tNkREG4 UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555 SOUTHERN CALIFORNIA EDISON COMPANY SAN DIEGO GAS AND ELECTRIC COMPANY DOCKET NO. 50-206 SAN ONOFRE NUCLEAR GENERATING STATION, UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 152 License No. DPR-13

1.

The Nuclear Regulatory Commission (the Commission or the NRC) has found that:

A.

The application for amendment by Southern California Edison Company (the licensee) and the San Diego Gas and Electric Company dated October 29, 1992, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, as amended, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C(2) of Facility Operating License No. DPR-13 is hereby amended to read as follows:

9301060177 921229 PDR ADOCK 05000206 P

PDR

-2 (2) Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No.152, are hereby incorporated in the license.

Southern California Edison Company shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance and must be fully implemented no later than 30 days from the date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION 4 wTheodore R. Quay, Director Project Directorate V Division of Reactor Projects III/IV/V Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance:

December 29, 1992

ATTACHMENT TO LICENSE AMENDMENT AMENDMENT NO. 152 TO FACILITY OPERATING LICENSE NO. DPR-13 DOCKET NO. 50-206 Revise Appendix A Technical Specifications by removing the pages identified below and inserting the enclosed pages. The revised pages are identified by the captioned amendment number and contain marginal lines indicating the areas of change.

REMOVE INSERT i

i ii ii 3.7-7 3.7-7

0 0

APPENDIX A TECHNICAL SPECIFICATIONS LIST OF EFFECTIVE PAGES Page Amendment No.

Page Amendment No.

Page Amendment No.

.i52-2.1-4 43, 117, 121, 122, 3.1-23 83, 130 152 130 3.2-1 102, 130 114 W, 151 2.1-5 43, 97, 117, 121, 3.2-2 25, 102, 130 iv 139, 145 122, 130 3.3-1 25, 37, 86, 124 v

90, 130, 131 2.1-6 55, 130 130, 146 vi 90, 130, 131, 145 3.0-1 43, 56, 64, 83 3.3-2 25, 130, 146 vii 90, 102, 130, 131 130 3.3-3 25, 38, 86, 124, 145 3.0-2 56, 64, 83, 130, 130, 142, 146 viii 90, 130, 131, 145 135 3.3-4 25, 37, 124, 130, 146 ix 90, 91, 102, 130 3.0-3 135 3.3-5 25, 130, 146 131, 145 3.0-4 135 3.3-6 25, 102, 120, 130 x

90, 91, 130, 131 3.1-1 29, 38, 70, 83, 3.3-7 25, 102, 130 145 91, 96, 130 3.3-8 25, 38, 122, 130, 148 xi 55, 92, 102, 110, 3.1-2 29, 83, 96, 130 3.3-9 25, 38, 122, 130, 148 111, 130, 131, 143 3.1-3 43, 77, 103, 130 3.3-10 25, 130 xii 56, 58, 71, 79, 3.1-4 77, 130 3.3-11 NRC Order 83, 104, 117, 130, 3.1-5 77, 125, 130 4/20/81, 130 131, 143, 145 3.1-6 77, 102, 130 3.3-12 NRC Order xiii 31, 56, 58, 79, 3.1-7 77, 102, 103, 130 4/20/81, 130 83, 84, 91, 117, 3.1-8 43, 102, 103, 130 3.4-1 29, 82, 125, 130 130, 131, 143, 145 3.1-9 77, 102, 130 3.4-2 29, 130 xiv 131, 143, 145 3.1-10 Change No. 14, 38, 3.4-3 82, 125, 130, 138 xv 143 102, 130 3.4-4 82, 125, 130, 138 1.0-1 31, 56, 59, 83, 3.1-11 Change No. 14, 38, 3.5-1 83, 117, 130, 143 117, 130 102, 130 3.5-2 43, 56, 58, 83, 1.0-2 31, 56, 59, 83, 3.1-12 Change No. 14, 92, 117, 128, 130 104, 117, 130 130 3.5-3 43, 56, 58, 83, 1.0-3 31, 56, 59, 79, 3.1-13 Change No. 14, 92,

117, 121,
122, 83, 104, 117, 130, 130 130, 143 145 3.1-14 Change No. 14, 3.5-4 55, 58, 83, 117, 1.0-4 31, 56, 59, 79, 102, 130 118, 121, 128, 130 83, 117, 130, 145 3.1-15 Change No. 14, 3.5-5 83, 117, 130 1.0-5 77, 79, 83, 117, 102, 130 3.5-5a 143 130, 145 3.1-16 Change No. 14, 3.5-5b 143 1.0-6 79, 83, 96, 117, 102, 130 3.5-5c 143 130 3.1-17 Change No. 14, 3.5-6 7, 11, 25, 35, 55, 1.0-7 58, 83, 117, 130 102, 130 56, 111, 130, 148 1.0-8 56, 83, 117, 130 3.1-18 Change No. 7, 37, 3.5-7 7, 11, 25, 35, 49, 2.1-1 43, 55, 97, 117, 55, 91, 119, 130 55, 56, 111, 122, 130 3.1-19 Change No. 7, 55, 130, 148 2.1-2 43, 97, 117, 121, 119, 130 3.5-8 11, 49, 111, 122, 130 3.1-20 37, 55, 119, 130 130, 148 2.1-3 43, 117, 121, 122, 3.1-21 58, 59, 83, 130 3.5-9 11, 25, 56, 111, 130 3.1-22 58, 130 130 SAN ONOFRE - UNIT 1 i

AMENDMENT NO. 152

00 LIST OF EFFECTIVE PAGES (Cont.)

Page Amendment No.

Page Amendment No.

Page Amendment No.

3.5-10 56, 130 3.7-7 134, 136, 152 3.14-24 130, 131 3.5-11 56, 130 3.7-8 136 3.14-25 130, 131 3.5-12 56, 130 3.8-1 25, 36, 37, 3.14-26 130, 131 3.5-13 56, 130 73, 77, 130 3.15-1 79, 130, 145 3.5-14 56, 130 3.8-2 36, 77, 130 3.16-1 79, 130, 145 3.5-15 58, 83, 130 3.8-3 25, 36, 73, 3.16-2 79, 90, 91, 3.5-16 58, 83, 130, 145 77, 130 105, 130, 145 3.5-17 58, 83, 130 3.8-4 36, 73, 77, 130 3.16-3 79, 90, 91, 3.5-18 58, 72, 130 3.8-5 36, 73, 77, 130 105, 130, 145 3.5-19 58, 83, 125, 130 3.9-1 3, 10, 112, 130, 148 3.16-4 79, 90, 91, 3.5-20 125, 130 3.9-2 3, 10, 112, 130, 148 105, 130, 145 3.5-21 58, 83, 117, 124, 3.10-1 7, 8, 112, 122, 3.16-5 79, 90, 130, 125, 130 130 145 3.5-22 64, 82, 125, 130 3.10-2 7, 112, 122, 130 3.16-6 79, 90, 130, 3.5-23 58, 82, 125, 130 3.11-1 7, 8, 11, 35, 145 3.5-24 58, 82, 125, 130 55, 112, 117, 3.17-1 79, 90, 91, 3.5-25 58, 82, 125, 129, 122, 130 105, 130, 145 130 3.11-2 7, 11, 112, 3.18-1 79, 91, 105, 130, 3.5-26 79, 90, 105, 130, 117, 122, 130 145 145 3.12-1 14, 130 3.19-1 79, 90, 105, 130, 3.5-27 79, 90, 105, 130, 3.13-1 21, 63, 81, 130 145 145 3.13-2 21, 63, 81, 130 3.20-1 102, 130 3.5-28 83, 130, 145 3.14-1 31, 44, 93, 130, 3.20-2 102, 130 3.5-29 83, 130, 145 131 4.0-1 83, 130, 137 3.5-30 83, 91, 130, 145 3.14-2 31, 130, 131 4.0-2 83, 130, 137 3.6-1 25, 56, 58, 3.14-3 31, 130, 131 4.0-3 135 73, 130 3.14-4 31, 93, 130, 131 4.0-4 135 3.6-2 Change No. 7, 3.14-5 31, 130, 131 4.1-1 29, 56, 83, 56, 130 3.14-6 130, 131, 134 117, 130 3.6-3 58, 99, 130 3.14-7 130, 131 4.1-la 143 3.6-4 58, 71, 99, 130 3.14-8 130, 131 4.1-2 7, 22, 83, 117, 3.6-5 58, 59, 71, 3.14-9 130, 131 122, 130, 143 99, 130 3.14-10 130, 131 4.1-3 117, 130 3.6-6 58, 59, 83, 130 3.14-11 31, 93, 130, 131 4.1-4 25, 29, 70, 3.7-1 25, 52, 68, 84, 3.14-12 31, 130, 131 96, 117, 130 130, 134, 136 3.14-13 31, 130, 131 4.1-5 25, 29, 70, 3.7-2 25, 84, 106, 130, 3.14-14 31, 130, 131 96, 130 134, 136 3.14-15 31, 93, 130, 131 4.1-6 25, 29, 56, 70, 3.7-3 25, 84, 130, 134, 3.14-16 31, 130, 131 100, 122, 130, 134 136 3.14-17 31, 130, 131, 134 4.1-7 25, 29, 36 3.7-4 25, 52, 68, 84, 3.14-18 31, 130, 131 77, 103, 130, 142 106, 130, 134, 136 3.14-19 130, 131 4.1-8 77, 125, 130 3.7-5 25, 52, 68, 84, 3.14-20 130, 131 4.1-9 77, 122, 125, 130 106, 120, 130, 3.14-21 130, 131 134, 136, 143 3.14-22 130, 131 3.7-6 134, 136, 143 3.14-23 130, 131 SAN ONOFRE - UNIT 1 ii AMENDMENT NO. 152

3.7.2 ELECTRICAL SUPPLY:

SHUTDOWN APPLICABILITY: MODES 5 and 6 OBJECTIVE:

To define those conditions of available electrical power to ensure that the station can be maintained in the shutdown or refueling condition for extended periods.

SPECIFICATION:

a. One offsite high voltage transmission line to the switchyard and one transmission circuit from the switch yard, immediate or delayed access, to the onsite safety related distribution system shall be OPERABLE.
b. One diesel generator shall be OPERABLE with a total connected design load not to exceed 6,000 kW and with:
1. A day tank containing a minimum 290 gallons of fuel,
2. A fuel storage system containing a minimum of 37,500 gallons of fuel, and
3. A fuel transfer pump.
c. One train of AC buses shall be OPERABLE comprised of:
1. 4,160 volt Bus 1C, and 480 volt Buses 1 and 3 with at least one associated station service transformer; OR
2. 4,160 volt Bus 2C, and 480 volt Buses 2 and 4 with at least one associated station service transformer.
d. 120 volt Vital Buses 1, 2, and 4 energized from associated inverters connected to DC Bus 1.
e. One 125 volt DC Bus OPERABLE and energized from the associated battery with at least one full capacity charger.

ACTION:

With less than the minimum required AC and DC electrical sources specified above, suspend all operations involving CORE ALTERATIONS or positive reactivity changes. Initiate correc tive actions to energize the required electrical buses. Within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, depressurize and vent the RCS through at least a 1.75 square inch vent.

BASIS:

In MODES 5 and 6, the requirement for one source of offsite power and one diesel generator to be OPERABLE will provide diverse and redundant electrical power sources in order that the station can be maintained in the COLD SHUTDOWN or REFUELING condition for extended time periods. Additionally, this SAN ONOFRE -

UNIT 1 3.7-7 AMENDMENT NO. 152