ML13317A327
| ML13317A327 | |
| Person / Time | |
|---|---|
| Site: | San Onofre |
| Issue date: | 09/17/1982 |
| From: | Krieger R Southern California Edison Co |
| To: | Crutchfield D Office of Nuclear Reactor Regulation |
| References | |
| TASK-02-01.C, TASK-2-1.C, TASK-RR NUDOCS 8209210096 | |
| Download: ML13317A327 (38) | |
Text
Southern California Edison Company P. 0. BOX 800 2244 WALNUT GROVE AVENUE ROSEMEAD, CALIFORNIA 91770 September 17, 1982 Director, Office of Nuclear Reactor Regulation Attention:
D. M. Crutchfield, Chief Operating Reactors Branch No. 5 Division of Licensing U. S. Nuclear Regulatory Commission Washington, D.C. 20555 Gentlemen:
Subject:
Docket No. 50-206 SEP Topic II-1.C San Onofre Nuclear Generating Station Unit 1 By letter dated November 12, 1981 we provided an assessment for SEP Topic II-1.C, Potential Hazards.or Changes in Potential Hazards Due to Transportation, Institutional, Industrial and Military Facilities. As indicated in that submittal, additional information was required to complete that evaluation.
Provided as an enclosure to this letter is a revised topic assessment which incorporates the additional information and updates the previous evaluation of explosions on Interstate 5 and the Atchison, Topeka and Santa Fe Railroad.
If you have any questions on this assessment, please let us know.
Very truly yours, R. W. Krieg Supervising Engineer San Onofre Unit 1 Licensing Enclosure 3209210096 820917
'DR ADOCK 05000206, PDR
San Onofre Nuclear Generating Station, Unit 1 SEP Safety Assessment Report Revision 1 Topic II-1.C - Potential Hazards or Changes in Potential Hazards Due to Transportation, Institutional, Industrial, and Military Facilities
1.0 INTRODUCTION
The objective of this topic is to assure that San Onofre Unit 1 is adequately protected and can be operated with an acceptable degree of safety with regard to potential accidents which may occur as the result of activities at nearby industrial, transportation, and military facilities.
2.0 CRITERIA Standard Review Plan Section 2.2.1-2.2.2 states that all identified facilities and activities within 5 miles of the plant should be reviewed. Facilities and activities at greater distances should be considered if they otherwise have the potential for affecting safety-related features.
Standard Review Plan 2.2.3 defines design basis events external to the station as those accidents for which a realistic estimate of the annual probability of exceeding 10CFR100 exposure guidelines is in excess of approximately 10-7 or for which a conservative estimate of this probability is in excess of approximately 10-6.
3.0 RELATED SAFETY TOPICS AND INTERFACES A. Topic III-4.0, Site Proximity Missiles (Including Aircraft), October 23, 1981.
B. SCE submittals on NUREG-0737 Item III.D.3.4 - Control Room Habitability, June 13, and June 20, 1981.
C.
San Onofre Nuclear Generating Station, Units 2 and 3 FSAR.
D. Analysis of Hazards For Rail and Highway Transportation Routes Near San Onofre Nuclear Generating Station, Unit 1, NUS-4099.
4.0 REVIEW GUIDELINES Standard Review Plans 2.2.1, 2.2.2 and 2.2.3 were used as review guidelines.
5.0 EVALUATION Data for hazardous materials, frequency of shipments of hazardous materials and accident rates were extracted from the San Onofre Units 2 and 3 FSAR and are reproduced here for completeness.
Additional data and analytic methods are contained in Reference D. These data were analyzed for their effect on Unit 1, taking into account differences in plant design criteria and location with respect to transportation routes.
-2 5.1 Nearby Industrial, Transportation and Military Facilities Nearby industrial, transportation and military facilities are illustrated in Figure 1. Items illustrated on Figure 1 are described below.
There exists, within 5 miles of the plant:
- 1. a quarry.
- 2. U.S. Marine Corps Base, Camp Pendleton
- 3. three transportation routes
- 4.
three pipe lines 5.1.1 Quarrying Operations The only facility involving the processing of products and the employment of personnel within 5 miles of the plant is Camp Pendleton quarry located 4 miles north of the plant site as shown in Figure 1. Quarry operations are to crush and sort aggregate material for maintenance and construction.
Explosives are not used.
5.1.2 Military Operations Fuel storage areas include the following gasoline facilities at Camp Pendleton Special Services gas stations:
(1) The nearest is located 0.1 mile east of the San Onofre gate to Camp Pendleton on Basilone Road, 1.5 miles northwest of the plant; (2) Camp San Onofre on Basilone Road; (3) On the corner of Cristianitos and San Mateo Roads near Camp San Mateo; and (4) At Camp San Onofre at the intersection of Basilone and San Mateo Roads.
Ammunition is stored by the U.S. Marine Corps in the Las Pulgas area of Camp Pendleton approximately 9 miles from San Onofre Unit 1. The material is Class 7 explosive and is stored in underground bunkers. This facility is separated from the plant site by the San Onofre mountains.
Except for amphibious landings, most Marine Corps activities are conducted inland from Camp San Onofre and the range of coastal hills that parallels the coast near the plant. With regard to amphibious landings, San Onofre is located in a separate, designated sector of the beach, and discussions with the Marine Corps indicated no landings will be made in this sector.
No firing of live ammunition is permitted throughout a strip along the seacoast, which is approximately 2 miles wide at its narrowest point.
This strip extends from the northern reservation boundary to approximately 10 miles south of Unit 1.
-3 Where firing or weapon impact is permitted, training is conducted under very close supervision since populated areas, the highway, railroad, and infantry maneuvering areas are located along the seacoast of the reservation to a distance of approximately 5 miles inland.
Firing ranges are shown on U.S. Geological Survey (1968), 7.5 minute quadrangle sheets:
San Clemente, Margarita Peak, San Onofre Bluffs, and Las Pulgas Canyon.
The nearest firing range (approximately 3 miles away) is a known-distance range over which small arms are used to gain sighting data.
The maximum range of firing is about 100 feet, with rounds impacting into a steep hillside.
All other firing ranges are generally inland from Camp San Onofre and located such that the maximum range of the weapons would not permit an impact closer than approximately 2 miles from the plant, even assuming firing was directed toward the plant rather than into the designated sectors. Firing is also directed into hillsides or valleys to avoid any danger of projectile skipping.
Aircraft practice firing and artillery bombardment is controlled at all times and is directed into impact areas located further than 5 miles inland.
Aircraft approaches and pullouts do not pass near the plant.
There are two bombing and strafing ranges located approximately 6 miles from the plant.
Various types of aircraft delivered ordnance of up to 500-pound bombs are employed on these ranges.
No bombardment from the sea is ever permitted, and the shore landing maneuvers do not involve the use of live ammunition.
Thus, Marine Corps activities which could otherwise conceivably constitute a hazard to the plant are all conducted well away from the coastline and do not constitute a credible hazard to plant safety.
The Marine Corps indicated that there are no missile sites on Camp Pendleton and none within at least 10 miles of Unit 1.
5.1.3 Transportation Routes The three transportation routes within 5 miles of the plant are described below:
(1) The old Highway 101, immediately east of the site, does not carry through traffic, but is the entrance road to the south end of San Onofre State Beach.
(2) Interstate 5 (1-5) is east of the site and is the only public coastal vehicular link between Orange County and San Diego County.
The 1974-75 estimated average daily traffic was 63,570 vehicles, with an estimated passenger population of 130,240. The years 1970-1974 averaged 3,672 trucks per day adjacent to the plant.
This figure includes vehicles over 6,000 pounds, with two or more axles, but does not include buses, vans, campers, and pickups.
-4 (3) The Atchison, Topeka and Santa Fe Railroad (AT&SF) right-of-way is east of the site between Highway 101 and 1-5. This is an active line with Amtrack passenger service and cargo service.
Other transportation routes near the plant, but farther than 5 miles are:
- 1. Commercial vessel shipping lanes are southwest of the plant in the Pacific Ocean.
- 2. Aircraft routes near the plant are described in the assessment of Topic III-4.D, Site Proximity Missiles (including aircraft).
5.1.4 Oil and Gas Pipelines There are three pipelines in the vicinity of the plant:
(1) San Diego Gas and Electric Company inch natural gas pipeline adjacent to Basilone Road. The characteristics of this pipeline are:
A. Size:
6-inclh diameter, 12,058 feet long, 4-inch diameter, 3,634 feet long B. Age:
1968 C. Operating pressure: 200 psi D. Depth of burial:
36 inches average E. Location:
Adjacent to Basilone Road F. Valves:
Plug type, manual G. Material:
Natural Gas H. Storage:
The pipeline is not used for gas storage I. Future plans:
No plans to expand J. Leaks:
None K. Flow direction:
Northeast L. Release event:
Gas would be lost at rate of 875 x 106 ft3/h for about 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. Release would be noticed prior to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> because of drop at U.S. Marine Corps control house, or by regular Marine Patrols.
(2) Southern California Gas Company inch natural gas pipeline adjacent to 1-5.
The characteristics of this pipeline are:
-5 A.
Size:
12-inch diameter B. Age:
It was constructed in several phases. The section from 0.4 miles northwest to 1.6 miles northwest of the plant was built in 1932. The section from 1.6 to 1.9 miles northwest was constructed in 1960. The section from 1.9 to 2.8 miles northwest was built in 1966. The section from 2.8 to 5.0 miles northwest was built in 1929. And the section from 0.4 miles northwest to 5.0 miles southeast of the plant was built in 1966.
About 0.1 miles of pipeline 3.3 miles north of the plant was replaced in 1963.
C. Operating pressure: 400 psig (maximum allowable)
- 0. Depth of burial:
30 inches average E. Location:
See Figure 1. The pipeline is located approximately 673 feet northeasterly from the centerline of Unit 1 containment.
The pipeline is located within the right-of-way of U.S. Highway.101, approximately 5 feet southwesterly of the northeast edge of the right-of-way.
F. Valves:
There are three plug valves located 1.3 and 2.8 miles northwest of the plant and 2.1 miles southeast (see Figure 1).
G. Material:
Natural gas (91% methane, 5% ethane, 4%
miscellaneous)
H. Storage:
The pipeline is not used for gas storage I. Future plans:
There are no plans for expansion or to use the pipeline for a product other than natural gas.
J. Leaks:
There have been two leaks within 5 miles of the plant.
One, in 1967, was approximately 3.5 miles north of the plant, a small corrosion leak with no fire or explosion.
The other, in 1963, was approximately 3.3 miles north of the plant, a break in the pipeline due to exterior stress, with no fire or explosion.
Repair was made by replacing 449 feet of pipe.
(3) San Diego Pipeline Company -
10-inch refined petroleum products pipeline 2 to 5 miles northeast of the plant in Camp Pendleton.
The characteristics of this pipeline are:
A. Size:
10-inch diameter B. Age:
Constructed in 1962 C. Operating pressure:
1,440 psi (maximum)
-6 D. Depth of burial:
30-inches average E. Location:
See Figure 1 F. Valves:
Manually operated gate valve at milepost 58.24 (see Figure 1)
G. Material:
Gasoline, diesel fuel, turbine fuel, navy jet fuel (JP-5)
H. Storage:
The pipeline is not used for gas storage I. Fugure plans:
No immediate plans to expand. Future demand could necessitate construction of a parallel pipeline.
J. Leaks:
None within 5 miles K. Flow direction:
South L. Release even.t:
Product initially released at flowrate. Within 20 seconds the pressure drop would be detected and the pipeline shut down by automatic warning devices. The nearest main line valves upstream and downstream of the break would be closed.
5.2 Description of Products and Materials 5.2.1 Atchison, Topeka and San Fe Railroad (AT&SF) 5.2.1.1 Toxic Chemicals.
The AT&SF has indicated that none of the hazardous chemicals listed in U.S.N.R.C. Regulatory Guide 1.78 (June 1974) Table C-2 were shipped by the plant during the first 11 months of 1975.
5.2.1.2 Gaseous and Liquid Fuels. The AT&SF has indicated that 113 carloads of liquified petroleum gas (LPG) were shipped by the plant during a representative period of the first 11 months of 1975. These noninsulated steel fusion welded tank cars have a water capacity of 33,500 gallons and weight approximately 70 tons. These carloads of LPG arrive more frequently during the winter months with 12 to 18 cars in the heaviest months. There are no more than 2 or 3 cars in any one train.
AT&SF forecasted the same number of shipments for 1976 as in 1975, and did not anticipate an increase in these shipments in the future.
5.2.1.3 Explosives.
Information from the Department of the Army indicated there were eight rail shipments of military explosives past the plant during the year June 1977 through May 1978. The maximum net explosive weight per shipment was 20,548 pounds.
5.2.2 Interstdte 5 (1-5)
A truck traffic survey was conducted on 1-5 in order to gather data for the San Onofre Units 2 and 3 FSAR.
-7 The number of shipments of hazardous cargo shipped on 1-5 adjacent to the plant is given in the second column of Table 1. Several of the cargo categories used for presenting the survey results in Table 1 contain a number of different materials. Table 2' lists the various cargoes contained within these categories.
The expected number of military explosive shipments past the plant on I-5 was estimated to be 1,411 for the year June 1978 through May 1979. The Navy stated that chdnges in shipment routes and requirements for 911 of the shipments would occur after 1980 so that there will be less than 10% of the 911 shipments. Assuming that the remaining shipments are unaffected, the projected 1-5 military explosive shipment frequency is 592.
The maximum net explosive weight per I-5 shipment is 11,400 lbs.
5.2.3 Waterways The principal uses of the coastal waters are pleasure boating, industrial cooling, military exercises, and sport and commercial fishing. Commercial vessel traffic lanes.lie at distances greater than 5 miles from the plant.
Military exercises are discussed elsewhere in this report.
5.2.4 Projections of Industrial Growth There are no plans for expansion of existing facilities or new industrial development with 5 miles of the plant.
Existing pipelines and waterways are also not scheduled for expansion.
San Diego County, in conjunction with the CALTRANS, has forecast an increase of 45% in truck traffic on 1-5 in the vicinity of the plant.
Hazardous cargo shipments are expected to decrease on I-5 as a percent of total shipments because increased industrialization in San Diego will provide these products locally.
Fuel shipments (gasoline, LPG, LNG, etc.) may decrease in absolute number because of the development of these processing facilities in San Diego and the increasing cost to ship fuels by truck.
Explosive shipments by the U.S. Navy will remain constant to the U.S. Marine Corp Camp Pendleton and will decrease for other shipments.
Industrial gas and chemical shipments will vary as a function of future industrial process requirements, availability from local sources, products manufactured and shipment costs. The largest increase in truck activity can be expected in food and other consumer products.
5.3 EVALUATION OF POTENTIAL ACCIDENTS The accidents considered in this section include:
- 1. explosions of hazardous materials,
- 2. delayed ignition of flammable vapor clouds,
- 3.
liquid spills,
- 4. release of toxic vapors,
- 5.
offsite brush fires, and
- 6. accidents at sea.
-8 5.3.1 Determination of Design Basis Events Available statistical data were analyzed to determine the probability of occurrence of potential accidents based upon their historical frequency of occurrence. In those cases where data relating to particular classes of accidents were not available, conservative assumptions were used to evaluate order-of-magnitude accident probabilities. A description of data sources, assumptions, and computational methods are presented in the San Onofre Units 2 and 3 FSAR, Reference D of this report and in the body of this report.
The various safety-related structures were analyzed to determine their peak positive normal reflected explosion overpressure capability.
The results are shown in Table 8. Although components located outside of structures were not specificaly evaluated to determine their overpressure capability, it is concluded that a value of 0.5 psi is a conservative value to use for the evaluation of accident probabilities.
This is based on the fact that the majority of structures and components can withstand pressures far in excess of this value (see, for example, Table 8) and the fact that outside components are located west of major structures (including the diesel generator building, sphere enclosure building, control building and turbine building) which effectively shield them fron the explosion overpressure. Therefore, a value for the site of 0.5 psi was used.
5.3.2 Transportation Accidents on 1-5 Hazardous materials transported past San Onofre on 1-5 are discussed above and include military ordnance, flammable and explosive chemicals, toxic chemicals, and pressurized noncombustible gasses.
5.3.2.1 Accident Rates for Motor Carriers of Hazardous Cargo The probability of transportation accidents on I-5 involving hazardous materials was estimated from statistical data on the frequency of truck accidents on 1-5 within 5 miles of the San Onofre plant site and nationwide accident rates.
Accident rates for all trucks(a), tank trucks and trucks with explosive cargo were determined for a 10 mile segment of 1-5 extending approximately equidistant in both directions from the San Onofre site.
From the data in Table 3A, the observed truck accident rate is 0.566 x 10-6 accidents per truck mile.
Truck traffic rates are based on weighted sample counting and extrapolated to annual counts.
Northbound and southbound data are combined.
Traffic accidents are reported to the state if property damage is $200.00 or greater or there has been personal injury or death.
In this analysis, I-b accident rates are combined with U.S. Department of Transportation (U.S. DOT) data where the property damage threshold for reporting accidents has been increased from $250.00 to $2,000.00.
To correct for the data base inequities, U.S. DOT data before and after the reporting threshold change were used to generate a correction factor. Table 3B presents data covering the transition period.
- a.
Truck is defined as any vehicle 5,000 pounds or more excluding pickup trucks, vans and buses.
-9 Correction factor =
1973 accident rate 0.952 x 106 1971-72 accient rate (2.19 x 10-6 + 2.31 x 106 )/2
= 0.423 This factor is applied to the 1-5 accident rates based on the assumption that California accident rates would be reduced by the same proportion as that observed on the national level.
The fact that the California threshold is
$200.00 vs. $250.00 for the U.S. DOT would make the correction factor a conservative assumption.
The 1-5 accident rate for all trucks corrected to the $2,000.00, death or injury reporting criteria:
0.423 x 0.566 x 10-6 = 0.239 x 10-6 accidents/truck-mile The bulk of hazardous commodities carried on 1-5 past the plant are in tank trucks. Nationwide truck accident statistics show that loaded tank trucks have a lower accident rate than all types of trucks combined (1.33 x 10-2 vs. 2.41 x 10-6 for years,.1968 through 1972 with the same reporting criteria). Therefore, the 1-5 accident rate for all types of trucks (0.239 x 1u-6 ) is corrected to loaded tank-truck accident rate by assuming the same relative improvement exists in California (1-5) as observed nationwide.
Loaded tank truck = 0.239 x 106 1.33 x 1-6 = 0.132 x 106 accidents/mile accident rate on 1-5 2.41 x 10 6 The accident rate for trucks carrying explosives was determined in a similar manner. The nationwide accident rate for trucks carrying explosives is 0.96 x 106 accidents/mile. Therefore, the accident rate for trucks carrying explosives on 1-5 is:
Explosive Truck = 2.39 x 106 x 0.96 x 10- 6 = 0.95 x 10-7 accidents/mile accident rate 2.41 x 10- 6 5.3.2.2 Explosions Due to Transportation Accidents on 1-5 There are three categories of materials transported on 1-5 which have a potential for creating a hazard for San Onofre Unit 1 in the event of an accident on the highway. These materials are military ordnance, flammable liquids and flammable gasses (shipped as either compressed liquid or compressed gas).
5.3.2.2.1 Military Ordnance The expected number and size of explosive shipments past the San Onofre site are shown in Table 7. This table is based on information provided by the Departments of the Army and Navy.
The explosives are Class 7 (1 pound of explosive is equal to 1 pound of TNT).
-10 Figure 2 shows the various safety-related structures and their distances from the highway and the railroad.
For the purpose of analyzing site overpressure due to explosions, the plant is characterized by a circle 480 feet in diameter whose center is 780 feet from 1-5.
This circle encloses all safety related structures as shown in Figure 3. It is conservative to calculate the probability of exceeding 0.5 psi at the boundary of this circle since:
- 1. all safety related structures are inside the circle,
- 2. the most limiting building (reactor auxiliary building) is located on the edge of the circle remote from the highway and railroad,
- 3.
all other structures can withstand at least 0.67 psi.
The probability that an accident would result in an explosion was determined for commercial shipments of explosives. During the 4-year period of,
1972-1975, there were 70 accidents involving munitions trucks (nationwide) reported, of which 3 invojyed explosions.
From this information, it is estimated that the conditional probability of an explosion due to an accident is 3/70 or 0.043.
For solid explosives, the probability of exceeding a certain overpressure was obtained from:
P'E = P(A/M)
- P(E/A) *
(NSHi
- Li)
(1) where:
P(A/M) = conditional probability of an accident per shipment mile
= 0.95 x 10-7 accidents/mile P(E/A) = conditional probability of an explosion per accident
= 0.043 NSHi = annual number of shipments of size i. See Table 7.
Li = length of route along which an explosion would yield an overpressure of 0.5 psi or more The length of the route, Li, is obtained from the geometrical configuration of the plant and the route and the overpressure - range relationship of:
-11 R = KW1/ 3 where:
R = distance from explosion site to point of interest K = constant related to overpressure
= 131 feet/1bl/ 3 for 0.5 psi W = weight of explosive (1b)
Thus:
Li = 3.79 x 10- 4 [(131W1/3 + 240)2 -
7802]1/2 miles The probability of exceeding 0.5 psi overpressure at the site due to a munitions truck accident on 1-5 is calculated to be 1.92 x 10-6 per year.
All other explosive shipments past the plant are Class B explosives which, in general, function by rapid combustion rather than detonation and therefore do not pose an explosion hazard to the plant.
5.3.2.2.2 Flammable Liquids Flammable liquids are shipped at ambient temperature and pressure and would not pose an explosion hazard unless vaporized. The nature of the explosion or fire for the flammable liquids listed in Table 1 is dependent on the chemical and physical properties of the materials.
These chemicals, in general, have low vapor pressures and high vapor densities. Thus, the vapor formed tends to hug the ground, and only a thin vapor interface exists between the air and the liquid. Therefore, spilled liquids are unlikely to produce an explosion with a strong blast wave but will produce a simple flash-over flame igniting the remainder of the fuel.
A review of the materials shipped indicates that gasoline has the highest vapor pressure and therefore the highest evaporation rate.
The next most volatile liquid shipped is acetone. For gasoline, the estimate downwind distance to the lower flammable limits is estimated to be less than 460 feet compared to minimum distance to the plant from the highway of 635 feet.
This calculation assumes Class G stability, 1.43 m/sec wind speed and 100OF temperature for evaporation.
For acetone, the distance to the lower flammable limit is less than 120 feet.
From the above, it is concluded that because of their low vapor pressures, flammable liquids shipped past San Onofre do not contribute to the overpressure or flammable cloud hazards at the plant.
-12 5.3.2.2.3 Flammable Gases The flammable yases listed in Table 1 are shipped by the plant site as compressed liquids and compressed gas.
Propane (LPG), butane, liquified natural gas (LNG), and hydrogen are shipped in tank trucks as compressed liquids, and hydrogen and acteylene are shipped as compressed gases.
The compressed liquids are shipped by tank trucks. The spills per tank truck accident rate was determined from a review of Bureau of Motor Carrier Safety data for compressed hydrocarbon gases for the years 1973 through 1977. During that period there were 109 accidents similar to those that could occur on 1-5 near San Onofre, of which 7 resulted in a spill.
The probability of a spill given an accident is 7/109 or 0.064. There was insufficient data to determine the spill rate for other compressed gases; therefore, 0.064 is used for all compressed gas trucks. During that same period, data for all LPG truck spills for highway accidents indicated that, given a spill, 4.2% resulted in explosions, 45.8% resulted in a fire and 50% in a spill only.
The probability of exposing the plant to an overpressure greater than a certain value is the sum of the contributions from accident site explosions plus drifting cloud explosions. The former is:
P'E NSH.
P(A/M)
N
[P(St/A)
- P(E/S)
- Li]
(2) where:
NSH = number of shipments of the commodity being evaluated.
See Table 1.
P(A/M) = conditional probability of an accident per shipment mile
= 1.32 x 10- 7 tank truck accidents/mile of 1-5 P(Si/A) = conditional probability of the spill size given an accident P(E/S) = conditional probability of an explosion with a significant overpressure given a spill
= 0.042 explosions/spill Li = Length of route along which an explosion would yield an overpressure in excess of a specified value. See Section 5.3.2.2.1.
The summation allows an historical spill size distribution to be utilized.
-13 For vapor cloud explosions, it is common practice to utilize a TNT equivalent calculated as follows:
W =
F
/
H E 500 Kcal/lb - TNT (3)
F = Fraction of spill quantity involved in vapor cloud S = gm-mole of combustible chemicals spilled Si = spill fraction Q = maximum quantity of shipment in volume 0 = density of liquid A = mulecular weight H = Heat of combustion ( Kcal C
gm mole E = Yield of explosion For liquified gases shippeld at atmospheric temperature under their own vapor pressure, the fraction of spill quantity in the vapor cloud is the isenthalpic flash fraction. For compressed gases it is 1.0.
These values are consistent with the conservatively assumed instantaneous puff release model.
For cryogenic liquids shipped at essentially atmospheric pressure, a 10% flash fraction was used to account for initial vaporization on mixing with warm air and boiling from the spilled liquid pool.
The entire quantity in the cloud was assumed to be involved in the fuel air reaction. The change in the quantity of vapor between upper and lower flammable limits as the cloud disperses was conservatively neglected.
Analysis of a drifting puff release has shown that the maximum quantity between flammable limits is on the order of 60-70% for materials of interest here and that for much of the travel distance, it is less than this amount.
To obtain the equivalent TNT yield, the range of explosion yields reported in the literature were surveyed and Table 9 compiled. In Table 9, the yields are roughly combined so as to approximate a value for probability distribution.
The given values of the yield are applied to the total quantity of material released from the tanker, rather than the flash fraction.
This is consistent with the way tiiat the yield has been defined in the literature.
Equations 2 and 3 give the maximum distance from any structure at which the explosion involving a particular commodity could yield the specified overpressure.. The length of route within this distance of a plant safety related structure can be obtained from the geometrical plant layout shown in Figure 4. This length (and the size of Region I) is spill size and commodity dependent.
-14 For drifting cloud explosions, the probability of exposing the plant to an overpressure greater than a certain value is:
PE= NSH P(A/M)
P(Si/A)
- 1 -
P(F/S) -
P(E/S M
- Pj (Ignition 01) *P(E/I)
ALj (4) j=1 where:
P(F/S) = conditional probability of a fire given a spill Pj(Ignition Oi) = probability of ignition (fire or explosion) in Region I given a spill at accident site j P(E/I) = conditional probability of an explosion given an ignition Lj = incremental length of route located a given distance and direction'from the plant The probability of ignition in Region I is a function of where the accident occurs (inside Region I, outside Region I and distance away), the wind direction, and a probability of ignition as a function of cloud travel distance. The first summation allows for varying spill sizes, while the second summation allows for different accident sites.
For accidents inside Region I, the wind blows with a seaward component about half of the time and a landward component the other half of the time. The distance traveled in Region I used for calculating the ignition probability was the maximum distance normal to the transportation route to the edge of Region I for each of the wind directions (seaward and landward).
The transportation routes outside Region I were divided into small (approximately 500 feet) increments. For each increment, the probability of the cloud centerline being blown through Region I was calculated utilizing site wind direction probabilities. The probability of an ignition in Region I was based on the shortest distance from the accident site to the Region I boundary and the maximum cloud path length in Region I (which is the Region I diameter). The maximum accident site to plant distance considered was the maximum downwind distance to the lower flammable limit.
A dispersion model was used to determine the distance that the vapor cloud has to travel to reach the lower flammable limit. The downwind distance is used only to determine the maximum length of transportation route which must be
-15 considered. The crosswind distance is effectively added to the boundary of Region II to determine the probability of a flammable cloud being swept into a plant air intake.
Most spills of flammable vapor are ignited essentially at the accident site.
For example, statistics from the-Association of American Railroads indicated that for 81 vapor cloud ignitions, 58% occurred from a few feet up to 50 feet, 18% between 50 and 100 feet and 24% from 100 feet to 300 feet.
Integrated ignition probability as a function of distance from historical data for LPG spill accidents were published in "Risk Assessment of Storage and Transport of Liquified Natural Gas and LP-Gas" by J. A. Simmons.
The data indicates that 10.5% of the drifting cloud ignitions resulted in an explosion while 89.5% resulted in a fire.
The magnitude of explosions is dependent on the chemical and physical properties of the material.
For LPG, LNG, and liquified hydrogen, the amount of flashing of liquid to vapor was calculated from the enthalpy differences at the cryogenic shipping condition and at atmospheric pressure. The enthalpy of combustion of a stoichiometric fuel-air mixture for each of the flammable gases was equated to the enthalpy of detonation of TNT.
For the unconfined vapor cloud explosions of LPG and LNG it was assumed that the maximum yield of the TNT equivalent weight was based upon the probability distribution discussed above. For hydrogen and acetylene, it was conservatively assumed that the maximum yield was 100% of the TNT equivalent weight. Analys s shows that the probability of exceeding 0.5 psi is 0 for LNG and 3.93 x 10-for liquified hydrogen.
The annual probability of an overpressurization from a release of LPG was realistically analyzed as an extension of the previous analysis using the following modified inputs:
(1) The single value of possible accident locations on 1-5 has been replaced by a distribution across the southbound lanes and shoulder.
(2) Sixty percent of the LPG shipments on 1-5 are in tandem trailers with a maximum of 5,000 gallons available for involvement in a vapor cloud detonation. Forty percent are in single tanks with a capacity of 10,000 gallons available for involvement in a vapor cloud detonation.
(3) The single yield of explosion has been replaced by a distribution of yields which is applied to the entire quantity of material released.
A review of LPG shipment data on 1-5 shows that most shipments are southbound or on the side of the highway nearest the plant.
The possible accident locations used in the realistic analysis were derived from actual truck accident locations along the ten-mile stretch of 1-5 near the plant.
The resulting locations and the assigned relative probabilities are:
-16 o
West edge of right-of-way 0.22 o
West edge of roadway 0.38 o
Center of roadway 0.24 o
East edge of roadway 0.16 Finally, a probability distribution for the yield of an explosion was derived. The results of this realistic analysis show that the probability of exceeding 0.5 psi is 2.09 x 10-6.
Hydrogen and acetylene are also shipped past the plant as compressed gases in cylinders. The number of shipments and cylinder sizes are listed in Table 1.
There are no results available on the probability of cylinder failure in an accident. To obtain a probability of this type of failure, it is possible to relate the probability of steel drum failure to the probability of gas cylinder failure.
The probability of breaching a cylinder or drum is assumed to be inversely proportional to the cube of the wall thickness. The wall thickness for the 219 cubic feet hydrogen gas cylinders is a nominal 0.24 inches, for the 10 large cylinders it is a minimum of 0.375 inches, and for the acetylene cylinders it is a nominal D.15 inches.
The wall thickness for the steel drum is a nominal 0.0478 inches. Using the conservative value of 0.125 for the failure probability of steel drums, the probabilities of rupturing each type of cylind rs per accident is 1.0 x 10-3 (219 cubic flet hydrogen cylinders),
2.6 x 10- (large hydrogen cylinders) and 4.05 x 10-(acetylene cylinders).
For conservatism it is assumed that the entire cargo is released. This is extremely conservative since the probability of failing more than 3 cylinders per accident is essentially zero. The annual probabilities of a plant overpressure of 0.5 psi or greater due to the detonation of a drifting cloud from an 1-5 release of flammable gas are 3.75 x 10-8 for 260 shipments of 219 cubic feet hydrogen cylinders 9.72 x 10- 9 for 24 shipments of large hydrogen cylinders and 7.21 x 10-for 52 shipments of acetylene.
The analysis for delayed detonation of vapor clouds is conservative since it is very probable that escaping vapors will find an ignition source near the accident site.
Car and truck traffic along 1-5 would provide ample heat sources from hot manifolds and mufflers.
Data for 81 vapor releases from tank cars indicated that 58% were ignited within 50 feet of the accident and all leaks found sources of ignition within 300 feet.
The effect of bouyancy was neglected in the analysis. The probability of a flammable vapor cloud being swept into the plant was calculated for LNG, hydrogen and acetyline. The results are 1.03 x 10-8 for LNG, 9.3 x 10-9 for hydrogen and 7.63 x 10-10 for acetylene.
-17 Another possible cause of damage to the plant is a fireball generated by the explosion of tank trucks on 1-5.
Ignition of a 10,100 gallon LPG tank consuming the entire contents would result in a fireball with a radius of 156 feet with a duration of 7.4 seconds. Since the outer dimension of the fireball is a minimum of 479 feet away from the nearest safety-related building, a fireball caused by an LPG tank truck will not be a hazard to the plant.
5.3.2.2.3 Release of Toxic Gases Due to Transportation Accidents on I-S Toxic chemicals are transported along 1-5 on a. regular basis. Tables 1 and 2 list the observed materials transported past the site and their estimated frequency of shipment.
The following five substances have been identified as a result of the probabilistic risk assessment as having probabilities near to or greater than 10- 7/years:
(1) Chlorine 1 x 10- 6/year (2) Butane 1 x 10- 6/year (3) Gasoline 1 x 10-6 /year (4) Ammonia 9 x 10- 7/year (5) Propane 2 x 10- 6/year As a result of the control room habitability review performed on Unit 1 as required by NUREG-0737 Item IlI.D.3.4-Control Room Habitability, the Unit 1 control room HVAC will be replaced. The new HVAC system will include an automatic isolation feature sensitive to the above chemicals.
5.3.3 Transportation Accidents on the Atchison, Topeka, and Santa Fe Railroad Hazardous materials transported past San Onofre on the AT&SF railroad track are military ordnance and LPG. The AT&SF Railway Company does not anticipate any other hazardous materials being shipped through the San Onofre area.
5.3.3.1 Accident Rates for AT&SF Railroad accident rates were determined from data supplied by the AT&SF Railroad for a section of track from Fullerton, California to San Diego (102.5 miles) and passing by San Onofre. Data is for 11 years between 1968 to 1978.
During this period, there were 26,378 trains and 10 accidents. Therefore, the accident rate for trains passing San Onofre is:
10 accidents (102.5 miles)(26,378 trains) 3.70 x 10-6 accidents/train mile
-18 5.3.3.2 Explosions Due to Accidents on the AT&SF 5.3.3.2.1 Military Ordnance The AT&SF report hauling 74 carloads of ammunition past the San Onofre site during the first 11 months of 1975. Shipments occur with a frequency of about 7 carloads per month. The U.S. Navy states that the 1975 shipments had the following distribution by net explosive weight(a):
1 boxcar/year at 37,000 pounds net explosive weight 1 boxcar/year at 25,500 pounds net explosive wweight 82 boxcars/year at less than 25,500 pounds but more than 400 pounds averaging 13,000 pounds.
To predict the overpressures that might be produced by the explosion of ordnance boxcars on the AT&SF track, assumptions are required about the weight of explosive in the 82 boxcars shipments where the value was not specified, and also about the number of ordnance boxcars which are carried in a single train.
Table 5 gives the assumed frequency distribution of net explosive weight per boxcar vs. the number of boxcars/year hauling this quantity of explosive. The mean net weight for the 82 boxcar loads of 25,000 pounds and less is approximately 13,000 pounds, which agrees well with the mean net explosive weight reported for these shipments by the U.S. Navy.
It is assumed that all ordnance train shipments involve two loaded boxcars.
For conservatism, the boxcar net explosive weights given in Table 5 were combined such as to maximize the weight of explosive per train shipment.
It is further conservatively assumed that if either of the boxcars in a shipment detonates, the second will also detonate. The total weight and number of each size shipment is given in Table 6.
No data were found on the conditional probability of a munitions car explosion, given a munitions car accident.
However a report by the Illinois Institute of Technology (IT) Research Institute gives a compilation of data from which the probability of an explosion in a munitions train accident can be estimated.
- a. One pound of net explosive weight equals one pound of TNT
-19 It has been estimated that there were 1.98 x 107 explosive train-miles per year based on statistics for a 57 year period from 1917 to 1973. The annual average train miles during this same period was 1.36 x 109.
During this 57-year period there were 35 explosions involving in-transit shipments of explosives. The national annual probability of an explosion due to a train accident involving explosives is 3.1 x 10-8 explosions per explosive train mile. The accident rate for the AT&SF is significantly less than the national average. Therefore, using the ratio of AT&SF to the national rate, the probability of an explosion on the AT&SF is 1.05 x 10-8 explosions per explosive train mile. The IIT report also determined a significance factor to account for those accidents which did not yield a significant explosive overpressure. This significance factor is 0.154.
The probability that a munitions train explosion on the AT&SF will cause a peak positive normal reflected pressure at the station which exceeds 0.5 psi is estimated by the following equation:
Pop
= Pex x SF x ZNiLi where Pop = The annual probability of an overpressure at the station exceeding the design basis overpressure of 0.5 psi Pex = probability of an explosion per AT&SF explosive train mile (1.05 x 10-8)
SF = significance factor (0.154)
Ni = the number of munitions train shipments/year which carry a total of Wi pounds net explosive weight past the San Onofre site Li = the critical length of track over which the detonation of Wi pounds of TNT would produce an overpressure at the station exceeding the design basis overpressure of 0.5 psi Values for W1 and Ni assumed for the calculation are given in Table 6.
The length of track, Li, is calculated in a manner similar to that for explosions on 1-5, discussed above.
Assuming the entire explosive cargo of a train detonates in-mass, the annual probability of peak positive normal reflected overpressure at the station exceeding 0.5 psi caused by ordnance detonations on the AT&SF track, is 2.0 x 10-8.
This number can be considered to be conservative, and the actual probability of occurrence is expected to be much lower since, if an explosion were to occur in a boxcar of ordnance of the type normally shipped past San Onofre (small arms ammunition) it is more likely to detonate in small individual bursts rather than as a single large blast.
Overpressures experienced at the site would be correspondingly lower.
-20 5.3.3.2.2 LPG Tank Cars There are two types of accidents involving LPG cars which could lead to an explosion:
(1) accidental puncture of an LPG tank car, and (2) exposure of an LPG tank car to fire.
During the 6-year period 1965 to 1970, there were 63 mechanical damage-induced loss-of-lading accidents involving type 112A cars carrying flammable compressed gases. The fleet of 112A (the type used to transport LPG by the plant) caps loaded with flammable compressed gases traveled a total of 5.38 x 10' car-miles/year during this period. Therefore, the national rate of loss-of-lading accidents per shipment mile was 1.95 x 10-7 loss-of lading accidents caused by mechanical damage/LPG tank car mile. The accident rate for the AT&SF is signifcantly less than the national average and therefore by using the ratio of the AT&SF and national average, the AT&SF rate of loss-of-lading accidents per shipment mile is 1.0 x -7 loss-of-lading accidents by mechanical damage/LPG tank car mile.
Reported incidents between 1965 and 1977 show that 163 cars experienced loss-of-lading from tank cars carrying LPG, propane, or butane by mechanical puncture. Tank car accidents can be categorized according to their severity as follows:
A.
Type I - This type of incident would be caused by a major rupture of the containment vessel resulting in a gross spill without ignition.
The result would be that a very large vapor cloud would be formed.
If this cloud would be ignited after an explosive fuel/air mixture had been formed, a maximum incident explosion would result. This type of incident is characterized by an unconfined fuel/air detonation.
B.
Type II - This type of incident would be caused by a separate fire or a tank puncture resulting in a fire that would overheat the punctured tank or another tank in the near vicinity. The result would be an explosive pressure rupture of the heated tank, causing nearby overpressure damage and possible shrapnel damage from the ruptured tank.
This type of incident is characterized by a tank explosion.
C.
Type III - This type of incident would result from a leak or a tank puncture resulting in a large spill with ignition occurring immediately or shortly after the incident. The liquid would burn uncontrollably in a large, intense fireball.
No tank explosion would occur since the tank puncture would be large enough to relieve the pressure. This type of incident is characterized by a large uncontrollable fireball with no explosion.
-21 D. Type IV - This type of incident would be caused by a leak, a tank puncture, a released safety valve or a burst transfer line or valve resulting in a controllable fire. The fire may be of considerable time duration and does not result in tank rupture, either due to fire control measures or protective insulation. This type of incident is characterized by a controllable fire with no explosion.
E.
Type V - This type of incident would involve a leak or a puncture, either small or large, which does not result in fire. If no source of ignition occurs, the.liquid will be dispersed in the atmosphere in a relatively short time.
This type of incident is characterized by loss of lading, but no fire.
Reviewing the information available about the incidents cited above, it is concluded that these 163 tank car accidents can be classified as follows:
Type Number Frequency of Occurrence I
3 0.0184 II 19 0.1166 III 54 0.3313 IV 4
0.0245 V
83 0.5092 In addition to the mechanical damage, exposure of LPG cars to fire can lead to explosions. There were 17 incidents involving 49 LPG tank cars during the period of 1965-1970. These accidents can be classified as follows:
Type Number Frequency of Occurrence I
0 0.0 II 39 0.796 III 2
0.041 IV 7
0.143 V
1 0.020 Although fuel-air detonations from fire-induced loss-of-lading accidents are conceivable, it is not credible that the escaping gas would fail to detonate very near the car (the heat from the fire which caused the tank car failure would also be available to initiate the detonation).
The probability of a delayed detonation for these cases is accordingly assumed to be zero.
One hundred thirteen carloads of LPG were shipped past the San Onofre site during the first 11 months of 1975.
The annual frequency of shipments is taken to be 124 LPG cars/year, based upon the opinion of the AT&SF that there will be minimal future growth in LPG haulage. The AT&SF has also stated that there are no more than two or three LPG tank cars in any one train.
-22 There are three possible hazards that could adversely affect the plant from an explosion of an LPG tank car; overpressurization, fireball, and missiles generated by tank car explosion. Detonation and resulting shock wave would occur only for Type I events.
For Type II events, the overpressure failure of the tank car results in an explosive energy release but not detonation.
A realistic analysis of the overpressurization potential to the plant site from LPG tank cars has been performed using the following inputs:
(1) The single yield of explosion has been replaced by a distribution of yields which is applied to the entire quantity of material released.
(2) The probability of a significant explosion per train mile is reduced by a factor of 2 to account for the effects of improved couplers and head shields.
The results of this realistic analysis show that the probability of exceeding 0.5 psi from an LPG explosion on AT&SF railroad is 0.45 x 10-6.
A second possible cause of plant damage is an accident resulting in a fireball.
The maximum size fireball would be the result of a Type III accident. A considerably smaller fireball could result from a Type II accident. Ignition of 30,000-pound tank car of LPG would result in a fireball with a radius of 221 feet,with a duration of 10.4 seconds. A fireball of this duration at a distance of'585 feet from the plant will not cause damage to concrete buildings.
Furthermore, safety-related equipment located outside would not be affected. The effect of the fireball would be to overheat equipment by radiation heating. Because the plant is located below a steep bluff, out of line of sight from the railroad track, it is expected that no radiation heating of equipment would occur.
The final potential hazard to the plant is the generation of self propelled (or rocketing) missiles due to Type II ruptures of the tank car. Accident reports indicate that a fragment from an LPG tank car explosion was hurled 2,640 feet while the great majority of the rocketing tank car fragments generated by exploding tank cars have a range of less than 1,000 feet.
The largest range of a car fragment from a flammable gas tank car rupture was 4,900 feet due to an ethylene oxide tank car rupture. Using the value of 4,900 feet as the missile range gives a track length of 1.93 miles for which a train generated missile could reach the plant.
The annual probability for Type II occurrence due to mechagical puncture of an LPG car per AT&SF track mile is estimated to be 4.21 x 10-In addition to the probability of an LPG tank car fire, there is the probability that a train fire will be initiated by means of other than a puncture of an LPG tank car.
WASH 1238 states that fire occurs in about 1.5% of all train accidents.
Conservatively assuming that none of these fires are caused by LPG tank punctures, the probability of a fire per train accident is 1.5 x 10-2. The accident rate of AT&SF trains is 3.70 x 10-6 accidents per train mile.
Using 62 LPG trains per year carrying 2 LPG cars the probability of a train fire on a 1-mile length of track is 3.44 x 10-6.
-23 Using an average train length of 70 cars and 10 cars involved in the accident, the annual probability of a Type II rupture due to non-LPG tank car induced fire is 6.5 x 10- 8 per track mile.
The combined annual probability for Type II rupture from all causes is 4.28 x 10-6. If it is conservatively assumed that all Type II events will produce one rocketing fragment, the total annual probabilitythat an LPG tank generated fragment strikes a safety-related structure of the unit is 2.0 x 10-8.
The effects of missile impacts on the plant are discussed in the assessment of Topic III-4.D, Site Proximity Missiles (Including Aircraft).
5.3.4 Accidents Involving Natural Gas Pipelines A 12-inch nature gas pipeline is located approximately 510 feet from the nearest safety-related plant structure. An analysis has been performed to determine the likelihood of a pipeline accident that leads to an unacceptable concentration of 4.4% natural gas at the air intake and is documented in the San Onofre Units 2 and 3 FSAR. The analysis results in a negligibly small probability (6.75 x 10- 9/year) of intersection of the 4.4% concentration with the plant intake. The analysis is also applicable to and conservtive for San Onofre Unit 1 for the following reasons:
- 1.
The terrain at Unit 1 is similar to that at Units 2 and 3. However, the bluff between the plant and the pipe line is both higher and steeper at Unit 1 than at Units 2 and 3. Therefore, flow separation from the ground is more likely for Unit 1.
- 2.
The Unit 1 control room air intake is at a lower elevation than Units 2 and 3. Therefore, the gas concentration would be lower at the intake for Unit 1 than Units 2 and 3.
- 3. The Unit 1 air intake is farther from the pipe line than Units 2 and 3.
5.3.5 Offsite Fires Offsite fires are not considered a credible hazard to the plant.
5.3.6 Accidents at Nearby Industrial and Military Facilities There are no significant manufacturing plants, chemical plants, refineries, wells, oil or gas storage facilities, or mining operations within 5 miles of the site. Hazards associated with the Camp Pendleton Marine Corps base are discussed above.
-24 5.3.7 Accidents at Sea The closest shipping lane to the site is located more than 5 miles from shore. Therefore postulated shipping accidents are not evaluated as possible design basis events.
6.0 CONCLUSION
Based upon the above information, it is concluded that:
- 1. the risk to the plant from nearby industrial facilities is negligible,
- 2. the risk to the plant from the Camp Pendleton Marine Corps Base and associated operations, except for munitions shipments, is neglibible,
- 3. the risk to the plant from the commercial shipping lines at sea is neglibible,
- 4. the risk to the plant from the three nearby gas pipe lines is neglibible,
- 5. although the probability of explosions due to accidents involving materials on both I-5 and the AT&SF railroad exceeds current criteria, the probability is low enough that explosives do not present a hazard to the health and-safety of the public, and
- 6. the probability of a toxic gas cloud being swept into the control room air vent exceeds current criteria.
The control room HVAC will be replaced and the new system will be provided with toxic gas monitors to automatically isolate the control room.
HSS:4936
AB S g F E WA, i RSAT 5-C lD EA.
MWA
/
7 44 ATCHIS' TGFRAAM D-o-~~t LAS ES PIPEIBEStOFFME
-an PETRO3ig PADDUTS fITT SCALS s,
y) 2N
"" ATURAL AS PIPE E
iea n 0 AtWAY 232185 VALVE SSAN ONOFRE NULERGEEATNGSATO ok LOCATIO OFL NEARBY INUTIL TRNPRTTO AND MILIT SAO FIN PIUSFAC11LIT15ES KTIFigur 1OW
I-5 RAILWAY
++-l+
+111+
+44H' +H11t41t-+
!!++++++++++-+1
+++--Hill++-H+4 635' 680' 740' 785' Diesel 840' Generator 80'*
953 p--
Control Buildg
-rBuilding Containment Turbine Build-Building uel Li torzge Idg Reactor Ventilation Auxiliary Equipment
.Building Bldg.
FIGURE CRITICAL BUILDINGS TO OVERPRESSURE DAMAGE
REGION II DEFINED BY THE BUILDING LAYOUT 1-5 Radius = 240' Diesel Generator Building otl Building Containment Turbine Building age Ventilation Reactor Equipment Auxiliary Building Buldn
-a2 or Pailway L/z)+
780 -
+
- 4) 78o
~"+zo 1-5~"
=
14o0)
REGION I-Explosive Overpressure is of Concern REGION II-Flammable Gas is of Concern FIGURE 4 REGION DEFINITIONS
Table 1
HAZARDOUS CARGO TRAFFIC ESTIMATES (Sheet 1 of 2)
Annual1a)
Average Maximum(b)
Cargo Type Shipments Shipment Size Shipment Size Flammable Liquids Gasoline 17.000 8,600 gal 9.000 gal Diesel oil 650 7.600 gal 7.900 gal Jet fuel 910 8,000 gal 9,000 gal Solvents (See table 2
)
Miscellaneous Petroleum Products (See table 2
)
Flammable Gasses Propane (LPG) and Butane 2,200 9,700 gal 10,100 gal LNG 420 9,200 gal 9,200 gal Hydrogen (liquid) 52 8,500 gal 33 Hydrogen (gas) 260 38 - 219 ft 75 -
219 ft3 cylinders cylinders 3
Hydrogen (gas) 24 (c) 10 -
11,400 ft3 10 -
11,400 ft cylinders cylinders 3
Acetylene 10 -
330 ft cylinders
- a.
Estimate of annual shipments based on survey at truck weighing sta tion except where shipper estimates exceeded that number.
- b.
Maximum size is based on the actual observed shipments.
- c. Not actually observed, identified through a questionnaire survey of all chemical manufacturers in the region.
Table 1
HAZARDOUS CARGO TRAFFIC ESTIMATES (Sheet 2 of 2)
Annual Average Maximum(b)
Cargo Type Shipments Shipment Size Shipment Size Compressed Gasses Carbon dioxide 260 20 tons 20 tons Argon 200 1,800 gal 8,000 gal Helium 130 12,000 lb 12,000 lb Nitrogen 2,400 40,000 lb 44,000 lb Chorine 754 7.5 tons 13 tons
.Anhydrous amonia 1 32(c) 5 tons 7.5 tons Miscellaneous Poison & Pesticides 260 8,000 lb 19,000 lb Corrosives (acid) 850 26,000 lb 50,000 lb Used Batteries 490 20,000 lb 42,000 lb Paint 1,400 18,000 lb 40,000 lb Cleaning Products 520 9,000 lb 36,000 lb Pool Chemicals 1,000 8.000 lb 45,000 lb
Table 2
INFREQUENT BAZARDOUS CARGO SHIPMENTS (Sheet 1 of 2)
Chemical Shipment Size Solvents Acetone(a) 7,600 gal Diacetone
(
2,600 gal Xylene (24 annual shipments b))
7,500 gal Shell SOL M-75 1,575 gal TOLU-SOL-6 975 gal Naptha 2,725 gal Methanol(a) 1,000 gal Ms 20H 8,000 gal Pentachlorophenol 20,000 lb Miscellaneous Petroleum Products Benzene 300 gal Motor oil 34,000 lb (typical Formaldehyde(a)
(14 annual shipments(b))
6,000 gal Weed oil 54,000 lb Crude oil 7.600 gal Hydraulic oil 3,900 gal Perchloroethylene 4,000 gal Methyl butyl ketone 1,000 Methylene chloride 3,800 gal Methyl ethyl ketone 13,000 lb Ethylene dichloride(a) 1,000 Butyl Acetate 22,000 lb Epoxy 1.000 lb Poisons and Pesticides Methyl bromide 3,500 lb Corrosives Hydrochloric acid 40,000 lb Surfuic acid 3,340 to 50,000 lb Muriatic acid 3.120 lb Nitric acid(a) 2,800 lb
- a.
Not actually observed; identified through a questionnaire survey of all chemical manufacturers in the region
- b.
Based on shippers estimate
Table 2
INFREQUENT HAZARDOUS CARGO SHIPMENTS (Sheet 2 of 2)
Chemical Shipment Size Cleaning Products Caustic soda 5,000 to 37,000 lb Chemical soap 36,000 lb Detergent (powder) 693 to 1,200 lb Soap 800 to 9,000 lb Miscellaneous Plastic resin 2,000 lb Alum sulfate (liquid) 10,700 lb Titanium dioxide 11,000 lb Nitrous oxide 1,904 ft. 3 Aerosol cans 40,000 lb Chromium oxide (powder) 2,000 lb Roofing resin 50,000 lb Potassium nitrate 1,000 lb Amonium nitrate 51,000 lb
Table 3A
SUMMARY
OF DATA SUPPLIED BY CALIFORNIA DEPARTMENT OF TRANSPORTATION Calendar Truck Miles Number Accidents per Year on 1-5 i of Accidents 106 Miles 1974 20.38 x 106 12 0.589 1975 19.88 x 106 9
0.453 1976 21.83 x 106 15 0.687 1977 22.65 x 106 12 0.530 Combined 84.14 x 106 48 0.566 Table 3B U.S. DOT INTERCITY HIGHWAY TRUCK ACCIDENT RATES PER MILE Accident Reported Accident Injury Year If Over(a)
Rate x 10-6 Rate x 10-6 Rate x 106 1971
$ 250 2.19 1.00 0.083 1972
$ 250 2.31 0.996 0.081 1973
$ 2000 0.952 1.02 0.071
- a.
Accident also reported if there was an injury or fatality.
Table 3C NATIONAL TRUCK ACCIDENT RATES Calendar Total Intercity Total Intercity Accident Rate Year Veicle Miles Accidents per 106 Miles 1968 11704 x 106 29209 2.50 1969 12461 x 106 30672 2.46 1970 12390 x 106 33203 2.68 1971 13951 x 106 30581 2.19 1972 15883 16 36682
- 2.
Combined 66389 x 106 160347 2.41
Table 4
TABULATION OF THE RELATIVE FREQUENCY WITH WHICH WINDS BLOW TOWARDS THE SAN ONOFRE SITE FROM EACH OF THE 22-1/2 DEC WIND ROSE SECTORS, AND THE LENGTH OF INTERSTATE 5 LYING WITHIN EACH SECTOR AREA Frequency of Estimated Winds Blowing Length of Toward the Interstate 5 Wind Direction Site from Included within the Sector Sector Sector Area (miles)
NW 0.0614 4.85 NNW 0.0320 0.27 N
0.0343 0.10 NNE 0.1092 0.07 NE 0.1404 0.07 ENE 0.0289 0.10 E
0.0163 0.25 ESE 0.0220 1.84 SE 0.0485 2.84 SSE 0.0698 0
S 0.0652 0
SSW 0.0607 0
SW 0.0533 0
WSW 0.0639 0
W 0.0857 0
WNW 0.1078 0
Table 5
ASSUMED BOX CAR WEIGHT DISTRIBUTION OF ORDNANCE TRANSPORTED BY RAIL PAST THE SAN ONOFRE SITE Boxcar Shipments/yr Net Explosive Weight/Boxcar (lb) 1 37,000 25,500 10 25,000 15 20,000 25 15,000 15 13,000 10 10,000 2
6,000 1
3,000 400 84 boxcars/yr Table 6
ASSUMED SHIPMENT WEIGHT DISTRIBUTION OF ORDNANCE TRANSPORTED BY RAIL PAST THE SAN ONOFRE SITE Munitions Train thiments/Yr Total Net Explosive Weight/Shipment W (lbs) 1 62,500 2
50,000 5
40,000 7
30,000 1
28,000 12 26,000 7
20,000 1
-16,000 4
.12,000 9,000
.1 3,400 42 shipments/yr
TABLE 7 HIGHWAY MILITARY EXPLOSIVE SHIPMENT SIZE DISTRIBUTION Net Explosive Number 7 Length of 1-5 of Weight (1bs)
Shipments Interest (miles) 0-3400 559 0.783 3400-4400 6
0.820 4400-5400 6
0.886 5400-6400 5
0.942 6400-7400 5
0.993 7400-8400 4
1.038 8400-9400 3
1.080 9400-10400 3
1.118 10400-11400 3
1.154 594*
The actual expected number of shipments per year is 592. This sum is greater because fractional shipments calculated from the size distribution were rounded up to the next higher number.
TABLE 8 RESISTANCE TO OVERPRESSURIZATION Building psi Control 0.671 Reactor Auxiliary 0.503 Fuel Storage 1.165 Turbine 0.856 Ventilation Equipment 1.249 Diesel Generator 4.476 Sphere Enclosure 10.132 TABLE 9 DISTRIBUTION OF EXPLOSION YIELDS Range of No. of Yields*
Incidents Typical Yield E*
Probability 10-12 2
10.0 0.14 6-10 4
7.5 0.29 2-6 5
5.0 0.36 2
13 0.25 0.21
- Energy Equivalence (%) of Contents of Single Container