Letter Prairie Island Nuclear Generating Plant - Request for Information for Management of Gas Accumulation in Emergency Core Cooling, Decay Heat Removal, and Containment Spray Systems Inspection; 05000282-11-002 and 05000306-11-002
ML103070372
Person / Time
Site: Prairie Island  
Issue date: 11/03/2010
From: Ann Marie Stone
NRC/RGN-III/DRS/EB2
To: Schimmel M
Northern States Power Co
References
IR-11-002
Download: ML103070372 (5)


See also: IR 05000282/2011002

Text

UNITED STATES

NUCLEAR REGULATORY COMMISSION

REGION III

2443 WARRENVILLE ROAD, SUITE 210

LISLE, IL 60532-4352

November 3, 2010

Mr. Mark A. Schimmel

Site Vice President

Prairie Island Nuclear Generating Plant

Northern States Power Company, Minnesota

1717 Wakonade Drive East

Welch, MN 55089

SUBJECT: PRAIRIE ISLAND NUCLEAR GENERATING PLANT - REQUEST FOR

INFORMATION FOR MANAGEMENT OF GAS ACCUMULATION IN

EMERGENCY CORE COOLING, DEACY HEAT REMOVAL, AND

CONTAINMENT SPRAY SYSTEMS INSPECTION; 05000282/2011-002;

05000306/2011-002(DRS)

Dear Mr. Schimmel:

On January 24, 2011, the NRC will begin the on-site portion of the Gas Accumulation

Management in Emergency Core Cooling, Decay Heat Removal, and Containment Spray

Systems Temporary Instruction at your Prairie Island Nuclear Generating Plant. This inspection

will be performed in accordance with NRC Temporary Instruction (TI) 2515/177.

In order to minimize the impact that the inspection have on the site and to ensure a productive

inspection, we have enclosed a request for documents needed for the inspection. The

documents have been divided into three groups for each stage of the inspection.

The first group lists information necessary for our initial inspection scoping activities.

This information should be available to the inspector no later than November 29, 2010.

By December 10, 2010, the inspector will communicate the initial selected samples.

The second group of documents lists items needed to support our in-office preparation

activities. This set of documents should be available at the Regional Office no later than

January 10, 2011. This information should be separated by information request number,

especially if provided electronically (e.g., folder with the information request number).

During the in-office preparation activities, the inspectors may identify additional

information needed to support the inspection.

The last group includes the additional information mentioned above as well as plant

specific reference material. This information should be available to the inspectors on

January 24, 2011. It is also requested that corrective action documents and/or

questions developed during the inspections be provided to the inspectors as the

documents are generated.

M. Schimmel

-2-

It is important that these documents be as complete as possible, in order to minimize the

number of documents requested during the preparation week or during the on-site inspection.

If no activities were accomplished associated with a specific request, then provide a statement

indicating that the request is not applicable.

The lead inspector for this inspection is Caroline Tilton. If there are questions about the material

requested, or the inspection, please call Ms. Tilton at (630) 829-9718. Please send the

information to the following e-mail address caroline.tilton@nrc.gov. A hard-copy with the

required information is also an acceptable option.

This letter does not contain new or previous changes information collection requirements

subject to the Paperwork Reduction Act of 1995 (44 U.S.C. 3501 et seq.). Existing information

collection requirements were approved by the Office of Management and Budget, control

number 3150-0011. The NRC may not conduct or sponsor, and a person is not required to

respond to, a request for information or an information collection requirement unless the

requesting document displays a currently valid Office of Management and Budget control

number.

In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter and its

enclosure will be available electronically for public inspection in the NRC Public Document

Room or from the Publicly Available Records (PARS) component of NRC's document system

(ADAMS), accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the

Public Electronic Reading Room).

Sincerely,

/RA/

Ann Marie Stone, Chief

Engineering Branch 2

Division of Reactor Safety

Docket Nos. 50-282; 50-306

License Nos. DPR-42; DPR-60

Enclosures:

TEMPORARY INSTRUCTION (TI 2515/177) DOCUMENT REQUEST

cc w/encl:

Distribution via Listserve

TEMPORARY INSPECTION (TI 2515/177) DOCUMENT REQUEST

1

Enclosure

Inspection Report: 05000282/2011-002; 05000306/2011-002(DRS)

Inspection Dates:

January 24-28, 2011, and February 7-11, 2011

Inspection Procedure:

TI 2515/177, Management of Gas Accumulation in Emergency

Core Cooling, Decay Heat Removal, and Containment Spray

Systems

Inspectors:

Caroline Tilton (lead inspector)

(630) 829-9718

caroline.tilton@nrc.gov

Néstor J. Féliz Adorno

(630) 829-9739

nestor.feliz-adorno@nrc.gov

I.

Information Requested By November 29, 2010

1.

Copy of the station response to Generic Letter (GL) 2008-01 and any supplemental

reports.

2.

Copies of all the requests for additional information (RAIs) and the associated

responses.

3.

List of corrective action program documents (with a short description) associated

with GL 2008-01, voids in piping, and pressure transients for the previous three

years.

4.

List of the suction piping sections identified as susceptible to gas accumulation (the

list should identify the corresponding system).

5.

List of the discharge piping sections identified as susceptible to gas accumulation

(the list should identify the corresponding system).

6.

List of changes (with a short description and tracking number) to the Final Safety

Evaluation Report (FSAR), Technical Specifications, Technical Specification

Bases, and Technical Requirement Manual associated with the resolution of

GL 2008-01.

7.

List of calculations associated with GL 2008-01 (with a short description of the

calculation and the change), including calculations that have been changed or

created in response to GL 2008-01.

TEMPORARY INSPECTION (TI 2515/177) DOCUMENT REQUEST

2

Enclosure

II.

Information Requested By January 10, 2011

1. Copies of program documents and procedures developed to implement the

resolution of GL 2008-01.

2.

Copies of the selected corrective action program documents.

3.

Copies of the selected licensing and design basis document changes.

4.

Copies of isometric drawings of the subject systems (hard-copies are preferred).

5.

Copies of piping and instrumentation diagrams (P&IDs) of the subject systems

(hard-copies are preferred).

6.

List of commitments (with a description) made in response to GL 2008-01 including

the status of each.

7.

List of actions that were completed in response to GL 2008-01.

8.

Copies of all the corrective actions identified in the nine-month response and

supplemental reports.

9.

List (with a short description) of gas intrusion mechanisms that apply to the plant

and the affected system locations (e.g., identify the source, conditions, and

expected void locations).

10. Design basis documents of the subject systems (i.e., emergency core cooling,

decay heat removal, and containment spray systems).

11. Design basis documents of keep-full systems of the subject systems.

12. Copies of self-assessments associated with the implementation of the GL 2008-01

program.

13. If available, electronic copies of the current Technical Specifications, Technical

Specifications Basis, Final Safety Analysis Report, and Technical Report Manual.

III.

Information Requested to be Available on First Day of Inspection, January 24,

2011

1.

Copies of surveillance procedures associated with the resolution of GL 2008-01

and the results of the last two surveillances for the subject systems.

2.

Copies of the modification packages for hardware modifications as part of the

resolution of GL 2008-01.

3.

Copies of the selected calculations.

TEMPORARY INSPECTION (TI 2515/177) DOCUMENT REQUEST

3

Enclosure

4.

Copies of procedures use for detecting and determining void volumes.

5.

Copies of procedures use for filling and venting.

6.

Subject systems walkdown work documents associated with the resolution of

GL 2008-01 and the results of these walkdowns.

7.

Copies of the engineering evaluations performed for all identified voids.

8.

Copies of trends of periodic venting results.

9.

Copy of the design change review checklist that establish if a design change

introduces or increases the potential for gas accumulation beyond established

acceptance criteria.

10. Copies of training documents that ensure that personnel are aware of gas-related

concerns.

11. Copy of the void transport analysis.

12. Basis for the void acceptance criteria (e.g., calculation). If applicable, provide the

justification for any deviation from the void acceptance criteria established by the

Office of Nuclear Reactor Regulations (NRR).

13. Basis for horizontal pipe acceptance criteria (e.g., calculation).

14. Copy of vortexing calculations associated with systems under the scope of

GL 2008-01.

15. If applicable, provide a list of inaccessible locations where plant walkdowns of the

subject systems have not been completed. Include an explanation of why each

area is considered inaccessible.

If you have questions regarding the information requested, please contact the lead inspector.

M. Schimmel

-2-

It is important that these documents be as complete as possible, in order to minimize the number of

documents requested during the preparation week or during the on-site inspection.

If no activities were accomplished associated with a specific request, then provide a statement indicating

that the request is not applicable.

The lead inspector for this inspection is Caroline Tilton. If there are questions about the material

requested, or the inspection, please call Ms. Tilton at (630) 829-9718.

This letter does not contain new or previous changes information collection requirements subject to the

Paperwork Reduction Act of 1995 (44 U.S.C. 3501 et seq.). Existing information collection requirements

were approved by the Office of Management and Budget, control number 3150-0011. The NRC may not

conduct or sponsor, and a person is not required to respond to, a request for information or an

information collection requirement unless the requesting document displays a currently valid Office of

Management and Budget control number.

In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter and its enclosure

will be available electronically for public inspection in the NRC Public Document Room or from the

Publicly Available Records (PARS) component of NRC's document system (ADAMS), accessible from the

NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Sincerely,

/RA/

Ann Marie Stone, Chief

Engineering Branch 2

Division of Reactor Safety

Docket Nos. 50-282; 50-306

License Nos. DPR-42; DPR-60

Enclosures:

TEMPORARY INSTRUCTION (TI 2515/177) DOCUMENT REQUEST

cc w/encl:

Distribution via Listserve

DISTRIBUTION:

See next page

DOCUMENT NAME: G:\\DRSIII\\DRS\\WIP\\Ltr 11__10 Prairie Island RFI - TI177 PI NFA.docx

9 Publicly Available

9 Non-Publicly Available 9 Sensitive 9 Non-Sensitive

To receive a copy of this document, indicate in the concurrence box C = Copy without attach/encl; E = Copy with attach/encl N = No copy

OFFICE

RIII

RIII

NAME

AMStone for NFAdorno:ls

AMStone for CTilton

AMStone

DATE

11/03/10

11/03/10

11/03/10

OFFICIAL RECORD COPY

Letter to Mr. Mark A. Schimmel from Ms. Ann Marie Stone dated November 3, 2010.

SUBJECT:

PRAIRIE ISLAND NUCLEAR GENERATING PLANT - REQUEST FOR

INFORMATION FOR MANAGEMENT OF GAS ACCUMULATION IN EMERGENCY CORE

COOLING, DEACY HEAT REMOVAL, AND CONTAINMENT SPRAY SYSTEMS INSPECTION;