Forwards Assessment of SEP Topic II-1.C, Potential Hazards or Changes in Potential Hazards Due to Transportation, Institutional,Industrial & Military Facilities. Complete Evaluation Will Be Submitted by 820201
ML13317A727
Person / Time
Site: San Onofre Southern California Edison icon.png
Issue date: 11/12/1981
From: Krieger R
Southern California Edison Co
To: Crutchfield D
Office of Nuclear Reactor Regulation
References
TASK-02-01.C, TASK-2-1.C, TASK-RR NUDOCS 8111180400
Download: ML13317A727 (31)


Text

Southern California Edison Company P.O. BOX 800 2244 WALNUT GROVE AVENUE ROSEMEAD, CALIFORNIA 91770 November 12, 1981 Director, Office of Nuclear Reactor Regulation Attention: D. M. Crutchfield, Chief Operating Reactors Branch No. 5 Division of Licensing U. S. Nuclear Regulatory Commission Washington, D.C.

20555 NOVI 7 1981 0,~WUOAR ItMUATOM COMMISM"*

Gentlemen:

Subject:

Docket No. 50-206 Systematic Evaluation Program I

Topic II-1.C Potential Hazards or Changes in Potential Hazards Due to Transportation, Institutional Industrial, and Military Facilities San Onofre Nuclear Generating Station Unit 1 Enclosed is an assessment report on the subject topic.

It is concluded that only explosions due to accidents on Interstate 5 and the Atchison, Topeka and Santa Fe Railroad present a potential hazard to the plant.

The evaluation of such accidents are not complete, as indicated in Section 5.3, Evaluation of Potential Accidents and Section 6.0, Conclusions.

The completed evaluation and a revised assessment report will be submitted by approximately February 1, 1982.

If you have any questions, please let me know.

Very truly yours, R. W. Krieger Supervising Engineer, San Onofre Unit 1 Licensing Enclosure 1111906400 911\\112 PDR ADOCK 050002061 PRR

San Onofre Nuclear Generating Station, Unit 1 SEP Safety Assessment Report Revision 0 Topic II-1.C - Potential Hazards or Changes in Potential Hazards Due to Transportation, Institutional, Industrial, and Military Facilities

1.0 INTRODUCTION

The objective of this topic is to assure that San Onofre Unit 1 is adequately protected and can be operated with an acceptable degree of safety with regard to potential accidents which may occur as the result of activities at nearby industrial, transportation, and military facilities.

2.0 CRITERIA Standard Review Plan Section 2.2.1-2.2.2 states that all identified facilities and activities within 5 miles of the plant should be reviewed. Facilities and activities at greater distances should be considered if they otherwise have the potential for affecting safety related features.

Standard Review Plan 2.2.3 defines design basis events external to the station as those accidents for which a realistic estimate of the annual probability of exceeding 10CFR100 exposure guidelines is in excess of approximately 10-7 or for which a conservative estimate of this probability is in excess of approxi mately 10-6.

3.0 RELATED SAFETY TOPICS AND INTERFACES A. Topic III-4.0, Site Proximity Missiles (Including Aircraft), October 23, 1981.

B. SCE submittals on NUREG-0737 Item III.D.3.4 - Control Room Habitability, June 13, and June 20, 1981.

C.

San Onofre Nuclear Generating Station, Units 2 and 3 FSAR.

4.0 REVIEW GUIDELINES Standard Review Plans 2.2.1, 2.2.2 and 2.2.3 were used as review guidelines..

5.0 EVALUATION The data for hazardous materials, frequency of shipments of hazardous materials and accident rates was extracted from the San Onofre Units 2 and 3 FSAR and are reproduced here for completeness. These data were analyzed for their effect on Unit 1, taking into account differences in plant design criteria and location with respect to transportation routes.

-2 5.1 Nearby Industrial, Transportation and Military Facilities Nearby industrial, transportation and military facilities are illustrated in Figure 1. Items illustrated on Figure 1 are described below.

There exists, within 5 miles of the plant:

1. a quarry
2. U.S. Marine Corps Base, Camp Pendleton
3. three transportation routes
4. three pipe lines 5.1.1 Quarrying Operations The only facility involving the processing of products and the employment of personnel within 5 miles of the plant is Camp Pendleton quarry located 4 miles north of the plant site as shown in Figure 1. Quarry operations are to crush and sort aggregate material for maintenance and construction.

Explosives are not used.

5.1.2 Military Operations Fuel storage areas include the following gasoline facilities at Camp Pendleton Special Services gas stations:

(1) The nearest is located 0.1 mile east of the San Onofre gate to Camp Pendleton on Basilone Road, 1.5 miles northwest of the plant; (2) Camp San Onofre on Basilone Road; (3) On the corner of Cristianitos and San Mateo Roads near Camp San Mateo; and (4) At Camp San Onofre at the intersection of Basilone and San Mateo Roads.

Ammunition is stored by the U.S. Marine Corps in the Las Pulgas area of Camp Pendleton approximately 9 miles from San Onofre Unit 1. The material is Class 7 explosive and is stored in underground bunkers. This facility is separated from the plant site by the San Onofre mountains.

Except for amphibious landings, most Marine Corps activities are conducted inland from Camp San Onofre and the range of coastal hills that parallels the coast near the plant.

With regard to amphibious landings, San Onofre is located in a separate, designated sector of the beach, and discussions with the Marine Corps indicated no landings will be made in this sector.

No firing of live ammunition is permitted throughout a strip along the seacoast, which is approximately 2 miles wide at its narrowest point.

This strip extends from the northern reservation boundary to approximately 10 miles south of Unit 1.

0 Where firing or weapon impact is permitted, training is conducted under very close supervision since populated areas, the highway, railroad, and infantry maneuvering areas are located along the seacoast of the reservation to a distance of approximately 5 miles inland.

Firing ranges are shown on U.S. Geological Survey (1968), 7.5 minute quadrangle sheets:

San Clemente, Margarita Peak, San Onofre Bluffs, and Las Pulgas Canyon.

The nearest firing range (approximately 3 miles away) is a known-distance range over which small arms are used to gain sighting data.

The maximum range of firing is about 100 feet, with rounds impacting into a steep hillside. All other firing ranges are generally inland from Camp San Onofre and located such that the maximum range of the weapons would not permit an impact closer than approximately 2 miles from the plant, even assuming firing was directed toward the plant rather than into the designated sectors.

Firing is also directed into hillsides or valleys to avoid any danger of projectile skipping.

Aircraft practice firing and artillery bombardment is controlled at all times and is directed into impact areas located further than 5 miles inland.

Aircraft approaches and pullouts do not pass near the plant.

There are two bombing and strafing ranges located approximately 6 miles from the plant. Various types of aircraft delivered ordnance of up to 500-pound bombs are employed on these ranges.

No bombardment from the sea is ever permitted, and the shore landing maneuvers do not involve the use of live ammunition.

Thus, Marine Corps activities which could otherwise conceivably constitute a hazard to the plant are all conducted well away from the coastline and do not constitute a credible hazard to plant safety.

The Marine Corps indicated that there are no missile sites on Camp Pendleton and none within at least 10 miles of Unit 1.

5.1.3 Transportation Routes The three transportation routes within 5 miles of the plant are described below:

(1) The old Highway 101, immediately east of the site, does not carry through traffic, but is the entrance road to the south end of San Onofre State Beach.

(2)

Interstate 5 (1-5) is east of the site and is the only public coastal vehicular link between Orange County and San Diego County.

The 1974-75 estimated average daily traffic was 63,570 vehicles, with an estimated passenger population of 130,240. The years 1970-1974 averaged 3,672 trucks per day adjacent to the plant.

This figure includes vehicles over 6,000 pounds, with two or more axles, but does not include buses, vans, campers, and pickups.

S

-4 (3)

The Atchison, Topeka and Santa Fe Railroad (AT&SF) right-of-way is east of the site between Highway 101 and 1-5. This is an active line with Amtrack passenger service and cargo service.

Other transportation routes near the plant, but farther than 5 miles are:

1. Commercial vessel shipping lanes are southwest of the plant in the Pacific Ocean.
2. Aircraft routes near the plant are described in the assessment of Topic III-4.D, Site Proximity Missiles (including aircraft).

5.1.4 Oil and Gas Pipelines There are three pipelines in the vicinity of the plant:

(1) San Diego Gas & Electric inch natural gas pipeline adjacent to.

Basilone Road. The characteristics of this pipeline are:

A.

Size: 6-inch diameter, 12,058 feet long, 4-inch diameter, 3,634 feet long B.

Age:

1968 C. Operating pressure:

200 psi D. Depth of burial:

36 inches average E. Location:

Adjacent to Basilone Road F. Valves: Plug type, manual G. Material:

Natural Gas H.

Storage: The pipeline is not used for gas storage I.

Future plans:

No plans to expand J. Leaks:

None K. Flow direction:

Northeast L. Release event:

Gas would be lost at rate of 875 x 106 ft3/h for about 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. Release would be noticed prior to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> because of drop at U.S. Marine Corps control house, or by regular Marine Patrols.

(2) Southern California Gas Co. -

12-inch natural gas pipeline adjacent to 1-5.

The characteristics of this pipeline are:

A.

Size:

12-inch diameter

0 0

-5 B.

Age:

It was constructed in several phases. The section from 0.4 miles northwest to 1.6 miles northwest of the plant was built in 1932. The section from 1.6 to 1.9 miles northwest was constructed in 1960. The section from 1.9 to 2.8 miles northwest was built in 1966.

The section from 2.8 to 5.0 miles northwest was built in 1929. And the section from 0.4 miles northwest to 5.0 miles southeast of the plant was built in 1966. About 0.1 miles of pipeline 3.3 miles north of the plant was replaced in 1963.

C.

Operating pressure: 400 psig (maximum allowable).

D. Depth of burial:

30 inches average E. Location:

See Figure 1. The pipeline is located approximately 673 feet northeasterly from the centerline of Unit 1 containment.

The pipeline is located within the right of way of U.S. Highway 101, approximately 5 feet southwesterly of the northeast edge of the right of way.

F. Valves:

There are three plug valves located 1.3 and 2.8 miles northwest of the plant and 2.1 miles southeast (see Figure 1).

G. Material: Natural gas (91% methane, 5% ethane, 4%

miscellaneous).

H.

Storage:

The pipeline is not used for gas storage.

I. Future plans:

There are no plans for expansion or to use the pipeline for a product other than natural gas.

J. Leaks:

There have been two leaks within 5 miles of the plant.

One, in 1967, was approximately 3.5 miles north of the plant, a small corrosion leak with no fire or explosion. The other, in 1963, was approximately 3.3 miles north of the plant, a break in the pipeline due to exterior stress, with no fire or explosion. Repair was made by replacing 449 feet of pipe.

(3) San Diego Pipeline Company inch refined petroleum products pipeline 2 to 5 miles northeast of the plant in Camp Pendleton.

The characteristics of this pipeline are:

A.

Size:

10-inch diameter B.

Age: Constructed in 1962 C. Operating pressure: 1,440 psi (maximum)

D.

Depth of burial: 30-inches average E. Location:

See Figure 1 F.

Valves: Manually operated gate valve at milepost 58.24 (See Figure 1)

-6 G. Material:- Gasoline, diesel fuel, turbine fuel, navy jet fuel (JP-5)

H.

Storage: The pipeline is not used for gas storage I.

Future plans:

No immediate plans to expand. Future demand could necessitate construction of a parallel pipeline.

J.

Leaks:

None within 5 miles K.

Flow direction:

South L.

Release event:

Product initially released at flowrate. Within 20 seconds the pressure drop would be detected and the pipeline shut down hy automatic warning devices.

The nearest main line valves upstream and downstream of the break would be closed.

5.2 Description of Products and Materials 5.2.1 Atchison, Topeka and Santa Fe Railroad (AT&SF) 5.2.1.1 Toxic Chemicals.

The AT&SF has indicated that none of the hazardous chemicals listed in U.S.N.R.C. Regulatory Guide 1.78 (June 1974) Table C-2 were shipped by the plant during the first 11 months of 1975.

5.2.1.2 Gaseous and Liguid Fuels. The AT&SF has indicated that 113 carloads of liquified petroleum gas (LPG) were shipped by the plant during a representative period of the first 11 months of 1975. These noninsulated steel fusion welded tank cars have a water capacity of 33,500 gallons and weigh approximately 70 tons. These carloads of LPG arrive more frequently during the winter months with 12 to 18 cars in the heaviest months.

There are no more than 2 or 3 cars in any one train.

AT&SF forecasted the same number of shipments for 1976 as in 1975, and did not anticipate an increase in these shipments in the future.

5.2.1.3 Explosives.

Information from the Department of the Army indicated there were eight rail shipments of military explosives past the plant during the year June 1977 through May 1978. The maximum net explosive weight per shipment was 20,548 pounds.

5.2.2 Interstate 5 (1-5)

A truck. traffic survey was conducted on I-5 in order to gather data for the San Onofre Units 2 and 3 FSAR.

-7 The number of shipments of hazardous cargo shipped on 1-5 adjacent to the plant is given in the second column of Table 1.

Several of the cargo categories used for presenting the survey results in Table 1 contain a number of different materials.

Table 2 lists the various cargoes contained within these categories.

The expected number of military explosive shipments past the plant on 1-5 were estimated to be 1,411 for the year June 1978 through May 1979.

The Navy stated that changes in shipment routes and requirements for 911 of the shipments would occur after 1980 so that there will be less than 10% of the 911 shipments.

Assuming that the remaining shipments are unaffected, the projected 1-5 military explosive shipment frequency is 592.

The maximum net explosive weight per 1-5 shipment is 11,400 lbs.

5.2.3 Waterways The principal uses of the coastal waters are pleasure boating, industrial cooling, military exercises, and sport and commercial fishing. Commercial vessel traffic lanes lie at distances greater than 5 miles from the plant.

Military exercises are discussed elsewhere in this report.

5.2.4 Projections of Industrial Growth There are no plans for expansion of existing facilities or new industrial development within 5 miles of the plant. Existing pipelines and waterways are also not scheduled for expansion.

San Diego County, in conjunction with the CALTRANS, has forecast an increase of 45% in truck traffic on I-5 in the vicinity of the plant. Hazardous cargo shipments are expected'to decrease on I-5 as a percent of total shipments because increased industrialization in San Diego will provide these products locally. Fuel shipments (gasoline, LPG, LNG, etc.) may decrease in absolute number because of the development of these processing facilities in San Diego and the increasing cost to ship fuels by truck.

Explosive shipments by the U.S. Navy will remain constant to the U.S. Marine Corp Camp Pendleton and will decrease for other shipments.

Industrial gas and chemical shipments will vary as a function of future industrial process requirements, availability from local sources, products manufactured and shipment costs.

The largest increase in truck activity can be expected in food and other consumer products.

5.3 EVALUATION OF POTENTIAL ACCIDENTS The accidents considered in this section include:

1. explosions of hazardous materials,
2.

delayed ignition of flammable vapor clouds,

3. liquid spills,
4.

release of toxic vapors,

5. off-site brush fires, and
6. accidents at sea.

-8 5.3.1 Determination of Design Basis Events Available statistical data were analyzed to determine the probability of occurrence of potential accidents based upon their historical frequency of occurrence. In those cases where data relating to particular classes of accidents were not available, conservative assumptions were used to evaluate order-of-magnitude accident probabilities. A description of data sources, assumptions, and computational methods is presented in the San Onofre Units 2 and 3 FSAR. The containment can withstand (later) psid and maintain integrity.

The other safety-related buildings can withstand (later) psid.

In the following analysis, the peak positive normal reflected explosion overpressure of (later) psid was used as design basis for evaluating probabilities.

5.3.2 Transportation Accidents on 1-5 Hazardous materials transported past San Onofre on 1-5 are discussed above and include military ordnance, flammable and explosive chemicals, toxic chemicals, and pressurized noncombustible gasses.

5.3.2.1 Accident Rates for Motor Carriers of Hazardous Cargo The probability of transportation accidents on 1-5 involving hazardous materials was estimated from statistical data on the frequency of truck accidents on I-5 within 5 miles of the San Onofre plant site and nationwide accident rates.

Accident rates for all trucks(a), tank trucks and trucks with explosive cargo were determined for a 10 mile segment of 1-5 extending approximately equidistant in both directions from the San Onofre site. From the data in Table 3A, the observed truck accident rate is 0.566 x 10-6 accidents per truck mile. Truck traffic rates are based on weighted sample counting and extrapolated to annual counts. Northbound and southbound data are combined.

Traffic accidents are reported to the state if property damage is $200.00 or greater or there has been personal injury or death.

In this analysis, I-5 accident rates are combined with U.S. Department of Transportation (U.S. DOT) data where the property damage threshold for reporting accidents has been increased from $250.00 to $2,000.00. To correct for the data base inequities, U.S. DOT data before and after the reporting threshold change were used to generate a correction factor. Table 3B presents data covering the.transition period.

1973 accident rate 0.952 x 10-6 Correction factor 1971-72 accident rate

-6

-6 (2.19 x 10

+ 2.31 x 10" )/2

= 0.423

a.

Truck is defined as any vehicle 5,000 pounds or more excluding pickup trucks, vans and buses.

-9 This factor is applied to the I-5 accident rates based on the assumption that California accident rates would be reduced by the same proportion as that observed on the national level.

The fact that the California threshold is

$200.00 vs. $250.00 for the U.S. DOT would make the correction factor a conservative assumption.

The I-5 accident rate for all trucks corrected to the $2,000.00, death or injury reporting criteria.

0.423 x 0.566 x 10-6 = 0.239 x 10-6 accidents/truck-mile The bulk of hazardous commodities carried on 1-5 past the plant are in tank trucks. Nationwide truck accident statistics show that loaded tank trucks have a lower accident rate than all types of trucks combined (1.33 x 10-6 vs. 2.41 x 10-6 for years 1968 through 1972 with the same reporting criteria). Therefore, the 1-5 accident rate for all types of trucks (0.239 x 10-6) is corrected to loaded tank-truck accident rate by assuming the same relative improvement exists in California (1-5) as observed nationwide.

Loaded tank truck = 0.239 x 106 1.33 x 10-6 = 0.132 x 10-6 accidents/

accident rate on 1-5 2.41 x 106 mile The accident rate for trucks carrying explosives was determined in a similar manner. The nationwide accident rate for trucks carrying explosives is 0.96 x 106 accidents/mile.

Therefore, the accident rate for trucks carrying explosives on I-5 is:

2 239 x 10-67 Explosive truck = 2.39 6 x 0.96 x 1o 6 = 0.95 x 10- accidents/

accident rate 2.41 x 10-mile 5.3.2.2 Explosions Due to Transportation Accidents on 1-5 There are three categories of materials transported on 1-5 which have a potential for creating a hazard to San Onofre Unit 1 in the event of an accident on the highway. These materials are military ordinance, flammable liquids and flammable gasses (shipped as either compressed liquid or compressed gas).

5.3.2.2.1 Military Ordinance The average number and size of the explosive shipments past the San Onofre plant site were provided by the U.S. Navy. The average shipment size is 700 pounds equivalent TNT with the maximum single shipment being 5,000 pounds of Class 7 explosive (1 pound of Class 7 explosive is equivalent to 1 pound of TNT).

Present analysis conservatively assumes that there were 10 annual shipments of 5,000 pounds of equivalent TNT explosives.

The minimum distance from 1-5 is approximately 620 feet to the nearest safety-related structure (diesel generator building).

The peak positive normal reflected overpressure at the plant site produced by the surface detonation of 700 pounds of TNT at this distance is approximately (later) psi.

The surface detonation of 5,000 lbs of TNT at this distance will produce an overpressure of approximately (later) psi.

The probability that an accident would result in an explosion was determined for commercial shipments of

-10 explosives. During the 4-year period of 1972-1975, there were 70 accidents involving munitions trucks (nationwide) reported, of which 3 involved explosions. From this information, it is estimated that the conditional probability of an explosion due to an accident is 3/70 or 0.043.

The minimum shipment size of explosives which will cause a (later) psi over pressure is approximately (later) equivalent pounds of TNT. Based on a distribution of 216 shipments with an average weight of 700 pounds and a maximum weight of 5,000 pounds, it is conservative to assume that there are 10 annual shipments of 5,000 pounds. Based on the assumed 10 annual shipments of 5,000 pounds equivalent TNT with a probability of a truck accident of 0.95 x 10-7 per truck mile, and 0.043 probability of an explosion, the annual probability of ordnance detonations on a (later) mile length of 1-5 causing an overpressurization of (later) psi at the plant site is (later).

All other explosive shipments past the plant are Class B explosives which, in general, function by rapid combustion rather than detonation and therefore do not pose an explosion hazard to the plant.

5.3.2.2.2 Flammable Liquids Flammable liquids are shipped at ambient temperature and pressure and would not pose an explosion hazard unless vaporized.

To calculate the probability of an explosion due to a truck accident, it is necessary to determine the conditional probabilities of a spill and an explosion occurring due to a spill.

The bulk of the flammable materials move by tank truck.

The probability of a tank truck accident per mile of I-5 is 1.32 x 10-7.

The probability of a spill is estimated to be 0.02 since fewer than 2% of the accidents result in a spill.

The probability of an explosion resulting from an in-transit tank truck spill of flammable liquid is 0.0113, as determined from the accident reports from DOT covering the period from July, 1973, to

December, 1975, and included a total of 442 spills of flammable liquids from tank trucks, of which 5 resulted in explosions. It was conservatively assumed that all of these explosions were fuel-air detonations which yield the maximum possible overpressure. An in-transit explosion of a tank truck carrying a flammable liquid on I-5 is calculated to be 2.98 x 10-11 tank truck explosions/tank truck mile.

The effect of the explosion for the flammable liquids listed in Table 1 is dependent on the chemical and physical properties of the materials. These chemicals are liquids at ambient temperature and pressure, and, in general, they have low vapor pressures and high vapor densities. Thus, the vapor formed tends to hug the ground, and only a thin vapor interface exists between the air and the liquid. Therefore, spilled liquids are unlikely to produce an explosion with a strong blast wave but will produce a simple flash-over flame igniting the remainder of the fuel.

To be extremely conservative, it is assumed that 10% of the liquid is vaporized to form an explosive cloud for all flammable liquids, except for formaldehyde where 37% is used to correspond to the amount of formaldehyde in solution. It is assumed that the explosion occurs at the point of the accident. Delayed denotations of vapor clouds are discussed below.

0 0

-11 The enthalpy of combustion of a stoichiometric fuel-air mixture for each of the flammable liquids is equated to the enthalpy of detonation of TNT (500 K cal/1b).

In accordance with empirical observations of blast damage in unconfined vapor cloud explosions, it is assumed that the maximum fraction of the fuel in the combustion range or the maximum yield of the TNT equivalent weight is calculated based upon a probability distribution. The given value's of the yield are applied to the total quantity of material released, rather than the flash fraction.

Since the average shipment size is almost equal to the maximum size, the maximum shipment size for each chemical listed in Table 1 was used to calculate the peak positive normal reflected overpressure at the plant site for a surface detonation.

Only (later) are capable of causing a peak overpressure which exceed the design overpressure.

5.3.2.2.3 Flammable Gasses The flammable gasses listed in Table 1 are shipped by the plant site as compressed liquids and compressed gas. Propane (LPG), butane, liquified natural gas (LNG), and hydrogen are shipped in tank trucks as compressed liquids, and hydrogen and acteylene are shipped as compressed gasses.

The compressed liquids are shipped by tank trucks, and the conditional probability of a spill is 2.64 x 10-9 spills/tank truck mile (1.32 x 10- 7 x 0.02).

The probability of a liquified compressed gas-air detonation was determined from the Department of Transportation (DOT),

Office of Hazardous Materials, Incident Reports for July 1973, to December 1975, and the University of Southern California study of DOT propane tank truck accidents from January 1970, through August 1972. In each of these reports, there was 1 explosion out of 17 spills of.the cargo. Using 0.06 as the conditional probability of an explosion per spill, the total probability for a tank truck carrying compressed flammable liquified gas is 1.58 x 10-10 explosions/tank truck mile of 1-5.

The magnitude of explosions is dependent on the chemical and physical properties of the material.

For LPG, LNG, and liquified hydrogen, the amount of flashing of liquid to vapor was calculated from the enthalpy differences at the cryogenic shipping condition and at atmospheric pressure. The enthalpy of combustion of a stoichiometric fuel-air mixture for each of the flammable gasses was equated to the enthalpy of detonation of TNT. For the unconfined vapor cloud explosions of LPG and LNG it was assumed that the maximum yield of the TNT equivalent weight was based upon the probability distribution discussed above. For hydrogen and acetylene, it was conservatively assumed that the maximum yield was 100% of the TNT equivalent weight.

The shipment weights used were the maximum weights given in Table 1 for LPG, LNG and liquid hydrogen. At the minimum distance of (later) feet, the fuel-air detonation of LPG will produce an overpressure of (later) psi and liquid hydrogen will produce an overpressure of (later) psi.

LNG will produce a (later) psi overpressure.

Hydrogen gas is shipped in 219 cubic feet cylinders with a maximum shipment size of 75 cylinders reported. Even in the case of assuming that all 75 cylinders rupture to form a vapor cloud, the fuel air detonation of this cloud

-12 will create an overpressure of (later) psi.

Hydrogen gas is also shipped in a tank trailer consisting of 10 cylinders having a total capacity of 640 pounds or 114,000 standard cubic feet.

Instantaneous rupture of all 10 cylinders could produce a vapor cloud which, if detonated, could produce a 6.0 lb/in. 2 overpressure. Similarly the shipment of 10-198 pound, (gross weight) acetylene cylinders containing 330 cubic feet will cause an overpressure of (later) psi if all cylinders rupture to produce a vapor cloud.

This analysis is extremely conservative since it assumed total release of all hydrogen and acetylene gas from all cylinders in an accident.

Another possible cause of damage to the plant is a fireball generated by the explosion of tank trucks on 1-5. Ignition of a 10,100 gallon LPG tank consuming the entire contents would result in a fireball with a radius of 156 feet with a duration of 7.4 seconds.

Since the outer dimension of the fireball is 460 feet away from the nearest safety-related building, a fireball caused by the explosion of an LPG tank truck will not be a hazard to the plant.

The delayed detonation of vapor clouds that result from spills of compressed liquids and gasses on I-5 are a possible hazard to the plant.

No flammable liquids except formaldehyde (which is shipped as a gas in solution) are capable of forming a vapor cloud of significant proportions that could drift toward the plant. This is due to the fact that the flammable liquids form a thin vapor level between the air and liquid.

Flammable gasses in liquid or gaseous state can form a vapor cloud which could drift toward the plant. To analyze this effect the puff release of the contents of these cargoes in the amount stated in the previous section was assumed to occur on 1-5 anywhere within 5 miles of the plant.

The potential consequences of an explosion involving these releases is dependent on the location of the release relative to the direction of the prevailing wind.

Table 4 gives the relative frequency with which the wind blows towards the plant from each of sixteen 22 1/20 wind rose sectors. The unrestricted vapor cloud is assumed to move downward from the release point under very stable atmospheric conditions (Pasquill Stability G).

The effective length of 1-5 for which the detonation of a drifting puff release of the tank truck cargo would cause an overpressure of greater than (later) psi at the plant site was determined. The drifting cloud's capability ofexploding was based on its concentration being above the lower explosive limit concentration for the material being released. For conservatism it was assumed that vapor release within the distance calculated to produce overpressurization at the plant from an explosion at the accident site would not drift away from the plant.

Using the value of 400 feet for the length of the plant parallel to 1-5, the effective length of 1-5 that could produce an overpressure greater than (later) psi due to a drifting unconfined vapor cloud explosion are for LPG (later), LNG (later), Hydrogen-liquid (later) and formaldehyde (later).

The maximum explosive yields for LPG and LGN were 10% of the TNT equivalent weights and assumed to be 100% for hydrogen and formaldehyde.

These values were multiplied by the probability of an explosion and number of annual

-132 shipments given in Table 1. The annual probabilities of a plant site overpressurization explosion due to a drifting cloud from an 1-5 tank truck spill are for LPG (later), LNG (later), hydrogen-liquid (later) and formaldehyde (later).

The annual probability of an overpressurization from a release of LPG was further analyzed.

This realistic analysis is an extension of the previous analysis using the following modified inputs:

(1) The peak reflected overpressures required to cause release which could lead to consequences in excess of 10CFR100 guidelines is (later).

(2) The single value of possible accident locations on 1-5 has been replaced by a distribution across the southbound lanes and shoulder.

(3) Sixty percent of the LPG shipments on 1-5 are in tandem trailers with a maximum of 5,000 gallons available for involvement in a vapor cloud detonation.

(4) The single yield of explosion has been replaced by a distribution of yields which is applied to the entire quantity of material released.

(5) The probability of a significant explosion per train mile is reduced by a factor of two to account for the effects of improved couplers and head shields.

A review of LPG shipment data on 1-5 shows that most shipments are southbound or on the side of the highway nearest the plant. The possible accident locations used in the realistic analysis were derived from actual truck accident locations along the ten-mile stretch of 1-5 near the plant.

The resulting locations and the assigned relative probabilities are:

o West edge of right-of-way 0.21 o

West edge of roadway 0.37 o

Center of roadway 0.26 o

East edge of roadway 0.16 Finally, a probability distribution for the yield of an explosion was derived. The results of this realistic analysis show that the probability of exceeding the 10CFR100 guidelines are as follows:

(1) Due to LPG on 1-5 (later)/year (2) Due to LPG on ATSF (later)/year (3) Total (later)/year The delayed detonation of hydrogen and acetylene was analyzed due to ruptures of gas cylinders containing these substances.

There are no results available

-14 on the probability of cylinder failure in an accident. To obtain a probability of this type of failure, it is possible to relate the probability of steel drum failure to the probability of gas cylinder failure.

The probability of breaching a cylinder or drum is assumed to be inversely proportional to the cube of the wall thickness. The wall thickness for the 219 cubic ft. hydrogen gas cylinders is a nominal 0.24 inches, for the 10 large cylinders it is a minimum of 0.375 inches, and for the acetylene cylinders it is a nominal 0.15 inches. The wall thickness for the steel drum is a nominal 0.0478 inches. Using the conservative value of 0.125 for the failure probability of steel drums, the probabilities of rupturing each type of cylinders per accident is 1.0 x 10-3 (219 cubic f. hydrogen cylinders),

2.6 x 10-4 (large hydrogen cylinders) and 4.05 x 10- (acetylene cylinders).

The probabilities of failing one or more cylinders in an accident are 0.07 (shipment size of 75 hydrogen cylinders of 219 cubic ft.), 0.0026 (shipment size of 10 large hydrogen cylinders) and 0.04 (shipment size of 10 acetylene cylinders).

For conservatism it is assumed that the entire cargo is released. This is extremely conservative since the probability of failing more than 3 cylinders per accident is essentially zero. Using the value of 400 feet for the plant, the effective lengths of 1-5 capable of causing an overpressure of (later) or greater are (later) miles (later) ft. hydrogen cylinders), (later) miles (large hydrogen cylinders) and (later) miles (acetylene). The annual probabilities of a plant overpressure of (later) psi or greater due to the detonation of a drifting cloud from an I-5 release of flammable gas are (later) (for 260 shipments of 219 cubic ft. cylinders),

(later) (for 24 shipments of large hydrogen cylinders) and (later) (for 52 shipments of acetylene).

The analysis for delayed detonation of vapor clouds is conservative since it is very probable that escaping vapors will find an ignition source near the accident site. Car and truck traffic along I-5 would provide ample heat sources from hot manifolds and mufflers. Data for 81 vapor releases from tank cars indicated that 58% were ignited within 50 feet of the accident and all leaks found sources of ignition within 300 feet. In addition, the maximum size was used with the assumption that the entire contents of the tank truck was capable of forming the vapor cloud. The effect of bouyancy was neglected in the analysis.

5.3.2.2.3 Release of Toxic Gasses Due to Transportation Accidents on I-5 Toxic chemicals are transported along I-5 on a regular basis. Tables 1 and 2 list the observed materials transported past the site and their estimated frequency of shipment.

The following five substances have been identified as a result of the probabilistic risk assessment as having probabilities near to or greater than 10- 7/yrs:

-15 (1) Chlorine 1 x 10- 6/yr (2) Butane 1 x 10- 6/yr (3) Gasoline 1 x 10- 6/yr (4) ammonia 9 x 10- 7/yr (5) Propane' 2.x 10- 6/yr As a result of the control room habiability review performed on Unit 1 as required by NUREG-0737 Item III.D.3.4-Control Room Habitability, the Unit 1 control room HVAC will be replaced. The new HVAC system will include an automatic isolation feature sensitive to the above chemicals.

5.3.3 Transportation Accidents on the Atchison, Topeka, and Santa Fe Railroad Hazardous materials transported past San Onofre on the AT&SF railroad track are military ordnance and LPG.

The AT&SF Railway Company does not anticipate any other hazardous materials being shipped through the San Onofre area.

5.3.3.1 Accident Rates for AT&SF.

Railroad accident rates are determined from the statistical data published by the Office of Safety, Federal Railroad Administration, U.S.

DOT.

Data was obtained from the Accident Bulletins, Summary and Analysis of Accidents on Railroads in the United States for the calendar years of 1968-1974. During this period there were 59,894 accidents nationwide with a total train mileage of over 5.8 billion miles.. The average accident rate is 10.3 x 10-6 accidents per train mile. During this same period the AT&SF had 2,077 accidents in 379,391,000 train miles for an average of 5.29 x 10-6 accidents per train mile.

Using these accident rates for the stretch of AT&SF past the plant site are conservative since these rates include all train accidents including yard switching operations. Yard switching operations generally account for over 75% of the collision accidents that occur on railroads.

5.3.3.2 Explosions Due to Accidents on the AT&SF.

5.3.3.2.1 Military Ordnance.

The AT&SF report hauling 74 carloads of ammunition past the San Onofre site during the first 11 months of 1975.

Shipments occur with a frequency of about 7 carloads per month. The U.S. Navy states that the 1975 shipments had the following distribution by net explosive weight (a):

1 boxcar/yr at 37,000 pounds net explosive weight 1 boxcar/yr at 25,500 pounds net explosive weight 82 boxcars/yr at less than 25,500 pounds but more than 400 lbs. averaging 13,000 pounds.

a.

Une pound of net explosive weight equals one pound of TNT

-16 To predict the overpressures that might be produced by the explosion of ordnance boxcars on the AT&SF track, assumptions are required about the weight of explosive in the 82 boxcars shipments where the value was not specified, and also about the number of ordnance boxcars which are carried in a single train.

Table 5 gives the assumed frequency distribution of net explosive weight per boxcar vs. the number of boxcars/yr hauling this quantity of explosive. The mean net weight for the 82 boxcar loads of 25,000 pounds and less is approximately 13,000 pounds, which agrees well with the mean net explosive weight reported for these shipments by the U.S. Navy.

It is assumed that all ordnance train shipments involve two loaded boxcars.

For conservatism, the boxcar net explosive weights given in Table 5 were combined such as to maximize the weight of explosive per train shipment. It is further conservatively assumed that if either of the boxcars in a shipment detonates, the second will also detonate. The total weight and number of each size shipment is given in Table 6.

No data were found on the conditional probability of a munitions car explosion, given a munitions car accident. However a report by the IIT Research Institute gives a compilation of data from which the probability of an explosion in a munitions train accident can be estimated.

It has been estimated that there were 1.98 x 107 explosive train-miles per year based on statistics for a 57 year period from 1917 to 1973. The annual average train miles during this same period was 1.36 x 109.

During this 57-year period there were 35 explosions involving in-transit shipments of explosives. The national annual probability of an explosion due to a train accident involving explosives is 3.1 x 10-8 explosions per explosive train mile. The accident rate for the AT&SF is significantly less than the national average and therefore using the ratio of AT&SF accident rate to the national railroad rate, the probability of an explosion on the AT&SF involving explosives is 1.59 x 10-8 explosions per explosive train mile.

The probability that a munitions train explosion on the AT&SF will cause a peak positive normal reflected pressure at the station which exceeds the design basis overpressure is estimated by the following equation:

Pop Pex x SF xT 1 NiLi where Pop

=

the annual probability of an overpressure at the station exceeding the design basis overpressure of (later)

-17 Pex

=

probability of an explosive AT&SF per explosive train mile (1.59 x 10-8)

SF

=

Significance factor (0.154)

Ni

=

the number of munitions train shipments/yr which carry a total of Wi pounds net explosive weight past the San Onofre site Li

=

the critical length of track over which the detonation on Wi pounds of TNT would produce an overpressure at the station exceeding the design basis overpressure of (later) psi The significance factor is to eliminate those explosions that do not result in an explosive blast.

Values for Wi and Ni assumed for the calculation are given in Table 6. Peak explosion overpressures are based upon standard scaling laws for surface, hemispherical burst of TNT at sea level.

Assuming the entire explosive cargo of a train detonates in-mass, the annual probability of a peak positive normal reflected overpressure at the station exceeding (later) psi caused by ordnance detonations on the AT&SF track, is (later).

This number can be considered to be conservative, and the actual probability of occurrence is expected to be much lower for the following reasons:

(1) The number of accidents involving explosives included a large number of shipments that were made during both World Wars and the Korean and Vietnam conflicts.

(2) If an explosion were to occur in a boxcar of ordnance of the type normally shipped past San Onofre (small arms ammunition) it is more likely to detonate in small individual bursts rather than as a single large blast. Overpressures experienced at the site would be correspondingly lower.

5.3.3.2.2 LPG Tank Cars.

There are two types of accidents involving LPG cars which could lead to an explosion:

(1) Accidental puncture of an LPG tank car, and (2) Exposure of an LPG tank car to fire.

During the 6-year period 1965 to 1970, there were 63 mechanical damage-induced loss-of-lading accidents involving type 112A cars carrying flammable compressed gases. The fleet of 112A (the type used to transport LPG by the plant) cars loaded with flammable compressed gases traveled a total of 5.38 x 107 car-miles/yr during this period. Therefore, the national rate of loss-of-lading accidents per shipment mile was 1.95 x 10- 7 loss-of-lading accidents caused by mechanical damage/LPG tank car mile. The accident rate

-18 for the AT&SF is significantly less than the national average and therefore by using the ratio of the AT&SF and national average,-the AT&SF rate of loss-of-lading accidents per shipment mile is 1.0 x 10-7 loss-of-lading accidents by mechanical damage/LPG tank car mile.

Forty incidents were reported between 1965 and 1970 in which 50 cars experienced loss-of-lading from tank cars carrying LPG, propane, or butane that were caused by mechanical puncture.

In 24 of these cases, the release caused a fire, and in 26 cases the gas escaped without incident.

Propane tank car accidents can be categorized according to their severity as follows:

A. Type I - This type of incident would be caused by a major rupture of the LPG containment vessel resulting in a gross spill without ignition. The result would be that a very large vapor cloud would be formed. If this cloud would be ignited after an explosive fuel/air mixture had been formed, a maximum-incident explosion would result.

This type of incident is characterized by an unconfined fuel/air detonation.

B. Type II - This type of incident would he caused by a separate fire or a tank puncture resulting in a fire that would overheat the punctured propane tank or another propane tank in the near vicinity.

The result would be an explosive pressure rupture of the heated tank, causing nearby overpressure damage and possible shrapnel damage from the ruptured tank.

This type of incident is characterized by a propane tank explosion.

C.

Type III - This type of incident would result from a leak or a tank puncture resulting in a large spill with ignition occurring immediately or shortly after the incident. The propane would burn uncontrollably in a large, intense fireball.

No tank explosion would occur since the tank puncture would be large enough to relieve the pressure. This type of incident is characterized by a large uncontrollable fireball with no explosion.

D.

Type IV - This type of incident would be caused by a leak, a tank puncture, a released safety valve or a burst transfer line or valve resulting in a controllable fire. The fire may be of considerable time duration and does not result in tank rupture, either due to fire control measures or protective insulation. This type of incident is characterized by a controllable fire with no explosion.

E. Type V - This type of incident would involve a leak or a puncture, either small or large, in a propane tank of loading lines which does not result in fire. If no source of ignition occurs, the propane will be dispersed in the atmosphere in a relatively short time.

This type of incident is characterized by loss of lading, but no fire.

-19 Reviewing the information available about the 40 incidents.cited above, it is concluded that these 50 tank car accidents can be classified as follows:

Type Number of Accidents I

0 II 2

III 20 IV 2

V 26 No tank car Type I severity accidents involving either LPG or propane have been reported in the period from 1965 to 1970. However, there was one such incident resulting from the puncture of a propylene car (January 22, 1972, St.

Louis, Missouri) and a second due to the puncture of a car laden with isobutane (July 19, 1974, Decature, Illinois).

To be conservative, these incidents are included in the data base to obtain the following relative frequency of occurrence per tank car for each type of accident due to mechanical damage to LPG tank cars:

Relative Frequency Type of Occurrence I

0.038 II 0.038 III 0.385 IV 0.038 V

0.500 In addition to the mechanical damage, exposure of LPG cars to fire can lead to explosions. There were 17 incidents involving 49 LPG tank cars during the period of 1965-1970. These accidents can be classified as follows:

Type Number Frequency of Occurrence I

0 0.0 II 39 0.796 III 2

0.041 IV 7

0.143 V

1 0.020 Although fuel-air detonations from fire-induced loss-of-lading accidents are conceivable, it is not credible that the escaping gas would fail to detonate very near the car (the heat from the fire which caused the tank car failure would also be available to initiate the detonation). The probability of a delayed detonation for these cases is accordingly assumed to be zero.

One hundred thirteen carloads of LPG were shipped past the San Onofre site during the first 11 months of 1975. The annual frequency of shipments is taken to be 124 LPG cars/yr., based upon the opinion of the AT&SF that there will be minimal future growth in LPG haulage. The AT&SF has also stated that there are no more than two or three LPG tank cars in any one train.

-20 There are three possible hazards that could adversely affect the plant from an explosion of an LPG tank car; overpressurization, fireball, and missiles generated by tank car explosion. Detonation and resulting shock wave would occur only for Type I events.

For Type II events, the overpressure failure of the tank car results in an explosive energy release but not detonation. A very conservative analysis of this yielded a maximum overpressure at the plant of approximately 1.0 lb/in. 2.

A realistic analysis of the overpressurization potential to the plant site from LPG tank cars has been performed using the following inputs:

(1) The peak reflected overpressures required to cause release which could lead to consequences in excess of 10CFR100 guidelines as (later) psi.

(2) The single yield of explosion has been replaced by a distribution of yields which is applied to the entire quantity of material released.

(3) The probability of a significant explosion per train mile is reduced by a factor of 2 to account for the effects of improved couplers and head shields.

The results of this realistic analysis show that the probability of exceeding 10CFR100 guidelines from an LPG explosion on AT&SF railroad is (later).

A second possible cause of plant damage is the detonation resulting in a fireball causing damage to the plant.

The maximum size fireball would be the result of a Type III accident. A considerably smaller fireball could result from a Type II accident.

Ignition of 30,000-pound tank car of LPG would result in a fireball with a radius of 221 feet with a duration of 10.4 seconds. A fireball of this duration at a distance of about 300 feet from the plant will not cause damage to concrete buildings. Furthermore, safety-related equipment located outside would not be affected. The effect of the fireball would be to overheat equipment by radiation heating.

Because the plant is located below a steep bluff, out of line of sight from the railroad track, it is expected that no radiation heating of equipment would occur.

The final potential hazard to the plant is the generation of self propelled (or rocketing) missiles due to Type II ruptures of the tank car. A fragment from an LPG tank car explosion was hurled 2,640 feet while the great majority of the rocketing tank car fragments generated by exploding tank cars have a range of less than 1,000 feet. The largest range of a car fragment from a flammable gas tank car rupture was 4,900 feet due to an ethylene oxide tank car rupture.

Using the value of 4,900 feet for generating missiles and 400 feet for the length of the plant parallel to the tracks gives a track length of 10,200 feet or 1.93 miles. The probability that a fragment will impact the plant is obtained from the ratio of the solid angle at the accident site which would yield a plant impact to the total solid angle of a hemisphere.

Considering the plant effective area and the maximum range discussed above, this probability of impact is a maximum of (later). The effects of missile impacts on the plant are discussed in the assessment of Topic III-4.0, Site Proximity Missiles (Including Aircraft).

-21 The probability of a directly occurring Type II accident due to mechanical damage is 0.038. The probability of a Type II event occurring due to a fire is 0.796.

Most Type II LPG tank car accidents (10 out of 12 in years 1965-1970) are caused by fires from other LPG tank cars.

These other tank car fires were the result of Type II or Type III accidents which occur with a probability of 0.423. The overall probability that a fire in one LPG tank car will result in a Type II event in a second LPG tank car is 0.28. Therefore the total probability of Type II event due to puncture accident of an LPG tank car is 0.318. The annual probability for Type II occurrence due to mechanical puncture of an LPG car per AT&SF track mile is 3.94 x 10-6.

In addition to the probability of an LPG tank car fire, there is the probability that a train fire will be initiated by means of other than a puncture of an LPG tank care. WASH 1238 states that fire occurs in about 1.5%

of all train accidents. Conservatively assuming that none of these fires are caused by LPG tank punctures, the probability of a fire per train accident is 1.5 x 10-2. The average accident rate of AT&SF trains are 5.29 x 10-6 accidents per train mile. Using 62 LPG trains per year carrying 2 LPG cars the probability of a train fire on a 1-mile length of track is 4.92 x 10-6.

Using an average train length of 70 cars and 10 cars involved in the accident with the probability that a non-LPG tank.car will cause a Type II rupture (0.167) and the probability that either or both of the LPG cars are involved in the accident, the annual probability for a Type II rupture due to non-LPG tank car induced fire is 9.3 x 10-8 per track mile.

The combined annual probability for Type II rupture from all causes is 4.03 x 10- 6.

If it is conservatively assumed that all Type II events will produce one rocketing fragment, the total annual probability that an LPG tank generated fragment strikes the safety-related a structure of the unit is (later).

The analysis of explosions on AT&SF railway is conservative for the following reasons:

(1) The accident rate within 5 miles of the plant should be lower since there are no grade crossings.

(2) The accident rate used included switching operations.

(3) The probability of tank head puncture of LPG tank cars should be reduced due to the required installation of tank head protective shields by 1977.

(4) The entire contents of the tank car was assumed to be capable of flashing to form a vapor and be available to fuel a fireball.

5.3.4 Accidents Involving Natural Gas Pipelines A 12-inch natural gas pipeline is located approximately 510 feet from the nearest safety-related plant structure. An analysis has been performed to determine the likelihood of a pipeline accident that leads to an unacceptable

-22 concentration of 4.4% natural gas at the air intake and is documented in the San Onofre Units 2 and 3 FSAR.

The analysis results in a negligibly small probability (6.75 x 10- 9/year) of intersection of the 4.4% concentration with the plant intake. The analysis is also applicable to and conservative for San Onofre Unit 1 for the following reasons:

1. The terrain at Unit 1 is similar to that at Units 2 and 3. However, the bluff between the plant and the pipe line is both higher and steeper at Unit 1 than at Units 2 and 3. Therefore, flow separation from the ground is more likely for Unit 1.
2. The Unit 1 control room air intake is at a lower elevation than Units 2 and-3. Therefore, the gas concentration would be lower at the intake for Unit 1 than Units 2 and 3.
3. The Unit 1 air intake is farther from the pipe line than Units 2 and 3.

5.3.5 Offsite Fires Offsite fires are not considered a credible hazard to the plant.

5.3.6 Accidents at Nearby Industrial and Military Facilities There are no significant manufacturing plants, chemical plants, refineries, wells, oil or gas storage facilities, or mining operations within 5 miles of the site. Hazards associated with the Camp Pendleton Marine Corps base are discussed above.

5.3.7 Accidents at Sea The closest shipping lane to the site is located more than 5 miles from shore. Therefore postulated shipping accidents are not evaluated as possible design basis events.

6.0 CONCLUSION

Based upon the above information, it is concluded that:

1. the risk to the plant from nearby industrial facilities is negligible,
2. the risk to the plant from the Camp Pendleton Marine Corps Base and associated operations, except for munitions shipments, is negligible,
3. the risk to the plant from the commercial shipping lines at sea is negligible,
4. the risk to the plant from the three nearby gas pipe lines is negligible, and
5. there exists a potential hazard to the plant from explosions due to accidents involving hazardous materials on both 1-5 and the AT&SF railroad. Further analyses of these hazards will be performed and submitted approximately February 1, 1982.
  • 0 la, 1 r,-J, 77 7:

jii

.7

  • J LEGEND SANONOFRE S AN DIEGO
FREEWAY, IRSATE~1~~~4 It CAMINO
REAL, NISIEAYj ATCHISOM TOPEKIA AU SANTA FE RAILRDO SAN DIEGO PIPELINE CO. 311110 PEIOLEUM PRODUCT$
80. CAL.

GAS CO, Q

NATURAL GAS PIPELINE VICTOR AIRWAY n-1115 0 VALVE F\\ IRING RANGE G ASOLINE STORAGE________________________

SQUARRY

Table 1

HAZARDOUS CARGO TRAFFIC ESTIMATES (Sheet 1 of 2)

Annual(a)

Average Maximum(b)

Cargo Type Shipments Shipment Size Shipment Size Flamable Liquids Gasoline 17,000 8,600 gal 9.000 gal Diesel oil 650 7,600 gal 7,900 gal Jet fuel 910 8,000 gal 9,000 gal Solvents (See table-2

)

Miscellaneous Petroleum Products (See table 2

)

Flamable Gasses Propane (LPG) and Butane 2,200 9,700 gal 10,100 gal LNG 420 9,200 gal 9,200 gal Hydrogen (liquid) 52 8,500 gal 3

3 Hydrogen (gas) 260 38 -219 ft 75 -219 ft cylinders cylinders Hydrogen (gas) 2 4(c) 10 -

11,400 ft3 10 -

11,400 ft3 cylinders cylinders 3

Acetylene 10 -

330 ft cylinders a..

Estimate of annual shipments based on survey at truck weighing sta tion except where shipper estimates exceeded that number.

b.

Maximum size is based on the actual observed shipments.

c.

Not actually observed, identified through a questionnaire survey of all chemical manufacturers in the region.

Table 1

HAZARDOUS CARGO TRAFFIC ESTIMATES (Sheet 2 of 2)

Annual (a)

Average maximum(b)

Cargo Type Shipments Shipment Size Shipment Size Compressed Gasses Carbon dioxide 260 20 tons 20 tons Argon 200 1,800 gal 8,000 gal Helium 130 12,000 lb 12,000 lb Nitrogen 2,400 40,000 lb 44,000 lb Chorine 754 7.5 tons 13 tons Anhydrous ammonia 132(c) 5 tons 7.5 tons Miscellaneous Poison & Pesticides 260 8,000 lb 19,000 lb Corrosives (acid) 850 26,000 lb 50,000 lb Used Batteries 490 20,000 lb 42,000 lb Paint 1,400 18,000 lb 40,000 lb Cleaning Products 520 9,000 lb 36,000 lb Pool Chemicals 1,000 8,000 lb 45,000 lb

Table 2

INFREQUENT HAZARDOUS CARGO SHIPMENTS (Sheet 1 of 2)

Chemical Shipment Size Solvents Acetone(a) 7,600 gal Diacetone (b

2,600 gal Xylene (24 annual shipments'b) 7,500 gal Shell SOL M-75 1,575 gal TOLU-SOL-6 975 gal Naptha 2,725 gal Methanol(a) 1,000 gal Ms 20H 8,000 gal Pentachlorophenol 20,000 lb Miscellaneous Petroleum Products Benzene 300 gal Motor oil 34,000 lb (typical Formaldehyde(a)

(14 annual shipments(b))

6,000 gal Weed oil h

54,000 lb Crude oil 7,600 gal Hydraulic oil 3,900 gal Perchloroethylene 4,000 gal Methyl butyl ketone 1,000 Methylene chloride

-3,800 gal Methyl ethyl ketone 13,000 lb Ethylene dichloride(a) 1,000 Butyl Acetate 22,000 lb Epoxy 1,000 lb Poisons and Pesticides Methyl bromide 3,500 lb Corrosives Hydrochloric acid 40,000 lb Surfuic acid 3,340 to 50,000 lb Muriatic acid 3,120 lb Nitric acid(a) 2,800 lb

a.

Not actually observed; identified through a questionnaire survey of all chemical manufacturers in the region

b.

Based on shippers estimate

Table 2

INFREQUENT BAZARDOUS CARGO SHIPMENTS (Sheet 2 of 2)

Chemical Shipment Size Cleaning Products Caustic soda 5,000 to 37,000 lb Chemical soap 36,000 lb Detergent (powder) 693 to 1,200 lb Soap 800 to 9,000 lb miscellaneous Plastic resin 2,000 lb Alum sulfate (liquid) 10,700 lb Titanium dioxide 11,000 lb Nitrous oxide 1,904 ft. 3 Aerosol cans 40,000 lb Chromium oxide (powder) 2,000 lb Roofing resin 50,000 lb Potassium nitrate 1,000 lb Ammonium nitrate 51,000 lb

Table 3A

SUMMARY

OF DATA SUPPLIED BY CALIFORNIA DEPARTMENT OF TRANSPORTATION lesNumber Accidents per Calendar Tronk il of Accidents 106 Miles 1974 20.38 x 106 12 0.589 1975 19.88 x 106 9

0.453 1976 21.83 x 106 15 0.687 1977 22.65 x 106 12 0.530 Combined 84.74 x 106 48 0.566 Table 3B U.S. DOT INTERCITY HIGHWAY TRUCK.ACCIDENT RATES PER MILE AccidentOReported AceidenO-Ranjxty0-Fatalil0 Year i

vra aex1-aex1-aex1 1971

$ 250.

2.19 1.00 0.083 1972 250 2.31 0.996 0.081 1973

$ 2000 0.952 1.02 0.071

a.

Accident also reported if there was an injury or fatality.

Table 3C NATIONAL TRUCK ACCIDENT RATES Calendar Total Intercity Total Intercity Accident Rate Year Vehicle Miles Accidents per 106 Miles 1968 11704 x 106 29209 2.50 1969 12461 x 106 30672 2.46 1970 12390 x 106 33203 2.68 1971 13951 x 106 30581 2.19 1972 15883 x 106 36682 2.31 Combined 66389 x 106 160347 2.41

Table 4

TABULATION OF THE RELATIVE FREQUENCY WITH WHICH WINDS BLOW TOWARDS THE SAN ONOFRE SITE FROM EACH OF THE 22-1/2 DEG WIND ROSE SECTORS, AND THE LENGTH OF INTERSTATE 5 LYING WITHIN EACH SECTOR AREA Frequency of Estimated Winds Blowing Length of Toward the Interstate 5 Wind Direction Site from Included within the Sector Sector Sector Area (miles)

NW 0.0614 4.85 NNW 0.0320 0.27 N

0.0343 0.10 NNE 0.1092 0.07 NE 0.1404 0.07 ENE 0.0289 0.10 E

0.0163 0.25 ESE 0.0220 1.84 SE 0.0485 2.84 SSE 0.0698 0

S 0.0652 0

SSW 0.0607 0

SW 0.0533 0

WSW 0.0639 0

W 0.0857 0

WNW 0.1078 0

Table 5

ASSUMED BOX CAR WEIGHT DISTRIBUT1JION OF ORDNANqCE TRANSPORTED BY RAIL PAST THE SAN ONOFE SITE Boxcar Shipments/yr Net Explosive Weight/Boxcar (lb) 1 37,000 4

25,500 10 25,000 15 20,000 25 15,000 15 13,000 10 10,000 2

6,000 3,000 400 84 boxcars/yr Table 6

ASSUMED SHIPMENT WEIGHT DISTRIBUTION OF ORDNANCE TRNSPORTED BY RAIL PAST THE SAN ONOFRE SITE Muitions Tra n ments/Yr Total Net Explosive Weight/Shipment Wi (1bs) 2 62,500 5

50,000 5

40,000 1

30,000 12 28,000 26,000 1

20,000 16,000 1-12,000 19,000 3,400 42 shipments/yr