ML12264A320

From kanterella
Jump to navigation Jump to search

Meeting Handout for 10/11/12 Pre-licensing Meeting License Amendment Request to Revise the Fire Protection Program
ML12264A320
Person / Time
Site: South Texas  STP Nuclear Operating Company icon.png
Issue date: 10/11/2012
From: Taplett K
South Texas
To: Balwant Singal
Plant Licensing Branch IV
Singal B
References
TAC ME9182, TAC ME9183
Download: ML12264A320 (14)


Text

Pre-licensing Meeting for License Amendment Request to Revise Amendment Request to Revise the Fire Protection Program at the South Texas Project October 11, 2012 October 11, 2012 1

Agenda Agenda

  • Introductions
  • Purpose B

k d

  • Background
  • Bases of Change
  • Bases of Change
  • Additional Information to be Developed
  • Summary
  • Questions 2

South Texas Project (STP) Representatives South Texas Project (STP) Representatives

  • Mike Murray - Manager, Regulatory Affairs
  • Ken Taplett - Licensing Engineer Ken Taplett Licensing Engineer
  • Charles Albury - Thermal-Hydraulic Analysis Supervisor y

y y

p

  • Donald Rohan - Operations Procedure Writer Responsible for plant off-normal procedures in response to fire Previously licensed as a Senior Reactor Operator 3

Previously licensed as a Senior Reactor Operator

Purpose Purpose Describe the STP Nuclear Operating Company proposal p

g p

y p p

to revise the South Texas Project, Units 1 and 2, Fire Protection Program 4

=

Background===

Background

  • The change involves revising the STP Licensing Basis f

ti th lt ti h td bilit for meeting the alternative shutdown capability.

  • STP is required by their licensing basis to meet the i

t f 10 CFR 50 A di R S ti III L requirements of 10 CFR 50, Appendix R, Section III.L, Alternative and dedicated shutdown capability.

STP is currently relying on compensatory measures to

  • STP is currently relying on compensatory measures to meet their licensing basis.
  • STP recently withdrew a license amendment request
  • STP recently withdrew a license amendment request because insufficient information was provided to the NRC staff to approve the amendment request.

5

Fire Protection Program Change Fire Protection Program Change

  • In order to meet the regulatory requirements of Appendix R,Section III.L, the proposed amendment request:

- Credits the performance of operator actions in the control room, in addition to tripping the reactor, prior to evacuation due to a fire fire.

- Credit the automatic trip of the main turbine in response to a reactor trip reactor trip.

6

Bases of Change Bases of Change Regulatory Guide 1.189, Fire Protection for Nuclear Power Plants, usually credits a reactor trip prior to control room evacuation usually credits a reactor trip prior to control room evacuation.

In order to credit additional control room actions:

Th li t d t

t th ti b

f d

- The licensee must demonstrate the actions can be performed

- The licensee should ensure that such actions cannot be negated by subsequent spurious actuation signals resulting from the postulated fire.

- The licensee should consider one spurious actuation to occur before t

l f th l

t i hi d th h th lt ti d di t d control of the plant is achieved through the alternative or dedicated shutdown system.

Both (1) the loss of offsite power and (2) maintaining offsite power

( )

p

( )

g p

scenarios should be considered.

Automatic functions of circuits in the control room fire should not be credited if the function would mitigate the consequences 7

credited if the function would mitigate the consequences.

Bases for Change (continued)

Bases for Change (continued)

  • The feasibility and reliability of the additional operator actions have been demonstrated.
  • A single spurious actuation analysis demonstrates that no single spurious actuation could negate a control room action in manner that Appendix R,Section III.L action in manner that Appendix R,Section III.L requirements are not met.
  • The automatic turbine trip analysis provides reasonable assurance that the turbine will trip when actuated by a reactor trip and would not subsequently be negated by a fire induce circuit failure 8

fire-induce circuit failure.

Bases for Change (continued)

Bases for Change (continued)

  • Defense-in-Depth Analysis addresses the p

y following:

- Fire Prevention Measures Fire Prevention Measures

- Capability to detect, control and extinguish fires

- Protection of structures, systems and components so that fires will not prevent safe shutdown that fires will not prevent safe shutdown

- Safety margin analyses

  • Analysis for those actions with small time margins shows the plant can achieve safe shutdown conditions when plant can achieve safe shutdown conditions when considering instrument uncertainties.
  • Analysis to justify plant safe shutdown is achievable in event all the requested actions are not completed.

9

Additional Information t

b D

l d

to be Developed Address the following scenario:

- Spurious actuation of pressurizer power-operated relief valve p

p p

p (PORV), and

- Pressurizer PORV block valve cannot be closed due to fire-induced circuit failure, and

- No actions credited in the control room other than manual reactor trip and automatic turbine trip, and

- Loss of offsite power.

10 p

Additional Information t

b D

l d

to be Developed

  • Scenario will address the following:

- Ability to maintain and/or restore natural circulation

- Impact on sub-cooling margin I

t f

l i t it

- Impact on fuel integrity 11

Addi i l I f i

Additional Information to be Developed Add th i

t t

l t

l l

  • Address the impact of a control room fire on the initiation of safety injection.

initiation of safety injection.

12

Summary Summary

  • License Amendment Request will be resubmitted Request approval of same operator actions and automatic

- Request approval of same operator actions and automatic turbine trip as the previously withdrawn request.

- Bases for approval are the actions can be performed and that the actions cannot be negated by subsequent spurious actuation signals resulting from the postulated fire.

- Automatic turbine trip relies on success of reactor trip.

- Sufficient defense-in-depth/safety margin exists to demonstrate safe shutdown conditions can be achieved based on analyses previously performed and additional information to be developed.

13

Questions?

Questions?

14