Corrected Amend 143 to License DPR-13 Adding Marginal Line Indicating Change to Tech Spec 3.5-1 Re Mods to Safeguards Load Sequencer Sys
ML13309A122
Person / Time
Site: San Onofre 
Issue date: 06/10/1991
From:
Office of Nuclear Reactor Regulation
To:
Shared Package
ML13309A120 List:
References
DPR-13-A-143 NUDOCS 9106110392
Download: ML13309A122 (4)


Text

3.5 INSTRUMENTATION AND CONTROL 3.5.1 REACTOR TRIP SYSTEM INSTRUMENTATION APPLICABILITY: As shown in Table 3.5.1-1.

OBJECTIVE:

To delineate the conditions of the Plant instrumentation and safety circuits necessary to ensure reactor safety.

SPECIFICATION: As a minimum, the reactor trip system instrumentation channels and interlocks of Table 3.5.1-1 shall be OPERABLE with the SETPOINTS and RESPONSE TIMES as shown in Tables 3.5.1-2 and 3.5.1-3, respectively.

ACTION:

As shown in Table 3.5.1-1.

BASIS:

During plant operations, the complete instrumentation systems will normally be in service. (1) Reactor safety is provided by the Reactor Protection System, which automatically initiates appropriate action to prevent exceeding established limits.(2)

Safety is not compromised, however, by continuing operation with certain instrumentation channels out of service since provisions were made for this in the plant design. (1)(3) This Standard outlines limiting conditions for operation necessary to preserve the effectiveness of the reactor control and protection system when any one or more of the channels is out of service.

REFERENCES:

(1) Final Engineering Report and Safety Analysis, Section 6.

(2) Final Engineering Report and Safety Analysis, Section 6.2.

(3) NIS Safety Review Report, April 1988 SAN ONOFRE - UNIT 1 3.5-1 AMENDMENT NO:

83, 41-7, 130, 143 9106110392 910610 PDR ADOCK 05000206

APPENDIX A TECHNICAL SPECIFICATIONS LIST OF EFFECTIVE PAGES Page Amendment No.

Page Amendment No.

Page Amendment No.

i 143 2.1-6 55, 130 3.3-2 25, 130 ii 143 3.0-1 43, 56, 64, 83, 3.3-3 25, 38, 86, 124, iii 143 130 130, 142 iv 139 3.0-2 56, 64, 83, 130, 3.3-4 25, 37, 124, 130 v

90, 130, 131 135 3.3-5 25, 130 vi 90, 130, 131 3.0-3 135 3.3-6 25, 102, 120, 130 vii 90, 102, 130, 131 3.0-4 135 3.3-7 25, 102, 130 viii 90, 130, 131 3.1-1 29, 38, 70, 83, 3.3-8 25, 38, 122, 130 ix 90, 91, 102, 130, 91, 96, 130 3.3-9 25, 38, 122, 130 131 3.1-2 29, 83, 96, 130 3.3-10 25, 130 x

90, 91, 130, 131 3.1-3 43, 77, 103, 130 3.3-11 NRC Order xi 55, 92, 102, 110, 3.1-4 77, 130 4/20/81, 130 111, 130, 131, 143 3.1-5 77, 125, 130 3.3.12 NRC Order xii 56, 58, 71, 79, 3.1-6 77, 102, 130 4/20/81, 130 83, 104, 117, 130, 3.1-7 77, 102, 103, 130 3.4-1 29, 82, 125, 130 131, 143 3.1-8 43, 102, 103, 130 3.4-2 29, 130 xiii 31, 56, 58, 79, 3.1-9 77, 102, 130 3.4-3 82, 125, 130, 138 83, 84, 91,

117, 3.1-10 Change No. 14, 38, 3.4-4 82, 125, 130, 138 130, 131, 143 102, 130 3.5-1 83, 117, 130, 143 xiv 131, 143 3.1-11 Change No. 14, 38, 3.5-2 43, 56, 58, 83, xv 143 102, 130 117, 128, 130 1.0-1 31, 56, 59, 83, 3.1-12 Change No. 14, 92, 3.5-3 43, 56, 58, 83, 117, 130 130
117, 121, 122, 130, 1.0-2 31, 56, 59, 83, 3.1-13 Change No. 14, 92, 143 104, 117, 130 130 3.5-4 55, 58, 83, 117, 1.0-3 31, 56, 59, 79, 3.1-14 Change No. 14, 118, 121, 128, 130 83, 104, 117, 130 102, 130 3.5-5 83, 117, 130 1.0-4 31, 56, 59, 79, 3.1-15 Change No. 14, 3.5-5a 143 83, 117, 130 102, 130 3.5-5b 143 1.0-5 77, 79, 83, 117, 3.1-16 Change No. 14, 3.5-5c 143 130 102, 130 3.5-6 7, 11, 25, 35, 55, 1.0-6 79, 83, 96, 117, 3.1-17 Change No. 14, 56, 111, 130 130 102, 130 3.5-7 7, 11, 25, 35, 49, 1.0-7 58, 83, 117, 130 3.1-18 Change No.

7, 37, 55, 56, 111, 122, 1.0-8 56, 83, 117, 130 55, 91, 119, 130 130 2.1-1 43, 55, 97, 117, 3.1-19 Change No.

7, 55, 3.5-8 11, 49, 111, 122, 130 119, 130 130 2.1-2 43, 97, 117, 121, 3.1-20 37, 55, 119, 130 3.5-9 11, 25, 56, 111, 130 3.1-21 58, 59, 83, 130 130 2.1-3 43, 117, 121, 122, 3.1-22 58, 130 3.5-10 56, 130 130 3.1-23 83, 130 3.5-11 56, 130 2.1-4 43, 117, 121, 122, 3.2-1 102, 130 3.5-12 56, 130 130 3.2-2 25, 102, 130 3.5-13 56, 130 2.1-5 43, 97, 117, 121 3.3-1 25, 37, 86, 124, 122, 130 130 SAN ONOFRE - UNIT 1 i

AMENDMENT NO. 143

LIST OF EFFECTIVE PAGES (Cont.)

Page Amendment No.

Page Amendment No.

Page Amendment No.

3.5-14 56, 130 3.8-1 25, 36, 37, 3.14-26 130, 131 3.5-15 58, 83, 130 73, 77, 130 3.15-1 79, 130 3.5-16 58, 83, 130 3.8-2 36, 77, 130 3.15-2 79, 90, 91, 3.5-17 58, 83, 130 3.8-3 25, 36, 73, 105, 130 3.5-18 58, 72, 130 77, 130 3.15-3 79, 90, 91, 3.5-19 58, 83, 125, 130 3.8-4 36, 73, 77, 130 105, 130 3.5-20 125, 130 3.8-5 36, 73, 77, 130 3.16-1 79, 130 3.5-21 58, 83, 117, 124, 3.9-1 3, 10, 112, 130 3.16-2 79, 90, 91, 125, 130 3.9-2 3, 10, 112, 130 105, 130 3.5-22 64, 82, 125, 130 3.10-1 7, 8, 112, 122, 3.16-3 79, 90, 91, 3.5-23 58, 82, 125, 130 130 105, 130 3.5-24 58, 82, 125, 130 3.10-2 7, 112, 122, 130 3.16-4 79, 90, 91, 3.5-25 58, 82, 125, 129, 3.11-1 7, 8, 11, 35, 105, 130 130 55, 112, 117, 3.16-5 79, 130 3.5-26 79, 90, 105, 130 122, 130 3.16-6 79, 90, 130 3.5-27 79, 90, 130 3.11-2 7, 11, 112, 3.16-7 79, 90, 130 3.5-28 79, 130 117, 122, 130 3.17-1 79, 90, 91, 3.5-29 79, 90, 105, 130 3.12-1 14, 130 105, 130 3.5-30 79, 90, 130 3.13-1 21, 63, 81, 130 3.17-2 79, 90, 130 3.5-31 79, 90, 130 3.13-2 21, 63, 81, 130 3.18-1 79, 91, 105, 130 3.5-32 83, 130 3.14-1 31, 44, 93, 130, 3.18-2 79, 90, 130 3.5-33 83, 130 131 3.18-3 79, 130 3.5-34 83, 91, 130 3.14-2 31, 130, 131 3.18-4 79, 130 3.6-1 25, 56, 58, 3.14-3 31, 130, 131 3.18-5 79, 130 73, 130 3.14-4 31, 93, 130, 131 3.18-6 79, 130 3.6-2 Change No. 7, 3.14-5 31, 130, 131 3.18-7 79, 91, 105, 130 56, 130 3.14-6 130, 131, 134 3.18-8 79, 90, 130 3.6-3 58, 99, 130 3.14-7 130, 131 3.18-9 79, 90, 105, 130 3.6-4 58, 71, 99, 130 3.14-8 130, 131 3.19-1 79, 90, 105, 130 3.6-5 58, 59, 71, 3.14-9 130, 131 3.20-1 102, 130 99, 130 3.14-10 130, 131 3.20-2 102, 130 3.6-6 58, 59, 83, 130 3.14-11 31, 93, 130, 131 4.0-1 83, 130, 137 3.7-1 25, 52, 68, 84, 3.14-12 31, 130, 131 4.0-2 83, 130, 137 130, 134, 136 3.14-13 31, 130, 131 4.0-3 135 3.7-2 25, 84, 106, 130, 3.14-14 31, 130, 131 4.0-4 135 134, 136 3.14-15 31, 93, 130, 131 4.1-1 29, 56, 83, 3.7-3 25, 84, 130, 134, 3.14-16 31, 130, 131 117, 130 136 3.14-17 31, 130, 131, 134 4.1-la 143 3.7-4 25, 52, 68, 84, 3.14-18 31, 130, 131 4.1-2 7, 22, 83, 106, 130, 134, 136 3.14-19 130, 131 117, 122, 130, 143 3.7-5 25, 52, 68, 84, 3.14-20 130, 131 4.1-3 117, 130 106, 120, 130, 134, 3.14-21 130, 131 4.1-4 25, 29, 70, 136, 143 3.14-22 130, 131 96, 117, 130 3.7-6 134, 136, 143 3.14-23 130, 131 4.1-5 25, 29, 70, 3.7-7 134, 136 3.14-24 130, 131 96, 130 3.7-8 136 3.14-25 130, 131 4.1-6 25, 29, 56, 70, 100, 122, 130, 134 SAN ONOFRE - UNIT 1 ii AMENDMENT NO. 143

LIST OF EFFECTIVE PAGES (Cont.)

Page Amendment No.

Page Amendment No.

Page Amendment No.

4.1-7 25, 29, 36, 4.3-3 24, 58, 87, 118, 4.10-1 13, 94, 130 77, 103, 130 130 4.10-2 13, 94, 130 4.1-8 77, 125, 130 4.3-4 24, 87, 130 4.11-1 14, 109, 130 4.1-9 77, 122, 125, 130 4.3-5 24, 75, 87, 130 4.11-2 14, 109, 130 4.1-10 117, 130 4.3-6 75, 87, 130 4.12-1 91, 130 4.1-11 25, 130 4.3-7 58, 130 4.13-1 18, 113, 4.1-12 Change No. 5, 25, 4.3-8 58, 59, 83, 130 130 130 4.3-9 58, 83, 130 4.14-1 21, 33, 63, 81, 4.1-13 79, 130 4.4-1 Change No. 12, 25, 130 4.1-14 79, 90, 130 56, 82, 84, 95, 4.14-2 21, 63, 81, 130 4.1-15 79, 130 104, 123, 130, 136 4.14-3 21, 63, 81, 130 4.1-16 79, 130 4.4-2 25, 84, 130, 136 4.14-4 21, 63, 81, 105, 4.1-17 79, 90, 130 4.4-3 25, 56, 82, 84, 130 4.1-18 79, 130 117, 130 4.15-1 31, 37, 38, 44, 4.1-19 58, 130 4.4-4 25, 82, 84, 95, 130, 131 4.1-20 58, 130 104, 123, 124, 4.15-2 31, 44, 130, 131 4.1-21 58, 130 130, 134, 136, 143 4.15-3 31, 130, 131 4.1-22 58, 83, 130 4.4-5 84, 130, 136 4.15-4 130, 131 4.1-23 58, 83, 117, 125, 4.4-6 25, 56, 84, 104, 4.15-5 130, 131 130 123, 130, 136 4.15-6 31, 130, 131 4.1-24 58, 109, 130 4.4-7 25, 56, 84, 130, 4.15-7 31, 130, 131 4.1-25 58, 130 134, 136 4.15-8 130, 131 4.1-26 58, 82, 125, 130 4.4-8 136 4.15-9 130, 131 4.1-27 58, 82, 125, 130 4.4-9 136 4.15-10 130, 131 4.1-28 65, 82, 125, 130 4.4-10 136 4.15-11 130, 131 4.1-29 65, 125, 130 4.5-1 Change No. 10, 38, 4.15-12 130, 131 4.1-30 82, 130 79, 130 4.16-1 31, 101, 115, 130, 4.1-31 83, 130 4.5-2 79, 90, 130 133 4.1-32 83, 130 4.5-3 79, 130 4.16-2 37, 101, 115, 130, 4.1-33 83, 130 4.5-4 79, 130 133 4.1-34 119, 130 4.5-5 79, 130 4.16-3 37, 101, 115, 130, 4.1-35 119, 130 4.5-6 79, 130 133 4.2-1 25, 37, 54, 114, 4.6-1 38, 79, 130 4.16-4 37, 55, 101, 115, 130 4.6-2 79, 90, 130 130, 133 4.2-2 25, 37, 114, 130 4.6-3 79, 130 4.16-5 37, 91, 101, 105, 4.2-3 25, 37, 114, 130 4.6-4 79, 130 115, 130, 133 4.2-4 25, 37, 114, 124, 4.6-5 79, 130 4.17-1 79, 130 130 4.6-6 79, 130 4.18-1 79, 130 4.2-5 25, 37, 114, 124, 4.6-7 79, 130 4.18-2 79, 130 130 4.6-8 79, 130 4.18-3 79, 130 4.2-6 37, 114, 130 4.6-9 79, 130 4.18-4 79, 130 4.2-7 NRC order 4.7-1 Change No. 14, 46, 4.18-5 79, 130 4/20/81, 54, 130 130 4.18-6 79, 130 4.3-1 24, 58, 75, 130 4.8-1 91, 130 4.19-1 79, 105, 130 4.3-2 5, 24, 58, 75, 87, 4.9-1 Change No. 14, 130 118, 130 4.9-2 130 SAN ONOFRE - UNIT 1 111 AMENDMENT NO. 143