SUBJECT:
DEGRADED GRID VOLTAGE PROTECTION -
SAN ONOFRE UNIT NO. 1 We are continuing our review of degraded grid voltage protection at San Onofre Unit No. 1 and find that the information identified in the enclosure is needed.
Please provide your response within 30 days of receipt of this letter.
Sincerely, Original signed by Dennis M. CrutchfDeld, Chief Operating Reactors Branch #5 Division of Licensing Enlosure:
As stated cc w/enclosure:
See next page Oriina sine0b A
V DFiE DL
- 5 DL:A1
- 5
~
/
SURNAME WPaulsonDcc rutchenfi elMd Cirus tchfid C
DATE~.J1 j1 I.4v PDR NRC FORM 318 (10-80) NRCM 0240 OFFICIAL RECORD COPY USGPO: 1981-335-960
Mr.
January 11, 1982 cc Charles R. Kocher, Assistant General Counsel James Beoletto, Esquire Southern California Edison Company Post Office Box 800 Rosemead, California 91770 David.R. Pigott Orrick, Herrington & Sutcliffe 600 Montgomery Street San Francisco, California 94111 Harry B. Stoehr San Diego Gas & Electric Company P. 0. Box 1831 San Diego, -California 92112 Resident Inspector/San Onofre NPS c/o U. S. NRC P. 0. Box 4329 San Clemente, California 92672 Mission Viejo Branch Library 24851 Chrisanta Drive Mission Viejo, California 92676 Mayor City of San Clemente San Clemente, California *92672 Chairman Board of Supervisors County of San Diego San Diego, California 92101 California Department of Health ATTN:
Chief, Environmental Radiation Control Unit Radiological Health Section 714 P Street, Room 498 Sacramento, California 95814 U. S. Environmental Protection Agency Region IX Office ATTN:
Regional Radiation Representative 215 Freemont Street San Francisco, California 94111
REQUEST FOR INFORMATION SAN ONOFRE NUCLEAR GENERATING STATION, UNIT 1 DEGRADED GRID PROTECTION
- 1. Detailed information on the design and operation of the degraded grid undervoltage protection system.
- 2. Drawings that show relay location and logic.
- 3. Detailed information addressing the interaction of the proposed design changes with the existing loss-of-voltage scheme and the effects.of an SI signal on this system.
- 4. Draft Technical Specifications which provide the relay setpoints and tolerances (voltage and time delay), surveillance requirements and limiting conditions of operation.
- 5. Discussion on time restraints and operator actions required to restore power to the Class 1E buses.
- 6.
Verification that the proposed design modifications meet the require ments of IEEE-279-1971.
- 7.
Detailed design information and technical specifications to cover load shedding, load sequencing and the bypassing of load shedding while the emergency diesel generators are supplying onsite power. Addition ally, discuss how your design will reinstate the load shedding and sequencing features if the diesel generator breaker should trip.