ML13029A676
| ML13029A676 | |
| Person / Time | |
|---|---|
| Site: | North Anna |
| Issue date: | 01/24/2013 |
| From: | NRC/RGN-II |
| To: | Virginia Electric & Power Co (VEPCO) |
| References | |
| 50-338/12-302, 50-339/12-302 | |
| Download: ML13029A676 (107) | |
Text
Dominion North Anna Power Station JOB PERFORMANCE MEASURE EVALUATION OPERATOR PROGRAM INITIAL CONDITIONS Leakage has been identified on the "A" Service Water Supply Header.
The operating crew has implemented 0-AP-12, Loss of Service Water.
High volume blowdown of the Service Water Reservoir is NOT in service.
INITIATING CUE You are requested to makeup to the Service Water Reservoir using 0-AP-12, Attachment 10, Operation of the Auxiliary Service Water Pumps.
The Unit Supervisor requests that you align 1-SW-P-4, Aux Service Water Pump, to the B Service Water Header.
Joey Linder is standing by in the rack room with the key and a copy of the attachment.
NAPS 2012 NRC Exam - RETAKE SIM JPM a - Rev_1 Page: 2 of 12 Dominion North Anna Power Station JOB PERFORMANCE MEASURE EVALUATION OPERATOR PROGRAM TASK Makeup to the Service Water Reservoir in accordance with 0-AP-12, Attachment 10.
TASK STANDARDS Service Water MOVs are aligned, 1-SW-P-4 is started, and Service Water Spray valves are opened.
K/A
REFERENCE:
076-A4.01, Ability to manually operate and/or monitor in the control room: SWS pumps (RO 2.9 / SRO 2.9)
ALTERNATE PATH:
N/A TASK COMPLETION TIMES Validation Time =
10 minutes Start Time = _______
Actual Time = _______ minutes Stop Time = _______
PERFORMANCE EVALUATION Rating
[ ] SATISFACTORY [ ] UNSATISFACTORY Candidate (Print)
Evaluator (Print)
Evaluator's Signature /
Date EVALUATOR'S COMMENTS
NAPS 2012 NRC Exam - RETAKE SIM JPM a - Rev_1 Page: 3 of 12 Dominion North Anna Power Station JOB PERFORMANCE MEASURE (Evaluation)
OPERATOR PROGRAM R452 READ THE APPLICABLE INSTRUCTIONS TO THE CANDIDATE Instructions for Simulator JPMs I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
Instructions for In-Plant JPMs I will explain the initial conditions, and state the task to be performed. All steps, including any required communications, shall be simulated for this JPM. Under no circumstances are you to operate any plant equipment. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
PREREQUISITES The trainee has completed the applicable course knowledge training at the reactor operator level.
NAPS 2012 NRC Exam - RETAKE SIM JPM a - Rev_1 Page: 4 of 12 INITIAL CONDITIONS Leakage has been identified on the "A" Service Water Supply Header.
The operating crew has implemented 0-AP-12, Loss of Service Water.
High volume blowdown of the Service Water Reservoir is NOT in service.
INITIATING CUE You are requested to makeup to the Service Water Reservoir using 0-AP-12, Attachment 10, Operation of the Auxiliary Service Water Pumps.
The Unit Supervisor requests that you align 1-SW-P-4, Aux Service Water Pump, to the B Service Water Header.
Joey Linder is standing by in the rack room with the key and a copy of the attachment.
EVALUATION METHOD Perform if conducted in the simulator or in a laboratory (use Performance Cue(s))
Simulate if conducted in the station or on a dead simulator (use Simulation Cue(s))
TOOLS AND EQUIPMENT Copy of 0-AP-12, Attachment 10
NAPS 2012 NRC Exam - RETAKE SIM JPM a - Rev_1 Page: 5 of 12 PERFORMANCE STEPS START TIME Note: Applicant will read the following procedure note:
NOTE: This Attachment provides instructions for aligning the Auxiliary Service Water Pumps for Service Water Makeup and for Lake-To-Lake Operation.
1 Request the Safeguards Operator to place the key-lock switches for the Service Water Overboard Discharge Valves in DEFEAT.
Procedure Step _____
SAT [ ] UNSAT [ ]
Standards Safeguards operator is requested to place the key-lock switches for the following valves in DEFEAT:
1-SW-MOV-120A 2-SW-MOV-220A 1-SW-MOV-120B 2-SW-MOV-220B Evaluators Note The following are expected alarms that will occur when the key-lock switches are placed in DEFEAT:
K-E3, SER WTR SYS LOGIC CABS UNITS 1 & 2 DOOR OPEN (will come in and then clear twice, simulating opening and closing of each door)
J-F8, UNIT 1 SW KEY LOCK SWITCH DEF J-G8, UNIT 2 SW KEY LOCK SWITCH DEF Notes/Comments When requested, Booth Operator will acknowledge direction from applicant and call back when action is complete.
NAPS 2012 NRC Exam - RETAKE SIM JPM a - Rev_1 Page: 6 of 12 2
Verify Screen Wash Pumps are stopped.
Procedure Step _____
SAT [ ] UNSAT [ ]
Standards The following Screen Wash Pumps are verified STOPPED, (Green Light - LIT, Red Light - NOT LIT):
1-CW-P-2B 2-CW-P-2A Notes/Comments 3
Close Service Water System MOVs.
Procedure Step _____
SAT [ ] UNSAT [ ]
Standards Candidate verifies the following Service Water System MOV closed:
- 1-SW-MOV-118 (valve is normally closed)
AND Candidate momentarily depresses the CLOSE pushbutton for the following Service Water System MOVs:
1-SW-MOV-119 2-SW-MOV-219 Notes/Comments
NAPS 2012 NRC Exam - RETAKE SIM JPM a - Rev_1 Page: 7 of 12 4
IF 1-SW-P-4 will be started on the A Header, THEN open the following valves:
Procedure Step _____
SAT [ ] UNSAT [ ]
Standards Applicant N/As this step (based on the Initiating Cue provided).
Notes/Comments 5
IF 1-SW-P-4 will be started on the B Header, THEN open the following valves:
Procedure Step _____
Critical Step SAT [ ] UNSAT [ ]
Standards The following valves are OPENED by momentarily depressing the OPEN push-button for each valve:
1-SW-MOV-118 1-SW-MOV-115B 2-SW-MOV-215A 1-SW-MOV-117 Notes/Comments
NAPS 2012 NRC Exam - RETAKE SIM JPM a - Rev_1 Page: 8 of 12 6
IF 2-SW-P-4 will be started on the B Header, THEN open the following valves:
Procedure Step _____
SAT [ ] UNSAT [ ]
Standards Applicant N/As this step (based on the Initiating Cue provided).
Notes/Comments 7
IF 2-SW-P-4 will be started on the A Header, THEN open the following valves:
Procedure Step _____
SAT [ ] UNSAT [ ]
Standards Applicant N/As this step (based on the Initiating Cue provided).
Notes/Comments
NAPS 2012 NRC Exam - RETAKE SIM JPM a - Rev_1 Page: 9 of 12 8
Start the desired auxiliary service water pump.
Procedure Step _____
Critical Step SAT [ ] UNSAT [ ]
Standards 1-SW-P-4 is STARTED by momentarily placing the control switch in START.
Evaluators Note Annunciator J-E3, AUX SW PP 1-P4 LO FLOW, will alarm and remain locked in when the pump is started. As stated in the Annunciator Response Procedure for this alarm, When 1-SW-P-4 is aligned to "B" SW header and running, this alarm is expected to be locked in".
Notes/Comments IF requested, Booth Operator will acknowledge direction from applicant to check out pump and call back that pump is ready for start and operating satisfactorily (as applicable).
NAPS 2012 NRC Exam - RETAKE SIM JPM a - Rev_1 Page: 10 of 12 9
IF Service Water Reservoir makeup is desired, THEN do the following:
9a Open all Service Water Spray Valves.
Procedure Step _____
Critical Step SAT [ ] UNSAT [ ]
Standards The following Service Water Spray Valves are OPENED, or verified OPEN as described for each valve:
1-SW-MOV-121A (valve verified open) 1-SW-MOV-122A (momentarily depress OPEN pushbutton) 1-SW-MOV-121B (valve verified open) 1-SW-MOV-122B (momentarily depress OPEN pushbutton) 2-SW-MOV-221A (valve verified open) 2-SW-MOV-222A (momentarily depress OPEN pushbutton) 2-SW-MOV-221B (valve verified open) 2-SW-MOV-222B (momentarily depress OPEN pushbutton)
ONLY those items shown in BOLD type are critical to this element, remaining items are NOT critical since they are already open (normal plant alignment).
Notes/Comments 9b Close Service Water Overboard Discharge Isolation Valves.
Procedure Step _____
SAT [ ] UNSAT [ ]
Standards The following Service Water Overboard Discharge Valves are verified CLOSED, (Green Light - LIT, Red Light - NOT LIT) 1-SW-MOV-120A 1-SW-MOV-120B 2-SW-MOV-220A 2-SW-MOV-220B Notes/Comments
NAPS 2012 NRC Exam - RETAKE SIM JPM a - Rev_1 Page: 11 of 12 10 IF Lake-To-Lake operation is desired, THEN do the following:
Procedure Step _____
SAT [ ] UNSAT [ ]
Standards Applicant N/As this step (based on the Initial Conditions provided).
Notes/Comments 11 IF high volume blowdown of Service Water Reservoir is in service, THEN secure high volume blowdown Procedure Step _____
SAT [ ] UNSAT [ ]
Standards Applicant N/As this step (based on the Initial Conditions provided).
Notes/Comments 12 Return to step in effect.
Procedure Step _____
SAT [ ] UNSAT [ ]
Standards Candidate informs you they have completed their task.
Notes/Comments
>>>>> END OF EVALUATION <<<<<
STOP TIME
NAPS 2012 NRC Exam - RETAKE SIM JPM a - Rev_1 Page: 12 of 12 SIMULATOR SETUP Reset to IC #167 (this IC has SW reservoir level slightly lower than the typical 100% IC value based on the Initial Conditions that leakage was identified on the "A" SW Supply Header)
WHEN called by applicant to perform 0-AP-12, Att. 10, Step 2, (place SW OVBD Disch Vlvs in defeat), perform the following:
actuate Trigger 1 ( to override on annunciator to ON) then actuate trigger 2 (to place key lock switches for unit 1 in DEFEAT) then toggle annunciator OFF and then ON again (to simulate closing Unit 1 door and opening Unit 2 door) then actuate trigger 3 (to place key lock switches for unit 2 in DEFEAT) then set annunciator override to OFF AND report back that action is complete.
IF called by applicant to check out pump for start (0-AP-12, Att. 10, Step 8) and/or check for operation after start, acknowledge request and report back that pump is ready for start and/or operating satisfactorily as applicable.
Note: This alignment causes the pump low flow alarm to come in (normal as stated in the AR) thus candidate may ask to check out pump twice (once prior to start and again after pump is running) and/or check valve lineup locally.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program INITIAL CONDITIONS Unit 1 is in Mode 5 following refueling.
1-OP-1.1, Unit Startup from Mode 5 at less than 140°F to Mode 5 at less than 200°F, is in progress.
1-RC-P-1C has been started and is operating normally.
The plant is solid.
RHR System is in operation.
1-CH-FCV-1122 is in MANUAL.
1-CH-PCV-1145 is in AUTO.
RCS pressure is approximately 340# (ordered band is 325 to 340 psig).
RCS Temperature is approximately 159°F (ordered band is 150°F - 170°F).
Plant is being maintained in stable condition while preparations are being made to increase RCS temperature and sample the RCS.
INITIATING CUE You are requested to maintain stable plant conditions in accordance with the ordered bands.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 2 of 13 TASK Terminate spurious SI in accordance with 1-AP-0.1.
TASK STANDARDS Running RCP (1-RC-P-1C) is stopped AND SI flow is terminated within 10 minutes from time of actuation.
K/A
REFERENCE:
006 A2.13 (3.9 / 4.2)
ALTERNATE PATH:
The BIT inlet valve 1-SI-MOV-1867B will fail to close from the control room. The Operator will have to dispatch Operations personnel to locally close the valve in order to terminate SI flow.
TASK COMPLETION TIMES Validation Time =
8 minutes Start Time = __________
Actual Time = _______ minutes Stop Time = __________
SIMULATION EVALUATION Rating
[ ] SATISFACTORY [ ] UNSATISFACTORY Operator (Print)
Evaluator (Print)
Evaluator's Signature /
Date
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 3 of 13 READ THE APPLICABLE INSTRUCTIONS TO THE OPERATOR Instructions for Simulator JPMs I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
Instructions for In-Plant JPMs I will explain the initial conditions, and state the task to be performed. All steps, including any required communications, shall be simulated for this JPM. Under no circumstances are you to operate any plant equipment. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS Unit 1 is in Mode 5 following refueling.
1-OP-1.1, Unit Startup from Mode 5 at less than 140°F to Mode 5 at less than 200°F, is in progress.
1-RC-P-1C has been started and is operating normally.
The plant is solid.
RHR System is in operation.
1-CH-FCV-1122 is in MANUAL.
1-CH-PCV-1145 is in AUTO.
RCS pressure is approximately 340# (ordered band is 325 to 340 psig).
RCS Temperature is approximately 159°F (ordered band is 150°F - 170°F).
Plant is being maintained in stable condition while preparations are being made to increase RCS temperature and sample the RCS.
INITIATING CUE You are requested to maintain stable plant conditions in accordance with the ordered bands.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 4 of 13 EVALUATION METHOD Perform if conducted in the simulator or in a laboratory (use Simulation Cue(s))
Simulate if conducted in the station or on a dead simulator (use Simulation Cue(s))
TOOLS AND EQUIPMENT Copy of 1-AP-0.1 may be provided once the procedure entrance/applicability is stated, or operator will obtain a controlled copy from bookshelf or cabinet.
(discretion of evaluator)
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 5 of 13 START TIME
__________ Note: termination of SI (completion of element 4 of this JPM is time critical). The time critical portion of the JPM begins when SI is actuated (start time) and ends when the conditions of element 4 are satisfied (1-SI-MOV-1867A &
1-SI-MOV-1867B are BOTH closed thus terminating SI injection to the RCS).
1 STOP ALL RCPs.
Procedure Step 1 Critical Step SAT [ ] UNSAT [ ]
Standards Operator momentarily places control switch for 1-RC-P-1C in STOP (RED LIGHT LIT).
Simulation / Verbal Cue(s)
If the Operator is reluctant to leave the board to continue with AP actions due to Pressurizer PORVs cycling, act as the SRO and tell the Operator that another Operator will monitor the PORV operation.
Notes/Comments Step 1 should be performed from memory since this is an Immediate Operator Action step.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 6 of 13 2
RESET BOTH TRAINS OF SI AFTER 60 SECOND TIME DELAY.
Procedure Step 2 Critical Step SAT [ ] UNSAT [ ]
Standards Operator momentarily places BOTH SI Reset switches in RESET.
Notes/Comments Operator should note the change in status windows. (P-H1 will clear and P-H2 will illuminate upon successful reset of BOTH trains of SI.)
SI will not reset if the Operator does not wait 60 seconds.
3 CHECK ONLY ONE CHARGING PUMP RUNNING YES Procedure Step 3 SAT [ ] UNSAT [ ]
Standards Operator verifies that 1-CH-P-1A is the only running charging pump (RED LIGHT LIT).
Notes/Comments
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 7 of 13 4
CLOSE BIT INLET ISOLATION VALVES.
(Alternate Path Step)
Procedure Step 4 Critical Step SAT [ ] UNSAT [ ]
Standards (ONLY those items in BOLD type are critical to this element)
Operator establishes required alignment.
Operator momentarily depresses CLOSE pushbutton for 1-SI-MOV-1867A and verifies valve indicates closed.
Operator momentarily depresses CLOSE pushbutton for 1-SI-MOV-1867B and observes that valve position (full open) DID NOT Change.
Operator dispatches operations personnel to open breaker 1-EE-BKR-1J1-2N C3 and close 1-SI-MOV-1867B per procedure step 4 RNO (see evaluator's note below).
Notes/Comments Booth operator will acknowledge the request to open the breaker and close the MOV and call back in 2 minutes to report that the requested action is complete.
Record the time the booth operator reports 1-SI-MOV-1867B closed ______________.
Evaluator's Note:
Valves 1-SI-MOV-1867A & 1-SI-MOV-1867B are in parallel. As such BOTH valves must be closed within the time frame specified below to satisfy this critical step.
Determine elapsed time as follows:
SI terminated (1-SI-MOV-1867B closed) - SI actuated (Start time of JPM) = elapsed time
___________ - _____________ = __________ Minutes.
Verify the calculated time is less than or equal to 10 minutes.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 8 of 13 5
STOP RUNNING LOW-HEAD SI PUMPS AND PUT IN AUTO-STANDBY.
Procedure Step 5 SAT [ ] UNSAT [ ]
Standards Operator momentarily places control switches for any running LHSI Pump (1-SI-P-1A and 1-SI-P-1B) in STOP (GREEN LIGHT LIT).
Notes/Comments 6
STABILIZE RCS PRESSURE AS NECESSARY FOR PLANT CONDITIONS.
Procedure Step 6 SAT [ ] UNSAT [ ]
Standards Operator monitors RCS pressure and determines that the PORV is cycling properly and controlling plant pressure at LTOP setpoint.
Cue(s)
As the SRO, confirm that you desire to allow the PORVs to cycle at the LTOP setpoint while recovery actions continue.
Notes/Comments Cue may not be necessary (operator may determine based on plant conditions that this option is the most appropriate).
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 9 of 13 7
CHECK AFW - IN-SERVICE NO Procedure Step 7 SAT [ ] UNSAT [ ]
Standards Operator determines AFW is NOT in-service by Control Board indications and/or knowledge of plant conditions (AFW isolated in this Mode) and goes to Step 8 (per RNO).
Notes/Comments 8
EVALUATE CONTAINMENT EVACUATION, AS APPLICABLE.
Procedure Step 8 SAT [ ] UNSAT [ ]
Cue(s)
As the SRO, inform the operator that the Shift Manager will evaluate the need for Containment evacuation.
Notes/Comments
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 10 of 13 9
CLOSE BIT OUTLET ISOLATION VALVES.
Procedure Step 9 SAT [ ] UNSAT [ ]
Standards Operator verifies/establishes required alignment.
Operator momentarily depresses CLOSE pushbutton for 1-SI-MOV-1867C and verifies valve indicates closed (GREEN LIGHT LIT).
Operator momentarily depresses CLOSE pushbutton for 1-SI-MOV-1867D (SEE NOTE).
Notes/Comments 1-SI-MOV-1867D will NOT close. There is no RNO for this action so there is no action required. The candidate may merely note the malfunction and continue to the next step of the procedure, they may choose to notify the SRO of the component malfunction at this time and request guidance, or they may choose to dispatch an operator to open the breaker and close the valve locally.
CUE IF operator notifies SRO of 1-SI-MOV-1867D failure to close and requests guidance, THEN as the Unit Supervisor tell them that you will address failure of the valve to close; continue with the procedure. (As stated above cue may not be necessary) 10 RESET BOTH TRAINS OF PHASE A ISOLATION.
Procedure Step 10 Critical Step SAT [ ] UNSAT [ ]
Standards Operator momentarily places BOTH Phase A Isolation Reset switches in RESET.
Notes/Comments Operator should note change in annunciator window status, (K-H7 clears upon successful reset of BOTH trains of Phase A).
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 11 of 13 11 CHECK IF RCP SEAL WATER RETURN CAN BE ESTABLISHED YES.
Procedure Step 11 SAT [ ] UNSAT [ ]
Standards Operator confirms RCP Seal Water return parameters are satisfied and performs the following:
Operator momentarily depresses OPEN pushbutton for 1-CH-MOV-1380 and verifies valve indicates open (RED LIGHT LIT).
Operator momentarily depresses OPEN pushbutton for 1-CH-MOV-1381 and verifies valve indicates open (RED LIGHT LIT).
Notes/Comments
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 12 of 13 12 CHECK CHARGING AND LETDOWN REQUIRED FOR RCS PRESSURE AND LEVEL CONTROL YES Procedure Step 12 SAT [ ] UNSAT [ ]
Standards Operator determines that Charging and Letdown are required to control RCS pressure.
Notes/Comments Cue(s)
Assume that another operator will perform the remainder of this attachment.
This completes the JPM.
>>>>> END OF EVALUATION <<<<<
STOP TIME
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program NAPS 2012 NRC Exam - RETAKE SIM JPM b - rev_1 Page: 13 of 13 SIMULATOR SETUP TASK Terminate spurious SI in accordance with 1-AP-0.1.
CHECKLIST NOTE: An instructor may be assigned as an extra operator on the floor to silence any unrelated nuisance alarms. Nuisance alarms can also be overridden as part of the IC shoot if desired.
Recall IC #163 (Mode 5, solid, RHR in-serivce)
Ensure P/T display is called up on ICCM (pressure difference since only 1 RCP is running)
Override close pushbutton (OFF) for 1-SI-MOV-1867B Override close pushbutton (OFF) for 1-SI-MOV-1867D (ensures critical task integrity since the only way to terminate SI in the AP will be to perform the RNO of Step 4).
Ensure Charging & Letdown are setup with 1-CH-FCV-1122 in manual and adjusted such that 1-CH-PCV-1145 is controlling at ~50% demand in auto.
Once operator has assumed Unit responsibility, perform the following to initiate the spurious SI:
Trigger 1 / Spurious SI Train A/B Delete the malfunction after triggering to allow SI to be reset by the Operator per Step 2 of the AP.
As Aux Bldg Operator, acknowledge order to open breaker 1-EE-BKR-1J1-2N C3 for 1-SI-MOV-1867B and locally close the valve; De-energize the MOV : Trigger 2 / SIMOV867B_RACKIN Close the MOV: Trigger 3 / SIMOV867B After 2 minutes, report back that the action is complete. (Terminating SI is a time critical action)
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program INITIAL CONDITIONS Unit 1 is at 100% power and stable.
There are no limiting actions and there is no equipment out-of-service.
INITIATING CUE You are directed to perform 1-PT-17.1, Control Rod Operability.
The following activities have been completed in preparation for performance of the PT:
The Bank Overlap Counter reading is 614 Predictive Analysis was contacted and will NOT be taking thermography data.
HP has been notified of the potential for dose rates to increase.
An additional set of PRZR heaters has been locked on.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 2 of 11 NAPS 2012 NRC Exam - RETAKE JPM c SIM - DRAFT TASK Perform Control Rod Operability PT.
TASK STANDARDS Candidate begins performance of Control Rod Operability PT IAW 1-PT-17.1; while withdrawing CBD two (2) CBB rods will drop without an automatic reactor trip; candidate will perform IOA Step 1, of 1-AP-1.2, Dropped Rod, and manually trip the reactor.
K/A
REFERENCE:
001A2.11, Ability to (a) predict the impacts of the following malfunction or operations on the CRDS-and (b) based on those predictions, use procedures to correct, control, or mitigate the consequences of those malfunctions or operations: Situations requiring a reactor trip.
ALTERNATE PATH:
YES TASK COMPLETION TIMES Validation Time =
10 minutes Start Time = __________
Actual Time = ________ minutes Stop Time = __________
PERFORMANCE EVALUATION Rating
[ ] SATISFACTORY [ ] UNSATISFACTORY Candidate (Print)
Evaluator (Print)
Evaluator's Signature / Date EVALUATOR'S COMMENTS
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 3 of 11 NAPS 2012 NRC Exam - RETAKE JPM c SIM - DRAFT READ THE APPLICABLE INSTRUCTIONS TO THE CANDIDATE Instructions for Simulator JPMs I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
Instructions for In-Plant JPMs I will explain the initial conditions, and state the task to be performed. All steps, including any required communications, shall be simulated for this JPM. Under no circumstances are you to operate any plant equipment. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS Unit 1 is at 100% power and stable.
There are no limiting actions and there is no equipment out-of-service.
INITIATING CUE You are directed to perform 1-PT-17.1, Control Rod Operability.
The following activities have been completed in preparation for performance of the PT:
The Bank Overlap Unit reading is 614 Predictive Analysis was contacted and will NOT be taking thermography data.
HP has been notified of the potential for dose rates to increase.
An additional set of PRZR heaters has been locked on.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 4 of 11 NAPS 2012 NRC Exam - RETAKE JPM c SIM - DRAFT EVALUATION METHOD Demonstration if conducted in the simulator or in a laboratory (use DEMONSTRATION cues)
Verbal-visual if conducted in the station or on a dead simulator (use VERBAL-VISUAL cues)
TOOLS AND EQUIPMENT Copy of 1-PT-17.1 (SRO step signed off)
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 5 of 11 NAPS 2012 NRC Exam - RETAKE JPM c SIM - DRAFT Start Time:
Evaluators Note: Steps that appear in brackets [ ] are Immediate Operator Action (IOA) steps and are expected to be performed from memory.
Step / Action Notes / Comments 1
Reviews ICs and P&Ls Procedure Step Section 3.0 & 4.0 SAT [ ] UNSAT [ ]
Standards Candidate reviews ICs and P&Ls of procedure.
Step / Action Notes / Comments 2
Record bank overlap counter reading Procedure Step 6.1.1 SAT [ ] UNSAT [ ]
Note: information provided in ICs Standards Candidate records 614.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 6 of 11 NAPS 2012 NRC Exam - RETAKE JPM c SIM - DRAFT Step / Action Notes / Comments 3
Record Control Bank D step counter Reading Procedure Step 6.1.2 SAT [ ] UNSAT [ ]
Standards Candidate records 230.
Step / Action Notes / Comments 4
Calculate difference Procedure Step 6.1.3 Critical Step SAT [ ] UNSAT [ ]
Critical Step because if candidate calculates the incorrect value they will not be able to continue with the task Standards Candidate calculates 384 Evaluators Note: Step 6.1.4 is N/A (information provided in ICs)
Step 6.1.5 is already signed off by the SRO (information provided in ICs)
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 7 of 11 NAPS 2012 NRC Exam - RETAKE JPM c SIM - DRAFT Step / Action Notes / Comments 5
Determine correct Subsection.
Procedure Step 6.1.6 SAT [ ] UNSAT [ ]
Standards Candidate determines Subsection 6.2 based on plant conditions Step / Action Notes / Comments 6
Verify Bank Overlap Counter correct for plant conditions.
Procedure Step 6.2.1 SAT [ ] UNSAT [ ]
Standards Candidate N/As this step since the counter is reading the required value (384 steps)
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 8 of 11 NAPS 2012 NRC Exam - RETAKE JPM c SIM - DRAFT Step / Action Notes / Comments 7
Test Control Bank D Procedure Step 6.2.2a-c Critical Step*
SAT [ ] UNSAT [ ]
ONLY those item(s) in BOLD type are critical to this element Standards Candidate performs the following:
checks that control bank D step counters both read the same.
Place Bank Selector switch in CBD
Record position for CBD Evaluators Note: Step 6.2.2.d is N/A (based on plant conditions)
Step / Action Notes / Comments 8
Complete data sheet for CBD Initial Position.
Procedure Step 6.2.2.e SAT [ ] UNSAT [ ]
Standards Candidate records data
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 9 of 11 NAPS 2012 NRC Exam - RETAKE JPM c SIM - DRAFT Step / Action Notes / Comments 9
Insert CBD 18 steps Procedure Step 6.2.2.f Critical Step SAT [ ] UNSAT [ ]
Standards Candidate inserts CBD to 212 steps Step / Action Notes / Comments 10 Observe IRPIs and record data.
Procedure Step 6.2.2.g & 6.2.2.h Critical Step SAT [ ] UNSAT [ ]
Standards Candidate observes that IRPIs responded properly and records data
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 10 of 11 NAPS 2012 NRC Exam - RETAKE JPM c SIM - DRAFT Evaluators Note: once candidate begins CBD withdrawal two (2) CBB rods will drop requiring the candidate to suspend performance of the PT and implement 1-AP-1.2, Dropped Rod Step / Action Notes / Comments 11 Return CBD to previous position.
Procedure Step 6.2.2.i SAT [ ] UNSAT [ ]
Standards Candidate begins withdrawing CBD to 230 steps.
Step / Action Notes / Comments 12 ALTERNATE PATH Verify only ONE control rod dropped (NO)
Procedure Step 1-AP-1.2, Step [1]
CUE:
WHEN candidate states that they have completed the IOAs of 1-E-0, THEN acknowledge 1-E-0 IOAs complete and tell them this completes your task.
Critical Step SAT [ ] UNSAT [ ]
Standards Candidate identifies that two (2) rods have dropped and manually trips the reactor.
END OF EVALUATION Stop Time:
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 11 of 11 NAPS 2012 NRC Exam - RETAKE JPM c SIM - DRAFT Simulator Booth Instructions 1
Recall 100% IC 2
Ensure both non-emergency group (2 and 5) backup heaters are locked on 3
Pre-load two control bank B rods drop (J7 & J9 Trigger 1) 4 Pre-load override RBL OFF for J9 5
Pre-load reactor fails to trip automatically (insurance) 6 Using mon-screen set nik403=10 (neg rate trip bistable sensor WHEN operator begins withdrawing control rods to restore CBD to ARO, THEN actuate Trigger 1.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program INITIAL CONDITIONS Unit is at 100% power and stable.
The POD has an activity to stroke 1-RC-LCV-1460A INITIATING CUE To support the POD activity, the Shift Manager has directed you to place Excess Letdown in service IAW 1-OP-8.5, Operation of Excess Letdown, Sub-section 5.1
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 2 of 12 NAPS 2012 NRC Exam - RETAKE SIM JPM d - DRAFT TASK Place Excess Letdown in service.
TASK STANDARDS Excess Letdown is placed in service IAW 1-OP-8.5.
K/A
REFERENCE:
004A4.06, Ability to manually operate and/or monitor in the control room: Letdown isolation and flow control valves.
ALTERNATE PATH:
N/A TASK COMPLETION TIMES Validation Time =
10 minutes Start Time = __________
Actual Time = ________ minutes Stop Time = __________
PERFORMANCE EVALUATION Rating
[ ] SATISFACTORY [ ] UNSATISFACTORY Candidate (Print)
Evaluator (Print)
Evaluator's Signature / Date EVALUATOR'S COMMENTS
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 3 of 12 NAPS 2012 NRC Exam - RETAKE SIM JPM d - DRAFT READ THE APPLICABLE INSTRUCTIONS TO THE CANDIDATE Instructions for Simulator JPMs I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
Instructions for In-Plant JPMs I will explain the initial conditions, and state the task to be performed. All steps, including any required communications, shall be simulated for this JPM. Under no circumstances are you to operate any plant equipment. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS Unit is at 100% power and stable.
The POD has an activity to stroke 1-RC-LCV-1460A INITIATING CUE To support the POD activity, the Shift Manager has directed you to place Excess Letdown in service IAW 1-OP-8.5, Operation of Excess Letdown, Sub-section 5.1
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 4 of 12 NAPS 2012 NRC Exam - RETAKE SIM JPM d - DRAFT EVALUATION METHOD Demonstration if conducted in the simulator or in a laboratory (use DEMONSTRATION cues)
Verbal-visual if conducted in the station or on a dead simulator (use VERBAL-VISUAL cues)
TOOLS AND EQUIPMENT Copy of 1-OP-8.5, Operation of Excess Letdown
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 5 of 12 NAPS 2012 NRC Exam - RETAKE SIM JPM d - DRAFT Start Time:
Step / Action Notes / Comments 1
Verify ICs and review P&Ls.
Procedure Step 5.1 & 5.2 SAT [ ] UNSAT [ ]
Standards Candidate reviews Section 3.0 &
4.0 Step / Action Notes / Comments 2
Verify sufficient Component Cooling Water is supplied to Excess Letdown Heat Exchanger.
Procedure Step 5.1.3 SAT [ ] UNSAT [ ]
Standards Candidate confirms that G Panel E-2, EXC LTDN HX CC OUT LO FLOW, is NOT LIT.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 6 of 12 NAPS 2012 NRC Exam - RETAKE SIM JPM d - DRAFT Step / Action Notes / Comments 3
Close 1-CH-HCV-1137, Excess Letdown Pressure Control Valve.
Procedure Step 5.1.4 SAT [ ] UNSAT [ ]
Standards Candidate verifies 1-CH-HCV-1137 is at 0% demand..
Step / Action Notes / Comments 4
Verify Seal Water Return Valves OPEN.
Procedure Step 5.1.5 SAT [ ] UNSAT [ ]
Standards Candidate confirms that 1-CH-MOV-1380 and 1-CH-MOV-1381 are open
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 7 of 12 NAPS 2012 NRC Exam - RETAKE SIM JPM d - DRAFT Step / Action Notes / Comments 5
Energize Loop Drain Valves.
Procedure Step 5.1.6 Note: Booth operator will acknowledge order and call back when action is complete.
Critical Step*
SAT [ ] UNSAT [ ]
Note: Critical because the operator must direct this action to establish the required flowpath in order to complete the Task.
Standards Candidate directs operator to close 1-EP-CB-26B Bkr #22.
Step / Action Notes / Comments 6
Divert Excess Letdown to PDTT.
Procedure Step 5.1.7 Critical Step*
SAT [ ] UNSAT [ ]
Note: Critical because if this action is not performed there is a potential to cause a reactivity transient and/or render Safety Related ESF equipment inoperable (running Charging Pump).
Standards Candidate places selector switch for 1-CH-HCV-1389, Excess Letdown Flow Divert, in the PDTT position
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 8 of 12 NAPS 2012 NRC Exam - RETAKE SIM JPM d - DRAFT Step / Action Notes / Comments 7
Delete F0134A (Letdown flow) from processing.
Procedure Step 5.1.8 SAT [ ] UNSAT [ ]
CUE:
Tell candidate the STA has deleted the point from processing.
Standards Candidate acknowledges Step / Action Notes / Comments 8
Align Loop Drains.
Procedure Step 5.1.9 Critical Step*
SAT [ ] UNSAT [ ]
Standards Candidate opens ONLY 1 valve IAW Sub-step 5.1.9a by placing only 1 control switch for 1-RC-HCV-1557A OR 1-RC-HCV-1557B OR 1-RC-HCV-1557C in the OPEN position
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 9 of 12 NAPS 2012 NRC Exam - RETAKE SIM JPM d - DRAFT Step / Action Notes / Comments 9
Open Excess Letdown HX Isolation Valve.
Procedure Step 5.1.10 Critical Step*
SAT [ ] UNSAT [ ]
Standards Candidate places control switch for 1-CH-HCV-1201 in the OPEN position.
Step / Action Notes / Comments 10 Initiate Excess Letdown.
Procedure Step 5.1.11 Critical Step*
SAT [ ] UNSAT [ ]
Standards Candidate increases demand on 1-CH-HCV-1137.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 10 of 12 NAPS 2012 NRC Exam - RETAKE SIM JPM d - DRAFT Step / Action Notes / Comments 11 Verify acceptable parameters.
Procedure Step 5.1.12 SAT [ ] UNSAT [ ]
Standards Candidate confirms the following:
1-CH-TI=1139 < 195°F 1-CH-PI=1138 < 130 psig 1-CC-TI=151 < 140°F Step / Action Notes / Comments 12 Align Excess Letdown to VCT.
Procedure Step 5.1.13 CUE:
WHEN candidate identifies 1-DG-LI-101, AND that they are waiting for a 10% level change THEN tell the candidate to assume the required level change has occurred.
Critical Step*
SAT [ ] UNSAT [ ]
Standards Candidate places selector switch for 1-CH-HCV-1389, Excess Letdown Flow Divert, in the VCT position
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 11 of 12 NAPS 2012 NRC Exam - RETAKE SIM JPM d - DRAFT Step / Action Notes / Comments 13 Maintain Pressurizer Level.
Procedure Step 5.1.14 CUE:
Tell the candidate that another operator will continue with the procedure.
SAT [ ] UNSAT [ ]
Standards Candidate acknowledges.
END OF EVALUATION Stop Time:
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 12 of 12 NAPS 2012 NRC Exam - RETAKE SIM JPM d - DRAFT Simulator Booth Instructions 1
Recall 100% IC 2
If desired Pre-load closing loop drain valve breaker 3
When directed by operator to close 1-EP-CB-26B Bkr #22 (JPM Element 5) then acknowledge direction, close bkr (using pre-load or Page RC1 of Extremeview), and report back action complete.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program INITIAL CONDITIONS Unit 1 is at 100% power and stable.
There are no limiting actions and there is no equipment out-of-service.
INITIATING CUE Maintain stable plant conditions.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 2 of 11 NAPS 2012 NRC Exam - RETAKE JPM e SIM - DRAFT TASK Respond to Power Range N-44 malfunction.
TASK STANDARDS Candidate responds to N-44 malfunction IAW 1-AP-4.3 and actuates a manual reactor trip based on a full load rejection.
K/A
REFERENCE:
015A2.02, Ability to (a) predict the impacts of the following malfunctions or operations on the NIS; and (b) based on those predictions, use procedures to correct, control, or mitigate the consequences of those malfunctions or operations: Faulty or erratic operation of detectors or compensating components.
ALTERNATE PATH:
N/A TASK COMPLETION TIMES Validation Time =
15 minutes Start Time = __________
Actual Time = ________ minutes Stop Time = __________
PERFORMANCE EVALUATION Rating
[ ] SATISFACTORY [ ] UNSATISFACTORY Candidate (Print)
Evaluator (Print)
Evaluator's Signature / Date EVALUATOR'S COMMENTS
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 3 of 11 NAPS 2012 NRC Exam - RETAKE JPM e SIM - DRAFT READ THE APPLICABLE INSTRUCTIONS TO THE CANDIDATE Instructions for Simulator JPMs I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
Instructions for In-Plant JPMs I will explain the initial conditions, and state the task to be performed. All steps, including any required communications, shall be simulated for this JPM. Under no circumstances are you to operate any plant equipment. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS Unit 1 is at 100% power and stable.
There are no limiting actions and there is no equipment out-of-service.
INITIATING CUE Maintain stable plant conditions.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 4 of 11 NAPS 2012 NRC Exam - RETAKE JPM e SIM - DRAFT EVALUATION METHOD Demonstration if conducted in the simulator or in a laboratory (use DEMONSTRATION cues)
Verbal-visual if conducted in the station or on a dead simulator (use VERBAL-VISUAL cues)
TOOLS AND EQUIPMENT Copy of 1-AP-4.3
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 5 of 11 NAPS 2012 NRC Exam - RETAKE JPM e SIM - DRAFT Start Time:
Evaluators Note: Steps that appear in brackets [ ] are Immediate Operator Action (IOA) steps and are expected to be performed from memory.
Step / Action Notes / Comments 1
Stop power increase (YES).
Procedure Step
[1]
SAT [ ] UNSAT [ ]
Standards Candidate verbalizes that power is not increasing Step / Action Notes / Comments 2
Verify N-44 NOT failed - NO.
(RNO Step)
Note: Critical per NUREG-1021 since a failure to implement this Abnormal Procedure correctly will result in an unnecessary actuation of the RPS and ESF systems.
Procedure Step
[2]
Cue:
Once candidate states they have completed the IOAs provide them a copy of 1-AP-4.3 and tell them that the Unit Supervisor requests you perform 1-AP-4.3 Critical Step*
SAT [ ] UNSAT [ ]
Note: Placing Rods in manual is the ONLY critical portion of this element since Main Feed Reg Bypass Valves are already in Manual (normal plant configuration at 100% power).
Standards Candidate places Rod Control in MANUAL and verifies Main Feed Reg Bypass Valves in Manual.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 6 of 11 NAPS 2012 NRC Exam - RETAKE JPM e SIM - DRAFT Step / Action Notes / Comments 3
Verify 3 Power Range Instruments Operable (YES).
Procedure Step 3
SAT [ ] UNSAT [ ]
Standards Candidate observes that N-41, N-42, and N-43 are indicating properly.
Step / Action Notes / Comments 4
Verify Unit in Mode 1 or 2 (YES).
Procedure Step 4
SAT [ ] UNSAT [ ]
Standards Candidate confirms that power is
~100% (by definition Mode 1)
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 7 of 11 NAPS 2012 NRC Exam - RETAKE JPM e SIM - DRAFT Step / Action Notes / Comments 5
Check Reactor Trip System Interlocks.
Procedure Step 5
SAT [ ] UNSAT [ ]
Standards Candidate verifies the following annunciators NOT LIT:
Panel "P" G-2 Panel "P" D-2 Panel "P" F-1 Step / Action Notes / Comments 6
Check Tavg within 1.5°F of Tref.
Procedure Step 6
Cue: IF Tavg & Tref are NOT within 1.5°F, THEN tell them that Operations Management is still discussing the method to be used to restore Tavg &
Tref and the Unit Supervisor directs you to flag the step and continue with 1-AP-4.3.
SAT [ ] UNSAT [ ]
Standards Candidate either
- 1) confirms Tavg & Tref are within 1.5°F OR
- 2) acknowledges cue
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 8 of 11 NAPS 2012 NRC Exam - RETAKE JPM e SIM - DRAFT Step / Action Notes / Comments 7
Maintain RILs and AFD limits.
Procedure Step 7
SAT [ ] UNSAT [ ]
Standards Candidate verifies the following annunciators NOT LIT:
Panel "A" H-1, H-2, H-3, & H-4 Panel "A" H-7 Step / Action Notes / Comments 8
Remove failed channel (N-44) from service.
Procedure Step 8.a & 8.b SAT [ ] UNSAT [ ]
Standards Candidate performs the following operations:
a) on comparator and rate drawer select N-44 b) on Misc Cntrl & ind drawer select N-44 for:
Rod Stop Bypass Upper Section Lower Section
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 9 of 11 NAPS 2012 NRC Exam - RETAKE JPM e SIM - DRAFT Step / Action Notes / Comments 9
Remove failed channel (N-44) from service (cont'd).
Procedure Step 8.c CUE: When asked, as the SRO tell the candidate it is NOT desired to remove the Instrument power fuses.
Critical Step*
SAT [ ] UNSAT [ ]
Standards Candidate removes control power fuses for N-44 Evaluators Note: Once candidate has pulled control power fuses and comes back around the Benchboard, the Booth Operator will trigger the full load rejection.
Step / Action Notes / Comments 10 ALTERNATE PATH STEP Transition to 1-E-0 Procedure Step AR-D-B1 SAT [ ] UNSAT [ ]
Standards Candidate suspends performance of 1-AP-4.3 and enters 1-E-0 based on annunciator response for valid reactor trip signal.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 10 of 11 NAPS 2012 NRC Exam - RETAKE JPM e SIM - DRAFT Step / Action Notes / Comments 11 Manually trip Reactor.
Procedure Step 1-E-0, Step [1 - 4]
CUE:
WHEN candidate states that they have completed the IOAs of 1-E-0, THEN acknowledge 1-E-0 IOAs complete and tell them this completes your task.
Critical Step SAT [ ] UNSAT [ ]
Note: Only those items that are BOLDED are critical to this element.
Standards Candidate performs the following:
- 1) Manually trip reactor
- 2) Manually trip turbine AND Reset Reheaters
- 3) Verify power to Emergency Busses
- 4) Check SI END OF EVALUATION Stop Time:
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 11 of 11 NAPS 2012 NRC Exam - RETAKE JPM e SIM - DRAFT Simulator Booth Instructions 1
Recall 100% IC 2
Pre-load N-44 upper detector fails high (trigger 1) 3 Pre-load Rods Insert at max speed in auto (trigger 1 with 3 second time delay)
Note:
item 3 simulates an industry event where the large rapid power mismatch caused the power mismatch controller to go into saturation; after the drawer was removed from service operators attempted to return rod control to auto (as expected) but when doing so rods began to step (due to the controller saturation) and rods were returned to manual and had to be maintained in manual control until troubleshooting discovered and corrected the problem.
4 Pre-load:
ATWS reactor fails to trip automatically and switch override 1-RC-PCV-1455C CLOSE 5
Pre-load override valve position limiter LOWER ON (trigger 2)
Actuate trigger 2 after element 9 when candidate comes back around the benchboard
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program INITIAL CONDITIONS Unit startup from mode 5 to mode 4 is in progress The Reactor Coolant System has been filled and vented per 1-OP-5.1.
Reactor coolant pump "C" is in operation Hot-leg and cold-leg loop "A" stop valves are open Conditions have been established for starting the "A" reactor coolant pump Reactor Coolant System pressure is 350 psig Reactor Coolant System temperature is 190°F "A" station service bus is not being supplied from reserve station service Pressurizer bubble is being used for Reactor Coolant System pressure control Reactor coolant filters and a mixed-bed ion exchanger are in service 1-OP-5.2 has been completed through step 5.1.8 INITIATING CUE You are requested to start the "A" reactor coolant pump in accordance with 1-OP-5.2.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 2 of 11 NAPS 2012 NRC Exam - RETAKE JPM f SIM - DRAFT TASK Start a Reactor Coolant Pump.
TASK STANDARDS "A" RCP was started, then both RCPs are tripped when spurious closure of 1-RC-MOV-1380 causes loss of #1 Seal D/P.
K/A
REFERENCE:
ALTERNATE-PATH YES.
TASK COMPLETION TIMES Validation Time =
15 minutes Start Time = _______
Actual Time = _______ minutes Stop Time = _______
PERFORMANCE EVALUATION Rating
[ ] SATISFACTORY [ ] UNSATISFACTORY Candidate (Print)
Evaluator (Print)
Evaluator's Signature /
Date EVALUATOR'S COMMENTS
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 3 of 11 NAPS 2012 NRC Exam - RETAKE JPM f SIM - DRAFT READ THE APPLICABLE INSTRUCTIONS TO THE CANDIDATE Instructions for Simulator JPMs I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
Instructions for In-Plant JPMs I will explain the initial conditions, and state the task to be performed. All steps, including any required communications, shall be simulated for this JPM. Under no circumstances are you to operate any plant equipment. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS Unit startup from mode 5 to mode 4 is in progress The Reactor Coolant System has been filled and vented per 1-OP-5.1 Reactor coolant pump "C" is in operation Hot-leg and cold-leg loop "A" stop valves are open Conditions have been established for starting the "A" reactor coolant pump Reactor Coolant System pressure is 350 psig Reactor Coolant System temperature is 190°F "A" station service bus is not being supplied from reserve station service Pressurizer bubble is being used for Reactor Coolant System pressure control Reactor coolant filters and a mixed-bed ion exchanger are in service 1-OP-5.2 has been completed through step 5.1.8 INITIATING CUE You are requested to start the "A" reactor coolant pump in accordance with 1-OP-5.2.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 4 of 11 NAPS 2012 NRC Exam - RETAKE JPM f SIM - DRAFT EVALUATION METHOD Demonstration if conducted in the simulator or in the electrical laboratory (use DEMONSTRATION cues)
Verbal-visual if conducted in the station or on a dead simulator (use VERBAL-VISUAL cues)
TOOLS AND EQUIPMENT Copy of 1-OP-5.2 signed off through step 5.1.8
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 5 of 11 NAPS 2012 NRC Exam - RETAKE JPM f SIM - DRAFT PERFORMANCE STEPS START TIME 1
Start "A" Reactor Coolant Pump Oil Lift Pump Procedure Step 5.1.9 CRITICAL STEP SAT [ ] UNSAT [ ]
Standards Candidate momentarily places the control switch for "A" Reactor Coolant Pump Oil Lift Pump to START Notes/Comments: Applicant may review precautions and limitations prior to beginning task.
2 Verify that the "A" reactor coolant pump oil pressure start permissive indicating light is lit.
Procedure Step 5.1.10 SAT [ ] UNSAT [ ]
Standards Oil pressure start permissive white indicating light is verified lit Notes/Comments:
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 6 of 11 NAPS 2012 NRC Exam - RETAKE JPM f SIM - DRAFT 3
Verify that the "A" reactor coolant pump annunciators are not lit.
Procedure Step 5.1.11 SAT [ ] UNSAT [ ]
Standards The following RCP annunciators are verified NOT lit:
C-C1, C-E1, C-F1, C-G1, C-H1 Notes/Comments: Step 5.1.12 is N/A 4
Ensure the Chemical and Volume Control System is operating Procedure Step 5.1.13 SAT [ ] UNSAT [ ]
Standards CVCS parameters are verified within specifications:
Seal injection flow rate is between 6 gpm and 10 gpm Seal injection (VCT) temperature is between 60°F and 150°F VCT pressure is between 15 psig and 65 psig Notes/Comments
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 7 of 11 NAPS 2012 NRC Exam - RETAKE JPM f SIM - DRAFT 5
Verify the Component Cooling Water System is operating Procedure Step 5.1.14a SAT [ ] UNSAT [ ]
Standards CCW parameters are verified within specifications:
Upper oil cooler flow is between 140 and 180 gpm Stator cooler flows are between 100 and 140 gpm Lower oil cooler flows is between 4 and 10 gpm Thermal Barrier flow is between 40 and 60 gpm CC HX outlet temperature is 105°F or less Notes/Comments: Step 5.1.14b is N/A 6
Ensure that RCS pressure is above the required value Procedure Step 5.1.15b SAT [ ] UNSAT [ ]
Standards RCS pressure is verified above 280 psig Notes/Comments: Step 5.1.15a is N/A based on Initial Conditions of the JPM
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 8 of 11 NAPS 2012 NRC Exam - RETAKE JPM f SIM - DRAFT 7
Ensure no pressurizer spray flow exists during the RCP start.
Procedure Step 5.1.16 SAT [ ] UNSAT [ ]
Standards All spray valves are closed Notes/Comments 8
Verify that the bearing lift pump has operated for at least two minutes.
Procedure Step 5.1.17 SAT [ ] UNSAT [ ]
Standards RCP "A" bearing lift pump is verified running at least two minutes Notes/Comments: Step 5.1.18 is N/A based on plant conditions.
9 Ensure that all personnel are clear of the reactor coolant pump to be started.
Procedure Step 5.1.19 SAT [ ] UNSAT [ ]
Standards RCP start is announced on the plant paging system Notes/Comments
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 9 of 11 NAPS 2012 NRC Exam - RETAKE JPM f SIM - DRAFT 10 Start the "A" Reactor Coolant Pump, 1-RC-P-1A Procedure Step 5.1.20 CRITICAL STEP SAT [ ] UNSAT [ ]
Standards Control switch for 1-RC-P-1A is momentarily placed in START Notes/Comments 11 Verify that reactor coolant flow is increasing.
Procedure Step 5.1.21 SAT [ ] UNSAT [ ]
Standards Flow in "A" Reactor Coolant Loop is verified increasing by observing the following:
1-RC-FI-1414 1-RC-FI-1415 1-RC-FI-1416 Notes/Comments 12 Verify that annunciator 1A-E5, RCP 1A VIBRATION ALERT/DANGER, is not lit.
Procedure Step 5.1.22 SAT [ ] UNSAT [ ]
Standards Annunciator is verified NOT lit Notes/Comments:
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 10 of 11 NAPS 2012 NRC Exam - RETAKE JPM f SIM - DRAFT 13 Respond to decreasing #1 Seal D/P ALTERNATE PATH STEP Procedure Step 1C-G5 SAT [ ] UNSAT [ ]
Standards Candidate observes seal D/P indications and determines that both running RCPs are affected.
Notes/Comments 14 Stop RCPs Procedure Step See Note CRITICAL STEP SAT [ ] UNSAT [ ]
Standards Control switches for 1-RC-P-1A & 1-RC-P-1C are momentarily placed in STOP (although not required it is acceptable for the candidate to place the control switches in P-T-L)
Notes/Comments This action may be performed from memory.
>>>>> END OF EVALUATION <<<<<
STOP TIME
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 11 of 11 NAPS 2012 NRC Exam - RETAKE JPM f SIM - DRAFT SIMULATOR SETUP CHECKLIST Recall the IC for mode 5, 350 psig, 180°F, bubble in the pressurizer Ensure initial conditions match IC Sheet Pre-load switch override 1-CH-MOV-1380 Close Pushbutton ON (Trigger 1)
Actuate Trigger 1 shortly after the A RCP is started.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program INITIAL CONDITIONS Unit is at 100% power and stable.
INITIATING CUE You are requested to raise PRT to between 10-11psig using 1-OP-5.7, Sub-section 5.4.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 2 of 11 NAPS 2012 NRC Exam - RETAKE JPM g SIM - DRAFT TASK Raise PRT pressure by adding nitrogen.
TASK STANDARDS PRT pressure is raised to between 10-11psig IAW 1-OP-5.7, Section 5.4.
K/A
REFERENCE:
007A1.02, Ability to predict and/or monitor changes in parameters (to prevent exceeding design limits) associated with operating the PRTS controls including: Maintaining Quench Tank pressure.
ALTERNATE PATH:
N/A TASK COMPLETION TIMES Validation Time =
10 minutes Start Time = __________
Actual Time = ________ minutes Stop Time = __________
PERFORMANCE EVALUATION Rating
[ ] SATISFACTORY [ ] UNSATISFACTORY Candidate (Print)
Evaluator (Print)
Evaluator's Signature / Date EVALUATOR'S COMMENTS
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 3 of 11 NAPS 2012 NRC Exam - RETAKE JPM g SIM - DRAFT READ THE APPLICABLE INSTRUCTIONS TO THE CANDIDATE Instructions for Simulator JPMs I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
Instructions for In-Plant JPMs I will explain the initial conditions, and state the task to be performed. All steps, including any required communications, shall be simulated for this JPM. Under no circumstances are you to operate any plant equipment. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS Unit is at 100% power and stable.
INITIATING CUE You are requested to raise PRT to between 10-11psig using 1-OP-5.7, Sub-section 5.4.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 4 of 11 NAPS 2012 NRC Exam - RETAKE JPM g SIM - DRAFT EVALUATION METHOD Demonstration if conducted in the simulator or in a laboratory (use DEMONSTRATION cues)
Verbal-visual if conducted in the station or on a dead simulator (use VERBAL-VISUAL cues)
TOOLS AND EQUIPMENT Copy of 1-OP-5.7
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 5 of 11 NAPS 2012 NRC Exam - RETAKE JPM g SIM - DRAFT Start Time:
Step / Action Notes / Comments 1
Verify ICs and review P&Ls.
Procedure Step 5.4.1 & 5.4.2 SAT [ ] UNSAT [ ]
Standards Candidate reviews Section 3.0 &
4.0 Step / Action Notes / Comments 2
Verify nitrogen is aligned to the supply header.
Procedure Step 5.4.3 SAT [ ] UNSAT [ ]
Standards Candidate confirms nitrogen is aligned.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 6 of 11 NAPS 2012 NRC Exam - RETAKE JPM g SIM - DRAFT Step / Action Notes / Comments 3
Reduce demand on 1-SI-HIC-100 to 0%.
Procedure Step 5.4.4 SAT [ ] UNSAT [ ]
Standards Candidate turns potentiometer for 1-SI-HIC-100 counter-clockwise to obtain 0% demand.
Step / Action Notes / Comments 4
Open 1-SI-TV-100.
Procedure Step 5.4.5 Critical Step SAT [ ] UNSAT [ ]
Standards Candidate opens 1-SI-TV-100 by momentarily depressing 1-SI-TV-100A AND B OPEN pushbuttons.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 7 of 11 NAPS 2012 NRC Exam - RETAKE JPM g SIM - DRAFT Step / Action Notes / Comments 5
Open 1-RC-HCV-1550.
Procedure Step 5.4.6 Critical Step SAT [ ] UNSAT [ ]
Standards Candidate opens 1-RC-HCV-1550 by placing control switch to OPEN.
Step / Action Notes / Comments 6
Open 1-SI-HCV-1898.
Procedure Step 5.4.7 Critical Step SAT [ ] UNSAT [ ]
Standards Candidate opens 1-SI-HCV-1898 by momentarily depressing the OPEN pushbuttons.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 8 of 11 NAPS 2012 NRC Exam - RETAKE JPM g SIM - DRAFT Step / Action Notes / Comments 7
Secure raising PRT pressure.
Procedure Step 5.4.8 a & b Critical Step*
SAT [ ] UNSAT [ ]
NOTE: Since valves are in series it is only critical to close ONE of the valves.
Standards WHEN PRT pressure is 10-11 psig, THEN candidate secures lineup by performing the following:
- 1) close 1-SI-HCV-1898 by momentarily depressing the CLOSE pushbutton AND
- 2) close 1-RC-HCV-1550 by placing the control switch in CLOSE.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 9 of 11 NAPS 2012 NRC Exam - RETAKE JPM g SIM - DRAFT Step / Action Notes / Comments 8
Secure nitrogen lineup.
Procedure Step 5.4.8 c SAT [ ] UNSAT [ ]
NOTE: Sub-step 5.4.8.d is N/A (based on the Initial Conditions of the JPM).
Standards Candidate secures Nitrogen lineup by performing the following:
- 1) close 1-SI-TV-100 by momentarily depressing the CLOSE pushbutton for 1-SI-TV-100A OR B.
AND
- 2) Raises output of 1-SI-HIC-100 by turning the potentiometer clockwise to obtain 100% demand.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 10 of 11 NAPS 2012 NRC Exam - RETAKE JPM g SIM - DRAFT Step / Action Notes / Comments 9
Report task completion to Unit Supervisor.
Procedure Step N/A Cue:
Acknowledge task completion.
SAT [ ] UNSAT [ ]
Standards Candidate reports that PRT pressure has been raised IAW 1-OP-5.7 END OF EVALUATION Stop Time:
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 11 of 11 NAPS 2012 NRC Exam - RETAKE JPM g SIM - DRAFT Simulator Booth Instructions 1
Recall 100% IC.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program INITIAL CONDITIONS Fire has occurred in the Control Room.
INITIATING CUE The WCCS directs you to perform 0-FCA-1, Attachment 12, steps 1-3.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 2 of 8 NAPS 2012 NRC Exam - RETAKE IP JPM i - DRAFT TASK Transfer Aux Monitoring Panel and Remote Monitoring Excore Neutron Flux Detectors to backup power.
TASK STANDARDS The Aux Monitoring Panel and Remote Monitoring Excore Neutron Flux Detectors for BOTH units are transferred to backup IAW 0-FCA-1, Attachment 12, Steps 1-3.
K/A
REFERENCE:
067AA2.16, Ability to determine and interpret the following as they apply to the Plant Fire on Site:
Vital equipment and control systems to be maintained and operated during a fire (RO 3.3 / SR 4.0)
ALTERNATE PATH:
NO TASK COMPLETION TIMES Validation Time =
10 minutes Start Time = __________
Actual Time = ________ minutes Stop Time = __________
PERFORMANCE EVALUATION Rating
[ ] SATISFACTORY [ ] UNSATISFACTORY Candidate (Print)
Evaluator (Print)
Evaluator's Signature / Date EVALUATOR'S COMMENTS
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 3 of 8 NAPS 2012 NRC Exam - RETAKE IP JPM i - DRAFT READ THE APPLICABLE INSTRUCTIONS TO THE CANDIDATE Instructions for Simulator JPMs I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
Instructions for In-Plant JPMs I will explain the initial conditions, and state the task to be performed. All steps, including any required communications, shall be simulated for this JPM. Under no circumstances are you to operate any plant equipment. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS Fire has occurred in the Control Room.
INITIATING CUE The WCCS directs you to perform 0-FCA-1, Attachment 12, steps 1-3.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 4 of 8 NAPS 2012 NRC Exam - RETAKE IP JPM i - DRAFT EVALUATION METHOD Demonstration if conducted in the simulator or in a laboratory (use DEMONSTRATION cues)
Verbal-visual if conducted in the station or on a dead simulator (use VERBAL-VISUAL cues)
TOOLS AND EQUIPMENT Copy of 0-FCA-1, Att.12, to be provided to applicant.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 5 of 8 NAPS 2012 NRC Exam - RETAKE IP JPM i - DRAFT Start Time:
Step / Action Notes / Comments 1
Obtain keys.
Procedure Step Att. 12, step 1 See Note Below Cue:
You have the keys you described.
SAT [ ] UNSAT [ ]
Note: Provide cue once candidate describes the location (how) they would get the required keys.
Standards Candidate describes how to obtain the following keys:
10, 11, 12, OR 13 AND 73 AND 74 Step / Action Notes / Comments 2
Place disconnect switch on 2-EB-CB-001 to OFF.
Procedure Step Att. 12, step 2a Cue:
The disconnect switch is positioned as you described it.
Critical Step SAT [ ] UNSAT [ ]
Note: Administrative lock key is required to operate this switch.
Standards 2-EB-CB-001 disconnect switch is placed in OFF.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 6 of 8 NAPS 2012 NRC Exam - RETAKE IP JPM i - DRAFT Step / Action Notes / Comments 3
Verify 2-VB-INV-01 supplying load Procedure Step Att. 12, step 2b Cue:
The indication you described is as you see it now.
SAT [ ] UNSAT [ ]
Standards 2-VB-INV-01 Inverter supplying load light is verified LIT.
Step / Action Notes / Comments 4
Place transfer switch in backup.
Procedure Step Att. 12, step 2c Cue:
The switch appears as you described it.
Critical Step SAT [ ] UNSAT [ ]
Note: Key 73 is required to operate this switch.
Standards 1-XFR-SW-202 on panel 2-EI-CB-202 is positioned to backup.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 7 of 8 NAPS 2012 NRC Exam - RETAKE IP JPM i - DRAFT Step / Action Notes / Comments 5
Place disconnect switch on 1-EB-CB-001 to OFF.
Procedure Step Att. 12, step 3a Cue:
The disconnect switch is positioned as you described it.
Critical Step SAT [ ] UNSAT [ ]
Note: Administrative lock key is required to operate this switch.
Standards 1-EB-CB-001 disconnect switch is placed in OFF.
Step / Action Notes / Comments 6
Verify 1-VB-INV-01 supplying load Procedure Step Att. 12, step 3b Cue:
The indication you described is as you see it now.
SAT [ ] UNSAT [ ]
Standards 1-VB-INV-01 Inverter supplying load light is verified LIT.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 8 of 8 NAPS 2012 NRC Exam - RETAKE IP JPM i - DRAFT Step / Action Notes / Comments 7
Place transfer switch in backup.
Procedure Step Att. 12, step 2c Cue:
The switch appears as you described it.
Critical Step SAT [ ] UNSAT [ ]
Note: Key 74 is required to operate this switch.
Standards 1-XFR-SW-202 on panel 2-EI-CB-202 is positioned to backup.
Step / Action Notes / Comments 8
Report status to WCCs.
Procedure Step N/A Cue:
Acknowledge completion of 0-FCA-0.1, Attachment 12, Steps 1-3.
SAT [ ] UNSAT [ ]
Standards WCCS is notified that 0-FCA-0.1, Attachment 12, Steps 1-3 are complete.
END OF EVALUATION Stop Time:
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program INITIAL CONDITIONS The OATC attempted to trip UNIT 2 and the reactor DID NOT trip.
INITIATING CUE You have been directed to trip UNIT 2 locally IAW Attachment 4, Remote Reactor Trip, of 2-FR-S.1, Response to Nuclear Power Generation/ATWS.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 2 of 10 NAPS 2012 NRC Exam - RETAKE IP JPM j - Rev_1 TASK Trip the reactor by opening the reactor trip breakers or the rod-drive motor generator breakers locally (2-FR-S.1).
TASK STANDARDS The reactor is tripped by locally tripping MG set supply breakers in 307 Switchgear.
K/A
REFERENCE:
029-EA1.12, Ability to operate and monitor the following as they apply to a ATWS: M/G set power supply and reactor trip breakers (RO 4.1 / SRO 4.0)
(Note: This task is categorized as Safety Function 1 per ES-401-2)
ALTERNATE PATH:
YES TASK COMPLETION TIMES Validation Time =
10 minutes Start Time = __________
Actual Time = ________ minutes Stop Time = __________
PERFORMANCE EVALUATION Rating
[ ] SATISFACTORY [ ] UNSATISFACTORY Candidate (Print)
Evaluator (Print)
Evaluator's Signature / Date EVALUATOR'S COMMENTS
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 3 of 10 NAPS 2012 NRC Exam - RETAKE IP JPM j - Rev_1 READ THE APPLICABLE INSTRUCTIONS TO THE CANDIDATE Instructions for Simulator JPMs I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
Instructions for In-Plant JPMs I will explain the initial conditions, and state the task to be performed. All steps, including any required communications, shall be simulated for this JPM. Under no circumstances are you to operate any plant equipment. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS The OATC attempted to trip UNIT 2 and the reactor DID NOT trip.
INITIATING CUE You have been directed to trip UNIT 2 locally IAW Attachment 4, Remote Reactor Trip, of 2-FR-S.1, Response to Nuclear Power Generation/ATWS.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 4 of 10 NAPS 2012 NRC Exam - RETAKE IP JPM j - Rev_1 EVALUATION METHOD Demonstration if conducted in the simulator or in a laboratory (use DEMONSTRATION cues)
Verbal-visual if conducted in the station or on a dead simulator (use VERBAL-VISUAL cues)
TOOLS AND EQUIPMENT Copy of 2-FR-S.1, Att.4, to be provided to applicant.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 5 of 10 NAPS 2012 NRC Exam - RETAKE IP JPM j - Rev_1 Start Time:
Evaluators Note: The candidate may perform actions 1-4, checking for a response after each individual action is performed, or may elect to perform all of the actions (1-4) then check the responses afterwards; either method is acceptable.
Step / Action Notes / Comments 1
Locally trip the reactor from the rod drive room.
Procedure Step Att. 4, step 1a Cue:
The breaker indication is how you see it now.
SAT [ ] UNSAT [ ]
Note: Bypass breakers are normally racked in and open. Pushbuttons on the bypass breakers DO NOT have to be depressed PROVIDED they are verified OPEN (green OPEN mechanical flag showing).
Standards TRIP pushbuttons for the Reactor Trip and Reactor Trip Bypass breakers are depressed.
Step / Action Notes / Comments 2
Put both M-G Set Generator Output Breakers control switches to TRIP.
Procedure Step Att. 4, step 1a (cont'd)
Cue:
The breaker indication is how you see it now.
SAT [ ] UNSAT [ ]
Standards Control switches for both motor generator sets are placed in TRIP.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 6 of 10 NAPS 2012 NRC Exam - RETAKE IP JPM j - Rev_1 Step / Action Notes / Comments 3
Press the TRIP buttons for both M-G Set Generator Output Breakers.
Procedure Step Att. 4, step 1a (cont'd)
Cue:
The breaker indication is how you see it now.
SAT [ ] UNSAT [ ]
Standards Depresses the TRIP push-button for each motor generator output breakers.
Step / Action Notes / Comments 4
Put both M-G Set Motor Supply Breakers control switches to TRIP.
Procedure Step Att. 4, step 1a (cont'd)
Cue:
The breaker indication is how you see it now.
SAT [ ] UNSAT [ ]
Standards Control switches for both motor generator set supply breakers are placed in TRIP.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 7 of 10 NAPS 2012 NRC Exam - RETAKE IP JPM j - Rev_1 Step / Action Notes / Comments 5
Verify at least one of the following conditions satisfied:
All reactor trip and bypass breakers are open - NO Both M-G set output breakers are open -NO Both M-G set supply breakers are open - NO Procedure Step Att. 4, step 1b Cue:
The breaker indication is how you see it now (cue may not be necessary IF information was provided previously as the individual actions were performed).
SAT [ ] UNSAT [ ]
NOTE: ALTERNATE PATH STEP Standards Candidate proceeds to Step 3 based on the Response Not Obtained.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 8 of 10 NAPS 2012 NRC Exam - RETAKE IP JPM j - Rev_1 Evaluators Note: The next 2 actions (elements 6 & 7) of this JPM are bulleted items in the procedure and thus may be performed in any order.
Step / Action Notes / Comments 6
Locally trip the reactor from the 307 Switchgear room.
Procedure Step Att. 4, step 3a (1st bullet)
Cue:
SEE NOTE BELOW When the candidate describes the expected response for the action (breaker changes state as indicated by the green OPEN mechanical flag),
inform the candidate that the breaker shows a green OPEN flag.
Critical Step SAT [ ] UNSAT [ ]
NOTE: This breaker has two TRIP pushbuttons. The right pushbutton ONLY works with the breaker in test. IF the candidate pushes ONLY the RIGHT pushbutton they should be cued that the breaker appears as they see it now (i.e. no change of state occurs so the breaker remains closed)
Standards LEFT Mechanical TRIP pushbutton for the M-G set motor supply breaker is momentarily depressed:
2-EP-BKR-24A1-3, 2-ED-MG-1A Rod Drive M-G Set Motor Supply Breaker.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 9 of 10 NAPS 2012 NRC Exam - RETAKE IP JPM j - Rev_1 Step / Action Notes / Comments 7
Locally trip the reactor from the 307 Switchgear room.
Procedure Step Att. 4, step 3a (2nd bullet)
Cue:
SEE NOTE BELOW When the candidate describes the expected response for the action (breaker changes state as indicated by the green OPEN mechanical flag),
inform the candidate that the breaker shows a green OPEN flag.
Critical Step SAT [ ] UNSAT [ ]
NOTE: This breaker has two TRIP pushbuttons. The right pushbutton ONLY works with the breaker in test. IF the candidate pushes ONLY the RIGHT pushbutton they should be cued that the breaker appears as they see it now (i.e. no change of state occurs so the breaker remains closed)
Standards LEFT Mechanical TRIP pushbutton for the M-G set motor supply breaker is momentarily depressed:
2-EP-BKR-24C2-12, 2-ED-MG-1B Rod Drive M-G Set Motor Supply Breaker.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 10 of 10 NAPS 2012 NRC Exam - RETAKE IP JPM j - Rev_1 Step / Action Notes / Comments 8
Notify the control room operator of status of the rod power supply breakers.
Procedure Step Att. 4, step 3b CUE: Acknowledge report and inform candidate that their task is complete.
SAT [ ] UNSAT [ ]
Standards Candidate reports status of Rod Drive MG Set power supply breakers to the Control Room.
END OF EVALUATION Stop Time:
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program INITIAL CONDITIONS An unisolable leak has been identified on the Unit 2 CC supply header.
INITIATING CUE You have been directed by the WCCS to split CC IAW 1-AP-15, Attachment 5.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 2 of 8 NAPS 2012 NRC Exam - RETAKE JPM k IP - DRAFT TASK Align CC system for split operations (1-AP-15).
TASK STANDARDS The CC system cross-connects valves are closed and common loads are aligned to Unit 1.
K/A
REFERENCE:
026AA2.03, Ability to determine and interpret the following as they apply to the Loss of Component Cooling Water: The valve lineups necessary to restart the CCWS while bypassing the portion of the system causing the abnormal condition.
(Note: CC is a shared system)
ALTERNATE PATH:
NO TASK COMPLETION TIMES Validation Time =
10 minutes Start Time = __________
Actual Time = ________ minutes Stop Time = __________
PERFORMANCE EVALUATION Rating
[ ] SATISFACTORY [ ] UNSATISFACTORY Candidate (Print)
Evaluator (Print)
Evaluator's Signature / Date EVALUATOR'S COMMENTS
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 3 of 8 NAPS 2012 NRC Exam - RETAKE JPM k IP - DRAFT READ THE APPLICABLE INSTRUCTIONS TO THE CANDIDATE Instructions for Simulator JPMs I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
Instructions for In-Plant JPMs I will explain the initial conditions, and state the task to be performed. All steps, including any required communications, shall be simulated for this JPM. Under no circumstances are you to operate any plant equipment. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.
INITIAL CONDITIONS An unisolable leak has been identified on the Unit 2 CC supply header.
INITIATING CUE You have been directed by the WCCS to split CC IAW 1-AP-15, Attachment 5.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 4 of 8 NAPS 2012 NRC Exam - RETAKE JPM k IP - DRAFT EVALUATION METHOD Demonstration if conducted in the simulator or in a laboratory (use DEMONSTRATION cues)
Verbal-visual if conducted in the station or on a dead simulator (use VERBAL-VISUAL cues)
TOOLS AND EQUIPMENT Copy of 1-AP-15, Attachment 5, to be provided to applicant.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 5 of 8 NAPS 2012 NRC Exam - RETAKE JPM k IP - DRAFT Start Time:
Step / Action Notes / Comments 1
Close CC pump suction header cross-connect.
Procedure Step Att. 5, step 1 Cue:
The valve is positioned as you described it.
Critical Step SAT [ ] UNSAT [ ]
Standards Candidate closes 1-CC-40 by turning the valve handwheel in the clockwise direction.
Step / Action Notes / Comments 2
Close CC pump discharge header cross-connect.
Procedure Step Att. 5, step 2 Cue:
The valve is positioned as you described it.
Critical Step SAT [ ] UNSAT [ ]
Standards Candidate closes 1-CC-49 by turning the valve handwheel in the clockwise direction.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 6 of 8 NAPS 2012 NRC Exam - RETAKE JPM k IP - DRAFT Step / Action Notes / Comments 3
Close CC heat exchanger cross-connect.
Procedure Step Att. 5, step 3 Cue:
The valve is positioned as you described it.
Critical Step SAT [ ] UNSAT [ ]
Standards Candidate closes 1-CC-57 by turning the valve handwheel in the clockwise direction.
Step / Action Notes / Comments 4
Put both M-G Set Motor Supply Breakers control switches to TRIP.
Procedure Step Att. 5, step 4.a.1 Cue:
The valve is positioned as you described it.
SAT [ ] UNSAT [ ]
Standards Control switches for both motor generator set supply breakers are placed in TRIP.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 7 of 8 NAPS 2012 NRC Exam - RETAKE JPM k IP - DRAFT Step / Action Notes / Comments 5
Put both M-G Set Motor Supply Breakers control switches to TRIP.
Procedure Step Att. 5, step 4.a.2 Cue:
The valve is positioned as you described it.
SAT [ ] UNSAT [ ]
Standards Control switches for both motor generator set supply breakers are placed in TRIP.
Step / Action Notes / Comments 6
Put both M-G Set Motor Supply Breakers control switches to TRIP.
Procedure Step Att. 5, step 4.a.3 Cue:
The valve is positioned as you described it.
SAT [ ] UNSAT [ ]
Standards Control switches for both motor generator set supply breakers are placed in TRIP.
North Anna Power Station Job Performance Measure (Evaluation) - Operator Program Page 8 of 8 NAPS 2012 NRC Exam - RETAKE JPM k IP - DRAFT Step / Action Notes / Comments 7
Put both M-G Set Motor Supply Breakers control switches to TRIP.
Procedure Step Att. 5, step 4.a.4 Cue:
The valve is positioned as you described it.
SAT [ ] UNSAT [ ]
Standards Control switches for both motor generator set supply breakers are placed in TRIP.
Step / Action Notes / Comments 8
Notify the control room / WCCS.
Procedure Step Att. 4, step 5 CUE: Acknowledge report and inform candidate that their task is complete.
SAT [ ] UNSAT [ ]
Standards Candidate reports that 1-AP-15, is complete.
END OF EVALUATION Stop Time:
__________