Text
.
7590-01 UNITED STATES NUCLEAR REGULATORY COMMISSION SOUTHERN CALIFORNIA EDISON COMPANY, ET AL DOCKET NO. 50-206 NOTICE OF ISSUANCE OF AMENDMENT TO PROVISIONAL OPERATING LICENSE The U.S. Nuclear Regulatory Commission (Commission) has issued Amendment No.115to Provisional Operating License No. DPR-13, issued to Southern California Edison Company and San Diego Gas and Electric Company (the licensees), which revised the Technical Specifications for operation of the San Onofre Nuclear Generating Station, Unit 1, located in San Diego County, California. The amendment was effective as of the date of issuance.
The amendment revised the steam generator tube plugging criteria to allow tubes with defects in the rolled region of the tube sheet to remain in service provided that the first inch of rolled tube contains no imperfections, and made permanent the interim approval granted by Amendment No. 101, issued May 6, 1988.
The application for the amendment complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations. The Commission has made appropriate findings as required by the Act and the Commission's rules and regulations in 10 CFR Chapter 1, which are set forth in the license amendment.
Notice of Consideration of Issuance of Amendment and Opportunity for Hearing in connection with this action was published in the FEDERAL REGISTER on May 16, 1988 (53 FR 17282). No request for a hearing or petition for leave to intervene was filed following this notice.
881206.0096 :8112:
PDR ADOCK o5000206 pric
-2 The Commission has prepared an Environmental Assessment related to the action and has concluded that an environmental impact statement need not be prepared because operation of the facility in accordance with this amendment will have no significant adverse effect on the quality of the human environment.
For further details with respect to the action see (1) the application for amendment dated March 10, 1988, as supplemented March 22 and 29, 1988, (2)
Amendment No.115 to License No. DPR-13, (3) the Commission's related Safety Evaluation and (4) the Commission's Environmental Assessment. All of these items are available for public inspection at the Commission's Public Document Room, 2120 L Street NW, Washington, DC 20555, and at the General Library, University of California, P. 0. Box 19557, Irvine, California 92713. A copy of items (2), (3) and (4) may be obtained upon request addressed to the U.S.
Nuclear Regulatory Commission, Washington, DC 20555, Attention: Director, Division of Reactor Projects -
III, IV, V and Special Projects.
Dated at Rockville, Maryland this 28 day of November, 1988.
FOR THE NUCLEAR REGULATORY COMMISSION Charles M. Trammell, Project Manager Project Directorate V Division of Reactor Projects -
- III, IV, V and Special Projects Office of Nuclear Reactor Regulation