Submittal of Pre-Op Test Instruction, 2-PTI-030H-01, Rev. 0, Lower Compartment Coolers
ML11111A122
Person / Time
Site: Watts Bar 
Issue date: 04/19/2011
From: Stinson D
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
2-PTI-030H-01, Rev. 0
Download: ML11111A122 (145)


Text

Tennessee Valley Authority, Post Office Box 2000, Spring City, Tennessee 37381-2000 April 19, 2011 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555-0001 Watts Bar Nuclear Plant, Unit 2 NRC Docket No. 50-391

Subject:

Watts Bar Nuclear Plant (WBN) Unit 2 - Submittal of Pre-op Test Instruction The following approved WBN Unit 2 Pre-op Test Instruction (PTI) is enclosed:

PTI NUMBER Rev.

TITLE 2-PTI-030H-01 0

Lower Compartment Coolers If you have any questions, please contact Pete Olson at (423) 365-3294.

Respectfully, David Stinson Watts Bar Unit 2 Vice President Enclosure cc (Enclosure):

U. S. Nuclear Regulatory Commission Region II Marquis One Tower 245 Peachtree Center Ave., NE Suite 1200 Atlanta, Georgia 30303-1257 NRC Resident Inspector Unit 2 Watts Bar Nuclear Plant 1260 Nuclear Plant Road Spring City, Tennessee 37381 7NeL

WATTS BAR NUCLEAR PLANT UNIT 2 PREOPERATIONAL TEST TITLE:

Lower Compartment Coolers Instruction No: 2-PTI-030H-01 Revision No:

0000 PREPARED BY:

Keith Jones

[16-k DATE:

0 -

PRINT NAME I SIGNATURE REVIEWED BY:

Bethany Merriman I9 A'

DATE:

PRINT NAAE rsi 6AT'URE INSTRUCTION APPROVAL JTG MEETING al:

0-I bg JTG CHAIRMA DATE:

APPROVED BY: ~AVIDATE:

PREOPERATIONAL STARTUP MANAGER TEST RESULTS APPROVAL JTG MEETING No:

JTG CHAIRMAN:

DATE:

APPROVED BY:

DATE:

PREOPERATIONAL STARTUP MANAGER SMP-8.0 R7 Administration of Preoperational Test instructions, Appendix B

Revision Log Revision Affected or Change Effective Page Number Date Numbers Description of Revision/Change 0000 DIilf-,1 (

ALL This procedure is written using the Unit 1 PTI-030J-01 Rev 0 as a guide.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 3 of 144 Table of Contents

1.0 INTRODUCTION

5 1.1 Test Objectives........................................................................................................

5 1.2 S c o p e............................................................................................................................

5

2.0 REFERENCES

7 2.1 Performance References.........................................................................................

7 2.2 Developmental References.......................................................................................

7 3.0 PRECAUTIONS AND LIMITATIONS.....................................................................

12 4.0 PREREQUISITE ACTIONS....................................................................................

14 4.1 Preliminary Actions..................................................................................................

14 4.2 Special Tools, Measuring and Test Equipment, Parts, and Supplies.......................

17 4.3 Field Preparations..................................................................................................

18 4.4 Approvals and Notifications....................................................................................

24 5.0 ACCEPTANCE CRITERIA....................................................................................

25 6.0 PERFORMANCE........................................................................................................

31 6.1 Lower Compartment Cooler Logic Test.................................................................

32 6.1.1 Lower Compartment Cooler 2A-A Logic...................................................

32 6.1.2 Lower Compartment Cooler 2B-B Logic....................................................

45 6.1.3 Lower Compartment Cooler 2C-A Logic..................................................

58 6.1.4 Lower Compartment Cooler 2D-B Logic..................................................

71 6.2 Lower Compartment Coolers Response to Phase B Containment Isolation Signal......................................................................................................

84 6.2.1 Train A Lower Compartment Coolers (2A-A and 2C-A) 2........................... 84 6.2.2 Train B Lower Compartment Coolers (2B-B and 2D-B)............................

88 6.3 Lower Compartment Coolers Response to Bus Undervoltage................................

92 6.3.1 Lower Compartment Cooler 2A-A.............................................................

92 6.3.2 Lower Compartment Cooler 2B-B.............................................................

95 6.3.3 Lower Compartment Cooler 2C-A.............................................................

98 6.3.4 Lower Compartment Cooler 2D-B...............................................................

101

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 4 of 144 Table of Contents (continued) 6.4 Lower Compartment Coolers Auto-Start on Low Air Flow.........................................

104 6.5 Lower Compartment Cooler Performance................................................................

114 7.0 POST PERFORMANCE ACTIVITY..........................................................................

123 8.0 R EC O R D S................................................................................................................

123 Appendix A:

TEST PROCEDURES/INSTRUCTIONS REFERENCE R EV IEW...................................................................................................

124 Appendix B:

TEMPORARY CONDITION LOG.............................................................

125 Appendix C:

PERMANENT PLANT INSTRUMENTATION LOG..................................

126 Appendix D:

ELECTRICAL LINEUP.............................................................................

128 Appendix E:

Background Calculations.......................................................................

132 Data Sheet 1:

Lower Compartment Cooler 2A-A Performance..................................

137 Data Sheet 2:

Lower Compartment Cooler 2B-B Performance..................................

139 Data Sheet 3:

Lower Compartment Cooler 2C-A Performance..................................

141 Data Sheet 4:

Lower Compartment Cooler 2D-B Performance..................................

143

Data Package: Page of Date

1.0 INTRODUCTION

1.1 Test Objectives A.

Demonstrate the proper operation of the Reactor Building Lower Compartment Cooling Units.

B.

Demonstrate the proper operation of the Essential Raw Cooling Water (ERCW) control valves associated with each Lower Compartment Cooler (LCC).

1.2 Scope NOTES

1) 2-PTI-030L-01, HFT Containment Temperature Survey, will demonstrate the Lower Compartment Coolers' ability to maintain design temperatures.
2)

ERCW flowrates are verified during performance of 2-PTI-067-02-A and 2-PTI-067-02-B, ERCW System Flow Balance Train A and Train B.

3)

ERCW Temperature Control Valves' logic is tested during performance of 2-PTI-067-03, ERCW Valve Logic Test.

4)

System vibration testing will be performed during performance of GTM-05, HVAC Air Balance for this system.

This test demonstrates the operability of the Unit 2 Lower Compartment Coolers to ensure the following:

A.

The LCC Units operate correctly from their respective handswitches in the Main Control Room and on the 480V Shutdown Boards, and their indicating lights indicate correct status.

B.

Each LCC Unit stops on a simulated Phase B Containment Isolation Signal, and remains off when the signal is reset C.

Each LCC Unit stops on a simulated Bus Undervoltage condition (Loss of Offsite Power).

D.

The air inlet and outlet temperatures for each LCC can be monitored on the Plant Computer System.

E.

LCC Units' backdraft dampers open and close upon start and stop of their respective LCC.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 6 of 144 1.2 Data Package: Page _

of Date Scope (continued)

F.

The LCC Units maintain design air flows.

G.

The LCC Units will operate correctly during accident conditions.

H. Each ERCW control valve modulates open upon start and closes upon stop of its associated LCC.

1.

The following features function only when the LCC Units' Transfer Switch is in AUX:

1.

Each LCC Unit can be started manually while a simulated Phase B Containment Isolation Signal is present.

2.

Each LCC Unit restarts after a time delay when a simulated Loss of Offsite Power (LOOP) is restored.

3.

Each LCC unit starts on low flow condition from any other LCC to maintain 3 of 4 coolers in operation.

Data Package: Page _

of Date

2.0 REFERENCES

2.1 Performance References A.

SMP-9.0, Conduct of Test B.

GTM-05, HVAC Air Balance C.

0-SOI-67.01, Essential Raw Cooling Water System D.

2-SOI-30.03, Containment HVAC and Pressure Control 2.2 Developmental References A.

Final Safety Analysis Report, Amendment 102

1. Section 9.2.1, Essential Raw Cooling Water (ERCW)
2.

Section 9.4.7, Containment Air Cooling System

3.

Table 14.2-1, Sheets 4 & 5, Essential Raw Cooling Water System Test Summary

4.

Table 14.2-1, Sheets 38 & 39, Containment Ventilation System Test Summary B.

Drawings

1.

Flow Diagrams

a.

2-47W866-1, Rev 2, HEATING AND VENTILATION AIR FLOW DRA 52861-06, Rev 0 DRA 52861-15, Rev 0 DRA 52861-16, Rev 0 DRA 52861-17, Rev 0 DRA 54923-42, Rev 0 DRA 54923-43, Rev 0

b.

2-47W845-3, Rev 1, ESSENTIAL RAW COOLING WATER

2.2 WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 8 of 144 Data Package: Page _

of Date Developmental References (continued)

2.

Electrical

a.

2-45W760-30-9, Rev 1, VENTILATING SYSTEM SCHEMATIC DIAGRAMS

b.

2-45W760-30-10, Rev 1, VENTILATING SYSTEM SCHEMATIC DIAGRAMS

c.

45W760-30-21, Rev 11, VENTILATING SYSTEM SCHEMATIC DIAGRAMS

d.

45W760-55-1, Rev 6, ANNUNCIATOR SYSTEM SCHEMATIC DIAGRAMS

e.

45W760-55-2, Rev 7, ANNUNCIATOR SYSTEM SCHEMATIC DIAGRAMS DRA 52639-76, Rev 0

f.

2-45W600-57-9, Rev 0, SEPARATION & MISC AUX RELAYS SCHEMATIC DIAGRAMS

g.

2-45W600-57-18, Rev 1, SEPARATION & MISC AUX RELAYS SCHEMATIC DIAGRAMS

h.

2-45W600-57-20, Rev 0, SEPARATION MISC AUX RELAYS SCHEMATIC DIAGRAMS

i.

2-45W600-57-21, Rev 0, SEPARATION & MISC AUX RELAYS SCHEMATIC DIAGRAMS

j.

2-45W600-67-1, Rev 0, ESSENTIAL RAW COOLING WATER SYS SCHEMATIC DIAGRAM

k.

2-45W600-67-2, Rev 0, ESSENTIAL RAW COOLING WATER SCHEMATIC DIAGRAM

1.

1-45W760-212-4, Rev 16,480V SHUTDOWN POWER SCHEMATIC DIAGRAMS

m.

2-45W749-1, Rev 1, 480V SHUTDOWN BD 2A1-A SINGLE LINE DRA 54172-01, Rev 0

n.

2-45W749-2, Rev 1, 480V SHUTDOWN BD 2A2-A SINGLE LINE DRA 54172-02, Rev 0

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 9 of 144 Data Package: Page of Date 2.2 Developmental References (continued)

o.

2-45W749-3, Rev 1, 480V SHUTDOWN BD 2B1-B SINGLE LINE DRA 54172-03, Rev 0

p.

2-45W749-4, Rev 2, 480V SHUTDOWN BD 2B2-B SINGLE LINE DRA 54172-04, Rev 0

q.

45N2676-4, Rev 16, SOLID STATE PROTECTION SYS TRAIN A CONNECTION DIAGRAM

r.

45N2677-4, Rev 18, SOLID STATE PROTECTION SYS TRAIN B CONNECTION DIAGRAM

s.

6947D02 (AC), Rev G, LVME 'DS' SWGR 480V 3PH 60HZ SUBSTATION INTERNALS

t.

618F938, Rev 913, LVME 'DS' SWGR 480V SHUTDOWN BD 2A1-A 480V 3PH 60HZ SUBSTATION CONN DIAG UNIT 6

u.

6947D67, Rev 915, LVME 'DS' SWGR 480V SHUTDOWN BD 2A2-A 480V 3PH 60HZ SUBSTATION CONN DIAG UNIT 6

v.

618F941, Rev 913 LVME 'DS' SWGR 480V SHUTDOWN BD 2B1-B 480V 30 60HZ SUBSTATION CONN DIAG UNIT 6

w.

6947D85, Rev 915, LVME 'DS' SWGR 480V SHUTDOWN BD 2B2-B 480V 30 60HZ SUBSTATION CONN DIAG UNIT 6

3.

Logic/Control

a.

2-47W610-30-2, Rev 1, CONTROL DIAGRAM VENTILATION SYSTEM DRA 54172-283, Rev 0 DRA 54172-284, Rev 0 DRA 54172-285, Rev 0 DRA 54172-286, Rev 0

b.

2-47W611-30-4, Rev 1, LOGIC DIAGRAM VENTILATION SYSTEM DRA 53788-032, Rev 0 DRA 54172-281, Rev 0

c.

2-47W610-67-2, Rev 1, CONTROL DIAGRAM ERCW SYSTEM

d.

2-47W611-67-3, Rev 1, LOGIC DIAGRAM ESSENTIAL RAW COOLING WATER

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 10 of 144 2.2 Data Package: Page of Developmental References (continued)

4.

Other Date

a.

2-47W600-171, Rev 0, ELECTRICAL INSTRUMENTS AND CONTROLS DRA 53630-04, Rev 0 DRA 53630-46, Rev 1

b.

2-47B601-55-1, ELECTRICAL INSTRUMENT TABULATION, [Later]

DRA 52453-04, Rev 0

c.

2-47B601-55-2, ELECTRICAL INSTRUMENT TABULATION, [Later]

DRA 52453-05, Rev 0

d.

2-47B601-55-3, ELECTRICAL INSTRUMENT TABULATION, [Later]

DRA 52453-06, Rev 0

e.

2-47B601-55-4, ELECTRICAL INSTRUMENT TABULATION, [Later]

DRA 52453-07, Rev 0

f.

2-45B655-5C, Rev 0, ANNUNCIATOR INPUTS WINDOW BOX XA-55-5C

g.

2-45B655-E5C, Rev 0. ANNUNCIATOR WINDOW BOX XA-55-5C ENGRAVING

h.

2-45B655-6E, Rev 0, ANNUNCIATOR INPUTS WINDOW BOX XA-55-6E DCA 52630-91, Rev 0

i.

2-45B655-E6E, Rev 0. ANNUNCIATOR WINDOW BOX XA-55-6E ENGRAVING

j.

2-45B655-6F, Rev 0, ANNUNCIATOR INPUTS WINDOW BOX XA-55-6F DCA 52630-92, Rev 0

k.

2-45B655-E6F, Rev 0. ANNUNCIATOR WINDOW BOX XA-55-6F ENGRAVING

5.

Vendor Manuals

a.

VM-F180-3066, Rev 0, Foxboro Instruction Book 3473 743CB Field Station Micro Controller

Data Package: Page of Date 2.2 Developmental References (continued)

C.

Documents

1.

GTM-05, HVAC Air Balance (Draft)

2.

WBN2-30RB-4002, Rev 1, Reactor Building Ventilation System

3.

G-37, Rev 4, Testing and Balancing of HVAC Systems During Installation, Modification, and Maintenance

4.

2-TSD-30H-1, Rev 1, Containment Air Cooling System -

Lower Compartment Coolers

5.

2-PTI-030L-01, HFT Containment Temperature Survey (Draft)

6.

2-PTI-067-02-A, Rev 0, ERCW System Flow Balance - Train A

7.

2-PTI-067-02-B, Rev 0, ERCW System Flow Balance - Train B

8.

2-PTI-067-03, ERCW Valve Logic Test (Draft)

9.

MI-57.002, Rev 39, Westinghouse DS Circuit Breaker Routine Maintenance, Inspection and Testing

10. SSD-2-LPT-67-84, Rev 0, Lower Cntmt Vent Cooler A Temp
11.

SSD-2-LPT-67-1 00, Rev 0, Lower Cntmt Vent Cooler B Temp

12. SSD-2-LPT-67-92, Rev 0, Lower Cntmt Vent Cooler C Temp
13. SSD-2-LPT-67-108, Rev 0, Lower Cntmt Vent Cooler D Temp

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 12 of 144 Data Package: Page of Date 3.0 PRECAUTIONS AND LIMITATIONS A.

Standard precautions shall be followed for working around energized electrical equipment in accordance with TVA Safety Procedure 1021.

B.

Steps may be repeated if all components cannot be tested in a step. However, if the test has been exited, prerequisite steps must be re-verified and a Chronological Test Log (CTL) entry made.

C.

Discrepancies between component ID tags and the description in a procedure/instruction if the UNIDs match, exclusive of place keeping zeros and train designators (e.g.; 2-HS-31-468 vs. 2-HS-031-0468) and the noun description is sufficient to identify the component. This condition does not require a TDN in accordance SMP-14.0.

If the component label needs to be changed, a Tag Request Form (TR Card) should be processed in accordance with TI-12.14. Make an entry in the CTL and continue testing.

D.

IF/THEN steps may be marked N/A if stated condition does not exist.

E.

All wires removed/lifted from a terminal shall be identified and taped or covered with an insulator to prevent personnel or equipment hazard and possible spurious initiations. The wires should be grouped together and labeled with the work implementing document number that required them to be lifted if left unattended.

F.

All terminal points and connections are to be considered energized.

Instrumentation must be used to determine if the circuits are de-energized.

G.

Retermination of lifted leads requires that their restored bend radius is equal to or greater than the as-found condition.

H.

LCC Circuit Breakers have Overload Trip Switch (OTS) reset coils. Placing the Handswitch to STOP will energize the OTS Reset Coil and reset the OTS. The OTS Reset Coil should only be energized momentarily; the OTS contact in series with the coil should open to de-energize the coil. To avoid overheating the coil, do not hold Handswitch in STOP if the coil does not de-energize.

1.

When installing fuses with actuators, ensure that the actuating rod is oriented correctly to provide for proper alarm initiation and visual indication.

J.

All open problems are to be tracked by a corrective action document and entered on the appropriate system punchlist.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 13 of 144 Data Package: Page _

of Date 3.0 PRECAUTIONS AND LIMITATIONS (continued)

K. Problems identified during the test shall be annotated on the Chronological Test Log from SMP-9.0, including a description of the problem, the procedure step when/where the problem was identified, corrective action steps taken to resolve the problem, and the number of the corrective action document, if one was required.

L.

Observe all Radiation Protection requirements when working in or near radiological areas.

M. Ensure there are no adverse effects to the operation of Unit 1 structures, systems, or components.

N. Vibration testing of this system is performed during the GTM-05, HVAC Air Balance for this system.

0.

During the performance of this procedure, visual observation of fans and ductwork is required. This includes steady-state and transient operations (fan starts and stops) with visual confirmation that vibration is not excessive.

P.

To verify that transient conditions are not causing excessive vibration, observe components (duct, dampers, fans, etc) during the transient, to the extent practical. If not practical to observe during the transient, verify after the transient that no damage has occurred.

Q.

If the vibration is determined to be excessive, the Test Engineer shall initiate a Test Deficiency Notice.

R.

LCC control switches in the Main Control Room may NOT be placed in PULL A-P AUTO. Auto-start features enabled by this switch position are disabled and are not tested in this instruction.

S.

The Setpoint and Scaling Documents for the Time Delay Relays that cause the LCCs to automatically start after bus voltage is restored (after a Loss of Offsite Power) have been voided and these relays are no longer calibrated. Therefore, their response times will be described as approximately 1 minute in this instruction. Reference EDC 50345 and EDC 50330 for further information.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 14 of 144 Data Package: Page of Date 4.0 PREREQUISITE ACTIONS NOTE Prerequisite steps may be performed in any order, unless otherwise stated, and should be completed as close in time as practicable to the start of the instruction subsection to which they apply.

4.1 Preliminary Actions

[1]

VERIFY the test/performance copy of this Preoperational Test Instruction (PTI) is the current revision and as needed, each test person assisting in this test has the current revision.

[2]

OBTAIN copies of the applicable forms from the latest revision of SMP-9.0, AND ATTACH to this PTI for use during the performance of this PTI.

[3]

ENSURE changes to the references listed on Appendix A have been reviewed and determined NOT to adversely affect the test performance.

[4]

VERIFY current revisions and change paper for referenced drawings have been reviewed and determined NOT to adversely affect the test performance, AND ATTACH documentation of the current drawing revision numbers and change papers that were reviewed to the data package.

[5]

ENSURE components contained within the boundaries of this test are under the jurisdictional control of Preoperational Startup Engineering (PSE) and/or Plant Operations.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 15 of 144 Data Package: Page _

of Date 4.1 Preliminary Actions (continued)

[6]

EVALUATE open items in Watts Bar Integrated Task Equipment List (WITEL), AND ENSURE that they will NOT adversely affect the test performance.

A.

SubSection 6.1 B.

SubSection 6.2 C.

SubSection 6.3 D.

SubSection 6.4 E.

SubSection 6.5

[7]

ENSURE required Component Testing has been completed prior to start of test.

A.

SubSection 6.1 B.

SubSection 6.2 C.

SubSection 6.3 D.

SubSection 6.4 E.

SubSection 6.5

[8]

ENSURE outstanding Design Change Notices (DCNs),

Engineering Document Construction Releases (EDCRs), or Temporary Alterations (TAs) do NOT adversely impact testing, AND ATTACH documentation of DCNs, EDCRs, and TAs that were reviewed to the data package.

[9]

ENSURE GTM-05, HVAC Air Balance, has been submitted to the JTG for concurrence that it adequately satisfies the requirements of this instruction.

JTG Meeting Number:

[10]

ATTACH completed GTM-05, HVAC Air Balance package for system 30H to this instruction.

Data Package: Page _

of Date 4.1 Preliminary Actions (continued)

[11]

ENSURE a review of outstanding Clearances has been coordinated with Unit 2 Operations for impact to the test performance, AND RECORD in Appendix B, Temporary Condition Log if required.

[12]

VERIFY plant instruments required for test performance have been placed in service and are within their calibration interval, AND RECORD on Appendix C, Permanent Plant Instrumentation Log.

A.

SubSection 6.1 B.

SubSection 6.4

[13]

REVIEW preventive maintenance records for equipment within the scope of this test, AND VERIFY no conditions exist that will impact test performance.

A.

SubSection 6.1 B.

SubSection 6.2 C.

SubSection 6.3 D. SubSection 6.4

[14]

PERFORM a pretest walkdown on equipment to be tested to ensure no conditions exist that will impact test performance.

A.

SubSection 6.1 B.

SubSection 6.2 C.

SubSection 6.3 D. SubSection 6.4

[15]

CONDUCT a pretest briefing with Test and Operations personnel in accordance with SMP-9.0.

[16]

ENSURE that communications are available for areas where testing is to be conducted.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 17 of 144 Data Package: Page of Date 4.2 Special Tools, Measuring and Test Equipment, Parts, and Supplies

[1]

ENSURE the following are available:

A.

Switched jumpers [2]

B.

Handheld jumper [1]

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 18 of 144 Data Package: Page of Date 4.3 Field Preparations

[1]

ENSURE the following systems are operable and have been placed in service to the extent necessary to support this test:

A.

System 32, Control Air System B.

System 55, Annunciator and Sequential Events Recording System C.

System 67, Essential Raw Cooling Water System D.

System 99, Reactor Protection System E.

System 212, 480V Shutdown Power F.

System 235, 120V AC Vital Power System G.

System 236, 125V DC Vital Power System H. System 261, Integrated Computer System (ICS)

NOTES

1)

Any Annunciator points associated with 2-MUX-55-12 and 2-MUX-55-13 ONLY have master switches at the bottom of each terminal strip.

2)

All points associated with 2-TBK-55-25, 2-TBK-55-26, 2-TBK-55-27, and 2-TBK-55-28 will not have individual switches or a master switch.

[2]

ENSURE System 55, Annunciator and Sequential Events Recording System, applicable TBK Switches are ON, the applicable Master Switches are ON, and window software input(s) are ENABLED for the following Annunciator Windows:

A.

2-XA-55-5C-1 04A, LWR CNTMT CLR FLOW LO B. 2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT C.

2-XA-55-6F-149B, 480 SD BD 2A1-A/2A2-A/CA VT BD 2A1-A D.

2-XA-55-6F-150B, 480 SD BD 2B1-B/2B2-B/CA VT BD 2B1-B

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 19 of 144 Data Package: Page _

of Date 4.3 Field Preparations (continued)

[3]

ENSURE Essential Raw Cooling Water Temperature Control Valves (TCVs) and Temperature Indicating Controllers (TICs) are available to support test activities.

A.

2-TCV-67-84, LWR CNTMT VENT CLR 2A-A OUT TEMP CNTL (SubSection 6.1.1)

B.

2-TIC-67-84, LOWER CNTMT VENT CLR 2A TEMP CNTL (SubSection 6.1.1)

C.

2-TCV-67-100, LWR CNTMT VENT CLR 2B-B OUT TEMP CNTL (SubSection 6.1.2)

D.

2-TIC-67-100, LOWER CNTMT VENT CLR 2B TEMP CNTL (SubSection 6.1.2)

E.

2-TCV-60-92, LWR CNTMT VENT CLR 2C-A OUT TEMP CNTL (SubSection 6.1.3)

F.

2-TIC-67-92, LOWER CNTMT VENT CLR 2C TEMP CNTL (SubSection 6.1.3)

G.

2-TCV-67-108, LWR CNTMT VENT CLR 2D-B OUT TEMP CNTL (SubSection 6.1.4)

H. 2-TIC-67-108, LOWER CNTMT VENT CLR 2D TEMP CNTL (SubSection 6.1.4)

[4]

ENSURE ERCW system is aligned per 0-SOI-67.01 and/or 2-SOI-30.03, as applicable to support test performance (SubSection 6.1).

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 20 of 144 Data Package: Page of Date 4.3 Field Preparations (continued)

[5]

RECORD the As-Found position of the following ERCW Temperature Indicating Controllers' Auto/Manual (A/M) Status, Setpoints and Outputs on Panel 2-L-26,

[A115U/692 (Pent Rm)]:

A.

2-TIC-67-84, LOWER CNTMT VENT CLR 2A TEMP CNTL (SubSection 6.1.1)

Auto/Manual Status:

Indicated Controller Setpoint:

Indicated Controller Output:

B.

2-TIC-67-100, LOWER CNTMT VENT CLR 2B TEMP CNTL (SubSection 6.1.2)

Auto/Manual Status:

Indicated Controller Setpoint:

Indicated Controller Output:

C.

2-TIC-67-92, LOWER CNTMT VENT CLR 2C TEMP CNTL (SubSection 6.1.3)

Auto/Manual Status:

Indicated Controller Setpoint:

Indicated Controller Output:

D.

2-TIC-67-108, LOWER CNTMT VENT CLR 2D TEMP CNTL (SubSection 6.1.4)

Auto/Manual Status:

Indicated Controller Setpoint:

Indicated Controller Output:

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 21 of 144 4.3 Data Package: Page of Field Preparations (continued)

[6]

ENSURE the following system 67, ERCW Temperature Indicating Controllers on Panel 2-L-26, Auto/Manual Status is in Manual (M) and outputs are adjusted for maximum cooling (valve full open):

A.

2-TIC-67-84, LOWER CNTMT VENT CLR 2A TEMP CNTL (SubSection 6.1.1)

B.

2-TIC-67-1 00, LOWER CNTMT VENT CLR 2B TEMP CNTL (SubSection 6.1.2)

C.

2-TIC-67-92, LOWER CNTMT VENT CLR 2C TEMP CNTL (SubSection 6.1.3)

D.

2-TIC-67-108, LOWER CNTMT VENT CLR 2D TEMP CNTL (SubSection 6.1.4)

[7]

ENSURE the following ICS points are in scan:

A.

HD2030, VENT SYS HS-38A, 88A, 74A, 77A, 83A B.

HD2064, VENT SYS HS-39A, 78A, 75A, 92A, 80A C.

T1i11 A, LOWR COMPT COOL UNIT A-A EXHAUST D.

TI 111A, LOWR COMPT COOL UNIT B-B EXHAUST E.

T1112A, LOWR COMPT COOL UNIT C-A EXHAUST F.

T1113A, LOWR COMPT COOL UNIT D-B EXHAUST G.

Ti 1 14A, LOWER COMPT COOL UNIT A-A INTAKE H. T1115A, LOWER COMPT COOL UNIT B-B INTAKE I.

Ti 11 6A, LOWER COMPT COOL UNIT C-A INTAKE J.

T1117A, LOWER COMPT COOL UNIT D-B INTAKE Date

Data Package: Page _

of D

Date 4.3 Field Preparations (continued)

[8]

VERIFY there are no Unit 2 Phase B Containment Isolation Signals present by the OB window NOT LIT on either the TR-A or TR-B MASTER ISOL SIGNAL STATUS PNL (Window 3 on 2-XX-55-6C and 2-XX-55-6D) on 2-M-6.

[9]

ENSURE system is configured in accordance with Appendix D, Electrical Lineup.

[10]

VERIFY that the Reactor Coolant System (RCS) is NOT filled and vented. (SubSection 6.4)

[11]

INSTALL switched jumpers at the following locations, AND ENSURE that the jumper test switches are OPEN (OFF).

[11.1]

Labeled TS-1:

In SSPS Train-A Output Cabinet 2-R-48, at TB615, between Pt. 11 (Wire 2340VL) and Pt. 12 (Wire CNA1).

(Drawing 45N2676-4)

A.

Jumper Installed 1st CV B.

Test Switch OPEN (OFF)

[11.2]

Labeled TS-2:

In SSPS Train-B Output Cabinet 2-R-51, at TB615, between Pt. 11 (Wire 2435VL) and Pt. 12 (Wire CNB1).

(Drawing 45N2677-4)

A.

Jumper Installed 1st CV B.

Test Switch OPEN (OFF)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 23 of 144 Data Package: Page _

of Date 4.3 Field Preparations (continued)

NOTE The following step will disable the Train A LCCs' Auto-start on Low Flow function.

[12]

LIFT Wire Al 7C2 from point 8 of Terminal Block 65B5, inside the front panel of 480V SHUTDOWN BOARD 2A1 -A, Compartment 6A. (Drawing 618F938) 1st Cv NOTE The following step will disable the Train B LCCs' Auto-start on Low Flow function.

[13]

LIFT Wire B17D2 from point 5 of Terminal Block 65B2, inside the front panel of 480V SHUTDOWN BOARD 2B1-B Compartment 6A. (Drawing 618F941) 1 st Cv

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 24 of 144 Data Package: Page _

of Date 4.4 Approvals and Notifications

[1]

OBTAIN permission of the Preoperational Startup Manager to perform this test.

Preoperational Startup Manager Signature Date

[2]

OBTAIN the Unit 2 Supervisor's (US/SRO) or Shift Manager's (SM) authorization.

Unit 2 US/SRO/SM Signature Date

[3]

OBTAIN the Unit 1 Supervisor's (US/SRO) or Shift Manager's (SM) authorization.

Unit 1 US/SRO/SM Signature Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 25 of 144 Data Package: Page _

of Date 5.0 ACCEPTANCE CRITERIA NOTE Acceptance Criteria values have been adjusted as necessary to account for instrument inaccuracies. See Appendix E for calculation bases.

A.

The Lower Compartment Coolers' manual and automatic controls, interlocks, annunciations, alarms, and indications operate correctly.

Controls and Indications Controls and Indications (Main Control Room)

(remote)

LOG 2A-A (CCU-3 SubSection 6.1.1 SubSection 6.1.1 (2-CCU-30-74)

LCC 2B-B (CC2-3 SubSection 6.1.2 SubSection 6.1.2 (2-CCU-30-75)

LCC 2C-A (2-CCU-30-77)

SubSection 6.1.3 SubSection 6.1.3 LCC 20-B (CCU-3 SubSection 6.1.4 SubSection 6.1.4 (2-CCU-30-78):LI B.

The Backdraft Dampers associated with each Lower Compartment Cooler operate correctly.

Damper Opens/Closes when associated LCC Unit starts/stops 2-BKD-30-514 6.1.1 [9]F (LCC 2A-A) 6.1.1[12]E 2-BKD-30-507 6.1.2[9]F (LCC 2B-B) 6.1.2[12]E 2-BKD-30-503 6.1.3[9]F (LCC 2C-A) 6.1.3[12]E 2-BKD-30-518 6.1.4[9]F (LCC 2D-B) 6.1.4[12]E

Data Package: Page of Date 5.0 ACCEPTANCE CRITERIA (continued)

C. Lower Compartment Cooler intake and exhaust air temperatures output to the Plant Computer (ICS) properly.

ICS Points ICS Point Qualities are GOOD LCC 2A-A:

T1114A 6.1.1[10]

T1110A LCC 2B-B:

T1115A 6.1.2[10]

T1111A LCC 2C-A:

T1 1 16A 6.1.3[10]

T1 1 12A LCC 2D-B:

T1117A 6.1.4[10]

T1113A D.

The ERCW Control operate correctly.

Valves associated with each Lower Compartment Cooler Valve modulates open/closes Valve when LCC Unit starts/stops XS in NOR XS in AUX 2-TCV-67-84 6.1.1[9]F 6.1.1[16]C (LCC 2A-A) 6.1.1[12]E 6.1.1[17]C 2-TCV-67-100 6.1.2[9]F 6.1.2[16]C (LCC 2B-B) 6.1.2[12]E 6.1.2[17]C 2-TCV-67-92 6.1.3[9]F 6.1.3[16]C (LCC 2C-A) 6.1.3[12]E 6.1.3[17]C 2-TCV-67-108 6.1.4[9]F 6.1.4[1 6]C (LCC 2D-B) 6.1.4[12]E 6.1.4[17]C

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 27 of 144 5.0 Data Package: Page of Date ACCEPTANCE CRITERIA (continued)

E. The Lower Compartment Coolers respond appropriately to Engineered Safety Feature Actuation System (ESFAS) signals:

Phase B (OB) Containment Isolation Signal LCC XS in NORMAL XS in AUX Remains stopped Can be manually started and run after OB reset with 0B signal in effect LC2A-A 6.2.1[7]A 6.2.1[9]A 6.2.1[13]

(2-CCU-30-74)

LCC 2B-B 6.2.2[7]A 6.2.2[9]A 6.2.2[13]

(2-CCU-30-75)

LCC2C-A 6.2.1[7]B 6.2.1[9]B 6.2.1[15]

(2-CCU-30-77)

LCC 2D-B3 6.2.2[7]B 6.2.2[9]B 6.2.2[15]

(2-CCU-30-78)

I________

I_______________

F.

The Lower Compartment Coolers respond appropriately to a Bus Undervoltage condition (LOOP).

XS in NORMAL XS in AUX LCC Remains stopped LCC Stops on after bus voltage Stops on Restarts after bus LOOP is restored LOOP voltage is restored LCC 2A-A

( CC 2-3 6.3.1[6]

6.3.1[8]

6.3.1[12]

6.3.1[14]

(2-CCU-30-74)

LCC 2B-B (2-CCU-30-75) 6.3.2[6]

6.3.2[8]

6.3.2[12]

6.3.2[14]

LCC 2C-A (2-CCU-30-77) 6.3.3[6]

6.3.3[8]

6.3.3[12]

6.3.3[14]

LCC 2D-B (2-CCU-30-78) 6.3.4[6]

6.3.4[8]

6.3.4[12]

6.3.4[14]

Data Package: Page _

of Date 5.0 ACCEPTANCE CRITERIA (continued)

G.

The Lower Compartment Coolers can operate correctly during Design Basis Accident conditions LCC Motor Design Density Motor Horsepower is*< Motor Nameplate Horsepower of 56 HP*

LCC 2A-A (2-MTR-30-74) 6.5110]A LCC 2B-B (2-MTR-30-75) 6.5110]B LCC 2C-A (2-MTR-30-77) 6.5110]C LCC 2D-B (2-MTR-30-78) 6.5110]D

  • Nameplate HP = 60 HP, reduced to 56 HP to account for instrument inaccuracies H. The Lower Compartment Coolers respond appropriately to a Low Flow condition in another Lower Compartment Cooler. (Only when XS is in AUX)

Auto-start on Low Flow in 2/4 LCCs to maintain 3/4 LCCs in operation.

Running LCCs LCC with Low Flow LCC that Auto-Starts Step C-A D-B B-B A-A 6.4[11]

C-A D-B A-A B-B 6.4[14]

B-B D-B C-A A-A 6.4[17]

B-B D-B A-A C-A 6.4[20]

B-B C-A D-B A-A 6.4[23]

B-B C-A A-A D-B 6.4[26]

A-A D-B C-A B-B 6.4[31]

A-A D-B B-B C-A 6.4[34]

A-A C-A D-B B-B 6.4[37]

A-A C-A B-B D-B 6.4[40]

A-A B-B D-B C-A 6.4145]

A-A B-B C-A D-B 6.4[48]

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 29 of 144 Data Package: Page _

of Date 5.0 ACCEPTANCE CRITERIA (continued)

1.

The Lower Compartment Coolers provide the required minimum air flows in the following configurations:

1.

Each LCC Operating Individually:

LCC Total per cooler: 48,700 CFM LCC 2A-A 6.5[4]A LCC 2B-B 6.5[4]B LCC 2C-A 6.5[4]C LCC 2D-B 6.5[4]D

2.

Any Three LCCs Operating Together:

Running Total:

Each S/G

Enclosure:

Pressurizer

Enclosure:

Reactor Cavity:

LCCs 146,000 CFM 5,625 CFM 3,700 CFM 10,000 CFM LCC 2A-A LCC 2B-B 6.5[5]A 6.5[5]A 6.5[5]A 6.5[5]A LCC 2C-A LCC 2A-A LCC 2C-A 6.5[5]B 6.5[5]B 6.5[5]B 6.5[5]B LCC 2D-B LCC 2A-A LCC 2B-B 6.5[5]C 6.5[5]C 6.5[5]C 6.5[5]C LCC 2D-B LCC 2B-B LCC 2C-A 6.5[5]D 6.5[5]D 6.5[5]D 6.5[5]D LCC 2D-B

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 30 of 144 Data Package: Page _

of 5.0 ACCEPTANCE CRITERIA (continued)

3.

Each Train of LCCs Operating Together Date Running Total:

Pressurizer

Enclosure:

Reactor Cavity:

LCCs 105,000 CFM 2,400 CFM 6,700 CFM Train A:

LCC 2A-A 6.5[6]A 6.5[6]A 6.5[6]A LCC 2C-A Train B:

LCC 2B-B 6.5[6]B 6.5[6]B 6.5[6]B LCC 2D-B

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 31 of 144 Data Package: Page of Date 6.0 PERFORMANCE NOTES

1) The Sections and SubSections of this test shall be performed per the flow chart below:

Train A Train B LCC 2A-A LCC 2C-A LCC 2B-B LCC 2D-B

2)

The Subsections of Sections 6.1, 6.2, and 6.3 may be performed in any order provided that each Subsection's applicable predecessor Subsection(s) are completed. Section 6.4 is to be performed last and Section 6.5 may be performed at any time during this instruction. Unless otherwise noted, steps within each section are to be performed in the order written. The flowchart above may be used as a placekeeping tool throughout the performance of this instruction.

3)

Lower Compartment Cooler (LCC) Handswitches in the Main Control Room spring return to A AUTO from START and STOP positions.

4)

LCC Handswitches on the 480V Shutdown Boards spring return to AUTO from CLOSE and TRIP positions.

5)

LCC Units have status indication lights at two locations in the Main Control Room:

On 2-M-9 at their associated Handswitch On 2-M-6, on Train A (2-XX-55-6E) or Train B (2-XX-55-6F) CONTAINMENT ISOL STATUS PNL, hereafter abbreviated in this instruction as CISP.

6)

LCC Units are located in the Fan Rooms above the Raceway in Lower Containment.

LCC 2A-A and 2D-B are located together in the South Fan Room (Fan Room 1).

LCC 2B-B and 2C-A are located together in the North Fan Room (Fan Room 2).

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 32 of 144 Data Package: Page of Date 6.1 Lower Compartment Cooler Logic Test NOTE Unless otherwise noted, SubSections 6.1.1 through 6.1.4 may be performed in any order.

Unless otherwise noted, the steps within each SubSection shall be performed in the order written. The diagram at the beginning of Section 6.0 may be used as a placekeeping tool throughout the performance of this Section.

6.1.1 Lower Compartment Cooler 2A-A Logic

[1]

ENSURE all prerequisites listed in Section 4.0 for Section 6.1 and SubSection 6.1.1 have been completed.

[2]

RACK Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74), [480V SHUTDOWN BOARD 2A1-A, Compartment 7C], to the TEST position.

[3]

VERIFY 2-XA-55-5C-1 04A, LWR CNTMT CLR FLOW LO, is CLEAR.

[4]

PRESS the REAC LWR COMPT CLR FAN 2A-A BKR TEST CLOSE switch at Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74), AND VERIFY the following:

A.

At Breaker 2-BKR-30-74:

Green Light OFF Red Light ON Red Flag at Breaker Panel B.

2-XA-55-5C-1 04A, LWR CNTMT CLR FLOW LO, is in ALARM (after approximately 30 seconds).

C.

Unit 2 Alarm Events Display Screen indicates 104-A LOWER CNTMT CLR A-A FLOW LO (FS-30-74),

is in ALARM (Red).

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 33 of 144 Data Package: Page of Date 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

[5]

PRESS the REAC LWR COMPT CLR FAN 2A-A BKR TEST TRIP switch at Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74), AND VERIFY the following:

A.

At Breaker 2-BKR-30-74:

Green Light ON Red Light OFF Green Flag at Breaker Panel B.

2-XA-55-5C-1 04A, LWR CNTMT CLR FLOW LO, is CLEAR.

C.

Unit 2 Alarm Events Display Screen indicates 104-A LOWER CNTMT CLR A-A FLOW LO (FS-30-74),

is NORMAL (Green).

[6]

ENSURE Transfer Switch 2-XS-30-74, LOWER COMPT COOLER 2A-A, [480V SHUTDOWN BOARD 2A1-A, Compartment 5A], is in NORMAL.

[7]

RACK Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74) to the CONNECTED position.

[8]

VERIFY the following:

A.

Cooler 2-CCU-30-74, CNTMT LOWER COMPARTMENT COOLER 2A-A, [Lwr Cntmt/716 AZ 210 (S Fan Rm)],

is OFF.

B.

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

C.

2-XA-55-6F-1 49B, 480 SD BD 2A1-A/2A2-A/CA VT BD 2A1-A, is CLEAR.

Data Package: Page of 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

[9]

PLACE Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A,

[2-M-9], to START, AND VERIFY the following:

A.

On Handswitch 2-HS-30-74A:

Green Light OFF Red Light ON White Light OFF B.

On 2-XX-55-6E, Train A CISP, Window 103, LWR CNTMT A FAN-30-74, [2-M-6]:

Green Light OFF Red Light ON C.

2-XA-55-5C-1 04A, LWR CNTMT CLR FLOW LO, remains CLEAR (after approximately 30 seconds).

D.

On Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, [480V SHUTDOWN BOARD 2A1-A, Compartment 5A]:

Green Light OFF Red Light ON E.

At Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74):

Green Light OFF Red Light ON Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 35 of 144 Data Package: Page _

of Date 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

F.

Locally:

Cooler 2-CCU-30-74, CNTMT LOWER COMPARTMENT COOLER 2A-A, is ON.

Backdraft Damper 2-BKD-30-514, LOWER COMPT CLR SUP, [Lwr Cntmt/731 AZ 210 (S Fan Rm)],

is OPEN. (Acc Crit)

Valve 2-TCV-67-84, LWR CNTMT VENT CLR 2A-A OUT TEMP CNTL, [Lwr Cntmt/721 AZ 100 (S Fan Rm)], modulates OPEN. (Acc Crit)

[10]

VERIFY that the LCC 2A-A intake and exhaust air temperature ICS Point Qualities are GOOD (Green). (Acc Crit)

Point T1 114A, LOWER COMPT COOL UNIT A-A INTAKE Point Ti 11 OA, LOWER COMPT COOL UNIT A-A EXHAUST

[11]

RECORD LCC 2A-A intake and exhaust air temperatures as indicated by the ICS points:

T1114A, LOWER COMPT COOL UNIT A-A INTAKE:

OF

T1110A, LOWER COMPT COOL UNIT A-A EXHAUST:

OF

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 36 of 144 Data Package: Page _

of Date 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

[12]

PLACE Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A, to STOP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-74A:

Green Light ON Red Light OFF White Light OFF B.

On 2-XX-55-6E, Train A CISP, Window 103, LWR CNTMT A FAN-30-74:

Green Light ON Red Light OFF C.

On Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A:

Green Light ON Red Light OFF D.

At Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74):

Green Light ON Red Light OFF E.

Locally:

Cooler 2-CCU-30-74, CNTMT LOWER COMPARTMENT COOLER 2A-A, is OFF.

Backdraft Damper 2-BKD-30-514, LOWER COMPT CLR SUP, is CLOSED. (Acc Crit)

Valve 2-TCV-67-84, LWR CNTMT VENT CLR 2A-A OUT TEMP CNTL, is CLOSED. (Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 37 of 144 Data Package: Page of 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

[13]

ENSURE 2-XA-55-6F-149B, 480 SD BD 2A1-A/2A2-A/CA VT BD 2A1-A, is CLEAR.

[14]

PLACE the following Transfer Switches to AUX:

A.

2-XS-30-74, LOWER COMPT COOLER 2A-A.

B.

2-XS-67-84, LWR CNTMT CLR A-A ERCW OUTLET TCV, [2-L-1 1A].

[15]

VERIFY the following:

A.

On Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A:

Green Light OFF Red Light OFF White Light OFF B.

On 2-XX-55-6E, Train A CISP, Window 103, LWR CNTMT A FAN-30-74:

Green Light OFF Red Light OFF C.

Annunciation and Alarms:

2-XA-55-6F-149B, 480 SD BD 2A1-A/2A2-A/CA VT BD 2A1-A, is in ALARM.

Unit 2 Alarm Events Display Screen indicates 149-B 480 SD BD 2A1-A/2A2-A XS IN AUX, is in ALARM (Red).

D.

On Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A:

Green Light ON Red Light OFF Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 38 of 144 Data Package: Page _

of Date 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

E.

At Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74):

Green Light ON Red Light OFF

[16]

PLACE Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, to CLOSE, AND VERIFY the following:

A.

On Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A:

Green Light OFF Red Light ON B.

At Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74):

Green Light OFF Red Light ON C.

Locally:

Cooler 2-CCU-30-74, CNTMT LOWER COMPARTMENT COOLER 2A-A, is ON.

Valve 2-TCV-67-84, LWR CNTMT VENT CLR 2A-A OUT TEMP CNTL, modulates OPEN. (Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 39 of 144 Data Package: Page of__

Date 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

[17]

PLACE Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, to TRIP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A:

Green Light ON Red Light OFF B. At Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74):

Green Light ON Red Light OFF C.

Locally:

Cooler 2-CCU-30-74, CNTMT LOWER COMPARTMENT COOLER 2A-A, is OFF.

Valve 2-TCV-67-84, LWR CNTMT VENT CLR 2A-A OUT TEMP CNTL, is CLOSED. (Acc Crit)

[18]

PLACE Transfer Switch 2-XS-30-74, LOWER COMPT COOLER 2A-A, to NORMAL.

[19]

PLACE Transfer Switch 2-XS-67-84, LWR CNTMT CLR A-A ERCW OUTLET TCV to NOR.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 40 of 144 Data Package: Page _

of 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

[20]

VERIFY the following:

A.

On Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A:

a Green Light ON Red Light OFF a

White Light OFF B.

On 2-XX-55-6E, Train A CISP, Window 103, LWR CNTMT A FAN-30-74:

Green Light ON Red Light OFF C.

Annunciation and Alarms:

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

Motor Tripout Buzzer, [2-M-2], is OFF.

2-XA-55-6F-149B, 480 SD BD 2A1-A/2A2-A/CA VT BD 2A1-A, is CLEAR.

Unit 2 Alarm Events Display Screen indicates 149-B 480 SD BD 2A1-A/2A2-A XS IN AUX, is NORMAL (Green).

Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 41 of 144 Data Package: Page _

of Date 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

[21]

RACK Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74), to the REMOVED position.

[22]

REMOVE front cover of Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74).

1 st CV

[23]

PLACE Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74), Overload Trip Switch (OTS) mechanical lever (DTA plunger) to the TRIP position.

[24]

INSTALL front cover of Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74).

1 st CV

[25]

RACK Breaker 2-BKR-30-74, LOWER COMPT COOLER 2A-A (2-CCU-30-74), to the CONNECTED position.

[26]

VERIFY the following:

A.

On Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A:

Green Light ON Red Light OFF White Light ON B.

Annunciation and Alarms:

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is in ALARM.

Unit 2 Alarm Events Display Screen indicates 138-E PANEL M-9 MOTOR TRIPOUT, is in ALARM (Red).

Motor Tripout Buzzer is ON.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 42 of 144 Data Package: Page of Date 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

NOTES

1)

The following step will electrically reset the Overload Trip Switch (OTS) for Breaker 2-BKR-30-74. Refer to Precaution 3.0H for further details.

2)

If the following step does not reset the OTS, then the OTS may be reset manually by pressing the OTS Reset button on the front of the Breaker, and a Test Deficiency Notice shall be initiated.

[27]

RESET the OTS by PLACING Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A, to STOP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A:

Green Light ON Red Light OFF White Light OFF B. Annunciation and Alarms:

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

Unit 2 Alarm Events Display Screen indicates 138-E PANEL M-9 MOTOR TRIPOUT, is NORMAL (Green).

Motor Tripout Buzzer is OFF

Data Package: Page of Date 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

[28]

RECORD the As-Found position of the following Handswitches on 2-M-9, AND IF any of the following Handswitches are found in STOP PULL TO LOCK, THEN PLACE that Handswitch in A AUTO.

A.

2-HS-30-38A, AIR RETURN FAN A-A As-Found:

As Left:

B.

2-HS-30-77A, LWR CNTMT CLR C-A As-Found:

As Left:

C.

2-HS-30-83A, CRDM CLR A-A As-Found:

As Left:

D.

2-HS-30-88A, CRDM CLR C-A As-Found:

As Left:

[29]

VERIFY ICS Point HD2030, VENT SYS HS-38A, 88A, 74A, 77A, 83A, displays NOT P-L.

[30]

PLACE Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A, in STOP PULL TO LOCK, AND VERIFY ICS Point HD2030, VENT SYS HS-38A, 88A, 74A, 77A, 83A, displays PULLT-L.

Data Package: Page of Date 6.1.1 Lower Compartment Cooler 2A-A Logic (continued)

[31]

ENSURE the following Handswitches are returned to their As-Found position recorded in Step 6.1.1[28].

(The As-Left position recorded in this step should match the As-Found position recorded in Step 6.1.1[28].)

A.

2-HS-30-38A, AIR RETURN FAN A-A As-Found:

As Left:

B. 2-HS-30-77A, LWR CNTMT CLR C-A As-Found:

As Left:

C.

2-HS-30-83A, CRDM CLR A-A As-Found:

As Left:

D.

2-HS-30-88A, CRDM CLR C-A As-Found:

As Left:

[32]

ENSURE ERCW Temperature Indicating Controller 2-TIC-67-84, LOWER CNTMT VENT CLR 2A TEMP CNTL, is returned to its As-Found positions recorded in Step 4.3[5]A.

Auto/Manual Status:

Indicated Controller Setpoint:

Indicated Controller Output:

1st CV

[33]

VERIFY successful completion of this SubSection 6.1.1.

(Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 45 of 144 Data Package: Page of Date 6.1.2 Lower Compartment Cooler 2B-B Logic

[1]

ENSURE all prerequisites listed in Section 4.0 for Section 6.1 and SubSection 6.1.2 have been completed.

[2]

RACK Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75), [480V SHUTDOWN BOARD 2B1-B, Compartment 7D], to the TEST position.

[3]

VERIFY 2-XA-55-5C-1 04A, LWR CNTMT CLR FLOW LO, is CLEAR.

[4]

PRESS the REAC LWR COMPT CLR FAN 2B-B BKR TEST CLOSE switch at Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75), AND VERIFY the following:

A.

At Breaker 2-BKR-30-75:

Green Light OFF Red Light ON Red Flag at Breaker Panel B. 2-XA-55-5C-104A, LWR CNTMT CLR FLOW LO, is in ALARM (after approximately 30 seconds).

C.

Unit 2 Alarm Events Display Screen indicates 104-A LOWER CNTMT CLR B-B FLOW LO (FS-30-75),

is in ALARM (Red).

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 46 of 144 Data Package: Page _

of Date 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

[5]

PRESS the REAC LWR COMPT CLR FAN 2B-B BKR TEST TRIP switch at Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75), AND VERIFY the following:

A.

At Breaker 2-BKR-30-75:

Green Light ON Red Light OFF Green Flag at Breaker Panel B.

2-XA-55-5C-1 04A, LWR CNTMT CLR FLOW LO, is CLEAR.

C.

Unit 2 Alarm Events Display Screen indicates 104-A LOWER CNTMT CLR B-B FLOW LO (FS-30-75),

is NORMAL (Green).

[6]

ENSURE Transfer Switch 2-XS-30-75, LOWER COMPT COOLER 2B-B, [480V SHUTDOWN BOARD 2B1-B, Compartment 5A], is in NORMAL.

[7]

RACK Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75) to the CONNECTED position.

[8]

VERIFY the following:

A.

Cooler 2-CCU-30-75, CNTMT LOWER COMPARTMENT COOLER 2B-B, [Lwr Cntmt/716 AZ 1590 (N Fan Rm)],

is OFF.

B.

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

C.

2-XA-55-6F-1 50B, 480 SD BD 2B1-B/2B2-B/CA VT BD 2B1-B, is CLEAR.

Data Package: Page of 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

[9]

PLACE Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B,

[2-M-9], to START, AND VERIFY the following:

A.

On Handswitch 2-HS-30-75A:

Green Light OFF Red Light ON White Light OFF B.

On 2-XX-55-6F, Train B CISP, Window 103, LWR CNTMT B FAN-30-75, [2-M-6]:

Green Light OFF Red Light ON C.

2-XA-55-5C-104A, LWR CNTMT CLR FLOW LO, remains CLEAR (after approximately 30 seconds).

D.

On Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, [480V SHUTDOWN BOARD 2B1-B, Compartment 5A]:

Green Light OFF Red Light ON E.

At Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75):

Green Light OFF Red Light ON Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 48 of 144 Data Package: Page _

of Date 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

F.

Locally:

Cooler 2-CCU-30-75, CNTMT LOWER COMPARTMENT COOLER 2B-B, is ON.

Backdraft Damper 2-BKD-30-507, LOWER COMPT CLR SUP, [Lwr Cntmt/731 AZ 1590 (N Fan Rm)],

is OPEN. (Acc Crit)

Valve 2-TCV-67-1 00, LWR CNTMT VENT CLR 2B-B OUT TEMP CNTL, [Lwr Cntmt/721 AZ 1700 (N Fan Rm)], modulates OPEN. (Acc Crit)

[10]

VERIFY that the LCC 2B-B intake and exhaust air temperature ICS Point Qualities are GOOD (Green). (Acc Crit)

Point T1115A, LOWER COMPT COOL UNIT B-B INTAKE Point T1111A, LOWER COMPT COOL UNIT B-B EXHAUST

[11]

RECORD LCC 2B-B intake and exhaust air temperatures as indicated by the ICS points:

T1115A, LOWER COMPT COOL UNIT B-B INTAKE:

OF

T1111A, LOWER COMPT COOL UNIT B-B EXHAUST:

OF

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 49 of 144 Data Package: Page _

of Date 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

[12]

PLACE Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B, to STOP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-75A:

Green Light ON Red Light OFF White Light OFF B.

On 2-XX-55-6F, Train B CISP, Window 103, LWR CNTMT B FAN-30-75:

Green Light ON Red Light OFF C.

On Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B:

Green Light ON Red Light OFF D.

At Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75):

Green Light ON Red Light OFF E.

Locally:

Cooler 2-CCU-30-75, CNTMT LOWER COMPARTMENT COOLER 2B-B, is OFF.

Backdraft Damper 2-BKD-30-507, LOWER COMPT CLR SUP, is CLOSED. (Acc Crit)

Valve 2-TCV-67-1 00, LWR CNTMT VENT CLR 2B-B OUT TEMP CNTL, is CLOSED. (Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 50 of 144 Data Package: Page of Date 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

[13]

ENSURE 2-XA-55-6F-150B, 480 SD BD 2B1-B/2B2-B/CA VT BD 2B1-B, is CLEAR.

[14]

PLACE the following Transfer Switches to AUX:

A.

2-XS-30-75, LOWER COMPT COOLER 28-B.

B.

2-XS-67-100, LWR CNTMT CLR B-B ERCW OUTLET TCV, [2-L-1 1B].

[15]

VERIFY the following:

A.

On Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B:

Green Light OFF Red Light OFF White Light OFF B.

On 2-XX-55-6F, Train B CISP, Window 103, LWR CNTMT A FAN-30-75:

Green Light OFF Red Light OFF C.

Annunciation and Alarms:

2-XA-55-6F-150B, 480 SD BD 2B1-B/2B2-B/CA VT BD 2B1-B, is in ALARM.

Unit 2 Alarm Events Display Screen indicates 150-B 480 SD BD 281-8/282-B XS IN AUX, is in ALARM (Red).

D.

On Handswitch 2-HS-30-75C, LOWER COMPT COOLER 28-B:

Green Light ON Red Light OFF

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 51 of 144 Data Package: Page _

of Date 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

E. At Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75):

Green Light ON Red Light OFF

[16]

PLACE Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, to CLOSE, AND VERIFY the following:

A.

On Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B:

Green Light OFF Red Light ON B.

At Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75):

Green Light OFF Red Light ON C.

Locally:

Cooler 2-CCU-30-75, CNTMT LOWER COMPARTMENT COOLER 2B-B, is ON.

Valve 2-TCV-67-1 00, LWR CNTMT VENT CLR 2B-B OUT TEMP CNTL, modulates OPEN. (Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 52 of 144 Data Package: Page _

of Date 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

[17]

PLACE Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, to TRIP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B:

Green Light ON Red Light OFF B.

At Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75):

Green Light ON Red Light OFF C.

Locally:

Cooler 2-CCU-30-75, CNTMT LOWER COMPARTMENT COOLER 2B-B, is OFF.

Valve 2-TCV-67-1 00, LWR CNTMT VENT CLR 2B-B OUT TEMP CNTL, is CLOSED. (Acc Crit)

[18]

PLACE Transfer Switch 2-XS-30-75, LOWER COMPT COOLER 2B-B, to NORMAL.

[19]

PLACE Transfer Switch 2-XS-67-100, LWR CNTMT CLR B-B ERCW OUTLET TCV to NOR.

Data Package: Page _

of 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

[20]

VERIFY the following:

A.

On Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B:

Green Light ON Red Light OFF White Light OFF B.

On 2-XX-55-6F, Train B ClSP, Window 103, LWR CNTMT B FAN-30-75:

Green Light ON Red Light OFF C.

Annunciation and Alarms:

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

0 Motor Tripout Buzzer, [2-M-2], is OFF.

2-XA-55-6F-150B, 480 SD BD 2B1-B/2B2-B/CA VT BD 2B1-B, is CLEAR.

Unit 2 Alarm Events Display Screen indicates 150-B 480 SD BD 2B1-B/2B2-B XS IN AUX, is NORMAL (Green).

Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 54 of 144 Data Package: Page _

of Date 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

[21]

RACK Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75), to the REMOVED position.

[22]

REMOVE front cover of Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75).

1 st CV

[23]

PLACE Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75), Overload Trips Switch (OTS) mechanical lever (DTA plunger) to the TRIP position.

[24]

INSTALL front cover of Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75).

1 st CV

[25]

RACK Breaker 2-BKR-30-75, LOWER COMPT COOLER 2B-B (2-CCU-30-75), to the CONNECTED position.

[26]

VERIFY the following:

A.

On Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B:

Green Light ON Red Light OFF White Light ON B.

Annunciation and Alarms:

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is in ALARM.

Unit 2 Alarm Events Display Screen indicates 138-E PANEL M-9 MOTOR TRIPOUT, is in ALARM (Red).

0 Motor Tripout Buzzer is ON.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 55 of 144 Data Package: Page _

of Date 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

NOTES

1)

The following step will electrically reset the Overload Trip Switch (OTS) for Breaker 2-BKR-30-75. Refer to Precaution 3.OH for further details.

2)

If the following step does not reset the OTS, then the OTS may be reset manually by pressing the OTS Reset button on the front of the Breaker, and a Test Deficiency Notice shall be initiated.

[27]

RESET the OTS by:

PLACING Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B, to STOP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B:

Green Light ON Red Light OFF White Light OFF B.

Annunciation and Alarms:

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

Unit 2 Alarm Events Display Screen indicates 138-E PANEL M-9 MOTOR TRIPOUT, is NORMAL (Green).

Motor Tripout Buzzer is OFF.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 56 of 144 Data Package: Page _

of Date 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

[28]

RECORD the As-Found position of the following Handswitches on 2-M-9, AND IF any of the following Handswitches are found in STOP PULL TO LOCK, THEN PLACE that Handswitch in A AUTO.

A.

2-HS-30-39A, AIR RETURN FAN B-B As-Found:

As Left:

B.

2-HS-30-78A, LWR CNTMT CLR D-B As-Found:

As Left:

C.

2-HS-30-92A, CRDM CLR B-B As-Found:

As Left:

D.

2-HS-30-80A, CRDM CLR D-B As-Found:

As Left:

[29]

VERIFY ICS Point HD2064, VENT SYS HS-39A, 78A, 75A, 92A, 80A, displays NOT P-L.

[30]

PLACE Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B, in STOP PULL TO LOCK, AND VERIFY ICS Point HD2064, VENT SYS HS-39A, 78A, 75A, 92A, 80A, displays PULLT-L.

Data Package: Page _

of Date 6.1.2 Lower Compartment Cooler 2B-B Logic (continued)

[31]

ENSURE the following Handswitches are returned to their As-Found position recorded in Step 6.1.2[28].

(The As-Left position recorded in this step should match the As-Found position recorded in Step 6.1.2[28].)

A.

2-HS-30-39A, AIR RETURN FAN B-B As-Found:

As Left:

B.

2-HS-30-78A, LWR CNTMT CLR D-B As-Found:

As Left:

C.

2-HS-30-92A, CRDM CLR B-B As-Found:

As Left:

D.

2-HS-30-80A, CRDM CLR D-B As-Found:

As Left:

[32]

ENSURE ERCW Temperature Indicating Controller 2-TIC-67-1 00, LOWER CNTMT VENT CLR 2B TEMP CNTL, is returned to its As-Found positions recorded in Step 4.3[5]B.

Auto/Manual Status:

Indicated Controller Setpoint:

Indicated Controller Output:

1st CV

[33]

VERIFY successful completion of this SubSection 6.1.2.

(Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 58 of 144 Data Package: Page of Date 6.1.3 Lower Compartment Cooler 2C-A Logic

[1]

ENSURE all prerequisites listed in Section 4.0 for Section 6.1 and SubSection 6.1.3 have been completed.

[2]

RACK Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77), [480V SHUTDOWN BOARD 2A2-A, Compartment 7D], to the TEST position.

[3]

VERIFY 2-XA-55-5C-104A, LWR CNTMT CLR FLOW LO, is CLEAR.

[4]

PRESS the REAC LWR COMPT CLR FAN 2C-A BKR TEST CLOSE switch at Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77), AND VERIFY the following:

A.

At Breaker 2-BKR-30-77:

Green Light OFF Red Light ON Red Flag at Breaker Panel B.

2-XA-55-5C-104A, LWR CNTMT CLR FLOW LO, is in ALARM (after approximately 30 seconds).

C.

Unit 2 Alarm Events Display Screen indicates 104-A LOWER CNTMT CLR C-A FLOW LO (FS-30-77),

is in ALARM (Red).

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 59 of 144 Data Package: Page _

of Date 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

[5]

PRESS the REAC LWR COMPT CLR FAN 2C-A BKR TEST TRIP switch at Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77), AND VERIFY the following:

A.

At Breaker 2-BKR-30-77:

Green Light ON Red Light OFF Green Flag at Breaker Panel B.

2-XA-55-5C-104A, LWR CNTMT CLR FLOW LO, is CLEAR.

C.

Unit 2 Alarm Events Display Screen indicates 104-A LOWER CNTMT CLR C-A FLOW LO (FS-30-77),

is NORMAL (Green).

[6]

ENSURE Transfer Switch 2-XS-30-77, LOWER COMPT COOLER 2C-A, [480V SHUTDOWN BOARD 2A2-A, Compartment 5A], is in NORMAL.

[7]

RACK Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77) to the CONNECTED position.

[8]

VERIFY the following:

A.

Cooler 2-CCU-30-77, CNTMT LOWER COMPARTMENT COOLER 2C-A, [Lwr Cntmt/716 AZ 2010 (N Fan Rm)],

is OFF.

B.

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

C.

2-XA-55-6F-149B, 480 SD BD 2A1-A/2A2-A/CA VT BD 2A1-A, is CLEAR.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 60 of 144 Data Package: Page of Date 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

[9]

PLACE Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A,

[2-M-9], to START, AND VERIFY the following:

A.

On Handswitch 2-HS-30-77A:

Green Light OFF Red Light ON White Light OFF B.

On 2-XX-55-6E, Train A CISP, Window 104, LWR CNTMT C FAN-30-77, [2-M-6]:

Green Light OFF Red Light ON C.

2-XA-55-5C-1 04A, LWR CNTMT CLR FLOW LO, remains CLEAR (after approximately 30 seconds).

D.

On Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, [480V SHUTDOWN BOARD 2A2-A, Compartment 5A]:

Green Light OFF Red Light ON E.

At Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77):

Green Light OFF Red Light ON

Data Package: Page of Date 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

F.

Locally:

Cooler 2-CCU-30-77, CNTMT LOWER COMPARTMENT COOLER 2C-A, is ON.

Backdraft Damper 2-BKD-30-503, LOWER COMPT CLR SUP, [Lwr Cntmt/731 AZ 201 0 (N Fan Rm)],

is OPEN. (Acc Crit)

Valve 2-TCV-67-92, LWR CNTMT VENT CLR 2C-A OUT TEMP CNTL, [Lwr Cntmt/721 AZ 1900 (N Fan Rm)], modulates OPEN. (Acc Crit)

[10]

VERIFY that the LCC 2C-A intake and exhaust air temperature ICS Point Qualities are GOOD (Green). (Acc Crit)

Point T1116A, LOWER COMPT COOL UNIT C-A INTAKE Point T1112A, LOWER COMPT COOL UNIT C-A EXHAUST

[11]

RECORD LCC 2C-A intake and exhaust air temperatures as indicated by the ICS points:

T1116A, LOWER COMPT COOL UNIT C-A INTAKE:

OF

T1I12A, LOWER COMPT COOL UNIT C-A EXHAUST:

OF

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 62 of 144 Data Package: Page of Date 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

[12]

PLACE Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A, to STOP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-77A:

Green Light ON Red Light OFF White Light OFF B.

On 2-XX-55-6E, Train A CISP, Window 104, LWR CNTMT C FAN-30-77:

Green Light ON Red Light OFF C.

On Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A:

Green Light ON Red Light OFF D.

At Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77):

Green Light ON Red Light OFF E.

Locally:

Cooler 2-CCU-30-77, CNTMT LOWER COMPARTMENT COOLER 2C-A, is OFF.

Backdraft Damper 2-BKD-30-503, LOWER COMPT CLR SUP, is CLOSED. (Acc Crit)

Valve 2-TCV-67-92, LWR CNTMT VENT CLR 2C-A OUT TEMP CNTL, is CLOSED. (Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 63 of 144 Data Package: Page _

of Date 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

[13]

ENSURE 2-XA-55-6F-149B, 480 SD BD 2A1-A/2A2-A/CA VT BD 2A1-A, is CLEAR.

[14]

PLACE the following Transfer Switches to AUX:

A.

2-XS-30-77, LOWER COMPT COOLER 2C-A.

B.

2-XS-67-92, LWR CNTMT CLR C-A ERCW OUTLET TCV, [2-L-11 A].

[15]

VERIFY the following:

A.

On Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A:

Green Light OFF Red Light OFF White Light OFF B.

On 2-XX-55-6E, Train A CISP, Window 104, LWR CNTMT C FAN-30-77:

Green Light OFF Red Light OFF C.

Annunciation and Alarms:

2-XA-55-6F-149B, 480 SD BD 2A1-A/2A2-A/CA VT BD 2A1-A, is in ALARM.

Unit 2 Alarm Events Display Screen indicates 149-B 480 SD BD 2A1-A/2A2-A XS IN AUX, is in ALARM (Red).

D.

On Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A:

Green Light ON Red Light OFF

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 64 of 144 Data Package: Page of Date 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

E. At Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77):

Green Light ON Red Light OFF

[16]

PLACE Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, to CLOSE, AND VERIFY the following:

A.

On Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A:

0 Green Light OFF Red Light ON B. At Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77):

Green Light OFF Red Light ON C.

Locally:

Cooler 2-CCU-30-77, CNTMT LOWER COMPARTMENT COOLER 2C-A, is ON.

Valve 2-TCV-67-92, LWR CNTMT VENT CLR 2C-A OUT TEMP CNTL, modulates OPEN. (Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 65 of 144 Data Package: Page _

of Date 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

[17]

PLACE Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, to TRIP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A:

Green Light ON Red Light OFF B.

At Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77):

Green Light ON Red Light OFF C.

Locally:

Cooler 2-CCU-30-77, CNTMT LOWER COMPARTMENT COOLER 2C-A, is OFF.

Valve 2-TCV-67-92, LWR CNTMT VENT CLR 2C-A OUT TEMP CNTL, is CLOSED. (Acc Crit)

[18]

PLACE Transfer Switch 2-XS-30-77, LOWER COMPT COOLER 2C-A, to NORMAL.

[19]

PLACE Transfer Switch 2-XS-67-92, LWR CNTMT CLR C-A ERCW OUTLET TCV to NOR.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 66 of 144 Data Package: Page of 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

[20]

VERIFY the following:

A.

On Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A:

Green Light ON Red Light OFF White Light OFF B.

On 2-XX-55-6E, Train A CISP, Window 104, LWR CNTMT C FAN-30-77:

Green Light ON Red Light OFF C.

Annunciation and Alarms:

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

Motor Tripout Buzzer, [2-M-2], is OFF.

2-XA-55-6F-149B, 480 SD BD 2A1-A/2A2-A/CA VT BD 2A1-A, is CLEAR.

Unit 2 Alarm Events Display Screen indicates 149-B 480 SD BD 2A1-A/2A2-A XS IN AUX, is NORMAL (Green).

Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 67 of 144 Data Package: Page _

of Date 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

[21]

RACK Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77), to the REMOVED position.

[22]

REMOVE front cover of Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77).

1 st CV

[23]

PLACE Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77), Overload Trips Switch (OTS) mechanical lever (DTA plunger) to the TRIP position.

[24]

INSTALL front cover of Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77).

1st CV

[25]

RACK Breaker 2-BKR-30-77, LOWER COMPT COOLER 2C-A (2-CCU-30-77), to the CONNECTED position.

[26]

VERIFY the following:

A.

On Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A:

Green Light ON Red Light OFF White Light ON B.

Annunciation and Alarms:

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is in ALARM.

Unit 2 Alarm Events Display Screen indicates 138-E PANEL M-9 MOTOR TRIPOUT, is in ALARM (Red).

0 Motor Tripout Buzzer is ON.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 68 of 144 Data Package: Page _

of Date 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

NOTES

1)

The following step will electrically reset the Overload Trip Switch (OTS) for Breaker 2-BKR-30-77. Refer to Precaution 3.0H for further details.

2)

If the following step does not reset the OTS, then the OTS may be reset manually by pressing the OTS Reset button on the front of the Breaker, and a Test Deficiency Notice shall be initiated.

[27]

RESET the OTS by:

PLACING Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A, to STOP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A:

Green Light ON Red Light OFF White Light OFF B.

Annunciation and Alarms:

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

Unit 2 Alarm Events Display Screen indicates 138-E PANEL M-9 MOTOR TRIPOUT, is NORMAL (Green).

0 Motor Tripout Buzzer is OFF.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 69 of 144 Data Package: Page _

of Date 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

[28]

RECORD the As-Found position of the following Handswitches on 2-M-9, AND IF any of the following Handswitches are found in STOP PULL TO LOCK, THEN PLACE that Handswitch in A AUTO.

A.

2-HS-30-38A, AIR RETURN FAN A-A As-Found:

As Left:

B.

2-HS-30-74A, LWR CNTMT CLR A-A As-Found:

As Left:

C.

2-HS-30-83A, CRDM CLR A-A As-Found:

As Left:

D.

2-HS-30-88A, CRDM CLR C-A As-Found:

As Left:

[29]

VERIFY ICS Point HD2030, VENT SYS HS-38A, 88A, 74A, 77A, 83A, displays NOT P-L.

[30]

PLACE Handswitch 2-HS-30-77A, LWR CNTMT CLR A-A, in STOP PULL TO LOCK, AND VERIFY ICS Point HD2030, VENT SYS HS-38A, 88A, 74A, 77A, 83A, displays PULLT-L.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 70 of 144 Data Package: Page _

of Date 6.1.3 Lower Compartment Cooler 2C-A Logic (continued)

[31]

ENSURE the following Handswitches are returned to their As-Found position recorded in Step 6.1.3[28].

(The As-Left position recorded in this step should match the As-Found position recorded in Step 6.1.3[28].)

A.

2-HS-30-38A, AIR RETURN FAN A-A As-Found:

As Left:

B.

2-HS-30-74A, LWR CNTMT CLR A-A As-Found:

As Left:

C.

2-HS-30-83A, CRDM CLR A-A As-Found:

As Left:

D.

2-HS-30-88A, CRDM CLR C-A As-Found:

As Left:

[32]

ENSURE ERCW Temperature Indicating Controller 2-TIC-67-92, LOWER CNTMT VENT CLR 2C TEMP CNTL, is returned to its As-Found positions recorded in Step 4.3[5]C.

Auto/Manual Status:

Indicated Controller Setpoint:

Indicated Controller Output:

1st CV

[33]

VERIFY successful completion of this SubSection 6.1.3.

(Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 71 of 144 Data Package: Page of Date 6.1.4 Lower Compartment Cooler 2D-B Logic

[1]

ENSURE all prerequisites listed in Section 4.0 for Section 6.1 and SubSection 6.1.4 have been completed.

[2]

RACK Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78), [480V SHUTDOWN BOARD 2B2-B, Compartment 7D], to the TEST position.

[3]

VERIFY 2-XA-55-5C-104A, LWR CNTMT CLR FLOW LO, is CLEAR.

[4]

PRESS the REAC LWR COMPT CLR FAN 2D-B BKR TEST CLOSE switch at Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78), AND VERIFY the following:

A.

At Breaker 2-BKR-30-78:

Green Light OFF Red Light ON Red Flag at Breaker Panel B.

2-XA-55-5C-104A, LWR CNTMT CLR FLOW LO, is in ALARM (after approximately 30 seconds).

C.

Unit 2 Alarm Events Display Screen indicates 104-A LOWER CNTMT CLR D-B FLOW LO (FS-30-78),

is in ALARM (Red).

Data Package: Page _

of__

Date 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

[5]

PRESS the REAC LWR COMPT CLR FAN 2D-B BKR TEST TRIP switch at Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78), AND VERIFY the following:

A.

At Breaker 2-BKR-30-78:

Green Light ON Red Light OFF Green Flag at Breaker Panel B.

2-XA-55-5C-1 04A, LWR CNTMT CLR FLOW LO, is CLEAR.

C.

Unit 2 Alarm Events Display Screen indicates 104-A LWR CNTMT CLR D-B FLOW LO (FS-30-78),

is NORMAL (Green).

[6]

ENSURE Transfer Switch 2-XS-30-78, LOWER COMPT COOLER 2D-B, [480V SHUTDOWN BOARD 2B2-B, Compartment 5A], is in NORMAL.

[7]

RACK Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78) to the CONNECTED position.

[8]

VERIFY the following:

A.

Cooler 2-CCU-30-78, CNTMT LOWER COMPARTMENT COOLER 2D-B, [Lwr Cntmt/716 AZ 3390 (S Fan Rm)],

is OFF.

B.

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

C.

2-XA-55-6F-150B, 480 SD BD 2B1-B/2B2-B/CA VT BD 2B1-B, is CLEAR.

Data Package: Page of 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

[9]

PLACE Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B,

[2-M-9], to START, AND VERIFY the following:

A.

On Handswitch 2-HS-30-78A:

Green Light OFF Red Light ON White Light OFF B.

On 2-XX-55-6F, Train B CISP, Window 104, LWR CNTMT D FAN-30-78, [2-M-6]:

Green Light OFF Red Light ON C.

2-XA-55-5C-1 04A, LWR CNTMT CLR FLOW LO, remains CLEAR (after approximately 30 seconds).

D.

On Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, [480V SHUTDOWN BOARD 2B2-B, Compartment 5A]:

Green Light OFF Red Light ON E.

At Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78):

Green Light OFF Red Light ON Date

Data Package: Page _

of Date 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

F.

Locally:

Cooler 2-CCU-30-78, CNTMT LOWER COMPARTMENT COOLER 2D-B, is ON.

Backdraft Damper 2-BKD-30-518, LOWER COMPT CLR SUP, [Lwr Cntmt/731 AZ 3390 (S Fan Rm)],

is OPEN. (Acc Crit)

Valve 2-TCV-67-108, LWR CNTMT VENT CLR 2D-B OUT TEMP CNTL, [Lwr Cntmt/721 AZ 3500 (S Fan Rm)], modulates OPEN. (Acc Crit)

[10]

VERIFY that the LCC 2D-B intake and exhaust air temperature ICS Point Qualities are GOOD (Green). (Acc Crit)

Point T1117A, LOWER COMPT COOL UNIT D-B INTAKE Point T1113A, LOWER COMPT COOL UNIT D-B EXHAUST

[11]

RECORD LCC 2D-B intake and exhaust air temperatures as indicated by the ICS points:

T1117A, LOWER COMPT COOL UNIT D-B INTAKE:

01

T1113A, LOWER COMPT COOL UNIT D-B EXHAUST:

01

2-PTI-030H-01 Rev. 0000 Page 75 of 144 Data Package: Page of Date 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

[121 PLACE Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B, to STOP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-78A:

Green Light ON Red Light OFF White Light OFF B.

On 2-XX-55-6F, Train B CISP, Window 104, LWR CNTMT D FAN-30-78:

Green Light ON Red Light OFF C.

On Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B:

Green Light ON Red Light OFF D.

At Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78):

Green Light ON Red Light OFF E.

Locally:

Cooler 2-CCU-30-78, CNTMT LOWER COMPARTMENT COOLER 2D-B, is OFF.

Backdraft Damper 2-BKD-30-518, LOWER COMPT CLR SUP, is CLOSED. (Acc Crit)

Valve 2-TCV-67-108, LWR CNTMT VENT CLR 2D-B OUT TEMP CNTL, is CLOSED. (Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 76 of 144 Data Package: Page _

of Date 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

[13]

ENSURE 2-XA-55-6F-150B, 480 SD BD 2B1-B/2B2-B/CA VT BD 2B1-B, is CLEAR.

[14]

PLACE the following Transfer Switches to AUX:

A.

2-XS-30-78, LOWER COMPT COOLER 2B-B.

B.

2-XS-67-108, LWR CNTMT CLR B-B ERCW OUTLET TCV, [2-L-1 1 B].

[15]

VERIFY the following:

A.

On Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B:

Green Light OFF Red Light OFF White Light OFF B.

On 2-XX-55-6F, Train B CISP, Window 104, LWR CNTMT D FAN-30-78:

Green Light OFF Red Light OFF C.

Annunciation and Alarms:

2-XA-55-6F-1 50B, 480 SD BD 2B1-B/2B2-B/CA VT BD 2B1-B, is in ALARM.

Unit 2 Alarm Events Display Screen indicates 150-B 480 SD BD 2B1-B/2B2-B XS IN AUX, is in ALARM (Red).

D.

On Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B:

Green Light ON Red Light OFF

Data Package: Page _

of Date 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

E. At Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78):

Green Light ON Red Light OFF

[16]

PLACE Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, to CLOSE, AND VERIFY the following:

A.

On Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B:

Green Light OFF Red Light ON B.

At Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78):

Green Light OFF Red Light ON C.

Locally:

Cooler 2-CCU-30-78, CNTMT LOWER COMPARTMENT COOLER 2D-B, is ON.

Valve 2-TCV-67-108, LWR CNTMT VENT CLR 2D-B OUT TEMP CNTL, modulates OPEN. (Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 78 of 144 Data Package: Page _

of Date 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

[17]

PLACE Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, to TRIP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B:

Green Light ON Red Light OFF B.

At Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78):

Green Light ON Red Light OFF C.

Locally:

Cooler 2-CCU-30-78, CNTMT LOWER COMPARTMENT COOLER 2D-B, is OFF.

Valve 2-TCV-67-108, LWR CNTMT VENT CLR 2D-B OUT TEMP CNTL, is CLOSED. (Acc Crit)

[18]

PLACE Transfer Switch 2-XS-30-78, LOWER COMPT COOLER 2D-B, to NORMAL.

[19]

PLACE Transfer Switch 2-XS-67-108, LWR CNTMT CLR D-B ERCW OUTLET TCV to NOR.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 79 of 144 Data Package: Page _

of Date 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

[20]

VERIFY the following:

A.

On Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B:

Green Light ON Red Light OFF White Light OFF B.

On 2-XX-55-6F, Train B CISP, Window 104, LWR CNTMT D FAN-30-78:

Green Light ON Red Light OFF C.

Annunciation and Alarms:

2-XA-55-6E-1 38E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

Motor Tripout Buzzer, [2-M-2], is OFF.

2-XA-55-6F-150B, 480 SD BD 2B1-B/2B2-B/CA VT BD 2B1-B, is CLEAR.

Unit 2 Alarm Events Display Screen indicates 150-B 480 SD BD 2B1-B/2B2-B XS IN AUX, is NORMAL (Green).

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 80 of 144 Data Package: Page _

of Date 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

[21]

RACK Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78), to the REMOVED position.

[22]

REMOVE front cover of Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78).

1 st CV

[23]

PLACE Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78), Overload Trips Switch (OTS) mechanical lever (DTA plunger) to the TRIP position.

[24]

INSTALL front cover of Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78).

1 st CV

[25]

RACK Breaker 2-BKR-30-78, LOWER COMPT COOLER 2D-B (2-CCU-30-78), to the CONNECTED position.

[26]

VERIFY the following:

A.

On Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B:

Green Light ON Red Light OFF White Light ON B.

Annunciation and Alarms:

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is in ALARM.

Unit 2 Alarm Events Display Screen indicates 138-E PANEL M-9 MOTOR TRIPOUT, is in ALARM (Red).

Motor Tripout Buzzer is ON.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 81 of 144 Data Package: Page _

of Date 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

NOTES

1)

The following step will electrically reset the Overload Trip Switch (OTS) for Breaker 2-BKR-30-78. Refer to Precaution 3.0H for further details.

2)

If the following step does not reset the OTS, then the OTS may be reset manually by pressing the OTS Reset button on the front of the Breaker, and a Test Deficiency Notice shall be initiated.

[27]

RESET the OTS by:

PLACING Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B, to STOP, AND VERIFY the following:

A.

On Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B:

Green Light ON Red Light OFF White Light OFF B.

Annunciation and Alarms:

2-XA-55-6E-138E, PANEL M-9 MOTOR TRIPOUT, is CLEAR.

Unit 2 Alarm Events Display Screen indicates 138-E PANEL M-9 MOTOR TRIPOUT, is NORMAL (Green).

Motor Tripout Buzzer is OFF.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 82 of 144 Data Package: Page _

of Date 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

[28]

RECORD the As-Found position of the following Handswitches on 2-M-9, AND IF any of the following Handswitches are found in STOP PULL TO LOCK, THEN PLACE that Handswitch in A AUTO.

A.

2-HS-30-39A, AIR RETURN FAN B-B As-Found:

As Left:

B.

2-HS-30-75A, LWR CNTMT CLR B-B As-Found:

As Left:

C.

2-HS-30-92A, CRDM CLR B-B As-Found:

As Left:

D.

2-HS-30-80A, CRDM CLR D-B As-Found:

As Left:

[29]

VERIFY ICS Point HD2064, VENT SYS HS-39A, 78A, 75A, 92A, 80A, displays NOT P-L.

[30]

PLACE Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B, in STOP PULL TO LOCK, AND VERIFY ICS Point HD2064, VENT SYS HS-39A, 78A, 75A, 92A, 80A, displays PULLT-L.

Data Package: Page _

of Date 6.1.4 Lower Compartment Cooler 2D-B Logic (continued)

[31]

ENSURE the following Handswitches are returned to their As-Found position recorded in Step 6.1.4[28].

(The As-Left position recorded in this step should match the As-Found position recorded in Step 6.1.4[28].)

A.

2-HS-30-39A, AIR RETURN FAN B-B As-Found:

As Left:

B.

2-HS-30-75A, LWR CNTMT CLR B-B As-Found:

As Left:

C.

2-HS-30-92A, CRDM CLR B-B As-Found:

As Left:

D.

2-HS-30-80A, CRDM CLR D-B As-Found:

As Left:

[32]

ENSURE ERCW Temperature Indicating Controller 2-TIC-67-108, LOWER CNTMT VENT CLR 2D TEMP CNTL, is returned to its As-Found positions recorded in Step 4.3[5]D.

Auto/Manual Status:

Indicated Controller Setpoint:

Indicated Controller Output:

1st CV

[33]

VERIFY successful completion of this SubSection 6.1.4.

(Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 84 of 144 Data Package: Page _

of Date 6.2 Lower Compartment Coolers Response to Phase B Containment Isolation Signal NOTE SubSubsections 6.2.1 and 6.2.2 may be performed in any order, provided their applicable predecessor SubSections are completed. Unless otherwise noted, the steps within each SubSection shall be performed in the order written. The diagram at the beginning of Section 6.0 may be used as a placekeeping tool throughout the performance of this Section.

6.2.1 Train A Lower Compartment Coolers (2A-A and 2C-A)

[1]

ENSURE all prerequisites listed in Section 4.0 for SubSection 6.2 have been completed.

[2]

ENSURE SubSections 6.1.1 and 6.1.3 have been completed.

[3]

PLACE Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A, to START, AND VERIFY on Handswitch 2-HS-30-74A:

Green Light OFF Red Light ON

[4]

PLACE Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A, to START, AND VERIFY on Handswitch 2-HS-30-77A:

Green Light OFF Red Light ON

[5]

ENSURE the following Control Rod Drive Mechanism coolers are OFF:

2-CLR-30-83, CRDM COOLER 2A-A 0

2-CLR-30-88, CRDM COOLER 2C-A

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 85 of 144 Data Package: Page _

of Date 6.2.1 Train A Lower Compartment Coolers (2A-A and 2C-A)

(continued)

NOTE The following steps will simulate a Train A Phase B Containment Isolation Signal and Phase B signal reset by closing and opening a test switch (TS-1, installed in step 4.3[1 1.1])

in SSPS Train A Output Cabinet 2-R-48.

[6]

PLACE Test Switch TS-1 in the CLOSED (ON) position.

[7]

VERIFY the following:

A.

On Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

B.

On Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

[8]

PLACE Test Switch TS-1 in the OPEN (OFF) position.

[9]

VERIFY the following:

A.

On Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A:

Green Light ON (Acc Crit) o Red Light OFF (Acc Crit)

B.

On Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

[10]

PLACE the following Transfer Switches in AUX:

A.

2-XS-30-74, LOWER COMPT COOLER 2A-A B.

2-XS-30-77, LOWER COMPT COOLER 2C-A

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 86 of 144 Data Package: Page of 6.2.1 Train A Lower Compartment Coolers (2A-A and 2C-A)

(continued)

[11]

PLACE Test Switch TS-1 in the CLOSED (ON) position.

[12]

VERIFY the following:

A.

On Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A:

Green Light ON Red Light OFF B.

On Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A:

Green Light ON Red Light OFF

[13]

PLACE Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, to CLOSE, AND VERIFY the following on Handswitch 2-HS-30-74C:

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[14]

PLACE Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-74C:

Green Light ON Red Light OFF

[15]

PLACE Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, to CLOSE, AND VERIFY the following on Handswitch 2-HS-30-77C:

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 87 of 144 Data Package: Page of Date 6.2.1 Train A Lower Compartment Coolers (2A-A and 2C-A)

(continued)

[16]

PLACE Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-77C:

Green Light ON Red Light OFF

[17]

PLACE Test Switch TS-1 in the OPEN (OFF) position.

[18]

VERIFY the following:

A.

On Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A:

Green Light ON Red Light OFF B.

On Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A:

Green Light ON Red Light OFF

[19]

PLACE the following Transfer Switches in NORMAL:

A.

2-XS-30-74, LOWER COMPT COOLER 2A-A B.

2-XS-30-77, LOWER COMPT COOLER 2C-A

[20]

PLACE the following Handswitches in STOP PULL TO LOCK:

A.

2-HS-30-74A, LWR CNTMT CLR A-A B.

2-HS-30-77A, LWR CNTMT CLR C-A

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 88 of 144 Data Package: Page _

of Date 6.2.2 Train B Lower Compartment Coolers (2B-B and 2D-B)

[1]

ENSURE all prerequisites listed in Section 4.0 for SubSection 6.2 have been completed.

[2]

ENSURE SubSections 6.1.2 and 6.1.4 have been completed.

[3]

PLACE Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B, to START, AND VERIFY on Handswitch 2-HS-30-75A:

Green Light OFF Red Light ON

[4]

PLACE Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B, to START, AND VERIFY on Handswitch 2-HS-30-78A:

Green Light OFF Red Light ON

[5]

ENSURE the following Control Rod Drive Mechanism coolers are OFF:

2-CLR-30-92, CRDM COOLER 2B-B 2-CLR-30-80, CRDM COOLER 2D-B

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 89 of 144 Data Package: Page _

of Date 6.2.2 Train B Lower Compartment Coolers (2B-B and 2D-B)

(continued)

NOTE The following steps will simulate a Train B Phase B Containment Isolation Signal and Phase B signal reset by closing and opening a test switch (TS-2, installed in step 4.3[11.2])

in SSPS Train B Output Cabinet 2-R-51.

[6]

PLACE Test Switch TS-2 in the CLOSED (ON) position.

[7]

VERIFY the following:

A.

On Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

B.

On Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

[8]

PLACE Test Switch TS-2 in the OPEN (OFF) position.

[9]

VERIFY the following:

A.

On Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

B.

On Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

[10]

PLACE the following Transfer Switches in AUX:

A.

2-XS-30-75, LOWER COMPT COOLER 2B-B13 B.

2-XS-30-78, LOWER COMPT COOLER 2D-B

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 90 of 144 Data Package: Page _

of 6.2.2 Train B Lower Compartment Coolers (2B-B and 2D-B)

(continued)

[11]

PLACE Test Switch TS-2 in the CLOSED (ON) position.

[12]

VERIFY the following:

A.

On Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B:

Green Light ON Red Light OFF B.

On Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B:

Green Light ON Red Light OFF

[13]

PLACE Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, to CLOSE, AND VERIFY the following on Handswitch 2-HS-30-75C:

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[14]

PLACE Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-75C:

Green Light ON Red Light OFF

[15]

PLACE Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, to CLOSE, AND VERIFY the following on Handswitch 2-HS-30-78C:

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 91 of 144 Data Package: Page of Date 6.2.2 Train B Lower Compartment Coolers (2B-B and 2D-B)

(continued)

[16]

PLACE Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-78C:

Green Light ON Red Light OFF

[17]

PLACE Test Switch TS-2 in the OPEN (OFF) position.

[18]

VERIFY the following:

A.

On Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B:

Green Light ON Red Light OFF B.

On Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B:

Green Light ON Red Light OFF

[19]

PLACE the following Transfer Switches in NORMAL:

A.

2-XS-30-75, LOWER COMPT COOLER 2B-B13 B.

2-XS-30-78, LOWER COMPT COOLER 2D-B

[20]

PLACE the following Handswitches in STOP PULL TO LOCK:

A.

2-HS-30-75A, LWR CNTMT CLR B-B B.

2-HS-30-78A, LWR CNTMT CLR D-B

Data Package: Page _

of Date 6.3 Lower Compartment Coolers Response to Bus Undervoltage NOTE SubSubsections 6.3.1 through 6.3.4 may be performed in any order, provided their applicable predecessor SubSection is completed. Unless otherwise noted, the steps within each SubSection shall be performed in the order written. The diagram at the beginning of Section 6.0 may be used as a placekeeping tool throughout the performance of this Section.

6.3.1 Lower Compartment Cooler 2A-A

[1]

ENSURE all prerequisites listed in Section 4.0 for SubSection 6.3 have been completed.

[2]

ENSURE SubSection 6.1.1 has been completed.

[3]

ENSURE Handswitch 2-HS-30-83A, CRDM CLR A-A, is in STOP PULL TO LOCK.

[4]

PLACE Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A, to START, AND VERIFY on Handswitch 2-HS-30-74A:

Green Light OFF Red Light ON NOTE The following step will simulate a Loss of Offsite Power.

[5]

MOMENTARILY PLACE a handheld jumper between Terminal Point 7 (Wire Al 7CTP) and Point 8 (Wire Al 7CT1) of Relay 2A1Y1, [480V SHUTDOWN BOARD 2A1-A, Compartment 6A]. (Drawing 618F938) 1st Cv

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 93 of 144 Data Package: Page of Date 6.3.1 Lower Compartment Cooler 2A-A (continued)

[6]

VERIFY on Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

NOTE The following step will simulate a restoration of bus voltage.

[7]

MOMENTARILY PLACE a handheld jumper between Terminal Point 3 (Wire DCE4) and Point 4 (Wire DCE5) of Relay 2A1 X1,

[480V SHUTDOWN BOARD 2A1-A, Compartment 6A].

(Drawing 618F938) 1 st Cv

[8]

VERIFY that LCC 2A-A remains OFF after approximately 1 minute, as indicated on Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

[9]

PLACE Transfer Switch 2-XS-30-74, LOWER COMPT COOLER 2A-A in AUX.

[10]

PLACE Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, to CLOSE, AND VERIFY the following on Handswitch 2-HS-30-74C:

Green Light OFF Red Light ON

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 94 of 144 Data Package: Page of Date 6.3.1 Lower Compartment Cooler 2A-A (continued)

NOTE The following step will simulate a Loss of Offsite Power.

[11]

MOMENTARILY PLACE a handheld jumper between Terminal Point 7 (Wire Al 7CTP) and Point 8 (Wire Al 7CT1) of Relay 2A1Y1. (Drawing 618F938) 1 st Cv

[12]

VERIFY on Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

NOTE The following step will simulate a restoration of bus voltage.

[13]

MOMENTARILY PLACE a handheld jumper between Terminal Point 3 (Wire DCE4) and Point 4 (Wire DCE5) of Relay 2A1X1.

(Drawing 618F938) 1 st Cv

[14]

VERIFY that LCC 2A-A STARTS after approximately 1 minute, as indicated on Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A:

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[15]

PLACE Transfer Switch 2-XS-30-74, LOWER COMPT COOLER 2A-A in NORMAL.

[16]

PLACE Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A, in STOP PULL TO LOCK.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 95 of 144 Data Package: Page _

of Date 6.3.2 Lower Compartment Cooler 2B-B

[1]

ENSURE all prerequisites listed in Section 4.0 for SubSection 6.3 have been completed.

[2]

ENSURE SubSection 6.1.2 has been completed.

[3]

ENSURE Handswitch 2-HS-30-92A, CRDM CLR B-B, is in STOP PULL TO LOCK.

[4]

PLACE Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B, to START, AND VERIFY on Handswitch 2-HS-30-75A:

Green Light OFF Red Light ON NOTE The following step will simulate a Loss of Offsite Power.

[5]

MOMENTARILY PLACE a handheld jumper between Terminal Point 7 (Wire B17DTP) and Point 8 (Wire B17DT1) of Relay 2B1Y1, [480V SHUTDOWN BOARD 2B1-B, Compartment 6A]. (Drawing 618F941) 1 st Cv

[6]

VERIFY on Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B:

a Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 96 of 144 Data Package: Page _

of Date 6.3.2 Lower Compartment Cooler 2B-B (continued)

NOTE The following step will simulate a restoration of bus voltage.

[7]

MOMENTARILY PLACE a handheld jumper between Terminal Point 3 (Wire DCE4) and Point 4 (Wire DCE5) of Relay 2B1X1,

[480V SHUTDOWN BOARD 2B1-B, Compartment 6A].

(Drawing 618F941) 1 st Cv

[8]

VERIFY that LCC 2B-B remains OFF after approximately 1 minute, as indicated on Handswitch 2-HS-30-75A, LWR CNTMT CLR 2B-B:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

[9]

PLACE Transfer Switch 2-XS-30-75, LOWER COMPT COOLER 2B-B in AUX.

[10]

PLACE Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, to CLOSE, AND VERIFY the following on Handswitch 2-HS-30-75C:

0 Green Light OFF 0

Red Light ON

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 97 of 144 Data Package: Page of Date 6.3.2 Lower Compartment Cooler 2B-B (continued)

NOTE The following step will simulate a Loss of Offsite Power.

[11]

MOMENTARILY PLACE a handheld jumper between Terminal Point 7 (Wire B17DTP) and Point 8 (Wire B17DT1) of Relay 2B1Y1. (Drawing 618F941) 1 st Cv

[12]

VERIFY on Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

NOTE The following step will simulate a restoration of bus voltage.

[13]

MOMENTARILY PLACE a handheld jumper between Terminal Point 3 (Wire DCE4) and Point 4 (Wire DCE5) of Relay 2B1X1.

(Drawing 618F941) 1st Cv

[14]

VERIFY that LCC 28-B STARTS after approximately 1 minute, as indicated on Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B:

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[15]

PLACE Transfer Switch 2-XS-30-75, LOWER COMPT COOLER 2B-B in NORMAL.

[16]

PLACE Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B, in STOP PULL TO LOCK.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 98 of 144 Data Package: Page of Date 6.3.3 Lower Compartment Cooler 2C-A

[1]

ENSURE all prerequisites listed in Section 4.0 for SubSection 6.3 have been completed.

[2]

ENSURE SubSection 6.1.3 has been completed.

[3]

ENSURE Handswitch 2-HS-30-88A, CRDM CLR C-A, is in STOP PULL TO LOCK.

[4]

PLACE Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A, to START, AND VERIFY on Handswitch 2-HS-30-77A:

Green Light OFF Red Light ON NOTE The following step will simulate a Loss of Offsite Power.

[5]

MOMENTARILY PLACE a handheld jumper between Terminal Point 7 (Wire A27DTP) and Point 8 (Wire A27DT1) of Relay 2A2Y1, [480V SHUTDOWN BOARD 2A2-A, Compartment 6A]. (Drawing 6947D67) 1st CV

[6]

VERIFY on Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 99 of 144 Data Package: Page _

of Date 6.3.3 Lower Compartment Cooler 2C-A (continued)

NOTE The following step will simulate a restoration of bus voltage.

[7]

MOMENTARILY PLACE a handheld jumper between Terminal Point 3 (Wire DCE4) and Point 4 (Wire DCE5) of Relay 2A2X1,

[480V SHUTDOWN BOARD 2A2-A, Compartment 6A].

(Drawing 6947D67) 1 st Cv

[8]

VERIFY that LCC 2C-A remains OFF after approximately 1 minute, as indicated on Handswitch 2-HS-30-77A, LWR CNTMT CLR 2C-A:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

[9]

PLACE Transfer Switch 2-XS-30-77, LOWER COMPT COOLER 2C-A in AUX.

[10]

PLACE Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, to CLOSE, AND VERIFY the following on Handswitch 2-HS-30-77C:

Green Light OFF Red Light ON

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 100 of 144 Data Package: Page _

of Date 6.3.3 Lower Compartment Cooler 2C-A (continued)

NOTE The following step will simulate a Loss of Offsite Power.

[11]

MOMENTARILY PLACE a handheld jumper between Terminal Point 7 (Wire A27DTP) and Point 8 (Wire A27DT1) of Relay 2A2Y1. (Drawing 6947D67) 1 st Cv

[12]

VERIFY on Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

NOTE The following step will simulate a restoration of bus voltage.

[13]

MOMENTARILY PLACE a handheld jumper between Terminal Point 3 (Wire DCE4) and Point 4 (Wire DCE5) of Relay 2A2X1.

(Drawing 6947D67) 1st Cv

[14]

VERIFY that LCC 2C-A STARTS after approximately 1 minute, as indicated on Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A:

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[15]

PLACE Transfer Switch 2-XS-30-77, LOWER COMPT COOLER 2C-A in NORMAL.

[16]

PLACE Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A, in STOP PULL TO LOCK.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 101 of 144 Data Package: Page _

of Date 6.3.4 Lower Compartment Cooler 2D-B

[1]

ENSURE all prerequisites listed in Section 4.0 for SubSection 6.3 have been completed.

[2]

ENSURE SubSection 6.1.4 has been completed.

[3]

ENSURE Handswitch 2-HS-30-80A, CRDM CLR D-B, is in STOP PULL TO LOCK.

[4]

PLACE Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B, to START, AND VERIFY on Handswitch 2-HS-30-78A:

Green Light OFF Red Light ON NOTE The following step will simulate a Loss of Offsite Power.

[5]

MOMENTARILY PLACE a handheld jumper between Terminal Point 7 (Wire B27DTP) and Point 8 (Wire B27DT1) of Relay 2B2Y1, [480V SHUTDOWN BOARD 2B2-B, Compartment 6A]. (Drawing 6947D85) 1st CV

[6]

VERIFY on Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B:

0 Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 102 of 144 Data Package: Page _

of Date 6.3.4 Lower Compartment Cooler 2D-B (continued)

NOTE The following step will simulate a restoration of bus voltage.

[7]

MOMENTARILY PLACE a handheld jumper between Terminal Point 3 (Wire DCE4) and Point 4 (Wire DCE5) of Relay 2B2X1,

[480V SHUTDOWN BOARD 2B2-B, Compartment 6A].

(Drawing 6947D85) 1st Cv

[8]

VERIFY that LCC 2D-B remains OFF after approximately 1 minute, as indicated on Handswitch 2-HS-30-78A, LWR CNTMT CLR 2D-B:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

[9]

PLACE Transfer Switch 2-XS-30-78, LOWER COMPT COOLER 2D-B in AUX.

[10]

PLACE Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, to CLOSE, AND VERIFY the following on Handswitch 2-HS-30-78C:

Green Light OFF Red Light ON

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 103 of 144 Data Package: Page _

of Date 6.3.4 Lower Compartment Cooler 2D-B (continued)

NOTE The following step will simulate a Loss of Offsite Power.

[11]

MOMENTARILY PLACE a handheld jumper between Terminal Point 7 (Wire B27DTP) and Point 8 (Wire B27DT1) of Relay 2B2Y1. (Drawing 6947D85) 1 st Cv

[12]

VERIFY on Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B:

Green Light ON (Acc Crit)

Red Light OFF (Acc Crit)

NOTE The following step will simulate a restoration of bus voltage.

[13]

MOMENTARILY PLACE a handheld jumper between Terminal Point 3 (Wire DCE4) and Point 4 (Wire DCE5) of Relay 2B2X1.

(Drawing 6947D85) 1 st Cv

[14]

VERIFY that LCC 2D-B STARTS after approximately 1 minute, as indicated on Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B:

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[15]

PLACE Transfer Switch 2-XS-30-78, LOWER COMPT COOLER 2D-B in NORMAL.

[16]

PLACE Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B, in STOP PULL TO LOCK.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 104 of 144 Data Package: Page _

of Date 6.4 Lower Compartment Coolers Auto-Start on Low Air Flow

[1]

ENSURE all prerequisites listed in Section 4.0 for SubSection 6.4 have been completed.

[2]

ENSURE SubSections 6.1, 6.2 and 6.3 have been completed.

NOTE The following step will enable the Train A LCCs' Auto-start on Low Flow function.

[3]

LAND Wire A17C2 (lifted in step 4.3[12]) on point 8 of Terminal Block 65B5, inside the front panel of 480V SHUTDOWN BOARD 2A1-A, Compartment 6A.

(Drawing 618F938) 1st Cv NOTE The following step will enable the Train B LCCs' Auto-start on Low Flow function.

[4]

LAND Wire B17D2 (lifted in step 4.3[13]) on point 5 of Terminal Block 65B2, inside the front panel of 480V SHUTDOWN BOARD 2B1-B Compartment 6A.

(Drawing 618F941) 1st Cv

[5]

PLACE Handswitch 2-HS-30-74A, LWR CNTMT CLR A-A, to A AUTO, AND VERIFY the following on Handswitch 2-HS-30-74A:

0 Green Light ON 0

Red Light OFF

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 105 of 144 Data Package: Page of _

Date 6.4 Lower Compartment Coolers Auto-Start on Low Air Flow (continued)

[6]

PLACE Handswitch 2-HS-30-75A, LWR CNTMT CLR B-B, to START, AND VERIFY the following on Handswitch 2-HS-30-75A:

Green Light OFF Red Light ON

[7]

PLACE Handswitch 2-HS-30-77A, LWR CNTMT CLR C-A, to START, AND VERIFY the following on Handswitch 2-HS-30-77A:

Green Light OFF Red Light ON

[8]

PLACE Handswitch 2-HS-30-78A, LWR CNTMT CLR D-B, to START, AND VERIFY the following on Handswitch 2-HS-30-78A:

Green Light OFF Red Light ON

[9]

PLACE the following Transfer Switches to AUX:

A.

2-XS-30-74, LOWER COMPT COOLER 2A-A B.

2-XS-30-75, LOWER COMPT COOLER 2B-B13 C.

2-XS-30-77, LOWER COMPT COOLER 2C-A D.

2-XS-30-78, LOWER COMPT COOLER 2D-B

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 106 of 144 6.4 Data Package: Page _

of Lower Compartment Coolers Auto-Start on Low Air Flow (continued)

[10]

PLACE and HOLD Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-75C:

Green Light ON Red Light OFF

[11]

VERIFY on Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, that LCC 2A-A is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[12]

RELEASE Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B.

[13]

PLACE and HOLD Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-74C:

Green Light ON Red Light OFF

[14]

VERIFY on Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, that LCC 2B-B is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[15]

RELEASE Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 107 of 144 6.4 Data Package: Page of Lower Compartment Coolers Auto-Start on Low Air Flow (continued)

[16]

PLACE and HOLD Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-77C:

Green Light ON Red Light OFF

[17]

VERIFY on Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, that LCC 2A-A is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[18]

RELEASE Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A.

[19]

PLACE and HOLD Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-74C:

Green Light ON Red Light OFF

[20]

VERIFY on Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, that LCC 2C-A is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[21]

RELEASE Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A.

Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 108 of 144 Data Package: Page of Date 6.4 Lower Compartment Coolers Auto-Start on Low Air Flow (continued)

[22]

PLACE and HOLD Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-78C:

Green Light ON Red Light OFF

[23]

VERIFY on Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, that LCC 2A-A is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[24]

RELEASE Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B.

[25]

PLACE and HOLD Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-74C:

Green Light ON Red Light OFF

[26]

VERIFY on Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, that LCC 2D-B is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[27]

RELEASE Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 109 of 144 6.4 Data Package: Page _

of Date Lower Compartment Coolers Auto-Start on Low Air Flow (continued)

[28]

PLACE Handswitch 2-HS-30-74C, LOWER COMPT COOLER 2A-A, to CLOSE, AND VERIFY the following on Handswitch 2-HS-30-74C:

Green Light OFF Red Light ON

[29]

PLACE Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-75C:

Green Light ON Red Light OFF

[30]

PLACE and HOLD Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-77C:

Green Light ON Red Light OFF

[31]

VERIFY on Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, that LCC 2B-B is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[32]

RELEASE Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 110 of 144 6.4 Data Package: Page of Lower Compartment Coolers Auto-Start on Low Air Flow (continued)

[33]

PLACE and HOLD Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-75C:

Green Light ON Red Light OFF

[34]

VERIFY on Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, that LCC 2C-A is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[35]

RELEASE Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B.

[36]

PLACE and HOLD Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-78C:

Green Light ON Red Light OFF

[37]

VERIFY on Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, that LCC 28-B is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[38]

RELEASE Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B.

Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 111 of 144 6.4 Data Package: Page of Date Lower Compartment Coolers Auto-Start on Low Air Flow (continued)

[39]

PLACE and HOLD Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-75C:

Green Light ON Red Light OFF

[40]

VERIFY on Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, that LCC 2D-B is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[41]

RELEASE Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B.

[42]

PLACE Handswitch 2-HS-30-75C, LOWER COMPT COOLER 2B-B, to CLOSE, AND VERIFY the following on Handswitch 2-HS-30-75C:

Green Light OFF Red Light ON

[43]

PLACE Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A:

Green Light ON Red Light OFF

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 112 of 144 Data Package: Page _

of Date 6.4 Lower Compartment Coolers Auto-Start on Low Air Flow (continued)

[44]

PLACE and HOLD Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-78C:

Green Light ON Red Light OFF

[45]

VERIFY on Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, that LCC 2C-A is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[46]

RELEASE Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B.

[47]

PLACE and HOLD Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A, to TRIP, AND VERIFY the following on Handswitch 2-HS-30-77C:

Green Light ON Red Light OFF

[48]

VERIFY on Handswitch 2-HS-30-78C, LOWER COMPT COOLER 2D-B, that LCC 2D-B is ON.

Green Light OFF (Acc Crit)

Red Light ON (Acc Crit)

[49]

RELEASE Handswitch 2-HS-30-77C, LOWER COMPT COOLER 2C-A.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 113 of 144 Data Package: Page _

of Date 6.4 Lower Compartment Coolers Auto-Start on Low Air Flow (continued)

[50]

PLACE the following Transfer Switches to NORMAL:

A.

2-XS-30-74, LOWER COMPT COOLER 2A-A B.

2-XS-30-75, LOWER COMPT COOLER 2B-B13 C.

2-XS-30-77, LOWER COMPT COOLER 2C-A D.

2-XS-30-78, LOWER COMPT COOLER 2D-B

[51]

PLACE the following Handswitches to STOP PULL TO LOCK:

A.

2-HS-30-74A, LWR CNTMT CLR A-A B.

2-HS-30-75A, LWR CNTMT CLR B-B C.

2-HS-30-77A, LWR CNTMT CLR C-A D.

2-HS-30-78A, LWR CNTMT CLR D-B

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 114 of 144 Data Package: Page of Date 6.5 Lower Compartment Cooler Performance

[1]

ENSURE all prerequisites listed in Section 4.0 for SubSection 6.5 have been completed.

[2]

ENSURE motor operating data and air flow measurements for the following Lower Compartment Coolers have been performed using GTM-05, HVAC Air Balance:

A.

2-CCU-30-74, CNTMT LOWER COMPARTMENT COOLER 2A-A B.

2-CCU-30-75, CNTMT LOWER COMPARTMENT COOLER 2B-B C.

2-CCU-30-77, CNTMT LOWER COMPARTMENT COOLER 2C-A D.

2-CCU-30-78, CNTMT LOWER COMPARTMENT COOLER 2D-B

[3]

ENSURE completed GTM-05 data sheets are attached to this instruction.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 115 of 144 Data Package: Page of Date 6.5 Lower Compartment Cooler Performance (continued)

[4]

RECORD the air flow measurement for each LCC individually, AND VERIFY it meets acceptance criteria:

A.

2-CCU-30-74, CNTMT LOWER COMPARTMENT COOLER 2A-A CFM Acc Crit: 48,700 CFM minimum B.

2-CCU-30-75, CNTMT LOWER COMPARTMENT COOLER 2B-B CFM Acc Crit: 48,700 CFM minimum C.

2-CCU-30-77, CNTMT LOWER COMPARTMENT COOLER 2C-A CFM Acc Crit: 48,700 CFM minimum D.

2-CCU-30-78, CNTMT LOWER COMPARTMENT COOLER 2D-B CFM Acc Crit: 48,700 CFM minimum

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 116 of 144 6.5 Data Package: Page of Lower Compartment Cooler Performance (continued)

[5]

RECORD the air flow measurements for each combination of any three LCCs operating together, AND VERIFY they meet acceptance criteria:

A.

LCCs 2A-A, 2B-B, and 2C-A operating together:

Total Air Flow to the Lower Compartment CFM Acc Crit: 146,000 CFM minimum Date Air flow to each Steam Generator Enclosure S/G #1:

CFM S/G #2:

CFM S/G #3:

CFM S/G #4:

CFM Acc Crit: 5,625 CFM minimum to each S/G enclosure Air Flow to the Pressurizer Cubicle CFM Acc Crit: 3,700 CFM minimum Air Flow to the Reactor Vessel Cavity CFM Acc Crit: 10,000 CFM minimum

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 117 of 144 6.5 Data Package: Page _

of Lower Compartment Cooler Performance (continued)

B.

LCCs 2A-A, 2C-A, and 2D-B operating together:

Total Air Flow to the Lower Compartment CFM Acc Crit: 146,000 CFM minimum Air flow to each Steam Generator Enclosure S/G #1:

CFM S/G #2:

CFM S/G #3:

CFM S/G #4:

CFM Acc Crit: 5,625 CFM minimum to each S/G enclosure Air Flow to the Pressurizer Cubicle CFM Acc Crit: 3,700 CFM minimum Air Flow to the Reactor Vessel Cavity CFM Acc Crit: 10,000 CFM minimum Date

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 118 of 144 Data Package: Page__ of 6.5 Lower Compartment Cooler Performance (continued)

C.

LCCs 2A-A, 2B-B, and 2D-B operating together:

Total Air Flow to the Lower Compartment CFM Acc Crit: 146,000 CFM minimum Air flow to each Steam Generator Enclosure S/G #1:

CFM S/G #2:

CFM S/G #3:

CFM S/G #4:

CFM Acc Crit: 5,625 CFM minimum to each S/G enclosure Air Flow to the Pressurizer Cubicle CFM Acc Crit: 3,700 CFM minimum Air Flow to the Reactor Vessel Cavity CFM Acc Crit: 10,000 CFM minimum Date

Data Package: Page of 6.5 Lower Compartment Cooler Performance (continued)

D. LCCs 2B-B, 2C-A, and 2D-B operating together:

Total Air Flow to the Lower Compartment CFM Acc Crit: 146,000 CFM minimum Air flow to each Steam Generator Enclosure S/G #1:

CFM S/G #2:

CFM S/G #3:

CFM S/G #4:

CFM Acc Crit: 5,625 CFM minimum to each S/G enclosure Air Flow to the Pressurizer Cubicle CFM Acc Crit: 3,700 CFM minimum Air Flow to the Reactor Vessel Cavity CFM Acc Crit: 10,000 CFM minimum Date

Data Package: Page of 6.5 Lower Compartment Cooler Performance (continued)

[6]

RECORD the air flow measurements for each train of LCCs operating together, AND VERIFY they meet acceptance criteria:

A.

Train A:

LCCs 2A-A and 2C-A operating together:

Total Air Flow to the Lower Compartment CFM Acc Crit: 105,000 CFM minimum Air Flow to the Pressurizer Cubicle CFM Acc Crit: 2,400 CFM minimum Air Flow to the Reactor Vessel Cavity CFM Acc Crit: 6,700 CFM minimum B.

Train B:

LCCs 2B-B and 2D-B operating together:

Total Air Flow to the Lower Compartment CFM Acc Crit: 105,000 CFM minimum Air Flow to the Pressurizer Cubicle CFM Acc Crit: 2,400 CFM minimum Air Flow to the Reactor Vessel Cavity CFM Acc Crit: 6,700 CFM minimum Date

Data Package: Page _

of Date 6.5 Lower Compartment Cooler Performance (continued)

[7]

RECORD the following data obtained during operation of Train A LCCs (2A-A and 2C-A operating together) on Data Sheets 1 & 3:

Motor Current Motor Voltage Atmospheric conditions

[8]

RECORD the following data obtained during operation of Train B LCCs (LCCs 2B-B and 2D-B operating together) on Data Sheets 2 & 4:

Motor Current Motor Voltage Atmospheric conditions

[9]

CALCULATE the Motor Horsepower at Design Density (HPDD) for each LCC using Data Sheets 1 through 4.

Data Package: Page of Date 6.5 Lower Compartment Cooler Performance (continued)

[10]

RECORD the HPDD of each LCC, AND VERIFY they are less than or equal to the LCC Motor Nameplate Horsepower:

A.

2-CCU-30-74, CNTMT LOWER COMPARTMENT COOLER 2A-A HP Acc Crit: 56 HP maximum B.

2-CCU-30-75, CNTMT LOWER COMPARTMENT COOLER 2B-B HP Acc Crit: 56 HP maximum C.

2-CCU-30-77, CNTMT LOWER COMPARTMENT COOLER 2C-A HP Acc Crit: 56 HP maximum D.

2-CCU-30-78, CNTMT LOWER COMPARTMENT COOLER 2D-B HP Acc Crit: 56 HP maximum

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 123 of 144 Data Package: Page _

of Date 7.0 POST PERFORMANCE ACTIVITY NOTE Post-performance steps may be performed in any order unless otherwise stated and should be completed as close in time as practicable to the end of the instruction performance.

[1]

REMOVE the switched jumpers installed in step 4.3[1 1] from the following locations:

[1.1]

Labeled TS-1:

In SSPS Train-A Output Cabinet 2-R-48, at TB615, between Pt. 11 (2340VL) and Pt. 12 (Wire CNA1).

(Drawing 45N2676-4) 1st Cv

[1.2]

Labeled TS-2:

In SSPS Train-B Output Cabinet 2-R-51, at TB615, between Pt. 11 (Wire 2435VL) and Pt. 12 (Wire CNB1).

(Drawing 45N2677-4) 1st Cv

[2]

NOTIFY the Unit 2 US/SRO/SM of the test completion and system alignment.

[3]

NOTIFY the Unit 1 US/SRO/SM of the test completion and system alignment.

RECORDS A.

QA Records Completed Test Package B.

Non-QA Records 8.0 None

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 124 of 144 Appendix A (Page 1 of 1)

TEST PROCEDURES/INSTRUCTIONS REFERENCE REVIEW Data Package: Page _

of Date NOTES

1)

Additional copies of this table may be made as necessary.

2)

Initial and date indicates review has been completed for impact.

PROCEDURE/

IMPACT INITIAL AND DATE.

INSTRUCTION Yes/No (N/A for no change)

GTM-05 FSAR Section 9.2.1 Section 9.4.7 Table 14.2-1, Sh 4 & 5 Table 14.2-1, Sh 38 & 39 WBN2-30RB-4002 G-37 2-TSD-30H-1 2-PTI-030L-01 2-PTI-067-02-A 2-PTI-067-02-B 2-PTI-067-03 MI-57.002 SSD-2-LPT-67-84 SSD-2-LPT-67-1 00 SSD-2-LPT-67-92 SSD-2-LPT-67-108 VM-F180-3066

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 125 of 144 Appendix B (Page 1 of 1)

TEMPORARY CONDITION LOG Data Package: Page of Date NOTES

1)

Additional copies of this table may be made as necessary.

2)

These steps will be N/A'd if no temporary condition existed.

ITEM TEMPORARY CONDITION PERFORMED RETURNED TO NORMAL No.

DESCRIPTION Step Performed By/Date Step Returned By/Date No.

CV By/Date No.

CV By/Date

Appendix C (Page 1 of 2)

PERMANENT PLANT INSTRUMENTATION LOG Data Package: Page _

of Date INSTRUMENT FILLED AND PLACED IN USED FOR POST-TEST OR CAL DUE VENTED1 SERVICE1 QUANTITATIVE POST-TEST CALIBRATION INSTRUMENT DATE ACC CRIT CAL DATE2 ACCEPTABLE 2 LOOP #

INIT/DATE INIT/DATE YES NO INITIAL/DATE 2-TE-30-21 1 G N/A NO N/A N/A 2-TE-30-21 1 H N/A NO N/A N/A 2-TE-30-21 11 N/A NO N/A N/A 2-TE-30-21 1J N/A NO N/A N/A 2-TE-30-21 1K N/A NO N/A N/A 2-TE-30-21 1 L N/A NO N/A N/A 2-TE-30-21 1 M N/A NO N/A N/A 2-TE-30-21 1 N N/A NO N/A N/A 2-FS-30-74A/B N/A NO N/A N/A 2-FS-30-74C/D N/A NO N/A N/A 2-FS-30-75A/B N/A NO N/A N/A 2-FS-30-75C/D N/A NO N/A N/A

Appendix C (Page 2 of 2)

PERMANENT PLANT INSTRUMENTATION LOG Data Package: Page _

of Date INSTRUMENT FILLED AND PLACED IN USED FOR POST-TEST OR CAL DUE VENTED1 SERVICE1 QUANTITATIVE POST-TEST CALIBRATION INSTRUMENT DATE ACC CRIT CAL DATE 2 ACCEPTABLE 2 LOOP #

INIT/DATE INIT/DATE YES NO INITIAL/DATE 2-FS-30-77A/B N/A NO N/A N/A 2-FS-30-77C/D N/A NO N/A N/A 2-FS-30-78A/B N/A NO N/A N/A 2-FS-30-78C/D N/A NO N/A N/A 2-LPT-67-84 N/A NO N/A N/A 2-LPT-67-92 N/A NO N/A N/A 2-LPT-67-100 N/A NO N/A N/A 2-LPT-67-108 N/A NO N/A N/A 1

These items may be initialed and dated by personnel performing the task. Instrumentation not required to be filled and vented may be identified as Not Applicable. (N/A) 2 May be identified as Not Applicable (N/A) if instrument was not used to verify/record quantitative acceptance criteria data.

3artment Coolers 2-PTI-030H-01 Rev. 0000 Page 128 of 144 Appendix D (Page 1 of 4)

ELECTRICAL LINEUP Data Package: Page of Date IDENTIFICATION LOCATION NOMENCLATURE POSITION VERIFIED BY:

INITIAL Main Control Room STOP 2-HS-30-74A 2-M-9 LWR CNTMT CLR A-A P

TOL PULL TO LOCK STOP 2-HS-30-75A 2-M-9 LWR CNTMT CLR B-B P

TOL PULL TO LOCK STOP 2-HS-30-77A 2-M-9 LWR CNTMT CLR C-A P

TOL PULL TO LOCK STOP 2-HS-30-78A 2-M-9 LWR CNTMT CLR D-B P

TOL PULL TO LOCK 2-HS-67-84A 0-M-27A LWR CNTMT CLR A P AUTO OUTLET TCV 2-HS-67-92A 0-M-27A LWR CNTMT CLR C P AUTO OUTLET TCV 2-HS-67-1 OOA 0-M-27A LWR CNTMT CLR B P AUTO OUTLET TCV 2-HS-67-1 08A 0-M-27A LWR CNTMT CLR D P AUTO OUTLET TCV Auxiliary Control Room LWR CNTMT CLR A-A 2-XS-67-84 2-L-11IA ECOULTCVNOR 2-XS-67-84 2-L-1 lA LWR CNTMT CLR C-A NOR ERCW OUTLET TCV 2-XS-67-92 2-L-11A LWR CNTMT CLR B-B NOR ERCW OUTLET TCV 2-XS-67-100 2-L-1 1 B LWR CNTMT CLR D-B NOR ERCW OUTLET TCV 2-XS-67-108 2-L-1 1B LWR CNTMT CLR A-A NOR ERCW OUTLET TCV 2-HS-67-84C 2-L-1 0 LWR CNTMT CLR C-A P AUTO ERCW OUTLET TCV 2-XS-67-92C 2-L-1 0 LWR CNTMT CLR B-B P AUTO ERCW OUTLET TCV 2-HS-67-100OC 2-L-1 0 LRCT L B P AUTO ERCW OUTLET TCV 2-HS-67-108C 2-L-10 LWR CNTMT CLR D-B P AUTO ERCW OUTLET TCV

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 129 of 144 Appendix D (Page 2 of 4)

ELECTRICAL LINEUP Data Package: Page of Date IDENTIFICATION LOCATION NOMENCLATURE POSITION VERIFIED BY:

INITIAL 480V Shutdown Board Room 2A 480V SHUTDOWN 2-BKR-30-74 BOARD SHUTDOW LOWER COMPT COOLER 2A-A DISCONNECTED Compartment 7C (2-CCU-30-74) 480V SHUTDOWN 2-HS-30-74C BOARD 2A1-A, LOWER COMPT COOLER 2A-A AUTO Compartment 5A 480V SHUTDOWN 2-XS-30-74 BOARD 2A1-A, LOWER COMPT COOLER 2A-A NORMAL Compartment 5A 480V SHUTDOWN 2-BKR-30-77 BOARD 2A2-A, LOWER COMPT COOLER 2C-A DISCONNECTED Compartment 7D (2-CCU-30-77) 480V SHUTDOWN 2-HS-30-77C BOARD 2A2-A, LOWER COMPT COOLER 2C-A AUTO Compartment 5A 480V SHUTDOWN 2-XS-30-77 BOARD 2A2-A, LOWER COMPT COOLER 2C-A NORMAL Compartment 5A 480V Shutdown Board Room 2B 2-BKR-30-75 480V SHUTDOWN LOWER COMPT COOLER 2-DISCONNECTED Compartment 7D (2-CCU-30-75) 480V SHUTDOWN 2-HS-30-75C BOARD 2B1-B, LOWER COMPT COOLER 2B-B AUTO Compartment 5A 480V SHUTDOWN 2-XS-30-75 BOARD 2B1-B, LOWER COMPT COOLER 2B-B NORMAL Compartment 5A 2-BKR-30-78 480V SHUTDOWN LOWER COMPT COOLER 2D-B DSONCE Compartment 7D (2-CCU-30-78) 480V SHUTDOWN 2-HS-30-78C BOARD 2132-13, LOWER COMPT COOLER 2D-B AUTO Compartment 5A 480V SHUTDOWN 2-XS-30-78 BOARD 2B2-B, LOWER COMPT COOLER 2D-B NORMAL Compartment 5A

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 130 of 144 Appendix D (Page 3 of 4)

ELECTRICAL LINEUP Data Package: Page of Date IDENTIFICATION LOCATION NOMENCLATURE OSITION VERIFIED BY:

IPOSIO INITIAL Vital Battery Board Room I 120V AC VITAL INSTR 2-BKR-235-1/7 POWR BOARD 2-1 AUX RELAY RACK 2-R-76 BUS A ON BKR 7 R120V AC VITAL INSTR AUX RELAY RACK C BUS TO 2-BKR-235-1/8 POWR BOARD 2-1 PNL 2-R-76ON BKR 8 1 120V AC VITAL INSTR AUX RELAY RACK A BUS TO 2-BKR-235-1/11 POWR BOARD 2-1 PNL 2-R-75ON BKR 11 Vital Battery Board Room II 120V AC VITAL INSTR 2-BKR-235-2/6 POWR BOARD 2-11 AUX RELAY RACK 2-R-76 BUS B ON BKR 6 BR120V AC VITAL INSTR AUX RELAY RACK B BUS TO 2-BKR-235-2/9 POWR BOARD 2-11 PNL 2-R-75ON BKR 9 Vital Battery Board Room III O-FU-236-3/A21 125V DC BATT BD III LOWER CONTAINMENT VENT CLR INSTALLED*

CKT A21 A SUPPLY VALVE 0-FU-236-3/A23 125V DC BATT BD III LOWER CONTAINMENT VENT CLR INSTALLED*

CKT A23 C SUPPLY VALVE R120V AC VITAL INSTR BOP INST RACK 1-R-141 2-BKR-235-3/26 POWR BOARD 2-111 1-R-144146/147 BUSON BKR 26 120V AC VITAL INSTR AUX RELAY RACK 2-BKR-235-3/40 POWR BOARD 2-111 SSPS AUX RELAYS ON BKR 40 Vital Battery Board Room IV O-FU-236-4/A9 125V DC BATT BD IV LOWER CONTAINMENT VENT CLR INSTALLED CKT A9 B SUPPLY VALVE O-FU-236-41A1 1 125V DC BATT BD IV LOWER CONTAINMENT VENT CLR INSTALLED CKT Al 1 D SUPPLY VALVE S

120V AC VITAL INSTR AUX BLD INSTR BUS B TO 2-BKR-235-4/26 POWR BOARD 2-IV PNL 2-L-26ON BKR 26 120V AC VITAL INSTR AUX RELAY RACK 2-BKR-235-4/35 POWR BOARD 2-IV SSPS AUX RELAYS ON BKR 35

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 131 of 144 Appendix D (Page 4 of 4)

ELECTRICAL LINEUP of Data Package: Page Date VERIFIED BY:

IDENTIFICATION LOCATION NOMENCLATURE POSITION INITIAL I

I I

I INITIAL Unit 2 Auxiliary Instrument Room LOWER COMPARTMENT COOLER 2-FU-275-R75/L23 2-R-75 UNITS 2A-A, 2B-B, 2C-A & 2D-B 2-FU-275-R75/L24 Row L, Fuse 23 & 24 ANNUNCIATION SEPERATION RELAYS LOWER COMPARTMENT COOLER 2-FU-275-R75/M7 2-R-75 UNITS 2A-A, 2B-B, 2C-A & 2D-B INSTALLED*

2-FU-275-R75/M8 Row M, Fuse 7 & 8 ANNUNCIATION SEPERATION RELAYS LOWER COMPARTMENT COOLER 2-FU-275-R75/M9 2-R-75 UNITS 2A-A, 2B-B, 2C-A & 2D-B INSTALLED*

2-FU-275-R75/M10 Row M, Fuse 9 & 10 ANNUNCIATION SEPERATION RELAYS LOWER COMPARTMENT COOLER 2-FU-275-R75/M23 2-R-75 UNITS 2A-A, 2B-B, 2C-A & 2D-B INSTALLED*

2-FU-275-R75/M24 Row M, Fuse 23 & 24 ANNUNCIATION SEPERATION RELAYS 2-FU-275-R76/19 2-R-76 PANEL 2-M-9 MOTOR TRIPOUT ANNUNCIATION SEPARATION INSTALLED*

2-FU-275-R76/I10 Row I, Fuse 9 & 10REA RELAY 2-FU-275-R76/113 2-R-76 PANEL 2-M-9 MOTOR TRIPOUT ANNUNCIATION SEPARATION INSTALLED*

2-FU-275-R76/I14 Row I, Fuse 13 & 14REA RELAY 2-FU-275-R76/N1 2-R-76 MOTOR TRIPOUT BUZZER FOR PANELS M-1 THROUGH M-6 AND INSTALLED*

2-FU-275-R76/N2 Row N, Fuse 1 & 2M9 M-9We

  • When installing fuses with actuators, ensure that the actuating rod is oriented correctly to provide for proper alarm initiation and visual indication.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 132 of 144 Appendix E (Page 1 of 5)

Background Calculations Data Package: Page _

of Date 1.0 Measurement uncertainties for parameters measured in this test must be incorporated into the test acceptance criteria Motor Design Density Horsepower From Reference 2.2C.4, the Lower Compartment Cooler Fan Motors' Nameplate Horsepower is 60 HP and the Motor Horsepower at Design Density conditions cannot exceed the Nameplate Horsepower.

Assuming each measured current and voltage values are within +/-2.4% as given in Reference 2.2C.1, then the adjusted Motor Horsepower and Design Density (HPDD) can be calculated:

HPDD = HPTD x DD DT Tes530Dnst40 +

(

T Tes Dnsiy DT 460 + T) 29.92) ftW D D = Design Density Where T = Temperature (OF) and B = Barometric Pressure (inHg) at time of test.

HPTD = IAVG X VAVG xPFxE 431 Power (P)= VAVG X 'AVG PF x E = Constant (0C 431 Where PF = Power Factor and E = Efficiency, which are both constants.

Therefore:

HPDD=PxCx DD DT

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 133 of 144 1.0 Appendix E (Page 2 of 5)

Background Calculations Data Package: Page__ of Motor Design Density Horsepower (continued)

The Operating Current and Voltage can be calculated:

Operating Current (IAVG)

=EI -

IA + IB + IC 3

3 IA = IAM+/- 0.0241AM = IAM (1+/- 0.024) 1 IB = IBM-0.0241BM =IBM(1-+/- 0.024) 1 IC = ICM +/- 0.0241cM = ICM (1 +/- 0.024) 1 Where IAM, IBM, and 'CM are measured currents in A, B, IAM (1 +/- 0.024)+ IBM (1 0.024) + Ic (I +/- 0.024)= (1i 3

Date A =1.0241AM or 0.9761AM B =1.0241BM or 0.9761 BM C =1.0241CM or 0.9761CM and C phases, respectively.

-0.024).(I,

+IBM + ICM) 3 And by applying that same logic to the measured Voltage (V):

VABM(I +/- 0.024)+ VACM (1 0.024)+ VBCM (I +/- 0.024) _ (I +/- 0.024)" (VABM + VACM + VBCM) 3 3

Appendix E (Page 3 of 5)

Background Calculations Data Package: Page _

of Date 1.0 Motor Design Density Horsepower (continued)

Assuming that the Barometric Pressure (B) and Temperature (T) are within +/-0.4% of range (27-31 inHg) and +/- 20F, respectively, as given in Reference 2.2C.1:

0.4% of 4 inHg = 0.016 inHg The Maximum percent error for the Barometric Pressure would occur at the lower end of the scale with an indicated Barometric Pressure of 27.00 inHg and an actual Barometric Pressure of 27.016 inHg.

( 27.00). = 0.00059 1-I.27.16)

This equates to a maximum error of 0.059%

The Maximum percent error for the Temperature would occur at the lower end of the scale with an indicated Temperature of 32 0F and an actual Temperature of 341F 1 -

= 0.0588 This equates to a maximum error of 5.88%

Looking at the equation for Test Density (DT):

Assuming that the numerator has an error equal to that of Barometric Pressure (B),

and the denominator has an error equal to that of Temperature (T), the total maximum error of Test Density will be:

0.059% = 1.00%

5.88%

Therefore, DT may only be 99.0% of its actual value.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 135 of 144 Appendix E (Page 4 of 5)

Background Calculations Data Package: Page__ of Date 1.0 Motor Design Density Horsepower (continued)

HPDD = Px Cx DD DT DD is also a constant and can be accounted for in C, so:

HPDD = P x C x 1 --

PxC DT DT Maximum calculated Power would be:

VAVG_ x I AVG P

0.976 0.976 0.9526 H D-PxC PxC HPDD =

X C

0.9526 x 0.990DT 0.943 IDT Therefore:

PxC

- 0.9431 x HPDD DT and since HPDD cannot be greater than 60 HP:

PxC = 0.9431xHPDD =0.9431x(60)= 56.59 DT Therefore the Acceptance Criteria for Motor Horsepower at Design Density will be adjusted to less than or equal to 56 HP to conservatively account for instrument inaccuracies.

Appendix E (Page 5 of 5)

Background Calculations Data Package: Page of Date 2.0 Air Flow Measurements This instruction does not perform any air flow measurements; these are done in GTM-05, HVAC Air Balance. The uncertainties associated with taking Air Flow measurements will be handled under GTM-05 and will not be calculated in this instruction.

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 137 of 144 Data Sheet 1 (Page 1 of 2)

Lower Compartment Cooler 2A-A Performance Data Package: Page _

of Date LOWER COMPARTMENT COOLER 2A-A MOTOR OPERATING DATA PHASE CURRENT (Amps)

A B

C Sum of Currents (11) =

PHASE VOLTAGE (Volts)

A to B Ato C B to C Sum of Voltages (XV) =

TEST CONDITIONS Design Density (DD) = 0.078 lb/ft3 Barometric Pressure (B) =

Power Factor (PF) = 82.5%

Ambient Temperature (T) =

Efficiency (E) = 94.7%

inHg OF Average Current (IAvG)

Amps 3

3 X-V Average Voltage (VAVG) = -

=

3 3

Volts

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 138 of 144 Data Sheet 1 (Page 2 of 2)

Lower Compartment Cooler 2A-A Performance Data Package: Page of Calculate the Air Density during the test:

Test Density (DT) =

530 +

B T

(460 +T )Y29.92)

/ft, Date DT= 4650

)x(

29.92

)0.075=

lb/3

/ft3I Calculate the Motor Horsepower at Test Density (HPTD)

HPDTD = IAVG x VAVc x PF x E 431 X

x 0.825 x 0.947 HPTD =

HP 431 Calculate the Motor Horsepower at Design Density (HPDD)

HPDD = HPTD x DD DT HPDD =

0.078 lb x

/ft 3

%t3 HP Calculations Performed By:

Calculations Verified By:

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 139 of 144 Data Sheet 2 (Page 1 of 2)

Lower Compartment Cooler 2B-B Performance Data Package: Page _

of Date LOWER COMPARTMENT COOLER 2B-B MOTOR OPERATING DATA PHASE CURRENT (Amps)

A B

C Sum of Currents (11) =

PHASE VOLTAGE (Volts)

A to B Ato C B to C Sum of Voltages (IV) =

TEST CONDITIONS Design Density (DD) = 0.078 lb/ft3 Barometric Pressure (B) =

Power Factor (PF) = 82.5%

Ambient Temperature (T) =

Efficiency (E) = 94.7%

inHg oF Average Current (IAvG)

Amps 3

3 IV Average Voltage (VAVG) =-

=

=

3 3

Volts

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 140 of 144 Data Sheet 2 (Page 2 of 2)

Lower Compartment Cooler 2B-B Performance Data Package: Page _

of Calculate the Air Density during the test:

Test Density (DT) =C 530 +

B x

9

.0752 (460+T 29.92) f13 Date DT =530

2. x0.075 =_1/_/_l K 29.92

/ft 3 Calculate the Motor Horsepower at Test Density (HPTD)

HPDTD= IAVG x VA VGxPFxE 431 x

x 0.825 x 0.947 HPTD =

HP 431 Calculate the Motor Horsepower at Design Density (HPDD)

HPDD = HPTD x DD DT 0.0781bIV 3

HPDD =

x

=

lb

% 3 HP Calculations Performed By:

Calculations Verified By:

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 141 of 144 Data Sheet 3 (Page 1 of 2)

Lower Compartment Cooler 2C-A Performance Data Package: Page of Date LOWER COMPARTMENT COOLER 2C-A MOTOR OPERATING DATA PHASE CURRENT (Amps)

A B

C Sum of Currents (11) =

PHASE VOLTAGE (Volts)

A to B AtoC B to C Sum of Voltages (YXV) =

TEST CONDITIONS Design Density (DD) = 0.078 lb/ft3 Barometric Pressure (B) =

inHg Power Factor (PF) = 82.5%

Ambient Temperature (T) =

OF Efficiency (E) = 94.7%

Al Average Current (IAvG) -

Amps 3

3 XV Average Voltage (VAVG) = -

=

3 3

Volts

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 142 of 144 Data Sheet 3 (Page 2 of 2)

Lower Compartment Cooler 2C-A Performance Data Package: Page _

of Calculate the Air Density during the test:

Test Density (DT) =-

530 B*(

x0.075Ib*

460+T 29.92) ft3 DT= 460+

29.92

>0.075 Calculate the Motor Horsepower at Test Density (HPTD)

I AGx V AxPFxE HPDTD =

AvG AVG 431 Date lb

.ft 3 x

x 0.825 x 0.947 HPTD =

HP 431 Calculate the Motor Horsepower at Design Density (HPDD)

HPDD = HPTD x DD DT HPDD =

0.0781b/f 3 lb ft 3 HP Calculations Performed By:

Calculations Verified By:

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 143 of 144 Data Sheet 4 (Page 1 of 2)

Lower Compartment Cooler 2D-B Performance Data Package: Page _

of Date LOWER COMPARTMENT COOLER 2D-B MOTOR OPERATING DATA PHASE CURRENT (Amps)

A B

C Sum of Currents (ZI) =

PHASE VOLTAGE (Volts)

A to B Ato C B to C Sum of Voltages (YXV) =

TEST CONDITIONS Design Density (DD) = 0.078 lb/ft3 Barometric Pressure (B) =

inHg Power Factor (PF) = 82.5%

Ambient Temperature (T) =

OF Efficiency (E) = 94.7%

Average Current (IAVG)

Amps 3

3 X-V Average Voltage (VAVG) = -

=

3 3

Volts

WBN Lower Compartment Coolers 2-PTI-030H-01 Unit 2 Rev. 0000 Page 144 of 144 Data Sheet 4 (Page 2 of 2)

Lower Compartment Cooler 2D-B Performance Data Package: Page _

of Calculate the Air Density during the test:

Test Density (DT) = C,530

+B x 0.275

.b9 (460 +T 29.92)

/ft, Date DT =

460+

530 29.92 x 0.075=

,. 29.92 lb ft3 Calculate the Motor Horsepower at Test Density (HPTD)

HPDTD = IAVG xVAVGxPFxE 431 x

x 0.825 x 0.947 HPTD 431 HP Calculate the Motor Horsepower at Design Density (HPDD)

HPDD = HPTD x DD DT 0.078 Ib HPDD =

x

=

%f 3

HP Calculations Performed By:

Calculations Verified By: