PNP 2013-021, Response to Request for Additional Information on 2012 Refueling Outage Steam Generator Inspection Report

From kanterella
(Redirected from ML13151A046)
Jump to navigation Jump to search

Response to Request for Additional Information on 2012 Refueling Outage Steam Generator Inspection Report
ML13151A046
Person / Time
Site: Palisades Entergy icon.png
Issue date: 05/28/2013
From: Gustafson O
Entergy Nuclear Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
PNP 2013-021
Download: ML13151A046 (122)


Text

Entergy Entergy Nuclear Operations, Inc.

Palisades Nuclear Plant 27780 Blue Star Memorial Highway Covert, MI 49043-9530 Tel 269 764 2000 Otto W Gustafson Licensing Manager PNP 2013-021 May 28, 2013 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001

SUBJECT:

Response to Request for Additional Information - Palisades Nuclear Plant 2012 Refueling Outage Steam Generator Inspection Report Palisades Nuclear Plant Docket 50-255 License No. DPR-20

References:

1. ENO letter to NRC, PNP 2012-094, "2012 Steam Generator Tube Inspection Report," dated November 1, 2012 (ADAMS Accession Number ML12306A534)
2. NRC e-mail to ENO, "Request for Additional Information - Palisades -

2012 SG Inspection Report - ME9924," dated February 19, 2013 (ADAMS Accession Number ML13051A777)

Dear Sir or Madam:

Entergy Nuclear Operations, Inc. (ENO) submitted Reference 1 to the Nuclear Regulatory Commission (NRC) providing the results of steam generator tube inspections conducted during the 2012 Palisades Nuclear Plant (PNP) refueling outage.

ENO received an electronic request for additional information (RAI) from the NRC in Reference 2. ENO and the NRC held a conference call on March 21, 2013, to clarify the RAI.

Attached is the ENO response to the RAI.

This letter contains no new or revised commitments.

Sincerely, owg/jpm

PNP 2013-021 Page 2 : RAI Response on "Palisades Nuclear Plant Steam Generator Tube Inspection Report for the 2012 Refueling Outage, 1 R22" : Errata Information, "Replacement Information for the Palisades Nuclear Plant Steam Generator Tube Inspection Report for the 2012 Refueling Outage, 1 R22" cc:

Administrator, Region Ill, USNRC Project Manager, Palisades, USNRC Resident Inspector, Palisades, USNRC

Attachment I PALISADES NUCLEAR PLANT STEAM GENERATOR TUBE INSPECTION REPORT FOR THE 2012 REFUELING OUTAGE, 1R22 Request for additional information received by electronic mail February 19, 2013 Nuclear Regulatory Commission (NRC) Request

1. Page 3 states that the Palisades replacement steam generators (RSGs) are in their 2 2 nd sequential inspection period. Table A shows that the RSGs are in their 4 th sequential inspection period. Please clarify.

Entergy Nuclear Operations, Inc (ENO) Response

1. Palisades' replacement steam generators. are in their 4t sequential inspection.

period and therefore Table A is correct. The second paragraph on page 3 of the "Palisades Nuclear Plant Steam Generator Tube Inspection Report for the 2012 Refueling Outage, 1 R22," was revised. The revised wording is provided below and in.Attachment. 2..

"ENO performed a SG inspection in April, 2012 during refueling outage 1R22. This inspection was the 1 4 th in-service inspection (ISI) following SG installation in 1:990 and the 1st of 4 scheduled inspections in the 4 th sequential inspection period. The unit initially entered MODE 4 following this inspection on May 9, 2012."

NRC Request

2.

Table 2 indicates that historical foreign object wear is an active damage mechanism in SG E-50B only, and does not refer to foreign object wear being currently active in either SG E-50A or E-50B. However, Tables 5 and 6 show that three tubes in SG E-50A were plugged in the 2012 refueling outage due to loose part wear. Please clarify.

ENO Response

2.

During the 2012 refueling outage steam generator inspections, the three tubes listed in table 6 for steam generator (SG) E-50A as "LP Preventive Stabilization" were plugged because loose parts could not be retrieved. Even though wear due to these loose parts was not present, the three tubes were plugged as a preventive measure should future wear occur.

To further clarify the 2012 refueling outage inspection results, the following inspection report changes were made:

Page 1 of 4

Two changes were made to Table 2, "Active Damage Mechanisms." The first is that the location "Historical foreign object (FO) wear" was changed to "Loose Part (LP) wear." Second, since historical FO wear, now labeled LP wear, is an active damage mechanism in both E-50A and E-50B, E-50A was added to the LP wear location.

To better categorize the bases for SG tubes plugged in 1 R22, Table 5, "Tube Plugging Summary by Damage Mechanism," was revised to change the row "Wear

- Loose Part" for SG E-50A from "3" to "0." A row was added to the Tube Plugging Summary column labeled "Preventive - Loose Part (LP)" with a "3" in the SG E-50A column.

NRC.Request,

3.

Please. define the acronyms "BED" and "BEL," used in the "Sizing." column. of Table 3.-

ENO Response

3.

ENO will add the acronym definitions for "BED" and "BEL," to the "Palisades Nuclear Plant Steam Generator Tube Inspection Report for the 2012 Refueling Outage, 1 R22," Table 7B, "Acronyms and Abbreviations," see Attachment 2. The definitions that will be added to Table 7B are; "BED" - "Burst Equivalent Depth" and "BEL" - "Burst Equivalent Length."

NRC Request

4. Please discuss the results of the secondary side steam drum and feedring visual inspections performed in SG B.

ENO Response

4.

ENO has revised the "Palisades Nuclear Plant Steam Generator Tube Inspection Report for the 2012 Refueling Outage, 1 R22," which was previously submitted on November 1,2012 (ADAMS Accession Number ML12306A534). The inspection summary section was changed to include a discussion of secondary side steam generator inspection results. See Attachment 2.

Page 2 of 4

NRC Request

5. Please discuss if any tube-to-tube wear was detected this outage.

ENO Response

5. ENO did not detect tube-to-tube wear in SG E-50A or SG E-50B during the 2012 refueling outage. This was documented in Table 5, "Tube Plugging Summary by Damage Mechanism," since zero tubes were plugged in SG E-50A or SG E-50B due to "Wear - Tube to Tube (TBP)."

NRC Request

6. Please discuss any efforts underway (and schedules) to address the NRC staff's comments in its July 17, 2012 letter.

ENO Response

6.

A letter that addresses the NRC staff comments, listed in the NRC letter to ENO, dated July 17, 2012 (ADAMS Accession Number ML12188A578), is planned for submittal to the NRC document control desk on or before June 30, 2013.

NRC Request

7. Please discuss why the tube in Row 51 Column 150 in SG A was preventively plugged.

ENO Response

7.

SG E-50A tube in Row 51, Column 150 was preventively plugged due to a PTE (Partial Tube Expansion) located at the cold leg top of tubesheet. The tube in question was further examined using a plus point rotating pancake coil (RPC) from tube end - cold side (TEC) to top of tubesheet - cold side (TSC) with no degradation detected.

Page 3 of 4

NRC Request

8. Please discuss whether any cracks were detected at historical wear locations, eggcrates, diagonal bars, or vertical straps. Please confirm that all new wear indications were inspected with a rotating probe to characterize the indications.

ENO Response

8.

There were no cracks detected at historical wear locations within, eggcrates, diagonal bars, or vertical straps. ENO has confirmed that all new wear locations were inspected with a plus point rotating pancake coil (RPC) to characterize the indications.

Page 4 of 4

ATTACHMENT 2 ERRATA INFORMATION REPLACEMENT INFORMATION FOR THE PALISADES NUCLEAR PLANT STEAM GENERATOR TUBE INSPECTION REPORT FOR THE 2012 REFUELING OUTAGE, 1R22 Replace the report in its entirety due to page number revisions. Previous report was 111 pages in length. The revised report is 115 pages in length.

Content changes were made to the pages below:

Report Page 3,,

Report Pages 5 and 6 Report Table 2, Report Table. 5 and Report Table 7B Changes to the information submitted in the "Palisades Nuclear Plant Steam Generator Tube Inspection Report for the 2012 Refueling Outage, 1R22 EC 39068" submitted on November 1, 2012, are indicated by vertical lines in the right hand column.

1 of 1

Steam Generator Tube Inspection Report for the 2012 Refueling Outage PALISADES NUCLEAR PLANT STEAM GENERATOR TUBE INSPECTION REPORT for the 2012 REFUELING OUTAGE, 1.R22 EC 44066 May 24, 2013 1

Steam Generator Tube Inspection Report for the 2012 Refueling Outage TABLE OF CONTENTS Inspection Summary 3

Table A Refueling Outage (RFO) Information since Steam Generator Replacement 7

Table 1 Scope and Extent of Tubes Inspected 8

Table 2 Active Damage Mechanisms 8

Table 3 Eddy Current Techniques 10 Table 4A-Location-and Measured Sizes of Service. Induced Indications, 15 Table 4B1 Steam Generator E-50A Indications 18 Table.-4C Steam. Generator E-50B Indications, 72 Table 5 Tube Plugging Summary by Damage Mechanism 1 111 Table 6 Condition Monitoring Results Identification of Tubes Plugged 112 Table 7A Steam Generator Support Structure Nomenclature 114 Table 7B Acronyms and Abbreviations 115 2

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Inspection Summary Palisades Technical Specification (TS) 5.6.8, Steam Generator Tube Inspection Reports, requires Entergy Nuclear Operations, Inc. (ENO), to submit a report to the NRC within 180 days after initial entry into mode 4 following a steam generator inspection performed in accordance with Specification 5.5.8, Steam Generator (SG) Program. The report shall include:

a. The scope of inspections performed on each SG.(Table 1),
b. Active degradation mechanisms found (Table 2),
c. Nondestructive examination techniques utilized for each degradation mechanism (Table 3),
d. Location, orientation (if linear), and measured sizes (if available) of service induced indications (Tables.4A, 48 and 4C),
e. Number of tubes plugged during the& inspection outage, for each active degradation mechanism (Table 5),
f. Total number and percentage of tubes plugged to date (Table-5),
g. The results-of condition monitoring, including the results of tube pulls and in-situ testing, (Table 6), and"
h. The effective tube plugging percentage for, alF~plugging in each SG (Table 5).

ENO performed a SG inspection in April, 2012 during refueling outage 1R22.

This inspection was the 1 4th in-service inspection (ISI) following SG installation in 1990 and the 1st of 4 scheduled inspections in the 4 th sequential inspection period. The unit initially entered MODE 4 following this inspection on May 9, 2012.

The TS section 5.5.8b.1 steam generator tube integrity structural integrity performance criterion was satisfied. The TS section 5.5.8b.2 steam generator tube integrity accident induced leakage performance criterion was satisfied.

Leakage did not exceed the 0.3 gallon per minute (gpm) accident induced leakage limit. Primary-to-secondary leak rate measured using condenser off-gas (Xenon-1 35) was measured at 0.0003 gpm for the start of operating cycle 22, finished at < 0.0001 gpm and had a decreasing trend over the cycle.

No leakage was predicted for either operating or accident conditions for the 2010 to 2012 operating cycle due to observed SG tube degradation in the 2012 refueling outage. All plugs installed were Alloy 690 in the Palisades SGs post-operation and are either Westinghouse ribbed mechanical plugs or Areva mechanically rolled plugs. The Westinghouse plugs are leak-tight for all plant conditions. The Areva roll expansion provides a leak-limiting seal between the plug and tube wall.

3

Steam Generator Tube Inspection Report for the 2012 Refueling Outage The Palisades SGs also contain 308 tubes plugged pre-service in SG E-50A, and 309 tubes plugged pre-service in SG E-50B. Of the tubes plugged pre-service, one tube in SG E-50A and four tubes in SG E-50B are plugged using welded plugs, which are leak tight. The remaining tubes plugged pre-service are plugged using CE Alloy 690 roll plugs. There have been no reported industry events related to corrosion degradation of these Alloy 690 plugs.

Thirty eight tubes were plugged in SG E-50A and eleven tubes in SG E-50B during the 2012 refueling outage. Refer to Tables 5 and 6 for details. No tubes were pulled in either SG. No tubes required in-situ pressure testing.

There were no new damage mechanisms identified in the steam generator eddy current inspection in 2012.

Service Induced Indications Table 4A provides the location and measured. sizes of service induced indications. The majority of these indications are a result of tube indications from outside diameter stress corrosion cracking (ODSCC): The remaining indications were from tube wear by support structures. There is one tube in SG. E-50A Row 51 Column 150 that was removed from service preventively without a service induced indication. There are three tubes in SG E-50A that were removed from service preventively in contact with a loose part at the top of the hot leg tubesheet (TSH) in Row 130 Column 61, Row 132 Column 61, and Row 133 Column 62. These tubes had no wear indications from the loose part but were stabilized and removed from service by tube plugging to prevent issues due to wear from the loose part in the future.

Tables 4B & 4C provide listings of service induced indications with their location, orientation (if linear), and measured sizes. These two tables list all the wear indications for SG E-50A and SG E-50B identified in eddy current testing including those removed from service by tube plugging.

Tube Plugging Summary Table 5 provides a summary of the tubes plugged during 1 R22 for each active degradation mechanism in each steam generator. This table also includes the total number and percentage of tubes plugged to date along with the effective percentage for all plugging in each SG. No repairs other than plugging (e.g.

sleeving) have been performed in the Palisades SGs so the effective plugging is equal to the total plugging. Table 6 provides a list of the individual tubes plugged during 1 R22 with Tables 7A and 7B providing SG support and acronym information.

4

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Tube Pulls and In-Situ Pressure Testing No tubes required in-situ pressure testing per eddy current inspection results in the 2012 refueling outage.

Secondary Side Inspection Results The scope of the secondary side. inspections, during the 2012 refueling outage included the following:

SG A - FOSAR (foreign object search and retrieval) of the annulus and tube lane SG B - FOSAR of the annulus and tube lane; visual inspections of the feedwater ring, J-nozzles and distribution box, cyclone-can separators, chevron dryers and the main steam nozzle.

There was a light, uniform dusting: of loose deposit material throughout the, viewed regions of both steam generators with isolated patches of deeper deposits. From a previous FME inspection, known demister wire was also seen in the viewed areas of the steam generators, predominately in the viewed divider lane regions.

100% bobbin, 100% TTS Hot Leg plus point, and periphery TTS Cold Leg plus point Eddy current testing (ECT) were performed, along with various special interest items as per historical data. Possible Loose Parts (PLP) calls were derived from the ECT analysis and visual inspections.

Annulus and Tube Lane An extensive review of all potential loose parts (PLPs) was performed during 1 R22. There was no tube wear identified due to loose parts.

In SG A, one part at location R102 C29 was removed and three parts at locations R96 C25, R133 C62 and R1l 1 C130, were not. Loose parts at locations R96 C25 and R1 11 C130 were evaluated to leave "as is." The loose part at location R133, 96, also evaluated to leave "as is," resulted in tubes R133 C62, R133 C61, and R130 C61 being preventively plugged and stabilized.

In SG B, three parts at locations R102 C 29, R103 C30 and R64 C123 could not be removed and were evaluated to leave "as-is."

Loose parts evaluated to leave "as-is" was done by comparing the visual inspection results to the eddy current inspection results. Other parameters considered in the evaluation were local velocities, wear, size and history. All parts were minimal in mass or in low velocity areas.

5

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Another item of interest is that PNP SGs have residual deposits of small demister wires. The source of the demister wires were moisture separator reheaters (MSRs) installed prior to 1R21 (Fall 2010). This source has been eliminated with the replacement of the MSRs in 1 R21. The replacement models do not contain demister wire pads. The demister wires that remain are approximately 0.06 inches in diameter and are constructed of 304 stainless. To date there has been no degradation associated with these wires. The wires have been previously evaluated as acceptable for the life of PNP's SGs due to having minimal mass and no tube wear has been associated with the wires.

Reference PNP document, EC-36775, "Steam Generator Potential Loose Parts Evaluation" Steam Drum Visual Inspection SG B steam drum inspection was performed in 1R22. The inspection was accomplished using a Pan Tilt Zoom (PTZ) camera and an 8 mm video probe.

Inspection scope included the feedwater piping ring, supports, distribution box, and selected J nozzles; moisture separator deck, lower access hatch, and a sample population of moisture separator cans; upper dryer deck and deck components.

" Feed ring system; there were no abnormalities noted with the feed ring, J-nozzles, welds or support brackets. Three of the J-nozzles were inspected internally for erosion at the base weld and the mouth of the nozzle. No erosion was observed

  • Separator cans; nine randomly spaced cans were inspected. There were no erosion issues identified. There was a slight amount of corrosion at the base of the cans that was surface related only. There was also a light coating of deposits in the steam drum.

" Upper Steam Drum, two of the upper chevron dryers were removed to provide access to the upper portion of the generator. This section contains the outlets of the chevron separators, the main steam nozzle and the deflection plate. All components were in good condition with no degradation noted.

6

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table A Refueling Outage (RFO) Information since Steam Generator Replacement First Second Third Fourth Outage Cycle Cumulative Inspection Inspection Inspection Inspection Outage Year EFPD EFPY Period ý Period Period Period (EFPMs)'

(EFPMs)

(EFPMs)

(EFPMs) 1R9 1992.

298.5 0.82 9.84 1R10 1993 356.8 1.79 11.72 1R11 1995 430.5 2.97 25.87,

1R12 1996 407.4 4.09 39.25, 1R13

1998, 419.6 5.24 53.04 1R14 1999 449.3 6.47 7.80:

1R15 2001 401.3 7.57 20.98 1R16

2003, 444.3 8.78 35.58, 1R17 2004 493.1 10.13 51.78 1R18 2006 487.9 11.47 7.81 1R19 2007 459.3 12.73 22.90 1R20 2009 499.8 14.09 39.32 1 R21 2010 507.7 15.48 56.00 1R22 2012 504.0 16.84 12.54 EFPD = effective full power days EFPM = effective full power months EFPY = effective full power years 7

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 1 Scope and Extent of Tubes Inspected Scope Probe Type SG E-50A SG E-50B Full LengthO Bobbin

  • 100%

100%

Row 1 through 3 U-bends MRPC 100%

100%

Hot Leg Tubesheets TTS+3"/-1 3.5" MRPC 100%

100%

Cold Leg Outer Three Periphery Tubes TTS+3"/-2" for detection of MRPC 11.3%

11.4%

possible loose parts or wear signals Freespan Dings,> 5.0. Volts between MRPC 100%.

100%

TSH -and TSC, in bothý SGs.

Vertical Strap, Diagonal Bar Dents &

MRPC 100%

100%

Eggcrate Dents > 2.0 Volts Historical Wear-at Eggcrates MRPC.

25%

25%,;

Historical Wear at Diagonal Bars MRPC 25%

25%

and Vertical Straps MRPC_25%_25 Supplemental@

MRPC 100%

100%

Plug Visual N/A 100%

100%

TD Except the bend portion of rows 1 through 3 0 All DNI, DSI, NQI, PLP (Bound MRPC PLPs), PVN and new wear indications.

Table 2 Active Damage Mechanisms SG Location Damage Mechanism E-50A&B Diagonal bar (DB) support wear Wear E-50A&B Vertical strap (VS) support wear Wear E-50A&B Eggcrate (EC) support wear Wear E-50A&B Loose Part (LP) wear Wear Axial outer diameter stress corrosion E-50A&B cracking (ODSCC) at hot leg EC Axial ODSCC intersections E-50B Axial ODSCC at hot leg freespan locations Axial ODSCC (at a ding)

E-50A&B Axial ODSCC at hot leg top-of-tubesheet Axial ODSCC (TTS) locations E-50A&B Circumferential ODSCC at hot leg top-of-Circumferential ODSCC tubesheet (TTS) locations 8

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Nondestructive Examination Techniques Beginning on the next page, Table 3 lists the nondestructive examination techniques utilized for each degradation mechanism.

9

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 3 Degradation Probe EPRI Demonstrated Extended Mechanism Type ETSS Applicability Applicability Detection Sizing Freespan (excluding u-bend), eggcrate, Axial ODSCC Bobbin 128413 sludge pile, &

None Yes No broached TSPs with or without dents <2Vpp Freespan Axial ODSCC Bobbin 24013.1 including dings None Yes No

-55v Foreign object Foreign wear Extended for Object Wear Bobbin 27091.2 (part not Yes CMOA present); 1-690 1-600 tubing tubing AVBs, TSPs, Support Wear Bobbin 96004.1 vertical and None Yes CMOA diagonal straps Freespan in the Pitting Bobbin 96005.2 presence of Sludge Pile Yes CMOA copper TSP (with or

+28424 without dents BED: CMOA Axial ODSCC TM (detect);

<=2vpp) and None Yes Axial ODSCC pM 128431 (sizing) sludge pile BEL: CMOA 10

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 3 Eddy Current Technique Palisades 1 R22 Degradation Probe EPRI Demonstrated Extended Mechanism Type ETSS Applicability Applicability Freespan 128425 (excluding u-

+Point (detect) bend), eggcrate, BED: CMOA Axial ODSCC TM

& broached None Yes 128432 TSPs with or BEL: CMOA (sizing) without dents

<2Vpp Axial ODSCC t

10411.1 Low Row U-Higher Row Yes CMOA TM bends U-bends Support structures, PDA: Information

+Point 21409.1

freespan, U-bends Yes Axial ODSCC TM sludge pile, &

ILength:

tubesheet Information crevice Freespan Depth:

Axial ODSCC

+Point 22401.1 Dented TSPs dings &

Yes Information dented AVBs Length: CMOA Tubesheet &

PDA: Information Axial PWSCC TM 20511.1 Transitions non-dented Yes supports Length: CMOA CMOA Axial PWSCC t

Low Row U-Higher Row Yes

+PonTM 96511.2 bends U-bends 11

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 3 Current Technique Demonstrated Applicability I

12

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 3 Eddv Current Techniaue Palisades 1R22 Degradation Probe EPRI Demonstrated Extended Mechanism Type ETSS Applicability Applicability Axial ODSCC MHI bends in Higher

+PointTM will be Axial ODSCC Intellige 10415.1 (ETSS used Row Yes used for sizing nt Array Rows U-bends and Rows 3-5)

AVB Wear MHI 23514.1, Low Row U-Higher Row

+Point TM will be Axial PWSCC Intellige 23514.2, bends U-bends Yes used for sizing nt Array 23514.3 MHI 23514.1, Low Row U-Higher Row

+Point TM will be Circ PWSCC Intellige 23514.2, bends U-bends Yes used for sizing nt Array 23514.3 Both: CMOA Ghent**

20407.1, Support Avg. Depth/

Axial ODSCC 20407.2 structures &

None Yes Length applies to freespan technique 20407.1 CMOA Axial PWSCC Ghent**

20508.1, Expansion None Yes Length applies to 20508.2 Transitions technique 20508.1 Not qualified Axial PWSCC Ghent**

20509.1 Dented support None Yes structures 13

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 3 Eddy Current Technique Palisades 1 R22 Degradation Probe EPRI Demonstrated Extended Mechanism Type ETSS Applicability Applicability CMOA Top of Circ ODSCC Ghent**

20406.1 tubesheet &

None Yes Depth/ Length/

20406.2 expansion PDA apply to transitions technique 20406.1 Circ PWSCC Ghent**

20507.1 Expansion None Yes CMOA Transitions

  • There are multiple ETSSs available for depth sizing of foreign object wear, each depending on the shape of the wear scar and the coil being used. If foreign object wear (with no part present) is reported, an appropriate +Point TM or pancake coil technique will be selected for performing CMOA. The associated NDE uncertainties and CMOA limits will be documented in the CMOA report.
    • The Ghent probe will only be used if needed for clarification of the eddy current response or for additional sizing information associated with unusual or unexpected indications.

14

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4A Location and Measured Sizes of Service Induced Indications Axial ODSCC Indications

+Point Maximum Structural 300 kHz Depth Axial Structural Depth Amplitu

(%TW)

Length Length (in)

(%TW)

SG Row Col Location de (Vpp)

(Note 1)

(in)

(Note 1)

(Note 1)

SGA 75 96 TSH +0.59 0.36 49.99 0.28 0.22 42.7 SGA 78 91 TSH +0.88 0.39 49.76 0.28 0.16 46.2 SGA 80 89 TSH +0.37 0.47 52.14 0.33 0.22 45.8 SGA 80 93 TSH +0.61 0.29 42.21 0.21 0.12 36.0 SGA 80 95 TSH +0.65 0.64 59.64 0.31 0.18 53.4 SGA 83 94 TSH +0.57 0.44 51.10 0.27 0.27 43.6 SGA 3

52 01H -0.47 0.25 35.35 0.48 0.39 30.9 SGA 4

17 03H +0.78 0.24 37.26 0.57 0.21 31.5 SGA 4

109 02H -0.24 0.22 34.85 0.27 0.15 27.4 SGA 5

24 01H -0.78 0.36 45.43 0.33 0.27 40.4 SGA 5

24 01H -0.33 0.29 40.22 0.76 0.54 37.0 SGA 6

107 01H -0.83 0.33 44.48 0.69 0.39 41.0 SGA 6

107 01H +0.86 0.15 26.12 0.30 0.18 23.0 SGA 9

52 01H -0.16 0.26 35.35 1.70 1.29 30.3 SGA 10 57 01H -0.44 0.31 40.99 0.94 0.75 30.6 SGA 10 59 01H -0.44 0.21 34.85 0.60 0.42 28.7 SGA 10 111 02H -0.43 0.32 41.37 0.90 0.47 36.8 SGA 11 126 02H -0.03 0.31 44.8 1.34 0.84 40.4 SGA 12 57 01H -0.64 0.61 57.30 0.73 0.36 44.3 SGA 15 132 01H +0.73 0.28 43.16 0.42 0.24 34.5 SGA 19 118 01H -0.58 0.34 47.75 1.01 0.74 42.2 SGA 21 108 01H +0.95 0.26 39.81 0.66 0.41 30.1 15

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4A Location and Measured Sizes of Service Induced Indications

+Point Maximum Structural 300 kHz Depth Axial Structural Depth Amplitu

(%TW)

Length Length (in)

(%TW)

SG Row Col Location de (Vpp)

(Note 1)

(in)

(Note 1)

(Note 1)

SGA 23 106 04H -0.19 0.28 41.37 0.57 0.33 34.6 SGA 25 106 01H +0.01 0.34 44.16 1.05 0.56 40.0 SGA 29 108 01H +0.53 0.29 40.99 0.99 0.44 34.4 SGA 29 108 03H +0.88 0.24 37.26 0.93 0.50 28.8 SGA 48 103 01H +0.18 0.29 39.41 0.42 0.27 33.9 SGA 80 83 01H +0.85 0.23 32.13 0.51 0.30 26.8 SGA 92 83 01H -0.29 0.38 45.12 1.66 0.87 35.3 SGA 92 121 02H +0.55 0.23 37.26 0.92 0.39 32.0 SGA 100 93 01H +0.26 0.23 37.26 0.67 0.42 31.9 SGA 110 85 01H -0.63 0.18 33.80 0.94 0.81 29.8 SGB 24 47 TSH +0.97 0.71 62.36 0.58 0.48 49.3 SGB 26 47 TSH +0.42 0.44 53.87 0.33 0.24 47.2 SGB 74 101 TSH +0.57 0.23 41.84 0.24 0.09 39.2 SGB 75 100 TSH +0.66 0.53 54.92 0.33 0.21 47.4 SGB 2

39 01H -11.12 0.33 43.83 0.21 0.12 39.0 SGB 24 55 01H -0.44 0.42 48.29 0.66 0.36 38.2 SGB 74 87 01H +0.14 0.21 35.35 0.84 0.66 27.0 SGB 77 112 01H -0.45 0.23 39.41 0.96 0.36 32.4 SGB 80 25 05H -0.88 0.20 32.70 0.30 0.21 29.0 SGB 122 85 01H -0.21 0.30 41.37 0.86 0.39 37.3 Note 1: The maximum depth, structural depth, and structural length values reported in this table reflect the effect of the Entergy Appendix I deviation from the EPRI PWR NDE Guidelines.

16

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4A Location and Measured Sizes of Service Induced Indications Circumferential ODSCC Indications

+Point 300 kHz Ro Amplitude Maximum Circumferential SG w

Col Location (Vpp)

Depth (%TW)

Length (deg)

SGA 28 53 TSH +0.34 0.34 77 32 SGA 91 62 TSH -0.11 0.28 56 32 SGA 103 68 TSH +0.13 0.36 70 108 SGB 97 126 TSH +0.16 0.16 67 53 17

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

SIG Row Column Depth Location Elevation Status 1

A 1

2 11 02H 0.8

<TS 2

A 1

2 13 04C

-0.87

<TS 3

A 1

128 11 02C 0.85

<TS 4

A 1

136 15 02H

-0.87

<TS 5

A 1

140 8

DBH

-1.3

<TS 6

A 1

150 22 02C 0.88

<TS 7

A 1

150 12 01C

-0.17

<TS 8

A 1

162 13 01C 0.87

<TS 9

A 2

7 11 02H 0.83

<TS 10 A

2 9

11 02C

-0.91

<TS 11 A

2 31 13 03H 0.87

<TS 12 A

2 127 20 05C 0.53

<TS 13 A

2 127 12 DBH 1.2

<TS 14 A

2 159 13 03C

-0.13

<TS 15 A

3 128 15 02C 0.82

<TS 16 A

3 144 13 04H 0.88

<TS 17 A

3 164 11 03H

-0.93

<TS 18 A

3 164 15 02C 0.84

<TS 19 A

4 115 11 04C 0.89

<TS 20 A

4 137 13 02C 0.81

<TS 21 A

4 157 14 02C 0.84

<TS 22 A

4 157 11 02C

-0.13

<TS 23 A

5 38 13 03H 0.84

<TS 24 A

5 130 10 02C 0.88

<TS 25 A

5 132 9

03C

-0.89

<TS 26 A

6 131 8

02H

-0.19

<TS 27 A

6 147 10 04H

-0.85

<TS 28 A

8 161 11 02C

-0.83

<TS 29 A

9 2

21 02C 0.17

<TS 30 A

9 4

10 02C

-0.1

<TS 31 A

9 32 15 DBC 1.21

<TS 32 A

10 7

13 02C 0.84

<TS 33 A

10 21 12 04H 0.92

<TS 34 A

10 29 13 02H 0.82

<TS 35 A

10 39 14 05H 0

<TS 36 A

11 4

8 02C

-0.13

<TS 37 A

11 146 15 03C 0.83

<TS 38 A

12 3

14 02C 0.8

<TS 39 A

12 7

10 02C

-0.9

<TS 40 A

12 57 10 04H 0.91

<TS 41 A

12 133 10 03C 0.15

<TS 42 A

12 137 9

02H

-0.78

<TS 43 A

12 159 13 05H 0.95

<TS 18

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 44 A

13 2

22 02H 0.86

<TS 45 A

13 2

14 02H

-0.86

<TS 46 A

13 4

15 02C 0.88

<TS 47 A

13 8

10 03C 0.81

<TS 48 A

13 8

10 02C

-0.25

<TS 49 A

13 34 20 03C

-0.94

<TS 50 A

13 36 15 05C 0.78

<TS 51 A

13 158 8

03H 0.8

<TS 52 A

14 3

28 02C 0.97

<TS 53 A

14 59 19 05H 0.76

<TS 54 A

14 59 13 02H 0.92

<TS 55 A

15 2

9 03C

-0.15

<TS 56 A

15 14 10 05C 0.88

<TS 57 A

15 36 9

02C

-0.89

<TS 58 A

15 62 13 04C

-0.13

<TS 59 A

15 156 9

03H

-0.19

<TS 60 A

16 9

10 03C 0.8

<TS 61 A

16 11 10 02H

-0.85

<TS 62 A

17 2

9 04H 0.77

<TS 63 A

17 58 13 02C 0.84

<TS 64 A

17 60 13 02C

-0.8

<TS 65 A

18 3

14 02H 0.82

<TS 66 A

18 3

13 02H

-0.86

<TS 67 A

18 59 10 02H 0.88

<TS 68 A

19 112 12 04C 0.86

<TS 69 A

19 144 13 04C 0.91

<TS 70 A

20 3

10 02C

-0.82

<TS 71 A

20 55 10 02C 0.77

<TS 72 A

20 57 10 02H 0.89

<TS 73 A

20 59 7

03C

-0.86

<TS 74 A

20 103 12 04H

-0.18

<TS 75 A

20 163 10 02C 0.13

<TS 76 A

20 163 13 02C 0.9

<TS 77 A

21 2

12 04H 0.87

<TS 78 A

21 60 9

04C

-0.91

<TS 79 A

21 64 13 DBH

-1.85

<TS 80 A

21 114 12 02H 0.09

<TS 81 A

21 114 10 02H 0.9

<TS 82 A

22 9

13 02C

-0.91

<TS 83 A

22 159 16 02H 0.93

<TS 84 A

22 161 7

02H 0.88

<TS 85 A

22 163 11 02H

-0.85

<TS 86 A

23 4

15 02C

-0.84

<TS 87 A

23 40 17 VS4 0.89

<TS 19

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 88 A

23 40 21 VS4

-1.03

<TS 89 A

23 58 12 04C 0.86

<TS 90 A

23 60 11 02H

-0.86

<TS 91 A

23 62 20 02C 0.85

<TS 92 A

23 104 11 03C

-0.75

<TS 93 A

23 104 7

03C 0.13

<TS 94 A

24 33 9

01H 0.86

<TS 95 A

24 41 12 VS4

-1.01

<TS 96 A

24 61 13 03C

-0.89

<TS 97 A

24 161 14 02C

-0.93

<TS 98 A

24 161 18 02C 0.94

<TS 99 A

24 163 23 02C 0.93

<TS 100 A

25 56 10 03C

-0.86

<TS 101 A

25 60 10 03C 0.84

<TS 102 A

25 106 10 03C 0.17

<TS 103 A

25 110 16 04C 0.94

<TS 104 A

26 3

18 02C

-0.89

<TS 105 A

26 5

14 02H

-0.84

<TS 106 A

26 5

14 02H

-0.14

<TS 107 A

26 51 13 02H 0.92

<TS 108 A

26 121 11 VS4

-0.88

<TS 109 A

26 125 10 VS4 0.27

<TS 110 A

26 161 14 03H 0.87

<TS 111 A

26 163 16 01H 0.89

<TS 112 A

27 6

10 02H

-0.78

<TS 113 A

27 10 9

05H

-0.15

<TS 114 A

27 10 11 05H 1.03

<TS 115 A

27 58 15 02H 0.79

<TS 116 A

28 3

12 02C

-0.97

<TS 117 A

28 19 20 VS4

-1.13

<TS 118 A

28 31 20 VS4

-0.96

<TS 119 A

28 43 8

VS4

-1.03

<TS 120 A

28 53 19 02H 0.9

<TS 121 A

28 53 20 VS4

-0.96

<TS 122 A

28 63 15 05H 0.64

<TS 123 A

28 63 21 VS4

-1.12

<TS 124 A

28 105 15 03C 0.19

<TS 125 A

28 161 12 01H

-0.9

<TS 126 A

29 64 9

05H 0.77

<TS 127 A

29 122 10 02H 0.84

<TS 128 A

29 162 13 01H

-0.81

<TS 129 A

30 35 12 02H 0.84

<TS 130 A

30 55 9

03H 0.89

<TS 131 A

30 57 14 04H 0.92

<TS 20

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

SIG Row Column Depth Location Elevation Status 132 A

30 59 11 04C 0.9

<TS 133 A

30 59 15 02C

-0.92

<TS 134 A

31 4

13 02H

-0.87

<TS 135 A

31 16 28 VS4 0.88

<TS 136 A

31 42 9

02C 0.87

<TS 137 A

31 44 13 02C 0.89

<TS 138 A

31 60 13 02H 0.91

<TS 139 A

32 7

19 02C

-0.91

<TS 140 A

32 37 10 03H 0.13

<TS 141 A

32 37 15 03H 0.86

<TS 142 A

32 59 18 DBH 0.39

<TS 143 A

32 109 9

VS4

-0.28

<TS 144 A

32 145 17 VS4

-0.99

<TS 145 A

32 161 15 03H

-0.18

<TS 146 A

33 38 14 03H

-0.82

<TS 147 A

33 46 14 02H 0.86

<TS 148 A

33 48 11 02H 0.86

<TS 149 A

33 58 9

04H 0.84

<TS 150 A

33 62 11 04C

-0.78

<TS 151 A

33 116 11 03H 0.86

<TS 152 A

33 116 13 02H

-0.85

<TS 153 A

33 124 17 03C 0.99

<TS 154 A

34 37 13 04H 0.83

<TS 155 A

34 39 12 02H 0.87

<TS 156 A

34 43 17 VS4

-0.77

<TS 157 A

34 57 13 04H 0.88

<TS 158 A

34 57 13 04C 0.89

<TS 159 A

34 59 10 04H 0.87

<TS 160 A

34 59 9

04H

-0.06

<TS 161 A

34 63 13 DBC 1.59

<TS 162 A

34 63 12 04C 0.96

<TS 163 A

34 109 15 04H 0.88

<TS 164 A

34 117 13 03C

-0.9

<TS 165 A

34 119 11 03H 0.91

<TS 166 A

34 121 12 03C 0.9

<TS 167 A

34 131 11 05C

-0.19

<TS 168 A

35 48 12 02C

-0.83

<TS 169 A

35 48 15 03C

-0.85

<TS 170 A

36 49 13 02C

-0.92

<TS 171 A

36 59 10 03H 0.86

<TS 172 A

36 61 15 04H

-0.22

<TS 173 A

36 105 16 02C 0.91

<TS 174 A

36 109 8

VS4 0.04

<TS 175 A

36 117 15 02H 0.9

<TS 21

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 176 A

36 117 11 03C 0.18

<TS 177 A

37 6

15 02C

-0.84

<TS 178 A

37 6

10 02C 0.87

<TS 179 A

37 24 13 05C 0.77

<TS 180 A

37 30 11 05H 0.91

<TS 181 A

37 30 6

05H

-0.95

<TS 182 A

37 34 13 04H 0.9

<TS 183 A

37 36 9

04H

-0.94

<TS 184 A

37 36 11 04H

-0.24

<TS 185 A

37 38 19 03C 0.92

<TS 186 A

37 42 13 02H 0.87

<TS 187 A

37 48 11 04H

-0.81

<TS 188 A

37 50 16 04H 0.83

<TS 189 A

37 50 8

04H

-0.94

<TS 190 A

37 50 10 04C 0.2

<TS 191 A

37 52 14 04C

-0.9

<TS 192 A

37 56 22 04H 0.84

<TS 193 A

37 56 12 05H 0.92

<TS 194 A

37 56 14 05C

-0.02

<TS 195 A

37 56 11 04C

-0.93

<TS 196 A

37 60 12 03H

-0.85

<TS 197 A

37 62 19 04H 0.9

<TS 198 A

37 62 15 05H

-0.85

<TS 199 A

37 106 15 03C

-0.77

<TS 200 A

37 116 15 03C 0.92

<TS 201 A

37 134 10 05H 0.97

<TS 202 A

38 11 10 05H 0.98

<TS 203 A

38 13 12 05C 0.9

<TS 204 A

38 17 19 05H

-0.17

<TS 205 A

38 35 24 03H 0.93

<TS 206 A

38 35 28 04H 0.93

<TS 207 A

38 35 16 05H 0.13

<TS 208 A

38 35 19 05H 0.96

<TS 209 A

38 39 12 02C 0.81

<TS 210 A

38 45 15 03C

-0.89

<TS 211 A

38 47 16 02H 0.87

<TS 212 A

38 47 11 03C

-0.15

<TS 213 A

38 51 33 04C 0.9

<TS 214 A

38 53 13 04H 0.91

<TS 215 A

38 53 14 05C

-0.92

<TS 216 A

38 59 17 04H 0.92

<TS 217 A

38 59 15 05H

-0.17

<TS 218 A

38 61 9

04H

-0.09

<TS 219 A

38 115 13 02C 0.9

<TS 22

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 220 A

38 115 7

02C

-0.58

<TS 221 A

38 119 13 02C 0.9

<TS 222 A

38 123 8

02C

-0.88

<TS 223 A

38 127 15 03H 0.89

<TS 224 A

39 14 14 05H

-0.17

<TS 225 A

39 26 9

04H 0.94

<TS 226 A

39 36 13 05H

-0.83

<TS 227 A

39 40 12 02H 0.93

<TS 228 A

39 42 13 04H

-0.85

<TS 229 A

39 42 17 03C

-0.87

<TS 230 A

39 46 14 04H

-0.95

<TS 231 A

39 58 17 04H

-0.84

<TS 232 A

39 62 15 05H 0.95

<TS 233 A

39 62 12 05H 0.18

<TS 234 A

39 104 15 02C

-0.13

<TS 235 A

39 104 17 03C

-0.81

<TS 236 A

39 104 15 04H 0.83

<TS 237 A

39 106 8

03C

-0.24

<TS 238 A

39 112 14 02C 0.77

<TS 239 A

39 120 17 04H 0.9

<TS 240 A

39 126 16 03C 0.9

<TS 241 A

40 5

11 01C

-0.92

<TS 242 A

40 7

13 02C 0.81

<TS 243 A

40 35 12 04H 0.9

<TS 244 A

40 35 11 02C 0.13

<TS 245 A

40 49 10 04H 0.86

<TS 246 A

40 51 12 03H

-0.81

<TS 247 A

40 51 10 03C 0.86

<TS 248 A

40 51 10 04H 0.92

<TS 249 A

40 57 8

03H 0.96

<TS 250 A

40 59 17 05H 0.98

<TS 251 A

40 117 19 03C

-0.48

<TS 252 A

40 125 9

02C 0.91

<TS 253 A

40 161 15 01H 0.87

<TS 254 A

41 6

14 02C

-0.13

<TS 255 A

41 8

12 02C

-0.15

<TS 256 A

41 16 16 05H

-0.84

<TS 257 A

41 20 12 05H 0.88

<TS 258 A

41 22 11 05H

-0.92

<TS 259 A

41 34 14 03H

-0.87

<TS 260 A

41 40 7

05C

-0.11

<TS 261 A

41 44 10 05C

-0.88

<TS 262 A

41 44 13 03C

-0.92

<TS 263 A

41 50 12 02C

-0.84

<TS 23

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 264 A

41 52 11 03H 0.81

<TS 265 A

41 52 28 VS4

-0.98

<TS 266 A

41 54 12 04C

-0.86

<TS 267 A

41 60 24 05H 0.96

<TS 268 A

41 60 9

04H 0.94

<TS 269 A

41 64 11 04H 0.97

<TS 270 A

41 108 13 03C 0.88

<TS 271 A

41 120 5

03C 0.87

<TS 272 A

41 126 16 02C

-0.85

<TS 273 A

41 160 15 01H 0.91

<TS 274 A

41 160 10 03C

-0.17

<TS 275 A

41 160 9

03C 0.86

<TS 276 A

42 5

11 VS4

-0.8

<TS 277 A

42 5

15 02H 0.95

<TS 278 A

42 5

14 VS4 0

<TS 279 A

42 7

24 02C 0.87

<TS 280 A

42 7

9 02C 0.07

<TS 281 A

42 33 10 DBH

-1.91

<TS 282 A

42 35 16 05C 0.9

<TS 283 A

42 43 23 04H 0.81

<TS 284 A

42 43 10 03C 0.96

<TS 285 A

42 45 15 02H 0.91

<TS 286 A

42 45 12 04H 0.89

<TS 287 A

42 55 10 03H

-0.96

<TS 288 A

42 55 8

03H

-0.11

<TS 289 A

42 57 15 03H 0.88

<TS 290 A

42 59 18 04H 0.82

<TS 291 A

42 63 10 02H 0.83

<TS 292 A

42 117 14 02C 0.9

<TS 293 A

43 44 14 04C 0.85

<TS 294 A

43 46 19 03H

-0.53

<TS 295 A

43 46 33 VS4

-0.92

<TS 296 A

43 46 11 VS4

-0.2

<TS 297 A

43 46 19 VS4 0.83

<TS 298 A

43 46 10 VS4

-1.2

<TS 299 A

43 46 15 DBH 0.11

<TS 300 A

43 52 11 03H

-0.89

<TS 301 A

43 60 14 VS4 0.61

<TS 302 A

43 106 13 03C 0.93

<TS 303 A

43 126 29 VS4 0.79

<TS 304 A

44 15 13 DBH

-1.34

<TS 305 A

44 37 12 05C

-0.9

<TS 306 A

44 41 20 VS4

-0.4

<TS 307 A

44 49 20 04H 0.84

<TS 24

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 308 A

44 49 23 05C

-0.9

<TS 309 A

44 59 11 03H 0.92

<TS 310 A

44 109 14 03C 0.11

<TS 311 A

44 123 16 06H

-0.07

<TS 312 A

44 127 18 03C

-0.13

<TS 313 A

44 127 13 03C

-0.96

<TS 314 A

44 129 11 03C 0.9

<TS 315 A

44 131 17 05C 0.79

<TS 316 A

44 143 12 05C 0.89

<TS 317 A

45 30 14 04H

-0.92

<TS 318 A

45 30 9

04H

-0.21

<TS 319 A

45 52 14 03H 0.9

<TS 320 A

45 60 13 04H 0.94

<TS 321 A

45 60 10 06H 0.42

<TS 322 A

45 62 10 05H 0.96

<TS 323 A

45 104 19 02C 0.74

<TS 324 A

45 104 18 03C 0.85

<TS 325 A

45 108 21 03C 0.89

<TS 326 A

45 122 14 03C

-0.92

<TS 327 A

45 124 11 02C

-0.9

<TS 328 A

45 128 8

03H

-0.11

<TS 329 A

45 132 13 03C

-0.88

<TS 330 A

45 134 16 03C 0.88

<TS 331 A

46 7

15 06H 1.65

<TS 332 A

46 17 13 VS4

-0.13

<TS 333 A

46 37 15 03H 0.87

<TS 334 A

46 41 13 04H 0.95

<TS 335 A

46 47 15 02H 0.93

<TS 336 A

46 51 17 03H 0.87

<TS 337 A

46 57 17 VS4 0.86

<TS 338 A

46 69 18 VS4

-0.71

<TS 339 A

46 111 10 02C 0.83

<TS 340 A

46 111 7

02C

-1.12

<TS 341 A

46 127 8

02C 0.79

<TS 342 A

46 141 16 04C 0.92

<TS 343 A

47 8

19 01H

-0.83

<TS 344 A

47 12 15 DBC 1.75

<TS 345 A

47 24 14 04H

-0.83

<TS 346 A

47 24 14 VS4 0.74

<TS 347 A

47 34 15 03C 0.91

<TS 348 A

47 70 14 04H 0.92

<TS 349 A

47 112 16 02C 0.83

<TS 350 A

47 126 10 04C 0.07

<TS 351 A

48 7

26 01C 0.86

<TS 25

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 352 A

48 19 13 05H

-0.84

<TS 353 A

48 21 24 VS4

-1.02

<TS 354 A

48 29 17 04H 0.83

<TS 355 A

48 29 20 03C 0.85

<TS 356 A

48 37 12 06H 0.97

<TS 357 A

48 39 10 04H

-0.92

<TS 358 A

48 41 38 VS4

-0.99

<TS 359 A

48 41 19 VS4 0.9

<TS 360 A

48 43 12 02H 0.92

<TS 361 A

48 45 11 06H 0.92

<TS 362 A

48 53 11 VS4

-0.88

<TS 363 A

48 55 15 04H 0.84

<TS 364 A

48 69 33 VS4 0.83

<TS 365 A

48 69 12 VS4

-0.83

<TS 366 A

48 111 13 02C 0.93

<TS 367 A

48 125 20 02C 0.83

<TS 368 A

48 125 16 02C 0.11

<TS 369 A

48 159 15 01H 0

<TS 370 A

48 159 10 01H

-0.9

<TS 371 A

48 159 12 01H 0.81

<TS 372 A

49 10 18 VS4 1.02

<TS 373 A

49 16 15 02C

-0.94

<TS 374 A

49 20 26 VS4

-0.96

<TS 375 A

49 20 22 VS4 1.11

<TS 376 A

49 24 13 VS4

-1.03

<TS 377 A

49 28 16 03C 0.87

<TS 378 A

49 30 8

DBC 1.75

<TS 379 A

49 32 8

DBC 1.33

<TS 380 A

49 36 15 03C 0.83

<TS 381 A

49 66 19 VS4 0.69

<TS 382 A

49 66 21 VS4 0.04

<TS 383 A

49 68 10 04H

-0.11

<TS 384 A

49 70 14 DBC 2

<TS 385 A

49 70 2

DBC

-2

<TS 386 A

49 74 11 DBC 1.9

<TS 387 A

49 92 18 03C

-0.9

<TS 388 A

49 92 21 DBC 1.75

<TS 389 A

49 94 13 02C 0.81

<TS 390 A

49 94 16 03C 0.14

<TS 391 A

49 94 14 VS4 0.7

<TS 392 A

49 96 15 02C

-0.83

<TS 393 A

49 96 19 03C 0.87

<TS 394 A

49 98 9

03C 0.91

<TS 395 A

49 98 11 02C 0.92

<TS 26

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 396 A

49 112 12 VS4

-0.67

<TS 397 A

49 112 18 VS4

-0.24

<TS 398 A

49 122 8

04C 0.86

<TS 399 A

49 122 11 04C

-0.92

<TS 400 A

49 132 13 02C 0.81

<TS 401 A

49 134 10 03C

-0.2

<TS 402 A

49 138 9

04H

-0.85

<TS 403 A

49 138 7

04H

-0.15

<TS 404 A

49 158 8

01H 0.85

<TS 405 A

50 29 8

05H 0.91

<TS 406 A

50 29 12 04C 0.94

<TS 407 A

50 39 13 04H 0.98

<TS 408 A

50 45 15 03H 0.84

<TS 409 A

50 45 15 VS5

-0.83

<TS 410 A

50 49 11 05H

-0.8

<TS 411 A

50 51 15 03H 0.89

<TS 412 A

50 53 12 04H 0.84

<TS 413 A

50 55 11 05H 1.02

<TS 414 A

50 57 14 05H 1.01

<TS 415 A

50 65 18 02H

-0.96

<TS 416 A

50 71 10 03H 0.74

<TS 417 A

50 91 15 VS4 0.73

<TS 418 A

50 97 17 02C 0.91

<TS 419 A

50 105 11 04C

-0.9

<TS 420 A

50 115 9

03C

-0.92

<TS 421 A

50 123 17 04C 0.09

<TS 422 A

50 127 7

03C 0.18

<TS 423 A

50 127 11 03C

-0.9

<TS 424 A

50 157 19 VS3 0.84

<TS 425 A

50 157 33 VS3

-0.97

<TS 426 A

51 20 15 VS5

-0.07

<TS 427 A

51 24 12 02C

-0.93

<TS 428 A

51 30 11 06H

-0.89

<TS 429 A

51 38 12 04H

-0.91

<TS 430 A

51 40 15 04C 0.79

<TS 431 A

51 54 14 04H 0.88

<TS 432 A

51 60 12 04H 0.91

<TS 433 A

51 64 13 05H 0.9

<TS 434 A

51 66 13 05H 0.85

<TS 435 A

51 66 8

04H

-0.98

<TS 436 A

51 70 12 05H 0.96

<TS 437 A

51 90 21 04C

-0.44

<TS 438 A

51 92 17 02C 0.87

<TS 439 A

51 102 17 03C 0.06

<TS 27

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 440 A

51 104 10 04C

-0.81

<TS 441 A

51 108 9

03C

-0.95

<TS 442 A

51 116 9

05H 0.92

<TS 443 A

51 116 8

04C

-0.33

<TS 444 A

51 118 19 02C

-0.85

<TS 445 A

51 122 16 02C

-0.15

<TS 446 A

51 124 12 04C

-0.9

<TS 447 A

51 126 11 03C

-0.89

<TS 448 A

51 126 6

03C 0.85

<TS 449 A

51 126 18 02C 0.11

<TS 450 A

51 126 10 02C 0.85

<TS 451 A

51 134 8

04C 0.15

<TS 452 A

51 134 6

04C 0.88

<TS 453 A

51 154 13 VS3

-0.79

<TS 454 A

52 9

9 01C

-0.8

<TS 455 A

52 19 9

06H

-0.02

<TS 456 A

52 25 9

04H 0.97

<TS 457 A

52 31 17 03C 0.9

<TS 458 A

52 33' 12 06H 0.81

<TS 459 A

52 53 11 03H 0.92

<TS 460 A

52 55 15 03H

-0.84

<TS 461 A

52 89 13 03C 0.92

<TS 462 A

52 89 17 06C 0.9

<TS 463 A

52 91 14 05H

-0.88

<TS 464 A

52 97 17 02C

-0.95

<TS 465 A

52 97 15 VS5

-0.74

<TS 466 A

52 109 10 04C

-0.98

<TS 467 A

52 111 18 02C 0.91

<TS 468 A

52 115 8

04C

-0.77

<TS 469 A

52 117 22 02C 0.89

<TS 470 A

52 149 8

VS4

-0.83

<TS 471 A

52 149 15 VS3 0.94

<TS 472 A

53 10 14 01H

-0.86

<TS 473 A

53

'10 17 01C

-0.93

<TS 474 A

53 10 10 01C

-0.17

<TS 475 A

53 52 10 04H

-0.9

<TS 476 A

53 56 15 03H 0.9

<TS 477 A

53 80 13 03H 0.99

<TS 478 A

53 80 10 03H

-0.95

<TS 479 A

53 80 12 02H

-0.85

<TS 480 A

53 88 15 03C

-0.94

<TS 481 A

53 90 18 03C 0.57

<TS 482 A

53 92 20 03C 0.9

<TS 483 A

53 94 15 03C 0.1

<TS 28

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 484 A

53 94 12 03C 0.91

<TS 485 A

53 94 12 04C 0.91

<TS 486 A

53 104 17 03C 0.92

<TS 487 A

53 112 10 04C

-0.91

<TS 488 A

53 118 11 02C 0.83

<TS 489 A

53 122 4

04C

-0.86

<TS 490 A

53 122 18 02C

-0.11

<TS 491 A

53 122 8

04C 0.88

<TS 492 A

53 136 5

DBC 1.82

<TS 493 A

53 142 9

03C 0.46

<TS 494 A

54 21 10 06H

-0.11

<TS 495 A

54 23 12 03H 0.97

<TS 496 A

54 29 18 02C 0.83

<TS 497 A

54 33 11 03H 0.88

<TS 498 A

54 39 16 03H 0.91

<TS 499 A

54 39 11 05H 0.91

<TS 500 A

54 63 13 02H 0.94

<TS 501 A

54 83 14 04H

-0.11

<TS 502 A

54 83 20 03H 0.84

<TS 503 A

54 93 17 02C 0.94

<TS 504 A

54 93 12 03C 0.89

<TS 505 A

54 93 11 04C

-0.91

<TS 506 A

54 95 9

02C

-0.86

<TS 507 A

54 105 17 02C 0.92

<TS 508 A

54 109 10 04C 0.86

<TS 509 A

54 119 12 02C 0.83

<TS 510 A

54 143 12 04C 0.85

<TS 511 A

55 8

15 01C

-0.11

<TS 512 A

55 38 11 05C

-0.17

<TS 513 A

55 46 14 04H

-0.8

<TS 514 A

55 78 7

04H 0.96

<TS 515 A

55 80 10 02H 0.94

<TS 516 A

55 82 9

02H

-0.81

<TS 517 A

55 84 10 02C 0.17

<TS 518 A

55 86 11 DBH 1.49

<TS 519 A

55 88 16 02C

-0.92

<TS 520 A

55 96 13 02C

-0.23

<TS 521 A

55 96 12 03C

-0.87

<TS 522 A

55 106 9

06H 0.99

<TS 523 A

55 112 6

04C

-0.79

<TS 524 A

55 112 10 03C

-0.11

<TS 525 A

55 114 10 03C 0.83

<TS 526 A

55 114 11 02C 0.83

<TS 527 A

55 114 5

03C

-0.92

<TS 29

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 528 A

55 120 14 02C

-0.22

<TS 529 A

55 122 15 02C

-0.13

<TS 530 A

55 140 20 06C

-0.09

<TS 531 A

56 27 11 03H

-0.93

<TS 532 A

56 33 10 03H

-0.87

<TS 533 A

56 39 14 04H

-0.09

<TS 534 A

56 41 13 02H

-0.13

<TS 535 A

56 59 11 04H 0.92

<TS 536 A

56 59 11 03H 0.94

<TS 537 A

56 83 10 04C 0.85

<TS 538 A

56 115 13 03C

-0.83

<TS 539 A

56 115 17 02C 0.87

<TS 540 A

56 137 13 03C 0.15

<TS 541 A

56 141 11 04C 0.89

<TS 542 A

57 10 11 01C

-0.13

<TS 543 A

57 18 12 VS3

-0.89

<TS 544 A

57 32 11 06H

-0.15

<TS 545 A

57 40 10 DBC

-1.7

<TS 546 A

57 64 13 02H 0.9

<TS 547 A

57 90 13 04C

-0.08

<TS 548 A

57 90 12 03C

-0.13

<TS 549 A

57 110 14 02C 0.89

<TS 550 A

57 110 10 02C

-0.13

<TS 551 A

57 114 16 03C

-0.85

<TS 552 A

57 136 9

03C

-0.9

<TS 553 A

57 138 10 02C 0.81

<TS 554 A

57 142 12 04C

-0.11

<TS 555 A

57 142 11 04C

-0.88

<TS 556 A

57 142 14 03C 0.9

<TS 557 A

58 33 10 04H

-0.92

<TS 558 A

58 57 12 03H 0.85

<TS 559 A

58 57 13 04H 0.88

<TS 560 A

58 81 13 03H

-0.24

<TS 561 A

58 81 13 02H

-0.2

<TS 562 A

58 85 16 03H 0.89

<TS 563 A

58 85 9

02H

-0.9

<TS 564 A

58 87 15 02C

-0.82

<TS 565 A

58 105 9

05H

-0.09

<TS 566 A

58 113 9

04C 0.95

<TS 567 A

58 115 12 04C 0.82

<TS 568 A

58 121 15 03C 0.76

<TS 569 A

58 121 14 02C 0.81

<TS 570 A

58 123 11 03C 0.09

<TS 571 A

58 127 20 04C 0.93

<TS 30

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 572 A

58 127 7

04C 0.02

<TS 573 A

58 143 10 03C 0.84

<TS 574 A

59 30 11 03H

-0.87

<TS 575 A

59 30 17 03C 0.87

<TS 576 A

59 30 8

03H 0.84

<TS 577 A

59 38 16 03H 0.85

<TS 578 A

59 50 16 06H 0.96

<TS 579 A

59 60 12 04H 0.87

<TS 580 A

59 66 11 06C 0.99

<TS 581 A

59 70 16 03H 0.96

<TS 582 A

59 70 8

03H

-1.01

<TS 583 A

59 82 13 03H 0.74

<TS 584 A

59 90 15 02C

-0.86

<TS 585 A

59 106 15

.02C 0.89

<TS 586 A

59 114 14 03C

-0.94

<TS 587 A

59 114 15 03C 0.89

<TS 588 A

59 118 10 02C 0.97

<TS 589 A

59 118 10 02C

-0.13

<TS 590 A

59 120 11 02C

-0.87

<TS 591 A

59 126 10 06H 0.93

<TS 592 A

59 144 13 04C 0.92

<TS 593 A

60 11 13 0iC 0.11

<TS 594 A

60 25 17 04H 0.9

<TS 595 A

60 27 14 03C 0.86

<TS 596 A

60 29 21 04H 0.96

<TS 597 A

60 31 14 03H 0.93

<TS 598 A

60 39 16 04H 0.93

<TS 599 A

60 39 9

05H

-0.11

<TS 600 A

60 39 16 06H 1.01

<TS 601 A

60 83 11 DBH

-1.81

<TS 602 A

60 85 13 02C 0.91

<TS 603 A

60 103 11 05H 0.88

<TS 604 A

60 111 11 02H 0.92

<TS 605 A

60 119 23 02C 0.89

<TS 606 A

60 121 18 02C 0.87

<TS 607 A

61 34 15 03H 0.94

<TS 608 A

61 34 11 04H 0.9

<TS 609 A

61 40 12 04H 0.88

<TS 610 A

61 44 14 04H

-0.13

<TS 611 A

61 48 15 06H 0.85

<TS 612 A

61 54 9

03H

-0.85

<TS 613 A

61 56 10 03H

-0.83 TS 614 A

61 86 13 03C

-0.08

<TS 615 A

61 104 12 02C

-0.87

<TS 31

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 616 A

61 108 9

03H

-0.88

<TS 617 A

61 112 14 04C

-0.75

<TS 618 A

61 120 11 04C

-0.9

<TS 619 A

61 120 11 03C 0.87

<TS 620 A

61 138 10 04C 0.88

<TS 621 A

61 144 9

DBH 1.99

<TS 622 A

62 11 14 01C

-0.91

<TS 623 A

62 19 13 06H 0.88

<TS 624 A

62 23 8

DBC

-1.88

<TS 625 A

62 33 16 03H 0.93

<TS 626 A

62 35 11 03H 0.93

<TS 627 A

62 49 14 05H 1.01

<TS 628 A

62 59 11 04H 0.85

<TS 629 A

62 73 10 04H

-0.09

<TS 630 A

62 89 9

03C

-0.96

<TS 631 A

62 95 10 04C

-0.9

<TS 632 A

62 109 11 04H

-0.92

<TS 633 A

62 111 10 03H 0.06

<TS 634 A

62 121 14 02C 0.85

<TS 635 A

63 12 17 01C

-0.96

<TS 636 A

63 40 9

DBC

-1.86

<TS 637 A

63 52 14 06C 0.93

<TS 638 A

63 58 13 03H 0.95

<TS 639 A

63 60 11 03H 0.85

<TS 640 A

63 62 13 04C 0.83

<TS 641 A

63 66 12 04H

-0.88

<TS 642 A

63 80 14 03H 0.93

<TS 643 A

63 80 11 03H

-0.81

<TS 644 A

63 82 7

02H

-0.91

<TS 645 A

63 82 7

06H 0.89

<TS 646 A

63 82 23 03H 0.94

<TS 647 A

63 86 13 03C

-0.85

<TS 648 A

63 86 13 02C

-0.78

<TS 649 A

63 86 15 05C 1.01

<TS 650 A

63 102 14 04H 0.96

<TS 651 A

63 104 12 05C

-0.91

<TS 652 A

63 104 14 04C

-0.2

<TS 653 A

63 104 18 03C 0.87

<TS 654 A

63 106 13 03H 0.92

<TS 655 A

63 118 18 03C 0.87

<TS 656 A

63 120 9

03C

-0.83

<TS 657 A

63 122 23 03C 0.81

<TS 658 A

63 124 16 04C 0.92

<TS 659 A

63 124 12 04C

-0.17

<TS 32

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 660 A

63 126 15 04C 0.89

<TS 661 A

63 134 21 03C 0.85

<TS 662 A

63 136 16 03C

-0.9

<TS 663 A

63 136 16 06H

-0.3

<TS 664 A

63 142 16 04C 0.85

<TS 665 A

64 11 12 06H 0.84

<TS 666 A

64 11 32 VS4

-0.95

<TS 667 A

64 11 10 VS4 0.6

<TS 668 A

64 11 18 VS5 0.84

<TS 669 A

64 13 18 04H 0.98

<TS 670 A

64 13 21 VS4

-0.97

<TS 671 A

64 19 9

06H 0

<TS 672 A

64 25 13 06C 0.83

<TS 673 A

64 57 14 05H 0.91

<TS 674 A

64 57 12 06C 0.88

<TS 675 A

64 59 15 05C 0.83

<TS 676 A

64 59 11 04C 0.81

<TS 677 A

64 67 16 06C

-0.61

<TS 678 A

64 71 12 VS5

-0.91

<TS 679 A

64 71 12 VS5 0.87

<TS 680 A

64 111 9

02H 0.91

<TS 681 A

64 123 13 04C 0.97

<TS 682 A

64 153 12 01C

-0.9

<TS 683 A

65 12 20 06H 0.82

<TS 684 A

65 14 13 06H 0.88

<TS 685 A

65 16 15 05H 0.87

<TS 686 A

65 32 9

DBC 1.61

<TS 687 A

65 32 7

DBC

-1.45

<TS 688 A

65 32 9

04H 0.9

<TS 689 A

65 40 16 03H 0.95

<TS 690 A

65 56 15 06C 0.95

<TS 691 A

65 56 10 03C

-0.9

<TS 692 A

65 60 12 02H

-0.87

<TS 693 A

65 60 13 04H

-0.84

<TS 694 A

65 60 13 03C 0.86

<TS 695 A

65 62 10 05C

-0.97

<TS 696 A

65 66 12 06H 0.83

<TS 697 A

65 76 12 02H

-0.13

<TS 698 A

65 88 12 02C

-0.9

<TS 699 A

65 90 16 02C 0.93

<TS 700 A

65 92 10 02C 1.03

<TS 701 A

65 92 13 03C 0.92

<TS 702 A

65 104 9

04H 0.96

<TS 703 A

65 104 15 03H 0.47

<TS 33

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 704 A

65 106 10 06C 0.84

<TS 705 A

65 106 18 04C 0.84

<TS 706 A

65 106 13 03C 0.89

<TS 707 A

65 106 15 02C 0.86

<TS 708 A

65 106 10 01C 0.13

<TS 709 A

65 108 15 03H

-0.88

<TS 710 A

65 114 10 06H 0.88

<TS 711 A

65 120 13 03C 0.87

<TS 712 A

65 120 9

03C

-0.94

<TS 713 A

65 124 12 03C 0.96

<TS 714 A

65 126 18 06C

-0.92

<TS 715 A

65 138 24 04C

-0.22

<TS 716 A

66 13 9

01C

-0.91

<TS 717 A

66 25 11 04H 0.88

<TS 718 A

66 27 13 06C 0.84

<TS 719 A

66 31 16 04H 0.91

<TS 720 A

66 31 12 05H

-0.89

<TS 721 A

66 35 14 04H 0.86

<TS 722 A

66 35 12 03H 0.91

<TS 723 A

66 37 12 06H

-0.07

<TS 724 A

66 39 9

05H 0.9

<TS 725 A

66 45 11 05H 0.83

<TS 726 A

66 49 6

05H 0.94

<TS 727 A

66 55 9

02H 0.87

<TS 728 A

66 59 16 06C 0.86

<TS 729 A

66 61 16 04H 0.92

<TS 730 A

66 63 10 02H

-0.93

<TS 731 A

66 63 12 06C 0.83

<TS 732 A

66 75 8

05H 0.96

<TS 733 A

66 77 8

DBC

-0.51

<TS 734 A

66 77 11 06C 0.86

<TS 735 A

66 79 12 01H

-0.11

<TS 736 A

66 79 12 03H

-0.83

<TS 737 A

66 83 16 06C 0.88

<TS 738 A

66 89 11 03C

-0.21

<TS 739 A

66 89 16 04C

-0.83

<TS 740 A

66 107 15 03H 0.15

<TS 741 A

66 107 12 02C

-1.05

<TS 742 A

66 109 15 03H

-0.9

<TS 743 A

66 109 15 04C 0.96

<TS 744 A

66 109 14 04C 0.18

<TS 745 A

66 109 18 02C 0.77

<TS 746 A

66 111 10 02H 0.94

<TS 747 A

66 111 10 02H

-0.96

<TS 34

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 748 A

66 113 18 03H 0.87

<TS 749 A

66 113 13 02C 0.85

<TS 750 A

66 123 15 06C

-0.96

<TS 751 A

66 123 13 03C 0.75

<TS 752 A

66 137 14 06C

-0.89

<TS 753 A

66 147 13 03C

-0.19

<TS 754 A

66 153 12 02C

-0.98

<TS 755 A

66 153 10 02C 0.95

<TS 756 A

67 12 10 03H 0.92

<TS 757 A

67 14 24 05H 0.85

<TS 758 A

67 24 13 06C 0.83

<TS 759 A

67 24 26 06H 0.92

<TS 760 A

67 24 9

06H 0.26

<TS 761 A

67 30 14 06C

-0.95

<TS 762 A

67 34 11 06C 0.77

<TS 763 A

67 38 10 06H 1.06

<TS 764 A

67 38 5

06H

-0.29

<TS 765 A

67 50 13 03C 0.87

<TS 766 A

67 50 9

03C 0.13

<TS 767 A

67 56 12 VS3 0.99

<TS 768 A

67 58 12 04C 0.9

<TS 769 A

67 58 16 03C 0.2

<TS 770 A

67 58 14 02C 0.88

<TS 771 A

67 106 10 02H 0.96

<TS 772 A

67 106 15 03H 0.83

<TS 773 A

67 106 15 05C 0.78

<TS 774 A

67 106 17 03C 0.5

<TS 775 A

67 110 13 04H

-0.89

<TS 776 A

67 110 11 03C 0.85

<TS 777 A

67 114 15 03C

-0.87

<TS 778 A

67 114 27 02C 0.91

<TS 779 A

67 118 15 03C 0.85

<TS 780 A

67 120 13 06H

-0.11

<TS 781 A

67 120 9

06H 0.76

<TS 782 A

67 130 15 DBH 1.77

<TS 783 A

67 132 26 DBC 1.21

<TS 784 A

67 136 25 VS3 0.85

<TS 785 A

67 154 14 01C

-0.49

<TS 786 A

67 154 14 02C 0.84

<TS 787 A

67 154 12 04C 0.82

<TS 788 A'

68 15 11 05H

-0.15

<TS 789 A

68 17 8

VS4

-0.95

<TS 790 A

68 17 14 VS4 0.8

<TS 791 A

68 27 11 VS3

-0.87

<TS 35

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 792 A

68 41 16 04H 0.94

<TS 793 A

68 45 16 06H 0.83

<TS 794 A

68 53 12 04H

-0.15

<TS 795 A

68 61 10 06H 0.83

<TS 796 A

68 61 9

03C

-0.88

<TS 797 A

68 81 17 03H 0.96

<TS 798 A

68 81 7

03H

-0.92

<TS 799 A

68 87 13 03C

-0.86

<TS 800 A

68 103 9

02H

-0.83

<TS 801 A

68 105 11 04H 0.13

<TS 802 A

68 107 12 03H

-0.11

<TS 803 A

68 111 12 03H

-0.87

<TS 804 A

68 111 13 04H

-0.89

<TS 805 A

68 139 34 VS3

-0.87

<TS 806 A

69 30 15 DBC 1.9

<TS 807 A

69 34 13 06C 0.89

<TS 808 A

69 40 15 04H 0.94

<TS 809 A

69 40 12 DBH 2

<TS 810 A

69 50 12 DBH 1.81

<TS 811 A

69 54 17 03C

-0.94

<TS 812 A

69 56 9

06H 0.9

<TS 813 A

69 56 14 03C 0.44

<TS 814 A

69 58 10 02C 0.84

<TS 815 A

69 60 9

06H

-0.84

<TS 816 A

69 60 13 06H 0.88

<TS 817 A

69 68 14 05C

-0.87

<TS 818 A

69 76 13 04H

-0.89

<TS 819 A

69 76 8

04H 0.22

<TS 820 A

69 80 9

03H

-0.87

<TS 821 A

69 86 19 06C 0.9

<TS 822 A

69 90 11 03C

-0.93

<TS 823 A

69 102 15 04H 1.04

<TS 824 A

69 106 15 05C 0.9

<TS 825 A

69 108 14 04H 0.87

<TS 826 A

69 110 12 03C 0.98

<TS 827 A

69 110 6

03C

-0.04

<TS 828 A

69 112 11 02C 0.93

<TS 829 A

69 112 14 06C 1.01

<TS 830 A

69 116 11 03H

-0.08

<TS 831 A

69 126 15 DBC 2

<TS 832 A

69 132 15 03C 0.99

<TS 833 A

69 132 12 DBC 1.45

<TS 834 A

69 134 19 06C

-0.9

<TS 835 A

69 136 11 VS5 0.81

<TS 36

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 836 A

69 136 12 VS3

-0.81

<TS 837 A

69 152 23 VS3 0.92

<TS 838 A

69 152 21 VS3

-0.86

<TS 839 A

70 19 11 05H 0.9

<TS 840 A

70 25 7

DBC 1.26

<TS 841 A

70 53 10 04H 0.89

<TS 842 A

70 53 9

05H

-0.09

<TS 843 A

70 53 21 03C 0.13

<TS 844 A

70 53 9

02C

-0.86

<TS 845 A

70 55 21 03C

-0.82

<TS 846 A

70 57 8

05H

-0.11

<TS 847 A

70 61 13 04C 0.81

<TS 848 A

70 65 11 04C 0.85

<TS 849 A

70 69 15 05H

-0.15

<TS 850 A

70 81 17 DBC 1.86

<TS 851 A

70 81 10 03H 0.88

<TS 852 A

70 85 13 03H 0.9

<TS 853 A

70 107 15 04C

-0.95

<TS 854 A

70 107 9

04H 0.15

<TS 855 A

70 109 14 03C 0.89

<TS 856 A

70 115 11 03H 0.91

<TS 857 A

70 119 12 04C 0.88

<TS 858 A

70 123 11 03C

-0.87

<TS 859 A

70 137 14 06H 0.88

<TS 860 A

70 145 12 DBC

-1.73

<TS 861 A

70 153 13 DBH

-1.69

<TS 862 A

71 34 9

03H

-0.91

<TS 863 A

71 54 12 04H 0.9

<TS 864 A

71 54 12 03C 0.79

<TS 865 A

71 58 16 04C

-0.88

<TS 866 A

71 78 14 06C

-0.85

<TS 867 A

71 82 11 03H 0.94

<TS 868 A

71 90 15 05C 0.66

<TS 869 A

71 108 9

06C 0.83

<TS 870 A

71 108 14 05C 0.92

<TS 871 A

71 108 16 04C 0.15

<TS 872 A

71 108 12 03C

-0.91

<TS 873 A

71 108 13 02C

-0.13

<TS 874 A

71 110 12 03H

-0.19

<TS 875 A

71 110 14 04H 0.84

<TS 876 A

71 110 6

04H

-0.57

<TS 877 A

71 116 15 03C 0.8

<TS 878 A

71 122 13 03C 0.85

<TS 879 A

71 126 23 05C 0.91

<TS 37

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 880 A

71 126 10 05C 0.11

<TS 881 A

71 150 12 06H 0.84

<TS 882 A

72 21 9

06H 0.83

<TS 883 A

72 47 21 04C

-0.61

<TS 884 A

72 53 15 04C

-0.92

<TS 885 A

72 53 16 02C 0.88

<TS 886 A

72 53 9

04C 0.94

<TS 887 A

72 55 16 04C

-0.18

<TS 888 A

72 55 20 03C

-0.95

<TS 889 A

72 61 12 04C

-0.9

<TS 890 A

72 83 10 DBC

-1.66

<TS 891 A

72 85 12 05C 0.13

<TS 892 A

72 89 13 02C 0.75

<TS 893 A

72 109 13 02H 0.85

<TS 894 A

72 109 9

04H 0.15

<TS 895 A

72 111 11 04H 0.87

<TS 896 A

72 127 19 04C 0.85

<TS 897 A

72 151 12 01H

-0.13

<TS 898 A

73 14 15 05H

-0.96

<TS 899 A

73 44 16 04H 0.83

<TS 900 A

73 44 22 06C

-0.96

<TS 901 A

73 46 14 04H 0.93

<TS 902 A

73 56 12 05C

-0.95

<TS 903 A

73 66 15 04C 0.86

<TS 904 A

73 110 10 03H

-0.86

<TS 905 A

73 112 12 03C 0.9

<TS 906 A

73 124 13 06C 0.88

<TS 907 A

73 134 18 06C

-0.9

<TS 908 A

74 15 19 VS4 0.78

<TS 909 A

74 15 10 01C

-0.96

<TS 910 A

74 33 10 DBC 1.23

<TS 911 A

74 59 10 02C 0.88

<TS 912 A

74 79 15 05C

-0.9

<TS 913 A

74 121 13 03H

-0.87

<TS 914 A

74 123 16 04H

-0.87

<TS 915 A

74 123 16 05C

-0.83

<TS 916 A

74 123 18 04C 0.91

<TS 917 A

74 125 13 03H

-0.92

<TS 918 A

74 127 13 03C 1

<TS 919 A

74 129 12 VS5

-0.9

<TS 920 A

75 16 15 03H 0.58

<TS 921 A

75 16 17 06C 0.07

<TS 922 A

75 20 17 03H 0.87

<TS 923 A

75 20 16 04H

-0.83

<TS 38

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 924 A

75 28 11 DBH 1.54

<TS 925 A

75 40 12 06C 0.86

<TS 926 A

75 44 21 VS3 0.88

<TS 927 A

75 44 38 VS3

-0.84

<TS 928 A

75 48 12 01C

-0.89

<TS 929 A

75 56 14 03C 0.91

<TS 930 A

75 66 10 03C 0.85

<TS 931 A

75 68 17 02C 0.86

<TS 932 A

75 76 11 02H

-0.91

<TS 933 A

75 76 11 02H 0.9

<TS 934 A

75 82 13 03H 0.84

<TS 935 A

75 92 13 06H

-0.93

<TS 936 A

75 104 16 02C

-0.87

<TS 937 A

75 120 22 03C 0.82

<TS 938 A

75 128 15 VS5 0.94

<TS 939 A

75 136 15 04C 0.87

<TS 940 A

75 136 11 04C

-0.15

<TS 941 A

75 148 10 06C 0.91

<TS 942 A

75 150 22 02C 0.9

<TS 943 A

75 150 16 04C 0.85

<TS 944 A

76 15 13 04H

-0.82

<TS 945 A

76 15 37 DBC

-1.84

<TS 946 A

76 15 14 DBC 1.81

<TS 947 A

76 15 12 06C 0.84

<TS 948 A

76 15 16 01C 0.15

<TS 949 A

76 15 13 03H

-0.22

<TS 950 A

76 19 13 DBC 1.74

<TS 951 A

76 21 13 03H 0.91

<TS 952 A

76 21 16 04H 0.89

<TS 953 A

76 37 9

06H

-0.04

<TS 954 A

76 51 11 VS3

-0.88

<TS 955 A

76 51 10 04C 0.15

<TS 956 A

76 51 9

VS3 0.81

<TS 957 A

76 53 15 03C 0.92

<TS 958 A

76 55 26 03C 0.88

<TS 959 A

76 57 12 05C

-0.88

<TS 960 A

76 57 14 02C 0.86

<TS 961 A

76 65 12 04C

-0.11

<TS 962 A

76 69 13 04H

-0.13

<TS 963 A

76 79 13 03H 0.99

<TS 964 A

76 89 14 DBC 1.94

<TS 965 A

76 91 18 02C 0.9

<TS 966 A

76 97 15 04C 0.8

<TS 967 A

76 97 9

04C

-0.81

<TS 39

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 968 A

76 101 18 02H

-0.87

<TS 969 A

76 101 15 03H 0.89

<TS 970 A

76 103 12 03H

-0.11

<TS 971 A

76 107 17 05C 0.72

<TS 972 A

76 111 16 04C 0.92

<TS 973 A

76 111 9

05C 0.85

<TS 974 A

77 16 35 VS4

-0.87

<TS 975 A

77 18 10 07C 0

<TS 976 A

77 18 16 05H

-0.94

<TS 977 A

77 18 17 06H

-0.15

<TS 978 A

77 20 11 06H

-0.13

<TS 979 A

77 22 11 03H 0.78

<TS 980 A

77 22 13 06H 0.95

<TS 981 A

77 24 15 06H 0.93

<TS 982 A

77 24 9

03H 0.87

<TS 983 A

77 24 9

04H

-0.13

<TS 984 A

77 28 11 06H 0.94

<TS 985 A

77 44 19 VS3 0.94

<TS 986 A

77 44 26 VS5 1.14

<TS 987 A

77 50 9

07C 0.02

<TS 988 A

77 52 13 06C

-0.88

<TS 989 A

77 52 14 03C

-0.9

<TS 990 A

77 52 13 02C 0.83

<TS 991 A

77 62 15 03C 0.94

<TS 992 A

77 68 13 02H 0.92

<TS 993 A

77 76 11 VS5 0.92

<TS 994 A

77 82 12 05C 0.92

<TS 995 A

77 92 16 02C

-0.93

<TS 996 A

77 98 12 03H

-0.18

<TS 997 A

77 98 13 03H

-0.96

<TS 998 A

77 102 15 03H 0.91

<TS 999 A

77 114 14 04H 0.92

<TS 1000 A

77 116 11 04H

-0.95

<TS 1001 A

77 122 23 06C 0.83

<TS 1002 A

77 124 21 03C 0.79

<TS 1003 A

77 124 13 03C

-0.86

<TS 1004 A

77 126 10 06H 0.9

<TS 1005 A

77 132 16 07C 0.94

<TS 1006 A

77 132 10 DBC

-1.68

<TS 1007 A

77 138 13 07C

-1.47

<TS 1008 A

77 144 10 04C 0.81

<TS 1009 A

77 148 21 03C 0.9

<TS 1010 A

77 148 16 07H

-1.03

<TS 1011 A

77 150 15 02C 0.9

<TS 40

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 1012 A

78 19 11 DBC

-1.73

<TS 1013 A

78 25 11 05C

-0.86

<TS 1014 A

78 75 10 02H 0.04

<TS 1015 A

78 101 16 03H 0.89

<TS 1016 A

78 105 15 02H

-0.83

<TS 1017 A

78 109 11 04H 0

<TS 1018 A

78 111 9

04H

-0.86

<TS 1019 A

78 113 21 02C 0.89

<TS 1020 A

78 119 17 03H 0.87

<TS 1021 A

78 119 14 02C 0.96

<TS 1022 A

78 127 14 03C 0.92

<TS 1023 A

78 147 17 02C

-0.17

<TS 1024 A

79 18 17 VS4

-0.93

<TS 1025 A

79 18 12 VS4 0.95

<TS 1026 A

79 18 14 DBC 1.7

<TS 1027 A

79 20 14 05H 0.91

<TS 1028 A

79 22 10 07C 0.85

<TS 1029 A

79 48 12 04C

-0.15

<TS 1030 A

79 66 16 01C 0.39

<TS 1031 A

79 68 12 04C

-0.88

<TS 1032 A

79 68 12 07H 0.94

<TS 1033 A

79 72 9

05H

-0.87

<TS 1034 A

79 72 16 04H 0.84

<TS 1035 A

79 72 18 VS3 0

<TS 1036 A

79 74 10 05C

-0.94

<TS 1037 A

79 78 13 05C 0.81

<TS 1038 A

79 82 18 03H 0.89

<TS 1039 A

79 82 11 05C 0.88

<TS 1040 A

79 84 9

03H

-0.9

<TS 1041 A

79 90 11 04C

-0.92

<TS 1042 A

79 90 20 04C

-0.1

<TS 1043 A

79 94 11 03C

-0.84

<TS 1044 A

79 100 11 05H 0.73

<TS 1045 A

79 100 14 03H 0.89

<TS 1046 A

79 100 11 02H 0.78

<TS 1047 A

79 104 17 05H 0.97

<TS 1048 A

79 104 8

05H

-0.11

<TS 1049 A

79 114 15 05C

-0.87

<TS 1050 A

79 116 16 03H

-0.89

<TS 1051 A

79 116 16 03C

-0.86

<TS 1052 A

79 120 12 04H 0.87

<TS 1053 A

79 128 24 04C 0.83

<TS 1054 A

79 148 13 02C 0.92

<TS 1055 A

79 150 17 02C 0.09

<TS 41

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

SIG Row Column Depth Location Elevation Status 1056 A

79 150 10 02C 0.88

<TS 1057 A

80 27 17 VS3 0.92

<TS 1058 A

80 47 10 05C

-0.89

<TS 1059 A

80 57 19 04H 0.91

<TS 1060 A

80 57 13 04H 0.13

<TS 1061 A

80 59 15 04C 0.81

<TS 1062 A

80 65 12 04C 0.87

<TS 1063 A

80 71 11 04H

-0.88

<TS 1064 A

80 77 20 04H 0.88

<TS 1065 A

80 77 12 02H

-0.89

<TS 1066 A

80 77 14 02H 0.87

<TS 1067 A

80 99 14 07C 1.12

<TS 1068 A

80 119 12 03C 0.82

<TS 1069 A

80 133 13 04H 0.94

<TS 1070 A

80 143 14 05C 0.85

<TS 1071 A

80 145 12 02C

-0.15

<TS 1072 A

80 147 15 07H 0.77

<TS 1073 A

81 18 13 01H 0.94

<TS 1074 A

81 18 14 VS4

-0.76

<TS 1075 A

81 20 10 04H 0.86

<TS 1076 A

81 20 6

04H

-0.19

<TS 1077 A

81 22 7

DBC

-1.57

<TS 1078 A

81 46 26 VS5 0.81

<TS 1079 A

81 54 17 05C

-0.92

<TS 1080 A

81 56 10 05C

-0.9

<TS 1081 A

81 84 30 VS4 1.11

<TS 1082 A

81 84 22 07C

-0.07

<TS 1083 A

81 84 10 07C

-0.86

<TS 1084 A

81 84 12 05C

-0.94

<TS 1085 A

81 84 11 04C

-0.83

<TS 1086 A

81 94 11 02C

-0.88

<TS 1087 A

81 94 12 02C

-0.14

<TS 1088 A

81 100 14 05H 0.8

<TS 1089 A

81 102 9

07C

-0.11

<TS 1090 A

81 102 18 07C

-0.87

<TS 1091 A

81 106 12 05C 0.83

<TS 1092 A

81 118 13 04C

-0.86

<TS 1093 A

81 118 17 03C

-0.77

<TS 1094 A

81 118 9

04C 0.83

<TS 1095 A

81 148 16 02C 0.91

<TS 1096 A

81 148 21 05C 0.09

<TS 1097 A

82 19 13 VS4 0.6

<TS 1098 A

82 19 6

VS4

-1

<TS 1099 A

82 33 14 VS3 0.88

<TS 42

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 1100 A

82 79 11 07C 0.81

<TS 1101 A

82 89 19 05C 0.98

<TS 1102 A

82 91 13 07C 0.91

<TS 1103 A

82 101 8

05H

-0.08

<TS 1104 A

82 107 13 04H 0.53

<TS 1105 A

82 121 12 05H 0.89

<TS 1106 A

82 123 12 03C

-0.87

<TS 1107 A

83 50 14 05C 0.85

<TS 1108 A

83 74 15 05H 0.84

<TS 1109 A

83 76 17 02H 0.89

<TS 1110 A

83 84 14 02C 0.98

<TS 1111 A

83 84 12 05H 0.81

<TS 1112 A

83 84 12 04H

-0.96

<TS 1113 A

83 86 15 04H 0.89

<TS 1114 A

83 88 21 04C 0.94

<TS 1115 A

83 88 8

04C

-0.87

<TS 1116 A

83 90 17 07H 0.91

<TS 1117 A

83 90 13 05H

-0.16

<TS 1118 A

83 100 12 05H 0.84

<TS 1119 A

83 100 22 04H 0.91

<TS 1120 A

83 100 11 03H

-1

<TS 1121 A

83 102 16 05C

-0.17

<TS 1122 A

83 102 12 05C

-0.89

<TS 1123 A

83 108 15 04H 0.85

<TS 1124 A

83 112 16 02C

-0.13

<TS 1125 A

83 114 12 VS2

-0.68

<TS 1126 A

83 114 10 VS2 0.55

<TS 1127 A

83 116 18 VS2

-0.2

<TS 1128 A

83 116 12 VS2 0.75

<TS 1129 A

83 118 10 03H 0.93

<TS 1130 A

83 120 15 04C 0.85

<TS 1131 A

83 128 13 DBH 1.61

<TS 1132 A

83 146 12 04C

-0.9

<TS 1133 A

83 148 19 03C

-0.99

<TS 1134 A

83 148 11 07C 0.81

<TS 1135 A

84 19 21 01H

-0.49

<TS 1136 A

84 29 15 05C

-0.96

<TS 1137 A

84 33 23 VS2

-0.85

<TS 1138 A

84 41 15 07H 0.83

<TS 1139 A

84 47 11 06H 0.91

<TS 1140 A

84 61 31 03C 0.92

<TS 1141 A

84 61 11 03C 0.15

<TS 1142 A

84 73 10 02H 0.17

<TS 1143 A

84 73 18 04H 0.88

<TS 43

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 1144 A

84 73 17 05C 0.92

<TS 1145 A

84 73 8

05C 0.09

<TS 1146 A

84 73 8

05C

-0.87

<TS 1147 A

84 75 10 06C

-0.88

<TS 1148 A

84 81 9

04H 0.88

<TS 1149 A

84 85 11 02H 0.82

<TS 1150 A

84 85 10 02H

-0.97

<TS 1151 A

84 85 19 04H 0.88

<TS 1152 A

84 85 12 04H

-0.9

<TS 1153 A

84 93 13 05C

-0.58

<TS 1154 A

84 93 10 04C

-0.59

<TS 1155 A

84 97 10 05H 0.13

<TS 1156 A

84 119 11 04C 0.95

<TS 1157 A

84 125 14 04C

-0.92

<TS 1158 A

84 141 22 04C 0.79

<TS 1159 A

84 143 12 03C 0.81

<TS 1160 A

84 147 11 VS5 0.79

<TS 1161 A

85 20 24 VS4

-0.95

<TS 1162 A

85 20 21 VS4 0.62

<TS 1163 A

85 26 16 03H 0.84

<TS 1164 A

85 32 9

VS5 0.93

<TS 1165 A

85 32 12 03C

-0.94

<TS 1166 A

85 40 10 VS5

-0.83

<TS 1167 A

85 62 18 04C 0.55

<TS 1168 A

85 84 15 05H 0.86

<TS 1169 A

85 92 18 02C 0.85

<TS 1170 A

85 94 11 02C 0.12

<TS 1171 A

85 104 18 03C 0.87

<TS 1172 A

85 116 15 03C 0.48

<TS 1173 A

85 124 11 03C 0.87

<TS 1174 A

85 130 12 04C

-0.94

<TS 1175 A

85 146 23 02C 0.82

<TS 1176 A

85 146 27 03C

-0.95

<TS 1177 A

86 55 14 06C 0.88

<TS 1178 A

86 57 10 05C 0.46

<TS 1179 A

86 59 11 03C 0.88

<TS 1180 A

86 59 11 02C 0.92

<TS 1181 A

86 63 11 06C 0.86

<TS 1182 A

86 65 12 05H 0.93

<TS 1183 A

86 67 14 04C

-0.85

<TS 1184 A

86 67 11 02C 0.88

<TS 1185 A

86 69 15 06C

-0.87

<TS 1186 A

86 81 11 02H

-0.86

<TS 1187 A

86 85 9

05H

-0.13

<TS 44

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

SIG Row Column Depth Location Elevation Status 1188 A

86 97 19 03H 0.81

<TS 1189 A

86 101 12 05C

-0.91

<TS 1190 A

86 101 16 04H

-0.85

<TS 1191 A

86 107 10 04H 0.87

<TS 1192 A

86 111 11 04H 0.15

<TS 1193 A

86 111 16 05C 0.85

<TS 1194 A

86 111 9

03H

-0.93

<TS 1195 A

86 115 11 02C

-0.94

<TS 1196 A

86 117 15 03H 0.84

<TS 1197 A

86 117 12 06C 0.91

<TS 1198 A

86 143 14 03C

-0.91

<TS 1199 A

86 145 11 03C

-0.84

<TS 1200 A

86 145 15 04C 0.86

<TS 1201 A

86 145 9

03C 0.89

<TS 1202 A

87 20 18 VS4

-0.18

<TS 1203 A

87 20 25 VS4 0.64

<TS 1204 A

87 22 11 01H 0.89

<TS 1205 A

87 22 12 04H 0.89

<TS 1206 A

87 36 13 DBH 1.99

<TS 1207 A

87 40 9

VS4 0.66

<TS 1208 A

87 40 17 07H

-0.95

<TS 1209 A

87 40 8

07H

-0.15

<TS 1210 A

87 40 16 07C 0.86

<TS 1211 A

87 56 15 04C 0.79

<TS 1212 A

87 56 13 05H 0.88

<TS 1213 A

87 58 16 VS2

-0.85

<TS 1214 A

87 60 12 03C 0.9

<TS 1215 A

87 60 13 02C 0.86

<TS 1216 A

87 82 10 03H 0

<TS 1217 A

87 82 15 05H 1.01

<TS 1218 A

87 82 11 05C 0.97

<TS 1219 A

87 88 12 04H 0.2

<TS 1220 A

87 90 11 02C

-0.17

<TS 1221 A

87 90 10 04H 0.82

<TS 1222 A

87 92 7

04H 0.9

<TS 1223 A

87 92 13 04H

-0.9

<TS 1224 A'

87 92 17 02C 0.58

<TS 1225 A

87 92 20 04C 0.89

<TS 1226 A

87 92 16 05C 0.98

<TS 1227 A

87 100 1 1 05C

-0.9

<TS 1228 A

87 100 18 04H 0.75

<TS 1229 A

87 102 11 03H 0.87

<TS 1230 A

87 102 21 05H 0.86

<TS 1231 A

87 102 8

04H

-0.09

<TS 45

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 1232 A

87 104 12 06H 0.98

<TS 1233 A

87 106 14 06H 0.28

<TS 1234 A

87 106 11 03H 0.92

<TS 1235 A

87 110 10 05H 0.09

<TS 1236 A

87 110 13 03H 0.83

<TS 1237 A

87 112 11 04H 0.88

<TS 1238 A

87 114 11 06H 0.13

<TS 1239 A

87 116 20 04C 0.94

<TS 1240 A

87 116 15 03C

-0.15

<TS 1241 A

87 120 14 05H

-0.23

<TS 1242 A

87 124 14 04C

-0.9

<TS 1243 A

87 136 15 03C

-0.87

<TS 1244 A

87 138 18 03H 0.87

<TS 1245 A

87 142 8

03C

-0.98

<TS 1246 A

87 144 16 04C 0.85

<TS 1247 A

87 144 27 03C

-0.9

<TS 1248 A

87 146 10 02C 0.91

<TS 1249 A

88 21 24 VS4

-0.96

<TS 1250 A

88 21 11 VS4 0.07

<TS 1251 A

88 33 11 04H 0.87

<TS 1252 A

88 53 25 07C 0.9

<TS 1253 A

88 57 15 06H 0.94

<TS 1254 A

88 57 23 07C 0.88

<TS 1255 A

88 59 22 05C 0.85

<TS 1256 A

88 59 17 05C 0.13

<TS 1257 A

88 59 11 03C 0.83

<TS 1258 A

88 59 11 04C 0.85

<TS 1259 A

88 61 13 06C 0.83

<TS 1260 A

88 61 26 03C 0.57

<TS 1261 A

88 61 25 02C 0.87

<TS 1262 A

88 73 19 02H

-0.15

<TS 1263 A

88 81 12 02C 1.02

<TS 1264 A

88 83 15 04H

-0.86

<TS 1265 A

88 83 17 05H

-0.91

<TS 1266 A

88 89 13 06H 0.86

<TS 1267 A

88 89 11 05H 0.09

<TS 1268 A

88 91 13 05C 0.13

<TS 1269 A

88 91 15 04H 0.88

<TS 1270 A

88 93 10 04H 0.86

<TS 1271 A

88 99 15 06H

-0.95

<TS 1272 A

88 107 11 04C

-0.09

<TS 1273 A

88 117 12 06H 0.86

<TS 1274 A

88 125 15 04C

-0.89

<TS 1275 A

88 125 13 03C

-0.85

<TS 46

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 1276 A

88 145 23 04C

-0.81

<TS 1277 A

88 145 30 02C 0.15

<TS 1278 A

89 34 15 04H

-0.92

<TS 1279 A

89 38 10 04H

-0.9

<TS 1280 A

89 42 9

07H

-0.87

<TS 1281 A

89 42 11 07H 0.93

<TS 1282 A

89 60 12 04H

-0.87

<TS 1283 A

89 70 9

05C 0.04

<TS 1284 A

89 70 17 06C 0.85

<TS 1285 A

89 70 13 05C

-0.91

<TS 1286 A

89 72 14 01C 0.85

<TS 1287 A

89 78 17 07H 1.03

<TS 1288 A

89 78 8

07H

-0.92

<TS 1289 A

89 84 14 04H

-0.95

<TS 1290 A

89 84 11 03H 0.93

<TS 1291 A

89 108 11 04H 0.92

<TS 1292 A

89 108 16 05H 0.94

<TS 1293 A

89 108 25 06H 0.95

<TS 1294 A

89 112 13 05H

-0.87

<TS 1295 A

89 112 16 05H 0.2

<TS 1296 A

89 112 16 05H 0.91

<TS 1297 A

89 114 11 03H

-0.94

<TS 1298 A

89 128 16 03H 0.89

<TS 1299 A

89 128 12 05H 0.83

<TS 1300 A

89 136 11 03H 0.88

<TS 1301 A

90 25 12 VS4 0.95

<TS 1302 A

90 25 6

VS4

-0.86

<TS 1303 A

90 31 8

04H 0.91

<TS 1304 A

90 35 10 05H 0.86

<TS 1305 A

90 55 9

04C

-0.93

<TS 1306 A

90 59 8

04H

-0.12

<TS 1307 A

90 59 10 04H 0.92

<TS 1308 A

90 79 8

05H 0.93

<TS 1309 A

90 79 12 06C 0.86

<TS 1310 A

90 81 12 06H 0.92

<TS 1311 A

90 87 19 03H 0.81

<TS 1312 A

90 87 19 06H 0.4

<TS 1313 A

90 87 15 04C 0.48

<TS 1314 A

90 87 15 02C 0.92

<TS 1315 A

90 91 17 03C 0.96

<TS 1316 A

90 93 21 03C 0.93

<TS 1317 A

90 93 16 04C 0.99

<TS 1318 A

90 95 12 02C

-0.93

<TS 1319 A

90 95 20 04C 0.95

<TS 47

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 1320 A

90 95 19 06C 0.97

<TS 1321 A

90 95 18 07C 0.51

<TS 1322 A

90 99 12 07H

-0.97

<TS 1323 A

90 101 11 02C 0.89

<TS 1324 A

90 101 15 02C 0.13

<TS 1325 A

90 101 11 03H

-0.85

<TS 1326 A

90 103 12 04H 0.85

<TS 1327 A

90 105 23 05C 0.91

<TS 1328 A

90 107 13 04H 0.89

<TS 1329 A

90 107 19 05C 0.51

<TS 1330 A

90 109 11 05H

-0.91

<TS 1331 A

90 115 19 VS2

-0.95

<TS 1332 A

90 115 10 VS2 0.95

<TS 1333 A

90 115 17 VS6

-0.79

<TS 1334 A

90 115 14 VS6

-0.15

<TS 1335 A

90 115 15 07C 0.73

<TS 1336 A

90 115 12 03C

-0.92

<TS 1337 A

90 135 16 04H 0.87

<TS 1338 A

90 135 18 04C 0.82

<TS 1339 A

90 137 9

04C 0.02

<TS 1340 A

90 137 15 06C 0.9

<TS 1341 A

90 143 19 02C

-0.96

<TS 1342 A

90 143 17 02C 0.13

<TS 1343 A

90 143 14 03C

-0.94

<TS 1344 A

90 143 12 03C

-0.04

<TS 1345 A

91 22 37 VS4 0.66

<TS 1346 A

91 22 11 VS6

-0.77

<TS 1347 A

91 36 13 06H

-0.88

<TS 1348 A

91 48 17 07C 0.07

<TS 1349 A

91 48 15 05C

-0.93

<TS 1350 A

91 54 9

03C

-0.86

<TS 1351 A

91 60 10 03C

-0.88

<TS 1352 A

91 60 10 02C

-0.18

<TS 1353 A

91 66 18 05C 0.9

<TS 1354 A

91 70 10 06H

-0.13

<TS 1355 A

91 80 13 05C 0.85

<TS 1356 A

91 86 15 05H 0.15

<TS 1357 A

91 90 19 03C 0.8

<TS 1358 A

91 90 11 04C 0.94

<TS 1359 A

91 90 17 05H 0.46

<TS 1360 A

91 92 13 05H 0.93

<TS 1361 A

91 94 16 05C 0.17

<TS 1362 A

91 94 10 06H 0.11

<TS 1363 A

91 94 13 05H 0.15

<TS 48

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 1364 A

91 96 10 02C 0.89

<TS 1365 A

91 106 14 03C 0.81

<TS 1366 A

91 110 12 04C

-0.94

<TS 1367 A

91 128 13 04H

-0.93

<TS 1368 A

91 134 8

06C 0.13

<TS 1369 A

91 134 15 04H

-0.87

<TS 1370 A

91 136 13 04C 0.87

<TS 1371 A

91 138 8

04C

-0.94

<TS 1372 A

91 138 16 05C

-0.91

<TS 1373 A

91 138 14 04C 0.83

<TS 1374 A

91 144 10 03C

-0.86

<TS 1375 A

92 23 27 VS6 1.03

<TS 1376 A

92 23 8

VS6 0.66

<TS 1377 A

92 23 18 VS2 0.99

<TS 1378 A

92 23 23 VS2 0.61

<TS 1379 A

92 23 14 04H 0.85

<TS 1380 A

92 25 13 VS4 0.85

<TS 1381 A

92 25 14 VS4

-0.9

<TS 1382 A

92 29 16 03H 0.93

<TS 1383 A

92 33 14 04H 0.83

<TS 1384 A

92 35 15 06H 0.89

<TS 1385 A

92 37 10 04H 0.96

<TS 1386 A

92 51 12 05C 0.13

<TS 1387 A

92 59 14 VS4

-0.85

<TS 1388 A

92 59 18 VS4 0.83

<TS 1389 A

92 59 11 VS4 0.12

<TS 1390 A

92 69 10 05C 0.9

<TS 1391 A

92 69 12 05C 0.13

<TS 1392 A

92 77 19 05C

-0.74

<TS 1393 A

92 77 10 06C

-0.92

<TS 1394 A

92 81 9

06H

-0.96

<TS 1395 A

92 83 12 05H

-0.15

<TS 1396 A

92 83 15 05C 0.98

<TS 1397 A

92 87 15 05C 0.83

<TS 1398 A

92 87 12 03H 0.9

<TS 1399 A

92 89 20 04C 0.87

<TS 1400 A

92 89 15 05C 0.98

<TS 1401 A

92 89 14 06H 0.81

<TS 1402 A

92 93 12 02C 0.87

<TS 1403 A

92 93 18 04H 0.84

<TS 1404 A

92 97 11 05C

-0.12

<TS 1405 A

92 101 18 VS2

-0.85

<TS 1406 A

92 101 18 VS2 0.92

<TS 1407 A

92 105 14 04C 0.87

<TS 49

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 1408 A

92 107 16 04H

-0.17

<TS 1409 A

92 109 13 05C

-0.88

<TS 1410 A

92 111 9

04H 0.94

<TS 1411 A

92 115 14 04C 0.87

<TS 1412 A

92 117 10 VS4

-0.63

<TS 1413 A

92 117 10 VS4 0.89

<TS 1414 A

92 125 17 03H 0.88

<TS 1415 A

92 127 11 04H

-0.19

<TS 1416 A

92 129 13 07H

-0.93

<TS 1417 A

92 131 12 04H 0.88

<TS 1418 A

92 133 18 07H 0.76

<TS 1419 A

92 133 18 05C

-0.89

<TS 1420 A

92 133 20 04C 0.89

<TS 1421 A

92 135 14 04C 0.76

<TS 1422 A

92 137 11 04C 0.82

<TS 1423 A

92 141 13 04C 0.85

<TS 1424 A

92 141 16 02C

-0.22

<TS 1425 A

92 141 8

04C

-0.7

<TS 1426 A

93 26 13 VS4

-0.89

<TS 1427 A

93 26 11 VS4 0.91

<TS 1428 A

93 52 13 04C 0.83

<TS 1429 A

93 58 10 04C

-0.24

<TS 1430 A

93 58 10 07C 0.9

<TS 1431 A

93 58 40 VS2

-0.86 PLG 1432 A

93 58 32 VS2 0.95

<TS 1433 A

93 58 30 VS4 0.95

<TS 1434 A

93 70 12 02H

-1.04

<TS 1435 A

93 70 13 04H 0.96

<TS 1436 A

93 76 17 VS4 0.04

<TS 1437 A

93 76 18 VS4 0.77

<TS 1438 A

93 82 12 05C

-0.87

<TS 1439 A

93 82 12 VS2 0.91

<TS 1440 A

93 84 16 04H

-0.88

<TS 1441 A

93 84 14 03H

-0.88

<TS 1442 A

93 88 17 03H 0

<TS 1443 A

93 94 13 04C 0.88

<TS 1444 A

93 94 10 04C

-0.45

<TS 1445 A

93 96 12 04C

-0.13

<TS 1446 A

93 104 38 VS4

-0.75

<TS 1447 A

93 104 14 02C

-0.87

<TS 1448 A

93 106 21 VS2

-0.78

<TS 1449 A

93 106 10 VS2 0.02

<TS 1450 A

93 114 12 03C

-0.8

<TS 1451 A

93 116 13 04H 0.91

<TS 50

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 1452 A

93 118 10 DBH 1.87

<TS 1453 A

93 130 17 03H

-0.95

<TS 1454 A

93 132 10 04H

-0.91

<TS 1455 A

93 134 11 04H

-0.97

<TS 1456 A

93 136 14 03C 0.82

<TS 1457 A

93 136 15 03C

-0.95

<TS 1458 A

93 138 18 05C 0.85

<TS 1459 A

94 25 9

03H

-0.95

<TS 1460 A

94 25 14 VS4

-0.91

<TS 1461 A

94 25 6

VS4

-0.16

<TS 1462 A

94 27 12 03H 0.93

<TS 1463 A

94 31 22 VS4

-0.86

<TS 1464 A

94 51 14 04C 0.79

<TS 1465 A

94 51 9

04C 0.09

<TS 1466 A

94 57 11 05C 0.86

<TS 1467 A

94 57 6

05C

-0.24

<TS 1468 A

94 61 11 04H 0.92

<TS 1469 A

94 71 14 05C

-0.94

<TS 1470 A

94 85 16 02C 1.01

<TS 1471 A

94 89 16 05C 0.59

<TS 1472 A

94 91 15 05H

-0.42

<TS 1473 A

94 95 18 07C

-1.04

<TS 1474 A

94 101 23 04C

-0.97

<TS 1475 A

94 107 11 03H

-0.92

<TS 1476 A

94 109 20 04C

-0.84

<TS 1477 A

94 111 12 04H

-0.91

<TS 1478 A

94 129 12 03H

-0.92

<TS 1479 A

94 135 15 04C 0.8

<TS 1480 A

94 139 10 03C

-0.81

<TS 1481 A

94 141 15 03C 0.79

<TS 1482 A

95 24 22 VS4 0.44

<TS 1483 A

95 24 31 VS4

-1.12

<TS 1484 A

95 26 13 VS4 0.92

<TS 1485 A

95 30 35 VS4

-0.91

<TS 1486 A

95 30 29 VS4 0.93

<TS 1487 A

95 32 11 04H

-0.15

<TS 1488 A

95 48 20 06C 0.9

<TS 1489 A

95 48 9

06C 0.07

<TS 1490 A

95 48 9

06H 0.99

<TS 1491 A

95 48 10 07H

-0.92

<TS 1492 A

95 48 11 07H 0.92

<TS 1493 A

95 48 7

07C 0.04

<TS 1494 A

95 54 9

05C 0.11

<TS 1495 A

95 58 14 VS2

-0.88

<TS 51

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 1496 A

95 58 11 05C

-0.88

<TS 1497 A

95 58 13 04H 0.97

<TS 1498 A

95 60 13 06H 0.99

<TS 1499 A

95 72 16 07C 0.89

<TS 1500 A

95 72 17 07C 0.04

<TS 1501 A

95 74 13 06C

-0.91

<TS 1502 A

95 84 20 05C 1.01

<TS 1503 A

95 94 14 04C

-0.02

<TS 1504 A

95 94 13 DBC 1.67

<TS 1505 A

95 104 12 04C 0.11

<TS 1506 A

95 104 12 02C 0.11

<TS 1507 A

95 110 11 04H 0.9

<TS 1508 A

95 110 11 04C 0.92

<TS 1509 A

95 110 12 02C

-0.98

<TS 1510 A

95 118 16 VS2

-0.15

<TS 1511 A

95 124 20 VS2

-0.78

<TS 1512 A

95 124 22 VS2 0.94

<TS 1513 A

95 126 19 VS2 0.95

<TS 1514 A

95 126 6

VS2

-1.01

<TS 1515 A

95 130 8

VS2

-0.72

<TS 1516 A

95 130 14 VS2 0.02

<TS 1517 A

95 130 22 VS2 0.87

<TS 1518 A

95 130 13 04H 0.93

<TS 1519 A

95 132 23 VS2 0.91

<TS 1520 A

95 132 14 VS4 0.95

<TS 1521 A

95 132 16 07C

-0.93

<TS 1522 A

95 132 17 03C

-0.83

<TS 1523 A

95 134 28 04C

-0.86

<TS 1524 A

95 134 13 03C

-0.91

<TS 1525 A

95 140 24 04C 0.83

<TS 1526 A

95 142 15 02C 0.81

<TS 1527 A

95 142 15 02C 0.07

<TS 1528 A

96 25 13 04H 0.91

<TS 1529 A

96 25 20 02H 0.83

<TS 1530 A

96 33 11 06H

-0.98

<TS 1531 A

96 41 13 04C 0.88

<TS 1532 A

96 59 15 07C

-0.92

<TS 1533 A

96 59 13 06C

-0.94

<TS 1534 A

96 59 23 04C

-0.91

<TS 1535 A

96 61 12 04H 0.21

<TS 1536 A

96 61 15 06H 0.87

<TS 1537 A

96 61 18 06C 0.09

<TS 1538 A

96 63 23 04C 0.85

<TS 1539 A

96 65 12 05H

-1

<TS 52

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 1540 A

96 69 10 04H 0.94

<TS 1541 A

96 73 11 05H 0.92

<TS 1542 A

96 87 21 05C 0.98

<TS 1543 A

96 87 14 05H 0.9

<TS 1544 A

96 89 12 05H

-0.86

<TS 1545 A

96 89 8

04H 0.99

<TS 1546 A

96 91 9

06H

-0.95

<TS 1547 A

96 91 12 04H

-0.13

<TS 1548 A

96 91 7

04H 0.84

<TS 1549 A

96 97 10 06C 0.92

<TS 1550 A

96 97 10 06C

-0.8

<TS 1551 A

96 99 10 04H

-0.15

<TS 1552 A

96 99 11 04H

-0.92

<TS 1553 A

96 103 15 05C 0.85

<TS 1554 A

96 105 19 VS6

-0.85

<TS 1555 A

96 105 13 07H 0.94

<TS 1556 A

96 109 17 04C 0.9

<TS 1557 A

96 111 18 05C 0.79

<TS 1558 A

96 111 17 04C 0.92

<TS 1559 A

96 111 11 04C 0.09

<TS 1560 A

96 131 20 04C

-0.96

<TS 1561 A

96 131 12 03C 1.03

<TS 1562 A

96 131 11 05C 0.9

<TS 1563 A

97 26 14 VS4

-0.82

<TS 1564 A

97 26 16 VS4 0.58

<TS 1565 A

97 46 13 VS4 0.87

<TS 1566 A

97 54 16 05C 0.88

<TS 1567 A

97 54 23 05C

-0.46

<TS 1568 A

97 58 17 07C 0.9

<TS 1569 A

97 62 18 06C 0.88

<TS 1570 A

97 62 16 05C

-0.97

<TS 1571 A

97 64 9

05H 0.95

<TS 1572 A

97 64 17 06C

-0.92

<TS 1573 A

97 68 14 05H 0.9

<TS 1574 A

97 70 10 07H 1.02

<TS 1575 A

97 80 12 01C 0.85

<TS 1576 A

97 82 14 05C 0.99

<TS 1577 A

97 90 16 05C 0.85

<TS 1578 A

97 90 23 VS6

-0.55

<TS 1579 A

97 96 15 04C

-0.91

<TS 1580 A

97 96 15 VS2 0.71

<TS 1581 A

97 96 12 VS2 0

<TS 1582 A

97 100 16 VS2 0.07

<TS 1583 A

97 106 24 VS4

-0.9

<TS 53

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 1584 A

97 106 17 VS4 0.92

<TS 1585 A

97 112 13 05C 0.89

<TS 1586 A

97 116 19 VS4

-0.96

<TS 1587 A

97 116 27 05C 0.5

<TS 1588 A

97 118 28 VS4 0.72

<TS 1589 A

97 120 13 VS4 0.73

<TS 1590 A

97 120 15 VS2

-0.93

<TS 1591 A

97 120 27 VS2 0.93

<TS 1592 A

97 132 13 04C

-0.92

<TS 1593 A

97 132 11 DBH 1.82

<TS 1594 A

97 138 16 02C 0.73

<TS 1595 A

97 140 8

03C

-0.9

<TS 1596 A

98 27 13 VS6 0.82

<TS 1597 A

98 27 7

VS6

-0.84

<TS 1598 A

98 35 11 05H 0.86

<TS 1599 A

98 39 16 05H 0.9

<TS 1600 A

98 45 7

05H

-0.13

<TS 1601 A

98 49 11 07C 0.86

<TS 1602 A

98 51 17 05C 0.79

<TS 1603 A

98 55 19 05H 0.75

<TS 1604 A

98 59 16 05C

-0.95

<TS 1605 A

98 63 14 05C

-0.86

<TS 1606 A

98 65 22 VS2

-0.75

<TS 1607 A

98 71 9

07C 0.09

<TS 1608 A

98 75 18 06C 0.9

<TS 1609 A

98 85 18 06C 0.8

<TS 1610 A

98 85 13 DBC 2

<TS 1611 A

98 87 26 06C 0.93

<TS 1612 A

98 87 11 06C

-0.94

<TS 1613 A

98 89 11 02C 0.81

<TS 1614 A

98 95 14 03C 0.99

<TS 1615 A

98 105 21 05C

-0.94

<TS 1616 A

98 105 26 04C 0.96

<TS 1617 A

98 109 22 05C 0.89

<TS 1618 A

98 109 15 04H 0.97

<TS 1619 A

98 109 17 05H

-0.82

<TS 1620 A

98 109 14 07H

-1

<TS 1621 A

98 111 11 07H 0.06

<TS 1622 A

98 111 18 VS2 0.56

<TS 1623 A

98 111 9

VS2

-0.24

<TS 1624 A

98 127 19 07H 0.83

<TS 1625 A

98 133 12 04C 0.97

<TS 1626 A

98 135 16 03C 0.07

<TS 1627 A

98 139 14 02C

-0.13

<TS 54

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SlG Row Column Depth Location Elevation Status 1628 A

99 26 20 VS4

-0.94

<TS 1629 A

99 26 23 VS4

-0.57

<TS 1630 A

99 60 10 03H

-0.84

<TS 1631 A

99 70 10 06H

-0.15

<TS 1632 A

99 94 16 03C 0.96

<TS 1633 A

99 96 12 07C 0.07

<TS 1634 A

99 104 13 05C

-1.02

<TS 1635 A

99 104 14 02C 0.22

<TS 1636 A

99 104 18 02C

-0.87

<TS 1637 A

99 106 11 02C

-0.94

<TS 1638 A

99 112 19 04C 0.88

<TS 1639 A

99 118 10 04H 0.13

<TS 1640 A

99 136 14 VS4

-0.87

<TS 1641 A

99 136 7

VS4 0.54

<TS 1642 A

99 138 13 02C 0.11

<TS 1643 A

99 138 15 03H 0.92

<TS 1644 A

99 138 21 03C 70.39

<TS 1645 A

99 138 16 02C

-0.91

<TS 1646 A

99 140 30 VS4

-0.83

<TS 1647 A

99 140 22 03C

-0.13

<TS 1648 A

99 140 16 03C

-0.92

<TS 1649 A

100 27 29 VS4

-0.87

<TS 1650 A

100 27 16 VS4

-0.24

<TS 1651 A

100 27 18 VS4 0.92

<TS 1652 A

100 29 15 04H 0.81

<TS 1653 A

100 29 17 05H 0.88

<TS 1654 A

100 29 21 06H 0.87

<TS 1655 A

100 31 15 06H

-0.13

<TS 1656 A

100 31 12 04H 0.85

<TS 1657 A

100 31 11 06H

-0.96

<TS 1658 A

100 33 15 03H 0.91

<TS 1659 A

100 35 14 03H

-0.82

<TS 1660 A

100 35 11 05C 0.11

<TS 1661 A

100 41 10 06C 0.83

<TS 1662 A

100 49 16 05C 0.91

<TS 1663 A

100 51 10 06H

-0.15

<TS 1664 A

100 61 11 03H

-0.81

<TS 1665 A

100 65 12 06H

-0.92

<TS 1666 A

100 67 29 VS6

-0.92

<TS 1667 A

100 75 12 06C 0.91

<TS 1668 A

100 87 14 05C 0.96

<TS 1669 A

100 87 14 04H

-0.92

<TS 1670 A

100 89 15 03C 0.96

<TS 1671 A

100 89 11 04C

-0.81

<TS 55 0

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

SIG Row Column Depth Location Elevation Status 1672 A

100 99 14 05C 0.93

<TS 1673 A

100 103 17 05C

-0.85

<TS 1674 A

100 103 22 02C 0.91

<TS 1675 A

100 107 13 04C 0.85

<TS 1676 A

100 115 15 05H

-0.88

<TS 1677 A

100 131 13 05C 0.92

<TS 1678 A

100 133 15 DBH 1.93

<TS 1679 A

100 137 15 05C

-0.98

<TS 1680 A

100 137 19 03C

-0.85

<TS 1681 A

100 137 33 03C

-0.5

<TS 1682 A

100 137 13 04C 0.83

<TS 1683 A

100 139 20 03C

-0.11

<TS 1684 A

101 28 11 03H 0.86

<TS 1685 A

101 30 20 04H

-0.15

<TS 1686 A

101 36 11 03H 1.08

<TS 1687 A

101 40 9

05H 0.06

<TS 1688 A

101 56 14 06C

-0.92

<TS 1689 A

101 68 14 06H 0.87

<TS 1690 A

101 70 16 05H 0.89

<TS 1691 A

101 70 12 07C

-0.13

<TS 1692 A

101 78 9

07H

-0.87

<TS 1693 A

101 78 8

07H 0.61

<TS 1694 A

101 86 15 07C 0.95

<TS 1695 A

101 102 10 04C 0.11

<TS 1696 A

101 104 16 05C

-0.19

<TS 1697 A

101 106 16 04C 0.83

<TS 1698 A

101 108 11 VS2 0.79

<TS 1699 A

101 112 14 06H 0.95

<TS 1700 A

101 114 12 VS2

-0.94

<TS 1701 A

101 114 15 07C

-0.85

<TS 1702 A

101 114 16 03C

-0.83

<TS 1703 A

101 118 17 DBH 1.91

<TS 1704 A

101 120 13 03C 0.85

<TS 1705 A

101 124 14 07C 0.88

<TS 1706 A

101 128 11 04H

-0.97

<TS 1707 A

101 136 11 02C 0.07

<TS 1708 A

101 136 7

03C

-0.83

<TS 1709 A

101 138 25 VS4 0.7

<TS 1710 A

102 29 25 VS4

-0.92

<TS 1711 A

102 29 16 VS4

-0.13

<TS 1712 A

102 29 18 04C

-0.91

<TS 1713 A

102 31 8

07C 0.84

<TS 1714 A

102 31 10 02C 0.88

<TS 1715 A

102 49 9

06H 0.95

<TS 56

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 1716 A

102 55 11 03C

-0.9

<TS 1717 A

102 65 30 05H

-0.87

<TS 1718 A

102 67 12 07H 0.92

<TS 1719 A

102 67 10 07C 0.07

<TS 1720 A

102 73 14 07C

-0.88

<TS 1721 A

102 83 13 01C 0.83

<TS 1722 A

102 85 12 05C 1.05

<TS 1723 A

102 89 20 04C 0.83

<TS 1724 A

102 89 13 03H 0.44

<TS 1725 A

102 89 9

04C 0.29

<TS 1726 A

102 91 13 04C

-0.87

<TS 1727 A

102 95 16 05C

-0.1

<TS 1728 A

102 95 14 02C

-0.66

<TS 1729 A

102 105 14 02C 0.2

<TS 1730 A

102 105 19 05C 0.85

<TS 1731 A

102 105 11 03C 0.15

<TS 1732 A

102 105 15 03C

-0.98

<TS 1733 A

102 113 15 05C 0.85

<TS 1734 A

102 117 22 03H 0.91

<TS 1735 A

102 121 23 VS4

-0.88

<TS 1736 A

102 133 14 03C

-0.92

<TS 1737 A

102 135 11 02C 0.86

<TS 1738 A

102 135 20 04C 0.74

<TS 1739 A

102 135 20 03C

-0.18

<TS 1740 A

102 135 9

02C

-0.19

<TS 1741 A

102 137 17 04C

-0.89

<TS 1742 A

103 30 14 05H

-0.78

<TS 1743 A

103 30 9

06H

-0.91

<TS 1744 A

103 30 8

05C 0.82

<TS 1745 A

103 30 13 07H

-0.97

<TS 1746 A

103 30 16 VS4 0.62

<TS 1747 A

103 30 7

VS4

-0.22

<TS 1748 A

103 32 18 VS4

-0.92

<TS 1749 A

103 32 9

VS4 0.57

<TS 1750 A

103 32 9

03C 0.11

<TS 1751 A

103 32 14 02C

-0.15

<TS 1752 A

103 36 11 05C

-0.89

<TS 1753 A

103 36 12 VS2 1

<TS 1754 A

103 36 10 VS2

-0.96

<TS 1755 A

103 54 10 05H 0.91

<TS 1756 A

103 54 8

04H

-0.93

<TS 1757 A

103 68 11 07H

-0.94

<TS 1758 A

103 82 11 05H

-0.81

<TS 1759 A

103 82 16 05H

-0.09

<TS 57

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 1760 A

103 82 14 06H 0.96

<TS 1761 A

103 82 7

06H

-0.17

<TS 1762 A

103 84 11 07H 0.92

<TS 1763 A

103 86 19 VS2 0.6

<TS 1764 A

103 86 14 VS2 0.15

<TS 1765 A

103 92 16 05C 0.98

<TS 1766 A

103 92 12 04C 0.85

<TS 1767 A

103 92 7

04C

-0.74

<TS 1768 A

103 96 15 05C 0.87

<TS 1769 A

103 100 15 05C

-0.82

<TS 1770 A

103 102 13 03C

-0.15

<TS 1771 A

103 108 10 07C 0.85

<TS 1772 A

103 108 15 07C

-0.18

<TS 1773 A

103 118 11 04C

-0.82

<TS 1774 A

103 122 19 DBC 1.69

<TS 1775 A

103 122 10 07C 0.92

<TS 1776 A

103 134 16 04C 0.78

<TS 1777 A

103 134 15 04C 0.02

<TS 1778 A

103 136 15 02C 0.87

<TS 1779 A

104 31 22 VS4

-0.87

<TS 1780 A

104 31 21 VS4 0.87

<TS 1781 A

104 33 14 04C

-0.89

<TS 1782 A

104 33 15 03C

-0.89

<TS 1783 A

104 61 14 06C 0.87

<TS 1784 A

104 63 14 05C

-0.9

<TS 1785 A

104 63 16 07C

-0.94

<TS 1786 A

104 69 10 07H

-0.94

<TS 1787 A

104 77 15 06C 0.87

<TS 1788 A

104 85 12 04C 0.96

<TS 1789 A

104 85 14 VS2

-0.9

<TS 1790 A

104 85 18 04C

-0.89

<TS 1791 A

104 87 23 04C

-0.97

<TS 1792 A

104 87 13 04C

-0.12

<TS 1793 A

104 89 14 02C

-0.86

<TS 1794 A

104 93 13 06H 0.86

<TS 1795 A

104 95 16 VS2

-0.79

<TS 1796 A

104 97 10 03C

-0.04

<TS 1797 A

104 97 13 03C 0.86

<TS 1798 A

104 97 22 04C

-1.01

<TS 1799 A

104 99 17 06C 0.86

<TS 1800 A

104 103 14 05C 0.89

<TS 1801 A

104 121 14 06C 0.85

<TS 1802 A

104 123 16 04C 0.9

<TS 1803 A

104 133 17 05C

-0.17

<TS 58

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

SIG Row Column Depth Location Elevation Status 1804 A

104 135 24 03C 0.8

<TS 1805 A

105 32 13 04H

-0.85

<TS 1806 A

105 32 14 01C 0.09

<TS 1807 A

105 90 19 05C 0.91

<TS 1808 A

105 92 14 07C

-0.99

<TS 1809 A

105 112 20 05H 0.93

<TS 1810 A

105 112 12 06H

-0.11

<TS 1811 A

105 120 12 04C 0.82

<TS 1812 A

105 120 12 03C

-1.02

<TS 1813 A

105 122 13 06C 0.78

<TS 1814 A

105 132 23 03C 0.9

<TS 1815 A

105 136 14 VS4 0.94

<TS 1816 A

105 136 18 VS4

-0.76

<TS 1817 A

106 31 14 03C 0.95

<TS 1818 A

106 31 15 01C

-0.89

<TS 1819 A

106 31 22 04C 0.87

<TS 1820 A

106 33 16 VS4

-0.73

<TS 1821 A

106 33 12 VS4

-1.02

<TS 1822 A

106 35 18 03C 0.88

<TS 1823 A

106 35 14 03C 0.04

<TS 1824 A

106 43 8

07H

-0.76

<TS 1825 A

106 45 11 05H

-0.15

<TS 1826 A

106 47 14 04C 0.9

<TS 1827 A

106 47 15 04C 0.12

<TS 1828 A

106 57 19 07H 0.86

<TS 1829 A

106 59 14 VS2

-0.9

<TS 1830 A

106 67 19 VS6 0.72

<TS 1831 A

106 69 14 VS2 0.69

<TS 1832 A

106 69 14 07C

-0.15

<TS 1833 A

106 101 18 04H 0.9

<TS 1834 A

106 117 13 04H 0.74

<TS 1835 A

106 117 17 06C

-0.91

<TS 1836 A

106 119 14 04C

-0.87

<TS 1837 A

106 121 11 04C 0.2

<TS 1838 A

106 121 18 04C 0.97

<TS 1839 A

106 121 19 05C 0.46

<TS 1840 A

106 125 8

06C 0.87

<TS 1841 A

106 131 13 04H

-0.74

<TS 1842 A

106 131 12 03C

-0.2

<TS 1843 A

106 131 13 03C

-0.93

<TS 1844 A

106 133 20 DBC 1.92

<TS 1845 A

106 133 12 03C 0.94

<TS 1846 A

106 135 12 01H 0.11

<TS 1847 A

106 135 16 03C

-0.81

<TS 59

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 1848 A

107 32 13 VS4

-0.35

<TS 1849 A

107 32 8

04C

-0.91

<TS 1850 A

107 32 36 VS4

-0.76

<TS 1851 A

107 32 15 04C

-0.22

<TS 1852 A

107 32 17 03C 0.93

<TS 1853 A

107 34 9

01H 0.88

<TS 1854 A

107 36 9

03C 0.85

<TS 1855 A

107 44 13 05H

-0.93

<TS 1856 A

107 44 16 05H

-0.15

<TS 1857 A

107 44 13 VS2 0.71

<TS 1858 A

107 84 9

05C

-0.83

<TS 1859 A

107 92 15 05C 0.95

<TS 1860 A

107 94 14 04C

-0.86

<TS 1861 A

107 98 12 03C

-0.06

<TS 1862 A

107 98 11 04C

-0.11

<TS 1863 A

107 114 10 03C 0.13

<TS 1864 A

107 118 11 04C

-0.84

<TS 1865 A

107 122 11 03C

-0.13

<TS 1866 A

107 124 14 VS2

-0.84

<TS 1867 A

107 124 13 VS2

-0.09

<TS 1868 A

107 124 14 VS2 0.69

<TS 1869 A

107 128 15 04C

-0.92

<TS 1870 A

107 130 26 VS2

-0.77

<TS 1871 A

107 130 13 VS2 0.75

<TS 1872 A

107 130 14 03C

-0.89

<TS 1873 A

107 134 18 03H 0.85

<TS 1874 A

107 134 26 VS4

-0.93

<TS 1875 A

107 134 20 VS4 0.82

<TS 1876 A

107 134 14 03C

-0.88

<TS 1877 A

107 134 29 02C

-0.93

<TS 1878 A

108 33 34 VS4

-0.94

<TS 1879 A

108 33 28 VS4 0.92

<TS 1880 A

108 35 22 01C 0.89

<TS 1881 A

108 35 29 01C 0.09

<TS 1882 A

108 39 10 04H 0.87

<TS 1883 A

108 63 10 VS2 0.2

<TS 1884 A

108 63 20 VS2 0.83

<TS 1885 A

108 65 18 DBH 1.8

<TS 1886 A

108 67 12 06C

-0.94

<TS 1887 A

108 69 13 07C 0.88

<TS 1888 A

108 87 14 05C 1

<TS 1889 A

108 89 15 06C

-0.83

<TS 1890 A

108 93 19 06C 0.55

<TS 1891 A

108 95 16 03C 0.77

<TS 60

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 1892 A

108 99 12 DBH 1.98

<TS 1893 A

108 115 13 05H 0.89

<TS 1894 A

108 117 14 05C 0.9

<TS 1895 A

108 119 13 03C 0.28

<TS 1896 A

108 131 13 02C

-0.87

<TS 1897 A

108 133 14 04C 0.74

<TS 1898 A

108 133 21 04C

-0.92

<TS 1899 A

109 34 9

0iC 0.83

<TS 1900 A

109 34 31 VS4 0.7

<TS 1901 A

109 34 12 VS4

-0.92

<TS 1902 A

109 34 11 05H

-0.9

<TS 1903 A

109 34 12 04H

-0.91

<TS 1904 A

109 34 11 01H 0.92

<TS 1905 A

109 42 10 03H 0.89

<TS 1906 A

109 62 14 06C 0.88

<TS 1907 A

109 90 14 07C

-0.09

<TS 1908 A

109 90 9

07C

-0.88

<TS 1909 A

109 98 31 VS2

-0.87

<TS 1910 A

109 114 20 06C 0.82

<TS 1911 A

109 114 12 03C 0.83

<TS 1912 A

109 116 11 04H

-0.79

<TS 1913 A

109 118 19 04C

-0.87

<TS 1914 A

109 120 21 03C

-0.11

<TS 1915 A

109 124 13 08C

-0.92

<TS 1916 A

109 124 10 02C 0.86

<TS 1917 A

109 132 22 04C 0.81

<TS 1918 A

110 35 18 01H 0.89

<TS 1919 A

110 39 18 VS2 0.9

<TS 1920 A

110 47 13 05C 0.92

<TS 1921 A

110 79 12 06C

-0.13

<TS 1922 A

110 83 17 06C 1.1

<TS 1923 A

110 91 15 04C

-0.88

<TS 1924 A

110 109 10 05C 0.83

<TS 1925 A

110 109 11 04C 0.81

<TS 1926 A

110 115 10 04C 0.92

<TS 1927 A

110 115 12 08H 1.17

<TS 1928 A

110 123 24 08H

-1.13

<TS 1929 A

110 131 14 01H 0.15

<TS 1930 A

110 131 15 05C

-0.22

<TS 1931 A

110 131 12 04C

-0.82

<TS 1932 A

110 131 19 03C 0.76

<TS 1933 A

110 131 34 DBH

-1.76

<TS 1934 A

111 44 16 06C

-0.15

<TS 1935 A

111 50 11 04H

-0.93

<TS 61

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

SIG Row Column Depth Location Elevation Status 1936 A

111 62 23 VS2

-0.85

<TS 1937 A

111 82 9

02H 0.89

<TS 1938 A

111 86 13 02C 0.91

<TS 1939 A

111 100 11 05C 0.85

<TS 1940 A

111 104 15 04C

-0.13

<TS 1941 A

111 116 11 03C 0.86

<TS 1942 A

111 116 12 03H 0.9

<TS 1943 A

111 126 15 04C 0.85

<TS 1944 A

111 126 8

04C 0.09

<TS 1945 A

111 128 19 03C 0.79

<TS 1946 A

111 128 22 03C

-0.84

<TS 1947 A

111 128 14 VS4 0.89

<TS 1948 A

111 130 17 03H

-0.91

<TS 1949 A

111 130 22 04C

-0.17

<TS 1950 A

112 37 22 02C

-0.89

<TS 1951 A

112 37 11 DBH

-1.52

<TS 1952 A

112 41 20 VS4

-1.01

<TS 1953 A

112 41 10 VS6

-0.84

<TS 1954 A

112 59 23 VS4

-0.85

<TS 1955 A

112 59 25 VS4 0.04

<TS 1956 A

112 59 36 VS6 0.92

<TS 1957 A

112 89 10 04C

-0.91

<TS 1958 A

112 103 13 VS2

-0.83

<TS 1959 A

112 103 13 VS2 0.87

<TS 1960 A

112 103 7

04H 0.04

<TS 1961 A

112 103 16 04H 0.89

<TS 1962 A

112 115 16 04C

-0.85

<TS 1963 A

112 119 12 04H 0.79

<TS 1964 A

112 125 17 05C

-0.82

<TS 1965 A

112 125 15 04C 0.78

<TS 1966 A

112 127 17 05C

-0.92

<TS 1967 A

113 36 9

01H

-0.08

<TS 1968 A

113 36 14 01H 0.95

<TS 1969 A

113 38 13 02C 0.88

<TS 1970 A

113 38 10 0iC

-0.95

<TS 1971 A

113 68 21 VS2

-0.74

<TS 1972 A

113 68 15 VS4

-0.84

<TS 1973 A

113 68 13 VS4 0.84

<TS 1974 A

113 68 12 VS2 0.19

<TS 1975 A

113 90 13 03C

-1

<TS 1976 A

113 90 13 VS4

-0.7

<TS 1977 A

113 90 12 VS6

-0.74

<TS 1978 A

113 118 16 04C 0.11

<TS 1979 A

113 128 13 03H 0.9

<TS 62

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 1980 A

113 128 17 04H

-0.89

<TS 1981 A

114 47 10 05H 0.94

<TS 1982 A

114 51 10 04C 0.86

<TS 1983 A

114 53 10 04H 0.8

<TS 1984 A

114 53 10 04C 0.84

<TS 1985 A

114 75 11 06H 0.81

<TS 1986 A

114 79 10 05H 0.89

<TS 1987 A

114 119 13 07C 0.78

<TS 1988 A

114 119 14 03C 0.76

<TS 1989 A

114 121 12 04C 0.88

<TS 1990 A

114 121 9

03C

-0.95

<TS 1991 A

114 123 17 04C

-0.85

<TS 1992 A

114 123 21 03C

-0.88

<TS 1993 A

114 129 10 03H 0.92

<TS 1994 A

114 129 12 08H

-1.04

<TS 1995 A

115 38 13 VS4 0.75

<TS 1996 A

115 38 16 02C 0.07

<TS 1997 A

115 38 15 02C

-0.92

<TS 1998 A

115 50 12 VS4

-0.79

<TS 1999 A

115 78 19 06H

-0.86

<TS 2000 A

115 82 13 05H 0.86

<TS 2001 A

115 82 9

05H

-0.25

<TS 2002 A

115 90 38 VS4

-0.85

<TS 2003 A

115 92 28 VS1 0.71

<TS 2004 A

115 124 14 05C 0.8

<TS 2005 A

115 124 20 04C

-0.85

<TS 2006 A

115 124 12 03C 0.81

<TS 2007 A

115 128 15 05H 0.91

<TS 2008 A

116 39 17 VS6

-0.53

<TS 2009 A

116 39 34 02C

-0.9

<TS 2010 A

116 39 18 01C

-0.46

<TS 2011 A

116 45 14 02H 0.84

<TS 2012 A

116 51 19 07H 0.81

<TS 2013 A

116 51 12 05H

-0.17

<TS 2014 A

116 53 14 05C 0.88

<TS 2015 A

116 55 13 05H

-0.88

<TS 2016 A

116 63 14 VS6

-0.76

<TS 2017 A

116 81 9

06C 0.89

<TS 2018 A

116 81 11 06C

-0.92

<TS 2019 A

116 81 12 05H 0.88

<TS 2020 A

116 81 13 VS6

-0.92

<TS 2021 A

116 95 11 06C 0.98

<TS 2022 A

116 95 15 07C

-0.94

<TS 2023 A

116 97 12 DBH

-1.58

<TS 63

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 2024 A

116 97 12 VS2

-0.88

<TS 2025 A

116 111 13 05C 0.02

<TS 2026 A

116 119 20 03C 0.76

<TS 2027 A

116 121 25 04C 0.85

<TS 2028 A

116 121 14 03C

-0.9

<TS 2029 A

116 121 11 04C

-0.09

<TS 2030 A

116 123 16 06C 0.09

<TS 2031 A

117 40 24 VS4

-0.99

<TS 2032 A

117 40 26 02C 0.9

<TS 2033 A

117 40 12 02C

-0.17

<TS 2034 A

117 42 11 02C 0.86

<TS 2035 A

117 42 34 01C

-0.95

<TS 2036 A

117 44 8

02C 0.87

<TS 2037 A

117 58 13 06C 0.59

<TS 2038 A

117 70 17 06C 0.89

<TS 2039 A

117 72 11 07H 0.11

<TS 2040 A

117 76 11 07H 0.15

<TS 2041 A

117 78 9

04H 0.85

<TS 2042 A

117 82 13 05H

-0.92

<TS 2043 A

117 94 13 03C 0.88

<TS 2044 A

117 110 14 03C 0.83

<TS 2045 A

117 114 14 03C

-0.85

<TS 2046 A

117 120 15 03H 0.82

<TS 2047 A

117 120 14 02C 0.82

<TS 2048 A

117 122 17 04C

-0.26

<TS 2049 A

117 122 15 VS4 0.09

<TS 2050 A

118 41 14 01H 0.89

<TS 2051 A

118 41 19 VS4

-0.97

<TS 2052 A

118 41 30 02C 0

<TS 2053 A

118 43 10 03H 0.86

<TS 2054 A

118 43 10 06H

-1.13

<TS 2055 A

118 43 9

02C

-0.95

<TS 2056 A

118 43 34 01C

-0.97

<TS 2057 A

118 43 6

02C 0.88

<TS 2058 A

118 47 15 02H 0.85

<TS 2059 A

118 51 15 06C 0.86

<TS 2060 A

118 97 17 VS2

-1.04

<TS 2061 A

118 101 12 04H

-0.13

<TS 2062 A

118 105 23 04C 0.87

<TS 2063 A

118 125 20 VS7

-0.59

<TS 2064 A

119 44 10 02H 0.85

<TS 2065 A

119 52 28 06C 0.86

<TS 2066 A

119 60 16 VS4

-0.92

<TS 2067 A

119 60 14 VS4 0.97

<TS 64

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 2068 A

119 76 15 06C 0.87

<TS 2069 A

119 98 11 07H 0.81

<TS 2070 A

119 110 21 04C

-0.88

<TS 2071 A

119 122 14 03C 0.74

<TS 2072 A

120 45 10 02H 0.82

<TS 2073 A

120 75 15 08C

-0.87

<TS 2074 A

120 77 12 07C 0.09

<TS 2075 A

120 81 18 07C 0.87

<TS 2076 A

120 81 9

VS4 0.98

<TS 2077 A

120 81 18 07C 0.09

<TS 2078 A

120 81 14 06C 0.85

<TS

.2079 A

120 89 17 06C

-0.89

<TS 2080 A

120 93 18 06C 0.99

<TS 2081 A

120 111 16 04C 0.09

<TS 2082 A

120 111 11 03C

-0.99

<TS 2083 A

120 115 17 05C

-0.95

<TS 2084 A

120 115 15 04C 0.78

<TS 2085 A

120 117 12 04C 0.85

<TS 2086 A

120 119 21 03C 0.72

<TS 2087 A

120 121 23 05C 0.85

<TS 2088 A

120 123 14 01H

-0.13

<TS 2089 A

121 44 22 VS4 0

<TS 2090 A

121 44 15 VS7 0.9

<TS 2091 A

121 44 10 02C 0.88

<TS 2092 A

121 44 18 01C

-0.9

<TS 2093 A

121 44 10 VS4 0.7

<TS 2094 A

121 50 16 06C 0.81

<TS 2095 A

121 88 11 07C

-0.94

<TS 2096 A

121 104 14 VS6

-0.84

<TS 2097 A

121 104 13 VS6

-0.09

<TS 2098 A

121 104 9

VS6 0.84

<TS 2099 A

121 106 12 02C 0.88

<TS 2100 A

121 112 24 VS7

-0.71

<TS 2101 A

121 116 15 04C

-0.84

<TS 2102 A

121 116 22 03C 0.82

<TS 2103 A

121 118 33 VS4

-0.8

<TS 2104 A

121 118 21 VS4

-0.07

<TS 2105 A

121 118 23 VS4 0.76

<TS 2106 A

121 118 27 03C 0.92

<TS 2107 A

121 120 15 05H 0.8

<TS 2108 A

121 120 16 06H 0.85

<TS 2109 A

121 120 7

05H

-0.84

<TS 2110 A

122 45 16 01C 0.91

<TS 2111 A

122 53 12 06H 0.79

<TS 65

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 2112 A

122 63 13 05H 0.84

<TS 2113 A

122 105 14 04C 0.85

<TS 2114 A

122 105 11 04C 0.09

<TS 2115 A

122 111 19 05C

-0.85

<TS 2116 A

122 111 13 02C

-0.2

<TS 2117 A

123 48 11 05C 0.88

<TS 2118 A

123 52 12 06H

-0.99

<TS 2119 A

123 110 14 06C

-0.57

<TS 2120 A

123 112 12 03C 0.87

<TS 2121 A

123 114 16 04C

-0.18

<TS 2122 A

123 120 10 02H

-0.87

<TS 2123 A

123 120 11 04H

-0.96

<TS 2124 A

123 120 11 02H 0.88

<TS 2125 A

123 120 8

04H 0.88

<TS 2126 A

124 49 15 01H 0.9

<TS 2127 A

124 51 16 03H 0.84

<TS 2128 A

124 57 12 05C 0.9

<TS 2129 A

124 117 11 06C

-0.18

<TS 2130 A

124 117 14 03C 0.07

<TS 2131 A

124 119 8

02C

-0.8

<TS 2132 A

124 119 12 VS4

-0.99

<TS 2133 A

125 48 26 VS4

-0.96

<TS 2134 A

125 88 18 08H 0.88

<TS 2135 A

125 110 24 03C 0.85 TS 2136 A

125 112 20 07H

-0.28

<TS 2137 A

125 112 15 04C

-0.89

<TS 2138 A

125 112 19 03C 0.13

<TS 2139 A

125 114 15 03H

-0.19

<TS 2140 A

125 114 17 02C 0.87

<TS 2141 A

125 118 11 VS4

-0.82

<TS 2142 A

125 118 8

VS4

-0.22

<TS 2143 A

126 51 12 01H 0.11

<TS 2144 A

126 51 24 03H 0.8

<TS 2145 A

126 61 12 07H

-1.03

<TS 2146 A

126 61 8

08C

-0.92

<TS 2147 A

126 63 11 07H 0.88

<TS 2148 A

126 69 15 08H

-0.91

<TS 2149 A

126 73 11 08C

-0.85

<TS 2150 A

126 77 14 VS1 0.91

<TS 2151 A

126 77 13 VS1

-0.87

<TS 2152 A

126 83 14 07H 0.11

<TS 2153 A

126 85 11 06C 0.9

<TS 2154 A

126 95 10 06H 0

<TS 2155 A

126 103 32 VS4

-1.07

<TS 66

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 2156 A

126 109 16 05C 0.81

<TS 2157 A

126 109 11 05C 0.07

<TS 2158 A

126 109 11 03C 0.83

<TS 2159 A

126 109 12 03C 0.04

<TS 2160 A

126 111 16 VS7 0.99

<TS 2161 A

126 111 9

04C

-0.15

<TS 2162 A

126 111 19 03C

-0.9

<TS 2163 A

126 111 13 02C

-0.89

<TS 2164 A

126 115 10 05H 0.94

<TS 2165 A

126 115 17 04C 0.88

<TS 2166 A

126 115 12 03C 0.95

<TS 2167 A

126 115 17 02C

-0.88

<TS 2168 A

126 115 12 02C 0.2

<TS 2169 A

127 52 16 02C

-0.89

<TS 2170 A

127 52 10 01C 0.85

<TS 2171 A

127 52 13 03C

-0.13

<TS 2172 A

127 56 11 DBH 1.94

<TS 2173 A

127 72 21 VS6

-0.37

<TS 2174 A

127 80 16 VS7 0.48

<TS 2175 A

127 80 16 06C 0.83

<TS 2176 A

127 90 13 08H

-1

<TS 2177 A

127 98 12 04C

-1.07

<TS 2178 A

127 108 16 05C

-0.96

<TS 2179 A

127 112 28 03C

-0.96

<TS 2180 A

127 112 12 02C

-0.9

<TS 2181 A

127 114 13 05C

-0.22

<TS 2182 A

128 53 23 02H

-0.97

<TS 2183 A

128 69 14 08H 0.83

<TS 2184 A

128 77 20 07C 0.88

<TS 2185 A

128 91 15 08C 0.88

<TS 2186 A

128 93 15 VS6

-0.97

<TS 2187 A

128 107 13 03C 0.82

<TS 2188 A

128 107 15 02C 0.86

<TS 2189 A

128 111 16 05C 0.83

<TS 2190 A

128 113 14 05C

-0.94

<TS 2191 A

129 54 30 02C

-0.94

<TS 2192 A

129 56 21 02H 0.92

<TS 2193 A

129 58 30 02H 0.9

<TS 2194 A

129 58 10 07H

-1.06

<TS 2195 A

129 74 16 VS1

-0.9

<TS 2196 A

129 84 12 VS4 0.59

<TS 2197 A

129 92 15 VS4

-0.9

<TS 2198 A

129 92 8

VS4 0.99

<TS 2199 A

129 110 26 02C 0.88

<TS 67

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 2200 A

129 110 18 04C 0.09

<TS 2201 A

129 112 10 VS1

-0.94

<TS 2202 A

130 55 18 02H 0.88

<TS 2203 A

130 57 13 02H 0.94

<TS 2204 A

130 57 25 08H 0.86

<TS 2205 A

130 89 13 DBC

-1.94

<TS 2206 A

130 95 24 VS4

-1.12

<TS 2207 A

130 99 10 03C

-0.83

<TS 2208 A

130 99 26 03C

-0.14

<TS 2209 A

130 107 19 02C 0.97

<TS 2210 A

130 107 15 03C

-0.2

<TS 2211 A

131 58 12 02H 0.92

<TS 2212 A

131 76 14 06C 0.96

<TS 2213 A

131 94 16 08H 0.9

<TS 2214 A

131 94 17 08H

-0.99

<TS 2215 A

131 96 23 06C 0.82

<TS 2216 A

131 98 15 03C 0.82

<TS 2217 A

131 106 14 03C

-0.24

<TS 2218 A

132 59 14 01C 0.83

<TS 2219 A

132 61 13 01H 0.19

<TS 2220 A

132 63 6

07H

-1.03

<TS 2221 A

132 67 17 VS2

-0.92

<TS 2222 A

132 67 13 VS2 0.9

<TS 2223 A

132 81 14 DBC 1.95

<TS 2224 A

132 87 13 DBH 1.23

<TS 2225 A

132 97 9

08C 0.04

<TS 2226 A

132 99 14 06C 0.91

<TS 2227 A

132 107 13 04C 0.11

<TS 2228 A

132 107 10 03C 0.83

<TS 2229 A

132 107 16 03C

-0.95

<TS 2230 A

133 60 16 02H

-0.85

<TS 2231 A

133 60 13 02H 0.89

<TS 2232 A

133 62 19 07H

-1.03

<TS 2233 A

133 62 11 07H 0.92

<TS 2234 A

133 62 16 03H 0.89

<TS 2235 A

133 64 17 05H

-0.15

<TS 2236 A

133 70 15 08C 0.85

<TS 2237 A

133 74 21 VS4 0.15

<TS 2238 A

133 74 22 VS4 0.79

<TS 2239 A

133 84 16 08H

-0.2

<TS 2240 A

133 86 16 DBC

-1.62

<TS 2241 A

133 88 17 DBC 1.95

<TS 2242 A

133 92 22 VS6 0.94

<TS 2243 A

133 94 15 VS4

-0.88

<TS 68

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

S/G Row Column Depth Location Elevation Status 2244 A

133 94 12 DBC

-1.84

<TS 2245 A

133 94 14 DBC 1.71

<TS 2246 A

133 94 16 VS2 0.7

<TS 2247 A

133 98 18 DBC 1.94

<TS 2248 A

133 104 14 07C 0.87

<TS 2249 A

133 104 11 06C

-0.26

<TS 2250 A

133 104 15 05C 0.87

<TS 2251 A

133 104 12 08C 0.8

<TS 2252 A

133 104 10 05C 0.06

<TS 2253 A

133 104 12 08C

-0.8

<TS 2254 A

134 65 22 07H

-0.17

<TS 2255 A

134 65 15 06H 0.96

<TS 2256 A

134 65 15 08H 0.79

<TS 2257 A

134 69 23 VS7 0.22

<TS 2258 A

134 69 31 VS7 0.71

<TS 2259 A

134 71 16 VS1 0.24

<TS 2260 A

134 71 24 VS1 0.76

<TS 2261 A

134 71 14 VS1

-0.89

<TS 2262 A

134 87 13 VS7 0.66

<TS 2263 A

134 99 18 04C

-0.85

<TS 2264 A

134 103 17 02C

-0.87

<TS 2265 A

135 68 15 07H 0.87

<TS 2266 A

135 76 16 DBC 1.78

<TS 2267 A

135 78 12 VS4 0.91

<TS 2268 A

135 78 26 08C

-1.02

<TS 2269 A

135 78 9

08C 0.89

<TS 2270 A

135 78 10 VS4

-0.07

<TS 2271 A

135 78 22 VS7 0.7

<TS 2272 A

135 82 16 08H 0.9

<TS 2273 A

135 82 14 08C

-1.05

<TS 2274 A

135 86 16 DBC

-1.72

<TS 2275 A

135 86 18 VS4 0.93

<TS 2276 A

135 90 22 08C 0.92

<TS 2277 A

135 96 42 VS6 0.97 PLG 2278 A

135 98 11 03C

-0.99

<TS 2279 A

135 100 22 02C 0.8

<TS 2280 A

135 100 16 04C

-1.02

<TS 2281 A

136 69 12 VS7 0.88

<TS 2282 A

136 69 15 VS7

-0.9

<TS 2283 A

136 71 11 04H 0.87

<TS 2284 A

136 79 13 VS7

-0.77

<TS 2285 A

136 79 21 VS7 0.77

<TS 2286 A

136 79 14 08C

-1.09

<TS 2287 A

136 79 31 07C

-0.18

<TS 69

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear Percent in No.

SIG Row Column Depth Location Elevation Status 2288 A

136 79 11 07C

-1.01

<TS 2289 A

136 85 17 08H

-0.99

<TS 2290 A

136 85 10 07H 0.07

<TS 2291 A

136 89 12 DBC 1.95

<TS 2292 A

136 91 10 04C

-0.89

<TS 2293 A

136 91 21 06C

-1.02

<TS 2294 A

136 91 15 06C

-0.26

<TS 2295 A

136 91 20 07C

-1.08

<TS 2296 A

136 91 22 08C

-0.77

<TS 2297 A

136 91 29 08C 0.7

<TS 2298 A

136 91 12 05C

-1

<TS 2299 A

136 91 13 05C 0.02

<TS 2300 A

136 91 13 DBC 1.99

<TS 2301 A

136 91 12 VS1 0.75

<TS 2302 A

137 74 8

08H

-1.12

<TS 2303 A

137 74 11 03H 0.89

<TS 2304 A

137 76 28 VS4

-0.79

<TS 2305 A

137 76 28 VS4

-0.11

<TS 2306 A

137 78 12 08C 0.84

<TS 2307 A

137 82 9

08C

-1.05

<TS 2308 A

137 88 20 VS6

-0.22

<TS 2309 A

137 88 16 VS6

-0.84

<TS 2310 A

137 90 16 DBC 0.79

<TS 2311 A

137 92 18 02C 0.89

<TS 2312 A

137 92 12 03C 0.9

<TS 2313 A

137 92 17 04C 0.84

<TS 2314 A

137 92 31 05C 0.09

<TS 2315 A

137 92 10 06C

-1.08

<TS 2316 A

137 92 18 07C

-0.92

<TS 2317 A

137 92 18 08C

-0.81

<TS 2318 A

137 92 27 08C 0.7

<TS 2319 A

138 75 17 08C 0.09

<TS 2320 A

138 75 6

08C

-0.81

<TS 2321 A

138 75 10 07H 0.85

<TS 2322 A

138 75 6

08C 0.87

<TS 2323 A

138 75 10 07C 0.81

<TS 2324 A

138 75 10 07H

-1.11

<TS 2325 A

138 81 12 08H 0.72

<TS 2326 A

138 81 20 08C

-1.02

<TS 2327 A

138 81 12 08H

-0.15

<TS 2328 A

138 83 15 08H

-1.1

<TS 2329 A

138 83 11 08H

-0.04

<TS 2330 A

138 83 27 DBH 1.94

<TS 2331 A

138 83 15 VS1

-0.79

<TS 70

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4B Steam Generator E-50A Indications (all indications due to tube wear)

Percent in No.

S/G Row Column Depth Location Elevation Status 2332 A

138 85 17 08H

-1.05

<TS 2333 A

138 85 14 VS6 0.99

<TS 2334 A

138 85 26 VS7 0.85

<TS 2335 A

138 85 17 08C

-0.26

<TS 2336 A

138 85 16 DBC

-1.56

<TS 2337 A

138 85 10 08C 0.92

<TS 2338 A

138 87 16 08C 0.81

<TS 71

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1

B 1

10 13 03C

-0.15

<TS 2

B 1

28 12 02C 0.96

<TS 3

B 1

36 13 03C 0.83

<TS 4

B 1

124 11 02C 0.81

<TS 5

B 1

130 11 03C 0.97

<TS 6

B 1

150 16 01C

-0.91

<TS 7

B 1

150 13 01C

-0.21

<TS 8

B 1

158 16 02C 0.75

<TS 9

B 1

160 11 03C

-0.1

<TS 10 B

1 160 16 04H 0.87

<TS 11 B

1 160 11 04H

-0.15

<TS 12 B

1 164 17 02C

-0.92

<TS 13 B

2 11 12 02C 0.9

<TS 14 B

2 141 17 03H

-0.88

<TS 15 B

2 143 11 02C 0.91

<TS 16 B

2 163 14 02H 0.9

<TS 17 B

2 165 15 01C 0.88

<TS 18 B

3 2

12 03H 0.86

<TS 19 B

3 6

15 02C 0.77

<TS 20 B

3 36 15 03C 0.85

<TS 21 B

3 42 18 03C 0.78

<TS 22 B

3 162 12 02H

-0.27

<TS 23 B

4 125 11 04C

-0.86

<TS 24 B

4 165 12 02C 0.88

<TS 25 B

4 165 11 02C

-0.91

<TS 26 B

5 138 12 02H

-0.9

<TS 27 B

6 23 12 04C 0.83

<TS 28 B

6 137 11 04C

-0.91

<TS 29 B

6 165 19 02C

-0.93

<TS 30 B

7 2

13 05H 0.85

<TS 31 B

7 26 13 01C

-0.78

<TS 32 B

7 140 13 04C 0.89

<TS 33 B

7 148 11 02H 0.24

<TS 34 B

8 3

15 03C

-0.17

<TS 35 B

8 33 11 03H

-0.88

<TS 36 B

8 129 11 04C

-0.68

<TS 37 B

8 159 10 04C 0.88

<TS 38 B

8 161 10 03H 0.88

<TS 39 B

8 161 13 04H 0.62

<TS 40 B

8 165 16 02C

-0.82

<TS 41 B

9 2

11 03C

-0.17

<TS 42 B

9 140 13 03C 0.87

<TS 43 B

10 133 16 04C

-0.71

<TS 44 B

10 133 12 02C 0.86

<TS 45 B

10 133 7

04C 0.17

<TS 72

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 46 B

10 165 16 02H 0.85

<TS 47 B

11 2

15 02H 0.93

<TS 48 B

11 32 11 04C

-0.93

<TS 49 B

11 32 10 05H 0.94

<TS 50 B

11 32 11 DBH

-1.82

<TS 51 B

11 112 8

DBC 1.17

<TS 52 B

11 136 10 02C

-0.13

<TS 53 B

11 164 22 04C 0.72

<TS 54 B

11 164 21 02C

-0.97

<TS 55 B

12 3

14 03C

-0.95

<TS 56 B

12 3

10 02C 0.8

<TS 57 B

13 2

10 04C

-0.08

<TS 58 B

13 4

16 02H

-0.85

<TS 59 B

13 6

12 03C 0.82

<TS 60 B

13 8

11 03C

-0.84

<TS 61 B

13 12 13 02C

-0.89

<TS 62 B

13 56 12 04H 0.82

<TS 63 B

13 62 14 05C

-0.93

<TS 64 B

13 140 14 02H 0.8

<TS 65 B

14 57 11 03H 0.94

<TS 66 B

14 61 11 02H 0.86

<TS 67 B

14 121 11 05C 1.15

<TS 68 B

14 137 12 03H 0.93

<TS 69 B

14 157 12 02C 0.82

<TS 70 B

15 32 10 03H 0.06

<TS 71 B

15 130 25 05C

-0.92

<TS 72 B

15 154 16 04H 0.82

<TS 73 B

15 162 7

DBC

-1.91

<TS 74 B

15 164 15 02H 1.04

<TS 75 B

15 164 12 02C 0.8

<TS 76 B

16 3

10 02C 0.06

<TS 77 B

16 37 9

05C

-0.19

<TS 78 B

16 55 8

DBH

-1.77

<TS 79 B

16 131 10 03C 0.89

<TS 80 B

16 139 11 DBC 1.55

<TS 81 B

16 145 10 04C

-0.9

<TS 82 B

17 2

12 03C 0.82

<TS 83 B

17 36 12 04H

-0.79

<TS 84 B

17 60 12 02C 0.93

<TS 85 B

17 62 9

DBH 1.74

<TS 86 B

17 62 11 01C

-0.98

<TS 87 B

17 62 8

02H 0.96

<TS 88 B

17 144 12 03H 0.85

<TS 89 B

17 152 8

02H 0.88

<TS 90 B

18 5

12 03C

-0.23

<TS 73

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 91 B

18 141 12 03C

-0.69

<TS 92 B

19 60 10 03H

-0.9

<TS 93 B

19 138 10 03C

-0.85

<TS 94 B

19 156 12 04C 0.83

<TS 95 B

19 164 23 02C 0.86

<TS 96 B

20 161 14 02C 0.94

<TS 97 B

21 4

12 03C 0.85

<TS 98 B

21 8

14 03C

-0.89

<TS 99 B

21 58 16 02C 0.9

<TS 100 B

21 164 10 02C

-0.24

<TS 101 B

22 11 13 02C 0.83

<TS 102 B

22 115 11 04C

-0.88

<TS 103 B

22 133 20 VS4 0.84

<TS 104 B

22 133 9

VS4

-0.82

<TS 105 B

22 163 18 02C 0.9

<TS 106 B

23 106 9

VS4

-0.88

<TS 107 B

23 160 9

02C

-0.87

<TS 108 B

23 160 10 02C

-0.11

<TS 109 B

23 160 11 03C

-0.88

<TS 110 B

24 53 12 02C 0.87

<TS 111 B

25 6

14 04H 0.93

<TS 112 B

25 6

12 02C

-0.84

<TS 113 B

25 36 10 04H

-0.85

<TS 114 B

25 40 10 04H

-0.83

<TS 115 B

25 52 10 03H

-0.93

<TS 116 B

25 58 15 02C

-0.96

<TS 117 B

25 64 13 DBH

-1.7

<TS 118 B

27 26 13 05H 1.15

<TS 119 B

27 64 15 DBH

-1.71

<TS 120 B

27 64 11 05H

-0.06

<TS 121 B

27 64 9

VS4 0.18

<TS 122 B

28 39 19 VS4 0.81

<TS 123 B

28 63 7

VS4 0.33

<TS 124 B

29 44 8

VS4

-0.07

<TS 125 B

29 58 9

VS4

-0.13

<TS 126 B

29 120 17 03H 0.9

<TS 127 B

29 156 13 03C

-1.03

<TS 128 B

29 156 11 02H 0.89

<TS 129 B

30 5

9 02H

-0.18

<TS 130 B

30 7

11 03C 0.85

<TS 131 B

30 9

13 02C 0.87

<TS 132 B

30 45 15 VS4 1.05

<TS 133 B

30 49 14 03H 0.04

<TS 134 B

30 51 10 02H 0.91

<TS 135 B

30 53 14 02C 0.88

<TS 74

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 136 B

30 57 12 03C

-0.81

<TS 137 B

30 111 11 03C

-0.98

<TS 138 B

30 115 13 02H 0.78

<TS 139 B

30 127 10 05C 0.86

<TS 140 B

30 163 9

02H 0.84

<TS 141 B

31 4

12 03C

-0.91

<TS 142 B

31 4

14 02C

-0.83

<TS 143 B

31 14 11 05H

-0.99

<TS 144 B

31 46 12 03C 0.78

<TS 145 B

31 50 13 03C 0.85

<TS 146 B

31 160 10 03C 0.94

<TS 147 B

31 160 13 02C 0.88

<TS 148 B

32 5

15 02C 0.87

<TS 149 B

32 5

12 04H 0.75

<TS 150 B

32 7

9 02H 0.84

<TS 151 B

32 13 14 03C 0.88

<TS 152 B

32 45 12 02H 0.93

<TS 153 B

32 45 12 03H 0.9

<TS 154 B

32 109 11 04C 0.83

<TS 155 B

32 151 12 VS4 1.11

<TS 156 B

32 157 13 DBH 1.47

<TS 157 B

33 4

12 01C

-0.86

<TS 158 B

33 32 11 04H 0.89

<TS 159 B

33 52 13 03C 0.83

<TS 160 B

33 150 12 02H 0.68

<TS 161 B

33 158 17 02C 0.92

<TS 162 B

33 160 13 02C

-0.94

<TS 163 B

33 162 14 03C 0.85

<TS 164 B

33 162 14 02C

-1.09

<TS 165 B

34 17 22 VS4

-0.83

<TS 166 B

34 43 11 03H 0.98

<TS 167 B

34 47 10 03H

-0.92

<TS 168 B

34 59 9

03H

-1.02

<TS 169 B

34 103 13 04H

-0.87

<TS 170 B

34 109 11 03C 0.85

<TS 171 B

34 133 18 03C 0.88

<TS 172 B

34 161 12 02C 0.85

<TS 173 B

35 4

15 01C

-0.92

<TS 174 B

35 6

11 03C 0.9

<TS 175 B

35 6

8 01H

-0.92

<TS 176 B

35 36 12 03H 0.97

<TS 177 B

35 36 19 VS4 0.79

<TS 178 B

35 42 17 05H 1.09

<TS 179 B

35 46 11 03H

-0.97

<TS 180 B

35 46 12 03H 1.02

<TS 75

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 181 B

35 46 11 03C 0.92

<TS 182 B

35 48 9

05H

-0.85

<TS 183 B

35 52 15 05C 0.91

<TS 184 B

35 56 12 03H

-0.88

<TS 185 B

35 60 11 03H

-0.82

<TS 186 B

35 64 13 05H 0.94

<TS 187 B

36 5

18 03C 0.87

<TS 188 B

36 5

10 03C 0.04

<TS 189 B

36 41 12 03H

-0.94

<TS 190 B

36 49 10 04H 0.85

<TS 191 B

36 109 9

04C 0.9

<TS 192 B

36 113 15 03C 0.9

<TS 193 B

36 119 11 03C

-0.91

<TS 194 B

36 157 16 02C

-0.85

<TS 195 B

36 161 11 02H 0.96

<TS 196 B

36 161 11 04C

-0.11

<TS 197 B

37 6

14 01H

-0.82

<TS 198 B

37 6

19 03H 0.86

<TS 199 B

37 6

14 02C

-0.9

<TS 200 B

37 6

13 02C

-0.13

<TS 201 B

37 10 19 03C

-0.95

<TS 202 B

37 10 9

03C

-0.13

<TS 203 B

37 32 17 03H 0.75

<TS 204 B

37 36 9

03H

-0.95

<TS 205 B

37 46 12 04H

-0.82

<TS 206 B

37 48 13 02H

-0.86

<TS 207 B

37 50 13 02H

-0.86

<TS 208 B

37 54 19 02H 0.86

<TS 209 B

37 54 14 04C 0.81

<TS 210 B

37 150 12 05H 0.97

<TS 211 B

37 160 15 02H 0.83

<TS 212 B

38 5

9 02C

-0.94

<TS 213 B

38 9

15 03C

-0.95

<TS 214 B

38 13 16 VS4 0.64

<TS 215 B

38 39 13 02H 0.93

<TS 216 B

38 45 17 02C 0.2

<TS 217 B

38 45 11 01C 0.88

<TS 218 B

38 47 12 04C 0.86

<TS 219 B

38 49 16 VS4 0.15

<TS 220 B

38 49 24 VS4 0.64

<TS 221 B

38 51 10 02C 0.9

<TS 222 B

38 53 14 VS4 0.23

<TS 223 B

38 53 12 03H

-0.92

<TS 224 B

38 53 17 VS4 0.84

<TS 225 B

38 107 15 02C 0.85

<TS 76

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 226 B

38 111 12 04C

-0.9

<TS 227 B

38 115 10 04C 0.88

<TS 228 B

38 127 10 04C 0.18

<TS 229 B

38 127 15 02C

-0.9

<TS 230 B

38 129 10 02C

-0.46

<TS 231 B

38 161 21 02H 1.01

<TS 232 B

38 161 10 DBH 1.87

<TS 233 B

39 6

12 05H 0.97

<TS 234 B

39 8

11 03C 0.9

<TS 235 B

39 8

12 03C

-0.93

<TS 236 B

39 10 13 03C 0.88

<TS 237 B

39 22 11 DBC 1.47

<TS 238 B

39 50 13 VS4

-0.53

<TS 239 B

39 50 7

VS4 0.16

<TS 240 B

39 52 12 03H

-0.82

<TS 241 B

39 102 17 VS4

-0.75

<TS 242 B

39 116 36 VS4 0.9

<TS 243 B

39 116 16 VS4

-0.91

<TS 244 B

39 120 20 VS4 0.92

<TS 245 B

39 120 10 VS4

-0.94

<TS 246 B

39 122 14 VS4 0.9

<TS 247 B

39 122 13 02C

-0.88

<TS 248 B

39 134 22 VS4

-0.92

<TS 249 B

39 134 15 VS4 0.9

<TS 250 B

39 146 11 DBC 2

<TS 251 B

39 150 21 VS4 0.66

<TS 252 B

39 150 13 VS4 0.02

<TS 253 B

39 160 13 02H 0.93

<TS 254 B

40 5

19 02C

-0.92

<TS 255 B

40 25 10 05H

-0.82

<TS 256 B

40 31 15 03H 0.75

<TS 257 B

40 35 12 04H

-0.15

<TS 258 B

40 39 11 04H

-0.89

<TS 259 B

40 51 16 01H 0.86

<TS 260 B

40 55 11 03H

-0.74

<TS 261 B

40 115 16 04C 0.4

<TS 262 B

40 115 17 03C 0.53

<TS 263 B

40 117 18 03C 0.88

<TS 264 B

40 123 11 03C

-0.83

<TS 265 B

40 125 15 02C

-0.96

<TS 266 B

40 129 16 04C

-0.83

<TS 267 B

40 143 15 05H 0.84

<TS 268 B

41 6

14 01C 0.9

<TS 269 B

41 6

11 01C

-0.86

<TS 270 B

41 8

19 04C 0.88

<TS 77

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 271 B

41 12 8

05C 0.81

<TS 272 B

41 12 16 05C 0.07

<TS 273 B

41 14 27 VS4 0.07

<TS 274 B

41 14 13 VS4 0.59

<TS 275 B

41 28 11 05H 0.96

<TS 276 B

41 34 12 04H 0.89

<TS 277 B

41 36 14 03H

-0.38

<TS 278 B

41 40 10 02C

-0.09

<TS 279 B

41 48 11 03H 0.7

<TS 280 B

41 54 18 VS4

-0.83

<TS

281, B

41 54 34 VS4 0.94

<TS 282 B

41 56 12 02H 0.93

<TS 283 B

41 120 7

05C 0.81

<TS 284 B

41 128 8

04C

-0.15

<TS 285 B

41 128 14 04C

-0.88

<TS 286 B

41 130 12 05C

-0.91

<TS 287 B

41 132 12 03C

-0.59

<TS 288 B

41 132 14 02C

-0.48

<TS 289 B

41 132 16 04C 0.35

<TS 290 B

41 134 12 03C 0.88

<TS 291 B

42 37 14 VS4

-0.07

<TS 292 B

42 39 15 VS4 0

<TS 293 B

42 41 9

04H

-0.82

<TS 294 B

42 47 14 03H

-0.85

<TS 295 B

42 57 18 VS4 0.09

<TS 296 B

42 57 35 VS4 0.65

<TS 297 B

42 123 30 VS4 0.79

<TS 298 B

42 133 13 02H

-0.9

<TS 299 B

42 139 11 VS4 0.73

<TS 300 B

43 6

21 02C

-0.17

<TS 301 B

43 6

10 02C

-0.92

<TS 302 B

43 6

9 05H

-0.26

<TS 303 B

43 8

12 03C 0.87

<TS 304 B

43 40 12 02C

-0.9

<TS 305 B

43 42 14 05C 0.81

<TS 306 B

43 46 11 03C

-0.97

<TS 307 B

43 48 18 05C 0.87

<TS 308 B

43 126 17 04C

-0.85

<TS 309 B

43 134 14 03C

-0.92

<TS 310 B

43 160 13 01H

-0.84

<TS 311 B

44 21 22 VS4

-0.73

<TS 312 B

44 21 28 VS4 0.59

<TS 313 B

44 23 14 VS4 0.66

<TS 314 B

44 23 25 DBH

-1.78

<TS 315 B

44 27 23 VS4

-0.6

<TS 78

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 316 B

44 27 23 VS4 0.73

<TS 317 B

44 31 37 VS4

-0.69

<TS 318 B

44 31 20 VS4 0.13

<TS 319 B

44 31 15 02C 0.84

<TS 320 B

44 41 16 02C

-0.13

<TS 321 B

44 45 25 VS4 0.81

<TS 322 B

44 45 15 03C 0.85

<TS 323 B

44 45 20 04C 0.48

<TS 324 B

44 53 10 VS4

-0.61

<TS 325 B

44 61 10 02H

-0.09

<TS 326 B

44 63 9

VS4

-0.88

<TS 327 B

44 63 20 VS4 0.88

<TS 328 B

44 101 14 04C 0.8

<TS 329 B

44 103 30 VS4 0.83

<TS 330 B

44 107 9

06C

-0.04

<TS 331 B

44 113 12 DBH 1.79

<TS 332 B

44 121 10 03C 0.94

<TS 333 B

44 127 20 02C 0.87

<TS 334 B

44 131 15 03C 1.01

<TS 335 B

44 159 13 01H

-0.97

<TS 336 B

45 6

21 02C

-0.15

<TS 337 B

45 6

23 02C

-0.96

<TS 338 B

45 8

9 01C

-0.13

<TS 339 B

45 16 10 DBH

-1.43

<TS 340 B

45 34 14 06H 1.1

<TS 341 B

45 36 24 VS4 0

<TS 342 B

45 36 17 VS4 0.61

<TS 343 B

45 36 13 04H

-0.86

<TS 344 B

45 38 16 VS4 0.02

<TS 345 B

45 38 11 VS4

-0.62

<TS 346 B

45 42 22 VS4

-0.81

<TS 347 B

45 42 17 VS4 0.94

<TS 348 B

45 56 13 03H 0.8

<TS 349 B

45 108 10 04C

-0.15

<TS 350 B

45 108 11 03H 0.16

<TS 351 B

45 110 11 02C 0.87

<TS 352 B

45 114 12 03C 0.85

<TS 353 B

45 118 15 06H

-0.09

<TS 354 B

45 122 22 VS4

-0.97

<TS 355 B

45 122 29 VS4 1.01

<TS 356 B

45 122 15 06C

-0.92

<TS 357 B

45 126 17 02C 0.92

<TS 358 B

45 128 13 03H

-0.89

<TS 359 B

45 132 14 VS4 0.79

<TS 360 B

45 140 15 DBH

-1.49

<TS 79

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 361 B

45 140 14 06C

-0.35

<TS 362 B

45 140 13 VS4

-0.78

<TS 363 B

45 140 27 VS4 0.78

<TS 364 B

45 148 15 06C

-0.57

<TS 365 B

45 160 9

01H

-0.87

<TS 366 B

45 160 11 01H 0.83

<TS 367 B

46 7

7 01C 0.86

<TS 368 B

46 7

19 01C

-0.15

<TS 369 B

46 23 17 VS4

-0.83

<TS 370 B

46 23 20 VS4 0.72

<TS 371 B

46 33 24 VS4

-0.71

<TS 372 B

46 33 10 VS4 0.04

<TS 373 B

46 37 11 02H 0.82

<TS 374 B

46 37 11 VS4

-0.85

<TS 375 B

46 37 18 VS4 0.78

<TS 376 B

46 37 12 DBC

-1.72

<TS 377 B

46 41 13 04H 0.91

<TS 378 B

46 47 12 02H

-0.06

<TS 379 B

46 59 11 03C 0.96

<TS 380 B

46 59 13 02H 0.84

<TS 381 B

46 103 15 04C 0.86

<TS 382 B

46 115 11 02C 0.9

<TS 383 B

46 125 10 02C

-0.88

<TS 384 B

46 129 12 03C 0.85

<TS 385 B

46 131 9

VS4 0.15

<TS 386 B

46 131 10 VS4

-0.82

<TS 387 B

46 131 11 VS4 0.82

<TS 388 B

46 135 10 VS4

-0.73

<TS 389 B

46 159 14 01C 0.13

<TS 390 B

47 8

8 01H 0.86

<TS 391 B

47 14 23 VS4 0.07

<TS 392 B

47 14 22 VS4 0.66

<TS 393 B

47 20 25 VS4

-0.9

<TS 394 B

47 20 27 VS4 0.9

<TS 395 B

47 40 12 06C

-0.84

<TS 396 B

47 46 19 VS4

-0.04

<TS 397 B

47 46 21 VS4

-0.7

<TS 398 B

47 46 11 VS4 0.87

<TS 399 B

47 48 13 06C 0.89

<TS 400 B

47 70 16 VS4

-0.81

<TS 401 B

47 96 10 06C

-0.04 PLG 402 B

47 96 22 VS4 0.76

<TS 403 B

47 96 18 VS4

-0.89

<TS 404 B

47 96 16 DBH 2

<TS 405 B

47 98 20 VS4 0.92

<TS 80

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 406 B

47 102 13 VS4

-0.92

<TS 407 B

47 108 25 06H 1.03

<TS 408 B

47 108 18 VS4

-1.03

<TS 409 B

47 108 19 VS4

-0.11

<TS 410 B

47 108 21 VS4 0.83

<TS 411 B

47 114 12 06C 0.99

<TS 412 B

47 116 13 04C

-0.95

<TS 413 B

47 126 30 VS4

-0.68

<TS 414 B

47 126 28 VS4 0.77

<TS 415 B

47 132 9

03C

-0.89

<TS 416 B

47 134 10 02C

-0.11

<TS 417 B

47 148 12 04C 0.75

<TS 418 B

47 156 8

01C 0.02

<TS 419 B

48 7

9 01H 0.88

<TS 420 B

48 39 11 04H 0.91

<TS 421 B

48 61 14 04H 0.82

<TS 422 B

48 67 17 VS4

-0.04

<TS 423 B

48 67 13 VS4 0.77

<TS 424 B

48 99 14 03C 0.82

<TS 425 B

48 107 12 02C 0.88

<TS 426 B

48 107 15 04C 0.85

<TS 427 B

48 111 16 04C 0.79

<TS 428 B

48 119 18 04C

-0.79

<TS 429 B

48 125 13 03C 0.97

<TS 430 B

48 129 12 03C

-0.15

<TS 431 B

48 133 9

04C 0.11

<TS 432 B

48 139 12 03H 0.93

<TS 433 B

48 141 10 03H

-0.96

<TS 434 B

48 159 12 01C

-1.06

<TS 435 B

48 159 10 01H

-0.92

<TS 436 B

49 8

23 VS4 0.85

<TS 437 B

49 8

9 DBC

-1.49

<TS 438 B

49 10 21 01C 0.89

<TS 439 B

49 12 7

DBC 1.91

<TS 440 B

49 26 11 03H 0.88

<TS 441 B

49 34 34 VS4 0.91

<TS 442 B

49 34 13 VS4

-0.89

<TS 443 B

49 46 22 VS4

-0.75

<TS 444 B

49 56 11 03H

-0.9

<TS 445 B

49 106 14 VS4 0.44

<TS 446 B

49 122 12 04C 0.77

<TS 447 B

49 132 14 03C

-0.9

<TS 448 B

49 158 15 01C 0.11

<TS 449 B

50 9

10 01C

-0.94

<TS 450 B

50 109 12 03C 0.85

<TS 81

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 451 B

50 127 13 03C

-0.94

<TS 452 B

50 157 18 01H

-0.85

<TS 453 B

50 159 12 01C 0.87

<TS 454 B

51 36 10 03C 0.84

<TS 455 B

51 36 13 03C

-0.91

<TS 456 B

51 58 12 01H 0.84

<TS 457 B

51 58 13 03H 0.86

<TS 458 B

51 64 17 02C 0.83

<TS 459 B

51 134 14 03C

-0.99

<TS 460 B

51 136 11 03C

-0.93

<TS 461 B

51 138 11 02C

-0.15

<TS 462 B

51 138 10 02C

-0.97

<TS 463 B

51 156 22 VS5

-0.7

<TS 464 B

52 11 9

01C

-0.2

<TS 465 B

52 11 8

01C

-0.92

<TS 466 B

52 25 12 02H 0.85

<TS 467 B

52 65 12 03C 0.86

<TS 468 B

52 107 14 02C 0.92

<TS 469 B

52 123 9

03C 0

<TS 470 B

52 125 9

03C 0.92

<TS 471 B

53 8

13 01C 0.87

<TS 472 B

53 32 14 05C 0.82

<TS 473 B

53 50 12 04H 0.93

<TS 474 B

53 56 12 03H 0.88

<TS 475 B

53 60 10 04H 0.87

<TS 476 B

53 80 18 03C 0.81

<TS 477 B

53 106 11 04C 0.83

<TS 478 B

53 108 11 03C 0.84

<TS 479 B

53 118 13 02C

-0.18

<TS 480 B

53 120 11 04C 0.77

<TS 481 B

53 128 13 03C 0.79

<TS 482 B

53 132 15 02C 0.92

<TS 483 B

53 134 11 03C 0.94

<TS 484 B

54 61 10 05H 1.1

<TS 485 B

54 69 8

03H 0.94

<TS 486 B

54 71 12 02H 0.98

<TS 487 B

54 103 11 04C 0.94

<TS 488 B

54 117 12 02C 0.88

<TS 489 B

54 121 13 04C

-0.9

<TS 490 B

55 56 11 03H 0.95

<TS 491 B

55 62 11 03C 0.07

<TS 492 B

55 64 17 02C 0.79

<TS 493 B

55 78 13 01C 0.85

<TS 494 B

55 78 11 04H 0.92

<TS 495 B

55 80 9

03H 0.92

<TS 82

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 496 B

55 86 12 06C 0.94

<TS 497 B

55 96 12 01C 0.91

<TS 498 B

55 114 13 03C 0.87

<TS 499 B

55 114 9

03C 0.13

<TS 500 B

55 120 13 04H

-0.86

<TS 501 B

55 126 13 03C 0.07

<TS 502 B

56 59 10 04H 0.96

<TS 503 B

56 77 9

02C 0.96

<TS 504 B

56 77 9

03H

-1

<TS 505 B

56 85 11 02C

-0.81

<TS 506 B

56 85 19 03C 0.92

<TS 507 B

56 97 17 04C 0.84

<TS 508 B

56 103 11 DBH 0.11

<TS 509 B

56 129 18 03C 0.89

<TS 510 B

56 129 11 03C

-0.91

<TS 511 B

56 145 16 04C

-0.78

<TS 512 B

56 151 12 06C 0.81

<TS 513 B

56 151 6

06C 0

<TS 514 B

57 16 6

06H

-0.98

<TS 515 B

57 16 12 06H

-0.13

<TS 516 B

57 26 13 06H 0.97

<TS 517 B

57 62 15 04H 0.89

<TS 518 B

57 62 9

02H

-0.69

<TS 519 B

57 78 11 03H

-0.96

<TS 520 B

57 80 13 03C 0.87

<TS 521 B

57 90 11 03C

-0.87

<TS 522 B

57 90 18 03C 0.87

<TS 523 B

57 118 10 03C

-0.2

<TS 524 B

57 120 9

05C 0.51

<TS 525 B

57 120 11 04C

-0.09

<TS 526 B

57 142 12 04C 0.88

<TS 527 B

57 144 13 04C 0.82

<TS 528 B

57 144 11 03C 0.86

<TS 529 B

57 148 11 04C 0.75

<TS 530 B

58 9

11 05H 0.99

<TS 531 B

58 25 9

06H 1.17

<TS 532 B

58 27 15 05H 0.99

<TS 533 B

58 47 14 03C

-0.96

<TS 534 B

58 57 11 06C 0.81

<TS 535 B

58 63 11 04H 0.8

<TS 536 B

58 65 9

04H

-0.09

<TS 537 B

58 71 13 04H

-0.92

<TS 538 B

58 71 7

04H

-0.21

<TS 539 B

58 117 12 06C 0.87

<TS 540 B

58 155 13 01C

-0.9

<TS 83

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 541 B

59 26 13 04H 1.01

<TS 542 B

59 26 12 03C 0.87

<TS 543 B

59 48 15 06H 1.06

<TS 544 B

59 48 20 03C 0.86

<TS 545 B

59 56 9

03H 0.23

<TS 546 B

59 66 15 02H

-0.91

<TS 547 B

59 70 10 03H

-0.88

<TS 548 B

59 72 12 03H 0.94

<TS 549 B

59 88 13 03C 0.89

<TS 550 B

59 116 11 03C 0.83

<TS 551 B

59 118 14 03C

-0.92

<TS 552 B

59 120 13 04H

-0.88

<TS 553 B

59 122 13 03C

-0.13

<TS 554 B

60 41 21 02H

-0.06

<TS 555 B

60 63 9

02H

-0.13

<TS 556 B

60 63 11 05H 0.93

<TS 557 B

60 63 11 03H

-0.9

<TS 558 B

60 71 10 03H

-0.88

<TS 559 B

60 81 12 02H 1.08

<TS 560 B

60 119 13 03C 0.88

<TS 561 B

60 133 16 03C

-0.87

<TS 562 B

61 12 13 06H

-0.14

<TS 563 B

61 28 10 04H

-0.95

<TS 564 B

61 28 15 DBC 2

<TS 565 B

61 48 12 03C 0.8

<TS 566 B

61 62 10 03H

-0.82

<TS 567 B

61 68 14 02H

-0.88

<TS 568 B

61 102 15 05C

-0.06

<TS 569 B

61 114 12 04C 0.78

<TS 570 B

61 120 15 02C

-0.91

<TS 571 B

61 124 14 02C 0.83

<TS 572 B

61 142 14 03C 0.94

<TS 573 B

61 144 12 06H 0.91

<TS 574 B

61 156 10 01H 0.93

<TS 575 B

62 11 11 04H 0.85

<TS 576 B

62 23 13 VS5 0.96

<TS 577 B

62 39 12 04H

-0.26

<TS 578 B

62 47 11 03C 0.86

<TS 579 B

62 53 9

06H 0.99

<TS 580 B

62 57 11 02H

-0.85

<TS 581 B

62 59 11 02C 0.87

<TS 582 B

62 111 13 03H 0.17

<TS 583 B

62 155 10 01H

-0.1

<TS 584 B

62 155 9

01H

-0.85

<TS 585 B

62 155 12 01H 0.57

<TS 84

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 586 B

63 28 10 06H

-0.95

<TS 587 B

63 56 11 03H

-0.9

<TS 588 B

63 56 9

04H

-0.82

<TS 589 B

63 56 14 03C 0.87

<TS 590 B

63 60 9

03C

-0.94

<TS 591 B

63 70 15 04H 0.96

<TS 592 B

63 76 12 03H

-0.89

<TS 593 B

63 78 9

03H

-0.34

<TS 594 B

63 82 23 VS5 1.04

<TS 595 B

63 82 11 VS5

-0.3

<TS 596 B

63 82 27 VS4 0.91

<TS 597 B

63 86 11 02C

-0.8

<TS 598 B

63 106 14 03H 0.89

<TS 599 B

63 110 13 03H

-0.21

<TS 600 B

63 114 11 03C 0.99

<TS 601 B

63 114 13 03C 0.11

<TS 602 B

63 124 12 04C

-0.91

<TS 603 B

63 128 15 06C 0.72

<TS 604 B

63 136 16 03C 0.87

<TS 605 B

63 138 15 03C 0.76

<TS 606 B

63 140 17 03C 0.83

<TS 607 B

63 140 13 06C

-0.24

<TS 608 B

63 146 13 06C 0.9

<TS 609 B

64 35 10 DBC

-1.97

<TS 610 B

64 37 12 06H

-0.32

<TS 611 B

64 59 18 01C 0.19

<TS 612 B

64 61 12 04H 0.9

<TS 613 B

64 81 10 06H

-0.87

<TS 614 B

64 103 11 04C 0.87

<TS 615 B

64 111 12 03H 1.02

<TS 616 B

64 121 13 03C 0.91

<TS 617 B

64 153 10 01C

-0.9

<TS 618 B

65 16 10 06H

-0.14

<TS 619 B

65 32 11 VS3

-0.9

<TS 620 B

65 62 15 04H

-0.92

<TS 621 B

65 110 18 03H 0.98

<TS 622 B

65 118 11 02C 0.86

<TS 623 B

65 122 12 06C 0.86

<TS 624 B

65 122 11 02C 0.76

<TS 625 B

65 130 12 03C 0.85

<TS 626 B

66 17 14 06H 0.84

<TS 627 B

66 17 9

06C 0.82

<TS 628 B

66 21 21 06H 0.55

<TS 629 B

66 29 10 06C

-0.9

<TS 630 B

66 31 9

06C 0.85

<TS 85

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 631 B

66 35 14 06C 0.86

<TS 632 B

66 35 15 DBC 1.71

<TS 633 B

66 39 13 VS5

-0.88

<TS 634 B

66 39 10 04H

-0.61

<TS 635 B

66 41 12 VS4

-0.85

<TS 636 B

66 45 11 06C 0.9

<TS 637 B

66 47 10 06C

-0.15

<TS 638 B

66 47 10 06C

-0.94

<TS 639 B

66 51 12 06H 0.96

<TS 640 B

66 51 11 06C 0.85

<TS 641 B

66 51 12 04C

-0.18

<TS 642 B

66 59 11 04C 0.87

<TS 643 B

66 97 12 01C 0.68

<TS 644 B

66 105 14 VS5 0.89

<TS 645 B

66 107 13 02H

-0.86

<TS 646 B

66 125 14 02C 0.85

<TS 647 B

66 137 8

03C 0.87

<TS 648 B

66 137 6

03C 0.02

<TS 649 B

66 149 17 06H 0.97

<TS 650 B

66 153 11 04C

-0.96

<TS 651 B

67 36 12 06H 0.87

<TS 652 B

67 46 11 DBC 1.97

<TS 653 B

67 52 11 04H 0.91

<TS 654 B

67 56 9

02H 0.92

<TS 655 B

67 56 10 02C 0.87

<TS 656 B

67 56 11 04H

-0.93

<TS 657 B

67 56 13 03C 0.89

<TS 658 B

67 58 17 03C 1.01

<TS 659 B

67 58 6

03C 0.09

<TS 660 B

67 62 15 03C 0.87

<TS 661 B

67 62 13 02C

-0.11

<TS 662 B

67 74 12 04H

-0.9

<TS 663 B

67 76 11 02H

-0.88

<TS 664 B

67 78 10 03H 0.95

<TS 665 B

67 96 12 06C

-0.13

<TS 666 B

67 104 21 06C

-0.09

<TS 667 B

67 104 9

04H 0.84

<TS 668 B

67 104 11 03H 0.91

<TS 669 B

67 108 12 03H 0.91

<TS 670 B

67 112 16 02C

-0.87

<TS 671 B

67 128 13 06H 0.26

<TS 672 B

67 134 24 06C

-0.99

<TS 673 B

67 134 13 03C 0.87

<TS 674 B

67 138 22 03C 0.85

<TS 675 B

67 138 17 03C 0.11

<TS 86

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 676 B

67 148 16 DBH 1.69

<TS 677 B

67 150 19 VS3 0.85

<TS 678 B

67 150 17 VS3

-0.7

<TS 679 B

68 17 11 04H 0.85

<TS 680 B

68 41 16 04H 0.95

<TS 681 B

68 45 10 DBC

-1.55

<TS 682 B

68 85 12 02C

-0.88

<TS 683 B

68 91 10 03C

-0.9

<TS 684 B

68 93 11 04C

-0.17

<TS 685 B

68 93 14 04C

-0.96

<TS 686 B

68 107 10 02H 0.98

<TS 687 B

68 109 14 02H 0.9

<TS 688 B

68 113 14 03H 0.95

<TS 689 B

68 113 11 04H

-0.78

<TS 690 B

68 113 20 04H 0.83

<TS 691 B

68 117 16 04H 0.79

<TS 692 B

68 143 17 06H 0.85

<TS 693 B

68 151 8

06H

-0.13

<TS 694 B

69 16 9

06H 0.82

<TS 695 B

69 28 12 06H

-0.84

<TS 696 B

69 28 14 06C 0.89

<TS 697 B

69 28 11 06H

-0.15

<TS 698 B

69 34 12 06C 0.83

<TS 699 B

69 34 15 06C

-0.94

<TS 700 B

69 36 13 DBC 1.73

<TS 701 B

69 36 11 04C 0.79

<TS 702 B

69 48 9

04C 0.15

<TS 703 B

69 56 14 VS5

-0.88

<TS 704 B

69 56 15 VS3 0.75

<TS 705 B

69 56 11 VS3 0.04

<TS 706 B

69 66 12 02H 0.89

<TS 707 B

69 72 16 06C

-0.89

<TS 708 B

69 102 12 03H 0.91

<TS 709 B

69 106 11 06H

-0.88

<TS 710 B

69 110 12 03C 0.85

<TS 711 B

69 114 12 04H 0.9

<TS 712 B

69 120 12 03C 0.11

<TS 713 B

69 120 16 03C 0.71

<TS 714 B

69 122 8

04H 0.97

<TS 715 B

69 124 13 03C

-0.91

<TS 716 B

69 126 14 03H 0.79

<TS 717 B

69 128 13 03C 0.94

<TS 718 B

69 132 15 04H 0.99

<TS 719 B

69 134 15 VS5

-0.81

<TS 720 B

69 134 8

VS5 0.78

<TS 87

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 721 B

69 140 19 VS5

-0.85

<TS 722 B

69 140 10 VS5 0.83

<TS 723 B

69 144 25 VS5

-0.8

<TS 724 B

70 31 11 06C 0.83

<TS 725 B

70 45 13 03H 0.79

<TS 726 B

70 51 12 03C 0.92

<TS 727 B

70 75 18 03H

-0.41

<TS 728 B

70 83 10 02C 0.9

<TS 729 B

70 115 14 04H 0.86

<TS 730 B

70 117 10 03C

-0.78

<TS 731 B

70 129 17 06C

-0.94

<TS 732 B

70 141 19 VS3

-0.89

<TS 733 B

70 143 11 DBC 1.39

<TS 734 B

70 153 20 03C 0

<TS 735 B

71 14 14 02H

-0.61

<TS 736 B

71 20 17 DBH

-1.56

<TS 737 B

71 20 16 VS5 0.94

<TS 738 B

71 20 14 DBC 1.58

<TS 739 B

71 36 19 VS4 0.79

<TS 740 B

71 36 12 VS5

-0.72

<TS 741 B

71 36 23 VS5

-0.02

<TS 742 B

71 36 9

DBC

-1.81

<TS 743 B

71 36 8

DBC 2.05

<TS 744 B

71 38 16 05H 0.97

<TS 745 B

71 42 11 04H

-0.93

<TS 746 B

71 52 14 03C 0.89

<TS 747 B

71 52 12 02C

-0.93

<TS 748 B

71 58 10 02C

-0.06

<TS 749 B

71 62 13 03C

-0.15

<TS 750 B

71 62 10 02C

-0.15

<TS 751 B

71 80 11 03C 0.12

<TS 752 B

71 86 14 02C

-0.9

<TS 753 B

71 86 9

02C

-0.13

<TS 754 B

71 102 12 05C 0.94

<TS 755 B

71 104 12 02H 0.89

<TS 756 B

71 110 13 04H

-0.77

<TS 757 B

71 116 12 03C

-0.89

<TS 758 B

71 118 10 02C 0

<TS 759 B

71 132 12 VS5 0.82

<TS 760 B

71 136 11 06C

-0.2

<TS 761 B

71 136 18 06C

-0.98

<TS 762 B

71 142 9

06H

-0.93

<TS 763 B

71 144 28 VS3

-0.92

<TS 764 B

71 144 17 VS3 0.94

<TS 765 B

71 144 13 DBH 1.6

<TS 88

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 766 B

71 146 12 06H 0.17

<TS 767 B

71 146 14 VS4 0.85

<TS 768 B

71 146 28 VS5

-0.85

<TS 769 B

72 25 21 VS3

-0.7

<TS 770 B

72 25 10 VS3

-0.13

<TS 771 B

72 41 22 06C 0.94

<TS 772 B

72 47 12 03C

-0.95

<TS 773 B

72 49 28 03C 0.96

<TS 774 B

72 59 14 04C 0.93

<TS 775 B

72 61 15 02C 0.9

<TS 776 B

72 85 13 05C 0.95

<TS 777 B

72 85 11 030 0.87

<TS 778 B

72 91 11 02C 0.89

<TS 779 B

72 109 12 03H

-0.82

<TS 780 B

72 113 11 04H 0.94

<TS 781 B

72 113 11 04C 0.89

<TS 782 B

72 113 13 02H

-0.82

<TS 783 B

72 113 9

02H 0.91

<TS 784 B

72 125 21 06C 0.89

<TS 785 B

73 14 10 VS4

-1.05

<TS 786 B

73 14 10 VS4 0.11

<TS 787 B

73 40 11 05H 1.08

<TS 788 B

73 46 11 040

-0.89

<TS 789 B

73 58 14 06C

-0.15

<TS 790 B

73 58 11 02C

-0.09

<TS 791 B

73 104 15 06C

-0.98

<TS 792 B

73 132 14 06H 0.98

<TS 793 B

74 23 17 VS3

-0.95

<TS 794 B

74 23 13 VS4

-0.64

<TS 795 B

74 23 12 DBC 1.58

<TS 796 B

74 29 11 05H 0.92

<TS 797 B

74 35 15 DBH 1.62

<TS 798 B

74 37 15 06H 1.1

<TS 799 B

74 37 11 04C

-0.9

<TS 800 B

74 37 9

DBC 1.75

<TS 801 B

74 43 13 VS3

-0.95

<TS 802 B

74 43 19 VS4

-0.66

<TS 803 B

74 45 16 VS5

-0.73

<TS 804 B

74 47 8

06C 0.07

<TS 805 B

74 51 11 03C

-0.9

<TS 806 B

74 55 17 04C 0.81

<TS 807 B

74 55 12 04C

-0.96

<TS 808 B

74 71 13 03H 0.87

<TS 809 B

74 107 12 04H

-0.89

<TS 810 B

74 111 14 02C

-0.91

<TS 89

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 811 B

74 115 12 04C 0.87

<TS 812 B

74 117 12 VS3

-1.02

<TS 813 B

74 119 14 03H 0.86

<TS 814 B

74 119 15 04H 0.9

<TS 815 B

74 141 17 VS5

-0.7

<TS 816 B

75 16 14 02H 0.87

<TS 817 B

75 16 13 06H 0.84

<TS 818 B

75 24 13 VS3 0.09

<TS 819 B

75 24 16 VS3 0.79

<TS 820 B

75 24 11 VS4 0.83

<TS 821 B

75 42 15 04C 0.95

<TS 822 B

75 54 11 04C 0.78

<TS 823 B

75 60 15 03C 0.87

<TS 824 B

75 84 8

02C 0.82

<TS 825 B

75 84 14 02C

-0.78

<TS 826 B

75 102 12 04H 0.85

<TS 827 B

75 104 20 03H 0.91

<TS 828 B

75 106 10 02H 0.97

<TS 829 B

75 106 13 02H

-0.86

<TS 830 B

75 110 14 04C

-0.93

<TS 831 B

75 112 12 03H

-0.83

<TS 832 B

75 132 10 06H

-0.89

<TS 833 B

75 132 10 DBH

-1.85

<TS 834 B

75 150 12 04C 0.83

<TS 835 B

76 25 13 06H 0.92

<TS 836 B

76 27 8

06H

-0.84

<TS 837 B

76 29 6

DBC 1.66

<TS 838 B

76 35 18 DBH 1.93

<TS 839 B

76 41 16 03C

-0.46

<TS 840 B

76 41 10 05C

-0.91

<TS 841 B

76 51 19 VS3 0.8

<TS 842 B

76 53 9

03C

-0.09

<TS 843 B

76 55 15 DBH 1.7

<TS 844 B

76 59 14 VS3

-0.93

<TS 845 B

76 59 15 05H 0.92

<TS 846 B

76 65 11 VS4

-0.24

<TS 847 B

76 73 9

02H 0

<TS 848 B

76 111 14 04C 0.82

<TS 849 B

76 113 11 04H 0.21

<TS 850 B

76 115 6

03H

-0.13

<TS 851 B

76 121 16 04C 0.87

<TS 852 B

76 123 11 03H 0.79

<TS 853 B

76 135 13 VS5 0.85

<TS 854 B

76 141 22 DBH 1.93

<TS 855 B

76 151 13 04C 0.87

<TS 90

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 856 B

77 34 11 VS3 0.07

<TS 857 B

77 34 22 VS3 0.79

<TS 858 B

77 50 10 05H

-0.83

<TS 859 B

77 56 11 DBH 0.93

<TS 860 B

77 104 16 05C 0.87

<TS 861 B

77 104 15 05H 0.8

<TS 862 B

77 116 12 04H

-0.89

<TS 863 B

77 122 12 03H 0.93

<TS 864 B

78 23 15 DBH

-1.95

<TS 865 B

78 33 12 03C 0.81

<TS 866 B

78 47 17 02C 0.9

<TS 867 B

78 57 21 03C 0.97

<TS 868 B

78 61 18 VS3

-0.96

<TS 869 B

78 81 13 03H 0.84

<TS 870 B

78 87 15 03C

-0.91

<TS 871 B

78 91 15 07H 1.31

<TS 872 B

78 105 12 02H

-0.93

<TS 873 B

78 109 12 02H

-0.83

<TS 874 B

78 109 8

03H 0.11

<TS 875 B

78 109 12 03H 0.93

<TS 876 B

78 137 9

04C

-0.89

<TS 877 B

79 24 12 VS3

-0.9

<TS 878 B

79 24 26 VS4 0.72

<TS 879 B

79 24 10 VS3 0.92

<TS 880 B

79 24 24 VS4 0.04

<TS 881 B

79 44 10 04C

-0.88

<TS 882 B

79 44 10 03C 0.86

<TS 883 B

79 52 13 02C

-0.07

<TS 884 B

79 54 10 03C 0.81

<TS 885 B

79 60 11 03C

-0.89

<TS 886 B

79 62 11 04C

-0.98

<TS 887 B

79 62 11 02C

-0.11

<TS 888 B

79 86 11 03C 0.96

<TS 889 B

79 86 16 03H 0.85

<TS 890 B

79 108 17 05H 0.75

<TS 891 B

79 122 17 03H 0.8

<TS 892 B

79 128 13 03C 0.82

<TS 893 B

79 150 12 03C

-0.94

<TS 894 B

80 17 29 DBH 1.71

<TS 895 B

80 49 13 VS4

-0.94

<TS 896 B

80 49 10 VS4 0.83

<TS 897 B

80 95 18 04H 0.87

<TS 898 B

80 95 11 02H 0.87

<TS 899 B

80 95 15 03H 0.94

<TS 900 B

80 115 17 VS4

-0.84

<TS 91

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 901 B

80 115 11 VS3 1.03

<TS 902 B

80 129 12 03H 0.85

<TS 903 B

80 145 29 VS4

-0.68

<TS 904 B

80 145 12 VS5

-0.9

<TS 905 B

80 145 15 VS5 0.7

<TS 906 B

80 149 14 01H

-0.79

<TS 907 B

81 22 25 VS3 0.83

<TS 908 B

81 22 26 VS4 0.78

<TS 909 B

81 24 14 VS3

-0.58

<TS 910 B

81 24 12 VS3 1.08

<TS 911 B

81 60 15 03C 0.8

<TS 912 B

81 92 11 02C

-1.04

<TS 913 B

81 110 11 03H 0.91

<TS 914 B

81 112 12 02H 0.91

<TS 915 B

81 114 11 03H 0.97

<TS 916 B

81 124 12 03C

-0.89

<TS 917 B

81 126 20 07C 1.06

<TS 918 B

81 148 16 04C 0.9

<TS 919 B

81 148 9

03C 0.94

<TS 920 B

82 19 13 03H 0.98

<TS 921 B

82 19 13 04H 0.99

<TS 922 B

82 41 20 VS3 0.96

<TS 923 B

82 43 11 VS4

-0.81

<TS 924 B

82 43 12 VS4

-0.02

<TS 925 B

82 43 16 VS4 0.74

<TS 926 B

82 53 11 05C 0.92

<TS 927 B

82 59 12 02C 0.89

<TS 928 B

82 79 14 04H 0.92

<TS 929 B

82 91 13 04C

-0.84

<TS 930 B

82 105 10 02H 0.89

<TS 931 B

82 129 15 DBH 1.91

<TS 932 B

82 137 15 DBH 1.59

<TS 933 B

82 143 18 VS4

-0.85

<TS 934 B

82 143 26 VS3

-0.89

<TS 935 B

83 26 7

06H

-0.95

<TS 936 B

83 28 20 VS6

-0.82

<TS 937 B

83 28 17 VS6 1.15

<TS 938 B

83 54 12 04H 0.86

<TS 939 B

83 64 14 03C 0.92

<TS 940 B

83 78 13 01C 0.87

<TS 941 B

83 78 11 02C 0.79

<TS 942 B

83 106 12 03H 0.86

<TS 943 B

83 114 12 02H 0.9

<TS 944 B

83 130 11 DBH 1.76

<TS 945 B

83 130 10 DBC

-1.61

<TS 92

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 946 B

84 19 18 07H

-0.99

<TS 947 B

84 49 11 04C

-0.94

<TS 948 B

84 55 15 02C 0.94

<TS 949 B

84 73 11 04H 0.9

<TS 950 B

84 77 11 05C

-0.96

<TS 951 B

84 79 10 03H 0.92

<TS 952 B

84 81 11 02C 0.86

<TS 953 B

84 87 12 03H 0.77

<TS 954 B

84 87 11 04C 0.83

<TS 955 B

84 93 16 02C

-0.85

<TS 956 B

84 103 7

04C 0.35

<TS 957 B

84 107 14 02H

-0.84

<TS 958 B

84 111 12 04H

-0.96

<TS 959 B

84 111 10 05H 0.9

<TS 960 B

84 125 14 VS2

-0.85

<TS 961 B

84 145 15 03C

-0.81

<TS 962 B

84 147 27 DBH 1.54

<TS 963 B

84 147 10 07H 0.77

<TS 964 B

85 20 13 VS4 1.17

<TS 965 B

85 20 11 VS4

-0.79

<TS 966 B

85 36 14 04H

-0.85

<TS 967 B

85 78 13 05H 1.09

<TS 968 B

85 80 10 01H 0.88

<TS 969 B

85 110 15 04C 0.89

<TS 970 B

85 112 17 03H 0.67

<TS 971 B

85 142 17 03C

-0.79

<TS 972 B

85 144 15 03C

-1.14

<TS 973 B

85 146 14 04C

-0.85

<TS 974 B

85 146 12 03C

-0.94

<TS 975 B

86 21 12 01C

-0.94

<TS 976 B

86 31 13 06H 0.83

<TS 977 B

86 33 11 06H 0.91

<TS 978 B

86 51 15 03C 0.96

<TS 979 B

86 61 7

02C 0.15

<TS 980 B

86 67 11 03C

-0.91

<TS 981 B

86 79 13 04H 0.97

<TS 982 B

86 89 15 03C 1.08

<TS 983 B

86 91 9

03C

-0.89

<TS 984 B

86 111 14 04C

-0.88

<TS 985 B

86 145 14 03C 0.92

<TS 986 B

87 30 11 04H 1.04

<TS 987 B

87 62 12 04C

-0.96

<TS 988 B

87 74 13 07H 0.87

<TS 989 B

87 82 17 03H 0.84

<TS 990 B

87 84 13 02C 0.92

<TS 93

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 991 B

87 88 17 04C

-0.72

<TS 992 B

87 116 13 04C 0.84

<TS 993 B

87 146 29 03C 0.78

<TS 994 B

88 23 10 04H 0.87

<TS 995 B

88 23 7

04H

-0.9

<TS 996 B

88 27 27 DBH 2.16

<TS 997 B

88 27 11 04H 0.84

<TS 998 B

88 29 12 06H 0.98

<TS 999 B

88 67 11 VS2

-0.78

<TS 1000 B

88 67 12 VS2 0.76

<TS 1001 B

88 79 14 07C 0.87

<TS 1002 B

88 87 11 05C 0.9

<TS 1003 B

88 95 20 03C 0.93

<TS 1004 B

88 107 14 04C

-0.87

<TS 1005 B

88 117 11 04C

-0.89

<TS 1006 B

88 133 9

04H 0

<TS 1007 B

89 38 13 VS2

-0.99

<TS 1008 B

89 38 9

05H

-0.94

<TS 1009 B

89 42 11 VS6 0.81

<TS 1010 B

89 54 11 06H

-0.89

<TS 1011 B

89 60 18 04C

-0.92

<TS 1012 B

89 78 13 07C 0.85

<TS 1013 B

89 82 13 07C 0.82

<TS 1014 B

89 84 17 03H 0.91

<TS 1015 B

89 92 13 04C 0.02

<TS 1016 B

89 100 11 03H 0.83

<TS 1017 B

89 104 10 05C

-0.89

<TS 1018 B

89 104 11 04H 0.84

<TS 1019 B

89 134 14 04H 0.9

<TS 1020 B

89 144 13 01H

-0.88

<TS 1021 B

90 23 12 VS4

-0.7

<TS 1022 B

90 55 15 02C 0

<TS 1023 B

90 55 12 02C

-0.87

<TS 1024 B

90 57 13 02C 0.91

<TS 1025 B

90 65 13 03C 0.92

<TS 1026 B

90 69 12 07H

-1

<TS 1027 B

90 87 11 02C

-0.1

<TS 1028 B

90 89 10 03H 0.88

<TS 1029 B

90 95 13 04C 0.97

<TS 1030 B

90 97 15 04C 0.85

<TS 1031 B

90 115 13 03H

-0.87

<TS 1032 B

90 115 11 03H 0.15

<TS 1033 B

90 127 15 04H

-0.89

<TS 1034 B

90 131 10 07H 0.97

<TS 1035 B

91 22 26 VS6 1.01

<TS 94

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1036 B

91 26 12 02C 0.88

<TS 1037 B

91 32 15 02C

-0.94

<TS 1038 B

91 38 10 03H

-0.85

<TS 1039 B

91 54 13 02C 0.96

<TS 1040 B

91 58 15 03C 0.8

<TS 1041 B

91 60 10 04C

-0.92

<TS 1042 B

91 60 12 03C

-0.91

<TS 1043 B

91 64 18 03C

-0.89

<TS 1044 B

91 70 10 04H 0.9

<TS 1045 B

91 70 13 06C

-0.89

<TS 1046 B

91 88 16 04H

-0.85

<TS 1047 B

91 88 10 03C 0.91

<TS 1048 B

91 94 13 06C

-0.85

<TS 1049 B

91 124 17 04C 0.89

<TS 1050 B

91 140 9

04H 0.94

<TS 1051 B

92 23 10 03H

-0.83

<TS 1052 B

92 23 11 02C 0.86

<TS 1053 B

92 23 8

VS4

-0.98

<TS 1054 B

92 23 10 VS4 0.74

<TS 1055 B

92 23 13 02C

-0.55

<TS 1056 B

92 35 9

05H 0.95

<TS 1057 B

92 49 15 05H 0.92

<TS 1058 B

92 55 12 03C 0.87

<TS 1059 B

92 57 13 04H 0.97

<TS 1060 B

92 61 12 03C

-0.89

<TS 1061 B

92 69 14 04C 0.86

<TS 1062 B

92 75 11 05H 1.03

<TS 1063 B

92 83 20 05H 0.85

<TS 1064 B

92 85 12 03H

-0.89

<TS 1065 B

92 89 14 04H 0.8

<TS 1066 B

92 97 16 04C 0.92

<TS 1067 B

92 97 8

04C 0.17

<TS 1068 B

92 105 10 04C

-0.9

<TS 1069 B

92 111 11 07C 0.89

<TS 1070 B

93 80 13 03C

-0.89

<TS 1071 B

93 104 12 04H

-0.89

<TS 1072 B

93 112 11 03H 0.96

<TS 1073 B

93 112 13 VS6 0.85

<TS 1074 B

93 130 13 04H 0.77

<TS 1075' B

93 132 15 04H 0.85

<TS 1076 B

93 136 12 03C 0.85

<TS 1077 B

94 53 12 05H

-0.84

<TS 1078 B

94 57 13 02C 0.91

<TS 1079 B

94 57 10 03C 0.91

<TS 1080 B

94 81 13 02C 0.94

<TS 95

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1081 B

94 93 12 04C

-0.14

<TS 1082 B

94 93 9

04C

-0.91

<TS 1083 B

94 93 10 03C

-0.88

<TS 1084 B

94 101 15 06H

-0.96

<TS 1085 B

94 115 15 04C

-0.87

<TS 1086 B

94 129 16 04H 1.02

<TS 1087 B

95 24 11 VS4

-0.15

<TS 1088 B

95 24 9

VS4 0.57

<TS 1089 B

95 24 16 VS4

-0.67

<TS 1090 B

95 70 15 VS6

-0.83

<TS 1091 B

95 70 11 04H 0.88

<TS 1092 B

95 84 8

07C 0.13

<TS 1093 B

95 84 16 07C 0.79

<TS 1094 B

95 88 13 02C 0.98

<TS 1095 B

95 102 18 05H 0.89

<TS 1096 B

95 104 13 03C 0.19

<TS 1097 B

95 106 20 04C

-0.87

<TS 1098 B

95 116 17 VS2

-1.04

<TS 1099 B

95 126 13 04H 0.88

<TS 1100 B

95 136 15 03C

-0.39

<TS 1101 B

95 138 36 VS4 0.91

<TS 1102 B

95 138 12 03C 0.85

<TS 1103 B

95 138 23 VS4

-0.67

<TS 1104 B

95 140 12 03C

-1

<TS 1105 B

95 142 18 VS4 0.93

<TS 1106 B

96 25 10 02H

-0.98

<TS 1107 B

96 53 13 05H 0.87

<TS 1108 B

96 57 13 02H 0.86

<TS 1109 B

96 61 14 02H 0.86

<TS 1110 B

96 65 12 04C 0.93

<TS 1111 B

96 65 12 02C 0.95

<TS 1112 B

96 71 12 04H

-0.87

<TS 1113 B

96 71 7

04H

-0.13

<TS 1114 B

96 79 11 VS2 0.65

<TS 1115 B

96 95 21 VS2

-1.01

<TS 1116 B

96 95 14 VS2 0.11

<TS 1117 B

96 95 18 VS2 0.89

<TS 1118 B

96 103 13 04C 0.82

<TS 1119 B

96 133 8

04H

-0.13

<TS 1120 B

96 133 8

03H

-0.79

<TS 1121 B

96 137 17 04C

-0.15

<TS 1122 B

96 137 12 03C 0.87

<TS 1123 B

96 137 25 VS4 1.16

<TS 1124 B

96 137 15 VS4 0

<TS 1125 B

96 139 21 03C

-0.84

<TS 96

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1126 B

96 139 8

03C 0.76

<TS 1127 B

96 141 19 VS4 1.05

<TS 1128 B

97 28 20 03C 0.86

<TS 1129 B

97 38 9

05H 0.86

<TS 1130 B

97 42 14 VS2

-0.85

<TS 1131 B

97 54 10 07C 0.89

<TS 1132 B

97 60 15 06C 0.95

<TS 1133 B

97 72 18 04H 0.85

<TS 1134 B

97 84 10 07C

-0.09

<TS 1135 B

97 84 16 07C

-0.9

<TS 1136 B

97 86 12 03C 0.93

<TS 1137 B

97 100 13 VS2 0.74

<TS 1138 B

97 126 11 VS2

-0.87

<TS 1139 B

97 130 14 04H 0.92

<TS 1140 B

97 140 12 03H 0.77

<TS 1141 B

97 140 10 DBH 1.7

<TS 1142 B

97 140 12 VS4

-0.94

<TS 1143 B

98 27 17 04C

-1.05

<TS 1144 B

98 27 14 VS4

-1.03

<TS 1145 B

98 39 14 VS4 0.77

<TS 1146 B

98 41 25 VS4 0.81

<TS 1147 B

98 51 9

04H 0.88

<TS 1148 B

98 59 14 VS2

-0.85

<TS 1149 B

98 59 13 VS2 0.94

<TS 1150 B

98 71 13 VS2 0.96

<TS 1151 B

98 71 10 VS2

-0.85

<TS 1152 B

98 79 11 03C 0.91

<TS 1153 B

98 79 9

03C 0.13

<TS 1154 B

98 81 17 VS2 0.84

<TS 1155 B

98 93 16 03C 1.03

<TS 1156 B

98 133 15 02C 0.83

<TS 1157 B

98 135 24 VS4

-0.84

<TS 1158 B

98 135 23 VS4 0.95

<TS 1159 B

98 139 10 03C

-0.96

<TS 1160 B

98 139 13 04H

-0.15

<TS 1161 B

98 139 9

DBH

-2.06

<TS 1162 B

99 32 12 02C 0.92

<TS 1163 B

99 40 10 02H 0.88

<TS 1164 B

99 44 10 05H 0.94

<TS 1165 B

99 50 20 05H 0.45

<TS 1166 B

99 52 11 03C 0.89

<TS 1167 B

99 86 11 VS6 0.09

<TS 1168 B

99 132 22 VS2

-0.76

<TS 1169 B

99 132 15 VS2

-0.13

<TS 1170 B

99 132 26 VS2 0.74

<TS 97

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1171 B

99 136 17 04C 0.85

<TS 1172 B

99 138 6

DBH 1.98

<TS 1173 B

100 27 21 VS4

-1.03

<TS 1174 B

100 27 11 VS4 0.85

<TS 1175 B

100 29 15 03C 0.84

<TS 1176 B

100 115 10 03C 0.64

<TS 1177 B

100 121 14 06C 0.91

<TS 1178 B

100 125 12 DBC

-1.36

<TS 1179 B

100 125 16 VS6 0.02

<TS 1180 B

100 125 26 VS6 0.85

<TS 1181 B

100 135 15 03H 0.88

<TS 1182 B

101 28 14 VS4

-0.83

<TS 1183 B

101 28 11 VS4

-0.17

<TS 1184 B

101 30 10 03H

-0.94

<TS 1185 B

101 30 18 04C 0.88

<TS 1186 B

101 30 10 02C 0.9

<TS 1187 B

101 30 10 03C 0.86

<TS 1188 B

101 30 19 03C

-0.9

<TS 1189 B

101 32 21 VS2 0.81

<TS 1190 B

101 32 8

VS4 0.88

<TS 1191 B

101 36 11 05H 0.97

<TS 1192 B

101 36 9

03C 0.92

<TS 1193 B

101 54 17 02C 0.82

<TS 1194 B

101 78 9

05H 0.92

<TS 1195 B

101 98 16 04C

-0.88

<TS 1196 B

101 136 16 03H 0.9

<TS 1197 B

101 138 9

03H 0.86

<TS 1198 B

101 138 11 VS4

-1.02

<TS 1199 B

102 29 11 04C 0.87

<TS 1200 B

102 31 17 02C

-0.94

<TS 1201 B

102 33 21 03C

-0.9

<TS 1202 B

102 35 20 03C 0.9

<TS 1203 B

102 37 10 02C

-0.92

<TS 1204 B

102 41 16 06H 0.89

<TS 1205 B

102 41 10 06H

-1.03

<TS 1206 B

102 51 15 07C 0.96

<TS 1207 B

102 93 10 04C

-0.12

<TS 1208 B

102 93 9

04C

-0.95

<TS 1209 B

102 99 16 07C 0.85

<TS 1210 B

102 99 9

07C 0.11

<TS 1211 B

102 113 10 DBH 2

<TS 1212 B

102 123 9

04H 0.81

<TS 1213 B

102 131 12 DBC 1.25

<TS 1214 B

103 30 11 01C 0.09

<TS 1215 B

103 30 11 06C

-0.9

<TS 98

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1216 B

103 36 13 07C 0.89

<TS 1217 B

103 36 11 07H 1

<TS 1218 B

103 38 13 02C

-0.92

<TS 1219 B

103 48 12 07C

-0.02

<TS 1220 B

103 62 15 03C 0.85

<TS 1221 B

103 64 25 VS2 0.89

<TS 1222 B

103 94 19 VS2

-0.74

<TS 1223 B

103 100 15 07C 0.87

<TS 1224 B

103 120 14 03H 0.87

<TS 1225 B

103 120 10 03H

-0.85

<TS 1226 B

103 122 16 03H 0.89

<TS 1227 B

103 126 16 04H 0.94

<TS 1228 B

103 126 30 VS6 0.85

<TS 1229 B

103 126 24 VS2 0.07

<TS 1230 B

103 128 13 04C 0.8

<TS 1231 B

103 130 20 VS2

-0.07

<TS 1232 B

103 130 10 VS2 0.91

<TS 1233 B

103 136 18 VS4

-0.84

<TS 1234 B

103 136 19 VS4 0.93

<TS 1235 B

104 31 16 02C

-0.22

<TS 1236 B

104 33 12 03H 0.02

<TS 1237 B

104 59 12 VS6

-0.93

<TS 1238 B

104 117 10 05C 0.84

<TS 1239 B

104 127 11 04H 0.91

<TS 1240 B

104 131 12 03C 0.76

<TS 1241 B

104 133 8

05C 0.8

<TS 1242 B

104 135 15 VS4 0.91

<TS 1243 B

105 30 13 VS4 0.13

<TS 1244 B

105 30 17 02C 0.88

<TS 1245 B

105 30 28 VS4 0.57

<TS 1246 B

105 32 8

VS4

-1.05

<TS 1247 B

105 32 13 VS4 1.05

<TS 1248 B

105 32 11 01H 0.88

<TS 1249 B

105 34 14 07C

-0.92

<TS 1250 B

105 34 14 03C

-0.9

<TS 1251 B

105 34 20 02C 0.09

<TS 1252 B

105 36 10 04H

-0.19

<TS 1253 B

105 38 17 03C 0.86

<TS 1254 B

105 40 10 03C

-0.94

<TS 1255 B

105 42 11 07C 0.86

<TS 1256 B

105 54 23 VS6

-0.78

<TS 1257 B

105 58 15 VS4

-0.74

<TS 1258 B

105 58 15 VS4 0.04

<TS 1259 B

105 68 15 VS2 0

<TS 1260 B

105 88 15 07C

-0.88

<TS 99

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1261 B

105 88 9

07C

-0.11

<TS 1262 B

105 90 17 VS4 0.9

<TS 1263 B

105 90 16 VS2 0.81

<TS 1264 B

105 90 16 07C 1.03

<TS 1265 B

105 90 16 03C 0.51

<TS 1266 B

105 96 12 04C

-0.92

<TS 1267 B

105 110 23 DBH 0.94

<TS 1268 B

105 116 13 03H 0.86

<TS 1269 B

105 118 9

03H 0.97

<TS 1270 B

105 120 12 03H

-0.8

<TS 1271 B

105 130 21 03C 0.87

<TS 1272 B

105 132 14 04H 0.78

<TS 1273 B

105 134 19 02C 0.76

<TS 1274 B

105 134 15 VS4 1.18

<TS 1275 B

105 136 13 01H 0.91

<TS 1276 B

106 31 18 03C 0.98

<TS 1277 B

106 31 17 02C 0.55

<TS 1278 B

106 33 11 VS4

-0.74

<TS 1279 B

106 33 14 03C 0.13

<TS 1280 B

106 35 13 03H 0.86

<TS 1281 B

106 35 17 04H 0.85

<TS 1282 B

106 35 15 02C

-0.2

<TS 1283 B

106 35 16 03C 0.75

<TS 1284 B

106 37 18 VS2

-0.83

<TS 1285 B

106 39 21 VS2

-0.96

<TS 1286 B

106 39 23 03C 0.91

<TS 1287 B

106 49 10 04H

-0.1

<TS 1288 B

106 51 9

VS2 1

<TS 1289 B

106 51 15 07C 0.94

<TS 1290 B

106 63 10 VS4

-0.96

<TS 1291 B

106 75 16 VS2 1.04

<TS 1292 B

106 129 16 04C 0.89

<TS 1293 B

106 131 14 03C

-0.39

<TS 1294 B

107 32 12 VS4

-0.96

<TS 1295 B

107 34 10 VS6

-0.72

<TS 1296 B

107 36 14 VS6

-0.68

<TS 1297 B

107 36 12 VS6 0

<TS 1298 B

107 40 17 VS2 0.87

<TS 1299 B

107 44 19 07C 0.15

<TS 1300 B

107 44 14 06C

-0.15

<TS 1301 B

107 46 20 VS6

-0.78

<TS 1302 B

107 46 10 VS6 0.8

<TS 1303 B

107 52 12 07C 0.89

<TS 1304 B

107 58 14 DBH 1.78

<TS 1305 B

107 78 13 VS2

-0.87

<TS 100

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1306 B

107 78 18 VS2 0.96

<TS 1307 B

107 82 30 VS2 0.82

<TS 1308 B

107 82 34 VS2

-0.86

<TS 1309 B

107 96 11 VS4 0.46

<TS 1310 B

107 96 24 VS2 0.76

<TS 1311 B

107 124 14 04C 0.84

<TS 1312 B

107 124 10 04C

-0.8

<TS 1313 B

107 130 14 02H 0.88

<TS 1314 B

107 130 16 03H 0.9

<TS 1315 B

107 132 16 07C 0.78

<TS 1316 B

107 132 18 04C 0.78

<TS 1317 B

107 132 32 03C 0.85

<TS 1318 B

107 132

.16 02C 0.94

<TS 1319 B

108 33 14 DBH

-1.7

<TS 1320 B

108 33 25 08H 0.2

<TS 1321 B

108 35 24 04H 0.93

<TS 1322 B

108 35 14 04C 0.85

<TS 1323 B

108 35 17 04C

-0.96

<TS 1324 B

108 37 12 04C

-0.9

<TS 1325 B

108 37 14 02C 0.94

<TS 1326 B

108 37 24 03C 0

<TS 1327 B

108 43 15 VS4

-0.83

<TS 1328 B

108 45 14 07C 0.87

<TS 1329 B

108 49 13 05H 0.98

<TS 1330 B

108 51 26 VS2

-0.85

<TS 1331 B

108 51 15 VS2 1.02

<TS 1332 B

108 63 13 07H 0.09

<TS 1333 B

108 63 12 07H 0.89

<TS 1334 B

108 69 12 05H 0.91

<TS 1335 B

108 103 11 07C 0.82

<TS 1336 B

108 111 12 VS2

-0.15

<TS 1337 B

108 113 26 VS4

-0.91

<TS 1338 B

108 113 23 VS4 0.93

<TS 1339 B

108 115 15 07C 0.89

<TS 1340 B

108 129 13 04H

-0.13

<TS 1341 B

108 131 19 02C 0.78

<TS 1342 B

108 131 13 03C 0.09

<TS 1343 B

108 133 17 02C 0.11

<TS 1344 B

109 34 19 04C 0.04

<TS 1345 B

109 34 20 VS4

-0.81

<TS 1346 B

109 54 10 06H 0.73

<TS 1347 B

109 62 20 07C 0.76

<TS 1348 B

109 64 16 08C

-0.89

<TS 1349 B

109 78 18 04C

-0.91

<TS 1350 B

109 84 10 04H

-0.15

<TS 101

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1351 B

109 92 11 07C 1.01

<TS 1352 B

109 112 22 07H 0.87

<TS 1353 B

109 112 15 07C 0.96

<TS 1354 B

109 112 13 06C 0.87

<TS 1355 B

109 126 21 04H 0.9

<TS 1356 B

109 130 26 02C 0.85

<TS 1357 B

109 130 15 03C 0.89

<TS 1358 B

109 132 15 DBH 1.33

<TS 1359 B

109 132 19 05C 0.87

<TS 1360 B

109 132 11 04C 0.74

<TS 1361 B

109 132 21 04C

-0.02

<TS 1362 B

110 37 14 04C

-0.97

<TS 1363 B

110 37 10 03C

-0.89

<TS 1364 B

110 41 13 02C 0.11

<TS 1365 B

110 51 11 05H 0.92

<TS 1366 B

110 55 27 VS2

-0.97

<TS 1367 B

110 55 12 VS2 0.99

<TS 1368 B

110 69 11 06H

-0.92

<TS 1369 B

110 79 23 VS2

-0.02

<TS 1370 B

110 97 17 08H 1.04

<TS 1371 B

110 115 15 03H

-0.89

<TS 1372 B

110 131 28 03C 0.85

<TS 1373 B

110 131 14 02C 0.91

<TS 1374 B

110 131 13 02C

-0.92

<TS 1375 B

110 131 15 03C

-0.96

<TS 1376 B

111 40 9

DBC

-1.59

<TS 1377 B

111 56 11 08H

-0.09

<TS 1378 B

111 66 12 07H 0.89

<TS 1379 B

111 74 11 05H 0.88

<TS 1380 B

111 84 11 04H

-0.86

<TS 1381 B

111 118 13 04H 0.87

<TS 1382 B

111 120 14 04H 0.87

<TS 1383 B

111 122 12 03C

-0.91

<TS 1384 B

111 122 11 03C

-0.15

<TS 1385 B

111 126 16 03C 0.8

<TS 1386 B

111 128 17 03H

-0.53

<TS 1387 B

111 130 19 02H 0.21

<TS 1388 B

111 130 22 VS4 0.95

<TS 1389 B

112 37 32 04C

-0.92

<TS 1390 B

112 39 12 02H 0.89

<TS 1391 B

112 43 16 VS2 0.91

<TS 1392 B

112 43 17 VS2

-0.94

<TS 1393 B

112 45 11 03H 0.91

<TS 1394 B

112 47 24 VS2

-0.85

<TS 1395 B

112 47 12 VS2 0.9

<TS 102

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1396 B

112 47 22 VS4 0.92

<TS 1397 B

112 49 10 VS4 0.69

<TS 1398 B

112 55 12 04H

-0.91

<TS 1399 B

112 71 14 VS2

-0.82

<TS 1400 B

112 79 14 04H

-0.83

<TS 1401 B

112 119 11 03H

-0.91

<TS 1402 B

112 121 13 02C 0.83

<TS 1403 B

112 127 26 03C 0.11

<TS 1404 B

113 36 11 08H 0.72

<TS 1405 B

113 36 12 VS2

-0.67

<TS 1406 B

113 36 14 VS2 0.85

<TS 1407 B

113 36 17 VS6

-0.91

<TS 1408 B

113 36 11 VS6 0.72

<TS 1409 B

113 36 16 02C 0.91

<TS 1410 B

113 36 10 04H

-0.93

<TS 1411 B

113 38 13 VS4

-0.9

<TS 1412 B

113 40 13 04H

-0.04

<TS 1413 B

113 40 15 VS4

-0.87

<TS 1414 B

113 40 19 03C

-0.57

<TS 1415 B

113 42 11 05H

-0.1

<TS 1416 B

113 42 11 03C

-0.15

<TS 1417 B

113 44 16 01H 0.86

<TS 1418 B

113 48 12 VS2 0.93

<TS 1419 B

113 48 38 VS2

-0.89

<TS 1420 B

113 48 38 VS4

-0.84

<TS 1421 B

113 48 10 VS4 0.63

<TS 1422 B

113 66 11 06H 0.93

<TS 1423 B

113 70 18 07C 0.13

<TS 1424 B

113 70 18 07C 0.89

<TS 1425 B

113 84 9

04H

-0.88

<TS 1426 B

113 84 14 02H

-0.94

<TS 1427 B

113 110 15 04C 0.85

<TS 1428 B

113 122 12 03C

-0.96

<TS 1429 B

114 37 12 04C 0.92

<TS 1430 B

114 39 34 VS4 0.72

<TS 1431 B

114 39 11 02C 0.92

<TS 1432 B

114 43 12 07H 0.76

<TS 1433 B

114 127 14 05C 0.85

<TS 1434 B

114 127 16 04C 0.8

<TS 1435 B

114 127 23 03C 0.87

<TS 1436 B

114 129 14 VS4

-0.92

<TS 1437 B

115 38 13 08H 0.85

<TS 1438 B

115 38 14 02C 0.92

<TS 1439 B

115 38 37 01C 0.44

<TS 1440 B

115 58 9

07H

-1.02

<TS 103

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1441 B

115 68 7

05H 0.86

<TS 1442 B

115 84 14 03H

-0.86

<TS 1443 B

115 86 16 03H 0.7

<TS 1444 B

115 104 10 04H

-0.9

<TS 1445 B

115 114 14 07H 0.95

<TS 1446 B

115 122 13 07H 1.01

<TS 1447 B

115 124 17 05C

-0.93

<TS 1448 B

115 126 18 03C 0.93

<TS 1449 B

115 126 16 03C

-0.87

<TS 1450 B

115 126 14 04H 0.84

<TS 1451 B

115 128 14 VS4

-0.89

<TS 1452 B

116 45 13 06H 0.91

<TS 1453 B

116 55 15 04C 0.95

<TS 1454 B

116 55 13 VS2

-0.95

<TS 1455 B

116 55 19 VS4 0.93

<TS 1456 B

116 81 11 07C

-0.88

<TS 1457 B

116 81 8

07C

-0.17

<TS 1458 B

116 93 10 04C

-0.83

<TS 1459 B

116 97 11 04C

-0.21

<TS 1460 B

116 103 15 05C 0.86

<TS 1461 B

116 111 12 05H

-0.97

<TS 1462 B

116 111 10 08C 0.91

<TS 1463 B

116 111 20 04C

-1

<TS 1464 B

116 111 7

05H 0.89

<TS 1465 B

116 115 19 VS4 0.93

<TS 1466 B

116 117 13 03C

-0.99

<TS 1467 B

116 117 17 03C

-0.13

<TS 1468 B

116 125 12 05C 0.82

<TS 1469 B

116 125 17 04C 0.86

<TS 1470 B

116 125 15 04C 0.04

<TS 1471 B

116 125 35 03C 0.78

<TS 1472 B

117 40 11 01C

-0.94

<TS 1473 B

117 40 22 02C

-0.85

<TS 1474 B

117 40 14 02C

-0.07

<TS 1475 B

117 40 13 02C 0.9

<TS 1476 B

117 40 19 03C

-0.96

<TS 1477 B

117 40 11 03C

-0.07

<TS 1478 B

117 40 10 04C

-1.02

<TS 1479 B

117 40 17 04C

-0.07

<TS 1480 B

117 40 12 05C 0.76

<TS 1481 B

117 44 10 02C 0.8

<TS 1482 B

117 48 11 03C

-0.89

<TS 1483 B

117 66 14 06H 0.99

<TS 1484 B

117 66 14 07C 0.88

<TS 1485 B

117 68 14 05H 0.9

<TS 104

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1486 B

117 82 9

06H

-0.95

<TS 1487 B

117 90 16 08C 0.87

<TS 1488 B

117 108 12 03H

-0.84

<TS 1489 B

117 108 10 04H 0.91

<TS 1490 B

117 112 18 04H 0.87

<TS 1491 B

118 41 12 02H 0.85

<TS 1492 B

118 41 12 03C

-0.09

<TS 1493 B

118 73 13 VS7

-0.8

<TS 1494 B

118 87 15 VS2 0.98

<TS 1495 B

118 89 15 VS4 0.7

<TS 1496 B

118 89 23 VS2 0.96

<TS 1497 B

118 97 14 VS2

-1

<TS 1498 B

118 101 10 08C 1.04

<TS 1499 B

118 117 14 04C

-0.2

<TS 1500 B

118 121 11 03H

-0.93

<TS 1501 B

118 123 19 04C

-0.88

<TS 1502 B

118 123 12 03C 0.8

<TS 1503 B

118 123 12 02C 0.87

<TS 1504 B

119 42 12 05C 0.85

<TS 1505 B

119 42 16 VS7

-0.76

<TS 1506 B

119 42 12 02H 0.88

<TS 1507 B

119 42 18 03C 0.46

<TS 1508 B

119 42 17 04C

-0.15

<TS 1509 B

119 42 13 04C

-0.9

<TS 1510 B

119 44 16 02H 0.92

<TS 1511 B

119 44 14 01C 0.9

<TS 1512 B

119 46 19 02C 0.87

<TS 1513 B

119 88 19 08C 0.9

<TS 1514 B

119 88 7

08C

-0.09

<TS 1515 B

119 104 14 VS1

-0.85

<TS 1516 B

119 110 14 04C 0.89

<TS 1517 B

119 112 17 04C 0.83

<TS 1518 B

119 112 13 03C 0.85

<TS 1519 B

119 112 11 03C

-0.82

<TS 1520 B

119 122 14 04H

-0.93

<TS 1521 B

120 43 18 01C

-0.9

<TS 1522 B

120 43 7

01C 0.96

<TS 1523 B

120 43 11 02H 0.84

<TS 1524 B

120 45 11 02C 0.83

<TS 1525 B

120 47 24 03C 0.87

<TS 1526 B

120 47 12 03C

-0.59

<TS 1527 B

120 49 11 03C

-0.87

<TS 1528 B

120 55 12 07C

-0.89

<TS 1529 B

120 61 13 08C 0.85

<TS 1530 B

120 103 15 07H 0.8

<TS 105

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1531 B

120 115 8

05C 0.06

<TS 1532 B

120 115 19 03C 0.72

<TS 1533 B

120 121 9

03H 0.93

<TS 1534 B

121 44 12 03C

.0.87

<TS 1535 B

121 44 16 01H 0.8

<TS 1536 B

121 104' 13 05H 0.82

<TS 1537 B

121 104 10 03H 0.89

<TS 1538 B

121 114 11 04C

-0.98

<TS 1539 B

121 114 10 03C 0.76

<TS 1540 B

121 118 18 02C 0.77

<TS 1541 B

121 120 11 02C

-0.22

<TS 1542 B

121 122 12 02H 0.85

<TS 1543 B

122 71 11 05H 0.96

<TS 1544 B

122 111 12 06C 0.78

<TS 1545 B

123 52 16 02C 0.93

<TS 1546 B

123 72 13 VS7 0.91

<TS 1547 B

123 78 18 05H

-1.13

<TS 1548 B

123 84 10 04H

-0.27

<TS 1549 B

123 98 9

06C 0.87

<TS 1550 B

123 116 39 VS6

-0.8

<TS 1551 B

123 116 19 05C

-1.06

<TS 1552 B

123 116 13 04C 0.87

<TS 1553 B

123 116 13 03C 0.76

<TS 1554 B

123 118 11 08C 0.88

<TS 1555 B

124 47 10 03C 0.98

<TS 1556 B

124 47 10 01C

-0.44

<TS 1557 B

124 49 17 02C

-0.87

<TS 1558 B

124 55 11 05H

-0.19

<TS 1559 B

124 95 16 VS4

-0.87

<TS 1560 B

124 95 19 VS4 0.91

<TS 1561 B

124 105 10 06C 0.93

<TS 1562 B

124 111 7

02C

-0.18

<TS 1563 B

124 113 13 03C

-0.17

<TS 1564 B

124 113 14 03C 0.82

<TS 1565 B

124 117 22 04C 0.84

<TS 1566 B

124 117 11 06C

-0.86

<TS 1567 B

124 117 11 06C 0.84

<TS 1568 B

124 119 11 08C

-0.17

<TS 1569 B

124 119 14 08C 0.78

<TS 1570 B

125 48 9

VS4

-0.8

<TS 1571 B

125 48 14 VS4 0.91

<TS 1572 B

125 48 16 VS6 0.91

<TS 1573 B

125 78 11 03H

-0.82

<TS 1574 B

125 82 11 05H

-0.88

<TS 1575 B

125 100 13 08C 1.06

<TS 106

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1576 B

125 104 16 07C

-0.11

<TS 1577 B

125 104 16 07H 0.78

<TS 1578 B

125 112 20 02C 0.88

<TS 1579 B

125 114 14 03C 0.74

<TS 1580 B

125 116 19 02H 0.87

<TS 1581 B

125 116 13 03H 0.87

<TS 1582 B

125 118 14 05H

-0.87

<TS 1583 B

126 51 11 01C 0.87

<TS 1584 B

126 55 13 02C 0.87

<TS 1585 B

126 55 10 06H 0.94

<TS 1586 B

126 81 11 VS4

-0.92

<TS 1587 B

126 95 21 VS4

-0.89

<TS 1588 B

126 95 15 VS6 0.98

<TS 1589 B

126 99 12 07C 0.95

<TS 1590 B

126 99 18 08C 1.04

<TS 1591 B

126 103 17 VS4 0.78

<TS 1592 B

126 109 15 04H 0.78

<TS 1593 B

126 115 9

02C 0.13

<TS 1594 B

126 115 20 02C 0.8

<TS 1595 B

127 52 12 01H

-0.42

<TS 1596 B

127 54 17 01H

-0.93

<TS 1597 B

127 72 12 05H 0.88

<TS 1598 B

127 92 19 08C

-0.19

<TS 1599 B

127 92 9

VS6

-1.01

<TS 1600 B

127 102 15 07C

-0.17

<TS 1601 B

127 104 13 06C 0.94

<TS 1602 B

127 106 19 07C

-0.22

<TS 1603 B

127 108 14 06C 0.89

<TS 1604 B

127 110 16 02C 0.8

<TS 1605 B

127 112 19 02C 0.8

<TS 1606 B

127 114 18 01H

-0.88

<TS 1607 B

127 114 13 02H 0.86

<TS 1608 B

127 114 13 03C 0.82

<TS 1609 B

127 114 13 02C 0.85

<TS 1610 B

128 53 16 01H

-0.04

<TS 1611 B

128 55 22 01C

-0.5

<TS 1612 B

128 57 9

01H

-0.9

<TS 1613 B

128 73 14 06H 0.93

<TS 1614 B

128 73 25 VS1 0.04

<TS 1615 B

128 73 10 06H 0.13

<TS 1616 B

128 73 16 VS4 0.91

<TS 1617 B

128 99 11 07C 0.95

<TS 1618 B

128 101 21 05C 0.88

<TS 1619 B

128 109 13 02C

-0.02

<TS 1620 B

128 113 26 02C

-0.9

<TS 107

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1621 B

129 56 19 01C 0.88

<TS 1622 B

129 56 20 01H 0.81

<TS 1623 B

129 58 12 01H

-0.83

<TS 1624 B

129 64 20 VS7

-0.73

<TS 1625 B

129 68 12 02H

-0.89

<TS 1626 B

129 84 20 06H 0.81

<TS 1627 B

129 102 7

06C

-0.06

<TS 1628 B

129 102 16 08C

-1.04

<TS 1629 B

129 102 10 08C 0.19

<TS 1630 B

129 104 10 07C

-0.17

<TS 1631 B

129 106 20 08C 0.98

<TS 1632 B

129 106 12 06C 0.8

<TS 1633 B

129 106 10 08C

-0.28

<TS 1634 B

129 108 12 06C 0.94

<TS 1635 B

129 108 12 02C 0.98

<TS 1636 B

129 110 18 02C 0.73

<TS 1637 B

130 55 19 01H 0.89

<TS 1638 B

130 55 16 02C 0.93

<TS 1639 B

130 69 12 05H 0.75

<TS 1640 B

130 107 16 DBC

-1.84

<TS 1641 B

130 109 16 04H 0.89

<TS 1642 B

131 58 30 01C 0.89

<TS 1643 B

131 60 14 VS6 0.74

<TS 1644 B

131 64 25 VS7 0.91

<TS 1645 B

131 70 13 03C 0.87

<TS 1646 B

131 74 10 02H

-0.85

<TS 1647 B

131 82 14 08H

-0.91

<TS 1648 B

131 88 14 07C 0.88

<TS 1649 B

131 96 9

08H

-0.11

<TS 1650 B

131 96 20 04C 0.94

<TS 1651 B

131 98 11 DBC 2.06

<TS 1652 B

131 100 10 06C 0.85

<TS 1653 B

131 102 12 04C 0.85

<TS 1654 B

131 102 17 05C 0.94

<TS 1655 B

131 102 22 06C

-0.9

<TS 1656 B

131 104 28 VS7 0.86

<TS 1657 B

131 104 16 DBC 2

<TS 1658 B

132 61 13 01H 0.89

<TS 1659 B

132 75 11 02H 0.81

<TS 1660 B

132 81 14 05H 0.88

<TS 1661 B

132 97 11 VS1 0.83

<TS 1662 B

132 97 16 VS2

-0.83

<TS 1663 B

132 97 11 VS2

-0.19

<TS 1664 B

132 97 16 VS7 0.85

<TS 1665 B

132 97 12 VS4

-0.94

<TS 108

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1666 B

132 97 9

VS4 0.53

<TS 1667 B

132 101 11 06C

-0.17

<TS 1668 B

132 101 16 06C 0.89

<TS 1669 B

132 101 13 VS7 0.93

<TS 1670 B

132 107 26 02C

-0.84

<TS 1671 B

133 68 13 02H 0.89

<TS 1672 B

133 74 16 03H 0.8

<TS 1673 B

133 76 14 07C 0.93

<TS 1674 B

133 100 14 VS7

-0.15

<TS 1675 B

133 102 17 07C

-0.97

<TS 1676 B

133 104 11 DBC 2.06

<TS 1677 B

134 63 17 07C 0.76

<TS 1678 B

134 63 18 DBH

-1.85

<TS 1679 B

134 65 21 02H 0.89

<TS 1680 B

134 65 14 VS2

-0.76

<TS 1681 B

134 69 10 04H 0.08

<TS 1682 B

134 69 7

VS7

-0.93

<TS 1683 B

134 69 24 VS7 0.91

<TS 1684 B

134 69 16 04H 0.9

<TS 1685 B

134 95 12 06C 0.85

<TS 1686 B

134 95 16 DBC 1.26

<TS 1687 B

135 68 12 02H

-0.91

<TS 1688 B

135 68 17 VS7 0.85

<TS 1689 B

135 76 15 08C 0.8

<TS 1690 B

135 76 21 08C

-1

<TS 1691 B

135 80 18 07H

-0.98

<TS 1692 B

135 82 27 VS7 0.93

<TS 1693 B

135 82 23 VS7

-0.93

<TS 1694 B

135 90 29 VS7 0.71

<TS 1695 B

135 92 22 07C 0.82

<TS 1696 B

135 92 34 08C 0.82

<TS 1697 B

136 77 14 03H 0.84

<TS

.1698 B

136 87 16 08C

-1.05

<TS 1699 B

136 91 10 08C

-0.15

<TS 1700 B

136 95 18 03C 0.88

<TS 1701 B

136 97 8

08C

-0.02

<TS 1702 B

136 97 10 08C

-0.93

<TS 1703 B

136 97 14 07C 0.87

<TS 1704 B

136 97 18 03C 0.88

<TS 1705 B

137 74 14 06H 0.85

<TS 1706 B

137 76 11 05H 0.87

<TS 1707 B

137 80 16 08H 0.9

<TS 1708 B

137 92 14 08C

-1.03

<TS 1709 B

137 92 13 07C 0.15

<TS 1710 B

137 92 13 04C 0.83

<TS 109

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 4C Steam Generator E-50B Indications (all indications due to tube wear)

No.

SG Row Column Percent Location Elevation TS in Depth 1711 B

138 77 20 VS4 0.89

<TS 1712 B

138 77 17 02H 0.9

<TS 1713 B

138 77 9

03H

-0.9

<TS 1714 B

138 79 13 03H 0.85

<TS 1715 B

138 81 8

08C

-1.03

<TS 1716 B

138 81 18 VS4

-0.88

<TS 1717 B

138 85 12 08H 0.79

<TS 1.718 B

138 87 18 VS1

-0.81

<TS 1719 B

138 87 12 VS1 0.81

<TS 1720 B

138 87 16 VS4

-0.81

<TS 1721 B

138 89 12 VS6

-0.96

<TS 1722 B

138 89 14 VS6 0.81

<TS 1723 B

138 89 18 VS7

-1.01

<TS 1724 B

138 89 17 VS4

-0.76

<TS 1725 B

138 89 29 VS7 0.94

<TS 1726 B

138 89 14 07C 0.85

<TS 1727 B

138 89 7

VS7

-0.09

<TS 1728 B

138 89 4

07C

-0.13

<TS 110

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 5 Tube Plugging Summary by Damage Mechanism TUBE PLUGGING

SUMMARY

SG E-50A SG E-50B Wear - Vertical Straps 2

0 Wear-Diagonal Bar 0

0 Wear - Eggcrate 0

0 Wear - Loose Part 0

0 Wear-Dent (could not be sized TBP) 0 0

Wear - Tube to Tube (TBP) 0 0

Wear-Volumetric 0

0 Preventive - Loose Part (LP) 3 0

Circumferential ODSCC TTS 3

1:

Axial ODSCC TTS 6

4 Axial: ODSCC"Freespan Ding 0

1 Axial ODSCC Eggcrate & Vertical Strap 23 5

Axial ODSCC in Greater-Than 5 Volt Dents

.0..

0 Axial ODSCC in Less Than 5 Volt Dents 0

0 Axial PWSCC Tubesheet 0

0 Circumferential PWSCC Tubesheet 0

0 Axial ODSCC in U-bend 0

0 Restricted Tube 0

0 Administrative (PTE) 1 0

2012 Outage Total 38 11 Pre-service Tubes Plugged 308 309 Effective Tubes Plugged 524 436 Effective Tubes Plugged Percentage 6.4%

5.3%

SG Total Number of Tubes 8219 8219 111

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 6 Condition Monitoring Results Identification of Tubes Plugged (all conditions for tubes that were plugged in the 2012 refueling outage)

SG Row Column Location Reason For Plugging E-50A 3

52 01H-0.47 SAI No Stabilization E-50A 4

17 03H+0.85 SAI No Stabilization E-50A 4

109 02H-0.24 SAI No Stabilization E-50A 5

24 011H-0.78 SAI No Stabilization E-50A 6

107 01H+0.89 SAI No Stabilization E-50A 9

52 01H+0.50 SAI No Stabilization E-50A 10 57 01 H-0.44 SAI No Stabilization E-50A 10 59 01H-0.53 SAI No Stabilization E-50A 10 111 02H-0.38 SAI No Stabilization E-50A 11 126 02H+0.82 SAI No Stabilization E-50A 12 57 01H-0.64 SAI No Stabilization E-50A 15 132 01H+0.68 SAI No Stabilization E-50A 19 118 01H-0.64 SAI No Stabilization E-50A 21 108 01H+0.85 SAI No Stabilization E-50A 23 106 04H-0.18 SAI No Stabilization E-50A 25 106 01H-0.04 SAI No Stabilization E-50A 28 53 TSH+0.31 SCI Stabilization E-50A 29 108 01H+0.50 SAI No Stabilization E-50A 48 103 01H+0.16 SAI No Stabilization E-50A 51 150 TEC+17.54 Administrative (PTE)

No Stabilization E-50A 75 96 TSH+0.55 SAI No Stabilization E-50A 78 91 TSH+0.87 SAI I

_ I I

INo Stabilization 112

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 6 Condition Monitoring Results Identification of Tubes Plugged (all conditions for tubes that were plugged in the 2012 refueling outage)

SG Row Column Location Reason For Plugging E-50A 80 83 01 H+0.77 SAI No Stabilization E-50A 80 89 TSH+0.37 SAI No Stabilization E-50A 80 93 TSH+0.58 SAI No Stabilization E-50A 80 95 TSH+0.65 SAI No Stabilization E-50A 83 94 TSH+0.51 SAI No Stabilization E-50A 91 62 TSH-0.12 SCI Stabilization E-50A 92 83 01H-0.48 SAI No Stabilization E-50A 92 121 02H+0.51 SAI No Stabilization E-50A 93 58 VS2-0.86 WEAR No Stabilization E-50A 100 93 01H+0.26 SAI No Stabilization E-50A 103 68 TSH+0.18 SO Stabilization E-50A 110 85 01H-0.68 SAI No Stabilization E-50A 130 61 TSH+0.00 LP Preventive Stabilization E-50A 132 61 TSH+0.00 LP Preventive Stabilization E-50A 133 62 TSH+0.00 LP Preventive Stabilization E-50A 135 96 VS6+0.97 WEAR No Stabilization E-50B 2

39 01H-11.14 SAI No Stabilization E-50B 24 47 TSH+0.89 SAI No Stabilization E-50B 24 55 01H-0.41 SAI No Stabilization E-50B 26 47 TSH+0.40 SAI No Stabilization E-50B 74 87 01H+0.19 SAI No Stabilization E-50B 74 101 TSH+0.58 SAI No Stabilization 113

Steam Generator Tube Inspection Report for the 2012 Refueling Outage Table 6 Condition Monitoring Results Identification of Tubes Plugged (all conditions for tubes that were plugged in the 2012 refueling outage)

SG Row Column Location Reason For Plugging E-50B 75 100 TSH+0.61 SAI No Stabilization E-50B 77 112 01H-0.42 SAI No Stabilization E-50B 80 25 05H-0.87 SAI I_

No Stabilization E-50B 97 126 TSH+0.14 SCl Stabilization E-50B 122 85 01H-0.17 SAI I

I_

No Stabilization Table 7A Steam Generator Support Structure Nomenclature Name Description Name Description TEH Tube End - Hot Side VS4 Fourth Vertical Strap TSH Top of Tubesheet - Hot Side VS5 Fifth Vertical Strap 01H First Eggcrate - Hot Side VS6 Sixth Vertical Strap 02H Second Eggcrate - Hot Side VS7 Seventh Vertical Strap 03H Third Eggcrate - Hot Side DBC Diagonal Strap - Cold Side 04H Fourth Eggcrate - Hot Side 08C Eighth Eggcrate - Cold Side 05H Fifth Eggcrate - Hot Side 07C Seventh Eggcrate - Cold Side 06H Sixth Eggcrate - Hot Side 06C Sixth Eggcrate - Cold Side 07H Seventh Eggcrate - Hot Side 05C Fifth Eggcrate - Cold Side 08H Eighth Eggcrate - Hot Side 04C Fourth Eggcrate - Cold Side DBH Diagonal Strap - Hot Side 03C Third Eggcrate - Cold Side VS1 First Vertical Strap 02C Second Eggcrate - Cold Side VS2 Second Vertical Strap 01C First Eggcrate - Cold Side VS3 Third Vertical Strap TSC Top of Tubesheet - Cold Side I

TEC Tube End - Cold Side 114

Table 7B Acronyms and Abbreviations Acronym Definition CMOA Condition Monitoring and Operational Assessment BED Burst Equivalent Depth BEL Burst Equivalent Length DNI Dent or Ding with Indication DSI Distorted Support Indication LP Loose Part.

MRPC Motorized Rotating Pancake Coil (+Pt.TM)

MBM Manufacturing Burnish Mark NDE Non Destructive Examination NQI Non-Quantifiable Indication NTE No Tube Expansion ODSCC Outside Diameter Stress Corrosion Cracking PLG Tube Is Plugged PLP Possible Loose Part PTE Partial Tube Expansion PVN Permeability Variation PWSCC Primary Water Stress Corrosion Cracking SAI Single Axial Indication SCI Single Circumferential Indication SVI Single Volumetric Indication TBP To Be Plugged TTS Top of Tubesheet

<TS Less Than Technical Specification WAR Wear Indication 115