ML101750117
ML101750117 | |
Person / Time | |
---|---|
Site: | Dresden ![]() |
Issue date: | 06/08/2009 |
From: | Charles Phillips NRC/RGN-III/DRP/B1 |
To: | Steven Orth, Ring M, Slawinski W NRC/RGN-III, NRC/RGN-III/DRP/B1, Division of Reactor Safety III |
References | |
FOIA/PA-2010-0209 | |
Download: ML101750117 (2) | |
Similar Documents at Dresden | |
---|---|
Category:Drawing
MONTHYEARML1014705942010-05-25025 May 2010
[Table view]Yard Diagram Showing Sample Points and Sample Results at Dresden ML1014705962010-05-25025 May 2010 Diagram of the CSTs in Relation to the Reactor Building and the Locations of the Storm Drains at Dresden SVPLTR 09-0045, Revised License Renewal Commitment for the Testing of Drywell to Suppression Chamber Vent Lines Expansion Bellows2009-10-0202 October 2009 Revised License Renewal Commitment for the Testing of Drywell to Suppression Chamber Vent Lines Expansion Bellows ML1017501172009-06-0808 June 2009 Email from C. Phillips to M. Ring and Others Dresden Station Diagram W/Attachment Site Diagram ML1015505552009-06-0606 June 2009 Drawing - Dresden Csts, Clean Demin Tank and Well Water Tank ML1017501152009-06-0505 June 2009 Email from C. Phillips to M. Ring and Others Potential Dresden Tritium Leak W/ Attachment ML0614501052006-05-12012 May 2006 Drawing, Dresden Sample Points ML0614501102006-05-12012 May 2006 Drawing, Dresden Ground Water Monitoring Wells Trending RS-03-001, RAI 2.1.1- Supplemental Information Request Boundary Diagrams - Dresden Units 2 & 3 - 3rd Drawing2003-01-0303 January 2003 RAI 2.1.1- Supplemental Information Request Boundary Diagrams - Dresden Units 2 & 3 - 3rd Drawing ML0226107092002-09-0606 September 2002 Fourth Interval Inservice Inspection Program Plan, Attachment C ML17252B5771978-04-14014 April 1978 Drawing 12E2079, Rev. AC, Elec. Installation Reactor Bldg. El. 545'-6 North. ML17252B5781977-06-0606 June 1977 Drawing 12E2161, Rev. AD, Instrument System Control Room-Plan. ML17252B5751977-04-14014 April 1977 Drawing 4E-6508, Rev. C, Electrical Installation Air-Seals and Fire-Stops Quad-Cities Station Units 1-2. ML17252B5761977-04-14014 April 1977 Drawing 4E-6508A, Rev. a, Electrical Installation Air-Seals and Fire-Stops Quad-Cities Station Units 1 and 2. ML17252B5791977-03-16016 March 1977 Drawing 12E6508, Rev. C, Electrical Installation Air-Seals and Fire-Stops Dresden Nuclear Station. ML17252B5801977-03-16016 March 1977 Drawing 12E6508A, Rev. a, Electrical Installation Air-Seals and Fire-Stops Dresden Nuclear Power Station. ML17252B5811975-09-0303 September 1975 Drawing 22E03130, Rev. a, Electrical Installation Air Seals and Fire Stops Zion Station Units 1 and 2. ML17252A9541973-08-16016 August 1973 Letter Regarding Inspection of Bergen-Patterson Hydraulic Shock Suppressor at Dresden Nuclear Power Station Unit 3 ML17252B5831967-09-19019 September 1967 Drawing 94D98OIED745 ML17252B5821967-08-22022 August 1967 Drawing 75C242679, Rev. 1, Turbine Bldg, MOC #25-1. 2010-05-25 Category:E-Mail MONTHYEARML23339A0882023-12-0404 December 2023
[Table view]NRR E-mail Capture - NRC Acceptance Review Re Dresden, Units 2 and 3 Request for Relief I5R-22 ML23328A0092023-11-22022 November 2023 Supplement - Dresden Security Rule Exemption Request ISFSI Docket No. Reference (EPID L-2023-LLE-0031) (Email) ML23304A0172023-10-30030 October 2023 NRR E-mail Capture - Final RCI - Constellation Energy Generation, LLC - Dresden 1, 2 & 3 - Exemption from Security Rule (L-2023-LLE-0031) ML23268A0022023-09-22022 September 2023 NRR E-mail Capture - Constellation Energy Generation, LLC - Fleet Request - Acceptance of License Amendment Request to Adopt TSTF-264-A, Revision 0 ML23264A7992023-09-21021 September 2023 NRR E-mail Capture - Final RAI - Constellation Energy Generation, LLC Fleet Request License Amendment Request to Adopt TSTF-580, Revision 1 ML23263A9932023-09-20020 September 2023 NRR E-mail Capture - Dresden Nuclear Power Station, Units 2 and 3 - Acceptance of Licensing Action Submittal Re Amendment to Adopt TSTF-564 ML23163A2292023-06-12012 June 2023 NRR E-mail Capture - Constellation Energy Generation, LLC - Fleet Request - Acceptance of License Amendment Request to Adopt TSTF-580, Revision 1 ML23052A0652023-02-21021 February 2023 NRR E-mail Capture - Dresden Units 2 and 3 - Request for Additional Information for Alternative Request RV-23H ML23026A0172023-01-23023 January 2023 NRR E-mail Capture - (External_Sender) IEMA Response Action - Request for Comments on the Proposed Issuance of Amendment to Technical Specification 4.3.1 for Dresden Nuclear Power Station, Units 2 and 3 ML23019A0132023-01-12012 January 2023 NRR E-mail Capture - Final RAI Dresden 2 and 3 - License Amendment Pertaining to GNF3 Fuel Transition ML22354A2622022-12-20020 December 2022 NRR E-mail Capture - Constellation Energy Generation, LLC - Fleet Request - Acceptance of Request to Use Certain Provisions of the 2019 Edition of the ASME BPV Code, Section XI ML22325A1212022-11-21021 November 2022 NRR E-mail Capture - NRC Acceptance Review Re Dresden, Units 2 and 3 Request for Relief RV-02D (EPID L-2022-LLR-0075), RV-03 (EPID L-2022-LLR-0076), and RV-23H ML22301A0902022-10-28028 October 2022 NRR E-mail Capture - Constellation Energy Generation, LLC - Fleet Request - Acceptance of License Amendment Request to Adopt TSTF-301, Revision 2 ML22290A0842022-10-13013 October 2022 NRR E-mail Capture - Dresden 2 and 3 - RAI License Amendment Request Regarding New Fuel Storage Vault and Spent Fuel Storage Pool Criticality Methodologies ML22258A1882022-09-15015 September 2022 NRR E-mail Capture - Acceptance Review: Dresden 2 and 3 License Amendment Request to Revise Technical Specification 3.1.4, ML22258A1872022-09-13013 September 2022 NRR E-mail Capture - NRC Acceptance Review Dresden, Units 2 and 3, Amendment Request - Transition to GNF3 Fuel ML22229A0752022-08-16016 August 2022 NRR E-mail Capture - NRC Acceptance Review Dresden, Units 2 and 3 Request for Relief 16R-09 ML22229A0762022-08-16016 August 2022 NRR E-mail Capture - NRC Acceptance Review Dresden, Units 2 and 3 Request for Relief 16R-10 ML22203A0442022-07-21021 July 2022 Request for Additional Information (RAI) ML22200A0782022-07-19019 July 2022 NRR E-mail Capture - Constellation Energy Generation, LLC - Fleet Request to Use Honeywell Mururoa V4F1 R Supplied Air Suits ML22199A2412022-07-18018 July 2022 NRR E-mail Capture - Acceptance Review: Dresden Units 2 and 3 - License Amendment Request New Fuel Vault Storage and SFP Criticality Safety Analysis Methodology ML22199A2422022-07-13013 July 2022 NRR E-mail Capture - Draft RAI Dresden 2 and 3 Proposed Alternative Related to Sblc Nozzle Inspection for the Sixth Inservice Inspection Interval ML22103A2112022-04-12012 April 2022 NRR E-mail Capture - NRC Acceptance Review Dresden, Units 2 and 3 Request for Relief (16R-01) - EPID L-2022-LLR-0037 ML22103A2132022-04-12012 April 2022 NRR E-mail Capture - NRC Acceptance Review Dresden, Units 2 and 3 Request for Relief (16R-02) - EPID L-2022-LLR-0038 ML22041B5362022-02-10010 February 2022 NRR E-mail Capture - Constellation Energy Generation, LLC - Request for Additional Information Regarding Fleet License Amendment Request to Adopt TSTF-541 ML22039A2042022-02-0808 February 2022 NRR E-mail Capture - Public Meeting Dresden/Quad Cities - Proposed Alternative to Use ASME Code Case N-921 ML22027A3592022-01-26026 January 2022 U1: CY2022 Inspection Plan, Docket No. 05000010, License No. DPR-2 ML22020A0642022-01-13013 January 2022 NRR E-mail Capture - Exelon Generation Company, LLC - Request for Additional Information Regarding Proposed Fleet Alternative for Repair of Water Level Instrumentation Partial Penetration Nozzles ML21321A3802021-11-17017 November 2021 NRR E-mail Capture - NRC Acceptance Review of Dresden Nuclear Power Station, Units 2 and 3, Request for Exemption from 10 CFR 2.109(b) ML21301A0672021-10-28028 October 2021 NRR E-mail Capture - Exelon Generation Company, LLC - Acceptance of License Amendment Request to Adopt TSTF-541 ML21256A1902021-09-10010 September 2021 NRR E-mail Capture - Exelon Generation Company, LLC - Request for Additional Information Regarding License Transfer Application ML21252A0482021-09-0707 September 2021 NRR E-mail Capture - Exelon Generation Company, LLC - Fleet Alternative Request for Repair of Water Level Instrumentation Partial Penetration Nozzles ML21244A4012021-08-10010 August 2021 (Final) Request for Information (RAI) Dresden, Units 1, 2, 3, and ISFSI Request for Exemptions from Portions of 10 CFR 50.47 and 10 CFR 50 Appendix E ML21215A3502021-08-0303 August 2021 NRR E-mail Capture - Exelon Generation Company, LLC - Acceptance of License Amendment Request to Adopt TSTF-554 ML21190A0192021-07-0808 July 2021 NRR E-mail Capture - Exelon Fleet - Request for Additional Information Regarding Adoption of TSTF-582 and TSTF-583-T ML21154A0112021-05-28028 May 2021 NRR E-mail Capture - Extension of Comment Period for the Exelon Generation Company, LLC License Transfer Application ML21154A0142021-05-28028 May 2021 NRR E-mail Capture - Extension of Comment Period for the Exelon Generation Company, LLC License Transfer Application ML21154A0132021-05-28028 May 2021 NRR E-mail Capture - Extension of Comment Period for the Exelon Generation Company, LLC License Transfer Application ML21144A2132021-05-24024 May 2021 NRR E-mail Capture - Exelon Generation Company, LLC - Request for Additional Information Regarding License Transfer Application ML21139A1722021-05-19019 May 2021 Acceptance Review Memo Proposed Alternative Concerning ASME Section XI Repair/Replacement Documentation for Pressure Retaining Bolting Requirements ML21117A0442021-04-26026 April 2021 NRR E-mail Capture - Exelon Generation Company, LLC - Proposed Fleet Alternative to Documentation Requirements for Pressure Retaining Bolting ML21105A0002021-04-12012 April 2021 Acceptance Review (LAR)-Dresden Nuclear Power Station, Units 1, 2, and 3, Proposed Changes to the Dresden Nuclear Power Station Emergency Plan and Emergency Action Level Scheme for the Permanently De-fueled Condition ML21103A0082021-04-12012 April 2021 Acceptance Review (Exemption Request): Dresden Nuclear Power Station, Units 1, 2, and 3-Request for Exemption from Portions of 10 CFR 50.47 and 10 CFR 50, Appendix E ML21084A2532021-03-24024 March 2021 NRR E-mail Capture - Exelon Generation Company, LLC - Acceptance of License Transfer Application ML21081A0722021-03-19019 March 2021 Acceptance Review for Dresden Order EA-12-049, Order Modifying Licenses with Regard to Requirements for Mitigation Strategies for Beyond-Design-Basis-External Events (EPID L-2021-JLD-0000) (E-mail) ML21078A2182021-03-19019 March 2021 Acceptance Review for Dresden Order EA-13-109, Order Modifying Licenses with Regard to Reliable Hardened Containment Vents Capable of Operation Under Severe Accident Conditions ML21063A3202021-03-0202 March 2021 RAIs for Dresden, Units 2 and 3, Proposed Defueled Technical Specifications and Revised License Conditions for Permanently Defueled Condition (EPID L-2020-LLA-0239) (E-mail) ML21062A0652021-03-0101 March 2021 NRR E-mail Capture - Exelon Generation Company, LLC - Request for Additional Information Regarding Proposed Fleet Alternative to Documentation Requirements for Pressure Retaining Bolting ML21049A2572021-02-18018 February 2021 Request for Additional Information Byron/Dresden Proposed Changes to Site Emergency Plans to Support Post-Shutdown and Permanently Defueled Conditions (EPID-2020-LLA-0240 & EPID-2020-LLA-0237) ML21033A8552021-02-0202 February 2021 NRR E-mail Capture - Exelon Generation Company, LLC - Fleet Alternative Request to Expand the Use ASME Codes Cases N-878 and N-880 2023-09-22 |
Text
Ring, Mark From: Phillips Charles Xeb Sent: Monday, June 08, 2009 8:34 AM To: Ring, Mark; Slawinski, Wayne; Orth, Steven; Edmonds, Shavon; Melendez-Colon, Daneira; Benjamin, Jamie; Draper, Jason; Coffman, Ellery
Subject:
FW: DATA Attachments: Document.pdf; Dresden Site Diagram.doc Latest Licensee sample results DSP-1 32 is the storm drain nearest the U1 intake canal.
DSP-140 is the storm drain near the 2/3 CST's that the original sample was found.
MW-DN-107 S - is the shallow well near the 1A CST Thee is also a simplified diagram attached for locations - it's not to scale and the U1 intake is NOT next to the 1A CST I
Pit 213 3350-A500 E-3 Well North Tritium Detected Bladder installed ..- HPCI Suction/Return X-tie lines on downstream CST X-tie to LPCI Covered "*-...\ T Storm Drains --* Dra Tile HPCI Suction HPCI Return Unit 3 LPC I Suction N2 Storage Tanks 00 2/3 Reactor Building Cond transfer