Part 21 Notification of Valve Failed Leak Test Due to a Disc/Shaft Assembly Machining Issue
ML11193A007
Person / Time
Site: Palo Verde  Arizona Public Service icon.png
Issue date: 07/09/2011
From: Crosser T
Emerson Process Management
To:
Office of Nuclear Reactor Regulation
References
47036
Download: ML11193A007 (4)


Text

07/09/2011 Part 21 (PAR)

U.S. Nuclear Regulatory Commission Operations Center Event Report Paze I Event#

47036 Rep Org: EMERSON PROCESS MANAGEMENT Notification Date / Time: 07/08/2011 14:24 (EDT)

Supplier: EMERSON PROCESS MANAGEMENT Event Date / Time: 05/13/2011 (CDT)

Last Modification: 07/08/2011 Region:

3 Docket #:

City: MARSHALLTOWN Agreement State:

Yes County:

License #:

State: IA NRC Notified by: TRISH CROSSER Notifications:

DAVID HILLS R3DO HQ Ops Officer: VINCE KLCO BOB HAGAR R4DO Emergency Class: NON EMERGENCY PART 21 GRP 10 CFR Section:

21.21 UNSPECIFIED PARAGRAPH VALVE FAILED LEAK TEST DUE TO A DISC/SHAFT ASSEMBLY MACHINING ISSUE The following information was received by facsimile:

"After a valve failed a leak test, it was determined that a fixture to machine the valve disc was missing one of the locating pins that maintained the integrity of the shaft bore centerline when machining. It was determined that the pin was missing from the fixture from January 8, 2011, to April 7, 2011 "Fisher has conducted a review and determined that the only ASME Section III code and commercial grade dedicated parts machined during this time that would use this fixture were the parts used for the orders referenced

[below].

"Fisher Controls has implemented a corrective action program to address this issue.

"Although this notice is dated July 5, 2011, Palo Verde was officially notified May 13, 2011, when Fisher first became aware of this issue. In the mean time, all affected discs have been returned to Fisher Controls for evaluation.

Subject:

NPS 16 Type Al1 Disc/Shaft Assemblies for Palo Verde Orders 500541604 and 500548617 (Fisher Orders 019-F514977 and 019-F515346)."

4s EMERSON Process MainagemeAt (FISER Facsimile 301 South Firsi Ave Marshalltown, IA 50158 T

F NRC To: Vernon Hodge Fax: 301-816-5151 Trish Crosser Executive Assistant From: For QA Director NA Date: 7/8/2011 Pages: 1 (inl cover)

Attached is a copy of Emerson Process Management - Fisher Division's Nuclear FIN Notice (FIN 2011-02) to be distributed today to our Nuclear Customers via Certified Mail.

Any questions or concern, do not hesitate to give me a call.

TrIsh Crosser I Executive Assistant I FishAr Division Emerson Procesa Management j301 S. 1st Avenue I Marshalltown, Iowa 50158 I USA T +1 641.754.2688 I F +1 641,754.2688 Trish.Crosser@Emersoncom

4 EMERSON.

Fisher Controls Internatlonal LLC Process Management 301 South First Ave.

P.O. Box 190 Marshalltown, Iowa 50158-0190 USA T (641) 754-3011 F (641) 754-2830 Fisher Information Notice: FIN 2011-02 July 5, 2011

Subject:

NPS 16 Type All Disc/Shaft Assemblies for Palo Verde Orders 500541604 and 500548617 (Fisher Orders 019--F514977 and 019-F515346)

From:

Bill Fitzgerald Vice President, Nuclear Business Unit Fisher Controls International LLC 301 South First Avenue Marshalltown, IA 50158 Fax: (641) 754-2854 Equipment Affected By This Information Notice:

Quantity four (4) Disc/Shaft Assemblies, Part Number GE47935X012 provided to APS - Palo Verde Nuclear Generating Station per Palo Verde Orders 500541604 and 500548617 (Fisher Orders 019-F514977 Items 0001 and 0002 and 019-F515346 Item 000)1.

Purpose:

The purpose of this Fisher Information Notice (FIN) is to alert APS that as of May 13, 2011, Fisher Controls International LLC became aware of the possibility of a situation, which may affect the performance of the applicable equipment.

We are informing you of this circumstance in accordance with Section 21.21(b) of 10CFR Part 21.

Applic~ability:

This notice applies only to the subject equipment supplied by Fisher Controls International LLC, identified above, that was provided to APS - Palo Verde Nuclear Generating Station.

FISHER]

Page 1 of 2

Fisher Information Notice: FIN 2011-02 Discussion:

After a valve failed a leak test, it was determined that a fixture to machine the valve disc was missing one of the locating pins that maintained the integrity of the shaft bore centerline when machining. It was determined that the pin was missing from the fixture from January 8, 2011, to April 7, 2011.

Fisher has conducted a review and determined that the only ASME Section III code and commercial grade dedicated parts machined during this time that would use this fixture were the parts used for the orders referenced above.

Fisher Controls has implemented a corrective action program to address this issue.

Although this notice is dated July 5, 2011, Palo Verde was officially notified May 13, 2011, when Fisher first became aware of this issue. In the mean time, all affected discs have -been returned to Fisher Controls for evaluation.

Action Required No action is required.

IOCFR21 Implications:

Fisher Controls requests that the recipient of this notice review it and take appropriate action in accordance with 10CFR Part 21.

If there are any technical questions or concerns, please contact:

George Baitinger Manager, Quality Fisher Controls International LLC 301 South First Avenue Marshalltown, IA 50158 Fax: (641) 754-2854 Phone: (641) 754-2026 George. Baitinger@Emerson.com (FISHER]

Page 2 of 2