Request for Additional Information Related to Generic Letter 2008-01, Managing Gas Accumulation in Emergency Core Cooling, Decay Heat Removal, and Containment Spray Systems
ML093340389
Person / Time
Site: Perry FirstEnergy icon.png
Issue date: 12/04/2009
From: Sands S
Plant Licensing Branch III
To: Bezilla M
FirstEnergy Nuclear Operating Co
Mahoney, M NRR/DORL/LPLIII- 2 415-3867
References
GL-08-001, TAC MD7862
Download: ML093340389 (4)


Text

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555*0001 December 4, 2009 Mr. Mark B. Bezilla Site Vice President FirstEnergy Nuclear Operating Company Perry Nuclear Power Plant Mail Stop A-PY-A290 P.O. Box 97,10 Center Road Perry,OH 44081-0097 SUB~IECT:

PERRY NUCLEAR POWER PLANT, UNIT NO.1 - REQUEST FOR ADDITIONAL INFORMATION RELATED TO GENERIC LETTER 2008-01, "MANAGING GAS ACCUMULATION IN EMERGENCY CORE COOLING, DECAY HEAT REI\\IIOVAL, AND CONTAINMENT SPRAY SYSTEMS" (TAC NO. MD7862)

Dear Mr. Bezilla:

By letters to the Nuclear Regulatory Commission (NRC) dated October 14, 2008 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML082980365),

December 19, 2008 (ADAMS Accession No. ML090430426) and August 10, 2009 (ADAMS Accession No. IVIL092320128), FirstEnergy Nuclear Operating Company (FENOC or the licensee) provided responses to Generic Letter 2008-01, for the Perry Nuclear Power Plant, Unit NO.1.

The NRC staff is reviewing your submittal and has determined that additional information is required to complete the review. The specific information requested is addressed in the enclosure to this letter. During a discussion with your staff on November 18, 2009, it was agreed that you would provide a response within 60 days from the date of this letter.

M. Bezilla

- 2 The NRC staff considers that timely responses to requests for additional information help ensure sufficient time is available for staff review and contribute toward the NRC's goal of efficient and effective use of staff resources. If circumstances result in the need to revise the requested response date, please contact me at (301) 415-3154.

Stephen P. Sands, Project Manager Plant Licensing Branch 111-2 Division of Operating Reactor Licensing Office of Nuclear !Reactor Regulation Docket No. 50-440

Enclosure:

Request for Additional Information cc w/encl: Distribution via Listserv

REQUEST FOR ADDITIONAL INFORMATION PERRY NUCLEAR POWER PLANT, UNIT NO.1 DOCKET NO. 50-440 In reviewing the FirstEnergy Nuclear Operating Company's submittals dated October 14, 2008, December 19, 2008, and August 10, 2009 (Agencywide Documents Access and Management System Accession Nos. ML082980365, ML090430426 and ML092320128 respectively), related to the 9-month response to Generic Letter (GL) 2008-01, "Managing Gas Accumulation in Emergency Core Cooling, Decay Heat Removal, and Contain Spray Systems' Evaluation and 3 Month Response Template," for the Perry Nuclear Power Plant, Unit No.1, the Nuclear Regulatory Commission (NRC) staff has determined that the following information is needed in order to complete its review:

1.

In page 26 of Attachment 1 of Reference 3, it was stated, "

a RHR pump is not manually re-started if the pump stops while in the Suppression Pool cooling mode, prior to performing a high point fill and vent through 1 E1 2F0400NB. This precaution would minimize the potential for the above conditions to result in a RHR water hammer during a LOOP scenario or pump failure."

The staff requests the licensee to clarify whether the operators will have sufficient time to complete a high point fill and vent procedure if a LOOP concurrent with a LOCA is postulated, while in the Suppression Pool cooling mode. If not, then please explain.

2.

Consistent with Section 3.7 of Ref. 1, briefly discuss the training that is considered to be a necessary part of applying procedures and other activities when addressing the issues identified in the GL.

REFERENCES

1.

Ruland, William H., "Preliminary Assessment of Responses to Generic Letter 2008-01,

'Managing Gas Accumulation in Emergency Core Cooling, Decay Heat Removal, and Containment Spray Systems,' and Future NRC Staff Review Plans," NRC letter to James H. Riley, Nuclear Energy Institute, ML091390637, May 28,2009.

2.

Riley, James H., "Generic Letter (GL) 2008-01, 'Managing Gas Accumulation in Emergency Core Cooling, Decay Heat Removal, and Contain Spray Systems' Evaluation and 3 Month Response Template," Letter to Administrative Points of Contact from Director, Engineering, Nuclear Generation Division, Nuclear Energy Institute,, "Generic Letter 2008-01 Response Guidance," March 20, 2008.

3.

Bezilla, Mark B., "Nine Month Response to NRC Generic Letter 2008-01, "Managing Gas Accumulation in Emergency Core Cooling, Decay Heat Removal, and Containment Spray Systems," Vice President, Perry Nuclear Power Plant, FirstEnergy Nuclear Operating Company, October 14, 2008.

ML093340389 NRR-088 OFFICE LPL3-2/PM LPL3-2/PM LPL3-2/LA LPL3-2/BC NAME MMahoney SSands SPS bye-mail THarris CGoodwin for SCampbell DATE 12/03/09 11/30/09 12/03/09 12/04/09