ML13331A783

From kanterella
Jump to navigation Jump to search

Forwards Amend Application 126 to License DPR-13,revising Tech Specs Re Emergency Diesel Generator Testing.Fee Paid
ML13331A783
Person / Time
Site: San Onofre 
Issue date: 02/14/1985
From: Baskin K
Southern California Edison Co
To: Harold Denton
Office of Nuclear Reactor Regulation
Shared Package
ML13331A784 List:
References
TAC-55900, TAC-60370 NUDOCS 8502190277
Download: ML13331A783 (3)


Text

REGULATURY 9 FORMATION 0sTRI8UTION SYA M (RIDS)

ACCESSION NBR:8502190277 DC,DATE; 85/02/14 NOTARIZEO YES DOCKET #

FACIL:50-206 San Onotre Nuclear Station, Unit 1, Southern Calitorn 05000206 AUTHNAME AUTHOR AFFILIATION

BASKINK, Southern California Edison Co, RECIP.NAME RECIPIENT AFFILIATION DENTONH,R.

Office of Nuclear Reactor Regulation, Director

SUBJECT:

Forwards Amend Application 126 to License DPR-13,revising Tech Specs re emergency diesel generator testingFee paid.

DISTRIBUTION CODE: AOOID COPIES RECEIVED:LTR -! ENCLi.SIZE:_E

".t.2:

TITLE: OR Submittal: General Distribution NOTES:J Henchett Icy POR Documents, NRR/DL/SEP icy.

05000206 OL:03/27/67 RECIPIENT COPIES RECIPIENT COPIES 10 CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL NRR ORBS BC 01 7

7 INTERNAL: ACRS 09 b

6 ADM/LFMB 0

ELD/HDS2 1

0 NRR/DE/MTE5 1

I NRR/DL DIR I

I NRR/DL/ORAB 1

0 NRR/DL/TSRG I

I (r

ETB NRR/DSI/RAB F;LE 04 RGNS EXTERNAL: LPOR 03 1

1 NRC PDR 02 1

1 NSIC 05 1

1 NOTES:

e 2

TOTAL NUMBER OF COPIES REUUIRED; LTTR 28 ENCL 25

Southern California Edison Company P 0. BOX 800 2244 WALNUT GROVE AVENUE KENNETH P. BASKIN ROSEMEAD, CALIFORNIA 91770 TELEPHONE VICE PRESIDENT 818-302-1401 February 14, 1985 Office of Nuclear Reactor Regulation Attention:

Mr. H. R. Denton, Director U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Gentlemen:

Subject:

Docket No. 50-206 Amendment Application No. 126 San Onofre Nuclear Generating Station Unit 1

References:

A) Letter D. M. Crutchfield (NRC) to K. P. Baskin (SCE),

November 19, 1984, TDI Diesel Engine Reliability and Operability B) Letter M. 0. Medford (SCE) to 3. A. Zwolinski (NRC),

December 19, 1984, TDI Diesel Engine Reliability and Operability By Reference A, the NRC requested that Southern California Edison (SCE) propose Technical Specification changes to the San Onofre Unit 1 Provisional Operating License. These proposed changes would, on an interim basis, limit emergency diesel engine loading to 4500 kw + 5% for engine testing and emergency service requirements. Additionally, the proposed changes would eliminate fast engine starts from the monthly surveillance testing, but retain the refueling interval fast start test which simulates design basis emergency power requirements.

By Reference B, SCE informed you that proposed Technical Specification changes as requested by Reference A will be submitted to the NRC by approximately February 1, 1985, but will not include any loading limits pertaining to emergency service, which will be handled by the San Onofre Unit 1 Emergency Operating Instructions.

Enclosed are three executed and forty conformed copies of Amendment Application No. 126 to Provisional Operating License No. DPR-13. Amendment Application No. 126 consists of Proposed Change No. 147, which is a change to the Appendix A Technical Specifications incorporated into Provisional Operating License No. DPR-13. Proposed Change No. 147 is intended to fulfill the commitment made in Reference B and also includes two additional changes deemed appropriate by the Licensee.

27850214 I,

~lp PPDRAtIIDCI4 PDOOR~

Mr. H.

February 14, 1985 Pursuant to 10 CFR 170.12, SCE's Check No. T034092 in the amount of

$150 is enclosed to cover the fee for Amendment Application No. 126.

If you have any questions, please contact me.

Very truly yours, Enclosures cc: W. A. Paulson, NRC/NRR, San Onofre Unit 1 Project Manager F. R. Huey (NRC Senior Resident Inspector, Units 1, 2 and 3)

3. B. Martin, NRC Region V, Regional Administrator J. 0. Ward, California Department of Health Services