ML101260534

From kanterella
Jump to navigation Jump to search
Technical Requirements Manual
ML101260534
Person / Time
Site: Susquehanna 
Issue date: 04/28/2010
From:
Susquehanna
To: Gerlach R
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML101260534 (28)


Text

Apr.

28, 2010 Page 1

of 2

MANUAL HARD COPY DISTRIBUTION DOCUMENT TRANSMITTAL 2010-19852 USER INFORMATION:

GERLACH*ROSE M EMPL#:028401 CA#:

0363 Address: NUCSA2 Phone#:

254-3194 TRANSMITTAL INFORMATION:

TO:

GERLACH*ROSE M 04/28/2010 LOCATION:

USNRC FROM:

NUCLEAR RECORDS DOCUMENT CONTROL CENTER (NUCSA-2)

THE FOLLOWING CHANGES HAVE OCCURRED TO THE HARDCOPY OR ELECTRONIC MANUAL ASSIGNED TO YOU.

HARDCOPY USERS MUST ENSURE THE DOCUMENTS PROVIDED MATCH THE INFORMATION ON THIS TRANSMITTAL.

WHEN REPLACING THIS MATERIAL IN YOUR HARDCOPY MANUAL, ENSURE THE UPDATE DOCUMENT ID IS THE SAME DOCUMENT ID YOU'RE REMOVING FROM YOUR MANUAL.

TOOLS FROM THE HUMAN PERFORMANCE TOOL BAG SHOULD BE UTILIZED TO ELIMINATE THE CHANCE OF ERRORS.

ATTENTION:

"REPLACE" directions do not affect the Table of Contents, Therefore no TOC will be issued with the updated material.

TRMI -

TECHNICAL REQUIREMENTS MANUAL UNIT 1 REMOVE MANUAL TABLE OF CONTENTS DATE: 04/20/2010 ADD MANUAL TABLE OF CONTENTS DATE: 04/27/2010 CATEGORY:

DOCUMENTS TYPE: TRMI

,utiC

Apr.

28, 2010 Page 2

of 2

ID:

TEXT 3.4.6 ADD:

REV:

0 CATEGORY:

DOCUMENTS ID:

TEXT B3.4.6 ADD:

REV:

0 TYPE: TRMI CATEGORY:

ID:

TEXT REMOVE:

DOCUMENTS LOES REV:58 TYPE:

TRM1 ADD:

REV:

59 CATEGORY:

DOCUMENTS ID:

TEXT TOC ADD:

REV:

18 TYPE: TRMI REMOVE:

REV:17 ANY DISCREPANCIES WITH THE MATERIAL PROVIDED, CONTACT DCS @ X3107 OR X3136 FOR ASSISTANCE.

UPDATES FOR HARDCOPY MANUALS WILL BE DISTRIBUTED WITHIN 3 DAYS IN ACCORDANCE WITH DEPARTMENT PROCEDURES.

PLEASE MAKE ALL CHANGES AND ACKNOWLEDGE COMPLETE IN YOUR NIMS INBOX UPON COMPLETION OF UPDATES.

FOR ELECTRONIC MANUAL

USERS, ELECTRONICALLY REVIEW THE APPROPRIATE DOCUMENTS AND ACKNOWLEDGE COMPLETE IN YOUR NIMS INBOX.

SSEq MANUAL Manual Name:

TRM1 Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 Table Of Contents Issue Date:

04/27/2010 Procedure Name Rev Issue Date Change ID Change Number TEXT LOES 59 04/27/2010

Title:

LIST OF EFFECTIVE SECTIONS TEXT TOC 18 04/27/2010

Title:

TABLE OF CONTENTS TEXT 1.1 0

11/18/2002

Title:

USE AND APPLICATION DEFINITIONS TEXT 2.1 1

02/0205

Title:

PLANT PROGRAMS AND SETPOINTS PLANT PROGRAMS TEXT 2.2 8

A/0i2/-2/2010

Title:

PLANT PROGRAMS AND SETPOINTS INSTRUMENT TRIP SETPOINT TABLE NV LDCN 4414 TEXT 3.0 4

05/23/2008

Title:

TECHNICAL REQUIREMENT FOR OPERATION (TRO)

APPLICABILITY & SURVEILLANCE (TRS)

APPLICABILITY TEXT 3.1.1 1

11/09/2007

Title:

REACTIVITY\\ CONTROL SYSTEMS ANTICIPATED TRANSIENT WITHOUT SCRAM ALTERNATE ROD INJECTION (ATWS

  • ARI) INSTRUMENTATION TEXT 3.1.2 K0 11/18/2002

Title:

REACTIV*I-TY\\

CONTROL SYSTEMS CONTROL ROD DRIVE (CRD)

HOUSING SUPPORT TEXT 3.1.3 5

04/16/2009

Title:

REACTIVITY CONTROL SYSTEMS CONTROL ROD BLOCK INSTRUMENTATION TEXT 3.1.4 0

11/18/2002

Title:

REACTIVITY CONTROL SYSTEMS CONTROL ROD SCRAM ACCUMULATORS INSTRUMENTATION &

CHECK VALVE TEXT 3.2.1 11 03/16/2010

Title:

CORE OPERATING LIMITS REPORT (COLR)

Pagel of

~

Report Date: 04/27/10 Page I of 16 Report Date: 04/27/10

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT 3. 4.1

Title:

REACTOR TEXT 3.4.2

Title:

REACTOR TEXT 3.4.3

Title:

REACTOR TEXT 3.4.4

Title:

REACTOR TEXT 3.4.5

Title:

REACTOR TEXT 3.5.1 1

04/26/2006 COOLANT SYSTEM REACTOR COOLANT SYSTEM CHEMISTRY-1 04/16/2009 COOLANT SYSTEM STRUCTURAL INTEGRITY 1

11/09/2007 COOLANT SYSTEM HIGH/LOW PRESSURE INTERFACE LEAKAGE MONITORS 2

04/17/2008 COOLANT SYSTEM REACTOR RECIRCULATION FLOW AND ROD LINE LIMIT 1

04/26/2006 COOLANT SYSTEM REACTOR VESSEL MATERIALS 1

02/04/2005

Title:

EMERGENCY CORE COOLING AND RCIC ADS MANUAL INHIBIT TEXT 3.5.2 1

11/09/2007

Title:

EMERGENCY CORE COOLING AND RCIC ECCS AND RCIC SYSTEM MONITORING INSTRUMENTATION TEXT 3.5.3 0

11/18/2002

Title:

EMERGENCY CORE COOLING AND RCIC LONG TERM NITROGEN SUPPLY TO ADS TEXT 3.6.1 0

11/18/2002

Title:

CONTAINMENT VENTING OR PURGING TEXT 3.6.2 0

11/18/2002

Title:

CONTAINMENT SUPPRESSION CHAMBER-TO-DRYWELL VACUUM BREAKER POSITION INDICATION TEXT 3.6.3 0

11/18/2002

Title:

CONTAINMENT SUPPRESSION POOL ALARM INSTRUMENTATION TEXT 3.6.4 0

11/18/2002

Title:

CONTAINMENT PRIMARY CONTAINMENT CLOSED SYSTEM BOUNDARIES Page 3 of 16 Report Date: 04/27/10

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT 3.7.5.2

Title:

PLANT TEXT 3.7.5.3

Title:

PLANT TEXT 3. 7.6

Title:

PLANT 0

11/18/2002 SYSTEMS MAIN CONDENSER OFFGAS EXPLOSIVE GAS MIXTURE 1

04/26/2006 SYSTEMS LIQUID HOLDUP TANKS 2

06/27/2008 SYSTEMS ESSW PUMPHOUSE VENTILATION TEXT 3. 7.7

Title:

PLANT SYSTEMS MONITORING 2

09/05/2008 MAIN CONDENSER OFFGAS PRETREATMENT LOGARITHMIC RADIATION TEXT 3.7.8 4

06/21/2007

Title:

PLANT SYSTEMS SNUBBERS TEXT 3.7.9 1

08/28/2006

Title:

PLANT SYSTEMS CONTROL STRUCTURE HVAC TEXT 3.7.10 1

12/14/2004

Title:

PLANT SYSTEMS SPENT FUEL STORAGE POOLS (SFSPS)

TEXT 3.7.11 0

04/16/2009

Title:

STRUCTURAL INTEGRITY TEXT 3.8.1 2

04/05/2010

Title:

ELECTRICAL POWER PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TEXT 3.8.2.1 2

11/09/2007

Title:

ELECTRICAL POWER MOTOR OPERATED VALVES (MOV)

THERMAL OVERLOAD PROTECTION -

CONTINUOUS TEXT 3.8.2.2 2

12/14/2004

Title:

ELECTRICAL POWER MOTOR OPERATED VALVES (MOV)

THERMAL OVERLOAD PROTECTION -

AUTOMATIC TEXT 3.8.3 1

04/05/2010

Title:

ELECTRICAL POWER DIESEL GENERATOR (DG)

MAINTENANCE ACTIVITIES Page 5

. of 16 Report Date: 04/27/10

SSES MANUA-L Manual Name:

TRM1 Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT 3.11.1.2 1

04/26/2006

Title:

RADIOACTIVE EFFLUENTS LIQUID EFFLUENTS DOSE TEXT 3.11.1.3

Title:

RADIOACTIVE TEXT 3.11.1.4

Title:

RADIOACTIVE TEXT 3.11.1.5

Title:

RADIOACTIVE TEXT 3.11.2.1

Title:

RADIOACTIVE TEXT 3.11.2.2

Title:

RADIOACTIVE TEXT 3.11.2.3

Title:

RADIOACTIVE FORM TEXT 3.11.2.4

Title:

RADIOACTIVE TEXT 3.11.2.5

Title:

RADIOACTIVE TEXT 3.11.2.6

Title:

RADIOACTIVE TEXT 3.11.3

Title:

RADIOACTIVE TEXT 3.11.4.1

Title:

RADIOACTIVE EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS 1

LIQUID 1

LIQUID 04/26/2006 WASTE TREATMENT SYSTEM 12/14/2004 RADWASTE EFFLUENT MONITORING INSTRUMENTATION 2

05/02/2007 RADIOACTIVE LIQUID PROCESS MONITORING INSTRUMENTATION 3

04/26/2006 DOSE RATE 1

04/26/2006 DOSE -

NOBLE GASES 1

04/26/2006 DOSE -

IODINE, TRITIUM, AND RADIONUCLIDES IN PARTICULATE 0

11/18/2002 GASEOUS RADWASTE TREATMENT SYSTEM 3

11/14/2006 VENTILATION EXHAUST TREATMENT SYSTEM 4

09/16/2009 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION 1

04/26/2006 TOTAL DOSE 4

08/08/2006 MONITORING PROGRAM Page 2 of 16 Report Date: 04/27/10 Page7 of 16 Report Date: 04/27/10

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT B3.0 4

05/23/2008

Title:

APPLICABILITY BASES TECHNICAL REQUIREMENT FOR OPERATION (TRO)

APPLICABILITY TEXT B3.1.1 1

11/09/2007

Title:

REACTIVITY CONTROL SYSTEMS BASES ANTICIPATED TRANSIENT WITHOUT SCRAM ALTERN.

ROD INJECTION (ATWS-ARI)

INSTRUMENTATION TEXT B3.1.2 0

11/19/2002

Title:

REACTIVITY CONTROL SYSTEMS BASES CONTROL ROD DRIVE (CRD)

HOUSING SUPPORT TEXT B3.1.3 3

03/31/2006

Title:

REACTIVITY CONTROL SYSTEMS BASES CONTROL ROD BLOCK INSTRUMENTATION TEXT B3.1.4 0

11/19/2002

Title:

REACTIVITY CONTROL SYSTEMS BASES CONTROL ROD SCRAM ACCUMULATORS INSTRUMENTA ATE TION ION AND CHECK VALVE TEXT B3.2.1 0

11/19/2002

Title:

CORE OPERATING LIMITS BASES CORE OPERATING LIMITS REPORT (COLR)

TEXT B3.3.1 0

11/19/2002

Title:

INSTRUMENTATION BASES RADIATION MONITORING INSTRUMENTATION TEXT B3.3.2 1

11/09/2007

Title:

INSTRUMENTATION BASES SEISMIC MONITORING INSTRUMENTATION TEXT B3.3.3 3

12/18/2008

Title:

INSTRUMENTATION BASES METEOROLOGICAL MONITORING INSTRUMENTATION TEXT B3.3.4 3

11/09/2007

Title:

INSTRUMENTATION BASES TRM POST ACCIDENT MONITORING (PAM)

INSTRUMENTATION TEXT B3.3.5 2

11/09/2007

Title:

INSTRUMENTATION BASES THIS PAGE INTENTIONALLY LEFT BLANK TEXT B3.3.6 3

10/19/2005

Title:

INSTRUMENTATION BASES TRM ISOLATION ACTUATION INSTRUMENTATION Page 9 of

.16 Report Date: 04/27/10

SSES MANUAL Manual Name:

TRM1 Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT B3.5.2 1

11/09/2007

Title:

ECCS AND RCIC BASES ECCS AND RCIC SYSTEM MONITORING INSTRUMENTATION TEXT B3.5.3 1

11/09/2007

Title:

ECCS AND RCIC BASES LONG TERM NITROGEN SUPPLY TO ADS TEXT B3.6.1 0

11/19/2002

Title:

CONTAINMENT BASES VENTING OR PURGING TEXT B3.6.2 0

11/19/2002

Title:

CONTAINMENT BASES SUPPRESSION CHAMBER-TO-DRYWELL VACUUM BREAKER POSITION INDICATION TEXT B3.6.3 2

04/17/2008

Title:

CONTAINMENT BASES SUPPRESSION POOL ALARM INSTRUMENTATION LDCN 3933 TEXT B3.6.4 1

12/14/2004

Title:

CONTAINMENT BASES PRIMARY CONTAINMENT CLOSED SYSTEM BOUNDARIES TEXT B3.7.1

Title:

PLANT TEXT B3.7.2

Title:

PLANT TEXT B3.7.3.1

Title:

PLANT TEXT B3.7.3.2

Title:

PLANT TEXT B3.7.3.3

Title:

PLANT TEXT B3.7.3.4

Title:

PLANT SYSTEMS BASES SYSTEMS BASES SYSTEMS BASES SYSTEMS BASES SYSTEMS BASES SYSTEMS BASES 0

11/19/2002 EMERGENCY SERVICE WATER SYSTEM (SHUTDOWN) 0 11/19/2002 ULTIMATE HEAT SINK (UHS)

GROUND WATER LEVEL 2

01/07/2008 FIRE SUPPRESSION WATER SUPPLY SYSTEM 2

04/26/2006 SPRAY AND SPRINKLER SYSTEMS 0

11/19/2002 C02 SYSTEMS 1

04/26/2006 HALON SYSTEMS Page2i of 16 Report Date: 04/27/10 Page 11

. of

.16 Report Date: 04/27/10

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT B3.7.10 1

12/14/2004

Title:

PLANT SYSTEMS BASES SPENT FUEL STORAGE POOLS TEXT B3.7.11

Title:

STRUCTURAL TEXT B3.8.1

Title:

ELECTRICAL PROTECTIVE TEXT B3.8.2.1

Title:

ELECTRICAL CONTINUOUS TEXT B3.8.2.2

Title:

ELECTRICAL AUTOMATIC TEXT B3.8.3

Title:

ELECTRICAL TEXT B3.8.4

Title:

ELECTRICAL TEXT B3.8.5

Title:

ELECTRICAL TEXT B3.8.6

Title:

ELECTRICAL TEXT B3.8.7 1

04/14/2010 INTEGRITY 2

03/10/2010 POWER BASES PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT DEVICES 0

11/19/2002 POWER BASES MOTOR OPERATED VALVES (MOV)

THERMAL OVERLOAD PROTECTION -

1 09/17/2004 POWER BASES MOTOR OPERATED VALVES (MOV)

THERMAL OVERLOAD PROTECTION -

0 11/19/2002 POWER BASES DIESEL GENERATOR (DG)

MAINTENANCE ACTIVITIES 0

11/19/2002 BASES 24 VDC ELECTRICAL POWER SUBSYSTEM POWER 0

11/19/2002 POWER BASES DEGRADED VOLTAGE PROTECTION 1

02/04/2005 POWER BASES EMERGENCY SWITCHGEAR ROOM COOLING 1

06/15/2009

Title:

BATTERY MAINTENANCE AND MONITORING PROGRAM TEXT B3.9.1 0

11/19/2002

Title:

REFUELING OPERATIONS BASES DECAY TIME TEXT B3.9.

Title:

2 0

11/19/2002 REFUELING OPERATIONS BASES COMMUNICATIONS Page i3~

of 2i Report Date:. 04/27/10 Page 13 of 16 Report Date: 04/27/10

SSES MANUJAL.

Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT B3.11.2.3

Title:

RADIOACTIVE EFFLUENTS PARTICULATES FORM TEXT B3.11.2.4

Title:

RADIOACTIVE EFFLUENTS 0

BASES 0

BASES 11/19/2002 DOSE -

IODINE, TRITIUM, AND RADIONUCLIDES IN 11/19/2002 GASEOUS RADWASTE TREATMENT SYSTEM TEXT B3.11.2.5 4

11/14/2006

Title:

RADIOACTIVE EFFLUENTS BASES VENTILATION EXHAUST TREATMENT SYSTEM TEXT B3.11.2.6

Title:

RADIOACTIVE EFFLUENTS INSTRUMENTATION 1

BASES 01/27/2004 RADIOACTIVE GASEOUS EFFLUENT MONITORING TEXT B3.11.3 0

11/19/2002

Title:

RADIOACTIVE EFFLUENTS BASES TOTAL DOSE TEXT B3.11.4.1

Title:

RADIOACTIVE EFFLUENTS TEXT B3.11.4.2

Title:

RADIOACTIVE EFFLUENTS 2

BASES 0

BASES 01/06/2006 MONITORING PROGRAM 11/19/2002 LAND USE CENSUS TEXT B3.11.4.3 0

11/19/2002

Title:

RADIOACTIVE EFFLUENTS BASES INTERLABORATORY COMPARISON PROGRAM TEXT B3.12.1 1

10/04/2007

Title:

LOADS CONTROL PROGRAM BASES CRANE TRAVEL-SPENT FUEL STORAGE POOL TEXT B3.12.2 0

11/19/2002

Title:

LOADS CONTROL PROGRAM BASES HEAVY LOADS REQUIREMENTS TEXT B3.12.3 0

11/19/2002

Title:

LOADS CONTROL PROGRAM BASES LIGHT LOADS REQUIREMENTS TEXT 3.4.6 0

04/27/2010

Title:

REACTOR RECIRCULATION SINGLE LOOP OPERATION SLO FLOW RATE RESTRICTION Page ~

of 16 Report Date: 04/27/10 Page 15 of.16 Report Date: 04/27/10

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 18 TABLE OF CONTENTS (TECHNICAL REQUIREMENTS MANUAL)

SECTION TITLE PAGE 1.0 USE AND APPLICATION TRM/1.0-1 1.1 D efinitio ns.........................................................................................

T R M /1.0-2 2.0 P LA N T P R O G RA M S.......................................................................................

2.0-1 2.1 P la nt P rogra m s..........................................................................................

2.0-1 2.2 Instrument Trip Setpoint Table..........................................................

TRM/2.0-5 3.0 A P P LIC A B ILITY......................................................................................

T R M /3.0-1 3.0 TRO) - TR for Operation (TRO) Applicability.....................................

TRM/3.0-1 3.0 (TRS) - TR Surveillance (TRS) Applicability......................................

TRM/3.0-3 3.1 REACTIVITY CONTROL SYSTEMS.......................................................

TRM/3.1-1 3.1.1 Alternate Rod Injection......................................................................

TRM/3.1-1 3.1.2 C R D H ousing S upport................................................................................

3.1-4 3.1.3 Control Rod Block Instrumentation.............................................................

3.1-5 3.1.4 Control Rod Scram Accumulators Instrumentation and C heck V alve......................................................................................

T R M /3.1-9 3.2 CORE OPERATING LIMITS REPORT...................................................

TRM/3.2-1 3.2.1 Core Operating Limits Report...........................................................

TRM/3.2-1 3.3.

INSTRUMENTATION..............................................................................

TRM/3.3-1 3.3.1 Radiation Monitoring Instrumentation................................................

TRM/3.3-1 3.3.2 Seismic Monitoring Instrumentation...................................................

TRM/3.3-4 3.3.3 Meteorological Monitoring Instrumentation........................................

TRM/3.3-7 3.3.4 TRM Post-Accident Monitoring Instrumentation.................................

TRM/3.3-9 3.3.5 S ection Not U sed..............................................................................

TR M /3.3-12 3.3.6 TRM Containment Isolation Instrumentation......................................

TRM/3.3-13 3.3.7 Turbine Overspeed Protection System..............................................

TRM/3.3-17 3.3.8 S ection Not Used..............................................................................

T R M /3.3-19 3.3.9 OPRM Instrumentation..........................................

I........................... TRM/3.3-22 3.3.10 Reactor Recirculation Pump MG Set Electrical and M echanical Stops..............................................................................

T R M /3.3-23 3.3.11 MVP Isolation Instrumentation...........................................................

TRM/3.3-25 3.3.12 Water Monitoring Instrumentation.....................................................

TRM/3.3-27 3.4 REACTOR COOLANT SYSTEM.............................................................

TRM/3.4-1 3.4.1 Reactor Coolant System Chemistry...................................................

TRM/3.4-1 3.4.2 N ot U sed...........................................................................................

T R M /3.4-6 3.4.3 High/Low Pressure Interface Leakage Monitors..................

3.4-9 3.4.4 Reactor Recirculation Flow and Rod Line Limit.................................

TRM/3.4-12 3.4.5 Reactor Vessel Material Surveillances Program................................ TRM/3.4-13 3.4.6 Reactor Recirculation Single Loop Operation (SLO)

Flow Rate Restriction.......................................................................

TRM/3.4-14 SUSQUEHANNA - UNIT 1 TRM /TOC-1 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 18 TABLE OF CONTENTS (TECHNICAL REQUIREMENTS MANUAL)

SECTION TITLE PAGE 3.5 EMERGENCY CORE COOLING AND RCIC...........................................

TRM/3.5-1 3.5.1 ADS Manual Inhibit.................................

TRM/3.5-1 3.5.2 ECCS and RCIC System Monitoring Instrumentation.................................

3.5-3 3.5.3 Long Term Nitrogen Supply to ADS...........................................................

3.5-6 3.6 C O N TA IN M E N T...............................................................................................

3.6-1 3.6.1 VENTING or PURGING.............................................................................

3.6-1 3.6.2 Suppression Chamber-to-Drywell Vacuum Breaker Position In d ica tio n....................................................................................................

3.6 -2 3.6.3 Suppression Pool Alarm Instrumentation....................................................

3.6-3 3.6.4 Primary Containment Closed System Boundaries.............................

TRM/3.6-6 3.7 P LA N T S Y S T E M S...........................................................................................

3.7-1 3.7.1 Emergency Service Water System (Shutdown)..........................................

3.7-1 3.7.2 Ultimate Heat Sink and Ground Water Level..............................................

3.7-3 3.7.3.1 Fire Suppression Water Supply System............................................

TRM/3.7-4 3.7.3.2 Spray and Sprinkler Systems............................................................

TRM/3.7-8 3.7.3.3 C 0 2 System s....................................................................................

T R M /3.7-12 3.7.3.4 Halon Systems..................................................................................

TRM/3.7-16 3.7.3.5 Fire Hose Stations.............................................................................

TRM/3.7-18 3.7.3.6 Yard Fire Hydrants and Hydrant Hose Houses.................................

TRM/3.7-22 3.7.3.7 Fire Rated Assemblies.....................................................................

TRM/3.7-24 3.7.3.8 Fire Detection Instrumentation.........................................................

TRM/3.7-26 3.7.4 Solid Radwaste System....................................................................

TRM/3.7-35 3.7.5.1 Main Condenser Offgas Hydrogen Monitor................................................

3.7-38 3.7.5.2 Main Condenser Explosive Gas Mixture....................................................

3.7-39 3.7.5.3 Liquid Holdup Tanks.........................................................................

TRM/3.7-40 3.7.6 ESSW Pumphouse Ventilation..........................................................

TRM/3.7-41 3.7.7 Main Condenser Offgas Pretreatment Logarithmic Radiation Monitoring Instrumentation................................................................

TRM/3.7-42 3.7.8 S nubbers...........................................................................................

T R M /3.7-44 3.7.9 Control Structure HVAC....................................................................

TRM/3.7-50 3.7.10 Spent Fuel Storage Pools.................................................................

TRM/3.7-52 3.7.11 Structural Integrity.............................................................................

TRM/3.7-55 SUSQUEHANNA - UNIT 1 TRM / TOC-2 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION TABLE OF CONTENTS (TECHNICAL REQUIREMENTS MANUAL)

PPL Rev. 18 SECTION TITLE PAGE 3.8 3.8.1 3.8.2.1 3.8.2.2 3.8.3 3.8.4 3.8.5 3.8.6 3.8.7 3.9 3.9.1 3.9.2 3.9.3 3.10 3.10.1 3.10.2 3.10.3 3.11 3.11.1.2 3.11.1.2 3.11.1.3 3.11.1.4, 3.11.1.5 3.11.2.1 3.11.2.2 3.11.2.3 3.11.2.4 3.11.2.5 3.11.2.6 3.11.3 3.11.4.1 3.11.4.2 3.11.4.3 ELECTRICAL POW ER...........................................................................

TRM/3.8-1 Primary Containment Penetration Conductor Overcurrent Protective Devices............................................................................

TRM/3.8-1 Motor Operated Valves Thermal Overload Protection -

Continuous.........................................................................................

TRM/3.8-5 Motor Operated Valves Thermal Overload Protection -

Automatic..........................................................................................

TRM/3.8-1 1 Diesel Generator (DG) Maintenance Activities..................................

TRM/3.8-13 24VDC Electrical Power Subsystem..................................................

TRM/3.8-15 Degraded Voltage Protection............................................................

TRM/3.8-21 Emergency Switchgear Room Cooling.......................................................

3.8-24 Battery Monitoring and Maintenance Program..................................

TRM/3.8-26 REFUELING OPERATIONS............................................................................

3.9-1 D e cay T im e................................................................................................

3.9-1 Communications........................................................................................

3.9-2 Refueling Platform......................................................................................

3.9-3 MISCELLANEOUS...............................

.................................... TRM/3.10-1 Sealed Source Contamination.............................................................

TRM/3.10-1 MODE 5 Shutdown Margin Test RPS Instrumentation...............................

3.10-4 Independent Spent Fuel Storage Installation (ISFSI).........................

TRM/3.10-7 RADIOACTIVE EFFLUENTS.............................

TRM/3.11-1 Liquid Effluents Concentration...........................................................

TRM/3.11-1 Liquid Effluents Dose........................................................................

TRM/3.11-4 Liquid W aste Treatment System.......................................................

TRM/3.11-6 Liquid Radwaste Effluent Monitoring Instrumentation..............

3.11-8 Radioactive Liquid Process Monitoring Instrumentation................... TRM/3.11-13 Dose Rate........................................................................................

TRM/3.11-17 Dose - Noble Gases.........................................................................

TRM/3.11-20 Dose - Iodine, Tritium, and Radionuclides in Particulate Form................................................................................

TRM/3.11-21 Gaseous Radwaste Treatment System.............................................

TRM/3.11-22 Ventilation Exhaust Treatment System..............................................

TRM/3.11-23 Radioactive Gaseous Effluent Monitoring Instrumentation...................................................................................

TRM/3.11-25 Total Dose...........................................................................................

TRM/3.11-33 Monitoring Program.............................................................................

TRM/3.11-35 Land Use Census................................................................................

TRM/3.11-45 Interlaboratory Comparison Program..................................................

TRM/3.11-47 SUSQUEHANNA - UNIT 1 TRM /TOC-3 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 18 TABLE OF CONTENTS (TECHNICAL REQUIREMENTS MANUAL)

SECTION TITLE PAGE 3.12 LOADS CO NTROL PROGRAM..............................................................

TRM/3.12-1 3.12.1 Crane Travel - Spent Fuel Storage Pool.................................................

TRM/3.12-1 3.12.2 Heavy Loads Requirements....................................................................

TRM/3.12-3 3.12.3 Light Loads Requirements......................................................................

TRM/3.12-5 4.0 ADMINISTRATIVE CONTROLS......................................................................

4.0-1 4.1 Organization....................................................................................................

4.0-1 4.2 Reportable Event Action..................................................................................

4.0-2 4.3 Safety Limit Violation.......................................................................................

4.0-3 4.4 Procedures and Programs...............................................................................

4.0-4 4.5 Reporting Requirements..................................................................................

4.0-5 4.6 Radiation Protection Program.........................................................................

4.0-7 4.7 Training............................................................................................................

4.0-8 SUSQUEHANNA - UNIT 1 TRM / TOC-4 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 18 TABLE OF CONTENTS (TECHNICAL REQUIREMENTS MANUAL)

SECTION TITLE PAGE B 3.0 A pplicability................................................................................................

B 3.0-1 B 3.0 (TRO) - TR for Operation (TRO) Applicability.............................................

B 3.0-1 B 3.0 (TRS) - TR Surveillance (TRS) Applicability...............................................

B 3.0-9 B 3.1.1 Alternate Rod Injection......................................................................

TRM/B 3.1-1 B 3.1.2 CRD Housing Support.......................................................................

TRM/B 3.1-4 B 3.1.3 Control Rod Block Instrumentation....................................................

TRM/B 3.1-5 B 3.1.4 Control Rod Scram Accumulators Instrumentation and C heck V alve......................................................................................

T R M /B 3.1-8 B 3.2.1 Core Operating Limits Report (COLR).......................................................

B 3.2-1 B 3.3.1 Radiation Monitoring Instrumentation................................................

TRM/B 3.3-1 B 3.3.2 Seismic Monitoring Instrumentation...................................................

TRM/B 3.3-2 B 3.3.3 Meteorological Monitoring Instrumentation........................................

TRM/B 3.3-3 B 3.3.4 TRM Post-Accident Monitoring Instrumentation.................................

TRM/B 3.3-4 B 3.3.5 Section Not Used..............................................................................

TRM/B 3.3-9, B 3.3.6 TRM Containment Isolation Instrumentation...............................................

B 3.3-10 B 3.3.7 Turbine Overspeed Protection System..............................................

TRM/B 3.3-14 B 3.3.8 Section Not Used..............................................................................

TRM/B 3.3-15 B 3.3.9 OPRM Instrumentation......................................................................

TRM/B 3.3-17 B 3.3.10 Reactor Recirculation Pump MG Set Electrical and Mechanical Stops..............................................................................

TRM/B 3.3-18 B 3.3.11 MVP Isolation Instrumentation...........................................................

TRM/B 3.3-20 B 3.3.12 Water Monitoring Instrumentation.....................................................

TRM/B 3.3-22 B 3.4.1 Reactor Coolant System Chemistry............................................................

B 3.4-1 B 3.4.2 N ot U sed...........................................................................................

T R M /B 3.4-2 B 3.4.3 High/Low Pressure Interface Leakage Monitors................................

TRM/B 3.4-4 B 3.4.4 Reactor Recirculation Flow and Rod Line Limit.................................

TRM/B 3.4-5 B 3.4.5 Reactor Vessel Material Surveillances Program..................

B 3.4-6 B 3.4.6 Reactor Recirculation Single Loop Operation (SLO)

Flow Rate Restriction.......................................................................

TRM/B 3.4-7 B 3.5.1 A D S M anual Inhibit....................................................................................

B 3.5-1 B 3.5.2 ECCS and RCIC System Monitoring Instrumentation........................ TRM/B 3.5-3 B 3.5.3 Long Term Nitrogen Supply to ADS..................................................

TRM/B 3.5-4 SUSQUEHANNA-UNIT I TRM I TOC-5 EFFECTIVE DATE 04/14/2010 SUSQUEHANNA - UNIT 1 TRM / TOC-5 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 18 TABLE OF CONTENTS (TECHNICAL REQUIREMENTS MANUAL)

SECTION TITLE PAGE B 3.6.1 VENTING or PURGING....................................................................

TRM/B 3.6-1 B 3.6.2 Suppression Chamber-to-Drywell Vacuum Breaker Position In d ica tio n....................................................................................................

B 3.6 -3 B 3.6.3 Suppression Pool Alarm Instrumentation...........................................

TRM/B 3.6-4 B 3.6.4 Primary Containment Closed System Boundaries.............................

TRM/B 3.6-6 B 3.7.1 Emergency Service Water System (Shutdown)..........................................

B 3.7-1 B 3.7.2 Ultimate Heat Sink and Ground Water Level..............................................

B 3.7-2 B 3.7.3.1 Fire Suppression Water Supply System...........................................

TRM/B 3.7-3 B 3.7.3.2 Spray and Sprinkler Systems............................................................

TRM/B 3.7-5 B 3.7.3.3 C02 systems....................................................................................

TRM/B 3.7-7 B 3.7.3.4 Halon Systems..................................................................................

TRM/B 3.7-8 B 3.7.3.5 Fire Hose Stations............................................................................

TRM/B 3.7-10 B 3.7.3.6 Yard Fire Hydrants and Hydrant Hose Houses..................................

TRM/B 3.7-11 B 3.7.3.7 Fire Rated Assemblies......................................................................

TRM/B 3.7-12 B 3.7.3.8 Fire Detection Instrumentation..........................................................

TRM/B 3.7-14 B 3.7.4 Solid Radwaste System....................................................................

TRM/B 3.7-15 B 3.7.5.1 Main Condenser Offgas Hydrogen Monitor................................................

B 3.7-17 B 3.7.5.2 Main Condenser Explosive Gas Mixture.....................................................

B 3.7-19 B 3.7.5.3 Liquid H oldup Tanks..................................................................................

B 3.7-20 B 3.7.6 ESSW Pumphouse Ventilation..........................................................

TRM/B 3.7-21 B 3.7.7 Main Condenser Offgas Pretreatment Logarithmic Radiation Monitoring Instrumentation................................................................

TRM/B 3.7-22 B 3.7.8 S nubbers..........................................................................................

T R M /B 3.7-24 B'3.7.9 Control Structure HVAC....................................................................

TRM/B 3.7-31 B 3.7.10 Spent Fuel Storage Pools.................................................................

TRM/B 3.7-33 B 3.7.11 Structural Integrity.............................................................................

TRM/B 3.7-36 B 3.8.1 Primary Containment Penetration Conductor Overcurrent Protective D evices............................................................................

T R M /B 3.8-1 B 3.8.2.1 Motor Operated Valves Thermal Overload Protection -

C ontinuous........................................................................................

T R M /B 3.8-3 B 3.8.2.2 Motor Operated Valves Thermal Overload Protection -

A utom atic..........................................................................................

T R M /B 3.8-4 B 3.8.3 Diesel Generator (DG) Maintenance Activities...........................................

B 3.8-5 B 3.8.4 24VDC Electrical Power Subsystem...........................................................

B 3.8-6 B 3.8.5 Degraded Voltage Protection............................................................

TRM/B 3.8-16 B 3.8.6 Emergency Switchgear Room Cooling..............................................

TRM/B 3.8-17 B 3.8.7 Battery Monitoring and Maintenance Program..................................

TRM/B 3.8-18 B.3.9.1 D e cay T im e................................................................................................

B 3.9-1 B 3.9.2 C om m unications........................................................................................

B 3.9-2 SUSQUEHANNA UNIT I TRM / TOC-6 EFFECTIVE DATE 04/14/2010 SUSQUEHANNA - UNIT 1 TRM / TOC-6 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION TABLE OF CONTENTS (TECHNICAL REQUIREMENTS MANUAL)

PPL Rev. 18 SECTION B 3.9.3 B 3.10.1 B 3.10.2 B 3.10.3 B 3.11.1.1 B 3.11.1.2 B 3.11.1.3 B 3.11.1.4 B 3.11.1.5 B 3.11.2.1 B 3.11.2.2 B 3.11.2.3 B 3.11.2.4 B 3.11.2.5 B 3.11.2.6 B 3.11.3 B 3.11.4.1 B 3.11.4.2 B 3.11.4.3 B.3.12.1 B.3.12.2 B.3.12.3 TITLE PAGE Refueling Platform......................................................................................

B 3.9-3 Sealed Source Contamination....................................................................

B 3.10-1 MODE 5 Shutdown Margin Test RPS Instrumentation...................... TRM/B 3.10-2 Independent Spent Fuel Storage Installation (ISFSI).........................

TRM/B 3.10-4 Liquid Effluents Concentration....................................................................

B 3.11-1 Liquid Effluents Dose.................................................................................

B 3.11-4 Liquid W aste Treatment System................................................................

B 3.11-6 Liquid Radwaste Effluent Monitoring Instrumentation.................................

B 3.11-7 Radioactive Liquid Process Monitoring Instrumentation.................... TRM/B 3.11-10 Dose Rate.........................................................................................

TRM/B 3.11-12 Dose - Noble Gases...................................................................................

B 3.11-16 Dose - Iodine, Tritium, and Radionuclides in Particulate Form.........................................................................................

B 3.11-18 Gaseous Radwaste Treatment System.............................................

TRM/B 3.11-20 Ventilation Exhaust Treatment System..............................................

TRM/B 3.11-21 Radioactive Gaseous Effluent Monitoring Instrumentation.................................................................................

TRM/B 3.11-24 T o ta l D o se..................................................................................................

B 3.1 1-2 6 Monitoring Program...........................................................................

TRM/B 3.11-28 Land Use Census.......................................................................................

B 3.11-34 Interlaboratory Comparison Program................................................

TRM/B 3.11-36 Crane Travel - Spent Fuel Storage Pool...........................................

TRM/B 3.12-1 Heavy Loads Requirements..............................................................

TRM/B 3.12-2 Light Loads Requirements................................................................

TRM/B 3.12-3 TRM1 text TOC 04/14/2010 SUSQUEHANNA - UNIT 1 TRM /TOC-7 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 59 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date TOC 1.0 2.0 TABLE OF CONTENTS USE AND APPLICATION Pages TRM / 1.0-1 through TRM / 1.0-3 PLANT PROGRAMS Page 2.0-1 Pages TRM / 2.0-2 and TRM / 2.0-3 Page TRM / 2.0-4 Page TRM / 2.0-5 Page TRM / 2.0-6 Page TRM / 2.0-7 Page TRM / 2.0-8 Page TRM / 2.0-9 Page TRM / 2.0-10 Page TRM / 2.0-11 Page TRM / 2.0-12 Pages TRM / 2.0-13 and TRM / 2.0-14 Page TRM /2.0-15 3.0 APPLICABILITY Page TRM / 3.0-1 Page TRM / 3.0-2 Page TRM / 3.0-3 Page TRM / 3.0-4 04/14/2010 10/04/2002 08/31/1998 01/28/2005 06/25/2002 04/02/1999 03/27/2008 05/15/2008 03/27/2008 11/15/2004 02/02/2010 11/15/2004 03/27/2008 11/15/2004 11/15/2005 04/14/2008 04/12/2007 03/15/2002 11/30/2005 10/31/2007 08/31/1998 03/22/2006 04/07/2009 03/27/2008 02/18/1999 02/18/1999 07/07/1999 03/11/2010 07/16/1999 10/31/2007 08/31/1998 10/31/2007 08/31/1998 04/12/2007 3.1 3.2 REACTIVITY CONTROL SYSTEMS Page TRM / 3.1-1 Pages TRM / 3.1-2 through TRM / 3.1-5 Page TRM / 3.1-6 Page TRM / 3.1-7 Page TRM / 3.1-8 Pages TRM / 3.1-9 and TRM / 3.1-9a Page TRM / 3.1-10 CORE OPERATING LIMITS REPORT Page TRM / 3.2-1 Pages TRM / 3.2-2 through TRM / 3.2-54 INSTRUMENTATION Pages TRM / 3.3-1 through TRM / 3.3-3 Page TRM / 3.3-4 and TRM / 3.3-5 Page TRM / 3.3-6 Page TRM / 3.3-7 Page 3.3-8 Page TRM / 3.3-9 3.3 SUSQUEHANNA

- UNIT I TRM / LOES-1 EFFECTIVE DATE 04/14/2010 SUSQUEHANNA - UNIT 1 TRM / LOES-1 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 59 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date 3.4 Page TRM / 3.3-9a Page TRM / 3.3-10 Page TRM / 3.3-11 Page TRM / 3.3-11 a Page TRM / 3.3-12 Page TRM / 3.3-13 Page TRM / 3.3-14 Page TRM / 3.3-15 Page TRM / 3.3-16 Page TRM / 3.3-17 Page TRM / 3.3-18 Pages TRM / 3.3-19 through TRM / 3.3-21 Page TRM / 3.3-22 Page TRM / 3.3-22a Pages TRM / 3.3-22b through TRM / 3.3-22d Page TRM / 3.3-23 Pages TRM / 3.3-24 and TRM / 3.3-25 Page TRM / 3.3-26 Pages TRM / 3.3-27 and TRM / 3.3-28 REACTOR COOLANT SYSTEM Page TRM / 3.4-1 Pages 3.4-2 through 3.4-5 Pages TRM / 3.4-6 through TRM / 3.4-8 Page TRM / 3.4-9 Page TRM / 3.4-10 Page TRM / 3.4-11 Page TRM / 3.4-12 Page TRM / 3.4-13 Page TRM / 3.4-14 EMERGENCY CORE COOLING AND RCIC EPage TRM / 3.5-1 Pages 3.5-2 and 3.5-3 Pages TRM / 3.5-4 and TRM / 3.5-5 Pages 3.5-6 and 3.5-7 CONTAINMENT Pages 3.6-1 through 3.6-3 Page TRM / 3.6-4 Page 3.6-5 Pages TRM / 3.6-6 through TRM / 3.6-8 12/17/1998 10/31/2007 06/02/2005 04/14/2008 03/30/2001 09/13/2005 12/14/1998 10/22/2003 06/27/2001 06/14/2002 10/31/2007 10/22/2003 03/27/2008 11/15/2004 03/22/2006 12/03/2004 05/16/2003 10/22/2003 04/07/2009 03/31/2006 10/23/1998 04/01/2009 08/31/1998 10/31/2007 08/31/1998 03/27/2008 03/31/2006 04/14/2010 01/28/2005 08/31/1998 10/31/2007 08/31/1998 08/31/1998 01/07/2002 08/31/1998 12/31/2002 3.5 3.6 SUSQUEHANNA - UNIT 1 TRM / LOES-2 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 59 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date 3.7 PLANT SYSTEMS Pages 3.7-1 through 3.7-3 Page TRM / 3.7-4 Pages TRM / 3.7-5 Pages TRM / 3.7-6 through TRM / 3.7-8 Pages TRM / 3.7-9 and TRM / 3.7-10 Page TRM / 3.7-11 Page TRM / 3.7-12 Page TRM / 3.7.13 Page TRM / 3.7-14 Pages TRM / 3.7-15 and TRM / 3.7-16 Page TRM / 3.7-17 Page TRM / 3.7-18 Page TRM / 3.7-19 Pages TRM / 3.7-20 through TRM / 3.7-22 Page TRM / 3.7-23 Page TRM / 3.7-24 Pages TRM / 3.7-25 and TRM 3.7-26 Page TRM 3.7-27 Page TRM / 3.7-28 Page TRM / 3.7-29 Page TRM / 3.7-30 Pages TRM / 3.7-31 and TRM / 3.7-32 Page TRM / 3.7-33 Page TRM / 3.7-34 Page TRM / 3.7-34a Page TRM / 3.7-35 Pages TRM / 3.7-36 and TRM / 3.7-37 Pages 3.7-38 and 3.7-39 Page TRM / 3.7-40 Page TRM / 3.7-41 Page TRM / 3.7-41a Page TRM / 3.7-42 Page TRM / 3.7-43 Pages TRM / 3.7-44 through TRM / 3.7-46 Page TRM / 3.7-47 Page TRM / 3.7-48 Page TRM / 3.7-49 Page TRM / 3.7-50 Page TRM / 3.7-51 Page TRM / 3.7-52 Page TRM / 3.7-53 Page TRM / 3.7-54 Pages TRM / 3.7-55 through TRM / 3.7-57 08/31/1998 03/31/2006 04/07/2009 08/02/1999 04/07/2009 12/29/1999 08/02/1999 04/07/2009 08/09/2005 08/02/1999 04/07/2009 08/02/1999 04/07/2009 08/02/1999 04/07/2009 03/31/2006 08/02/1999 10/31/2007 11/29/2006 08/09/2005 01/13/2010 11/16/2001 01/09/2004 11/16/2001 10/05/2002 03/31/2006 02/01/1999 08/31/1998 03/31/2006 02/14/2005 06/20/2008 09/04/2008 08/31/1998 10/05/2006 06/07/2007 10/05/2006 06/07/2007 03/09/2001 08/16/2006 12/03/2004 04/15/2003 07/29/1999 04/01/2009 SUSQUEHANNA - UNIT I TRM/LOES-3 EFFECTIVE DATE 04/14/2010 SUSQUEHANNA - UNIT 1 TRM / LOES-3 EFFECTIVE DATE 04114/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 59 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date 3.8 3.9 ELECTRICAL POWER Page TRM / 3.8-1 Page TRM / 3.8-2 Pages TRM / 3.8-3 and TRM /3.8-4 Pages TRM / 3.8-5 and TRM / 3.8-6 Page TRM / 3.8-7 Pages TRM / 3.8-8 through TRM / 3.8-10 Page TRM / 3.8-11 Page TRM / 3.8-12 Page TRM / 3.8-13 Page TRM / 3.8-14 Pages TRM / 3.8-15 through TRM / 3.8-17 Page 3.8-18 Page TRM / 3.8-19 Page 3.8-20 Pages TRM / 3.8-21 through TRM / 3.8-23 Pages 3.8-24 and 3.8-25 Page TRM / 3.8-26 Page TRM / 3.8-27 Pages TRM / 3.8-28 and TRM / 3.8-29 REFUELING OPERATIONS Pages 3.9-1 through 3.9-3 MISCELLANEOUS Page TRM / 3.10-1 Pages 3.10-2 and 3.10-3 Pages 3.10-2 and 3.10-3 Page TRM / 3.10-4 Pages TRM / 3.10-5 and TRM / 3.10-6 Page TRM / 3.10-7 RADIOACTIVE EFFLUENTS Page TRM /3.11-1 Pages 3.11-2 and 3.11-3 Page TRM / 3.11-4 Page 3.11-5 Page TRM /3.11-6 Pages TRM / 3.11-7 through TRM / 3.11-9 Page TRM / 3.11-10 Pages 3.11-11 and 3.11-12 Page TRM / 3.11-13 04/02/2002 01/28/2005 03/25/2010 04/02/2002 10/31/2007 12/03/2004 09/03/2004 12/03/2004 03/25/2010 08/31/1998 04/02/2002 08/31/1998 04/02/2002 08/31/1998 06/06/1999 08/31/1998 05/28/2009 11/29/2006 05/28/2009 08/31/1998 03/31/2006 08/31/1998 08/31/1998 08/01/2006 03/22/2006 03/31/2006 03/31/2006 08/31/1998 03/31/2006 08/31/1998 03/31/2006 08/31/1998 12/03/2004 08/31/1998 04/12/2007 3.10 3.11 SUSQUEHANNA - UNIT 1 TRM / LOES-4 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 59 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date Page TRM / 3.11-14 Pages 3.11-15 and 3.11-16 Page TRM /3.11-17 Page 3.11-18 Page TRM / 3.11-19 Pages TRM / 3.11-20 and TRM / 3.11-21 Page TRM / 3.11-22 Page TRM / 3.11-23 Page TRM / 3.11-24 Page TRM / 3.11-25 Pages TRM / 3.11-26 and TRM / 3.11-27 Page TRM / 3.11-28 Page TRM / 3.11-29 Pages TRM / 3.11.30 through TRM / 3.11.32 Page TRM / 3.11-33 Page 3.11-34 Page TRM / 3.11-35 Pages TRM / 3.11-36 through TRM / 3.11-39 Pages 3.11-40 through 3.11-43 Page TRM / 3.11-44 Page TRM / 3.11-45 Page 3.11-46 Page TRM / 3.11-47 LOADS CONTROL PROGRAM Pages TRM / 3.12-1 through TRM / 3.12-3 Page TRM / 3.12-4 Page TRM / 3.12-5 ADMINISTRATIVE CONTROLS Pages TRM / 4.0-1 through TRM / 4.0-3 Page TRM / 4.0-4 Pages TRM / 4.0-5 through TRM / 4.0-8 12/03/2004 09/01/1998 03/31/2006 08/31/1998 08/15/2005 03/31/2006 04/02/2002 11/14/2006 05/13/2005 04/12/2007 01/21/2004 09/08/2009 12/03/2004 01/21/2004 03/31/2006 08/31/1998 03/31/2006 11/30/2005 08/31/1998 08/01/2006 03/31/2006 08/31/1998 03/31/2006 02/05/1999 03/14/2008 02/05/1999 08/31/1998 12/11/2008 08/31/1998 3.12 4.0 SUSQUEHANNA - UNIT 1 TRM / LOES-5 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 59 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date B 3.0 B 3.1 B 3.2 B 3.3 APPLICABILITY BASES Pages TRM / B 3.0-1 through TRM / B 3.0-3 Page TRM / B 3.0-4 Page TRM / B 3.0-5 Page TRM / B 3.0-6 Page TRM / B 3.0-7 Pages TRM / B 3.0-8 through TRM / B 3.0-10 Pages TRM / B 3.0-11 and TRM / B 3.0-12 Pages TRM / B 3.0-13 and TRM / B 3.0-14 Page TRM / B 3.0-15 REACTIVITY CONTROL SYSTEMS BASES Page TRM / B 3.1-1 Pages TRM / B 3.1-2 and TRM / B 3.1-3 Page B 3.1-4 Page TRM / B 3.1-5 Pages TRM / B 3.1-6 and TRM / B 3.1-7 Page TRM / B 3.1-8 CORE OPERATING LIMITS BASES Page B 3.2-1 INSTRUMENTATION BASES Page TRM / B 3.3-1 Pages TRM / B 3.3-2 and TRM / B 3.3-2a Page TRM / B 3.3-3 Page TRM / B 3.3-3a Pages TRM / B 3.3-4 and TRM / B 3.3-5 Pages TRM / B 3.3-6 through TRM / B 3.3-9 Page B 3.3-10 Pages TRM / B 3.3-11 and TRM / B 3.3-12 Page TRM / B 3.3-13 Page TRM / B 3.3-14 Page TRM / B 3.3-14a Page TRM / B 3.3-14b Pages TRM / B 3.3-15 and TRM / B 3.3-16 Page TRM / B 3.3-17 Pages TRM / B 3.3-17a through TRM / B 3.3-17c Page TRM / B 3.3-17d Pages TRM / B 3.3-17e and TRM / B 3.3-17f Page TRM /B 3.3-18 Page TRM / B 3.3-19 Page TRM / B 3.3-20 Page TRM / B 3.3-21 Pages TRM / B 3.3-22 and TRM / B 3.3-23 08/31/1998 01/10/2007 04/14/2008 08/31/1998 04/12/2007 08/31/1998 03/15/2002 11/30/2005 03/15/2002 07/13/1999 10/31/2007 08/31/1998 11/15/2005 03/22/2006 02/18/1999 08/31/1998 04/07/2000 10/31/2007 12/11/2008 10/31/2007 05/30/2006 10/31/2007 08/31/1998 09/13/2005 12/03/2004 06/25/2002 10/31/2007 10/31/2007 10/22/2003 03/22/2006 03/22/2006 03/27/2008 03/22/2006 03/25/2010 05/16/2008 10/22/2003 05/16/2003 04/07/2009 SUSQUEHANNA - UNIT 1 TRM / LOES-6 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 59 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date B 3.4 B 3.5 B 3.6 B 3.7 REACTOR COOLANT SYSTEM BASES Page B 3.4-1 Pages TRM / B 3.4-2 and TRM / B 3.4-3 Pages TRM / B 3.4-4 and TRM / B 3.4-4a Page TRM / B 3.4-5 Page B 3.4-6 Page TRM / B 3.4-7 ECCS AND RCIC BASES Pages B 3.5-1 and B 3.5-2 Pages TRM / B 3.5-3 through TRM / B 3.5-5 CONTAINMENT BASES Page TRM / B 3.6-1 Page TRM / B 3.6-2 Page B 3.6-3 Page TRM / B 3.6-4 Page TRM / B 3.6-5 Page TRM / B 3.6-6 Pages B.3.6-7 through TRM / B 3.6-11 PLANT SYSTEMS BASES Pages B 3.7-1 and B 3.7-2 Pages TRM / B 3.7-3 and TRM / B 3.7-3a Page TRM / B 3.7-4 Page TRM / B 3.7-5 Page TRM / B 3.7-6 Pages TRM / B 3.7-7 and TRM / B 3.7-7a Page TRM / B 3.7-8 Page TRM / B 3.7-9 Page TRM / B 3.7-10 Page TRM / B 3.7-10a Page TRM / B 3.7-11 Page TRM / B 3.7-11a Pages TRM / B 3.7-12 through TRM / B 3.7-14 Page TRM / B 3.7-14a Page TRM / B 3.7-14b Pages TRM / B 3.7-15 and TRM / B 3.7-16 Pages B 3.7-17 through B 3.7-20 Page TRM / B 3.7-21 Page TRM / B 3.7-21a Page TRM / B 3.7-22 and TRM / B 3.7-23 Pages TRM / B 3.7-24 through TRM / B 3.7-28 Pages TRM / B 3.7-29 and TRM / B 3.7-30 08/31/1998 04/01/2009 10/31/2007 10/15/1999 08/31/1998 04/14/2010 08/31/1998 10/31/2007 07/26/2001 02/01/1999 08/31/1998 03/27/2008 04/04/2007 12/03/2004 12/31/2002 08/31/1998 12/27/2007 03/31/2006 08/02/1999 03/31/2006 08/02/1999 08/02/1999 03/31/2006 08/02/1999 03/31/2006 08/02/1999 03/31/2006 08/02/1999 08/02/1999 01/09/2004 02/01/1999 08/31/1998 02/14/2005 06/20/2008 01/30/2008 10/05/2006 06/07/2007 SUSQUEHANNA

- UNIT 1 TRM I LOES-7 EFFECTIVE DATE 04/14/2010 SUSQUEHANNA - UNIT 1 TRM / LOES-7 EFFECTIVE DATE 04/1412010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 59 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date B 3.8 B.3.9 Pages TRM / B 3.7-30a and TRM / B 3.7-30b Page TRM / B 3.7-31 Page TRM / B 3.7-32 Page TRM / B 3.7-33 Page TRM / B 3.7-34 Page TRM / B 3.7-35 Pages TRM / B 3.7-36 through TRM / B 3.7-39 Page TRM / B 3.7-40 ELECTRICAL POWER BASES Page TRM / B 3.8-1 Pages TRM / B 3.8-2 and TRM / B 3.8-2 Page TRM / B 3.8-2a Page TRM / B 3.8-3 Page TRM / B 3.8-3a Page TRM / B 3.8-4 Page TRM / B 3.8-4a Page TRM / B 3.8-5 Pages TRM / B 3.8-6 through TRM / B 3.8-16 Page TRM / B 3.8-17 Pages TRM / B 3.8-18 through TRM / B 3.8-20 Pages TRM / B 3.8-21 through TRM / B 3.8-24 REFUELING OPERATIONS BASES Pages B 3.9-1 through B 3.9-7 10/05/2006 12/03/2004 03/09/2001 04/15/2003 12/03/2004 07/05/2000 04/01/2009 04/08/2010 04/02/2002 01/28/2005 03/01/2010 04/02/2002 04/02/2002 08/10/2004 04/02/2002 08/31/1998 04/02/2002 01/28/2005 11/29/2006 05/28/2009 08/31/1998 08/31/1998 03/22/2006 08/23/1999 08/30/1998 02/01/1999 04/07/2000 02/01/1999 12/03/2004 02/01/1999 08/30/1998 04/02/2002 04/02/2002 05/13/2005 11114/2006 05/13/2005 B 3.10 MISCELLANEOUS BASES Page B 3.10-1 Pages TRM / B 3.10-2 and TRM / B 3.10-3 Pages TRM / B 3.10-4 and TRM / B 3.10-5 B 3.11 RADIOACTIVE EFFLUENTS BASES Pages B 3.11-1 through B 3.11-9 Page TRM / B 3.11-10 Pages TRM/B 3.11-11 and TRM/B 3.11-1l a Pages TRM/B 3.11-12 and TRM/B 3.11-13 Page TRM / B 3.11-14 Page TRM / B 3.11-15 Pages B 3.11-16 through B 3.11-19 Page TRM / B 3.11-20 Page TRM / B 3.11-20a Page TRM / B 3.11-21 Pages TRM / B 3.11-22 and TRM / B 3.11.23 Page TRM / B 3.11.23a SUSQUEHANNA

- UNIT I TRM / LOES-8 EFFECTIVE DATE 04/14/2010 SUSQUEHANNA - UNIT 1 TRM / LOES-8 EFFECTIVE DATE 04/14/2010

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 59 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date Pages TRM / B 3.11-24 and TRM / B 3.11-25 Pages B 3.11-26 and B 3.11-27 Pages TRM / B 3.11-28 and TRM / B 3A11-29 Page TRM / B 3.11-30 Pages B 3.7-31 through B 3.7-35 Page TRM / B 3.11-36 01/21/2004 08/30/1998 11/30/2005 12/03/2004 08/30/1998 02/12/1999 09/19/2007 02/05/1999 B.3.12 LOADS CONTROL PROGRAM BASES Page TRM / B 3.12-1 Pages TRM / B 3.12-2 and TRM / B 3.12-3 TRM1 text LOES 4/14/2010 SUSQUEHANNA - UNIT 1 TRM / LOES-9 EFFECTIVE DATE 04/14/2010

PPL Rev. 0 Reactor Recirculation Single Loop Operation (SLO) Flow Rate Restriction 3.4.6 3.4 3.4.6 TRO Reactor Coolant System (RCS)

Reactor Recirculation Single Loop Operation (SLO) Flow Rate Restriction 3.4.6 In single loop operation, establish operating Reactor Recirculation Loop Flow Rate to less than or equal to 53.0 MIbm/hr ICABILITY:

MODES 1 and 2 APPL ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

Requirements of the TRO A.1 Restore reactor recirculation 30 minutes not met loop flow rate to within limits B.

Requirements of B.1 Place Reactor Mode Switch in Immediately Condition A not met Shutdown AND B.2 Restore reactor recirculation Immediately loop flow rate to within limits TECHNICAL REQUIREMENT SURVEILLANCE SURVEILLANCE FREQUENCY TRS 3.4.6.1 Verify the operating loop flow rate is less than or Once every four hours equal to 53.0 Mlbm/hr.

SUSQUEHANNA UNIT 1 TRM / 3.4-14 EFFECTIVE DATE 04/14/2010

PPL Rev. 0 Reactor Recirculation Single Loop Operation (SLO) Flow Rate Restriction B 3.4.6 B 3.4.6 Reactor Recirculation Single Loop Operation (SLO) Flow Rate Restriction BASES TRO TRO 3.4.6 requires that the operating loop flow rate be maintained less than or equal to 53.0 Mlbm/hr during single loop operation. Note that the parameter of concern is the 3 minute average recirculation system loop flow (e.g., PICSY point NJF02B and NJF03B) not core flow. This restriction avoids excessive vibration of jet pump components. Fatigue usage can be accumulated when loop flow rates are above 54 Mlbm/hr if large gaps are present. In reference 2 the analysis determined that during Unit 1 17th cycle operation, the normal dual loop operation flow rates are limited to 53 Mlbm/hr on the "A" loop and 54 Mlbm/hr on the "B" loop. The single loop operation limits in either loop are set at 53 Mlbm/hr to provide margin to the limit of 54 Mlbm/hr. Excessive vibration can lead to cracking of the jet pump riser brace welds. The limitation contained in this TRO will assure jet pump integrity will be maintained and thus the FSAR Chapter 15 analysis assumption of maintaining 2/3 core height will be met. Additionally, these measures will assure asset preservation and avoid lengthy repairs due to potential riser brace cracking. The required action to place the reactor mode switch in shutdown in 30 minutes assures the flow rate is established within limits. The time frames are required to avoid excessive vibrations that occur at higher loop flow rates and the subsequent impact on jet pump riser brace.

APPLICABILITY This Requirement is applicable whenever in reactor recirculation single loop operation in Modes 1 and 2.

ACTIONS The Actions assure that excessive jet pump vibration can not occur when in single loop operation.

TRS The required surveillance assures that the maximum loop flow rate is not exceeded.

REFERENCES

1.

FSAR Section 15.6

2.

GE Report "Fatigue Usage Evaluation for Jet Pump Assembly with Set Screw Gap Condition and Justification for Continued Operation,"

April 2010 SUSQUEHANNA - UNIT 1 TRM / B 3.4-7 EFFECTIVE DATE 04/14/2010