Forwards Rev 5 to Updated Fire Hazards Analysis,San Onofre Nuclear Generating Station Units 1,2 & 3. Unit 1 Specific Info Revised to Reflect Changes to Facility & Approved Exemption from Branch Technical Position Apcsb 9.5-1,App a
ML13330B474
Person / Time
Site: San Onofre  
Issue date: 02/15/1989
From: Baskin K
Southern California Edison Co
To:
NRC/IRM
Shared Package
ML13330B475 List:
References
TAC-71043, TAC-71044 NUDOCS 8902160310
Download: ML13330B474 (15)


Text

Southern California Edison Company P.O. BOX 800 2244 WALNUT GROVE AVENUE ROSEMEAD, CALIFORNIA 91770 KENNETH P. BASKIN TELEPHONE VICE PRESIDENT 818-302-1401 February 15, 1989 U. S. Nuclear Regulatory Commission Attention:

Document Control Desk Washington, D.C.

20555 Gentlemen:

Subject:

Docket Nos. 50-206, 50-361 and 50-362 Updated Fire Hazards Analysis San Onofre Nuclear Generating Station Units 1, 2 and 3 (TAC Nos. 71043 and 71044)

In accordance with 10 CFR 50.71, Southern California Edison Company (SCE) is transmitting Revision 5 of the Updated Fire Hazards Analysis (UFHA) for the San Onofre Nuclear Generating Station, Units 1, 2 and 3. This annual revision includes additional information which amplifies, clarifies or updates the existing text and reflects all changes made in the San Onofre Units 1, 2 and 3 facility up to a maximum of six months prior to the date of this filing.

Revision 5 consists of the appropriate revised UFHA pages for San Onofre Units 1, 2 and 3. Each revised page includes a vertical change bar drawn in the margin adjacent to the changed portion, the date of the change and the corresponding revision number. The information included in this revision supersedes and replaces the previously issued UFHA information.

Revision 5 to the UFHA reflects modifications implemented in Units 2 and 3 since the Unit 2, Cycle 4 refueling outage to comply with the requirements of 10 CFR 50, Appendix R, Sections III.G, III.3, III.L and 111.0 and deviations thereto approved in the NRC's Safety Evaluation dated June 29, 1988. In addition, the San Onofre Unit 1 specific information has been revised to reflect changes to the Unit 1 facility and an approved exemption from Branch Technical Position APCSB 9.5-1, Appendix A requirements.

This revision to the UFHA does not alter any conclusions regarding the ability to achieve and maintain safe shutdown in the event of a fire at San Onofre Units 1, 2 and 3.

If you have any questions regarding this matter, please call me.

-1 8 1

Very truly yours, 8,902160:310 890215 PDR ADOCK 05000206 Enclosure I

cc: 3. B. Martin, Regional Administrator, NRC Region V F. R. Huey, NRC Senior Resident Inspector, San Onofre Units 1, 2 and 3 D. 3. Kubicki, NRC Staff C. B. Ramsey, Inspector, NRC Region V T. Storey, SAIC

UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION Application of SOUTHERN CALIFORNIA EDISON

)

COMPANY and SAN DIEGO GAS & ELECTRIC COMPANY )

for a Class 104(b) License to Acquire,

)

DOCKET NO. 50-206, Unit 1 Possess, and Use a Utilization Facility as

)

UPDATED FHA REVISION 5 Part of Unit No. 1 of the San Onofre Nuclear )

Generating Station

)

SOUTHERN CALIFORNIA EDISON COMPANY and.SAN DIEGO GAS & ELECTRICAL COMPANY hereby submit Revision 5 to the Updated Fire Hazards Analysis (UFHA) for San Onofre Nuclear Generating Station, Units 1, 2 and 3. This revision to the UFHA includes additional information which amplifies, clarifies or updates the original text and reflects all changes up to a maximum of 6 months prior to the date of this filing for San Onofre Units 1, 2 and 3. This revision to the UFHA reflects modifications implemented in Units 2 and 3 since the Unit 2, Cycle 4 refueling outage to comply with the requirements of 10 CFR 50, Appendix R, Sections III.G, III.3, III.L and 111.0, including NRC approved deviations thereto.

This submittal fulfills the requirements of 10 CFR 50.71 for both.San Onofre Unit 2 and Unit 3.

The Unit 1 specific information has been revised to reflect changes to the Unit 1 facility and an approved exemption from Branch Technical Position APCSB 9.5-1, Appendix A requirements.

The information included in this revision supersedes and replaces the previously issued UFHA information.

Subscribed on this 15th day of February 1989.

Respectfully submitted, SOUTHERN CALIFORNIA EDISON COMPANY By: s/s Kenneth P. Baskin Subscribed and sworn to before me this 15th day of February 1989 s/s Agness Crabtree Notary Public in and for the County of Los Angeles, State of California Charles R. Kocher James A. Beoletto Attorneys for Southern California Edison Company By:

s/s James A. Beoletto

UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION Application of SOUTHERN CALIFORNIA

)

EDISON COMPANY, ET AL. for a Class 103

)

DOCKET NO. 50361, Unit 2 License to Acquire, Possess, and Use

)

UPDATED FHA REVISION 5 Two Utilization Facilities and Related

)

Licenses in Connection with Units No. 2

)

DOCKET NO. 50-362, Unit 3 and 3 of the San Onofre Nuclear

)

UPDATED FHA REVISION 5 Generating Station SOUTHERN CALIFORNIA EDISON COMPANY, ET AL. hereby submit Revision 5 to the Updated Fire Hazards Analysis (UFHA) for San Onofre Nuclear Generating Station, Units 1, 2 and 3. This revision to the UFHA includes additional.

information which amplifies, clarifies or updates the original text and reflects all changes up to a maximum of 6 months prior to the date of this filing for San Onofre Units 1, 2 and 3. This revision to the UFHA reflects modifications implemented in Units 2 and 3 since the Unit 2, Cycle 4 refueling outage to comply with the requirements of 10 CFR 50, Appendix R, Sections III.G, III.3, III.L and 111.0, including NRC approved deviations thereto.

This submittal fulfills the requirements of 10 CFR 50.71 for both San Onofre Unit 2 and Unit 3.

The Unit 1 specific information has been revised to reflect changes to the Unit 1 facility and an approved exemption from Branch Technical Position APCSB 9.5-1, Appendix A requirements.

The information included in this revision supersedes and replaces the previously issued UFHA information.

15thFebruary

,1989.

Subscribed on this 15ih day of Febrary---

Respectfully submitted, SOUTHERN CALIFORNIA EDISON COMPANY By:

s/s Kenneth P. Baskin Subsgribed and sworn to before me this 1bth day of _Feruary 1989 s/s Agnes Crabtree Notary Public in and for the County of Los Angeles, State of California Charles R. Kocher James A. Beoletto Attorneys for Southern California Edison Company By:

s A. Beoletto

UPDATED FIRE HAZARDS ANALYSIS INSTRUCTION FOR REVISION NO. 5 Revision No. 5 to the Updated Fire Hazards Analysis for San Onofre Nuclear Generating Station Units 1, 2 and 3 consists of insert pages to the UFHA.

The Revision 5 pages to the UFHA provide:

A.

Changes to update, or clarify, the report and are indicated by a line in the outside margin. The date and revision number are provided at the bottom of each page.

B.

Revisions to figures are identified with a revision number and date and the change area is clouded.

The attached List of Effective Pages should be used as a guide for inserting the O

pages.

UPDATED FIRE HAZARDS ANALYSIS San Onofre Nuclear Generating Station Units 1, 2, and 3 LIST OF EFFECTIVE PAGES Page or Figure No.

Issue Page or Figure No.

Issue VOLUME 1 1/AB-14 Rev 3 1/AB 1/AB-16 Rev 5 Title Page Rev 5 1/AB 1/AB-18 Rev 4 iii, iv Rev 1 1/AB 1/AB-21 Rev 5 LOEP LOEP-9 Rev 5 1/AB 1/AB-24 Rev 4 v -

ix Rev 4 1/AB-25 Rev 3 Section 1.0 Tab Updated 1/AB 1/AB-29 Rev 4 1-1 Rev 1 1/AB 1/AB-31 Rev 5 1-2 Rev 4 1/AB 1/AB-33 Rev 4 1 1-5 Rev I 1FH Tab Rev 1 Section 2.0 Tab Updated 1/FH-i - 1/FH-ii Rev 3 2 2-8 Rev 4 1/FH 1/FH-2 Rev 5 Section 3.0 Tab Updated 1/FH 1/FH-4 Rev 3 3 3-5 Rev 4 1/FH 1/FH-7 Rev 5 3 3-14 Rev 5 I/FH 1/FH-14 Rev 4 3-15 Rev 4 1TB Tab Rev 1 Section 4.0 Tab Updated 1/TB-i - 1/TB-li Rev 3 4 4-6 Rev 4 1/TB 1/TB-2 Rev 4 4 4-10 Rev 5 1/TB 1/TB-4 Rev 3 4 4-16 Rev 4 1/TB 1/TB-11 Rev 4 Section 5.0 Tab Updated 1/TB 1/TB-13 Rev 3 5 5-10 Rev 4 1/TB 1/TB-19 Rev 4 5-11 Rev 3 1/TB 1/TB-21 Rev 5 5 5-20 Rev 4 1/TB 1/TB-27 Rev 4 5 5-22 Rev 3 l/TB 1/TB-29 Rev 5 Section 6.0 Tab Updated I/TB 1/TB-31 Rev 3 6-1 Rev 3 1/TB l/TB-33 Rev 5 1CO Tab Rev 1 1/TB-34 Rev 4 1/CO-i Rev 3 1/TB-35 Rev 3 1/CO-il Rev 1 1/TB 1/TB-37 Rev 5 1/CO-1 Rev 4 1/TB 1/TB-40 Rev 4 1/CO 1/CO-4 Rev 3 1/TB-41 Rev 3 1/CO 1/CO-13 Rev 4 1PB Tab Rev I IAB Tab Rev 1 1/PB-i -

1/PB-il Rev 3 1/AB-i -

1/AB-ii Rev 3 1/PB 1/PB-5 Rev 4 1/AB 1/AB-2 Rev 5 1/PB-6 Rev 3 1/AB 1/AB-7 Rev 4 1/PB-7 Rev 4 1/AB-8 Rev 3 1/PB-8 Rev 3 1/AB 1/AB-11 Rev 5 I/PB I/PB-12 Rev 4 I/AB-12 Rev 3 1/PB-13 Rev 3 1/AB-13 Rev 5 2/89 LOEP-1 REVISION 5

0 LIST OF EFFECTIVE PAGES (cont)

Page or Fiqure No.

Issue Page or Figure No.

Issue 1/PB-14 Rev 4 1/DG-12 Rev 3 1/PB-15 Rev 3 1/DG 1/DG-14 Rev 5 1/PB 1/PB-21 Rev 4 1/DG 1/DG-18 Rev 3 1/PB 1/PB-23 Rev 5 1/DG 1I/DG-20 Rev 5 1/PB 1/PB-26 Rev 4 1/DG 1/DG-22 Rev 3 1/PB-27 Rev 3 1/DG 1/DG-24 Rev 5 1/PB 1/PB-29 Rev 5 1/DG I/DG-26 Rev 3 1/PB 1/PB-31 Rev 3 1/DG 1/DG-28 Rev 5 1/PB I/PB-34 Rev 5 1/DG 1/DG-30 Rev 3 1/PB 1/PB-37 Rev 3 1/DG 1/DG-32 Rev 5 1/PB 1/PB-39 Rev 5 1/DG 1/DG-35 Rev 3 1/PB-40 Rev 3 I/DG-36 Rev 5 1/PB 1/PB-42 Rev 4 1YD Tab Rev 3 1/PB-43 Rev 3 1/YD-i Rev 3 1/PB 1/PB-45 Rev 5 1/YD-ii Rev 4 1/PB 1/PB-49 Rev 4 1/YD-1 Rev 4 1/PB 1/PB-51 Rev 5 1/YD 1/YD-3 Rev 3 1/PB 1/PB-53 Rev 3 1/YD 1/YD-6 Rev 4 1/PB 1/PB-55 Rev 5 1/YD 1/YD-8 Rev 3 1/PB 1/PB-57 Rev 4 1/YD 1/YD-12 Rev 4 1/PB-58 Rev 3 1/YD 1/YD-14 Rev 3 1/PB 1/PB-62 Rev 5 1/YD 1I/YD-24 Rev 4 1/PB 1/PB-64 Rev 3 1/YD 1/YD-26 Rev 5 1/PB 1/PB-67 Rev 4 1/YD 1I/YD-29 Rev 4 1/PB 1/PB-69 Rev 3 1/YD 1/YD-31 Rev 5 1I/PB 1/PB-73 Rev 4 1/YD-32 Rev 3 1/PB-74 Rev 3 1/YD 1/YD-36 Rev 4 1/PB 1I/PB-80 Rev 4 1/YD 1/YD-38 Rev 3 1/PB lIPB-85 Rev 3 1/YD 1I/YD-41 Rev 4 1/PB 1I/PB-87 Rev 5 1I/YD-42 Rev 3 1/PB 1/PB-89 Rev 3 1/YD 1/YD-44 Rev 5 1/PB 1/PB-92 Rev 5 1/YD 1/YD-46 Rev 3 1/PB 1/PB-94 Rev 3 1/YD-47 Rev 4 1/PB 1/PB-99 Rev 5 1/YD-48 Rev 3 1/PB-100 -

1/PB-101 Rev 3 1/YD 1I/YD-50 Rev 4 1/PB-102 Rev 4 1/YD-51 Rev 3 1/PB-103 Rev 3 1/YD 1/YD-53 Rev 5 1DG Tab Rev 1 1/YD 1/YD-56 Rev 4 1/DG-i -

1/DG-ii Rev 3 1/YD 1/YD-61 Rev 5 1/DG 1/DG-2 Rev 5 1/YD-62 Rev 3 1/DG-3 Rev 4 1/YD-62A Rev 5 1/DG 1/DG-9 Rev 3 1/YO 1/YD-65 Rev 5 1/DG 1/DG-11 Rev 4 1/YD Rev 3 2/89 LOEP-2 REVISION 5

LIST OF EFFECTIVE PAGES (cont)

Page or Figure No.

Issue Page or Figure No.

Issue i/YD-67 Rev 4 2/SE 2/SE-75 Rev 5 1/YD 1/YD-69 Rev 5 2/SE 2/SE-78 Rev 4 1/YD-70 Rev 3 2/SE-79 Rev 5 1/YD-71 Rev 4 2/SE-80 Rev 4 IVN Tab Rev 3 2/SE 2/SE-82 Rev 5 1/VN-i -

1/VN-ii Rev 3 2/SE 2/SE-84 Rev 4 1/VN-1 Rev 5 2/SE-85 Rev 5 Section 7.0 Tab Updated 2/SE 2/SE-87 Rev 4 7-1 Rev 4 2FH Tab Updated 2CO Tab Updated 2/FH-i -

2/FH-ii Rev 4 2/CO-i -

2C0-ii Rev 4 2/FH 2/FH-2 Rev 5 2/CO-i -

2/CO-13 Rev 4 2/FH 2/FH-11 Rev 4 2/CO 2/CO-15 Rev 5 2/FH 2/FH-13 Rev 5 2/CO 2/CO-24 Rev 4 2/FH 2/FH-34 Rev 4 2PE Tab Updated 2TB Tab Updated 2/PE-i -

2PE-li Rev 4 2/TB-i -

2/TB-i Rev 4' 2/PE 2/PE-8 Rev 4 2/TB 2/TB-12 Rev 4 2/PE 2/PE-10 Rev 5 2/TB 2/TB-14 Rev 5 2/PE 2/PE-16 Rev 4 2/TB 2/TB-16 Rev 4 2/PE 2/PE-18 Rev 5 2/TB 2/TB-18 Rev 5 2/PE 2/PE-31 Rev 4 2/TB-19 Rev 4 2/PE 2/PE-33 Rev 5 2/TB 2/TB-21 Rev 5 2/PE 2/PE-41 Rev 4 2/TB 2/TB-23 Rev 4 2SE Tab Updated 2/TB 2/TB-25 Rev 5 2/SE-i -

2SE-ii Rev 4 2/TB 2/TB-28 Rev 4 2/SE 2/SE-2 Rev 5 2/TB 2/TB-30 Rev 5 2/SE 2/SE-18 Rev 4 2/TB 2/TB-37 Rev 4 2/SE 2/SE-20 Rev 5 2/TB-38 Rev 5 2/SE 2/SE-32 Rev 4 2/TB-39 Rev 4 2/SE 2/SE-34 Rev 5 2/TB-40 Rev 5 2/SE 2/SE-37 Rev 4 2/TB 2/TB-44 Rev 4 2/SE 2/SE-39 Rev 5 2/TB 2/TB-46 Rev 5 2/SE 2/SE-41 Rev 4 2CT Tab Updated 2/SE 2/SE-43 Rev 5 2/CT-i -

2/CT-i Rev 4 2/SE 2/SE-45 Rev 4 2/CT-1 Rev 5 2/SE 2/SE-47 Rev 5' 2/CT-2 Rev 4 2/SE 2/SE-50 Rev 4 2/CT 2/CT-4 Rev 5 2/SE 2/SE-52 Rev 5 2/CT 2/CT-9 Rev 4 2/SE 2/SE-54 Rev 4 2DG Tab Updated 2/SE 2/SE-56 Rev 5 2/DG-i -

2/DG-ii Rev 4 2/SE 2/SE-65 Rev 4 2/DG 2/DG-2 Rev 5 2/SE 2/SE-71 Rev 5 2/DG 2/DG-5 Rev 4 2/SE 2/SE-73 Rev 4 -

2/DG 2/DG-8 Rev 5 2/89 LOEP-3 REVISION 5

LIST OF EFFECTIVE PAGES (cont)

Page or Figure No.

Issue Page or Figure No.

Issue 2/DG 2/DG-10 Rev 4 AC AC-99 Rev 5 2/DG 2/DG-12 Rev 5 AC-100 Rev 4 2/DG 2/DG-16 Rev 4 AC-101 -

AC-110 Rev 5 2/DG 2/DG-18 Rev 5 AC-111 -

AC-112 Rev 4 2/DG 2/DG-24 Rev 4 AC-113 -

AC-114 Rev 5 2TK Tab Updated AC-115 -

AC-117 Rev 4 2/TK-i -

2/TK-i Rev 4 AC-118 - AC-119 Rev 5 2/TK-1 Rev 5 AC-120 -

AC-121 Rev 4 2/TK-2 Rev 4 AC-122 -

AC-124 Rev 5 2/TK-3 Rev 5 AC-125 -

AC-127 Rev 4 2/TK-4 Rev 4 AC-128 Rev 5 2/TK 2/TK-6 Rev 5 AC-129 Rev 4 2/TK-7 Rev 4 AC-130 Rev 5 2/TK 2/TK-9 Rev 5 AC-131 -

AC-133 Rev 4 2/TK 2/TK-30 Rev 4 AC-134 -

AC-135 Rev 5 AC-136 - AC-156 Rev 4 VOLUME 2 AC-157 Rev 5 AC-158 Rev 4 AC Tab Updated AC-159 Rev 5 AC-i -

AC-vi Rev 4 AC-160 -

AC-162 Rev 4 AC AC-3 Rev 5 AC-163 Rev 5 AC AC-6 Rev 4 AC-164 -

AC-169 Rev 4 AC AC-15 Rev 5 AC-170 -

AC-171 Rev 5 AC AC-18 Rev 4 AC-172 - AC-177 Rev 4 AC AC-23 Rev 5 AC-178 Rev 5 AC-24 Rev 4 AC-179 -

AC-182 Rev 4 AC AC-27 Rev 5 AC-183 Rev 5 AC AC-30 Rev 4 AC-184 -

AC-204 Rev 4 AC AC-36 Rev 5 AC-205 -

AC-206 Rev 5 AC AC-50 Rev 4 AC-207 -

AC-211 Rev 4 AC AC-52 Rev 5 AC-212 -

AC-216 Rev 5 AC AC-58 Rev 4 AC-217 -

AC-225 Rev 4 AC-59 Rev 5 AC-226 Rev 5 AC-60 Rev 4 AC-227 -

AC-230 Rev 4 AC-61 Rev 5 AC-231 -

AC-232 Rev 5 AC AC-64 Rev 4 AC-233 -

AC-237 Rev 4 AC AC-70 Rev 5 AC-238 Rev 5 AC-71 Rev 4 AC-239 -

AC-249 Rev 4 AC AC-73 Rev 5 AC-250 -

AC-251 Rev 5 AC AC-80 Rev 4 AC-252 -

AC-261 Rev 4 AC AC-82 Rev 5 AC-262 Rev 5 AC AC-88 Rev 4 AC-263 -

AC-268 Rev 4 AC AC-93 Rev 5 AC-269 -

AC-270 Rev 5 AC AC-96 Rev 4 AC-271 - AC-275 Rev 4 2/89 LOEP-4 REVISION 5

LIST OF EFFECTIVE PAGES (cont)

Page or Figure No.

Issue Page or Fiqure No.

Issue AC-276 Rev 5 AR AR-98 Rev 4 AC-277 -

AC-304 Rev 4 AR AR-100 Rev 5 AC-305 Rev 5 AR-101 -

AR-102 Rev 4 AC-306 -

AC-319 Rev 4 AR-103 -

AR-104 Rev 5 AC-320 -

AC-321 Rev 5 AR-105 -

AR-117 Rev 4 AC-322 -

AC-325 Rev 4 AR-118 Rev 5 AC-326 Rev 5 AR-119 Rev 4 AC-327 -

AC-400 Rev 4 AR-120 Rev 5 AC-401 -

AC-402 Rev 5 AR-121 Rev 4 AC-403 -

AC-419 Rev 4 AR-122 -

AR-123 Rev 5 AC-420 -

AC-421 Rev 5 AR-124 -

AR-128 Rev 4 AC-422 -

AC-426 Rev 4 AR-129 -

AR-130 Rev 5 AC-427 Rev 5 AR-131 -

AR-132 Rev 4 AC-428 -

AC-436 Rev 4 AR-133 - AR-134 Rev 5 AC-437 - AC-438 Rev 5 AR-135 - AR-160 Rev 4 AC-439 - AC-463 Rev 4 AR-161 Rev 5 AC-464 Rev 5 AR-162 Rev 4 AC-465 - AC-485 Rev 4 YD Tab Rev 4 AC-486 -

AC-487 Rev 5 2/3YD-i -

2/3YD-ii Rev 4 AC-488 -

AC-489 Rev 4 2/3YD 2/3YD-13 Rev 4 AC-490 Rev 5 AC-491 Rev 4 VOLUME 3 AR Tab Updated AR-i -

AR-iv Rev 4 3CO Tab Updated AR AR-5 Rev 5 3/CO-i -

3/CO-ii Rev 4 AR AR-12 Rev 4 3/CO-i -

3/CO-18 Rev 4 AR AR-14 Rev 5 3/CO 3/CO-20 Rev 5 AR AR-17 Rev 4 3/CO 3/CO-24 Rev 4 AR AR-19 Rev 5 3PE Tab Updated AR AR-21 Rev 4 3/PE-i -

3/PE-ii Rev 4 AR AR-25 Rev 5 3/PE 3/PE-2 Rev 5 AR-26 Rev 4 3/PE 3/PE-8 Rev 4 AR AR-28 Rev 5 3/PE-9 3/PE-10 Rev 5 AR AR-30 Rev 4 3/PE 3/PE-16 Rev 4 AR AR-32 Rev 5 3/PE 3/PE-18 Rev 5 AR AR-35 Rev 4 3/PE 3/PE-32 Rev 4 AR AR-37 Rev 5 3/PE 3/PE-34 Rev 5 AR AR-80 Rev 4 3/PE 3/PE-43 Rev 4 AR AR-82 Rev 5 3SE Tab Updated AR AR-85 Rev 4 3/SE-i -

3/SE-ui Rev 4 AR AR-87 Rev 5 3/SE 3/SE-2 Rev 5 AR AR-94 Rev 4 3/SE 3/SE-18 Rev 4 AR AR-96 Rev 5 3/SE 3/SE-20 Rev 5 2/89 LOEP-5 REVISION 5

LIST OF EFFECTIVE PAGES (cont)

Page or Fiqure No.

Issue Page or Figure No.

Issue 3/SE 3/SE-22 Rev 4 3/TB-19 Rev 4 3/SE-23 Rev 5 3/TB-20 Rev 5 3/SE 3/SE-33 Rev 4 3/TB 3/TB-24 Rev 4 3/SE 3/SE-35 Rev 5 3/TB 3/TB-26 Rev 5 3/SE 3/SE-38 Rev 4 3/TB 3/TB-28 Rev 4 3/SE 3/SE-40 Rev 5 3CT Tab Updated 3/SE 3/SE-42 Rev 4 3/CT-i -

3CT-ii Rev 4 3/SE 3/SE-44 Rev 5 3/CT 3/CT-4 Rev 5 3/SE 3/SE-46 Rev 4 3/CT 3/CT-9 Rev 4 3/SE 3/SE-48 Rev 5 3DG Tab Updated 3/SE 3/SE-51 Rev 4 3/DG-i -

3DG-ii Rev 4 3/SE 3/SE-53 Rev 5 3/DG 3/DG-2 Rev 5 3/SE 3/SE-55 Rev 4 3/DG 3/DG-5 Rev 4 3/SE 3/SE-57 Rev 5 3/DG 3/DG-9 Rev 5 3/SE 3/SE-67 Rev 4 3/DG 3/DG-13 Rev 4 3/SE-68 Rev 5 3/DG 3/DG-15 Rev 5 3/SE-69 Rev 4 3/DG 3/DG-17 Rev 4 3/SE-70 Rev 5 3/DG 3/DG-19 Rev 5 3/SE 3/SE-72 Rev 4 3/DG 3/DG-21 Rev 4 3/SE 3/SE-75 Rev 5 3TK Tab Updated 3/SE 3/SE-78 Rev 4 3/TK-i -

3TK-ii Rev 4 3/SE-79 Rev 5 3/TK-1 Rev 5 3/SE-80 Rev 4 3/TK-2 Rev 4 3/SE 3/SE-82 Rev 5 3/TK-3 Rev 5 3/SE 3/SE-84 Rev 4 3/TK-4 Rev 4 3/SE-85 Rev 5 3/TK-5 Rev 5 3/SE-86 Rev 4 3/TK 3/TK-7 Rev 4 3FH Tab Updated 3/TK-8 Rev 5 3/FH-i -

3/FH-ii Rev 4 3/TK 3/TK-28 Rev 4 3/FH 3/FH-2 Rev 5 Section 8.0 Tab Rev 4 3/FH 3/FH-11 Rev 4 8 8-11 Rev 5 3/FH 3/FH-13 Rev 5 U/i Fire Areas Tab Updated 3/FH 3/FH-31 Rev 4 Fig 8A (Sht 1) 3TB Tab Updated Fig 8B (Sht 1)

Rev 4 3/TB-i Rev 4.

Fig 8C (Sht 1) 3/TB-ui Rev 5 Fig 8F (Sht 1)

Rev 3 3/TB 3/TB-2 Rev 5 Fig 8G (Sht 1)

Rev 4 3/TB 3/TB-5 Rev 4 U/1 Features Tab Updated 3/TB 3/TB-7 Rev 5 Fig 8A (Sht 2) 3/TB-8 Rev 4 Fig 8B (Sht 2)

Rev 4 3/TB 3/TB-10 Rev 5 Fig 8C (Sht 2) 3/TB 3/TB-13 Rev 4 Fig 8D (Sht 2)

Rev 3 3/TB 3/TB-18 Rev 5 Fig 8G (Sht 2)

Rev 4 2/89 LOEP-6 REVISION 5

LIST OF EFFECTIVE PAGES (cont)

Page or Figure No.

Issue Page or Figure No.

Issue U/I Barriers Tab Updated Fig 8-7 (Sht 2)

Rev 2 Fig 8A (Sht 3)

Rev 4 Fig 8-8 (Sht 2)

Rev 5 Fig 8B (Sht 3)

Rev 5 Fig 8-9 (Sht 2)

Fig 8C (Sht 3)

Fig 8-11 (Sht 2)

Rev 3 Fig 80 (Sht 3)

Rev 3 Fig 8-12 (Sht 2)

U/1 Lighting Tab Updated Fig 8-13 (Sht 2)

Rev 4 Fig 8A (Sht 4)

Fig 8-14 (Sht 2)

Rev 5 Fig 8B (Sht 4)

Rev 4 Fig 8-14A (Sht 2)

Rev 4 Fig 8C (Sht 4)

Fig 8-15 (Sht 2)

Rev 2 Fig 8D (Sht 4)

Rev 3 Fig 8-16 (Sht 2)

Rev 5 Fig 8G (Sht 3)

Rev 4 Fig 8-17 (Sht 2)

U/2 Fire Areas Tab Updated Fig 8-21 (Sht 2)

Rev 4 Fig 8-1 (Sht 1)

Updated Fig 8-22 (Sht 2)

Fig 8-2 (Sht 1)

Rev 3 Fig 8-24 (Sht 2)

Rev 3 Fig 8-3 (Sht 1)

Rev 2 Fig 8-25 (Sht 2)

Rev 5 Fig 8-4 (Sht 1)

Rev 4 Fig 8-26 (Sht 2)

Fig 8-5 (Sht 1)

Updated Fig 8-26A (Sht 2)

Rev 4 Fig 8-6 (Sht 1)

Rev 5 Fig 8-7 (Sht 1)

Rev 2 VOLUME 4 Fig 8-8 (Sht 1)

Rev 4 Fig 8-9 (Sht 1)

Rev 3 U/2 Barriers Tab Updated Fig 8-10 (Sht 1)

Rev 1 Fig 8-1 (Sht 3)

Fig 8-11 (Sht 1)

Updated

- Fig 8-5 (Sht 3)

Rev 4 Fig 8-12 (Sht 1)

Fig 8-6 (Sht 3)

Rev 5 Fig 8-13 (Sht 1)

Rev 4 Fig 8-7 (Sht 3)

Rev 4 Fig 8-14 (Sht 1)

Rev 5 Fig 8-8 (Sht 3)

Rev 5 Fig 8-14A (Sht 1)

Rev 4 Fig 8-9 (Sht 3)

Fig 8-15 (Sht 1)

Updated Fig 8-13 (Sht 3)

Rev 4 Fig 8-16 (Sht 1)

Rev 5 Fig 8-14 (Sht 3)

Rev 5 Fig 8-17 (Sht 1)

Fig 8-15 (Sht 3)

Rev 4

- Fig 8-21 (Sht 1)

Rev 4 Fig 8-16 (Sht 3)

Rev 5 Fig 8-22 (Sht 1)

Fig 8-17 (Sht 3)

Fig 8-24 (Sht 1)

Rev 3 Fig 8-24 (Sht 3)

Rev 4 Fig 8-25 (Sht 1)

Rev 5 Fig 8-25 (Sht 3)

Rev 5 Fig 8-26 (Sht 1)

Fig 8-26 (Sht 3)

Fig 8-26A (Sht 1)

Rev 4 Fig 8-26A (Sht 3)

Rev 4 U/2 Features Tab Updated U/2 Lighting Tab Updated Fig 8-1 (Sht 2)

Updated Fig 8-1 (Sht 4)

Fig 8-2 (Sht 2)

Rev 3 Fig 8-2 (Sht 4)

Rev 4 Fig 8-3 (Sht 2)

Rev 2 Fig 8-3 (Sht 4)

Rev 5 Fig 8-4 (Sht 2)

Rev 4 Fig 8-4 (Sht 4)

Rev 4 Fig 8-5 (Sht 2)

Updated Fig 8-6 (Sht 4)

Fig 8-6 (Sht 2)

Rev 5 Fig 8-8 (Sht 4)

Rev 5 2/89 LOEP-7 REVISION 5

LIST OF EFFECTIVE PAGES (cont)

Page or Figure No.

Issue Page or Figure No.

Issue Fig 8-9 (Sht 4)

Fig 8-28 (Sht 3)

Fig 8-13 (Sht 4)

Rev 4 Fig 8-29 (Sht 3)

Rev 4 Fig 8-14 (Sht 4)

Rev 5 Fig 8-30 (Sht 3)

Rev 5 Fig 8-16 (Sht 4)

Rev 5 Fig 8-31 (Sht 3)

Rev 4 Fig 8-17 (Sht 4)

Fig 8-32 (Sht 3)

Fig 8-18 (Sht 4)

Rev 4 Fig 8-33 (Sht 3)

Rev 5 Fig 8-21 (Sht 4)

Rev 4 Fig 8-34 (Sht 3)

Fig 8-26 (Sht 4)

Rev 5

- Fig 8-41 (Sht 3)

Rev 4 U/3 Fire Areas Tab Updated Fig 8-42 (Sht 3)

Rev 5 Fig 8-27 (Sht 1)

Rev 5 U/3 Lighting Tab Updated Fig 8-28 (Sht 1)

Rev 3 Fig 8-27 (Sht 4)

Rev 5 Fig 8-29 (Sht 1)

Rev 4 Fig 8-28 (Sht 4)

Fig 8-30 (Sht 1)

Rev 5

- Fig 8-29 (Sht 4)

Rev 4 Fig 8-31 (Sht 1)

Updated Fig 8-30 (Sht 4)

Rev 5 Fig 8-32 (Sht 1)

Rev 5 Fig 8-32 (Sht 4)

Rev 5 Fig 8-33 (Sht 1)

Rev 4 Fig 8-33 (Sht 4)

Fig 8-34 (Sht 1)

Rev 1 Fig 8-34 (Sht 4)

Rev 4 Fig 8-35 (Sht 1)

Updated Fig 8-37 (Sht 4)

Rev 4 Fig 8-36 (Sht 1)

Fig 8-41 (Sht 4)

Rev 5

- Fig 8-37 (Sht 1)

Rev 2 U/2 & 3 Sections Tab Updated Fig 8-38 (Sht 1)

Fig 8-43 (Sht 1)

Rev 3 Fig 8-40 (Sht 1)

Rev 3 Fig 8-44 (Sht 1)

Rev 4 Fig 8-41 (Sht 1)

Rev 4 Fig 8-45 (Sht 1)

Updated Fig 8-42 (Sht 1)

Rev 5 Fig 8-46 (Sht 1)

Rev 4 U/3 Features Tab Updated Fig 8-47 (Sht 1)

Rev 4 Fig 8-27 (Sht 2)

Rev 5 Fig 8-48 (Sht 1)

Updated Fig 8-28 (Sht 2)

Rev 3 Fig 8-49 (Sht 1)

Updated Fig 8-29 (Sht 2)

Rev 4 Fig 8-50 (Sht 1)

Rev 3 Fig 8-30 (Sht 2)

Rev 5 Section 9.0 Tab Updated Fig 8-31 (Sht 2)

Rev 2 9 9-2 Rev 4 Fig 8-32 (Sht 2)

Rev 5 9-3 Rev 5 Fig 8-33 (Sht 2)

Rev 4 Appendix A Tab Updated Fig 8-34 (Sht 2)

Rev 1 A A-14 Rev 3 Fig 8-35 (Sht 2)

Updated Fig A-1 (Sht 1)

Fig 8-36 (Sht 2)

Fig A-1 (Sht 3)

Rev 3 Fig 8-37 (Sht 2)

Rev 2 Fig A Fig A-3 Rev 3 Fig 8-38 (Sht 2)

Appendix B Tab Updated

-.Fig 8-40 (Sht 2)

Rev 3 B B-13 Rev 4 Fig 8-41 (Sht 2)

Rev 4 Fig B Fig B-2 Rev 4 Fig 8-42 (Sht 2)

Rev 5 Fig B-3 Rev 5 U/3 Barriers Tab Updated Fig B Fig B-9 Rev 4 Fig 8-27 (Sht 3)

Rev 5 Fig B B-11 Rev 5 Fig B Fig B-14 Rev 4 2/89 LOEP-8 REVISION 5

LIST OF EFFECTIVE PAGES (cont)

Page or Figure No.

Issue Page or Figure No.

Issue Appendix C Tab Updated Section E 1-20 Rev 4 C-i -

C-ii Rev 3 Section F 1-7 Updated C C-5 Rev 3 Section F 8 Rev 4 C C-7 Rev 1 Section F 9-14 Updated C C-9 Rev 3 Section F 15 Rev 4 C-10 Rev 1 Section F 16-19 Updated C-11 Rev 3 Section F 20 Rev 4 C-12 Rev 1 Section F 21-22 Updated C-13 Rev 3 Section G 1-2 Updated C C-17 Rev 1 10CFR50 App. R 1-12 Rev 4 C C-19 Rev 3 C-20 Rev 1 C C-23 Rev 3 C-24 Rev 1 C-25 Rev 3 C-26 Rev 1 C C-29 Rev 3 C-30 Rev 5 C-30.a -

C-30.b Rev 5 C-31 Rev 5 C-32 Rev 3 C-33 Rev 1 C C-38 Rev 3 C C-41 Rev 1 C C-71 Rev 3 C-72 Rev 5 C C-96 Rev 3 C-97 Rev 1 C C-99 Rev 4 C-100 -

C-104 Rev 3 C-105 Rev 1 C-106 - C-107 Rev 3 C-108 -

C-109 Rev 1 Appendix D Tab Updated D-i.

Updated Section A 1 Updated Section A 2 Rev 4 Section A 3-8 Updated Section B 1-2 Updated Section B 3-5 Rev 4 Section B 6-14 Updated Section C 1-10 Updated Section D 1-26 Rev 4 2/89 LOEP-9 REVISION 5