Exeklon.
Nuclear May 15, 2012 TMI-12-071 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 Three Mile Island, Unit 1 (TMI Unit 1)
Facility Operating License No. DPR-50 NRC Docket No. 50-289
Subject:
TMI-1 Steam Generator Tube Inspection Report
Reference:
Letter from P. Cowan, Exelon Generation Company, LLC, to the U.S.
Nuclear Regulatory Commission, 'Three Mile Island Unit 1 -Response to June 25, 2009, Public Meeting Between the U.S. Nuclear Regulatory Commission and the Pressurized Water Reactor Owners Group (PWROG) Related to PWROG Topical Report BAW-2374, Revision 2,"
dated September 4, 2009 Exelon Generation Company, LLC (Exelon) completed an examination of the tubing in the Three Mile Island Unit 1 (TMI-1) steam generators during Refueling Outage T1 R1 9.
TMI-1 Technical Specification 6.9.6 requires a report of the inspection results be submitted within 180 days after reactor coolant temperature exceeds 200 0 F. Attachment 1, documents the results of the examinations.
In Reference 1, Exelon made the following commitment relative to tube integrity following a large break loss of coolant accident (LBLOCA).
"Provide the NRC with the structural limit(s) associated with the most limiting LBLOCA for the replacement SGs as part of the next SG tube inspection report (required by technical specifications) following completion of the next inspection of the tubes in the replacement SGs."
The response to this commitment is also included in Attachment 1.
No new regulatory commitments are established by this submittal. If any additional information is needed, please contact Michael Fitzwater at 717-948-8228.
Respectfully, R. W. Libra Site Vice President, Three Mile Island Unit 1 Exelon Generation Co., LLC - TMI-1 Steam Generator Tube Inspection Report (T1 R1 9)
May 15, 2012 TMI-12-071 cc: USNRC, Regional Administrator, Region I USNRC, Senior Resident Inspector, TMI Unit 1 USNRC, Project Manager, TMI Unit 1
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19)
Page 1 of 14 Overview During the period of 10/25/2011 to 11/25/2011 TMI-1 was shutdown for Refueling Outage TIR19. While the unit was shutdown, Exelon performed examinations of the tubing in the steam generators (SG). The examinations were performed in accordance with Technical Specification 4.19 and 6.19.
Technical Specification 6.9.6 requires a report be submitted within 180 days after the average reactor coolant system temperature exceeds 200°F following completion of an inspection performed in accordance with Section 6.19, Steam Generator (SG) Program.
The average reactor coolant temperature exceeded 200'F on 11/22/2011.
In Reference 1, Exelon Generation Company, LLC (Exelon) made the following commitment relative to tube integrity following a large break loss of coolant accident (LBLOCA).
"Provide the NRC with the structural limit(s) associated with the most limiting LBLOCA for the replacement SGs as part of the next SG tube inspection report (required by technical specifications) following completion of the next inspection of the tubes in the replacement SGs."
As required by the technical specifications and the commitment contained in Reference 1, the following information is being submitted LBLOCA Structural Limits The limiting loads for the LBLOCA event are the axial loads that result from the temperature difference between the tube and the shell as the tube rapidly cools in relation to the slow cooling shell. The maximum tube load is limited by the yield strength of the material. For TMI, the limiting load is 3104 lbs based on the average material properties of the TMI tubing.
The allowable circumferential extents for a 100% through-wall flaw at the yield axial load of 3104 lbs are:
Best estimate structural limit = 0.63 inches which equals 123 degrees End of Cycle, High Probability limit = 0.55 inches which equals 107 degrees The equivalent allowable circumferential extents for a 60% through-wall flaw are:
Best estimate structural limit = (0.63/0.6) = 1.05 inches which equals 204 degrees End of Cycle, High Probability limit = (0.55/0.6) = 0.91 inches which equals 178 degrees The results show the EOTSG tubes can experience degradation with significant amounts of circumferential extent and depth and will not be in jeopardy of pulling apart (rupturing) during a LBLOCA event.
TMI- 12-071, TMI- 1 Steam Generator Tube Inspection Report (T 1R 19)
Page 2 of 14 Tube Support Plate Wear Limits The limits provided above are basic limits for circumferential degradation without any relation to a specific degradation source. At the time of the analysis, the only active degradation in the EOTSG with Alloy 690 tubing was wear at the tube supports. A conservative estimate of circumferential extent based on a flat wear scar that just does intersect the ID of the tube yields an extent of 0.30". A review of the data shows that degradation of this extent would not challenge the structural limits for the tube. Specifically:
The allowable axial strength due to a 100% through-wall wear scar at a single TSP land (0.30")
is:
Best estimate structural limit allowable load = 4130 lbs End of Cycle, High Probability limit allowable load = 3900 lbs These allowable loads are much greater than the limiting yield load of 3104 lbs.
The allowable axial strength due to a 100% through-wall wear scar at two TSP lands (0.60") is:
Best estimate structural limit allowable load = 3184 lbs End of Cycle, High Probability limit allowable load = 2965 lbs The best estimate limit allowable load is greater than the 3104 lb limiting yield load. Although the End of Cycle, High Probability (EOC) allowable load is slightly lower than the limiting yield load of 3104 lbs, due to the conservatism in defining the circumferential extent of the wear scar, it is concluded that the EOC limit is also acceptable for a 100% TW wear at two TSP lands.
During outage T1R19, the structural limits defined above were determined to be applicable to both the tube-to-tube support plate (T-TSP wear) and tube-to-tube wear (T-T wear) identified during the T1R19 examinations. Both the condition monitoring and operational assessment evaluations for both damage mechanisms considered the LBLOCA structural limits and conditions. These evaluations are discussed in section T.S.6.9.6.g of this report.
Information Required by Technical Specification (T.S.) 6.9.6 The following information is required to be submitted per T.S. 6.9.6. The applicable T.S.
paragraph is shown in parenthesis followed by the T.S. reporting requirement.
(T.S. 6.9.6.a) The scope of examinations performed on each SG, The T1R19 examinations were the first examinations following replacement of the steam generators during outage T1R18. In accordance with the requirements of TS 6.19.d.1, the examinations included 100% of the tubes in each steam generator. All of the tubes in each steam generator were examined over their full length using the bobbin coil probe.
A combination bobbin coil / array coil probe was used to examine the periphery tubes (2 tubes deep). The data from the array probe was evaluated for the detection of foreign objects in the span between the lower tube sheet and the first tube support plate. Tubes with anomalies (e.g. dings >1.5 volt, manufacturing buffing marks (MBM) >0.5 volt)
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19)
Page 3 of 14 recorded during the pre-service (PSI) examinations were also examined using the array probe.
In addition, array probes and/or rotating probes were used to examine tubes with indications identified during the T1R19 bobbin coil examinations. This population of tubes, referred to as special interest (SI) tubes, included all tubes with indications recorded as I-Codes (i.e. ADI, DSI and NQI), all tubes with tube-to-tube wear and a sample of tubes with tube-to-tube support plate wear.
The total scope of the examinations is as follows:
T1R19, Scope of Examinations Examination Group Probe Extent SG A SG B Bobbin Coil Analysis Single Pass Full Length 51OUL Full Length 15,597 15,597 Examinations or (LTEUTE) 510XB Array Coil Analysis Periphery Tubes and 510XP Array data 920 958 Tubes with PSI evaluated Indications, Top of LTS01S Lower Tubesheet to 1 st TSP PSI Indications 510XP Array data 18 56 evaluated for specific locations Special Interest 510XP Array data 258 413 (e.g. Sizing T-T Wear, evaluated for specific locations MRPC Analysis Special Interest 520PP (08S09S) 64 0 (Sizing T-T Wear)
Notes.
- 520UL = Bobbin Coil Probe, 5 1OXB = X-Probe Bobbin Coil Analysis, 5 1OXP = X-Probe Array Coil Analysis, 520PP = MRPC +Point
- Tube supports are identified as 01S (lower) to 15S (upper).
- Full length examinations are from the lower tube end (LTE) to the upper tube end (UTE).
- Array data for periphery tubes was evaluated in the span from the lower tube sheet (LTS) to the ISt TSP (0IS) for detection of foreign material or loose parts.
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19)
Page 4 of 14 (T.S. 6.9.6.b) Active degradation mechanisms found, The eddy current examinations identified two active degradation mechanisms. The first mechanism is tube-to-tube support plate wear (T-TSP wear). The second mechanism is tube-to-tube wear (T-T Wear). Both degradation mechanisms are present in both steam generators.
(T.S. 6.9.6.c) Nondestructive examination techniques utilized for each degradation mechanism, The T-TSP wear was initially screened by the bobbin coil probe. Sizing was also accomplished using the bobbin coil probe and EPRI technique ETSS 96004.1, Rev. 13.
Rotating and/or array probes were used to perform line by line sizing on a sample of indications to characterize the length and width of the degradation and to verify no cracking was present.
The T-T Wear was initially screened using the bobbin coil probe. The screened indications were then sized using the rotating probe and EPRI technique 27905.3, Rev. 0 or the array probe and the TMI Site Qualification technique Rev. 0.
The TMI Site Qualification technique was developed in conjunction with EPRI to allow depth sizing using the array probe. The technique was developed using the same standards used to develop EPRI technique 27905.3 for the detection and sizing of wear using the MRPC probe. The calibration methodology for the array probe is the same as defined in EPRI technique 11956.3, Rev. 0, which was developed for the detection and sizing of mechanically induced wear at stainless steel support plates using the array probe. The technique was developed and qualified in accordance with requirements of the EPRI Pressurized Water Reactor Steam Generator Examination Guidelines, Revision 7.
(T.S. 6.9.6.d) Location, orientation (if linear), and measured sizes (if available) of service induced indications, The following information is provided to aid in understanding the location of indications within the SGs. The TMI-1 SGs have 15 tube support plates (TSPs), numbered 01S through 15S with 01S being the bottom TSP. The TSPs are 1.18" thick SA 240 type 410M stainless steel. The distance between the support structures ranges from 35" to 46.38". The tube bundle is essentially circular with a maximum diameter of approximately 114" (maximum radius= 57"). Exhibits 1 and 2 are listings of all service induced indications.
T-TSP Wear The T-TSP wear is located primarily at the 7th through 15th TSP with the highest number of indications occurring at the 8th TSP. At the 8th TSP, the radial location of the T-TSP
TMI- 12-071, TMI-1 Steam Generator Tube Inspection Report (T 1R 19)
Page 5 of 14 wear is approximately the same as the T-T wear indications. The radial location of the T-TSP wear indications is more towards the periphery at the higher tube support plate locations.
In SG A, a total of 952 T-TSP wear indications ranging from 5% - 27% through wall were recorded in 847 tubes. In SG B, a total of 1342 T-TSP wear indications ranging from 5% - 52% through wall were recorded in 1035 tubes. The indications are volumetric in nature and tend to be axially oriented. Length sizing on a sample of indications showed the structural length for most of the indications is < 0.5" with the longest observed structural length being 0.66".
Figures 1 and 2 show the radial distribution of T-TSP wear indications. Figure 3 shows the axial distribution of the T-TSP wear indications.
TMI- 12-071, TMI- 1 Steam Generator Tube Inspection Report (T 1R 19)
Page 6 of 14 Figure 1 SG "A" Tube-to-Tube Support Plate Wear XA1 TMI Unit 1 Repi 1R19- 10/11 Tube Support Wear S/G A PRIMARY FACE INLET TOTAL TUBES. 15897:
TUBES SELECTED: 847 OUT OF SERVICE (#) NA GROUP TUBES Tube Support Wear 847 z x SCALE. 008887 X Thu N 10774411 Y
TMI- 12-071, TMI- 1 Steam Generator Tube Inspection Report (T1R 19)
Page 7 of 14 Figure 2 SG "B" Tube-to-Tube Support Plate Wear w
TMI Unit 1 Repi 1R19- 10/11 Tube Support Wear SIr B PRIMARY FACE INLET TOTAL TUBES: 15597 TUBES SELECTED. 1035 OUT OF SERVICE (*: 0 GROUP TUBES Tube Support Wear 1035 z x SCALE 006W87X Thu NoM100&40:04 21 Y
TMl-12-07x, TMI-1 Steam Generator Tube Inspection Repor (T1 9)
AkttachmenIt 1 Page8 of 14 igure 3 SG "A" e4Te SupPOri piate Wear 25C1 2000 l0szo oT-. 10 10030
-T.W.
TSP Number Tube-to-TUbe SSul)' Plate Wear 250 020-29%
1510-2-9%
OIS 02S 503 03S 04S >= 0 %T.W.
05S 06S 07S 08S 09S JOS JIS 12S TSP Number 13S 14S 15S
TMI- 12-071, TMI- 1 Steam Generator Tube Inspection Report (T 1R 19)
Page 9 of 14 T-T Wear The T-T wear indications are located primarily in the span between the 8th and 9th tube support plates (counted from the bottom). There is one tube that has tube-to-tube wear between both the 7th and 8th and the 8th and 9th tube support plate. (Including the above tube, there are 5 tubes with wear between the 7th and 8th tube support plate and 2 tubes with wear between the 4th and 5th tube support plate.) All other tube-to-tube wear indications are between the 8th and 9th tube support plate.
Most of the tubes with T-T wear indications are located between 30" - 45" from the center of the bundle. Generally speaking, there is a ring of tubes with indications.
In SG A, a total of 89 T-T wear indications ranging from 1% - 21% through wall were recorded in 74 tubes. In SG B, a total of 206 T-T wear indications ranging from 3% -
19% through wall were recorded in 183 tubes.
The wear indications are essentially centered between the tube support plates and in most cases are in pairs with similar through wall depths. In some cases there is a cluster of three or more affected tubes. The wear indications are axially oriented with lengths ranging from approximately 2" to 8".
Figures 4 and 5 show the radial distribution of the T-T wear indications. Figure 6 shows the percent through wall depth distribution of the T-T wear indications.
TMI- 12-071, TMI- 1 Steam Generator Tube Inspection Report (T 1R19)
Page 10 of 14 Figure 4 SG "A" Tube-to-Tube Wear
\AI TMI Unit 1 Repi 1R19 - 10/11 Tube-to-Tube Contact SIGB PRIMARY FACE INLET TOTAL TUBES 15697 TUBES SELECTED: 183::
OUT OF SERVICE A1) NA GROUP TUBES Tubeto-Tube Contact 183 z x SCALE: 0.088887X Thu Nov 10 08:43:19 2011 Y
TMI- 12-071, TMI- 1 Steam Generator Tube Inspection Report (T 1R 19)
Page 11 of 14 Figure 5 SG "B" Tube-to-Tube Wear W
TMI Unit 1 Repl 1R19 - 10/11 Tube-to-Tube Contact SfGA PRIMARY FACE INLET TOTALTUBES 15597 TUBES SELECTED: 74 OUT OF SERVICE (#) 0 GROUP TUBES Tube--Tube Cot.. 74 z x SCALE: 0088887X Thu No 10 08:28:21 2011 Y
TMI- 12-071, TMI- 1 Steam Generator Tube Inspection Report (T 1R 19)
Page 12 of 14 Figure 6 SG "A" Tube-to-Tube Wear Indications 30 25 2
20 C
z 0
Z O
z i a .
10 Iii
m 5] I I I I I I I.M. I I 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 DEPTH (%TW)
SG "B" Tube-to-Tube Wear Indications 45 ---
40 35 30 zCD 0
25-
- 20 z
15 10 5
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 DEPTH (%TW)
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19)
Page 13 of 14 (T.S. 6.9.6.e) Number of tubes plugged during the inspection outage for each active degradation mechanism, Thirty-seven tubes were plugged during T1R19. Thirty tubes, all in SG B were plugged for T-TSP wear. Seven tubes, (4 in SG A and 3 in SG B) were plugged for T-T Wear.
(T.S. 6.9.6.0 Total number and percentage of tubes plugged to date, There were no tubes plugged prior to T1R19. The total number and percentage of plugged tubes is as follows.
SG A, Total Tubes = 15,597 Year Outage Number of Cumulative Cumulative Tubes Plugged Plugged Tubes Percent 2009 Fabrication 0 0 0 2009 Baseline 0 0 0 2011 1st ISI 4 4 0.03%
SG B, Total Tubes = 15,597 Year Outage Number of Cumulative Cumulative Tubes Plugged Plugged Tubes Percent 2009 Fabrication 0 0 0 2009 Baseline 0 0 0 2011 1st ISI 33 33 0.2%
(T.S. 6.9.6.g) The results of condition monitoring, including the results of tubes pulls and in-situ testing, The condition monitoring evaluations demonstrated all identified indications were acceptable at the end of Cycle 18 (T1R19 examinations). There were no tube pulls and in-situ pressure testing was not required. The condition monitoring was evaluated separately for both T-TSP wear and T-T wear. For both degradation mechanisms, the limiting structural performance criterion for TMI- 1 is three times the normal operating differential pressure (NOPD). The evaluations also considered large break loss of coolant accident (LBLOCA) conditions.
T-TSP Wear The condition monitoring limit for T-TSP wear, assuming a length of 1.18" axial length is about 58% through wall, The deepest T-TSP wear indication was 52% through wall with a structural length of 0.48".
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR 19)
Page 14 of 14 The T-TSP indications were also evaluated for LBLOCA conditions. Structural integrity for LBLOCA conditions is satisfied with 100% through wall flaws at two land areas.
Since none of the wear indications approach 100% through wall, LBLOCA conditions are satisfied.
T-T Wear The condition monitoring limit for T-T wear was established for both the rotating and array probes. The bounding condition monitoring limit for both techniques is greater than 50% through wall, assuming a flaw length of 39". Since the deepest measured T-T wear was 21% through wall with a structural length of less than 10", all condition monitoring conditions were satisfied.
The T-T wear indications were also evaluated for LBLOCA conditions. The LBLOCA conditions are satisfied with a 100% through wall flaw with a 107 degree circumferential extent which results in a percent degraded area (PDA) of 29.7%. The T-T wear flaws generally had NDE measured circumferential extents of 50-70 degrees. Conservatively assuming two flaws, at the same axial location, with 90 degree circumferential extent gives a total circumferential extent of 180 degrees. The resultant allowable PDA for a 180 degree flaw is 59.4% through wall. Since the deepest flaw is 21% through wall all LBLOCA conditions are satisfied.
(T.S. 6.9.6.h) The effective plugging percentage for all plugging in each SG, There are no sleeves or repairs other than plugs installed in the steam generators. The effective plugging percentage is the same as the actual plugged tube percentage.
Following T1R19, the effective plugging percentage for SG A is 0.03% and for SG B 0.2%.
Summary This report meets the reporting requirements for Technical Specification 6.9.6. The information provided relative to the TMI LBLOCA Structural Limits satisfies Commitment 2 from Reference 1.
References Reference 1 Letter from P. Cowan, Exelon Generation Company, LLC, to the U.S.
Nuclear Regulatory Commission, "Three Mile Island Unit 1 -Response to June 25, 2009, Public Meeting Between the U.S. Nuclear Regulatory Commission and the Pressurized Water Reactor Owners Group (PWROG)
Related to PWROG Topical Report BAW-2374, Revision 2," dated September 4, 2009
TMI-12--071, TMI-J Steam GeneratorTube Inspection Report (TJR19) , Exhibit 1 SG A, All Service Induced Indications,Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 1 5 T-TSP Wear 1lS 0.4 7 0.09 136 P1 510XB 022 A 1 9 T-TSP Wear 11S 0.4 7 0.09 149 P1 510XB 022 A 6 30 T-TSP Wear 09S 0.4 12 0.2 151 P1 51OUL 551 A 7 5 T-TSP Wear 13S 0.4 9 0.13 145 P1 510XB 022 A 7 10 T-TSP Wear 15S 0.2 11 0.18 150 P1 51OUL 551 A 7 16 T-TSP Wear 11S -0.8 11 0.18 143 P1 51OUL 551 A 7 42 T-TSP Wear 09S 0.5 17 0.24 154 P1 51OUL 553 A 7 50 T-TSP Wear 10S 0.5 10 0.15 145 P1 510XB 028 A 8 1 T-TSP Wear 13S -0.7 11 0.15 143 P1 510XB 022 A 8 40 T-TSP Wear 09S 0.4 19 0.28 149 P1 51OUL 553 A 8 53 T-TSP Wear 13S -0.7 11 0.18 147 P1 510XB 028 A 9 11 T-TSP Wear 09S 0.4 11 0.18 140 P1 51OUL 551 A 9 50 T-TSP Wear 09S 0.5 15 0.23 145 P1 51OUL 513 A 9 58 T-TSP Wear 09S 0.5 18 0.31 146 P1 510XB 028 A 10 10 T-TSP Wear 15S -0.9 8 0.12 141 P1 51OUL 611 A 10 13 T-TSP Wear 13S 0.4 14 0.23 141 P1 51OUL 551 A 10 62 T-TSP Wear 09S 0.4 10 0.13 145 P1 510XB 026 A 11 10 T-TSP Wear 09S 0.5 11 0.17 144 P1 51OUL 613 A 11 13 T-TSP Wear 09S 0.4 9 0.13 147 P1 51OUL 611 A 11 52 T-TSP Wear 09S 0.5 10 0.13 143 P1 51OUL 511 A 11 53 T-TSP Wear 09S 0.4 14 0.21 142 P1 51OUL 513 A 12 15 T-TSP Wear 09S 0.4 12 0.16 154 P1 51OUL 603 A 13 5 T-TSP Wear 13S 0.4 10 0.14 151 P1 51OUL 613 A 13 7 T-TSP Wear 09S 0.4 12 0.18 137 P1 51OUL 613 Tuesday, April 24, 2012 Page 1 of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 13 8 T-TSP Wear 14S -0.9 9 0.12 131 P1 51OUL 611 A 13 8 T-TSP Wear 09S 0.4 11 0.17 148 P1 51OUL 611 A 13 10 T-TSP Wear 13S -0.7 10 0.15 143 P1 51OUL 611 A 13 11 T-TSP Wear 15S 0.2 10 0.14 139 P1 51OUL 613 A 13 11 T-TSP Wear 11S -0.8 9 0.13 149 P1 51OUL 613 A 13 12 T-TSP Wear 11S -0.7 12 0.17 149 P1 51OUL 611 A 13 13 T-TSP Wear 14S -0.7 10 0.14 142 P1 51OUL 613 A 13 17 T-TSP Wear 09S 0.4 8 0.11 151 P1 51OUL 603 13 59 T-TSP Wear 13S 0.3 9 0.12 142 P1 51OUL 511 14 8 T-TSP Wear 09S 0.4 10 0.14 145 P1 51OUL 611 14 11 T-TSP Wear 15S -0.7 9 0.13 149 P1 51OUL 613 14 15 T-TSP Wear 14S -0.8 8 0.11 138 P1 51OUL 613 14 68 T-TSP Wear 09S 0.5 11 0.16 142 P1 51OUL 511 14 77 T-TSP Wear 09S -0.7 11 0.17 140 P1 510XB 028 15 8 T-TSP Wear 09S 0.4 10 0.14 150 P1 51OUL 611 15 9 T-TSP Wear 15S 0.2 8 0.1 119 P1 51OUL 613 15 15 T-TSP Wear 15S 0.2 9 0.12 148 P1 51OUL 613 15 19 T-TSP Wear 15S 0.2 11 0.15 145 P1 51OUL 613 15 64 T-TSP Wear 09S 0.4 10 0.13 138 P1 51OUL 511 15 67 T-TSP Wear 13S 0.3 10 0.14 140 P1 51OUL 513 16 67 T-TSP Wear 09S 0.4 10 0.13 136 P1 51OUL 511 17 8 T-TSP Wear 13S 0.3 9 0.13 123 P1 51OUL 613 17 8 T-TSP Wear 09S 0.5 12 0.17 143 P1 51OUL 613 18 7 T-TSP Wear 09S 0.4 12 0.17 153 P1 51OUL 613 Tuesday, April 24, 2012 Page2of 43
, .1
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TJR19) , Exhibit 1 SG A, All Service Induced Indications, Outage TJR19 Location % Ind. IncL Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 19 8 T-TSP Wear 09S 0.4 10 0.15 146 P1 51OUL 613 A 19 9 T-TSP Wear 09S 0.4 0.12 135 P1 51OUL 611 A 20 80 T-TSP Wear 11S -0.8 0.1 115 P1 51OUL 513 A 21 5 T-TSP Wear 13S 0.3 0.09 144 P1 51OUL 613 A 21 7 T-TSP Wear 09S 0.4 0.18 140 P1 51OUL 613 A 21 77 T-TSP Wear 11S -0.8 0.09 124 P1 51OUL 511 A 21 84 T-TSP Wear 10S 0.2 0.11 121 P1 51OUL 513 A 21 85 T-TSP Wear 09S 0.4 0.09 131 P1 51OUL 511 A 22 7 T-TSP Wear 15S 0.2 0.1 142 P1 51OUL 613 A 22 9 T-TSP Wear 09S 0.4 0.13 151 P1 51OUL 613 A 22 22 T-TSP Wear 09S 0.4 0.12 144 P1 51OUL 611 A 22 86 T-TSP Wear 13S 0.3 0.15 134 P1 51OUL 513 A 23 7 T-TSP Wear 09S 0.4 0.14 140 P1 51OUL 611 A 23 8 T-TSP Wear 09S 0.4 0.13 131 P1 51OUL 611 A 23. 46 T-T Wear 08S 17.9 14.8 21.0 6.2 53 0.47 85 5 520PP 815 A 23 94 T-TSP Wear 12S -0.7 0.23 131 P1 510XB 028 A 24 6 T-TSP Wear 09S 0.4 0.14 147 P1 51OUL 611 A 24 7 T-TSP Wear 09S 0.4 0.15 144 .i P1 51OUL 613 A 24 40 T-TSP Wear 08S 0.4 0.22 130 P1 51OUL 573 A 24 44 T-TSP Wear 08S 0.4 0.19 128 ! P1 51OUL 573 A 24 45 T-T Wear 08S 17.8 14.7 21.0 6.3 47 0.45 82 5 520PP 815 A 25 36 T-TSP Wear 08S 0.4 0.11 138 P1 51OUL 573 A 25 44 T-TSP Wear 08S 0.4 0.11 129 P1 51OUL 573 A 25 52 T-TSP Wear 09S -0.7 0.09 120 P1 51OUL 573 Page 3 of 43 2012 April24, Tuesday, April Tuesday, 24, 2012 Page 3of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TJR19) , Exhibit 1 SG A, All Service Induced Indications, Outage T1R19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 25 52 T-TSP Wear 08S 0.4 8 0.1 119 P1 51OUL 573 A 25 58 T-TSP Wear 08S 0.3 0.12 139 P1 51OUL 551 A 25 58 T-TSP Wear 08S -0.7 0.21 140 P1 51OUL 551 A 25 58 T-TSP Wear 07S 0.5 0.14 139 P1 51OUL 551 A 26 24 T-TSP Wear 08S -0.7 0.09 120 P1 51OUL 613 A 26 31 T-TSP Wear 08S 0.4 0.14 138 P1 51OUL 571 A 26 36 T-TSP Wear 08S 0.3 0.13 149 P1 51OUL 573 A 26 36 T-T Wear 08S 18.9 14.7 23.0 8.3 57 0.83 89 5 520PP 815 A 26 37 T-T Wear 08S 18.8 14.7 23.0 8.3 52 0.85 87 5 520PP 815 A 26 45 T-TSP Wear 08S 0.3 0.09 125 P1 51OUL 571 A 26 54 T-TSP Wear 08S -0.7 0.12 106 P1 51OUL 573 A 26 54 T-TSP Wear 08S 0.4 0.11 136 P1 51OUL. 573 A 26 56 T-TSP Wear 08S 0.3 0.12 121 P1 51OUL 573 A 26 59 T-TSP Wear 08S 0.3 0.21 146 P1 51OUL 571 A 26 60 T-TSP Wear 08S 0.5 0.12 140 P1 51OUL 573 A 27 43 T-TSP Wear 08S 0.3 0.22 142 P1 51OUL 571 A 27 44 T-T Wear 08S 18.6 17.1 20.0 2.9 53 0.21 63 69 510XP 823 A 27 51 T-TSP Wear 07S 0.5 0.14 140 P1 51OUL 571 A 27 61 T-TSP Wear 08S 0.4 0.13 142 P1 51OUL 571 A 27 61 T-TSP Wear 08S -0.8 0.2 119 P1 51OUL 571 A 27 63 T-TSP Wear 08S -0.7 0.13 97 P1 51OUL 571 A 27 64 T-TSP Wear 08S -0.7 0.21 115 P1 51OUL 573 A 27 64 T-TSP Wear 08S 0.4 0.12 133 P1 51OUL 573 A 27 69 T-TSP Wear 10S -0.8 0.12 128 P1 51OUL 511 A 27 96 T-TSP Wear 14S 0.2 0.1 134 P1 51OUL 513 Tuesday, April 24, 2012 Page 4 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications, Outage T1R19 Location %d. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 27 96 T-TSP Wear - 11S -0.8 9 0.13 120 P1 51OUL 513 A 27 102 T-TSP Wear 12S 0.4 8 0.12 136 P1 510XB 028 A 27 102 T-TSP Wear 10S 0.3 10 0.16 147 P1 510XB 028 A 28 24 T-TSP Wear 08S -0.7 7 0.1 87 P1 510UL 613 A 28 38 T-TSP Wear 08S -0.7 11 0.15 119 P1 51OUL 573 A 28 38 T-TSP Wear 08S 0.4 9 0.11 133 P1 51OUL 573 A 28 44 T-T Wear 08S 18.0 5 17.0 19.0 2.0 53 0.19 93 53 510XP 823 A 28 48 T-TSP Wear 07S 0.4 10 0.13 145 P1 51OUL 573 A 28 58 T-TSP Wear 08S 0.4 10 0.13 126 P1 51OUL 573 A 28 58 T-TSP Wear 08S -0.7 14 0.19 123 P1 51OUL 573 A 28 60 T-TSP Wear 08S 0.4 18 0.26 136 P1 51OUL 573 A 28 62 T-TSP Wear 08S 0.4 13 0.17 134 P1 51OUL 573 A 28 62 T-TSP Wear 07S 0.4 8 0.11 126 P1 51OUL 573 A 28 64 T-TSP Wear 08S -0.6 14 0.19 111 P1 51OUL 573 A 28 64 T-TSP Wear 08S 0.4 17 0.24 125 P1 51OUL 573 A 28 65 T-TSP Wear 08S 0.4 8 0.1 114 P1 51OUL 571 A 28 65 T-TSP Wear 08S -0.7 10 0.13 118 P1 S5OUL 571 A 28 66 T-TSP Wear 08S 0.4 16 0.23 139 P1 51OUL 573 A 28 66 T-TSP Wear 07S 0.5 9 0.12 138 P1 51OUL 573 A 28 67 T-TSP Wear 08S 0.4 10 0.13 142 P1 51OUL 571 A 28 69 T-TSP Wear 08S 0.4 10 0.13 124 P1 51OUL 571 A 28 70 T-TSP Wear 08S -0.7 6 0.08 126 P1 51OUL 511 A 28 73 T-TSP Wear 08S 0.4 12 0.17 119 P1 51OUL 511 A 28 73 T-TSP Wear 08S -0.7 5 0.06 64 P1 51OUL 511 A 29 9 T-TSP Wear 14S 0.2 8 0.11 143 P1 51OUL 613 Page S of 43 Tuesday, April24, Tuesday, April 2612 24, 2012 Page 5 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location %d. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 29 67 T-TSP Wear 08S 0.4 8 0.1 133 P1 51OUL 573 A 29 67 T-TSP Wear 08S -0.7 16 0.22 115 P1 51OUL 573 A 29 69 T-TSP Wear 08S 0.3 12 0.17 123 P1 51OUL 571 A 30 7 T-TSP Wear 10S 0.3 9 0.12 142 P1 51OUL 613 A 30 39 T-TSP Wear 08S 0.4 10 0.13 142 P1 51OUL 573 A 30 41 T-TSP Wear 08S -0.7 7 0.09 87 P1 51OUL 573 A 30 53 T-TSP Wear 07S 0.4 10 0.14 152 P1 51OUL 573 A 30 55 T-TSP Wear 07S 0.5 9 0.11 140 P1 51OUL 573 A 30 57 T-TSP Wear 08S 0.4 9 0.11 139 P1 51OUL 573 A 30 59 T-TSP Wear 08S 0.4 11 0.14 135 P1 51OUL 573 A 30 61 T-TSP Wear 08S 0.5 7 0.09 107 P1 51OUL 573 A 30 64 T-TSP Wear 08S 0.4 7 0.09 133 P1 51OUL 571 A 30 74 T-TSP Wear 08S 0.4 7 0.09 141 P1 51OUL 515 A 31 40 T-TSP Wear 08S 0.4 10 0.13 123 P1 51OUL 573 A 31 47 T-TSP Wear 08S 0.3 17 0.26 135 P1 51OUL 571 A 31 47 T-TSP Wear 07S -0.7 10 0.13 136 P1 51OUL 571 A 31 58 T-TSP Wear 08S 0.4 7 0.09 116 P1 51OUL 573 A 31 62 T-TSP Wear 08S 0.4 15 0.22 134 P1 51OUL 573 A 31 63 T-TSP Wear 08S 0.4 13 0.19 138 P1 51OUL 571 A 31 64 T-TSP Wear 08S 0.5 8 0.11 123 P1 51OUL 573 A 31 65 T-TSP Wear 08S 0.4 18 0.27 139 P1 51OUL 571 A 31 66 T-TSP Wear 08S 0.4 10 0.12 149 P1 51OUL 573 A 31 67 T-TSP Wear 08S 0.4 7 0.1 141 P1 51OUL 571 A 31 67 T-TSP Wear 07S 0.5 8 0.1 135 P1 51OUL 571 Page 6of43 Tuesday, April 24,2 Tuesday, April 24,2 012 012 Page 6 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications, Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 31 70 T-TSP Wear 08S 0.3 9 0.12 138 P1 51OUL 571 A 31 71 T-TSP Wear 08S 0.4 0.1 139 P1 51OUL 515 A 31 74 T-TSP Wear 08S -0.7 0.1 118 P1 51OUL 517 A 31 75 T-TSP Wear 08S 0.4 0.1 141 P1 51OUL 515 A 31 76 T-TSP Wear 08S 0.4 0.16 128 P1 51OUL 517 A 32 27 T-TSP Wear 08S 0.4 0.11 130 P1 51OUL 649 A 32 29 T-TSP Wear 08S 0.3 0.1 132 P1 51OUL 605 A 32 56 T-TSP Wear 07S 0.5 0.22 136 P1 51OUL 571 A 32 65 T-TSP Wear 08S 0.4 0.11 121 P1 51OUL 573 A 32 71 T-TSP Wear 08S 0.4 0.11 140 P1 51OUL 515 A 32 74 T-TSP Wear 08S -0.7 0.1 87 P1 51OUL 517 A 32 90 T-TSP Wear 09S 0.4 0.12 159 P1 51OUL 515 A 33 21 T-TSP Wear 08S -0.8 0.09 98 P1 51OUL 621 A 33 29 T-TSP Wear 08S -0.7 0.11 114 P1 51OUL 605 A 33 30 T-TSP Wear 08S -0.8 0.15 114 P1 51OUL 603 A 33 42 T-TSP Wear 08S 0.4 0.11 129 P1 51OUL 571 A 33 57 T-TSP Wear 08S 0.4 0.12 120 P1 51OUL 573 A 33 58 T-TSP Wear 08S 0.5 0.1 135 P1 51OUL 571 A 33 59 T-TSP Wear 08S 0.4 0.12 113 P1 51OUL 573 A 33 69 T-TSP Wear 08S 0.4 0.13 142 P1 51OUL 573 A 33 72 T-TSP Wear 08S 0.4 0.09 124 P1 S1OUL 515 A 33 76 T-TSP Wear 08S 0.4 0.13 134 P1 51OUL 515 A 33 76 T-TSP Wear 07S 0.4 0.09 118 P1 51OUL 515 A 33 95 T-TSP Wear 10S -0.8 0.11 151 P1 51OUL 507 Tuesday, April 24, 2012 Page 7 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TJR19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 33 107 T-TSP Wear 09S 0.4 0.22 146 510XB 026 A 34 23 T-TSP Wear 08S5 -0.7 0.12 100 51OUL 619 A 34 34 T-TSP Wear 08S 0.4 0.12 147 51OUL 621 A 34 35 T-TSP Wear 08S -0.8 0.11 100 51OUL 619 A 34 57 T-TSP Wear 08S 0.5 0.08 121 51OUL 571 A 34 60 T-TSP Wear 08S 0.4 0.17 133 51OUL 573 A 34 65 T-TSP Wear 08S 0.4 0.11 55 51OUL 571 A 34 72 T-TSP Wear 08S 0.4 0.12 134 51OUL 573 A 34 74 T-TSP Wear 08S 0.4 0.12 131 510UL 515 A 34 79 T-TSP Wear 08S 0.4 0.14 139 51OUL 507 A 34 83 T-TSP Wear 08S 0.4 0.13 143 51OUL 507 A 35 37 T-TSP Wear 08S -0.7 0.11 121 51OUL 573 A 35 68 T-TSP Wear 08S 0.4 0.11 131 51OUL 573 A 35 69 T-TSP Wear 08S 0.5 0.15 143 51OUL 571 A 35 73 T-TSP Wear 08S 0.5 0.09 122 51OUL 571 A 35 75 T-TSP Wear 08S 0.5 0.12 123 51OUL 517 A 35 77 T-TSP Wear 08S 0.4 0.13 139 51OUL 517 A 35 79 T-TSP Wear 08S 0.4 0.19 130 51OUL 507 A 35 81 T-TSP Wear 08S 0.4 0.11 127 51OUL 507 A 35 82 T-TSP Wear 08S 0.4 0.16 131 51OUL 507 A 36 46 T-TSP Wear 08S 0.4 0.13 143 51OUL 571 A 36 65 T-TSP Wear 08S -0.7 0.2 127 51OUL 573 A 36 65 T-TSP Wear 08S 0.4 0.12 139 51OUL 573 A 36 67 T-TSP Wear 08S 0.5 0.12 140 51OUL 573 Tuesday, April 24, 2012 Page 8 of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications, Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 36 69 T-TSP Wear 08S 0.5 10 0.13 134 P1 51OUL 573 A 36 73 T-TSP Wear 07S 0.5 10 0.13 138 P1 51OUL 573 A 36 75 T-TSP Wear 08S 0.5 7 0.1 131 P1 51OUL 515 A 36 75 T-TSP Wear 07S 0.5 6 0.08 115 P1 51OUL 515 A 36 77 T-TSP Wear 08S 0.4 11 0.15 143 P1 51OUL 517 A 36 80 T-TSP Wear 08S 0.4 0.15 132 51OUL 515 A 36 80 T-TSP Wear 07S 0.4 0.08 122 51OUL 515 A 36 84 T-T Wear 08S 18.3 15.6 21.0 5.4 42 0.21 85 520PP 817 A 36 85 T-TSP Wear 08S 0.4 0.12 136 51OUL 517 A 36 86 T-TSP Wear 08S 0.4 0.18 138 51OUL 515 A 36 89 T-TSP Wear 10S -0.8 0.1 130 51OUL 517 A 36 112 T-TSP Wear 12S 0.3 0.11 145 510XB 026 A 37 7 T-TSP Wear 10S 0.3 0.15 155 51OUL 621 A 37 71 T-TSP Wear 08S 0.4 0.09 108 51OUL 577 A 37 72 T-TSP Wear 08S 0.5 0.14 142 51OUL 579 A 37 74 T-TSP Wear 08S 0.5 0.11 121 510UL 577 A 37 75 T-TSP Wear 08S 0.4 0.11 121 51OUL 515 A 37 76 T-TSP Wear 08S 0.4 0.1 130 51OUL 517 A 37 76 T-TSP Wear 08S -0.7 0.07 86 51OUL 517 A 37 81 T-TSP Wear 08S 0.5 0.08 105 51OUL 515 A 37 85 T-TSP Wear 08S 0.4 0.08 87 51OUL 515 A 37 85 T-T Wear 08S 18.3 15.7 21.0 5.4 42 0.19 85 520PP 817 A 37 86 T-TSP Wear 07S 0.5 0.14 130 51OUL 517 A 37 87 T-TSP Wear 08S 0.4 0.16 140 51OUL 515 A 37 110 T-TSP Wear 11S -0.7 8 0.1 133 P1 51OUL 517 Page 9 of 43 Tuesday, April 24, 2012 April24, Tuesday, 2012 Page 9 of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications,Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 38 13 T-TSP Wear 09S 0.4 9 0.12 149 P1 51OUL 619 A 38 16 T-TSP Wear 09S 0.4 10 0.14 162 P1 51OUL 621 A 38 35 T-TSP Wear 08S 0.4 8 0.11 150 P1 51OUL 619 A 38 71 T-TSP Wear 08S 0.4 12 0.16 152 P1 51OUL 577 A 38 83 T-TSP Wear 08S 0.5 19 0.29 122 P1 51OUL 517 A 38 86 T-TSP Wear 08S 0.4 8 0.11 124 P1 51OUL 515 A 38 86 T-TSP Wear 07S 0.5 6 0.08 98 P1 51OUL 515 A 38 87 T-TSP Wear 08S 0.4 8 0.11 140 P1 51OUL 517 A 38 89 T-TSP Wear 08S 0.4 16 0.23 132 P1 51OUL 517 A 39 35 T-TSP Wear 08S 0.4 10 0.15 145 P1 51OUL 619 A 39 37 T-TSP Wear l0s -0.8 7 0.1 126 P1 51OUL 619 A 39 40 T-TSP Wear 08S 0.5 11 0.14 137 P1 51OUL 577 A 39 46 T-TSP Wear 08S -0.7 11 0.14 89 P1 51OUL 577 A 39 64 T-TSP Wear 08S 0.5 7 0.09 118 P1 51OUL 577 A 39 67 T-TSP Wear 08S 0.5 8 0.11 122 P1 51OUL 579 A 39 70 T-TSP Wear 08S 0.5 13 0.17 140 P1 51OUL 577 A 39 74 T-TSP Wear 08S 0.5 13 0.16 134 P1 51OUL 577 A 39 78 T-TSP Wear 08S 0.4 6 0.08 99 P1 51OUL 515 A 39 80 T-TSP Wear 08S 0.4 6 0.08 71 P1 51OUL 515 A 39 81 T-TSP Wear 08S 0.4 13 0.18 130 P1 51OUL 517 A 39 83 T-TSP Wear 08S 0.5 .16 0.23 137 P1 51OUL 517 A 39 84 T-TSP Wear 08S 0.4 8 0.11 102 P1 51OUL 515 A 39 87 T-TSP Wear 08S 0.4 10 0.13 111 P1 51OUL 517 A 39 92 T-TSP Wear 08S 0.4 12 0.17 131 P1 51OUL 515 Page 10 of 43 Tuesday, Tuesday,.4pril 24, 2012 April24, Page 10 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 40 13 T-TSP Wear 09S 0.4 7 0.1 155 P1 510UL 619 A 40 30 T-TSP Wear 08S 0.4 7 0.1 136 P1 51OUL 621 A 40 53 T-TSP Wear 088 -0.7 11 0.14 132 P1 51OUL 577 A 40 55 T-TSP Wear 08S -0.7 10 0.12 136 P1 51OUL 577 A 40 75 T-TSP Wear 08S 0.4 7 0.09 122 P1 51OUL 577 A 40 76 T-TSP Wear 08S 0.5 6 0.08 134 P1 51OUL 515 A 40 78 T-TSP Wear 08S 0.4 6 0.09 65 P1 51OUL 515 A 40 81 T-TSP Wear 08S 0.5 12 0.16 123 P1 51OUL 517 A 40 82 T-TSP Wear 08S 0.4 6 0.07 105 P1 51OUL 515 A 40 84 T-TSP Wear 08S 0.4 9 0.12 117 P1 51OUL 515 A 40 85 T-TSP Wear 08S 0.5 8 0.11 130 P1 51OUL 517 A 40 86 T-TSP Wear 08S 0.4 14 0.2 133 P1 51OUL 515 A 40 87 T-TSP Wear 08S 0.5 12 0.16 134 P1 51OUL 517 A 40 89 T-TSP Wear 088 0.4 11 0.15 124 P1 51OUL 517 A 40 90 T-TSP Wear 085 0.4 9 0.13 126 P1 51OUL 515 A 40 112 T-TSP Wear 09S 0.4 9 0.12 149 P1 51OUL 515 A 41 12 T-TSP Wear 09S 0.4 10 0.14 155 P1 51OUL 619 A 41 14 T-TSP Wear 098 0.4 6 0.08 136 P1 51OUL 619 A 41 24 T-TSP Wear 08S 0.4 9 0.13 159 P1 51OUL 619 A 41 27 T-TSP Wear 08S 0.4 9 0.13 151 P1 51OUL 621 A 41 28 T-TSP Wear 085 0.4 8 0.11 150 P1 51OUL 619 A 41 41 T-TSP Wear 08S 0.4 7 0.09 123 P1 51OUL 579 A 41 48 T-TSP Wear 08S -0.7 11 0.13 90 P1 51OUL 577 A 41 60 T-TSP Wear 08S -0.7 11 0.15 137 P1 51OUL 577 Page 11 of 43 Tuesday, April 24, 2012 Tuesday, April24, 2012 Page 11 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications,Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 41 85 T-TSP Wear 08S 0.5 9 0.12 127 P1 510UL 517 A 41 95 T-TSP Wear 08S 0.3 10 0.13 140 P1 51OUL 517 A 41 114 T-TSP Wear 11S -0.7 8 0.1 134 P1 51OUL 517 A 41 116 T-TSP Wear loS -0.7 10 0.13 130 P1 510XB 026 A 42 27 T-TSP Wear 08S 0.4 8 0.11 148 P1 51OUL 619 A 42 47 T-TSP Wear 08S 0.4 11 0.16 143 P1 51OUL 581 A 42 50 T-TSP Wear 08S -0.7 7 0.09 128 P1 51OUL 583 A 42 51 T-TSP Wear 08S -0.7 8 0.12 131 P1 51OUL 583 A 42 52 T-TSP Wear 08S 0.5 9 0.12 137 P1 51OUL 581 A 42 57 T-TSP Wear 08S 0.4 10 0.15 145 P1 51OUL 583 A 42 76 T-TSP Wear 08S -0.7 6 0.09 125 P1 51OUL 515 A 42 76 T-TSP Wear 08S 0.5 6 0.09 128 P1 51OUL 515 A 42 77 T-TSP Wear 08S 0.4 16 0.23 129 P1 51OUL 517 A 42 78 T-TSP Wear 08S 0.4 7 0.09 111 P1 51OUL 515 A 42 79 T-TSP Wear 08S 0.5 10 0.12 134 P1 51OUL 517 A 42 80 T-TSP Wear 08S 0.5 6 0.08 110 P1 51OUL 515 A 42 81 T-TSP Wear 08S 0.4 12 0.16 106 P1 51OUL 517 A 42 82 T-TSP Wear 08S 0.4 9 .0.13 125 P1 51OUL 515 A 42 83 T-TSP Wear 08S 0.4 17 0.26 138 P1 51OUL 517 A 42 84 T-TSP Wear 08S 0.4 5 0.07 117 P1 51OUL 515 A 42 90 T-TSP Wear 08S 0.4 6 0.08 128 P1 51OUL 515 A 42 92 T-TSP Wear 08S 0.4 8 0.1 123 P1 51OUL 515 A 43 27 T-TSP Wear 08S -0.7 8 0.12 75 P1 51OUL 621 A 43 38 T-TSP Wear 08S -0.7 7 0.09 100 P1 51OUL 619
===== 2- M - -
Tuesday, April 24, 2012 Page 12 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TJR19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 43 53 T-TSP Wear 08S -0.7 8 0.11 117 P1 51OUL 583 A 43 54 T-TSP Wear 08S 0.5 8 0.11 132 P1 51OUL 581 A 43 77 T-TSP Wear 08S -0.8 9 0.11 123 P1 51OUL 517 A 43 84 T-TSP Wear 08S 0.5 6 0.08 90 P1 51OUL 515 A 43 88 T-TSP Wear 08S 0.4 10 0.14 114 P1 51OUL 515 A 43 90 T-TSP Wear 08S 0.4 0.11 140 51OUL 515 A 43 92 T-TSP Wear 08S 0.4 0.09 120 51OUL 515 A 43 99 T-TSP Wear 08S 0.4 0.09 131 51OUL 517 A 43 116 T-TSP Wear loS ý0.7 0.13 129 510XB 026 A 44 14 T-TSP Wear 09S 0.4 0.12 153 51OUL 619 A 44 16 T-TSP Wear 09S 0.4 0.09 148 51OUL 619 A 44 50 T-TSP Wear 08S -0.7 0.12 131 51OUL 581 A 44 51 T-TSP Wear 08S -0.7 0.16 132 51OUL 583 A 44 59 T-TSP Wear 08S -0.7 0.11 106 51OUL 583 A 44 61 T-TSP Wear 08S -0.7 0.09 121 51OUL 583 A 44 65 T-TSP Wear 08S 0.5 0.09 113 51OUL 583 A 44 79 T-TSP Wear 08S -0.7 0.11 128 51OUL 523 A 44 82 T-TSP Wear 08S 0.5 0.09 98 51OUL 525 A 44 84 T-TSP Wear 08S 0.5 0.18 131 51OUL 525 A 44 90 T-TSP Wear 08S 0.4 0.12 138 51OUL 525 A 44 95 T-TSP Wear 08S 0.4 0.18 137 51OUL 523 A 44 111 T-TSP Wear 10S -0.7 0.11 139 51OUL 525 A 44 113 T-TSP Wear 09S 0.4 13 0.18 142 P1 51OUL 525 A 44 115 T-TSP Wear 10S 0.4 12 0.15 147 P1 51OUL 525 CIMMAM=
Pag 13MMof 43 &= 2 -- --
201 Apil4 Tueday Tuesday, April 24, 2012 Page 13 of 43
TM1-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications, Outage T1R19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 44 117 T-TSP Wear 10S -0.7 10 0.13 143 P1 510XB 026 A 45 51 T-TSP Wear 08S 0.5 8 0.1 134 P1 51OUL 581 A 45 52 T-TSP Wear 08S -0.7 7 0.09 132 P1 51OUL 583 A 45 64 T-TSP Wear 08S 0.5 9 0.13 146 P1 51OUL 583 A 45 66 T-TSP Wear 08S -0.7 9 0.13 128 P1 51OUL 583 A 45 78 T-TSP Wear 08S -0.7 9 0.1i 137 P1 51OUL 525 A 45 80 T-TSP Wear 08S -0.7 10 0.13 136 P1 51OUL 525 45 86 T-TSP Wear 08S -0.7 7 0.08 103 P1 51OUL 525 45 88 T-TSP Wear 08S 0.4 9 0.11 142 P1 51OUL 525 45 90 T-TSP Wear 08S 0.4 10 0.13 126 P1 51OUL 525 45 90 T-TSP Wear 08S -0.7 7 0.09 83 P1 51OUL 525 45 113 T-TSP Wear 09S 0.4 14 0.19 135 P1 51OUL 523 45 114 T-TSP Wear 09S 0.5 7 0.09 137 P1 51OUL 525 46 20 T-TSP Wear 09S 0.4 6 0.09 147 P1 51OUL 619 46 28 T-TSP Wear 08S 0.4 10 0.14 153 P1 51OUL 621 46 58 T-TSP Wear 08S -0.7 10 0.14 146 P1 51OUL 583 46 87 T-TSP Wear 08S -0.7 7 0.09 80 P1 51OUL 525 46 90 T-TSP Wear 08S 0.5 9 0.12 128 P1 51OUL 523 46 98 T-TSP Wear 08S 0.4 11 0.15 135 P1 51OUL 505 46 102 T-TSP Wear 08S 0.4 9 0.12 142 P1 51OUL 523 46 113 T-TSP Wear 09S 0.4 10 0.13 151 P1 51OUL 523 46 118 T-TSP Wear 10S 0.4 11 0.16 153 P1 510XB 026 47 18 T-TSP Wear 09S 0.3 7 0.11 151 P1 51OUL 621 47 26 T-T Wear 08S 19.0 11 16.1 22.0 5.9 52 0.31 85 5 520PP 815 MM3- ý Page 14 of 43 2012 24, 2012 Tuesday, AprilTuesday, 24, April Page 14of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications,Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 47 26 T-T Wear 08S 19.1 5 17.1 21.0 3.9 47 0.14 80 5 520PP 815 A 47 56 T-TSP Wear 08S -0.7 12 0.18 144 P1 51OUL 583 A 47 72 T-T Wear 07S 21.7 7 19.4 24.0 4.6 53 0.36 109 93 510XP 823 A 47 86 T-TSP Wear 08S -0.7 7 0.09 101 P1 510UL 525 A 47 87 T-TSP Wear 08S 0.5 10 0.12 139 P1 51OUL 523 A 47 89 T-TSP Wear 08S 0.4 8 0.1 122 P1 51OUL 523 A 47 90 T-TSP Wear 08S 0.5 13 0.18 142 P1 51OUL 525 A 47 117 T-TSP Wear 10S -0.7 10 0.13 151 P1 510XB 026 A 47 118 T-TSP Wear 10S -0.7 10 0.14 138 P1 510XB 026 A 48 8 T-TSP Wear 14S 0.2 5 0.07 134 P1 51OUL 629 A 48 24 T-TSP Wear 08S -0.7 6 0.09 82 P1 51OUL 627 A 48 27 T-T Wear 08S 19.0 7 17.0 21.0 4.0 53 0.33 61 81 510XP 823 A 48 28 T-T Wear 08S 19.1 11 16.1 22.0 5.9 47 0.36 88 5 520PP 815 A 48 61 T-TSP Wear 08S -0.7 9 0.12 143 P1 51OUL 583 A 48 73 T-T Wear 07S 21.5 8 18.9 24.0 5.1 53 0.44 62 81 510XP 823 A 48 94 T-TSP Wear 08S 0.4 17 0.24 136 P1 51OUL 525 A 48 95 T-TSP Wear 08S 0.4 13 0.17 142 P1 51OUL 523 A 48 98 T-TSP Wear 08S 0.4 16 0.22 121 P1 51OUL 525 A 48 99 T-TSP Wear 09S 0.4 8 0.1 139 P1 51OUL 505 A 48 99 T-TSP Wear 08S -0.7 7 0.1 127 P1 51OUL 505 A 49 7 T-TSP Wear 10S 0.1 7 0.11 146 P1 51OUL 629 A 49 18 T-TSP Wear 09S 0.3 10 0.17 149 P1 51OUL 629 A 49 75 T-TSP Wear 03S 0.6 10 0.15 153 P1 51OUL 581 A 49 92 T-TSP Wear 08S 0.5 14 0.2 128 P1 51OUL 525 Tuesday, April 24, 2012 Page 15 of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19) , Exhibit I SG A, All Service InducedIndications, Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 49 94 T-TSP Wear 08S 0.4 13 0.17 136 P1 51OUL 525 A 49 95 T-TSP Wear 08S 0.4 0.1 119 P1 51OUL 523 A 49 96 T-TSP Wear 08S 0.4 0.08 134 P1 51OUL 525 A 49 104 T-TSP Wear 09S 0.4 0.09 126 P1 51OUL 525 A 49 122 T-TSP Wear loS 0.4 0.12 156 P1 510XB 026 A 50 7 T-TSP Wear 10S 0.0 0.1 141 P1 51OUL 629 A 50 23 T-TSP Wear 08S -0.7 0.1 99 P1 51OUL 629 A 50 24 T-TSP Wear 08S -0.7 0.1 93 P1 51OUL 627 A 50 29 T-T Wear 08S 17.6 16.1 19.0 2.9 37 0.09 94 5 520PP 821 A 50 42 T-TSP Wear 03S 0.6 0.14 147 P1 51OUL 581 A 50 67 T-TSP Wear 07S 0.5 0.12 133 P1 51OUL 583 A 50 96 T-TSP Wear 08S 0.4 0.12 145 P1 51OUL 523 A 50 99 T-T Wear 08S 18.5 15.9 21.0 5.1 53 0.27 77 33 510xP 823 A 50 100 T-TSP Wear 08S -0.7 0.11 144 P1 51OUL 523 A 50 111 T-TSP Wear 10S -0.8 0.13 134 P1 51OUL 525 A 50 115 T-TSP Wear 10S -0.7 0.12 138 P1 51OUL 525 A 50 117 T-TSP Wear 10S -0.7 0.17 139 P1 51OUL 525 A 50 120 T-TSP Wear 10S -0.7 0.11 133 P1 510XB 030 A 51 7 T-TSP Wear 12S 0.3 0.14 140 P1 51OUL 629 A 51 21 T-TSP Wear 08S -0.7 0.13 95 P1 51OUL 629 A 51 29 T-T Wear 08S 17.7 16.5 19.0 2.5 42 0.14 86 5 520PP 821 A 51 30 T-T Wear 08S 18.3 16.5 20.0 3.5 42 0.15 82 5 520PP 815 A 51 32 T-T Wear 08S 18.1 16.2 20.0 3.8 53 0.26 110 81 510XP 823 A 51 49 T-TSP Wear 08S -0.7 0.08 112 P1 51OUL 583 Tuesday, April 24, 2012 Page 16 of 43
TMI-12-0 71, TMI-1 Steam GeneratorTube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications, Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 51 92 T-TSP Wear 08S 0.5 10 0.12 130 P1 51OUL 525 A 51 94 T-TSP Wear 08S 0.4 9 0.11 140 P1 51OUL 525 A 51 96 T-TSP Wear 08S 0.4 14 0.19 122 P1 51OUL 525 A 51 96 T-TSP Wear 08S -0.6 9 0.11 84 P1 51OUL 525 A 51 98 T-TSP Wear 08S 0.4 16 0.22 138 P1 51OUL 525 A 51 98 T-TSP Wear 08S -0.7 15 0.2 106 P1 51OUL 525 A 51 100 T-TSP Wear 08S -0.7 9 0.12 83 P1 51OUL 525 A 51 100 T-TSP Wear 08S 0.4 9 0.12 128 P1 51OUL 525 A 51 119 T-TSP Wear 10S -0.7 13 0.19 140 P1 510XB 030 A 52 22 T-TSP Wear 08S -0.7 7 0.11 86 P1 51OUL 629 A 52 39 TITSP Wear 08S -0.7 7 0.1 120 P1 51OUL 627 A 52 68 T-TSP Wear 08S -0.7 9 0.13 141 P1 51OUL 583 A 52 68 T-TSP Wear 08S 0.5 10 0.14 149 P1 51OUL 583 A 52 97 T-TSP Wear 08S -0.7 9 0.12 104 P1 51OUL 525 A 52 97 T-TSP Wear 08S 0.4 16 0.22 131 P1 51OUL 525 A 52 98 T-TSP Wear 08S -0.7 11 0.14 140 P1 51OUL 523 A 52 98 T-TSP Wear 08S 0.4 19 0.29 127 P1 51OUL 523 A 52 98 T-TSP Wear 07S 0.5 7 0.09 133 P1 51OUL 523 A 52 99 T-TSP Wear 08S -0.7 8 0.1 86 P1 51OUL 525 A 52 99 T-TSP Wear 08S 0.4 13 0.17 130 P1 51OUL 525 A 52 102 T-TSP Wear 08S 0.4 11 0.15 142 P1 51OUL 523 A 52 103 T-TSP Wear 08S -0.7 9 0.11 86 P1 51OUL 525 A 52 123 T-TSP Wear 10S -0.6 11 0.15 141 P1 510XB 030 A 52 123 T-TSP Wear 09S 0.4 10 0.14 136 P1 510XB 030 A 53 22 T-TSP Wear 08S -0.7 8 0.12 91 P1 51OUL 627 Tuesday, April 24, 2012 Page 17 of 43
TMI-12-O071, TMI-1 Steam GeneratorTube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 53 98 T-TSP Wear 08S 0.4 6 0.08 119 P1 51OUL 523 A 53 98 T-TSP Wear 08S -0.7 0.09 123 P1 51OUL 523 A 53 100 T-TSP Wear 08S 0.4 0.22 126 P1 51OUL 523 A 53 100 T-TSP Wear 08S -0.7 0.16 130 P1 51OUL 523 A 53 100 T-TSP Wear 07S 0.5 0.09 131 P1 51OUL 523 A 53 102 T-TSP Wear 08S 0.4 0.15 139 P1 51OUL 523 A 53 103 T-TSP Wear 08S -0.7 0.09 98 P1 51OUL 525 A 53 103 T-TSP Wear 08S 0.4 0.33 134 P1 51OUL 525 A 53 108 T-TSP Wear 08S -0.7 0.1 132 P1 51OUL 523 A 53 120 T-TSP Wear 09S 0.4 0.16 139 P1 51OUL 523 A 53 124 T-TSP Wear 10S -0.6 0.18 140 P1 51OXB 030 A 54 17 T-TSP Wear 09S 0.4 0.11 143 P1 51OUL 639 A 54 97 T-TSP Wear 08S 0.4 0.13 150 P1 51OUL 529 A 54 98 T-TSP Wear 08S 0.4 0.11 137 P1 51OUL 527 A 54 99 T-TSP Wear 08S 0.5 0.13 115 P1 51OUL 529 A 54 100 T-TSP Wear 08S 0.4 0.2 130 P1 51OUL 527 A 54 101 T-TSP Wear 08S -0.7 0.13 99 P1 51OUL 529 A 54 101 T-TSP Wear 08S 0.4 0.38 .133 P1 51OUL 529 A 54 103 T-TSP Wear 08S -0.7 0.11 102 P1 51OUL 529 A 54 104 T-T Wear 08S 17.9 14.9 21.0 6.1 48 0.21 88 5 520PP 817 A 54 105 T-TSP Wear 08S 0.4 0.34 131 P1 51OUL 525 A 54 121 T-TSP Wear 09S 0.4 0.17 150 P1 51OUL 525 A 54 122 T-TSP Wear 09S 0.5 0.18 145 P1 51OUL 523 A 55 21 T-TSP Wear 08S -0.7 0.14 79 P1 51OUL 639 A 55 99 T-TSP Wear 08S 0.4 0.16 137 P1 51OUL 527 Page 18 of 43 Tuesday, April24, Tuesday, April 2012 24, 2012 Page 18 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TJR19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind. Axial Cire.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 55 102 T-TSP Wear 08S 0.4 13 0.16 131 P1 51OUL 529 A 55 102 T-TSP Wear 08S -0.7 0.17 114 P1 51OUL 529 A 55 104 T-T Wear 08S 18.0 16.1 20.0 3.9 53 0.27 75 125 510XP 823 A 55 105 T-TSP Wear 08S 0.4 0.27 136 P1 51OUL 527 A 55 105 T-T Wear 08S 17.5 15.1 20.0 5.0 26 0.22 83 .5 520PP 817 A 55 105 T-T Wear 08S 17.7 16.5 19.0 2.6 26 0.1 73 5 520PP 817 A 55 106 T-TSP Wear 08S -0.7 0.1 95 P1 51OUL 529 A 55 106 T-TSP Wear 08S 0.4 0.2 154 P1 51OUL 529 A 55 111 T-TSP Wear 08S 0.4 0.07 129 P1 51OUL 527 A 55 118 T-TSP Wear 10S -0:7 0.18 134 P1 51OUL 529 A 55 118 T-TSP Wear 09S 0.4 0.17 143 P1 51OUL 529 A 55 120. T-TSP Wear 10S -0.7 0.09 119 P1 51OUL 529 A 55 120 T-TSP Wear 09S 0.4 0.23 144 P1 51OUL 529 A 55 123 T-TSP Wear 09S 0.5 0.13 137 P1 51OUL 527 A 56 23 T-T Wear 08S 19.4 15.8 23.0 7.2 52 0.48 82 5 520PP 815 A 56 46 T-TSP Wear 03S 0.5 0.11 133 P1 51OUL 593 A 56 101 T-TSPWear 08S 0.4 0.2 132 P1 51OUL 529 A 56 102 T-TSP Wear 08S 0.4 0.19 123 P1 51OUL 527 A 56 - 103 T-TSP Wear 08S 0.4 0.38 134 P1 51OUL 529 A 56 103 T-TSP Wear 08S -0.7 0.09 84 P1 51OUL 529 A 56 103 T-TSP Wear 07S 0.5 0.14 144 -, P1 51OUL 529 A 56 104 T-TSP Wear 08S -0.7 0.12 130 P1 51OUL 527 A 56 104 T-TSP Wear 08S 0.4 0.11 143 P1 51OUL 527 A 56 105 T-TSP Wear 08S -0.8 0.07 80 P1 51OUL 529 A 56 105 T-TSP Wear 08S 0.4 0.38 131 P1 51OUL 529 A 56 119 T-TSP Wear 10S -0.7 0.12 139 P1 51OUL 529 Tuesday, A1pril 24, 2012 Page 19 of 43.
TMI-12-O071, TMI-1 Steam GeneratorTube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications, Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal I
A 56 125 T-TSP Wear 10S -0.7 13 0.16 136 P1 51OUL 529 A 57 24 T-TSP wear 08S -0.7 8 0.12 58 P1 51OUL 639 A 57 24 T-T Wear 08S 19.5 15 16.0 23.0 7.0 47 0.54 84 5 520PP 815 A 57 *29 T-T Wear 08S 18.7 6 16.4 21.0 4.6 42 0.22 84 5 520PP 821 A 57 37 T-TSP Wear 08S -0.8 7 0.1 119 P1 51OUL 627 A 57 101 T-TSP Wear 08S 0.4 14 0.18 134 P1 51OUL 529 A 57 102 T-TSP Wear 08S 0.4 5 0.07 90 P1 51OUL 527 57 103 T-TSP Wear 08S 0.4 24 0.36 132 P1 51OUL 529 57 103 T-TSP Wear 08S -0.7 10 0.12 95 P1 51OUL 529 57 104 T-TSP Wear 08S 0.4 9 0.12 135 P1 51OUL 527 57 106 T-TSP Wear 08S 0.4 16 0.23 140 P1 51OUL 527 58 29 T-T Wear 08S 18.7 6 16.4 21.0 4.6 42 0.2 91 5 520PP 815 58 35 T-TSP Wear 08S 0.5 13 0.2 142 P1 51OUL 639 58 103 T-TSP Wear 08S 0.4 25 0.39 132 P1 51OUL 529 58 104 T-TSP Wear 08S 0.5 14 0.2 130 P1 51OUL 527 58 105 T-TSP Wear 08S 0.4 15 0.19 133 P1 51OUL 529 58 105 T-TSP Wear 08S -0.7 8 0.1 90 P1 51OUL 529 58 106 T-TSP Wear 08S -0.7 7 0.09 113 P1 51OUL 527 59 102 T-TSP Wear 08S 0.4 16 0.23 136 P1 51OUL 527 59 103 T-TSP Wear 08S 0.4 12 0.15 139 P1 51OUL 529 59 104 T-TSP Wear 08S 0.4 9 0.11 124 P1 51OUL 527 59 105 T-TSP Wear 08S -0.7 11 0.13 100 P1 51OUL 529 59 105 T-TSP Wear 08S 0.4 17 0.22 123 P1 51OUL 529 59 106 T-T Wear 08S 18.3 4 16.6 20.0 3.4 37 0.13 89 5 520PP 819 e2 f4 Tuesday, ApiM 4 02 Tuesday, April 24,2012 Page20of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TJR19) , Exhibit I SG A, All Service Induced Indications,Outage TJR19 Location % Indc IndL Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 59 107 T-T Wear 08S 18.4 3 16.8 20.0 3.2 42 0.09 78 5 520PP 817 A 59 107 T-TSP Wear 08S 0.4 18 0.24 144 P1 51OUL 529 A 59 107 T-TSP Wear 08S -0.7 9 0.1 93 P1 51OUL 529 A 59 108 T-TSP Wear 08S 0.4 13 0.18 141 P1 51OUL 527 A 59 109 T-TSP Wear 08S -0.7 10 0.12 62 P1 51OUL 529 A 59 109 T-TSP Wear 08S 0.4 15 0.19 137 P1 51OUL 529 A 59 125 T-TSP Wear 11S -0.7 11 0.13 143 P1 51OUL 529 A 60 29 T-T Wear 08S 18.9 7 16.8 21.0 4.2 42 0.24 76 5 520PP 815 A 60 29 T-TSP Wear 08S 0.4 11 0.15 156 P1 51OUL 643 A 60 34 T-T Wear 08S 19.1 2 18.2 20.0 1.8 37 0.06 75 5 520PP 821 A 60 103 T-TSP Wear 08S 0.4 9 0.11 107 P1 51OUL 529 A 60 103 T-TSP Wear 08S -0.7 10 0.12 61 P1 51OUL 529 1
A 60 105 T-TSP Wear 08S 0.5 10 0.12 17 P1 51OUL 529 1
A 60 106 T-TSP Wear 08S 0.4 11 0.14 31 P1 51OUL 527 1
A 60 107 T-TSP Wear 08S -0.7 10 0.12 01 P1 51OUL 529 1
A 60 107 T-TSP Wear 08S 0.4 24 0.36 29 P1 51OUL 529 A 60 109 T-T Wear 08S 17.6 4 15.3 20.0 4.7 48 0.14 85 5 520PP 817 A 60 125 T-TSP Wear 09S 0.4 13 0.17 136 P1 51OUL 529 A 61 24 T-TSP Wear 09S -0.7 7 0.11 139 P1 51OUL 641 A 61 26 T-T Wear 08S 18.7 6 16.4 21.0 4.6 42 0.21 81 5 520PP 815 A 61 29 T-T Wear 08S 18.8 7 16.7 21.0 4.3 48 0.25 81 5 520PP 821 A 61 34 T-T Wear 08S 20.5 3 18.0 23.0 5.0 58 0.12 68 5 520PP 821 A 61 35 T-T Wear 08S 20.5 4 18.1 23.0 4.9 68 0.12 65 5 520PP 815 A 61 38 T-TSP Wear 08S 0.4 10 0.16 141 P1 51OUL 641 A 61 106 T-TSP Wear 08S. 0.4 8 0.1 128 P1 51OUL 529 Page 21 of 43 i2 Tuesday, April 24, 20Tuesday, April 24, 20 12 Page 21 of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TJR19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 61 107 T-TSP Wear 08S 0.4 18 0.27 139 51OUL 527 A 61 108 T-TSP Wear 08S 0.4 16 0.21 149 51OUL 529 A 61 108 T-TSP Wear 08S -0.7 8 0.09 63 51OUL 529 A 61 110 T-TSP Wear 08S -0.7 10 0.12 120 51OUL 529 A 61 110 T-TSP Wear 08S 0.4 12 0.15 146 51OUL 529 A 61 110 T-T Wear 08S 18.4 2 16.8 20.0 3.2 37 0.07 72 520PP 819 A 61 110 T-T Wear 08S 17.7 4 15.5 20.0 4.5 42 0.17 87 520PP 819 A 61 111 T-TSP Wear 08S 0.4 18 0.27 134 51OUL 527 A 61 116 T-TSP Wear 1is -0.7 11 0.13 136 51OUL 529 A 61 125 T-TSP Wear 09S 0.4 6 0.08 127 51OUL 527 A 62 1 T-TSP Wear 09S -0.7 8 0.13 152 510XB 042 A 62 25 T-T Wear 08S 19.0 7 16.1 22.0 5.9 42 0.22 83 520PP 815 A 62 31 T-T Wear 08S 19.6 7 17.2 22.0 4.8 42 0.25 83 520PP 821 A 62 32 T-T Wear 08S 19.7 7 17.4 22.0 4.6 42 0.21 87 520PP 815 A 62 34 T-T Wear 08S 19.3 3 17.6 21.0 3.4 48 0.11 78 520PP 821 A 62 35 T-T Wear 08S 18.9 3 17.8 20.0 2.2 38 0.09 85 520PP 821 A 62 105 T-TSP Wear 08S 0.4 21 0.3 137 51oUL 529 A 62 106 T-TSP Wear 08S 0.4 11 0.14 121 51OUL 527 A 62 108 T-TSP Wear 08S 0.4 13 0.18 131 51OUL 527 A 62 123 T-TSP Wear 09S 0.5 12 0.14 143 51OUL 529 A 63 4 T-TSP Wear los 0.4 9 0.13 156 51OUL 679 A 63 25 T-T Wear 08S 19.2 4 17.3 21.0 3.7 53 0.16 75 520PP 821 A 63 25 T-T Wear 08S 19.2 2 18.3 20.0 1.7 32 0.07 82 520PP 821 A 63 31 T-TP Wear 08S 0.4 11 0.15 151 51OUL 643 A 63 109 T-TSP Wear 08S 0.4 19 0.3 129 51OUL 527 Page 22 of 43 Tuesday, April 24, 2012 Tuesday, April24, 2012 Page 22 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1RJ9 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 63 110 T-TSP Wear 08S 0.4 14 0.18 144 P1 51OUL 529 A 63 113 T-TSP Wear 08S -0.7 8 0.11 138 P1 51OUL 527 A 63 114 T-TSP Wear 08S -0.7 8 0.1 114 P1 51OUL 529 A 63 126 T-TSP Wear 09S 0.4 13 0.16 142 P1 51OUL 529 A 64 2 T-TSP Wear los -0.7 12 0.21 135 P1 510XB 042 A 64 19 T-TSP Wear 09S 0.3 7 0.09 136 P1 51OUL 643 A 64 20 T-TSP Wear 09S -0.8 8 0.12 142 P1 51OUL 641 A 64 25 T-T Wear 08S 19.3 4 17.6 21.0 3.4 42 0.13 77 5 520PP 815 A 64 108 T-TSP Wear 08S 0.4 23 0.37 136 P1 51OUL 527 A 64 108 T-TSP Wear 07S 0.5 6 0.08 119 P1 51OUL 527 A 64 109 T-TSP Wear 08S -0.7 9 0.11 93 P1 51OUL 529 A 64 109 T-TSP Wear 08S 0.4 15 0.19 140 P1 51OUL 529 A 64 111 T-TSP Wear 08S 0.4 16 0.21 146 P1 51OUL 529 A 64 113 T-TSP Wear 08S -0.7 9 0.1 107 P1 51OUL 529 A 64 114 T-TSP Wear 08S -0.7 9 0.11 131 P1 51OUL 527 A 64 115 T-TSP Wear 08S -0.7 9 0.1 107 P1 51OUL 529 A 64 117 T-TSP Wear 08S :0.8 9 0.1 130 P1 51OUL 529 A 64 129 T-TSP Wear 10S 0.4 13 0.18 149 P1 510XB 030 A 65 2 T-TSP Wear 10S -0.7 9 0.16 136 P1 510XB 042 A 65 4 T-TSP Wear 09S 0.4 7 0.11 144 P1 51OUL 679 A 65 22 T-TSP Wear 08S 0.3 8 0.11 133 P1 51OUL 643 A 65 107 T-TSP Wear 08S 0.4 17 0.26 139 P1 51OUL 539 A 65 117 T-TSP Wear 08S -0.7 10 0.11 109 P1 51OUL 541 A 66 104 T-TSP Wear 08S 0.4 16 0.18 144 P1 51OUL 541
= M M zzzý Tuesday, April 24, 2012 Page23 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications,Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 66 108 T-TSP Wear 08S 0.4 20 0.25 142 P1 51OUL 541 A 66 108 T-TSP Wear 08S -0.7 7 0.07 102 P1 51OUL 541 A 66 109 T-TSP Wear 08S -0.7 11 0.15 109 P1 51OUL 505 A 66 109 T-TSP Wear 08S 0.4 14 0.2 135 P1 51OUL 505 A 66 110 T-TSP Wear 08S 0.4 7 0.1 128 P1 51OUL 505 A 66 113 T-TSP Wear 08S 0.4 14 0.17 154 P1 51OUL 541 A 66 115 T-TSP Wear 08S -0.7 7 0.07 98 P1 51OUL 541 A 67 2 T-TSP Wear 10S 0.4 9 0.15 152 P1 510XB 042 A 67 12 T-TSP Wear 09S 0.3 9 0.12 146 P1 51OUL 643 A 67 17 T-TSP Wear 09S 0.3 6 0.09 141 P1 51OUL 641 A 67 108 T-TSP Wear 08S 0.5 9 0.12 130 P1 51OUL 543 A 67 113 T-TSP Wear 08S 0.3 12 0.16 144 P1 51OUL 543 A 67 116 T-TSP Wear 08S -0.7 6 0.08 87 P1 51OUL 545 A 67 118 T-TSP Wear 11S -0.8 8 0.11 121 P1 51OUL 545 A 67 130 T-TSP Wear 10S 0.3 17 0.25 140 P1 510XB 030 A 68 110 T-TSP Wear 08S 0.4 12 0.17 144 P1 51OUL 543 A 68 112 T-TSP Wear 08S 0.4 20 0.32 130 P1 51OUL 543 A 69 11 T-TSP Wear 09S 0.4 7 0.11 152 P1 51OUL 675 A 69 107 T-TSP Wear 08S 0.4 11 0.15 133 P1 51OUL 543 A 69 109 T-TSP Wear 08S 0.4 9 0.11 139 P1 51OUL 543 A 69 111 T-TSP Wear 08S 0.4 10 0.13 141 P1 51OUL 543 A 70 24 T-TSP Wear 10S -0.8 8 0.11 123 P1 51OUL 643 A 70 98 T-TSP Wear 08S -0.7 13 0.17 136 P1 51OUL 543 A 70 99 T-TSP Wear 08S -0.7 10 0.13 110 P1 51OUL 545 Page 24 of 43 April24, Tuesday, Tuesday,.4pril 24, 2012 2012 Page 24 of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications,Outage TIRJ9 Location % Ind. Indt Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 70 100 T-TSP Wear 08S -0.7 8 0.11 111 P1 51OUL 543 A 70 103 T-T Wear 08S 18.9 4 16.9 21.0 4.2 53 0.17 91 5 520PP 819 A 70 106 T-TSP Wear 08S 0.5 15 0.21 139 P1 51OUL 543 A 70 107 T-TSP Wear 08S 0.4 11 0.15 147 P1 51OUL 545 A 70 110 T-TSP Wear 08S 0.4 11 0.15 141 P1 51OUL 543 A 70 115 T-TSP Wear 08S 0.4 11 0.15 139 P1 51OUL 545 A 71 1 T-TSP Wear 09S -0.7 9 0.15 141 P1 510XB 042 A 71 14 T-TSP Wear 09S 0.3 6 0.08 145 P1 51OUL 643 A 71 15 T-TSP Wear 09S 0.3 7 0.09 148 P1 51OUL 643 A 71 17 T-TSP Wear 09S 0.3 10 0.14 138 P1 51OUL 643 A 71 25 T-TSP Wear 08S 0.3 10 0.14 144 P1 51OUL 643 A 71 104 T-T Wear 08S 19.0 4 17.1 21.0 3.9 42 0.17 89 520PP 817 A 71 110 T-TSP Wear 08S 0.4 16 0.24 130 P1 51OUL 543 A 71 112 T-TSP Wear 08S 0.4 24 0.41 126 P1 51OUL 543 A 71 112 T-TSP Wear 07S 0.5 9 0.11 134 P1 51OUL 543 A 71 131 T-TSP Wear 10S 0.4 12 0.17 147 P1 510XB 030 A 72 12 T-TSP Wear 09S 0.3 9 0.12 151 P1 51OUL 643 A 72 14 T-TSP Wear 09S 0.4 6 0.08 142 P1 51OUL 643 A 72 98 T-T Wear 08S 24.1 3 21.3 27.0 5.7 48 0.08 98 5. 520PP 817 A 72 98 T-T Wear 08S 15.4 3 12.8 18.0 5.2 48 0.1 88 5 520PP 817 A 72 98 T-T Wear 08S 19.6 3 17.3 22.0 4.7 37 0.08 97 5 520PP 817 A 72 99 T-TSP Wear 07S 0.5 7 0.1 127 P1 51OUL 545 A 72 101 T-TSP Wear 08S 0.5 8 0.11 135 P1 51OUL 545 A 72 103 T-TSP Wear 08S 0.4 0.07 119 P1 51OUL 545 Page 25 of 43 Tuesday, April 2012April24, Tuesdaj',
24, 2012 Page 2-5of 43
TMI-12--071, TMI-1 Steam GeneratorTube Inspection Report (TIR19) , Exhibit I SG A, All Service Induced Indications, Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 72 104 T-TSP Wear 08S 0.5 10 0.13 133 P1 51OUL 543 A 72 105 T-TSP Wear 08S 0.4 0.15 135 P1 51OUL 545 A 72 106 T-TSP Wear 08S 0.5 0.17 137 P1 51OUL 543 A 72 107 T-TSP Wear 08S 0.5 0.09 135 P1 51OUL 545 A 72 108 T-TSP Wear 08S 0.4 0.1 129 P1 51OUL 543 A 72 131 T-TSP Wear 10S 0.3 0.25 134 P1 510XB .030 A 73 14 T-TSP Wear 09S 0.3 0.12 145 P1 51OUL 643 A 73 16 T-TSP Wear 09S 0.3 0.09 143 P1 51OUL 643 A 73 98 T-TSP Wear 08S -0.7 0.12 134 P1 51OUL 543 A 73 103 T-TSP Wear 08S 0.5 0.11 130 P1 51OUL 545 A 73 105 T-TSP Wear 08S -0.7 0.15 117 P1 51OUL 545 A 73 106 T-TSP Wear 08S 0.4 0.22 144 P1 51OUL 543 A 73 107 T-TSP Wear 08S 0.4 0.35 129 P1 51OUL 545 A 73 108 T-TSP Wear. 08S -0.7 0.1 135 P1 51OUL 543 A 73 109 T-TSP Wear 08S 0.4. 0.19 140 P1 51OUL 545 A 73 110 T-TSP Wear 08S 0.4 0.19 135 P1 51OUL 543 A 73 132 T-TSP Wear 10S 0.3 0.14 134 P1 510XB 030 A 74 98 T-TSP Wear 08S -0.7 0.09 125 P1 51OUL 543 A 74 101 T-TSP Wear 08S -0.7 0:12 122 P1 51OUL 545 A 74 101 T-TSP Wear 08S 0.4 0.14 147 P1 51OUL 545 A 74 102 T-TSP Wear 08S 0.5 0.1 137 P1 51OUL 543 A 74 104 T-TSP Wear 08S 0.5 0.09 128 P1 51OUL 543 A 74 105 T-TSP Wear 08S 0.4 0.11 148 P1 51OUL 545 A 74 106 T-TSP Wear 08S 0.4 0.16 136 P1 51OUL 543 Apil4 201 Tusdy -- Page 26 of 43 Tuesday, April 24, 2012 Page26 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications, Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 74 107 T-TSP Wear 08S -0.7 10 0.14 121 P1 510UL 545 A 74 123 T-TSP Wear loS 0.3 6 0.08 153 P1 51OUL 545 A 75 15 T-TSP Wear 09S 0.3 8 0.11 149 P1 510UL 643 A 75 16 T-TSP Wear 09S 0.3 7 0.09 142 P1 51OUL 643 A 75 23 T-TSP Wear 08S 0.4 9 0.12 148 P1 51OUL 643 A 75 101 T-TSP Wear 08S 0.5 11 0.15 141 P1 51OUL 545 A 75 102 T-TSP Wear 08S -0.7 10 0.13 129 P1 51OUL 543 A 75 103 T-TSP Wear 08S 0.4 8 0.1 132 P1 51OUL 545 A 75 104. T-TSP Wear 08S 0.4 9 0.12 126 P1 51OUL 543 A 75 105 T-TSP Wear 08S 0.4 11 0.15 138 P1 51OUL 545 A 75 106 T-TSP wear 08S -0.7 15 0.22 140 P1 51OUL 543 A 75 107 T-TSP Wear 08S 0.4 17 0.27 139 P1 51OUL 545 A 75 110 T-TSP Wear 08S 0.4 11 0.15 139 P1 51OUL 543 A 75 111 T-TSP Wear 08S 0.3 14 0.21 148 P1 51OUL 545 A 76 16 T-TSP Wear 09S 0.4 8 0.13 140 P1 51OUL 667 A 76 22 T-TSP Wear 08S 0.3 14 0.21 150 P1 51OUL 643 A 76 98 T-TSP Wear 08S -0.7 10 0.14 143 P1 51OUL 543 A 76 99 T-TSP Wear 08S 0.4 8 0.11 128 P1 51OUL 545 A 76 101 T-TSP Wear 08S 0.5 18 0.28 144 P1 51OUL 545 A 76 105 T-TSP Wear 08S 0.4 12 0.17 152 P1 51OUL 545 A 77 96 T-TSP Wear 08S 0.4 7 0.11 134 P1 51OUL 663 A 77 97 T-TSP Wear 08S -0.7 6 0.07 114 P1 51OUL 665 A .77 97 T-TSP Wear 08S 0.4 8 0.11 150 P1 51OUL 665 A 77 98 T-TSP Wear 08S 0.4 8 0.12 149 P1 51OUL 663 Tuesday, April 24, 2012 Page 27 of 43
TMI-12-0 71, TMI-1 Steam GeneratorTube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 77 100 T-TSP Wear 08S 0.5 8 0.12 140 P1 51OUL 663 A 77 101 T-TSP Wear 08S 0.4 0.09 132 P1 51OUL 665 A 77 105 T-TSP Wear 08S 0.4 0.13 134 P1 51OUL 665 A 77 108 T-TSP Wear 08S 0.4 0.21 135 P1 51OUL 663 A 77 109 T-TSP Wear 08S -0.7 0.12 120 P1 51OUL 665 A 77 110 T-TSP Wear 08S -0.7 0.12 107 P1 51OUL 663 A 77 110 T-TSP Wear 08S 0.4 0.18 133 P1 51OUL 663 A 77 111 T-TSP Wear 08S -0.8 0.08 84 P1 51OUL 665 A 78 1 T-TSP Wear 11S -0.7 0.17 136 P1 510XB 042 A 78 16 T-TSP Wear 09S 0.4 0.11 146 P1 51OUL 537 A 78 100 T-TSP Wear 08S -0.8 0.16 140 P1 51OUL 663 A 78 101 T-TSP Wear 08S 0.4 0.12 141 P1 51OUL 665 A 78 102 T-TSP Wear 08S -0.7 0.12 107 P1 51OUL 663 A 78 102 T-TSP Wear 07S 0.4 0.12 144 P1 51OUL 663 A 78 103 T-TSP Wear 08S -0.7 0.09 120 P1 51OUL 665 A 78 105 T-TSP Wear 08S -0.7 0.09 101 P1 51OUL 665 A 78 105 T-TSP Wear 07S 0.4 0.1 151 P1 51OUL 665 A 78 106 T-TSP Wear 08S 0.4 0.22 141 P1 51OUL 663 A 78 107 T-TSP Wear 08S 0.4 0.16 147 P1 51OUL 665 A 78 108 T-TSP Wear 08S 0.3 0.17 151 P1 51OUL 663 A 79 4 T-TSP Wear 10S -0.8 0.1 130 P1 51OUL 675 A 79 35 T-T Wear 08S 18.8 16.5 21.0 4.5 53 0.18 85 5 520PP 815 A 79 105 T-TSP Wear 08S 0.4 0.08 136 P1 51OUL 665 A 79 107 T-TSP Wear 08S -0.8 0.08 80 P1 51OUL 665 T=sdy Api 24 201 Pag 28 of 43 IMXM Tuesday, April 24, 2012 Page 28of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (T1R19) , Exhibit I SG A, All Service Induced Indications,Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 80 35 T-T Wear 08S 18.9 5 16.7 21.0 4.3 48 0.18 89 5 520PP 821 A 80 104 T-TSP Wear 08S 0.4 13 0.22 146 P1 51OUL 663 A 80 105 T-TSP Wear 08S 0.4 16 0.24 144 P1 51OUL 665 A 80 106 T-TSP Wear 08S -0.8 9 0.14 108 P1 51OUL 663 A 80 106 T-TSP Wear 08S 0.4 7 0.1 143 P1 51OUL 663 A 80 107 T-TSP Wear .08S 0.4 7 0.09 138 P1 51OUL 665 A 80 108 T-TSP Wear 08S -0.8 8 0.12 102 P1 51OUL 663 A 80 109 T-TSP Wear 08S 0.4 15 0.22 128 P1 51OUL 665 A 80 109 T-TSP Wear 08S -0.8 6 0.08 65 P1 51OUL 665 A 81 11 T-TSP Wear 10S -0.8 7 0.11 134 P1 51OUL 675 A 81 99 T-TSP Wear 08S 0.4 9 0.12 148 P1 51OUL 665 A 81 104 T-TSP Wear 08S 0.4 6 0.09 139 P1 51OUL 663 A 81 105 T-TSP Wear 08S -0.7 6 0.07 72 P1 51OUL 665 A 81 108 T-TSP Wear 08S 0.3 14 0.24 130 P1 51OUL 663 A 81 109 T-TSP Wear 08S -0.7 7 0.09 129 P1 51OUL 665 A 81 110 T-TSP Wear 08S -0.8 10 0.16 109 P1 51OUL 663 A 81 113 T-TSP Wear 08S -0.7 6 0.08 87 P1 -51OUL 665 A 82 105 T-TSP Wear 08S 0.4 8 0.11 133 P1 51OUL 665 A 83 22 T-TSP Wear 09S 0.4 6 0.08 125 P1 51OUL 535 A 83 105 T-TSP Wear 08S 0.4 11 0.15 147 P1 51OUL 665 A 83 106 T-TSP Wear 08S -0.7 8 0.13 94 P1 51OUL 663 A 83 108 T-TSP Wear 08S 0.4 15 0.25 139 P1 51OUL 663 A 83 109 T-TSP Wear 08S 0.4 6 0.07 124 P1 51OUL 665 A 83 110 T-TSP Wear 08S 0.4 14 0.24 131 P1 51OUL 663 Tuesday, April 24, 2012 Page29 of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications, Outage T1R19 Location % Ind Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 83 110 T-TSP Wear 08S -0.7 7 0.11 102 P1 51OUL 663 A 83 111 T-TSP Wear 08S -0.8 8 0.1 98 P1 51OUL 665 A 83 111 T-TSP Wear 08S 0.3 15 0.22 133 P1 51OUL 665 A 83 112 T-TSP Wear 08S -0.8 9 0.14 121 P1 51OUL 663 A 84 104 T-TSP Wear 08S 0.4 10 0.16 135 P1 51OUL 663 A 84 105 T-TSP Wear 08S 0.4 8 0.11 140 P1 51OUL 665 A 85 4 T-TSP Wear loS -0.8 8 0.12 122 P1 51OUL 675 A 85 23 T-TSP Wear 09S 0.3 10 0.13 128 P1 51OUL 535 A 85 108 T-TSP Wear 08S 0.4 11 0.17 105 P1 51OUL 659 A 85 108 T-TSP Wear 08S -0.7 9 0.13 113 P1 51OUL 659 A 85 109 T-TSP Wear 08S -0.6 8 0.12 157 P1 51OUL 663 A 85 115 T-TSP Wear 10S -0.8 8 0.12 137 P1 51OUL 659 A 85 121 T-TSP Wear 10S -0.8 13 0.21 158 P1 51OUL 659 A 86 19 T-TSP Wear 10S -0.8 7 0.09 132 P1 51OUL 535 A 86 23 T-TSP Wear 09S 0.3 9 0.11 137 P1 51OUL 535 A 86 105 T-TSP Wear 08S -0.7 12 0.18 125 P1 51OUL 659 A 86 105 T-TSP Wear 08S 0.4 8 0.12 143 P1 51OUL 659 A 86 109 T-TSP Wear 08S -0.8 7 0.09 81 P1 51OUL 665 A 87 24 T-TSP Wear 09S 0.3 8 0.11 135 P1 51OUL 537 A 87 25 T-TSP Wear 09S 0.4 9 0.1 148 P1 51OUL 535 A 87 26 . T-TSP Wear 09S 0.3 9 0.12 134 P1 51OUL 537 A 87 107 T-T Wear 08S 18.1 4 16.1 20.0 3.9 . 53 0.14 82 5 520PP 819 A 88 7 T-TSP Wear 10S -0.7 10 0.16 137 P1 51OUL 675 A 88 9 T-TSP Wear l0S -0.8 8 0.08 147 P1 51OUL 677 Tuesday, April 24, 2012 Page 30of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications,Outage TJR19 Location ' % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 88 107 T-T Wear 08S 18.2 4 16.4 20.0 3.6 42 0.11 84 5 520PP 817 A 89 4 T-TSP Wear 10S -0.8 11 0.18 143 P1 51OUL 675 A 89 23 T-TSP Wear 09S 0.4 6 0.1 136 P1 51OUL 547 A 89 103 T-TSP Wear 08S 0.4 8 0.12 137 P1 51OUL 659 A 89 105. T-TSP Wear 08S -0.7 8 0.13 110 P1 51OUL 659 A 89 105 T-TSP Wear 08S 0.4 8 0.11 128 P1 51OUL 659 89 107 T-TSP Wear 08S 0.4 14 0.21 138 P1 51OUL 659 89 107 T-TSP Wear 08S -0.8 7 0.1 50 P1 51OUL 659 89 109 T-TSP Wear 08S 0.4 10 0.15 129 P1 51OUL 659 89 109 T-TSP Wear 08S -0.8 15 0.25 128 P1 51OUL 659 89 122 T-TSP Wear 10S -0.8 10 0.14 128 P1 51OUL 661 90 30 T-T Wear 08S 18.8 2 17.5 20.0 2.5 58 0.09 77 5 520PP 821 90 31 T-T Wear 08S 18.7 4 17.4 20.0 2.6 37 0.08 76 5 520PP 815 90 31 T-T Wear 08S 18.7 4 17.4 20.0 2.6 42 0.08 76 5 520PP 815 90 34 T-T Wear 08S 19.0 4 16.9 21.0 4.1 48 0.15 83 5 520PP 821 90 34 T-T Wear 08S 18.9 1 17.8 20.0 2.2 42 0.06 77 5 520PP 821 90 38 T-T Wear 08S 19.1 3 17.3 21.0 3.7 43 0.12 88 5 520PP 821 90 39 T-T Wear 08S 18.6 3 17.3 20.0 2.7 37 0.1 86 5 520PP 821 90 101 T-TSP Wear 08S 0.4 9 0.12 134 P1 51OUL 661 91 34 T-T Wear 08S 18.9 4 16.8 21.0 4.2 48 0.14 83 5 520PP 815 91 34 T-T Wear 08S 18.9 2 16.8 21.0 4.2 32 0.14 83 5 520PP 815 91 35 T-T Wear 08S 18.9 4 16.9 21.0 4.1 42 0.16 75 5 520PP 821 91 87 T-TSP Wear 08S -0.8 6 0.08 117 P1 51OUL 659 A 91 101. T-TSP Wear 08S -0.8 7 0.1 80 P1 51OUL 659 A 91 101 T-TSP Wear 08S 0.4 8 0.12 133 P1 51OUL 659 2- Pag 31 43 MT1 Muesd==Apil4 201 Mf Tuesday, April 24, 2012 Page 31 of 43
TMI-12--071, TMI-1 Steam Generator Tube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 92 34 T-T Wear 08S 18.9 16.8 21.0 4.2 42 0.15 83 520PP 821 A 92 96 T-TSP Wear 04S -0.6 0.16 .153 51OUL 659 A 92 101 T-TSP Wear 08S -0.7 0.1 102 51OUL 661 A 92 103 T-TSP Wear 08S 0.4 0.1 131 51OUL 661 A 93 1 T-TSP Wear 10S -0.8 0.09 124 510XB 042 A 93 22 T-TSP Wear 09S 0.4 0.14 152 51OUL 547 A 93 58 T-TSP Wear 08S 0.4 0.17 155 51OUL 667 A 93 106 T-TSP Wear 08S -0.8 0.09 69 51OUL 659 A 93 110 T-TSP Wear 14S 0.2 0.16 144 51OUL 659 A 94 99 T-TSP Wear 08S 0.3 0.09 140 51OUL 661 A 94. 102 T-TSP Wear 08S 0.4 0.19 120 51OUL 659 A 94 104 T-TSP Wear 08S 0.4 0.26 131 51OUL 659 A 94 104 T-TSP Wear 08S -0.8 0.11 110 51OUL 659 A 94 107 T-TSP Wear 08S -0.7 0.07 95 51OUL 661 A 94 108 T-TSP Wear 08S -0.8 0.08 93 51OUL 659 A 95 102 T-TSP Wear 08S -0.7 0.1 95 51OUL 659 A 95 102 T-TSP Wear 08S 0.4 0.22 130 51OUL 659 A 95 104 T-TSP Wear 08S 0.4 7 0.1 109 51OUL 659 A 95 104 T-TSP Wear 08S -0.7 7 0.1 53 51OUL 659 A 95 107 T-TSP Wear 08S -0.8 10 0.14 101 51OUL 661 A 95 110 T-TSP Wear 08S 0.4 9 0.14 144 51OUL 659 A 95 117 T-TSP Wear 10S 0.3 8 0.11 150 51OUL 661 A 96 33 T-TSP Wear 08S -0.8 8 0.13 128 51OUL 547 A 96 33 T-TSP Wear 08S 0.3 10 0.18 134 51OUL 547 A .96 102 T-TSP Wear 08S -0.7 8 0.12 97 51OUL 659 Page 32 of 43 Tuesday, April 24, 2012 Tuesday, April24, 2012 Page 32 of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19) , Exhibit I SG A, All Service Induced Indications, Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 96 102 T-TSP Wear 08S 0.4 11 0.17 131 P1 51OUL 659 A 96 104 T-TSP Wear 08S -0.7 7 0.1 82 P1 51OUL 659 A 96 104 T-TSP Wear 08S 0.4 13 0.21 132 P1 51OUL 659 A 96 117 T-TSP Wear 10S 0.3 0.12 155 P1 51OUL 661 A 97 89 T-TSP Wear 04S -0.7 14 0.22 159 P1 51OUL 659 A 97 102 T-TSP Wear 08S -0.8 10 0.14 108 51OUL 661 A 97 102 T-TSP Wear 08S 0.3 10 0.14 134 51OUL 661 A 97 103 T-TSP Wear 08S -0.7 10 0.15 105 51OUL 659 A 97 104 T-TSP Wear 08S -0.8 10 0.14 99 51OUL 661 A 97 104 T-TSP Wear. 08S 0.4 13" 0.19 140 51OUL 661 A 97 106 T-TSP Wear 08S 0.4 0.26 144 51OUL 673 A 97 106 T-TSP Wear 08S -0.8 0.14 109 510UL 673 A 98 2 T-TSP Wear 10S -0.7 0.14 128 510XB 042 A 98 4 T-TSP Wear 10S -0.8 0.2 132 51OUL 675 A 98 99 T-TSP Wear 08S 0.4 0.11 121 51OUL 657 A 98 100 T-TSP Wear 08S 0.4 0.12 148 51OUL 655 A .98 101 T-TSP Wear 08S 0.4 0.21 139 51OUL 657 A 98 101 T-TSP Wear 08S -0.7 0.12 66 51OUL 657 A 99 1 T-TSP Wear 10S -0.7 0.16 142 510XB 042 A 99 2 T-TSP Wear 10S -0.7 0.24 128 510XB 042 A 99 21 T-TSP Wear 09S 0.4 0.07 146 51OUL 669 A 99 46 T-T Wear 08S 18.4 15.7 21.0 5.3 42 0.25 78 520PP 815 A 100 8 T-TSP Wear 10S -0.8 0.1 130 51OUL 669 A 100 36 T-TSP Wear 08S 0.4 0.14 144 51OUL 669 A 100 46 T-T Wear 08S 18.3 15.6 21.0 5.4 53 0.23 83 520PP 815 Tuesday, April 24, 2012 Page 33 of 43
TMI-12--071, TMI-1 Steam Generator Tube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications,Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 100 96 T-TSP Wear 08S 0.4 9 0.14 137 P1 51OUL 655 A 100 97 T-TSP Wear 08S 0.3 7 0.1 152 P1 51OUL 657 A 100 98 T-TSP Wear 08S 0.4 8 0.12 140 P1 51OUL 655 A 100 103 T-TSP Wear 08S 0.4 7 0.1 148 P1 51OUL 657 A 101 43 T-TSP Wear 09S -0.8 5 0.07 116 P1 51OUL 669 A 101 119 T-TSP Wear 10S 0.3 8 0.13 140 P1 51OXB 006 A 102 97 T-TSP Wear 08S 0.4 7 0.09 132 P1 51OUL 657 A 102 99 T-TSP Wear 08S 0.4 13 0.2 135 P1 51OUL 657 A 102 100 T-TSP Wear 08S -0.7 9 0.14 88 P1 51OUL 655 A 102 100 T-TSP Wear 08S 0.4 14 0.24 140 P1 51OUL 655 A 102 104 T-TSP Wear 08S 0.4 8 0.12 148 P1 51OUL 655 A 102 114 T-TSP Wear 13S -0.6 8 0.12 137 P1 51OUL 655 A 102 115 T-TSP Wear 13S -0.7 7 0.1 133 P1 51OUL 657 A 103 93 T-TSP Wear 08S 0.4 7 0.11 135 P1 51OUL 655 A 103 96 T-TSP Wear 08S -0.8 6 0.08 71 P1 51OUL 657 A 103 97 T-TSP Wear 08S 0.4 11 0.18 136 P1 51OUL 655 A 103 106 T-TSP Wear 08S -0.7 7 0.09 92 P1 51OUL 657 A 103 114 T-TSP Wear 09S 0.4 7 0.09 147 P1 51OUL 657 A 103 117 T-TSP Wear 10S 0.3 7 0.1 155 P1 51OUL 655 A 104 23 T-TSP Wear 10S -0.8 9 0.13 147 P1 51OUL 531 A 104 121 T-TSP Wear 10S -0.7 9 0.12 148 P1 51OXB 008 A 106 27 T-TSP Wear 08S 0.4 8 0.1 131 P1 51OUL 569 A 106 92 T-TSP Wear 08S 0.4 6 0.09 139 P1 51OUL 655 A 106 93 T-TSP Wear 08S 0.4 6 0.08 141 P1 51OUL 657 Page 34 of 43 Tuesday, April 24, 2012 Tuesday, April24, 2012 Page 34 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 108 15 T-TSP Wear loS -0.8 .6 0.08 121 P1 51OUL 569 A 108 93 T-TSP Wear 08S -0.7 8 0.11 63 P1 51OUL 657 6 0.09 123 P1 51OUL 655 A 108 94 T-TSP Wear 08S 0.4 A 108 95 T-TSP Wear 08S 0.4 7 0.1 153 P1 51OUL 657 A 108 101 T-TSP Wear 08S 0.4 7 0.09 142 P1 51OUL 657 A 108 117 T-TSP Wear 10S -0.8 8 0.11 146 P1 510XB 008 10 51OUL 569 A 109 33 T-TSP Wear 08S -0.7 0.13 94 P1 A 109 35 T-TSP Wear 08S 0.3 8 0.1 142 P1 51OUL 569 A 110 26 T-TSP Wear 09S 0.3 8 0.14 131 P1 51OUL 575 A 110 29 T-TSP Wear 09S 0.4 6 0.08 145 P1 51OUL 569 A 110 31 T-TSP Wear 09S 0.4 9 0.13 151 P1 51OUL 569 A 110 39 T-TSP Wear 08S -0.7 7 0.11 131 P1 51OUL 663 A 111 26 T-TSP Wear 09S 0.3 7 0.11 152 P1 51OUL 575 A 111 33 T-TSP Wear 08S -0.8 10 0.13 99 P1 51OUL 569 A 111 33 T-TSP Wear 08S 0.4 7 0.09 140 P1 51OUL 569 A 11i 33 T-TSP Wear 07S 0.4 9 0.12 163 P1 51OUL 569 A 111 34 T-TSP Wear 08S 0.4 12 0.21 135 P1 51OUL 575 A 111 36 T-T Wear 08S 18.8 2 -17.6 20.0 2.4 58 0.08 80 5 520PP 815 A 111 37 T-T Wear 08S 18.7 2 17.3 20.0 2.7 37 0.06 59 5 520PP 821 A 111 86 T-TSP Wear 08S .- 0.8 7 0.1 20 P1 51OUL 651 A 112 24 T-TSP Wear 09S 0.4 8 0.1 142 P1 51OUL 569 A 112 27 T-TSP Wear 09S 0.3 7 0.11 147 P1 51OUL 575 A 112 36 T-T Wear 08S 18.9 2 17.7 20.0 2.3 42 0.09 81 5 520PP 821 A 114 40 T-T Wear 08S 18.3 19 14.5 22.0 7.5 58 0.72 82 5 520PP 815 Tuesday, April 24, 2012 Page 35 of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal I
A 114 41 T-T Wear 08S 19.1 4 17.2 21.0 3.8 37 0.1 87 5 520PP 815 114 41 T-T Wear 08S 19.1 17.2 21.0 3.8 42 0.1 87 5 520PP 815 114 42 T-T Wear 08S 20.0 17.9 22.0 4.1 53 0.4 79 69 510XP 823 114 97 T-TSP Wear loS -0.8 0.08 133 P1 51OUL 647 115 40 T-T Wear 08S 18.3 14.7 22.0 7.3 58 0.68 87 5 520PP 815 115 40 T-T Wear 08S 18.6 17.2 20.0 2.8 26 0.13 91 5 520PP 815 115 108 T-TSP Wear 10S -0.8 0.12 128 P1 51OUL 647 115 109 T-TSP Wear 10S -0.7 0.11 112 P1 51OUL 645 115 111 T-TSP Wear 10S -0.7 0.08 128 P1 51OUL 645 115 112 T-TSP Wear 10S -0.7 0.09 129 P1 51OUL 647 116 7 T-TSP Wear 11S 0.3 0.13 156 P1 51OUL 587 116 108 T-TSP Wear 10S -0.7 0.09 127 P1 51OUL 645 116 109 T-TSP Wear 10S -0.8 0.09 121 P1 51OUL 647 116 110 T-TSP Wear 10S 0.3 0.1 146 P1 51OUL 645 117 30 T-TSP Wear 09S 0.3 0.09 119 P1 51OUL 585 117 32 T-TSP Wear 09S 0.3 0.12 131 P1 51OUL 585 117 33 T-TSP Wear 08S 0.4 0.17 139 P1 51OUL 587 117 34 T-TSP Wear 08S 0.3 0.14 147 P1 51OUL 585 117 35 T-TSP Wear 08S 0.4 0.11 147 P1 51OUL 587 117 40 T-T Wear 08S 18.7 17.3 20.0 2.7 37 0.04 58 5 520PP 815 117 40 T-T Wear 08S 18.3 16.7 20.0 3.3 42 0.11 72 5 520PP 815 117 40 T-T Wear 08S 18.6 16.1 21.0 4.9 42 0.21 83 5 520PP 815 117 107 T-TSP Wear 10S -0.8 0.12 142 P1 51OUL 647 117 111 T-TSP Wear 10S -0.7 0.15 146 P1 510XB 008 118 32 T-TSP Wear 08S 0.4 0.08 136 P1 51OUL 587 Page 36 of 43 Tuesday, April24, Tuesday, April 2012 24,2012 Page36of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19) , Exhibit I SG A, All Service Induced Indications, Outage T1R19 Location % Ind Ind Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal A 118 35 T-TSP Wear 09S 0.3 7 0.1 120 P1 51OUL 585 A 118 39 T-T Wear 08S 18.5 4 17.0 20.0 3.1 42 0.15 87 5 520PP 821 A 118 40 T-T Wear 08S 18.7 7 16.4 21.0 4.6 53 0.22 78 5 520PP 815 A 119 8 T-TSP Wear 10S -0.7 7 0.11 139 P1 51OUL 585 A 119 35 T-TSP Wear 09S 0.3 8 0.11 147 P1 51OUL 665 A 119 36 T-TSP Wear 08S 0.4 10 0.15 145 P1 51OUL 663 A 119 40 T-T Wear 08S 18.4 7 15.9 21.0 5.1 53 0.3 84 5 520PP 815 A 119 40 T-TSP Wear 07S 0.4 9 0.16 149 P1 51OUL 625 A 120 34 T-TSP Wear 08S 0,3 7 0.12 151 P1 51OUL 625 A 120 39 T-T Wear 08S 18.3 3 16.6 20.0 3.4 42 0.08 77 5 520PP 815 A 120 39 T-T Wear 08S 18.4 8 15.8 21.0 5.2 53 0.27 81 5 520PP 815 A 120 52 T-T Wear 08S 18,3 4 16.6 20.0 3.4 53 0.16 53 77 510XP 823 A 120 92 T-TSP Wear 10S -0.8 9 0.13 146 P1 51OUL 645 A 121 35 T-TSP Wear 08S 0.3 8 0.13 162 P1 51OUL 625 A 121 49 T-TSP Wear 07S 0.4 8 0.13 156 P1 51OUL 625 A 121 52 T-T Wear 08S 17.4 5 15.7 19.0 3.3 53 0.16 95 5 520PP 815 A 121 52 T-T Wear 08S 18.4 3 16.7 20.0 3.3 48 0.12 75 5 520PP 815 A 121 53 T-T Wear 08S 17.5 5 16.0 19.0 3.0 58 0.16 88 5 520PP 815 A 121 55 T-TSP Wear 08S -0.8 8 0.12 107 P1 51OUL 625 A 121 55 T-TSP Wear 07S 0.4 10 0.17 156 P1 51OUL 625 A 121 98 T-TSP Wear 10S -0.7 10 0.15 143 P1 51OUL 645 A 121 100 T-TSP Wear 10S 0.3 7 0.1 142 P1 51OUL 645 A 121 101 T-TSP Wear 11S -0.7 8 0.11 153 P1 51OUL 647 A 121 101 T-TSP Wear 10S -0.8 8 0.11 138 P1 51OUL 647 A 121 102 T-TSP Wear 10S -0.8 11 0.17 123 P1 51OUL 645 Tuesday, April 24, 2012 Page37 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TJR19) , Exhibit 1 SG A, All Service Induced Indications, Outage TJR19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 122 47 T-TSP Wear 07S 0.4 8 0.12 151 P1 51OUL 615 A 122 49 T-TSP Wear 08S 0.4 8 0.12 150 P1 51OUL 615 A 122 51 T-TSP Wear 08S 0.3 11 0.17 156 P1 510UL 615 A 122 100 T-TSP Wear 10S -0.7 12 0.18 140 P1 510UL 645 A 123 51 T-TSP Wear 08S 0.3 9 0.14 146 P1 51OUL 615 A 123 88 T-TSP Wear 10S -0.8 6 0.09 133 P1 51OUL 645 A 123 98 T-TSP Wear 10S 0.3* 8 0.12 146 P1 51OUL 645 A 125 43 T-TSP Wear 08S 0.4 8 0.11 143 P1 51OUL 617 A 125 44 T-TSP Wear 08S 0.3 16 0.26 150 P1 51OUL 615 A 125 44 T-TSP Wear 08S -0.8 7 0.11 130 P1 51OUL 615 A 126 42 T-TSP Wear 09S 0.3 6 0.09 141 P1 51OUL 615 A 126 56 T-TSP Wear 08S 0.3 13 0.21 145 P1 51OUL 615 A 126 56 T-TSP Wear 08S -0.8 13 0.21 139 P1 51OUL 615 A 126 56 T-TSP Wear 07S 0.4 13 0.21 150 P1 51OUL 615 A 127 13 T-TSP Wear 10S -0.8 11 0.17 149 P1 51OUL 597 A 127 42 T-TSP Wear 08S -0.7 7 0.11 103 P1 510XB 036 A 127 42 T-TSP Wear 08S 0.4 8 0.14 143 P1 510XB 036 A 127 89 T-TSP Wear 10S -0.7 8 0.12 137 P1 51OUL 635 A 127 93 T-TSP Wear 10S -0.7 11 0.17 132 P1 51OUL 635 A 128 87 T-TSP Wear 12S 0.3 9 0.14 143 P1 51OUL 637 A 129 89 T-TSP Wear 10S -0.7 9 0.14 125 P1 51OUL 635 A 130 9 T-TSP Wear 09S 0.4 10 0.16 150 P1 51OUL 597 A 130 84 T-TSP Wear 10S 0.3 12 0.2 162 P1 51OUL 637 A 131 84 T-TSP Wear 10S -0.8 7 0.11 130 P1 51OUL 637 Tuesday, April 24, 2012 Page 38of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 132 13 T-TSP Wear 10S 0.3 7 0.1 137 P1 51OUL 599 A 132 83 T-TSP Wear 10S -0.7 11 0.18 136 P1 51OUL 635 A 133 1 T-TSP Wear 13S 0.3 8 0.12 132 P1 510XB 014 A 133 17 T-TSP Wear 10S 0.3 5 0.06 131 P1 51OUL 599 A 134 37 T-TSP Wear 10S -0.8 8 0.13 137 P1 51OUL 615 A 134 48 T-TSP Wear 10S -0.8 7 0.1 142 P1 51OUL 617 A 134 76 T-TSP Wear 11S 0.3 8 0.13 144 P1 51OUL 637 A 135 11 T-TSP Wear 10S 0.3 7 0.09 145 P1 51OUL 599 A 135 69 T-TSP Wear 10S -0.8 6 0.1 134 P1 51OUL 637 A 135 73 T-TSP Wear 10S 0.3 10 0.17 157 P1 51OUL 637 A 135 79 T-TSP Wear 10S -0.8 5 0.07 118 P1 51OUL 637 A 136 6 T-TSP Wear 10S -0.8 10 0.13 126 P1 51OUL 599 A 136 10 T-TSP Wear 10S 0.3 6 0.07 152 P1 51OUL 599 A 136 16 T-TSP Wear 13S -0.8 10 0.14 135 P1 51OUL 599 A 136 35 T-TSP Wear 10S -0.8 7 0.11 147 P1 51OUL 607 A 136 43 T-TSP Wear 10S -0.8 6 0.1 140 P1 51OUL 607 A 136 55 T-TSP Wear 10S -0.8 9 0.15 138 P1 51OUL 607 A 136 68 T-TSP Wear 10S 0.3 12 0.2 149 P1 51OUL 637 A 136 70 T-TSP Wear 10S -0.8 9 0.15 148 P1 51OUL 637 A 137 8 T-TSP Wear 09S 0.4 9 0.15 150 P1 51OUL 597 A 137 15 T-TSP Wear 11S 0.3 8 0.12 145 P1 51OUL 599 A 137 17 T-TSP Wear 11S 0.3 8 0.1 147 P1 51OUL 599 A 137 22 T-TSP Wear 10S -0.8 9 0.12 139 P1 51OUL 609 A 137 32 T-TSP Wear 10S -0.8 7 0.09 135 P1 51OUL 609 I IIMMMVMMMý - 4 = - -
Tuesday, April 24, 2012 Page39 of 43
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications,Outage T1R19 Location % Indt Indt Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal I
A 137 35 T-TSP Wear 10S -0.8 7 0.1 140 P1 51OUL 607 A 137 60 T-TSP Wear 10S -0.8 0.13 137 P1 51OUL 635 A 137 61 T-TSP Wear 10S -0.7 0.13 140 P1 51OUL 637 A 137 62 T-TSP Wear 10S -0.8 0.12 141 P1 51OUL 635 A 137 63 T-TSP Wear 11S 0.3 0.25 144 P1 51OUL 637 A 138 7 T-TSP Wear 10S -0.8 0.18 126 P1 51OUL 599 A 138 14 T-TSP Wear 11S 0.4 0.17 150 P1 51OUL 597 A 138 15 T-TSP Wear 11S 0.4 0.1 150 P1 51OUL 599 A 138 19 T-TSP Wear 10S -0.8 0.17 147 P1 51OUL 607 A 138 21 T-TSP Wear 10S -0.8 0.2 148 P1 51OUL 607 A 138 44 T-TSP Wear 11S 0.3 0.09 138 P1 51OUL 609 A 138 57 T-TSP Wear 13S -0.8 0.17 134 P1 51OUL 635 A 138 63 T-TSP Wear 11S 0.3 0.23 140 P1 51OUL 637 A 138 64 T-TSP Wear 10S -0.8 0.15 130 P1 51OUL 635 A 139 13 T-TSP Wear 10S -0.8 0.08 113 P1 51OUL 599 A 139 27 T-TSP Wear 10S -0.8 0.11 149 P1 51OUL 607 A 139 53 T-TSP Wear 10S -0.8 0.14 134 P1 51OUL 607 A 139 60 T-TSP Wear 11S 0.3 0.29 128 P1 51OUL 637 A 139 62 T-TSP Wear 10S -0.7 0.12 146 P1 51OUL 637 A 139 65 T-TSP Wear 11S 0.4 0.32 137 P1 51OUL 635 A 140 6 T-TSP Wear 10S -0.8 0.13 133 P1 51OUL 597 A 140 40 T-TSP Wear 10S -0.8 0.14 153 P1 51OUL 609 A 140 41 T-TSP Wear 10S -0.8 0.09 136 P1 51OUL 607 A 140 51 T-TSP Wear 10S -0.7 0.13 148 P1 51OUL 607 Tuesday, April 24, 2012 Page 40 of 43
TMI-12-071, TMI-I Steam Generator Tube Inspection Report (T1R19) , Exhibit I SG A, All Service Induced Indications,Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 140 57 T-TSP Wear 11S 0.4 6 0.1 144 P1 51OUL 637 A 140 57 T-TSP Wear 10S -0.7 5 0.08 129 P1 51OUL 637 A 140 58 T-TSP Wear 11S 0.4 17 0.31 140 P1 51OUL 635 A 140 60 T-TSP Wear 11S 0.4 12 0.19 138 P1 51OUL 635 A 140 63 T-TSP Wear 11S 0.4 27 0.57 133 P1 51OUL 637 A 140 68 T-TSP Wear 11S -0.7 10 0.16 136 P1 510XB 006 A 141 4 T-TSP Wear 10S -0.7 10 0.18 133 P1 510XB 036 A 141 52 T-TSP Wear 10S 0.4 8 0.12 140 P1 51OUL 633 A 141 55 T-TSP Wear 11S 0.3 24 0.45 129 P1 51OUL 633 A 141 55 T-TSP Wear 10S 0.3 8 0.12 150 P1 51OUL 633 A 141 56 T-TSP Wear 11S 0.4 10 0.15 158 P1 51OUL 633 A 141 62 T-TSP Wear 11S 0.4 12 0.19 143 P1 51OUL 635 A 141 63 T-TSP Wear 10S -0.7 7 0.11 142 P1 51OUL 637 A 142 13 T-TSP Wear 105 -0.7 13 0.23 155 P1 51OUL 607 A 142 30 T-TSP Wear 11S -0.8 8 0.11 155 P1 51OUL 609 A 142 47 T-TSP Wear 10S -0.8 9 0.14 157 P1 51OUL 607 A 142 52 T-TSP Wear 11S 0.4 11 0.17 139 P1 51OUL 633 A 142 53 T-TSP Wear 11S 0.3 14 0.22 142 P1 51OUL 633 A 142 54 T-TSP Wear 11S 0.4 11 0.16 150 P1 51OUL 633 A 142 54 T-TSP Wear 08S 0.4 9 0.14 155 P1 51OUL 633 A 142 60 T-TSP Wear 10S -0.7 10 0.17 134 P1 510XB 006 A 142 62 T-TSP Wear 11S 0.4 16 0.29 136 P1 510XB 006 A 142 62 T-TSP Wear 10S -0.7 15 0.27 143 P1 510XB 006 A 143 32 T-TSP Wear 11S 0.3 6 0.08 133 P1 51OUL 607 A 143 49 T-TSP Wear 11S 0.4 7 0.1 132 P1 51OUL 633 Page 41 of 43 Tuesday, 24, 2012 April24, Tuesdaj', April 2012 Page41 of 43
TMI-12-071, TMI-1 Steam GeneratorTube InspectionReport (T1R19) , Exhibit 1 SG A, All Service Induced Indications, Outage T1R19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal A 143 50 T-TSP Wear 11S 0.4 14 0.22 145 P1 51OUL 633 A 143 51 T-TSP Wear 11S 0.4 27 0.51 129 P1 51OUL 633 A 143 52 T-TSP Wear 11S 0.4 9 0.13 151 P1 51OUL 633 A 144 45 T-TSP Wear 11S 0.4 7 0.1 144 P1 51OUL 633 A 145 8 T-TSP Wear 09S 0.5 9 0.15 142 P1 51OUL 607 A 145 14 T-TSP Wear 10S 0.4 8 0.12 150 P1 51OUL 607 A 145 38 T-TSP Wear 11S 0.4 10 0.14 155 P1 51OUL 609 A 146 15 T-TSP Wear 10S -0.8 10 0.13 128 P1 51OUL 609 A 146 16 T-TSP Wear 10S -0.8 13 0.22 138 P1 51OUL 607 A 146 24 T-TSP Wear 11S -0.8 7 0.11 146 P1 51OUL 607 A 146 24 T-TSP Wear 10S -0.7 6 0.09 143 P1 51OUL 607 A 146 33 T-TSP Wear 10S -0.8 11 0.15 115 P1 51OUL 609 A 146 36 T-TSP Wear 10S -0.8 9 0.14 141 P1 51OUL 607 A 147 3 T-TSP Wear 10S -0.8 6 0.09 122 P1 510XB 010 A 147 13 T-TSP Wear 10S -0.8 11 0.18 139 P1 51OUL 607 A 147 14 T-TSP Wear 10S -0.8 10 0.13 140 P1 51OUL 609 A 147 15 T-TSP Wear 10S -0.8 13 0.23 140 P1 51OUL 607 A 147 19 T-TSP Wear 10S -0.7 10 0.16 124 P1 51OUL 607 A 147 24 T-TSP Wear 10S -0.8 9 0.13 124 P1 51OUL 609 A 147 27 T-TSP Wear l0S -0.8 15 0.26 140 P1 51OUL 607 A 147 29 T-TSP Wear 10S -0.7 10 0.17 157 P1 51OUL 607 A 148 4 T-TSP Wear 10S -0.7 16 0.28 118 P1 510XB 010 A 148 12 T-TSP Wear 10S -0.8 8 0.11 141 P1 51OUL 609 A 148 13 T-TSP Wear 10S -0.8 16 0.28 133 P1 51OUL 607 Tucsdqv, April 24, 2012 Page 42 of 43
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19) , Exhibit 1 SG A, All Service Induced Indications, Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe -Cal 148 14 T-TSP Wear loS -0.8 11 0.15 132 P1 51OUL 609 148 15 T-TSP Wear loS -0.7 10 0.17 140 P1 51OUL 607 148 19 T-TSP Wear 10S -0.8 8 0.13 140 P1 51OUL 607 148 20 T-TSP Wear 10S -0.8 0.16 133 P1 51OUL 609 148 21 T-TSP Wear 10S -0.8 0.34 135 P1 51OUL 607 148 25 T-TSP Wear 10S -0.8 0.14 146 P1 51OUL 607 148: 37 T-TSP Wear loS -0.8 0.18 122 P1 510XB 002 149 6 T-TSP Wear 11S -0.8 0.12 121 P1 510XB 002 149 15 T-TSP Wear 10S -0.8 0.19 133 P1 51OUL 609 149 20 T-TSP Wear 10S -0.8 0.15 133 P1 51OUL 607 150 1 T-TSP Wear 11S -0.7 0.14 129 P1 510XB 010 150 2 T-TSP Wear 11S -0.7 0.17 154 P1 510XB 012 150 3 T-TSP Wear 11S -0.7 0.13 140 P1 510XB 010 150 7 T-TSP Wear 11S -0.7 0.11 111 P1 510XB 002 A 150 10 T-TSP Wear loS 0.4 0.15 145 P1 510XB 004 A 150 11 T-TSP Wear loS 0.4 0.19 141 P1 510XB 002 A 150 17 T-TSP Wear 10S -0.8 0.33 127 P1 510XB 002 A 151 24 T-TSP Wear 13S 0.3 0.1 137 P1 510XB 004 Total Tubes 913 Total Indications 1041 Tuesday, April 24, 2012 Page 43 of 43
EM TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment 1, Exhibit2 SG BA All Service Induced Indications,Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 1 1 T-TSP Wear 13S -0.8 8 0.13 113 P1 510XB 004 B 1 1 T-TSP Wear 12S -0.7 11 0.18- 110 P1 510XB 004 B 1 1 T-TSP Wear 11S -0.8 14 0.22 115 P1 51OXB 004 B 1 2 T-TSP Wear 13S -0.8 24 0.38 132 P1 510XB 006 B 1 2 T-TSP Wear 13S 0.2 8 0.1 124 P1 510XB 006 B 1 2 T-TSP Wear 12S -0.7 16 0.22 143 P1 510XB 006 B 1 2 T-TSP Wear 11S -0.7 18 0.25 132 P1 510XB 006 B 1 3 T-TSP Wear 13S 0.2 9 0.13 132 P1 510XB 004 B 1 3 T-TSP Wear 13S -0.8 26 0.5 116 P1 51OXB 004 B 1 3 T-TSP Wear 12S -0.8 9 0.14 109 P1 510XB 004 B 1 4 T-TSP Wear 13S 0.0 42 1.01 127 P1 510XB 006 B 1 4 T-TSP Wear 12S -0.8 34 0.67 124 P1 510XB 006 B 1 5 T-TSP Wear 13S -0.8 8 0.12 65 P1 510XB 004 B 1 5 T-TSP Wear 12S -0.3 47 1.49 104 P1 510XB 004 B 6 T-TSP Wear 12S -0.7 52 1.69 111 P1 510XB 006 1
B 6 T-TSP Wear 12S 0.3 13 0.18 141 P1 510XB 006 B 1 6 T-TSP Wear 11S -0.8 24 0.38 127 P1 510XB 006 1
B 7 T-TSP Wear 12S 0.0 43 1.21 120 P1 510XB 004 B 1 7 T-TSP Wear 11S 0.4 11 0.16 142 P1 510XB 004 1
B 8 T-TSP Wear 12S -0.7 19 0.27 129 P1 510XB 006 B 8 T-TSP Wear 11S -0.8 38 0.8 119 P1 510XB 006 B 1 9 T-TSP Wear 12S -0.8 19 0.34 115 P1 510XB 004 1
B 9 T-TSP Wear 11S -0.8 29 0.62 119 P1 510XB 004 1
B 9 T-TSP Wear 11S 0.3 12 0.19 151 P1 510XB 004 B 1 10 T-TSP Wear 12S -0.8 8 0.1 122 P1 510XB 006 Page) of 67 Tuesday, April24, Tuesday, April 2012 24, 2012 Page I of 67
TMJ-12-O 71, TMI-J Steam Generator Tube Inspection Report (TJRJ9)
-~Attachment l7,Exhibit-2 SG BA All Service Induced Indications.Outa2e TJR19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 1 10 T-TSP Wear 11S -0.8 0.08 131 P1 510XB 006 B 1 10 T-TSP Wear 09S -0.7 0.09 130 P1 510XB 006 B 1 11 T-TSP Wear 12S -0.8 0.34 114 P1 510XB 004 B 1 11 T-TSP Wear 11S -0.8 0.1 72 P1 510XB 004 B 1 13 T-TSP Wear 13S -0.9 0.06 152 P1 510XB 006 B 1 13 T-TSP Wear 10S 0.4 0.09 136 P1 510XB 006 B 1 14 T-TSP Wear 12S -0.8 0.66 124 P1 510XB 002 B 1 14 T-TSP Wear 12S 0.3 0.12 135 P1 510XB 002 B 1 15 T-TSP Wear 13S 0.3 0.13 140 P1 510XB 002 B 1 15 T-TSP Wear 12S -0.7 0.64 119 P1 510XB 002 B 1 16 T-TSP Wear 13S 0.3 0.11 137 P1 510XB 002 B 1 16 T-TSP Wear 13S -0.8 0.1 129 P1 510XB 002 B 1 16 T-TSP Wear 12S -0.7 0.48 122 P1 510XB 002 B 1 16 T-TSP Wear 12S 0.3 0.22 136 P1 510XB 002 B 1 17 T-TSP Wear 12S -0.7 0.28 112 P1 510XB 002 B 1 17 T-TSP Wear 12S 0.3 0.23 139 P1 510XB 002 B 1 18 T-TSP Wear 12S 0.3 0.28 152 P1 510XB 002 B 1 19 T-TSP Wear 13S -0.8 7 0.11 141 P1 510XB 002 B 1 19 T-TSP Wear 12S -0.8 15 0.24 133 P1 510XB 002 B 1 19 T-TSP Wear 12S 0.3 9 0.14 144 P1 510XB 002 B 1 20 T-TSP Wear 12S -0.7 32 0.68 127 P1 510XB 002 B 1 21 T-TSP Wear 13S 0.2 7 0.11 150 P1 510XB 002 B 1 21 T-TSP Wear 12S 0.3 14 0.22 156 P1 510XB 002 B 1 21 T-TSP Wear 12S -0.8 36 0.86 112 P1 510XB 002 B 1 22 T-TSP Wear 12S 0.4 11 0.18 143 P1 510XB 002 Tuesday, April 24, 2012 Page 2 of 67 14
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B. All Service Induced Indications.Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 1 22 T-TSP Wear 12S -0.8 36 0.86 120 P1 510XB 002 B 1 23 T-TSP Wear 13S 0.2 8 0.12 160 P1 510XB 004 B 1 23 T-TSP Wear 12S -0.7 28 0.56 103 P1 510XB 004 B 1 23 T-TSP Wear 12S 0.3 21 0.39 154 P1 510XB 004 B 1 24 T-TSP Wear 13S 0.3 8 0.1 141 510XB 006 B 1 24 T-TSP Wear 12S 0.4 18 0.25 145 510XB 006 1 T-TSP Wear 12S -0.7 23 0.44 124 510XB 004 I I-TSP Wear 12S 0.4 18 0.32 135 51OXB 004 1 T-TSP Wear 11S -0.7 15 0.25 121 510XB 004 2 T-TSP Wear 13S 0.0 27 0.46 145 510XB 006 2 T-TSP Wear 12S 0.3 10 0.13 147 510XB 006 2 T-TSP Wear .12S -0.7 12 0.15 105 510XB 006 2 T-TSP Wear 11S 0.4 29 0.51 140 510XB 006 2 T-TSP Wear 11S -0.7 38 0.82 114 510XB 006 2 T-TSP Wear lOS 0.3 8 0.1 159 510XB 006 3 T-TSP Wear 12S -0.7 27 0.54 123 510XB 004 3 T-TSP Wear 12S 0.3 20 0.36 137 510XB 004 3 T-TSP.Wear 11S -0.7 30 0.62 120 510XB 004 3 T-TSP Wear 11S 0.3 11 0.17 147 510XB 004 4 T-TSP Wear 12S -0.8 20 0.3 119 510XB 006 4 T-TSP Wear 12S 0.3 22 0.34 146 510XB 006 4 T-TSP Wear 11S -0.7 24 0.38 118 510XB 006 5 T-TSP Wear 12S 0.3 20 0.35 134 510XB 004 5 T-TSP Wear 11S 0.3 12 0.19 143 510XB 004 5 T-TSP Wear 11S -0.7 25 0.48 121 510XB 004 Aril2, Tuesdy, 201 .. g..f6 Tuesday, April 24, 2012 Page 3of 67
TMI-12-O071, TMI-1 Steam Generator Tube Inspection Report (T1R19)
-Attachment-,Exhibit-2 SG BA All Service Induced Indications. Outage T1R19 Location % Ind. In d Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 2 6 T-TSP Wear 12S -0.8 32 0.6 119 P1 510XB 006 B 2 6 T-TSP Wear 11S .- 0.7 28 0.49 108 P1 510XB 006 B 2 7 T-TSP Wear 13S 0.3 7 0.11 146 P1 510XB 004 B 2 7 T-TSP Wear 12S -0.7 19 0.35 119 P1 510XB 004 B 2 7 T-TSP Wear 11S -0.7 24 0.45 117 P1 510XB 004 B 2 7 T-TSP Wear 1S 0.3 12 0.2 149 P1 510XB 004 B 2 8 T-TSP Wear 13S -0.8 5 0.07 105 P1 510XB 006 B 2 8 T-TSP Wear 13S 0.2 10 0.12 148 P1 510XB 006 B 2 8 T-TSP Wear 12S -0.7 19 0.28 99 P1 510XB 006 B 2 8 T-TSP Wear 11S -0.8 31 0.56 113 P1 510XB 006 B 2 9 T-TSP Wear 12S -0.8 22 0.41 130 P1 510XB 004 B 2 9 T-TSP Wear 11S -0.7 34 0.76 118 P1 510XB 004 B 2 9 T-TSP Wear 11S 0.4 10 0.15 148 P1 510XB 004 B 2 9 T-TSP Wear 10S 0.3 11 0.17 152 P1 510XB 004 B 2 10 T-TSP Wear 12S -0.7 14 0.18 109 P1 510XB 006 B 2 10 T-TSP Wear 11S -0.8 23 0.37 117 P1 510XB 006 B 2 11 T-TSP Wear 12S -0.7 11 0.17 113 P1 51OXB 004 B 2 11 T-TSP Wear 11S -0.7 22 0.4 125 P1 51OXB 004 B 2 11 T-TSP Wear 10S 0.3 11 0.18 147 P1 510XB 004 B 2 12 T-TSP Wear 12S -0.8 8 0.09 103 P1 510XB 006 B 2 12 T-TSP Wear 12S 0.3 12 0.15 144 P1 51OXB 006 B 2 12 T-TSP Wear loS 0.3 15 0.2 151 P1 510XB 006 B 2 14 T-TSP Wear 11S -0.8 7 0.09 122 P1 51OXB 006 B 2 14 T-TSP Wear 10S 0.3 27 0.46 145 P1 51OXB 006 B 2 15 T-TSP Wear 11S -0.8 11 0.17 130 P1 510XB 004 April24, Tuesday, 2012 Page4of67 Tuesday, April 24, 2012 Page 4 of 67
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG BA All Service Induced Indications.Outage T1R19 Location % InL Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 2 15 T-TSP Wear loS 0.3 18 0.31 134 P1 510XB 004 B 2 16 T-TSP Wear 12S -0.8 9 0.12 129 P1 510XB 006 B 2 16 T-TSP Wear 11S -0.8 13 0.17 118 P1 510XB 006 B 2 16 T-TSP Wear 10S 0.4 26 0.44 134 P1 510XB 006 B 2 17 T-TSP Wear 11S -0.8 31 0.67 124 P1 510XB 002 B 2 17 T-TSP Wear 10S 0.4 18 0.3 143 P1 510XB 002 2 18 T-TSP Wear 11S -0.8 38 0.95 118 510XB 002 2 18 T-TSP Wear 11S 0.3 14 0.23 157 510XB 002 2 18 T-TSP Wear loS -0.7 23 0.41 126 510XB 002 2 18 T-TSP Wear loS 0.4 12 0.19 158 510XB 002 2 19 T-TSP Wear 11S -0.7 8 0.11 121 510XB 002 2 19 T-TSP Wear 11S 0.4 7 0.11 149 51OXB 002 2 19 T-TSP Wear 10S -0.8 21 0.39 127 510XB 002 2 19 T-TSP Wear loS 0.4 21 0.38 140 510XB 002 2 20 T-TSP Wear 11S -0.8 35 0.82 116 510XB 002 2 20 T-TSP Wear 10S -0.8 24 0.45 123 510XB 002 2 20 T-TSP Wear loS 0.4 14 0.22 156 510XB 002 2 21 T-TSP Wear 11S -0.8 43 1.17 110 510XB 002 2 21 T-TSP Wear loS -0.7 7 0.1 108 510XB 002 2 21 T-TSP Wear 10S 0.4 25 0.48 139 510XB 002 2 22 T-TSP Wear 12S 0.4 11 0.16 145 510XB 002 2 22 T-TSP Wear -12S -0.7 10 0.16 141 510XB 002 2 22 T-TSP Wear 11S -0.8 42 1.11 117 510XB 002 2 22 T-TSP Wear 10S 0.4 20 0.35 138 510XB 002 B 2 23 T-TSP Wear 12S 0.4 12 0.2 146 P1 51OXB 002 Tuesday, April 24, 2012 Pg 5 off667 Page
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attt-chmne)tI-.Exhib-it-2 SG B, All Service Induced Indications, Outa, e TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 2 23 T-TSP Wear 11S -0.8 42 1.12 114 P1 510XB 002 B 2 24 T-TSP Wear 12S -0.8 14 0.23 127 P1 510XB 002 B 2 24 T-TSP Wear 12S 0.4 14 0.23 151 P1 510XB 002 B 2 24 T-TSP Wear 11S 0.3 18 0.31 161 P1 510XB 002 B 2 24 T-TSP Wear 11S -0.8 45 1.29 109 P1 510XB 002 B 2 24 T-TSP Wear lOS -0.8 6 0.09 117 P1 510XB 002 B 2 25 T-TSP Wear 11S -0.7 6 0.08 134 P1 510XB 002 B 2 25 T-TSP Wear 11S 0.4 6 0.08 150 P1 510XB 002 B 2 26 T-TSP Wear 12S -0.7 11 0.17 129 P1 510XB 002 B 2 26 T-TSP Wear 12S 0.4 18 0.3 131 P1 510XB 002 B 2 26 T-TSP Wear 11S -0.8 41 1.05 120 P1 510XB 002 B 2 26 T-TSP Wear 10S 0.4 18 0.3 139 P1 510XB 002 B 2 27 T-TSP Wear 12S -0.7 11 0.17 150 P1 510XB 002 B 2 28 T-TSP Wear 12S 0.4 22 0.41 144 P1 510XB 002 B 2 28 T-TSP Wear 11S 0.4 19 0.33 159 P1 510XB 002 B 2 29 T-TSP Wear 12S 0.4 23 0.43 156 P1 510XB 002 B 2 29 T-TSP Wear 11S 0.4 18 0.31 161 P1 510XB 002 B 2 29 T-TSP Wear 10S 0.4 20 0.34 152 P1 510XB 002 B 2 30 T-TSP Wear 12S -0.8 6 0.09 116 P1 510XB 002 B 2 31 T-TSP Wear 12S -0.7 12 0.15 151 P1 510XB 006 B 3 1 T-TSP Wear 12S -0.7 12 0.2 117 P1 510XB 004 B 3 1 T-TSP Wear 12S 0.3 27 0.53 131 P1 510XB 004 B 3 1 T-TSP Wear 11S -0.7 6 0.09, 82 P1 510XB 004 B 3 2 T-TSP Wear 12S 0.4 12 0.14 150 P1 510XB 040 B 3 2 T-TSP Wear 10S 0.4 11 0.14 154 P1 510XB 040 Page 6 of 67 Tuesday, April 24, 2012 April24, Tuesday, 2012 Page 6 of 67
TMI-12-0 71, TMI-1 Steam Generator Tube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications.Outage T1R19 Location % Ind. Ind Axial Circ.
SG Row Tube Tyvpe TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 3 4 T-TSP Wear 11S -0.7 9 0.11 127 P1 510XB 040 B 3 4 T-TSP Wear 11S 0.4 18 0.24 145 P1 510XB 040 B 3 4 T-TSP Wear 10S 0.4 13 0.17 146 P1 510XB 040 B 3 5 T-TSP Wear 12S 0.3 15 0.24 161 P1 510XB 004 B 3 5 T-TSP Wear 11S -0.7 25 0.48 112 P1 510XB 004 B 3 6 T-TSP Wear 12S 0.3 23 0.37 155 P1 510XB 006 B 3 6 T-TSP Wear 11S 0.4 17 0.23 149 P1 510XB 006 B 3 6 T-TSP Wear 11S -0.7 27 0.46 115 P1 510XB 006 B 3 8 T-TSP Wear 11S -0.7 29 0.53 129 P1 51OUL 675 B 3 9 T-TSP Wear 12S 0.4 9 0.13 160 P1 51OUL 673 B 3 9 T-TSP Wear 11S -0.7 23 0.39 126 P1 51OUL 673 B 3 9 T-TSP Wear 11S 0.3 13 0.19 156 P1 51OUL 673 B 3 10 T-TSP Wear 14S 0.2 8 0.1 143 P1 51OUL 675 B 3 10 T-TSP Wear 11S -0.7 23 0.37 133 P1 51OUL 675 B 3 11 T-TSP Wear 12S 0.7 9 0.13 161 P1 51OUL 673 B 3. 11 T-TSP Wear 11S -0.7 30 0.56 122 P1 51OUL 673 B 3 12 T-TSP Wear 11S -0.8 21 0.33 132 P1 51OUL 675 B 3 13 T-TSP Wear 11S -0.7 12 0.18 129 P1 51OUL 673 B 3 14 T-TSP Wear 11S -0.8 .14 0.2 129 P1 51OUL 675 B 3 15 T-TSP Wear 11S -0.7 7 0.09 108 P1 51OUL 673 B 3 16 T-TSP Wear 11S -0.7 10 0.14 143 P1 51OUL 675 B 3 17 T-TSP Wear 11S 0.3 15 0.23 143 P1 51OUL 673 B 3 17 T-TSP Wear 11S -0.5 18 0.29 164 P1 51OUL 673 B 3 18 T-TSP Wear 10S -0.8 13 0.19 128 P1 51OUL 667 Page 7 of 67 Tuesday, April 24, 2012 April24, Tuesday, 2012 Page 7 of 67
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19),
Attachment-i .Exhibit-2 SG B. All Service Induced Indications, Outage TJR19 Location % Ind Ind Axial Circ.
SG Row Tube Tyvpe TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal 3 19 T-TSP Wear 1S -0.7 6 0.09 87 51OUL 665 3 19 T-TSP Wear 10S -0.7 17 0.31 109 51OUL 665 3 20 T-TSP Wear 11S -0.8 8 0.11 135 51OUL 667 3 20 T-TSP Wear loS -0.7 11 0.15 93 51OUL 667 3 21 T-TSP Wear 11S 0.3 17 0.3 139 51OUL 665 3 21 T-TSP Wear 10S -0.7 20 0.37 112 51OUL 665 3 22 T-TSP Wear 11S -0.8 17 0.26 132 51OUL 667 3 22 T-TSP Wear lOS -0.8 25 0.42 117 51OUL 667 3 23 T-TSP Wear 14S 0.2 10 0.16 150 51OUL 665 3 23 T-TSP Wear 12S 0.3 8 0.13 130 51OUL 665 3 23 T-TSP Wear 11S -0.8 7 0.11 139 51OUL 665 3 24 T-TSP Wear 12S 0.3 16 0.23 143 51OUL 667 3 24 T-TSP Wear 11S -0.7 15 0.21 119 51OUL 667 3 25 T-TSP Wear 11S -0.8 28 0.6 114 51OUL 665 3 25 T-TSP Wear 11S 0.4 17 0.31 140 51OUL 665 3 26 T-TSP Wear 11S -0.7 20 0.31 123 51OUL 667 3 26 T-TSP Wear 10S 0.3 12 0.16 158 51OUL 667 3 27 T-TSP Wear 11S 0.3 11 0.19 149 51OUL 665 3 27 T-TSP Wear 11S -0.7 32 0.74 122 51OUL 665 3 28 T-TSP Wear 11S -0.7 21 0.34 124 51OUL 667 3 29 T-TSP Wear 11S 0.4 15 0.26 144 51OUL 665 3 29 T-TSP Wear 11S -0.7 10 0.17 120 51OUL 665 3 30 T-TSP Wear 11S -0.7 6 0.08 120 510XB 002 3 30 T-TSP Wear 11S 0.4 31 0.66 145 51OXB 002 Page8of67 Tuesday, April24, Tuesday, April 2012 24, 2012 Page 8 of67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications,Outage TJR19 Location % Ind. Indt Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 3 31 T-TSP Wear 11S 0.4 24 0.45 152 P1 510XB 002 B 3 31 T-TSP Wear 11S 0.4 14 0.22 147 P1 510XB 002 B 3 32 T-TSP Wear 14S 0.2 10 0.15 133 P1 510XB 002 B 3 32 T-TSP Wear los -0.7 10 0.15 134 P1 510XB 002 B 3 33 T-TSP Wear 12S -0.7 12 0.18 131 P1 510XB 002 B 3 34 T-TSP Wear 14S 0.3 12 0.18 143 P1 510XB 002 B 3 34 T-TSP Wear 13S 0.2 9 0.14 151 P1 510XB 002 B 3 34' T-TSP Wear loS 0.4 26 0.51 137 P1 510XB 002 B 4 3 T-TSP Wear 14S 0.2 9 0.11 150 P1 510XB 006 B 4 3 T-TSP Wear lOS -0.7 10 0.13 81 P1 51OXB 006 B 4 8 T-TSP Wear 12S -0.7 17 0.25 139 P1 51OUL 675 B 4 9 T-TSP Wear 10S 0.4 21 0.34 138 P1 51OUL 673 B 4 11 T-TSP Wear 10S -0.7 11 0.15 154 P1 51OUL 673 B 4 12 T-TSP Wear 10S -0.7 7 0.09 117 P1 51OUL 675 B 4 13 T-TSP Wear 10S -0.8 6 0.08 111 P1 51OUL 673 B 4 14 T-TSP Wear 14S 0.2 9 0.12 145 P1 51OUL 675 B 4 14 T-TSP Wear lOS -0.7 10 0.13 93 P1 51OUL 675 B 4 22 T-TSP Wear 14S 0.2 8 0.11 143 P1 51OUL 667 B 4 23 T-TSP Wear 14S -0.8 10 0.16 147 P1 51OUL 665 B 4 23 T-TSP Wear 11S 0.3 15 0.26 160 P1 51OUL 665 B 4 25 T-TSP Wear 11S 0.3 23 0.45 141 P1 51OUL 665 B 4 26 T-TSP Wear 11S 0.4 27 0.47 140 P1 51OUL 667 B 4 27 T-TSP Wear 11S 0.4 21 0.41 148 P1 51OUL 665 B 4 27 T-TSP Wear loS -0.7 7 0.11 47 P1 51OUL 665 Tuesday, April 24, 2012 Page 9 of 67
TMI-12-O 71, TMI-1 Steam GeneratorTube Inspection Report (TJRJ9)
-~~Ai~diiiment-17E~rh-ibi12 SG B, All Service Induced Indications.Outawe T1R19 Location % Ind Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal 4 28 T-TSP Wear 11S 0.4 0.46 149 P1 51OUL 667 4 30 T-TSP Wear 12S 0.3 0.14 154 P1 51OUL 667 4 33 T-TSP Wear 12S -0.7 0.14 104 P1 51OUL 665 4 34 T-TSP Wear 10S -0.7 0.14 73 P1 51OUL 665 4 35 T-TSP Wear loS -0.7 0.14 97 P1 510XB 002 5 1 T-TSP Wear 14S 0.1 0.24 132 P1 51OXB 004 5 4 T-TSP Wear 10S -0.8 0.18 144 P1 510XB 006 5 11 T-TSP Wear 10S -0.7 0.17 140 P1 51OUL 675 5 23 T-TSP Wear 14S 0.2 0.14 145 P1 51OUL 667 5 23 T-TSP Wear 10S -0.8 0.11 112 P1 51OUL 667 5 25 T-TSP Wear 14S 0.3 0.15 144 P1 51OUL 667 5 26 T-TSP Wear 11S 0.3 0.22 168 P1 51OUL 665 5 28 T-TSP Wear 11S 0.4 0.16 160 P1 51OUL 665 5 31 T-TSP Wear 14S -0.8 0.1 114 P1 51OUL 667 5 40 T-TSP Wear 14S -0.8 0.11 132 P1 51OXB 002 5 41 T-TSP Wear 10S 0.4 0.17 156 P1 510XB 002 5 42 T-TSP Wear 14S 0.3 0.28 135 P1 510XB 002 5 42 T-TSP Wear 13S 0.3 0.19 152 P1 510XB 002 6 1 T-TSP Wear 14S 0.1 0.19 132 P1 510XB 004 6 2 T-TSP Wear 14S -0.7 0.11 120 P1 510XB 004 6 2 T-TSP Wear 13S 0.0 0.35 144 P1 510XB 004 6 3 T-TSP Wear 14S -0.8 0.13 145 P1 51OXB 006 6 5 T-TSP Wear loS -0.8 19 0.29 133 P1 510XB 006 2012 Page 10 of 67 April24, Tuesday, Tuesday, April 24, 2012 Page 10 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG B. All Service Induced Indications. Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal 6 9 T-TSP Wear 14S -0.8 8 0.1 137 P1 51OUL 675 6 9 T-TSP Wear 12S 0.3 14 0.19 147 51OUL 675 6 12 - T-TSP Wear 14S 0.2 0.11 135 51OUL 673 6 12 T-TSP Wear 14S -0.8 0.1 128 51OUL 673 6 13 T-TSP Wear 14S -0.8 0.1 139 51OUL 675 6 13 T-TSP Wear 13S -0.8 0.13 148 51OUL 675 6 13 T-TSP Wear 11S 0.3 0.12 154 51OUL 675 6 13 T-TSP Wear 10S -0.7 0.11 118 51OUL 675 6 14 T-TSP Wear 13S -0.8 0.13 146 51OUL 673 6 17 T-TSP Wear 14S 0.2 0.15 148 51OUL 675 6 17 T-TSP Wear lOS -0.7 0.21 139 51OUL 675 6 18 T-TSP Wear lOS -0.8 0.08 115 51OUL 673 6 19 T-TSP Wear 14S -0.8 0.09 130 51OUL 667 6 20 T-TSP Wear 10S -0.7 0.19 141 51OUL 665 6 21 T-TSP Wear 14S -0.8 0.09 123 51OUL 667 6 21 T-TSP Wear 10S -0.8 0.15 110 51OUL 667 6 23 T-TSP Wear 14S -0.8 0.11 137 51OUL 667 6 23 T-TSP Wear 11S 0.3 0.19 152 51OUL 667 6 24 T-TSP Wear 11S 0.3 0.2 149 51OUL 665 6 25 T-TSP Wear 14S 0.2 0.18 132 51OUL 667 6 25 T-TSP Wear 11S 0.3 0.28 152 51OUL 667 6 25 T-TSP Wear 10S -0.8 0.25 112 51OUL 667 6 26 T-TSP Wear 14S -0.9 0.12 108 51OUL 665 6 26 T-TSP Wear 11S 0.3 0.23 152 51OUL 665 Tuesday, April 24, 2012 Page 11 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Atta-cdfment-i .Exhidbit-2 SG B. All Service Induced Indications. Outae TJRI9 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 6 27 T-TSP Wear 11S 0.3 8 0.11 149 P1 51OUL 667 B 6 29 T-TSP Wear 14S -0.8 8 0.11 138 P1 510UL 667 B 6 30 T-TSP Wear 14S -0.9 9 0.15 146 P1 51OUL 665 B 6 30 T-TSP Wear 12S 0.3 6 0.1 142 P1 51OUL 665 B 6 45 T-TSP Wear loS 0.4 23 0.42 139 P1 510XB 002 B 7 2 T-TSP Wear 14S -0.9 6 0.08 131 P1 51OXB 006 B 7 4 T-TSP Wear 14S 0.2 13 0.18 143 P1 510XB 006 B 7 4 T-TSP Wear 14S -0.9 8 0.1 125 P1 51OXB 006 B 7 6 T-TSP Wear 14S 0.2 11 0.15 152 P1 51OUL 675 B 7 8 T-TSP Wear 14S 0.2 9 0.12 134 P1 51OUL 675 B 7 11 T-TSP Wear 14S -0.8 9 0.12 137 P1 51OUL 673 B 7 11 T-TSP Wear 14S .0.2 8 0.11 152 P1 51OUL 673 B 7 11 T-TSP Wear 11S -0.7 19 0.3 142 P1 51OUL 673 B 7 11 T-TSP Wear 11S 0.3 17 0.26 154 P1 51OUL 673 B 7 14 T-TSP Wear 15S -0.8 9 0.12 127 P1 51OUL 675 B 7 14 T-TSP Wear 11S -0.7 13 0.18 147 P1 51OUL 675 B 7 14 T-TSP Wear 11S 0.3 13 0.18 139 P1 51OUL 675 B 7 15 T-TSP Wear 14S -0.8 11 0.16 149 P1 51OUL 673 B 7 15 T-TSP Wear 11S 0.3 16 0.25 142 P1 51OUL 673 B 7 15 T-TSP Wear loS 0.4 17 0.26 163 P1 51OUL 673 B 7 16 T-TSP Wear 11S -0.7 7 0.09 138 P1 51OUL 675 B 7 16 T-TSP Wear 11S 0.3 16 0.24 153 P1 51OUL 675 B 7 17 T-TSP Wear 15S 0.2 16 0.23 157 P1 51OUL 673 B 7 17 T-TSP Wear 11S 0.3 10 0.13 152 P1 51OUL 673 Tuesday, April 24, 2012 Page 12 of 67
TMI-12-0 71, TMI-1 Steam Generator Tube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG BA All Service Induced Indications.Outare TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 7 18 T-TSP Wear 10S -0.7 8 0.11 81 P1 51OUL 673 B 7 24 T-TSP Wear 11S 0.3 11 0.18 137 P1 51OUL 665 B 7 26 T-TSP Wear 10S -0.8 7 0.11 137 P1 51OUL 665 B 7 33 T-TSP Wear 14S -0.7 9 0.12 111 P1 51OUL 667 B 7 34 T-TSP Wear 14S -0.9 6 0.09 111 P1 51OUL 665 B 7 35 T-TSP Wear 14S 0.2 10 0.13 145 P1 51OUL 667 B 7 35 T-TSP Wear 11S 0.3 9 0.12 154 P1 51OUL 667 B 7 36 T-TSP Wear 14S 0.2 8 0.12 142 P1 51OUL 665 B 7 36 T-TSP Wear 11S 0.3 10 0.16 149 P1 51OUL 665 B 7 36 T-TSP Wear 10S 0.0 8 0.13 145 P1 51OUL 665 B 7 37 T-TSP Wear 11S 0.4 21 0.33 139 P1 51OUL 667 B 7 41 T-TSP Wear 14S 0.3 17 0.25 142 P1 51OUL 667 B 7 48 I-TSP Wear 14S -0.8 8 0.12 150 P1 51OXB 002 B 7 48 T-TSP Wear 10S 0.4 10 0.16 146 P1 510XB 002 B 7 49 T-TSP Wear 14S 0.0 28 0.55 149 P1 510XB 002 B 8 3 T-TSP Wear 14S -0.8 13 0.18 139 P1 510XB 006 B 8 4 T-TSP Wear 14S -0.8 8 0.12 147 P1 510XB 004 B 8 16 T-TSP Wear 11S 0.3 10 0.14 135 P1 51OUL 673 B 8 45 T-TSP Wear 15S 0.2 9 0.14 144 P1 51OUL 729 B 8 45 T-TSP Wear 14S -0.8 13 0.22 142 P1 51OUL 729 B 8 46 T-TSP Wear 14S -0.8 6 0.08 132 P1 51OUL 731 B 8 48 T-TSP Wear 14S 0.2 18 0.26 138 P1 51OUL 519 B 8 49 T-TSP Wear 14S -0.8 11 0.18 143 P1 51OUL 517 Tuesday, April 24, 2012 Page 13 of 67
TMI-12--071, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
-A-ttA ttih-me-nt-1*E*h-bFit 2 SG BA All Service Induced Indications. Outa, e TJR19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 8 50 T-TSP Wear 14S 0.3 11 0.18 138 P1 510XB 002 B 8 50 T-TSP Wear 14S -0.8 7 0.1 147 P1 510XB 002 B 8 50 T-TSP Wear los 0.4 7 0.1 149 P1 510XB 002 B 8 51 T-TSP Wear 14S 0.3 8 0.13 149 P1 510XB 002 B 8 51 T-TSP Wear 14S -0.8 5 0.07 145 P1 510XB 002 B 8 51 T-TSP Wear lOS 0.4 10 0.15 160 P1 510XB 002 B 8 52 T-TSP Wear 14S 0.0 22 0.4 147 P1 510XB 002 B 8 53 T-TSP Wear 14S -0.8 8 0.12 134 P1 510XB 002 B 8 53 T-TSP Wear 13S 0.2 9 0.14 138 P1 510XB 002 B 8 54 T-TSP Wear 14S 0.0 24 0.44 133 P1 51OXB 002 B 9 3 T-TSP Wear 14S 0.2 8 0.13 127 P1 510XB 004 B 9 8 T-TSP Wear 14S -0.8 7 0.12 143 P1 51OUL 609 B 9 12 T-TSP Wear 10S -0.7 27 0.47 137 P1 51OUL 675 B 9 14 T-TSP Wear 11S 0.3 12 0.17 146 P1 51OUL 675 B 9 53 T-TSP Wear 14S -0.8 9 0.15 139 P1 51OUL 517 B 9 55 T-TSP Wear 14S 0.0 22 0.4 136 P1 51OXB 002 B 9 56 T-TSP Wear 14S -0.2 14 0.22 142 P1 510XB 002 B 9 56 T-TSP Wear lOS 0.4 21 0.38 135 P1 510XB 002 B 9 57 T-TSP Wear 14S -0.8 14 0.23 130 P1 51OXB 002 B 9 57 T-TSP Wear 10S 0.4 25 0.47 134 P1 51OXB 002 B 9 59 T-TSP Wear 14S -0.8 5 0.07 111 P1 510XB 002 B 9 59 T-TSP Wear 14S 0.2 10 0.16 141 P1 510XB 002 B 9 60 T-TSP Wear 14S 0.3 13 0.2 147 P1 510XB 002 B 10 1 T-TSP Wear lOS 0.4 15 0.2 153 P1 510XB 014 Tuesday, April 24, 2012 Page 14 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG BA All Service Induced Indications.Outaze TJR19 Location % Ind Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 10 3 T-TSP Wear loS -0.8 14 0.22 131 P1 510XB 012 B 10 5 T-TSP Wear los -0.8 9 0.14 134 P1 510XB 012 B 10 6 T-TSP Wear 14S -0.8 9 0.14 139 P1 510XB 012 B 10 15 T-TSP Wear 11S 0.3 12 0.17 144 P1 51OUL 675 B 10 58 T-TSP Wear 14S 0.2 9 0.12 141 P1 51OUL 519 B 10 59 T-TSP Wear 14S -0.8 10 0.16 143 P1 51OUL 517 B 10 60 T-TSP Wear 10S 0.4 12 0.19 161 P1 510XB 002 B 11 3 T-TSP Wear 12S -0.7 11 0.14 140 P1 510XB 014 B 11 9 T-TSP Wear 15S 0.3 6 0.1 140 P1 51OUL 609 B 11 12 T-TSP Wear 14S -0.9 8 0.11 140 P1 51OUL 611 B 11 13 T-TSP Wear 10S -0.7 12 0.2 128 P1 51OUL 609 B 11 16 T-TSP Wear 11S 0.3 9 0.11 152 P1 51OUL 675 B 11 18 T-TSP Wear 11S 0.3 12 0.17 151 P1 51OUL 675 B 11 19 T-TSP Wear 11S 0.3 10 0.13 159 P1 51OUL 675 B 11 21 T-TSP Wear 14S -0.9 6 0.07 88 P1 51OUL 675 B 11 23 T-TSP Wear 11S 0.3 8 0.14 144 P1 51OUL 729 B 11 64 T-TSP Wear 14S 0.3 7 0.1 155 P1 51OXB 002 B 11 64 T-TSP Wear 14S -0;8 7 0.1 125 P1 510XB 002 B 11 66 T-TSP Wear 14S 0.2 11 0.16 128 P1 510XB 002 B 12 2 T-TSP Wear 14S 0.1 8 0.12 136 P1 510XB 012 B 12 5 T-TSP Wear 09S 0.4 8 0.13 148 PI 51OUL 609 B 12 6 T-TSP Wear 15S -1.0 11 0.17 151 P1 51OUL 611 B 12 8 T-TSP Wear 14S 0.1 12 0.19 137 P1 51OUL 611 2012 Page 15 of 67 April24, Tuesday, Tuesday, April 24, 2012 Page 15of 67
TMI-12--071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
A-tti h t-len7-1iEXhibit2 SG BA All Service Induced Indications.Outa2e T1RI9 Location % Ind. Ind. Axial Circ.
SG Row Tube Tvpe TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 12 10 T-TSP Wear 14S 0.1 15 0.23 134 P1 51OUL 611 B 12 12 T-TSP Wear 14S 0.2 8 0.11 143 P1 51OUL 611.
B 12 12" T-TSP Wear 10S -0.8 24 0.45 134 P1 51OUL 611 B 12 13 T-TSP Wear 10S -0.7 6 0.1 130 P1 51OUL 609 B 12 16 T-TSP Wear 11S 0.3 13 0.21 140 P1 51OUL 685 B 12 16 T-TSP Wear 11S -0.6 11 0.18 135 P1 51OUL 685 B 12 16 T-TSP Wear 09S 0.4 14 0.24 150 P1 51OUL 685 B 12 16 T-TSP Wear 09S -0.8 8 0.12 126 P1 51OUL 685 B 12 17 - T-TSP Wear 11S 0.3 9 0.14 151 P1 51OUL 685 B 12 67 T-TSP Wear 14S 0.3 6 0.09 144 P1 510XB 002 B 12 69 T-TSP Wear 12S -0.7 9 0.14 59. P1 510XB 002 B 12 69 T-TSP Wear 11S 0.4 13 0.2 161 P1 510XB 002 B 12 69 T-TSP Wear 10S 0.4 10 0.16 158 P1 510XB 002 B 13 7 T-TSP Wear 14S 0.1 11 0.17 143 P1 51OUL 611 B 13 13 T-TSP Wear 14S -0.9 8 0.11 134 P1 51OUL 611 B 13 16 T-TSP Wear 11S 0.3 7 0.11 142 P1 51OUL 609 B 13 17 T-TSP Wear 14S 0.2 9 0.15 .126 P1 51OUL 609 B 13 17 T-TSP Wear 11S 0.3 10 0.17 138 P1 51OUL 609 B 13 18 T-TSP Wear 11S 0.3 11 0.17 143 P1 51OUL 685 B 13 73 T-TSP Wear 12S -0.8 22 0.39 127 P1 510XB 002 B 13 73 T-TSP Wear 12S 0.3 9 0.13 152 P1 510XB 002 B 13 74 T-TSP Wear 12S -0.8 6 0.08 123 P1 510XB 002 B 13 74 T-TSP Wear 12S 0.3 13 0.2 140 P1 510XB 002 B 14 2 T-TSP Wear 14S 0.1 11 0.16 129 P1 510XB 012 Tuesday, April 24,2012 Page 16 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TJR19)
Attachment 1, Exhibit 2 SG BA All Service Induced Indications.Outaie T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 14 4 T-TSP Wear 14S -0.9 7 0.1 133 P1 510XB 012 B 14 10 T-TSP Wear 15S 0.2 8 0.14 141 P1 51OUL 609 B 14 15 T-TSP Wear 15S 0.2 8 0.11 136 P1 51OUL 611 B 14 16 T-TSP Wear 11S 0.3 6 0.09 145 P1 51OUL 609 B 14 17 T-TSP Wear 11S 0.2 13 0.21 138 P1 51OUL 611 B 14 21 T-TSP Wear 14S -0.8 12 0.15 125 P1 51OUL 699 B 14 35 T-TSP Wear 15S 0.1 8 0.1 142 P1 51OUL 699 B 14 67 T-TSP Wear 14S 0.2 8 0.12 135 P1 51OUL 517 B 14 75 T-TSP Wear 14S 0.2 6 0.09 127 P1 510XB 002 B 14 75 T-TSP Wear 12S 0.4 11 0.17 159 P1 510XB 002 B 14 75 T-TSP Wear 12S -0.8 5 0.08 92 P1 510XB 002 B 14 75 T-TSP Wear 11S 0.4 23 0.42 148 P1 510XB 002 B 14 75 T-TSP Wear 11S -0.7 17 0.29 113 P1 51OXB 002 B 14 76 T-TSP Wear 14S 0.2 11 0.17 133 P1 510XB 002 B 14 76 T-TSP Wear 12S -0.7 12 0.19 122 P1 510XB 002 B 14 76 T-TSP Wear 12S 0.4 30 0.64 128 P1 510XB 002 B 14 76 T-TSP Wear 10S 0.4 11 0.17 157 P1 510XB 002 B 14 77 T-TSP Wear 13S 0.3 7 0.1 150 P1 510XB 002 B 14 77 T-TSP Wear 12S -0.8 7 0.1 129 P1 510XB 002 B 14 77 T-TSP Wear 12S "0.4 18 0.32 142 P1 510XB 002 B 15 2 T-TSP Wear 14S 0.3 7 0.09 125 P1 510XB 012 B 15 7 T-TSP Wear 11S -0.7 10 0.15 143 P1 51OUL 611 B 15 7 T-TSP Wear' 11S 0.4 13 0.21 153 P1 510UL 611 B 15 9 T-TSP Wear 14S 0.2 8 0.11 146 P1 51OUL 611 Tuesday, April 24, 2012 Page 17 of 67
TMI-12-O 71, TMI-1 Steam GeneratorTube Inspection Report (TJRJ19)
A'ttachment-1-i-Exhibit-SG B, All Service Induced Indications. Outa2e T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 15 77 T-TSP Wear 12S -0.8 7 0.1 .128 P1 510XB 002 B 15 77 T-TSP Wear 11S 0.4 8 0.11 147 P1 510XB 002 15 78 T-TSP Wear 12S 0.4 14 0.23 140 P1 510XB 002 15 78 T-TSP Wear 11S -0.7 10 0.16 139 P1 510XB 002 15 79 T-TSP Wear 14S -0.8 8 0.12 128. P1 510XB 004 15 79 T-TSP Wear 14S 0.2 7 0.1 126 P1 510XB 004 15 79 T-TSP Wear 13S -0.8 5 0.07 142 P1 510XB 004 15 79 T-TSP Wear 13S 0.2 8 0.12 133 P1 510XB 004 15 79 T-TSP Wear 12S -0.8 21 0.39 128 P1 51OXB 004 15 79 T-TSP Wear 12S 0.4 30 0.62 125 P1 510XB 004 15 79 T-TSP Wear 10S 0.4 9 0.14 134 P1 510XB 004 15 80 T-TSP Wear 14S 0.3 6 0.09 136 P1 510XB 004 15 80 T-TSP Wear 13S 0.2 6 0.09 137 P1 510XB 004 15 80 T-TSP Wear 12S -0.7 11 0.17 124 P1 51OXB 004 15 80 T-TSP Wear 12S 0.3 8 0.13 145 P1 510XB 004 B 16 6 T-TSP Wear 10S -0.7 16 0.28 135 P1 51OUL 615 B 16 7 T-TSP Wear 12s 0.4 14 0.2 146 P1 51OUL 617 B 16 9 T-TSP Wear 11S -0.8 17 0.25 135 P1 51OUL 617 B 16 9 T-TSP Wear 11S 0.3 15 0.23 134 P1 51OUL 617 B 16 79 T-TSP Wear 12S -0.8 9 0.14 136 P1 510XB 004 B 16 79 T-TSP Wear 11S -0.7 8 0.12 131 P1 510XB 004 B 16 80 T-TSP Wear 12S -0.8 19 0.32 126 P1 510XB 004 B 16 80 T-TSP Wear 11S -0.8 36 0.88 123 P1 510XB 004 B 16 81 T-TSP Wear 12S -0.8 12 0.19 123 P1 510XB 004 B 16 81 T-TSP Wear 12S 0.4 18 0.31 135 P1 510XB 004 T.eda, pri24.212P.g 1...6 Tuesday, April 24, 2012 Page 18of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B. All Service Induced Indications.Outage TJR19 Location % Ilnd. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 17 6 T-TSP Wear 11S 0.4 14 0.2 156 P1 51OUL 617 B 17 8 T-TSP Wear 11S 0.4 15 0.22 146 P1 51OUL 617 B 17 81 T-TSP Wear 11S 0.3 12 0.18 136 P1 51OUL 521 B 17 82 T-TSP Wear 14S 0.2 7 0.1 133 P1 510XB 004 B 17 82 T-TSP Wear 12S -0.8 8 0.11 135 P1 510XB 004 B 17 82 T-TSP Wear 12S 0.4 10 0.16 137 P1 510XB 004 B 17 82 T-TSP Wear 11S -0.8 10 0.15 132 P1 510XB 004 B 17 83 T-TSP Wear 12S -0.8 27 0.54 119 P1 510XB 004 B 17 83 T-TSP Wear 12S 0.4 9 0.14 151 P1 510XB 004 B 18 7 T-TSP Wear 10S -0.8 15 0.23 126 P1 51OUL 617 B 18 8 T-TSP Wear 11S 0.3 16 0.28 151 P1 51OUL 615 B 18 8 T-TSP Wear 11S -0.8 7 0.11 117 P1 51OUL 615 B 18 9 T-TSP Wear 14S -0.9 8 0.12 145 P1 51OUL 617 B 18 21 T-TSP Wear 09S -0.7 7 0.1 104 P1 51OUL 617 B 18 79 T-TSP Wear 12S 0.3 14 0.18 162 P1 51OUL 523 B 18 81 T-TSP Wear 11S 0.4 21 0.3 153 P1 51OUL 523 B 18 83 T-TSP Wear 12S 0.3 11 0.18 141 P1 510XB 004 B 18 83 T-TSP Wear 10S 0.4 12 0.18 150 P1 510XB 004 B 18 84 T-TSP Wear 12S -0.7 10 0.15 121 P1 510XB 004 B 18 84 T-TSP Wear 11S -0.7 21 0.37 119 P1 510XB 004 B 18 85 T-TSP Wear 12S 0.3 8 0.13 165 P1 510XB 004 B 19 8 T-TSP Wear 11S 0.4 8 0.13 153 P1 51OUL 697 B 19 8 T-TSP Wear 10S -0.7 7 0.11 89 P1 51OUL 697 B 19 9 T-TSP Wear 15S 0.2 5 0.08 134 P1 51OUL 697 Tuesday, April 24, 2012 Page 19 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment-l.Exhibit-2 SG B, All Service Induced Indications.Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 19 9 T-TSP Wear 11S 0.4 17 0.31 132 P1 510UL .697 B 19 10 T-TSP Wear 11S 0.3 7 0.09 155 P1 51OUL 617 B 19 11 T-TSP Wear 14S -0.9 7 0.11 136 P1 510UL 615 B 19 85 T-TSP Wear 11S 0.4 16 0.21 158 P1 510UL 523 B 19 86 T-TSP Wear 12S 0.3 14 0.24 156 P1 510XB 004 B 19 86 T-TSP Wear 11S -0.8 19 0.33 123 P1 510XB 004 B 19 87 T-TSP Wear 13S -0.8 6 0.09 71 P1 51OXB 004 B 19 87 T-TSP Wear 138 0.2 19 0.33 128 P1 510XB 004 B 19 87 T-TSP Wear 12S -0.8 7 0.1 .103 P1 51OXB 004 B 19 87 T-TSP Wear 11S -0.8 8 0.12 96 P1 51OXB 004 B 20 8 T-TSP Wear 11S 0.3 6 0.1 147 P1 51OUL 615 B 20 86 T-TSP Wear 11S 0.3 18 0.25 155 P1 51OUL 523 B 20 87 T-TSP Wear 11S -0.8 10 0.16 131 P1 510XB 004 B 20 88 T-TSP Wear 11S -0.8 28 0.56 119 P1 510XB 004 B 20 88 T-TSP Wear 11S 0.3 9 0.13 159 P1 510XB 004 B 20 89 T-TSP Wear 11S -0.8 17 0.29 117 P1 510XB 004 B 20 89 T-TSP Wear 11S 0.3 14 0.22 144 P1 510XB 004 B 21 1 T-TSP Wear 14S 0.2 10 0.12 133 P1 510XB 014 B 21 2 T-TSP Wear 14S 0.2 8 0.12 134 P1 510XB 012 B 21 7 T-TSP Wear 15S 0.2 10 0.14 139 P1 51OUL 617 B 21 9 T-TSP Wear 15S 0.2 6 0.08 135 P1 51OUL 617 B 21 9 T-TSP Wear 11S 0.3 9 0.13 143 P1 510UL 617 B 21 14 T-TSP Wear 11S 0.3 11 0.18 154 P1 51OUL 615 B 21 39 T-TSP Wear 08S 0.3 12 0.16 153 P1 51OUL 699 Tuesday, April 24, 2012 Page 20 of 67
TMI-12-0 71, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications.Outage TJR19 Location % Ind Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 21 52 T-TSP Wear 08S 0.3 15 0.2 152 P1 51OUL 699 B 21 52 T-TSP Wear 07S 0.4 12 0.16 162 P1 51OUL 699 B 21 55 T-TSP Wear 07S 0.4 9 0.12 147 P1 51OUL 699 B 21 58 T-TSP Wear 07S 0.4 11 0.14 159 P1 51OUL 699 B 21 61 T-TSP Wear 08S 0.3 12 0.16 157 P1 51OUL 699 B 21 88 T-TSP Wear 11S 0.4 28 0.47 138 P1 51OUL 523 B 21 89 T-TSP Wear 12S 0.3 12 0.18 148 P1 510XB 004 B 21 89 T-TSP Wear 11S -0.8 9 0.14 102 P1 510XB 004 B 21 90 T-TSP Wear 14S 0.2 15 0.25 135 P1 510XB 004 B 21 90 T-TSP Wear 11S -0.7 9 0.13 117 P1 510XB 004 B 22 8 T-TSP Wear 1OS -0.7 6 0.1 101 P1 51OUL 615 B 22 9 T-TSP Wear 11S 0.3 12 0.18 152 P1 51OUL 617 B 22 27 T-TSP Wear 08S 0.4 19 0.27 163 P1 51OUL 711 B 22 33 T-TSP Wear .08S 0.3 9 0.11 146 P1 51OUL 711 B 22 52 T-T Wear 08S 18.3 5 15.8 20.8 5.0 53 0.23 103 129 510XP 803 B 22 52 T-T Wear 08S 19.6 9 16.5 22.7 6.3 53 0.57 75 53 510XP 803 B 22 53 T-T Wear 08S 20.3 10 16.9 23.8 6.9 67 0.62 73 65 510XP 803 B 22 62 T-TSP Wear 09S 0.4 8 0.1 150 P1 51OUL 699 B 22 62 T-TSP Wear 08S 0.4 9 0.11 154 P1 51OUL 699 B 22 62 T-T Wear 08S 17.4 15 13.6 21.2 7.6 67 1.29 84 57 510XP 803 B 22 63 T-TSP Wear 08S -0.8 13 0.17 106 P1 51OUL 699 B 22 63 T-T Wear 08S 17.4 13 13.7 21.1 7.5 67 0.99 93 69 510XP 803 B 22 63 T-T Wear 08S 18.6 10 15.5 21.7 6.2 67 0.63 99 5 510XP 803 B 22 67 T-T Wear 08S 18.5 6 16.3 20.7 4.4 53 0.3 73 93 510XP 809 Tuesday, April 24, 2012 Page21 of 6 7
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TJR19)
Attachment-li.Exhibit-2 SG BA All Service Induced Indications.Outare T1R19 Location % Ind Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 22 67 T-TSP Wear 08S -0.8 9 0.14 110 P1 51OUL 521 B 22 90 T-TSP Wear 11S 0.4 13 0.17 150 P1 51OUL 523 B 22 91 T-TSP Wear 11S -0.8 9 0.14 123 P1 510XB 004 B 22 91 T-TSP Wear 11S 0.4 17 0.29 155 P1 510XB 004 B 22 92 T-TSP Wear 12S 0.3 16 0.27 155 P1 510XB 004 B 23 8 T-TSP Wear 11S 0.3 9 0.13 151 P1 51OUL 617 B 23 8 T-TSP Wear loS -0.7 17 0.27 127 P1 51OUL 617 B 23 9 T-TSP Wear 11S 0.3 10 0.16 141 P1 51OUL 615 B 23 10 T-TSP Wear lOS -0.8 14 0.2 129 P1 51OUL 617 B 23 46 T-T Wear 08S 19.4 8 17.0 21.7 4.7 80 0.41 74 81 510XP 803 B 23 52 T-T Wear 08S 19.4 4 17.5 21.3 3.8 67 0.17 59 117 510XP 803 B 23 54 T-TSP Wear 08S 0.3 17 0.22 156 P1 51OUL 711 B 23 60 T-T Wear 08S 17.7 6 16.3 19.1 2.8 67 0.25 72 165 510XP 803 B 23 61 T-TSP Wear 08S 0.4 10 0.17 144 P1 51OUL 729 B 23 62 T-T Wear 07S 20.4 6 18.4 22.4 4.0 67 0.28 84 41 510XP 803 B 23 63 T-T Wear 08S 17.9 11 14.7 21.1 6.4 67 0.73 94 17 510XP 803 B 23 66 T-TSP Wear 08S 0.4 13 0.17 160 P1 51OUL 523 B 23 68 T-TSP Wear 08S 0.4 19 0.28 154 P1 51OUL 523 B 23 68 T-TSP Wear 07S 0.5 14 0.18 158 P1 51OUL 523 B 23 93 T-TSP Wear 12S 0.3 15 0.25 142 P1 510XB 004 B 23 93 T-TSP Wear 11S -0.8 7 0.11 91 P1 51OXB 004 B 24 7 T-TSP Wear 11S 0.3 8 0.13 151 P1 51OUL 615 B 24 8 T-TSP Wear 11S 0.3 11 0.16 151 P1 51OUL 617 iuesday, April24, 2012 Page 22 of 67 Tuesday, April 24, 2012 Page 22 of 6 7
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG BA All Service Induced Indications.Outage T1R19 Location %d. Ind. Axial Cire.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 24 18 T-TSP Wear 09S -0.7 0.07 83 P1 51OUL 615 B 24 38 T-TSP Wear 08S 0.4 0.23 143 P1 51OUL 709 B 24 38 T-TSP Wear 07S 0.4 0.17 149 P1 51OUL 709 B 24 41 T-TSP Wear 08S 0.3 0.14 153 P1 51OUL 711 B 24 43 T-TSP Wear 07S 0.4 0.1 151 P1 51OUL 711 B 24 47 T-TSP Wear 08S 0.4 0.17 153 P1 51OUL 711 B 24 53 T-TSP Wear 08S -0.7 0.08 45 P1 51OUL 711 B 24 53 T-TSP Wear 08S 0.3 0.13 148 P1 51OUL 711 B 24 55 T-TSP Wear 08S 0.3 0.2 149 P1 51OUL 711 B 24 55 T-T Wear 08S 18.8 16.7 20.9 4.2 67 0.32 78 153 510XP 803 B 24 90 T-TSP Wear 14S -0.8 0.08 140 P1 510XB 004 B 24 90 T-TSP Wear 11S -0.8 0.15 136 P1 510XB 004 B 25 8 T-TSP Wear 11S 0.3 0.11 141 P1 51OUL 617 B 25 8 T-TSP Wear 10S 0.4 0.14 149 P1 51OUL 617 B 25 11 T-TSP Wear 14S 0.2 0.1 141 P1 51OUL 615 B 25 29 T-T Wear 08S 19.4 16.5 22.3 5.8 53 0.42 77 89 510XP 809 B 25 33 T-T Wear 08S 18.9 15.2 22.6 7.4 53 0.91 82 45 510XP 803 B 25 34 T-TSP Wear 08S .0.3 0.15 158 P1 51OUL 711 B 25 35 T-TSP Wear 07S 0.4 0.18 132 P1 51OUL 709 B 25 39 T-TSP Wear 08S 0.3 0.16 139 P1 51OUL 709 B 25 39 T-T Wear 08S 18.5 14.8 22.3 7.6 53 1.2 90 21 510XP 803 B 25 45 T-TSP Wear 08S 0.3 0.26 151 P1 51OUL 709 B 25 56 T-TSP Wear 07S 0.4 0.16 149 P1 51OUL 709 B 25 59 T-T Wear 08S 18.9 16.9 21.0 4.1 67 0.23 103 17 510XP 803 Tuesday, April 24, 2012 Page 23 of 67
TMI-12-O 71, TMI-1 Steam GeneratorTube Inspection Report (TJRJ9)
-~AttachrnentlT;Exhibit-2 SG B, All Service InducedIndications.Outa2e T1R19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal 25 60 T-TSP Wear 08S 0.4 0.18 161 P1 51OUL 709 26 2 T-TSP Wear 14S 0.2 0.12 143 P1 510XB 014 26 29 T-TSP Wear 08S 0.4 0.14 149 P1 51OUL 615 26 29 T-T Wear 08S 18.7 15.8 21.6 5.8 53 0.43 79 45 510XP 809 26 30 T-T Wear 08S 18.9 16.6 21.3 4.7 53 0.36 86 89 510XP 803 26 30 T-T Wear 08S 19.4 17.2 21.7 4.5 53 0.38 92 165 510XP 803 26 32 T-TSP Wear 08S 0.3 0.09 157 P1 51OUL 711 26 33 T-T Wear 08S 18.8 15.3 22.4 7.1 53 0.98 89 33 510XP 803 26 39 T-T Wear 08S 18.4 14.8 22.1 7.3 53 1.02 88 9 510XP 803 26 41 T-TSP Wear 08S 0.3 0.2 146 P1 51OUL 709 26 43 T-T Wear 08S 18.6 16.0 21.2 5.2 67 0.57 76 45 510XP 803 26 61 T-TSP Wear 08S -0.8 0.13 97 P1 51OUL 709 26 62 T-TSP Wear 08S 0.3 0.11 156 P1 51OUL 711 26 69 T-TSP Wear 07S 0.4 0.18 153 P1 51OUL 521 26 71 T-TSP Wear 08S 0.4 0.2 150 P1 51OUL 521 26 77 T-TSP Wear 08S 0.4 0.22 129 P1 51OUL 521 26 98 T-TSP Wear 14S 0.2 0.09 125 P1 510XB 004 26 98 T-TSP Wear 11S -0.8 0.17 125 P1 510XB 004 26 98 T-TSP Wear 11S 0.4 0.14 159 P1 510XB 004 27 44 T-T Wear 08S 18.5 16.2 20.9 4.7 67 0.56 89 33 510XP 803 27 44 T-TSP Wear 07S 0.4 0.09 156 P1 51OUL 711 27 49 T-T Wear 08S 18.4 16.0 20.7 4.7 53 0.31 82 81 510XP 803 27 50 T-T Wear 08S 18.6 15.5 21.8 6.3 67 0.31 86 69 510XP 803 Page 24 of 67 Tuesday, April24, Tuesday, April 2012 24, 2012 Page24 of 6 7
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications, Outage TJR19 Location % In. Ind. Axial Cire.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 27 70 T-TSP Wear 08S 0.4 19 0.27 143 P1 51OUL 523 B 27 73 T-TSP Wear 08S 0.4 15 0.24 136 P1 51OUL 521 B 27 76 T-TSP Wear 07S 0.4 11 0.14 158 P1 51OUL 523 B 27 100 T-TSP Wear 14S 0.3 6 0.09 136 P1 510XB 004 B 27 100 T-TSP Wear 11S 0.4 19 0.33 146 P1 510XB 004 B 27 101 T-TSP Wear 12S 0.3 12 0.19 137 P1 51OXB 004 B 27 102 T-TSP Wear 11S -0.8 6 0.08 128 P1 510XB 004 B 28 6 T-TSP Wear 10S -0.7 12 0.19 126 P1 51OUL 621 B 28 7 T-TSP Wear 09S 0.4 8 0.12 154 P1 51OUL 619 B 28 8 T-TSP Wear 11S -0.8 22 0.39 134 P1 51OUL 621 B 28 42 T-T Wear 07S 20.1 6 17.8 22.3 4.5 53 0.27 50 45 510XP 803 B 28 56 T-TSP Wear 08S 0.4 11 0.13 150 P1 51OUL 711 B 28 57 T-TSP Wear 08S 0.4 10 0.17 147 P1 51OUL 709 B 28 68 T-T Wear 08S 18.3 5 16.5 20.0 3.5 67 0.18 76 149 510XP 803 B 28 68 T-T Wear 08S 17.8 4 16.1 19.5 3.4 67 0.17 65 65 510XP 803
-B 28 71 T-TSP Wear 08S -0.7 13 0.21 113 P1 51OUL 521 B 28 102 T-TSP Wear 11S -0.8 9 0.13 126 P1 510XB 004 B 28 102 T-TSP Wear 11S 0.3 10 0.15 156 P1 510XB 004 B 28 103 T-TSP Wear 14S 0.3 7 0.1 135 P1 510XB 004 B 28 103 T-TSP Wear 14S 0.0 10 0.15 132 P1 510XB 004 B 29 31 T-T Wear 08S 18.0 6 15.5 20.4 4.9 53 0.29 85 21 510XP 803 B 29 31 T-TSP Wear 08S 0.4 9 0.13 146 P1 51OUL 621 B 29 32 T-T Wear 08S 18.4 5 15.2 21.5 6.3 53 0.2 87 125 510XP 803 B 29 32 T-T Wear 08S 18.0 10 14.5 21.5 7.0 53 0.64 87 41 510XP 803 Tuesday, Apri124, 2012 Page 25 of 67
TMI-12-O 71, TMI-1 Steam Generator Tube Inspection Report (TJRJ19)
-Attachment-]yExhibit-2 SG B, All Service Induced Indications, Outage T1R19 Location % Ind. hid. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 29 32 T-T Wear 07S 20.5 6 18.5 22.6 4.2 53 0.26 66 29 510XP 803 B 29 33 T-T Wear 08S 19.1 5 17.5 20.7 3.3 0.23 64 45' 510XP 53 803 B 29 38 T-T Wear 08S 18.2 5 16.1 20.3 4.2 53 0.22 78 101 510XP 803 B 29 39 T-T Wear 08S 18.4 5 16.6 20.2 3.6 53 0.2 61 89 510XP 803 B 29 39 T-TSP Wear 08S 0.4 0.12 157 P1 51OUL 711 B 29 42 T-T Wear 08S 19.1 16.8 21.4 4.6 53 0.34 80 45 510XP 803 B 29 67 T-TSP Wear 08S -0.8 0.09 106 P1 51OUL 711 B 29 68 T-T Wear 08S 17.9 15.4 20.5 5.0 53 0.47 97 29 510XP 803 B 29 68 T-TSP Wear 08S 0.4 0.14 153 P1 51OUL 709 B 29 69 T-T Wear 08S 17.0 14.5 19.6 5.1 67 0.53 82 41 510XP 803 B 29 70 T-TSP Wear 08S 0.3 0.16 147 P1 51OUL 521 B 29 73 T-TSP Wear 08S 0.4 0.2 146 P1 51OUL 523k B 29 73 T-TSP Wear 08S -0.7 0.15 141 P1 51OUL 523 B 29 73 T-TSP Wear 07S 0.4 0.17 154 P1 51OUL 523 B 29 103 T-TSP Wear 11S 0.4 0.35 133 P1 510XB 004 B 30 31 T-T Wear 08S 17.2 14.3 20.2 5.9 53 0.16 46 9 510XP 803 B 30 31 T-T Wear 08S 18.7 16.3 21.1 4.8 53 0.25 75 5 510XP 803 B 30 32 T-T Wear 08S 18.0 14.7 21.4 6.6 53 0.69 88 29 510XP 803 B 30 33 T-T Wear 08S 17.8 15.2 20.3 5.1 53 0.2 66 137 510XP 803 B 30 34 T-TSP Wear 08S 0.3 0.13 151 P1 51OUL 709 B 30 34 T-T Wear 08S 18.8 16.4 21.2 4.7 53 0.29 74 29 510XP 803 B 30 35 T-T Wear 08S 19.1 16.7 21.5 4.8 53 0.28 83 45 510XP 803 B 30 36 T-T Wear 08S 18.4 16.4 20.4 4.0 53 0.21 77 41 510XP 803 B 30 42 T-T Wear 08S 19.5 17.2 21.7 4.5 53 0.43 78 33 510XP 803 Tuesday, April 24, 2012 Page 26 of 67
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B. All Service Induced Indications.Outaze TIR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 30 74 T-TSP Wear 08S 0.4 9 0.13 126 P1 51OUL 521 B 30 81 T-TSP Wear 08S 0.4 12 0.15 152 P1 51OUL 523 B 30 104 T-TSP Wear 11S 0.4 21 0.37 141 P1 510XB 004 B 30 105 T-TSP Wear 13S -0.7 9 0.13 138 P1 510XB 004 B 30 105 T-TSP Wear 13S 0.3 9 0.14 134 P1 510XB 004 B 31 2 T-TSP Wear 10S -0.8 7 0.09 100 P1 510XB 012 B 31 4 T-TSP Wear 10S -0.8 9 0.14 123 P1 51OUL 619 B 31 5 T-TSP Wear 14S -0.9 6 0.09 141 P1 51OUL 621 B 31 34 T-TSP Wear 07S -0.7 8 0.09 114 P1 51OUL 711 B 31 35 T-T Wear 08S 19.1 7 16.5 21.6 5.2 53 0.36 64 29 510XP 803 B 31 45 T-T Wear 08S 18.8 7 16.3 21.3 4.9 67 0.36 73 45 510XP 803 B 31 56 T-T Wear 08S 17.9 .8 15.2 20.7 5.5 67 0.43 98 129 510XP 803 B 31 64 T-T Wear 08S 18.8 5 16.7 21.0 4.2 67 0.21 69 53 510XP 803 B 31 73 T-TSP Wear 08S 0.3 10 0.15 141 P1 51OUL 521 B 31 76 T-TSP Wear 08S 0.4 10 0.12 146 P1 51OUL 523 B 31 105 T-TSP Wear 11S 0.3 16 0.26 142 P1 510XB 004 B 32 2 T-TSP Wear 14S 0.2 7 0.09 140 P1 510XB 012 B 32 7 T-TSP Wear 10S 5
-0.7 0.08 121 P1 51OUL 621 B 32 9 T-TSP Wear 10S -0.8 11 0.17 148 P1 51OUL 621 B 32 .25 T-T Wear 08S 18.6 4 16.7 20.5 3.8 53 0.15 97 21 510XP 803 B 32 26 T-T Wear 08S 19.6 5 17.2 21.9 4.7 53 0.18 85 69 510XP 803 B 32 26 T-T Wear 08S 19.6 5 17.2 21.9 4.7 53 0.19 66 5 510XP 803 B 32 27 T-T Wear 08S 18.4 9 15.6 21.2 5.5 53 0.55 94 153 510XP 803 Tuesday, April 24, 2012 Page 27 of 67
TMI-12-O071, TMI-1 Steam Generator Tube Inspection Report (TIR19)
Attch-me-nt-lEXhibit-2 SG B, All Service Induced Indications,Outa2e T1R19 Location Ind. IntL Axial Circ.
SG Row Tjube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal 28 T-T Wear 08S 17.9 4 16.3 19.4 3.2 0.16 76 69 510XP 803 29 T-T Wear 08S 18.0 10 15.2 20.9 5.8 0.67 88 41 510XP 803 32 T-TSP Wear 08S 0.4 8 0.13 151 P1 51OUL 619 34 T-T Wear 08S 19.2 7 16.9 21.5 4.6 0.35 71 77 510XP 803 35 T-T Wear 08S 19.5 6 17.5 21.5 4.0 0.25 88 89 510XP 803 38 T-TSP Wear 08S 0.4 9 0.14 155 P1 51OUL 709 40 T-T Wear 08S 18.3 5 15.7 20.9 5.2 0.19 71 53 510XP 803 44 T-T Wear 08S 18.5 6 16.2 20.7 4.5 0.31 69 29 510XP 803 55 T-T Wear 08S 18.7 5 17.0 20.5 3.5 0.22 102 57 510XP 803 56 T-T Wear 08S 18.4 8 15.4 21.4 6.1 0.43 88 137 510XP 803 56 T-T Wear 08S 18.5 4 16.9 20.1 3.2 0.16 86 69 510XP 803 59 T-T Wear 08S 19.0 5 17.3 20.7 3.4 0.23 91 105 510XP 803 63 T-TSP Wear 08S 0.3 10 0.13 151 P1 51OUL 711 67 T-T Wear 08S 18.1 8 15.5 20.6 5.1 0.43 91 101 510XP 803 69 T-T Wear 08S 18.1 6 16.0 20.3 4.3 0.31 87 101 510XP 803 69 T-T Wear 08S 18.1 7 15.9 20.2 4.4 0.34 89 P8 510XP 803 24 .T-TSP Wear 08S 0.4 9 0.14 164 P1 51OUL 619 26 T-T Wear 08S 19.8 5 17.8 21.9 4.1 0.23 72 153 510XP 807 27 T-T Wear 08S 19.4 5 17.6 21.2 3.6 0.19 87 101 510XP 807 28 T-T Wear 08S 18.5 7 15.9 21.1 5.2 0.34 92 101 510XP 807 30 T-T Wear 08S 18.4 3l 15.4 21.3 5.9 0.71 86 149 510XP 807 44 T-TSP Wear 08S 0.4 11 0.17 154 P1 51OUL 709 49 T-T Wear 08S 18.2 3 16.2 20.1 3.9 53 0.11 89 117 510XP 803 Page 28of 67 Tuesdqv, April 24, 2012 April24, Tuesday, 2012 Page28of 67
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG BA All Service InducedIndications.Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal
-.- j B 33 52 T-TSP Wear 08S 0.4 11 0.19 159 P1 51OUL 709 B 33 61 T-TSP Wear 08S 0.4 14 0.18 146 P1 51OUL 711 B 33 61 T-T Wear 08S 18.4 5 16.9 20.0 3.1 80 0.21 57 117 510XP 803 B 33 69 T-T Wear 08S 18.6 7 16.1 21.0 4.9 67 0.39 95 113 510XP 803 B 33 76 T-TSP Wear 08S 0.4 14 0.23 144 P1 51OUL 533 B 33 107 T-TSP Wear iS 0.3 11 0.18 142 P1 510XB 004 B 33 107 T-TSP Wear is -0.8 10 0.15 126 P1 510XB 004 B 34 3 T-TSP Wear 10S -0.7 0.08 69 P1 51OXB 012 B 34 6 T-TSP Wear 15S 0.2 0.15 144 P1 51OUL 621 B 34 8 T-TSP Wear 11s -0.8 0.15 135 P1 51OUL 621 B 34 20 T-TSP Wear 09S 0.4 0.16 142 P1 51OUL 621 B 34 25 T-T Wear 08S 20.1 17.4 22.8 5.4 53 0.46 78 165 510XP 807 B 34 25 T-T Wear 08S 18.9 16.5 21.3 4.8 53 0.18 85 93 510XP 807 B 34 26 T-T Wear 08S 20.3 18.0 22.5 4.5 53 0.44 70 165 510XP 807 B 34 27 T-T Wear 08S 20.3 17.0 23.6 6.7 40 0.78 88 165 510XP 807 B 34 27 T-T Wear 08S 19.2 16.6 21.7 5.1 40 0.36 92 89 510XP 807 B 34 28 T-TSP Wear 08S 0.3 0.27 152 P1 51OUL 621 B 34 29 T-TSP Wear 08S 0.4 0.13 162 P1 51OUL 619 B 34 64 T-TSP Wear 08S 0.3 0.1 142 P1 51OUL 711 B 34 69 T-TSP Wear 08S 0.4 0.14 151 P1 51OUL 729 B 34 71 T-TSP Wear 08S 0.4 0.12 152 P1 51OUL 729 B 34 85 T-TSP Wear 08S 0.4 0.24 148 P1 51OUL 533 B 34 110 T-TSP Wear 11S 0.4 0.15 143 P1 510XB 006 Tuesday, April 24, 2012 Page29qf67
TMI-12-O 71, TMI-1 Steam Generator Tube Inspection Report (TJRJ9)
-~~A-fdct~Me-ntF1yE..hibWjt2 SG B, All Service (T1R19)
Induced Indications. Outa2e TJR19 Report Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Inspection Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal Tube Generator Steam TMI-1 A-tt TMI-12-071, B 35 1 T-TSP Wear lS -0.7 9 0.11 128 P1 510XB 014 B 35 1 T-TSP Wear los -0.8 16 0.22 128 P1 510XB 014 B 35 4 T-TSP Wear 14S 0.2 7 0.1 145 P1 51OUL 621 B 35 6 T-TSP Wear 11S 0.3 8 0.12 154 P1 51OUL 621 B 35 23 T-TSP Wear 08S 0.4 7 0.1 148 P1 51OUL 619 B 35 25 T-T Wear 08S 20.1 8 17.6 22.5 5.0 53 0.44 102 153 510XP 807 B 35 26 T-T Wear 08S 20.1 8 17.5 22.8 5.4 53 0.42 91 153 510XP 807 B 35 27 T-T Wear 08S 20.3 13 17.0 23.6 6.7 53 0.97 87 153 510XP 807 B 35 28 T-T Wear 08S 19.4 8 16.9 21.9 5.0 53 0.41 101 77 510XP 807 B 35 30 T-T Wear 08S 19.2 9 16.4 21.9 5.5 53 0.53 83 161 510XP 807 B 35 31 T-T Wear 08S 19.3 5 17.0 21.6 4.5 53 0.22 71 149 510XP 807 B 35 33 T-TSP Wear 08S 0.3 13 0.21 162 P1 51OUL 619 B 35 34 T-T Wear 08S 19.4 6 16.7 22.2 5.5 53 0.26 67 89 510XP 807 B 35 35 T-T Wear 08S 18.7 5 16.7 20.8 4.1 53 0.2 77 161 510XP 807 B 35 35 T-TSP Wear 08S 0.3 10 0.16 163 P1 51OUL 619 B 35 56 T-TSP Wear 08S 0.3 9 0.14 146 P1 51OUL 709 B 35 74 T-TSP Wear 08S 0.4 12 0.18 143 P1 51OUL 533 B 35 82 T-TSP Wear 08S 0.4 10 0.16 142 P1 51OUL 533 B 35 111 T-TSP Wear 11S 0.4 21 0.33 140 P1 510XB 042 B 35 112 T-TSP Wear 10S 0.4 11 0.17 162 P1 510XB 004 B 36 5 T-TSP Wear 10S -0.7 11 0.17 145 P1 51OUL 621 B 36 28 T-TSP Wear 08S 0.4 7 0.11 159 P1 51OUL 619 B 36 30 T-T Wear 08S 19.2 8 16.4 22.1 5.7 53 0.47 81 149 510XP 807 2012 Page 30 of 67 April24, Tuesday, Tuesday, April 24, 2012 Page30 of 67 b-it-2
- Exh-i
- -*h-m-e*t-l
TMI-12-0 71, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG B. All Service InducedIndications, Outage T1R19 Location %d. d Ind Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 36 31 T-T Wear 08S 18.0 4 16.7 19.3 2.6 53 0.15 .66 29 510XP 807 B 36 34 T-T Wear 08S 20.2 4 17.8 22.5 4.8 53 0.17 68 29 510XP 807 B 36 79 T-TSP Wear 08S 0.4 12 0.16 154 P1 51OUL 535 B 36 82 T-TSP Wear 08S 0.4 8 0.12 142 P1 510UL 533 B 36 86 T-TSP Wear 08S 0.4 9 0.14 148 P1 51OUL 533 B 36 90 T-TSP Wear 08S 0.4 10 0.16 139 P1 51OUL 533 B 36 112 T-TSP Wear 11S 0.4 17 0.29 155 P1 510XB 004 B 36 113 T-TSP Wear 11S -0.8 12 0.17 140 P1 510XB 034 B 36 113 T-TSP Wear 11S 0.4 19 0.28 139 P1 510XB 034 B 37 7 T-TSP Wear 11S -0.8 11 0.17 148 P1 51OUL 621 B 37 28 T-TSP Wear 08S 0.4 11 0.17 154 P1 51OUL 619 B 37 33 T-TSP Wear 08S 0.4 11 0.16 156 P1 51OUL 621 B 37 73 T-TSP Wear 08S 0.4 10 0.15 145 P1 51OUL 717 B 37 74 T-TSP Wear 08S 0.4 9 0.14 138 P1 51OUL 717 B 37 81 T-TSP Wear 08S 0.4 11 0.16 133 P1 51OUL 533 B 37 83 T-TSP Wear 08S 0.4 8 0.11 130 P1 51OUL 533 B 37 84 T-TSP Wear 08S 0.4 13 0.16 154 P1 51OUL 535 B 37 85 T-TSP Wear 08S 0.4 12 0.18 136 P1 51OUL 533 B 37 87 T-TSP Wear 08S 0.4 8 0.11 142 P1 51OUL 533 B 37 91 T-TSP Wear 08S 0.4 7 0.11 136 P1 51OUL 533 B 37 94 T-TSP Wear 08S 0.3 14 0.18 153 P1 51OUL 535 B 37 114 T-TSP Wear 11S 0.4 23 0.37 134 P1 510XB 034 B 38 5 T-TSP Wear loS -0.7 6 0.09 133 P1 51OUL 619 Tluesday, April 24, 2012 Page31 of 67
TMI-12--071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment-l.Exhibit-2 SG BA All Service Induced Indications, Outage TJR19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal 38 30 T-TSP Wear 08S 0.3 0.21 157 P1 51OUL 621 38 33 T-TSP Wear 08S 0.4 0.18 161 P1 51OUL 619 38 33 T-T Wear 08S 19.9 17.3 22.4 5.1 53 0.48 69 161 510XP 807 38 34 T-TSP Wear 08S 0.4 0.19 154 P1 51OUL 621 38 37 T-TSP Wear 08S 0.3 0.19 161 P1 51OUL 619 38 74 T-T Wear 08S 18.8 .17.6 20.0 2.4 67 0.19 79 57 510XP 803 38 87 T-TSP Wear 07S -0.8 0.08 106 P1 51OUL 535 38 111 T-TSP Wear 11S 0.3 0.19 151 P1 51OUL 535 38 114 T-TSP Wear 14S 0.3 0.09 149 P1 510XB 034 39 4 T-TSP Wear 10S -0.7 0.1 127 P1 51OUL 621 39 5 T-TSP Wear 09S 0.4 0.19 164 P1 51OUL 619 39 7 T-TSP Wear 14S 0.2 0.11 150 P1 51OUL 619 39 30 T-TSP Wear 08S 0.4 0.17 160 P1 51OUL 621 39 33 T-TSP Wear 08S 0.3 0.12 154 P1 51OUL 619 39 34 T-T Wear 08S 18.7 16.3 21.0 4.8 53 0.42 91 113 510xP 807 39 34 T-T Wear 08S 18.2 16.1 20.2 4.1 53 0.34 84 165 510XP 807 39 35 T-TSP Wear 08S 0.4 0.19 164 P1 51OUL 619 39 74 T-TSP Wear 07S 0.4 0.13 148 P1 51OUL 717 39 77 T-TSP Wear 08S 0.4 0.11 155 P1 51OUL 535 39 90 T-T Wear 08S 17.7 15.4 20.0 4.7 67 0.37 94 57 510XP 803 39 91 T-T Wear 08S 18.5 16.0 20.9 5.0 53 0.49 79 77 510XP 803 40 33 T-T Wear 08S 18.3 16.5 20.1 3.6 53 0.26 108 153 510XP 807 B 40 34 T-T Wear 08S 18.8 7 16.4 21.2 4.8 53 0.4 85 101 . 510XP 807 Tuesday, April 24, 2012 Tuesay, pri24, 012Page 32 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications. Outaze TJR19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal 40 82 T-TSP Wear 08S 0.4 9 0.13 127 P1 51OUL 533 40 83 T-TSP Wear 08S 0.3 12 0.15 158 P1 51OUL 535 40 84 T-TSP Wear 08S 0.3 10 0.15 119 P1 51OUL 533 40 90 T-T Wear 08S 18.1 15.9 20.3 4.4 67 0.26 80 93 510XP 803 40 91 T-T Wear 08S 18.2 15.9 20.4 4.5 67 0.24 80 93 510XP 803 40 95 T-TSP Wear 08S -0.8 0.1 123 P1 51OUL 535 40 95 T-T Wear 08S 18.0 16.0 19.9 3.9 53 0.25 92 81 510XP 803 40 95 T-T Wear 08S 17.8 15.2 20.4 5.2 67 0.34 74 9 51OXP 803 40 95 T-TSP Wear 06S -0.7 0.08 107 P1 51OUL 535 40 96 T-T Wear 08S 17.4 15.0 19.9 5.0 80 0.36 90 21 510XP 803 41 32 T-TSP Wear 08S 0.3 0.17 161 P1 51OUL 627 41 37 T-TSP Wear 08S 0.3 0.23 157 P1 51OUL 629 41 38 T-TSP Wear 08S 0.4 0.16 154 P1 51OUL 627 41 90 T-TSP Wear 08S 0.4 0.13 120 P1 51OUL 533 41 95 T-TSP Wear 08S -0.7 0.1 81 P1 51OUL 535 41 95 T-TSP Wear 08S 0.4 0.16 156 P1 51OUL 535 41 96 T-TSP Wear 08S 0.3 0.11 129 P1 51OUL 533 42 2 T-TSP Wear 14S 0.2 0.14 134 P1 510XB 014 42 25 T-T Wear 08S 20.1 17.6 22.5 5.0 53 0.25 93 89 510XP 807 42 25 T-T Wear 08S 20.2 17.5 22.8 5.4 53 0.21 94 165 510XP 807 42 26 T-TSP Wear 08S 0.3 0.19 151 P1 S5OUL 629 42 26 ToT Wear 08S 19.2 7 17.0 21.5 4.5 53 0.32 78 165 51OXP 807 42 27 T-T Wear 08S 17.7 4 16.4 19.0 2.7 53 0.17 86 101 510XP 807 B 42 82 T-TSP Wear 08S 0.4 8 0.12 142 P1 51OUL 541 Page 33 of 67 Tuesday, April24, Tuesday, 2012 April 24, 2012 Page 33 of 6 7
TMI-12-O 71, TMI-1 Steam Generator Tube Inspection Report (TJRJ19)
-Attachment l7-Exhibit-2 SG B, All Service Induced Indications. Outawe TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 42 83 T-TSP Wear 08S 0.4 0.13 149 P1 51OUL 543 B 42 85 T-TSP Wear 08S 0.4 0.11 155 P1 51OUL 543 B 43 24 T-T Wear 08S 18.9 15.9 22.0 6.1 40 0.38 93 165 510XP 807 B 43 25 T-T Wear 08S 19.7 16.5 22.9 6.4 53 0.28 85 153 510XP 807 B 43 26 T-T Wear 08S 20.0 17.9 22.1 4.2 40 0.19 85 101 510XP 807 B 43 26 T-T Wear 08S 18.8 16.9 20.8 3.9 53 0.33 94 153 510XP 807 B 43 32 T-T Wear 08S 19.0 16.6 21.4 4.8 53 0.23 78 117 510XP 807 B 43 34 T-TSP Wear 08S 0.4 0.19 157 P1 51OUL 627 B 43 36 T-TSP Wear 08S 0.3 0.11 147 P1 51OUL 627 B 43 37 T-TSP Wear 08S -0.8 0.1 110 P1 51OUL 629 B 43 73 T-TSP Wear 08S 0.4 0.13 156 P1 51OUL 721 B 43 77 T-TSP Wear 08S 0.4 0.1 153 P1 51OUL 543 B 43 78 T-TSP Wear 08S 0.4 0.09 109 P1 51OUL 541 B 43 85 T-TSP Wear 08S 0.4 0.22 142 P1 51OUL 543 B 43 88 T-TSP Wear 08S 0.4 0.08 107 P1 51OUL 541 B 43 91 T-TSP Wear 08S 0.4 0.1 135 P1 51OUL 543 B 43 93 T-TSP Wear 08S 0.4 0..18 141 P1 51OUL 543 B 44 1 T-TSP Wear 10S -0.8 0.19 141 P1 510XB 022 B 44 24 T-T Wear 08S 19.0 16.1 21.9 5.8 53 0.43 82 153 510XP 807 B 44 26 T-TSP Wear 08S 0.4 0.14 149 P1 51OUL 627 B 44 32 T-T Wear 08S 18.5 '16.2 20.9 4.7 53 0.32 79 65 510XP 807 B 44 33 T-T Wear 08S 18.8 17.0 20.7 3.7 53 0.24 102 105 510XP 807 B 44 33 T-T Wear 08S 18.7 16.7 20.7 4.0 53 0.16 95 53 510XP 807 Tuesday, April 24, 2012 Page34 of 67
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG B. All Service Induced Indications.Outawe T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 44 73 T-TSP Wear 08S 0.4 7 0.11 152 P1 51OUL 721 B 44 74 T-TSP Wear - 08S 0.4 11 0.15 159 P1 51OUL 723 B 44 78 T-TSP Wear 08S 0.4 9 0;12 131 P1 51OUL 541 B 44 79 T-TSP Wear 08S 0.4 18 0.22 154 P1 51OUL 543 B 44 80 T-TSP Wear 08S 0.4 8 0.11 111 P1 51OUL 541 B 45 1 T-TSP Wear 14S 0.3 9 0.12 143 P1 510XB 022 B 45 3 T-TSP Wear 09S 0.4 7 0.13 152 P1 51OUL 725 B 45 4 T-TSP Wear 09S 0.5 0.15 163 P1 51OUL 725 B 45 24 T-T Wear 08S 19.0 15.9 22.0 6.1 53 0.55 88 89 510XP 807 B 45 28 T-T Wear 08S 19.5 16.2 22.7 6.5 53 0.45 80 113 510XP 807 B 45 32 T-T Wear 08S 19.3 17.5 21.0 3.5 63 0.35 73 101 510XP 011 B 45 76 T-TSP Wear 08S 0.4 0.14 157 P1 51OUL 721 B 45 84 T-TSP Wear 08S 0.4 0.17 132 P1 51OUL 541 B 45 90 T-TSP Wear 08S 0.4 0.13 128 P1 51OUL 541 B 45 94 T-TSP Wear 08S -0.7 0.07 88 P1 51OUL 543 B 46 2 T-TSP Wear 14S 0.2 0.12 129 P1 510XB 020 B 46 3 T-TSP Wear 10S -0.8 0.13 128 P1 51OUL 725 B 46 5 T-TSP Wear 15S 0.3 0.14 140 P1 51OUL 725 B 46 6 T-TSP Wear 08S 0.5 0.12 153 P1 51OUL 635 B 46 23 T-TSP Wear 09S 0.4 0.14 148 P1 51OUL 629 B 46 24 T-T Wear 08S 19.0 17.6 20.5 2.9 67 0.14 88 77 510XP 803 B 46 24 T-T Wear 08S 19.0 17.6 20.5 2.9 67 0.11 35 33 510XP 803 B 46 25 T-T Wear 08S 18.8 16.7 20.8 4.1 53 0.39 89 81 510XP 807 Tuesday, April 24, 2012 Page 35 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
-Attachment7-,Exhibit-2 SG BA All Service Induced Indications. Outage T1R19 Location % Imd. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase CChn. Probe Cal B 46 25 T-T Wear 08S 18.8 6 16.9 20.8 3.9 53 0.29 90 153 510XP 807 B 46 26 T-T Wear 08S 20.0 5 18.1 21.9 3.8 40 0.23 91 77 510XP 807 B 46 27 T-TSP Wear 09S 0.4 7 0.1 141 P1 51OUL 629 B 46 29 T-T Wear 08S 19.7 6 17.0 22.4 5.3 53 0.29 64 101 510XP 807 B 46 76 T-TSP Wear 08S 0.3 9 0.12 158 P1 51OUL 723 B 46 84 T-TSP Wear 08S 0.4 11 0.17 163 P1 51OUL 541 B 46 103 T-T Wear 08S 18.9 8 16.5 21.3 4.8 67 0.41 72 101 510XP 803 B 46 112 T-TSP Wear 11S 0.3 10 0.14 144 P1 51OUL 541 B 47 3 T-TSP Wear loS 0.4 13 0.26 161 P1 51OUL 725 B 47 4 T-TSP Wear 14S -0.8 8 0.16 138 P1 51OUL 725 B 47 4 T-TSP Wear 14S 0.3 10 0.19 147 P1 51OUL 725 B 47 7 T-TSP Wear 09S 0.4 8 0.11 145 P1 51OUL 635 B 47 22 T-TSP Wear 08S 0.4 8 0.12 147 P1 51OUL 637 B 47 28 T-TSP Wear 08S 0.3 11 0.15 157 P1 51OUL 637 B 47 73 T-TSP Wear 08S 0.4 12 0.17 152 P1 51OUL 673 B 47 74 T-TSP Wear 08S 0.4 13 0.17 164 P1 51OUL 723 B 47 76 T-TSP Wear 08S 0.4 15 0.21 154 P1 51OUL 723 B 47 81 T-TSP Wear 08S 0.4 8 0.1 148 P1 51OUL 541 B 47 98 T-TSP Wear 08S 0.4 10 0.15 118 P1 51OUL 541 B 47 101 T-T Wear 08S 19.0 8 16.5 21.5 5.0 67 0.46 85 113 510XP 803 B 47 101 T-T Wear 08S 17.8 10 14.6 21.1 6.4 67 0.67 91 165 510XP 803 B 47 102 T-T Wear 08S 18.6 11 15.4 21.9 6.5 67 0.71 91 153 510XP 803 B 47 102 T-TSP Wear 08S 0.4 9 0.11 149 P1 51OUL 543 Tuesday, April 24, 2012 Page 36 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B. All Service Induced Indications.Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 47 118 T-TSP Wear 11S 0.4 17 0.25 149 P1 510XB 034 B 47 118 T-TSP Wear 11S -0.7 9 0.11 119 P1 510XB 034 B 48 1 T-TSP Wear 14S 0.3 13 0.19 143 P1 510XB 022 B 48 4 T-TSP Wear los 0.3 8 0.13 144 P1 51OUL 727 B 48 5 T-TSP Wear 15S 0.3 6 0.12 141 P1 51OUL 725 B 48 6 T-TSP Wear 15S 0.2 9 0.14 134 P1 51OUL 727 B 48 18 T-TSP Wear 08S 0.4 8 0.12 153 P1 51OUL 635 B 48 24 T-TSP Wear 08S 0.3 15 0.26 136 P1 51OUL 635 B *48 78 T-TSP Wear 08S 0.4 8 0.13 151 P1 51OUL 721 B 48 93 T-TSP Wear 08S 0.4 12 0.18 144 P1 51OUL 553 B 48 94 T-TSP Wear 08S 0.4 19 0.29 165 P1 51OUL 555 B 48 117 T-TSP Wear 11S -0.8 9 0.12 128 P1 51OUL 555 B 48 118 T-TSP Wear 11S 0.3 9 0.14 152 P1 51OUL 553 B 49 4 T-TSP Wear 14S 0.3 16 0.28 132 P1 51OUL 727 B 49 5 T-TSP Wear 15S 0.2 7 0.14 137 P1 51OUL 725 B 49 5 T-TSP Wear 10S 0.3 8 0.15 148 P1 51OUL 725 B 49 6 T-TSP Wear 15S 0.2 7 0.11 131 P1 51OUL 727 B 49 9 T-TSP Wear 09S 0.4 11 0.16 158 P1 51OUL 637 B 49 24 T-TSP Wear 08S 0.3 6 0.09 146 P1 51OUL 635 B 49 28 T-TSP Wear 08S 0.4 9 0.14 155 P1 51OUL 635 B 49 30 T-TSP Wear 08S 0.4 9 0.13 154 P1 51OUL 635 B 49 31 T-TSP Wear 08S 0.4 7 0.1 147 P1 51OUL 637 B 49 89 T-TSP Wear 08S -0.8 6 0.07 132 P1 51OUL 555 Tuesday, April 241. 2012 Page 37 of 67
TMI-12-O 71, TMI-1 Steam Generator Tube Inspection Report (TJRJ9)
Atachmenti7-Exhibit-2 SG BA All Service Induced Indications,Outat e TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal 49 95 T-TSP Wear 08S 0.4 0.12 147 P1 51OUL 555 49 96 T-TSP Wear 08S 0.4 0.07 128 P1 51OUL 553 49 115 T-TSP Wear 09S 0.4 0.14 145 P1 51OUL 555 49 119 T-TSP Wear 10S -0.8 0.19 135 P1 51OUL 555 50 3 T-TSP Wear 14S 0.3 0.11 138 P1 51OUL 725 50 28 T-TSP Wear 08S 0.4 0.11 149 P1 51OUL 635 50 36 T-TSP Wear 08S 0.3 0.19 164 P1 51OUL 635 50 98 T-TSP Wear 08S 0.3 0.18 151 P1 51OUL 553 50 103 T-T Wear 08S 18.9 15.2 22.6 7.4 80 1.24 80 53 510XP 803 51 24 T-TSP Wear 08S -0.8 0.1 58 P1 51OUL 635 51 29 T-TSP Wear 08S -0.8 0.08 78 P1 51OUL 637 51 71 T-TSP Wear 08S 0.4 0.17 160 P1 51OUL 723 51 79 T-TSP Wear 09S -0.8 0.1 90 P1 51OUL 555 51 79 T-TSP Wear 08S -0.8 0.08 108 P1 51OUL 555 51 102 T-TSP Wear 08S 0.4 0.14 144 P1 51OUL 555 51 102 T-T Wear 08S 18.9 15.2 22.6 7.4 93 1.18 88 65 510XP 803 51 102 T-T Wear 08S 19.6 16.9 22.4 5.5 67 0.4 114 141 510XP 803 51 103. T-T Wear 08S 18.6 15.6 - 21.6 6.0 80 0.62 82 29 510XP 803 51 104 T-TSP Wear 08S -0.7 0.08 110 P1 51OUL 555 51 113 T-TSP Wear 09S 0.5 0.13 149 P1 51OUL 553 51 120 T-TSP Wear 11S 0.4 12 0.17 155 P1 510XB 034 52 2 T-TSP Wear 10S -0.7 8 0.12 142 P1 510XB 020 B 52 27 T-TSP Wear 08S 0.3 6 0.1 139 P1 51OUL 635 April24, Tuesday, 2012 Page 38 of 67 Tuesday, April 24, 2012 Page 38 of 6 7
TMI-12--071, TMI-1 Steam GeneratorTube Inspection Report (TJR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications. Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal I
52 29 T-TSP Wear 09S 0.4 7 0.1 132 P1 51OUL 635 52 36 T-TSP Wear 08S 0.3 6 0.08 144 P1 51OUL 637 52 89 T-TSP Wear 08S 0.4 9 0.12 146 P1 510XB 036 52 91 T-TSP Wear 08S 0.3 10 0.15 155 P1 51OUL 565 52 104 T-T Wear 08S 19.2 17.2 21.2 4.0 53 0.18 76 69 510XP 809 52 104 T-T Wear 08S 18.5 15.5 21.6 6.1 53 0.34 63 5 51oXP 809 52 104 T-TSP Wear 08S 0.3 0.13 152 P1 51OUL 565 52 106 T-T Wear 08S 18.5 15.2 21.8 6.6 53 0.62 108 117 510XP 809 53 2 T-TSP Wear 10S -0.7 0.1 134 P1 510XB 020 53 37 T-TSP Wear 08S 0.4 0.14 152 P1 51OUL 635 53 105 T-T Wear 08S 19.3 16.4 22.3 5.9 53 0.4 89 105 510XP 809 53 116 T-TSP Wear 11S 0.2 0.14 142 -P1 51OUL 565 53 117 T-TSP Wear 11S 0.3 0.14 157 P1 51OUL 565 53 123 T-TSP Wear 12S 0.3 0.11 159 P1 510XB 034 54 32 T-TSP Wear 08S 0.4 0.13 144 P1 51OUL 635 54 92 T-TSP Wear 08S 0.3 0.13 149 P1 51OUL 565 54 97 T-TSP Wear 08S 0.3 0.15 153 P1 51OUL 565 54 103 T-T Wear 08S 19.0 16.5 21.5 5.0 53 0.34 77 .129 510XP 809 54 105 T-T Wear 08S 18.3 16.2 20.5 4.3 53 0.24 58 129 510XP 809 54 106 T-T Wear 08S 19.3 1616 22.0 5.4 53 0.42 88 113 510XP 809 54 109 T-TSP Wear 09S 0.4 0.1 151 P1 51OUL 565 54 121 T-TSP Wear 11S 0.3 0.3 136 P1 51OUL 565 54 122 T-TSP Wear 11S -0.8 0.32 125 P1 51OUL 565 1'~~ge39 of67 ae 39of 67 Tuesday, April24, Tuesday, April 2012 24, 2012 Pf
TMI-122-O71, TMI-1 Steam Generator Tube Inspection Report (TJRJ9)
-- Attachment .l7Exhibit-2 SG BA All Service Induced Indications.Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal
__j B 55 5 T-TSP Wear 11S -0.7 10 0.2 130 P1 51OUL 725 B 55 6 T-TSP Wear 11S -0.8 11 0.19 139 P1 51OUL 727 B 55 9 T-TSP Wear 09S 0.4 9 0.13 145 P1 51OUL 637 B 55 55 T-TSP Wear 08S 0.4 14 0.21 165 P1 51OUL 673 B 55 65 T-TSP Wear 05S -0.6 9 0.12 138 P1 51OUL 673 B 55 87 T-TSP Wear 08S 0.4 0.15 138 P1 51OUL 565 B 55 104 T-T Wear 08S 19.2 16.7 21.6 4.9 67 0.28 71 141 510XP 809 B 55 106 T-T Wear 08S 18.3 15.3 21.3 6.0 67 0.32 73 117 510XP 809 B 56 32 T-TSP Wear 08S 0.3 0.11 129 P1 51OUL 637 B 56 34 T-T Wear 08S 19.5 17.2 21.7 4.6 53 0.3 71 33 510XP 807 B 56 97 T-TSP Wear 08S 0.4 0.17 144 P1 510XB 036 B 56 99 T-TSP Wear 08S 0.4 0.19 150 P1 51OUL 573 B 57 3 T-TSP Wear 11S -0.7 0.22 140 P1 51OUL 725 B 57 31 T-T Wear 08S 18.6 15.8 21.4 5.7 53 0.37 83 141 510XP 807 B 57 34 T-T Wear 08S 19.3 16.6 22.0 5.4 53 0.34 72 21 510XP 807 B 57 101 T-TSP Wear 08S 0.3 0.15 143 P1 51OUL 573 B 57 107 T-TSP Wear 08S 0.3 0.11 158 P1 51OUL 573 B 58 1 T-TSP Wear 10S -0.7 0.15 138 P1 510XB 022 B 58 3 T-TSP Wear 11S 725 0.4 0.21 162 P1 51OUL B 58 32 T-T Wear 08S 18.9 16.0 21.8 5.8 53 0.42 69 105 510XP 807 B 58 105 T-TSP Wear 08S 0.4 0.08 135 P1 51OUL 575 B 58 105 T-TSP Wear 07S 0.4 0.13 148 P1 51OUL 575 B 58 105 T-TSP Wear 06S -0.7 0.09 133 P1 51OUL 575 Tuesday, April 24,2012 Page 40 of 67
TM1-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications. Outaze T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Tvpe TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 58 106 T-TSP Wear 08S 0.3 10 0.16 151 P1 51OUL 573 B 58 107 T-TSP Wear 08S 0.4 8 0.11 137 P1 51OUL 575 B 58 108 T-TSP Wear 08S 0.4 13 0.2 159 P1 51OUL 573 B 59 106 T-TSP Wear 08S 0.4 8 0.12 155 P1 51OUL 573 B 59 107 T-TSP Wear 08S 0.4 8 0.1 136 P1 51OUL 575 B 59 124 T-TSP Wear 11S 0.3 8 0.12 150 P1 51OUL 573 B 60 83 T-TSP Wear 02S -0.6 8 0.13 147 P1 51OUL 577 B 60 92 T-TSP Wear 02S -0.6 15 0.25 160 P1 51OUL 577 B 61 5 T-TSP Wear 15S 0.3 6 0.11 145 P1 51OUL 725 B 61 113 T-TSP Wear 07S 0.4 9 0.14 138 P1 51OUL 577 B 62 102 T-TSP Wear 08S 0.4 7 0.12 138 P1 S5OUL 589 B 62 113 T-TSP Wear 09S 0.4 5 0.08 117 P1 51OUL 589 B 62 113 T-TSP Wear 08S 0.4 8 0.16 150 P1 S5OUL 589 B 62 127 T-TSP Wear 11S 0.3 15 0.21 153 P1 510XB 034 B 62 127 T-TSP Wear 11S -0.7 9 0.12 133 P1 510XB 034 B 62 127 T-TSP Wear los -0.7 8 0.1 128 P1 510XB 034 B 63 4 T-TSP Wear 09S 0.4 8 0.12 137 P1 510XB 020 B 64 103 T-TSP Wear 08S 0.3 6 0.11 127 P1 51OUL 589 B 64 104 T-TSP Wear 08S 0.4 9 0.16 143 P1 51OUL 589 B 65 35 T-TSP Wear 08S 0.3 5 0.08 141 P1 51OUL 661 B 65 130 T-TSP Wear 11S -0.7 10 0.12 110 P1 510XB 034 B 65 130 T-TSP Wear 11S 0.4 19 .0.29 156 P1 510XB 034 B 67 129 T-TSP Wear 11S -0.7 7 0.09 123 P1 510XS 034 Page 41 of 67 Tuesday, April24, Tuesday, April 2012 24, 2012 Page 41 of 6 7
TMI-12-O 71, TMI-1 Steam Generator Tube Inspection Report (TJRJ9)
-A ttachment-];-Exhibit-2 SG B, All Service Induced Indications.Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal 67 129 T-TSP Wear 11S 0.4 0.12 158 P1 510XB 034 67 129 T-TSP Wear 10S -0.8 0.1 126 P1 510XB 034 68 112 T-T Wear 08S 18.8 16.5 21.0 4.5 67 0.3 70 161 510XP 803 68 113 T-T Wear 08S 19.0 16.4 21.6 5.2 67 0.35 88 149 510XP 803 68 114 T-T Wear 08S 18.0 14.9 21.0 6.1 67 0.93 81 77 510XP 803 68 131 T-TSP Wear 11S -0.7 0.09 131 P1 510XB 034 69 5 T-TSP Wear 11S 0.3 0.1 148 P1 51OUL 745 69 113 T-T Wear 08S 17.5 13.8 21.2 7.4 67 1.17 81 81 510XP 803 69 114 T-TSP Wear 08S 0.4 0.21 140 P1 51OUL 595 69 114 T-T Wear 08S 18.1 14.7 21.6 6.9 67 0.83 94 89 510XP 803 70 27 T-TSP Wear 08S 0.3 0.1 146 P1 51OUL 659 70 28 T-TSP Wear 08S 0.3 0.16 154 P1 51OUL 661 70 30 T-TSP Wear 08S 0.4 0.17 148 P1 51OUL 661 70 112 T-T Wear 08S 18.3 14.6 22.0 7.5 80 0.98 85 93 510XP 803 70 128 T-TSP Wear 10S -0.7 0.21 142 P1 51OUL 595 71 131 T-TSP Wear 10S -0.8 0.1 139 P1 51OXB 036 72 20 T-TSP Wear 08S 0.4 0.14 145 P1 51OUL 697 72 30 T-TSP Wear 08S 0.3 0.18 149 P1 51OUL 661 72 113 T-TSP Wear 08S 0.4 0.2 150 P1 51OUL 611 72 127 T-TSP Wear 11S 0.3 0.21 141 P1 51OUL 603 73 4 T-TSP Wear 12S -0.8 5 0.1 108 P1 51OUL 733 73 15 T-TSP Wear 15S 0.2 12 0.21 152 P1 51OUL 659 73 101 T-TSP Wear 08S -0.7 7 0.1 126 P1 51OUL 603 Page 42 of67 Tuesday, April 24, 2012 April24, Tuesday, 2012 Page 42 of 6 7
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TJR19)
Attachment 1, Exhibit 2 SG BA All Service Induced Indications. Outaze TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 73 105 T-TSP Wear 08S -0.8 0.09 137 P1 51OUL 603 B 73 110 T-TSP Wear 08S -0.7 0.09 130 P1 51OUL 603 B 75 132 T-TSP Wear 1S -0.8 0.19 126 P1 510XB 036 B 76 9 T-TSP Wear loS -0.7 0.1 129 P1 51OUL 737 B 76 17 T-TSP Wear 15S 0.1 0.16 153 P1 51OUL 659 B 76 128 T-TSP Wear 10S -0.7 0.13 132 P1 51OXB 036 B 77 1 T-TSP Wear 11S -0.7 0.1 124 P1 51OXB 028 B 77 6 T-TSP Wear 09S 0.4 0.11 160 P1 51OUL 737 B 77 111 T-TSP Wear 08S 0.4 0.14 163 P1 51OUL 677 B 78 101 T-T Wear 04S 19.0 16.2 21.8 5.6 53 0.54 98 33 510XP 805 B 78 108 T-TSP Wear 08S 0.4 0.15 149 P1 51OUL 677 B 78 113 T-TSP Wear 08S 0.4 0.13 151 P1 51OUL 679 B 78 113 T-TSP Wear 07S 0.4 0.13 153 P1 51OUL 679 B 79 1 T-TSP Wear 14S -0.8 0.08 105 P1 510XB 028 B 79 102 T-T Wear 04S 18.8 15.8 21.8 6.0 53 0.56 90 21 510XP 805 B 79 106 T-TSP Wear 08S 0.4 0.18 150 P1 51OUL 679 B 79 109 T-TSP Wear 08S 0.4 0.16 151 P1 51OUL 677 B 79 114 T-T Wear 08S 19.7 17.9 21.4 3.5 40 0.27 75 149 510XP 805 B 79 128 T-TSP Wear 13S 0.3 0.08 126 P1 51OUL 679 B 79 128 T-TSP Wear loS -0.8 0.09 115 P1 51OUL 679 B 80 20 T-TSP Wear 08S 0.3 0.17 .156 P1 51OUL 651 B 80 26 T-T Wear 08S 18.6 16.2 21.0 4.9 53 0.36 88 165 510XP 801 B 80 34 T-TSP Wear 03S -0.6 0.1 130 P1 51OUL 651 Tuesday, April 24, 2012 Page 43 of 67
TMI-12-0 71, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
Attachment-l .Exhibit-2 SG B, All Service Induced Indications. Outaze T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 80 113 T-TSP Wear 08S -0.8 5 0.09 108 P1 51OUL 679 B 80 114 T-T Wear 08S 19.2 13 17.4 20.9 3.5 40 0.13 90 161 510XP 805 B 81 5 T-TSP Wear 14S -0.8 6 0.1 127 P1 51OUL 739 B 81 17 T-TSP Wear 09S 0.4 12 0.23 169 P1 51OUL 651 B 81 27 T-T Wear 08S 18.6 8 16.2 21.1 4.9 53 0.46 96 5 510XP 801 B 81 106 T-TSP Wear 08S 0.4 8 0.15 134 P1 51OUL 679 B 81 132 T-TSP Wear 13S 0.3 15 0.32 136 P1 510XB 018 B 82 109 T-TSP Wear 08S 0.3 8 0.16 144 P1 . 51OUL 679 B 82 130 T-TSP Wear 1OS -0.7 6 0.1 127 P1 51OXB 016 B 82 131 T-TSP Wear 12S -0.8 8 0.15 127 P1 510XB 018 B 83 109 T-TSP Wear 08S 0.4 8 0.14 140 P1 51OUL 677 B 83 110 T-TSP Wear 08S 0.3 10 0.2 143 P1 51OUL 679 B 83 132 T-TSP Wear 12S 0.3 10 0.21 137 P1 510XB 018 B 84 103 T-TSP Wear 08S 0.4 10 0.17 168 P1 51OUL 677 B 84 108 T-TSP Wear 08S 0.4 14 0.3 155 P1 51OUL 679 B 84 127 T-TSP Wear 10S -0.7 8 0.14 136 P1 51OUL. 677 B 84 128 T-TSP Wear lOS -0.7 10 0.19 142 P1 51OUL 679 B 85 22 T-TSP Wear 08S 0.3 6 0.1 129 P1 51OUL 641 B 85 27 T-TSP Wear 08S 0.4 10 0.16 148 P1 51OUL 639 B 85 53 T-TSP Wear 06S -0.7 6 0.1 128 P1 51OUL 653 B 85 100 T-TSP Wear 08S 0.4 7 0.13 161 P1 51OUL 683 B 85 109 T-TSP Wear 08S 0.4 7 0.13 144 P1 51OUL 747 B 85 109 T-T Wear 08S 18.1 6 16.1 20.1 4.1 53 0.29 69 21 510XP 805 Tuesday, April 24, 2012 . Page44 of67
TMI-12--071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG BA All Service Induced Indications. Outaee T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 85 129 T-TSP Wear 10S -0.7 11 0.2 138 P1 510XB 016 B 85 130 T-TSP Wear 12S 0.3 13 0.27 139 P1 510XB 018 B 86- 7 T-TSP Wear 14S 0.2 6 0.1 132 P1 51OUL 737 B 86 22 T-T Wear 08S 19.5 10 16.5 22.5 5.9 53 0.61 94 81 510XP 801 B 86 108 T-T Wear 08S 19.4 8 16.9 21.9 5.0 53 0.49 84 129 510XP 805 B 86 109 T-T Wear 08S 18.1 4 16.4 19.9 3.5 53 0.15 55 9 510XP 805 B 86 126 T-TSP Wear loS -0.8 7 0.13 144 P1 51OUL 683 B 87 4 T-TSP Wear 12S -0.8 7 0.11 133 P1 51OUL 737 B 87 4 T-TSP Wear 10S -0.7 7 0.12 144 P1 51OUL 737 B 87 22 T-T Wear 08S 19.7 9 16.8 22.6 5.8 53 0.5 91 89 510XP 801 B 87 103 T-TSP Wear 08S 0.4 9 0.18 156 P1 51OUL 683 B 87 109 T-T Wear 08S 19.4 8 16.7 22.0 5.3 53 0.45 88 117 510XP 805 B 88 60 T-TSP Wear 03S -0.6 9 0.15 138 P1 51OUL 585 B 88 102 T-TSP Wear 08S 0.3 10 0.19 150 P1 51OUL 683 B 88 110 T-T Wear 08S 19.1 10 16.2 22.0 5.7 53 0.63 91 129 510XP 805 B 89 4 T-TSP Wear 14S 0.2 5 0.09 135 P1 51OUL 737 B 89 28 T-TSP Wear 08S 0.3 13 0.25 143 P1 51OUL 641 B 89 111 T-T Wear 08S 19.2 8 16.5 21.9 5.4 53 0.48 84 "117 510XP 805 B 89 130 T-TSP Wear l0S -0.7 7 0.13 114 P1 510XB 018 B 90 48 T-TSP Wear 03S -0.6 13 0.23 147 P1 51OUL 585 B 90 105 T-TSP Wear 08S 0.3 10 0.21 152 P1 51OUL 687 B 90 106 T-TSP Wear 08S 0.3 9 0.18 145 P1 51OUL 689 B 90 127 T-TSP Wear 10S -0.7 15 0.32 125 P1 510XB 018 Tuesday, April 24, 2012 Page 45 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment-liExhibit-2 SG B, All Service InducedIndications,Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal 91 22 T-TSP Wear 08S 0.3 7 0.13 152 P1 51OUL 641 91 104 T-TSP Wear 08S 0.4 0.14 148 P1 51OUL 689 91 110 T-T Wear 08S 19.1 17.8 20.5 2.7 53 0.21 85 57 510XP 805 91 111 T-T Wear 08S 19.2 17.5 20.9 3.4 53 0.32 83 69 510XP 805 92 24 T-TSP Wear 08S 0.3 0.14 138 P1 51OUL 639 92 30 T-T Wear 08S 18.8 16.6 21.0 4.4 53 0.23 87 33 510XP 801 92 99 T-TSP Wear 08S -0.7 0.14 138 P1 51OUL 687 92 102 T-TSP Wear 08S 0.3 0.17 151 P1 51OUL 689 93 23 T-T Wear 08S 18.6 16.0 21.2 5.1 53 0.38 77 9 510XP 801 93 24 T-TSP Wear 08S 0.4 0.24 145 P1 51OUL 641 93 29 T-TSP Wear 08S 0.3 0.19 145 P1 51OUL 641 93 30 T-T Wear 08S 18.7 16.3 21.0 4.6 53 0.27 82 45 510XP 801 93 30 T-TSP Wear 03S -0.6 0.15 145 P1 51OUL 639 93 102 T-TSP Wear 08S 0.4 0.09 148 P1 51OUL 689 93 103 T-T Wear 08S 18.1 16.8 19.4 2.6 53 0.12 95 5 510XP 805 93 128 T-TSP Wear 10S -0.7 0.32 127 P1 510XB 018 94 24 T-TSP Wear 08S 0.4 0.1 143 P1 51OUL 631 94 24 T-T Wear 08S 18.9 16.3 21.5 5.2 40 0.3 98 45 510XP 801 94 26 T-T Wear 08S 19.9 17.5 22.3 4.9 53 0.29 76 33 510XP 801 94 98 T-TSP Wear 08S 0.4 0.19 162 P1 51OUL 689 94 99 T-TSP Wear 08S 0.3 0.24 145 P1 51OUL 687 94 102 T-TSP Wear 08S 0.3 0.16 151 P1 51OUL 689 94 126 T-TSP Wear 10S 0.4 0.26 156 P1 51OUL 689 April24, Tuesday, 2012 Page 46 of 67 Tuesday, April 24, 2012 Page46 of 67
TMI-12-0 71, TMI-1 Steam Generator Tube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG BA All Service Induced Indications. Outae TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 94 129 T-TSP Wear los -0.7 25 0.62 126 P1 510XB 018 B 95 26 T-T Wear 08S 19.7 7 16.8 22.6 5.8 53 0.4 105 41 51OXP 801 B 95 97 T-TSP Wear 08S 0.4 11 0.24 160 P1 51OUL 691 B 95 100 T-TSP Wear .08S 0.4 10 0.2 157 P1 51OUL 691 B. 95 100 T-T Wear 08S 17.7 4 16.4 19.0 2.6 53 0.13 79 153 51OXP 805 B 96 90 T-TSP Wear 08S 0.4 6 0.11 129 P1 51OUL 691 B 97 91 T-TSP Wear 08S -0.8 4 0.08 115 P1 51OUL 691 B 97 103 T-T Wear 08S 18.1 8 16.0 20.2 4.2 53 0.41 93 53 51OXP 805 B 97 104 T-T Wear 08S 18.0 8 16.2 19.9 3.7 53 0.46 81 65 510XP 805 B 97 104 T-TSP Wear 08S -0.7 9 0.18 111 P1 51OUL 691 B 97 119 T-TSP Wear 09S 0.4 8 0.16 149 P1 S5OUL 691 B 97 120 T-TSP Wear 09S 0.4 12 0.25 146 P1 51OUL 691 B 97 121 T-TSP Wear 09S -0.7 6 0.11 84 P1 51OUL 691 B 97 121 T-TSP Wear 09S 0.4 11 0.22 158 P1 51OUL 691 B 97 122 T-TSP Wear 09S 0.5 9 0.19 151 P1 51OUL 691 B 97 125 T-TSP Wear 13S 0.4 13 0.25 140 P1 510XB 016 B 97 126 T-TSP Wear 14S -0.7 9 0.18 116 P1 510XB 018 B 98 3 T-TSP Wear 09S -0.6 8 0.12 132 P1 51OUL 727 B 98 97 T-TSP Wear 08S 0.4 8 0.17 153 P1 51OUL 691 B 98 102 T-T Wear 08S 18.2 9 15.5 20.8 5.3 53 0.51 86 101 51OXP 805 B 98 117 T-TSP Wear 09S 0.4 11 I 0.24 144 P1 51OUL 691 B 98 118 T-TSP Wear 09S 0.3 .13 0.28 153 P1 51OUL 691 B 98 119 T-TSP Wear 09S 0.4 13 0.29 156 4P1 51OUL 691 April24, 2012 Page47 of 67 Tuesday, Tuesday, April 24, 2012 Page 47 of 6 7
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19)
A-tta fh-ent-.Eih-ibit-2 SG BA All Service Induced Indications.Outa, e TJR19 Location % Ind. Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 98 120 T-TSP Wear lOS -0.7 6 0.11 126 P1 510UL 691 B 98 121 T-TSP Wear 09S 0.5 11 0.24 161 P1 51OUL 691 B 98 122 T-TSP Wear 09S 0.4 .14 0.31 150 P1 51OUL 691 B 98 122 T-TSP Wear 09S -0.7 10 0.21 128 P1 51OUL 691 B 98 125 T-TSP Wear 14S -0.8 9 0.19 131 P1 510XB 018 B 99 95 T-TSP Wear 08S 0.4 12 0.25 152 P1 51OUL 691 B 99 97 T-TSP Wear 08S 0.4 10 0.21 160 P1 51OUL 691 B 99 98 T-TSP Wear 08S 0.4 10* 0.21 149 P1 51OUL 691 B 99 99 T-TSP Wear 08S 0.4 10 0.2 148 P1 51OUL 691 B 99 101 T-TSP Wear 08S 0.4 11 0.22 151 P1 51OUL 691 B 99 101 T-T Wear 08S 18.1 7 15.7 20.6 5.0 53 0.35 86 149 510XP 805 B 99 102 T-T Wear 08S 18.0 9 15.7 20.3 4.7 53 0.51 85 113 510XP 805 B 99 115 T-TSP Wear 09S 0.4 10 0.2 158 P1 51OUL 691 B 99 116 T-TSP Wear 09S 0.4 11 0.23 150 P1 51OUL 691 B 99 121 T-TSP Wear 13S 0.3 7 0.14 145 P1 51OUL 691 B 99 121 T-TSP Wear 09S 0.5 15 0.35 140 P1 51OUL 691 B 99 123 T-TSP Wear 09S 0.5 17 0.33 144 P1 510XB 016 B 99 124 T-TSP Wear 14S -0.7 7 0.14 121 P1 510XB 018 B 100 3 T-TSP Wear 09S -0.7 8 0.16 140 P1 51OUL 725 B 100 22 T-TSP Wear 08S -0.8 10 0.19 79 P1 51OUL 633 B 100 94 T-T Wear 08S 18.2 3 17.2 19.1 2.0 53 0.1 66 165 510XP 805 B 100 100 T-T Wear 08S 18.1 7 15.7 20.5 4.8 53 0.32 105 161 510XP 805 B 100 114 T-TSP Wear 09S 0.4 10 0.21 162 P1 51OUL 691 Tuesday, April 24, 2012 Page 48 of 67
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TJR19)
Attachment 1, Exhibit 2 SG BA All Service Induced Indications.Outa2e TIR19 Location %d. I Ind Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 100 118 T-TSP Wear 09S 0.4 12 0.24 151 P1 51OUL 693 B 101 22 T-TSP Wear 08S -0.8 8 0.14 115 P1 51OUL 631 B 101 26 T-TSP Wear 08S 0.4 8 0.14 153 P1 51OUL 631 B 101 83 T-TSP Wear 07S 0.4 14 0.29 151 P1 51OUL 693 B 101 89 T-TSP Wear 08S -0.8 4 0.07 98 P1 51OUL 693 B 101 94 T-T Wear 08S 17.7 9 15.0 20.5 5.5 53 0.55 84 53 510XP 805 B 101 95 T-T Wear 08S 17.7 10 15.3 20.2 4.9 53 0.59 88 65 510XP 805 B 101 96 T-TSP Wear 08S 0.3 10 0.2 155 P1 51OUL 693 B 101 102 T-TSP Wear 08S -0.8 4 0.09 95 P1 51OUL 693 B 101 102 T-TSP Wear 08S 0.4 9 0.19 152 P1 51OUL 693 B 101 112 T-TSP Wear 09S 0.4 7 0.15 139 P1 51OUL 693 B 101 115 T-TSP Wear 09S 0.4 14 0.29 151 P1 51OUL 693 B 101 116 T-TSP Wear 09S 0.4 14 0.3 154 P1 51OUL 693 B 101 117 T-TSP Wear loS -0.7 8 0.16 129 P1 51OUL 693 B 101 119 T-TSP Wear 14S -0.8 14 0.25 138 P1 510XB 016 B 101 119 T-TSP Wear los -0.7 28 0.66 119 P1 510XB 016 B 102 116 T-TSP Wear 09S 0.4 11 0.24 145 P1 51OUL 693 B 102 117 T-TSP Wear l0S -0.7 15 0.33 128 P1 51OUL 693 B 102 117. T-TSP Wear 09S 0.4 8 0.16 157 P1 51OUL 693 B 102 118 T-TSP Wear 10S -0.7 5 0.1 131 P1 51OUL 693 B 102 121 T-TSP Wear lOS -0.7 12 0.25 130 P1 510XB 018 B 103 1 T-TSP Wear 14S -0.8 6 0.1 149 P1 510XB 030 B 103 16 T-TSP Wear 08S 0.3 9 0.17 153 P1 51OUL 633 Tuesday, April 24, 2012 Page49 of 67
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19)
Attachment-lvExhibit-2 SG B, All Service Induced Indications.Outawe T1R19 Location % Ind Ind Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal 103 116 T-TSP Wear 09S 0.4 0.28 150 51OUL 693 103 117 T-TSP Wear 09S 0.4 0.29 155 51OUL 693 103 118 T-TSP Wear 135 0.3 0.2- 154 51OUL 693 103 118 T-TSP Wear los -0.7 0.45 131 51OUL 693 103 119 T-TSP Wear los -0.7 0.22 137 51OUL 693 103 120 T-TSP Wear los -0.7 0.17 142 51OUL 693 103 121 T-TSP Wear los -0.7 0.33 130 510XB 016 103 122 T-TSP Wear 13S -0.7 0.28 128 510XB 018 103 122 T-TSP Wear 13S 0.4 0.25 146 510XB 018 103 122 T-TSP Wear los -0.7 0.51 128 510XB 018 104 84 T-TSP Wear 08S 0.3 0.2 157 51OUL 715 104 89 T-TSP Wear 08S 0.4 0.13 137 51OUL 693 104 90 T-TSP Wear 08S 0.4 0.17 156. 51OUL 693 104 95 T-TSP Wear 08S 0.4 0.28 152 51OUL 693 104 99 T-TSP Wear 08S 0.4 0.24 158 51OUL 743 104 114 T-TSP Wear 09S 0.4 0.17 153 51OUL 713 104 115 T-TSP Wear los -0.7 0.17 139 51OUL 715 104 115 T-TSP Wear 09S 0.5 0.18 155 51OUL 715 104 116 T-TSP Wear 095 0.5 0.21 151 51OUL 713 104 117 T-TSP Wear los -0.7 0.31 140 51OUL 715 104 118 T-TSP Wear 10S -0.7 0.49 133 51OUL 713 104 120 T-TSP Wear 10S -0.7 0.17 134 510XB 016 104 121 T-TSP Wear 12S 0.3 0.11 131 510XB 018 Page 50 of 67 Tuesday, April 24, 2012 April24, Tuesday, 2012 Page 50 of 67
TMI-12-0 71, TMI-1 Steam GeneratorTube Inspection Report (TJR19)
Attachment 1, Exhibit 2 SG B. All Service Induced Indications.Outawe T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 104 121 T-TSP Wear 10S -0.7 0.23 132 P1 510XB 018 B 105 91 T-TSP Wear 08S 0.4 0.14 155 P1 51OUL 695 B 105 92 T-T Wear 08S 17.6 15.5 19.8 4.3 53 0.34 .82 153 510XP 805 B 105 95 T-T Wear 08S 18.2 15.4 21.1 5.7 53 0.42 80 21 510XP 805 B 105 111 T-TSP Wear 09S 0.4 0.21 159 P1 51OUL 713 B 105 113 T-TSP Wear 10S -0.7 0.29 139 P1 51OUL 713 B 105 114 T-TSP Wear 09S 0.4 0.31 162 P1 51OUL 715 B 105 116 T-TSP Wear loS -0.7 0.25 129 P1 51OUL 715 B 105 117 T-TSP Wear loS -0.7 0.16 115 P1 510XB 016 B 105 118 T-TSP Wear 10S -0.7 0.16 125 P1 510XB 018 B 106 89 T-TSP Wear. 08S 0.4 0.14 152 P1 51OUL 695 B 106 92 T-T Wear 08S 17.6 15.6 19.7 4.1 53 0.34 74 165 510XP 805 B 106 93 T-TSP Wear 08S 0.3 0.18 151 P1 51OUL 695 B 106 95 T-T Wear 08S 18.5 15.8 21.3 5.5 53 0.48 96 17 51OXP 805 B 106 113 T-TSP Wear 09S -0.7 0.18 135 P1 51OUL 713 B 106 113 T-TSP Wear 09S 0.4 0.17 143 P1 51OUL 713 B 106 114 T-TSP Wear 09S 0.5 0.28 162 P1 51OUL 715 B 106 115 T-TSP Wear 10S -0.7 0.3 130 P1 51OUL 713 B 106 116 T-TSP Wear 10S -0.7 0.1 122 P1 51OUL 715 B 106 116 T-TSP Wear 09S 0.5 0.26 149 P1 51OUL 715 B 106 117 T-TSP Wear 105 -0.7 0.31 136 P1 51OUL 713 B 106 118 T-TSP Wear 10S -0.7 0.36 131 P1 510XB 016 B 106 119 T-TSP Wear 10S -0.7 0.25 120 P1 510XB 018 Tuesday, April 24, 2012 Page51 of 67
TMI-12--071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Atta-chme-nt -i .Exhibit-2 SG BA All Service Induced Indications.Outaze TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 107 78 T-T Wear 08S 18.5 4 17.0 19.9 2.9 53 0.12 47 77 510XP 801 B 107 83 T-TSP Wear 08S 0.4 11 0.19 158 P1 51OUL 713 B 107 86 T-TSP Wear 08S 0.4 11 0.2 160 P1 510UL 715 B 107 113 T-TSP Wear 09S -0.6 8 0.14 114 P1 51OUL 713 B 107 114 T-TSP Wear 09S 0.4 8 0.14 147 P1 51OUL 715 B 107 115 T-TSP Wear loS -0.7 8 0.14 131 P1 51OUL 713 B 107 116 T-TSP Wear lOS -0.7 7 0.13 131 P1 51OUL 715 B 107 118 T-TSP Wear lOS 0.5 15 0.31 136 P1 510XB 018 B 107 118 T-TSP Wear 10S -0.7 11 0.22 130 P1 510XB 018 B 108 28 T-TSP Wear 08S -0.7 13 0.24 126 P1. 51OUL 623 B 108 41 T-TSP Wear 08S -0.7 8 0.16 126 P1 51OUL 571 B 108 43 T-TSP Wear 08S -0.7 5 0.1 107 P1 51OUL 571 B 108 92 T-TSP Wear 08S 0.4 10 0.18 157 P1 51OUL 715 B 108 92 T-TSP Wear 08S -0.7 4 0.07 74 P1 51OUL 715 B 108 113 T-TSP Wear lOS -0.7 9 0.16 135 P1 51OUL 713 B 108 117 T-TSP Wear lOS -0.7 12 0.24 123 P1 510XB 018 B 109 4 T-TSP Wear 09S -0.7 7 0.11 132 P1 51OUL 727 B 109 50 T-TSP Wear 08S 0.4 13 0.28 150 P1 51OUL 571 B 109 82 T-TSP Wear 08S 0.4 9 0.17 162 P1 51OUL 715 B 109 113 T-TSP Wear 09S -0.6 8 0.14 136 P1 51OUL 713 B 109 114 T-TSP Wear 09S 0.4 10 0.19 148 P1 51OUL 715 B 110 79 T-TSP Wear 08S 0.4 7 0.12 152 P1 51OUL 715 B 110 81 T-TSP Wear 08S 0.4 6 0.11 155 P1 51OUL 715 Tuesday, April 24, 2012 Page 52 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications. Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 110 83 T-TSP Wear 08S 0.4 10 0.2 150 P1 51OUL 715 B 110 84 T-TSP Wear 08S 0.3 16 0.29 142 P1 51OUL 713 B 110 86 T-TSP Wear 09S -0.7 6 0.1 124 P1 51OUL 713 B 110 86 T-TSP Wear 08S 0.4 15 0.28 142 P1 51OUL 713 B 110 111 T-TSP Wear 09S -0.6 6 0.11 107 P1 510XB 016 B 111 87 T-TSP Wear 08S 0.4 13 0.23 139 P1 51OUL 713 B 111 90 T-TSP Wear 08S 0.3 11 0.21 160 P1 51OUL 715 B 112 75 T-TSP Wear 08S 0.4 9 0.16 150 P1 51OUL 561 B 112 77 T-TSP Wear 08S 0.4 12 0.26 164 P1 51OUL 707 B 112 113 T-TSP Wear 09S -0.7 12 0.23 131 P1 51OUL 715 B 112 114 T-TSP Wear loS -0.7 9 0.16 132 P1 510XB 016 B 113 26 T-TSP Wear 08S -0.7 8 0.13 140 P1 51OUL 613 B 113 29 T-TSP Wear 08S -0.7 8 0.15 71 P1 51OUL 601 B 113 39 T-TSP Wear 08S 0.4 8 0.14 145 P1 51OUL 561 B 113 77 T-TSP Wear 08S -0.6 7 0.11 106 P1 51OUL 705 B 113 116 T-TSP Wear 10S -0.7 11 0.22 122 P1 510XB 018 B 114 64 T-TSP Wear 08S 0.4 7 0.13 152 P1 51OUL 563 B 114 66 T-TSP Wear 08S -0.8 7 0.13 105 P1 51OUL 563 B 114 68 T-TSP Wear 08S .0.4 11 0.21 156 P1 51OUL 563 B 114 77 T-TSP Wear 08S 0.4 12 0.26 169 P1 51OUL 707 B 114 77 T-TSP Wear 07S 0.4 13 0.28 163 P1 51OUL 707 B 114 79 T-TSP Wear 08S 0.4 12 0.25 168 P1 51OUL 707 B 114 85 T-TSP Wear 08S 0.3 8 0.16 158 P1 51OUL 707 Page S3 of 67 Tuesday, April 24, 2012 April24, Tuesday, 2012 Page 53 of 67
TMI-12--071, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
Attachment-l .Exhibi-2 SG B, All Service Induced Indications.Outae TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 114 109 T-TSP Wear 09S -0.7 5 0.09 135 P1 51OUL 707 B 114 110 T-TSP Wear 09S 0.5 11 0.2 146 P1 51OUL 705 B 114 115 T-TSP Wear lOS -0.6 14 0.27 118 P1 510XB 024 B 115 23 T-TSP Wear 08S -0.7 6 0.09 98 P1 51OUL 607 B 115 24 T-TSP Wear 08S -0.7 11 0.21 41 P1 51OUL 601 B 115 26 T-TSP Wear 08S -0.7 6 0.1 55 P1 51OUL 601 B 115 27 T-TSP Wear 08S -0.7 9 0.15 100 P1 51OUL 607 B 115 28 T-TSP Wear 08S 0.3 9 0.18 139 P1 51OUL 601 B 115 81 T-TSP Wear 08S 0.4 12 0.21 148 P1 51OUL 705 B 115 83 T-T Wear 08S 17.8 7 15.2 20.4 5.3 53 0.38 82 113 510XP 801 B 115 84 T-T Wear 08S 18.0 8 15.3 20.7 5.4 53 0.44 82 101 510XP 801 B 115 85 T-TSP Wear 08S 0.4 12 0.23 142 P1 51OUL 705 B 115 109 T-TSP Wear 09S 0.4 13 0.24 167 P1 51OUL 705 B 115 114 T-TSP Wear 10S -0.7 10 0.19 119 P1 510XB 024 B 116 28 T-TSP Wear 08S -0.7 7 0.11 95 P1 51OUL 607 B 116 29 T-TSP Wear 08S -0.8 8 0.14 53 P1 51OUL 601 B 116 31 T-TSP Wear 08S -0.8 9 0.16 55 P1 51OUL 601 B 116 33 T-TSP Wear 08S -0.8 8 0.16 69 P1 51OUL 601 B 116 34 T-TSP Wear 08S -0.8 5 0.08 94 P1 51OUL 607 B 116 36 T-TSP Wear 08S -0.7 15 0.26 126 P1 51OUL 607 B 116 36 T-T Wear 08S 18.0 17 14.0 22.1 8.1 67 1.45 94 89 510XP 805 B 116 36 T-TSP Wear 07S 0.4 9 0.14 145 P1 51OUL 607 B 116 76 T-TSP Wear 08S 0.4 16 0.36 166 P1 51OUL 707 Tuesday, April 24, 2012 Page 54 of6 7
TMI-12-0 71, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications,Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 116 78 T-TSP Wear 08S 0.4 0.26 159 P1 51OUL 707 B 116 80 T-TSP Wear 08S 0.4 0.22 153 P1 51OUL 707 B 116 81 T-TSP Wear 08S 0.4 0.37 139 P1 51OUL 705 B 116 82 T-TSP Wear 08S 0.4 0.33 163 P1 51OUL 707 B 116 84 T-TSP Wear 08S 0.4 0.24 154 P1 51OUL 707 B 116 86 T-T Wear 08S 17.7 15.0 20.5 5.5 53 0.41 85 161 510XP 801 B 116 87 T-T Wear 08S 18.3 15.9 20.7 4.8 53 0.42 90 149 510XP 801 B 116' 108 T-TSP Wear 09S 0.4 0.18 166 P1 51OUL 707 B 117 28 T-TSP Wear 08S -0.7 0.1 64 P1 51OUL 607 B 117 33 T-TSP Wear 08S -0.7 0.14 112 P1 51OUL 601 B 117 35 T-TSP Wear 08S -0.8 0.13 99 P1 51OUL 601 B 117 36 T-TSP Wear 08S 0.4 0.28 153 P1 51OUL 607 B 117 36 T-T Wear 08S 18.2 14.3 22.2 7.9 53 1.89 87 77 510XP 805 B 117 73 T-TSP Wear 08S 0.4 0.15 150 P1 51OUL 561 B 117 74 T-TSP Wear 08S 0.4 0.17 148 P1 51OUL 741 B 117 75 T-TSP Wear 08S 0.4 0.45 170 P1 51OUL 707 B 117 78 T-TSP Wear 08S 0.4 0.22 152 P1 51OUL 741 B 117 79 T-TSP Wear 08S 0.3 0.36 172 P1 51OUL 707 B 117 83 T-T Wear 08S 17.9 16.0 19.9 3.9 53 0.24 92 57 510XP 801 B 117 85 T-TSP Wear 08S 0.3 0.38 154 P1 51OUL 707 B 118 14 T-TSP Wear 15S 0.2 0.1 131 P1 51OUL 601 B 118 35 T-TSP Wear 08S -0.8 0.17 135 P1 51OUL 607 B 118 36 T-T Wear 08S 18.8 16.0 21.6 5.6 40 0.63 97 29 510XP 805 Tuesday, April 24, 2012 Page55 of 67
TMI-12-O 71, TMI-1 Steam GeneratorTube Inspection Report (TJRJ19)
Attachment-]l7Exhibit-2 SG B, All Service Induced Indications.Outage T1R19 Location % Ind. Imd Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 118 67 T-TSP Wear 08S 0.4 0.27 157 P1 51OUL 561 B 118 68 T-TSP Wear 08S 0.4 0.17 145 P1 51OUL 563 B 118 69 T-TSP Wear 08S 0.4 0.12 150 P1 51OUL 561 B 118 70 T-TSP Wear 08S 0.4 0.19 152 P1 51OUL 563 B 118 71 T-TSP Wear 08S 0.4 0.18 142 P1 51OUL 561 B 118 72 T-TSP Wear 08S 0.4 0.26 146 P1 51OUL 563 B 118 73 T-TSP Wear 08S 0.4 0.18 148 P1 51OUL 561 B 118 82 T-T Wear 08S 17.8 14.6 20.9 6.3 53 0.22 119 69 510XP 801 B 118 82 T-T Wear 08S 18.1 16.7 19.5 2.8 53 0.24 77 137 510XP 801 B 118 83 T-T Wear 08S 18.2 15.4 20.9 5.5 53 0.33 101 125 510XP 801 B 118 85 T-TSP Wear 08S 0.4 0.21 160 P1 51OUL 741 B 118 110 T-TSP Wear loS -0.6 0.19 114 P1 510XB 024 B 119 26 T-TSP Wear 08S -0.8 0.12 126 P1 51OUL 607 B 119 33 T-TSP Wear 08S -0.7 0.14 102 P1 51OUL 601 B 119 36 T-TSP Wear 08S 0.4 0.1 147 P1 51OUL 563 B 119 38 T-TSP Wear 06S -0.7 0.12 76 P1 51OUL 563 B 119 69 T-TSP Wear 08S 0.4 0.12 138 P1 51OUL 561 B 119 78 T-T Wear 08S 18.2 15.3 21.1 5.8 53 0.49 92 117 510XP 801 B 119 79 T-T Wear 08S 17.9 15.3 20.6 5.3 53 0.71 86 125 510XP 801 B 119 81 T-T Wear 08S 17.7 14.8 20.6 5.8 53 0.48 77 137 510XP 801 B 119 82 T-T Wear 08S 17.8 14.8 20.8 6.0 53 0.56 88 149 510XP 801 B 120 29 T-TSP Wear 08S 0.3 0.13 128 P1 51OUL 601 B 120 70 T-TSP Wear 08S 0.4 0.18 146 P1 51OUL 561 Tuesday, April 24, 2012 Page 56 of67
TMI-12-0 71, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications. Outaze T1R19 Location %d. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 120 71 T-TSP Wear 08S 0.4 12 0.22 150 P1 51OUL 705 B 120 75 T-TSP Wear 08S 0.4 9 0.16 152 P1 51OUL 705 B 120 76 T-TSP Wear 08S 0.4 12 0.26 155 P1 51OUL 707 B 120 79 T-TSP Wear 09S -0.7 8 0.13 109 P1 51OUL 705 B 120 79 T-TSP Wear 08S -0.7 8 0.14 91 P1 51OUL 705 B 120 79 T-TSP Wear 08S 0.3 14 0.26 134 P1 51OUL 705 B 120 80 T-TSP Wear 08S -0.7 4 0.08 106 P1 51OUL 707 B 121 6 T-TSP Wear 09S 0.4 9 0.16 153 P1 51OUL 601 B 121 35 T-TSP Wear 08S -0.8 6 0.11 99 P1 51OUL 563 B 121 63 T-TSP Wear 08S 0.4 9 0.16 143 P1 510UL 559 B 121 66 T-TSP Wear 08S 0.4 12 0.23 143 P1 51OUL 557 B 121 76 T-TSP Wear 08S -0.7 6 0.09 62 P1 510UL 705 B 121 76 T-TSP Wear 08S 0.4 12 0.22 157 P1 51OUL 705 B 121 105 T-TSP Wear los -0.7 15 0.31 124 P1 510XB 026 B 122 17 T-TSP Wear 15S 0.2 6 0.1 145 P1 51OUL 601 B 122 32 T-TSP Wear 08S -0.7 7 0.11 125 P1 51OUL 607 B 122 33 T-TSP Wear 08S -0.8 7 0.12 91 P1 51OUL 559 B 122 35 T-TSP Wear 08S -0.8 8 0.15 97 510UL 559 B 122 62 T-TSP Wear 08S 0.4 10 0.19 141 P1 51OUL 671 B 122 63 T-TSP Wear 08S -0.8 5 0.08 89 P1 51OUL 669 B 122 63 T-TSP Wear 08S 0.4 7 0.13 150 P1 51OUL 669 B 122 65 T-TSP Wear 08S 0.3 5 0.08 141 P1 51OUL 669 B 122 65 T-TSP Wear 07S 0.4 7 0.12 165 P1 51OUL 669 Tuesday, April 24, 2012 Page57 of 67
TMI-12-0 71, TMI-1 Steam GeneratorTube Inspection Report (TJR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications, Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP OJfset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 122 71 T-TSP Wear 08S 0.4 15 0.27 159 P1 51OUL 705 B 122 76 T-TSP Wear 09S -0.8 8 0.15 135 P1 51OUL 707 B 122 76 T-TSP Wear 08S -0.7 6 0.12 101 P1 51OUL 707 B 122 76 T-TSP Wear 08S 0.4 10 0.21 141 P1 51OUL 707 B 122 80 T-TSP Wear 09S -0.8 8 0.17 150 P1 51OUL 707 B 122 80 T-TSP Wear 08S -0.7 9 0.17 131 P1 51OUL 707 B 122 80 T-TSP Wear 08S 0.4 13 0.28 153 P1 510UL 707 B 122 104 T-TSP Wear lOS -0.7 10 0.19 131 P1 510XB 026 B 123 9 T-TSP Wear 14S -0.9 5 0.1 144 P1 51OUL 601 B 123 16 T-TSP Wear 14S 0.2 7 0.11 147 P1 51OUL 607 B 123 32 T-TSP Wear 08S -0.8 6 0.09 119 P1 51OUL 607 B 123 34 T-TSP Wear 08S -0.8 8 0.14 55 P1 51OUL 559 B 123 35 T-TSP Wear 08S -0.7 6 0.1 84 P1 51OUL 557 B 123 39 T-TSP Wear 09S -0.8 9 0.16 118 P1 51OUL 557 B 123 39 T-TSP Wear 08S 0.4 9 0.15 135 P1 51OUL 557 B 123 39 T-TSP Wear 08S -0.8 7 0.12 104 P1 51OUL 557 B 123 57 T-TSP Wear 08S 0.4 11 0.22 151 P1 51OUL 557 B 123 61 T-TSP Wear 08S 0.4 12 0.23 153 P1 51OUL 557 B 123 104 T-TSP Wear 12S 0.4 8 0.14 142 P1 510XB 024 B 124 31 T-TSP Wear 08S -0.7 10 0.16 120 P1 51OUL 607 B 124 32 T-TSP Wear 08S -0.7 6 0.11 71 P1 51OUL 559 B 124 34 T-TSP Wear 08S -0.7 11 0.21 87 P1 51OUL 559 B 124 35 T-TSP Wear 08S -0.7 11 0.21 102 P1 51OUL 557 B 124 36 T-TSP Wear 08S -0.8 7 0.12 96 P1 51OUL 559 Tuesday, April 24, 2012 Page 58 of 67
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications. Outage TJR19 Location % IndL Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 124 38 T-TSP Wear 08S -0.7 8 0.14 56 P1 51OUL 559 B 124 58 T-TSP Wear 08S -0.7 5 0.09 79 P1 51OUL 559 B 124 70 T-TSP Wear 08S -0.7 9 0.16 53 P1 51OUL 701 B 125 53 T-TSP Wear 08S 0.4 9 0.18 155 P1 51OUL 559 B 125 59 T-TSP Wear 08S -0.8 6 0.1 82 P1 51OUL 559 B 125 59 T-TSP Wear 08S 0.4 10 0.2 145 P1 51OUL 559 B 125 62 T-TSP Wear 08S -0.7 5 0.1 100 P1 51OUL 557 B 125 75 T-TSP Wear 08S -0.7 7 0.14 70 P1 51OUL 703 B 125 100 T-TSP Wear 13S 0.3 11 0.21 142 P1 510XB 026 B 125 101 T-TSP Wear 10S -0.7 14 0.27 122 P1 510XB 024 B 126 29 T-TSP Wear 08S -0.7 7 0.11 80 P1 51OUL 599 B 126 33 T-TSP Wear 08S -0.8 8 0.14 129 P1 51OUL 669 B 126 35 T-TSP Wear 08S -0.8 9 0.17 109 P1 51OUL 669 B 126 36 T-TSP Wear 08S -0.8 8 0.15 55 P1 51OUL 559 B 126 46 T-TSP Wear 08S -0.8 6 0.12 102 P1 51OUL 559 B 126 65 T-TSP Wear 08S -0.8 12 0.24 111 P1 51OUL 557 B 127 41 T-TSP Wear 08S -0.8 14 0.25 135 P1 51OUL 549 B 127 41 T-TSP Wear 08S 0.3 7 0.11 145 P1 51OUL 549 B 127 41 T-TSP Wear 07S 0.4 8 0.13 153 P1 51OUL 549 B 127 51 T-TSP Wear 08S -0.8 5 0.09 130 P1 51OUL 669 B 127 67 T-TSP Wear 08S -0.8 8 0.13 66 P1 51OUL 701 B 128 35 T-TSP Wear 08S -0.7 9 0.18 90 P1 51OUL 559 B 128 50 T-TSP Wear 08S 0.4 10 0.18 145 P1 51OUL 557 Tuesday, April 24, 2012 Page 59 of 67
TMI-12-O071, TMI-1 Steam Generator Tube Inspection Report (TJR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications.Outasie TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube T.vpe TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 128 51 T-TSP Wear 08S -0.8 7 0.14 63 P1 51OUL 559 B 128 53 T-TSP Wear 08S 0.4 11 0.21 141 P1 51OUL 557 B 128 53 T-TSP Wear 08S -0.8 10 0.19 111 P1 51OUL 557 B 128 54 T-TSP Wear 08S -0.8 9 0.15 125 P1 510UL 549 B 128 55 T-TSP Wear 08S -0.8 6 0.09 119 P1 51OUL 549 B 128 64 T-TSP Wear 08S -0.7 10 0.19 116 P1 51OUL 703 B 129 48 T-TSP Wear 08S 0.4 7 0.14 154 P1 51OUL 551 B 129 52 T-TSP Wear 08S -0.7 9 0.17 63 P1 51OUL 551 B 129 65 T-TSP Wear 08S -0.7 7 0.13 101 P1 51OUL 701 B 130 8 T-TSP Wear 09S 0.4 6 0.1 133 P1 51OUL 727 B 131 7 T-TSP Wear 09S 0.4 12 0.21 148 P1 51OUL 599 B 131 8 T-TSP Wear 09S 0.4 16 0.29 155 P1 51OUL 599 B 131 29 T-TSP Wear 08S -0.6 6 0.1 92 P1 51OUL 545 B 132 8 T-TSP Wear 09S 0.4 20 0.38 147 P1 51OUL 599 B 133 1 T-TSP Wear 13S -0.8 7 0.12 124 P1 510XB 010 B 133 1 T-TSP Wear 13S 0.3 12 0.24 146 P1 510XB 010 B 133 8 T-TSP Wear 09S 0.4 15 0.27 145 P1 51OUL 599 B 133 86 T-TSP Wear 09S 0.5 8 0.15 156 P1 510XB 038 B 133 87 T-TSP Wear 09S 0.4 12 0.23 154 P1 510XB 024 B 134 1 T-TSP Wear 13S -0.8 20 0.44 122 P1 510XB 010 B 134 7 T-TSP Wear 09S -0.7 11 0.18 89 P1 51OUL 591 B 134 7 T-TSP Wear 09S 0.4 21 0.39 160 P1 51OUL 591 B 134 14 T-TSP Wear 14S -0.8 12 0.18 147 P1 51OUL 591 Tuesday, April 24, 2012 Page60 of 6 7
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications.Outake T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 134 45 T-TSP Wear 08S -0.8 10 0.19 129 P1 51OUL 539 B 134 76 T-TSP Wear 14S 0.2 11 0.21 144 P1 51OUL 703 B 134 80 T-TSP Wear lOS 0.4 10 0.2 155 P1 51OUL 703 B 134 84 T-TSP Wear 13S 0.3 8 0.14 147 P1 510XB 024 B 134 84 T-TSP Wear 13S -0.8 7 0.12 141 P1 51OXB 024 B 135 8 T-TSP Wear 09S 0.4 10 0.15 142 P1 51OUL' 591 B 135 78 T-TSP Wear los 0.4 11 0.19 162 P1 51OUL 701 B 135 82 T-TSP Wear 13S 0.3 5 0.08 132 P1 510XB 026 B 136 8 T-TSP Wear 09S -0.6 5 0.21 114 P1 51OUL 593 B 136 43 T-TSP Wear 14S 0.2 8 0.15 138 P1 51OUL 539 B 136 81 T-TSP Wear 12S 0.3 8 0.16 139 P1 510XB 026 B 137 14 T-TSP Wear 14S -0.7 12 0.19 133 P1 51OUL 591 B 137 18- T-TSP Wear 14S -0.8 10 0.16 140 P1 51OUL 591 B 137 52 T-TSP Wear 15S 0.2 9 0.18 149 P1 51OUL 539 B 137 65 T-TSP Wear 09S 0.4 13 0.25 160 P1 51OUL 743 B 137 80 T-TSP Wear 13S -0.8 16 0.34 109 P1 510XB 026 B 137 80 T-TSP Wear 13S 0.3 10 0.2 144 P1 510XB 026 B 137 80 T-TSP Wear 12S 0.2 7 0.14 140 P1 510XB 026 B 137 80 T-TSP Wear. 11S 0.3 8 0.16 156 P1 51OXB 026 B 137 80 T-TSP Wear lOS -0.7 7 0.13 96 P1 51OXB 026 B 138 8 T-TSP Wear 09S 0.4 12 0.19 146 P1 51OUL 591 B 138 10 T-TSP Wear 14S -0.8 9 0.15 132 P1 51OUL 591 B 138 62 T-TSP Wear 09S 0.3 16 0.34 160 P1 51OUL 703 Tuesday, April 24, 2012 Page 61 of 67
TMI-12-0 71, TMI-1 Steam GeneratorTube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications. Outage T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 138 63 T-TSP Wear 09S 0.4 15 0.3 160 P1 51OUL 743 B 138 64 T-TSP Wear 09S 0.4 17 0.38 163 P1 51OUL 703 B 138 68 T-TSP Wear los 0.4 9 0.18 163 P1 51OUL 703 B 138 70 T-TSP Wear loS 0.5 9 0.18 156 P1 51OUL 703 B 138 72 T-TSP Wear loS 0.5 11 0.22 162 P1 51OUL 703 B 139 6 T-TSP Wear lOS -0.7 9 0.42 143 P1 51OUL 593 B 139 7 T-TSP Wear 09S 0.5 16 0.26 154 P1 51OUL 591 B 139 18 T-TSP Wear lOS -0.8 8 0.15 131 P1 51OUL 669 B 139 58 T-TSP Wear 09S 0.4 11 0.19 143 P1 51OUL 741 B 139 59 T-TSP Wear 09S 0.4 11 0.19 158 P1 51OUL 701 B 139 60 T-TSP Wear 09S 0.4 11 0.19 157 P1 51OUL 701 B 139 61 T-TSP Wear lOS 0.4 10 0.19 159 P1 51OUL 703 B 139 61 T-TSP Wear 09S 0.4 12 0.23 149 P1 51OUL 703 B 139 62 T-TSP Wear 10S 0.4 12 0.21 141 P1 51OUL 701 B 139 65 T-TSP Wear 09S 0.4 10 0.19 149 P1 51OUL 703 B 139 67 T-TSP Wear 09S 0.4 18 0.35 152 P1 51OUL 701 B 140 8 T-TSP Wear 09S 0.5 10 0.15 157 P1 51OUL 591 B 140 12 T-TSP Wear 09S 0.5 11 0.17 154 P1 51OUL 591 B 140 30 T-TSP Wear 14S 0.2 6 0.1 144 P1 51OUL 537 B 140 54 T-TSP Wear 09S -0.7 6 0.1 128 P1 51OUL 741 B 140 55 T-TSP Wear 10S 0.4 12 0.22 161 P1 51OUL 743 B 140 57 T-TSP Wear 09S 0.4 10 0.18 153 P1 51OUL 703 B 140 64 T-TSP Wear 12S -0.7 10 0.18 119 P1 51OUL 701 Tuesday, April 24, 2012 Page 62 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications.Outaae T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 141 7 T-TSP Wear 09S -0.6 13 0.61 139 P1 51OUL 593 B 141 8 T-TSP Wear 09S -0.7 17 0.3 131 P1 51OUL 591 B 141 14 T-TSP Wear 09S -0.6 12 0.18 129 P1 51OUL 591 B 141 38 T-TSP Wear 14S 0.2 5 0.09 141 P1 51OUL 539 B 141 53 T-TSP Wear 09S 0.4 7 0.13 144 P1 51OUL 703 B 141 54 T-TSPWear 09S 0.4 10 0.19 142 P1 51OUL 743 B 141 55 T-TSP Wear 11S -0.7 11 0.19 136 P1 51OUL 741 B 141 64 T-TSP Wear 09S 0.4 13 0.26 158 P1 510XB 026 B 141 65 T-TSP Wear 09S 0.4 7 0.13 150 P1 510XB 024 B 141 68 T-TSP Wear 12S 0.3 6 0.11 145 P1 510XB 024 B 141 68 T-TSP Wear 10S -0.7 11 0.21 132 P1 510XB 024 B 141 68 T-TSP Wear 09S 0.5 11 0.2 158 P1 510XB 024 B 142 12 T-TSP Wear 10S -0.7 17 0.3 130 P1 51OUL 591 B 142 13 T-TSP Wear 09S 0.4 16 0.28 147 P1 51OUL 531 B 142 62 T-TSP Wear 10S -0.7 9 0.18 112 P1 510XB 026 B 142 63 T-TSP Wear 10S -0.6 10 0.18 130 P1 510XB 024 B 142 63 T-TSP Wear 09S 0.4 13 0.25 152 P1 510XB 024 B 142 64 T-TSP Wear 09S 0.4 12 0.25 151 P1 510XB 026 B 142 65 T-TSP Wear 14S -0.8 6 0.11 151 P1 51OXB 024 B 142 65 T-TSP Wear 13S -0.7 7 0.12 157 P1 510XB 024 B 142 65 T-TSP Wear 12S 0.3 5 0.08 125 P1 510XB 024 B 142 65 T-TSP Wear 12S -0.8 10 0.18 129 P1 510XB 024 B 143 4 T-TSP Wear 10S -0.7 8 0.13 .99 P1 51OXB 008 B 143 11 T-TSP Wear .10S -0.7 11 0.2 138 P1 51OUL 529 Tuesday, April 24, 2012 Page 63 of 67
TMI-12-071, TMI-J Steam GeneratorTube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG B, All Service Induced Indications, Outaee TIR19 Location % Ind. nd Axial Circ.
SG Row Tube Tyvpe TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 143 17 T-TSP Wear 14S -0.8 10 0.18 139 P1 51OUL 525 B 143 32 T-TSP Wear 14S 0.2 6 0.1 141 P1 510UL 527 B 143 40 T-TSP Wear 14S 0.2 5 0.09 147 P1 51OUL 527 B 143 58 T-TSP Wear los 0.5 15 0.29 145 P1 510XB 024 B 143 59 T-TSP Wear loS 0.4 15 0.33 151 P1 510XB 026 B 143 60 T-TSP Wear loS 0.5 12 0.22 158 P1 510XB 024 B 144 5 T-TSP Wear los -0.8 13 0.26 .135 P1 510XB 008 B 144 8 T-TSP Wear loS -0.7 11 0.21 148 P1 51OUL 527 B 144 9 T-TSP Wear 09S 0.4 13 0.24 144 P1 51OUL 525 B 144 18 T-TSP Wear 09S 0.4 9 0.17 161 P1 51OUL 527 B 144 21 T-TSP Wear 09S 0.4 13 0.25 155 P1 51OUL 525 B 144 22 T-TSP Wear 09S 0.3 7 0.12 147 P1 51OUL 527 B 144 38 T-TSP Wear 09S 0.4 12 0.22 144 P1 51OUL 525 B 144 39 T-TSP Wear 09S 0.4 11 0.21 143 P1 51OUL 527 B 144 40 T-TSP Wear 09S 0.4 14 0.28 159 P1 51OUL 525 B 144 45 T-TSP Wear lOS 0.4 12 0.22 149 P1 51OUL 701 B 144 48 T-TSP Wear 09S 0.4 11 0.21 149 P1 51OUL 703 B 144 50 T-TSP Wear 10S 0.4 11 0.21 153 P1 510XB 026 B 144 52 T-TSP Wear 10S 0.4 11 0.22 150 P1 510XB 026 B 144 53 T-TSP Wear 10S 0.5 11 0.21 140 P1 510XB 024 B 145 7 T-TSP Wear 10S -0.7 20 0.43 126 P1 51OUL 527 B 145 17 T-TSP Wear 10S -0.7 9 0.16 129 P1 51OUL 527 Tuesday, April 24, 2012 Page 64 of 67
TMI-12-071, TMI-1 Steam Generator Tube Inspection Report (TIR19)
Attachment 1, Exhibit 2 SG BA All Service Induced Indications.Outake T1R19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T.W. Start End Length Degrees Volts Phase Chn. Probe Cal B 145 18 T-TSP Wear 10S -0.8 9 0.17 118 P1 510UL 525 B 145 19 T-TSP Wear 10S -0.7 7 0.13 144 P1 51OUL 527 B 145 20 T-TSP Wear 09S 0.3 10 0.19 152 P1 51OUL 525 B 145 33 T-TSP Wear 09S 0.4 11 0.21 147 P1 51OUL 527 B 145 34 T-TSP Wear 09S 0.4 15 0.3 134 P1 51OUL 525 B 145 35 T-TSP Wear 09S 0.4 9 0.15 153 P1 51OUL 527 B 145 36 T-TSP Wear 09S 0.4 13 0.24 143 P1 51OUL 525 B 145 37 I-TSP Wear 10S 0.4 9 0.17 157 P1 51OUL 527 B 145 37 T-TSP Wear 09S 0.4 15 0.29 146 P1 51OUL 527 B 145 40 T-TSP Wear 09S 0.4 12 0.22 135 P1 51OUL 525 B 145 48 T-TSP Wear 10S 0.4 8 0.14 148 P1 51OXB 024 B 145 49 T-TSP Wear 10S 0.4 21 0.5 133 P1 510XB 026 B 145 50 T-TSP Wear 10S 0.5 9 0.16 146 P1 510XB 024 B 146 11 T-TSP Wear 09S 0.3 18 0.38 133 P1 51OUL 525 B 146 15 T-TSP Wear 13S 0.1 10 0.17 127 P1 51OUL 525 B 146 19 T-TSP Wear 09S 0.4 13 0.25 143 P1 51OUL 525 B 146 20 T-TSP Wear 09S 0.4 12 0.24 150 P1 51OUL 527 B 146 25 T-TSP Wear 09S 0.4 11 0.2 155 P1 51OUL 525 B 146 28 T-TSP Wear 09S 0.5 11 0.2 162 P1 51OUL 527 B 146 35 T-TSP Wear 09S 0.4 13 0.26 138 P1 51OUL 525 B 146 45 T-TSP Wear 10S 0.4 19 0.43 141 P1 51OXB 026 B 146 46 T-TSP Wear 10S 0.4 19 0.4 137 P1 510XB 024 B 146 46 T-TSP Wear 09S 0.5 12 0.23 152 P1 510XB 024 Tuesday, April 24, 2012 Page 65 of 67
TMI-12-071, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG BA All Service Induced Indications. Outaie TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal B 146 47 T-TSP Wear los 0.5 15 0.3 136 P1 510XB 024 B 146 47 T-TSP Wear 09S 0.4 9 0.17 139 P1 510XB 024 B 147 6 T-TSP Wear los -0.7 11 0.2 146 P1 51OUL 525 B 147 13 T-TSP Wear lOS -0.7 9 0.17 140 P1 51OUL 527 B 147 24 T-TSP Wear 09S 0.3 7 0.13 148 P! 5 1OUL 525 B 147 30 T-TSP Wear 09S 0.4 8 0.15 146 P1 51OUL 525 B 147 31 T-TSP Wear loS 0.3 12 0.23 155 P1 51OUL 527 B 147 33 T-TSP Wear 09S 0.4 11 0.21 153 P1 51OUL 527 B 147 34 T-TSP Wear 09S 0.4 11 0.21 153 P1 51OUL 525 B 147 35 T-TSP Wear 09S 0.4 10 0.19 159 P1 51OUL 527 B 148 11 T-TSP Wear lOS -0.7 11 0.2 133 P1 51OUL 525 B 148 28 T-TSP Wear 09S 0.3 7 0.13 151 P1 51OUL 527 B 149 32 T-TSP Wear lOS 0.4 10 0.18 152 P1 510XB 016 B 150 7 T-TSP Wear 12S -0.8 8 0.15 117 P1 510XB 010 B 150 12 T-TSP Wear loS -0.7 7 0.12 123 P1 51OXB 008 B 150 27 T-TSP Wear 09S 0.4 16 0.33 149 P1 510XB 010 B 151 2 T-TSP Wear 12S -0.8 7 0.11 132 P1 510XB 008 B 151 5 T-TSP Wear 11S 0.3 5 0.09 134 P1 510XB 010 B 151 23 T-TSP Wear 12S 0.3 9 0.17 136 P1 510XB 010 B 151 24 T-TSP Wear 13S -0.8 14 0.3 124 P1 51OXB 010 B 151 24 T-TSP Wear 13S 0.3 32 0.89 119 P1 510XB 010 B 151 24 T-TSP Wear 12S 0.3 11 0.21 145 P1 510XB 010 B 151 24 T-TSP Wear 09S 0.4 12 0.25 147 P1 510XB 010 Tuesday, April 24, 2012 Page 66 of 6 7
TMI-12-O071, TMI-1 Steam GeneratorTube Inspection Report (T1R19)
Attachment 1, Exhibit 2 SG B, All Service InducedIndications. Outage TJR19 Location % Ind. Ind. Axial Circ.
SG Row Tube Type TSP Offset T. W. Start End Length Degrees Volts Phase Chn. Probe Cal Total Tubes 1190 Total Indications 1548 Page670!
Page 67 67 of 67 Tuesday, April24, Tuesday, April 20)2 24, 2012