dpm/10m)

Level I

Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys ER Floors

[3 10% E] 50% [D 100% [] N/A 0 Lowerwafls Z 10%

l50% E10% E-- N/A C3 Upper walls Cl 10% El 50% El 100% EDN/A El Ceilings El 10% [:150% [E 100% [D N/A E] Structures (Permanent Furnishings) Interior and Exterior Surfaces

[: 10% [] 50% El 100% ON/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

EKL-2360/43-93 Beta/Gamma 1 Minute I probe Tc-99 N/A 612 width/sec 0 L-2221/43-37 Beta/Gamma N/A I probe Tc-99 N/A 174 width/sec NASC 950 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Alpha - 25 S1 1_ Beta-150 A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL. values have been selected based on the most limiting nuclides of concern for the survey unit.

ADM-100O/Pagel1 of 8

Enercon Services Inc.

Survey Package General Survey Instructions: ADM-100 Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5.

Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.

6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8.

Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.

9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 ADM-100 /Page 2of 8

Enercon Services Inc.

Survey Package Location Code Description ADM- 00 1 Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

=

Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as Fl, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "I" (e.g., WI, F1, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (1 character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By:

Kurt Myers Reviewed By:

T J Keane Package Complete:

Frank Brown Date:

Date:

________z Date: zbltLL(

Pinted Name/Signature ADMA 00 /Page 3of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-100 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

K Myers R Shank Survey Technician(s):

D Border C Crott Floor Survey - Completed in accordance with the survey package UN/A

[

Beta Scan Date Completed 10/09/2013 Initials RS Step #1

[

Alpha Scan Date Completed N/A Initials N/A

[

Beta Static Date Completed 10/01/2013 Initials DB U] Alpha Static Date Completed N/A Initials N/A

[

Smears Date Completed 10/01/2013 Initials DB Lower Wall Survey - Completed in accordance with the survey package EU N/A Z Beta Scan Date Completed 10/01/2013 Initials DB Step #2 U] Alpha Scan Date Completed N/A Initials N/A

[

Beta Static Date Completed 10/01/2013 Initials DB U Alpha Static Date Completed N/A Initials N/A

[

Smears Date Completed 10/01/2013 Initials DB Upper Wall Survey - Completed in accordance with the survey package ED N/A EU Beta Scan Date Completed Initials Step #3 Ul Alpha Scan Date Completed Initials U Beta Static Date Completed Initials U Alpha Static Date Completed Initials Ul Smears Date Completed Initials ADM-100 /Page 4of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-100 I Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package 0 N/A El Beta Scan Date Completed Initials Step #4 El Alpha Scan.

Date Completed Initials El Beta Static Date Completed Initials E] Alpha Static Date Completed Initials El Smears Date Completed Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

[9 N/A El Beta Scan Date Completed Initials Step #5 El Alpha Scan Date Completed Initials E] Beta Static Date Completed Initials E] Alpha Static Date Completed Initials El Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6 0 N/A El Smears Date Completed Initials ADM-100 / Page 5 of 8

0 RADIOLO(K URVEY REPO~RT Pases sit....,

DemNsWmtis.

j m-Pad s Sammu I

ADU. 00 Lmwui Log s~

11 31.0 ow"d cobtsm~.

ua Tis ýb Air" Am Ialufiusmt Mumsr 3m.

Fimbs Plmbs Ais& Bsain*

bo Ay"b sm35" hmam moko AIDt" stsin NOWL fa-Dato 101 112013 ADC OW5 I 120&34 31112014 MI

/A 1

1 3&1%

24 60.0 211.7%

152 Tam 1130 LO M2" 267492 4/3/2014 43403 125 1

1 4.5%

137 77 2.7%

1259 mm Aire 100 DO". rate met..

_______adt

________/A view. Namsa.

19013 1212/2013, 4347 S36 is"______

1 7.9%

226 1

RUi N/A

! fNimngs*ifam I

46.140 CPU Us.

V.1 100 ab AID" wb us soft at3%T st erm oooý a

Ab"ftm inwing.

Oloo 10m~

0emma Use..

1868M" 1oome.'o Seam Woomm l00,,sm cP 100000""

lO05.2'1 golpk CPU CMP f De. Kit.

ADU-100.-U401 2

'MDA 3

55

-IDA

-19 MI U

MA 90 44DA 704 M/

/

IIA A.6..420 uN-DA

-3 34 4IDA

-101

'MIA 84

.I4DA 259

/MI MA ADU-1O".-34ft 0

4UDA

-3 56 4IDA

-16

ýMA,

-MI 100.

too DA 852 NI MA IA

  • DU-10041-VE0 I

'UDA 0

60

-UDA 1

0 MIA-109

-NDA 1185 MI I

KI ADU.-100V.U401 0

4MA

-3 68

-UDA 31 "MA NI______

0 gm 104 MI I

IA h3.IOW0-w-006 P

0,

-MA

-3 69

-UDA 35

1(

I,-,im 9

-0 4

I o

~

I ADK.-10O 4[47 I

08 60

-m_

0 PA-MDA 778 MIA soM 20 MIt ADM1PU-S wm_____ ____3__

53 MD 27________A 9

11, MA I

AU10WU00 4ýIDA

-3 64 uMDA 16

-P 5

-DA 415 MI 60 - ID00 I

A34~.4 MA 0

50 uS4DA

-39 91 ham 519 JA 60 - 110 MI ADU-100-W-4"11 I

0A0_9

.MA-_______A

.74 MI 0

0 I

A-100.P.U-12 0

____3__M___9_pýMA 77 JJ M&

AN400.V.4.13 0

3 52 4

A 31 pJM

$s W

VAIA AMU1004V.U-14 0

4MDA

.3 ss

'S4DA

-8 Nt "li so ilIAIA_

9bdw5U Smam 75-120 Nemmims MD swet ditis*m me 1 mine". sias otbswlesmeed "stmasIll Computed volo. Omomi to MbA IN) Cemsatd waft*

l l

ADM-100 /Page 6of 8

AGM-GAM-Lower Surfaces Area: Room 115A Label Type I

Surface I

LocalX I

LocalY 1

Random Floor 0.4 14.7 Area: Room 115 Label Type Surface Local X Local Y 2

Random Floor 8.3 2.4 Area: Room 113 Label Type Surface Local X Local Y 3

Random Floor 5.4 7.1 Area: Room 111 Label Type Surface Local X Local Y 4

Random Floor 19.3 18.4 Area: Gamma Hallway Label Type Surface Local X Local Y 5

Random Floor 66.9 1.3 6

Random Wall 12 5.6 2.3 7

Random Wall 12 71.6 5.6 Area: Room 118 Label Type Surface Local X Local Y 8

Random Floor 14.9 20.8 9

Random Wall 1 6.6 0.9 10 Random Wall 8 8.8 1.6 11 Random Wall 5 0.5 0.5 Area: Room 114 Label Type Surface Local X Local Y 12 Random Floor 19 9.9 Area: Room 110 Local X Local Y Label Type Surface LocaIX LocalY 13 Random Floor 4.5 23.5 14 Random Floor 10.1 17.1 Notes:

Local X and Local Y measured in feet from bottom left hand corner of wall or bottom left corner of floor as seen on floor plan drawing.

0 ADM-100 / Page 7 of 8

Admin Building, First Floor (excluding Room 115), Lower Surfaces ADM-1O0 / Page 8 of 8

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: ADM-115 Page 1 of 5 Classification:

Z Class 1 - Impacted El Class 2-Impacted LI Class 3 - Impacted Survey Type:

El Characterization Z Demolition LI Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/1OOcm 2)

Investigation 3,750 (dpm/100cm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys 0

Floors EI 10% E 50% Z 100% [L N/A Z

Lower walls

[: 10% [L 50% Z 100%

] N/A El Upper walls

[: 10% E]50% E] 100% Z N/A El Ceilings

[] 10% [L 50% [] 100% Z N/A LI Structures (Permanent Furnishings) Interior and Exterior Surfaces EI 10% E] 50% E] 100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

ZL-2360/43-93 Beta/Gamma I Minute 1 probe Tc-99 N/A 612 width/sec Z L-3030/43-10-1 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Alpha - 10 Beta - 120 Z

A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nucide specific (gross measurements), the applicable efficiency and DCGL. values have been selected based on the most limiting nuclides of concern for the survey unit.

ADM-115/ Pagel of 7

Enercon Services Inc.

Survey Package General Survey Instructions: ADM-115 Oage 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5.

Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.

6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8.

Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.

9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 AIJM-1 15 / Page 2of 7

Enercon Services Inc.

Survey Package Location Code Description ADM-1 15

[ Pae 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR = Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as FI, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "1" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (I character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By

~~IL_1'-

J Printd 1?(nc/Sinmtur Reviewed By:

k I I CifaizE (2+ 2ý:ý Ninted Wwielftnaun I

Date:

Date:

Date: L4Ži Package Complete:

ktit L.",

h A

Printed Name/Signature 0

ADM-1 15 1 Page 3of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey]Unit#: ADM-115 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

Survey Technician(s):

R Shank Floor Survey - Completed in accordance with the survey package M N/A Z Beta Scan Date Completed 3/26/14 Initials RS Step #1 LI Alpha Scan Date Completed N/A Initials N/A Z Beta Static Date Completed 3/26/14 Initials RS El Alpha Static Date Completed N/A Initials N/A Z Smears Date Completed 3/26/14 Initials RS Lower Wall Survey - Completed in accordance with the survey package

[] N/A Z Beta Scan Date Completed 3/26/14 Initials RS Step #2 E] Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/14 Initials RS E) Alpha Static Date Completed N/A Initials N/A 0 Smears Date Completed 3/26/14 Initials RS Upper Wall Survey - Completed in accordance with the survey package Z N/A El Beta Scan Date Completed Initials Step #3 E] Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials ADM-115 / Page 4 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: ADM-115 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package 0 N/A El Beta Scan Date Completed Initials Step #4 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials EL Alpha Static Date Completed Initials El Smears Date Completed Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

E N/A El Beta Scan Date Completed Initials Step #5 E] Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6 0 N/A El Smears Date Completed Initials ADM-115/ Page 5 of 7

RADIOLOSURVEY REPORT a

"-l Iab a

k o at T m s f Wasib Of Pm PO Au.,.'

k-l dý SA30 amD 14"4 mo 3.okg..,

Do 312612014 4.h so 27=

1121 39 126 1

0 20

.4%

4010

__+/-

wav pyg K_

E

-bm~

oww

nyu,
w.

wj AA6.

LDU-15-All0 wo____

AM__________

______8____

ADU.11U4.W.-6 6

20D 20 0

kfDA

.167 MA.

/

NA 7

MA 1

/

I ADMI115W.0402 0

'mDA 0

0

-MDA

.267 MI jas MD 12MANA MA

  • -1-.-40

'mDA 0

0

'MDL

-167 NA MA8 D

7

/

/

/

5361-..0

-kMDA 0

0 t

.DA

-167

____-!V_13 45___MmMA

/

AM-115-W-U-22 0

'mDA 0

0 kimD

-167 ADU.115.V.E-1 0

'mDA 0

14

'MDA

-194o k

7 I

/

02-1-VU1 wm___

0__m_17____-

wa a

05MAMI I

laf" ADM-1 15 / Pope6 of 7

211 7

16 3

~13 1

\\12 ROOM 115-CLASS 1 AREA ADM-115 / Page 7 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: ADM-IK-001 I Page 1 of 5 Classification:

Z Class I - Impacted El Class 2-Impacted El Class 3 - Impacted Survey Type:

El Characterization 0 Demolition El Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/100cm 2)

Investigation 3,750 (dpm/100cm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys Floors El 10% [: 50% Z 100% El N/A

" Lower walls

[E 10% El 50% ED 100% [_ N/A El Upper walls

[E 10% El 50% [] 100% Z N/A El Ceilings El 10% [- 50% E] 100% Z N/A El Structures (Permanent Furnishings) Interior and Exterior Surfaces El 10%

[E 50% [- 100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

ZL-2360/43-93 Beta/Gamma I Minute I probe Tc-99 N/A 612

_-2604_9_BtaGam 1

n width/sec Z L-3030/43-10-1 Alpha/Beta I Minute N/A Th-230 Tc-99 Alpha-25 Beta - 150 Z

A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL, values have been selected based on the most limiting nuclides of concem for the survey unit.

ADM-1K-001 I Page 1 of 7

Enercon Services Inc.

Survey Package General Survey Instructions: ADM-1K-001 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5.

Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.

6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8.

Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.

9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 ADM-IK-001 I Page 2 of 7

Enercon Services Inc.

Survey Package Location Code Description ADM-IK-001 I Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR =

Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as Fl, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "1" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (1 character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By:-K-6 t-S1,p,^X Reviewed By:

Pririfed'NedSignature Printed Namne/Signature Date:

Date:

t-/

L/

Date:

Package Complete:

A gwý*

E "

'Printed Name/Signatre ADM-1 K-001 I Page 3 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: ADM-IK-001

] Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

Survey Technician(s):

C Crott Floor Survey - Completed in accordance with the survey package E3 N/A Z Beta Scan Date Completed 3/26/14 Initials CC Step #1 E3 Alpha Scan Date Completed N/A Initials N/A

[

Beta Static Date Completed 3/26/14 Initials CC El Alpha Static Date Completed N/A Initials N/A

[

Smears Date Completed 3/26/14 Initials CC Lower Wall Survey - Completed in accordance with the survey package EN/A 0 Beta Scan Date Completed 3/26/14 Initials CC Step #2 E] Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 3/26/14 Initials CC E] Alpha Static Date Completed N/A Initials N/A 0 Smears Date Completed 3/26/14 Initials CC Upper Wall Survey - Completed in accordance with the survey package ON/A El Beta Scan Date Completed Initials Step #3 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials ADM-1 K-O01 / Page 4 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: ADM-IK-001 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package

[0 N/A El Beta Scan Date Completed Initials Step #4 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials

[] Alpha Static Date Completed Initials El Smears Date Completed Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

EN/A El Beta Scan Date Completed Initials Step #5 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6 0 N/A El Smears Date Completed Initials ADM-1K-001 I Page 5 of 7

"MoI#UV KY RFPORT "Wimi bw CA-_

c rc II w

j ft~bo "m. ftml to

-b" too" UUldbin Af"j dsdnw81119" DetIw 312612014 lmb M

29 13M4 43.10.1 15 100 31.3 toS 19A3%

110TMM0o 11 t 00%

i.

now %J.

100 I WWWWWi Al"-m~"s a _

_r4 x

amU/

0031 393 Wspb siii aO~

soft ll am".

10m m

.j04WO emiic Saone,*

ioftsmo qw m

go.III 108,21%

16,1 I--P1 P

rD

-A UUWI-4 lW -49 W 0

~

mm 0

0

-MDA

-167

_________8236 63IIA I

ADIME1101-W4-104S 0

'UDA 0

0 JAMD

-107 OA XA t

-W 3

I I

I AIIIII-1E401-W.410011 0

4MOA 0

20

.#Am

.107I AIIII&SWO1-V-U411101 0

afmD 0

0

-WMDA

-167

,J______W I

MI AU-301PU1

____0__

20 4

1

-__1_as 409_0 ADM4E4011.W4-U4104

___o_

__1_____A MI 9

km 1

MAN

-.*i Com I

~

n~m 7~s m IIIIIIIIIIIIIA lotl ADM-K-001I/ Pop of 7

ADM-1 K-O01 ADM-1 K-001 / Page 7 of 7

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RBC-201 I Page 1 of 5 Classification:

El Class I - Impacted El Class 2-Impacted Z

Class 3 - Impacted

{

Survey Type:

El Characterization Z Demolition El Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/100cm2)

Investigation 3,750 (dpm/lOOcm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys El Floors

[_ 10% [] 50% [] 100% Z N/A El Lower walls El 10% El 50% E] 100% E N/A E

Upper walls Z 10% El 50% [] 100% [1 N/A Z

Ceilings 0 10% El 50% [- 100% El N/A El Structures (Permanent Furnishings) Interior and Exterior Surfaces El 10% El 50% El 100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

L-2360/43-93 Beta/Gamma 1 Minute I probe Tc-99 N/A 612 L26/39Ba/am 1Miu width/sec ZASC 950 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Alpha - 25 BetaE-15 El A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGLvalues have been selected based on the most limiting nuclides of concern for the survey unit.

RBC-201 / Page 1 of 9

Enercon Services Inc.

Survey Package General Survey Instructions: RBC-201 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2. If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.
3. Document all scan survey results on the applicable survey maps and data results sheets.
4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5. Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.
6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8. Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.
9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 RBC-201 / Page 2 of 9

Enercon Services Inc.

Survey Package Location Code

Description:

RBC-201 I Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

=

Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as Fl, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "I" (e.g., WI, F I, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (I character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By:

K Reviewed By:

T Package Complete:

Date: _*

Date:

0~1 F Brown Printed Namne/Signatuire RBC-201 / Page 3of 9

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RBC-201 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

K Myers Survey Technician(s):

A Ball Floor Survey - Completed in accordance with the survey package E N/A Step #1

[I Beta Scan Date Completed Initials El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials E] Alpha Static Date Completed Initials El Smears Date Completed Initials Lower Wall Survey - Completed in accordance with the survey package (DN/A Step #2 LI Beta Scan Date Completed El Alpha Scan Date Completed El Beta Static Date Completed

[] Alpha Static Date Completed El Smears Date Completed Initials Initials i

Initials

+

Initials

+

Initials Upper Wall Survey - Completed in accordance with the survey package ED N/A Step #3 0l Beta Scan Date Completed 09/19/2013 Initials KM EL Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 09/19/2013 Initials KM E) Alpha Static Date Completed N/A Initials N/A 0 Smears Date Completed 09/19/2013 Initials KM RBC-201 / Page 4 of 9

Enercon Services Inc.

Survey Package Building: Reactor Building Survey Unit #: RBC-201 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package EN/A

[ Beta Scan Date Completed 09/19/2013 Initials KM Step #4 El Alpha Scan Date Completed N/A Initials N/A

[ Beta Static Date Completed 09/19/2013 Initials KM E Alpha Static Date Completed N/A Initials N/A

[ Smears Date Completed 09/19/2013 Initials KM RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

Z N/A El Beta Scan Date Completed Initials Step #5 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials E Alpha Static Date Completed Initials El Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6 0 N/A El Smears Date Completed Initials RBC-201 / Page 5 of 9

RADIOL4XURVLY REPOR~T hsnmm yulumer bssamieom Nut...

Iuiskw A

Re MI (4m)

(mni 1g.,, afto NOW..

Dae W191201340 ASC "

122034 31UM214 MIA XIA 1

3&.1%

34 G0.

25.7%

102 III=L.

Lu 3IS.

32007 1120M SN 13 43."3151 4A6%

134 go4.%

37 m00tm e

~~~~~

OWUI MWr M

lMW M

Apb m

3..umA Urn.~~~ltasss CIA 100ums*'

%Ju.

ls I

Ou*

9 10m VM

~

l~mt P

S~~'

l~i

.CU 9

~

3mRt 0

b.~m

__3_

63 MI_12 90-120 MA RRC4OI.-U4MA1 0____

______7____-1 11

ý:

RMC-2014411412 7_

122__0_IA 90_2

~~.

..U~rt N4 12 Iumm umh.

MIA 9012 MIA599.3%d m...

hR40444 0

mb3 S

JM.;.Io h

6 I

9 2

I N9a4F4 0

um

-3 so la iota RBC-201 / Pap 6 of 9

a RREACTOR-CTL-Upper Surfaces Area: Room 201A Label I

Surface South of A East of A Local Z 1

Systematic Cellin 0.6 1f5.3 Notes:

Distances are measured in feet from Reference Point as seen on floor plan drawing.

Area: Room 204 Label Te Surface South of B East of B Local Z 2

S stemalic Ceiling 16.3 7.8E Notes:

Distances are measured in feet from Reference Point as seen on floor plan drawing.

Area: Room 205 Label Type Surface South of C East of C Local Z 3

Systematic Roof 7.8 12.8f Notes:

Distances are measured in feet from Reference Point as seen on floor plan drawing.

Area: Uppr Ceiling Label I

Type a Surface North of D West of D Local Z 4

Systematic Ceiling 0.8 2.3 Label Type Surface North of E West of E Local Z 5

Systematic Ceiling 12.2 8.4 Label Tye Surface North of F East of F Local Z 6

o Systematic Ceilin 5.0 2.5ua Label Tye Surface South of G West of G Local Z 7

Systematic Ceiling 8.4 2.7 L

Area: Outer Walls Above Room Roofs Label Type Surface Distance from H Height above Roof SSystematic Wall 9.5 7.3 Area: Outer Wafls Above Room Roofs Label Typ Surface Distance from J Height above Roof 9

Systematic wall 13.2 7.3 Area: Outer Walls Above Room Roofs Label T

Surface Distance from K Height above Roof 10 Systematic I

Wall r11.5 3

Area. Outer Walls Above Room Roofs

13.

a Height above Roof7.

Label T e Surface Distance from KHehtaoeof 1S?

steaic Wall 19.7 11 7.3 Area: Outer Walls Above Room Roofs Label Tye Surface Distance from L Height above Roo 12 Systematic Wall 4.3 7.3 Area: Outer Walls Above Room Roofs Label I

Type Surface Distance from L Height above Roof 13 Systematic Wall 26.6 7.3 Area: Outer Walls Above Room Roofs Label Tye Surface Distance from M Height above Roof 14 Systematic Wall 1.9 7.

Notes:

Distances are measured in feet from Reference Point as seen on floor plan drawing.

RBC-201 / Page 7 of 9

Lor0 n

Control Leve Upper Surface Sample Locations RBC-201 I Page 8 of 9

RBC-201 / Page 9 of 9

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-000-4 I Page 1 of 5 Classification:

[] Class 1 - Impacted Z Class 2-Impacted E3 Class 3 - Impacted Survey Type:

El Characterization Z Demolition El Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/1OOcm 2)

Investigation 3,750 (dpm/100cm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys F-1 Floors E] 10% [:150% [] 100% Z N/A Z

Lower walls

[:110% 050% LI 100%

] N/A E] Upper walls E110% [-150% [] 100% Z N/A El Ceilings El 10% [- 50% F] 100% Z N/A El Structures (Permanent Furnishings) Interior and Exterior Surfaces LI 10% [1 50% Ej 100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

ZL-2360/43-93 Beta/Gamma 1 Minute I probe Tc-99 N/A 612 width /sec Alpha -25

[ASC 950 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Beta-150 B -

Z A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nucide specific (gross measurements), the applicable efficiency and DCGL. values have been selected based on the most limiting nuclides of concern for the survey unit.

ADM-000-4 / Page 1 of 8

Enercon Services Inc.

Survey Package General Survey Instructions: ADM-000-4 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5.

Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.

6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8.

Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.

9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 ADM-000-4 / Page 2 of 8

Enercon Services Inc.

Survey Package Location Code Description ADM-000-4 I Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBI3

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as Fl, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "1" (e.g., W 1, F 1, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (I character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By:

Reviewed By:

Package Complete:

Date:

/0 Date:

I&Lol /j Date: //

7 /l)

Pr~idi~ameISignature Frank Brown Printed Name/Signature ADM-000-4 / Page 3 of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-000-4 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

D Border Survey Technician(s):

C Crott Floor Survey - Completed in accordance with the survey package Z N/A El Beta Scan Date Completed Initials Step #1 F] Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials Lower Wall Survey - Completed in accordance with the survey package ElN/A Z Beta Scan Date Completed 9/26/2013 Initials DB Step #2 El Alpha Scan Date Completed N/A Initials N/A

[ Beta Static Date Completed 9/26/2013 Initials DB El Alpha Static Date Completed N/A Initials N/A

[ Smears Date Completed 9/26/2013 Initials DB Upper Wall Survey - Completed in accordance with the survey package ED N/A El Beta Scan Date Completed Initials Step #3 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials ADM-000-4 / Page 4 of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-000.4 j Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package 0 N/A El Beta Scan Date Completed Initials Step #4 E] Alpha Scan Date Completed Initials El Beta Static Date Completed Initials E] Alpha Static Date Completed Initials El Smears Date Completed Initials RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

Z N/A El Beta Scan Date Completed Initials Step #5 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6

[

N/A El Smears Date Completed Initials ADM-000-4 / Page 5 of 8

RADIOLOOURVEY REPORT oP ee...

D8-eUs leteitin 6my Iu e Package ADNM400.4 Lower ISfurve Log Nombe..

7 02/1012013-004 9,M41 calibratin Count Thm Mph.

fttkpud Mal.

D1A imadmumett Nu-b1, m

Inm Prbe Are 11 Alpha llkeoud lept) llde-7 Alpha BMDA (dNoe fe n:

ABC 950 1208344 311/2014 NIA N A 1

lO 32.1%

24 60.0 25.7%

162 Time:

1200 Ludhum 2360 267493 4/3/2014 43.93 5

1 1

4.5%

137 79 2.7%

1314 SmbOW Are.

100 Dose mette meterIL..

y.mesaueknd' N/A.

Flotes.m mete.

___j____

j___

RWP*.

N[A

/iT well~s.. -ne :

70.110 CPU Sa

%=

S0 Remneble Aloha Remov.able Beta E,

fatl__etal Alp_

tatler/etel Soft Deeorlptien Ism/

DMI DIE/

DtMI DPW/

0-De APEl DPm AMph. Scan Deta e

I (Li I0Oema C

iOOem 5

1000e0.1 0,a,_CPU 100e2m(

1

)

10Oema CM 2oom1 00-1 le&

t Ren*S nCPU lea.

In

_ DozeRate ADM4004-W-Ml001 0

-MDA

-3 66

<MDA 23

/AA N/A N/A 102

<MDA 852 N/A 70 -110 N/A ADZ-0004-W-M.002 0

<MDA

.3 19 cMDA

-4 N/A N/A N/A 85

-LIDA 222 N/A 70 -

110 N/A A.DK-404W-U4-03 0

dMDA

-3 63

'MDA 12 N/A N/A N/A 77 tMDA

-74 N/A

70. Ito N/A ADM-0O1-W-.M.04 0

'MDA

-3 57

<NDA

-12 N/A N/A N/A 95

<MDA 593 N/A 70-110 N/A AD3N4004-W-U-06 0

<MDA

-3 64 4MDA 16 N/A N/A NMA 72

<MDA

.259 N/A 70- 110 N/A ADM40(04-W-.M006 I

.MDA 0

70

<MDA 39 1/A N/A N/A 72

ýMDA

.259 NIA 70 -110 N/A ADflMo004-W.M-007 0

dMDA

-3 71

<MDA 43 N/A N/A N/A 82

<MDA Il]

N/A 70-110 N/A ADM4X).O4-W.M.008 0

dMDA

-3 76

-MDA 62 N/A N/A N/A.

90

<MDA 407 N/A 70- 110 N/A ADM-0004-W-.M009 0

<MDA

.3 48

<MDA 47 N/A N/A N/A 70 dADA

-333 N/A 70- 110 N/A ADMX40O4-WM-MILO 1

B4DA 0

55

-&DA

-19 N/A N/A N/A 93

-MDA 519 N A 70- 110 N/A Af]Z0004-W-U.O11 0

dMDA

-3 62 dMDA 8

M/A N/A N/A 75

<MDA

-148 N/A 70- 110 I/A ADME0004*W-MN012 0

04DA

-3 67 dMDA 27 N/A N/A N/A 87

<MDA 296 N/A 70m 110 N/A A]DM2004.W-E-013 I

dADA 0

57 dMDA

-12 NIA NIA N/A 90 4MDA 407 N/A 70- 1 t0 N/A ADm40004*-*.N*4 I

<MDA 0

59 11DA

-4 N/A N/A NIA 81

<1DA 74 NIA 70 -

O/A C.mment*

Reme~bO All eunst dutlsee. wrteA uia..t o n olted.theel.

.08 rootnatem III Compted vstel enaneued to MDA 12l Computed value lOfI ADM-000-4 / Page 6 of 8

ADM-SUB-Lower Surfaces (SU 000-4)

Area: Room N16 Label Type Surface Local X Local Y 1

Systematic Wall 9 23 1.3 2

Systematic Wall 9 13 1.3 3

Systematic Wall 9 7.7 1.3 4

Systematic Wall 8 37 1.3 5

Systematic Wall 8 28 1.3 6

Systematic Wall 8 19.1 1.3 7

Systematic Wall 8 10.1 1.3 8

Systematic Wall 8 1.2 1.3 9

Systematic Wall 7 8.3 1.3 10 Systematic Wall 6 2.7 1.3 11 Systematic Wall 5 7.6 1.3 12 Systematic Wall 3 15.1 1.3 13 Systematic Wall 2 22.7 1.3 14 Systematic Wall 1 30.4

1.3 Notes

Local X and Local Y measured in feet from bottom left hand corner of wall or bottom left corner of floor as seen on floor plan drawing.

0 ADM-000-4 / Page 7 of 8

ADM-O-4 / Page 8 of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-000-5 I Page 1 of 5 Classification:

E Class 1 - Impacted El Class 2-Impacted El Class 3 - Impacted

[Survey Type:

El Characterization E Demolition El Final Status Survey I

Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 1,000 (dpm/1 00cm 2)

Investigation 750 (dpm/1OOcm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys 0

Floors E] 10% E] 50% E]100% [ZN/A E Lower walls E] 10% E] 50% E 100% [] N/A El Upper walls El 10% [] 50% E] 100% E N/A E Ceilings E1 10% E] 50% E 100% Z N/A El Structures (Permanent Furnishings) Interior and Exterior Surfaces 0l 10% Dl 50% E] 100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

I probe

[DL-2360/43-93 Beta/Gamma 1 Minute width Tc-99 N/A 612 per/sec

]ASC 950 Alpha/Beta I Minute N/A Th-230 Tc-99 Alpha-25 Beta-150 0_

E A Planchet Counter shall be used for analysis of any required removal contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL. values have been selected based on the most limiting nuclides of concern for the survey unit.

ADM-000-5 / Page 1 of 24

Enercon Services Inc.

Survey Package General Survey Instructions: ADM-000-5 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14.

5.

Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.

6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8.

Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.

9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63; Sr-90 Floor and wall data from the post-decontamination survey will be used in place of the computer generated points resulting in 16 wall points and 12 floor points. These 28 points replace the 14 points on the list.

ADM-000-5 / Page 2 of 24

Enercon Services Inc.

Survey Package Location Code Description ADM-000-5 I Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as Fl, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "I" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (I character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "00 " means survey point location number I. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By:

Kurt Myers Reviewed By:

T J Keane Package Complete:

Frank Brown Date:

,/

ri.ited Name/Signature III_________

Date: /d 11/3 Printed Name5ignature ADM-000-5 / Page 3 of 24

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-000-5 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

Survey Technician(s):

R Boezar Floor Survey - Completed in accordance with the survey package

[I N/A Step #1 0 Beta Scan Date Completed 10/1/13 Initials RB LI Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 10/1/13 Initials RB LI Alpha Static Date Completed N/A Initials N/A 0 Smears Date Completed 10/1/13 Initials RB Lower Wall Survey - Completed in accordance with the survey package

[3 N/A Step #2 Z Beta Scan Date Completed 10/1/13 Initials RB LI Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 10/1/13 Initials RB E] Alpha Static Date Completed N/A Initials N/A 0 Smears Date Completed 10/1/13 Initials RB Upper Wall Survey - Completed in accordance with the survey package Step #3 O N/A EL Beta Scan Date Completed Initials E] Alpha Scan Date Completed Initials 0I Beta Static Date Completed Initials LI Alpha Static Date Completed Initials EL Smears Date Completed Initials

.5 1

5.

n

.5.

ADM-000-5 / Page 4 of 24

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-000-5 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package 0 N/A JR Beta Scan Date Completed 10/1/13 Initials RB Step #4 EL Alpha Scan Date Completed N/A Initials N/A Z Beta Static Date Completed 10/1/13 Initials RB E] Alpha Static Date Completed N/A Initials N/A E Smears Date Completed 10/1/13 Initials RB RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

ED N/A Step #5 E: Beta Scan Date Completed Initials

[] Alpha Scan Date Completed Initials 0I Beta Static Date Completed Initials FI Alpha Static Date Completed Initials 0I Smears Date Completed Initials renetrauions, irains, and upenings zurvey - C..omnpleted in accoraance with the survey package N/A ADM-000-5 / Page 5 of 24

RADIOL4OURVEY REPORT punaa of Sumve"e oa Survey s.way AD104XO-Lo lefy" Number*

01/10/2013-007 owae it sacem, a..an i

crmi C.Avlf Dec62l Calawtbo.

Count Tha.

Alpha sDckginmd Net. EIAM a.1//23 heatcment Iue Due hh.

Probe Ares (tem)

Codai Alpha BaDlcground (epmc )

Alpha =A (dp-A f--J i

Beta Elfficenec (deed D't.,

10 1 2013 ABC 960 1208344 3/1/2014 IIA MIA 1

1.0 82.1%

24 60.0 25.7%

152 Time:

1530 Ludlnro 2360 22026?

1111412013 43-93 125 1

1 4.6%

L4 1Loa 4.3%

925

-mear Ar.

100 rma ceta meter

_ndIA floor...n meoter

_____________I-____________

________.____I______

______________________________________________A1

/

BIT -al See Can 75-200 cm Some IL 10 R_ _

bI. Aloha ble Deft

/ t L

_____A__tttt./Tot.

De=143t/

DFI I

DIm!

DPM DMI D1U DPM/

DPK/

Ore..

DPMW DP/

Alpha Been Bet. SeaD

____CPM

lOOcmu, 1CeOm' 1

ar.

CPm 100cue'"

100emm Oro.CPU 100lom" 100emam CPm 100.m

t l 100cmm' M RaIleina 6CPU Run&

  • De.

t.

ADl-X0G05-U-.-001 0

-MDA

.3 58

'MDA

-8 N/A NIA MIA FZ

'IADA

-393 N/A 75-200

  • /A ADN-OS-W.U.0002 0

<MDA

-3 59

'MDA

-4 N/A N/A N/A 163 1410 1410 N/A 75 -200 2/IA AZYM-00S-W.K10003 0

'MDA

-3 60

'IMDA 0

N/A N/A N/A 133 cMDA 717 N/A 75 - 200 NIA A2M-0005-W.U-0004 0

'MDA

.3 63

<MDA 12 NIA M/A N/A 118

ýMDA 370 N/A 75-200 N/A ADM-0005-W.M-OOOS 0

OMDA 3

65

<MDA 19 N/A NIA N/A 96 rMDA

-139 N/A 75-200 NIA ADU-.ODM-U-0005 0

'MDA

-3 61

'MDA 4

N/A N/A NIA lOB

ýMDA 139 N/A 75 - 200 N/A A2)l.m-0-WK.f0007 0

0MDA

.3 55

'FdDA

-19 N/A N/A NMA 134 rMDA 740 N/A 75.200 N/A ADM-0005-W.M-.000 0

4MDA

.3 65

'MDA 19 N/A 6/A N/A 124

<MDA 509 N/A 75-200 N/A ADE-00-5.W-)0009 0

<MDA

-3 66

<MDA 23 N/A N/A NMA 98

<NMDA

-92 N/A 75.200 N/A ADfM.0005.WK.M0010 0

MDA

-3 58

'MDA

-8 NIA N/A NIA 89

'MDA

-301 NIA

75. 200 N A ADIMN-1000IF-1..0811 0

'MDA

-3 57 41MDA

-12 NIA N/A N/A 144 971 971 N/A 75 - 200 N/A AUADI-0005-WK-012_

0 1

btDA

-3 64 0MDA 16 N/A NIA MIA 149 1087 1087 N/A 75.200 N/A ADWI-.0 V-W-M.001S 0

NMDA

-3 64 UMDA 16 N/A N/IA N/A 117

.?DA 347 N/A 75 - 200 NIA ADM-U005-W-M.0014 0

'MDA

-3 59

'IDA

-4 N/A N/A N/A 98

'MDA

-92 N/A 75w 200 N/A ADM-000S-W4&W01s 0

'MDA

-3 71

'NMDA 43 NIA NIA NIA 172

.1618 1618 N/A 75-200 NIA ADI.-0005-W-N0016 0

44DA

-3 0

dclDA

-233 N/A N/A NIA 83

<MDA

-439 NIA 76-200 N/A 14 Tritiom Sm-.

Ths aS" Samples 1. 14 of atteeh"d lob Report ad attecehd s n loeatsoa S.O 100% Been of Floow and Well.

Itemsnrha All eount dur*tRnS ee 1 n.auto unless otherwie noted.

vootnoot. III Coinputed value compared to EDA 121 Computed valm I of 2 ADM-O00-5 / Page 6 of 24

RADIOLOGICAL SURVEY REPORT Backlpoand Bata 8W Cu.bmtlo Cousnt Thn.

Alpha

  • kg-md Bet. MDA lutv~

NImm~mm Dw

?&

Probe Am Im*, )

(vali Alp]ha Bakgound Blk,:

Alpha MDA idpl)

[".I)

Dat Fzmcfen (dpm)

Dat 1010/13/

ABC 950 1208344 a/1l2014'N'A MIA I

82.1%

24 60 25.7%

152 Tle*.

1530 Lud1m 2360 220267 It/14/2013 43-93 125 1

1 4.6%

134 102 4-%

925 flar

Aram, e

00 phrmaete" RP MIA

____ _ Sm oo

_e 75-150 C_ M 1___

_00 Remv~ W, Apha Re-al aet" Obtlllotad Alph--

S.atm/"d DesedpUon DPMI DPUI DPMI DPru DPMI DPW/

GDross DPI DPNI Alpha a.-.

Bat. 8-an a,... CUN 100,o.2111 100ova2(P Gfo0.CPIU 100m2l 1 0lem3

")

Gr.m.CFPM 1oMM21 100ill 1-21 CP2 100em02111 100,.02(2)

Rauoiu SCPM Rq.I.CP!

fi D-.. 5Rat.

AD)M-OOr-7.M-0017 0

<MDA

-3 59

ýMDA

-4 N/A N/A N/A 7S

-MDA

-624 N/A 75-150 NMA ADW-COOS-P-M-0018 0

-MDA

-3 55

.'DA

-19 NIA M/A N/A 82

<MDA

-462 MIA 75-150 NIA ADM-0005-1.U.019 0

<MDA

.3 62

<MDA 8

NIA N/A N/A 140

<MflA 879 NIA 75-150 N/A ADUCOOS-F-M-0020 0

<MDA

-3 78

<MDA 70 N/A N/A N/A 102

<MDA 0

N/A 75-150 N/A ADM-C000-F-U-00ZI 0

ýMDA

-3 62

ýMDA 8

N/A NIA N/A 148 1064 1064 N/A 75-150 N/A ADM-0005-F.U.0-52 0

<MDA

-3 71

ýMDA 43 N/A N/A N/A 109

ýMDA 162 N A 75-150 NIA ADM-0005-F.M-0023 0

MO.DA

-3 57

<MDA

-12 N/IA MA NA as85

'MDA

-393 NIA 75-150 N/A AD,.-OOS-p-U-0024 0

-MDA

-3 81

<MDA 82 N/A N/A N/A 123

<MDA 486 N/A 75-150 NIA ADM-005-V*U.11O5 0

NMDA

-3 59 3MDA

-4 N/A N/A N/A 94

<MDA

-385 N/A 75-150 N/A ADM-000C-l-M-0026 0

<MDA

-3 60 4MDA 0

N/A N/A N/A 90

'MDA

.277 NIA 71-150 N/A ADU.4100.F.M-0027 0

<MSDA

-3 56 i

1MDA

-16 N/A N/A N/A 105

<MDA 69 NIA 75-150 N A ADM-OOOSP-M-0028 0

'MDA

-3 58

<MDA

-8 N/A N/A N/A 95

'MDA

-162 N/A 75-150 N/A Re-mhm Ad.,.t du01Uo0.o. I aldnuo umsla oathoei note.&

2032 ADM-000-5 / Page 7 of 24

Ao 1

3 2

5 14 13 Tritium Sample Locations Neutron Level - Admin Bldg 1 K Pit Sample Locations North is Left ADM-000-5 / Page 8 of 24

0*

a w

D ENERCON Excellence-Every projecr. Every day.

Radiological Survey Form (Continuation Sheet)

Surveyed By:

R Boczar I

Log Number:

T 01/10/2013-007 13 14 15 16 28 20 24 10 12 9

11 27 19 23 26 22 18 3

2 4

1 K Tank Room Pit Static/Removeable Locations 25 21 17 ADM-000-5 / Page 9 of 24

,Fk6 TELEDYNE 01 BROWN ENGINEERING, INC.

A Teledyne Technologies Company 2508 Quality Lane Knoxville, TN 37931-3133 865-690-6819 Frank Brown Enercon 4490 Old William Penn Highway Murrysville, PA 15668 Report of Analysis/Certificate of Conformance 09/23/2013 LIMS #:

L56078 Project ID#:

EN005-3EUOFB-10 Received:

09/18/2013 Delivery Date:

P.O.#:

Release #:

09/25/2013 SUNYUB022 SDG#:

This is to certify that Teledyne Brown Engineering - Environmental Services located at 2508 Quality Lane, Knoxville, Tennessee, 37931, has analyzed, tested and documented samples, as received by the laboratory, as specified in the applicable purchase order.

This also certifies that requirements of applicable codes, standards and specifications have been fully met and that any quality assurance documentation which verified conformance to the purchase order is on file and may be examined upon request.

that the above statements are true and correct.

Operations Manager Cross Reference Table Client ID Laboratory ID Station ID (if applicable) 1 L56078-I 2

L56078-2 3'

L56078-3 4

L56078-4 5

L56078-5 6

L56078-6 7

L56078-7 8

L56078-8 Page 1 of 9 ADM-000-5 / Page 10 of 24

,0 6

TELEDYNE 01 BROWN ENGINEERING, INC.

A Teledyn Technoloies Comparfy 2508 Quality Lane Knoxville, TN 37931-3133 865-690-6819 Cross Reference Table Client ID Laboratory ID Station ID (if applicable) 9 L56078-9 10 L56078-10 11 L56078-11 12 L56078-12 13 L56078-13 14 L56078-14 15 L56078-15 16 L56078-16 17 L56078-17 18 L56078-18 19 L56078-19 20 L56078-20 21 L56078-21 22 L56078-22 23 L56078-23 24 L56078-24 25 L56078-25 26 L56078-26 27 L56078-27 28 L56078-28 This report shall not be reproduced or distributed except in its entirety.

Page 2 of 9 ADM-000-5 / Page 11 of 24

Repoof Analysis ArL TELEDYNE0 09/23/13 13:47 BROWN ENGINEERING, INC.

A Teledyne Technologies Company L56078 Enercon EN005-3EUOFB-10 Sample ID:

I Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-1 ISOP#

Activity Uncertainty

[im I

Aliquot Aliquot Reference Count Count Count 1 Radionuclide Cone 2 Sigma MDC Units I#n Volume Units Date Date Time Units Flag Values H-3 2010 ( 4.78E+00 6.56E-s-00 9.44E+00 [DPM/TOTAL 1 100

]

1 09/20/13 0

-5 M

/u Sample ID: 2 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-2 S

Activity Uncertainty SiC Runi Aliquot Aliquot Reference Count Count Count Radionucde SO Cone 2 Sigma Units I

Volume Units Date Date I Time Units Flag Values

- __[_

_i

_I_

i

_[_

H-3 P 2010 [ 9.31E+00 I 7.23E+00 9.38E+00 [DPM/rOTAL 1

100 1

[ _09/20/131 5

[ M---V-U.

--- V-Sample ID: 3 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

%Moisture:

LIMS Number:

L56078-3 1Activity Uncertainty S

J Run Aliquot Aliquot Reference Count Count Countr Radionuclide SOPr Cone MDC Units iln Volume Units Date Date Time Units Flag Values H-3 12010 1 1.62E+01 [ 8.27E-00 [ 9.52E+00 JDPM/TOTAL 1

100 T

1 09/20/13; 5.[

M-

-+I[

] [+

Sample ID:

4 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-4 1 op I Activity J Uncertainty Run f Aliquot Aliquot Reference Count fCount Count Radionuclide SO#

Cone f2 Sigma [ MDC I units a

Volume Units j Date Date I Time Units Flag Values H-3

.... 12010 1 1.04E+01 7.42E+00 9.42E+00 DPM/TOTAL I _

100 109/20315:

M

[U[]

I Flag Values U

=

Compound/Analyte not detected (< MDC) or less than 3 sigma No = Peak not identified in gamma spectrum

+

=

Activity concentration exceeds MDC and 3 sigma; peak identified(gamnna only)

Yes = Peak identificd in gamma spectnum U*

=

Compound/Analyte not detected. Peak not identified, but forced activity concentration exceeds MDC and 3 sigma High

=

Activity concentration exceeds customer reporting value

        • Unless otherwise noted, the analytical results reported Spec

=

MDC exceeds customer technical specification are related only to the samples tested in the condition they L

Low recovery are received by the laboratory.

H-

=

High recovery Hd ttin reov rt e aMDC

- Minimum Detectable Concentration Bolded text indicates reportable value.

Page 3 of 9 ADM-000-5 / Page 12 of 24

Repoof Analysis RTELEDYNE 09/23/13 13:47 BROWN ENGINEERING, INC.

A Teledyne Tachnologies Company L56078 Enercon Frank Brown EN005-3EUOFB-10 Sample ID: 5 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-5 1

Activity Uncertainty 1

] Run Aliquot Aliquot Reference Count Count Count Radionuclide SOP#

Cone 2

MDC Units Volume Units Date Date Time j Units Flag Values H-3

[2010 3.07E+00 6.25E+00 9.39E+00 I DPM/rOTALI 1

100 1_

I__

09/20/"131_

5______

___I_

Sample ID:

6 Collect Start 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:. L56078-6_______________

L SOP#T Activity 1Uncertainty1

]

t Run Aliquot Aliquot Reference Count Count Count1 Radionuclide Cone 2 Sigma Units Volume Units Date Date Time Units Flag Values H-3 2010

-2.81E+00 5.17E+00 J 9.43E+-0 ]DPM/TOTAL II 100 60%

1 [09/20/131 T

1 M

I U 1 M

Sample ID:

7 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-7 S Activity 1Uncertainty2 1i 1

rSRun Aliquot 1 Aliquot Reference Count:

Count Count Radionuclide SOP#

Cone 2 Sigma MDC Units Volume Units Date Date Time Units Flag Values H-3

_2010 I -6.70E_01]

5.60E+00 J 9.43E+00 DPM/TOTAL 1

100 J

1 109/20/131 5

1 M

FOI U I Sample ID: 8 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-8 Radionuclide SF'j Conc 2 Sigma MDC Units Volume Units Date Date Time Units Flag Values H-3 J 2010 T 3.49E+00 "

6.35E+00 9.44E+00 ]DPMII'OTAL [1 100 0

l-t[9/20/13.

5 M

U U Flag Values U

=

Compound/Analyte not detected (< MDC) or less than 3 sigma No = Peak not identified in gamma spectrum

+

=

Activity concentration exceeds MDC and 3 sigma; peak idcntified(gamnma only)

Yes = Peak identified in gamma spectrum U*

=

Compound/Analyte not detected. Peak not identified, but forced activity concentration exceeds MDC and 3 sigma High

=

Activity concentration exceeds customer reporting value

        • Unless otherwise noted, the analytical results reported Spec

=

MDC exceeds customer technical specification are related only to the samples tested in the condition they L

=

Low recovery are received by the laboratory.

H

=

High recovery Bolded text indicates reportable value.

MDC-Minimum Detecable Concentration Page 4 of 9 ADM-000-5 / Page 13 of 24

Repoof Analysis 111k TELEDYNE 09/23113 13:47 BROWN ENGINEERING, INC.

A Teledyne Technologies Compeny L56078 Enercon Frank Brown EN005-3EUOFB-10 Sample ID: 9 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-9 S

Activity Uncertainty M

Run Aliquot Aliquot Reference Count Count Count Radionuclide Conc 2 Sigma MDC Units Volume Units Date Date Time Units Flag Values H-3 2010 I -2.73E+00 5.18E+00 9.42&+00 I]DPMrT I

I

/

%13 5

M iU:

Sample ID:

10 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-10 Sop#

Activity -FUncertainty TRun Aliquot Aliquot Reference Count Count Count Radionuclide, Conc 2 Sigma J MDC Units Ni#

Volume Units Date Date Time Units Flag Values H-3 1 2010 1 3.60E+00 i 6.33E+00 9_38E+00 IDPM/TOTAL II 100

]

[09/20/1 5

M JUI Sample ID:

11 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/1812013

% Moisture:

LIMS Number:

L56078-1 1I N Activity Uncertainty Run Aliquot Aliquot Reference

Count, Count Count RadionuclideJ SOPT Conc j 2Sima MDC Units aI Volume Units Date Date I Time Units Flag Values HI-3 12010 1 3.75E+00 6.39E+00 9.44E+00 [DPM/TOTAL

]

100 1

,09120/131 5

1 M

UI I

I Sample ID: 12 Collect Start 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LTMS Number:

L56078-12 1 S Activity Uncertainty S

[

C Run Aliquot Aliquot u

Reference Countl Count Count Radionuclide SOPM Cone 2 Sigma MDC Units if Volume Units Date Date Time Units Flag Values JH-3 52010

] -6.68E-01 ] 5.58E+00 [9.40E+00 [DPMrrOTAL t

]

100

% [

[9/20/1 5 I M

-I ll XI i Flag Values U

=

Compound/Analyte not detected (< MDC) or less than 3 sigma No

= Peak not identified in gamma spectrum

+

=

Activity concentration exceeds MDC and 3 sigma; peak identified(gamma only)

Yes = Peak identified in gamma spectrum U*

=

Compound/Analyte not detected. Peak not identified, but forced activity concentration exceeds MDC and 3 sigma Unless otherwise noted, the analytical results reported High

=

Activity concentration exceeds customer reporting value Spec

=

MDC exceeds customer technical specification are related only to the samples tested in the condition they L

=

Low recovery arc received by the laboratory.

H

=

High recovery B

e =t Hin reov rt e vMDC

- Minimum Detectable Concentration Bolded text indicates reportable value.

Page 5 of 9 ADM-000-5 / Page 14 of 24

Repowf Analysis Ari TELEDYNE 0 09/23/13 13:47 BROWN ENGINEERING, INC.

A Teledyne Technologies Company L56078 Enercon Frank Brown EN005-3EUOFB-10 Sample ID:

13 Collect Start; 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number-L56078-13 Sop#

Activity Uncertainty MDCRun Aliquot [Aliquot 1 Reference Count Count 1Count Radionuclide S

Cone 2

Units D#

Volume Units Date Date I Time Units nag Values H-3

[ 2010 [ 3.08Ee00 [ 6.28E+00 j 9.44E+00 IDPM/TOTAL]

100

% J 09/20/13 5

M U

Sample ID:

14 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-14 Sop Activity.Uncertainty 1 1

Run Aliquot Aliquot 1 Reference Count Count 1 Count Radionuclide S

Cone P2 Sigma MDC Units Volume Units Date I

Date I Time Units Flag Values H-3 12010 1.54E+00 6.04E+00 9.48E+00 ]DP*

rrOT AL I to 1

[-

1

[09/20/131 5

1 M I UI I

I Sample ID:

15 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-15 1M Activity Uncertainty 1 C

Run Aliquot Aliquot Reference Count Count o

Radionuclide Cone 2 Sigma UnC Uits Volume Units Date

{ Date Tim e Unrit Flag Values H-3 2010

-6.16E-01 5.60E+00 9.42E+00 DPM TOTALJ 100 09/ 20/1 3

J___

m______

Sample ID:

16 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-16 Activity Uncertainty Unt ]Run Aliquot Aliquot Reference Count Count Count Radionuclide SOP#

Cone 2 Sigma

  • CUnit H VolumeI Unit Date I Datel I Tim Unit Flag Values H-3_"__20_0_-3.25E-01 5.73E+00 9.IE+00 DPM TOTAL 100 G

3 5

M u

Flag Values U

=

Compound/Analyte not detected (< MD) or less than 3 sigma No = Peak not identified in gamma spectrum

+

=

Activity concentration exceeds MDC and 3 sigma; peak identificd(gamma only)

Yes = Peak identified in gamma spectrum U*

Compound/Analytc not detected. Peak not identified, but forced activity concentration exceeds MDC and 3 sigma High

=

Activity concentration exceeds customer reporting value

        • Unless otherwise noted, the analytical results reported Spec vDC exceeds customer technical specification are related only to the samples tested in the condition they L

=

Low recovery are received by the laboratory.

H

=

High recovery MDC - Minimum Detectable Concentration Bolded text indicates reportable value.

Page 6 of 9 ADM-000-5 / Page 15 of 24

Repoof Analysis TELEDYNEO 021 7r BROWN ENGINEERING, INC.

A Teledyne Technologies Company L56078 Enercon Frank Brown EN005-3EUOFB-10 SampleID:

17 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

1.56078-17 SCv Uncertainty Run quot Reference Count Count Count1 RadAionuclide Uncertainn 2 Sigma MDC Units N

Volume Units Date Date Time Units Flag Values H--3

] 2010 ( l.23E+00 6.04E+00 9.58E+00 [DPMITOTAL I 1 00./

-o91-20/131 5-I 3rM I u Sample ID:

18 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number.

L56078-18 RaincieActivity Uncertainty FD nis Runi Aliquot fAliquot Reference Count Count JCount 1 lgVle Radionuclide SOP1#

Conc 2 Sigma MDC Units Volume Units Date Date Time Units Flag Values H-3 1 2010

-9.43E-01 T_5.57E+00 I 9.48E+00 IDPM/rOTAL 1

100

[

1

[

09/20/131 5

, M j UT IW) lI Sample ID:

19 Collect Start: 09/16/2013 13:00 Matrix:

Swipes.

(SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-19 ISp Activity Uncertainty

[ Run Aliquot Aliquot Reference 1 Count Count CountT Radionuclide SOP#

Cone 2 Sigma MDC Units Volume Units Date Date Time Units Flag Values H-3 L32010.!

1.88E-01 5.761E+00 9.43E+00 DPMTOTAL 100

[

% [

09/20/13 5

M I UI Sample ID: 20 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-20 I

Activity Uncertainty J

Runi Aliquot Aliquot Reference Count Count Count Radionucide SOP#

Cone 2 Sigma DC Units u I Volume Units Date Date Time Units Flag Values 11-3

] 2010 [ 2.26E-+00 1 6.28E+00 F 9.68E+00 DPM/TOTAL

]

I100

[ * [

109/20/131 5

M U

Flag Values U

=

Compound/Analyte not detected (< MDC) or less than 3 sigma No

= Peak not identified in gamma spectrum

+

=

Activity concentration exceeds MDC and 3 sigma; peak identified(gamma only)

Yes

= Peak identified in gamma spectrum U*

=

Compound/Analyte not detected. Peak not identified, but forced activity concentration exceeds MDC and 3 sigma High

=

Activity concentration exceeds customer reporting value

  • *** Unless otherwise noted, the analytical results reported Spec

=

MDC exceeds customer technical specification are related only to the samples tested in the condition they L

=

Low recovery are received by the laboratory.

H

=

High recovery BH =x Hin reov rt e vMDC

- Minimum Detectable Concentration Bolded text indicates reportable value.

Page 7 of 9 ADM-000-5 / Page 16 of 24

RepoOf Analysis T ELEDYNE

  • 09/23/13 13:47 r

BROWN ENGINEERING, INC.

0 3A Teledye Technotogies Company L56078 Enercon Frank Brown EN005-3EUOFB-10 Sample ID: 21 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-21 1 Activity Uncertainty Unis Ru Aliquot Aliquot Reference Count Count Count Radionuclide SOP#

Cone M2CSUgias uCn Volume I Units Date Date Time Units H-3

[ 2010

-2.78E+00 5.27E+00 [ 9.58E+00 0DPMTOTAL0

[

1 09/20/13

%5j M

[U Sample ID: 22 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-22 I-SOH Activity ~Uncertainty DC Uis IRun Aliquot IAliquot T Reference [Counti Count] Count Radionuclide SOPI Cone 2 Sigma MDC Units Volume Units Date Date Time Units Flag Values H-3 2010 !

3.79E+C00 6.44E+00 9.51E+00 ]DPM/TOTAL [

100 I

1 09/20/131 5

1 M I UI!

I i

Sample ID: 23 Collect Start 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09t18/2013

% Moisture:

LIMS Nuinber-L56078-23 S

Activity Uncertainty 1 1I Run Aliquot Aliquot Reference Count

.Count Count Radionuclide SOP#

Cone 2 Sigma MDC Units Volume Units Date Date Time Units Flag Values H-3 2010 ] 3.06E+00 6.23E+00 i9.37E+00 ]DPMrJTAL

[

100 0/13J 5

1 M lI U

II Sample ID:

24 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-24 I SOP#

Activity Uncertainty 1U1 Run Aliquot Aliquotf ReferenceI Count Count1Count Radionuclide SOP#

Cone 2 Sigma MDC Units Volume Units Date Date I Time Units Flag Values H-3 2010 72-12E+0°0 5.55+0 93E 0 DPM OTL I

10

[

% I 09 0131 5

IM lU, I

l Flag Values U

Compound/Analyte not detected (< MDC) or less than 3 sigma No = Peak not identified in gamma spectrum

+

=

Activity concentration exceeds MDC and 3 sigma; peak identified(gamma only)

Yes = Peak identified in gamma spectrum U*

=

Compound/Analyte not detected. Peak not identified, but forced activity concentration exceeds MDC and 3 sigma High

=

Activity concentration exceeds customer reporting value

        • Unless otherwise noted, the analytical results reported Spec

=

MDC exceeds customer technical specification are related only to the samples tested in the condition they L

Low recovery are received by the laboratory.

H

=

High recovery Boe =t Hini reov rt e v

.MC

- Minimum Detectable Concentration Bolded text indicates reportable value.

Page 8 of 9 ADM-000-5 / Page 17 of 24

Repoof Analysis apr TELEDYNE E

09/23/13 13:47 BROWN ENGINEERING, INC.

A Teledyne Technologles Company L56078 Enercon Frank Brown EN005-3EUOFB-10 Sample ID: 25 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number.

L56078-25 0P Activity Uncertainty C

I-nt Runj Aliquot Aliquot [ Reference Count 1Count 1Count Radionuclide S

Conc 2 Sigma MDC Units Volume Units Date Date Time I Units Flag Values H-3 2010 Z

-7.00E-01 5.85E+00 9.%5E-+00 [DPMJTOTAL

[

I00

[

_[09/20/131 5

1 M

I Uh I

Sample ID: 26 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number:

L56078-26 1

I Activity 1 U

n Run 1 Aliquot Aliquot Reference ou t

C ount Radionuclide SOP#

Cone 2 Sigma MDC Units Volume Units Date Date Time Units Flag Values H-3 12010 ý 4.10E-01]

5.91E+00 9.61E+070 [DPMroTL [

100

[

09/20/131 5

M u

Sample ID: 27 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/18/2013

% Moisture:

LIMS Number-L56078-27 Sop#

Activity Uncertainty S

Run Aliquotvu Aliquot Reference Count Count Count Radionuclide Conc 2 Sigm MDC Units n

Volume Units Date Date Time Units Flag Values H-3 J_2010 [ 5.43E-01 I

5.90E+00 9.SSE'+'00 JDPMJTOTAL j 100

[

1 09/20/13J 5

[

M I UI I

I I

Sample ID:

28 Collect Start: 09/16/2013 13:00 Matrix:

Swipes (SW)

Station:

Collect Stop:

Volume:

==

Description:==

Receive Date: 09/1812013

% Moisture:

LIMS Number:

L56078-28 I N Activity Uncertainty 2

I

[ Runi Aliquot Aliquot Reference Count Count Count Radionuclide SOP#

Cone 2MDC Units Volume Units Date Date Time Units Flag Values H-3 2010 1.03E+00 5.98E+00 ( 9-54E+00I DPMJTOTAL 1

100

[

1 09/20/131 5 [ M I UI I

1 Flag Valucs U

=

Compound/Analyte not detected (< MDC) or less than 3 sigma No

= Peak not identified in gamma spectrum

+

=

Activity concentration exceeds MDC and 3 sigma; peak identified(gamma only)

Yes = Peak identified in gamma spectrum U*

=

Compound/Analyte not detected. Peak not identified, but forced activity concentration exceeds MDC and 3 sigma High

=

Activity concentration exceeds customer reporting value

        • Unless otherwise noted, the analytical results reported Spec

=

MDC exceeds customer technical specification are related only to the samples tested in the condition they L

=

Low recovery arc received by the laboratory.

H

=

High recovery Bod

=t Hini reov rt e aMDC

- Minimum Detectable Concentration Bolded teit indicates reportable value.

Page 9 of 9 ADM-000-5 / Page 18 of 24

0 QC Summary Report for EN005-3EUOFB-10 09/23/2013 13:47 W'q'TELEDY 3

-I&

-BROWVNIENGINEERING A Teledyne Technoto.Ves Company L56078 H-3 Method Blank Summary TBE Sample ]D Radionuclide Matrix Count Date/Time Blank Result Units Ounalifier P/F WG16294-1 H-3 WO 09/20/2013 14:45

<4.250E+00 pCi/Total U

P WG16299-1 H-3 WO 09/2012013 19:36

<4.240E+00 pCi/Total U

P LCS Sample Summary TBE Sample ID Radionuclide Matrix Count Date/Time Spike Value LCS Result Units Spike Recovery Ranae Oualifier P/F WG16294-2 H-3 WO 09/20/2013 14:54 5.05E+02 5.050E+02 pCi/Total 100.0 70-130

+

P Spike ID:

3H-041706-1 Spike Conc:

5.05E+02 Spike Vol:

1.001E+00 WG16299-2 H-3 WO 09/20/2013 19:45 5.05E+02 4.830E+02 pCi/Total 95.7 70-130

+

P Spike ID:

3H-041706-1 Spike Conc:

5.05E+02 Spike Vol:

1.0013+00

+

U P

F NE Positive Result Compound/analytc was analyzed, peak not identified and/or not detected above MDC

< 5 times the MDC are not evaluated Nuclide not detected Spikdng level < 5 times activity Pass Fail Not evaluated Page I ADM-000-5 / Page 19 of 24

0 QC Summary Report for EN005-3EUOFB-10 09/23/2013 13:47

¶qTELE-D-YME B.ROW-VN: EGINE 'EfING A Weledyne Theiifoqtoel Company L56078 H-3 LCSD Sample Summary TBE Sample ID Radionuclide Matrix Count Date/Time Spike Value LCSD Result LCSD Recovery Units RPD Oualifier P/F WG16294-3 H-3 WO 09/20/2013 15:03 5.05E+02 4.940E+02 97.9 pCi/Total 2.1

+

P WG16294-2 Spike ID:

3H-041706-1 Spike Conc:

5.05E+02 Spike Vol:

1.OOE+00 WG16299-3 H-3 WO 09/20/2013 19:55 5.05E+02 4.950E+02 98.1 pCi/Total 2.5

+

P WG16299-2 Spike ID:

3H-041706-1 Spike Conc:

5.05E+02 Spike Vol:

L.OOE+00

+

U P

F NE Positive Result Compound/analyte was analyzed, peak not identified and/or not detected above MDC

< 5 times the MDC are not evaluated Nuclide not detected Spiking level < 5 times activity Pass Fail Not evaIuated Page 2 ADM-000-5 / Page 20 of 24

0 QC Summary Report for EN005-3EUOFB-10 09/23/2013 13:47 "PrILTELEDY.M BROWN ENGINEERING-A Teledyne Techno:Safes Company L56078 H-3 H-3 Associated Samples for Sample #

Client ID L56078-1 I

L56078-2 2

L56078-3 3

L56078-4 4

L56078-5 5

L56078-6 6

L56078-7 7

L56078-8 8

L56078-9 9

L56078-10 10 L56078-11 11 L56078-12 12 L56078-13 13 L56078-14 14 L56078-15 15 L56078-16 16 L56078-17 17 L56078-18 18 L56078-19 19 L56078-20 20 WG16294 U

P F

NE Positive Result Compound/analyte was analyzed, peak not identified and/or not detected above MDC

< 5 times the MDC are not evaluated Nuclide not detected Spiking level < 5 times activity Pass Fail Not evaluated Page 3 ADM-000-5 / Page 21 of 24

QC Summary Report for L56078 EN005-3EUOFB-10 09/23/2013 13:47 AWTELE OY10 BROWN-IENGINEERING.

A Teledylne Technologies Company' H-3 H-3 Associated Samples for Sample

.Client ID L56078-21 21 L56078-22 22 L56078-23 23 L56078-24 24 L56078-25 25 L56078-26 26 L56078-27 27 L56078-28 28 WG16299 U

P F

NE Positive Result Compound/analyte was analyzed, peak not identified and/or not detected above MDC

< 5 times the WDC are not evaluated Nuclide not detected Spiking level < 5 times activity Pass Fail Not evaluated Page 4 ADM-000-5 / Page 22 of 24

LS 7 Page I

of IN4OLaboratory foration Project #: SUNYUIB027 Name:

Teledyne Brown Eng COC Number"n: SUNYUB027-09162013 Street:

2508 Quality Lane City/StateiZip:

Knoxville, TN 37931-3133 Excellence-Every project Every day Phone:

865-934-0379 ENERCON P.O.C:

Frank Brown Phone: 814-599-0677 e-mail:

fbrown(aenercon.com Sample Analysis Requested (s) (Fill in the number of containers for each test)

Project/Site Name:

SUNY BMRC c-Preservative tyrpe (3)

Address:

Buffalo, NY "o

oComments Collected by (print/sign):

T J Keane Note: extra sample is

....e Cld-oI E E required for sample Sample ID (Mni)

QCC1 specific QC For composites - indicate start and stop dare/time I

is-TAT Requested: Normal:

Rush:

ASAP Specif:

FVResults

Yes I

No CircleDeliverable: CofA / QCSummo*y Lcvel I / Level2 / Lcvel3 I Level4 Remarks: Are there any known hazards applicable to these samples? If so, list the hazards.

1Samrpler Collection Time Zone Eastern Pacific Central Other Chain of Custody Signatures Sample Shipping and Delivery Details Relinquie B (S Dale rn ed by(sigoed)

Date Time Laboratory PM: Rebecca Charles 1 ~/p g 0 36 4

' 11 15 lb Method rfMipmaent Fed-X Date Shipped: 09/17/201.3 12 2

Airbill :

3 Airbil#:

1.) hain of Csody Nmber See Procedure V

For Lob P.cetving Use Only 2.) QC Codes: N - Nornal Sarnple, TO - Trip Black. FD - Field Duplirase. ED - Equiporsll Blank MS - Matrix Spike Sainple. MSD Matrbo Spike Duplicate Sample G - Grab. C - Compostite 3.) Preserative Type: 5IA - Hydnrocloric Acid. 1'l = Miirk Add. SH - Sodium Hydraide. SA - Sutfinig Acid. AA = Ascebic Acid. HX = flexat ST - Sodiuam Thioswulfatc Ifso presetive is added l teave fied blank Custody Sal Intact?

4.) Mais Coder: DW-DrMikie Woare. GW-ýGUmdwresr. SW*Stuface WoeL WW-WWU Water. W-Water. NSL.6-Mi Liquid. SO-Sot. SD-Sadi.-est SL-S[udar SS-Solid Wte, -O=Oil. FF-.lr. P-lioes. U=-Uine. FrFeal YS NO N..N*.l I

EOOltr Temp:

5.) SampleAaalysis Rqotpsed. Analytical ciedtod requested (i.e. 8260B.

6OBRf470A) ind umober of contaierns provided for each (ie. 81260B -3. 6010B17471A

- 1).

W[ý7,9-ý ADM-000-5 / Page 23 of 24

09/18/13 14:04 Teledyne Brown Engineering Sample Receipt Verification/Variance Report SR #:

SR36574 Client:

Enercon Services, Inc.

Project #:

EN005-3EUOFB-10 LIMS #L56078 tiated By: JSIMMONS Init Date: 09/18/13 Receive Date:

09/18/13 Notification of Variance Person Notified:

Contacted By:

Notify Date:

Notify Method:

Notify Comment:

Client Response Person Responding:

Response Date:

Response Method:

Response Comment Criteria Yes No NA Comment 1

Shipping container custody seals present NA and intact.

2 Sample container custody seals present NA and intact.

3 Sample containers received in good Y

condition 4

Chain of custody. received with samples Y

5 All samples listed on chain of custody Y

received 6

Sample container labels present and Y

legible.

7 Information on container labels Y

correspond with chain of custody 8

Sample(s) properly preserved and in NA appropriate container(s) 9 Other (Describe)

NA For Hazardous Materials Only:

10 Paperwork shows TBE and shippers name, NA address and phone number 11 Paperwork shows sample quantity NA information ADM-000-5 / Page 24 of 24

Enercon Services Inc.

Survey Package Building: Administration I Survey Unit #: ADM-001-1 I Page 1 of 5 Classification:

E3 Class 1 - Impacted 13 Class 2-Impacted Z

Class 3 - Impacted Survey Type:

E3 Characterization Z Demolition El Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/1OOcm 2)

Investigation 3,750 (dpm/I00cm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys F1 Floors EL 10% [U 50% E] 100% Z N/A r_] Lowerwalls EL 10% [150% [] 100% ZN/A Upper walls Z 10% 1350% [1 100% IZN/A Ceilings Z 10% L] 50% E] 100% [:] N/A E3 Structures (Permanent Furnishings) Interior and Exterior Surfaces E3 10% 13 50% [:1100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

ZL-2360/43-93 Beta/Gamma I Minute I probee

_____________________width/sec Tc9N/61 ZASC 950 Alpha/Beta iMinute N/A Th-230 Tc-99 Alpha - 25 ZASCBeta

- 150 E3 Z

A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL, values have been selected based on the most limiting nuclides of concern for the survey unit.

ADM-001-1 / Page 1 of 8

Enercon Services Inc.

Survey Package General Survey Instructions: ADM-001-1 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5. Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.
6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8. Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.
9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 ADM-001-i / Page 2 of 8

Enercon Services Inc.

Survey Package Location Code Description ADM-001-1 I Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as Fl, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "I" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (1 character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By:

Reviewed By:

Date:

Frank Brown Date:

A 1 1 3*

Package Complete:

Printed Name/Signature ADM-001-1 I Page 3 of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-001-1

-TPage 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

Survey Technician(s):

D Border C Croft Floor Survey - Completed in accordance with the survey package 0 N/A El Beta Scan Date Completed Initials Step #1 El Alpha Scan Date Completed Initials 0l Beta Static Date Completed Initials E] Alpha Static Date Completed Initials El Smears Date Completed Initials Lower Wall Survey - Completed in accordance with the survey package ED N/A El Beta Scan Date Completed Initials Step #2 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials Upper Wall Survey - Completed in accordance with the survey package El N/A Step #3 0 Beta Scan Date Completed 10/02/2013 Initials DB El Alpha Scan Date Completed N/A Initials N/A 0 Beta Static Date Completed 10/02/2013 Initials DB E] Alpha Static Date Completed N/A Initials N/A Z Smears Date Completed 10/02/2013 Initials DB ADM-001-1 / Page 4 of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-001-1 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package El N/A

[ Beta Scan Date Completed 10/2/2013 Initials DB Step #4 El Alpha Scan Date Completed N/A Initials N/A

[ Beta Static Date Completed 10/2/2013 Initials DB E] Alpha Static Date Completed N/A Initials N/A

[ Smears Date Completed 10/2/2013 Initials DB RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

EN/A U Beta Scan Date Completed Initials Step #5 U Alpha Scan Date Completed Initials El Beta Static Date Completed Initials U Alpha Static Date Completed Initials EU Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6

[ N/A Ul Smears Date Completed Initials ADM-001-1 / Page 5 of 8

RADIOLO*URVEY REPORT 0

Ploris o ur,* D ton Sure" Pacw AD39o00-1 Upper Survey Loa Number:

0211012013-OOS Ted b D~

'T Border ICA Crott C cr4

,r Ri)Zr B3 T~-

J___

Kan_

A

~

C &

T Bal~roand Beta Serial Cdllhraflon Count Tt Alpha Backgsre.d Beta UDA Instruamct Number D.e Probe Probo. Ae Uect (r)

Alpha Backzwtod feptal illefency Abble MDA Idpral Jej Beta Ef-l,,ncy (dpmA Date!

1012/2013 950 1205344 31112014 NIA HIA 1

1.0 32,1%

24 60.0 25.7%

152

lime, 1400

.Ludl am 2 360 267528 611012014 43-93 125 1

1 4.0%

154 as 2.2%

1650 Be-Area 100 Dose rat me, rat. waterac N/A Flocoscan note.

1WP N/A

_IT oolhscao canEO 40-140 CPU S

.i%

10 M

o.ba.l ha Removal"l Beta Sta otal Alpha _tteTot/tal set.

Description DP?

I DL/

DF3 I DPiW am/

DMIM Gruac DPE I DU1E Alpha S-Beta Seen o._CP_

100_ra__ _ _ _

100__a_

CpM 100_ma_

__ _ _1__

CPM 100c6_21n xOOcato CPM 100craam" 9t 1Oam' Ra.

in CPU Rang. In CP N Bas Rate AD-.0011-W-M-001 0

<MDA

-3 42

<MDA

-70 N/A N/A N/A 119

'MDA 1528 N/A 40 m 120 N/A AD1.1.0011-C-.-002 0

'MDA

-3 45

,MDA

-58 "JA N/A NIA 126 1843 1843 N/A 60.130 N/A ADM-0011.W-M-002 0

-MDA

-3 48

'MDA

-47 N/A N/A N/A 106

-MDA

,944 N/A 80- 140 N/A ADM.0011-"-U-004 0

'MDA

-3 70

<MDA 39 N/A N/A N/A 74

'MBA

-494 N/A N/A N/A ADN-O0loW-U-O05 0

<MDA

-3 52 PMDA

-31 N/A N/A N/A 91

'MDA 270 N/A 40- 100 N/A ADM-I0011-C-M-006 0

<MDA

-3 65

'MDA 19 N/A N/A NIA 78

'MDA

-315 N/A N/A N/A A.DM0-011-C-U-O07 0

'MDA

-3 56

<MDA

-t6 N/A N/A N/A 60 MBDA

-1124 N/A NIA N/A ADM-0011-W-M-00M 0

'MDA

-3 51

'MBA

-35 N"A NIA N/A 107

'MDA 989 N/A S0- 120 N/A ADM-0011-W-.-009 0

<MDA

-3 53

ýMDA

-27 N/A N/A N/A 99

'MDA 629 N/A 40- 120 N/A ADM-0011-C-M-010 0

'MDA

-3 56

'MBA

-16 N/A NIA N/A 82

'MDA

-135 N/A N/A N/A ADM-O1OS-W--.011 0

'MDA

-3 59

'MDA

-4 N/A N/A N/A 91 6MDA 270 N/A 40- 100 N/A ADM.0011.W-.M-012 0

hMDA

-3 62

<MDA 8

NIA N/A N A 93

'MDA 360 N/A 40- 100 NIA Annpo-t__-r-M-O13 0

<MDA

-3 59

'MDA

-4 N/A N/A N/A 70

'MBA

-674 N/A N/A N/A ADM.001 _-C-_-OI4 0

<MDA

-3 63 12 N/A N/A N/A 101

'MDA 719 N/A N/A N/A com-catt V,-aoArha AD count duration. eve I mnute unloth athe noted.

Footnotes: Ill Value compared to MA 121 Th.e co*ported value 1011 ADM-001-1 / Page 6 of 8

ADM-SUB-Upper (SU 001-1)

Area: Vert 10K Tank Room Label Type Surface Local X Local Y 1

Random Wall 2 8.8 0.2 2

Random Wall 4 18.1 5

Area: Room NO5 ADM-O01-1 Label Type Surface Local X Local Y 3

Random Wall 3 0.7 4.2 Area: Room 5N06 Label Type Surface Local X Local Y 4

Random Ceiling 8.6 1.2 5

Random Wall 4 13.7 3

Area: Room N04 Label Type Surface Local X Local Y 6

'Random Ceiling 7

19.7 7

Random Ceiling 19.9 33.6 8

Random Wall 18 2

1.5 9

Random Wall 19 13 3.5 10 Random Ceiling 10.3 40 11 Random Wall 9 16.7 0.4 12 Random Wall 5 0.1 2.4 13 Random Ceiling 15.1 30.5 14 Random Ceiling 8.6

7.3 Notes

Local X and Local Y measured in feet from bottom left hand corner of wall or bottom left corner of floor as seen on floor plan drawing.

ADM-001-1 / Page 7 of 8

Iý-'

V /

F,

//F A

/

z.

7-a \\

/

10K Tank Room, Rooms N05, SN06, and N04; Upper Surfaces 7

N I-ADM-001-1 I Page 8 of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-001-2 I Page 1 of 5 Classification:

El Class I - Impacted El Class 2-Impacted Z

Class 3 - Impacted Survey Type:

El Characterization Z Demolition El Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/100cm 2)

Investigation 3,750 (dpm/1OOcm 2 M).

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys

[] Floors E] 10% LI 50% EI 100% 0 N/A LI Lower walls El 10% LI 50% E] 100% Z N/A Z

Upper walls Z

1i0%

EI 50% E] 100% [-] N/A Z

Ceilings Z 10% [3 50% [:1 100% LIN/A RI Structures (Permanent Furnishings) Interior and Exterior Surfaces EI 10% EI 50% [] 100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

OL-2360/43-93 Beta/Gamma I Minute I probe Tc-99 N/A 612 width/sec ZASC 950 Alpha/Beta iMinute N/A Th-230 Tc-99 Alpha - 25 Beta - 150 LI Z

A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL, values have been selected based on the most limiting nuclides of concern for the survey unit.

ADM-001-2 / Page 1 of 8

Enercon Services Inc.

Survey Package General Survey Instructions: ADM-001-2 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3. Document all scan survey results on the applicable survey maps and data results sheets.
4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5. Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.
6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8. Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.
9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 ADM-001-2 / Page 2 of 8

Enercon Services Inc.

Survey Package Location Code Description ADM-001-2 I Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following fonnat shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as Fl, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "I" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (I character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number 1. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By:

Reviewed By:

Date:

Date:

Date:/a!6

/

Package Complete:

Frank Brown

-Printed Name/Signature ADM-001-2 / Page 3 of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #M ADM-01-2 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

D Border Survey Technician(s):

C Crott Floor Survey - Completed in accordance with the survey package Z N/A Step #1 El Beta Scan Date Completed El Alpha Scan Date Completed El Beta Static Date Completed El Alpha Static Date Completed El Smears Date Completed Initials Initials Initials Initials Initials Lower Wall Survey - Completed in accordance with the survey package ED N/A Step #2 El Beta Scan Date Completed El Alpha Scan Date Completed El Beta Static Date Completed El Alpha Static Date Completed El Smears Date Completed Initials Initials Initials Initials Initials Upper Wall Survey - Completed in accordance with the survey package n N/A Step #3 Beta Scan Date Completed 10/02/2013 Initials DB El Alpha Scan Date Completed N/A Initials N/A

[ Beta Static Date Completed 10/02/2013 Initials DB El Alpha Static Date Completed N/A Initials N/A

[K Smears Date Completed 10/02/2013 Initials DB ADM-001-2 / Page 4 of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-001-2 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package ElN/A

[ Beta Scan Date Completed 10/2/2013 Initials DB Step #4 LI Alpha Scan Date Completed N/A Initials N/A

[ Beta Static Date Completed 10/2/2013 Initials DB El Alpha Static Date Completed N/A Initials N/A Z Smears Date Completed 10/2/2013 Initials DB RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods)

MN/A El Beta Scan Date Completed Initials Step #5 El Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials Penetrations, Drains, and Openings Survey - Completed in accordance with the survey package Step #6 0 N/A El Smears Date Completed Initials ADM-001-2 / Page 5 of 8

RADIOL4SURVEY REPORT PuPpon of Scrver Devolikon S lsuwyft-m; ADW-001-2 upper SU,-.LOS Numb-,

02/10/2013-006 Suvydb D I DO.",cA CoAfat CA

-0 Sr.

a T

~

V JJ Knot___

Seda Clbrution Count im.e Alpha Baclaound Alpha Saft1= 7 beta EDA Loam~smet Nazaber DIM Prob.

lPbe A (ram w) lrain) lepta]

Kleiancy Alpha INDA ldpm)

Dowm semakll~ner ldp-)

Date:

10/2/2013 ABC 960 1208344 3/1/2014 M/A IA1 1.0 3%.1%

24 60.0 25.7%

152 T1ma 1600 Ludlum 2360 267528 611012014 43-93 126 1

1 4.0%

1"4 88 2.2%

1650 amess Am.

100 DoK 0

rate I

Itr yv Backtround N/A Flnomý mete_

RW7*

NIA plT__ _ _ _ _ _ _ _ _ __ _ __

_ _C Bean 10 IsAlohaemwvbla RJ Dart Btatia/To. l Alpha mticU7otl me Dca-lptlil DIPf lM up I

u'I/

O I

Im/

OM/

OPl arams D1 D1PM/

AMlph. S-D.ta Smn 0.0 CPU 100Gmt' (1&

00co

.CpM 1Oc.'
100cm2o, Gla.

CPU 100=104 100mozm CPU 100Cm"'I 1

100-n2M Ronp In CPU Ru..

to CPU 0 Doe. RIt.

ADE-0022-C.M-001 0

cMDA

-3 59

<MDA

-4 N/A N/A N/A 109

<MDA 1079 N/A N/A N/A AD3-001Z-W.M-002 0

-b1DA

.3 52

'MDA

-31 N/A N A NIA 100 tMDA 674 NIA 60- 100 N/A ADf-00124-C--003 0

.£dDA

-3 Si

<MDA

-35 N/A N/A N/A 93 OMDA 360 N/A N/A N/A ADU-0012-C-M-004 0

<KDA

-3 55 1

MDA

-19 N/A N/A N/A 64 MNDA

.944 N/A N/A N/A ADM-0012-W-M-0O8 0

dMDA

.3 42 0MDA

-70 N/A N/A N/A 88

<MDA 135 N/A 60- 100 N/A Ann-002-*-W-m-00 0

-MDA

-3 55 tMDA

-19 NIA N/A

"/A 89 WMDA 160 NiA 60- 100 N/A ADU.012-W-UM.00" 0

<MDA

.3 64

<MDA 16 N/A N/A N/A 76

'MDA

-404 N/A 40-100 N/A ADM-.OO-C.I-0O 0

-MDA

.3 53

<MDA

.27 NIA N/A N/A 71

<MDA

-629 N/A I/A N/A ADIBK-002-W.U-009 0

<MDA

.3 53

<I4DA

-27 N/A N/A N/A a3 tMrA

-90 NMA 60- 100 N/A AD]-E02.-W.M.010 0

MDA

-3 77

'MDA 66 N/A NIA N/A 90

-bIDA 225 N/A 60- 100 N/IA AVX-0012C-UZ-11 0

NMDA

-3 71

<MDA 43 N/A N/A N/A 69 tMDA 180 N/A N/A N/A ADM4012-C-M.12 0

<MDA

-3 61 0MDA 4

N/A N/A N/A 113 FmDA 1258 N/A N9A N/A AU0N-012-C-.013 0

uMDA

-3 66

<kflDA 23 N/A N/A N/A 99

'NDA 629 N/A N/A N/A ADM-.0012.-C-014 I

<MDA 0

66

<NDA 31 N/A N/A N/A 102 00IA 764 N/A N/A N/A Remarka; All coutt duratihee a.. 1 malente moless othmw.

not4..

.tewkotea; III Cemosvted valu. coutaue4 to WDA M 2spCametd vale.

lOf I ADM-001-2 / Page 6 of 8

ADM-SUB-Upper (SU 001-2)

Area: Room N02 Label Type Surface Local X Local Y 1

Random Ceiling 8.4 0.9 2

Random

.Wall 4 4.9 2.1 3

Random Ceiling 5.1 30.5 4

Random Ceiling 11.8 20.7 5

Random Wall 1 1.9 4.7 Area: Room N03 Label Type Surface Local X Local Y 6

Random Wall 16 0.4 1.5 7

Random Wall 14 13.7 3.5 8

Random Ceiling 19.2 1.8 9

Random Wall 14 16.5 5.7 Area: Room N16 Label Type Surface Loca IX Local Y 10 Random Wall 8 9.5 2.3 11 Random Ceiling 16 4.6 12 Random Ceiling 34 10 13 Random Ceiling 16.3 7.7 14 Random Ceiling 9.7 16.8 Notes:

Local X and Local Y measured in feet from bottom left hand corner of wall or bottom left corner of floor as seen on floor plan drawing.

ADM-001-2 / Page 7 of 8

Room N02, N03, and N16; Upper Surfaces ADM-001-2 / Page 8of 8

Enercon Services Inc.

Survey Package Building: Administration I Survey Unit #: ADM-201 I Page I of 5 Classification:

El Class 1 - Impacted F-1 Class 2-Impacted Z Class 3 - Impacted Survey Type:

Characterization Z Demolition El Final Status Survey Applicable Nuclides of Concern:

Nuclide SEE SPECIAL SURVEY INSTRUCTIONS SECTION Release Limit 5,000 (dpm/1OOcm 2)

Investigation 3,750 (dpm/100cm 2)

Level Applicable Survey Unit Surfaces:

% of Surface Requiring Scan Surveys

[] Floors E] 10% [] 50% LI100% Z N/A LI Lower walls E] 10% E] 50% E] 100% Z N/A Upper walls Z 10% [_150% [1 100%

-IN/A Ceilings M 10% EI 50% [I 100%

] N/A Ej Structures (Permanent Furnishings) Interior and Exterior Surfaces 0I 10% El 50% Ej 100% Z N/A Required Survey Measurement Static Scan Rate Instrument Typical.

Instrumentation Type Count Time Efficiencies Based on:

MDA(dpm)

L-2360/43-93 Beta/Gamma 1 Minute I probe Tc-99 N/A 612 L-2360/-93 Beta/Gam Minute width/sec Alpha -25 ZASC 950 Alpha/Beta 1 Minute N/A Th-230 Tc-99 Beta-150 EL-2221/43-37 Beta/Gamma N/A I probec I width/sec I

c9 N/I7 Z

A Planchet Counter shall be used for analysis of any required removable contamination measurements. See General Survey Instructions Item #7.

Since this instrumentation is non-nuclide specific (gross measurements), the applicable efficiency and DCGL, values have been selected based on the most limiting nuclides of concern for the survey unit.

ADM-201 / Page 1 of 8

Enercon Services Inc.

Survey Package General Survey Instructions: ADM-201 I Page 2 of 5

1. Perform scan surveys of the required surface area at the prescribed scan rates. If less than a 100% scan is required, use professional judgment to select the areas scan surveyed. Select areas with the highest probability to contain residual activity (i.e., areas of known radionuclide usage, floor traffic pathways, cracks and/or crevices not easily cleaned, countertop workspaces, storage locations, stained or water spotted areas, or areas with a known history of contamination).
2.

If elevated activity is detected during the scan surveys, then establish the extent (size) of the contaminated area(s) and mark the affected area(s) and quantify the activity by taking static measurements of the affected area(s). Notify the Project Manager or designee of the type, amount, and extent of any contamination.

3.

Document all scan survey results on the applicable survey maps and data results sheets.

4.

The established number of static measurement locations needed for the statistical evaluation of this survey unit is 14. However, due to statistical and geometrical considerations, the actual number of locations may vary. In this case, collect the actual locations provided on the survey map whether this number is greater than or less than 14

5.

Locate and mark the required static measurements locations using the survey map(s). Survey maps with sufficient detail to measure and locate all of these locations have been provided.

6.

Collect all required static measurements and document the results on the associated data results sheets.

Additional static measurements may be taken in suspect areas at the discretion of the Project Manager or survey technician. However, these additional locations are not included in the analysis of the statistical sample set.

7.

Removable contamination measurements (swipes) shall be performed at the established measurement locations and counted on a planchet counter accounting for alpha/beta contamination.

8.

Notify the Project Manager or designee if elevated activity is detected by any of the static measurements or applicable removable contamination measurements.

9.

Ensure that all package information is completed and signed prior to turning in this Survey Package to the RSO or designee for review.

Special Survey Instructions:

NUCLIDES: Co-60; Cs-137; Ag-108; Eu-152; Eu-154; Ni-63 ADM-201 / Page 2 of 8

Enercon Services Inc.

Survey Package Location Code Description ADM-201 I Page 3 of 5 A unique location code shall be assigned to each individual survey location to ensure proper data management of the survey results. The following format shall be used to ensure consistency throughout the final status survey process:

BBB-RRRR-SS-M-LLL Where:

BBB

= Building or area code. This field represents the facility area. This will be the building number of an assigned area number. (3 characters)

RRRR

= Survey unit ID code. This field represents the survey unit i.e. 2-01, 2-02 etc. (up to 4 characters).

Building system survey units (i.e. ventilation systems, drain systems, or vacuum systems) are assigned unique 4-digit numbers that are consistent with the building section and floor. (up to 4 characters)

SS

= Structural surface code. This field represents the structural surface such as floor, wall, ceiling, etc. and the surface division code. For example, if a room has a very large floor area, it may be divided into two or more divisions and each section would be assigned unique codes such as FI, F2, and so on. Walls may be divided on a frequent basis. If only one surface area is identified for a particular survey area, then the default number will be "I" (e.g., WI, Fl, etc.). (2 characters)

M

= Structural material code. This field represents the type of structural material on which a particular measurement is taken. This field is usually used to track and assign specific material natural background levels. If not material background value is to be assigned, the default character shall be "M." (I character)

LLL

= Numerical identification number. This field represents the survey point assigned numerical identifier.

The field "001" means survey point location number I. Numerical identifiers shall not be duplicated within the same survey unit. (3 characters)

Prepared By:

Reviewed By:

Package Complete:

Date:

I Name/Signature Frank Brown Date:

Printed Name/Signature ADM-201 I Page 3 of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-201 Page 4 of 5 Before Beginning Surveys Examine the area to ensure no hazards are present. Verify that all radiological instrumentation intended for use is source checked, in calibration, and operating properly.

Identify any area within a given survey unit where contamination has been measured, even if less than the release guidelines.

Survey Technician(s):

K Myers

.R Shank Floor Survey - Completed in accordance with the survey package Step #1 0 N/A El Beta Scan Date Completed F1 Alpha Scan Date Completed El Beta Static Date Completed El Alpha Static Date Completed El Smears Date Completed Initials Initials Initials Initials Initials i

Lower Wall Survey - Completed in accordance with the survey package

[E N/A Step #2 0l Beta Scan Date Completed Initials E] Alpha Scan Date Completed Initials El Beta Static Date Completed Initials El Alpha Static Date Completed Initials El Smears Date Completed Initials Upper Wall Survey - Completed in accordance with the survey package El N/A Step #3 Beta Scan Date Completed 10/1/13 Initials KM El Alpha Scan Date Completed N/A Initials N/A

[

Beta Static Date Completed 10/1/13 Initials KM El Alpha Static Date Completed N/A Initials N/A SmIr 0I I

13K I ED Smears Date Completed 10/1/13 Initials KM ADM-201 / Page 4 of 8

Enercon Services Inc.

Survey Package Building: Administration Survey Unit #: ADM-201 Page 5 of 5 Ceiling Survey - Completed in accordance with the survey package UN/A

[ Beta Scan Date Completed 10/1/13 Initials KM Step #4 U Alpha Scan Date Completed N/A Initials N/A

[ Beta Static Date Completed 10/1/13 Initials KM U Alpha Static Date Completed N/A Initials N/A

[ Smears Date Completed 10/1/13 Initials KM RAM Use and Storage Areas - Completed in accordance with the survey package (benches, countertops, sinks, and hoods) 0 N/A Step #5 U] Beta Scan Date Completed Initials U Alpha Scan Date Completed Initials U Beta Static Date Completed Initials U Alpha Static Date Completed Initials U Smears Date Completed Initials rene~uaionus, liras,adp ngu JpIIgS urvey -Co.~mpleteu mnaccordarice witnthe survey N/A ADM-201 / Page 5 of 8

RADIOIAKURVEY REPORT

-ameeo -aphmerp Sasyw lat.1MA 120 owner Igeurwortoeggiumben 01/1012013-008 T1yddb Y=IR bb(IMkdf K.

(6.

rV 1~U WUUAMW

DOW, IPu Push Arm. feum!

.dpm blo t

A...

L.

et 0...,l36.

0 2013 SUdd Cdbbab Id,,

Abi NV

-da sof Bb AOC O60 1206844 3/1/9014

  • /A

~

VI I

1.0 32.1%

24 60a0 25.7%

182 1Tbme 1145 LUM 26 267528 61101 04 43-63 1256 2

4.0%

193n go 8.6%

1071 smArSSN 100 views Nai

-s 90 121312013 4.+/-t4L N6I12A NIA rj.0%

an8 UU./A EUE!I

.&E27 A101140-W.34102 I___

Ji5 7

ýIA

-1 MIw~k J_

8 1m

-6 I0-120 N/A AVUE-01-W49M0 MA 3

6 5402 o

bm__

_9_

N/_

so-120 N/

ADU-201-W-3404 115A 3

o 2

MA,

  • A 11 4MDA 615 NIA 80- 120 NIIA ADMI-M0-C4U046

____3_9_

MD 103

'MA 280 MI 80-120 M/A ADOU-01W.4E4M 01 KI 3

4 1M

-4 i

1 l

DA 699 N/

80-120 MIA

  • E-1201-CMA Kc 3

6

-4012 Rk NA 7

6 16__

NIA__

W0.120 N/A AM401.C.U480

-3 5____3_1_fA I

MD 0

8-2 I

AU.i1WE.1 126 0MIA 923 NIA 90-ISO M/A ASM4101.C4-U012 0_m_3___A.7___

?,

M&

9

-WA 1

80-1320 MI AMU-201-C.4134 0_____

bu___3____2__ý IA 77

.cm 48 80- 120 NP sAwwr All even Awtmm awe I mim msm ~admna otewseem&6 rssyss6M 1 tu s

va4.. Ammomwe to 9" 0 Compss". usia.

1011 ADM-201 / Page 6 of 8

ADM-CTL-Upper Surfaces Area: Room 215 Label Type Surface Local X Local Y 1

Random Wall 1 24.1 0.3 2

Random Wall 3 6.6 2.1 Area: Room 213 Label Type Surface Local X Local Y 3

Random Wall 4 0.5 2.3 4

Random Wall 3 12.4 4.1 Area: Hallway Label Type Surface Local X Local Y 5

Random Ceiling 22.6 4.8 6

Random Wall 8 60.3 2.9 7

Random Ceiling 38.5 0.6 Area: Room 209 Label Type Surface Local X Local Y 8

Random Ceiling 5.2 9.3 Area: Room 216 Label I

Type Surface I

Local X I

Local Y 9

Random Wall 3 2.8 0.8 Area: Room 214 Label Type I

Surface I

LocalX x Local Y 10 Random Ceiling 7.1 8.4 Area: Room 212 Label I

Type I

Surface Local X Localy 11 Random Wall 7 13.7 1.6 Area: Room 208A Label I

Type Surface Local X Local Y 12 Random Ceiling 10.1 11.4 Area: Room 221 Label I

Type I

Surface I

Local X I

Local Y--

13 Random Ceiling 33.9 11.7

%rea: Room 115A Upper Label I

Type I

Surface Local X Local YV 14 Random Wall 5 2.6

0.5 Notes

Local X and Local Y measured in feet from bottom left hand corner of wall or bottom left corner of floor as seen on floor plan drawing.

ADM-201 / Page 7 of 8

Admin Building, Second Floor, Upper Surfaces ADM-201 / Page 8 of 8