ML13317A532

From kanterella
Jump to navigation Jump to search
Forwards Corrected Table 3 Per 820816 Evaluation of Seismic Safety Margins in Facility Seismic re-evaluation Program. Conclusions of Previous Evaluation Remain Unchanged. Nonlinear Evaluation of Reactor Coolant Loop Not Affected
ML13317A532
Person / Time
Site: San Onofre 
Issue date: 03/11/1983
From: Baskin K
Southern California Edison Co
To: Crutchfield D
Office of Nuclear Reactor Regulation
References
NUDOCS 8303150477
Download: ML13317A532 (2)


Text

Southern California Edison Company P. 0.

BOX 800 2244 WALNUT GROVE AVENUE ROSEMEAD, CALIFORNIA 91770 K. P. BASKIN TELEPHONE MANAGER OF NUCLEAR ENGINEERING, March 11, 1983 (213) 572-1401 SAFETY, AND LICENSING Director, Office of Nuclear Reactor Regulation Attention:

Mr. D. M. Crutchfield, Chief Operating Reactors Branch No. 5 Division of Licensing U. S. Nuclear Regulatory Commission Washington, D.C. 20555 Gentlemen:

Subject:

Docket No. 50-206 Seismic Safety Margins San Onofre Nuclear Generating Station Unit 1 By letter dated August 16, 1982, we provided a detailed evaluation of the seismic safety margins in the seismic reevaluation program for San Onofre Unit 1 considering 10 percent exceedances of the Housner response spectra. Since submittal of that evaluation, a discrepancy was discovered in the computation of the average percent envelope of the time histories used in the analysis of the reactor coolant loop (Table 3 on page 12 of the enclosure to the August 16, 1982 letter). Corrected numbers are provided on the enclosed page.

As shown on the enclosed page, the margins decrease. However, the overall effects of the 10% exceedances of the Housner spectra are not considered to be significant. This is because (1) for the reactor building and containment sphere more than 95% of the responses, which are the driving forces for the attached equipment and piping, are due to the fundamental modes of the soil-structure interaction system, and (2) the fundamental modes of the structures are outside the period range where the 10% exceedances of the Housner spectra are postulated to occur. It should also be noted that inclusion of the effects of the Sphere Enclosure Building on the analyses, as discussed in the February 17, 1983 meeting with the NRC Staff, may slightly reduce the contribution of the fundamental mode to the overall response.

However, it also results in a lower frequency which is further outside the period range of interest. Therefore, the conclusions in our previous evaluation are not changed. It is still concluded that the nonlinear evaluation of the reactor coolant loop will not be affected.

If you have any questions on this information, please let us know.

8303150477 830311

-Very truly yours, PDR ADOCK 05000206 P

PDR Enclosure

Table 3 Average Percent Envelope of Design Time Histories Used in Analysis of Reactor Coolant Loop Direction Percent Spectral Average Percent Damping Envelope Horizontal 2

11.5 (Trace A) 4 16.0 7

6.6 Horizontal 2

12.5 (Trace B) 4 12.2 7

2.4 Vertical 2

15.6 4

15.8 7

13.7