FNP LAR AUDIT PRESENTATION March 19, 2013 Session 5 - Monitoring Session 5 Monitoring Chip Westberry

Monitoring Overview

  • Provides means to ensure Assumptions remain Valid Valid

- Process Defined in FAQ 10-059 Scoping

  • Scoping
  • Screening Bi M

- Big M

- Little m

  • Target Value Determination
  • Monitoring Implementation Slide 2

Monitoring Scoping Per FAQ 59, we are scoping 6 categories of SSCs:

NSCA

- NSCA

- FPRA

- NPO

- Rad. Release

- FP Systems and features

- Programmatic Elements Slide 3

Monitoring Screening

  • Risk Criteria RAW > 2 0

- RAW > 2.0 AND

- CDF> 1E-6 OR LERF > 1E-7 CDF> 1E 6 OR LERF > 1E 7

  • Screened in gets Big M treatment using a monitoring program meeting the requirements of section 2.6 of p

g g

q NFPA 805.

  • Screened out gets Little m treatment using existing system and program health processes.
  • Corrective Action Program is used to document issues and issue resolution and issue resolution.

Slide 4

Monitoring Targets

  • Uses IPE and FPRA reliability and availability
  • Uses IPE and FPRA reliability and availability data
  • EPRI TR 1006756 report for baseline data
  • Surveillance Optimization is being committed to in Attachment S as implementation item 1.

Slide 5

Monitoring Commitments

  • Attachment S commitments for Monitoring:

The monitoring program will be implemented after the

- The monitoring program will be implemented after the safety evaluation issuance as part of the fire protection program transition to NFPA 805. A Monitoring Program Engineering Evaluation will be developed during implementation.

Slide 6

QUESTIONS ?

QUESTIONS ?

Slide 7