ML093280425

From kanterella
Jump to navigation Jump to search
Initial Exam 2009-301 Final Sim/In-Plant JPMs
ML093280425
Person / Time
Site: Vogtle  
Issue date: 11/18/2009
From:
NRC/RGN-II
To:
Southern Nuclear Operating Co
References
50-424/09-301, 50-425/09-301, ES-301-2 50-424/09-301, 50-425/09-301
Download: ML093280425 (123)


Text

ES-301 Control Room/In-Plant Systems Outline PINAL.

Form ES-301-2 Facility:

Vogtle Nuclear Plant Exam Level (circle one): RO / SRO-I / SRO-U (see each JPM)

Date of Examination: June 1-5, 2009 Operating Test No.: 2009-301 Control Room Systems@ (8 for RO; 7 for SRO-I; 2 or 3 for SRO-U, including 1 ESF)

System / JPM Title Type Code*

Safety Function

a. Emergency Borate due to Rods below insertion limits (RIL)

M,A,S 1

==

Description:==

RWST flow path required due to equipment failures. This JPM has been modified to require the student to determine if rods are below RIL by responding to a rod bank 10-10 limit alarm using the Core Operating Limits Report prior starting the emergency boration.

(RO/ SRO-I)

KIA: 004A2.14 (3.8/3.9)

b. Transfer ECCS to Cold Leg Recirculation M,E,A,S,L 2

==

Description:==

Equipment failures will prevent cold leg recirculation. Required to EN identify a loss of emergency coolant recirculation. This JPM has been modified by adding a failure of an RWST suction valve to close.

(RO / SRO-I / SRO-U)

KIA: 006A4.05 (3.9/3.8)

c. Fill SI Accumulator at low RCS pressure M,L,S 3

==

Description:==

Required to use SI pump B. This requires a different alignment to prevent injecting into the RCS while at low RCS pressure. The SI pump common suction valve will be shut. The student will have to open this valve prior to starting the SI pump to prevent pump damage. This is based on recent plant operating experience.

(RO / SRO-I)

KIA: 006A1.13 (3.5 / 3.7)

d. Identify and Isolate Ruptured SG with Failures D,P,E,L,A,S 4P

==

Description:==

MSIVs for ruptured SG fail to close requiring isolation of main steam loads from the ruptured SG. These include TDAFW steam supplies, condenser spargers, SJAE's, and steam dumps.

(RO / SRO-I)

KIA: 035A4.06 (4.5 / 4.6)

e. Transfer CNMT Spray to Recirculation D,A,S 5

==

Description:==

Train A IRC suction valve fails to open requiring student to secure EN one train of CNMT spray to prevent damage to the ESF pump.

(RO / SRO-I / SRO-U)

KIA: 026A2.07 (3.6/3.9)

ES-301 Control Room/In-Plant Systems Outline PINAL..

Form ES-301-2 Facility:

Vogtle Nuclear Plant Exam Level (circle one): RO / SRO-I / SRO-U (see each JPM)

Date of Examination: June 1-5, 2009 Operating Test No.: 2009-301 Control Room Systems@ (8 for RO; 7 for SRO-I; 2 or 3 for SRO-U, including 1 ESF)

System / JPM Title Type Code*

Safety Function

a. Emergency Borate due to Rods below insertion limits (RIL)

M,A,S 1

==

Description:==

RWST flow path required due to equipment failures. This JPM has been modified to require the student to determine if rods are below RIL by responding to a rod bank 10-10 limit alarm using the Core Operating Limits Report prior starting the emergency boration.

(RO/ SRO-I)

KIA: 004A2.14 (3.8/3.9)

b. Transfer ECCS to Cold Leg Recirculation M,E,A,S,L 2

==

Description:==

Equipment failures will prevent cold leg recirculation. Required to EN identify a loss of emergency coolant recirculation. This JPM has been modified by adding a failure of an RWST suction valve to close.

(RO / SRO-I / SRO-U)

KIA: 006A4.05 (3.9/3.8)

c. Fill SI Accumulator at low RCS pressure M,L,S 3

==

Description:==

Required to use SI pump B. This requires a different alignment to prevent injecting into the RCS while at low RCS pressure. The SI pump common suction valve will be shut. The student will have to open this valve prior to starting the SI pump to prevent pump damage. This is based on recent plant operating experience.

(RO / SRO-I)

KIA: 006A1.13 (3.5 / 3.7)

d. Identify and Isolate Ruptured SG with Failures D,P,E,L,A,S 4P

==

Description:==

MSIVs for ruptured SG fail to close requiring isolation of main steam loads from the ruptured SG. These include TDAFW steam supplies, condenser spargers, SJAE's, and steam dumps.

(RO / SRO-I)

KIA: 035A4.06 (4.5 / 4.6)

e. Transfer CNMT Spray to Recirculation D,A,S 5

==

Description:==

Train A IRC suction valve fails to open requiring student to secure EN one train of CNMT spray to prevent damage to the ESF pump.

(RO / SRO-I / SRO-U)

KIA: 026A2.07 (3.6/3.9)

ES-301 Control Room/In-Plant Systems Outline Form ES-301-2

f. DG Parallel Operation with voltage regulator failure M,A,S 6

==

Description:==

DG KVAR lowers uncontrollably after paralleling with bus. This EN requires tripping the DG output breaker. These actions are to protect the diesel generator from damage.

(RO / SRO-I / SRO-U)

KIA: 062A 1.01 (3.4 / 3.8)

g. Place CR HVAC on Recirculation with High Radiation N,A,S 7

==

Description:==

CRI will fail to automatically or manually actuate. Students required to manually align dampers to isolate control room from high radiation.

(RO / SRO-I)

KIA: 072A3.01 (2.9/3.1)

h. Place CNMT Main Purge In-Service N,S,L 8

==

Description:==

Unit in mode 5. Student required to shutdown mini-purge system and then place main purge system in service with equipment hatch open. Main purge supply fan should not be placed in service.

(RO)

KIA: 029A2.03 (2.7/3.1)

ES-301 Control Room/In-Plant Systems Outline Form ES-301-2

f. DG Parallel Operation with voltage regulator failure M,A,S 6

==

Description:==

DG KVAR lowers uncontrollably after paralleling with bus. This EN requires tripping the DG output breaker. These actions are to protect the diesel generator from damage.

(RO / SRO-I / SRO-U)

KIA: 062A 1.01 (3.4 / 3.8)

g. Place CR HVAC on Recirculation with High Radiation N,A,S 7

==

Description:==

CRI will fail to automatically or manually actuate. Students required to manually align dampers to isolate control room from high radiation.

(RO / SRO-I)

KIA: 072A3.01 (2.9/3.1)

h. Place CNMT Main Purge In-Service N,S,L 8

==

Description:==

Unit in mode 5. Student required to shutdown mini-purge system and then place main purge system in service with equipment hatch open. Main purge supply fan should not be placed in service.

(RO)

KIA: 029A2.03 (2.7/3.1)

Job Performance Measure "A" Facility: VogUe Task No: V-LO-TA-09029 Task

Title:

Emergency Borate from the RWST JPM No: V-RQ-JP-13009-005 KIA

Reference:

004A2.14 Examinee: __________ _

NRC Examiner: ________ _

Facility Evaluator: ________ _

Date: ____________ _

Method of testing:

Simulated Performance ______ _

Actual Performance _______ _

Classroom _____ _

Simulator _____ _

Plant _____ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

A rapid down power per AOP-18013-C, "Rapid Power Reduction" has just been performed by the operating crew.

Task Standard:

Student initiates emergency boration from the RWST using SOP 13009-1.

Required Materials:

1.
2.

General

References:

None SOP 13009-1 Control Room Simulator Initiating Cue:

The SS has directed you to emergency borate the RCS using SOP 13009-1 to clear the rod bank Lo-Lo Limit alarm.

Time Critical Task:

No Validation Time:

6 minutes 1

Job Performance Measure "A" Facility: VogUe Task No: V-LO-TA-09029 Task

Title:

Emergency Borate from the RWST JPM No: V-RQ-JP-13009-005 KIA

Reference:

004A2.14 Examinee: __________ _

NRC Examiner:

Facility Evaluator:

Date: ____________ _

Method of testing:

Simulated Performance ______ _

Actual Performance _______ _

Classroom _____ _

Simulator _____ _

Plant _____ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

A rapid down power per AOP-18013-C, "Rapid Power Reduction" has just been performed by the operating crew.

Task Standard:

Student initiates emergency boration from the RWST using SOP 13009-1.

Required Materials:

1.
2.

General

References:

None SOP 13009-1 Control Room Simulator Initiating Cue:

The SS has directed you to emergency borate the RCS using SOP 13009-1 to clear the rod bank Lo-Lo Limit alarm.

Time Critical Task:

No Validation Time:

6 minutes 1

SIMULATOR SETUP:

Simulator Setup:

1.

Reset to IC # 95 for HL-15 NRC Exam

2.

Place a Red Danger Tag on HS-0276A (Boric Acid Transfer # 1)

Simulator Setup from Scratch:

1.

Reset to IC # 14 (100% MOL)

2.

Insert the following overrides:

LV-112D closed HS-276A stop HS-276A green light - off HS-276A Red Danger Tag on hand switch HS-277 A stop - on Trigger 1 (T1)

HS-277 A amber light on - on Trigger 1 (T1)

ALB37 window 001 (BBD Trouble) on - on Trigger 1 (T1)

3.

Select the following hand switch positions:

HS-277 A auto

4.

Place 75 gpm letdown in service and adjust charging flow as appropriate to maintain PRZR level stable.

5.

Reduce reactor power to - 70% power and stabilize the plant, ensure that CBD rods are below the RIL to ensure ALB-10, 004 for ROD BANK LO-LO LIMIT is iJIuminated.

(Recommend 5 to 10 steps below the RIL to ensure the alarm does not inadvertently clear, some patience is required to accomplish this (- 106 steps on CBD should be pretty close).

6.

Acknowledge I Reset alarms

7.

Freeze Setup time: 10 minutes 2

SIMULATOR SETUP:

Simulator Setup:

1.

Reset to IC # 95 for HL-15 NRC Exam

2.

Place a Red Danger Tag on HS-0276A (Boric Acid Transfer # 1)

Simulator Setup from Scratch:

1.

Reset to IC # 14 (100% MOL)

2.

Insert the following overrides:

LV-112D closed HS-276A stop HS-276A green light - off HS-276A Red Danger Tag on hand switch HS-277 A stop - on Trigger 1 (T1)

HS-277 A amber light on - on Trigger 1 (T1)

ALB37 window 001 (BBD Trouble) on - on Trigger 1 (T1)

3.

Select the following hand switch positions:

HS-277 A auto

4.

Place 75 gpm letdown in service and adjust charging flow as appropriate to maintain PRZR level stable.

5.

Reduce reactor power to - 70% power and stabilize the plant, ensure that CBD rods are below the RIL to ensure ALB-10, 004 for ROD BANK LO-LO LIMIT is iJIuminated.

(Recommend 5 to 10 steps below the RIL to ensure the alarm does not inadvertently clear, some patience is required to accomplish this (- 106 steps on CBD should be pretty close).

6.

Acknowledge I Reset alarms

7.

Freeze Setup time: 10 minutes 2

Performance Information Critical steps denoted with an asterisk

Section 4.9 referenced Comment:

Reviews note at beginning of section 4.9 and may refer to table 1 for available flow paths TABLE 1 EMERGENCY BORATION FLOW PATH ALTERNATIVES Flow path BATP Valve Other Pump Flows Flow Alignments Required HV81 04 At least OPEN Any charging pump

>42GPM

>30GPM one 1HV-8104 1 FI-0121 C 1FI-0183A Charging Flow At least OPEN Any charging pump

>42GPM

>30GPM path one 1FV-0110A 1 FI-0121C 1 FI-0110A 1FV-0110B OPEN 1LV-0112D RWSTto 1LV-0112E

>100 GPM 8 to 13 GPM Regen Hx NA CLOSE Any charging pump 1FI-0121C seal injection 1LV-0112B flow 1HV-0182 1LV-0112C 1LV-0112A OPEN BIT flow Adjust 1 HV-8801A (1 FI-0917 A) + total 1FIC-0121C to RWSTto BIT NA 1HV-8801B Any charging pump seal flow

<13 GPM per

- seal retum flow

>87.5 GPM ACP OPEN AHA other than SID RHR NA HV-8812A1B Cooling

>100 gpm See Proc.

(Mode 6)

HV-8809A1B OPEN SI NA HV-8923A1B SI

>100 gpm See Proc.

(Mode 6)

HV-8821 AlB HV-8835 Student may use any method. Most likely method will be using HV-8104 or the charging flow path Standard:

N/A Comment:

3 Note Operate heaters Operate heaters Operate heaters Operate heaters Establish water removal path to prevent vessel overflow Establish water removal path to prevent vessel or cavity overflow Performance Information Critical steps denoted with an asterisk

Section 4.9 referenced Comment:

Reviews note at beginning of section 4.9 and may refer to table 1 for available flow paths TABLE 1 EMERGENCY BORATION FLOW PATH ALTERNATIVES Flow path BATP Valve Other Pump Flows Flow Alignments Required HV81 04 At least OPEN Any charging pump

>42GPM

>30GPM one 1HV-8104 1 FI-0121 C 1FI-0183A Charging Flow At least OPEN Any charging pump

>42GPM

>30GPM path one 1FV-0110A 1 FI-0121C 1 FI-0110A 1FV-0110B OPEN 1LV-0112D RWSTto 1LV-0112E

>100 GPM 8 to 13 GPM Regen Hx NA CLOSE Any charging pump 1FI-0121C seal injection 1LV-0112B flow 1HV-0182 1LV-0112C 1LV-0112A OPEN BIT flow Adjust 1 HV-8801A (1 FI-0917 A) + total 1FIC-0121C to RWSTto BIT NA 1HV-8801B Any charging pump seal flow

<13 GPM per

- seal retum flow

>87.5 GPM ACP OPEN AHA other than SID RHR NA HV-8812A1B Cooling

>100 gpm See Proc.

(Mode 6)

HV-8809A1B OPEN SI NA HV-8923A1B SI

>100 gpm See Proc.

(Mode 6)

HV-8821 AlB HV-8835 Student may use any method. Most likely method will be using HV-8104 or the charging flow path Standard:

N/A Comment:

3 Note Operate heaters Operate heaters Operate heaters Operate heaters Establish water removal path to prevent vessel overflow Establish water removal path to prevent vessel or cavity overflow

4.9.1 Emergency Boration Through 1-HV-8104 OR 4.9.2 Emergency Boration Through The Normal Charging Flow Path Standard:

Comment:

Start one (1) Boric Acid Transfer Pump.

Boric acid transfer pump hand switch placed in START Red light - ON Green light - OFF CUE:

Simulator operator actuates trigger 1 Determines that boric acid transfer pump has tripped Standard:

Comment:

Standard:

Comment:

Boric acid transfer pump:

Red light - OFF Green light - ON Amber light - ON 1 BBD Trouble Alarm Determines that sections 4.9.1 and 4.9.2 are N1A due to both boric acid transfer pumps being unavailable.

Refers to section 4.9.3 4

4.9.1 Emergency Boration Through 1-HV-8104 OR 4.9.2 Emergency Boration Through The Normal Charging Flow Path Standard:

Comment:

Start one (1) Boric Acid Transfer Pump.

Boric acid transfer pump hand switch placed in START Red light - ON Green light - OFF CUE:

Simulator operator actuates trigger 1 Determines that boric acid transfer pump has tripped Standard:

Comment:

Standard:

Comment:

Boric acid transfer pump:

Red light - OFF Green light - ON Amber light - ON 1 BBD Trouble Alarm Determines that sections 4.9.1 and 4.9.2 are N1A due to both boric acid transfer pumps being unavailable.

Refers to section 4.9.3 4

4.9.3 4.9.3.1 CUE:

Standard:

Comment:

  • 4.9.3.2 Standard:

Comment:

Emergency Boration From The RWST Through The Normal Charging Flow Path Verify one (1) Charging Pump is running and supplied with cooling water.

IF asked, Auxiliary Building Operator reports NCP is supplied with cooling water.

NCP: Red light - ON Green light - OFF Amber light - OFF Open the following Charging Pump Suctions from the RWST:

1-LV-01120 1-LV-0112E Places 1-L V -1120 in open position: Green light -

stays ON Red light -

stays OFF Places 1-LV-112E in open position: Green light-OFF Red light -

ON 5

4.9.3 4.9.3.1 CUE:

Standard:

Comment:

  • 4.9.3.2 Standard:

Comment:

Emergency Boration From The RWST Through The Normal Charging Flow Path Verify one (1) Charging Pump is running and supplied with cooling water.

IF asked, Auxiliary Building Operator reports NCP is supplied with cooling water.

NCP: Red light - ON Green light - OFF Amber light - OFF Open the following Charging Pump Suctions from the RWST:

1-LV-01120 1-LV-0112E Places 1-L V -1120 in open position: Green light -

stays ON Red light -

stays OFF Places 1-LV-112E in open position: Green light-OFF Red light -

ON 5

  • 4.9.3.3 Standard:

Comment:

  • 4.9.3.4 Standard:

Comment:

4.9.3.5 Standard:

Comment:

  • 4.9.3.6 Standard:

Comment:

Close the following VCT Outlet Isolations:

1-LV-0112B 1-LV-0112C Places 1-LV-112B to close position: Green light -

ON Red light -

OFF Places 1-LV-112C to close position: Green light -

ON Red light -

OFF Place 1-LV-0112A to the HUT position.

Places 1-LV-0112A to the HUT position:

Red light -

OFF Amber light -

ON Place 1-FIC-0121 in MANUAL, Checks 1-FIC-0121 in MANUAL Auto light - OFF Manual light - ON Adjust Charging Line Flow Controller 1-FIC-0121 to obtain Charging Flow 1-FI-0121 C greater than 100 gpm, Charging Flow 1-FI-0121 C greater than 100 gpm 6

  • 4.9.3.3 Standard:

Comment:

  • 4.9.3.4 Standard:

Comment:

4.9.3.5 Standard:

Comment:

  • 4.9.3.6 Standard:

Comment:

Close the following VCT Outlet Isolations:

1-LV-0112B 1-LV-0112C Places 1-LV-112B to close position: Green light -

ON Red light -

OFF Places 1-LV-112C to close position: Green light -

ON Red light -

OFF Place 1-LV-0112A to the HUT position.

Places 1-LV-0112A to the HUT position:

Red light -

OFF Amber light -

ON Place 1-FIC-0121 in MANUAL, Checks 1-FIC-0121 in MANUAL Auto light - OFF Manual light - ON Adjust Charging Line Flow Controller 1-FIC-0121 to obtain Charging Flow 1-FI-0121 C greater than 100 gpm, Charging Flow 1-FI-0121 C greater than 100 gpm 6

4.9.3.7 Standard:

Comment:

4.9.3.8 CUE:

Standard:

Comment:

4.9.3.9 Standard:

Comment:

Adjust Charging Seal Flow Control 1-HV -0182 as necessary to maintain RCP seal injection flow at approximately 40 gpm (between 8 and 13 gpm per pump).

RCP seal injection flows between 8 and 13 G PM per pump IF required for RCS inventory control, place an additional letdown orifice in service per 13006-1.

The extra operator will place an additional letdown orifice in service.

N/A Operate the Pressurizer Backup Heaters as necessary to equalize boron concentrations between the RCS and the Pressurizer.

Turns on Pressure back up heaters as needed:

1 HS-10469A 1 HS-10470A 1 HS-10472 7

4.9.3.7 Standard:

Comment:

4.9.3.8 CUE:

Standard:

Comment:

4.9.3.9 Standard:

Comment:

Adjust Charging Seal Flow Control 1-HV -0182 as necessary to maintain RCP seal injection flow at approximately 40 gpm (between 8 and 13 gpm per pump).

RCP seal injection flows between 8 and 13 G PM per pump IF required for RCS inventory control, place an additional letdown orifice in service per 13006-1.

The extra operator will place an additional letdown orifice in service.

N/A Operate the Pressurizer Backup Heaters as necessary to equalize boron concentrations between the RCS and the Pressurizer.

Turns on Pressure back up heaters as needed:

1 HS-10469A 1 HS-10470A 1 HS-10472 7

4.9.3.10 CUE:

Standard:

Comment:

Check for indications consistent with RCS boration:

RCS Tavg may be dropping.

NIS may be dropping.

The extra operator will monitor boron concentration and terminate emergency boration flow when the rod bank Lo-Lo Limit Alarm is clear.

N/A Reports to the SS that emergency boration from the RWST has been initiated per 13009-1.

Standard:

N/A Comment:

Terminating cue:

Student returns initiating cue sheet 8

4.9.3.10 CUE:

Standard:

Comment:

Check for indications consistent with RCS boration:

RCS Tavg may be dropping.

NIS may be dropping.

The extra operator will monitor boron concentration and terminate emergency boration flow when the rod bank Lo-Lo Limit Alarm is clear.

N/A Reports to the SS that emergency boration from the RWST has been initiated per 13009-1.

Standard:

N/A Comment:

Terminating cue:

Student returns initiating cue sheet 8

Verification of Completion Job Performance Measure No. V-RQ-JP-13009-005 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: _____________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date:

9 Verification of Completion Job Performance Measure No. V-RQ-JP-13009-005 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: _____________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date:

9

Initial Conditions:

A rapid down power per AOP-18013-C, "Rapid Power Reduction" has just been performed by the operating crew.

Initiating Cue:

The SS has directed you to emergency borate the RCS using SOP 13009-1 to clear the rod bank Lo-Lo Limit alarm.

10 Initial Conditions:

A rapid down power per AOP-18013-C, "Rapid Power Reduction" has just been performed by the operating crew.

Initiating Cue:

The SS has directed you to emergency borate the RCS using SOP 13009-1 to clear the rod bank Lo-Lo Limit alarm.

10

Job Performance Measure "8" Facility: Vogtle Task No: V-LO-TA-37009 Task

Title:

Transfer ECCS Pumps To Cold Leg Recirculation JPM No: V-LO-JP-19013-003 KIA

Reference:

006A4.05 Examinee: __________ _

NRC Examiner: ________ _

Facility Evaluator: ________ _

Date: ____________ _

Method of testing:

Simulated Performance ______ _

Actual Performance _______ _

Classroom _____ _

Simulator _____ _

Plant _____ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

THIS IS A TIME CRITICAL JPM A large break LOCA has occurred. While performing 19013, RWST level decreased below 29%. Transition to 19013 is required based on foldout page guidance.

Task Standard:

Determines Cold Leg recirculation flow path NOT available per 19013, Attachment A and a transition is required to 19111-C, Loss of Emergency Coolant Recirculation.

Required Materials:

19013-C, Transfer to Cold Leg Recirculation.

General

References:

None Initiating Cue:

The SS has directed you to "Transfer the ECCS pumps to cold leg recirculation using 19013".

Time Critical Task:

Yes Validation Time:

6 minutes Job Performance Measure "8" Facility: Vogtle Task No: V-LO-TA-37009 Task

Title:

Transfer ECCS Pumps To Cold Leg Recirculation JPM No: V-LO-JP-19013-003 KIA

Reference:

006A4.05 Examinee: __________ _

NRC Examiner: ________ _

Facility Evaluator: ________ _

Date: ____________ _

Method of testing:

Simulated Performance ______ _

Actual Performance _______ _

Classroom _____ _

Simulator _____ _

Plant _____ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

THIS IS A TIME CRITICAL JPM A large break LOCA has occurred. While performing 19013, RWST level decreased below 29%. Transition to 19013 is required based on foldout page guidance.

Task Standard:

Determines Cold Leg recirculation flow path NOT available per 19013, Attachment A and a transition is required to 19111-C, Loss of Emergency Coolant Recirculation.

Required Materials:

19013-C, Transfer to Cold Leg Recirculation.

General

References:

None Initiating Cue:

The SS has directed you to "Transfer the ECCS pumps to cold leg recirculation using 19013".

Time Critical Task:

Yes Validation Time:

6 minutes

SIMULATOR SETUP:

Snapped to IC # 97 for HL-15 NRC Exam.

If new setup is required, then perform the following:

1.

Reset to IC 14 (MOL 100%).

2.

Override HV-8812A to the OPEN position.

3.

Override HV-8811 B to the SHUT position.

4.

Insert malfunction RC03C at 100% (DBA LOCA)

5.

Trip all RCPs

6.

Reset SI

7.

After CNMT Emergency Sump levels are ~ 14 inches, set RF: TK02 = 28% (RWST)

8.

Ensure HV-8811A is FULL OPEN

9.

Acknowledge/Reset alarms

10.

Freeze Simulator Setup time: 18 minutes 2

SIMULATOR SETUP:

Snapped to IC # 97 for HL-15 NRC Exam.

If new setup is required, then perform the following:

1.

Reset to IC 14 (MOL 100%).

2.

Override HV-8812A to the OPEN position.

3.

Override HV-8811 B to the SHUT position.

4.

Insert malfunction RC03C at 100% (DBA LOCA)

5.

Trip all RCPs

6.

Reset SI

7.

After CNMT Emergency Sump levels are ~ 14 inches, set RF: TK02 = 28% (RWST)

8.

Ensure HV-8811A is FULL OPEN

9.

Acknowledge/Reset alarms

10.

Freeze Simulator Setup time: 18 minutes 2

Performance Information Critical steps denoted with an asterisk START TIME FOR TIME CRITICAL ___ _

Reviews NOTES prior to step 1 regarding FRP implementation, steps 1 - 12 performance without delay, and RWST inventory time limits.

Standard:

N/A Comment:

Reviews CAUTION prior to step 1 regarding offsite power loss after SI reset.

Standard:

N/A Comment:

Step 1 Standard:

Comment:

Step 2 Standard:

Comment:

Verifies SI reset BPLP window 1.5 (white Auto SI blocked light) - ON BPLP window 1.4 (red SI Actuated light) - OFF Checks CNMT Emergency Sump levels.::: 13.5 inches.

Both L/-764 and L/-765.::: 13.5 inches (should be - 60+ inches) 3 Performance Information Critical steps denoted with an asterisk START TIME FOR TIME CRITICAL ___

Reviews NOTES prior to step 1 regarding FRP implementation, steps 1 - 12 performance without delay, and RWST inventory time limits.

Standard:

N/A Comment:

Reviews CAUTION prior to step 1 regarding offsite power loss after SI reset.

Standard:

N/A Comment:

Step 1 Standard:

Comment:

Step 2 Standard:

Comment:

Verifies SI reset BPLP window 1.5 (white Auto SI blocked light) - ON BPLP window 1.4 (red SI Actuated light) - OFF Checks CNMT Emergency Sump levels.::: 13.5 inches.

Both L/-764 and L/-765.::: 13.5 inches (should be - 60+ inches) 3

Step # 3 CUE:

Standard:

Comment:

Step 1 Standard:

Comment:

Initiate ATTACHMENT A to align ECCS Pumps to the Cold Leg Recirculation flow path and continue with Step 4.

The SS will continue with step 4 while you perform Attachment A.

Initiates ATTACHMENT A ATTACHMENT A COLD LEG RECIRCULATION VALVE ALIGNMENT Check CCW cooling for RHR heat exchangers.

a.

CCW pumps - 2 running in each train.

b.

CCW pumps discharge pressures and flows - NORMAL

c.

NSCW cooling for CCW heat exchangers NCSW Pumps - TWO RUNNING EACH TRAIN.

NSCW CLG TOWER Fans - FOUR IN AUTO EACH TRAIN.

Determines the following:

2 CCW and 2 NSCW pumps per train Red lights - ON Green lights - OFF Amber lights - OFF CCW pressures - in green bands (PI-1874 and PI-1875 - 90 psig)

CCW flows - in green bands (FI-1876 and FI-1877 - 9500 gpm)

NSCW Cooling Tower Fans, all 8 hand switches in AUTO.

4 Step # 3 CUE:

Standard:

Comment:

Step 1 Standard:

Comment:

Initiate ATTACHMENT A to align ECCS Pumps to the Cold Leg Recirculation flow path and continue with Step 4.

The SS will continue with step 4 while you perform Attachment A.

Initiates ATTACHMENT A ATTACHMENT A COLD LEG RECIRCULATION VALVE ALIGNMENT Check CCW cooling for RHR heat exchangers.

a.

CCW pumps - 2 running in each train.

b.

CCW pumps discharge pressures and flows - NORMAL

c.

NSCW cooling for CCW heat exchangers NCSW Pumps - TWO RUNNING EACH TRAIN.

NSCW CLG TOWER Fans - FOUR IN AUTO EACH TRAIN.

Determines the following:

2 CCW and 2 NSCW pumps per train Red lights - ON Green lights - OFF Amber lights - OFF CCW pressures - in green bands (PI-1874 and PI-1875 - 90 psig)

CCW flows - in green bands (FI-1876 and FI-1877 - 9500 gpm)

NSCW Cooling Tower Fans, all 8 hand switches in AUTO.

4

Step 2 Standard:

Comment:

Step 2b Standard:

Comment:

Step 2c Standard:

Comment:

Align RHR Pump A flow path:

a.

Check RHR Pump A - RUNNING.

Red light - ON, Green light - OFF Amber light - OFF Check CNMT SUMP TO RHR PMP-A SUCTION HV-8811A - OPEN.

Red light - ON, Green light - OFF.

Close RWST TO RHR PMP-A SUCTION HV-8812A.

Attempts to close HV-8812A by turning hand switch counter clockwise to the left.

Determines HV-8812A will NOT close.

Red light remains - ON Green light remains - OFF 5

Step 2 Standard:

Comment:

Step 2b Standard:

Comment:

Step 2c Standard:

Comment:

Align RHR Pump A flow path:

a.

Check RHR Pump A - RUNNING.

Red light - ON, Green light - OFF Amber light - OFF Check CNMT SUMP TO RHR PMP-A SUCTION HV-8811A - OPEN.

Red light - ON, Green light - OFF.

Close RWST TO RHR PMP-A SUCTION HV-8812A.

Attempts to close HV-8812A by turning hand switch counter clockwise to the left.

Determines HV-8812A will NOT close.

Red light remains - ON Green light remains - OFF 5

  • Step 2c Standard:

Comment:

Step 3 Standard:

Comment:

Step 3.b Standard:

Comment:

RNO -,IF HV8812A will not close. ;THEN stop RHR Pump A.

Places RHR pump A hand switch to STOP.

Green light - ON Red light - OFF Amber light - OFF Goes to step 3.

Align RHR Pump B flow path:

a.

Check RHR Pump B - RUNNING.

Red light - ON Green light - OFF Amber light - OFF

~-------.------...:-

\\'

\\ "

\\

Check CNMT SUMP TO RHR PMP-B SUCTION HV-8811 B - OPEN.

Determines HV-8811 B is CLOSED Green light - ON Red light - OFF 6

-1 Formatted: Font: (Default) Arial, 11 pt, Bold, Underline Formatted: Font: (Default) Arial, 11 pt, Bold Formatted: Font: (Default) Arial, 11 pt, Bold, Underline

  • Step 2c Standard:

Comment:

Step 3 Standard:

Comment:

Step 3.b Standard:

Comment:

RNO -,IF HV8812A will not close. ;THEN stop RHR Pump A.

Places RHR pump A hand switch to STOP.

Green light - ON Red light - OFF Amber light - OFF Goes to step 3.

Align RHR Pump B flow path:

a.

Check RHR Pump B - RUNNING.

Red light - ON Green light - OFF Amber light - OFF

~-------.------...:-

\\'

\\ "

\\

Check CNMT SUMP TO RHR PMP-B SUCTION HV-8811 B - OPEN.

Determines HV-8811 B is CLOSED Green light - ON Red light - OFF 6

Formatted: Font: (Default) Arial, 11 pt, Bold, Underline Formatted: Font: (Default) Arial, 11 pt, Bold Formatted: Font: (Default) Arial, 11 pt, Bold, Underline

  • Step 3.b RNO - IF HV-8811 B is NOT open, THEN perform the following:
1.

Stop RHR Pump B.

STOP TIME FOR TIME CRITICAL. ___

Standard:

Comment:

Places RHR pump B hand switch to STOP.

Green light - ON Red light - OFF Amber light - OFF RNO 3.b.2)

Close RWST TO RHR PMP-B SUCTION HV-8812B.

Standard:

Places HS-8812B to the CLOSE position.

Comment:

Green light - ON Red light - OFF RNO 3.b.3)

Open HV-8811 B.

Standard:

Attempts to open HV-8811 B by placing rotating hand switch clock wise to open.

Comment:

Determines HV-8811 B will NOT open.

Red light remains - OFF Green light remains - ON 7

  • Step 3.b RNO - IF HV-8811 B is NOT open, THEN perform the following:
1.

Stop RHR Pump B.

STOP TIME FOR TIME CRITICAL, ___

Standard:

Comment:

Places RHR pump B hand switch to STOP.

Green light - ON Red light - OFF Amber light - OFF RNO 3.b.2)

Close RWST TO RHR PMP-B SUCTION HV-8812B.

Standard:

Places HS-8812B to the CLOSE position.

Comment:

Green light - ON Red light - OFF RNO 3.b.3)

Open HV-8811 B.

Standard:

Attempts to open HV-8811 B by placing rotating hand switch clock wise to open.

Comment:

Determines HV-8811 B will NOT open.

Red light remains - OFF Green light remains - ON 7

RNO 3.bA)

Start RHR Pump B.

Standard:

Does NOT start RHR pump B which has no suction source.

Comment:

NOTE: If candidate starts RHR pump B, the step would become critical and be evaluated as UNSAT.

RNO 3.b.5)

Go to Step 3.d.

Standard:

Goes to step 3.d.

Comment:

Step 3.d Standard:

Comment:

Step 3.e Standard:

Comment:

Check RHR PMP-B TO COLD LEG 3&4 ISO VLV HV-8809B - OPEN.

Red light - ON Green light - OFF Check RHR Heat Exchanger B flow indicator FI-619A - GREATER THAN 500 GPM.

Determines on FI-0619A that RHR flow is < 500 gpm ( - 0 gpm) 8 RNO 3.bA)

Start RHR Pump B.

Standard:

Does NOT start RHR pump B which has no suction source.

Comment:

NOTE: If candidate starts RHR pump B, the step would become critical and be evaluated as UNSAT.

RNO 3.b.5)

Go to Step 3.d.

Standard:

Goes to step 3.d.

Comment:

Step 3.d Standard:

Comment:

Step 3.e Standard:

Comment:

Check RHR PMP-B TO COLD LEG 3&4 ISO VLV HV-8809B - OPEN.

Red light - ON Green light - OFF Check RHR Heat Exchanger B flow indicator FI-619A - GREATER THAN 500 GPM.

Determines on FI-0619A that RHR flow is < 500 gpm ( - 0 gpm) 8

  • Step 3.e Standard:

CUE:

Comment:

RNO - IF no RHR Pump is delivering CNMT Sump water to its discharge header, THEN go to 19111-C, ECA-1.1 LOSS OF EMERGENCY COOLANT RECIRCULATION.

Determines a transition to 19111-C is required and informs the SS.

The SS will initiate 19111-C, ECA-1.1 Loss of Emergency Coolant Recirculation". Another operator will perform the actions of 19111-C.

Terminating cue:

Student returns initiating cue sheet 9

  • Step 3.e Standard:

CUE:

Comment:

RNO - IF no RHR Pump is delivering CNMT Sump water to its discharge header, THEN go to 19111-C, ECA-1.1 LOSS OF EMERGENCY COOLANT RECIRCULATION.

Determines a transition to 19111-C is required and informs the SS.

The SS will initiate 19111-C, ECA-1.1 Loss of Emergency Coolant Recirculation". Another operator will perform the actions of 19111-C.

Terminating cue:

Student returns initiating cue sheet 9

Verification of Completion Job Performance Measure No. V-LO-JP-19013-003 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: ______________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date: _____________ _

10 Verification of Completion Job Performance Measure No. V-LO-JP-19013-003 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: ______________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date: _____________ _

10

Initial Conditions:

THIS IS A TIME CRITICAL JPM Initiating Cue:

A large break LOCA has occurred. While performing 19013, RWST level decreased below 29%. Transition to 19013 is required based on foldout page guidance.

The SS has directed you to "Transfer the ECCS pumps to cold leg recirculation using 19013".

11 Initial Conditions:

THIS IS A TIME CRITICAL JPM Initiating Cue:

A large break LOCA has occurred. While performing 19013, RWST level decreased below 29%. Transition to 19013 is required based on foldout page guidance.

The SS has directed you to "Transfer the ECCS pumps to cold leg recirculation using 19013".

11

Job Performance Measure "C" Facility: Vogtle Task No: V-LO-TA-13003 Task

Title:

Increase Accumulator Level At Low RCS Pressure JPM No: V-LO-JP-13105-003 KIA

Reference:

006A 1.13 Examinee:

NRC Examiner:

Facility Evaluator:

Date: ______________________ __

Method of testing:

Simulated Performance Actual Performance Classroom --------

Simulator --------

Plant _________ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

The plant is in Mode 4 at 350 psig and stable.

Maintenance personnel have just reported a leak on Accumulator #2 has been repaired.

Task Standard:

Student raises accumulator level using SOP 13105-1 until the accumulator low level and pressure alarms are clear.

Required Materials:

13105-1, Safety Injection System General

References:

None Initiating Cue:

The SS has directed you to "Restore level and pressure in Accumulator #2" using SOP*13105 section 4.4.1 to raise accumulator level to clear the level and pressure alarms.

Time Critical Task:

No Validation Time:

20 minutes 1

Job Performance Measure "C" Facility: Vogtle Task No: V-LO-TA-13003 Task

Title:

Increase Accumulator Level At Low RCS Pressure JPM No: V-LO-JP-13105-003 KIA

Reference:

006A 1.13 Examinee: ___________ _

NRC Examiner:

Date:

Facility Evaluator: ________ _

Method of testing:

Simulated Performance __________ _

Actual Performance _________ _

Classroom Simulator Plant Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

The plant is in Mode 4 at 350 psig and stable.

Maintenance personnel have just reported a leak on Accumulator #2 has been repaired.

Task Standard:

Student raises accumulator level using SOP 13105-1 until the accumulator low level and pressure alarms are clear.

Required Materials:

13105-1, Safety Injection System General

References:

None Initiating Cue:

The SS has directed you to "Restore level and pressure in Accumulator #2" using SOP*13105 section 4.4.1 to raise accumulator level to clear the level and pressure alarms.

Time Critical Task:

No Validation Time:

20 minutes 1

SIMULATOR SETUP:

1.

Reset to IC # 92 for the HL-15 NRC Exam

2.

Place SIP "An in PTL with a Red Danger Tag on the hand switch.

Simulator Setup From Scratch

1.

Reset to IC # 3 (Mode 4, 350 psig)

2.

Insert malfunction SI028 with a Final Value of 100%

3.

Verify Accumulator Tank 2 Hi / Lo Level annunciator alarms

4.

Remove malfunction when level annunciator illuminates

5.

Place SIP "An in PTL with a Red Danger Tag on the hand switch

6.

Close 1-HV-8821A, SIP "A" Discharge Isolation valve

7.

Close 1-HV-8806, SIP Common Suction Valve

8.

Place HV-8806 Lockout Switch to OFF

8.

Acknowledge / Reset alarms

9.

Freeze simulator Setup time: 5 minutes 2

SIMULATOR SETUP:

1.

Reset to IC # 92 for the HL-15 NRC Exam

2.

Place SIP "An in PTL with a Red Danger Tag on the hand switch.

Simulator Setup From Scratch

1.

Reset to IC # 3 (Mode 4, 350 psig)

2.

Insert malfunction SI028 with a Final Value of 100%

3.

Verify Accumulator Tank 2 Hi / Lo Level annunciator alarms

4.

Remove malfunction when level annunciator illuminates

5.

Place SIP "An in PTL with a Red Danger Tag on the hand switch

6.

Close 1-HV-8821A, SIP "A" Discharge Isolation valve

7.

Close 1-HV-8806, SIP Common Suction Valve

8.

Place HV-8806 Lockout Switch to OFF

8.

Acknowledge / Reset alarms

9.

Freeze simulator Setup time: 5 minutes 2

Performance Information Critical steps denoted with an asterisk Reviews cautions at beginning of section 4.4.1 4.4.1.1 Standard:

Comment:

  • (2)

Standard:

Comment:

  • (3)

Standard:

Comment:

Check SI Pump Injection Capability to the RCS remains isolated:

a.

Check 1-HV-8835, CL INJ FROM SIS, is closed. If necessary, close 1-HV-8835, CL INJ FROM SIS as follows:

  • (1)

Place SI PMP DISCH TO ALL CL LP Power Lockout Switch 1*HS*8835A in ON.

Places 1-HS-8835A to ON White light - ON Close CL INJ FROM SIS 1*HV*8835.

Green light - ON Red light - OFF Place 1*HS*8835A in LOCKOUT White light - OFF 3

Performance Information Critical steps denoted with an asterisk Reviews cautions at beginning of section 4.4.1 4.4.1.1 Standard:

Comment:

  • (2)

Standard:

Comment:

  • (3)

Standard:

Comment:

Check SI Pump Injection Capability to the RCS remains isolated:

a.

Check 1-HV-8835, CL INJ FROM SIS, is closed. If necessary, close 1-HV-8835, CL INJ FROM SIS as follows:

  • (1)

Place SI PMP DISCH TO ALL CL LP Power Lockout Switch 1*HS*8835A in ON.

Places 1-HS-8835A to ON White light - ON Close CL INJ FROM SIS 1*HV*8835.

Green light - ON Red light - OFF Place 1*HS*8835A in LOCKOUT White light - OFF 3

b.

Standard:

Comment:

c.

Standard:

Comment:

d.

Standard:

Comment:

e.

Standard:

Comment:

Check closed SI PMP-A TO HOT LEG 1 & 4 ISO VL V 1-HV-8802A.

Green light - ON Red light - OFF Check 1-HS-8802C in LOCKOUT.

White light - OFF Check closed SI PMP-B TO HOT LEG 2 & 3 ISO VL V 1-HV-8802B.

Green light - ON Red light - OFF Check 1-HS-8802D in LOCKOUT.

White light - OFF 4

b.

Standard:

Comment:

c.

Standard:

Comment:

d.

Standard:

Comment:

e.

Standard:

Comment:

Check closed SI PMP-A TO HOT LEG 1 & 4 ISO VL V 1-HV-8802A.

Green light - ON Red light - OFF Check 1-HS-8802C in LOCKOUT.

White light - OFF Check closed SI PMP-B TO HOT LEG 2 & 3 ISO VL V 1-HV-8802B.

Green light - ON Red light - OFF Check 1-HS-8802D in LOCKOUT.

White light - OFF 4

  • f.

Standard:

Comment:

g.

CUE:

Standard:

Comment:

4.4.1.2 Standard:

Comment:

4.4.1.3 Standard:

Comment:

IF SI Pump B will be used, open 1-HV-8821A and 1-HV-8821B.

Opens 1-HV-8821A: Red light -

ON Green light - OFF Opens 1-HV-8821B: Red light-ON Green light - OFF Document alignment changes per the controlling UOP checklist.

"Alignment changes have been documented in the UOP checklist" N/A Check RWST TO SI PUMPS ISOLATION 1-HV-8806 open.

Determines 1-HV-8806 is closed Green light - ON Red light -

OFF IF 1-HV-8806 is NOT open, perform the following:

  • a.

Place Lockout Switch 1-HS-8806A in the ON position.

White light - ON 5

  • f.

Standard:

Comment:

g.

CUE:

Standard:

Comment:

4.4.1.2 Standard:

Comment:

4.4.1.3 Standard:

Comment:

IF SI Pump B will be used, open 1-HV-8821A and 1-HV-8821B.

Opens 1-HV-8821A: Red light -

ON Green light - OFF Opens 1-HV-8821B: Red light-ON Green light - OFF Document alignment changes per the controlling UOP checklist.

"Alignment changes have been documented in the UOP checklist" N/A Check RWST TO SI PUMPS ISOLATION 1-HV-8806 open.

Determines 1-HV-8806 is closed Green light - ON Red light -

OFF IF 1-HV-8806 is NOT open, perform the following:

  • a.

Place Lockout Switch 1-HS-8806A in the ON position.

White light - ON 5

  • b.

Standard:

Comment:

4.4.1.4 Standard:

Comment:

4.4.1.5 Standard:

Comment:

Open 1-HV-8806 using 1-HS-8806.

Red light - ON Green light - OFF Open or check suction isolation valve for the SI pump to be used is open:

SI Pump A 1-HV-8923A SI Pump 8 1-HV-89238 1-HV-89238: Red light -

ON Green light - OFF Open or check 1-HV-8813, SIS PMPS COMMON MINI FLOW ISO VLV, is open.

Red light -

ON Green light - OFF 6

  • b.

Standard:

Comment:

4.4.1.4 Standard:

Comment:

4.4.1.5 Standard:

Comment:

Open 1-HV-8806 using 1-HS-8806.

Red light - ON Green light - OFF Open or check suction isolation valve for the SI pump to be used is open:

SI Pump A 1-HV-8923A SI Pump 8 1-HV-89238 1-HV-89238: Red light -

ON Green light - OFF Open or check 1-HV-8813, SIS PMPS COMMON MINI FLOW ISO VLV, is open.

Red light -

ON Green light - OFF 6

4.4.1.6 Standard:

Comment:

4.4.1.7 Standard:

Comment:

  • 4.4.1.8 Standard:

Comment:

Open or check the Mini-flow for the pump to be started is open:

SI Pump A 1-HV-8814 SI Pump B 1-HV-8920 1-HV-8920:

Red light -

ON Green light - OFF Start one SI Pump:

SI Pump A 1-HS-0998A

  • 51 Pump B 1-HS-0999A 1-HS-0999A to start Red light - ON Green light - OFF Amber light - OFF Discharge pressures (PI-919 & PI-923) - 1500 psig Open ACCUM FILL ISO 1-HV-8888.

Red light - ON Green light - OFF 7

4.4.1.6 Standard:

Comment:

4.4.1.7 Standard:

Comment:

  • 4.4.1.8 Standard:

Comment:

Open or check the Mini-flow for the pump to be started is open:

SI Pump A 1-HV-8814 SI Pump B 1-HV-8920 1-HV-8920:

Red light -

ON Green light - OFF Start one SI Pump:

SI Pump A 1-HS-0998A

  • 51 Pump B 1-HS-0999A 1-HS-0999A to start Red light - ON Green light - OFF Amber light - OFF Discharge pressures (PI-919 & PI-923) - 1500 psig Open ACCUM FILL ISO 1-HV-8888.

Red light - ON Green light - OFF 7

  • 4.4.1.9 Standard:

Comment:

4.4.1.10

a.
  • b.
c.
d.

Standard:

Comment:

  • 4.4.1.11 CUE:

Standard:

Comment:

Open SIS CHECK VALVE TEST CNMT ISO 1-HV-8871.

Red light - ON Green light - OFF Open ACCUM WTR FILL VL V for the tank to be filled and monitor level indication:

Accumulator 1 1-HV-8878A 1-U-0950/0951 Accumulator 2 1-HV-8878B 1-Ll-0952/0953 Accumulator 3 1-HV-8878C 1-U-0954/0955 Accumulator 4 1-HV-8878D 1-U-0956/0957.

Red light - ON Green light - OFF U-0952 & U-0953 rising WHEN the desired Accumulator level is reached, close the Fill Valve opened in the previous step. (IV REQUIRED)

If asked, "Extra Operator will perform the IV".

ACCUM TANK 2 HilLa LEVEL alarm - CLEAR ACCUM TANK 2 HilLa PRESS alarm - CLEAR 1-HV-88788 placed in close Green light - ON Red light - OFF 8

  • 4.4.1.9 Standard:

Comment:

4.4.1.10

a.
  • b.
c.
d.

Standard:

Comment:

  • 4.4.1.11 CUE:

Standard:

Comment:

Open SIS CHECK VALVE TEST CNMT ISO 1-HV-8871.

Red light - ON Green light - OFF Open ACCUM WTR FILL VL V for the tank to be filled and monitor level indication:

Accumulator 1 1-HV-8878A 1-U-0950/0951 Accumulator 2 1-HV-8878B 1-Ll-0952/0953 Accumulator 3 1-HV-8878C 1-U-0954/0955 Accumulator 4 1-HV-8878D 1-U-0956/0957.

Red light - ON Green light - OFF U-0952 & U-0953 rising WHEN the desired Accumulator level is reached, close the Fill Valve opened in the previous step. (IV REQUIRED)

If asked, "Extra Operator will perform the IV".

ACCUM TANK 2 HilLa LEVEL alarm - CLEAR ACCUM TANK 2 HilLa PRESS alarm - CLEAR 1-HV-88788 placed in close Green light - ON Red light - OFF 8

4.4.1.12 Repeat Steps 4.4.1.10 and 4.4.1.11 if required to adjust levels in additional Accumulators.

Standard:

N/A Comment:

  • 4.4.1.13 CUE:

Standard:

Comment:

  • 4.4.1.14 CUE:

Standard:

Comment:

  • 4.4.1.15 Standard:

Comment:

Close 1*HV*8871. (IV REQUIRED)

If asked, "Extra Operator will perform the IV".

Green light - ON Red light - OFF Close 1*HV*8888. (IV REQUIRED)

If asked, "Extra Operator will perform the IV".

Green light - ON Red light - OFF Stop the SI Pump.

Places 1-HS-0999A in stop Green light - ON Red light - OFF Amber light - OFF Discharge pressures (PI-919 & PI-923) remain - 1500 psig 9

4.4.1.12 Repeat Steps 4.4.1.10 and 4.4.1.11 if required to adjust levels in additional Accumulators.

Standard:

N/A Comment:

  • 4.4.1.13 CUE:

Standard:

Comment:

  • 4.4.1.14 CUE:

Standard:

Comment:

  • 4.4.1.15 Standard:

Comment:

Close 1*HV*8871. (IV REQUIRED)

If asked, "Extra Operator will perform the IV".

Green light - ON Red light - OFF Close 1*HV*8888. (IV REQUIRED)

If asked, "Extra Operator will perform the IV".

Green light - ON Red light - OFF Stop the SI Pump.

Places 1-HS-0999A in stop Green light - ON Red light - OFF Amber light - OFF Discharge pressures (PI-919 & PI-923) remain - 1500 psig 9

Reviews caution prior to next step.

4.4.1.16 CUE:

Standard:

Comment:

Relieve Safety Injection Header pressure to less than or equal to Accumulator pressure by performing the following:

a.

Open SIS CHECK VALVE TEST CNMT ISO Valve, 1-HV-8871.

"The Extra will complete this procedure".

N/A Terminating cue:

Student returns initiating cue sheet 10 Reviews caution prior to next step.

4.4.1.16 CUE:

Standard:

Comment:

Relieve Safety Injection Header pressure to less than or equal to Accumulator pressure by performing the following:

a.

Open SIS CHECK VALVE TEST CNMT ISO Valve, 1-HV-8871.

"The Extra will complete this procedure".

N/A Terminating cue:

Student returns initiating cue sheet 10

Verification of Completion Job Performance Measure No. V-LO-JP-131 05-003 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: _____________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date: ______________ _

11 Verification of Completion Job Performance Measure No. V-LO-JP-131 05-003 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: ________________________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date:

11

Initial Conditions:

The plant is in Mode 4 at 350 psig and stable.

Initiating Cue:

Maintenance personnel have just reported a leak on Accumulator #2 has been repaired.

The 55 has directed you to "Restore level and pressure in Accumulator #2" using 50P-13105 section 4.4.1 to raise accumulator level to clear the level and pressure alarms.

12 Initial Conditions:

The plant is in Mode 4 at 350 psig and stable.

Initiating Cue:

Maintenance personnel have just reported a leak on Accumulator #2 has been repaired.

The 55 has directed you to "Restore level and pressure in Accumulator #2" using 50P-13105 section 4.4.1 to raise accumulator level to clear the level and pressure alarms.

12

Job Performance Measure "0" Facility: VogUe Task No: V-LO-TA-37011 Task

Title:

Isolate a ruptured SG with failure of TDAFW Steam and MSIV 3006A / B to close.

JPM No: V-LO-JP-19030-006 KIA

Reference:

035A4.06 Examinee: __________ _

NRC Examiner: ______________ __

Facility Evaluator: _________ _

Date: ______________________ ___

Method of testing:

Simulated Performance ________ _

Actual Performance _______ _

Classroom ________ __

Simulator ______ _

Plant ______ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

THIS IS A TIME CRITICAL JPM A reactor trip occurred from 100% power. While the crew was attempting to stabilize the plant, a low PRZR pressure SI occurred.

The crew transitioned from 19000, E-O to 19030.

Task Standard:

Identify SG # 1 as ruptured. Close all MSIVs and Bypasses on the intact SGs, set ARV loop # 1 potentiometer to 7.73, close the TDAFW pump T & T valve, close the Steam dumps, close the MDAFW throttle valve to SG # 1, closes SJAE # 2 steam supply 4085B.

Required Materials:

19030-C, Steam Generator Tube Rupture General

References:

None Initiating Cue:

The SS has directed you to "Isolate the ruptured SG using 19030 starting at step # 4".

Time Critical Task:

Yes Validation Time:

15 minutes (12 minutes time critical after ID of SG # 1 as ruptured).

Job Performance Measure "0" Facility: VogUe Task No: V-LO-TA-37011 Task

Title:

Isolate a ruptured SG with failure of TDAFW Steam and MSIV 3006A / B to close.

JPM No: V-LO-JP-19030-006 KIA

Reference:

035A4.06 Examinee: __________ _

NRC Examiner: ______________ __

Facility Evaluator: _________ _

Date: ______________________ ___

Method of testing:

Simulated Performance ________ _

Actual Performance _______ _

Classroom ________ __

Simulator ______ _

Plant ______ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

THIS IS A TIME CRITICAL JPM A reactor trip occurred from 100% power. While the crew was attempting to stabilize the plant, a low PRZR pressure SI occurred.

The crew transitioned from 19000, E-O to 19030.

Task Standard:

Identify SG # 1 as ruptured. Close all MSIVs and Bypasses on the intact SGs, set ARV loop # 1 potentiometer to 7.73, close the TDAFW pump T & T valve, close the Steam dumps, close the MDAFW throttle valve to SG # 1, closes SJAE # 2 steam supply 4085B.

Required Materials:

19030-C, Steam Generator Tube Rupture General

References:

None Initiating Cue:

The SS has directed you to "Isolate the ruptured SG using 19030 starting at step # 4".

Time Critical Task:

Yes Validation Time:

15 minutes (12 minutes time critical after ID of SG # 1 as ruptured).

SIMULATOR SETUP:

IC # 99 for HL-15 NRC exam, pre-snapped.

Simulator setup from scratch if needed.

1.

Reset to IC # 14 (MOL, 100%)

2.

Insert Over ride on 1 HV-3006A to OPEN

3.

Insert Over ride on 1 HV-3006A Green light to OFF

4.

Insert Over ride on 1 HV-30068 to OPEN

5.

Insert Over ride on 1 HV-30068 Green light to OFF

6.

Insert Over ride on 1 HV-3009 to OPEN

7.

Insert malfunction SG01A at 50% severity.

8.

Initiate manual Rx trip and SI

9.

Throttle AF'N flow to 200 gpm on ALL SGs.

10.

Verify ruptured SG # 1 level> 10% NR

11.

Acknowledge / Reset alarms

12.

Freeze simulator Setup time: minutes 2

SIMULATOR SETUP:

IC # 99 for HL-15 NRC exam, pre-snapped.

Simulator setup from scratch if needed.

1.

Reset to IC # 14 (MOL, 100%)

2.

Insert Over ride on 1 HV-3006A to OPEN

3.

Insert Over ride on 1 HV-3006A Green light to OFF

4.

Insert Over ride on 1 HV-30068 to OPEN

5.

Insert Over ride on 1 HV-30068 Green light to OFF

6.

Insert Over ride on 1 HV-3009 to OPEN

7.

Insert malfunction SG01A at 50% severity.

8.

Initiate manual Rx trip and SI

9.

Throttle AF'N flow to 200 gpm on ALL SGs.

10.

Verify ruptured SG # 1 level> 10% NR

11.

Acknowledge / Reset alarms

12.

Freeze simulator Setup time: minutes 2

Performance Information Critical steps denoted with an asterisk Step # 4 Standard:

Comment:

Step # 4 Standard:

Comment:

Step # 4.b Standard:

Comment:

Check if RCPs should be stopped:

a.

ECCS Pumps - AT LEAST ONE RUNNING:

CCP or SIP Checks CCPs and SIPs all running Red lights - ON Green lights - OFF Amber lights - OFF Note: The candidate may also check BIT flow (FI-0917) or SIP discharge pressure indications (PI-0919 and PI-0923) for confirmation the pumps are actually running.

b.

RCS pressure LESS THAN 1375 psig Checks any of various pressure indications.

Determines RCS pressure to be - 2000 psig.

RNO - IF RCS pressure lowers to less than 1375 psig prior to initiation of RCS cooldown in Step 20, THEN stop all RCPs and return to Step in affect.

Go to step 5 Notes RNO continuous actions.

Goes to step 5.

3 Performance Information Critical steps denoted with an asterisk Step # 4 Standard:

Comment:

Step # 4 Standard:

Comment:

Step # 4.b Standard:

Comment:

Check if RCPs should be stopped:

a.

ECCS Pumps - AT LEAST ONE RUNNING:

CCP or SIP Checks CCPs and SIPs all running Red lights - ON Green lights - OFF Amber lights - OFF Note: The candidate may also check BIT flow (FI-0917) or SIP discharge pressure indications (PI-0919 and PI-0923) for confirmation the pumps are actually running.

b.

RCS pressure LESS THAN 1375 psig Checks any of various pressure indications.

Determines RCS pressure to be - 2000 psig.

RNO - IF RCS pressure lowers to less than 1375 psig prior to initiation of RCS cooldown in Step 20, THEN stop all RCPs and return to Step in affect.

Go to step 5 Notes RNO continuous actions.

Goes to step 5.

3

  • Step # 5 Identify ruptured SG(s) by any of the following conditions:

_ Unexpected rise in any SG NR level.

_ High radiation from any SG sample.

_ High radiation from any SG steam line.

_ High radiation from any SG blow down line.

CUE: IF asked, SG sample results are NOT available at this time.

Standard:

Comment:

Identifies SG # 1 as the ruptured SG on unexpected level rise.

Note: The candidate may throttle AFW flow to the SG (HV-5139) to help in determining the ruptured SG or he may just call the SG ruptured on the level differential.

START TIME CRITICAL ____ (once ruptured SG # 1 identified)

Reviews CAUTION for maintaining one SG for cooldown.

  • Step # 6 Standard:

Comment:

Isolate ruptured SG ARV(s):

a.

Adjust ruptured SG ARV(s) controller set point to 1160 psig (pot setting 7.73).

b.

Check ruptured SG ARV - CLOSED PV-3000 (SG 1)

Sets PV-3000 (SG 1) potentiometer to 7.73 and in AUTO Checks SG # 1 ARV - closed as indicated on ZLB - 4, Miscellaneous Status Lights.

4

  • Step # 5 Identify ruptured SG(s) by any of the following conditions:

_ Unexpected rise in any SG NR level.

_ High radiation from any SG sample.

_ High radiation from any SG steam line.

_ High radiation from any SG blow down line.

CUE: IF asked, SG sample results are NOT available at this time.

Standard:

Comment:

Identifies SG # 1 as the ruptured SG on unexpected level rise.

Note: The candidate may throttle AFW flow to the SG (HV-5139) to help in determining the ruptured SG or he may just call the SG ruptured on the level differential.

START TIME CRITICAL ____ (once ruptured SG # 1 identified)

Reviews CAUTION for maintaining one SG for cooldown.

  • Step # 6 Standard:

Comment:

Isolate ruptured SG ARV(s):

a.

Adjust ruptured SG ARV(s) controller set point to 1160 psig (pot setting 7.73).

b.

Check ruptured SG ARV - CLOSED PV-3000 (SG 1)

Sets PV-3000 (SG 1) potentiometer to 7.73 and in AUTO Checks SG # 1 ARV - closed as indicated on ZLB - 4, Miscellaneous Status Lights.

4

Step # 7 Standard:

Comment:

Step # 8 Standard:

Comment:

  • Step # 8 Standard:

Comment:

Check at least one MDAFW Pump - RUNNING AND CAPABLE OF FEEDING SG(s) NEEDED FOR RCS COOLDOWN.

Checks MDAFW pumps A and B running Red lights - ON Green lights - OFF Amber lights - OFF Close affected TDAFW Pump Steam Supply Valve(s):

_ HV-3009 (SG 1) LP-1 MS SPLY TO AUX FW TO PMP-1 Attempts to close HV-3009 by rotating the hand switch counter clockwise to the CLOSE position.

Determines HV-3009 will NOT close.

Red light - ON Green light - OFF RNO

  • IF at least one MDAFW Pump running, THEN trip the TDAFW Pump b~ closing PV*1S129 using HS-1S111.

Trips the TDAFW pump by rotating the hand switch HV-15111 counter Clockwise to the CLOSE position.

Green light - ON Red light - OFF Amber light - OFF.

Speed on SI-15109A lowering 5

Step # 7 Standard:

Comment:

Step # 8 Standard:

Comment:

  • Step # 8 Standard:

Comment:

Check at least one MDAFW Pump - RUNNING AND CAPABLE OF FEEDING SG(s) NEEDED FOR RCS COOLDOWN.

Checks MDAFW pumps A and B running Red lights - ON Green lights - OFF Amber lights - OFF Close affected TDAFW Pump Steam Supply Valve(s):

_ HV-3009 (SG 1) LP-1 MS SPLY TO AUX FW TO PMP-1 Attempts to close HV-3009 by rotating the hand switch counter clockwise to the CLOSE position.

Determines HV-3009 will NOT close.

Red light - ON Green light - OFF RNO

  • IF at least one MDAFW Pump running, THEN trip the TDAFW Pump b~ closing PV*1S129 using HS-1S111.

Trips the TDAFW pump by rotating the hand switch HV-15111 counter Clockwise to the CLOSE position.

Green light - ON Red light - OFF Amber light - OFF.

Speed on SI-15109A lowering 5

Step # 9 Standard:

Comment:

Step # 10 Standard:

Comment:

Verify SG Blowdown Isolation Valves - CLOSED WITH HANDSWITCHES IN CLOSE POSITION.

Observes SGBD isolation valves closed.

Green lights - ON Red lights - OFF Places hand switches for all 4 SGBD (HS-7603A, B, C, D) to CLOSE position.

Isolate flow from the ruptured SG(s) by closing its Main Steamline Isolation and Bypass Valves.

Attempts to close SG # 1 MSIVs using HS-3006A and HS-3006B Determines HV-3006A and HV-3006B will NOT close Red lights - ON Green lights - OFF Closes MSIV bypasses using HS-1300SA and HS-1300SB Green lights - ON Red lights - OFF 6

Step # 9 Standard:

Comment:

Step # 10 Standard:

Comment:

Verify SG Blowdown Isolation Valves - CLOSED WITH HANDSWITCHES IN CLOSE POSITION.

Observes SGBD isolation valves closed.

Green lights - ON Red lights - OFF Places hand switches for all 4 SGBD (HS-7603A, B, C, D) to CLOSE position.

Isolate flow from the ruptured SG(s) by closing its Main Steamline Isolation and Bypass Valves.

Attempts to close SG # 1 MSIVs using HS-3006A and HS-3006B Determines HV-3006A and HV-3006B will NOT close Red lights - ON Green lights - OFF Closes MSIV bypasses using HS-1300SA and HS-1300SB Green lights - ON Red lights - OFF 6

  • Step # 10 RNO - Perform the following:

Standard:

Comment:

a.

Close all remaining Main Steam line Isolation and Bypass Valves.

Initiates an SLI using either hand switch (HS-300? A or HS-300?B) OR Individually closes SG 2, 3, and 4 MSIVs and Bypass valves.

SG 2, 3, and 4 MSIV and Bypass valves.

Green lights - ON Red lights - OFF

  • Step # 10 RNO - b. Verify the following valves are closed:

Standard:

Comment:

Steam dump valves Status light board ZLB - 2 Determines that steam dump valves are open using ZLB - 2, miscellaneous status lights.

Closes the steam dumps by using one of the following methods (not specified how in the procedure step).

Selecting an OFF / RESET switch to the OFF position (HS-0500A or B)

OR Selecting Steam Pressure Mode on HS-0500C and manually lowering demand on PIC-50? until the green down arrow is lit.

7

  • Step # 10 RNO - Perform the following:

Standard:

Comment:

a.

Close all remaining Main Steam line Isolation and Bypass Valves.

Initiates an SLI using either hand switch (HS-300? A or HS-300?B) OR Individually closes SG 2, 3, and 4 MSIVs and Bypass valves.

SG 2, 3, and 4 MSIV and Bypass valves.

Green lights - ON Red lights - OFF

  • Step # 10 RNO - b. Verify the following valves are closed:

Standard:

Comment:

Steam dump valves Status light board ZLB - 2 Determines that steam dump valves are open using ZLB - 2, miscellaneous status lights.

Closes the steam dumps by using one of the following methods (not specified how in the procedure step).

Selecting an OFF / RESET switch to the OFF position (HS-0500A or B)

OR Selecting Steam Pressure Mode on HS-0500C and manually lowering demand on PIC-50? until the green down arrow is lit.

7

Step # 10 Standard:

Comment:

RNO - b. Verify the following valves are closed:

AUX AND MAIN STEAM SPARGER valve HV-6194 Checks HV-6194 Aux and Main Steam Sparger valves closed.

Green lights - ON Red lights - OFF

  • Step # 10 RNO - b. Verify the following valves are closed:

Steam Jet Air Ejector valves HV-4084B, SJAE-1 MN & AUX STM SPLY VLV HV-4085B, SJAE-2 MN & AUX STM SPL Y VLV Possible - STOP TIME CRITICAL, ___ _

Note: If, the operator closed the MDAFW isolation valve HV-5139 to SG # 1 earlier when identifying the ruptured SG and left the valve closed, this is the last critical step.

IF the valve is open the critical time does NOT stop here.

Standard:

Comment:

Checks HV-4084B closed on ZLB-2, Miscellaneous Status Light Board.

Green light - ON Red light - OFF Places SJAE HS-4085 to the OFF position.

Checks HV-4085B closes (takes 15 seconds) on ZLB-3, Miscellaneous Status Light Board.

Green light - ON Red light - OFF Note: HV-4085A takes several minutes to close but is NOT specified in the procedure as this is a SJAE suction valve. The candidate should NOT wait on this valve to close.

8 Step # 10 Standard:

Comment:

RNO - b. Verify the following valves are closed:

AUX AND MAIN STEAM SPARGER valve HV-6194 Checks HV-6194 Aux and Main Steam Sparger valves closed.

Green lights - ON Red lights - OFF

  • Step # 10 RNO - b. Verify the following valves are closed:

Steam Jet Air Ejector valves HV-4084B, SJAE-1 MN & AUX STM SPLY VLV HV-4085B, SJAE-2 MN & AUX STM SPL Y VLV Possible - STOP TIME CRITICAL ___ _

Note: If, the operator closed the MDAFW isolation valve HV-5139 to SG # 1 earlier when identifying the ruptured SG and left the valve closed, this is the last critical step.

IF the valve is open the critical time does NOT stop here.

Standard:

Comment:

Checks HV-4084B closed on ZLB-2, Miscellaneous Status Light Board.

Green light - ON Red light - OFF Places SJAE HS-4085 to the OFF position.

Checks HV-4085B closes (takes 15 seconds) on ZLB-3, Miscellaneous Status Light Board.

Green light - ON Red light - OFF Note: HV-4085A takes several minutes to close but is NOT specified in the procedure as this is a SJAE suction valve. The candidate should NOT wait on this valve to close.

8

Step # 10 Standard:

Comment:

Step # 10 Standard:

Comment:

RNa - b. Verify the following valves are closed:

MSR steam supply HV-6030, MSR A & C REHEAT STEAM SOURCE STOP VALVE HV-601S, MSR B & 0 REHEAT STEAM SOURCE STOP VALVE Checks valves are closed.

Green lights - ON Red lights - OFF RNa - c. Use intact SG ARV(s) for dumping steam.

IF at least one intact SG can NOT be isolated from any ruptured SG, THEN go to 19131-C, ECA-3.1 SGTR WITH LOSS OF REACTOR COOLANT SUBCOOLED RECOVERY DESIRED.

Notes RNO step c to use intact SG ARV(s).

Determines a transition to 19131-C is NOT required.

9 Step # 10 Standard:

Comment:

Step # 10 Standard:

Comment:

RNa - b. Verify the following valves are closed:

MSR steam supply HV-6030, MSR A & C REHEAT STEAM SOURCE STOP VALVE HV-601S, MSR B & 0 REHEAT STEAM SOURCE STOP VALVE Checks valves are closed.

Green lights - ON Red lights - OFF RNa - c. Use intact SG ARV(s) for dumping steam.

IF at least one intact SG can NOT be isolated from any ruptured SG, THEN go to 19131-C, ECA-3.1 SGTR WITH LOSS OF REACTOR COOLANT SUBCOOLED RECOVERY DESIRED.

Notes RNO step c to use intact SG ARV(s).

Determines a transition to 19131-C is NOT required.

9

Reviews CAUTION prior to step # 11 regarding performing procedure in a timely manner.

Step # 11 Standard:

Comment:

Step # 12 Standard:

Comment:

Step # 12 Standard:

Comment:

Maintain any ruptured SG that is also faulted, isolated during subseguent recovery actions unless needed for RCS cooldown or SG activity sample.

Reviews CAUTION and step # 11 Check ruptured SG(s) isolated from intact SG(s):

a.

Check either of the following conditions satisfied:

_ Ruptured SG(s) steamline(s) ISOLATED OR

_Intact SG(s) to be used for cooldown, steamlines -ISOLATED Checks SG # 2, # 3, and # 4 steamlines isolated.

Green lights - ON Red lights - OFF Check ruptured SG(s) isolated from intact SG(s):

b.

Check TDAFW Pump steam supply from ruptured SG(s) - CLOSED.

Checks steam to TDAFW pump still isolated.

T & T valve - CLOSED Green light - ON Red light - OFF 10 Reviews CAUTION prior to step # 11 regarding performing procedure in a timely manner.

Step # 11 Standard:

Comment:

Step # 12 Standard:

Comment:

Step # 12 Standard:

Comment:

Maintain any ruptured SG that is also faulted, isolated during subseguent recovery actions unless needed for RCS cooldown or SG activity sample.

Reviews CAUTION and step # 11 Check ruptured SG(s) isolated from intact SG(s):

a.

Check either of the following conditions satisfied:

_ Ruptured SG(s) steamline(s) ISOLATED OR

_Intact SG(s) to be used for cooldown, steamlines -ISOLATED Checks SG # 2, # 3, and # 4 steamlines isolated.

Green lights - ON Red lights - OFF Check ruptured SG(s) isolated from intact SG(s):

b.

Check TDAFW Pump steam supply from ruptured SG(s) - CLOSED.

Checks steam to TDAFW pump still isolated.

T & T valve - CLOSED Green light - ON Red light - OFF 10

  • Step # 13 Check ruptured SG(s) level:
a.

SG NR level-GREATER THAN 10% [32% ADVERSE]

b.

Stop feed flow to ruptured SG(s)

STOP TIME CRITICAL ___ _

Note: If MDAFW throttle HV-5139 has NOT previously been closed, closing the valve at this time would stop the time critical clock.

Standard:

Comment:

Checks SG # 1 NR level> 10%

Rotates HS-5139 counter clockwise to the CLOSED position Green light - ON Red light - OFF White Light - ON Checks no AFW flow to SG # 1 (FI-5152A)

Note: The candidate may also elect to close the TDAFW throttle valve at this time (HV-5122), however, the TDAFW is NOT feeding forward at this time and is not part of the critical step.

Green light - ON Red light - OFF White light - ON Terminating cue:

"The SS will have another operator complete the procedure".

11

  • Step # 13 Check ruptured SG(s) level:
a.

SG NR level-GREATER THAN 10% [32% ADVERSE]

b.

Stop feed flow to ruptured SG(s)

STOP TIME CRITICAL ___ _

Note: If MDAFW throttle HV-5139 has NOT previously been closed, closing the valve at this time would stop the time critical clock.

Standard:

Comment:

Checks SG # 1 NR level> 10%

Rotates HS-5139 counter clockwise to the CLOSED position Green light - ON Red light - OFF White Light - ON Checks no AFW flow to SG # 1 (FI-5152A)

Note: The candidate may also elect to close the TDAFW throttle valve at this time (HV-5122), however, the TDAFW is NOT feeding forward at this time and is not part of the critical step.

Green light - ON Red light - OFF White light - ON Terminating cue:

"The SS will have another operator complete the procedure".

11

Verification of Completion Job Performance Measure No. V-LO-JP-19030-006 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: _____________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date: _____________ _

12 Verification of Completion Job Performance Measure No. V-LO-JP-19030-006 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: _____________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date: _____________ _

12

Initial Conditions:

THI5 15 A TIME CRITICAL JPM Initiating Cue:

A reactor trip occurred from 100% power. While the crew was attempting to stabilize the plant, a low PRZR pressure 51 occurred.

The crew transitioned from 19000, E-O to 19030.

The 55 has directed you to "Isolate the ruptured 5G using 19030 starting at step # 4".

13 Initial Conditions:

THI5 15 A TIME CRITICAL JPM Initiating Cue:

A reactor trip occurred from 100% power. While the crew was attempting to stabilize the plant, a low PRZR pressure 51 occurred.

The crew transitioned from 19000, E-O to 19030.

The 55 has directed you to "Isolate the ruptured 5G using 19030 starting at step # 4".

13

Job Performance Measure "E" Facility: Vogtle Task No: V-LO-TA-15003 Task

Title:

Transfer Containment Spray To Recirculation JPM No: V-LO-JP-19013-005 KIA

Reference:

Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance Actual Performance Classroom -------

Simulator -------

Plant _____ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

A large break LOCA has occurred. The crew performed the cold leg recirculation lineup using 19013, and returned to 19010. After transitioning to 19010, RWST level decreased below 8%. The Auxiliary Building Operator is standing by the local Containment Spray suction and discharge pressure gauges.

Task Standard:

Containment Spray aligned for recirculation with Containment Spray pump A stopped, Train B CNMT sump suctions HV-9002B and HV-9003B both open, Train B RWST suction HV-9017B shut, Containment Spray pump B running.

Required Materials:

19013-C, Transfer to Cold Leg Recirculation General

References:

None Initiating Cue:

The SS has directed you to "Align Containment Spray for recirculation beginning with step 17 of 19013".

Time Critical Task:

No Validation Time:

1 0 minutes 1

Job Performance Measure "E" Facility: Vogtle Task No: V-LO-TA-15003 Task

Title:

Transfer Containment Spray To Recirculation JPM No: V-LO-JP-19013-005 KIA

Reference:

Examinee: ___________ _

NRC Examiner: ______________ _

Facility Evaluator: ________ _

Date: --------------------

Method of testing:

Simulated Performance -------

Actual Performance ________ _

Classroom ________ __

Simulator ___________ _

Plant ----------

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

A large break LOCA has occurred. The crew performed the cold leg recirculation lineup using 19013, and returned to 19010. After transitioning to 19010, RWST level decreased below 8%. The Auxiliary Building Operator is standing by the local Containment Spray suction and discharge pressure gauges.

Task Standard:

Containment Spray aligned for recirculation with Containment Spray pump A stopped, Train B CNMT sump suctions HV-9002B and HV-9003B both open, Train B RWST suction HV-9017B shut, Containment Spray pump B running.

Required Materials:

19013-C, Transfer to Cold Leg Recirculation General

References:

None Initiating Cue:

The SS has directed you to "Align Containment Spray for recirculation beginning with step 17 of 19013".

Time Critical Task:

No Validation Time:

1 0 minutes 1

SIMULATOR SETUP:

This JPM has been snapped to IC # 98 for the HL-15 NRC Exam.

Simulator Setup from scratch.

1.

Reset to IC # 14 (100%, MOL)

2.

Insert malfunction RC03C (DBA LOCA)

3.

Trip all RCPs

4.

Throttle AFW flow to - 200 gpm/SG.

5.

When Containment Emergency Sump levels are - '5" Set RF: TK02 = 29% (RWST)

6.

Perform 19013-C steps 1 through 16.

7.

Set RF: TK02 = 8%

8.

Use Panel Drawings to over ride HV-9002A to SHUT

9.

Acknowledge / Reset alarms

10.

Freeze simulator Setup time: 20 minutes 2

SIMULATOR SETUP:

This JPM has been snapped to IC # 98 for the HL-15 NRC Exam.

Simulator Setup from scratch.

1.

Reset to IC # 14 (100%, MOL)

2.

Insert malfunction RC03C (DBA LOCA)

3.

Trip all RCPs

4.

Throttle AFW flow to - 200 gpm/SG.

5.

When Containment Emergency Sump levels are - '5" Set RF: TK02 = 29% (RWST)

6.

Perform 19013-C steps 1 through 16.

7.

Set RF: TK02 = 8%

8.

Use Panel Drawings to over ride HV-9002A to SHUT

9.

Acknowledge / Reset alarms

10.

Freeze simulator Setup time: 20 minutes 2

Performance Information Critical steps denoted with an asterisk Reviews CAUTION prior to step # 17 regarding performance of steps 17 - 19 and dispatching personnel to locally monitor spray pumps rad levels permitting.

Standard:

Rotates both Containment Spray reset hand switches to RESET position.

Comment:

Step # 18 Standard:

Comment:

HS - 40058 to RESET HS - 40059 to RESET Checks CNMT SPRAY ACTUATION annunciator window resets (ALB06, D06)

Align CS Pump A for recirculation:

a. Open CS Pump A suction valves from Containment Emergency Sump:

HV-9002A, CNMT SPRAY PUMP A CNMT SUMP SUCT IRC HV-9003A, CNMT SPRAY PUMP A CNMT SUMP SUCT ORC Determines HV-9002A will NOT open.

Green light - ON Red light - OFF 3

Performance Information Critical steps denoted with an asterisk Reviews CAUTION prior to step # 17 regarding performance of steps 17 - 19 and dispatching personnel to locally monitor spray pumps rad levels permitting.

Standard:

Rotates both Containment Spray reset hand switches to RESET position.

Comment:

Step # 18 Standard:

Comment:

HS - 40058 to RESET HS - 40059 to RESET Checks CNMT SPRAY ACTUATION annunciator window resets (ALB06, D06)

Align CS Pump A for recirculation:

a. Open CS Pump A suction valves from Containment Emergency Sump:

HV-9002A, CNMT SPRAY PUMP A CNMT SUMP SUCT IRC HV-9003A, CNMT SPRAY PUMP A CNMT SUMP SUCT ORC Determines HV-9002A will NOT open.

Green light - ON Red light - OFF 3

  • Step # 18 RNO - a. Locally open:

Standard:

Comment:

  • Step # 19 Standard:

Comment:

1-HV-9003A (AB-C134) 2-HV-9003A (AB-C124) lE valves can NOT be opened, THEN stop CS pump A.

Go to step 19.

Stops Containment Spray pump A by rotating hand switch HS-10940 counter clockwise and verifying the pump stops by:

Red light - OFF Green light - ON Amber light - OFF Align CS Pump B for recirculation:

a. Open CS Pump B suction valves from Containment Emergency Sump:

HV-9002B, CNMT SPRAY PUMP B CNMT SUMP SUCT IRC HV-9003B, CNMT SPRAY PUMP B CNMT SUMP SUCT ORC Opens HV-9002B Red light - ON Green light - OFF Opens HV-9003B Red light - ON Green lights - OFF 4

  • Step # 18 RNO - a. Locally open:

Standard:

Comment:

  • Step # 19 Standard:

Comment:

1-HV-9003A (AB-C134) 2-HV-9003A (AB-C124) lE valves can NOT be opened, THEN stop CS pump A.

Go to step 19.

Stops Containment Spray pump A by rotating hand switch HS-10940 counter clockwise and verifying the pump stops by:

Red light - OFF Green light - ON Amber light - OFF Align CS Pump B for recirculation:

a. Open CS Pump B suction valves from Containment Emergency Sump:

HV-9002B, CNMT SPRAY PUMP B CNMT SUMP SUCT IRC HV-9003B, CNMT SPRAY PUMP B CNMT SUMP SUCT ORC Opens HV-9002B Red light - ON Green light - OFF Opens HV-9003B Red light - ON Green lights - OFF 4

  • Step # 19
b. Close CNMT SPRAY PUMP A RWST SUCT ISO VLV:

Standard:

Comment:

Step # 19 HV-9017B Closes HV-9017B Green light - ON Red light - OFF

c. Check Train B CS proper operation using the following indications, if available:

Pump suction pressure, PI-0973 greater than 7 psig.

Pump discharge pressure, PI-0975 approximately 185 psig above suction pressure.

Containment pressure stable or lowering.

CUE: "Containment Spray pump B suction pressure is 18 psig" CUE: "Containment Spray pump B discharge pressure is 204 psig" Standard:

Comment:

Step # 20 Determines suction and discharge pressures are adequate.

Determines from IPC computer point that CNMT pressure is lowering.

Note: Candidate may also use control board meters for CNMT pressure.

Initiate RWST makeup using 13701, BORIC ACID SYSTEM CUE: "Another operator will complete this task" Standard:

Comment:

5

  • Step # 19
b. Close CNMT SPRAY PUMP A RWST SUCT ISO VLV:

Standard:

Comment:

Step # 19 HV-9017B Closes HV-9017B Green light - ON Red light - OFF

c. Check Train B CS proper operation using the following indications, if available:

Pump suction pressure, PI-0973 greater than 7 psig.

Pump discharge pressure, PI-0975 approximately 185 psig above suction pressure.

Containment pressure stable or lowering.

CUE: "Containment Spray pump B suction pressure is 18 psig" CUE: "Containment Spray pump B discharge pressure is 204 psig" Standard:

Comment:

Step # 20 Determines suction and discharge pressures are adequate.

Determines from IPC computer point that CNMT pressure is lowering.

Note: Candidate may also use control board meters for CNMT pressure.

Initiate RWST makeup using 13701, BORIC ACID SYSTEM CUE: "Another operator will complete this task" Standard:

Comment:

5

Terminating cue:

Student returns initiating cue sheet 6

Terminating cue:

Student returns initiating cue sheet 6

Verification of Completion Job Performance Measure No. V-LO-JP-19013-005 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: -------------------------------------------------------------

Response: __________________________________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date: ________________________ ___

7 Verification of Completion Job Performance Measure No. V-LO-JP-19013-005 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: _____________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date:

7

Initial Conditions:

A large break LOCA has occurred. The crew performed the cold leg recirculation lineup using 19013, and returned to 19010. After transitioning to 19010, RWST level decreased below 8%. The Auxiliary Building Operator is standing by the local Containment Spray suction and discharge pressure gauges.

Initiating Cue:

The 55 has directed you to "Align Containment Spray for recirculation beginning with step 11 of 19013".

8 Initial Conditions:

A large break LOCA has occurred. The crew performed the cold leg recirculation lineup using 19013, and returned to 19010. After transitioning to 19010, RWST level decreased below 8%. The Auxiliary Building Operator is standing by the local Containment Spray suction and discharge pressure gauges.

Initiating Cue:

The 55 has directed you to "Align Containment Spray for recirculation beginning with step 11 of 19013".

8

Job Performance Measure "F" Facility: Vogtle Task No: V-LO-TA-11014 Task

Title:

Parallel DG with Voltage Regulator Failure JPM No: V-NRC-JP-13427 -002 KJA

Reference:

062A 1.01 Examinee: __________ _

NRC Examiner:

Facility Evaluator: ________ _

Date: -----------------------

Method of testing:

Simulated Performance --------

Actual Performance _________ _

Classroom ______ _

Simulator -------

Plant ------

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

Following a 7 day DIG 1B outage, Maintenance and Engineering Support are standing by for a DIG 1 B test run. DIG 1 B was just started, and is now operating unloaded with the DIG output breaker open. You are relieving the UO, and will be performing the remainder of this test run. The outside area SO is stationed at the DIG to support the evolution.

Task Standard:

DG-1B paralleled to bus 1BA03 using 13427B-1, and DG-1B output breaker opened when KVAR load goes negative.

Required Materials:

13427B-1, 4160V AC BUS 1 BA03 1 E ELECTRICAL DISTRIBUTION SYSTEM Instructions:

Students should be pre-briefed to save simulator time for this JPM.

Initiating Cue:

The applicable portions of 13145-1 have been completed for starting DG-1B. In accordance with procedure 13427B-1, parallel DIG 1B to 1 BA03 and raise DG-1 B load to 7000 kw per Section 4.2.1., starting with step 4.2.1.3.

Time Critical Task:

No 1

Job Performance Measure "F" Facility: Vogtle Task No: V-LO-TA-11014 Task

Title:

Parallel DG with Voltage Regulator Failure JPM No: V-NRC-JP-13427 -002 KJA

Reference:

062A 1.01 Examinee:

NRC Examiner: -----------------

Facility Evaluator:

Date: ____________________ __

Method of testing:

Simulated Performance ______ _

Actual Performance --------------

Classroom ----------

Simulator --------

Plant ________ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

Following a 7 day DIG 1B outage, Maintenance and Engineering Support are standing by for a DIG 1 B test run. DIG 1 B was just started, and is now operating unloaded with the DIG output breaker open. You are relieving the UO, and will be performing the remainder of this test run. The outside area SO is stationed at the DIG to support the evolution.

Task Standard:

DG-1B paralleled to bus 1BA03 using 13427B-1, and DG-1B output breaker opened when KVAR load goes negative.

Required Materials:

13427B-1, 4160V AC BUS 1 BA03 1 E ELECTRICAL DISTRIBUTION SYSTEM Instructions:

Students should be pre-briefed to save simulator time for this JPM.

Initiating Cue:

The applicable portions of 13145-1 have been completed for starting DG-1B. In accordance with procedure 13427B-1, parallel DIG 1B to 1 BA03 and raise DG-1 B load to 7000 kw per Section 4.2.1., starting with step 4.2.1.3.

Time Critical Task:

No 1

Validation Time:

10 minutes SIMULATOR SETUP:

1.

Reset to IC # 94 for HL -15 NRC Exam Simulator Setup from Scratch:

1.

Reset to IC 14 (100% MOL)

2.

Start DIG 1 B allow it to run unloaded until all annunicators are clear

3.

Set Trigger 1 with the following overrides:

DG 1B Voltage Decrease push button-ON DG 1 B Voltage increase light - OFF DG 1 B Voltage decrease light - OFF

4.

Acknowledge alarms and freeze simulation Setup time: 5 minutes 2

Validation Time:

10 minutes SIMULATOR SETUP:

1.

Reset to IC # 94 for HL -15 NRC Exam Simulator Setup from Scratch:

1.

Reset to IC 14 (100% MOL)

2.

Start DIG 1 B allow it to run unloaded until all annunicators are clear

3.

Set Trigger 1 with the following overrides:

DG 1B Voltage Decrease push button-ON DG 1 B Voltage increase light - OFF DG 1 B Voltage decrease light - OFF

4.

Acknowledge alarms and freeze simulation Setup time: 5 minutes 2

Performance Information Critical steps denoted with an asterisk Student review precautions and limitations section of 13427B-1.

4.2.1.3 Standard:

Comment:

Verify DG1B SYNC MODE SELECTOR Switch 1TS-DG1B in AUTO.

1TS-DG1B in AUTO Reviews CAUTION about synchronizing switches 4.2.1.4 Standard:

Comment:

  • 4.2.1.5 Standard:

Comment:

Verify Breaker 1 BA0305 and1 BA0301 Synchronizing Switches are OFF:

1 BA0305 SYNCHRONIZING SWITCH 1 BA0301 SYNCHRONIZING SWITCH 1 BA0305 SYNCHRONIZING SWITCH 1 BA0301 SYNCHRONIZING SWITCH OFF OFF OFF OFF Place the BRKR 1BA0319 SYNCHRONIZING SWITCH to ON.

1BA0319 SYNCHRONIZING SWITCH - ON.

Synchroscope starts rotating 3

Performance Information Critical steps denoted with an asterisk Student review precautions and limitations section of 13427B-1.

4.2.1.3 Standard:

Comment:

Verify DG1B SYNC MODE SELECTOR Switch 1TS-DG1B in AUTO.

1TS-DG1B in AUTO Reviews CAUTION about synchronizing switches 4.2.1.4 Standard:

Comment:

  • 4.2.1.5 Standard:

Comment:

Verify Breaker 1 BA0305 and1 BA0301 Synchronizing Switches are OFF:

1 BA0305 SYNCHRONIZING SWITCH 1 BA0301 SYNCHRONIZING SWITCH 1 BA0305 SYNCHRONIZING SWITCH 1 BA0301 SYNCHRONIZING SWITCH OFF OFF OFF OFF Place the BRKR 1BA0319 SYNCHRONIZING SWITCH to ON.

1BA0319 SYNCHRONIZING SWITCH - ON.

Synchroscope starts rotating 3

  • 4.2.1.6 Standard:

Comment:

4.2.1.7 Standard:

Comment:

4.2.1.8 Standard:

Comment:

Momentarily place DSL GEN 18 UNIT/PARALLEL switch 1 HS*44528 to PARALLEL and check blue DSL GEN 18 UNIT MODE/FAST START light NOT lit.

Blue light - OFF Set DSL GEN 1 B LOADING SET PT CONTROL 1 SE-4916 to 1.00.

1SE-4916 set at 1.00.

Select the highest 1 BA03 4160V Bus phase voltage on the QEAB Voltmeter by moving the BUS 1 BA03 Normal Incoming Voltmeter Switch through all positions.

Highest reading 1 BA03 bus voltage selected Reviews CAUTION on bus voltage limits.

4.2.1.9 Standard:

Comment:

Check 1 BA03 4160V Bus voltage between 4025V and 4250V.

a.

IF NOT, coordinate with PCC to establish 1BA03 4160V Bus voltage between 4025V and 4250V.

1 BA03 4160V Bus voltage between 4025V and 4250V.

4

  • 4.2.1.6 Standard:

Comment:

4.2.1.7 Standard:

Comment:

4.2.1.8 Standard:

Comment:

Momentarily place DSL GEN 18 UNIT/PARALLEL switch 1 HS*44528 to PARALLEL and check blue DSL GEN 18 UNIT MODE/FAST START light NOT lit.

Blue light - OFF Set DSL GEN 1 B LOADING SET PT CONTROL 1 SE-4916 to 1.00.

1SE-4916 set at 1.00.

Select the highest 1 BA03 4160V Bus phase voltage on the QEAB Voltmeter by moving the BUS 1 BA03 Normal Incoming Voltmeter Switch through all positions.

Highest reading 1 BA03 bus voltage selected Reviews CAUTION on bus voltage limits.

4.2.1.9 Standard:

Comment:

Check 1 BA03 4160V Bus voltage between 4025V and 4250V.

a.

IF NOT, coordinate with PCC to establish 1BA03 4160V Bus voltage between 4025V and 4250V.

1 BA03 4160V Bus voltage between 4025V and 4250V.

4

4.2.1.10 Standard:

Comment:

Select the lowest OG 1 B voltage on the QEAB Voltmeter by moving the OG 1 B Voltmeter Switch through all positions.

Lowest OG-1 B voltage selected on voltmeter 5

4.2.1.10 Standard:

Comment:

Select the lowest OG 1 B voltage on the QEAB Voltmeter by moving the OG 1 B Voltmeter Switch through all positions.

Lowest OG-1 B voltage selected on voltmeter 5

NOTES It may be necessary to adjust DG speed slightly in order to verify the next step.

  • Synchronizing lights are bright at the 6 o'clock position. Synchronizing lights are dark at the 12 o'clock position. The red AUTO SYNC PERMISSIVE light is lit near the 12 o'clock position.

4.2.1.11 Check Sync Scope Meter is rotating.

Standard:

Sync Scope Meter - rotating Comment:

NOTE The following step adjusts DG voltage to slightly higher than bus voltage to ensure the DG kVAR loading will be positive. The DG voltage should be approximately 50 volts higher than the bus voltage.

4.2.1.12 Adjust DG voltage to slightly above the bus voltage.

Standard:

DG-1 B voltage - 50 V > 1 BA03 bus voltage Comment:

NOTE The following step adjusts DG frequency slightly higher than bus frequency to ensure the DG will start loading when the breaker is closed. The speed of rotation of the sync scope needle should be slow (at least 10 seconds per revolution).

4.2.1.13 Standard:

Comment:

Adjust the DG speed until the Sync Scope needle is rotating slowly in the clockwise (Fast) direction.

Sync Scope needle is rotating in the clockwise (Fast) direction with at least a 10 second period.

6 NOTES It may be necessary to adjust DG speed slightly in order to verify the next step.

  • Synchronizing lights are bright at the 6 o'clock position. Synchronizing lights are dark at the 12 o'clock position. The red AUTO SYNC PERMISSIVE light is lit near the 12 o'clock position.

4.2.1.11 Check Sync Scope Meter is rotating.

Standard:

Sync Scope Meter - rotating Comment:

NOTE The following step adjusts DG voltage to slightly higher than bus voltage to ensure the DG kVAR loading will be positive. The DG voltage should be approximately 50 volts higher than the bus voltage.

4.2.1.12 Adjust DG voltage to slightly above the bus voltage.

Standard:

DG-1 B voltage - 50 V > 1 BA03 bus voltage Comment:

NOTE The following step adjusts DG frequency slightly higher than bus frequency to ensure the DG will start loading when the breaker is closed. The speed of rotation of the sync scope needle should be slow (at least 10 seconds per revolution).

4.2.1.13 Standard:

Comment:

Adjust the DG speed until the Sync Scope needle is rotating slowly in the clockwise (Fast) direction.

Sync Scope needle is rotating in the clockwise (Fast) direction with at least a 10 second period.

6

CAUTION As soon as the DG Output breaker closes, kVAR must be controlled in the acceptable range specified in Figure 1, "Emergency Diesel Generator Operating Limits."

  • 4.2.1.14 WHEN Sync Scope needle reaches the 11 o'clock position, depress and hold the DG 1B AUTO SYNC PERMISSIVE pushbutton PB-DG1B.

NOTE:

Concurrent Verification should be requested for this step NOTE:

Insert TRIGGER 1 as soon as DG output breaker is closed.

Standard:

PB-DG1 B depressed when synch scope needle is at 11 o'clock Comment:

GENERATOR FREOUENCY WOOEL NO.

87~O KVA. 4160V 1214.4A 60 HZ 0.8 PF 60HZ 72 12500 100 10.000 LEADING KVAR LAGGING KVAR EMERGENCY DIESEL GENERATOR OPERATING LIMITS 7

9000 8000 7700 7000 6000 KILOWATTS 5000 4000 3000 2000 1750 1000 gO

~

CAUTION As soon as the OG Output breaker closes, kVAR must be controlled in the acceptable range specified in Figure 1, ~ Emergency Diesel Generator Operating Limits."

  • 4.2.1.14 WHEN Sync Scope needle reaches the 11 o'clock position, depress and hold the OG 1B AUTO SYNC PERMISSIVE pushbutton PB*OG1B.

NOTE:

Concurrent Verification should be requested for this step NOTE:

Insert TRIGGER 1 as soon as DG output breaker is closed.

Standard:

PB-DG1 B depressed when synch scope needle is at 11 o'dock Comment FREQUENCV WOD£l ND.

8 7!'>O KV... ~\\60Y 12 1 * * ~A 60 HZ 0.3 PF 72 I 2:'00 I CO 10.000 LEADING KVAR L ACG ING KVAR EMERGENCY DIESEL GENERATOR OPERATING LIM ITS 7

.~

.000 7700 6000 IC I LIJ'IIIATTS

.,00

.000 3000 700

,~

4.2.1.15 Standard:

Comment:

4.2.1.16 Standard:

Comment:

4.2.1.17 Standard:

Comment:

Check DG 1 B OUTPUT BRKR 1 BA03-19 closes WHEN Sync Scope needle reaches 12 o'clock position, THEN release Auto Sync Permissive pushbutton.

a.

IF Sync Scope needle passes the 12 o'clock position, release Auto Sync Permissive pushbutton.

1BA03-19:

Red light -

ON Green light - OFF Amber light - OFF Verify that DG loads to at least 700kW.

DG-1B load @ 700 KW Adjust DG voltage to obtain kVAR loading between 200 and 300 kVAR positive (Out).

  • a.

IF kVAR loading goes negative (In) and NO adjustment can be made With the voltage control to restore kVAR load positive (Out). trip DG Breaker 1BA0319.

When recognizes KVAR loads negative attempts to raise by depressing raise DG voltage push button. Opens breaker 1 BA0319 when KVAR load does not respond.

1 BA0319 opened:

Green light - ON Red light -

OFF Amber light - OFF 8

4.2.1.15 Standard:

Comment:

4.2.1.16 Standard:

Comment:

4.2.1.17 Standard:

Comment:

Check DG 1 B OUTPUT BRKR 1 BA03-19 closes WHEN Sync Scope needle reaches 12 o'clock position, THEN release Auto Sync Permissive pushbutton.

a.

IF Sync Scope needle passes the 12 o'clock position, release Auto Sync Permissive pushbutton.

1BA03-19:

Red light -

ON Green light - OFF Amber light - OFF Verify that DG loads to at least 700kW.

DG-1B load @ 700 KW Adjust DG voltage to obtain kVAR loading between 200 and 300 kVAR positive (Out).

  • a.

IF kVAR loading goes negative (In) and NO adjustment can be made With the voltage control to restore kVAR load positive (Out). trip DG Breaker 1BA0319.

When recognizes KVAR loads negative attempts to raise by depressing raise DG voltage push button. Opens breaker 1 BA0319 when KVAR load does not respond.

1 BA0319 opened:

Green light - ON Red light -

OFF Amber light - OFF 8

4.2.1.18 Place BRKR 1BA0319 SYNCHRONIZING SWITCH to OFF.

Standard:

1BA0319 SYNCHRONIZING SWITCH - OFF.

Comment:

Reports to the SS that OG-1 B was paralleled to 1 BA03 and that the output breaker was opened due to uncontrolled negative KVARs.

Standard:

N/A Comment:

Terminating cue:

Student returns initiating cue sheet 9

4.2.1.18 Place BRKR 1BA0319 SYNCHRONIZING SWITCH to OFF.

Standard:

1BA0319 SYNCHRONIZING SWITCH - OFF.

Comment:

Reports to the SS that OG-1 B was paralleled to 1 BA03 and that the output breaker was opened due to uncontrolled negative KVARs.

Standard:

N/A Comment:

Terminating cue:

Student returns initiating cue sheet 9

Verification of Completion Job Performance Measure No. V-NRC-JP-13427 -002 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: __________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date:

10 Verification of Completion Job Performance Measure No. V-NRC-JP-13427 -002 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: -------------------------------------------------------------

Response: __________________________________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date:

10

Initial Conditions:

Following a 7 day DIG 18 outage, Maintenance and Engineering Support are standing by for a DIG 18 test run. DIG 18 was just started, and is now operating unloaded with the DIG output breaker open. You are relieving the UO, and will be performing the remainder of this test run. The outside area SO is stationed at the DIG to support the evolution.

Initiating Cue:

The applicable portions of 13145*1 have been completed for starting DG*18. In accordance with procedure 134278*1, parallel DIG 18 to 18A03 and raise DG*18 load to 7000 kw per Section 4.2.1., starting with step 4.2.1.3.

11 Initial Conditions:

Following a 7 day DIG 18 outage, Maintenance and Engineering Support are standing by for a DIG 18 test run. DIG 18 was just started, and is now operating unloaded with the DIG output breaker open. You are relieving the UO, and will be performing the remainder of this test run. The outside area SO is stationed at the DIG to support the evolution.

Initiating Cue:

The applicable portions of 13145*1 have been completed for starting DG*18. In accordance with procedure 134278*1, parallel DIG 18 to 18A03 and raise DG*18 load to 7000 kw per Section 4.2.1., starting with step 4.2.1.3.

11

Job Performance Measure "G" Facility: Vogtle Task No: V-LO-TA-23005 Task

Title:

Manually Align for CRI on High Radiation JPM No: V-RQ-JP-13301-003 KIA

Reference:

071A3.01 Examinee: ___________ _

NRC Examiner:

Facility Evaluator: ________ _

Date: ______________ __

Method of testing:

Simulated Performance ______ _

Actual Performance _________ _

Classroom _____ _

Simulator _____ _

Plant _____ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

You are the Unit Operator.

Task Standard:

Identify failure of CRI to auto actuate and manually align CR HVAC for CRI in accordance with 13301, section 4.4.1.

Required Materials:

13301, CBCR Normal HVAC and Emergency Filtration System 17102, Annunciator Response for the Safety Related Display Console General

References:

None Initiating Cue:

The 55 has directed you to "Monitor the Control Room and respond to plant conditions".

Time Critical Task:

No Validation Time:

1 0 minutes 1

Job Performance Measure "G" Facility: Vogtle Task No: V-LO-TA-23005 Task

Title:

Manually Align for CRI on High Radiation JPM No: V-RQ-JP-13301-003 KIA

Reference:

071A3.01 Examinee: ---------------------

NRC Examiner: _____________ _

Facility Evaluator: _________ _

Date: __________________ __

Method of testing:

Simulated Performance -------

Actual Performance ________ _

Classroom _____ _

Simulator ______ _

Plant ------

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

You are the Unit Operator.

Task Standard:

Identify failure of CRI to auto actuate and manually align CR HVAC for CRI in accordance with 13301, section 4.4.1.

Required Materials:

13301, CBCR Normal HVAC and Emergency Filtration System 17102, Annunciator Response for the Safety Related Display Console General

References:

None Initiating Cue:

The 55 has directed you to "Monitor the Control Room and respond to plant conditions".

Time Critical Task:

No Validation Time:

1 0 minutes 1

SIMULATOR SETUP:

Snapped to IC # 96 for HL-15 NRC Exam.

If new setup is required, then perform the following:

1.

Reset to IC 14 (MOL 100%).

2.

Insert Malfunction ES04A (Failure of Train A CRI)

3.

Insert Malfunction ES048 (Failure of Train B CRI)

4.

Insert malfunctions for High Rad on RE-12116 and RE-12117 on Trigger 1

5.

Override BOTH SSMP TROUBLE alarms to OFF

6.

Acknowledge/Reset alarms.

7.

Freeze simulator Setup time: 3 minutes 2

SIMULATOR SETUP:

Snapped to IC # 96 for HL-15 NRC Exam.

If new setup is required, then perform the following:

1.

Reset to IC 14 (MOL 100%).

2.

Insert Malfunction ES04A (Failure of Train A CRI)

3.

Insert Malfunction ES048 (Failure of Train B CRI)

4.

Insert malfunctions for High Rad on RE-12116 and RE-12117 on Trigger 1

5.

Override BOTH SSMP TROUBLE alarms to OFF

6.

Acknowledge/Reset alarms.

7.

Freeze simulator Setup time: 3 minutes 2

Performance Information Critical steps denoted with an asterisk Annunciator Response 17005 Window C03 for High Radiation (IF referenced)

Annunciator response procedure should direct candidate to ARP 17102 for the Safety Related Display Console (SRDC)

Standard:

Comment:

References ARP-17102 (NOTE: The candidate may go directly to 17102 without referencing ARP-17005).

The candidate may also reference the IPC computer RAD button to determine which radiation monitors are in alarm or may look at the SRDC.

Annunciator Response 17102 for Safety Related Display Console References ARP-17102 for RE-12116 and RE-12117 High Radiation AUTOMATIC ACTIONS.

Standard:

Comment:

Step 1 Standard:

Comment:

Determines Control Room and Technical Support Center ventilation should have automatically swapped to the Post Accident Mode.

SUBSEQUENT ACTIONS: Verify Control Room HVAC in the Recirculation Mode Determines Control Room HVAC NOT in the Recirculation Mode Observes green lights lit on 1-HS-12195A and 1-HS-12196A (yellow switches).

Attempts CRI actuation by placing both 1-HS-12195A and 1-HS-12196A to the ACTUATE position. (Rotates clockwise to actuate)

NOTE: It would be acceptable for candidate to reference procedure 13301 prior to attempting this actuation. There is no ARP direction to reference this procedure. This would be up to the candidate to determine the correct procedure.

3 Performance Information Critical steps denoted with an asterisk Annunciator Response 17005 Window C03 for High Radiation (IF referenced)

Annunciator response procedure should direct candidate to ARP 17102 for the Safety Related Display Console (SRDC)

Standard:

Comment:

References ARP-17102 (NOTE: The candidate may go directly to 17102 without referencing ARP-17005).

The candidate may also reference the IPC computer RAD button to determine which radiation monitors are in alarm or may look at the SRDC.

Annunciator Response 17102 for Safety Related Display Console References ARP-17102 for RE-12116 and RE-12117 High Radiation AUTOMATIC ACTIONS.

Standard:

Comment:

Step 1 Standard:

Comment:

Determines Control Room and Technical Support Center ventilation should have automatically swapped to the Post Accident Mode.

SUBSEQUENT ACTIONS: Verify Control Room HVAC in the Recirculation Mode Determines Control Room HVAC NOT in the Recirculation Mode Observes green lights lit on 1-HS-12195A and 1-HS-12196A (yellow switches).

Attempts CRI actuation by placing both 1-HS-12195A and 1-HS-12196A to the ACTUATE position. (Rotates clockwise to actuate)

NOTE: It would be acceptable for candidate to reference procedure 13301 prior to attempting this actuation. There is no ARP direction to reference this procedure. This would be up to the candidate to determine the correct procedure.

3

Refers to procedure 13301 and determines section 4.4.1 should be performed.

Standard:

Comment:

4.4.1.1 Standard:

Comment:

  • 4.4.1.2 Standard:

Comment:

Section 4.4.1 used.

To manually initiate Control Room Isolation, place either CR ISO MANUAL ACTUATION Switch in ACTUATE:

TRAINA TRAIN B 1-HS-12195A [A4]

1-HS-12196A [A6]

Rotates both hand switches clockwise to the ACTUATE position and determines that the actuation did NOT occur.

Green lights - ON Red lights - OFF Verify that TRAIN B CR FLTR UNIT LEAD SUPPLY AIR FAN starts.

TRAIN B 1-1531-N7-002 [B10]

Starts Train B filter unit by rotating hand switch clockwise to the start position.

Red light - ON Green light - OFF Amber light - OFF 4

Refers to procedure 13301 and determines section 4.4.1 should be performed.

Standard:

Comment:

4.4.1.1 Standard:

Comment:

  • 4.4.1.2 Standard:

Comment:

Section 4.4.1 used.

To manually initiate Control Room Isolation, place either CR ISO MANUAL ACTUATION Switch in ACTUATE:

TRAINA TRAIN B 1-HS-12195A [A4]

1-HS-12196A [A6]

Rotates both hand switches clockwise to the ACTUATE position and determines that the actuation did NOT occur.

Green lights - ON Red lights - OFF Verify that TRAIN B CR FLTR UNIT LEAD SUPPLY AIR FAN starts.

TRAIN B 1-1531-N7-002 [B10]

Starts Train B filter unit by rotating hand switch clockwise to the start position.

Red light - ON Green light - OFF Amber light - OFF 4

4.4.1.3 Standard:

Comment:

  • 4.4.1.4 Standard:

Comment:

Verify that TRAIN A CR FL TR UNIT STANDBY SUPPLY AIR FAN does NOT start:

TRAIN A 1-1531-N7-001 [B8]

Checks green light remains - ON Red light remains - OFF Amber light remains - OFF Verify that both KIT TOIL + CONF RM EXH ISO OMPRs close:

TRAIN A TRAIN B A-HV-12162 [06]

A-HV-12163 [07]

Rotates both hand switches counter clockwise to the CLOSED position.

Green lights - ON Red lights - OFF 5

4.4.1.3 Standard:

Comment:

  • 4.4.1.4 Standard:

Comment:

Verify that TRAIN A CR FL TR UNIT STANDBY SUPPLY AIR FAN does NOT start:

TRAIN A 1-1531-N7-001 [B8]

Checks green light remains - ON Red light remains - OFF Amber light remains - OFF Verify that both KIT TOIL + CONF RM EXH ISO OMPRs close:

TRAIN A TRAIN B A-HV-12162 [06]

A-HV-12163 [07]

Rotates both hand switches counter clockwise to the CLOSED position.

Green lights - ON Red lights - OFF 5

  • 4.4.1.5 Standard:

Comment:

  • 4.4.1.6 Standard:

Comment:

Verify that both CR NORM AIR SUPPLY ISO DMPRs close:

TRAIN A TRAIN B 1*HV*12146 [C6]

1-HV-12147 [e7]

Rotates hand switch for HV-12146 counter clockwise to the CLOSE position.

HV-12146 Green light - ON Red light - OFF.

Observes HS-12147 already closed by:

Green light - ON Red light - OFF.

Verify that both CR NORM AIR RTN ISO DMPRs close:

TRAIN A TRAIN B 1*HV*12149 [E6]

1-HV-1214B [E7]

Rotates hand switch for HV-12149 counter clockwise to the CLOSE position.

HV-12149 Green light - ON Red light - OFF.

Observes HV-12148 already closed by:

Green light - ON Red light - OFF.

6

  • 4.4.1.5 Standard:

Comment:

  • 4.4.1.6 Standard:

Comment:

Verify that both CR NORM AIR SUPPLY ISO DMPRs close:

TRAIN A TRAIN B 1*HV*12146 [C6]

1-HV-12147 [e7]

Rotates hand switch for HV-12146 counter clockwise to the CLOSE position.

HV-12146 Green light - ON Red light - OFF.

Observes HS-12147 already closed by:

Green light - ON Red light - OFF.

Verify that both CR NORM AIR RTN ISO DMPRs close:

TRAIN A TRAIN B 1*HV*12149 [E6]

1-HV-1214B [E7]

Rotates hand switch for HV-12149 counter clockwise to the CLOSE position.

HV-12149 Green light - ON Red light - OFF.

Observes HV-12148 already closed by:

Green light - ON Red light - OFF.

6

4.4.1.7 Standard:

Comment:

4.4.1.8 Standard:

Comment:

4.4.1.9 Standard:

Comment:

Verify that the CR FILTER UNIT OUTLET AIR OMPR on the running train is open:

TRAIN 8 1-HV-12129 [C11]

Red light - ON Green light - OFF.

Verify that the CR RTN FAN INLET AIR OMPR on the running train is open:

TRAIN 8 1-HV-12131 [010]

Red light-ON Green light - OFF.

Verify that the CR NORMAL HVAC UNIT INTAKE ISO DMPR on the running train is closed:

TRAIN 8 A-HV-12152 [87]

Green light - ON Red light - OFF.

7 4.4.1.7 Standard:

Comment:

4.4.1.8 Standard:

Comment:

4.4.1.9 Standard:

Comment:

Verify that the CR FILTER UNIT OUTLET AIR OMPR on the running train is open:

TRAIN 8 1-HV-12129 [C11]

Red light - ON Green light - OFF.

Verify that the CR RTN FAN INLET AIR OMPR on the running train is open:

TRAIN 8 1-HV-12131 [010]

Red light-ON Green light - OFF.

Verify that the CR NORMAL HVAC UNIT INTAKE ISO DMPR on the running train is closed:

TRAIN 8 A-HV-12152 [87]

Green light - ON Red light - OFF.

7

4.4.1.10 Standard:

Comment:

4.4.1.11 Standard:

Comment:

4.4.1.12 CUE:

Standard:

Comment:

Verify that the CR NORM AC UNIT SUPPLY FANS, A-1531-A7-001 [C4]

and A-1531-A7-002 [C5], shut down.

Both AC units Green lights - ON Amber lights - ON Red lights - OFF Verify that the CR NORM AC UNIT EXH FAN, A-1531-B7-009 [D4] and A-1531-B7-010 [D5], shut down.

Both exhaust units Green lights - ON Red lights - OFF Verify that the KITCH TOILET AND CONF RM EXH FAN, A-HS-12164 in the Shift M'S Office, stops.

The Control Building Operator reports A-HS-12164's green light is lit and the fan has stopped.

Determines Kitchen Toilet and Conference room exhaust fan is stopped.

8 4.4.1.10 Standard:

Comment:

4.4.1.11 Standard:

Comment:

4.4.1.12 CUE:

Standard:

Comment:

Verify that the CR NORM AC UNIT SUPPLY FANS, A-1531-A7-001 [C4]

and A-1531-A7-002 [C5], shut down.

Both AC units Green lights - ON Amber lights - ON Red lights - OFF Verify that the CR NORM AC UNIT EXH FAN, A-1531-B7-009 [D4] and A-1531-B7-010 [D5], shut down.

Both exhaust units Green lights - ON Red lights - OFF Verify that the KITCH TOILET AND CONF RM EXH FAN, A-HS-12164 in the Shift M'S Office, stops.

The Control Building Operator reports A-HS-12164's green light is lit and the fan has stopped.

Determines Kitchen Toilet and Conference room exhaust fan is stopped.

8

Reviews NOTE prior to step 4.4.1.13 regarding isolation of outside air dampers.

4.4.1.13 Standard:

Comment:

4.4.1.14 CUE:

Standard:

Comment:

4.4.1.15 CUE:

Standard:

Comment:

IF Control Room outside air is restricted for Control Room habitability due to smoke or toxic gas intake, THEN close the CR OUTSIDE AIR SUPPLY DAMPERS for BOTH Units:

UNIT 1 1-HS-12114 [EB]

1-HS-12115 [E10]

Determines this step Not Applicable.

UNIT2 2-HS-12114 2-HS-12115 Verify proper operation of the TSC Air Filtration System per 13303-C, "Technical Support Center And Central Alarm Station HVAC Systems."

Another operator will verify proper operation of the TSC Air Filtration System.

Not applicable.

Verify proper Essential Chiller operation.

Another operator will verify proper operation of the ESF Chiller.

Terminating cue:

Student returns initiating cue sheet 9

Reviews NOTE prior to step 4.4.1.13 regarding isolation of outside air dampers.

4.4.1.13 Standard:

Comment:

4.4.1.14 CUE:

Standard:

Comment:

4.4.1.15 CUE:

Standard:

Comment:

IF Control Room outside air is restricted for Control Room habitability due to smoke or toxic gas intake, THEN close the CR OUTSIDE AIR SUPPLY DAMPERS for BOTH Units:

UNIT 1 1-HS-12114 [EB]

1-HS-12115 [E10]

Determines this step Not Applicable.

UNIT2 2-HS-12114 2-HS-12115 Verify proper operation of the TSC Air Filtration System per 13303-C, "Technical Support Center And Central Alarm Station HVAC Systems."

Another operator will verify proper operation of the TSC Air Filtration System.

Not applicable.

Verify proper Essential Chiller operation.

Another operator will verify proper operation of the ESF Chiller.

Terminating cue:

Student returns initiating cue sheet 9

Verification of Completion Job Performance Measure No. V-RQ-JP-13301-003 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: ________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date:

10 Verification of Completion Job Performance Measure No. V-RQ-JP-13301-003 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: _____________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date: _____________ _

10

Initial Conditions:

You are the Unit Operator.

Initiating Cue:

The 55 has directed you to "Monitor the Control Room and respond to plant conditions".

11 Initial Conditions:

You are the Unit Operator.

Initiating Cue:

The 55 has directed you to "Monitor the Control Room and respond to plant conditions".

11

Job Performance Measure "H" Facility: Vogtle Task No: V-LO-TA-29006 Task

Title:

Place Containment Main Purge in Service JPM No: V-LO-JP-13125-002 KIA

Reference:

029A2.03 Examinee: ___________ _

NRC Examiner: _________ _

Facility Evaluator:

Date:

Method of testing:

Simulated Performance Actual Performance Classroom ______ _

Simulator _________ _

Plant _______ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

The Plant is in Mode 5 with the Containment Equipment Hatch Open.

Task Standard:

Student shuts down the mini-purge exhaust system and then starts the main purge exhaust system per 13125-1.

Required Materials:

13125-1, Containment Main Purge System General

References:

None Initiating Cue:

The 55 has authorized Gaseous Release Permits and has directed you to "Place Containment Main (Preaccess) Purge in service" using procedure 13125-1.

"Checklist 1 for Main Purge isolation dampers and valves has been performed".

Time Critical Task:

No Validation Time:

20 minutes 1

Job Performance Measure "H" Facility: Vogtle Task No: V-LO-TA-29006 Task

Title:

Place Containment Main Purge in Service JPM No: V-LO-JP-13125-002 KIA

Reference:

029A2.03 Examinee: ___________ _

NRC Examiner: ------------------

Facility Evaluator:

Date:

Method of testing:

Simulated Performance Actual Performance Classroom Simulator Plant Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

The Plant is in Mode 5 with the Containment Equipment Hatch Open.

Task Standard:

Student shuts down the mini-purge exhaust system and then starts the main purge exhaust system per 13125-1.

Required Materials:

13125-1, Containment Main Purge System General

References:

None Initiating Cue:

The 55 has authorized Gaseous Release Permits and has directed you to "Place Containment Main (Preaccess) Purge in service" using procedure 13125-1.

"Checklist 1 for Main Purge isolation dampers and valves has been performed".

Time Critical Task:

No Validation Time:

20 minutes 1

SIMULATOR SETUP:

Snapped IC is 93. If new setup is required, then perform the following:

1.

Reset to mode 5 mid loop IC

2.

Place Mini-Purge supply fan in service per 13125 and ensure Containment Pressure is atmospheric.

3.

Verify Power to the Containment Main Purge dampers is on

4.

Acknowledge / Reset alarms

5.

Freeze simulator Setup time: 10 minutes 2

SIMULATOR SETUP:

Snapped IC is 93. If new setup is required, then perform the following:

1.

Reset to mode 5 mid loop IC

2.

Place Mini-Purge supply fan in service per 13125 and ensure Containment Pressure is atmospheric.

3.

Verify Power to the Containment Main Purge dampers is on

4.

Acknowledge / Reset alarms

5.

Freeze simulator Setup time: 10 minutes 2

Performance Information Critical steps denoted with an asterisk Student refers to SOP 13125-1 and determines section 4.1.2 should be performed.

Standard:

Section 4.1.2 used Comment:

Student reviews precautions and limitations of 13125-1 Student reviews notes and cautions at the beginning of section 4.1.2 Standard:

N/A Comment:

4.1.2.1 Standard:

Comment:

4.1.2.2 Standard:

Comment:

IF the unit is in MODE 5, 6 OR defueled, AND the Containment Equipment Hatch is open, operate the Containment Main Purge System with the Exhaust Fan on, and Supply Fan off to verify airflow is maintained into the building.

Student determines this step IS applicable from initial conditions.

Perform Checklist 1 as required, to restore power to the Main Purge Isolation dampers and fans.

Determines checklist 1 has been completed from initial conditions.

3 Performance Information Critical steps denoted with an asterisk Student refers to SOP 13125-1 and determines section 4.1.2 should be performed.

Standard:

Section 4.1.2 used Comment:

Student reviews precautions and limitations of 13125-1 Student reviews notes and cautions at the beginning of section 4.1.2 Standard:

N/A Comment:

4.1.2.1 Standard:

Comment:

4.1.2.2 Standard:

Comment:

IF the unit is in MODE 5, 6 OR defueled, AND the Containment Equipment Hatch is open, operate the Containment Main Purge System with the Exhaust Fan on, and Supply Fan off to verify airflow is maintained into the building.

Student determines this step IS applicable from initial conditions.

Perform Checklist 1 as required, to restore power to the Main Purge Isolation dampers and fans.

Determines checklist 1 has been completed from initial conditions.

3

Reviews NOTE concerning interlocks between main and mini-purge fans.

4.1.2.3 IF the Mini-Purge System is operating, perform the following:

a.

Notify Chemistry that containment purge will be shifted from the Mini-Purge to the Main Purge System.

CUE:

Chemistry has been notified that containment purge will be shifted from mini to main purge.

b.

Go To Section 4.3.2 and shut down the Mini-Purge System.

Standard:

Determines that section 4.3.2 needs to be performed Comment:

SECTION 4.3.2 Reviews note at beginning of section 4.3.2 4.3.2.1 Standard:

Comment:

Terminate Mini-Purge Supply flow as follows:

a.

Stop the CTB MINI-PURGE SPL Y FAN using 1-HS-2630B. (B32)

b.

Close CTB NORM PURGE SPLY ORC ISO VLV-MINI1-HV-2627B using 1-HS -2627B (032).

c.

Close CTB NORM PURGE SPLY IRC ISO VLV-MINI1-HV-2626B using 1-HS -2626B (C32).

Determines that these steps are N/A from initial conditions given and control board indications.

4 Reviews NOTE concerning interlocks between main and mini-purge fans.

4.1.2.3 IF the Mini-Purge System is operating, perform the following:

a.

Notify Chemistry that containment purge will be shifted from the Mini-Purge to the Main Purge System.

CUE:

Chemistry has been notified that containment purge will be shifted from mini to main purge.

b.

Go To Section 4.3.2 and shut down the Mini-Purge System.

Standard:

Determines that section 4.3.2 needs to be performed Comment:

SECTION 4.3.2 Reviews note at beginning of section 4.3.2 4.3.2.1 Standard:

Comment:

Terminate Mini-Purge Supply flow as follows:

a.

Stop the CTB MINI-PURGE SPL Y FAN using 1-HS-2630B. (B32)

b.

Close CTB NORM PURGE SPLY ORC ISO VLV-MINI1-HV-2627B using 1-HS -2627B (032).

c.

Close CTB NORM PURGE SPLY IRC ISO VLV-MINI1-HV-2626B using 1-HS -2626B (C32).

Determines that these steps are N/A from initial conditions given and control board indications.

4

  • 4.3.2.2 Standard:

Comment:

  • 4.3.2.2b.

Standard:

Comment:

  • 4.3.2.2c.

Standard:

Comment:

  • 4.3.2.2d.

Standard:

Comment:

Terminate Mini-Purge Exhaust flow as follows:

a.

Stop the CTB MINI-PURGE EXH FAN using 1-HS-2631B. (034) 1 HS-2631 B hand switch rotated counter clockwise.

Red light -OFF Green light -ON Close CTB MINI PURGE EXH ORC ISO VLV-MINI1-HV-2629B using 1-HS

-2629B (B34).

1 HS-2629B hand switch rotated counter clockwise.

Red light -OFF Green light -ON Close CTB NORM PURGE EXH IRC ISO VLV-MINI1-HV-2628B using 1-HS

-2628B (A34).

1 HS-2628B hand switch rotated counter clockwise.

Red light -OFF Green light -ON Place CTB MINI-PURGE EXH OMPR 1-HV-12592 in CLOSE using 1-HS

-12592 (C34).

1 HS-12592 hand switch rotated counter clockwise.

Red light -OFF Green light -ON 5

  • 4.3.2.2 Standard:

Comment:

  • 4.3.2.2b.

Standard:

Comment:

  • 4.3.2.2c.

Standard:

Comment:

  • 4.3.2.2d.

Standard:

Comment:

Terminate Mini-Purge Exhaust flow as follows:

a.

Stop the CTB MINI-PURGE EXH FAN using 1-HS-2631B. (034) 1 HS-2631 B hand switch rotated counter clockwise.

Red light -OFF Green light -ON Close CTB MINI PURGE EXH ORC ISO VLV-MINI1-HV-2629B using 1-HS

-2629B (B34).

1 HS-2629B hand switch rotated counter clockwise.

Red light -OFF Green light -ON Close CTB NORM PURGE EXH IRC ISO VLV-MINI1-HV-2628B using 1-HS

-2628B (A34).

1 HS-2628B hand switch rotated counter clockwise.

Red light -OFF Green light -ON Place CTB MINI-PURGE EXH OMPR 1-HV-12592 in CLOSE using 1-HS

-12592 (C34).

1 HS-12592 hand switch rotated counter clockwise.

Red light -OFF Green light -ON 5

4.3.2.2e.

CUE:

Standard:

Comment:

  • 4.3.2.3 Standard:

Comment:

4.3.2.4 CUE:

Standard:

Comment:

4.3.2.5 CUE:

Standard:

Comment:

Log the Containment Mini-Purge Termination TIME and DATE on the Release Permit on the same line where flow is recorded.

Containment Mini-Purge Termination TIME and DATE have been entered on the Release Permit N/A Close CTa PREACCESS PURGE SPL Y UNIT INLET DMPR, 1-HV-2593 using 1-HS -2593 (A31).

Hand switch 1-HS-2593 rotated counter clockwise.

Green light - ON Red light - OFF Notify Chemistry that Containment Mini-Purge has been terminated, and the Containment Gaseous Release Permit has been closed.

Chemistry has been notified that containment mini-purge has been terminated and the containment gaseous release permit has been closed.

N/A Record the name of the person contacted in the Unit Control Log.

Name of person contacted has been recorded in the unit control log.

N/A 6

4.3.2.2e.

CUE:

Standard:

Comment:

  • 4.3.2.3 Standard:

Comment:

4.3.2.4 CUE:

Standard:

Comment:

4.3.2.5 CUE:

Standard:

Comment:

Log the Containment Mini-Purge Termination TIME and DATE on the Release Permit on the same line where flow is recorded.

Containment Mini-Purge Termination TIME and DATE have been entered on the Release Permit N/A Close CTa PREACCESS PURGE SPL Y UNIT INLET DMPR, 1-HV-2593 using 1-HS -2593 (A31).

Hand switch 1-HS-2593 rotated counter clockwise.

Green light - ON Red light - OFF Notify Chemistry that Containment Mini-Purge has been terminated, and the Containment Gaseous Release Permit has been closed.

Chemistry has been notified that containment mini-purge has been terminated and the containment gaseous release permit has been closed.

N/A Record the name of the person contacted in the Unit Control Log.

Name of person contacted has been recorded in the unit control log.

N/A 6

4.3.2.6 Restore the Mini-Purge System per Checklist 3:

COMPONENT DESCRIPTION POSITION 1-HS-2593 CTB PREACCESS PURGE SPL Y UNIT INLET DMPR CLOSED (A31) 1-HS-2628B CTB NORM PURGE EXH IRC ISO VLV-MINI CLOSED (A34) 1-HS-2629B CTB NORM PURGE EXH ORC ISO VLV-MINI CLOSED (B34) 1-HS-2626B CTB NORM PURGE SPL Y IRC ISO VL V-MINI CLOSED (C32) 1-HS-2627B CTB NORM PURGE SPL Y ORC ISO VLV-MINI CLOSED (032)

CUE:

If asked, "the extra operator will perform the independent verification of checklist 3".

Standard:

Comment:

4.3.2.7 Standard:

Comment:

Each damper verified closed by Green light - ON and Red light OFF.

Student requests an independent verification for these steps.

IF the Main Purge System is being placed in service, Return To Step 4.1.2.4.

Determines that this step is applicable and returns to step 4.1.2.4 7

4.3.2.6 Restore the Mini-Purge System per Checklist 3:

COMPONENT DESCRIPTION POSITION 1-HS-2593 CTB PREACCESS PURGE SPL Y UNIT INLET DMPR CLOSED (A31) 1-HS-2628B CTB NORM PURGE EXH IRC ISO VLV-MINI CLOSED (A34) 1-HS-2629B CTB NORM PURGE EXH ORC ISO VLV-MINI CLOSED (B34) 1-HS-2626B CTB NORM PURGE SPL Y IRC ISO VL V-MINI CLOSED (C32) 1-HS-2627B CTB NORM PURGE SPL Y ORC ISO VLV-MINI CLOSED (032)

CUE:

If asked, "the extra operator will perform the independent verification of checklist 3".

Standard:

Comment:

4.3.2.7 Standard:

Comment:

Each damper verified closed by Green light - ON and Red light OFF.

Student requests an independent verification for these steps.

IF the Main Purge System is being placed in service, Return To Step 4.1.2.4.

Determines that this step is applicable and returns to step 4.1.2.4 7

Reviews note prior to next step 4.1.2.4

a.
b.

Standard:

Comment:

4.1.2.5 Standard:

Comment:

4.1.2.6 Standard:

Comment:

IF the Mini-Purge System is NOT operating, perform the following:

Notify Chemistry of the upcoming Main Purge operation:

Obtain the current approved Containment Gaseous Release Permit.

IF an updated permit is unavailable, request that Chemistry sample the containment atmosphere and prepare for the gaseous release.

WHEN a current approved Containment Gaseous Release Permit is obtained, continue with this section.

Determines release permit obtained from initial conditions given and proceeds.

Verify all conditions that must be satisfied prior to the release are met.

Determines all conditions satisfied:

Release permit obtained Place CTa PREACCESS PURGE EXH DMPR 1-HS-2632A (C33) in AUTO.

1-HS-2632A verified in the AUTO position 8

Reviews note prior to next step 4.1.2.4

a.
b.

Standard:

Comment:

4.1.2.5 Standard:

Comment:

4.1.2.6 Standard:

Comment:

IF the Mini-Purge System is NOT operating, perform the following:

Notify Chemistry of the upcoming Main Purge operation:

Obtain the current approved Containment Gaseous Release Permit.

IF an updated permit is unavailable, request that Chemistry sample the containment atmosphere and prepare for the gaseous release.

WHEN a current approved Containment Gaseous Release Permit is obtained, continue with this section.

Determines release permit obtained from initial conditions given and proceeds.

Verify all conditions that must be satisfied prior to the release are met.

Determines all conditions satisfied:

Release permit obtained Place CTa PREACCESS PURGE EXH DMPR 1-HS-2632A (C33) in AUTO.

1-HS-2632A verified in the AUTO position 8

Reviews cautions prior to next step 4.1.2.7

  • a.

Standard:

Comment:

  • 4.1.2.7b Standard:

Comment:

  • 4.1.2.7c.

Standard:

Comment:

Initiate Main Purge Exhaust flow as follows:

Open CTS PREACCE55 PURGE 5PLY UNIT INLET DMPR 1*HV*2593 using 1*H5 *2593 (A31).

1-HS-2593 rotated clockwise Red light - ON Green light - OFF Open CTS NORM PURGE EXH ORC ISO VLV*MAlN 1*HV*2629A using 1*H5

  • 2629A (S33).

1-HS-2629A rotated clockwise Red light-ON Green light - OFF Open CTS NORM PURGE EXH IRC ISO VLV*MAIN 1*HV*2628A using 1*H5

  • 2628A (A33).

1-HS-2628A rotated clockwise Red light-ON Green light - OFF 9

Reviews cautions prior to next step 4.1.2.7

  • a.

Standard:

Comment:

  • 4.1.2.7b Standard:

Comment:

  • 4.1.2.7c.

Standard:

Comment:

Initiate Main Purge Exhaust flow as follows:

Open CTS PREACCE55 PURGE 5PLY UNIT INLET DMPR 1*HV*2593 using 1*H5 *2593 (A31).

1-HS-2593 rotated clockwise Red light - ON Green light - OFF Open CTS NORM PURGE EXH ORC ISO VLV*MAlN 1*HV*2629A using 1*H5

  • 2629A (S33).

1-HS-2629A rotated clockwise Red light-ON Green light - OFF Open CTS NORM PURGE EXH IRC ISO VLV*MAIN 1*HV*2628A using 1*H5

  • 2628A (A33).

1-HS-2628A rotated clockwise Red light-ON Green light - OFF 9

  • 4.1.2.7d.

Standard:

Comment:

4.1.2.7e.

CUE:

Standard:

Comment:

Start the CTa PREACCESS PURGE EXH FAN using 1*HS*2631A (033),

1-HS-2631 A rotated clockwise Red light - ON Green light - OFF Log the Release Start Time and Date on the Chemistry data sheet provided.

Release start time and date has been logged on the Chemistry data sheet.

N/A Reviews note prior to next step 4.1.2.7 f.

CUE:

Standard:

Comment:

Note the Main Purge Exhaust Flow rate, and verify it is within allowable value as stated on Release Permit, Main Purge Exhaust flow rate is within its allowable value on the release permit.

N/A 10

  • 4.1.2.7d.

Standard:

Comment:

4.1.2.7e.

CUE:

Standard:

Comment:

Start the CTa PREACCESS PURGE EXH FAN using 1*HS*2631A (033),

1-HS-2631 A rotated clockwise Red light - ON Green light - OFF Log the Release Start Time and Date on the Chemistry data sheet provided.

Release start time and date has been logged on the Chemistry data sheet.

N/A Reviews note prior to next step 4.1.2.7 f.

CUE:

Standard:

Comment:

Note the Main Purge Exhaust Flow rate, and verify it is within allowable value as stated on Release Permit, Main Purge Exhaust flow rate is within its allowable value on the release permit.

N/A 10

4.1.2.7 g.

Standard:

Comment:

IF both Radiation Monitors 1-RE-12442C and 1-RE-12444C, become inoperable, immediately shut down the Main Purge System per section 4.3.1 and notify the SS.

N/A Reviews caution prior to next step 4.1.2.8

a.
b.
c.

4.1.2.9 4.1.2.10 CUE:

Standard:

Comment:

Initiate Main Purge Supply flow if desired as follows:

Open CTB NORM PURGE SPLY ORC ISO VLV-MAIN 1-HV-2627A using 1-HS -2627A (031).

Open CTB NORM PURGE SPL Y IRC ISO VL V-MAIN 1-HV-2626A using 1-HS -2626A (C31 ).

Start the CTB PREACCESS PURGE SPLY FAN using 1-HS-2630A (B31 ).

Note the Main Purge Exhaust Flow rate with Supply and Exhaust Fans in service, and verify it is within allowable value as stated on Release Permit.

Log flow rate on Chemistry data sheet provided.

If asked, "Flow rate is logged on the Chemistry data sheet".

These steps are determined to be N/A from initial conditions given. If step 4.1.2.8 is performed, then it becomes critical and is unsatisfactory.

11 4.1.2.7 g.

Standard:

Comment:

IF both Radiation Monitors 1-RE-12442C and 1-RE-12444C, become inoperable, immediately shut down the Main Purge System per section 4.3.1 and notify the SS.

N/A Reviews caution prior to next step 4.1.2.8

a.
b.
c.

4.1.2.9 4.1.2.10 CUE:

Standard:

Comment:

Initiate Main Purge Supply flow if desired as follows:

Open CTB NORM PURGE SPLY ORC ISO VLV-MAIN 1-HV-2627A using 1-HS -2627A (031).

Open CTB NORM PURGE SPL Y IRC ISO VL V-MAIN 1-HV-2626A using 1-HS -2626A (C31 ).

Start the CTB PREACCESS PURGE SPLY FAN using 1-HS-2630A (B31 ).

Note the Main Purge Exhaust Flow rate with Supply and Exhaust Fans in service, and verify it is within allowable value as stated on Release Permit.

Log flow rate on Chemistry data sheet provided.

If asked, "Flow rate is logged on the Chemistry data sheet".

These steps are determined to be N/A from initial conditions given. If step 4.1.2.8 is performed, then it becomes critical and is unsatisfactory.

11

4.1.2.11 CUE:

Standard:

Comment:

Notify Chemistry that the Main Containment Purge System is operating, and record the name of the person contacted in the Unit Control Log.

Chemistry has been notified that the Main Containment Purge System is operating, and the name of the person contacted has been recorded in the Unit Control Log.

N/A Student notifies SS that the main purge system has been placed in service per 13125-1.

Standard:

N/A Comment:

Terminating cue:

Student returns initiating cue sheet 12 4.1.2.11 CUE:

Standard:

Comment:

Notify Chemistry that the Main Containment Purge System is operating, and record the name of the person contacted in the Unit Control Log.

Chemistry has been notified that the Main Containment Purge System is operating, and the name of the person contacted has been recorded in the Unit Control Log.

N/A Student notifies SS that the main purge system has been placed in service per 13125-1.

Standard:

N/A Comment:

Terminating cue:

Student returns initiating cue sheet 12

Verification of Completion Job Performance Measure No. V-LO-JP-13125-002 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: ----------------------------------------------------------

Response: __________________________________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date: ______________ _

13 Verification of Completion Job Performance Measure No. V-LO-JP-13125-002 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: ------------------------------------------------------------

Response: __________________________________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date:

13

Initial Conditions:

The Plant is in Mode 5 with the Containment Equipment Hatch Open.

Initiating Cue:

The 55 has authorized Gaseous Release Permits and has directed you to "Place Containment Main (Preaccess) Purge in service" using procedure 13125-1.

"Checklist 1 for Main Purge isolation dampers and valves has been performed".

14 Initial Conditions:

The Plant is in Mode 5 with the Containment Equipment Hatch Open.

Initiating Cue:

The 55 has authorized Gaseous Release Permits and has directed you to "Place Containment Main (Preaccess) Purge in service" using procedure 13125-1.

"Checklist 1 for Main Purge isolation dampers and valves has been performed".

14

ES-301 Control Roomlln-Plant Systems Outline F /,., r.1 h.

Form ES-301-2 In-Plant Systems@ (3 for RO; 3 for SRO-I; 3 or 2 for SRO-U)

i. Establish RWST Gravity Drain through SI Pumps to RCS Cold Legs

==

Description:==

Use attachment B of AOP 18019-C (Loss of RHR cooling) to establish gravity drain during mid-loop operations to restore temporary core cooling.

(RO / SRO-I / SRO-U)

KIA: 025AK1.01 (3.9/4.3)

j. Shutdown 120V AC 1E Inverter During Loss of All AC Power

==

Description:==

Battery voltage less than 105 VDC on loss of all AC power. Requires student to shutdown AC inverter to prevent equipment damage.

(RO / SRO-I)

KIA: 055EK3.02 (4.3/4.6)

k. Bypass CNMT HI-1 Bistables Following Loss of Heat Sink

==

Description:==

Bistables must be bypassed using the BTl equipment in order to align a feedwater flow path to the SGs during a loss of secondary heat sink. This will also require knowledge of how / where to obtain multiple BTl keys to bypass 2 trains of equipment (RO / SRO-I / SRO-U)

KIA: 012A4.03 (3.6/3.6)

D,E,L,R 4P P,D,E,L,R 6

D,C,E,L 7

All control room (and in-plant) systems must be different and serve different safety functions; in-plant systems and functions may overlap those tested in the control room.

(A)ltemate path (C)ontrol room (D)irect from bank

  • Type Codes (E)mergency or abnormal in-plant (EN)gineered Safety Feature (L)ow-Power 1 Shutdown (N)ew or (M)odified from bank including 1 (A)

(P)revious 2 exams (R)CA (S)imulator Criteria for RO 1 SRO-I 1 SRO-U 4-6 1 4-6 1 2-3

.s9/.s81.s4

1 1 :::1 I::: 1 1 > 1 (control room system)
1/:::1/:::1
2/:::2/:::1

.s 3 J.s 3 1.s 2 (randomly selected)

1/:::1/:::1 ES-301 Control Roomlln-Plant Systems Outline F /,., r.1 h.

Form ES-301-2 In-Plant Systems@ (3 for RO; 3 for SRO-I; 3 or 2 for SRO-U)

i. Establish RWST Gravity Drain through SI Pumps to RCS Cold Legs

==

Description:==

Use attachment B of AOP 18019-C (Loss of RHR cooling) to establish gravity drain during mid-loop operations to restore temporary core cooling.

(RO / SRO-I / SRO-U)

KIA: 025AK1.01 (3.9/4.3)

j. Shutdown 120V AC 1E Inverter During Loss of All AC Power

==

Description:==

Battery voltage less than 105 VDC on loss of all AC power. Requires student to shutdown AC inverter to prevent equipment damage.

(RO / SRO-I)

KIA: 055EK3.02 (4.3/4.6)

k. Bypass CNMT HI-1 Bistables Following Loss of Heat Sink

==

Description:==

Bistables must be bypassed using the BTl equipment in order to align a feedwater flow path to the SGs during a loss of secondary heat sink. This will also require knowledge of how / where to obtain multiple BTl keys to bypass 2 trains of equipment (RO / SRO-I / SRO-U)

KIA: 012A4.03 (3.6/3.6)

D,E,L,R 4P P,D,E,L,R 6

D,C,E,L 7

All control room (and in-plant) systems must be different and serve different safety functions; in-plant systems and functions may overlap those tested in the control room.

(A)ltemate path (C)ontrol room (D)irect from bank

  • Type Codes (E)mergency or abnormal in-plant (EN)gineered Safety Feature (L)ow-Power 1 Shutdown (N)ew or (M)odified from bank including 1 (A)

(P)revious 2 exams (R)CA (S)imulator Criteria for RO 1 SRO-I 1 SRO-U 4-6 1 4-6 1 2-3

.s9/.s81.s4

1 1 :::1 I::: 1 1 > 1 (control room system)
1/:::1/:::1
2/:::2/:::1

.s 3 J.s 3 1.s 2 (randomly selected)

1/:::1/:::1

Job Performance Measure "i" Facility: Vogtle Task No: V-LO-TA-60025 Task

Title:

Establish RWST Gravity Drain Through 51 Pumps to RCS Cold Legs JPM No: V-RQ-JP-18019-005 KIA

Reference:

025AK1.01 Examinee:

NRC Examiner: -----------------

Facility Evaluator: ______________ _

Date:

Method of testing:

Simulated Performance Actual Performance Classroom ------------

Plant _____ _

Simulator ------

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

During mid-loop operations, Unit 1/2 experienced a loss of all AC power to the 1E buses. The crew is performing step B15 of AOP 18019-C, "Loss of RHR", attempting to a restore RCS level to greater than or equal to 188 feet.

RV head is on, RCS level is 188', all cold legs are intact (no openings), and all 3 Pressurizer Code Safeties are removed Task Standard:

Student determines an adequate vent path exists and opens the SI pump cold leg injection valves 1/2HV8821A and 1/2HV8821 B.

Required Materials:

AOP 18019-C General

References:

Requires RCA entry Initiating Cue:

The 55 has directed you to perform step B15 of 18019-C, "Loss of RHR - Mode 5 or 6 Below PRZR IR Or SG Nozzle Dams Installed Time Critical Task:

No Validation Time:

15 minutes 1

Job Performance Measure "i" Facility: Vogtle Task No: V-LO-TA-60025 Task

Title:

Establish RWST Gravity Drain Through 51 Pumps to RCS Cold Legs JPM No: V-RQ-JP-18019-005 KIA

Reference:

025AK1.01 Examinee:

NRC Examiner: -----------------

Facility Evaluator: ______________ _

Date:

Method of testing:

Simulated Performance Actual Performance Classroom ------------

Plant _____ _

Simulator ------

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

During mid-loop operations, Unit 1/2 experienced a loss of all AC power to the 1E buses. The crew is performing step B15 of AOP 18019-C, "Loss of RHR", attempting to a restore RCS level to greater than or equal to 188 feet.

RV head is on, RCS level is 188', all cold legs are intact (no openings), and all 3 Pressurizer Code Safeties are removed Task Standard:

Student determines an adequate vent path exists and opens the SI pump cold leg injection valves 1/2HV8821A and 1/2HV8821 B.

Required Materials:

AOP 18019-C General

References:

Requires RCA entry Initiating Cue:

The 55 has directed you to perform step B15 of 18019-C, "Loss of RHR - Mode 5 or 6 Below PRZR IR Or SG Nozzle Dams Installed Time Critical Task:

No Validation Time:

15 minutes 1

Performance Information Critical steps denoted with an asterisk NOTE prior to step 815 Gravity drain paths through the RHR pumps are preferable since these can achieve the greatest flow rate. Gravity drain paths are listed in order of preferability.

Standard: N/A Comment:

B15 AER Makeup to RCS to restore level greater than or equal to 188 feet using any of the following:

a.

Standard:

Comment:

815 RNO:

Check RHR pump - AVAILABLE RHR pump determined not available due to loss of all AC power from initial conditions Use any of the following:

ATTACHMENT A Section A, RWST GRAVITY DRAIN THROUGH RHR PUMPS TO COLD LEGS.

CUE:

Standard:

Comment:

The SS reports the RHR flow paths to the RCS Cold Legs are NOT available.

Bypasses Attachment A section A 2

Performance Information Critical steps denoted with an asterisk NOTE prior to step 815 Gravity drain paths through the RHR pumps are preferable since these can achieve the greatest flow rate. Gravity drain paths are listed in order of preferability.

Standard: N/A Comment:

B15 AER Makeup to RCS to restore level greater than or equal to 188 feet using any of the following:

a.

Standard:

Comment:

815 RNO:

Check RHR pump - AVAILABLE RHR pump determined not available due to loss of all AC power from initial conditions Use any of the following:

ATTACHMENT A Section A, RWST GRAVITY DRAIN THROUGH RHR PUMPS TO COLD LEGS.

CUE:

Standard:

Comment:

The SS reports the RHR flow paths to the RCS Cold Legs are NOT available.

Bypasses Attachment A section A 2

815 RNO continued:

ATTACHMENT A Section 8, RWST GRAVITY DRAIN THROUGH SI PUMPS TO COLD LEGS.

Standard:

Attachment A Section 8 selected for use Comment:

ATTACHMENT A RWST GRAVITY DRAIN TO RCS CAUTION:

An RCS pressure of 35 psig allows no RWST to RCS gravity drain.

CUE:

If asked: The SS reports RCS pressure is 0 psig Standard:

N/A Comment:

NOTE:

This attachment should not be used if an ECCS pump is available.

Standard:

Determines Attachment A is applicable Comment:

3 815 RNO continued:

ATTACHMENT A Section 8, RWST GRAVITY DRAIN THROUGH SI PUMPS TO COLD LEGS.

Standard:

Attachment A Section 8 selected for use Comment:

ATTACHMENT A RWST GRAVITY DRAIN TO RCS CAUTION:

An RCS pressure of 35 psig allows no RWST to RCS gravity drain.

CUE:

If asked: The SS reports RCS pressure is 0 psig Standard:

N/A Comment:

NOTE:

This attachment should not be used if an ECCS pump is available.

Standard:

Determines Attachment A is applicable Comment:

3

An ACHMENT A STEP 1:

Check RCS pressure - LESS THAN 35 PSIG CUE:

If asked: The SS reports RCS pressure is 0 psig Standard:

Determines RCS pressure < 35 psig Comment:

Verify at least one of the following RCS Vent Paths:

a.

Standard:

Comment:

b.

Standard:

Comment:

RV head removed.

Determines RV head on from initial conditions RV head on and RCS level ~ 191' and with a cold leg opening, an adequate RCS vent path is an SG hot leg manway on an SG with no nozzle dam installed.

Determines no RCS cold leg opening from initial conditions 4

An ACHMENT A STEP 1:

Check RCS pressure - LESS THAN 35 PSIG CUE:

If asked: The SS reports RCS pressure is 0 psig Standard:

Determines RCS pressure < 35 psig Comment:

Verify at least one of the following RCS Vent Paths:

a.

Standard:

Comment:

b.

Standard:

Comment:

RV head removed.

Determines RV head on from initial conditions RV head on and RCS level ~ 191' and with a cold leg opening, an adequate RCS vent path is an SG hot leg manway on an SG with no nozzle dam installed.

Determines no RCS cold leg opening from initial conditions 4

c.

Standard:

Comment:

NOTE:

RV head on and RCS level:: 191' and with no cold leg opening:

(1) A minimum of three pressurizer code safeties removed,

-OR-(2) The pressurizer manway removed,

-OR-(3) An SG hot leg manway removed on an SG with no nozzle dams installed.

Determines vent path is adequate per step c.( 1) from initial conditions It is desirable to gravity drain to a closed cold leg using Section A or B.

If a closed cold leg is unavailable, then go to Section C or D for gravity drain to a hot leg.

Gravity drain paths through the RHR loops are preferable since these can achieve the greatest flow rate.

Standard:

N/A Comment:

3.

Standard:

Comment:

If desired to gravity drain from RWST through RHR pumps to cold legs, then go to Section A of this attachment.

Determines section A should not be used from previous SS cue that RHR cold path is not available 5

c.

Standard:

Comment:

NOTE:

RV head on and RCS level:: 191' and with no cold leg opening:

(1) A minimum of three pressurizer code safeties removed,

-OR-(2) The pressurizer manway removed,

-OR-(3) An SG hot leg manway removed on an SG with no nozzle dams installed.

Determines vent path is adequate per step c.( 1) from initial conditions It is desirable to gravity drain to a closed cold leg using Section A or B.

If a closed cold leg is unavailable, then go to Section C or D for gravity drain to a hot leg.

Gravity drain paths through the RHR loops are preferable since these can achieve the greatest flow rate.

Standard:

N/A Comment:

3.

Standard:

Comment:

If desired to gravity drain from RWST through RHR pumps to cold legs, then go to Section A of this attachment.

Determines section A should not be used from previous SS cue that RHR cold path is not available 5

4.

Standard:

Comment:

B.

B1.

CUE:

Standard:

Comment:

If desired to gravity drain from RWST through SI pumps to cold legs, then go to Section B of this attachment.

Selects Section B of ATTACHMENT A for use ATTACHMENT A RWST GRAVITY DRAIN THROUGH SI PUMPS TO COLD LEGS Verify HV-8835 - OPEN The SS reports that HV-8835 is OPEN Determines HV-8835 is open 6

4.

Standard:

Comment:

B.

B1.

CUE:

Standard:

Comment:

If desired to gravity drain from RWST through SI pumps to cold legs, then go to Section B of this attachment.

Selects Section B of ATTACHMENT A for use ATTACHMENT A RWST GRAVITY DRAIN THROUGH SI PUMPS TO COLD LEGS Verify HV-8835 - OPEN The SS reports that HV-8835 is OPEN Determines HV-8835 is open 6

B2 CUE:

Standard:

Comment:

Standard:

Comment:

Locally throttle open the following SI PMP-A(B) TO COLD LEG ISO VLV valves:

UNIT 1 1-HV-8821A (AB-B15) 1-HV-8821B(AB-B19)

UNIT2 2-HV-8821A (AB-B119) 2-HV-8821 B (AB-B117)

Locates valves and determines current position is closed based on valve position indicator IF ASKED:

If valve is closed: "Valve is positioned as you see it" If valve is open: provide visual cue that valve position pointer is aligned with closed indicator Determines valves are closed Disengages clutch and opens valve HV-8821A or HV-8821B Depresses clutch level arm on motor operator towards the disengage direction and turns valve hand wheel in the open direction (counter clockwise) marked on the hand wheel until valve position pointer moves to the open position indicator 7

B2 CUE:

Standard:

Comment:

Standard:

Comment:

Locally throttle open the following SI PMP-A(B) TO COLD LEG ISO VLV valves:

UNIT 1 1-HV-8821A (AB-B15) 1-HV-8821B(AB-B19)

UNIT2 2-HV-8821A (AB-B119) 2-HV-8821 B (AB-B117)

Locates valves and determines current position is closed based on valve position indicator IF ASKED:

If valve is closed: "Valve is positioned as you see it" If valve is open: provide visual cue that valve position pointer is aligned with closed indicator Determines valves are closed Disengages clutch and opens valve HV-8821A or HV-8821B Depresses clutch level arm on motor operator towards the disengage direction and turns valve hand wheel in the open direction (counter clockwise) marked on the hand wheel until valve position pointer moves to the open position indicator 7

Standard:

Comment:

Disengages clutch and opens valve HV-8821B or HV-8821A Depresses clutch level arm on motor operator towards the disengage direction and turns valve hand wheel in the open direction (counter clockwise) marked on the hand wheel until valve position pointer moves to the open position indicator Reports to the SS that the SI system has been aligned gravity drain the RWST through the SI pumps to the cold legs per ATTACHMENT A section B of AOP 18019-C.

Standard:

N/A Comment:

Terminating cue:

Student returns initiating cue sheet 8

Standard:

Comment:

Disengages clutch and opens valve HV-8821B or HV-8821A Depresses clutch level arm on motor operator towards the disengage direction and turns valve hand wheel in the open direction (counter clockwise) marked on the hand wheel until valve position pointer moves to the open position indicator Reports to the SS that the SI system has been aligned gravity drain the RWST through the SI pumps to the cold legs per ATTACHMENT A section B of AOP 18019-C.

Standard:

N/A Comment:

Terminating cue:

Student returns initiating cue sheet 8

Verification of Completion Job Performance Measure No. V-RQ-JP-18019-005 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: -----------------------------------------------------------

Response: __________________________________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date: _________________________ _

9 Verification of Completion Job Performance Measure No. V-RQ-JP-18019-005 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: _____________________________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date:

9

Initial Conditions:

During mid-loop operations, Unit 1/2 experienced a loss of all AC power to the 1 E buses. The crew is performing step B15 of AOP 18019-C, "Loss of RHR", attempting to a restore RCS level to greater than or equal to 188 feet.

Initiating Cue:

RV head is on, RCS level is 188', all cold legs are intact (no openings), and all 3 Pressurizer Code Safeties are removed The SS has directed you to perform step B15 of 18019-C, "Loss of RHR - Mode 5 or 6 Below PRZR IR Or SG Nozzle Dams Installed 10 Initial Conditions:

During mid-loop operations, Unit 1/2 experienced a loss of all AC power to the 1 E buses. The crew is performing step B15 of AOP 18019-C, "Loss of RHR", attempting to a restore RCS level to greater than or equal to 188 feet.

Initiating Cue:

RV head is on, RCS level is 188', all cold legs are intact (no openings), and all 3 Pressurizer Code Safeties are removed The SS has directed you to perform step B15 of 18019-C, "Loss of RHR - Mode 5 or 6 Below PRZR IR Or SG Nozzle Dams Installed 10

Job Performance Measure "j" Facility: Vogtle Task No: V-LO-TA-01014 Task

Title:

Shutdown 120V AC 1E Vital Inverter during a Loss of All AC Power JPM No: V-RQ-JP-13431-001 KIA

Reference:

055EK3.02 Examinee: __________ _

NRC Examiner: ________ _

Facility Evaluator: ________ _

Date: ----------------

Method of testing:

Simulated Performance ______ _

Actual Performance _______ _

Classroom Simulator Plant Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

Unit 1/2 control room has experienced a prolonged Loss of All AC Power, 125V 1E DC Bus 1/2BD1 voltage is currently reading 103V DC.

Task Standard:

Student shuts down inverter per 13431-112 and opens associated bus battery breaker per 19100-C.

Required Materials:

1. EOP 191 OO-C, Loss of All AC Power step 28
2. SOP 13431-1/2, 120V AC 1 E Vital Instrument Distribution System General

References:

None Initiating Cue:

You have been directed by the SS to perform step 28 of 19100*C, "Loss of All AC Power".

Time Critical Task:

No Validation Time:

15 minutes 1

Job Performance Measure "j" Facility: Vogtle Task No: V-LO-TA-01014 Task

Title:

Shutdown 120V AC 1E Vital Inverter during a Loss of All AC Power JPM No: V-RQ-JP-13431-001 KIA

Reference:

055EK3.02 Examinee:

NRC Examiner: ________ _

Facility Evaluator: ________ _

Date:

Method of testing:

Simulated Performance ______ _

Actual Performance ________ _

Classroom Simulator Plant Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

Unit 1/2 control room has experienced a prolonged Loss of All AC Power, 125V 1E DC Bus 1/2BD1 voltage is currently reading 103V DC.

Task Standard:

Student shuts down inverter per 13431-112 and opens associated bus battery breaker per 19100-C.

Required Materials:

1. EOP 191 OO-C, Loss of All AC Power step 28
2. SOP 13431-1/2, 120V AC 1 E Vital Instrument Distribution System General

References:

None Initiating Cue:

You have been directed by the SS to perform step 28 of 19100*C, "Loss of All AC Power".

Time Critical Task:

No Validation Time:

15 minutes 1

Performance Information Critical steps denoted with an asterisk EOP 19100-C STEP 28 Check DC Bus loads:

a.

Monitor all1E Battery Bus voltages - GREATER THAN 105V DC Standard:

Determines 1/2BD1 bus voltage is 103 V DC from initial conditions Comment:

STEP 28 RNO:

IF any 1E Inverter Battery Bus voltage drops to 105V DC or less, THEN perform the following:

1 )

Standard:

Comment:

Verify associated Inverter( s) shutdown per 13431, 120V AC 1 E VITAL INSTRUMENT DISTRIBUTION SYSTEM Determines 13431-112 must be completed to shutdown inverter( s)

SOP 13431-1/2 CUE:

Standard:

Comment:

Determines section 4.3.2 should be implemented to shutdown inverters 1/2BD112 and 1/2BD1112 You are directed to shut down inverter 1128D112 Goes to section 4.3.2 of SOP 13431-1/2 2

Performance Information Critical steps denoted with an asterisk EOP 19100-C STEP 28 Check DC Bus loads:

a.

Monitor all1E Battery Bus voltages - GREATER THAN 105V DC Standard:

Determines 1/2BD1 bus voltage is 103 V DC from initial conditions Comment:

STEP 28 RNO:

IF any 1E Inverter Battery Bus voltage drops to 105V DC or less, THEN perform the following:

1 )

Standard:

Comment:

Verify associated Inverter( s) shutdown per 13431, 120V AC 1 E VITAL INSTRUMENT DISTRIBUTION SYSTEM Determines 13431-112 must be completed to shutdown inverter( s)

SOP 13431-1/2 CUE:

Standard:

Comment:

Determines section 4.3.2 should be implemented to shutdown inverters 1/2BD112 and 1/2BD1112 You are directed to shut down inverter 1128D112 Goes to section 4.3.2 of SOP 13431-1/2 2

Student notes the CAUTION at start of section 4.3.2 4.3.2.1 Standard:

Comment:

4.3.2.2 Standard:

Comment:

  • 4.3.2.3 Standard:

Comment:

  • 4.3.2.4 Standard:

Comment:

Verifies closed breaker 1/2BD1-01

1. Green and Amber lights OFF
2. Red light ON OR
3. Green 1 Open flag - VISIBLE IF the associated Instrument Distribution Panel is to remain energized, transfer the panel to the alternate source per Section 4.2.1.

Determines this step is NIA due to loss of all AC power Opens INVERTER 1/2B0112 OUTPUT breaker Moves the molded case circuit breaker to the open (down) position.

Opens Inverter 1/2B0112 DC INPUT breaker Moves molded case breaker to the open (down) position 3

Student notes the CAUTION at start of section 4.3.2 4.3.2.1 Standard:

Comment:

4.3.2.2 Standard:

Comment:

  • 4.3.2.3 Standard:

Comment:

  • 4.3.2.4 Standard:

Comment:

Verifies closed breaker 1/2BD1-01

1. Green and Amber lights OFF
2. Red light ON OR
3. Green 1 Open flag - VISIBLE IF the associated Instrument Distribution Panel is to remain energized, transfer the panel to the alternate source per Section 4.2.1.

Determines this step is NIA due to loss of all AC power Opens INVERTER 1/2B0112 OUTPUT breaker Moves the molded case circuit breaker to the open (down) position.

Opens Inverter 1/2B0112 DC INPUT breaker Moves molded case breaker to the open (down) position 3

4.3.2.5 CUE:

Standard:

Comment:

  • 4.3.2.6 Standard:

Comment:

19100-C Check inverter completely shutdown, by observing zero volts on the Inverter AC OUTPUT Voltmeter.

When asked, indicate AC output voltmeter at 0 volts (This meter is located at the top right side of the inverter)

Determines AC output meter is at 0 volts At the associated 125V DC switchgear, open the Inverter DC Supply Breaker: 1/2B01-10

1. Rotates hand switch to the TRIP position OR depresses trip push button
2. Red light - OFF, Green light - ON, Amber light - OFF OR,
3. Green 1 Open flag - VISIBLE
  • STEP 28 RNO a.2)

Open associated battery breaker after inverter(s) shutdown CUE:

If asked, The 55 reports "inverter 112BD1112 has been shutdown" Standard:

Opens breaker 1/2BD1-01 by:

1. rotating hand switch to the TRIP position - OR - depressing trip push button
2. Red light - OFF, Green light - ON, Amber light - OFF.

OR

3. Green 1 Open flag - VISIBLE Comment:

4 4.3.2.5 CUE:

Standard:

Comment:

  • 4.3.2.6 Standard:

Comment:

19100-C Check inverter completely shutdown, by observing zero volts on the Inverter AC OUTPUT Voltmeter.

When asked, indicate AC output voltmeter at 0 volts (This meter is located at the top right side of the inverter)

Determines AC output meter is at 0 volts At the associated 125V DC switchgear, open the Inverter DC Supply Breaker: 1/2B01-10

1. Rotates hand switch to the TRIP position OR depresses trip push button
2. Red light - OFF, Green light - ON, Amber light - OFF OR,
3. Green 1 Open flag - VISIBLE
  • STEP 28 RNO a.2)

Open associated battery breaker after inverter(s) shutdown CUE:

If asked, The 55 reports "inverter 112BD1112 has been shutdown" Standard:

Opens breaker 1/2BD1-01 by:

1. rotating hand switch to the TRIP position - OR - depressing trip push button
2. Red light - OFF, Green light - ON, Amber light - OFF.

OR

3. Green 1 Open flag - VISIBLE Comment:

4

STEP 28b RNO:

As time permits, perform the following:.........

CUE:

"The SS will have another operator continue the procedure" Standard:

Comment:

Student reports to SS that Inverter 1/2B0112 has been shut down per 13431-1/2 and that the battery breaker for 1/2B01 has been opened.

Standard: N/A Comment:

Terminating cue:

Student returns initiating cue sheet 5

STEP 28b RNO:

As time permits, perform the following:.........

CUE:

"The SS will have another operator continue the procedure" Standard:

Comment:

Student reports to SS that Inverter 1/2B0112 has been shut down per 13431-1/2 and that the battery breaker for 1/2B01 has been opened.

Standard: N/A Comment:

Terminating cue:

Student returns initiating cue sheet 5

Verification of Completion Job Performance Measure No. V-RQ-JP-13431-001 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: -------------------------------------------------------------

Response: __________________________________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date:

6 Verification of Completion Job Performance Measure No. V-RQ-JP-13431-001 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: --------------------------------------------

Response: ____________________________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date: _____________ ___

6

Initial Conditions:

Unit 1/2 control room has experienced a prolonged loss of All AC Power, 125V 1E DC Bus 1/2BD1 voltage is currently reading 103V DC.

Initiating Cue:

You have been directed by the 55 to perform step 28 of 19100-C, "loss of All AC Power".

7 Initial Conditions:

Unit 1/2 control room has experienced a prolonged loss of All AC Power, 125V 1E DC Bus 1/2BD1 voltage is currently reading 103V DC.

Initiating Cue:

You have been directed by the 55 to perform step 28 of 19100-C, "loss of All AC Power".

7

Job Performance Measure "K" Facility: Vogtle Task No: V-LO-TA-37051 Task

Title:

Bypass Containment Hi-1 following a Loss of Heat Sink JPM No: V-RQ-JP-13509-001 KIA

Reference:

012A4.03 Examinee:

NRC Examiner: _________ __

Facility Evaluator:

Date: ------------------

Method of testing:

Simulated Performance Actual Performance Classroom ______ __

Simulator _____ _

Plant _________ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

While responding to a Loss of Heat Sink on Unit 1/2, Containment pressure reached the Hi-1 set point. The crew is preparing to establish feed water flow in accordance with step 19 of 19231-C.

Task Standard:

Student locates and bypasses Containment Hi-1 pressure channel bistables 112 - PB936B and 112 - PB935B per SOP 13509-C Required Materials:

1.
2.
3.

General

References:

None SOP 13509-C (2 copies of section 4.2.1 needed)

NSSS protection cabinet key 2 BTl panel bypass keys Initiating Cue:

The SS has directed you to "Bypass Containment Hi-1 pressure channels 1/2 - PB936B and 1/2 - PB935B by initiating 13509-C."

Time Critical Task:

No Validation Time:

1 0 minutes 1

Job Performance Measure "K" Facility: Vogtle Task No: V-LO-TA-37051 Task

Title:

Bypass Containment Hi-1 following a Loss of Heat Sink JPM No: V-RQ-JP-13509-001 KIA

Reference:

012A4.03 Examinee:

NRC Examiner:

Facility Evaluator: ________ _

Date: ____________ _

Method of testing:

Simulated Performance Actual Performance Classroom _____ _

Simulator _____ _

Plant _____ _

Read to the examinee:

I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues.

When you complete the task successfully, the objective for this job performance measure will be satisfied.

Initial Conditions:

While responding to a Loss of Heat Sink on Unit 1/2, Containment pressure reached the Hi-1 set point. The crew is preparing to establish feed water flow in accordance with step 19 of 19231-C.

Task Standard:

Student locates and bypasses Containment Hi-1 pressure channel bistables 112 - PB936B and 112 - PB935B per SOP 13509-C Required Materials:

1.
2.
3.

General

References:

None SOP 13509-C (2 copies of section 4.2.1 needed)

NSSS protection cabinet key 2 BTl panel bypass keys Initiating Cue:

The SS has directed you to "Bypass Containment Hi-1 pressure channels 1/2 - PB936B and 1/2 - PB935B by initiating 13509-C."

Time Critical Task:

No Validation Time:

1 0 minutes 1

Performance Information Critical steps denoted with an asterisk Student determines that section 4.2.1 of 13509-C is applicable Standard:

Section 4.2.1 referenced Comment:

Student reviews 13509-C precautions and limitations:

2.1.2

........ Multiple BTl Keys may also be used as needed to respond to abnormal or emergency plant conditions.

2.1.4 The NSSS and BOP BTl Annunciators will illuminate when the Key Lock is placed in BYPASS ENABLE OR a BTl switch is placed in the BYPASS position.

NSSS/BOP BTl switch LEOs will illuminate when the Key Lock is in BYPASS ENABLE ANO individual BTl switch is in BYPASS.

2.1.6 To provide a reasonable assurance that a channel has been bypassed, the BTl annunciator (on ALB04 or ALB05) and the BTl switch LEOs must be illuminated.

If a channel will be tripped or is already tripped, the TSLB should remain extinguished while bypassed.

Standard:

N/A Comment:

  • 4.2.1.1 Standard:

Comment:

Student notes CAUTION at beginning of section 4.2.1 for LCO 3.0.3 Circle the bistable(s} to be bypassed, on Checklist 1 (2,3,4) for the applicable channel.

Student circles PB-936B on checklist 2 and PB-935B on checklist 3 2

Performance Information Critical steps denoted with an asterisk Student determines that section 4.2.1 of 13509-C is applicable Standard:

Section 4.2.1 referenced Comment:

Student reviews 13509-C precautions and limitations:

2.1.2

........ Multiple BTl Keys may also be used as needed to respond to abnormal or emergency plant conditions.

2.1.4 The NSSS and BOP BTl Annunciators will illuminate when the Key Lock is placed in BYPASS ENABLE OR a BTl switch is placed in the BYPASS position.

NSSS/BOP BTl switch LEOs will illuminate when the Key Lock is in BYPASS ENABLE ANO individual BTl switch is in BYPASS.

2.1.6 To provide a reasonable assurance that a channel has been bypassed, the BTl annunciator (on ALB04 or ALB05) and the BTl switch LEOs must be illuminated.

If a channel will be tripped or is already tripped, the TSLB should remain extinguished while bypassed.

Standard:

N/A Comment:

  • 4.2.1.1 Standard:

Comment:

Student notes CAUTION at beginning of section 4.2.1 for LCO 3.0.3 Circle the bistable(s} to be bypassed, on Checklist 1 (2,3,4) for the applicable channel.

Student circles PB-936B on checklist 2 and PB-935B on checklist 3 2

4.2.1.1 Standard:

Comment:

4.2.1.2 CUE:

Standard:

Comment:

  • 4.2.1.3 For I&C surveillances, Refer To I&C procedure Step 3.2 or 3.3.

Student marks this step as N/A For the bistable(s) circled on Checklist 1 (2,3,4), obtain the SS authorization to bypass,. Document on Checklist 1 (2,3,4).

The SS has authorized bypass of PB935B and 936B and signed the checklist.

Student requests SS to sign the SS AUTH. Block on Checklist 2 for PB936B and Checklist 3 for PB-935B Obtain the BTl Enable Key from the 55.

Standard:

Requests BTl enable key from the SS.

NOTE:

Student may also request NSSS protection cabinet key if these panel doors are locked. These keys are held by the control room operators.

Comment:

Reviews precautions 2.1.1 and 2.1.2 as directed by a note in the procedure Standard:

N/A Comment:

3 4.2.1.1 Standard:

Comment:

4.2.1.2 CUE:

Standard:

Comment:

  • 4.2.1.3 For I&C surveillances, Refer To I&C procedure Step 3.2 or 3.3.

Student marks this step as N/A For the bistable(s) circled on Checklist 1 (2,3,4), obtain the SS authorization to bypass,. Document on Checklist 1 (2,3,4).

The SS has authorized bypass of PB935B and 936B and signed the checklist.

Student requests SS to sign the SS AUTH. Block on Checklist 2 for PB936B and Checklist 3 for PB-935B Obtain the BTl Enable Key from the 55.

Standard:

Requests BTl enable key from the SS.

NOTE:

Student may also request NSSS protection cabinet key if these panel doors are locked. These keys are held by the control room operators.

Comment:

Reviews precautions 2.1.1 and 2.1.2 as directed by a note in the procedure Standard:

N/A Comment:

3

4.2.1.4 Standard:

Comment:

4.2.1.5 Standard:

Comment:

4.2.1.6

a.
b.

Standard:

Comment:

Except as noted in 2.1.1, verify no other channel NSSS AND BOP BTl Panels are in the bypass condition WHEN in Modes 1-4.

Requests a concurrent verification and Verifies all NSSS and BOP BTl annunciator windows are dark.

Reviews NOTE prior step 4.2.1.5 On the BTl Panel on which bypassing is desired, verify all BTl switches are in the NORMAL position.

Verifies all switches on either BTl channel 2 or 3 panel are in the normal (down) position On the BTl NSSS Panel on which bypassing is desired:

Verify the circuit breaker is in the ON position, Verify power LED is illuminated.

Verifies BTl circuit breaker is on (upper portion of rocker switch in flush with panel) and the LED inside the switch is illuminated.

4 4.2.1.4 Standard:

Comment:

4.2.1.5 Standard:

Comment:

4.2.1.6

a.
b.

Standard:

Comment:

Except as noted in 2.1.1, verify no other channel NSSS AND BOP BTl Panels are in the bypass condition WHEN in Modes 1-4.

Requests a concurrent verification and Verifies all NSSS and BOP BTl annunciator windows are dark.

Reviews NOTE prior step 4.2.1.5 On the BTl Panel on which bypassing is desired, verify all BTl switches are in the NORMAL position.

Verifies all switches on either BTl channel 2 or 3 panel are in the normal (down) position On the BTl NSSS Panel on which bypassing is desired:

Verify the circuit breaker is in the ON position, Verify power LED is illuminated.

Verifies BTl circuit breaker is on (upper portion of rocker switch in flush with panel) and the LED inside the switch is illuminated.

4

  • 4.2.1.7
a.
b.
c.

Standard:

Comment:

4.2.1.8 Standard:

Comment:

4.2.1.9 Standard:

Comment:

Notes that ALB05-B02 (C02) NSSS PROT GR II (III) BYPASS alarm is expected in the following step Perform the following:

Insert the BTl Enable Key in the Key Lock, Place in the BYPASS ENABLE position, Verify LED illuminates.

Inserts BTl key into the bypass enable switch for channel II (III) panel and rotates the switch clockwise. Verifies LED immediately above the bypass enable switch illuminates.

Verify the annunciator for the applicable BTl NSSS Channel enabled illuminates:

NSSS PROT GR II BYPASS (ALB-05-B02)

OR NSSS PROT GR III BYPASS (ALB-05-C02)

Verifies NSSS PROT GR II (III) BYPASS window is alarming Notify the SS that performance of the next step may require entry into one or more functional units of TS LCOs 3.3.1 AND/OR 3.3.2.

Notifies SS 5

  • 4.2.1.7
a.
b.
c.

Standard:

Comment:

4.2.1.8 Standard:

Comment:

4.2.1.9 Standard:

Comment:

Notes that ALB05-B02 (C02) NSSS PROT GR II (III) BYPASS alarm is expected in the following step Perform the following:

Insert the BTl Enable Key in the Key Lock, Place in the BYPASS ENABLE position, Verify LED illuminates.

Inserts BTl key into the bypass enable switch for channel II (III) panel and rotates the switch clockwise. Verifies LED immediately above the bypass enable switch illuminates.

Verify the annunciator for the applicable BTl NSSS Channel enabled illuminates:

NSSS PROT GR II BYPASS (ALB-05-B02)

OR NSSS PROT GR III BYPASS (ALB-05-C02)

Verifies NSSS PROT GR II (III) BYPASS window is alarming Notify the SS that performance of the next step may require entry into one or more functional units of TS LCOs 3.3.1 AND/OR 3.3.2.

Notifies SS 5

  • 4.2.1.10 Standard:

Comment:

4.2.1.11 Standard:

Comment:

4.2.1.12 Standard:

Comment:

4.2.1.13 Standard:

Comment:

Place BTl NSSS Switch(es) circled in Step 4.2.1.1 to the BYPASS position.

Document on Checklist 1 (2, 3, 4). (CV REQUIRED)

Requests a concurrent verification and then moves toggle switch 34 for PB-936B (PB-935B) to the up position.

Verify BTl Switch LEDs are illuminated for Switch(es) in the BYPASS position.

Request concurrent verification and verifies LED immediately above toggle switch 34 for PB-936B (PB-935B) is illuminated.

For the channel bistable(s) bypassed on Checklist 1 (2,3,4), verify the TSLB(s) is extinguished.

Verifies TSLB 4,10.2 (10.3) is extinguished.

Notify SS to document the time of channel bypass in the Shift Supervisor Logbook.

SS notified to document time channel was bypassed.

6

  • 4.2.1.10 Standard:

Comment:

4.2.1.11 Standard:

Comment:

4.2.1.12 Standard:

Comment:

4.2.1.13 Standard:

Comment:

Place BTl NSSS Switch(es) circled in Step 4.2.1.1 to the BYPASS position.

Document on Checklist 1 (2, 3, 4). (CV REQUIRED)

Requests a concurrent verification and then moves toggle switch 34 for PB-936B (PB-935B) to the up position.

Verify BTl Switch LEDs are illuminated for Switch(es) in the BYPASS position.

Request concurrent verification and verifies LED immediately above toggle switch 34 for PB-936B (PB-935B) is illuminated.

For the channel bistable(s) bypassed on Checklist 1 (2,3,4), verify the TSLB(s) is extinguished.

Verifies TSLB 4,10.2 (10.3) is extinguished.

Notify SS to document the time of channel bypass in the Shift Supervisor Logbook.

SS notified to document time channel was bypassed.

6

4.2.1.14 Standard:

Comment:

4.2.1.1 Standard:

Comment:

4.2.1.2 Standard:

Comment:

WHEN surveillance testing is complete OR plant conditions require, restore the BTl NSSS Channel Switch(es) to NORMAL per Section 4.2.4 Student determines this step should not be performed until channel no longer requires bypassing.

If this step is performed, then it becomes critical and is unsatisfactory.

Student repeats section 4.2.1 for the second channel to be bypassed.

For I&C surveillances, Refer To I&C procedure Step 3.2 or 3.3.

Student marks this step as N/A For the bistable(s) circled on Checklist 1 (2, 3, 4), obtain the SS authorization to bypass,. Document on Checklist 1 (2,3,4).

Student requests SS to sign the SS AUTH. Block on Checklist 2 for PB-936B or Checklist 3 for PB-935B if not obtained when bypassing the first channel.

  • 4.2.1.3 Obtain the BTl Enable Key from the SS.

Standard:

Requests BTl enable key from the SS.

NOTE:

Student may also request NSSS protection cabinet key if these panel doors are locked. These keys are held by the control room operators.

Comment:

7 4.2.1.14 Standard:

Comment:

4.2.1.1 Standard:

Comment:

4.2.1.2 Standard:

Comment:

WHEN surveillance testing is complete OR plant conditions require, restore the BTl NSSS Channel Switch(es) to NORMAL per Section 4.2.4 Student determines this step should not be performed until channel no longer requires bypassing.

If this step is performed, then it becomes critical and is unsatisfactory.

Student repeats section 4.2.1 for the second channel to be bypassed.

For I&C surveillances, Refer To I&C procedure Step 3.2 or 3.3.

Student marks this step as N/A For the bistable(s) circled on Checklist 1 (2, 3, 4), obtain the SS authorization to bypass,. Document on Checklist 1 (2,3,4).

Student requests SS to sign the SS AUTH. Block on Checklist 2 for PB-936B or Checklist 3 for PB-935B if not obtained when bypassing the first channel.

  • 4.2.1.3 Obtain the BTl Enable Key from the SS.

Standard:

Requests BTl enable key from the SS.

NOTE:

Student may also request NSSS protection cabinet key if these panel doors are locked. These keys are held by the control room operators.

Comment:

7

Reviews precautions 2.1.1 and 2.1.2 as directed by a note in the procedure Standard:

N/A Comment:

4.2.1.4 Standard:

Comment:

4.2.1.5 Standard:

Comment:

4.2.1.6

a.
b.

Standard:

Comment:

Except as noted in 2.1.1, verify no other channel NSSS AND BOP BTl Panels are in the bypass condition WHEN in Modes 1-4.

Requests a concurrent verification and Verifies only the NSSS GR II (III) annunciator window is lit and all BOP BTl annunciator windows are dark.

Reviews NOTE prior step 4.2.1.5 On the BTl Panel on which bypassing is desired, verify all BTl switches are in the NORMAL position.

Verifies all switches on either BTl channel 2 or 3 panel are in the normal (down) position On the BTl NSSS Panel on which bypassing is desired:

Verify the circuit breaker is in the ON position, Verify power LED is illuminated.

Verifies BTl circuit breaker is on (upper portion of rocker switch in flush with panel) and the LED inside the switch is illuminated.

8 Reviews precautions 2.1.1 and 2.1.2 as directed by a note in the procedure Standard:

N/A Comment:

4.2.1.4 Standard:

Comment:

4.2.1.5 Standard:

Comment:

4.2.1.6

a.
b.

Standard:

Comment:

Except as noted in 2.1.1, verify no other channel NSSS AND BOP BTl Panels are in the bypass condition WHEN in Modes 1-4.

Requests a concurrent verification and Verifies only the NSSS GR II (III) annunciator window is lit and all BOP BTl annunciator windows are dark.

Reviews NOTE prior step 4.2.1.5 On the BTl Panel on which bypassing is desired, verify all BTl switches are in the NORMAL position.

Verifies all switches on either BTl channel 2 or 3 panel are in the normal (down) position On the BTl NSSS Panel on which bypassing is desired:

Verify the circuit breaker is in the ON position, Verify power LED is illuminated.

Verifies BTl circuit breaker is on (upper portion of rocker switch in flush with panel) and the LED inside the switch is illuminated.

8

Notes that ALB05-B02 (C02) NSSS PROT GR II (III) BYPASS alarm is expected in the following step

  • 4.2.1.7
a.
b.
c.

Standard:

Comment:

4.2.1.8 Standard:

Comment:

4.2.1.9 Standard:

Comment:

Perform the following:

Insert the BTl Enable Key in the Key Lock, Place in the BYPASS ENABLE position, Verify LED illuminates.

Inserts BTl key into the bypass enable switch for channel II (III) panel and rotates the switch clockwise. Verifies LED immediately above the bypass enable switch illuminates.

Verify the annunciator for the applicable BTl NSSS Channel enabled illuminates:

NSSS PROT GR " BYPASS (ALB-05-B02)

OR NSSS PROT GR III BYPASS (ALB-05-C02)

Verifies NSSS PROT GR II (III) BYPASS window is alarming Notify the SS that performance of the next step may require entry into one or more functional units of TS LCOs 3.3.1 AND/OR 3.3.2.

Notifies SS 9

Notes that ALB05-B02 (C02) NSSS PROT GR II (III) BYPASS alarm is expected in the following step

  • 4.2.1.7
a.
b.
c.

Standard:

Comment:

4.2.1.8 Standard:

Comment:

4.2.1.9 Standard:

Comment:

Perform the following:

Insert the BTl Enable Key in the Key Lock, Place in the BYPASS ENABLE position, Verify LED illuminates.

Inserts BTl key into the bypass enable switch for channel II (III) panel and rotates the switch clockwise. Verifies LED immediately above the bypass enable switch illuminates.

Verify the annunciator for the applicable BTl NSSS Channel enabled illuminates:

NSSS PROT GR " BYPASS (ALB-05-B02)

OR NSSS PROT GR III BYPASS (ALB-05-C02)

Verifies NSSS PROT GR II (III) BYPASS window is alarming Notify the SS that performance of the next step may require entry into one or more functional units of TS LCOs 3.3.1 AND/OR 3.3.2.

Notifies SS 9

  • 4.2.1.10 Standard:

Comment:

4.2.1.11 Standard:

Comment:

4.2.1.12 Standard:

Comment:

4.2.1.13 Standard:

Comment:

Place BTl NSSS Switch(es) circled in Step 4.2.1.1 to the BYPASS position.

Document on Checklist 1 (2, 3, 4). (CV REQUIRED)

Requests a concurrent verification and then moves toggle switch 34 for PB-936B (PB-935B) to the up position.

Verify BTl Switch LEDs are illuminated for Switch(es) in the BYPASS position.

Request concurrent verification and verifies LED immediately above toggle switch 34 for PB-936B (PB-935B) is illuminated.

For the channel bistable(s) bypassed on Checklist 1 (2,3,4), verify the TSLB(s) is extinguished.

Verifies TSLB 4, 10.2 (10.3) is extinguished.

Notify SS to document the time of channel bypass in the Shift Supervisor Logbook.

SS notified to document time channel was bypassed.

10

  • 4.2.1.10 Standard:

Comment:

4.2.1.11 Standard:

Comment:

4.2.1.12 Standard:

Comment:

4.2.1.13 Standard:

Comment:

Place BTl NSSS Switch(es) circled in Step 4.2.1.1 to the BYPASS position.

Document on Checklist 1 (2, 3, 4). (CV REQUIRED)

Requests a concurrent verification and then moves toggle switch 34 for PB-936B (PB-935B) to the up position.

Verify BTl Switch LEDs are illuminated for Switch(es) in the BYPASS position.

Request concurrent verification and verifies LED immediately above toggle switch 34 for PB-936B (PB-935B) is illuminated.

For the channel bistable(s) bypassed on Checklist 1 (2,3,4), verify the TSLB(s) is extinguished.

Verifies TSLB 4, 10.2 (10.3) is extinguished.

Notify SS to document the time of channel bypass in the Shift Supervisor Logbook.

SS notified to document time channel was bypassed.

10

4.2.1.14 Standard:

Comment:

WHEN surveillance testing is complete OR plant conditions require, restore the BTl NSSS Channel Switch(es) to NORMAL per Section 4.2.4 Student determines this step should not be performed until channel no longer requires bypassing.

If this step is performed, then it becomes critical and is unsatisfactory.

Terminating cue:

Student returns initiating cue sheet 11 4.2.1.14 Standard:

Comment:

WHEN surveillance testing is complete OR plant conditions require, restore the BTl NSSS Channel Switch(es) to NORMAL per Section 4.2.4 Student determines this step should not be performed until channel no longer requires bypassing.

If this step is performed, then it becomes critical and is unsatisfactory.

Terminating cue:

Student returns initiating cue sheet 11

Verification of Completion Job Performance Measure No. V-RQ-JP-13509-001 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: _____________________________ _

Response: ______________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date:

12 Verification of Completion Job Performance Measure No. V-RQ-JP-13509-001 Examinee's Name:

Examiner's Name:

Date Performed:

Number of Attempts:

Time to Complete:

Question Documentation:

Question: -------------------------------------------------------------

Response: __________________________________________________________ __

Result: Satisfactory/Unsatisfactory Examiner's signature and date: __________________________ ___

12

Initial Conditions:

While responding to a Loss of Heat Sink on Unit 1/2, Corttainment pressure reached the Hi-1 set point. The crew is preparing to establish feed water flow in accordance with step 190.1 19231-C.

Initiating Cue:

~~~'"

J;,I The SS has directed you to "Bypass Containment Hi-1 pressure channels 1/2 - PB936B and 1/2 - PB935B by initiating 13509-C."

13 Initial Conditions:

While responding to a Loss of Heat Sink on Unit 1/2, Corttainment pressure reached the Hi-1 set point. The crew is preparing to establish feed water flow in accordance with step 190.1 19231-C.

Initiating Cue:

~~~'"

J;,I The SS has directed you to "Bypass Containment Hi-1 pressure channels 1/2 - PB936B and 1/2 - PB935B by initiating 13509-C."

13