7/12/11 - Summary of Teleconference with Nebraska Public Power District to Discuss Coopers Request to Revise TS 3.4.3, Safety/Relief Valves (Srvs) and Safety Valves (Svs) at Cooper Nuclear Station
ML112170081
Person / Time
Site: Cooper 
(DPR-046)
Issue date: 08/18/2011
From: Lynnea Wilkins
Plant Licensing Branch IV
To:
Nebraska Public Power District (NPPD)
Wilkins, L E, NRR/DORL/LPL4, 415-1377
References
TAC ME5287
Download: ML112170081 (4)


Text

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 August 18, 2011 LICENSEE:

Nebraska Public Power District FACILITY:

Cooper Nuclear Station

SUBJECT:

SUMMARY

OF MEETING HELD ON JULY 12, 2011, WITH NEBRASKA PUBLIC POWER DISTRICT TO DISCUSS LICENSE AMENDMENT REQUEST TO REDUCE THE NUMBER OF SAFETY RELIEF VALVES AND SAFETY VALVES AT COOPER NUCLEAR STATION (TAC NO. ME5287)

On July 12, 2011, a Category 1 public meeting was held between the U.S. Nuclear Regulatory Commission (NRC) and representatives of Nebraska Public Power District (NPPD, the licensee) at NRC Headquarters, One White Flint North, 11555 Rockville Pike, Rockville, Maryland. The purpose of the meeting was to discuss NPPD's license amendment request (LAR) for Cooper Nuclear Station (CNS) dated January 5, 2011 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML110100291). The proposed amendment would revise Technical Specification (TS) 3.4.3, "Safety/Relief Valves (SRVs) and Safety Valves (SVs)," to reduce the number of SRVs required to be OPERABLE for over-pressure protection from eight to five.

The licensee's presentation slides are available in the Agencywide Documents Access and Management System (ADAMS) under ADAMS Accession No. ML112140179. The licensee addressed the NRC staff's request for additional information dated June 3, 2011 (ADAMS Accession No. ML111430704).

The licensee presented additional background information including the need for the LAR. The licensee stated that the limiting condition for operation (LCO) is more restrictive than necessary to meet SRV safety and support functions for overpressure protection or anticipated transient without scram. The licensee stated that, if relaxed, the LCO would provide operational flexibility to avoid an unnecessary plant shutdown. The licensee also stated that these valves have not previously caused a plant shutdown; however, the licensee noticed other plants have had issues with corrosion binding. The licensee also stated that evaluations would still be performed for functional failures of these valves.

The NRC staff questioned how reducing the number of required SRVs would affect the heat load on the suppression pool. The licensee stated that the suppression pool loads are bounded by the CNS Loss of Coolant Accident analysis values. The licensee also stated that localized heating was taken into account in the evaluations.

The licensee informed the NRC staff that it would submit a revision to the LAR adding a detailed justification on why the reduction in margin is not significant.

- 2 The meeting notice and agenda are available under ADAMS Accession No. ML111330643.

The public was invited to observe the meeting and was given an opportunity to communicate with the NRC after the business portion, but before the meeting was adjourned. No members of the public were present. No Public Meeting Feedback forms were received.

Please direct any inquiries to me at 301-4~1~.gov.

Lynnea Wilkins, Project Manager Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-298

Enclosure:

List of Attendees cc w/encl: Distribution via Listserv

LIST OF ATTENDEES U.S. NUCLEAR REGULATORY COMMISSION JULY 12. 2011. PUBLIC MEETING WITH NEBRASKA PUBLIC POWER DISTRICT REGARDING LICENSE AMENDMENT REQUEST FOR COOPER NUCLEAR STATION DOCKET NO. 50-298 Name Organization Lynnea Wilkins NRC/NRR/DORLlLPL4 Arthur Zaremba Nebraska Public Power District Edward Holcomb Nebraska Public Power District Gerald Horn Nebraska Public Power District Frank Kerner Nebraska Public Power District Edward McCutchen Nebraska Public Power District Anthony Ulses NRC/NRR/DSS/SRXB George Wilson NRC/NRR/DE/EICB Joshua Miller NRC/NRR/DSS/SRXB Michael Markley NRC/NRR/DORLlLPL4 Donnie Harrison NRC/NRR/DRA/APLA Andrew Howe NRC/NRR/DRA/APLA Abbreviations:

NRC - U.S. Nuclear Regulatory Commission NRR - Office of Nuclear Reactor Regulation DE - Division of Engineering DORL - Division of Operating Reactor Licensing DRA - Division of Risk Assessment DSS - Division of Safety Systems EICB -Instrumentation and Controls Branch SRXB - Reactor System Branch APLA - PRA Licensing Branch Enclosure

- 2 The meeting notice and agenda are available under ADAMS Accession No. ML111330643.

The public was invited to observe the meeting and was given an opportunity to communicate with the NRC after the business portion, but before the meeting was adjourned. No members of the public were present. No Public Meeting Feedback forms were received.

Please direct any inquiries to me at 301-415-1377 or Lynnea.Wilkins@nrc.gov.

Ira!

Lynnea Wilkins, Project Manager Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-298

Enclosure:

List of Attendees cc w/encl: Distribution via Listserv DISTRIBUTION:

PUBLIC RidsNrrLAJBurkhardt Resource LPLIV r/f RidsOgcRp Resource RidsAcrsAcnw_MailCTR Resource RidsRgn4MailCenter Resource RidsNrrDprPgcb Resource RidsOpaMail Resource RidsNrrDraApla Resource JMiller, NRRlDSS/SRXB RidsNrrDssSrxb Resource AHowe, NRR/DRAIAPLA RidsNrrDeEicb Resource CSteger, NRR RidsNrrDorl Resource

~ITrapp, EDO RIV Ridsl\\lrrDorlLpl4 Resource VDricks, OPA RIV RidsNrrPMCooper Resource ADAMS Accession Nos. Meeting Notice ML111810085, Meeting Summary ML112170081, Handouts ML111430704 DORULPL4/LA DORULPL4/PM SRXB/BC NRR/DE/EICB/BC LWilkins JBurkhardt GWilson 8/9/11 8/8/11 8/16111 8/9/11 NRR/DRNAPLAlBC DORULPL4/BC DORULPL4/PM MMarkley (MThadani for)

LWilkins DHarrison 8/11/11 8/18/11 8/18/11 OFFICIAL RECORD COpy