ML11231A667

From kanterella
Jump to navigation Jump to search
Submittal of Pre-Op Test Instruction, 2-PTI-090-01, Revision 0, Radiation Monitors - Area Dose Rate
ML11231A667
Person / Time
Site: Watts Bar 
Issue date: 08/17/2011
From: Stinson D
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
2-PTI-090-01, Rev 0
Download: ML11231A667 (118)


Text

Tennessee Valley Authority, Post Office Box 2000, Spring City, Tennessee 37381-2000 August 17, 2011 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555-0001 Watts Bar Nuclear Plant, Unit 2 NRC Docket No. 50-391

Subject:

Watts Bar Nuclear Plant (WBN) Unit 2 - Submittal of Pre-op Test Instruction The following approved WBN Unit 2 Pre-op Test Instruction (PTI) is enclosed:

PTI NUMBER Rev.

TITLE 2-PTI-090-01 0

Radiation Monitors - Area Dose Rate If you have any questions, please contact Pete Olson at (423) 365-3294.

Respectfully, David Stinson Watts Bar Unit 2 Vice President Enclosure cc (Enclosure):

U. S. Nuclear Regulatory Commission Region II Marquis One Tower 245 Peachtree Center Ave., NE Suite 1200 Atlanta, Georgia 30303-1257 NRC Resident Inspector Unit 2 Watts Bar Nuclear Plant 1260 Nuclear Plant Road Spring City, Tennessee 37381 (tit

WATTS BAR NUCLEAR PLANT UNIT 2 STARTUP TITLE: Radiation Monitors -Area Dose Rate Instruction No: 2-PTI-090-01 Revision No: 0000 Re-gina Ballard tan'n DATE PREPARED BY:

REVIEWED BY:

PRINT NAM/

SIGNATURE A. Blake Lowe // _-

4ýtý DAT I(02~

E

-A/614 PRINT NAME/ SIGNATURE INSTRUCTION. APPROVAL JTG MEETING 1JQ:

h-I DATE S)

DATE6 PREOPERATIONAL STARTUP MANAGER TEST RESULTS APPROVAL JTG MEETING NO:

JTG CHAIRMAN:

APPROVED BY:

DATE DATE PREOPERATIONAL STARTUP MANAGER SMIP-8.0, R4, Administration of Preoperational Test Instructions, Appendix B

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 2 of 117 Revision Log Revision Affected or Change Effective Page Number Date Numbers Description of RevisionlChange 0000 f/,,

I All INITIAL ISSUE

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 3 of 117 Table of Contents

1.0 INTRODUCTION

5 1.1 T est O bjectives...................................................................................................... 5 1.2 S c o p e.............................................................................................................................

5

2.0 REFERENCES

8 2.1 Perform ance References...........................................................................................

8 2.2 Developmental References.......................................................................................

9 3.0 PRECAUTIONS AND LIMITATIONS.....................................................................

11 4.0 PREREQUISITE ACTIONS....................................................................................

13 4.1 P re lim inary A ctions.................................................................................................

13 4.2 Special Tools, Measuring and Test Equipment, Parts, and Supplies...................... 17 4.3 F ie ld P re pa ratio ns.....................................................................................

............... 18 4.4 Approvals and Notifications....................................................................................

19 5.0 ACCEPTANCE CRITERIA....................................................................................

20 6.0 PERFORMANCE........................................................................................................

31 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT.......................... 32 6.2 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON........................... 44 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON.............................. 55 6.4 2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON......................... 67 6.5 2-LPR-90-271, CNTMT POST ACC HIGH RAD....................................................

78 6.6 2-LPR-90-272, CNTMT POST ACC HIGH RAD..........................................................

86 6.7 2-LPR-90-273, CNTMT POST ACC HIGH RAD....................................................

94 6.8 2-LPR-90-274, CNTMT POST ACC HIGH RAD.......................................................

103 7.0 POST PERFORMANCE ACTIVITY..........................................................................

112 8.0 R EC O R D S................................................................................................................

114 Appendix A:

TEST PROCEDURE/INSTRUCTION REFERENCE REVIEW................. 115 Appendix B:

TEMPORARY CONDITION LOG.............................................................

116

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 4 of 117 Table of Contents (continued)

PERMANENT PLANT INSTRUMENTATION LOG..................................

117 Appendix C:

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 5 of 117 Data Package: Page of Date

1.0 INTRODUCTION

1.1 Test Objectives A.

Demonstrate operation of the Area Dose Rate radiation monitors and their response to check sources, including verification of local and control room indicating and recording devices.

B.

Demonstrate the initiation of high radiation alarm signals and the ability of Area Dose Rate monitors to alert personnel of excessive dose rate levels.

1.2 Scope A.

2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT LOOP

1.

2-RM-90-2, ACCIDENT RAD MON OUTLET PERSONNEL ENT (MCR Panel 0-M-12)

2.

2-RR-90-1P003 RECORDER (POINT #3 MCR Panel 0-M-12)

3.

2-RI-90-2A, ACCIDENT RAD MON OUTLET PERSONNEL ENT (MCR Panel 0-M-12)

4.

2-RI-90-2B, PERSONNEL AIRLOCK AREA RADIATION (El. 757', Al 1Y).

5.

CONTROL ROOM AND LOCAL ALARMS AND ANNUNCIATION (MCR Panel 0-M-12 and El. 757', AllY).

B.

2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON LOOP

1.

2-RM-90-59, UP COMPARTMENT REAC BLDG AREA MON (MCR Panel 0-M-1 2)

2.

2-RR-90-1P001, RECORDER (POINT #1 MCR Panel 0-M-12)

3.

2-RI-90-59A, UP COMPARTMENT REAC BLDG - AREA MON (MCR Panel 0-M-1 2)

4.

2-RI-90-59B, UP COMPARTMENT REAC BLDG - AREA MON (El. 756',

Az. 3100)

5.

CONTROL ROOM AND LOCAL ALARMS AND ANNUNCIATION (MCR Panel 0-M-12 and El. 756', Az. 3100).

Data Package: Page of Date 1.2 Scope (continued)

C.

2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON LOOP

1.

2-RM-90-60, UP COMPARTMENT REAC BLDG AREA MON (MCR Panel 0-M-1 2)

2.

2-RR-90-1P002 RECORDER (POINT #2 MCR Panel 0-M-12)

3.

2-RI-90-60A, UP COMPARTMENT REAC BLDG -,AREA MON (MCR Panel 0-M-12)

4.

2-RI-90-60B, UP COMPARTMENT REAC BLDG - AREA MON (El. 756',

Az. 2250)

5.

CONTROL ROOM AND LOCAL ALARMS AND ANNUNCIATION (MCR Panel 0-M-12 and El. 756', Az. 2250).

D.

2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON LOOP

1.

2-RM-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (MCR

.Panel 0-M-12)

2.

2-RR-90-1P004 RECORDER (POINT #4 MCR Panel 0-M-12)

3.

2-RI-90-61A, LOWER COMPARTMENT INSTR RM - AREA MON (MCR Panel 0-M-12)

4.

2-RI-90-61 B, LOWER COMPARTMENT INSTR RM - AREA MON (El. 736', Az. 820)

5.

CONTROL ROOM AND LOCAL ALARMS AND ANNUNCIATION (MCR Panel 0-M-12 and El. 736', Az. 820).

E.

2-LPR-90-271, CNTMT POST ACC HIGH RAD

1.

2-RM-90-271, UPR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

2.

CONTROL ROOM ANNUNCIATION (MCR Panel 2-M-30).

F.

2-LPR-90-272, CNTMT POST ACC HIGH RAD

1.

2-RM-90-272, UPR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

2.

CONTROL ROOM ANNUNCIATION (MCR Panel 2-M-30).

Data Package: Page of Date 1.2 Scope (continued)

G.

2-LPR-90-273, CNTMT POST ACC HIGH RAD

1.

2-RM-90-273, LWR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

2.

CONTROL ROOM ANNUNCIATION (MCR Panel 2-M-30).

H. 2-LPR-90-274, CNTMT POST ACC HIGH RAD

1.

2-RM-90-274, LWR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

2.

CONTROL ROOM ANNUNCIATION (MCR Panel 2-M-30).

Data Package: Page

-of Date

2.0 REFERENCES

2.1 Performance References A.

SMP-9.0, Conduct of Test B.

2-IMI-90.021, 18 Mo. Channel Cal (Source) of Accident Rad Mon Outlet Pers Entrance Loop, [LATER]

C.

2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1000 Digital Ratemeters, [LATER]

D.

2-SI-90-1, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-271, [LATER]

E.

2-SI-90-2, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-272, [LATER]

F.

2-SI-90-3, 18 Mo Ch Source Cal CNTMT LWR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-273, [LATER]

G.. 2-SI-90-4, 18 Mo Ch Source Cal CNTMT LWR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-274, [LATER]

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 9 of 117 Data Package: Page

-of Date 2.2 Developmental References A.

Final Safety Analysis Report (FSAR)

1.

FSAR - Amendment 104

a.

Chapter 12, Section 12.3.4 and Table 12.3-4

b.

Chapter 14.2.12 and Table 14.2-1 Sheet 33 B.

Drawings

1.

Electrical

a.

1-45B655-12D, Rev 3, Main Control Room Annunciator Inputs Window Box XA-55-12D, CCD

b.

1-45B655-E1 2D, Rev 0, Electrical Annunciator Window Box XA-55-12D Engraving, CCD

c.

47B601-55-78, Rev 4, Electrical Instrument Tabulation, AD DRA 52338-003, Rev 0

d.

2-45W600-55-46, Wiring Diagrams Annunciator System Key Diagrams, Sheet 46, [ANT]

DRA 52338-113, Rev 0

e.

1-45W706-3, Rev 48, Wiring Diagram 120V Vital Inst Pwr Bds 1-111 &

2-111 Connection Diagram, Sheet 3, CCD

f.

1-45W706-4, Rev 50, Wiring Diagram 120V AC Vital Inst Pwr Bds 1-IV

& 2-IV Connection Diagrams, CCD

g.

45N708-3, Rev 9, Wiring Diagram Misc 120V AC Distribution Panels Connection Diagram, Sheet 3, AD

h.

45N2620-1, Rev 8, Wiring Diagrams Radiation Monitoring System Connection Diagrams Sh-1, AD DRA 52338-101, Rev 0 DRA 52341-101, Rev 0

i.

45W2620-4, Rev 7, Wiring Diagrams Radn Monitoring Sys Connection Diag Sh 4, AD DRA 52338-106, Rev 0

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 10 of 117 Data Package: Page of Date 2.2 Developmental References (continued)

j.

45W2651-3, Rev 3, Wiring Diagrams Unit Cont Bd PnI 2-M-30 Connection Diagrams Sh-3, AD DRA 52338-109, Rev 0 DRA 52374-07, Rev 0

k.

1-45W26246-3, Rev 14, Wiring Diagram Unit Control Bd Pnl 2-M-7 Connection Diagrams, CCD

1.

1-45W2646-3, Rev 16, Wiring Diagram Unit Control Bd PnI 2-M-7 Connection Diagram, CCD

2.

Logic/Control

a.

2-47W610-90-2, Rev 0, Electrical Instrument and Controls Radiation Monitoring Sys, CCD DRA 52338-002, Rev 0 DRA 52341-007, Rev 0

b.

2-47W610-90-4, Rev 1, Electrical Control Diagram Radiation Monitoring Sys, CCD DRA 52338-001, Rev 0 DRA 52339-003, Rev 0

3.

Vendor Drawings

a.

0281-5011-3, Rev 901, Wiring Diagram Radiation Monitoring System

b.

D281-0253, Rev H, ASSEMBLY, LOCAL INDICATOR C.

Vendor Manuals

1.

WBN-VTM-G292-0400, Vendor Technical Manual for GA Technologies Low, Intermediate and High Range Area Radiation Monitors, Rev 6

2.

SQN-VTD-G063-0460, Vendor Technical Documentation for Sorrento Electronics RM-1000 Digital Radiation Process Technical Manual -

Document 04508100-1TM, Revision C, October 2003.

To be verified against WBN-VTD-G292-2030 [Later] in Appendix A.

D.

Documents

1.

2-TSD-90-6, Area Radiation Monitoring System (Area Monitors) Test Scoping Document, Rev 1

Data Package: Page

-of Date 3.0 PRECAUTIONS AND LIMITATIONS A.

Standard precautions shall be followed for working around energized electrical equipment in accordance with TVA Safety Procedure 1021.

B. Steps may be repeated if all components cannot be tested in a step. However, if the test has been exited, prerequisite steps must be re-verified and a Chronological Test Log (CTL) entry made.

C.

Discrepancies between component ID tags and the description in a procedure/instruction if the UNIDs match, exclusive of place keeping zeros and train designators (e.g. 2-HS-31-468 vs. 2-HS-031-0468) and the noun description is sufficient to identify the component. This condition does not require a TDN in accordance with SMP-14.0. If the component label needs to be changed, a Tag Request Form (TR Card) should be processed in accordance with TI-12.14. Make an entry in the CTL and continue testing.

D.

All wires removed/lifted from a terminal shall be identified and taped or covered with an insulator to prevent personnel or equipment hazard and possible spurious initiations. The wires should be grouped together and labeled with the work implementing document number that required them to be lifted if left unattended.

E.

All open problems are to be tracked by a corrective action document and entered on the appropriate system punchlist.

F.

Problems identified during the test shall be annotated on the Chronological Test Log (CTL) from SMP-9.0 including a description of the problem, the procedure step when/where the problem was identified, corrective action steps taken to resolve the problem, and the number of the corrective action document, if one was required.

G.

Observe all Radiation Protection (RP) requirements when working in or near radiological areas.

H. Ensure there are no adverse effects to the operation of Unit 1 structures, systems, or components.

1.

Test personnel will coordinate with Unit 1 Operations when manipulating Unit 1 equipment if required.

J.

Radiological Worker and radioactive source handling training is required for handling radioactive sources.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 12 of 117 Data Package: Page

-of Date 3.0 PRECAUTIONS AND LIMITATIONS (continued)

K. Use of radioactive calibration sources shall be coordinated with Radiation Protection.

L.

Personnel assigned to perform steps requiring operation of the digital ratemeters must be familiar with the RM-1 000 operation and maintenance and should review the vendor technical manual prior to performing associated test steps. (Subsections 6.1 through 6.8).

M. Operations personnel should be advised that a High Radiation Alarm will be initiated when conducting the loss of power simulation in each subsection.

N. Testing of the containment high range area monitor channels in this test will require actions inside containment requiring climbing equipment and safety harnesses.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 13 of 117 Data Package: Page of Date 4.0 PREREQUISITE ACTIONS NOTE Prerequisite steps may be performed in any order unless otherwise stated and should be completed as close in time as practicable to the start of instruction subsection to which they apply.

4.1 Preliminary Actions

[1]

EVALUATE open items in Watts Bar Integrated Task Equipment List (WITEL), AND ENSURE they will NOT adversely affect the test performance and results.

[2]

ENSURE changes to the references listed on Appendix A, have been reviewed, and determined NOT to adversely affect the test performance.

[3]

VERIFY current revisions and change paper for referenced drawings has been reviewed and determined NOT to adversely affect the test performance, AND ATTACH documentation of current drawing revision numbers and change papers that were reviewed to the data package.

[4]

VERIFY the test/performance copy of this Preoperational Test Instruction (PTI) is the current revision including any change notices and as needed, each test person assisting in this test has the current revision including any change notices.

[5]

OBTAIN copies of the applicable forms from the latest revision of SMP-9.0, AND ATTACH to this PTI for use during the performance of this PTI.

Data Package: Page of Date 4.1 Preliminary Actions (continued)

[6]

ENSURE outstanding Design Change Notices (DCN's),

Engineering Document Construction Releases (EDCR's) or Temporary Alterations (TA's) do NOT adversely impact testing, AND ATTACH documentation of DCN's, EDCR's and TA's that were reviewed to the data package.

[7]

ENSURE required Component Testing has been completed prior to start of test.

(8]

ENSURE a review of outstanding Clearances has been coordinated with Unit 2 Operations for impact to the test performance, AND RECORD in Appendix B, Temporary Condition Log if required.

[9]

VERIFY plant instruments, listed on Appendix C, Permanent Plant Instrumentation Log, are placed in service and are within their calibration interval.

A.

Subsection 6.1 B.

Subsection 6.2 C.

Subsection 6.3 D.

Subsection 6.4 E.

Subsection 6.5 F.

Subsection 6.6 G.

Subsection 6.7 H. Subsection 6.8

Data Package: Page

-of Date 4.1 Preliminary Actions (continued)

[10]

ENSURE System 55, Annunciator and Sequential Events Recording System applicable TBK switches are ON, the applicable Master Switches are ON, and window software input(s) are ENABLED for the following Annunciator windows.

A.

0-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI (Subsections 6.1, 6.2, 6.3, and 6.4)

B.

0-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF (Subsections 6.1, 6.2, 6.3, and 6.4)

C.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF (Subsections 6.5, 6.6, 6.7, and 6.8)

[11]

ENSURE the following Integrated Computer System (ICS) points are in scan:

A.

R9015A, ACCIDENT RAD MON OUT PERSONNEL, 2-RE-90-2 (Subsection 6.1)

B.

R9016A, UP COMPT REAC BLDG AREA MON, 2-RE-90-59 (Subsection 6.2)

C.

R9017A, UP COMPT REAC BLDG AREA MON, 2-RE-90-60 (Subsection 6.3)

D.

R9018A, UPR CNTMT POST ACD AREA MON, 2-RE-90-271 (Subsection 6.5)

E.

R9019A, UPR CNTMT POST ACD AREA MON 2-RE-90-272 (Subsection 6.6)

F.

R9020A, LWR CNTMT POST ACC AREA MON 2-RE-90-273 (Subsection 6.7)

G.

R9021A, LWR CNTMT POST ACC AREA MON 2-RE-90-274 (Subsection 6.8)

[12]

ENSURE System 278, Main and Auxiliary Control Boards System is supplying power via plug mold outlets in Panels MCR Panel 2-M-30.

[13]

ENSURE components contained within the boundaries of this test are under the jurisdictional control of Preoperational Startup Engineering (PSE) and/or Plant Operations.

Data Package: Page

-of Date 4.1 Preliminary Actions (continued)

[14]

PERFORM a pretest walkdown on equipment to be tested to ensure no conditions exist that will impact test performance.

[15]

CONDUCT a pretest briefing with Test and Operations personnel in accordance with SMP-9.0.

[16]

ENSURE communications are available for areas where testing is to be conducted.

Data Package: Page

-of Date 4.2 Special Tools, Measuring and Test Equipment, Parts, and Supplies.

NOTE If no M&TE is used, then Step 4.2[1] is N/A.

[1]

ENSURE any M&TE or equivalent is available and within their calibration due dates, AND RECORD the M&TE data on SMP-9.0, Measuring and Test Equipment (M&TE) Log.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 18 of 117 Data Package: Page of 4.3 Field Preparations

[1]

ENSURE the following radiation monitor modules, located on 0-M-12 and 2-M-30, are reset and operational with the green OPERATE light ON, and the red HIGH (2) and yellow ALERT (1) lights OFF.

Date SUBSECTION MODULE INITIALS 6.1 2-RM-90-2 6.2 2-RM-90-59 6.3 2-RM-90-60 6.4 2-RM-90-61 6.5 2-RM-90-271 6.6 2-RM-90-272 6.7

ý 2-RM-90-273 6.8 2-RM-90-274

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev.0000 Page 19 of 117 Data Package: Page

-of Date 4.4 Approvals and Notifications

[1]

OBTAIN permission of the Preoperational Startup Manager to start the test.

Date Preoperational Startup Manager Signature

[2]

OBTAIN the Unit 2 Supervisor's (US/SRO) or Shift Manager's (SM) authorization.

Date U2 US/SRO/SM Signature

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 20 of 117 Data Package: Page

-of Date 5.0 ACCEPTANCE CRITERIA

[1]

The Local and Control Room Indicating and Recording Devices of each radiation monitor listed exhibits an increased deflection above background when the associated radiation detector is exposed to an appropriate check source.

[1.1]

2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT LOOP A.

2-RM-90-2, ACCIDENT RAD MON OUTLET PERSONNEL ENT (Step 6.1[29.2])

B.

2-RR-90-1P003, AREA RADIATION MONITORS, recorder point 3 (Step 6.1[29.3])

C.

2-RI-90-2B, PERSONNEL AIRLOCK AREA RADIATION (Step 6.1[29.3])

[1.2]

2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON LOOP A.

2-RM-90-59, UP COMPARTMENT REAC BLDG AREA MON (Step 6.2[28.2])

B.

2-RR-90-1P001, AREA RADIATION MONITORS, recorder point 1 (Step 6.2[28.3])

C.

2-RI-90-59B, UP COMPARTMENT REAC BLDG AREA MON (Step 6.2[28.3])

[1.3]

2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON LOOP A.

2-RM-90-60, UP COMPARTMENT REAC BLDG AREA MON (Step 6.3[28.2])

B.

2-RR-90-1 P002, AREA RADIATION MONITORS, recorder point 2 (Step 6.3[28.3])

C.

2-RI-90-60B, UP COMPARTMENT REAC BLDG AREA MON (Step 6.3[28.3])

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 21 of 117 Data Package: Page

-of Date 5.0 ACCEPTANCE CRITERIA (continued)

[1.4]

2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON LOOP A.

2-RM-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (Step 6.4[28.2])

B.

2-RR-90-1 P004, AREA RADIATION MONITORS, recorder point 4 (Step 6.4[28.3])

C.

2-RI-90-61 B, LWR COMPARTMENT INSTR RM-AREA MON (Step 6.4[28.3])

[1.5]

2-LPR-90-271, CNTMT POST ACC HIGH RAD 2-RM-90-271, UPR INS CNTMT POST ACD AREA MON (Step 6.5[26.2])

[1.6]

2-LPR-90-272, CNTMT POST ACC HIGH RAD 2-RM-90-272, UPR INS CNTMT POST ACD AREA MON (Step 6.6[26.2])

[1.7]

2-LPR-90-273, CNTMT POST ACC HIGH RAD 2-RM-90-273, LWR INS CNTMT POST ACD AREA MON (Step 6.7[26.2])

[1.8]

2-LPR-90-274, CNTMT POST ACC HIGH RAD 2-RM-90-274, LWR INS CNTMT POST ACD AREA MON (Step 6.8[26.2])

[2]

Control Room and Local Annunciations and Alarms function properly:

[2.1]

2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT A.

Control Room Annunciations and Alarms:

2-RM-90-2 (Steps 6.1[7], 6.1[11], 6.1[13], 6.1[18], 6.1[23],

6.1[27.1]C, 6.1[27.1]D, 6.1[27.2]C, 6.1[27.2]D, 6.1[28.2]B, 6.1[28.2]C, 6.1[28.3]B, 6.1[28.3]C, 6.1[29.4], 6.1[30]A)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 22 of 117 Data Package: Page

-of Date 5.0 ACCEPTANCE CRITERIA (continued)

O-XA-55-12D Window 193-B, 2-RR-90-1 AREA RAD HI (Steps 6.1[21]A, 6.1[24]A, 6.1[27.1]E, 6.1[27.2]E, 6.1[28.2]D, 6.1[28.3]D)

Event Display Monitor Displays 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-2)

(Steps 6.1[21]B, 6.1[24]B, 6.1[27.1]F, 6.1[27.2]F, 6.1[28.2]E, 6.1[28.3]E)

O-XA-55-12D Window 193-E, 2-RR-90-1 AREA MONITORS INSTR MALF (Steps 6.1[9]A, 6.1[14]A, 6.1[19]A, 6.1[21]C, 6.1[24]C, 6.1[30]B)

Event Display Monitor Displays 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (Steps 6.1[9]B, 6.1[14]B, 6.1[19]B, 6.1[21]D, 6.1[24]D, 6.1[30]C)

B.

Local Alarms 2-RI-90-B2, PERSONNEL AIRLOCK AREA RADIATION (Steps 6.1[8], 6.1[27.1]A, 6.1[27.1]B, 6.1 [27.2]A, 6.1 [27.2]B, 6.1 [27.3], 6.1 [28.2]A, 6.1[28.3]A)

[2.2]

2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON A.

Control Room Annunciations and Alarms:

2-RM-90-59 (Steps 6.2[6], 6.2[10], 6.2[12], 6.2[17], 6.2[22],

6.2[26.1]C, 6.2[26:1]D, 6.2[26.2]C, 6.2[26.2]D, 6.2[27.2]B, 6.2[27.2]C, 6.2[27.3]B, 6.2[27.3]C, 6.2[28.4], 6.2[29]A)

Data Package: Page

-of Date 5.0 ACCEPTANCE CRITERIA (continued)

O-XA-55-12D Window 193-B, 2-RR-90-1 AREA RAD HI (Steps 6.2[20]A, 6.2[23]A, 6.2[26.1]E, 6.2[26.2]E, 6.2[27.2]D, 6.2[27.3]D)

Event Display Monitor Displays 193-B ACCESS HATCH AREA RAD HI (2-RM-90-59)

(Steps 6.2[20]B, 6.2[231B, 6.2[26.1]F, 6.2[26.2]F, 6.2[27.2]E, 6.2[27.3]E) 0-XA-55-12D Window 193-E, 2-RR-90-1 AREA MONITORS INSTR MALF (Steps 6.2[8]A, 6.2[13]A, 6.2[18]A, 6.2[20]C, 6.2[23]C, 6.2[29]B)

Event Display Monitor Displays 193-E ACCESS HATCH AREA MON INSTR MALF (2-RM-90-59)

(Steps 6.2[8]B, 6.2[13]B, 6.2[18]B, 6.2[20]D, 6.2[23]D, 6.2[29]C)

B.

Local Alarms 2-RI-90-59B, UP COMPARTMENT REAC BLDG AREA MON (Steps 6.2[7], 6.2[26.1]A, 6.2[26. 1]B, 6.2[26.2]A, 6.2126.2]B, 6.2[26.3], 6.2[27.2]A, 6.2[27.3]A)

[2.3]

2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON A.

Control Room Annunciations and Alarms:

2-RM-90-60 (Steps 6.3[6], 6.3[10], 6.3(12], 6.3[17], 6.3(22],

6.3[26.1]C, 6.3[26.1]D, 6.3[26.2]C, 6.3[26.2]D, 6.3[27.2]B, 6.3[27.2]C, 6.3[27.3]B, 6.3[27.3]C, 6.3[28.4], 6.3[29]A) 0-XA-55-12D Window 193-B, 2-RR-90-1 AREA RAD HI (Steps 6.3[20]A, 6.3[23]A, 6.3[26. lIE, 6.3[26.2]E, 6.3[27.2]D, 6.3[27.3]D)

Data Package: Page

-of Date 5.0 ACCEPTANCE CRITERIA (continued)

Event Display Monitor Displays 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-60)

(Steps 6.3[20]B, 6.3(23]B, 6.3[26. 1]F, 6.3[26.2]F, 6.3[27.2]E, 6.3[27.3]E) 0-XA-55-12D Window 193-E, 2-RR-90-1 AREA MONITORS INSTR MALF (Steps 6.3[8]A, 6.3[13]A, 6.3[18]A, 6.3[20]C,

  • 6.3[23]C, 6.3[29]B)

Event Display Monitor Displays 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-60)

(Steps 6.3[8]B, 6.3[13]B, 6.3[18]B, 6.3[20]D, 6.3[23]D, 6.3129]C)

B.

Local Alarms:

2-RI-90-60B, UP COMPARTMENT REAC BLDG AREA MON (Steps 6.3[7], 6.3[26.1]A, 6.3[26.1]B, 6.3[26.2]A, 6.3[26.2]B, 6.3[26.3], 6.3[27.2]A, 6.3[27.3]A)

[2.4]

2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON A.

Control Room Annunciations and Alarms:

2-RM-90-61 (Steps 6.4[6], 6.4[10], 6.4[12], 6.4(17], 6.4[22],

6.4[26.1]C, 6.4[26.1 ID, 6.4[26.2]C, 6.4[26.2]D, 6.4[27.2]B, 6.4[27.2]C, 6.4[27.3]B, 6.4[27.3]C, 6.4[28.4], 6.4[29]A) 0-XA-55-12D Window 193-B, 2-RR-90-1 AREA RAD HI (Steps 6.4[20]A, 6.4[23]A, 6.4[26.1]E, 6.4[26.2]E, 6.4[27.2]D, 6.4[27.3]D)

Event Display Monitor Displays 193-B CONT INSTR RM AREA RAD HI (2-RM-90-61)

(Steps 6.4[20]B, 6.4[23]B, 6.4[26.1]F, 6.4126.2]F, 6.4[27.2]E, 6.4[27.3]E)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev.0000 Page 25 of 117 Data Package: Page of Date 5.0 ACCEPTANCE CRITERIA (continued) 0-XA-55-12D Window 193-E, 2-RR-90-1 AREA MONITORS INSTR MALF (Steps 6.4[8]A, 6.4[13]A, 6.4[18]A, 6.4[20]C, 6.4[23]C, 6.4[29]B)

Event Display Monitor Displays 193-E INCORE INSTR ROOM AREA MON INSTR MALF (2-RM-90-61)

(Steps 6.4[8]B, 6.4113]B, 6.4[18]B, 6.4[20]D, 6.4[23]D, 6.4[29]C)

B.

Local Alarms:

2-RI-90-61B, LOWER COMPARTMENT INSTR RM-AREA MON (Steps 6.4[7], 6.4[26.1 ]A, 6.2[26.1 ]B, 6.4126.2]A, 6.4[26.2]B, 6.4[26.3], 6.4[27.2]A, 6.4[27.3]A)

[2.5]

2-LPR-90-271, CNTMT POST ACC HIGH RAD A.

Control Room Annunciations and Alarms:

2-RM-90-271 (Steps 6.5[5], 6.5[8], 6.5[10], 6.5[15], 6.5[20],

6.5[24.1]A, 6.5[24.1]B, 6.5[24.2]A, 6.5[24.2]B, 6.5[25.2]A, 6.5[25.2]B, 6.5[25.3]A, 6.5[25.3]B, 6.5[26.3], 6.5[27]A) 2-XA-55-30 Window 256A, UPPER CNTMNT RE-271/272 RAD HI (Steps 6.5[18]A, 6.5[21]A, 6.5[24.1]C, 6.5[24.2]C, 6.6[25.2]C, 6.5[25.3]C) 0-XA-55-12D Window 191-E, PAS MON PNL 2M30/31 INSTR MALF (Steps 6.5[6]A, 6.5[11]A, 6.5[16]A, 6.5[18]B, 6.5[21]B, 6.5[27]B)

Event Display Monitor Displays 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-271 -A)

(Steps 6.5[6]B, 6.5[11]B, 6.5[16]B, 6.5[18]C, 6.5[21]C, 6.5[27]C)

Data Package: Page

-of Date 5.0 ACCEPTANCE CRITERIA (continued)

[2.6]

2-LPR-90-272, CNTMT POST ACC HIGH RAD A.

Control Room Annunciation and Alarms:

a 2-RM-90-272 (Steps 6.6[5], 6.6[8], 6.6[10], 6.6[15], 6.6[20],

6.6[24. 1]A, 6.6[24. 1]B, 6.6[24.2]A, 6.6124.2]B, 6.6125.2]A, 6.6[25.2]B, 6.6[25.3]A, 6.6[25.3]B, 6.6[26.3], 6.6[27]A) 2-XA-55-30 Window 256A, UPPER CNTMNT RE-271/272 RAD HI (Steps 6.6[18]A, 6.6[21 ]A, 6.6[24.1 ]C, 6.6[24.2]C, 6.6125.2]C, 6.6125.3]C) 0-XA-55-12D Window 191-E, PAS MON PNL 2M30/31 INSTR MALF (Steps 6.6[6]A, 6.6[l 1 ]A, 6.6116]A, 6.6(18]B, 6.6121]B, 6.6[27]B) 0 Event Display Monitor Displays 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-272-B)

(Steps 6.6[6]B, 6.6(111]B, 6.6116]B, 6.6[18]C, 6.6[21]C, 6.6[27]C)

[2.7]

2-LPR-90-273, CNTMT POST ACC HIGH RAD A.

Control Room Annunciations and Alarms:

2-RM-90-273 (Steps 6.715], 6.718], 6.7110), 6.7115], 6.7[20],

6.7(24.1 ]A, 6.7[24.1]B, 6.7124.2]A, 6.6(24.2]B, 6.7[25.2]A, 6.7[25.2]B, 6.7[25.3]A, 6.7[25.3]B, 6.6[26.3], 6.7[27]A) 2-XA-55-30 Window 256B, LOWER CNTMNT RE-273/274 RAD HI (Steps 6.7[18]A, 6.7[21]A, 6.7124.1]C, 6.7(24.2]C, 6.7[25.2]C, 6.7125.3]C)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 27 of 117 Data Package: Page of Date 5.0 ACCEPTANCE CRITERIA (continued)

O-XA-55-12D Window 191-E, PAS MON PNL 2M30/31 INSTR MALF (Steps 6.7[6]A, 6.7[11]A, 6.7[16]A, 6.7[18]B, 6.7[21]B, 6.7[27]B)

Event Display Monitor Displays 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-273-A)

(Steps 6.7[6]B, 6.7[11 ]B, 6.7[16]B, 6.7[18]C, 6.7[21]C, 6.7[27]C)

[2.8]

2-LPR-90-274, CNTMT POST ACC HIGH RAD A.

Control Room Annunciations and Alarms:

0 2-RM-90-274 (Steps 6.8[5], 6.818], 6.8[10], 6.8[15], 6.8[20],

6.8[24.1 ]A, 6.8[24..1]B, 6.8[24.2]A, 6.8[24.2]B, 6.8[25.2]A, 6.8[25.2]B, 6.8[25.3]A, 6.8[25.3]B, 6.8[26.3], 6.8[27]A) 2-XA-55-30 Window 256B, LOWER CNTMNT RE-273/274 RAD HI (Steps 6.8[18]A, 6.8[21]A, 6.8[24. 1]C, 6.8[24.2]C, 6.8[25.2]C, 6.8[25.3]C) 0 0-XA-55-12D Window 191-E, PAS MON PNL 2M30/31 INSTR MALF (Steps 6.8[6]A, 6.8[l1]A, 6.8[16]A, 6.8[18]B, 6.8[21]B, 6.8[27]B)

Event Display Monitor Displays 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-274-B)

(Steps 6.8[6]B, 6.8[11 ]B, 6.8[16]B, 6.8[18]C, 6.8[21]C, 6.8[27]C)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 28 of 117 5.0 Data Package: Page

-of ACCEPTANCE CRITERIA (continued)

Date

[3]

Ratemeter is capable of "being reset" after transition from any alarm condition to normal status.

[3.1]

2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (Step 6.1[28.3])

[3.2]

2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (Step 6.2[27.3])

[3.3]

2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (Step 6.3[27.3])

[3.4]

2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (Step 6.4[27.3])

[3.5]

2-LPR-90-271, CNTMT POST ACC HIGH RAD (Step 6.5[25.3])

[3.6]

2-LPR-90-272, CNTMT POST ACC HIGH RAD (Step 6.6[25.3])

[3.7]

2-LPR-90-273, CNTMT POST ACC HIGH RAD (Step 6.7[25.3])

[3.8]

2-LPR-90-274, CNTMT POST ACC HIGH RAD (Step 6.8[25.3])

[4]

Reset function of ratemeter is inoperable during alarm conditions.

[4.1]

2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (Step 6.1[27.2])

[4.2]

2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (Step 6.2[26.2])

[4.3]

2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (Step 6.3[26.2])

[4.4]

2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (Step 6.4[26.2])

[4.5]

2-LPR-90-271, CNTMT POST ACC HIGH RAD (Step 6.5[24.2])

[4.6]

2-LPR-90-272, CNTMT POST ACC HIGH RAD (Step 6.6[24.2])

[4.7]

2-LPR-90-273, CNTMT POST ACC HIGH RAD (Step 6.7[24.2])

[4.8]

2-LPR-90-274, CNTMT POST ACC HIGH RAD (Step 6.8[24.2])

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 29 of 117 Data Package: Page of Date 5.0 ACCEPTANCE CRITERIA (continued)

[5]

Alarms in the control room due to a loss of signal (zero counts over a specified time).

[5.1]

2-LPR-90-2, ACCIDENT PAD MON OUTLT PERSONNEL ENT (Step 6.1[30])

[5.2]

2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (Step 6.2[29])

[5.3]

2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (Step 6.3[29])

[5.4]

2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (Step 6.4[29])

[5.5]

2-LPR-90-271, CNTMT POST ACC HIGH RAD (Step 6.5[27])

[5.6]

2-LPR-90-272, CNTMT POST ACC HIGH RAD (Step 6.6[27])

[5.7]

2-LPR-90-273, CNTMT POST ACC HIGH RAD (Step 6.7[27])

[5.8]

2-LPR-90-274, CNTMT POST ACC HIGH RAD (Step 6.8[27])

[6]

Alarms in the control room due to loss of power.

[6.1]

2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (Step 6.1[21])

[6.2]

2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (Step 6.2[20])

[6.3]

2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (Step 6.3[20])

[6.4]

2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (Step 6.4[20])

[6.5]

2-LPR-90-271, CNTMT POST ACC HIGH RAD (Step 6.5[18])

[6.6]

2-LPR-90-272, CNTMT POST ACC HIGH HAD (Step 6.6[18])

[6.7]

2-LPR-90-273, CNTMT POST ACC HIGH HAD (Step 6.7[18])

[6.8]

2-LPR-90-274, CNTMT POST ACC HIGH HAD (Step 6.8[18])

Data Package: Page

-of 5.0 ACCEPTANCE CRITERIA (continued)

Date

[7]

Monitors transmit measured radiation exposure rate data to the Plant Computer System for display in the Technical Support Center (TSC).

[7.1]

2-RE-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT LOOP (Step 6.1[29.3])

[7.2]

2-RE-90-59, UP COMPARTMENT REAC BLDG AREA MON (Step 6.2[28.3])

[7.3]

2-RE-90-60, UP COMPARTMENT REAC BLDG AREA MON (Step 6.3[28.3])

[7.4]

2-RE-90-271, UPR INS CNTMT POST ACD AREA (Step 6.5[23])

[7.5]

2-RE-90-272, UPR INS CNTMT POST ACD AREA (Step 6.6[23])

[7.6]

2-RE-90-273, LWR INS CNTMT POST ACD AREA (Step 6.7[23])

[7.7]

2-RE-90-274, LWR INS CNTMT POST ACD AREA (Step 6.8[23])

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 31 of 117 Data Package: Page

-of Date 6.0 PERFORMANCE NOTES

1)

The format, [XXX], [###], [XXX] is used throughout this test to identify a sequence of digital keypad entries on the referenced radiation monitor required to accomplish the specified action. The XXX above represents function acronym and "##.#" or "##"

represents a number keypad sequence with or without a decimal point.

2)

Subsection 6.1 is to be performed in parallel with 2-IMI-90.021, 18 Mo. Channel Cal (Source) of Accident Rad Mon Outlet Pers Entrance Loop.

3)

Subsections 6.2, 6.3, and 6.4 are to be performed in parallel with 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1000 Digital Ratemeters.

4)

Subsection 6.5 is to be performed in parallel with 2-SI-90-1, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-271.

5)

Subsection 6.6 is to be performed in parallel with 2-SI-90-2, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-272.

6)

Subsection 6.7 is to be performed in parallel with 2-SI-90-3, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-273.

7)

Subsection 6.8 is to be performed in parallel with 2-SI-90-4, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-274.

8)

Subsections 6.1 through 6.8 may be performed in any order.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 32 of 117 Data Package: Page

-of Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT NOTES

1)

Subsection 6.1 isto be performed in parallel with 2-IMI-90.021, 18 Mo. Channel Cal (Source) of Accident Rad Mon Outlet Pers Entrance Loop.

2)

For consistency with 2-IMI-90.021, steps in Subsection 6.1 may be performed in any order.

[1]

ENSURE the prerequisites listed in Section 4.0 for Subsection 6.1 have been completed.

[2]

ESTABLISH communications between the MCR Panel 0-M-12 and local indicator 2-RI-90-2B, PERSONNEL AIRLOCK AREA RADIATION (El. 757', Al 1Y).

[3]

ENSURE 2-BKR-278-MO12D, TO PNL 0-M-12 RAD MON RATEMETERS & RECORDERS, at 2-BD-278-MO07A PANEL 2-M-7 INSTRUMENT POWER A RACK, is in the ON position.

CV

[4]

ENSURE 2-BKR-242-0001 B, RAD PROC & AREA MON DIST PNL 2 FEEDER, at 2-BD-278-MO07B PANEL 2-M-7 INSTRUMENT POWER B RACK, is in the ON position.

CV NOTE Radiation Process and Area Monitor Power Distribution Panel 2-DPL-242-1 is located at El. 737', column A8S.

[5]

ENSURE 2-BKR-90-2B, Breaker 4 at the Radiation Process and Area Monitor Power Distribution Panel, 2-DPL-242-1, to 2-RI-90-2B, is in the ON position.

CV

Data Package: Page of__

Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (continued)

[6]

VERIFY 2-IMI-90.020 has lowered the setpoints of 2-RM-90-2.

[7]

VERIFY the ratemeter indications on 2-RM-90-2 (MCR Panel 0-M-12) are as follows: (Acc Crit)

A.

Green OPERATE light is ON.

B.

Yellow ALERT (1) light is OFF.

C.

Red HIGH (2) light is OFF.

[8]

VERIFY the indications at 2-RI-90-2B (El. 757', AllY) are as follows: (Acc Crit)

A.

Green POWER ON light is ON.

B.

Red HIGH ALARM light is OFF.

[9]

VERIFY the following:

A.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, is NOT in ALARM. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-2) is NORMAL (Blue). (Acc Crit)

I

  • CAUTION 100 Vdc is present when the front panel of the RM-1 000 ratemeter is open. Do not touch the exposed circuitry on the display.

[10]

LOOSEN the left side thumb screws on the front panel of 2-RM-90-2, AND OPEN the hinged door.

[11]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-2 to the CAL (down) position, AND VERIFY the green OPERATE light is OFF. (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 34 of 117 Data Package: Page of Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (continued)

[12]

CLOSE the hinged door on the front of 2-RM-90-2.

[13]

PRESS the [CLR] button on the front panel of 2-RM-90-2, AND VERIFY the green OPERATE light remains OFF. (Acc Crit)

[14]

VERIFY the following:

A.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-2) is in ALARM (Red). (Acc Crit)

[15]

OPEN the hinged door on the front of 2-RM-90-2.

[16]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-2 to the OPERATE (up) position.

[17]

CLOSE the hinged door on the front panel of 2-RM-90-2, AND TIGHTEN the left side thumb screws.

[18]

PRESS the [CLR] button on the front panel of 2-RM-90-2, AND VERIFY the green OPERATE is ON. (Acc Crit)

[19]

VERIFY the following:

A.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, CLEARS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-2) is in NORMAL (Blue). (Acc Crit)

Data Package: Page

-of Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (continued)

[20]

REMOVE fuse F1 from 2-PX-90-2 ACD RAD MON OUTLET PERSONNEL ENT PWR SPLY located inside MCR Panel 0-M-1 2.

Cv

[21]

VERIFY the following: (Acc Crit)

A.

0-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, ALARMS.

(Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-2) is in ALARM (Red). (Acc Crit)

C.

0-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

D.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-2) is in ALARM (Red). (Acc Crit)

[22]

INSTALL fuse F1 in 2-PX-90-2 ACD RAD MON OUTLET PERSONNEL ENT PWR SPLY located inside MCR Panel 0-M-12.

CV

[23]

PRESS the [CLR] button on the front panel of 2-RM-90-2, AND VERIFY the green OPERATE is ON. (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 36 of 117 Data Package: Page

-of Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (continued)

[24]

VERIFY the following:

A.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, CLEARS.

(Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-2) is in NORMAL (Blue). (Acc Crit)

C.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, CLEARS. (Acc Crit)

D.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-2) is in NORMAL (Blue). (Acc Crit)

[25]

RECORD the following ambient dose rate indications:

Device Indication Initials/date 2-RM-90-2 PERSONNEL AIRLOCK AREA RADIATION (MCR Panel 0-M-1 2)

R/HR 2-RR-90-1 P003 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-2B ACCIDENT RAD MON OUTLET PERSONNEL ENT (757-A11X)

RJHR R9015A ICS Point for 2-RE-90-2 MR/HR

Data Package: Page of Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (continued)

ALARA The radioactive source hung by 2-IMI-90.021, 18 Mo. Channel Cal (Source) of Accident Rad Mon Outlet Pers Entrance Loop, has a high dose potential. Actions to reduce dose must be taken during performance of steps 6.1[26] through 6.1[27.3].

NOTE Steps 6.1126] through 6.1[27.3] are to be performed after 2-IMI-90.021, 18 Mo. Channel Cal (Source) of Accident Rad Mon Outlet Pers Entrance Loop, has hung the calibration source.

[26]

RECORD the following source response indications:

Device Indication Initials/date 2-RM-90-2 PERSONNEL AIRLOCK AREA RADIATION (MCR Panel 0-M-1 2)

R/HR 2-RR-90-1 P003 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-2B ACCIDENT RAD MON OUTLET PERSONNEL ENT (El. 757',

AllY)

R/HR R9015A ICS Point for 2-RE-90-2 MR/HR

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 38 of 117 Data Package: Page of Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (continued)

[27]

PERFORM the following radiation response verifications:

[27.1]

VERIFY the following local and main control room alarms actuated.

A.

2-RI-90-2B red HIGH ALARM light is ON.

(Acc Crit)

B.

2-RI-90-2B audible alarm is ON. (Acc Crit)

C.

2-RM-90-2 yellow ALERT (1) light is ON. (Acc Crit)

D.

2-RM-90-2 red HIGH (2) light is ON. (Acc Crit)

E.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, ALARMS. (Acc Crit)

F.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-2) is in ALARM (Red). (Acc Crit)

[27.2]

PRESS the [CLR] button on 2-RM-90-2, AND VERIFY the following: (Acc Crit)

A.

2-RI-90-2B red HIGH ALARM light is ON.

(Acc Crit)

B.

2-RI-90-2B audible alarm is ON. (Acc Crit)

C.

2-RM-90-2 yellow ALERT (1) light is ON. (Acc Crit)

D. 2-RM-90-2 red HIGH (2) light is ON. (Acc Crit)

E.

O-XA-55-12D/1 93-B, 2-RR-90-1 AREA RAD HI, is in ALARM. (Acc Crit)

F.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-2) is in ALARM (Red). (Acc Crit)

Data Package: Page

-of Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (continued)

[27.3]

PRESS the alarm acknowledge button on 2-RI-90-2B, AND VERIFY the audible alarm is OFF. (Acc Crit)

NOTE The remainder of Subsection 6.1 is to be performed after 2-IMI-90.021, 18 Mo. Channel Cal (Source) of Accident Rad Mon Outlet Pers Entrance Loop, has removed the calibration source from 2-RE-90-2.

[28]

PERFORM the following radiation response verifications:

[28.1]

RECORD the following ambient dose rate indications, AND VERIFY ambient dose rates are similar to those recorded in step 6.1[25].

Device Indication Initials/date 2-RM-90-2 PERSONNEL AIRLOCK AREA RADIATION (MCR Panel 0-M-12)

R/HR 2-RR-90-1 P003 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-2B ACCIDENT RAD MON OUTLET PERSONNEL ENT (El. 757',

AllY)

R/HR R9015A ICS Point for 2-RE-90-2 MR/HR

Data Package: Page

-of Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (continued)

[28.2]

VERIFY the local and main control room alarms and annunciators actuate as follows:

A.

2-RI-90-2B red HIGH ALARM light is ON.

(Acc Crit)

B.

2-RM-90-2 yellow ALERT (1) light is ON. (Acc Crit)

C.

2-RM-90-2 red HIGH (2) light is ON. (Acc Crit)

D.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, ALARMS. (Acc Crit)

E.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-2) is in ALARM (Red). (Acc Crit)

[28.3]

PRESS the [CLR] button on 2-RM-90-2, AND VERIFY the following: (Acc Crit)

A.

2-RI-90-2B red HIGH ALARM light is OFF.

(Acc Crit)

B.

2-RM-90-2 yellow ALERT (1) light is OFF.

(Acc Crit)

C.

2-RM-90-2 red HIGH (2) light is OFF. (Acc Crit)

D.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, CLEARS. (Acc Crit)

E.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-2) is in NORMAL (Blue). (Acc Crit)

[28.4]

COMPARE the source response recorded in step 6.1[26] to the ambient reading recorded in step 6.1[25]

for each device, AND VERIFY each device exhibited an increased deflection above background once exposed to the calibration source.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 41 of 117 Data Package: Page of Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (continued)

NOTE When the RM-1 000 is in the OPERATE mode the checksource function will clear after one minute so recording of response values needs to be completed within that time period or the sequence will have to be repeated.

[29]

PERFORM the following Check Source response verifications.

[29.1]

PRESS the [FUN], [2], [ENT] buttons on 2-RM-90-2 PERSONNEL AIRLOCK AREA RADIATION (MCR Panel 0-M-12) to actuate the CHKSRC function.

NOTE The RM-1000 meter responds to a checksource test by displaying the ambient reading on the left side of the scale and the checksource response on the right side of the scale with the checksource response value indicated at the bottom along with the function description "CHKSRC".

[29.2]

VERFIY the indication on 2-RM-90-2 shows a two level response with the left indication lower than the right indication. (Acc Crit)

[29.3]

RECORD the following indications, AND VERIFY each device exhibits an increased deflection above the ambient dose rates recorded in step 6.1[28.1].

(Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 42 of 117 Data Package: Page

-of Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (continued)

Device Indication Initials/date 2-RM-90-2 PERSONNEL AIRLOCK AREA RADIATION (MCR Panel 0-M-12)

R/HR 2-RR-90-1 P003 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R-HR 2-RI-90-2B ACCIDENT RAD MON OUTLET PERSONNEL ENT (El. 757',

Al1Y)

RPHR R9015A ICS Point for 2-RE-90-2 MR/HR

[29.4]

VERIFY the main control room alarms as follows:

(Acc Crit)

A.

2-RM-90-2 yellow ALERT (1) light is OFF.

B.

2-RM-90-2 red HIGH (2) light is OFF.

[29.5]

WHEN at least one minute has elapsed from the time the CHKSRC function actuated, THEN VERIFY the following devices indicate dose rates similar to those recorded in step 6.1128.1].

A.

2-RM-90-2 PERSONNEL AIRLOCK AREA RADIATION (MCR Panel 0-M-12).

B. 2-RR-90-1 P003 AREA RADIATION MONITORS (MCR Panel 0-M-12).

C.

2-RI-90-2B ACCIDENT RAD MON OUTLET PERSONNEL ENT (El. 757', Al1Y).

D.

R9015A ICS Point for 2-RE-90-2.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 43 of 117 Data Package: Page of Date 6.1 2-LPR-90-2, ACCIDENT RAD MON OUTLT PERSONNEL ENT (continued)

[30]

WHEN the Loss of Counts Setup portion of 2-IMI-90.021 has been completed,

THEN, VERIFY the following (actions should occur within approximately two minutes after 2-IMI-90.021 has set the Discriminator Voltage to 1 OVdc): (Acc Crit)

A.

The green OPERATE light is OFF (On the front panel of 2-RM-90-2). (Acc Crit)

B.

0-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-2) is in ALARM (Red). (Acc Crit)

Data Package: Page

-of Date 6.2 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON NOTES

1)

Subsection 6.2 is to be performed in parallel with 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1 000 Digital Ratemeters

2)

For consistency with 2-IMI-90.020, steps in Subsection 6.2 may be performed in any order.

[1]

ENSURE the prerequisites listed in Section 4.0 for Subsection 6.2 have been completed.

[2]

ESTABLISH communications between the MCR Panel 0-M-12 and local indicator 2-RI-90-59B, UP COMPARTMENT REAC BLDG-AREA MON (El. 756, Az. 3100).

[3]

ENSURE 2-BKR-278-MO12D, TO PNL 0-M-12 RAD MON RATEMETERS & RECORDERS, at 2-BD-278-MO07A PANEL 2-M-7 INSTRUMENT POWER A RACK, is in the ON position.

CV

[4]

ENSURE 2-BKR-242-0001 B, RAD PROC & AREA MON DIST PNL 2 FEEDER, at 2-BD-278-MO07B PANEL 2-M-7 INSTRUMENT POWER B RACK, is in the ON position.

CV NOTE Radiation Process and Area Monitor Power Distribution Panel 2-DPL-242-1 is located at El. 737', column ASS.

[5]

ENSURE 2-BKR-90-59B, Breaker 11 at the Radiation Process and Area Monitor Power Distribution Panel, 2-DPL-242-1, to 2-RI-90-59B, is in the ON position.

CV

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 45 of 117 6.2 Data Package: Page

.of Date 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (continued)

[6]

VERIFY the ratemeter indications on 2-RM-90-59 (MCR Panel 0-M-12) are as follows: (Acc Crit)

A.

Green OPERATE light is ON.

B.

Yellow ALERT (1) light is OFF.

C.

Red HIGH (2) light is OFF.

[7]

VERIFY the indications at 2-RI-90-59B are as follows:

(Acc Crit)

A.

Green POWER ON light is ON.

B.

Red HIGH ALARM light is OFF.

[8]

VERIFY the following:

A.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, is NOT in ALARM. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E ACCESS HATCH AREA MON INSTR MALF (2-RM-90-59) is in NORMAL (Blue). (Acc Crit)

CAUTION 100 Vdc is present when the front panel of the RM-1000 ratemeter is open. Donottouch the exposed circuitry on the display.

[9]

LOOSEN the left side thumb screws on the front panel of 2-RM-90-59, AND OPEN the hinged door.

[10]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-59 to the CAL (down) position, AND VERIFY the green OPERATE light is OFF. (Acc Crit)

[11]

CLOSE the hinged door on the front of 2-RM-90-59.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 46 of 117 Data Package: Page

-of Date 6.2 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (continued)

[12]

PRESS the [CLR] button on the front panel of 2-RM-90-59, AND VERIFY the green OPERATE light remains OFF. (Acc Crit)

[13]

VERIFY the following:

A.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E ACCESS HATCH AREA MON INSTR MALF (2-RM-90-59) is in ALARM (Red). (Acc Crit)

[14]

OPEN the hinged door on the front of 2-RM-90-59.

[15]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-59 to the OPERATE (up) position.

[16]

CLOSE the hinged door on the front panel of 2-RM-90-59, AND TIGHTEN the left side thumb screws.

[17]

PRESS the [CLR] button on the front panel of 2-RM-90-59, AND VERIFY the green OPERATE is ON. (Acc Crit)

[18]

VERIFY the following:

A.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, CLEARS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E ACCESS HATCH AREA MON INSTR MALF (2-RM-90-59) is in NORMAL (Blue). (Acc Crit)

[19]

REMOVE fuse F1 from 2-PX-90-59 UP COMPARTMENT REAC BLDG-AREA MON PWR SPLY located inside MCR Panel 0-M-12.

CV

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 47 of 117 Data Package: Page of Date 6.2 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (continued)

[20]

VERIFY the following: (Acc Crit)

A.

0-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, ALARMS.

(Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193--B ACCESS HATCH AREA RAD HI (2-RM-90-59) is in ALARM (Red).

(Acc Crit)

C.

0-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

D.

Unit 2 Event Display Monitor indicates 193-E ACCESS HATCH AREA MON INSTR MALF (2-RM-90-59) is in ALARM (Red). (Acc Crit)

[21]

INSTALL fuse F1 in 2-PX-90-59 UP COMPARTMENT REAC BLDG-AREA MON PWR SPLY located inside MCR Panel 0-M-1 2.

CV

[22]

PRESS the [CLR] button on the front panel of 2-RM-90-59, AND VERIFY the green OPERATE is ON. (Acc Crit)

[23]

VERIFY the following:

A.

0-XA-55-12D/1 93-B, 2-RR-90-1 AREA RAD HI, CLEARS.

(Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-B ACCESS HATCH AREA RAD HI (2-RM-90-59) is in NORMAL (Blue). (Acc Crit)

C.

0-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, CLEARS. (Acc Crit)

D.

Unit 2 Event Display Monitor indicates 193-E ACCESS HATCH AREA MON INSTR MALF (2-RE-90-59) is in NORMAL (Blue). (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 48 of 117 Data Package: Page

-of 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (continued)

Date 6.2

[24]

RECORD the following ambient dose rate indications:

Device Indication Initials/date 2-RM-90-59 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12)

R/HR 2-RR-90-1 P001 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-59B UP COMPARTMENT REAC BLDG-AREA MON (El. 756',

Az. 3100)

RJHR R9016A ICS Point for 2-RE-90-59 MR/HR

0 WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 49 of 117 Data Package: Page of Date 6.2 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (continued)

ALARA The radioactive source hung by 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1 000 Digital Ratemeters, has a high dose potential. Actions to reduce dose must be taken during performance of steps 6.2[25] through 6.2[26.3].

II "1

I I

I I

I1 i

NOTE Steps 6.2[25] through 6.2[26.3] are to be performed after 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1 000 Digital Ratemeters, has hung the calibration source in 2-RE-90-59.

[25]

RECORD the following source response indications:

Device Indication Initials/date 2-RM-90-59 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12)

R/HR 2-RR-90-1P001 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-59B UP COMPARTMENT REAC BLDG-AREA MON (El. 756',

Az. 3100)

RPHR R9016A ICS Point for 2-RE-90-59 MR/HR

Data Package: Page

-of Date 6.2 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (continued)

[26]

PERFORM the following radiation response verifications:

[26.1]

VERIFY the following local and main control room alarms actuated.

A.

2-RI-90-59B red HIGH ALARM light is ON.

(Acc Crit)

B. 2-RI-90-59B audible alarm is ON. (Acc Crit)

C.

2-RM-90-59 yellow ALERT (1) light is ON.

(Acc Crit)

D. 2-RM-90-59 red HIGH (2) light is ON. (Acc Crit)

E.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, ALARMS. (Acc Crit)

F.

Unit 2 Event Display Monitor indicates 193-B ACCESS HATCH AREA RAD HI (2-RM-90-59) is in ALARM (Red). (Acc Crit)

[26.2]

PRESS the [CLR] button on 2-RM-90-59, AND VERIFY the following: (Acc Crit)

A.

2-RI-90-59B red HIGH ALARM light is ON.

(Acc Crit)

B.

2-RI-90-59B audible alarm is ON. (Acc Crit)

C.

2-RM-90-59 yellow ALERT (1) light is ON.

(Acc Crit)

D. 2-RM-90-59 red HIGH (2) light is ON. (Acc Crit)

E.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, is in ALARM. (Acc Crit)

F.

Unit 2 Event Display Monitor indicates 193-B ACCESS HATCH AREA RAD HI (2-RM-90-59) is in ALARM (Red). (Acc Crit)

Data Package: Page of Date 6.2 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (continued)

[26.3]

PRESS the alarm acknowledge button on 2-RI-90-59B, AND VERIFY the audible alarm is OFF. (Acc Crit)

NOTE The remainder of subsection 6.2 is to be performed after 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1 000 Digital Ratemeters, has removed the calibration source from 2-RE-90-59.

[27]

PERFORM the following radiation response verifications:

[27.1]

RECORD the following ambient dose rate indications, AND VERIFY ambient dose rates are similar to those recorded in step 6.2[24].

Device Indication Initials/date 2-RM-90-59 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12)

R/HR 2-RR-90-1 P001 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-59B UP COMPARTMENT REAC BLDG-AREA MON (El. 756', Az. 3100)

R/HR R9016A ICS Point for 2-RE-90-59 MRPHR

Data Package: Page

_of Date 6.2 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (continued)

[27.2]

VERIFY the local and main control room alarms and annunciators actuate as follows:

A.

2-RI-90-59B red HIGH ALARM light is ON.

(Acc Crit)

B.

2-RM-90-59 yellow ALERT (1) light is ON.

(Acc Crit)

C.

2-RM-90-59 red HIGH (2) light is ON. (Acc Crit)

D.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, ALARMS. (Acc Crit)

E.

Unit 2 Event Display Monitor indicates 193-B ACCESS HATCH AREA RAD HI (2-RM-90-59) is in ALARM (Red). (Acc Crit)

[27.3]

PRESS the [CLR] button on 2-RM-90-59, AND VERIFY the following: (Acc Crit)

A.

2-RI-90-59B red HIGH ALARM light is OFF.

(Acc Crit)

B.

2-RM-90-59 yellow ALERT (1) light is OFF.

(Acc Crit)

C.

2-RM-90-59 red HIGH (2) light is OFF. (Acc Crit)

D.

O-XA-55-12D/193-B, 2-RR-90-1 2 AREA RAD HI, CLEARS. (Acc Crit)

E.

Unit 2 Event Display Monitor indicates 193-B ACCESS HATCH AREA RAD HI (2-RM-90-59) is in NORMAL (Blue). (Acc Crit)

[27.4]

COMPARE the source response recorded in step 6.2[25] to the ambient reading recorded in step 6.2[24]

for each device, AND VERIFY each device exhibited an increased deflection above background once exposed to the calibration source.

. Data Package: Page of Date 6.2 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (continued)

NOTE When the RM-1 000 is in the OPERATE mode the checksource function will clear after one minute so recording of response values needs to be completed within that time period or the sequence will have to be repeated.

[28]

PERFORM the following Check Source response verifications.

[28.1]

PRESS the [FUN], [2], [ENT] buttons on 2-RM-90-59 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12) to actuate the CHKSRC function.

NOTE The RM-1000 meter responds to a checksource test by displaying the ambient reading on the left side of the scale and the checksource response on the right side of the scale with the checksource response value indicated at the bottom along with the function description "CHKSRC".

[28.2]

VERFIY the indication on 2-RM-90-59 shows a two level response with the left indication lower than the right indication. (Acc Crit)

[28.3]

RECORD the following indications, AND VERIFY each device exhibited an increased deflection above the ambient dose rates recorded in step 6.2127.1].

(Acc Crit)

Device Indication Initials/date 2-RM-90-59 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12)

R/HR 2-RR-90-1 P001 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-59B UP COMPARTMENT REAC BLDG-AREA MON (El. 756', Az. 310-)

R/HR R9016A ICS Point for 2-RE-90-59 MR/HR

Data Package: Page of Date 6.2 2-LPR-90-59, UP COMPARTMENT REAC BLDG AREA MON (continued)

[28.4]

VERIFY the main control room alarms as follows:

(Acc Crit)

A.

2-RM-90-59 yellow ALERT (1) light is OFF.

B.

2-RM-90-59 red HIGH (2) light is OFF.

[28.5]

WHEN at least one minute has elapsed from the time the CHKSRC function actuated, THEN VERIFY the following devices indicate dose rates similar to those recorded in step 6.2[27.1].

A.

2-RM-90-59 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12).

B. 2-RR-90-1PO01 AREA RADIATION MONITORS (MCR Panel 0-M-12).

C.

2-RI-90-59B UP COMPARTMENT REAC BLDG-AREA MON (El. 756', Az. 3100).

D.

R9016A ICS Point for 2-RE-90-59.

[29]

WHEN the Loss of Counts Setup portion of 2-IMI-90.020 has been completed,

THEN, VERIFY the following (actions should occur within approximately two minutes after 2-IMI-90.020 has set the Discriminator Voltage to 1OVdc): (Acc Crit)

A.

The green OPERATE light is OFF (On the front panel of 2-RM-90-59). (Acc Crit)

B. 0-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 193-E ACCESS HATCH AREA MON INSTR MALF (2-RM-90-59) is in ALARM (Red). (Acc Crit)

Data Package: Page

-of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON NOTES

1)

Subsection 6.3 is to be performed in parallel with 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1 000 Digital Ratemeters.

2)

For consistency with 2-IMI-90.020, steps in Subsection 6.3 may be performed in any order.

[1]

ENSURE the prerequisites listed in Section 4.0 for Subsection 6.3 have been completed.

[2]

ESTABLISH communications between the MCR Panel 0-M-12 and local indicator 2-RI-90-60B, UP COMPARTMENT REAC BLDG-AREA MON (El. 756', Az. 2250).

[3]

ENSURE 2-BKR-278-MO12D, TO PNL 0-M-12 RAD MON RATEMETERS & RECORDERS, at 2-BD-278-MO07A PANEL 2-M-7 INSTRUMENT POWER A RACK, is in the ON position.

Cv

[4]

ENSURE 2-BKR-242-0001 B, RAD PROC & AREA MON DIST PNL 2 FEEDER, at 2-BD-278-MO07B PANEL 2-M-7 INSTRUMENT POWER B RACK, is in the ON position.

CV

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 56 of 117 Data Package: Page

-of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (continued)

NOTE Radiation Process and Area Monitor Power Distribution Panel 2-DPL-242-1 is located at El. 737', column A8S.

[5]

ENSURE 2-BKR-90-60B, Breaker 12 at the Radiation Process and Area Monitor Power Distribution Panel, 2-DPL-242-1, to 2-RI-90-60B, is in the ON position.

Cv

[6]

VERIFY the ratemeter indications on 2-RM-90-60 (MCR Panel 0-M-12) are as follows: (Acc Crit)

A.

Green OPERATE light is ON.

B.

Yellow ALERT (1) light is OFF.

C.

Red HIGH (2) light is OFF.

[7]

VERIFY the indications at 2-RI-90-60B (El. 756', Az. 2250) are as follows: (Acc Crit)

A.

Green POWER ON light is ON.

B.

Red HIGH ALARM light is OFF.

[8]

VERIFY the following:

A.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, is NOT in ALARM. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-60) is in NORMAL (Blue). (Acc Crit)

Data Package: Page

-of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (continued)

CAUTION 100 Vdc is present when the front panel of the RM-1000 ratemeter is open. Do not touch the exposed circuitry on the display.

[9]

LOOSEN the left side thumb screws on the front panel of 2-RM-90-60, AND OPEN the hinged door.

[10]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-60 to the CAL (down) position, AND VERIFY the green OPERATE light is OFF. (Acc Crit)

[11]

CLOSE the hinged door on the front of 2-RM-90-60.

[12]

PRESS the [CLR] button on the front panel of 2-RM-90-60, AND VERIFY the green OPERATE light remains OFF. (Acc Crit)

[13]

VERIFY the following:

A.

0-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-60) is in ALARM (Red). (Acc Crit)

[14]

OPEN the hinged door on the front of 2-RM-90-60.

[15]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-60 to the OPERATE (up) position.

[16]

CLOSE the hinged door on the front panel of 2-RM-90-60, AND TIGHTEN the left side thumb screws.

Data Package: Page of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (continued)

[17]

PRESS the [CLR] button on the front panel of 2-RM-90-60, AND VERIFY the green OPERATE is ON. (Acc Crit)

[18]

VERIFY the following:

A.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, CLEARS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-60) is NORMAL (Blue). (Acc Crit)

[19]

REMOVE fuse F1 from 2-PX-90-60 UP COMPARTMENT REAC BLDG-AREA MON PWR SPLY located inside MCR Panel 0-M-12.

CV

[20]

VERIFY the following: (Acc Crit)

A.

0-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, ALARMS.

(Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-60) is in ALARM (Red). (Acc Crit)

C.

0-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

D.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-60) is in ALARM (Red). (Acc Crit)

[21]

INSTALL fuse F1 in 2-PX-90-60 UP COMPARTMENT REAC BLDG-AREA MON PWR SPLY located inside MCR Panel 0-M-12.

CV

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 59 of 117 Data Package: Page

-of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (continued)

[22]

PRESS the [CLR] button on the front panel of 2-RM-90-60, AND VERIFY the green OPERATE is ON. (Acc Grit)

[23]

VERIFY the following:

A.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, CLEARS.

(Acc Grit)

B.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-60) is in NORMAL (Blue). (Acc Grit)

C.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, CLEARS. (Acc Grit)

D.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-60) is in NORMAL (Blue). (Acc Grit)

[24]

RECORD the following ambient dose rate indications:

Device Indication Initials/date 2-RM-90-60 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12)

R/HR 2-RR-90-1 P002 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-60B UP COMPARTMENT REAC BLDG-AREA MON (El. 756', Az. 2250)

R/HR R9017A ICS Point for 2-RE-90-60 MR/HR

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 60 of 117 Data Package: Page of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (continued)

ALARA The radioactive source hung by 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1 000 Digital Ratemeters, has a high dose potential. Actions to reduce dose must be taken during performance of steps 6.3[25] through 6.3126.2]E.

NOTE Steps 6.3[25] through 6.3[26.2]E are to be performed after 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1000 Digital Ratemeters, has hung the calibration source in 2-RE-90-60.

[25]

RECORD the following source response indications:

Device Indication Initials/date 2-RM-90-60 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12)

R/HR 2-RR-90-1 P002 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-60B UP COMPARTMENT REAC BLDG-AREA MON (El. 756', Az. 2250)

RPHR R9017A ICS Point for 2-RE-90-60 MR/HR

Data Package: Page

-of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (continued)

[26]

PERFORM the following radiation response verifications:

[26.1]

VERIFY the following local and main control room alarms actuated.

A.

2-RI-90-60B red HIGH ALARM light is ON.

(Acc Crit)

B.

2-RI-90-60B audible alarm is ON. (Acc Crit)

C.

2-RM-90-60 yellow ALERT (1) light is ON.

(Acc Grit)

D.

2-RM-90-60 red HIGH (2) light is ON. (Acc Crit)

E.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, ALARMS. (Acc Grit)

F.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-60) is in ALARM (Red). (Acc Grit)

[26.2]

PRESS the [CLR] button on 2-RM-90-60, AND VERIFY the following: (Acc Crit)

A.

2-RI-90-60B red HIGH ALARM light is ON.

(Acc Crit)

B.

2-RI-90-60B audible alarm is ON. (Acc Crit).

C.

2-RM-90-60 yellow ALERT (1) light is ON.

(Acc Crit)

D.

2-RM-90-60 red HIGH (2) light is ON. (Acc Crit)

E.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, is in ALARM. (Acc Grit)

F.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-60) is in ALARM (Red). (Acc Grit)

Data Package: Page

-of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (continued)

[26.3]

PRESS the alarm acknowledge button on 2-RI-90-60B, AND VERIFY the audible alarm is OFF. (Acc Crit)

NOTE The remainder of subsection 6.3 is to be performed after 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1000 Digital Ratemeters, has removed the source from 2-RE-90-60.

[271 PERFORM the following radiation response verifications

[27.1]

RECORD the following ambient dose rate indications, AND VERIFY ambient dose rates are similar to those recorded in step 6.3[24].

Device Indication Initials/date 2-RM-90-60 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12)

R/HR 2-RR-90-1 P002 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-60B UP COMPARTMENT REAC BLDG-AREA MON (El. 756',

Az. 2250)

R/HR R9017A ICS Point for 2-RE-90-60 MR/HR

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 63 of 117 Data Package: Page

-of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (continued)

[27.2]

VERIFY the local and main control room alarms and annunciators actuate as follows:

A.

2-RI-90-60B red HIGH ALARM light is ON.

(Acc Crit)

B.

2-RM-90-60 yellow ALERT (1) light is ON.

(Acc Crit)

C.

2-RM-90-60 red HIGH (2) light is ON. (Acc Crit)

D.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, ALARMS. (Acc Crit)

E.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-60) is in ALARM (Red). (Acc Crit)

[27.3]

PRESS the [CLR] button on 2-RM-90-60, AND VERIFY the following: (Acc Crit)

A.

2-RI-90-60B red HIGH ALARM light is OFF.

(Acc Crit)

B.

2-RM-90-60 yellow ALERT (1) light is OFF.

(Acc Crit)

C.

2-RM-90-60 red HIGH (2) light is OFF. (Acc Crit)

D.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, CLEARS. (Acc Crit)

E.

Unit 2 Event Display Monitor indicates 193-B PERSONNEL AIR LOCK AREA RAD HI (2-RM-90-60) is in NORMAL (Blue). (Acc Crit)

[27.4]

COMPARE the source response recorded in step 6.3[25] to the ambient reading recorded in step 6.3[24]

for each device, AND VERIFY each device exhibited an increased deflection above background once exposed to the calibration source.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 64 of 117 Data Package: Page of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (continued)

NOTE When the RM-1 000 is in the OPERATE mode the checksource function will clear after one minute so recording of response values needs to be completed within that time period or the sequence will have to be repeated.

[28]

PERFORM the following Check Source response verifications.

[28.1]

PRESS the [FUN], [2], [ENT] buttons on 2-RM-90-60 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12) to actuate the CHKSRC function.

NOTE The RM-1 000 meter responds to a checksource test by displaying the ambient reading on the left side of the scale and the checksource response on the right side of the scale with the checksource response value indicated at the bottom along with the function description "CHKSRC".

[28.2]

VERFIY the indication on 2-RM-90-60 shows a two level response with the left indication lower than the right indication. (Acc Crit)

[28.3]

RECORD the following indications, AND VERIFY each device exhibited an increased deflection above the ambient dose rates recorded in step 6.3[27.1].

(Acc Crit)

Data Package: Page of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (continued)

Device Indication initials/date 2-RM-90-60 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12)

R/HR 2-RR-90-1P002 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-60B UP COMPARTMENT REAC BLDG-AREA MON (El. 756', Az.

2250)

R/HR R9017A ICS Point for 2-RE-90-60 MR/HR

[28.4]

VERIFY the main control room alarms as follows:

(Acc Crit)

A.

2-RM-90-60 yellow ALERT (1) light is OFF.

B.

2-RM-90-60 red HIGH (2) light is OFF.

[28.5]

WHEN at least one minute has elapsed from the time the CHKSRC function actuated, THEN VERIFY the following devices indicate dose rates similar to those recorded in step 6.3[27.1].

A.

2-RM-90-60 UP COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12).

B.

2-RR-90-1 P002 AREA RADIATION MONITORS (MCR Panel 0-M-12).

C.

2-RI-90-60B UP COMPARTMENT REAC BLDG-AREA MON (El. 756', Az. 2250).

D.

R9017A ICS Point for 2-RE-90-60.

Data Package: Page

-of Date 6.3 2-LPR-90-60, UP COMPARTMENT REAC BLDG AREA MON (continued)

[29]

WHEN the Loss of Counts Setup portion of 2-IMI-90.020 has been completed,

THEN, VERIFY the following (actions should occur within approximately two minutes after 2-IMI-90.020 has set the Discriminator Voltage to 1 OVdc): (Acc Crit)

A.

The green OPERATE light is OFF (On the front panel of 2-RM-90-60). (Acc Crit)

B.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-60) is in ALARM (Red). (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 67 of 117 Data Package: Page

-of Date 6.4 2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON NOTES

1)

Subsection 6.4 is to be performed in parallel with 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1 000 Digital Ratemeters.

2)

For consistency with 2-IMI-90.020, steps in Subsection 6.4 may be performed in any order.

[1]

ENSURE the prerequisites listed in Section 4.0 for Subsection 6.4 have been completed.

[2]

ESTABLISH communications between the MCR Panel 0-M-12 and local indicator 2-RI-90-61 B, LWR COMPARTMENT REAC BLDG-AREA MON (El. 736', Az. 820).

[3)

ENSURE 2-BKR-278-MO12D, TO PNL 0-M-12 RAD MON RATEMETERS & RECORDERS, at 2-BD-278-MO07A PANEL 2-M-7 INSTRUMENT POWER A RACK, is in the ON position.

CV

[4]

ENSURE 2-BKR-242-0001 B, RAD PROC & AREA MON DIST PNL 2 FEEDER, at 2-BD-278-MO07B PANEL 2-M-7 INSTRUMENT POWER B RACK, is in the ON position.

CV

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 68 of 117 Data Package: Page of Date 6.4 2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (continued)

NOTE Radiation Process and Area Monitor Power Distribution Panel 2-DPL-242-1 is located at El. 737', column A8S.

[5]

ENSURE 2-BKR-90-61 B, Breaker 13 at the Radiation Process and Area Monitor Power Distribution Panel, 2-DPL-242-1, to 2-RI-90-61 B, is in the ON position.

CV

[6]

VERIFY the ratemeter indications on 2-RM-90-61 (MCR Panel 0-M-12) are as follows: (Acc Crit)

A.

Green OPERATE light is ON.

B.

Yellow ALERT (1) light is OFF.

C.

Red HIGH (2) light is OFF.

[7]

VERIFY the indications at 2-RI-90-61 B (El. 736', Az. 820) are as follows: (Acc Crit)

A.

Green POWER ON light is ON.

B.

Red HIGH ALARM light is OFF.

[8]

VERIFY the following:

A.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, is NOT in ALARM. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E INCORE INSTR ROOM AREA MON INSTR MALF (2-RM-90-61) is in NORMAL (Blue). (Acc Crit)

Data Package: Page of Date 6.4 2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (continued)

CAUTION 100 Vdc is present when the front panel of the RM-1000 ratemeter is open. Do not touch the exposed circuitry on the display.

[9]

LOOSEN the left side thumb screws on the front panel of 2-RM-90-61, AND OPEN the hinged door.

[10]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-61 to the CAL (down) position, AND VERIFY the green OPERATE light is OFF. (Acc Crit)

[11]

CLOSE the hinged door on the front of 2-RM-90-61.

[12]

PRESS the [CLR] button on the front panel of 2-RM-90-61, AND VERIFY the green OPERATE light remains OFF. (Acc Crit)

[13]

VERIFY the following:

A.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E INCORE INSTR ROOM AREA MON INSTR MALF (2-RM-90-61) is in ALARM (Red). (Acc Crit)

[14]

OPEN the hinged door on the front of 2-RM-90-61.

[15]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-61 to the OPERATE (up) position.

[16]

CLOSE the hinged door on the front panel of 2-RM-90-61, AND TIGHTEN the left side thumb screws.

Data Package: Page

-of Date 6.4 2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (continued)

[17]

PRESS the [CLR] button on the front panel of 2-RM-90-61, AND VERIFY the green OPERATE is ON. (Acc Crit)

[18]

VERIFY the following:

A.

0-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, CLEARS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-E INCORE INSTR ROOM AREA MON INSTR MALF (2-RM-90-61) is in NORMAL (Blue). (Acc Crit)

[19]

REMOVE fuse F1 from 2-PX-90-61 LWR COMPARTMENT REAC BLDG-AREA MON PWR SPLY located inside MCR Panel 0-M-12.

Cv

[20]

VERIFY the following: (Acc Crit)

A.

0-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, ALARMS.

(Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-B CONT INSTR RM AREA RAD HI (2-RM-90-61) is in ALARM (Red). (Acc Crit)

C.

0-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

D.

Unit 2 Event Display Monitor indicates 193-E PERSONNEL AIR LOCK AREA MON INSTR MALF (2-RM-90-61) is in ALARM (Red). (Acc Crit)

[21]

INSTALL fuse F1 in 2-PX-90-61 LWR COMPARTMENT REAC BLDG-AREA MON PWR SPLY located inside MCR Panel 0-M-12.

CV

Data Package: Page

-of Date 6.4 2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (continued)

[22]

PRESS the [CLR] button on the front panel of 2-RM-90-61, AND VERIFY the green OPERATE is ON. (Acc Crit)

[23]

VERIFY the following:

A.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, CLEARS.

(Acc Crit)

B.

Unit 2 Event Display Monitor indicates 193-B CONT INSTR RM AREA RAD HI (2-RM-90-61) is in NORMAL (Blue). (Acc Crit)

C.

O-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, CLEARS. (Acc Crit)

D.

Unit 2 Event Display Monitor indicates 193-E INCORE INSTR ROOM AREA MON INSTR MALF (2-RM-90-61) is in NORMAL (Blue). (Acc Crit)

[24]

RECORD the following ambient dose rate indications:

Device Indication Initials/date 2-RM-90-61 LWR COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12)

R/HR 2-RR-90-1 P004 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-61 B LWR COMPARTMENT REAC BLDG-AREA MON (El. 736', Az. 820)

R/HR

WBN RADIATION MONITORS - AREA DOSE 2-PTi-090-01 Unit 2 RATE Rev. 0000 Page 72 of 117 Data Package: Page

-of Date 6.4 2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (continued)

ALARA The radioactive source hung by 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1000 Digital Ratemeters, has a high dose potential. Actions to reduce dose must be taken during performance of steps 6.4[25] through 6.4[26.3].

NOTE Steps 6.4[25] through 6.4[26.3] are to be performed after 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1 000 Digital Ratemeters, has hung the calibration source in 2-RE-90-61.

[25]

RECORD the following source response indications:

Device Indication Initials/date 2-RM-90-61 LWR COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12)

RIHR 2-RR-90-1 P004 AREA RADIATION MONITORS (MCR Panel 0-M-12)

RJHR 2-RI-90-61 B LWR COMPARTMENT REAC BLDG-AREA MON (El. 736', Az. 820)

R/HR

WBN Unit 2 RADIATION MONITORS - AREA DOSE 2-PTI-090-01 RATE Rev. 0000 Page 73 of 117 6.4 Data Package: Page of D

2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (continued)

[26]

PERFORM the following radiation response verifications:

[26.1]

VERIFY the following local and main control room alarms actuated.

A.

2-RI-90-61B red HIGH ALARM light is ON.

(Acc Crit)

B.

2-RI-90-61 B audible alarm is ON. (Acc Crit)

C.

2-RM-90-61 yellow ALERT (1) light is ON.

(Acc Crit)

D. 2-RM-90-61 red HIGH (2) light is ON. (Acc Crit)

E.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, ALARMS. (Acc Crit)

F.

Unit 2 Event Display Monitor indicates 193-B CONT INSTR RM AREA RAD HI (2-RM-90-61) is in ALARM (Red). (Acc Crit)

[26.2]

PRESS the [CLR] button on 2-RM-90-61, AND VERIFY the following: (Acc Crit)

A.

2-RI-90-61B red HIGH ALARM light is ON.

(Acc Crit)

B.

2-RI-90-61B audible alarm is ON. (Acc Crit)

C.

2-RM-90-61 yellow ALERT (1) light is ON.

(Acc Crit)

D. 2-RM-90-61 red HIGH (2) light is ON. (Acc Crit)

E.

0-XA-55-12D/1!93-B, 2-RR-90-1 AREA RAD HI, is in ALARM. (Acc Crit)

F.

Unit 2 Event Display Monitor indicates 193-B CONT INSTR RM AREA RAD HI (2-RM-90-61) is in ALARM (Red). (Acc Crit)

Pate

Data Package: Page

-of Date 6.4 2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (continued)

[26.3]

PRESS the alarm acknowledge button on 2-RI-90-61 B, AND VERIFY the audible alarm is OFF. (Acc Crit)

NOTE The remainder of subsection 6.4 is to be performed after 2-IMI-90.020, Calibration of Low Range Area Radiation Monitors with RM-1000 Digital Ratemeters, has removed the source from 2-RE-90-61.

[27]

PERFORM the following radiation response verifications:

[27.1]

RECORD the following ambient dose rate indications, AND VERIFY ambient dose rates are similar to those recorded in step 6.4[24].

Device Indication Initials/date 2-RM-90-61 LWR COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-1 2)

R/HR 2-RR-90-1 P004 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-61B LWR COMPARTMENT REAC BLDG-AREA MON (El. 736',

Az. 820)

R/HR

Data Package: Page of Date 6.4 2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (continued)

[27.2]

VERIFY the local and main control room alarms and annunciators actuate as follows:

A.

2-RI-90-61 B red HIGH ALARM light is ON.

(Acc Crit)

B.

2-RM-90-61 yellow ALERT (1) light is ON.

(Acc Crit)

C.

2-RM-90-61 red HIGH (2) light is ON. (Acc Crit)

D.

O-XA-55-12D/1 93-B, 2-RR-90-1 AREA RAD HI, CLEARS. (Acc Crit)

E.

Unit 2 Event Display Monitor indicates 193-B CONT INSTR RM AREA RAD HI (2-RM-90-61) is in NORMAL (Blue). (Acc Crit)

[27.3]

PRESS the [CLR] button on 2-RM-90-61, AND VERIFY the following: (Acc Crit)

A.

2-RI-90-61B red HIGH ALARM light is OFF.

(Acc Crit)

B.

2-RM-90-61 yellow ALERT (1) light is OFF.

(Acc Crit)

C.

2-RM-90-61 red HIGH (2) light is OFF. (Acc Crit)

D.

O-XA-55-12D/193-B, 2-RR-90-1 AREA RAD HI, CLEARS. (Acc Crit)

E.

Unit 2 Event Display Monitor indicates 193-B CONT INSTR RM AREA RAD HI (2-RM-90-61) is in NORMAL (Blue). (Acc Crit)

[27.4]

COMPARE the source response recorded in step 6.4[25] to the ambient reading recorded in step 6.4[24]

for each device, AND VERIFY each device exhibited an increased deflection above background once exposed to the calibration source.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 76 of 117 Data Package: Page

-of Date 6.4 2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (continued)

NOTE When the RM-1 000 is in the OPERATE mode the checksource function will clear after one minute so recording of response values needs to be completed within that time period or the sequence will have to be repeated.

[28]

PERFORM the following Check Source response verifications.

[28.1]

PRESS the [FUN], [2], [ENT] buttons on 2-RM-90-61 LWR COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12) to actuate the CHKSRC function.

NOTE The RM-1000 meter responds to a checksource test by displaying the ambient reading on the left side of the scale and the checksource response on the right side of the scale with the checksource response value indicated at the bottom along with the function description "CHKSRC".

[28.2]

VERFIY the indication on 2-RM-90-61 shows a two level response with the left indication lower than the right indication. (Acc Crit)

[28.3]

RECORD the following indications, AND VERIFY each device exhibited an increased deflection above the ambient dose rates recorded in step 6.4[27.1].

(Acc Crit)

Device Indication 2-RM-90-61 LWR COMPARTMENT.

REAC BLDG-AREA MON (MCR Panel 0-M-12)

R/HR 2-RR-90-1 P004 AREA RADIATION MONITORS (MCR Panel 0-M-12)

R/HR 2-RI-90-61 B LWR COMPARTMENT REAC BLDG-AREA MON (El. 736',

Az. 820)

R/HR

Data Package: Page

-of Date 6.4 2-LPR-90-61, LWR COMPARTMENT INSTR ROOM AREA MON (continued)

[28.4]

VERIFY the main control room alarms as follows:

(Acc Crit)

A.

2-RM-90-61 yellow ALERT (1) light is OFF.

B.

2-RM-90-61 red HIGH (2) light is OFF.

[28.5]

WHEN at least one minute has elapsed from the time the CHKSRC function actuated, THEN VERIFY the following devices indicate dose rates similar to those recorded in step 6.4[27.1].

A.

2-RM-90-61 LWR COMPARTMENT REAC BLDG-AREA MON (MCR Panel 0-M-12).

B.

2-RR-90-1 P004 AREA RADIATION MONITORS (MCR Panel 0-M-12).

C.

2-RI-90-61 B LWR COMPARTMENT REAC BLDG-AREA MON (El. 736', Az. 820).

[29]

WHEN the Loss of Counts Setup portion of 2-IMI-90.020 has been completed,

THEN, VERIFY the following (actions should occur within approximately two minutes after 2-IMI-90.020 has set the Discriminator Voltage to 1OVdc): (Acc Crit)

A.

The green OPERATE light is OFF (On the front panel of 2-RM-90-61). (Acc Crit)

B.

0-XA-55-12D/193-E, 2-RR-90-1 AREA MONITORS INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 193-E INCORE INSTR ROOM AREA MON INSTR MALF (2-RM-90-61) is in ALARM (Red). (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 78 of 117 Data Package: Page _

of Date 6.5 2-LPR-90-271, CNTMT POST ACC HIGH RAD NOTES

1)

Subsection 6.5 is to be performed in parallel with 2-SI-90-1, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-271.

2)

For consistency with 2-SI-90-1, steps in Subsection 6.5 may be performed in any order.

[1]

ENSURE the prerequisites listed in Section 4.0 for Subsection 6.5 have been completed.

[2]

ESTABLISH communications between the MCR Panel 0-M-12 and detector 2-RE-90-271, UPR INS CNTMT POST ACD AREA MON (El. 815', Az. 1800).

.[3]

ENSURE 2-BKR-235-3/45, RAD RATERMETERS AND 2-81-90-106, is in the ON position.

Cv

[4]

VERIFY 2-SI-90-1 has lowered the setpoints for 2-RM-90-271.

[5]

VERIFY the ratemeter indication on 2-RM-90-271 (MCR Panel 2-M-30) are as follows: (Acc Crit)

A.

Green OPERATE light is ON.

B.

Yellow ALERT (1) light is OFF.

C.

Red HIGH (2) light is OFF.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 79 of 117 Data Package: Page of Date 6.5 2-LPR-90-271, CNTMT POST ACC HIGH RAD (continued)

[6]

VERIFY the following:

A.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, is CLEAR. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-271-A) is in NORMAL (Blue). (Acc Crit)

CAUTION 100 Vdc is present when the front panel of the RM-1 000 ratemeter is open. Do not touch the exposed circuitry on the display.

[7]

LOOSEN the left side thumb screws on the front panel of 2-RM-90-271, AND OPEN the hinged door.

[8]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-271 to the CAL (down) position, AND VERIFY the green OPERATE light is OFF. (Acc Crit)

[9]

CLOSE the hinged door on the front of 2-RM-90-271.

[10]

PRESS the [CLR] button on the front panel of 2-RM-90-271, AND VERIFY the green OPERATE light remains OFF. (Acc Crit)

[11]

VERIFY the following:

A.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-271-A) is in ALARM (Red). (Acc Crit)

[12]

OPEN the hinged door on the front of 2-RM-90-271.

[13]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-271 to the OPERATE (up) position.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 80 of 117 Data Package: Page

-of Date 6.5 2-LPR-90-271, CNTMT POST ACC HIGH RAD (continued)

[14]

CLOSE the hinged door on the front panel of 2-RM-90-271, AND TIGHTEN the left side thumb screws.

[15]

PRESS the [CLR] button on the front panel of 2-RM-90-271, AND VERIFY the green OPERATE is ON. (Acc Crit)

[16]

VERIFY the following:

A.

O-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, CLEARS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-271-A) is in NORMAL (Blue). (Acc Crit)

[17]

REMOVE fuse F1 from 2-PX-90-271 UPR INS CNTMT POST ACD AREA MON PWR SUPPLY located inside MCR Panel 2-M-30.

Cv

[18]

VERIFY the following: (Acc Crit)

A.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272 RAD HI, ALARMS. (Acc Crit)

B.

O-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-271-A) is in ALARM (Red). (Acc Crit)

(19]

INSTALL fuse F1 in 2-PX-90-271 UPR INS CNTMT POST ACD AREA MON PWR SUPPLY located inside MCR Panel 2-M-30.

Cv

Data Package: Page

-of 6.5 2-LPR-90-271, CNTMT POST ACC HIGH RAD (continued) 120]

PRESS the [CLR] button on the front panel of 2-RM-90-271, AND VERIFY the green OPERATE is ON. (Acc Crit)

[21]

VERIFY the following:

A.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272 RAD HI, CLEARS. (Acc Crit)

B.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, CLEARS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-271-A) is in NORMAL (Blue). (Acc Crit)

[22]

RECORD the following ambient dose rate indications:

Date Device Indication Initials/date 2-RM-90-271 UPR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

RJHR R90 18A ICS Point for 2-RE-90-271 R/HR

Data Package: Page of Date 6.5 2-LPR-90-271, CNTMT POST ACC HIGH RAD (continued)


I ALARA The radioactive source hung by 2-SI-90-1, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-271, has a high dose potential. Actions to reduce dose must be taken during performance of steps 6.5[23] through 6.5[24.2].

NOTE Steps 6.5[23] through 6.5[24.2] are to be performed after 2-SI-90-1, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-271, has hung the calibration source in 2-RE-90-271.

[23]

RECORD the following source response indications:

Device Indication Initials/date 2-RM-90-271 UPR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

R/HR R9018A ICS Point for 2-RE-90-271 (Acc Crit)

R/HR

[24]

PERFORM the following radiation response verifications:

[24.1]

VERIFY the following local and main control room alarms actuated.

A.

2-RM-90-271 yellow ALERT (1) light is ON.

(Acc Crit)

B.

2-RM-90-271 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272 RAD HI, ALARMS. (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 83 of 117 Data Package: Page of Date 6.5 2-LPR-90-271, CNTMT POST ACC HIGH RAD (continued)

[24.2]

PRESS the [CLR] button on 2-RM-90-271, AND VERIFY the following: (Acc Crit)

A.

2-RM-90-271 yellow ALERT (1) light is ON.

(Acc Crit)

B. 2-RM-90-271 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272 RAD HI, is in ALARM. (Acc Crit).

NOTE The remainder of subsection 6.5 is to be performed after 2-SI-90-1, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-271, has removed the source from 2-RE-90-271.

[25]

PERFORM the following radiation response verifications:

[25.1]

RECORD the following ambient dose rate indications, AND VERIFY ambient dose rates are similar to those recorded in step 6.5[22].

Device Indication Initials/date 2-RM-90-271 UPR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

R/HR R9018A ICS Point for 2-RE-90-271 R/HR

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 84 of 117 6.5 Data Package: Page

-of Date 2-LPR-90-271, CNTMT POST ACC HIGH RAD (continued)

[25.2]

VERIFY the local and main control room alarms and annunciators actuate as follows:

A.

2-RM-90-271 yellow ALERT (1) light is on.

(Acc Crit)

B.

2-RM-90-271 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272 RAD HI, ALARMS. (Acc Crit)

[25.3]

PRESS the [CLR] button on 2-RM-90-271, AND VERIFY the following: (Acc Crit)

A.

2-RM-90-271 yellow ALERT (1) light is OFF.

(Acc Crit)

B.

2-RM-90-271 red HIGH (2) light is OFF. (Acc Crit)

C.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272

. RAD HI, CLEARS. (Acc Crit)

[25.4]

COMPARE the source response recorded in step 6.5[23] to the ambient reading recorded in step 6.5[22]

for each device, AND VERIFY each device exhibited an increased deflection above background once exposed to the calibration source.

NOTE When the RM-1000 is in the OPERATE mode the checksource function will clear after one minute so recording of response values needs to be completed within that time period or the sequence will have to be repeated.

[26]

PERFORM the following Check Source response verifications.

[26.1]

PRESS the [FUN], [2], [ENT] buttons on 2-RM-90-271 UPR INS CNTMT POST ACD AREA MON (Panel 2-M-30) to actuate the CHKSRC function.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 85 of 117 Data Package: Page _

of Date 6.5 2-LPR-90-271, CNTMT POST ACC HIGH RAD (continued)

NOTE The RM-1000 meter responds to a checksource test by displaying the ambient reading on the left side of the scale and the checksource response on the right side of the scale with the checksource response value indicated at the bottom along with the function description "CHKSRC".

[26.2]

VERFIY the indication on 2-RM-90-271 shows a two level response with the left indication lower than the right indication. (Acc Crit)

[26.3]

VERIFY the main control room alarms as follows:

(Acc Crit)

A.

2-RM-90-271 yellow ALERT (1) light is OFF.

B.

2-RM-90-271 red HIGH (2) light is OFF.

[26.4]

WHEN at least one minute has elapsed from the time the CHKSRC function actuated, THEN VERIFY the indication on 2-RM-90-271 UPR INS CNTMT POST ACD AREA MON (Panel 2-M-30) indicates a dose rate similar to the one recorded in step 6.5[25.1].

[27]

WHEN the Loss of Counts Setup portion of 2-SI-90-1 has been completed,

THEN, VERIFY the following (actions should occur within approximately two minutes after 2-SI-90-1 has set the Discriminator Voltage to 1OVdc): (Acc Crit)

A.

The green OPERATE light is OFF (On the front panel of 2-RM-90-271). (Acc Crit)

B.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-271-A) is in ALARM (Red). (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 86 of 117 Data Package: Page of Date 6.6 2-LPR-90-272, CNTMT POST ACC HIGH RAD NOTES

1)

Subsection 6.6 is to be performed in parallel with 2-SI-90-2, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-272.

2)

For consistency with 2-SI-90-2, steps in Subsection 6.6 may be performed in any order.

[1]

ENSURE the prerequisites listed in Section 4.0 for Subsection 6.6 have been completed.

[2]

ESTABLISH communications between the MCR Panel 0-M-12 and detector 2-RE-90-272, UPR INS CNTMT POST ACD AREA MON (El. 815', Az. 360°).

[3]

ENSURE 2-BKR-235-4/47, Feed to MCR PNL 0-M-12 RAD RATERMETERS is in the ON position.

Cv

[4]

ENSURE 2-SI-90-2 has lowered the setpoints for 2-RM-90-272.

[5]

VERIFY the ratemeter indication on 2-RM-90-272 (MCR Panel 2-M-30) are as follows: (Acc Crit)

A.

Green OPERATE light is ON.

B.

Yellow ALERT (1) light is OFF.

C.

Red HIGH (2) light is OFF.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 87 of 117 Data Package: Page

-of Date 6.6 2-LPR-90-272, CNTMT POST ACC HIGH RAD (continued)

[6]

VERIFY the following:

A.

O-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, is CLEAR. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-272-B) is in NORMAL (Blue). (Acc Crit)

CAUTION 100 Vdc is present when the front panel of the RM-1000 ratemeter is open. Do not touch the exposed circuitry on the display.

[7]

LOOSEN the left side thumb screws on the front panel of 2-RM-90-272, AND OPEN the hinged door.

[8]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-272 to the CAL (down) position, AND VERIFY the green OPERATE light is OFF. (Acc Crit)

[9]

CLOSE the hinged door on the front of 2-RM-90-272.

[10]

PRESS the [CLR] button on the front panel of 2-RM-90-272, AND VERIFY the green OPERATE light remains OFF. (Acc Crit)

[11]

VERIFY the following:

A.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-272-B) is in ALARM (Red). (Acc Crit)

[12]

OPEN the hinged door on the front of 2-RM-90-272.

Data Package: Page

-of Date 6.6 2-LPR-90-272, CNTMT POST ACC HIGH RAD (continued)

[13]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-272 to the OPERATE (up) position.

[14]

CLOSE the hinged door on the front panel of 2-RM-90-272, AND TIGHTEN the left side thumb screws.

[15]

PRESS the [CLR] button on the front panel of 2-RM-90-272, AND VERIFY the green OPERATE is ON. (Acc Crit)

[16]

VERIFY the following:

A.

O-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, CLEARS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-272-B) is in NORMAL (Blue). (Acc Crit)

[17]

REMOVE F1 from 2-PX-90-272 UPR INS CNTMT POST ACD AREA MON PWR SUPPLY located inside MCR Panel 2-M-30.

CV

[18]

VERIFY the following: (Acc Crit)

A.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272 RAD HI, ALARMS. (Acc Crit)

B.

O-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-272-B) is in ALARM (Red). (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 89 of 117 Data Package: Page

-of Date 6.6 2-LPR-90-272, CNTMT POST ACC HIGH RAD (continued)

[19]

INSTALL fuse F1 in 2-PX-90-272 UPR INS CNTMT POST ACD AREA MON PWR SUPPLY located inside MCR Panel 2-M-30.

CV

[20]

PRESS the [CLR] button on the front panel of 2-RM-90-272, AND VERIFY the green OPERATE is ON. (Acc Crit)

[21]

VERIFY the following:

A.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272 RAD HI, CLEARS. (Acc Crit)

B.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, CLEARS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-272-B) is in NORMAL (Blue). (Acc Crit)

[22]

RECORD.the following ambient dose rate indications:

Device Indication Initials/date 2-RM-90-272 UPR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

R/HR R9019A ICS Point for 2-RE-90-272 R/HR

Data Package: Page

-of Date 6.6 2-LPR-90-272, CNTMT POST ACC HIGH RAD (continued)

ALARA The radioactive source hung by 2-SI-90-2, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-272, has a high dose potential. Actions to reduce dose must be taken during performance of steps 6.6[23] through 6.6[24.2].

NOTE Steps 6.6[23] through 6.6[24.2] are to be performed after 2-SI-90-2, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-272, has hung the calibration source in 2-RE-90-272.

[23]

RECORD the following source response indications:

Device Indication Initials/date 2-RM-90-272 UPR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

RJHR R9019A ICS Point for 2-RE-90-272 (Acc Crit)

R/HR

[24]

PERFORM the following radiation response verifications:

[24.1]

VERIFY the following local and main control room alarms actuated.

A.

2-RM-90-272 yellow ALERT (1) light is ON.

(Acc Crit)

B.

2-RM-90-272 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272 RAD HI, ALARMS. (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 91 of 117 Data Package: Page _

of Date 6.6 2-LPR-90-272, CNTMT POST ACC HIGH RAD (continued)

[24.2]

PRESS the [CLR] button on 2-RM-90-272, AND VERIFY the following: (Acc Crit)

A.

2-RM-90-272 yellow ALERT (1) light is ON.

(Acc Crit)

B.

2-RM-90-272 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272 RAD HI, is in ALARM. (Acc Crit)

NOTE The remainder of subsection 6.6 is to be performed after 2-SI-90-2, 18 Mo Ch Source Cal CNTMT UPR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-272, has removed the calibration source from 2-RE-90-272.

[25]

PERFORM the following radiation response verifications:

[25.1]

RECORD the following ambient dose rate indications, AND VERIFY ambient dose rates are similar to those recorded in step 6.6[22].

Device Indication Initials/date 2-RM-90-272 UPR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

R/HR R9019A ICS Point for 2-RE-90-272 R/HR

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 92 of 117 Data Package: Page

-of Date 6.6 2-LPR-90-272, CNTMT POST ACC HIGH RAD (continued)

[25.2]

VERIFY the local and main control room alarms and annunciators actuate as follows:

A.

2-RM-90-272 yellow ALERT (1) light is ON.

(Acc Crit)

B. 2-RM-90-272 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272 RAD HI, ALARMS. (Acc Crit)

[25.3]

PRESS the [CLR] button on 2-RM-90-272, AND VERIFY the following: (Acc Crit)

A.

2-RM-90-272 yellow ALERT (1) light is OFF.

(Acc Crit)

B.

2-RM-90-272 red HIGH (2) light is OFF. (Acc Crit)

C.

2-XA-55-30/265-A, UPPER CNTMNT RE-271/272 RAD HI, CLEARS. (Acc Crit)

[25.4]

COMPARE the source response recorded in step 6.6[23] to the ambient reading recorded in step 6.6[22]

for each device, AND VERIFY each device exhibited an increased deflection above background once exposed to the calibration source.

NOTE When the RM-1 000 is in the OPERATE mode the checksource function will clear after one minute so recording of response values needs to be completed within that time period or the sequence will have to be repeated.

[26]

PERFORM the following Check Source response verifications.

[26.1]

PRESS the [FUN], [2], [ENT] buttons on 2-RM-90-272 UPR INS CNTMT POST ACD AREA MON (Panel 2-M-30) to actuate the CHKSRC function.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 93 of 117 Data Package: Page of Date 6.6 2-LPR-90-272, CNTMT POST ACC HIGH RAD (continued)

NOTE The RM-1 000 meter responds to a checksource test by displaying the ambient reading on the left side of the scale and the checksource response on the right side of the scale with the checksource response value indicated at the bottom along with the function description "CHKSRC".

[26.2]

VERFIY the indication on 2-RM-90-272 shows a two level response with the left indication lower than the right indication. (Acc Crit)

[26.3]

VERIFY the main control room alarms as follows:

(Acc Crit)

A.

2-RM-90-272 yellow ALERT (1) light is OFF.

B.

2-RM-90-272 red HIGH (2) light is OFF.

[26.4]

WHEN at least one minute has elapsed from the time the CHKSRC function actuated, THEN VERIFY the indication on 2-RM-90-272 UPR INS CNTMT POST ACD AREA MON (Panel 2-M-30) indicates a dose rate similar to the one recorded in step 6.6[25.1].

[27]

WHEN the Loss of Counts Setup portion of 2-SI-90-2 has been completed,

THEN, VERIFY the following (actions should occur within approximately two minutes after 2-SI-90-2 has set the Discriminator Voltage to I OVdc): (Acc Crit)

A.

The green OPERATE light is OFF (On the front panel of 2-RM-90-272). (Acc Crit)

B.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-272-B) is in ALARM (Red). (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 94 of 117 Data Package: Page of Date 6.7 2-LPR-90-273, CNTMT POST ACC HIGH RAD NOTES

1)

Subsection 6.7 is to be performed in parallel with 2-SI-90-3, 18 Mo Ch Source Cal CNTMT LWR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-273.

2)

For consistency with 2-IMI-90.021, steps in Subsection 6.7 may be performed in any order.

[1]

ENSURE the prerequisites listed in Section 4.0 for Subsection 6.7 have been completed.

[2]

ESTABLISH communications between the MCR Panel 0-M-12 and detector 2-RE-90-273, LWR INS CNTMT POST ACD AREA MON (El. 729', Az. 1700).

[3]

ENSURE 2-BKR-235-3/45, RAD RATERMETERS AND 2-81-90-106, is in the ON position.

Cv

[4]

VERIFY 2-SI-90-3 has lowered the setpoints for 2-RM-90-273.

[5]

VERIFY the ratemeter indication on 2-RM-90-273 (MCR Panel 2-M-30) are as follows: (Acc Crit)

A.

Green OPERATE light is ON.

B.

Yellow ALERT (1) light is OFF.

C.

Red HIGH (2) light is OFF.

Data Package: Page

-of Date 6.7 2-LPR-90-273, CNTMT POST ACC HIGH RAD (continued)

[6]

VERIFY the following:

A.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, is CLEAR. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-273-A) is in NORMAL (Blue). (Acc Crit)

CAUTION 100 Vdc is present when the front panel of the RM-1 000 ratemeter is open. Do not touch the exposed circuitry on the display.

[7]

LOOSEN the left side thumb screws on the front panel of 2-RM-90-273, AND OPEN the hinged door.

[8]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-273 to the CAL (down) position, AND VERIFY the green OPERATE light is OFF. (Acc Crit)

[9]

CLOSE the hinged door on the front of 2-RM-90-273.

[10]

PRESS the [CLR] button on the front panel of 2-RM-90-273, AND VERIFY the green OPERATE light remains OFF. (Acc Crit)

[11]

VERIFY the following:

A.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-273-A) is in ALARM (Red). (Acc Crit)

[12]

OPEN the hinged door on the front of 2-RM-90-273.

[13]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-273 to the OPERATE (up) position.

Data Package: Page of Date 6.7 2-LPR-90-273, CNTMT POST ACC HIGH RAD (continued)

[14]

CLOSE the hinged door on the front panel of 2-RM-90-273, AND TIGHTEN the left side thumb screws.

[15]

PRESS the [CLR] button on the front panel of 2-RM-90-273, AND VERIFY the green OPERATE is ON. (Acc Crit)

[16]

VERIFY the following:

A.

O-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, CLEARS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-273-A) is in NORMAL (Blue). (Acc Crit)

[17]

REMOVE fuse F1 from 2-PX-90-273 LWR INS CNTMT POST ACD AREA MON PWR SUPPLY located inside MCR Panel 2-M-30.

Cv

[18]

VERIFY the following: (Acc Crit)

A.

2-XA-55-30/265-B, LOWER CNTMNT RE-273/274 RAD HI, ALARMS. (Acc Crit)

B.

O-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-273-A) is in ALARM (Red). (Acc Crit)

[19]

INSTALL fuse F1 in 2-PX-90-273 LWR INS CNTMT POST ACD AREA MON PWR SUPPLY located inside MCR Panel 2-M-30.

Cv

Data Package: Page

-of 6.7 2-LPR-90-273, CNTMT POST ACC HIGH RAD (continued)

[20]

PRESS the [CLR] button on the front panel of 2-RM-90-273, AND VERIFY the green OPERATE is ON. (Acc Crit)

[21]

VERIFY the following:

A.

2-XA-55-30/265-B, LOWER CNTMNT RE-273/274 RAD HI, CLEARS. (Acc Crit)

B.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, CLEARS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-273-A) is in NORMAL (Blue). (Acc Crit)

[22]

RECORD the following ambient dose rate indications:

Date Device Indication Initials/date 2-RM-90-273 LWR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

R/HR R9020A ICS Point for 2-RE-90-273 R/HR

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 98 of 117 Data Package: Page

-of Date 6.7 2-LPR-90-273, CNTMT POST ACC HIGH RAD (continued)

I--

ALARA The radioactive source hung by 2-SI-90-3, 18 Mo Ch Source Cal CNTMT LWR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-273, has a high dose potential. Actions to reduce dose must be taken during performance of steps 6.7[23] through 6.7[24.2].

NOTE Steps 6.7[23] through 6.7[24.2] are to be performed after 2-SI-90-3, 18 Mo Ch Source Cal CNTMT LWR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-273, has hung the calibration source in 2-RE-90-273.

[23]

RECORD the following source response indications:

Device Indication Initials/date 2-RM-90-273 LWR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

R/HR R9020A ICS Point for 2-RE-90-273 (Acc Crit)

R/HR

Data Package: Page

-of 6.7 2-LPR-90-273, CNTMT POST ACC HIGH RAD (continued)

[24]

PERFORM the following radiation response verifications:

[24.1]

VERIFY the following local and main control room alarms actuated.

A.

2-RM-90-273 yellow ALERT (1) light is ON.

(Acc Crit)

B.

2-RM-90-273 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/265-B, LOWER CNTMNT RE-273/274 RAD HI, ALARMS. (Acc Crit)

[24.2]

PRESS the [CLR] button on 2-RM-90-273, AND VERIFY the following. (Acc Crit)

A.

2-RM-90-273 yellow ALERT (1) light is ON.

(Acc Crit)

B.

2-RM-90-273 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/265-B, LOWER CNTMNT RE-273/274 RAD HI, is in ALARM. (Acc Crit)

Date

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 100 of 117 Data Package: Page

-of Date 6.7 2-LPR-90-273, CNTMT POST ACC HIGH RAD (continued)

NOTE The remainder of subsection 6.7 to be performed after 2-SI-90-3, 18 Mo Ch Source Cal CNTMT LWR COMPT HR Post Accident ARM Train A Loop 2-LPR-90-273, has removed the calibration source from 2-RE-90-273.

[25]

PERFORM the following radiation response verifications:

[25.1]

RECORD the following ambient dose rate indications, AND VERIFY ambient dose rates are similar to those recorded in step 6.7[22].

Device Indication Initials/date 2-RM-90-273 LWR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

R/HR R9020A ICS Point for 2-RE-90-273 R/HR

[25.2]

VERIFY the local and main control room alarms and annunciators actuate as follows:

A.

2-RM-90-273 yellow ALERT (1) light is ON.

(Acc Crit)

B.

2-RM-90-273 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/265-B, LOWER CNTMNT RE-273/274 RAD HI, ALARMS. (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 101 of 117 Data Package: Page

-of Date 6.7 2-LPR-90-273, CNTMT POST ACC HIGH RAD (continued)

[25.3]

PRESS the [CLR] button on 2-RM-90-273, AND VERIFY the following: (Acc Crit)

A.

2-RM-90-273 yellow ALERT (1) light is OFF.

(Acc Crit)

B.

2-RM-90-273 red HIGH (2) light is OFF. (Acc Crit)

C.

2-XA-55-30/256-B, LOWER CNTMNT RE-273/274 RAD HI, CLEARS. (Acc Crit)

[25.4]

COMPARE the source response recorded in step 6.7[23] to the ambient reading recorded in step 6.7[22]

for each device, AND VERIFY each device exhibited an increased deflection above background once exposed to the calibration source.

NOTE When the RM-1 000 is in the OPERATE mode the checksource function will clear after one minute so recording of response values needs to be completed within that time period or the sequence will have to be repeated.

[26]

PERFORM the following Check Source response verifications.

[26.1]

PRESS the [FUN], [2], [ENT] buttons on 2-RM-90-273 LWR INS CNTMT POST ACD AREA MON (Panel 2-M-30) to actuate the CHKSRC function.

NOTE The RM-1000 meter responds to a checksource test by displaying the ambient reading on the left side of the scale and the checksource response on the right side of the scale with the checksource response value indicated at the bottom along with the function description "CHKSRC".

[26.2]

VERFIY the indication on 2-RM-90-273 shows a two level response with the left indication lower than the right indication. (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 102 of 117 Data Package: Page

-of Date 6.7 2-LPR-90-273, CNTMT POST ACC HIGH RAD (continued).

[26.3]

VERIFY the main control room alarms as follows:

(Acc Crit)

A.

2-RM-90-273 yellow ALERT (1) light is OFF.

B.

2-RM-90-273 red HIGH (2) light is OFF.

[26.4]

WHEN at least one minute has elapsed from the time the CHKSRC function actuated, THEN VERIFY the indication on 2-RM-90-273 LWR -INS CNTMT POST ACD AREA MON (Panel 2-M-30) indicates a dose rate similar to the one recorded in step 6.7[25.1].

[27]

WHEN the Loss of Counts Setup portion of 2-SI-90-3 has been completed,

THEN, VERIFY the following (actions should occur within approximately two minutes after 2-SI-90-3 has set the Discriminator Voltage to 1OVdc): (Acc Crit)

A.

The green OPERATE light is OFF (On the front panel of 2-RM-90-273). (Acc Crit)

B.

O-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-273-A) is in ALARM (Red). (Acc Crit)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 103 of 117 Data Package: Page of Date 6.8 2-LPR-90-274, CNTMT POST ACC HIGH RAD NOTES

1)

Subsection 6.8 is to be performed in parallel with 2-SI-90-4, 18 Mo Ch Source Cal CNTMT LWR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-274.

2)

For consistency with 2-SI-90-4, steps in Subsection 6.8 may be performed in any order.

[1]

ENSURE the prerequisites listed in Section 4.0 for Subsection 6.8 have been completed.

[2]

ESTABLISH communications between the MCR Panel 0-M-12 and detector 2-RE-90-274, LWR INS CNTMT POST ACD AREA MON (El. 729, Az. 70).

[3]

ENSURE 2-BKR-235-4/47, Feed to MCR PNL 0-M-12 RAD RATERMETERS is in the ON position.

Cv

[4]

VERIFY 2-SI-90-4 has lowered the setpoints for 2-RM-90-274.

[5]

VERIFY the ratemeter indication on 2-RM-90-274 (MCR Panel 2-M-30) are as follows: (Acc Crit)

A.

Green OPERATE light is ON.

B.

Yellow ALERT (1) light is OFF.

C.

Red HIGH (2) light is OFF.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 104 of 117 Data Package: Page

-of Date 6.8 2-LPR-90-274, CNTMT POST ACC HIGH RAD (continued)

[6]

VERIFY the following:

A.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, CLEARS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-274-B) is in NORMAL (Blue). (Acc Crit)

CAUTION 100 Vdc is present when the front panel of the RM-1 000 ratemeter is open. Do not touch the exposed circuitry on the display.

[7]

LOOSEN the left side thumb screws on the front panel of 2-RM-90-274, AND OPEN the hinged door.

[8]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-274 to the CAL (down) position, AND VERIFY the green OPERATE light is OFF. (Acc Crit)

[9]

CLOSE the hinged door on the front of 2-RM-90-274.

[10]

PRESS the [CLR] button on the front panel of 2-RM-90-274, AND VERIFY the green OPERATE light remains OFF. (Acc Crit)

[11]

VERIFY the following:

A.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-274-B) is in ALARM (Red). (Acc Crit)

[12]

OPEN the hinged door on the front of 2-RM-90-274.

[13]

SET the OPERATE/CALIBRATE switch on the Output card in 2-RM-90-274 to the OPERATE (up) position.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 105 of 117 Data Package: Page of Date 6.8 2-LPR-90-274, CNTMT POST ACC HIGH RAD (continued)

[14]

CLOSE the hinged door on the front panel of 2-RM-90-274, AND TIGHTEN the left side thumb screws.

[15]

PRESS the [CLR] button on the front panel of 2-RM-90-274, AND VERIFY the green OPERATE is ON. (Acc Crit)

[16]

VERIFY the following:

A.

O-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, CLEARS. (Acc Crit)

B.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-274-B) is in NORMAL (Blue). (Acc Crit)

[17]

REMOVE fuse F1 from 2-PX-90-274 LWR INS CNTMT POST ACD AREA MON PWR SUPPLY located inside MCR Panel 2-M-30.

Cv

[18]

VERIFY the following: (Acc Crit)

A.

2-XA-55-30/256-B, LOWER CNTMNT RE-273/274 RAD HI, ALARMS. (Acc Crit)

B.

O-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-274-B) is in ALARM (Red). (Acc Crit)

[19]

INSTALL fuse F1 in 2-PX-90-274 LWR INS CNTMT POST ACD AREA MON PWR SUPPLY located inside MCR Panel 2-M-30.

Cv

WBN RADIATION MONITORS-AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 106 of 117 Data Package: Page of Date 6.8 2-LPR-90-274, CNTMT POST ACC HIGH RAD (continued)

[20]

PRESS the [CLR] button on the front panel of 2-RM-90-274, AND VERIFY the green OPERATE is ON. (Acc Crit)

[21]

VERIFY the following:

A.

2-XA-55-30/256-B, LOWER CNTMNT RE-273/274 RAD HI, CLEARS. (Acc Crit)

B.

0-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, CLEARS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-274-B) is in NORMAL (Blue). (Acc Crit)

[22]

RECORD the following ambient dose rate indications:

Device Indication Initials/date 2-RM-90-274 LWR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

RJHR R9021A ICS Point for 2-RE-90-274 R/HR

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 107 of 117 Data Package: Page

-of Date 6.8 2-LPR-90-274, CNTMT POST ACC HIGH RAD (continued)

ALARA The radioactive source hung by 2-SI-90-4, 18 Mo Ch Source Cal CNTMT LWR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-274, has a high dose potential. Actions to reduce dose must be taken during performance of steps 6.8[22] through 6.8[24.2].

NOTE Steps 6.8[22] through 6.8[24.2] are to be performed after 2-SI-90-4, 18 Mo Ch Source Cal CNTMT LWR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-274, has hung the calibration source in 2-RE-90-274.

[23]

RECORD the following source response indications:

Device Indication Initials/date 2-RM-90-274 LWR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

R/HR R9021A ICS Point for 2-RE-90-274 (Acc Crit)

R/HR

[24]

PERFORM the following radiation response verifications:

[24.1]

VERIFY the following local and main control room alarms actuated.

A.

2-RM-90-274 yellow ALERT (1) light is ON.

(Acc Crit)

B.

2-RM-90-274 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/256-B, LOWER CNTMNT RE-273/274 RAD HI, is in ALARM. (Acc Crit)

Data Package: Page

-of Date 6.8 2-LPR-90-274, CNTMT POST ACC HIGH RAD (continued)

[24.2]

PRESS the [CLR] button on 2-RM-90-274, AND VERIFY the following: (Acc Crit)

A.

2-RM-90-274 yellow ALERT (1) light is ON.

(Acc Crit)

B.

2-RM-90-274 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/256-B, LOWER CNTMNT RE-273/274 RAD HI, is in ALARM. (Acc Crit)

NOTE The remainder of subsection 6.8 is to be performed after 2-SI-90-4, 18 Mo Ch Source Cal CNTMT LWR COMPT HR Post Accident ARM Train B Loop 2-LPR-90-274, has removed the calibration source from 2-RE-90-274.

[25]

PERFORM the following radiation response verifications:

[25.1]

RECORD the following ambient dose rate indications, AND VERIFY ambient dose rates are similar to those recorded in step 6.8[22].

Device Indication Initials/date 2-RM-90-274 LWR INS CNTMT POST ACD AREA MON (MCR Panel 2-M-30)

R/HR R9021A ICS Point for 2-RE-90-274 R/HR

Data Package: Page of Date 6.8 2-LPR-90-274, CNTMT POST ACC HIGH RAD (continued)

[25.2)

VERIFY the local and main control room alarms and annunciators actuate as follows:

A.

2-RM-90-274 yellow ALERT (1) light is ON.

(Acc Crit)

B. 2-RM-90-274 red HIGH (2) light is ON. (Acc Crit)

C.

2-XA-55-30/256-B, LOWER CNTMNT RE-273/274 RAD HI, ALARMS. (Acc Crit)

[25.3]

PRESS the [CLR] button on 2-RM-90-274, AND VERIFY the following: (Acc Crit)

A.

2-RM-90-274 yellow ALERT (1) light is OFF.

(Acc Crit)

B.

2-RM-90-274 red HIGH (2) light is OFF. (Acc Crit)

C.

2-XA-55-30/256-B, LOWER CNTMNT RE-273/274 RAD HI, CLEARS. (Acc Crit)

[25.4]

COMPARE the source response recorded in step 6.8[23] to the ambient reading recorded in step 6.8[22]

for each device, AND VERIFY each device exhibited an increased deflection above background once exposed to the calibration source.

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 110 of 117 Data Package: Page

-of Date 6.8 2-LPR-90-274, CNTMT POST ACC HIGH RAD (continued)

NOTE When the RM-1 000 is in the OPERATE mode the checksource function will clear after one minute so recording of response values needs to be completed within that time period or the sequence will have to be repeated.

[26]

PERFORM the following Check Source response verifications.

[26.1]

PRESS the [FUN], [2], [ENT] buttons on 2-RM-90-274 LWR INS CNTMT POST ACD AREA MON (Panel 2-M-30) to actuate the CHKSRC function.

NOTE The RM-1000 meter responds to a checksource test by displaying the ambient reading on the left side of the scale and the checksource response on the right side of the scale with the checksource response value indicated at the bottom along with the function description "CHKSRC".

[26.2]

VERFIY the indication on 2-RM-90-274 shows a two level response with the left indication lower than the right indication. (Acc Crit)

[26.3]

VERIFY the main control room alarms as follows:

(Acc Crit)

A.

2-RM-90-274 yellow ALERT (1) light is OFF.

B.

2-RM-90-274 red HIGH (2) light is OFF.

[26.4]

WHEN at least one minute has elapsed from the time the CHKSRC function actuated, THEN VERIFY the indication on 2-RM-90-274 LWR INS CNTMT POST ACD AREA MON (Panel 2-M-30) indicates a dose rate similar to the one recorded in step 6.8[25.1].

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 111 of 117 Data Package: Page

-of Date 6.8 2-LPR-90-274, CNTMT POST ACC HIGH RAD (continued)

[27]

WHEN the Loss of Counts Setup portion of 2-SI-90-4 has been completed,

THEN, VERIFY the following (actions should occur within approximately two minutes after 2-SI-90-4 has set the Discriminator Voltage to 1OVdc): (Acc Crit)

A.

The green OPERATE light is OFF (On the front panel of 2-RM-90-274). (Acc Crit)

B.

O-XA-55-12D/191-E, PAS MON PNL 2M30/31 INSTR MALF, ALARMS. (Acc Crit)

C.

Unit 2 Event Display Monitor indicates 191-E UPPER CNTMT PAS MON INSTR MALF (2-RM-90-274-B) is in ALARM (Red). (Acc Crit)

Data Package: Page

-ofa Date 7.0 POST PERFORMANCE ACTIVITY NOTES

1)

Post-performance steps may be performed in any order unless otherwise stated and should be completed as close in time as practicable to the end of the instruction performance.

2)

If no M&TE is used, then Step 7.0[7] is N/A.

[1]

VERIFY 2-IMI-090.021 has returned the setpoints of 2-RM-90-2 back to normal.

[2]

VERIFY 2-SI-90-1 has returned the setpoints of 2-RM-90-271 back to normal.

[3]

VERIFY 2-SI-90-2 has returned the setpoints of 2-RM-90-272 back to normal.

[4]

VERIFY 2-SI-90-3 has returned the setpoints of 2-RM-90-273 back to normal.

[5]

VERIFY 2-SI-90-4 has returned the setpoints of 2-RM-90-274 back to normal.

[6]

NOTIFY the Unit 2 US/SRO of the test completion and system alignment.

[7]

VERIFY that Post-test calibration of the M&TE used to record quantitative acceptance criteria has been satisfactorily performed, AND RECORD the results on Measuring and Test Equipment (M&TE) Log.

CV

Data Package: Page

. of Date 7.0 POST PERFORMANCE ACTIVITY (continued)

[8]

VERIFY that Post-test calibration of permanent plant instruments used to record quantitative acceptance criteria has been satisfactorily performed AND RECORD the results on Appendix C, Permanent Plant Instrumentation Log.

CV

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 114 of 117 Data Package: Page

-of Date 8.0 RECORDS A.

QA Records Completed Test Package B.

Non-QA Records None

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 115 of 117 Appendix A (Page 1 of 1)

TEST PROCEDURE/INSTRUCTION REFERENCE REVIEW Data Package: Page of Date Additional copies of this table may be made as necessary.

PROCEDURE/

INITIAL AND DATE.

INSTRUCTION REVISION/CHANGES (N/A for no change)

FSAR Section 12.3.4 Section 14.2.12 Table 12.3-4 Table 12.3-5 Table 14.2-1 Sht 33 of 89 2-TSD-90-6 2-IMI-90.020 2-IMI-90.021 2-SI-90-1 2-SI-90-2 2-SI-90-3 2-SI-90-4 WBN-V'M-G292-0400 WBN-VTD-G292-2030 [Later]

(review against SQN-VTD-G063-0460)

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 116 of 117 Appendix B (Page 1 of 1)

TEMPORARY CONDITION LOG Data Package: Page.

of Date Additional copies of this table may be made as necessary.

ITEM TEMPORARY CONDITION PERFORMED RETURNED TO NORMAL No.

DESCRIPTION Step Performed By/Date Step Returned By/Date No.

CV By/Date No.

CV By/Date

WBN RADIATION MONITORS - AREA DOSE 2-PTI-090-01 Unit 2 RATE Rev. 0000 Page 117 of 117 Appendix C (Page 1 of 1)

PERMANENT PLANT INSTRUMENTATION LOG Data Package: Page of Date INSTRUMENT OR CAL DUE FILLED AND PLACED IN USED FOR POST-TEST POST-TEST INSTRUMENT LOOP #

DATE VENTED1 SERVICE1 QUANTITATIV CAL DATE 2 CALIBRATION SUBSECTION E ACC CRIT ACCEPTABLE 2 INITIALIDATE INITIDATE INITIDATE YES NO 2-LPR-90-2/6.1 2-LPR-90-59/6.2 2-LPR-90-60/6.3 2-LPR-90-61/6.4 2-LPR-90-271/6.5 2-LPR-90-272/6.6 2-LPR-90-273/6.7 2-LPR-90-274/6.8 These items may be initialed and dated by personnel performing the task. Instrumentation not required to be filled and vented may be identified as Not Applicable. (N/A) 2 May be identified as Not Applicable (N/A) if instrument was not used to verify/record quantitative acceptance criteria data.