MONTHYEARML1017602192010-06-22022 June 2010 NFPA 805 Transition Pilot Plant FAQ 07-0030, Revision 1 Project stage: Request ML1026401142010-09-16016 September 2010 NFPA 805 Transition Pilot Plant FAQ 07-0030, Revision 4 Project stage: Request ML1030906022010-11-0404 November 2010 NFPA 805 Transition Pilot Plant FAQ 07-0030, Revision 5 Project stage: Request ML1030802102010-11-0404 November 2010 NRC Staff Response to NFPA 805 Transition Pilot Plant FAQ 07-0030, Revision 4 Project stage: Request ML1100704852011-02-0404 February 2011 Close-out of National Fire Protection Association Frequently Asked 07-0030 on Establishing Recovery Actions Project stage: Request L-2011-312, Units 1 and 2 and Turkey Point, Units 3 and 4 - Regarding Online Reference Portal2011-08-0505 August 2011 Units 1 and 2 and Turkey Point, Units 3 and 4 - Regarding Online Reference Portal Project stage: Request NG-11-0267, Transition to 10 CFR 50.48(c) - NFPA 805 Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants (2001 Edition) (TSCR-128)2011-08-0505 August 2011 Transition to 10 CFR 50.48(c) - NFPA 805 Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants (2001 Edition) (TSCR-128) Project stage: Request ML11277A2852011-10-0303 October 2011 NRR E-mail Capture - FW: ME6818 - NFPA 805 Adoption Acceptance Review RAIs and Clarification Conference Call of 9/30/2011 Project stage: RAI NG-11-0384, Clarification of Information Contained in License Amendment Request (TSCR-128): Transition to 10 CFR 50.48(c) - NFPA 805 Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants (2001 Edition) (TSCR-128)2011-10-14014 October 2011 Clarification of Information Contained in License Amendment Request (TSCR-128): Transition to 10 CFR 50.48(c) - NFPA 805 Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants (2001 Edition) (TSCR-128) Project stage: Request ML11304A1242011-10-27027 October 2011 NRR E-mail Capture - ME6818 - Duane Arnold - LIC-109 Acceptance Review Results - Transition to 10 CFR 50.48(c) - Adoption of NFPA 805 Performance-Based Fire Protection Standard Project stage: Acceptance Review ML11304A1482011-10-28028 October 2011 NRR E-mail Capture - ME6818 - Duane Arnold Adoption of NFPA-805 - Generic List of Documents Requested for the Sharepoint Portal Project stage: Other ML11334A1502011-11-30030 November 2011 NRR E-mail Capture - ME6818 - DAEC NFPA-805 Adoption - Pre-Audit Discussion - 29 Nov 2011 Conference Call Project stage: Other ML12031A1122012-01-31031 January 2012 NRR E-mail Capture - ME6818 - DAEC Adoption of NFPA-805 - Afpb, Ihpb, Apla Request for Additional Information (RAI) Project stage: RAI 05000331/LER-2012-001, Regarding Inoperability of Low Pressure Coolant Injection Due to Discharge Line Voiding2012-01-31031 January 2012 Regarding Inoperability of Low Pressure Coolant Injection Due to Discharge Line Voiding Project stage: Request ML12058A5702012-02-24024 February 2012 NRR E-mail Capture - ME6818 Record of Duane Arnold RAI Clarification Call - Wednesday, February 22, 2012 2:15 PM-3:15 PM ET Project stage: RAI ML12058A5722012-02-27027 February 2012 NRR E-mail Capture - ME6818 - Clarification Conference Call of 2/22/2012 - Licensee and NRC Attendance - Supplemental Record Project stage: Approval ML12079A2322012-03-19019 March 2012 NRR E-mail Capture - ME6818 DAEC 60/90 Day Matrix - RAI Processing Identifier Syntax Project stage: RAI NG-12-0177, Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generational Plants2012-04-23023 April 2012 Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generational Plants Project stage: Response to RAI ML12115A0782012-04-24024 April 2012 NRR E-mail Capture - FW: ACRS July 2012 NFPA-805 Subcommittee Meeting - Invitation for DAEC Participation Project stage: Meeting ML1214300352012-05-21021 May 2012 NFPA 805 Transition FAQ 12-0062, Revision 1 Project stage: Request ML1214500142012-05-23023 May 2012 NFPA 805 LAR Status Matrix - May 2012 Project stage: Other NG-12-0225, Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants2012-05-23023 May 2012 Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants Project stage: Response to RAI ML12284A0212012-10-0808 October 2012 NRR E-mail Capture - ME6818 Duane Arnold NFPA-805 - Second Audit Visit Questions (Retrieved Copy) Project stage: Other NG-12-0419, Response to Second Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805 Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants2012-10-15015 October 2012 Response to Second Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805 Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants Project stage: Request ML12304A0692012-10-26026 October 2012 NRR E-mail Capture - ME6818, Additional RAIs for Duane Arnold Energy Center, LAR to Adopt NFPA 805 Project stage: RAI ML12318A3942012-11-0808 November 2012 NRR E-mail Capture - ME6818 - DAEC Adoption of NFPA-805 - Record of RAI Clarification Conference Call Conducted on 11/08/2012 Project stage: RAI ML12340A4502012-12-0505 December 2012 NRR E-mail Capture - ME6818 - DAEC Adoption of NFPA 805 - Request for Additional Information (RAI) Items - Round 2 (More) Project stage: RAI ML12355A0722012-12-19019 December 2012 NRR E-mail Capture - FW: ME6818 - DAEC NFPA-805 Adoption - Record of Revisions to RAI Items, Expected Response Schedule, Participants List for Meetings on 17-18 December 2012 Project stage: RAI ML12361A0192012-12-23023 December 2012 NRR E-mail Capture - Supplement to ML12355A072 (RAI Issed as an Email on 12/19/2012, at 4:08 PM ET) Project stage: RAI NG-12-0502, Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants2013-01-11011 January 2013 Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants Project stage: Response to RAI NG-13-0056, Response to RAI, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants2013-02-12012 February 2013 Response to RAI, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants Project stage: Response to RAI NG-13-0102, Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants2013-03-0606 March 2013 Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants Project stage: Response to RAI ML13070A0352013-03-0808 March 2013 NRR E-mail Capture - ME6818 - DA - NFPA-805 Adoption - Request for Portal Locations to Selected RAI Responses Project stage: RAI ML13084A0042013-03-22022 March 2013 NRR E-mail Capture - ME6818 DAEC Adoption of NFPA-805 - Request for Additional Information Project stage: RAI ML13098B0722013-04-0707 April 2013 NRR E-mail Capture - ME6818 - DAEC Adoption of NFPA-805 - Request for Additional Information (Revised) Project stage: RAI ML13119A2202013-04-26026 April 2013 NRR E-mail Capture - FW: ME6818-DAEC-Adoption of NFPA-805- RAI Dated 4/7/2013 - Record of Clarification Call of April 11, 2013 Project stage: RAI NG-13-0182, Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants2013-05-0101 May 2013 Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants Project stage: Response to RAI ML13129A0742013-05-0808 May 2013 NRR E-mail Capture - ME6818 - DAEC - Adoption of NFPA 805 - Request for Additional Information (RAI) Project stage: RAI NG-13-0240, Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants2013-05-29029 May 2013 Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants Project stage: Response to RAI ML13175A3932013-06-27027 June 2013 Request for Additional Information for Review Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI NG-13-0281, Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants2013-07-0202 July 2013 Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants Project stage: Response to RAI NG-13-0287, Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants2013-07-0202 July 2013 Response to Request for Additional Information, License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants Project stage: Response to RAI ML13210A4582013-07-30030 July 2013 Revised License Condition for the License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants Project stage: Other NG-13-0318, Response to Revised License Condition for the License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generation Plants2013-08-0505 August 2013 Response to Revised License Condition for the License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generation Plants Project stage: Request NG-13-0341, Response to Revised License Condition for the License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants2013-08-28028 August 2013 Response to Revised License Condition for the License Amendment Request to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor Generating Plants Project stage: Request ML13210A4492013-09-10010 September 2013 Issuance of Amendment Regarding Transition to a Risk-Informed Performance-Based Fire Protection Program in Accordance with 10 CFR 50.48(c) Project stage: Approval 2012-03-19
[Table View] |
Text
1 NRR-PMDAPEm Resource From:
Feintuch, Karl Sent:
Wednesday, December 19, 2012 4:08 PM To:
Swenzinski, Laura Cc:
Robinson, Jay; Harrison, Donnie; Litkett, Bernard; Pearson, Alayna; Hyslop, JS
Subject:
FW: ME6818 - DAEC NFPA-805 adoption - Record of revisions to RAI items, expected response schedule, Participants list for meetings on 17-18 December 2012 Attachments:
RAI due dates.xlsx.xlsx.xlsx The information that follows is a combined record of the attendance and results of the meetings conducted.
NRC Participant PRA Mtg 12/17, 1000-1200 ET FP Mtg 12/18, 1100-1130 ET PRA Mtg 12/18, 1130-1200 ET Karl Feintuch, DORL X
X X
Steve Dinsmore, PRA X
X Donnie Harrison, PRA X
X Bernard Litkett, FP X
Alayna Pearson, FP X
Jay Robinson, FP X
X JS Hyslop, PRA X
DAEC Participant PRA Mtg 12/17, 1000-1200 ET FP Mtg 12/18, 1100-1130 ET PRA Mtg 12/18, 1130-1200 ET Laura Swenzinski Jim Lechner Andy Ratchford (Kleinsorg Group)
Brad Hopkins Russ Severson Roy Hanson Gary Ellis Vinny Rubano X
X X
X X
X X
X Laura Swenzinski Andy Ratchford (Kleinsorg Group)
Russ Severson Gary Ellis Vinny Rubano Brad Hopkins Mike Saunders (Erin Engg)
X X
X X
X X
X X
X X
X X
X X
The information that follows affirms the schedule for expected responses and provides clarification to identified RAI items. A bullet mark indicates forthcoming information. Please proceed with the information provided.
RAI Response Schedule
2 The attached schedule is acceptable. For identification purposes in other documents, items due on January 11, 2013 are also identified as Round 2 RAI items and items due either February 12, 2013, or March 6, 2013, are also identified in other documents as either Round 2 (more) items, Round 3 items, and 60-day response items, or 90-day response items, as when discussing originally intended due dates.
The following RAI changes and decisions resulted from the conference calls held on 17-18 December 2012, regarding TAC No. ME6818, DAECs adoption of NFPA-805:
Fire Protection Engineering RAI 13 Fire Protection Engineering (FPE) RAI 13, item c, as it appears in an email message of November 8, 2012, sent 4:03 PM from Karl Feintuch to Laura Swenzinski, is modified as a result of the conference call on 18 December 2012 to be:
- c. The Transition Report stated that the design will be based on FAQ 08-0046 (ADAMS Accession No. ML093220426) and will meet the FAQ guidance such as: sensitivity, equipment voltage restrictions, and fast versus slow acting devices in regard to fire growth. In light of your revised approach to not use FAQ 08-0046, describe how the application of an incipient detection system will be integrated with this revised approach (NUREG 6850 Appendix L, credit for defense in depth only, etc.).
For reference purposes the changes in text are described below:
The Transition Report stated that the design will be based on FAQ 08-0046 (ADAMS Accession No. ML093220426) and will meet the FAQ guidance such as: sensitivity, equipment voltage restrictions, and fast versus slow acting devices in regard to fire growth. In light of your revised approach to not use FAQ 08-0046, However, the FAQ 08-0046 was not written for panels in the Control Room D describe how the application of an incipient detection system will be integrated with the this revised approach (NUREG 6850 Appendix L, credit for defense in depth only, etc.) the requirements of FAQ 08-0046.
The following RAI items originally appeared in an email message of December 5, 2012, sent 12:23 PM from Karl Feintuch to Laura Swenzinski:
Probabilistic Risk Assessment (PRA) RAI 06.01 (and others, where understanding locations is important to understanding your responses)
To support the conference discussions DAEC supplied a sketch which would be helpful to include with your RAI responses and consider incorporating the following improvements:
- 1. Account for labeling of areas, rooms, doorways, features in the text of your responses with the same labeling on your sketch.
- 2. To simplify locating features that you discuss, consider adding a map grid (one alpha axis and one numeric axis) so you can refer to located at sketch position B-4 type descriptions. This may be valuable where exact labeling is impractical or where you are referring to different parts of the same room or different areas with the same name.
Before transmitting your response to us review your sketch and descriptions for sensitivity marking if they meet appropriate criteria.
PRA RAI 08.01 In part a. delete the third paragraph beginning and ending with: This is not a stated guidance would not be met.
PRA RAI 11.01 A revision to part a. will be forthcoming when released.
3 PRA RAI 31.01 For your response please review Table G-1 and supply all MSOs for CIVs.
PRA RAI 35.01 A revision will be forthcoming when released. The revision replaces sensitivity analysis with analysis PRA RAI 47.01 Change the text to address typos and incorrect reference:
In part c. the reference should be to Section 3.5.2.2, as in the items preamble. The citation of 3.5.5.5 is erroneous.
In part d. fevelopment should be development.
PRA RAI 69 All references to sensitive electronics should be to electronics
Hearing Identifier:
NRR_PMDA Email Number:
565 Mail Envelope Properties (Karl.Feintuch@nrc.gov20121219160800)
Subject:
FW: ME6818 - DAEC NFPA-805 adoption - Record of revisions to RAI items, expected response schedule, Participants list for meetings on 17-18 December 2012 Sent Date:
12/19/2012 4:08:01 PM Received Date:
12/19/2012 4:08:00 PM From:
Feintuch, Karl Created By:
Karl.Feintuch@nrc.gov Recipients:
"Robinson, Jay" <Jay.Robinson@nrc.gov>
Tracking Status: None "Harrison, Donnie" <Donnie.Harrison@nrc.gov>
Tracking Status: None "Litkett, Bernard" <Bernard.Litkett@nrc.gov>
Tracking Status: None "Pearson, Alayna" <Alayna.Pearson@nrc.gov>
Tracking Status: None "Hyslop, JS" <JS.Hyslop@nrc.gov>
Tracking Status: None "Swenzinski, Laura" <Laura.Swenzinski@nexteraenergy.com>
Tracking Status: None Post Office:
Files Size Date & Time MESSAGE 5390 12/19/2012 4:08:00 PM RAI due dates.xlsx.xlsx.xlsx 13933 Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received:
DAEC NFPA 805 RAI RESPONSE DATES RAI CATEGORY #
SUBMITTAL DATE SSA 5.01 1/11/2013 FPE 11 1/11/2013 FPE 12 1/11/2013 FMOD 2.01 1/11/2013 FMOD 04.01 1/11/2013 FMOD 05.01 1/11/2013 FMOD 07 1/11/2013 PRA 04.01 1/11/2013 PRA 62 1/11/2013 PRA 63 1/11/2013 PRA 64 1/11/2013 PRA 02.01 2/12/2013 PRA 06.01 2/12/2013 PRA 10.01 2/12/2013 PRA 12.01 2/12/2013 PRA 14.01 2/12/2013 PRA 16.01 2/12/2013 PRA 20.01 2/12/2013 PRA 31.01 2/12/2013 PRA 32.01 2/12/2013 PRA 39.01 2/12/2013 PRA 41.01 2/12/2013 PRA 43.01 2/12/2013 PRA 44.01 2/12/2013 PRA 47.01 2/12/2013 PRA 48.01 2/12/2013 PRA 55.01 2/12/2013 PRA 57.01 2/12/2013 PRA 58.01 2/12/2013 PRA 60.01 2/12/2013 PRA 65 2/12/2013 PRA 67 2/12/2013 PRA 68 2/12/2013
DAEC NFPA 805 RAI RESPONSE DATES RAI CATEGORY #
SUBMITTAL DATE PRA 70 2/12/2013 PRA 71 2/12/2013 PRA 73 2/12/2013 PRA 74 2/12/2013 PRA 75 2/12/2013 PRA 77 2/12/2013 PRA 78 2/12/2013 PRA 79 2/12/2013 PRA 80 2/12/2013 PRA 81 2/12/2013 PRA 01.01 3/6/2013 PRA 08.01 3/6/2013 PRA 11.01 3/6/2013 PRA 35.01 3/6/2013 PRA 66 3/6/2013 PRA 69 3/6/2013 PRA 72 3/6/2013 PRA 76 3/6/2013 FPE 13 3/6/2013 SSA 1.01 3/6/2013