UNITED STATES NUCLEAR REGULATORY COMMISSION REGION III 2443 WARRENVILLE ROAD, SUITE 210 LISLE, IL 60532-4352 November 23, 2011 Mr. Larry Weber Chief Nuclear Officer Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106

SUBJECT:

D. C. COOK NUCLEAR POWER PLANT - NOTIFICATION OF AN NRC MANAGEMENT OF GAS ACCUMULATION IN EMERGENCY CORE COOLING, DEACY HEAT REMOVAL, AND CONTAINMENT SPRAY SYSTEMS INSPECTION; AND REQUEST FOR INFORMATION 05000315/2012002; 05000316/2012002(DRS)

Dear Mr. Weber:

On January 23, 2012, the U. S. Nuclear Regulatory Commission (NRC) will begin the on-site portion of the Gas Accumulation Management in Emergency Core Cooling, Decay Heat Removal, and Containment Spray Systems Temporary Instruction at your D.C. Cook Nuclear Power Plant. This inspection will be performed in accordance with NRC temporary instruction (TI) 2515/177. The lead inspector for this inspection is Ms. Caroline Tilton.

In order to minimize the impact that the inspections have on the site and to ensure productive inspections, we have enclosed a request for documents needed for the inspection. The documents have been divided into three groups.

The first group lists information necessary for our initial inspection scoping activities. This information should be available to the lead inspector no later than December 12, 2011. By December 16, 2011, the lead inspector will communicate the initial selected samples.

The second group of documents requested is those items needed to support our in-office preparation activities. This set of documents should be available at the Regional Office no later than January 9, 2012. This information should be separated by information request number, especially if provided electronically (e.g., folder with the information request number). During the in-office preparation activities, the inspectors may identify additional information needed to support the inspection. The lead inspector will provide a list of the additional information needed during the week of January 16, 2012.

The last group includes the additional information above, as well as plant specific reference material. This information should be available to the inspector on January 23, 2012. It is also requested that corrective action documents and/or questions developed during the inspection be provided to the inspector as the documents are generated.

Please send the information to the following e-mail address caroline.tilton@nrc.gov. A hard-copy with the required information is also an acceptable option. If there are questions about the material requested, or the inspection, please call Ms. Tilton at (630) 829-9718.

It is important that these documents are as complete as possible, in order to minimize the number of documents requested during the preparation week or during the on-site inspection.

If no activities were accomplished associated with a specific request, then provide a statement indicating that the request is not applicable.

This letter does not contain new or amended information collection requirements subject to the Paperwork Reduction Act of 1995 (44 U.S.C. 3501 et seq.). Existing information collection requirements were approved by the Office of Management and Budget, control number 3150-0011. The NRC may not conduct or sponsor, and a person is not required to respond to, a request for information or an information collection requirement unless the requesting document displays a currently valid Office of Management and Budget control number.

In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter and its enclosure will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRC's document system (ADAMS), accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Sincerely,

/RA/

Ann Marie Stone, Chief Engineering Branch 2 Division of Reactor Safety Docket Nos. 50-266; 50-301 License Nos. DPR-24; DPR-27

Enclosures:

MANAGEMENT OF GAS ACCUMULATION IN EMERGENCY CORE COOLING, DECAY HEAT REMOVAL, AND CONTAINMENT SPRAY SYSTEMS TEMPORARY INSTRUCTION DOCUMENT REQUEST cc w/encl: Distribution via ListServ'

MANAGEMENT OF GAS ACCUMULATION IN EMERGENCY CORE COOLING, DECAY HEAT REMOVAL, AND CONTAINMENT SPRAY SYSTEMS TEMPORARY INSPECTION DOCUMENT REQUEST 1

Enclosure Inspection Report: 05000315/2012002; 05000316/2012002(DRS)

Inspection Dates:

January 23 - 27, 2012; and February 06 - 10, 2012 Inspection Procedure:

TI 2515/177, Management of Gas Accumulation in Emergency Core Cooling, Decay Heat Removal, and Containment Spray Systems Inspectors:

Caroline Tilton (630) 829-9718 caroline.tilton@nrc.gov Néstor J. Féliz Adorno (630) 829-9739 nestor.feliz-adorno@nrc.gov I.

Information Requested By December 12, 2011:

1.

Copy of the station response to Generic Letter (GL) 2008-01 and any supplemental report.

2.

Copies of all the requests for additional information (RAI) and the associated responses.

3.

List of corrective action program documents (with a short description) associated with GL 2008-01, voids in piping, gas intrusion events, and pressure transients for the previous three years that affected the subject systems (i.e., emergency core cooling, decay heat removal, and containment spray systems).

4.

List of the suction piping sections identified as susceptible to gas accumulation (the list should identify the corresponding system).

5.

List of the discharge piping sections identified as susceptible to gas accumulation (the list should identify the corresponding system).

6.

List of changes (with a short description and tracking number) to the Final Safety Evaluation Report (FSAR), Technical Specifications, Technical Specification Bases, and Technical Requirement Manual associated with the resolution of GL 2008-01.

7.

List of calculations associated with GL 2008-01 (with a short description of the calculation and the change), including calculations that have been changed or created in response to GL 2008-01.

MANAGEMENT OF GAS ACCUMULATION IN EMERGENCY CORE COOLING, DECAY HEAT REMOVAL, AND CONTAINMENT SPRAY SYSTEMS TEMPORARY INSPECTION DOCUMENT REQUEST 2

Enclosure II.

Information Requested By January 9, 2012:

1.

Copies of program documents and procedures developed to implement the resolution of GL 2008-01.

2.

Copies of the selected corrective action program documents.

3.

Copies of the selected licensing and design basis document changes.

4.

Copies of the selected calculations.

5.

List of commitments (with a description) made in response to GL 2008-01.

6.

List of actions that were completed in response to GL 2008-01.

7.

List of outstanding actions that will be completed in response to GL 2008-01 and the completion schedule (include the documents that are tracking their completion such as work orders or corrective action documents).

8.

Copies of all the corrective actions identified in the nine-month response and supplemental reports.

9.

List (with a short description) of gas intrusion mechanisms that apply to the plant and the affected system locations (e.g., identify the source, conditions, and expected void locations).

10. Design basis documents of the subject systems.
11. Design basis documents of keep-full systems of the subject systems.
12. Copies of the construction code pages of the subject systems that discuss water-hammer or flow-induced dynamic loading. Also, include the associated Design Specification pages.
13. Provide the following description for the pumps of the subject systems: (1) flow-rate at best efficiency point; (2) maximum and minimum flow-rate during accident conditions and shutdown cooling; (3) number of pump stages; (4) if a pump is multi-stage, indicate if the shaft is stiff or flexible (include the basis for this determination); (5) pump head required to meet operability requirements; and (6) un-degraded pump head.
14. Copies of self-assessments associated with the implementation of the GL 2008-01 program and the associated corrective action program documents (include the Attachments, if any).

MANAGEMENT OF GAS ACCUMULATION IN EMERGENCY CORE COOLING, DECAY HEAT REMOVAL, AND CONTAINMENT SPRAY SYSTEMS TEMPORARY INSPECTION DOCUMENT REQUEST 3

Enclosure

15. Copies of corrective action program implementing procedures.
16. Copies of the operability determination procedures.
17. Electronic copies of piping and instrumentation diagrams (P&IDs) of the subject systems.
18. If available, electronic copies of the current Technical Specifications, Technical Specifications Basis, Final Safety Analysis Report, and Technical Report Manual.

III.

Information Requested to be Available on First Day of Inspection, January 23, 2012:

1.

Copies of surveillance procedures associated with the resolution of GL 2008-01 and the results of the last two surveillances for the subject systems.

2.

Copies of the modification packages for hardware modifications as part of the resolution of GL 2008-01.

3.

Copies of procedures use for detecting and determining void volumes.

4.

Copies of procedures use for filling and venting.

5.

Copies of surveillance procedures that establish flow at the subject systems (e.g.,

surveillances where the pumps are operated)

6.

Subject systems walkdown work documents associated with the resolution of GL 2008-01 and the results of these walkdowns.

7.

Copies of the engineering evaluations performed for all identified voids.

8.

Provide a list of all piping locations that are currently voided and their associated evaluation.

9.

Copies of trends of periodic gas accumulation monitoring results (e.g., venting, UTs).

10. Copy of the design change review checklist.
11. Copies of training documents that ensure that personnel are aware of gas-related concerns. Include the scheduled or attendance list of training that was already conducted.
12. Copy of the void transport analysis.

MANAGEMENT OF GAS ACCUMULATION IN EMERGENCY CORE COOLING, DECAY HEAT REMOVAL, AND CONTAINMENT SPRAY SYSTEMS TEMPORARY INSPECTION DOCUMENT REQUEST 4

Enclosure

13. Basis for the void acceptance criteria (e.g., calculation). If applicable, provide the justification for any deviation from the void acceptance criteria established by the Office of Nuclear Reactor Regulations (NRR).
14. Basis for horizontal pipe acceptance criteria (e.g., calculation).
15. If applicable, provide a list of inaccessible locations where plant walkdowns of the subject systems have not been completed. Include an explanation of why each area is considered inaccessible.
16. Hardcopies of isometric drawings of the subject systems (11X17 or similar size is preferred if legible).
17. Hardcopies of piping and instrumentation diagrams (P&IDs) of the subject systems (11X17 or similar size is preferred if legible).

If you have questions regarding the information requested, please contact the lead inspector.

Please send the information to the following e-mail address caroline.tilton@nrc.gov. A hard-copy with the required information is also an acceptable option. If there are questions about the material requested, or the inspection, please call Ms. Tilton at (630) 829-9718.

It is important that these documents are as complete as possible, in order to minimize the number of documents requested during the preparation week or during the on-site inspection.

If no activities were accomplished associated with a specific request, then provide a statement indicating that the request is not applicable.

This letter does not contain new or amended information collection requirements subject to the Paperwork Reduction Act of 1995 (44 U.S.C. 3501 et seq.). Existing information collection requirements were approved by the Office of Management and Budget, control number 3150-0011. The NRC may not conduct or sponsor, and a person is not required to respond to, a request for information or an information collection requirement unless the requesting document displays a currently valid Office of Management and Budget control number.

In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter and its enclosure will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRC's document system (ADAMS), accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Sincerely,

/RA/

Ann Marie Stone, Chief Engineering Branch 2 Division of Reactor Safety Docket Nos. 50-266; 50-301 License Nos. DPR-24; DPR-27

Enclosures:

MANAGEMENT OF GAS ACCUMULATION IN EMERGENCY CORE COOLING, DECAY HEAT REMOVAL, AND CONTAINMENT SPRAY SYSTEMS TEMPORARY INSTRUCTION DOCUMENT REQUEST cc w/encl: Distribution via ListServ' DISTRIBUTION:

See next page DOCUMENT NAME: G:\\DRSIII\\DRS\\Work in Progress\\-Ltr 11__11 DCCOOK TI177 ISI AMS.docx Publicly Available Non-Publicly Available Sensitive Non-Sensitive To receive a copy of this document, indicate in the concurrence box "C" = Copy without attach/encl "E" = Copy with attach/encl "N" = No copy OFFICE RIII RIII NAME CTilton:ls AMStone DATE 11/21/11 11/23/11 OFFICIAL RECORD COPY