From:
Singal, Balwant Sent:
Thursday, August 12, 2010 1:23 PM To:
tamera.ervin@luminant.com Cc:
Timothy.Hope@luminant.com; Waig, Gerald
Subject:
TSTF-501 Amendment Request - TACs ME4026 and ME4027 Tamera:
The U.S. Nuclear Regulatory commission (NRC) staff has the following clarification question for the subject amendment request.
RAI Question:
Comanche Peak Nuclear Power Plant (CPNPP), Units 1 and 2, Technical Specification (TS) 3.8.3, Diesel Fuel Oil, Lube Oil, and Stating Air, Condition B and the TS Bases B 3.8.3, Diesel Fuel Oil, Lube Oil, and Starting Air, Action B.1, provides stored lube oil numerical values in inches below the low static level of the lube oil dipstick. TSTF-501 provides, in part, for the relocation of stored lube oil volumetric values, in gallons, to licensee control.
Please provide the CPNPP, Units 1 and, stored lube oil volumetric values, in gallons, corresponding to 1.75 and 5.5 inches below the low static level on the lube oil dipstick consistent with the volumetric values identified in TSTF-501.
I do not intend to issue the formal Request for Additional Information (RAI) letter and this e-mail will be treated as formal RAI. Please provide your response by September 10, 2010.
Also, please advise me if you have any questions.
Thanks.
Balwant K. Singal Senior Project Manager (Comanche Peak and Wolf Creek)
Nuclear Regulatory Commission Division of Operating Reactor Licensing Balwant.Singal@nrc.gov Tel: (301) 415-3016 Fax: (301) 415-1222 E-mail Properties Mail Envelope Properties ()
Subject:
TSTF-501 Amendment Request - TACs ME4026 and ME4027 Sent Date: 8/12/2010 1:04:39 PM Received Date: 8/12/2010 1:22:00 PM The image cannot be displayed. Your computer may not have enough memory to open the image, or the image may have been corrupted. Restart your computer, and then open the file again. If the red x still appears, you may have to delete the image and then insert it again.
From: Singal, Balwant Created By: Balwant.Singal@nrc.gov Recipients:
tamera.ervin@luminant.com (tamera.ervin@luminant.com)
Tracking Status: None Timothy.Hope@luminant.com (Timothy.Hope@luminant.com)
Tracking Status: None Gerald.Waig@nrc.gov (Waig, Gerald)
Tracking Status: None Post Office:
Files Size Date & Time MESSAGE 11814 8/12/2010 image001.jpg 1693 Options Expiration Date:
Priority: olImportanceNormal ReplyRequested: False Return Notification: False Sensitivity: olNormal Recipients received: