FACILITY NAME:

McGuire Nulear Plant Section 5 REPORTNUMBER: ____ ~O~5~OO~O~3~69~/~37~O~~=O~09~-~30~1~ ____ _

DRAFT SIM/IN-PLANT JPMS CONTE~TS:

!iZl' Draft SIMULATOR liN-PLANT JPMs Location of Electronic Files:

Submitted By: I~-,L--~---+-,,+------

FACILITY NAME:

McGuire Nulear Plant Section 5 REPORTNUMBER: ____ ~O~5~OO~O~3~69~~~7~O~~~O~09~-~30~1~ ____ _

DRAFT SIM/IN-PLANT JPMS CONTE~TS:

!if' Draft SIMULATOR liN-PLANT JPMs Location of Electronic Files:

Submitted By: I~-T--=-=-----+-->+------ Verified By--il--=......t-~'---;,-:I-_---"-""L..:....>",..L~h

Appendix C Job Performance Measure Worksheet Form ES-C-1 SIM JPM A 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C Job Performance Measure Worksheet Form ES-C-1 SIM JPM A 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C Facility:

McGuire Job Performance Measure Worksheet Task No.:

Form ES-C-1 Task

Title:

Emergency Borate the Reactor JPM No.:

2009 Systems - Control Coolant System Using the PD Pump Room JPM A KIA

Reference:

004, A4.18, 4.3/4.1 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The PD Pump is running and both Boric Acid Transfer Pumps running with 30 gpm or greater emergency boration flow indicated.

Required Materials:

None General

References:

EP/1/A/5000/FR-S.1, Response To Nuclear Power Generation/ATWS EP/1A/5000/G-1, Generic Enclosure -17, PD Pump Start 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C Facility:

Task

Title:

McGuire Job Performance Measure Worksheet Task No.:

Form ES-C-1 Emergency Borate the Reactor JPM No.:

2009 Systems - Control Coolant System Using the PO Pump Room JPM A KIA

Reference:

004, A4.18, 4.3/4.1 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

x Classroom X

Plant Simulator READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Initial Conditions:

Unit 1 was at 100% power with "A" NV pump tagged for maintenance.

A lockout occurred on Zone "1 B". Due to a relaying failure, busses 1 TB and 1TD failed to. swap to their alternate power source. The "1 B" DieselGenerator started and loaded 1 ETB.

The reactor cgolant pumps tripped on under frequency.

An automatic reactor trip FAILED to occur. EP/1/N5000/FR-S.1 (Response To Nuclear Power Generator/ATWS) has been imple.ruented and completed through Step 4.

LetcjoWn has been isolated per AP/11N5500/12 Loss of Letdown,

Charging or$eallnjection.

Th.e reactor ha$ just been tripped locally:

Task Standard:

The PO Pump is running and both Boric Acid Transfer Pumps running with 30 gpm or greater emergency boration flow indicated.

Required Materials:

None

(

General

References:

EP/1/N5000/FR-S.1, Response To Nuclear Power Generation/ATWS EP/1N5000/G-1, Generic Enclosure -17, PO Pump Start 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C Handouts:

Time Critical Task:

Validation Time:

Job Performance Measure Worksheet Form ES-C-1 EP/1/N5000/FR-S.1, Response To Nuclear Power Generation/ATWS marked up for place-keeping through Step 4.

NO 20 minutes 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C Handouts:

initiating Cue:

Time Critical Task:

Validation Time:

Job Performance Measure Worksheet Form ES-C-1 EP/1 IA/SOOO/FR-S. 1, Response To Nuclear Power Generation/ATWS marked up for place-keeping through Step 4.

The CRSRO ha~ directed you to emergency borate the NC System in accordance with Step S of EP/1/A/SOOO/FR-S.1, Response To Nuclear Generator/A TWS.

NO 20 minutes 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C Job Performance Measure Worksheet SIMULATOR OPERATIONAL GUIDELINES

1.

Reset to IC # 39, 100% Power, MOL. Go to RUN.

2.

Insert:

a.
b.

MALF-IPE001A MALF-IPE001 B MALF-IPE002A MALF-IPE002B Failure of Auto Reactor Trips - Train A Failure of Auto Reactor Trips - Train B Failure of Manual Reactor Trips - Train A Failure of Manual Reactor Trips - Train B Form ES-C-1

c.

MALF-NV029B NV pump trips on over current set to trigger 1 delay of 15 seconds

d.

MALF-EP003C Zone 1 B Lockout set to trigger 1.

e.

MALF-EP006B MALF-EP006D Failure of 1 TB to auto swap Failure of 1 TD to auto swap

f.

LOA-NV046 Pump Rack out 1A NV pump; Place red tag sticker on 1A NV

3.

Actuate Trigger 1.

4.

Manually exercise AlB Reactor Trip Switches.

5.

Perform steps 1 through 4 of EP/1/Al5000/FR-S.1.

6.

Trip the reactor 1 minute after starting the JPM by deleting:

MALF-IPE001A, Failure of Auto Reactor Trips - Train A MALF-IPE001 B, Failure of Auto Reactor Trips - Train B

7.

Ensure Letdown isolated.

8.

Allow plant time to stabilize and then Freeze Simulator.

1. Reset Simulator to Temporary Snap IC-122 (December, 2008).
2. Momentarily place Simulator in Run to acknowledge alarms.
3. Leave Simulator in FREEZE until operator is ready to begin.

NOTE:

During the performance of this JPM, the simulator operator will need to control CA flow to avoid NCS Cool down and SI actuation.

2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C Job Performance Measure Worksheet SIMULATOR OPERATIONAL GUIDELINES

1.

Reset to IC # 39, 100% Power, MOL. Go to RUN.

2.

Insert:

a.
b.

MALF-IPE001A MALF-IPE001 B MALF-IPE002A MALF-IPE002B Failure of Auto Reactor Trips - Train A Failure of Auto Reactor Trips - Train B Failure of Manual Reactor Trips - Train A Failure of Manual Reactor Trips - Train B Form ES-C-1

c.

MALF-NV029B NV pump trips on over current set to trigger 1 delay of 15 seconds

d.

MALF-EP003C Zone 1 B Lockout set to trigger 1.

e.

MALF-EP006B MALF-EP006D Failure of 1TB to auto swap Failure of 1TD to auto swap

f.

LOA-NV046 Pump Rack out 1A NV pump; Place red tag sticker on 1A NV

3.

Actuate Trigger 1.

4.

Manually exercise AJB Reactor Trip Switches.

5.

Perform steps 1 through 4 of EP/1/AJ5000/FR-S.1.

6.

Trip the reactor 1 minute after starting the JPM by deleting:

MALF-IPE001A, Failure of Auto Reactor Trips - Train A MALF-IPE001 B, Failure of Auto Reactor Trips - Train B

7.

Ensure Letdown isolated.

8.

Allow plant time to stabilize and then Freeze Simulator.

1. Reset Simulator to Temporary Snap IC-122 (December, 2008).
2. Momentarily place Simulator in Run to acknowledge alarms.
3. Leave Simulator in FREEZE until operator is ready to begin.

NOTE:

During the performance of this JPM, the simulator operator will need to control CA flow to avoid NCS Cooldown and SI actuation.

2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C Page 5 of 16 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout EP/1/Al5000/FR-S.1, Response To Nuclear Power Generation/ATWS marked up for place-keeping through step 4.

START TIME:

STEPS ELEMENTS STANDARD S/U COMMENTS REQUIRED FOR UNSAT Simulator Instructor NOTE: Leave Simulator in FREEZE until operator is ready to begin.

1 (Step 5) Initiate emergency The operator recognizes boration of the NC System:

that there are no NV Pumps operating and proceeds to (Step 5.a) Ensure one NV Step 5.a RNO.

Pump-ON.

2 (Step 5.a RNO) Place PD The operator seeks to find pump in service PER EP/1/A/5000/G-1 (Generic EP/1/A/5000/G-1 (Generic Enclosures), Enclosure 17.

Enclosures), Enclosure 17 (PD Pump Startup).

3 (Enclosure 17, Step 1)

The operator observes that Check power available to the Green status light is LIT, PD pump - AVAILABLE.

and determines that power is available to the PD Pump.

2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C Page 5 of 16 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout EP/1/Al5000/FR-S.1, Response To Nuclear Power Generation/ATWS marked up for place-keeping through step 4.

START TIME:

STEPS ELEMENTS STANDARD S/U COMMENTS REQUIRED FOR UNSAT Simulator Instructor NOTE: Leave Simulator in FREEZE until operator is ready to begin.

1 (Step 5) Initiate emergency The operator recognizes boration of the NC System:

that there are no NV Pumps operating and proceeds to (Step 5.a) Ensure one NV Step 5.a RNO.

Pump - ON.

2 (Step 5.a RNO) Place PD The operator seeks to find pump in service PER EP/1/A/5000/G-1 (Generic EP/1/A/5000/G-1 (Generic Enclosures), Enclosure 17.

Enclosures), Enclosure 17 (PD Pump Startup).

3 (Enclosure 17, Step 1)

The operator observes that Check power available to the Green status light is LIT, PD pump - AVAILABLE.

and determines that power is available to the PD Pump.

2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C STEPS 4

5 Page 6 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Steps 2.a-d) Reset the The operator observes that following:

the SI reset lights are LIT.

SII The operator observes that Sequencers the A Train Sequencer reset Phase B Isolation light is LIT.

If at any time a B/O signal The operator depresses the occurs then start SII B Train Sequencer reset equipment previously on.

pushbutton and observes that the Sequencer reset light is LIT.

The operator observes that the Phase B Isolation reset lights are LIT.

(Step 3) Close the following:

The operator observes the Close 1 RN-279B (AB Vent 1 RN-279B Green status Sys Return Isol).

light LIT, Red status light OFF.

Close 1 RN-299A (AB Vent The operator depresses the 1 RN-299A CLOSE Sys Return Isol).

pushbutton and observes Green status light LIT, Red status light OFF.

Close 1 RV-79A (U1 VU The operator depresses AHUS RV Cont Outside and holds the 1 RV-79A Supply Hdr Isol).

CLOSE pushbutton and observes Green status light LIT, Red status light OFF.

The operator depresses Close 1RV-101A (U1 VU and holds the 1 RV-1 01A AHUS RV Cont Inside CLOSE pushbutton and Return Hdr Isol).

observes Green status light LIT, Red status light OFF.

Close 1 RV-32A (U1 VLIVT The operator depresses the 1 RV-32A CLOSE AHUS RV Cont Outside pushbutton and observes Supply Hdr Isol).

Green status light LIT, Red status light OFF.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C STEPS 4

5 Page 6 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Steps 2.a-d) Reset the The operator observes that following:

the SI reset lights are LIT.

SII The operator observes that Sequencers the A Train Sequencer reset Phase B Isolation light is LIT.

If at any time a B/O signal The operator depresses the occurs then start SII B Train Sequencer reset equipment previously on.

pushbutton and observes that the Sequencer reset light is LIT.

The operator observes that the Phase B Isolation reset lights are LIT.

(Step 3) Close the following:

The operator observes the Close 1 RN-279B (AB Vent 1 RN-279B Green status Sys Return Isol).

light LIT, Red status light OFF.

Close 1 RN-299A (AB Vent The operator depresses the 1 RN-299A CLOSE Sys Return Isol).

pushbutton and observes Green status light LIT, Red status light OFF.

Close 1 RV-79A (U1 VU The operator depresses AHUS RV Cont Outside and holds the 1 RV-79A Supply Hdr Isol).

CLOSE pushbutton and observes Green status light LIT, Red status light OFF.

The operator depresses Close 1 RV-1 01A (U1 VU and holds the 1 RV-1 01A AHUS RV Cont Inside CLOSE pushbutton and Return Hdr Isol).

observes Green status light LIT, Red status light OFF.

Close 1 RV-32A (U1 VLNT The operator depresses the 1 RV-32A CLOSE AHUS RV Cont Outside pushbutton and observes Supply Hdr Isol).

Green status light LIT, Red status light OFF.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C STEPS 5

(Cont'd) 6 Page 7 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD The operator depresses the Close 1 RV-76A (U1 VLNT 1 RV-76A CLOSE AHUS RV Cont Inside pushbutton and observes Return Hdr Isol).

Green status light LIT, Red status light OFF.

The operator depresses Close 1 RV-80B (U1 VU and holds the 1 RV-80B AHUS RV Cont Inside CLOSE pushbutton and Supply Hdr Isol).

observes Green status light LIT, Red status light OFF.

The operator depresses Close 1 RV-1 02B (U1 VU and holds the 1 RV-1 02B AHUS RV Cont Outside CLOSE pushbutton and Return Hdr Isol).

observes Green status light LIT, Red status light OFF.

The operator depresses the Close 1 RV-33B (U1 VLNT 1 RV-33B CLOSE AHUS RV Cont Inside pushbutton and observes Supply Hdr Isol).

Green status light LIT, Red status light OFF.

The operator depresses the Close 1 RV-77B (U1 VLNT 1 RV-77B CLOSE pushbutton and observes AHUS RV Cont Outside Green status light LIT, Red Return Hdr Isol).

status light OFF.

Note:

Sinc~thesesteps are bull~led, the operator neednotvv:aitforthe....*

valve to cpmpletely cycle betore.~aking~ctiol1with..

the next valve, (Step 4) Check any NC The operator observes the pump -ON NC Pump Safety breakers Green status light LIT, Red status lights OFF, determines that no NC pumps are on and proceeds to the Step 4 RNO.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C STEPS 5

(Cont'd) 6 Page 7 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD The operator depresses the Close 1 RV-76A (U 1 VLNT 1 RV-76A CLOSE AHUS RV Cont Inside pushbutton and observes Return Hdr Isol).

Green status light LIT, Red status light OFF.

The operator depresses Close 1 RV-80B (U 1 VU and holds the 1 RV-80B AHUS RV Cont Inside CLOSE pushbutton and Supply Hdr Isol).

observes Green status light LIT, Red status light OFF.

The operator depresses Close 1 RV-1 02B (U 1 VU and holds the 1 RV-1 02B AHUS RV Cont Outside CLOSE pushbutton and Return Hdr Isol).

observes Green status light LIT, Red status light OFF.

The operator depresses the Close 1 RV-33B (U1 VLNT 1 RV-33B CLOSE AHUS RV Cont Inside pushbutton and observes Supply Hdr Isol).

Green status light LIT, Red status light OFF.

The operator depresses the Close 1 RV-77B (U1 VLNT 1 RV-77B CLOSE pushbutton and observes AHUS RV Cont Outside Green status light LIT, Red Return Hdr Isol).

status light OFF.

Note:

Since these steps are bulleted, the operator need not wait for the valve to completely cycle before taking action with the next valve.

(Step 4) Check any NC The operator observes the pump -ON NC Pump Safety breakers Green status light LIT, Red status lights OFF, determines that no NC pumps are on and proceeds to the Step 4 RNO.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C STEPS

  • 7 8

9 10 Page 8 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 4 RNO) Close the following:

The operator depresses and holds the 1 RN-252B 1 RN-252B (RB Non Ess CLOSE pushbutton and Sup Cont Outside Isol) observes Green status light LIT, Red status light OFF.

The operator depresses 1 RN-277B (RB Non Ess and holds the 1 RN-277B Ret Cont Outside Isol)

CLOSE pushbutton and observes Green status light LIT, Red status light OFF.

(Step 5) Place the following The operator depresses the RF pumps in "MAN" and A RF Jockey Pump MAN ensure they are off:

pushbutton and observes the Green status light is LIT, A Jockey pump Red status light OFF.

B Jockey pump The operator depresses the B RF Jockey Pump MAN pushbutton and observes the Green status light is LIT, Red status light OFF.

(Step 6) Dispatch operator The operator contacts an to close 2RL-267 (Unit 2 NEO and directs that 2RL-6900V Swgr Room AHU 267 be closed.

Supply From RN Inlet Isol)

(service bldg, 739+5, U-31, Cue:

NE corner of service bldg over pit, near KR storage Art*oper~torh~~.been tank).

di$patched to close~~L~

267~

(Caution prior to Step 7)

The operator reads Caution Both trains RN valves must and proceeds to Note prior be aligned in Step 7 unless to Step 7.

specified otherwise, even if power is lost.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C STEPS

  • 7 8

9 10 Page 8 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 4 RNO) Close the following:

The operator depresses and holds the 1 RN-252B 1 RN-252B (RB Non Ess CLOSE pushbutton and Sup Cont Outside 1501) observes Green status light LIT, Red status light OFF.

The operator depresses 1 RN-277B (RB Non Ess and holds the 1 RN-277B Ret Cont Outside 1501)

CLOSE pushbutton and observes Green status light LIT, Red status light OFF.

(Step 5) Place the following The operator depresses the RF pumps in "MAN" and A RF Jockey Pump MAN ensure they are off:

pushbutton and observes the Green status light is LIT, A Jockey pump Red status light OFF.

B Jockey pump The operator depresses the B RF Jockey Pump MAN pushbutton and observes the Green status light is LIT, Red status light OFF.

(Step 6) Dispatch operator The operator contacts an to close 2RL-267 (Unit 2 NEO and directs that 2RL-6900V Swgr Room AHU 267 be closed.

Supply From RN Inlet Isol)

(service bldg, 739+5, U-31, Cue:

NE corner of service bldg over pit, near KR storage An operator has been tank).

dispatched to close 2RL-267.

(Caution prior to Step 7)

The operator reads Caution Both trains RN valves must and proceeds to Note prior be aligned in Step 7 unless to Step 7.

specified otherwise, even if power is lost.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C STEPS 11 12 13 Page 9 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Note prior to Step 7) If The operator reads Note OAC is unavailable to check and proceeds to Step 7.

any deenergized valve positions, RNO contains required actions if position unknown.

(Steps 7/7.a) Align RN to The operator observes that "AB Non Essential Header" the 1A RN Pump Red as follows:

Breaker status light is LIT.

Ensure 1A RN pump - ON.

(Step 7.b) Check at least one of the following valves -

closed:

The operator observes that 1 RN-41 B (Train B To Non the Green status light is LIT, Ess Hdr Isol) and the Red status light is OFF.

OR 1 RN-43A (Train B To Non The operator observes that the Red status light is LIT, Ess Hdr Isol).

and the Green status light is OFF.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

(

{

\\

Appendix C STEPS 11 12 13 Page 9 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Note prior to Step 7) If The operator reads Note OAC is unavailable to check and proceeds to Step 7.

any deenergized valve positions, RNO contains required actions if position unknown.

(Steps 7/7.a) Align RN to The operator observes that "AB Non Essential Header" the 1A RN Pump Red as follows:

Breaker status light is LIT.

Ensure 1A RN pump - ON.

(Step 7.b) Check at least one of the following valves -

closed:

The operator observes that 1RN-41B (Train B To Non the Green status light is LIT, Ess Hdr Isol) and the Red status light is OFF.

OR 1 RN-43A (Train B To Non The operator observes that the Red status light is LIT, Ess Hdr Isol).

and the Green status light is OFF.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C STEPS

  • 14
  • 15 16 Page 10 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 7.c.1-4) Open the following valves:

Open 1 RN-40A (Train A to The operator observes the Non Ess Hdr Isol) 1 RN-40A Red status light LIT, Green status light OFF.

Open 1 RN-42A (AS Non The operator observes the Ess Supply Isol) 1 RN-42A Red status light LIT, Green status light OFF.

The operator depresses the Open 1 RN-63S (AS Non 1 RN-63S OPEN pushbutton Ess Return Isol) and observes Red status light LIT, Green status light OFF.

1 RN-64A (AS Non Ess The operator depresses the 1 RN-64A OPEN pushbutton Return Isol) and observes Red status light LIT, Green status light OFF.

(Step 7.d) Check 1A RN The operator observes that pump flow as follows:

the 1A RN Pump suction valves are OPEN (Red If RN pump suction aligned status lights LIT, Green to Low Level Intake, then status lights OFF).

check 1A RN pump flow -

less than 16,000 gpm.

The operator observes 1 A OR RN flow (1 RNP-5040) to be

5500 gpm.

If RN pump suction aligned to SNSWP.....

(Step 7.e) GO TO Step 8.

The operator proceeds to Step 8.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

(

Appendix C STEPS

  • 14
  • 15 16 Page 10 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 7.c.1-4) Open the following valves:

Open 1 RN-40A (Train A to The operator observes the Non Ess Hdr Isol) 1 RN-40A Red status light LIT, Green status light OFF.

Open 1 RN-42A (AS Non The operator observes the Ess Supply Isol) 1 RN-42A Red status light LIT, Green status light OFF.

The operator depresses the Open 1 RN-63S (AS Non 1 RN-63S OPEN pushbutton Ess Return Isol) and observes Red status light LIT, Green status light OFF.

1 RN-64A (AS Non Ess The operator depresses the 1 RN-64A OPEN pushbutton Return Isol) and observes Red status light LIT, Green status light OFF.

(Step 7.d) Check 1A RN The operator observes that pump flow as follows:

the 1A RN Pump suction valves are OPEN (Red If RN pump suction aligned status lights LIT, Green to Low Level Intake, then status lights OFF).

check 1A RN pump flow -

less than 16,000 gpm.

The operator observes 1A OR RN flow (1 RNP-5040) to be

5500 gpm.

If RN pump suction aligned to SNSWP.....

(Step 7.e) GO TO Step 8.

The operator proceeds to Step 8.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C STEPS 17 18 19

  • 20
  • 21 Page 11 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 8) Check if NV S/I The operator observes the flow path is open as follows:

Green status light LIT for both valves, determines that 1 NI-9A (NC Cold Leg Inj neither valve is OPEN, and From NV) - OPEN proceeds to the Step 8 RNO.

OR 1 NI-1 OB (NC Cold Leg Inj From NV) - OPEN (Step 8 RNO a-b) Perform The operator observes that the following:

both NV Pump Green status IF 1A AND 1B NV pumps lig hts are lit, Red status OFF, THEN open 1NV-241 lights are OFF.

(Seal Inj Flow Control)

The operator adjusts the 1 NV-241 controller output to GO TO step 10.

100% (Both Red and Black Needles to 100%).

The operator proceeds to Step 10.

(Step 10) Place "PO pump The operator observes the speed control" in "MAN" and PO Pump Speed Controller set for minimum speed.

in MANUAL (Green and Yellow lights LIT) and observes controller output for minimum speed (0%

output).

(Step 11) Open 1 NV-1047A The operator depresses the (PO PUMP Recirculation) 1 NV-1047A OPEN pushbutton and observes Red status light LIT, Green status light OFF.

(Step 12) Start the PO The operator depresses the Pump.

PO Pump START pushbutton and observes the Red status light LIT, Green status light OFF.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

Appendix C STEPS 17 18 19

  • 20
  • 21 Page 11 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 8) Check if NV S/I The operator observes the flow path is open as follows:

Green status light LIT for both valves, determines that 1 NI-9A (NC Cold Leg Inj neither valve is OPEN, and From NV) - OPEN proceeds to the Step 8 RNO.

OR 1 NI-1 OB (NC Cold Leg Inj From NV) - OPEN (Step 8 RNO a-b) Perform The operator observes that the following:

both NV Pump Green status IF 1AAND 1B NVpumps lights are lit, Red status OFF, THEN open 1NV-241 lights are OFF.

(Seal Inj Flow Control)

The operator adjusts the 1 NV-241 controller output to GO TO step 10.

100% (Both Red and Black Needles to 100%).

The operator proceeds to Step 10.

(Step 10) Place "PO pump The operator observes the speed control" in "MAN" and PO Pump Speed Controller set for minimum speed.

in MANUAL (Green and Yellow lights LIT) and observes controller output for minimum speed (0%

output).

(Step 11) Open 1 NV-1 047 A The operator depresses the (PO PUMP Recirculation) 1 NV-1047A OPEN pushbutton and observes Red status light LIT, Green status light OFF.

(Step 12) Start the PO The operator depresses the Pump.

PO Pump START pushbutton and observes the Red status light LIT, Green status light OFF.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C STEPS 22 23 24 25 Page 12 of 16 PERFORMANCE INFORMATION ELEMENTS (Step 13) Ensure 1 NV-1047A (PO Pump Recirculation) closes after 2 minutes.

(Step 14) WHEN 1 NV-1047A (PO Pump Recirculation) is closed, THEN raise "PO PUMP SPEED CNTRL" to establish charging flow.

(Note prior to Step 15)

Cooling water for areas in next step was isolated by Step 6.

(Step 15) Notify station management to monitor temperature in both units 6900v switchgear room, turbine bldg, and service bldg areas.

STANDARD After two minutes, the operator observes that the 1 NV-1 047 Green status light is LIT, Red status light is OFF.

The operator depresses the PO PUMP SPEED CNTRL increase pushbutton (Red),

and observes Charging flow is increasing.

The operator reads Note and proceeds to Step 15.

The operator notifies the CRSRO.

The operator returns to EP/1/A/5000/FR-S.1, Step 5.b.

  • 26 (EP/1/A/5000/FR-S.1/Step The operator depresses the 5.b/.b1) Align boration 1 NV-265B OPEN flowpath:

pushbutton and observes Red status light LIT, Green Open 1 NV-265B (Boric Acid status light OFF.

To NV Pumps).

S/U Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

(

Appendix C STEPS 22 23 24 25

  • 26 Page 12 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 13) Ensure 1 NV-After two minutes, the 1047A (PO Pump operator observes that the Recirculation) closes after 2 1 NV-1 047 Green status minutes.

light is LIT, Red status light is OFF.

(Step 14) WHEN 1 NV-The operator depresses the 1047A (PO Pump PO PUMP SPEED CNTRL Recirculation) is closed, increase pushbutton (Red),

THEN raise "PO PUMP and observes Charging flow SPEED CNTRL" to is increasing.

establish charging flow.

(Note prior to Step 15)

The operator reads Note Cooling water for areas in and proceeds to Step 15.

next step was isolated by Step 6.

(Step 15) Notify station The operator notifies the management to monitor CRSRO.

temperature in both units 6900v switchgear room, Cue:

turbine bldg, and service bldg areas.

Station Management has been notified.

The operator returns to EP/1/N5000/FR-S.1, Step 5.b.

(EP/1 IN5000/FR-S.1 IStep The operator depresses the 5.b/.b1) Align boration 1 NV-265B OPEN flowpath:

pushbutton and observes Red status light LIT, Green Open 1 NV-265B (Boric Acid status light OFF.

To NV Pumps).

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C Page 13 of 16 Form ES-C-1 PERFORMANCE INFORMATION

(

STEPS ELEMENTS STANDARD StU COMMENTS REQUIRED FOR UNSAT

  • 27 (Step S.b.2) Start both boric The operator places the A acid transfer pumps.

Boric Acid Transfer Pump control switch to START and observes the Red status light LIT, Green status light OFF.

The operator observes the B Boric Acid Transfer Pump Red status light LIT, Green status light OFF.

28 (Step S.b.3) Check The operator observes emergency boration flow -

boration flow on 1 NVP-S440 GREATER THAN 30 GPM to be 60-80 gpm.

29 (Step S.c) Check if NV flowpath aligned to NC System The operator observes 1 NV-244A (Charging Line 1 NV-244A Red status light Cont 1501 Otsd) - OPEN LIT, Green status light OFF.

1 NV-24SB (Charging Line The operator observes Cont 1501 Otsd) - OPEN 1 NV-24SB Red status light LIT, Green status light OFF.

30 (Step S.d) Ensure charging The operator depresses the flow is greater than RAISE (Red) pushbutton on emergency boration flow.

the PD Pump controller to increase charging flow to greater than boration flow.

2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

\\

(

(

Appendix C STEPS

  • 27 28 29 30 Page 13 of 16 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step S.b.2) Start both boric The operator places the A acid transfer pumps.

Boric Acid Transfer Pump control switch to START and observes the Red status light LIT, Green status light OFF.

The operator observes the B Boric Acid Transfer Pump Red status light LIT, Green status light OFF.

(Step S.b.3) Check The operator observes emergency boration flow -

boration flow on 1 NVP-S440 GREATER THAN 30 GPM to be 60-80 gpm.

(Step S.c) Check if NV flowpath aligned to NC System The operator observes 1 NV-244A (Charging Line 1 NV-244A Red status light Cont Isol Otsd) - OPEN LIT, Green status light OFF.

1 NV-24SB (Charging Line The operator observes Cont Isol Otsd) - OPEN 1 NV-24SB Red status light LIT, Green status light OFF.

(Step S.d) Ensure charging The operator depresses the flow is greater than RAISE (Red) pushbutton on emergency boration flow.

the PD Pump controller to increase charging flow to greater than boration flow.

Examiner Note:

As charging flow is raised, boration flow will track parallel with charging flow. PO pump speed will have to be raised to 100% to gain any discernable separation. As long as flow is >60 GPM the step is satisfied.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C STEPS ELEMENTS Page 14 of 16 PERFORMANCE INFORMATION STANDARD Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 31 (Step 5.e) Check Pzr The operator observes that pressure - LESS THAN Pzr Pressure is less than 2335 PSIG 2335 psig on 1NCP-5161 (or equivalent).

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

(

Appendix C STEPS ELEMENTS Page 14 of 16 PERFORMANCE INFORMATION STANDARD Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 31 (Step 5.e) Check Pzr The operator observes that pressure - LESS THAN Pzr Pressure is less than 2335 PSIG 2335 psig on 1NCP-5161 (or equivalent).

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C Page 15 of 16 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM A Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

(

(

(

Appendix C Page 15 of 16 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM A Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM A NUREG 1021, Revision 9

Appendix C INITIAL CONDITIONS:

INITIATING CUE:

Form ES-C-1 JPM CUE SHEET Unit 1 was at 100% power with "A" NV pump tagged for maintenance.

A lockout occurred on Zone "1 B". Due to a relaying failure, busses 1 TB and 1 TD failed to swap to their alternate power source. The "1 B" Diesel Generator started and loaded 1 ETB.

The reactor coolant pumps tripped on under frequency.

An automatic reactor trip FAILED to occur. EP/1/A15000/FR-S.1 (Response To Nuclear Power Generator/ATWS) has been implemented and completed through Step 4.

Letdown has been isolated per AP/1/A15500/12 Loss of Letdown, Charging or Seal Injection.

The reactor has just been tripped locally.

The CRSRO has directed you to emergency borate the NC System in accordance with Step 5 of EP/1/A15000/FR-S.1, Response To Nuclear Generator/ATWS.

NUREG 1021, Revision 9 Appendix C

('

INITIAL CONDITIONS:

INITIATING CUE:

(

Form ES-C-1 JPM CUE SHEET Unit 1 was at 100% power with "A" NV pump tagged for maintenance.

A lockout occurred on Zone "1 B". Due to a relaying failure, busses 1TB and 1TD failed to swap to their alternate power source. The "1 B" Diesel Generator started and loaded 1 ETB.

The reactor coolant pumps tripped on under frequency.

An automatic reactor trip FAILED to occur. EP/1/A/SOOO/FR-S.1 (Response To Nuclear Power Generator/ATWS) has been implemented and completed through Step 4.

Letdown has been isolated per AP/1/A/SSOO/12 Loss of Letdown, Charging or Seal Injection.

The reactor has just been tripped locally.

The CRSRO has directed you to emergency borate the NC System in accordance with Step S of EP/1/A/SOOO/FR-S.1, Response To Nuclear Generator/ATWS.

NUREG 1021, Revision 9

Appendix C Job Performance Measure Worksheet Form ES-C-1 SIM JPM B 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

(

Appendix C Job Performance Measure Worksheet Form ES-C-1 SIM JPM B 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

Appendix C Job Performance Measure Worksheet Form ES-C-1 Facility:

McGuire Task No.:

215Z13001 Task

Title:

Align the ND. NI. and NV Systems to Cold Leg Recirculation JPM No.:

2009 Systems - Control Room JPM B KIA

Reference:

006, A4.02, 3.9/3.8 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

Upon receiving the "FWST Level Lo" annunciator, the operator transitions to EP/1/A/5000/ES-1.3 (Transfer to Cold Leg Recirc) per foldout page of E-1 or Step 15.b RNO. The "A" train of ND and both trains of NI and NV are then aligned to Cold Leg Recirc. All critical tasks evaluated as satisfactory.

Required Materials:

None General

References:

EP/1 /A/5000/E-1, Loss of Reactor or Secondary Coolant EP/1/A/5000/ES-1.3, Transfer to Cold Leg Recirc 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

(

(

Appendix C Job Performance Measure Form ES-C-1 Worksheet Facility:

McGuire Task No.:

21SZ13001 Task

Title:

Align the NO, NI, and NV S1::stems JPM No.:

2009 S1::stems - Control to Cold Leg Recirculation Room JPM B KIA

Reference:

006, A4.02, 3.9/3.8 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

Upon receiving the "FWST Level Lo" annunciator, the operator transitions to EP/1/A/SOOO/ES-1.3 (Transfer to Cold Leg Recirc) per foldout page of E-1 or Step 1S.b RNO. The "N train of NO and both trains of NI and NV are then aligned to Cold Leg Recirc. All critical tasks evaluated as satisfactory.

Required Materials:

None General

References:

EP/1/NSOOO/E-1, Loss of Reactor or Secondary Coolant EP/1/NSOOO/ES-1.3, Transfer to Cold Leg Recirc 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

Appendix C Handouts:

Time Critical Task:

Validation Time:

Job Performance Measure Worksheet Form ES-C-1 EP/11A15000/E-1, Loss of Reactor or Secondary Coolant marked up for place-keeping through Step 14.

NO 15 minutes 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

(

(

(

Appendix C Handouts:

Time Critical Task:

Validation Time:

Job Performance Measure Worksheet Form ES-C-1 EP/1/N5000/E-1! Loss of Reactor or Secondary Coolant marked up for place-keeping through Step 14.

NO 15 minutes 2009 Systems - Control Room JPM B NUREG 1021! Revision 9

Appendix C Job Performance Measure Worksheet Form ES-C-1 SIMULATOR OPERATIONAL GUIDELINES

1.

Reset Simulator to IC-39 100% MOL

2.

Insert Malfunction - NC008B, Cold Leg LOCA Loop B

3.

Setup Malfunction - N1002E, NI System Valve 1 NI-184B Failure, Value = 0

4.

Implement EP/E-O, FRP-P.1, FRP-Z.1, transition to EP/E-1 and perform steps 1 through 14. Allow FWST to drain to 200 inches.

5.

Freeze the Simulator

1.

Reset to IC-123 (December, 2008)

2.

Momentarily go to RUN to acknowledge Alarms then place Simulator in FREEZE.

3.

Leave Simulator in FREEZE until operator is ready to begin.

Note: Time to Reach 180 Inches in FWST is :::::45 sec.

2009 Systems - Control Room JPM B NUREG 1021, Revision 9

(

Appendix C Job Performance Measure Worksheet Form ES-C-1 SIMULATOR OPERATIONAL GUIDELINES

1.

Reset Simulator to IC-39 100% MOL

2.

Insert Malfunction - NC008B, Cold Leg LOCA Loop B

3.

Setup Malfunction - N1002E, NI System Valve 1 NI-184B Failure, Value = a

4.

Implement EP/E-O, FRP-P.1, FRP-Z.1, transition to EP/E-1 and perform steps 1 through 14. Allow FWST to drain to 200 inches.

5.

Freeze the Simulator

1.

Reset to IC-123 (December, 2008)

2.

Momentarily go to RUN to acknowledge Alarms then place Simulator in FREEZE.

3.

Leave Simulator in FREEZE until operator is ready to begin.

Note: Time to Reach 180 Inches in FWST is :::45 sec.

2009 Systems - Control Room JPM B NUREG 1021, Revision 9

Appendix C Page 5 of 5 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout EP/1/Al5000/E-1 marked up for place-keeping through step 14.

START TIME:

STEPS ELEMENTS STANDARD StU COMMENTS REQUIRED FOR UNSAT Simulator Instructor NOTE: Leave Simulator in FREEZE until operator is ready to begin.

NOTE: Operator uses control board indications to check equipment status. Operator transitions to ES-1.3 when "FWST LEVEL LO" annunciator is received (expected to come in while performing JPM Steps 1-4. When the alarm comes in, N/A any JPM Steps not performed and proceed to JPM Step 5.

1 2

3 (Step 15) Check transfer to Cold Leg Recirc criteria:

(Step 15.a) FWST level -

LESS THAN 180 INCHES

("FWST LEVEL LO" ALARM)

(Step 15.a RNO) RETURN TO Step 13.

(Step 13) Initiate evaluation of plant status:

(Step 13.a) Check Cold Leg Recirc capability from at least one train as follows:

Train A:

1A NO pump - AVAILABLE 1NI-185A (1A NO Pump Suction From Cont Sump Isol) - POWER AVAI LABLE OR Train B:

1 B NO pump - AVAILABLE 1NI-184B (1B NO Pump Suction From Cont Sump Isol) - POWER AVAILABLE 2009 Systems - Control Room JPM B The operator checks FWST level indications (1 FWP-5000, p001 and 5002) at approximately 200 inches and proceeds to RNO.

The operator returns to Step 13.

The operator observes 1A NO Pump Red status light LIT, Green status light OFF.

1 NI-185A Green light lit, Red Light Dark The operator observes 1 B NO Pump Red status light LIT, Green status light OFF.

1 NI-185A Green light lit, Red Light Dark The operator determines that both pumps and valves are available.

NUREG 1021, Revision 9

(

Appendix C Page 5 of 5 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout EP/1/Al5000/E-1 marked up for place-keeping through step 14.

START TIME:

STEPS ELEMENTS STANDARD S/U COMMENTS REQUIRED FOR UNSAT Simulator Instructor NOTE: Leave Simulator in FREEZE until operator is ready to begin.

NOTE: Operator uses control board indications to check equipment status. Operator transitions to ES-1.3 when "FWST LEVEL LO" annunciator is received (expected to come in while performing JPM Steps 1-4. When the alarm comes in, N/A any JPM Steps not performed and proceed to JPM Step 5.

1 2

3 (Step 15) Check transfer to Cold Leg Recirc criteria:

(Step 15.a) FWST level -

LESS THAN 180 INCHES

("FWST LEVEL LO" ALARM)

(Step 15.a RNO) RETURN TO Step 13.

(Step 13) Initiate evaluation of plant status:

(Step 13.a) Check Cold Leg Recirc capability from at least one train as follows:

Train A:

1A NO pump - AVAILABLE 1 NI-185A (1A NO Pump Suction From Cont Sump Isol) - POWER AVAILABLE OR Train B:

1B NO pump -AVAILABLE 1 NI-184B (1 B NO Pump Suction From Cont Sump Isol) - POWER AVAILABLE 2009 Systems - Control Room JPM B The operator checks FWST level indications (1 FWP-5000, 5001 and 5002) at approximately 200 inches and proceeds to RNO.

The operator returns to Step 13.

The operator observes 1A NO Pump Red status light LIT, Green status light OFF.

1 NI-185A Green light lit, Red Light Dark The operator observes 1 B NO Pump Red status light LIT, Green status light OFF.

1 NI-185A Green light lit, Red Light Dark The operator determines that both pumps and valves are available.

NUREG 1021, Revision 9

Appendix C Page 6 of 6 PERFORMANCE INFORMATION STEPS ELEMENTS 4

(Step 13.1b.1) Check for potential leak in aux bldg as follows: Check aux bldg radiation:

All area monitor EMF's -

NORMAL EMF-41 (Aux Bldg Ventilation) - NORMAL STANDARD The operator observes EMF's for Trip1ITrip2 lights are NOT LIT.

The operator observes associated EMF Annunciators are DARK.

S/U Form ES-C-1 COMMENTS REQUIRED FOR UNSAT NOTE: Based on the setup, the operator should be transitioned to ES-1.3 by this point.

5 6

(ES-1.3/Step 1) Have STA monitor foldout page (Step 2) Perform this EP without delay.

CSF procedures should not be implemented until directed by this procedure.

Double 3-way communication is not required.

2009 Systems - Control Room JPM B The operator looks for ST A.

Cue:

TheSTA will*monitor*the foldout page The operator reads Step and proceeds to Step 3.

NUREG 1021, Revision 9 Appendix C STEPS 4

Page 6 of 6 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 13./b.1) Check for potential leak in aux bldg as follows: Check aux bldg radiation:

All area monitor EMF's -

The operator observes NORMAL EMF's for Trip1ITrip2 lights are NOT LIT.

EMF-41 (Aux Bldg The operator observes Ventilation) - NORMAL associated EMF Annunciators are DARK.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT NOTE: Based on the setup, the operator should be transitioned to ES-1.3 by this point.

5 (ES-1.3/Step 1) Have STA The operator looks for ST A.

monitor foldout page Cue:

The STA will monitor the foldout page 6

(Step 2) Perform this EP The operator reads Step without delay.

and proceeds to Step 3.

CSF procedures should not be implemented until directed by this procedure.

Note:

Double 3-way The direction to perform communication is not required.

without delay, and the relaxation of the communication standard means that the operator will depress valve pushbuttons check ONLY that the valve has started moving and continue on with the procedure.

The operator will NOT wait for the valve to fully stroke before continuing with the procedure.

2009 Systems - Control Room JPM B NUREG 1021, Revision 9

Appendix C STEPS 7

8 9

10 Page 7 of 7 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 3) Check containment sump level by checking at least one of the following alarms -LIT:

"CONT SUMP LEVEL GREATER THAN 3 FT" on The operator observes that 1AD LIT the MCB Annunciator is LIT.

OR "CONT SUMP LEVEL The operator observes that GREATER THAN 3 FT" on the MCB Annunciator is LIT.

1AD LIT.

(Step 4) Check KC flow to The operator checks KC to ND heat exchangers-ND heat exchanger flow GREATER THAN 5000 indications (1 KCP-GPM.

5670/5680) and observes flow is greater than 5000 GPM to each heat exchanger.

(Step 5) Reset the following:

(Step 5.a) SII The operator observes SII RESET light is LIT for both trains.

(Step 5.b) Sequencers The operator observes Sequencer RESET light is LIT for both trains.

(Step 6) Align ND System for recirc:

(Step 6.a) Check 1 NI-185A The operator observes 1 NI-185A Red status light is LIT, (RB Sump To Train A ND &

Green status light OFF.

NS) -OPEN.

Form ES-C-1 SIU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

(

(

\\

Appendix C STEPS 7

8 9

10 Page 7 of 7 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 3) Check containment sump level by checking at least one of the following alarms -LIT:

"CONT SUMP LEVEL GREATER THAN 3 FT" on The operator observes that 1AD LIT the MCB Annunciator is LIT.

OR "CONT SUMP LEVEL The operator observes that GREATER THAN 3 FT" on the MCB Annunciator is LIT.

1AD LIT.

(Step 4) Check KC flow to The operator checks KC to NO heat exchangers -

NO heat exchanger flow GREATER THAN 5000 indications (1 KCP-GPM.

5670/5680) and observes flow is greater than 5000 GPM to each heat exchanger.

(Step 5) Reset the following:

(Step 5.a) S/I The operator observes S/I RESET light is LIT for both trains.

(Step 5.b) Sequencers The operator observes Sequencer RESET light is LIT for both trains.

(Step 6) Align NO System for recirc:

(Step 6.a) Check 1NI-185A The operator observes 1 NI-185A Red status light is LIT, (RB Sump To Train A NO &

Green status light OFF.

NS) - OPEN.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

Appendix C STEPS 11 12 13 14 15

  • 16 Page 8 of 8 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 6.b) Check 1A NO The operator observes 1A Pump - ON NO Red status light is LIT, Green status light OFF, as well as pump flow, motor amps, and discharge pressure.

(Step 6.c) Check 1 NI-184B The operator observes that (RB Sump To Train B NO &

1 NI-184B Green status light NS)-OPEN is LIT, Red status light OFF.

(Step 6.c RNO) Perform the following:

The operator depresses the (Step 6.c RNO 1) Place 1 NI-184B BYPASS control permissive in pushbutton.

"Bypass" and open 1 NI-184B The operator presses 1 NI-184B OPEN pushbutton.

The operator observes Green status light LIT and recognizes that valve is CLOSED.

(Step 6.c RNO 2) IF 1 NI-The operator determines 184B is opening, THEN wait that valve is not opening up to 30 seconds to allow and proceeds to RNO valve to open.

6.C.3.

(Step 6.c RNO 3) IF 1 NI-The operator determines 184B is full open, THEN GO that valve is not opening TO Step 6.d.

and proceeds to RNO 6.C.4.

(Step 6.c RNO 4) IF 1 NI-The operator presses the 184B is closed OR 1 B NO Pump STOP intermediate, THEN:

pushbutton and observes Green status light is LIT.

(Step 6.c RNO 4.a) Stop 1 B NO Pump.

The operator proceeds to (Step 6.c RNO 4.b) GO TO Step 6.e.

Step 6.e.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

(

(

(

Appendix C STEPS 11 12 13 14 15

  • 16 Page 8 of 8 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 6.b) Check 1A NO The operator observes 1A Pump - ON NO Red status light is LIT, Green status light OFF, as well as pump flow, motor amps, and discharge pressure.

(Step 6.c) Check 1 NI-184B The operator observes that (RB Sump To Train B NO &

1 NI-184B Green status light NS) - OPEN is LIT, Red status light OFF.

(Step 6.c RNO) Perform the following:

The operator depresses the (Step 6.c RNO 1) Place 1NI-184B BYPASS control permissive in pushbutton.

"Bypass" and open 1 NI-184B The operator presses 1 NI-184B OPEN pushbutton.

The operator observes Green status light LIT and recognizes that valve is CLOSED.

(Step 6.c RNO 2) IF 1 NI-The operator determines 184B is opening, THEN wait that valve is not opening up to 30 seconds to allow and proceeds to RNO valve to open.

6.C.3.

(Step 6.c RNO 3) IF 1 NI-The operator determines 184B is full open, THEN GO that valve is not opening TO Step 6.d.

and proceeds to RNO 6.CA.

(Step 6.c RNO 4) IF 1 NI-The operator presses the 184B is closed OR 1 B NO Pump STOP intermediate, THEN:

pushbutton and observes Green status light is LIT.

(Step 6.c RNO 4.a) Stop 1 B NO Pump.

The operator proceeds to (Step 6.c RNO 4.b) GO TO Step 6.e.

Step 6.e.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

Appendix C STEPS

  • 17 18 19
  • 20 Page 9 of 9 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 6.e) Enable power The operator rotates the disconnect and close 1 FW-1 FW-27 A control switch 27A (FWST Supply To ND).

clockwise and presses CLOSE pushbutton.

The operator observes Green status light is LIT.

(Step 6.f) Check any ND The operator observes 1 A pump - ON.

ND Red status light is LIT, Green status light OFF, as well as pump flow, motor amps, and discharge pressure.

(Step 7) Align NVand NI The operator observes NC Systems for recirc:

Pressure to== containment pressure.

(Step 7.a) Check NC pressure - LESS THAN 1600 PSIG.

N0t~:

ltis critical to close either 1NI.. 147A or both 1Nl...

'H56 and 1,NJ.. 144S in the Ilii!"I~pai.. e. Either

)'St.ZEl'1'ClfJ!t1is

.....,**t~:(*****<;*~/'i:

(Step 7.b) Close the following:

The operator presses the 1 NI-115B CLOSE 1 NI-115B (A NI Pump pushbutton, observes Miniflow)

Green status light LIT.

1 NI-144B (B NI Pump The operator presses the 1NI-144B CLOSE Miniflow) pushbutton, observes Green status light LIT.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

(

(

Appendix C STEPS

  • 17 18 19
  • 20 Page 9 of 9 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 6.e) Enable power The operator rotates the disconnect and close 1 FW-1 FW-27 A control switch 27A (FWST Supply To NO).

clockwise and presses CLOSE pushbutton.

The operator observes Green status light is LIT.

(Step 6.f) Check any NO The operator observes 1 A pump - ON.

NO Red status light is LIT, Green status light OFF, as well as pump flow, motor amps, and discharge pressure.

(Step 7) Align NV and NI The operator observes NC Systems for recirc:

Pressure to ::::: containment pressure.

(Step 7.a) Check NC pressure - LESS THAN 1600 PSIG.

Note:

It is critical to close either 1NI-147A Q!: both 1NI-115B and 1 NI-144B in the following steps (i.e. Either JPM Step 20 Q!: 21 is Critical).

(Step 7.b) Close the following:

The operator presses the 1 NI-115B CLOSE 1 NI-115B (A NI Pump pushbutton, observes Miniflow)

Green status light LIT.

1 NI-144B (B NI Pump The operator presses the 1 NI-144B CLOSE Miniflow) pushbutton, observes Green status light LIT.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

Appendix C STEPS

  • 21
  • 22 23
  • 24 Page 10 of 10 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 7.c) Enable power The operator rotates the disconnect and close 1 NI-1NI-147A power disconnect 147A (NI Pumps Miniflow switch clockwise to Hdr Isol).

ENABLE and presses CLOSE pushbutton.

Operator observes Green status light is LIT.

(Step 7.d) Close the following valves:

1 ND-30A (Train A ND To The operator presses the Hot Leg Isol).

1 ND-30A CLOSE pushbutton, observes Green status light LIT.

1 ND-15B (Train B ND To Hot Leg Isol).

The operator presses the 1ND-15B CLOSE pushbutton, observes Green status light LIT.

(Step 7.e) Check 1 NI-334B The operator observes the (NV & NI Pumps Suct X-1 NI-334B Red status light Over Blk) - OPEN.

LIT, Green status light OFF.

Note:

Op!ning either 1 NI.. 332A 01'1 ",1.. 3338 satisfies the

-critioafpanef'this step.

(Step 7.t) Open the following:

1 NI-332A (NV & NI Pumps The operator presses the 1 NI-332A OPEN Suction X-Over) pushbutton, observes Red status light LIT.

1 NI-333B (NV & NI Pumps The operator presses the Suction X-Over) 1 NI-333B OPEN pushbutton, observes Red status light LIT.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

(

(

Appendix C STEPS

  • 21
  • 22 23
  • 24 Page 10 of 10 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 7.c) Enable power The operator rotates the disconnect and close 1 NI-1 NI-147A power disconnect 147A (NI Pumps Miniflow switch clockwise to Hdr Isol).

ENABLE and presses CLOSE pushbutton.

Operator observes Green status light is LIT.

(Step 7.d) Close the following valves:

1 ND-30A (Train A NO To The operator presses the Hot Leg Isol).

1 ND-30A CLOSE pushbutton, observes Green status light LIT.

1 ND-15B (Train B NO To Hot Leg Isol).

The operator presses the 1ND-15B CLOSE pushbutton, observes Green status light LIT.

(Step 7.e) Check 1 NI-334B The operator observes the (NV & NI Pumps Suct X-1 NI-334B Red status light Over Blk) - OPEN.

LIT, Green status light OFF.

Note:

Opening either 1 NI-332A or 1 NI-3338 satisfies the critical part of this step.

(Step 7.f) Open the following:

1 NI-332A (NV & NI Pumps The operator presses the 1 NI-332A OPEN Suction X-Over) pushbutton, observes Red status light LIT.

1 NI-333B (NV & NI Pumps The operator presses the Suction X-Over) 1 NI-333B OPEN pushbutton, observes Red status light LIT.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

Appendix C STEPS 25

  • 26
  • 27 Page 11 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 7.g) Align NO discharge to suction of NI lfJi'tei******.......

~','.~",:4).<,,{~:: >.,

and NV pumps as follows:

1 Nli.13fS will not Clpen due to bein9interloc~ed withfNI~184B.

Open 1 ND-58A (Train A NO The operator presses the 1 ND-58A OPEN To NV & NI Pumps).

pushbutton, observes Red status light LIT.

Open 1NI-136B (B NI The operator presses the Pump Suction 1 NI-136B OPEN From NO).

pushbutton, observes Green status light LIT.

(Step 7.h) Isolate FWST The operator rotates the from NV and NI pumps:

1 NI-1 OOB power disconnect switch clockwise to (Step 7. h.1) Enable power ENABLE and presses disconnect and close 1 NI-CLOSE pushbutton.

100B (FWST To NI Pumps).

The operator observes Green status light is LIT.

(Step 7.h.2) Close the following:

1 NV-221A (NV Pumps Suct The operator presses the From FWST) 1 NV-221A CLOSE pushbutton, observes Green status light LIT.

1 NV-222B (NV Pumps Suct The operator presses the 1 NV-222B CLOSE From FWST) pushbutton, observes Green status light LIT.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

(

(

(

Appendix C STEPS 25

  • 26
  • 27 Page 11 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 7.g) Align NO discharge to suction of NI Note:

and NV pumps as follows:

1 NI-1368 will not open due to being interlocked with 1 NI-1848.

Open 1 ND-58A (Train A NO The operator presses the 1 ND-58A OPEN To NV & NI Pumps).

pushbutton, observes Red status light LIT.

Open 1 NI-136B (B NI The operator presses the Pump Suction 1 NI-136B OPEN From NO).

pushbutton, observes Green status light LIT.

(Step 7.h) Isolate FWST The operator rotates the from NV and NI pumps:

1 NI-1 OOB power disconnect switch clockwise to (Step 7.h.1) Enable power ENABLE and presses disconnect and close 1 NI-CLOSE pushbutton.

100B (FWST To NI Pumps).

The operator observes Green status light is LIT.

(Step 7.h.2) Close the following:

1 NV-221A (NV Pumps Suct The operator presses the From FWST) 1 NV-221A CLOSE pushbutton, observes Green status light LIT.

1 NV-222B (NV Pumps Suct The operator presses the 1 NV-222B CLOSE From FWST) pushbutton, observes Green status light LIT.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

Appendix C Page 13 of 13 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM B Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

(

(

Appendix C Page 13 of 13 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM B Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM B NUREG 1021, Revision 9

Appendix C Initial Conditions:

INITIATING CUE:

Form ES-C-1 JPM CUE SHEET You are the Unit 1 Balance of Plant (BOP) Operator.

Unit 1 has experienced a large break LOCA inside containment.

EP/1/A/5000/E-0 has been completed.

EP/1/A15000/FR-P.1 (Response to Imminent Pressurized Thermal Shock) and EP/1/A15000/FR-Z.1 (Response to High Containment Pressure) have been implemented to address existing CSF orange paths.

EP/1/A15000/E-1 (Loss of Reactor or Secondary Coolant) is currently in effect and has been completed through Step # 14.

The CRSRO has directed you to continue in EP/1/A15000/E-1 (Loss of Reactor or Secondary Coolant), beginning with Step #15, and perform ES-1.3, Transfer to Cold Leg Recirc when required.

NUREG 1021, Revision 9 Appendix C Initial Conditions:

INITIATING CUE:

(

Form ES-C-1 JPM CUE SHEET You are the Unit 1 Balance of Plant (BOP) Operator.

Unit 1 has experienced a large break LOCA inside containment.

EP/1/A/5000/E-0 has been completed.

EP/1/A/5000/FR-P.1 (Response to Imminent Pressurized Thermal Shock) and EP/1/A/5000/FR-Z.1 (Response to High Containment Pressure) have been implemented to address existing CSF orange paths.

EP/1/A/5000/E-1 (Loss of Reactor or Secondary Coolant) is currently in effect and has been completed through Step # 14.

The CRSRO has directed you to continue in EP/1/A/5000/E-1 (Loss of Reactor or Secondary Coolant), beginning with Step #15, and perform ES-1.3, Transfer to Cold Leg Recirc when required.

NUREG 1021, Revision 9

Appendix C Page 1 of 11 PERFORMANCE INFORMATION R

Form ES-C-1 81M JPM C 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

(

Appendix C Page 1 of 11 PERFORMANCE INFORMATION DR Form ES-C-1 SIM JPM C 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

Appendix C Facility:

McGuire Page 2 of 11 PERFORMANCE INFORMATION Task No.:

Form ES-C-1 Task

Title:

Place L TOP in Service JPM No.:

2009 Systems - Control Room JPM C KIA

Reference:

010, A4.03, 4.0/3.8 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

Manually decrease NC System Pressure to 320-330 psig and place L TOP in service. All critical tasks evaluated as satisfactory.

Required Materials:

None General

References:

OP/1/A16100/SD-4, Cooldown to 240 Degrees F OP/1/A161 00/SO-10, Controlling Procedure for LTOP Operation OP/1/A161001022, Unit 1 Data Book 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

(

Appendix C Facility:

McGuire Page 2 of 11 PERFORMANCE INFORMATION Task No.:

Form ES-C-1 Task

Title:

Place L TOP in Service JPM No.:

2009 Systems - Control Room JPM C KIA

Reference:

010, A4.03, 4.0/3.8 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

Manually decrease NC System Pressure to 320-330 psig and place L TOP in service. All critical tasks evaluated as satisfactory.

Required Materials:

None General

References:

OP/1/A/6100/SD-4, Cooldown to 240 Degrees F OP/1/A/61 00/SO-1 0, Controlling Procedure for L TOP Operation OP/1/A/61001022, Unit 1 Data Book 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

Appendix C Handouts:

Time Critical Task:

Validation Time:

Page 3 of 11 PERFORMANCE INFORMATION Form ES-C-1 OP/1/A/6100/S0-10, Controlling Procedure for LTOP Operation,.1, Placing L TOP System in Service per OP/1/A/61 00/SO-4 (Cooldown to 240 degrees F) marked up for place-keeping through step 3.13.1.

NO 10 minutes 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

(

Appendix C Handouts:

Time Critical Task:

Validation Time:

Page 3 of 11 PERFORMANCE INFORMATION Form ES-C-1 OP/1/N61 00/SO-1 0, Controlling Procedure for LTOP Operation,.1, Placing LTOP System in Service per OP/1/N61 00/SO-4 (Cooldown to 240 degrees F) marked up for place-keeping through step 3.13.1.

NO 10 minutes 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

Appendix C Page 4 of 11 PERFORMANCE INFORMATION SIMULATOR OPERATIONAL GUIDELINES Form ES-C-1

1.

Reset simulator to IC-41, Mode 4, 325 PSIG, 299 Deg Trn B ND is service.

2.

Place in RUN

3.

Secure 1 C and 1 D NCP's

4.

Place L TOP PORV switches is OFF

5.

Insert LOA NC043 and LOA NC044

6.

Adjust NC System Pressure to 340 psig.

7.

Adjust NC System Temperature to 306°F.

8.

Ensure that Simulator reflects that Enclosure 4.1 of OP/1/N61 00/SO-1 0 is completed through Step 3.13.1

9.

Freeze the Simulator

1.

Reset to IC-124 (December, 2008)

2.

Momentarily go to RUN to acknowledge Alarms then place Simulator in FREEZE.

3.

Ensure that the "AFD" Computer screen displays the "C/D Tab" panel and that the

4.

NOTE:

"OATC" screen displays the "NCL TOP" panel.

Leave Simulator in FREEZE until operator is ready to begin.

During the performance of this JPM, the simulator operator will need to control CF flow to the SGs.

2009 Systems - Control Room JPM C NUREG 1021, Revision 9

(

Appendix C Page 4 of 11 PERFORMANCE INFORMATION SIMULATOR OPERATIONAL GUIDELINES Form ES-C-1

1.

Reset simulator to IC-41, Mode 4,325 PSIG, 299 Deg Trn B ND is service.

2.

Place in RUN

3.

Secure 1 C and 1 D NCP's

4.

Place L TOP PORV switches is OFF

5.

Insert LOA NC043 and LOA NC044

6.

Adjust NC System Pressure to 340 psig.

7.

Adjust NC System Temperature to 306°F.

8.

Ensure that Simulator reflects that Enclosure 4.1 of OP/1/N61 00/SO-1 0 is completed through Step 3.13.1

9.

Freeze the Simulator

1.

Reset to IC-124 (December, 2008)

2.

Momentarily go to RUN to acknowledge Alarms then place Simulator in FREEZE.

3.

Ensure that the "AFD" Computer screen displays the "C/O Tab" panel and that the

4.

NOTE:

"OA TC" screen displays the "NCL TOP" panel.

Leave Simulator in FREEZE until operator is ready to begin.

During the performance of this JPM, the simulator operator will need to control CF flow to the SGs.

2009 Systems - Control Room JPM C NUREG 1021, Revision 9

Appendix C Page 5 of 11 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout OP/1/A161 00/SO-1 0, with Enclosure 4.1 marked up for place-keeping through step 3.13.1.

START TIME:

STEPS ELEMENTS STANDARD StU COMMENTS REQUIRED FOR UNSAT Simulator Instructor NOTE: Leave Simulator in FREEZE until operator is ready to begin.

1 (Step 3.13.2) Ensure in The operator calls up both service:

points on OAC.

M1A1359 (NC NR Pressure for 1 NC-32B actuation).

M1A1365 (NC NR Pressure for 1 NC-34A actuation).

2 (Step 3.13.3) Monitor:

The operator monitors both M1A1359 (NC NR Pressure points and observes NC NR for 1 NC-32B actuation).

Pressure to be 340 psig.

M1A1365 (NC NR Pressure for 1 NC-34A actuation).

  • 3 (Step 3.13.4) Decrease NC The operator adjusts Spray System Pressure to Valve(s) in the OPEN 320 - 330 PSIG direction using the Red Pushbutton, and lowers NC System Pressure to < 330 psig.

When NC System Pressure

< 330 psig, the operator adjusts Spray Valve(s) in the CLOSED direction in order to maintain pressure 320-330 psig.

2009 Systems - Control Room JPM C NUREG 1021, Revision 9 Appendix C Page 5 of 11 PERFORMANCE INFORMATION Form ES-C-1

(

(Denote Critical Steps with an asterisk*)

(

Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout OP/1/Al6100/S0-10, with Enclosure 4.1 marked up for place-keeping through step 3.13.1.

START TIME:

STEPS ELEMENTS STANDARD S/U COMMENTS REQUIRED FOR UNSAT Simulator Instructor NOTE: Leave Simulator in FREEZE until operator is ready to begin.

1 (Step 3.13.2) Ensure in The operator calls up both service:

points on OAC.

M1A1359 (NC NR Pressure for 1 NC-32B actuation).

M1A1365 (NC NR Pressure for 1 NC-34A actuation).

2 (Step 3.13.3) Monitor:

The operator monitors both M1A1359 (NC NR Pressure points and observes NC NR for 1 NC-32B actuation).

Pressure to be 340 psig.

M1A1365 (NC NR Pressure for 1 NC-34A actuation).

  • 3 (Step 3.13.4) Decrease NC The operator adjusts Spray System Pressure to Valve(s) in the OPEN 320 - 330 PSIG direction using the Red Pushbutton, and lowers NC System Pressure to < 330 psig.

When NC System Pressure

< 330 psig, the operator adjusts Spray Valve(s) in the CLOSED direction in order to maintain pressure 320-330 psig.

2009 Systems - Control Room JPM C NUREG 1021, Revision 9

Appendix C STEPS 4

5

  • 6 7

Page 6 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 3.13.5) Ensure the following for A Cold Leg Accumulator:

Pressure greater than 200 The operator observes 1 NIP-5050 and 1 NIP-5040, psig.

and determines A CLA pressure to be =625 psig.

Level less than 38.7%

The operator observes (7342 gallons maximum).

1NIP-5051 and 1 NIP-5041,

and determines A CLA Level to be =25%.

(Step 3.13.6) Ensure the following for B Cold Leg Accu m u lator:

Pressure greater than 200 The operator observes 1 NIP-5070 and 1 NIP-5060 psig.

and determines B CLA pressure to be =620 psig.

Level less than 38.7%

The operator observes (7342 gallons maximum).

1 NIP-5071 and 1 NIP-5061 and determines B CLA Level to be =24%.

(Step 3.13.7) Ensure open:

The operator observes Red status light LIT, Green 1 NC-31 B (pzr PORV Isol).

status light OFF for 1 NC-33B.

1 NC-33A (pzr PORV Isol).

The operator observes Red status light LIT, Green status light OFF for 1 NC-33A.

(Note prior to Step 3.13.8)

The operator reads the For NC Loop in which an Note, and proceeds to Step NC Pump is operating, NR 3.13.8.

pressure may indicate up to 20 psig higher than NR pressure for NC Loop in which an NC Pump is NOT operating.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

(

Appendix C STEPS 4

5

  • 6 7

Page 6 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 3.13.5) Ensure the following for A Cold Leg Accumulator:

Pressure greater than 200 The operator observes 1 NIP-5050 and 1 NIP-5040, psig.

and determines A CLA pressure to be =625 psig.

Level less than 38.7%

The operator observes (7342 gallons maximum).

1 NIP-5051 and 1 NIP-5041, and determines A CLA Level to be =25%.

(Step 3.13.6) Ensure the following for B Cold Leg Accumulator:

Pressure greater than 200 The operator observes 1 NIP-5070 and 1 NIP-5060 psig.

and determines B CLA pressure to be =620 psig.

Level less than 38.7%

The operator observes (7342 gallons maximum).

1 NIP-5071 and 1 NIP-5061 and determines B CLA Level to be =24%.

(Step 3.13.7) Ensure open:

The operator observes Red status light LIT, Green 1 NC-31 B (pzr PORV Isol).

status light OFF for 1 NC-33B.

1 NC-33A (pzr PORV Isol).

The operator observes Red status light LIT, Green status light OFF for 1 NC-33A.

(Note prior to Step 3.13.8)

The operator reads the For NC Loop in which an Note, and proceeds to Step NC Pump is operating, NR 3.13.8.

pressure may indicate up to 20 psig higher than NR pressure for NC Loop in which an NC Pump is NOT operating.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

Appendix C Page 7 of 11 Form ES-C-1 PERFORMANCE INFORMATION STEPS

  • 8 9

10 11 ELEMENTS n

M1A1359 indicates 320-330 psig, perform the following:

(Step 3.13.8.1) Select "LOW PRESS" on "PORV Overpress Protection Select 1NC-32B."

(Step 3.13.8.2) Check lit 1AD-6, F10 (PORV NC-32B Emerg CLA N2 Enabled)

(Step 3.13.8.3) ure open 1 NI-431 B (Emerg N2 from CLA to 1 NC-32B &

36B).

(Step 3.13.8.4) Place Info Sticker on control switch for 1 NI-431 B stating: "Do NOT operate, N2 aligned to 1 NC-32B for LTOP."

2009 Systems - Control Room JPM C STANDARD The operator observes M1A1359 is between 320-330 psig, and selects LOW PRESS on PORV Overpress Protection Select 1 NC-32B.

The operator observes that 1AD-6, F-10 is LIT.

The operator observes that Red status light is LIT, Green status light OFF for 1NI-431B.

The operator acknowledges and proceeds to Step 3.13.8.5.

StU COMMENTS REQUIRED FOR UNSAT NUREG 1021, Revision 9'

(

(

Appendix C STEPS

  • 8 9

10 11 Page 7 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 3.13.8) When M1A1359 indicates 320-330 psig, perform the following:

(Step 3.13.8.1) Select The operator observes M 1 A 1359 is between 320-

"LOW PRESS" on "PORV 330 psig, and selects LOW Overpress Protection Select PRESS on PORV 1 NC-32B."

Overpress Protection Select 1 NC-32B.

(Step 3.13.8.2) Check lit The operator observes that 1AD-6, F10 (PORV NC-32B 1AD-6, F-10 is LIT.

Emerg CLA N2 Enabled)

(Step 3.13.8.3) Ensure The operator observes that open 1 NI-431 B (Emerg N2 Red status light is LIT, from CLA to 1 NC-32B &

Green status light OFF for 36B).

1 NI-431 B.

(Step 3.13.8.4) Place Info Sticker on control switch for Cue:

1 NI-431 B stating: "Do NOT operate, N2 aligned to 1 NC-Another operator will fill 32B for LTOP."

out and place an Info Sticker for 1 NI431 B The operator acknowledges and proceeds to Step 3.13.8.5.

Note:

If operator is reluctant to proceed examiner should sign off step.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

Appendix C Page 8 of 11 Form ES-C-1 PERFORMANCE INFORMATION STEPS 12 13*

14 15 16 ELEMENTS (Step 3.13.8.5) Ensure 1 NC-32B (pzr PORV) in "Auto."

9)

M1A1365 indicates 320-330 psig, perform the following:

(Step 3.13.9.1) Select "LOW PRESS" on "PORV Overpress Protection Select 1 NC-34A."

(Step 3.13.9.2) Check lit 1AD-6, F9 (PORV NC-34A Emerg CLA N2 Enabled) 13.9.3) Ensure open 1 NI-430A (Emerg N2 from CLA to 1 NC-34A).

ce Sticker on control switch for 1 NI-430A stating: "Do NOT operate, N2 aligned to 1 NC-34A for LTOP."

2009 Systems - Control Room JPM C STANDARD The operator observes that Control Switch for 1 NC-32B is in AUTO.

The operator observes M1A 1365 is between 320-330 psig, and selects LOW PRESS on PORV Overpress Protection Select 1 NC-34A.

The operator observes that 1AD-6, F-9 is LIT.

The operator observes that Red status light is LIT, Green status light OFF for 1 NI-430A.

The operator acknowledges and proceeds to Step 3.13.9.5.

StU COMMENTS REQUIRED FOR UNSAT NUREG 1021, Revision 9

(

(

Appendix C STEPS 12 13*

14 15 16 Page 8 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 3.13.8.5) Ensure The operator observes that 1 NC-32B (pzr PORV) in Control Switch for 1 NC-32B "Auto."

is in AUTO.

(Step 3.13.9) When The operator observes M1A1365 indicates 320-330 M1A1365 is between 320-psig, perform the following:

330 psig, and selects LOW (Step 3.13.9.1) Select PRESS on PORV "LOW PRESS" on "PORV Overpress Protection Select Overpress Protection Select 1 NC-34A.

1 NC-34A."

(Step 3.13.9.2) Check lit The operator observes that 1 AD-6, F9 (PORV NC-34A 1 AD-6, F-9 is LIT.

Emerg CLA N2 Enabled)

(Step 3.13.9.3) Ensure The operator observes that open 1 NI-430A (Emerg N2 Red status light is LIT, from CLA to 1 NC-34A).

Green status light OFF for 1 NI-430A.

(Step 3.13.9.4) Place Info Sticker on control switch for Cue:

1 NI-430A stating: "Do NOT Another operator will fill operate, N2 aligned to 1 NC-out and place an Info 34A for LTOP."

Sticker for 1 NI-430A The operator acknowledges and proceeds to Step 3.13.9.5.

Note:

Ifope.r~tGr isreltictantto proceed examiner should sign off step_

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

Appendix C STEPS 17 Page 9 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 3.13.9.5) Ensure The operator observes that 1 NC-34A (pzr PORV) in Control Switch for 1 NC-34A "Auto."

is in AUTO.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

(

Appendix C STEPS 17 Page 9 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 3.13.9.5) Ensure The operator observes that 1 NC-34A (pzr PORV) in Control Switch for 1 NC-34A "Auto."

is in AUTO.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

Appendix C Page 10 of 11 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM C Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

{

Appendix C Page 10 of 11 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM C Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM C NUREG 1021, Revision 9

Appendix C INITIAL CONDITIONS:

INITIATING CUE:

Form ES-C-1 JPM CUE SHEET A Unit 1 NC cooldown and depressurization is in progress in accordance with OP/1/Al6100/SD-4, "Cooldown to 240 Degrees F."

The 1A and 1 B NCPs are operating.

NC System pressure is 340 psig and NC System temperature is 306-312°F.

NC Pressure control via normal spray and PZR heaters.

  • .1 ofOP/1/Al6100/S0-10, "Controlling Procedure for L TOP Operation," has been completed through Step 3.13.

The CRSRO has directed you to place the L TOP System in operation in accordance with Step 3.13 of Enclosure 4.1 of OP/1/Al6100/S0-10, "Controlling Procedure for LTOP Operation,"

and monitor for proper operation.

NUREG 1021, Revision 9 Appendix C INITIAL CONDITIONS:

INITIATING CUE:

(

Form ES-C-1 JPM CUE SHEET A Unit 1 NC cooldown and depressurization is in progress in accordance with OP/1/N6100/SD-4, "Cooldown to 240 Degrees F."

The 1A and 1 B NCPs are operating.

NC System pressure is 340 psig and NC System temperature is 306-312°F.

NC Pressure control via normal spray and PZR heaters.

  • .1 of OP/1/N61 OO/SO-1 0, "Controlling Procedure for L TOP Operation," has been completed through Step 3.13.

The CRSRO has directed you to place the L TOP System in operation in accordance with Step 3.13 of Enclosure 4.1 of OP/1/A/61 00/SO-10, "Controlling Procedure for LTOP Operation,"

and monitor for proper operation.

NUREG 1021, Revision 9

Appendix C Page 1 of 13 PERFORMANCE INFORMATION Form ES-C-1 SIM JPM D 2009 Systems - Control Room JPM D NUREG 1021, Revision 9

(

Appendix C Page 1 of 13 PERFORMANCE INFORMATION Form ES-C-1 SIM JPM D 2009 Systems - Control Room JPM 0 NUREG 1021, Revision 9

Appendix C Facility:

McGuire Page 2 of 13 PERFORMANCE INFORMATION Task No.:

Form ES-C-1 Task

Title:

Establish Feedwater Flow to the S/G's Following a Reactor Trip JPM No.:

2009 Systems - Control Room JPM D KIA

Reference:

059, A4.11, 3.1/3.3 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

1A CF Pump is in service and capable of providing feedwater flow to all four S/G's.

Required Materials:

None General

References:

EP/1 IAl5000/ES-0. 1, Reactor Trip Response EP/1 IAl5000/ES-0. 1, Reactor Trip Response, Enclosure 4, Re-establishing CF Flow.

Handouts:

EP/1 IAl5000/ES-0. 1, Reactor Trip Response, Enclosure 4, Re-establishing CF Flow.

2009 Systems - Control Room JPM D NUREG 1021, Revision 9

(

Appendix C Facility:

McGuire Page 2 of 13 PERFORMANCE INFORMATION Task No.:

Form ES-C-1 Task

Title:

Establish Feedwater Flow to the S/G's Following a Reactor Trip JPM No.:

2009 Systems - Control Room JPM D KIA

Reference:

059, A4.11, 3.1/3.3 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

1A CF Pump is in service and capable of providing feedwater flow to all four S/G's.

Required Materials:

None General

References:

EP/1 IA/5000/ES-0. 1, Reactor Trip Response EP/1 IA/5000/ES-0. 1, Reactor Trip Response, Enclosure 4, Re-establishing CF Flow.

Handouts:

EP/1/A/5000/ES-0.1, Reactor Trip Response, Enclosure 4, Re-establishing CF Flow.

2009 Systems - Control Room JPM D NUREG 1021, Revision 9

Appendix C Time Critical Task:

Validation Time:

NO 20 minutes Page 3 of 13 PERFORMANCE INFORMATION 2009 Systems - Control Room JPM D Form ES-C-1 NUREG 1021, Revision 9

(

(

\\

Appendix C Time Critical Task:

Validation Time:

NO 20 minutes Page 3 of 13 PERFORMANCE INFORMATION 2009 Systems - Control Room JPM D Form ES-C-1 NUREG 1021, Revision 9

Appendix C Page 4 of 13 PERFORMANCE INFORMATION SIMULATOR OPERATIONAL GUIDELINES

1.

Reset to IC-12, 15%, BOL

2.

Insert MAL Insert MAL Insert MAL Insert MAL CA004A Failure of CA Pump A to Start CA004B Failure of CA Pump B to Start CA003A CA Turbine Fails to Start CA003B CA Turbine Fails to Start

3.

Manually trip the Reactor.

BOTH BOTH Form ES-C-1

4.

Allow simulator to run until negative power mismatch and negative temp. mismatch clear.

5.

Place TD CA Pump start switch to "START'

6.

Freeze the simulator.

Simulator runner should monitor balance of plant. Adjust charging and letdown as necessary to minimize alarms.

1.

Reset Simulator to Temporary Snap IC-125 (December, 2008).

2.

Momentarily place Simulator in Run to acknowledge alarms.

NOTE: 1 NV-238 was placed in manual during setup and will need to be adjusted and returned to Auto within approx 10 minutes of start of JPM.

2009 Systems - Control Room JPM D NUREG 1021, Revision 9

(

(

Appendix C Page 4 of 13 PERFORMANCE INFORMATION SIMULATOR OPERATIONAL GUIDELINES

1.

Reset to IC-12, 15%, BOL

2.

Insert MAL Insert MAL Insert MAL Insert MAL CA004A Failure of CA Pump A to Start CA004B Failure of CA Pump B to Start CA003A CA Turbine Fails to Start CA003B CA Turbine Fails to Start

3.

Manually trip the Reactor.

BOTH BOTH Form ES-C-1

4.

Allow simulator to run until negative power mismatch and negative temp. mismatch clear.

5.

Place TO CA Pump start switch to "START"

6.

Freeze the simulator.

Simulator runner should monitor balance of plant. Adjust charging and letdown as necessary to minimize alarms.

1.

Reset Simulator to Temporary Snap IC-125 (December, 2008).

2.

Momentarily place Simulator in Run to acknowledge alarms.

NOTE: 1 NV-238 was placed in manual during setup and will need to be adjusted and returned to Auto within approx 10 minutes of start of JPM.

2009 Systems - Control Room JPM 0 NUREG 1021, Revision 9

Appendix C Page 5 of 13 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout EP/1/Al5000/ES*O.1, Reactor Trip Response, Enclosure 4, Reestablishing CF Flow.

START TIME:

STEPS ELEMENTS STANDARD StU COMMENTS REQUIRED FOR UNSAT

  • 1 (Step 1) Ensure the following in manual and close manual loaders for all:

The operator places the StG CF control valves S/G CF control valve controllers (4) in MANUAL by depressing the Amber pushbutton.

On each controller the operator depresses the CLOSE pushbutton (Green) and observes that the controller outputs move to O.

StG CF control bypass The operator observes the valves Amber light LIT for each of the StG CF control bypass valve controllers (4).

On each controller the operator observes the Green light LIT and controller outputs at O.

  • 2 (Step 2) Close the following CF Control isolation valves:

1CF-31 (A StG CF Cntrl The operator depresses the Inlet Isol) 1CF-31 CLOSE pushbutton and observes Green status light LIT, Red status light OFF.

2009 Systems - Control Room JPM D NUREG 1021, Revision 9

{

Appendix C Page 5 of 13 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout EP/1/Al5000/ES-O.1, Reactor Trip Response, Enclosure 4, Reestablishing CF Flow.

START TIME:

STEPS ELEMENTS STANDARD S/U COMMENTS REQUIRED FOR UNSAT

  • 1 (Step 1) Ensure the following in manual and close manual loaders for all:

The operator places the S/G CF control valves S/G CF control valve controllers (4) in MANUAL by depressing the Amber pushbutton.

On each controller the operator depresses the CLOSE pushbutton (Green) and observes that the controller outputs move to O.

S/G CF control bypass The operator observes the valves Amber light LIT for each of the S/G CF control bypass valve controllers (4).

On each controller the operator observes the Green light LIT and controller outputs at O.

  • 2 (Step 2) Close the following CF Control isolation valves:

1 CF-31 (A S/G CF Cntrl The operator depresses the Inlet Isol) 1 CF-31 CLOSE pushbutton and observes Green status light LIT, Red status light OFF.

2009 Systems - Control Room JPM D NUREG 1021, Revision 9

Appendix C STEPS

  • 2 (Cont'd)

Page 6 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD 1 CF-33 (A S/G CF Cntrl The operator depresses the Outlet Isol) 1 CF-33 CLOSE pushbutton and observes Green status light LIT, Red status light OFF.

1 CF-22 (8 S/G CF Cntrl The operator depresses the 1 CF-22 CLOSE pushbutton Inlet Isol) and observes Green status light LIT, Red status light OFF.

The operator depresses the 1 CF-24 (8 S/G CF Cntrl 1 CF-24 CLOSE pushbutton Outlet Isol) and observes Green status light LIT, Red status light OFF.

The operator depresses the 1 CF-19 (C S/G CF Cntrl 1 CF-19 CLOSE pushbutton Inlet Isol) and observes Green status light LIT, Red status light OFF.

The operator depresses the 1 CF-21 CLOSE pushbutton 1 CF-21 (C S/G CF Cntrl and observes Green status Outlet Isol) light LIT, Red status light OFF.

The operator depresses the 1CF-16 CLOSE pushbutton 1 CF-16 (D S/G CF Cntrl and observes Green status Inlet Isol) light LIT, Red status light OFF.

The operator depresses the 1 CF-18 (D S/G CF Cntrl 1 CF-18 CLOSE pushbutton Outlet Isol) and observes Green status light LIT, Red status light OFF.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM D NUREG 1021, Revision 9

(

Appendix C STEPS

  • 2 (Cont'd)

Page 6 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD 1 CF-33 (A S/G CF Cntrl The operator depresses the Outlet Isol) 1 CF-33 CLOSE pushbutton and observes Green status light LIT, Red status light OFF.

1 CF-22 (8 S/G CF Cntrl The operator depresses the 1 CF-22 CLOSE pushbutton Inlet Isol) and observes Green status light LIT, Red status light OFF.

The operator depresses the 1 CF-24 (8 S/G CF Cntrl 1CF-24 CLOSE pushbutton Outlet Isol) and observes Green status light LIT, Red status light OFF.

The operator depresses the 1CF-19 (C S/G CF Cntrl 1CF-19 CLOSE pushbutton Inlet Isol) and observes Green status light LIT, Red status light OFF.

The operator depresses the 1 CF-21 CLOSE pushbutton 1 CF-21 (C S/G CF Cntrl and observes Green status Outlet Isol) light LIT, Red status light OFF.

The operator depresses the 1 CF-16 CLOSE pushbutton 1 CF-16 (0 S/G CF Cntrl and observes Green status Inlet Isol) light LIT, Red status light OFF.

The operator depresses the 1CF-18 (0 S/G CF Cntrl 1 CF-18 CLOSE pushbutton Outlet Isol) and observes Green status light LIT, Red status light OFF.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM 0 NUREG 1021, Revision 9

Appendix C STEPS 2

(Cont'd) 3 4

5

  • 6 Page 7 of 13 PERFORMANCE INFORMATION ELEMENTS (Step 3) Check the following alarms - DARK:

"INNER DOGHOUSE LEVEL HI" (1AD-5, G-6)

"OUTER DOGHOUSE LEVEL HI" (1AD-5, H-6)

(Step 4) Check all StG NtR levels - HAVE REMAINED LESS THAN 83% (P-14 setpoint).

(Note prior to Step 5) The following step must be completed even if a Feedwater Isolation signal has not occurred.

(Step 5) Depress and release the Feedwater Isolation reset push buttons.

STANDARD The operator observes that both MCB Annunciator windows are DARK.

The operator observes all four SG NR levels and determines that all SG levels are less than 83%.

The operator reads the Note and proceeds to Step

5.

The operator depresses the Train A FWI Reset pushbutton, and observes that the Reset light is LIT.

The operator depresses the Train B FWI Reset pushbutton, and observes that the Reset ht is LIT.

StU Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM D NUREG 1021, Revision 9

(

(

Appendix C STEPS 2

(Cont'd) 3 4

5

  • 6 Page 7 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD Note:

Closing either the Inlet OR the Outlet for each S/G CF Cntrl valve satisfies the critical element of this step.

(Step 3) Check the following The operator observes that alarms - DARK:

both MCB Annunciator "INNER DOGHOUSE windows are DARK.

LEVEL HI" (1AD-5, G-6)

"OUTER DOGHOUSE LEVEL HI" (1AD-5, H-6)

(Step 4) Check all StG NtR The operator observes all levels - HAVE REMAINED four SG NR levels and LESS THAN 83% (P-14 determines that all SG setpoint).

levels are less than 83%.

Cue: If asked, S/G levels have remained <83%.

(Note prior to Step 5) The The operator reads the following step must be Note and proceeds to Step completed even if a

5.

Feedwater Isolation signal has not occurred.

(Step 5) Depress and The operator depresses the release the Feedwater Train A FWI Reset Isolation reset push buttons.

pushbutton, and observes that the Reset light is LIT.

The operator depresses the Train B FWI Reset pushbutton, and observes that the Reset light is LIT.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM D NUREG 1021, Revision 9

Appendix C STEPS 7

8 9

10 Page 8 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 6) Ensure the following are open on S/Gs to be fed:

The operator observes the 1 CF-35AB (A S/G CF Cont 1 CF-35AB Red status light Outside Isol)

LIT, Green status light OFF.

1 CF-30AB (B S/G CF Cont The operator observes the Outside Isol) 1 CF-30AB Red status light LIT, Green status light OFF.

1 CF-28AB (C S/G CF Cont The operator observes the Outside Isol) 1 CF-28AB Red status light LIT, Green status light OFF.

1 CF-26AB (D S/G CF Cont The operator observes the Outside Isol) 1 CF-26AB Red status light LIT, Green status light OFF.

(Step 7) Check both CF The operator observes that pumps - RESET the Reset light on "A" CF Pump is LIT, and the Trip light on "B" CF pump is LIT and proceeds to Step 7 RNO.

(Step 7 RNO a) Perform the The operator determines following: IF only one CF only "B" CF pump is tripped pump is tripped, THEN GO and proceeds to step 10.

TO Step 10.

(Steps 10/1 O.a) Perform the following:

The operator determines Check "RESET" light on "1A RESET light is LIT and OR 1 B CF PUMP RECIRC proceeds to the Step 10.a VALVE CLOSURE RNO.

CIRCUIT" - DARK Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM D NUREG 1021, Revision 9

(

Appendix C STEPS 7

8 9

10 Page 8 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 6) Ensure the following are open on S/Gs to be fed:

The operator observes the 1 CF-35AB (A S/G CF Cont 1 CF-35AB Red status light Outside Isol)

LIT, Green status light OFF.

1 CF-30AB (B S/G CF Cont The operator observes the Outside Isol) 1 CF-30AB Red status light LIT, Green status light OFF.

1 CF-28AB (C S/G CF Cont The operator observes the Outside Isol) 1 CF-28AB Red status light LIT, Green status light OFF.

1 CF-26AB (0 S/G CF Cont The operator observes the Outside Isol) 1 CF-26AB Red status light LIT, Green status light OFF.

(Step 7) Check both CF The operator observes that pumps - RESET the Reset light on "N CF Pump is LIT, and the Trip light on "B" CF pump is LIT and proceeds to Step 7 RNO.

(Step 7 RNO a) Perform the The operator determines following: IF only one CF only "B" CF pump is tripped pump is tripped, THEN GO and proceeds to step 10.

TO Step 10.

(Steps 10/1 O.a) Perform the following:

The operator determines Check "RESET" light on "1A RESET light is LIT and OR 1 B CF PUMP RECIRC proceeds to the Step 10.a VALVE CLOSURE RNO.

CIRCUIT" - DARK Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM 0 NUREG 1021, Revision 9

Appendix C STEPS 11 12 13 14 15 Page 9 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 10.a RNO) GO TO The operator proceeds to Step 11.

Step 11.

(Step 11) Ensure AS is After the cue, the operator supplied by either Unit 2 or proceeds to Step 12.

the Aux Electric Boiler PER Cue:

Step 24 in body of procedure.

ih,q.ft$ftOr,plJfts;AS is

$Up."ri~tf'by ViA;it.2 (Step 12) Check 1 HM-95 The operator observes the (U 1 Aux Steam Supply to 1 HM-95 Red status light CF Pumps turbine Isol) -

LIT, Green status light OFF.

OPEN (Step 13) Check CF flow -

After the cue, the operator HAS BEEN LOST FOR proceeds to Step 13 RNO.

OVER ONE HOUR.

Cue:

CF:*fte\\llnItastost 20

. mil(1utes ago.

(Step 13 RNO) GO TO Step The operator proceeds to

15.

Step 15.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM D NUREG 1021, Revision 9

(

(

Appendix C STEPS 11 12 13 14 15 Page 9 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 10.a RNO) GO TO The operator proceeds to Step 11.

Step 11.

(Step 11) Ensure AS is After the cue, the operator supplied by either Unit 2 or proceeds to Step 12.

the Aux Electric Boiler PER Cue:

Step 24 in body of procedure.

The CRSRO reports AS is supplied by Unit 2 (Step 12) Check 1 HM-95 The operator observes the (U1 Aux Steam Supply to 1 HM-95 Red status light CF Pumps turbine Isol) -

LIT, Green status light OFF.

OPEN (Step 13) Check CF flow -

After the cue, the operator HAS BEEN LOST FOR proceeds to Step 13 RNO.

OVER ONE HOUR.

Cue:

CF flow was lost 20 minutes ago.

(Step 13 RNO) GO TO Step The operator proceeds to

15.

Step 15.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM D NUREG 1021, Revision 9

Appendix C STEPS

  • 16 Page 10 of 13 PERFORMANCE INFORMATION ELEMENTS (Step 15) On CF pump to be placed in service, raise speed demand "DEM" to establish "CF HEADER PRESSURE" 50-100 psig above S/G pressure.

STANDARD The operator observes CF Header Pressure (1 CFP-5140) to be ::::800 psig, and Steam Header Pressure (1 SMP-5200) to be ::::1100 psig, and determines the current differential pressure to be ::::300 psig.

Note: '.........

rtl.~~~~r*a"~S'~l1e*.. '

~*~~ti~ft. ',~;:::;;0

.~lfit.tt.,.e AP.

The operator selects "1A" CF pump and depresses the "INC" and/or "DEC" push buttons as needed to establish CF header pressure 75 psig greater than S/G pressure.

. Tne.O~~rlltot1;~.. :n*e;x~eetiJ

~:3!::~~;~~:~1~~~<....

F~hestandard i$ fotJe.

between50~"1~Q<P~~

When lea.Viftgi~tJis ~.P~,

.>}.

S/U Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM D NUREG 1021, Revision 9

(

Appendix C STEPS

  • 16 Page 10 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 15) On CF pump to The operator observes CF be placed in service, raise Header Pressure (1 CFP-speed demand "OEM" to 5140) to be==800 psig, and establish "CF HEADER Steam Header Pressure PRESSURE" 50-100 psig (1 SMP-5200) to be==1100 above S/G pressure.

psig, and determines the current differential pressure to be==300 psig.

Note:

The operator may use the OAe (Unit 1 Overview Screen or equivalent) to monitor the AP.

The operator selects "1A" CF pump and depresses the "INC" and/or "DEC" push buttons as needed to establish CF header pressure 75 psig greater than S/G pressure.

Note:

The Operator can exceed 100 psid during attempts to obtain 50-100 psid.

The standard is to be between 50 - 100 psid when leaving this step.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM 0 NUREG 1021, Revision 9

Appendix C STEPS

  • 17 18 Page 11 of 13 PERFORMANCE INFORMATION ELEMENTS (Step 16) Establish desired feed flow to S/Gs by performing the following:

Slowly throttle open S/G CF control bypass valves Raise CF pump speed demand "OEM" to raise discharge pressure as required.

(Step 17) WHEN the following conditions are established, THEN S/G CF control bypass valves may be placed in auto as desired:

DIP between "CF HEADER PRESSURE" and S/G pressure between 50 and 100 psig.

S/G levels at 39%.

STANDARD The operator depresses the OPEN pushbutton (Red) and observes each S/G CF control bypass valve controller output rising.

The operator depresses the DEM pushbutton on the 1A CF pump speed controller until discharge pressure is adequate to provide flow.

The operator continues to feed the S/Gs.

will 1evet$a:nd b'0fnulete this ehctC:1Sttre.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

S/U Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM D NUREG 1021, Revision 9

(

(

Appendix C STEPS

  • 17 18 Page 11 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 16) Establish desired The operator depresses the feed flow to S/Gs by OPEN pushbutton (Red) performing the following:

and observes each S/G CF control bypass valve Slowly throttle open S/G CF controller output rising.

control bypass valves Raise CF pump speed The operator depresses the demand "OEM" to raise OEM pushbutton on the 1 A discharge pressure as CF pump speed controller required.

until discharge pressure is adequate to provide flow.

(Step 17) WHEN the following conditions are The operator continues to established, THEN S/G CF feed the S/Gs.

control bypass valves may be placed in auto as Cue:

desired:

D/P between "CF HEADER Another operator will monitor S/G levels and PRESSURE" and S/G complete this enclosure.

pressure between 50 and 100 psig.

S/G levels at 39%.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM 0 NUREG 1021, Revision 9

Appendix C Page 12 of 13 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM D Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM D NUREG 1021, Revision 9

(

Appendix C Page 12 of 13 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM D Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM D NUREG 1021, Revision 9

Appendix C INITIAL CONDITIONS:

INITIATING CUE:

Form ES-C-1 JPM CUE SHEET A U-1 Reactor Trip has occurred from 100% Power EP/11A15000/ES-0.1, Reactor Trip Response, is in progress and completed through subsequent step 11.

Total feed flow to S/G's is < 450 GPM and CA Pumps 1A and 1 B are not running. U-1 TD CA pump has tripped and is unavailable CF Isolation has not occurred.

The CRSRO directs you to place the 1A CF Pump in service, and establish CF to the S/G's in accordance with Enclosure 4 of EP/11A15000/ES-0.1.

If, as expected, a Red Path occurs on Heat Sink, continue with the assigned task, and the remaining crewmembers will implement EP/11A15000/FR-H.1, "Response to Loss of Secondary Heat Sink."

NUREG 1021, Revision 9 Appendix C INITIAL CONDITIONS:

INITIATING CUE:

(

Form ES-C-1 JPM CUE SHEET A U-1 Reactor Trip has occurred from 100% Power EP/1 IA/5000/ES-0. 1, Reactor Trip Response, is in progress and completed through subsequent step 11.

Total feed flow to S/G's is < 450 GPM and CA Pumps 1A and 1 B are not running. U-1 TD CA pump has tripped and is unavailable CF Isolation has not occurred.

The CRSRO directs you to place the 1A CF Pump in service, and establish CF to the S/G's in accordance with Enclosure 4 of EP/1/A/5000/ES-0.1.

If, as expected, a Red Path occurs on Heat Sink, continue with the assigned task, and the remaining crewmembers will implement EP/1/A/5000/FR-H.1, "Response to Loss of Secondary Heat Sink."

NUREG 1021, Revision 9

Appendix C Page 1 of 11 PERFORMANCE INFORMATION SIM JPM E RAFT Form ES-C-1 T

2009 Systems - Control Room JPM E NUREG 1021, Revision 9

(

Appendix C Page 1 of 11 PERFORMANCE INFORMATION Form ES-C-1 SIM JPM E DR 2009 Systems - Control Room JPM E NUREG 1021, Revision 9

Appendix C Facility:

McGuire Page 2 of 11 PERFORMANCE INFORMATION Task No.:

Form ES-C-1 Task

Title:

Manually Align Phase B HVAC Equipment JPM No.:

2009 Systems - Control Room JPM E KIA

Reference:

028, A4.01, 4.0/4.0 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The operator manually starts both Trains of the VE and VX Systems.

Required Materials:

None General

References:

EP/1/A/5000/E-0, Reactor Trip or Safety Injection, Phase B HVAC Equipment, of EP/1/A/5000/E-0, Reactor Trip or Safety Injection.

Handouts:, Phase B HVAC Equipment, of EP/1/A/5000/E-0, Reactor Trip or Safety Injection.

2009 Systems - Control Room JPM E NUREG 1021, Revision 9

(

(

Appendix C Facility:

McGuire Page 2 of 11 PERFORMANCE INFORMATION Task No.:

Form ES-C-1 Task

Title:

Manually Align Phase B HVAC Equipment JPM No.:

2009 Systems - Control Room JPM E KJA

Reference:

028, A4.01, 4.0/4.0 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The operator manually starts both Trains of the VE and VX Systems.

Required Materials:

None General

References:

EP/1/A/5000/E-0, Reactor Trip or Safety Injection Handouts:, Phase B HVAC Equipment, of EP/1/A/5000/E-0, Reactor Trip or Safety Injection., Phase B HVAC Equipment, of EP/1/A/5000/E-0, Reactor Trip or Safety Injection.

2009 Systems - Control Room JPM E NUREG 1021, Revision 9

Appendix C Time Critical Task:

Validation Time:

NO 5 minutes Page 3 of 11 PERFORMANCE INFORMATION 2009 Systems - Control Room JPM E Form ES-C-1 NUREG 1021, Revision 9

(

(

Appendix C Time Critical Task:

Validation Time:

NO 5 minutes Page 3 of 11 PERFORMANCE INFORMATION 2009 Systems - Control Room JPM E Form ES-C-1 NUREG 1021, Revision 9

Appendix C Page 4 of 11 PERFORMANCE INFORMATION SIMULATOR OPERATIONAL GUIDELINES

1.

Reset to IC # 39,100% Power, MOL. Go to RUN.

2.

Insert:

a.

MALF-NC008A Large Break LOCA on Trigger 1.

Form ES-C-1

b.

MALF-ISE004A (Both)Failure of Train A of Phase B Containment Isolation MALF-ISE004B (Both)Failure of Train B of Phase B Containment Isolation

3.

Actuate Trigger 1

4.

Perform steps 1 through 13 of EP/11A15000/E-0 (Including manually actions to overcome failure of Containment Phase B Isolation).

5.

Freeze Simulator.

1.

Reset Simulator to Temporary Snap IC-126 (December, 2008).

2.

Momentarily go to RUN to acknowledge Alarms then place Simulator in FREEZE.

3.

Leave Simulator in FREEZE until operator is ready to begin.

NOTE: FWST level is depleting rapidly and could interfere with the performance of this JPM.

2009 Systems - Control Room JPM E NUREG 1021, Revision 9 I (

Appendix C Page 4 of 11 PERFORMANCE INFORMATION Form ES-C-1

1.
2.
3.
4.
5.

OR

1.
2.
3.

SIMULATOR OPERATIONAL GUIDELINES Reset to IC # 39, 100% Power, MOL. Go to RUN.

Insert:

a.

MALF-NC008A Large Break LOCA on Trigger 1.

b.

MALF-ISE004A (Both)Failure of Train A of Phase B Containment Isolation MALF-ISE004B (Both)Failure of Train B of Phase B Containment Isolation Actuate Trigger 1 Perform steps 1 through 13 of EP/1/A/5000/E-0 (Including manually actions to overcome failure of Containment Phase B Isolation).

Freeze Simulator.

Reset Simulator to Temporary Snap IC-126 (December, 2008).

Momentarily go to RUN to acknowledge Alarms then place Simulator in FREEZE.

Leave Simulator in FREEZE until operator is ready to begin.

NOTE: FWST level is depleting rapidly and could interfere with the performance of this JPM.

2009 Systems - Control Room JPM E NUREG 1021, Revision 9

Appendix C Page 5 of 11 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout EP/1/Al5000/E-O, Enclosure 2, Phase B HVAC Equipment.

START TIME:

STEPS ELEMENTS STANDARD SIU COMMENTS REQUIRED FOR UNSAT Simulator Instructor NOTE: Leave Simulator in FREEZE until operator is ready to begin.

1 (Steps 1/1.a) Check VE The operator observes the System in operation as 1A VE Fan Green status follows: VE Fans - ON.

light LIT, and Red status light OFF and determines that the fan is OFF.

The operator observes the 1 B VE Fan Green status light LIT, and Red status light OFF and determines that the fan is OFF.

  • 2 (Steps 1.a RNO a.1-2) Start The operator places the 1 A fans as follows:

VE Fan control switch to ON, and observes the Red Select "ON".

status light LIT, Green Return switch to "AUTO".

status light OFF.

The operator returns the 1A VE Fan control switch to AUTO.

The operator places the 1 B VE Fan control switch to ON, and observes the Red status light LIT, Green status light OFF.

The operator returns the 1 B VE Fan control switch to AUTO.

2009 Systems - Control Room JPM E NUREG 1021, Revision 9 Appendix C Page 5 of 11 PERFORMANCE INFORMATION Form ES-C-1

(

(Denote Critical Steps with an asterisk*)

\\

(

Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout EP/1IA15000/E-O, Enclosure 2, Phase B HVAC Equipment.

START TIME:

STEPS ELEMENTS STANDARD S/U COMMENTS REQUIRED FOR UNSAT Simulator Instructor NOTE: Leave Simulator in FREEZE until operator is ready to begin.

1 (Steps 1 /1.a) Check VE The operator observes the System in operation as 1A VE Fan Green status follows: VE Fans - ON.

light LIT, and Red status light OFF and determines that the fan is OFF.

The operator observes the 1 B VE Fan Green status light LIT, and Red status light OFF and determines that the fan is OFF.

  • 2 (Steps 1.a RNO a.1-2) Start The operator places the 1A fans as follows:

VE Fan control switch to ON, and observes the Red Select "ON".

status light LIT, Green Return switch to "AUTO".

status light OFF.

The operator returns the 1 A VE Fan control switch to AUTO.

The operator places the 1 B VE Fan control switch to ON, and observes the Red status light LIT, Green status light OFF.

The operator returns the 1 B VE Fan control switch to AUTO.

2009 Systems - Control Room JPM E NUREG 1021, Revision 9

Appendix C STEPS 3

4 5

Page 6 of 11 PERFORMANCE INFORMATION ELEMENTS (Step 1.b) Ensure all damper mode select switches in "AUTO":

1 AVS-D-7 Mode Select 1 AVS-D-8 Mode Select 1 AVS-D-2 Mode Select 1 AVS-D-3 Mode Select.

(Step 1.c) Annulus pressure being maintained -

NEGATIVE.

(Steps 2/2.a) Check VX System in operation as follows: Time since Phase B actuation - GREATER THAN 10 MINUTES.

STANDARD The operator observes that the 1AVS-D-7 Mode Select Switch is in AUTO.

The operator observes that the 1AVS-D-8 Mode Select Switch is in AUTO.

The operator observes that the 1 AVS-D-2 Mode Select Switch is in AUTO.

The operator observes that the 1 AVS-D-3 Mode Select Switch is in AUTO.

The operator observes 1VEP-5100 and 1VEP-5110 are indicating -3" water column and determines that the Annulus pressure is negative.

After the cue, the operator recognizes that the time since Phase B actuation is greater than 10 minutes and proceeds to Step 2.b.

gi~~~.......

Pl1ase B Isolation()'n Un'it 1 actuated 12miRules

.$rg().

'/',

,>,<;.~~,.

SIU Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM E NUREG 1021, Revision 9 i

\\

(

Appendix C STEPS 3

4 5

Page 6 of 11 PERFORMANCE INFORMATION ELEMENTS STANOARO (Step 1.b) Ensure all damper mode select switches in "AUTO":

1AVS-O-7 Mode Select The operator observes that the 1AVS-O-7 Mode Select Switch is in AUTO.

1 AVS-O-8 Mode Select The operator observes that the 1AVS-O-8 Mode Select Switch is in AUTO.

1 AVS-O-2 Mode Select The operator observes that the 1 AVS-O-2 Mode Select Switch is in AUTO.

1 AVS-O-3 Mode Select.

The operator observes that the 1 AVS-O-3 Mode Select Switch is in AUTO.

(Step 1.c) Annulus pressure The operator observes being maintained -

1VEP-5100 and 1VEP-511 0 NEGATIVE.

are indicating -3" water column and determines that the Annulus pressure is negative.

(Steps 2/2.a) Check VX After the cue, the operator System in operation as recognizes that the time follows: Time since Phase B since Phase B actuation is actuation - GREATER greater than 10 minutes and THAN 10 MINUTES.

proceeds to Step 2.b.

Cue:

Phase B Isolation on Unit 1 actuated 12 minutes ago.

Form ES-C-1 S/U COMMENTS REQUIREO FOR UNSAT 2009 Systems - Control Room JPM E NUREG 1021, Revision 9

Appendix C STEPS 6

  • 7 Page 7 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2. b) Check the following - OPEN:

1 RAF-D-4 (1 B Cont Air Ret The operator observes that the 1 RAF-D-4 Green status Fan To Lwr Cont Test A) light is LIT, Red status light is OFF.

1VX-2B (1 B H2 Skimmer The operator observes that the 1VX-2B Green status Fan Isol Test A) light is LIT, Red status light is OFF.

1 RAF-D-2 (1A Cont Air Ret The operator observes that Fan To Lwr Cont Test A) the 1 RAF-D-2 Green status light is LIT, Red status light is OFF.

The operator observes that 1VX-1A (1A H2 Skimmer the 1VX-1A Green status Fan Isol Test A).

light is LIT, Red status light is OFF.

(Step 2.b RNO) open The operator presses and holds the 1 RAF-D-4 OPEN dampers.

pushbutton and observes the Red status light is LIT, Green status light is OFF.

The operator presses and holds the 1 VX-2B OPEN pushbutton and observes the Red status light is LIT, Green status light is OFF.

The operator presses and holds the 1 RAF-D-2 OPEN pushbutton and observes the Red status light is LIT, Green status light is OFF.

The operator presses and holds the 1VX-1A OPEN pushbutton and observes the Red status light is LIT, Green status light is OFF.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM E NUREG 1021, Revision 9

(

Appendix C STEPS 6

  • 7 Page 7 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.b) Check the following - OPEN:

1 RAF-D-4 (1 B Cont Air Ret The operator observes that the 1 RAF-D-4 Green status Fan To Lwr Cont Test A) light is LIT, Red status light is OFF.

1VX-2B (1 B H2 Skimmer The operator observes that the 1VX-2B Green status Fan Isol Test A) light is LIT, Red status light is OFF.

1 RAF-D-2 (1A Cont Air Ret The operator observes that Fan To Lwr Cont Test A) the 1 RAF-D-2 Green status light is LIT, Red status light is OFF.

The operator observes that 1VX-1A (1A H2 Skimmer the 1VX-1A Green status Fan Isol Test A).

light is LIT, Red status light is OFF.

(Step 2.b RNO) open The operator presses and holds the 1 RAF-D-4 OPEN dampers.

pushbutton and observes the Red status light is LIT, Green status light is OFF.

The operator presses and holds the 1VX-2B OPEN pushbutton and observes the Red status light is LIT, Green status light is OFF.

The operator presses and holds the 1 RAF-D-2 OPEN pushbutton and observes the Red status light is LIT, Green status light is OFF.

The operator presses and holds the 1VX-1A OPEN pushbutton and observes the Red status light is LIT, Green status light is OFF.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM E NUREG 1021, Revision 9

Appendix C STEPS 8

  • 9 10 Page 8 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.c) Check The operator observes the Containment Air Return 1A CAR Fan Green status fans - ON.

light LIT, and Red status light OFF.

The operator observes the 1 B CAR Fan Green status light LIT, and Red status light OFF.

(Step 2.c RNO) start fans.

The operator depresses the START pushbutton for the 1A CAR Fan, and observes the Red status light LIT, Green status light OFF.

The operator depresses the START pushbutton for the 1 B CAR Fan, and observes the Red status light LIT, Green status light OFF.

(Step 2.d) Check H2 The operator observes the Skimmer fans - ON.

1A H2 Skimmer Fan Green status light LIT, and Red status light OFF.

The operator observes the 1 B H2 Skimmer Fan Green status light LIT, and Red status light OFF.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM E NUREG 1021, Revision 9

(

{,

Appendix C STEPS 8

  • 9 10 Page 8 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.c) Check The operator observes the Containment Air Return 1A CAR Fan Green status fans - ON.

light LIT, and Red status light OFF.

The operator observes the 1 B CAR Fan Green status light LIT, and Red status light OFF.

(Step 2.c RNO) start fans.

The operator depresses the START pushbutton for the 1A CAR Fan, and observes the Red status light LIT, Green status light OFF.

The operator depresses the START pushbutton for the 1 B CAR Fan, and observes the Red status light LIT, Green status light OFF.

(Step 2.d) Check H2 The operator observes the Skimmer fans - ON.

1A H2 Skimmer Fan Green status light LIT, and Red status light OFF.

The operator observes the 1 B H2 Skimmer Fan Green status light LIT, and Red status light OFF.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM E NUREG 1021, Revision 9

Appendix C STEPS ELEMENTS Page 9 of 11 PERFORMANCE INFORMATION STANDARD

  • 11 (Step 2.d RNO) start fans.

The operator depresses the START pushbutton for the 1A H2 Skimmer Fan, and observes the Red status light LIT, Green status light OFF.

The operator depresses the START pushbutton for the 1 B H2 Skimmer Fan, and observes the Red status light LIT, Green status light OFF.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM E NUREG 1021, Revision 9

(

(

(

Appendix C STEPS ELEMENTS Page 9 of 11 PERFORMANCE INFORMATION STANDARD

  • 11 (Step 2.d RNO) start fans.

The operator depresses the START pushbutton for the 1 A H2 Skimmer Fan, and observes the Red status light LIT, Green status light OFF.

The operator depresses the START pushbutton for the 1 B H2 Skimmer Fan, and observes the Red status light LIT, Green status light OFF.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM E NUREG 1021, Revision 9

Appendix C Page 10 of 11 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM E Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM E NUREG 1021, Revision 9 Appendix C Page 10 of 11 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM E Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM E NUREG 1021, Revision 9

Appendix C INITIAL CONDITIONS:

INITIATING CUE:

Form ES-C-1 JPM CUE SHEET You are the Unit 2 BOP.

Unit 1 has experienced a Large Break LOCA.

The crew is implementing EP/1/Al5000/E-O, Reactor Trip or Safety Injection.

The CRSRO has directed you to check Phase B HVAC equipment in accordance with Enclosure 2, "Phase B HVAC Equipment," of EP/11A15000/E-O, "Reactor Trip or Safety Injection."

NUREG 1021, Revision 9 Appendix C INITIAL CONDITIONS:

INITIATING CUE:

(

(

Form ES-C-1 JPM CUE SHEET You are the Unit 2 BOP.

Unit 1 has experienced a Large Break LOCA.

The crew is implementing EP/1/A/SOOO/E-0, Reactor Trip or Safety Injection.

The CRSRO has directed you to check Phase B HVAC equipment in accordance with Enclosure 2, "Phase B HVAC Equipment," of EP/1/A/SOOO/E-0, "Reactor Trip or Safety Injection."

NUREG 1021, Revision 9

Appendix C Page 1 of 13 PERFORMANCE INFORMATION Form ES-C-1 81M JPM F FT 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

(

Appendix C Page 1 of 13 PERFORMANCE INFORMATION Form ES-C-1 SIM JPM F 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

Appendix C Facility:

McGuire Page 2 of 13 PERFORMANCE INFORMATION Task No.:

Form ES-C-1 Task

Title:

Perform Diesel Generator Operability Test JPM No.:

2009 Systems - Control Room JPM F KIA

Reference:

064, A4.06, 3.9/3.9 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The 1 B DG is started from the Control Room and prepared for parallel operation with 1 ETB. The 1 B DG is stopped using its normal stop switch when indications of a sudden loss of crankcase vacuum and a loss of Engine speed are observed.

Required Materials:

None General

References:

PT/1/Al4350/002B, "Diesel Generator 1 B Operability Test."

2009 Systems - Control Room JPM F NUREG 1021, Revision 9

(

(

Appendix C Facility:

McGuire Page 2 of 13 PERFORMANCE INFORMATION Task No.:

Form ES-C-1 Task

Title:

Perform Diesel Generator Operability Test JPM No.:

2009 Systems - Control Room JPM F KIA

Reference:

064, A4.06, 3.9/3.9 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

x Classroom Simulator x

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The 1 B DG is started from the Control Room and prepared for parallel operation with 1 ETB. The 1 B DG is stopped using its normal stop switch when indications of a sudden loss of crankcase vacuum and a loss of Engine speed are observed.

Required Materials:

None General

References:

PT/1/A/4350/002B, "Diesel Generator 1 B Operability Test."

2009 Systems - Control Room JPM F NUREG 1021, Revision 9

Appendix C Handouts:

Time Critical Task:

Validation Time:

Page 3 of 13 PERFORMANCE INFORMATION Form ES-C-1 PTl1/A143501002B, "Diesel Generator 1 B Operability Test," with 3.1 marked up for place-keeping through Step 2.6.

NO 20 minutes 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

(

Appendix C Handouts:

Time Critical Task:

Validation Time:

Page 3 of 13 PERFORMANCE INFORMATION Form ES-C-1 PT/1/A/43501002B, "Diesel Generator 1 B Operability Test," with 3.1 marked up for place-keeping through Step 2.6.

NO 20 minutes 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

Appendix C Page 4 of 13 PERFORMANCE INFORMATION SIMULATOR OPERATIONAL GUIDELINES

1.

Reset to IC # 20, 100% Power, MOL. Go to RUN.

2.

Ensure that the A Train is the operating Train.

3.

Insert DG006B2, over-under excitation value = 95.

Form ES-C-1

4.

1AD-11/D06 = ON, DIG B Panel trouble (Simulates Before & After LOP On).

5.

Insert MALF-DG002B, DIG B FAILS TO MINIMUM SPEED, Assign to Trigger #1.

1.

Reset Simulator to Temporary Snap IC-127 (December, 2008).

2.

Momentarily go to run and acknowledge alarms.

NOTE: During the NLO Actions of JPM Step 10, Simulator Instructor must DELETE 1AD-111D06

= ON (Simulates Before & After LOP Off)

THEN, assign 1AD-11/D06 = ON to Trigger #1, DIG B Panel trouble (Simulates High' Crankcase Pressure).

NOTE: At step 6 once DIG had come up to voltage and freq, DELETED DG006B2. This will allow the student to control voltage.

2009 Systems - Control Room JPM F NUREG 1021, Revision 9

(

Appendix C Page 4 of 13 PERFORMANCE INFORMATION SIMULATOR OPERATIONAL GUIDELINES

1.

Reset to IC # 20, 100% Power, MOL. Go to RUN.

2.

Ensure that the A Train is the operating Train.

3.

Insert DG006B2, over-under excitation value = 95.

Form ES-C-1

4.

1AD-111D06 = ON, DIG B Panel trouble (Simulates Before & After LOP On).

5.

Insert MALF-DG002B, DIG B FAILS TO MINIMUM SPEED, Assign to Trigger #1.

OR

1.

Reset Simulator to Temporary Snap IC-127 (December, 2008).

2.

Momentarily go to run and acknowledge alarms.

NOTE: During the NLO Actions of JPM Step 10, Simulator Instructor must DELETE 1AD-111D06

= ON (Simulates Before & After LOP Off)

THEN, assign 1AD-111D06 = ON to Trigger #1, DIG B Panel trouble (Simulates High' Crankcase Pressure).

NOTE: At step 6 once DIG had come up to voltage and freq, DELETED DG006B2. This will allow the student to control voltage.

2009 Systems - Control Room JPM F NUREG 1021, Revision 9

Appendix C Page 5 of 13 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout PT/1/A/4350/002B, Enclosure 13.1, marked up for place-keeping through Step 2.6.

START TIME:

STEPS

  • 1 2

3 ELEMENTS (Step 2.7) Place Control Room "1 B DIG Mode Select" to applicable position:

"LOCAL" to start DIG from local panel OR "C/R" to start DIG from Control Room (Step 2.8) Notify Unit 1 Control Room that adjusting Main Generator voltage while the DIG is tied to the grid will significantly affect the power factor on the operating DIG.

(Caution prior to Step 2.9)

Steps 2.9-2.12 should be performed in less than two minutes.

2009 Systems - Control Room JPM F STANDARD The operator places the Control Room" 1 B DIG Mode Select" to C/R.

The operator informs the OATC that adjusting Main Generator voltage while the DIG is tied to the grid will significantly affect the power factor on the operating DIG.

The operator reads Caution and proceeds to Step 2.9.

SIU COMMENTS REQUIRED FOR UNSAT NUREG 1021, Revision 9

(

(

Appendix C Page 5 of 13 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout PT/1/A/4350/002B, Enclosure 13.1, marked up for place-keeping through Step 2.6.

START TIME:

STEPS ELEMENTS STANDARD SIU COMMENTS REQUIRED FOR UNSAT

  • 1 (Step 2.7) Place Control The operator places the Room "1 B DIG Mode Control Room "1 B DIG Select" to applicable Mode Select" to C/R.

position:

"LOCAL" to start DIG from local panel OR "C/RI! to start DIG from Control Room 2

(Step 2.8) Notify Unit 1 The operator informs the Control Room that adjusting OA TC that adjusting Main Main Generator voltage Generator voltage while the while the DIG is tied to the DIG is tied to the grid will grid will significantly affect significantly affect the the power factor on the power factor on the operating DIG.

operating DIG.

Cue:

Acknowledge as the U-1 OATC.

3 (Caution prior to Step 2.9)

The operator reads Caution Steps 2.9-2.12 should be and proceeds to Step 2.9.

performed in less than two minutes.

2009 Systems - Control Room JPM F NUREG 1021, Revision 9

Appendix C STEPS 4

  • 5 6

Page 6 of 13 PERFORMANCE INFORMATION ELEMENTS (Step 2.9) Rotate "Load Limit" control knob on Woodward Governor Actuator counter-clockwise to "SLOW START" position.

(Step 2.10) Depress "START" on "18 Diesel Generator. "

(Step 2.11) Check DIG starts and reaches 95%

speed (57 Hz or local start timer times out).

STANDARD The operator contacts the NEO and directs that the "Load Limit" control knob on Woodward Governor Actuator be rotated counter-clockwise to "SLOW START" position.

Cue:

The operator depresses the START pushbutton on the 18 DIG, and observes Red status light LIT, and Green status light OFF.

The operator observes status light 1 SI-15/8-3 LIT momentarily then OFF, and THEN status light 1 SI-15/8-4 LIT.

The operator observes 18 DG Frequency to be :::::60.2 Hz.

S/U Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

(

(

\\

Appendix C STEPS 4

  • 5 6

Page 6 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.9) Rotate "Load The operator contacts the Limit" control knob on NEO and directs that the Woodward Governor "Load Limit" control knob on Actuator counter-clockwise Woodward Governor to "SLOW START" position.

Actuator be rotated counter-clockwise to "SLOW START" position.

Cue:

NEO reports that the Load Limit control knob is in the "SLOW START" position.

(Step 2.10) Depress The operator depresses the "START" on "18 Diesel START pushbutton on the Generator."

1 8 DIG, and observes Red status light LIT, and Green status light OFF.

The operator observes status light 1 SI-15/8-3 LIT momentarily then OFF, and THEN status light 1 SI-15/8-4 LIT.

(Step 2.11) Check DIG The operator observes 18 starts and reaches 95%

DG Frequency to be ::::60.2 speed (57 Hz or local start Hz.

timer times out).

Simulator Operator:

OELEt'E"DG00682" to allow student to control voltage.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

Appendix C STEPS 7

8 9

Page 7 of 13 PERFORMANCE INFORMATION ELEMENTS (Step 2.12) When DIG has started, rotate "Load Limit" control knob on Woodward Governor fully clockwise (MAX FUEL).

(Step 2.13) Record DIG start date/time:

(Step 2.14) Evaluate operability of 1 B DIG.

STANDARD The operator contacts the NEO and directs that the "Load Limit" control knob on Woodward Governor Actuator be rotated fully clockwise.

The operator records the current time and date in the space provided.

The operator requests the CRSRO to evaluate the operability of the 1 B DIG inoperable.

SIU Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

(

(

Appendix C STEPS 7

8 9

Page 7 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.12) When DIG has The operator contacts the started, rotate "Load Limit" NEO and directs that the control knob on Woodward "Load Limit" control knob on Governor fully clockwise Woodward Governor (MAX FUEL).

Actuator be rotated fully clockwise.

Cue:

,NIi:O.r~ports that the Load

.' Limitcontrol knob is in the "MAX FUEL" position.

(Step 2.13) Record DIG The operator records the start date/time:

current time and date in the space provided.

(Step 2.14) Evaluate The operator requests the operability of 1 B DIG.

CRSRO to evaluate the operability of the 1 B DIG inoperable.

Cue:

Examiner Acknowledge as the CRSRO and Initial Step 2.14 in procedure.

Form ES-C-1 SIU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

Appendix C STEPS 10 ELEMENTS (Steps 2.15-21) Local actions.

Page 8 of 13 PERFORMANCE INFORMATION STANDARD The operator observes that Step 2.15-2.21 are local actions and directs the NEO to perform these actions in the procedure and report back to the Control Room.

Q'EbETE 1 AD-i11'D06. = ON f~i'f'l'WlatesBefGre'& Alte'r 4&PO'ff)rHlitkas~.1f1 t~~\\o~\\tllli:~:QiN*te:.*.*.

    • tri~g~JI~'.#.,;,afG* B *P*ane1' troub1e (Sirriuliltes High CtC{:nkcase pres$ur.).

and "~'W""~

2.I'1a1'88* flfl'ed*"

j)'1fC!>neg!l:t,e.

Q;tl~:

'lJatfi(e'dr.the NLO rA"fort!:t*

StU Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

(

(

Appendix C STEPS ELEMENTS 10 (Steps 2.15-21) Local actions.

Page 8 of 13 PERFORMANCE INFORMATION STANDARD The operator observes that Step 2.15-2.21 are local actions and directs the NEO to perform these actions in the procedure and report back to the Control Room.

Simulator Operator:

DELETE 1AD-11/D06 = ON (Simulates Before & After LOP Off) THEN, assign 1AD-11/D06 = ON to Trigger #1, DIG B Panel trouble (Simulates High Crankcase Pressure).

Cue:

NEO reports that local actions have been taken and steps 2.15 through 2.21 are signed off in the procedure.

Cue:

If asked, the NLO reports:

Oil level is visible in the Governor sight glass.

Jacket Water pressure is

> 24 psig.

Lube Oil pressure is > 36 psig.

The Before & After LOP is OFF and in AUTO.

1LD-113B (1B DIG Lube Oil Filter Bypass) indicates Closed~

  • Fuel Oil Pressure is > 32 psig.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

Appendix C STEPS 11 12 13 14

  • 15 Page 9 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.22) Check the The operator turns on OAC following on OAC (Turn-on Code RNESS1 Band Code - RNESS1B):

observes that 1 RN-71 B is OPEN and that there is 1 RN-71 B (B KD HX Supply

===1500 gpm through the 1 B 1501) indicates "OPEN."

DIG Heat Exchanger.

RN flow indicated through DIG Heat Exchanger.

(Step 2.23) Check the following:

The operator observes 1 B Steady-state DIG volts 3740 DIG voltage to be===3953 V.

-4580 V.

The operator observes 1 B Steady-state DIG frequency DIG frequency to be===60.2 58.8 - 61.2 Hz.

Hz.

(Step 2.24) Ensure Control The operator observes the Room "1 B DIG Mode Control Room" 1 B DIG Select" to applicable Mode Select" to C/R.

position:

"LOCAL" to load DIG from local panel OR "C/R" to load DIG from Control Room (Step 2.25) Check "Line The operator observes line Volts" 3960-4360 V.

voltage to be===4069 V.

(Step 2.26) Adjust DIG The operator rotates the 1 B voltage 50-100 V higher DIG Voltage Adjust switch than line voltage using "1 B to RAISE and adjusts DG DIG Voltage Adjust."

voltage to===4119-4169 V.

Form ES-C-1 SIU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

(

Appendix C STEPS 11 12 13 14

  • 15 Page 9 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.22) Check the The operator turns on OAC following on OAC (Turn-on Code RNESS 1 Band Code - RNESS1 B):

observes that 1 RN-71 B is OPEN and that there is 1 RN-71 B (B KD HX Supply

1500 gpm through the 1 B Isol) indicates "OPEN."

DIG Heat Exchanger.

RN flow indicated through DIG Heat Exchanger.

(Step 2.23) Check the following:

The operator observes 1 B Steady-state DIG volts 3740 DIG voltage to be ::::3953 V.

-4580 V.

The operator observes 1 B Steady-state DIG frequency DIG frequency to be :::::60.2 58.8 - 61.2 Hz.

Hz.

(Step 2.24) Ensure Control The operator observes the Room "1 B DIG Mode Control Room "1 B DIG Select" to applicable Mode Select" to C/R.

position:

"LOCAL" to load DIG from local panel OR "C/R" to load DIG from Control Room (Step 2.25) Check "Line The operator observes line Volts" 3960-4360 V.

voltage to be :::::4069 V.

(Step 2.26) Adjust DIG The operator rotates the 1 B voltage 50-100 V higher DIG Voltage Adjust switch than line voltage using "1 B to RAISE and adjusts DG DIG Voltage Adjust."

voltage to ::::4119-4169 V.

Form ES-C-1 SIU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

Appendix C STEPS 16 17

  • 18
  • 19 Page 10 of 13 PERFORMANCE INFORMATION ELEMENTS (Caution prior to Step 2.27)

Failure of the Droop Permissive could result in erratic DIG operation while paralleled to the bus.

(Step 2.27) IF OAC available, check OAC point M1 D3356 (1 B DIG Droop Permissive) indicates "COMPLETE."

(Step 2.28) Place "1 B DIG Synch" to "ON."

(Step 2.29) Using 1 B DIG Gov Cntrl, adjust DIG speed to allow synchroscope to move slowly and smoothly in the FAST (clockwise) direction.

STANDARD The operator reads the Caution and proceeds to Step 2.27.

The operator observes OAC Point M1 D3356 indicates COMPLETE.

The operator places the 1 B DIG Synch Switch to ON, and observes synch scope stopped at 5 o'clock.

The operator uses the Governor Control adjust so that the synchroscope is moving slowly and smoothly in the FAST (clockwise) direction.

Simulator Operator:

Operate Key #11 to fail GIG to minimum speed.

Note;i;S,nchroscope. wUI rapid,\\,:Change;~f¥ection, and'1AD-11/b~6wiU alarm.

SIU Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

(

(

Appendix C STEPS 16 17

  • 18
  • 19 Page 10 of 13 PERFORMANCE INFORMATION ELEMENTS STANDARD (Caution prior to Step 2.27)

The operator reads the Failure of the Droop Caution and proceeds to Permissive could result in Step 2.27.

erratic DIG operation while paralleled to the bus.

(Step 2.27) IF OAC The operator observes OAC available, check OAC point Point M1 D3356 indicates M1 D3356 (1 B DIG Droop COMPLETE.

Permissive) indicates "COMPLETE."

(Step 2.28) Place "1 B DIG The operator places the 1 B Synch" to "ON."

DIG Synch Switch to ON, and observes synch scope stopped at 5 o'clock.

(Step 2.29) Using 1 B DIG The operator uses the Gov Cntrl, adjust DIG speed Governor Control adjust so to allow synchroscope to that the synchroscope is move slowly and smoothly moving slowly and smoothly in the FAST (clockwise) in the FAST (clockwise) direction.

direction.

Simulator Operator:

Operate Key #1 to fail DIG to minimum speed.

Note: Synchroscope will rapidly change direction, and 1AD-111D-6 will alarm.

Cue:

The operator may contact theNEO.

If so, report that the DG is making a great deal of noise.

Form ES-C-1 SIU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

Appendix C STEPS ELEMENTS Page 11 of 13 PERFORMANCE INFORMATION STANDARD Form ES-C-1 SIU COMMENTS REQUIRED FOR UNSAT

  • 20 (Precaution 6.7) IF a The operator places the 1 B sudden loss of crankcase DIG normal stop switch to vacuum is indicated, STOP.

together with an unusual knock or sudden decrease of speed, stop engine with normal stop switch to ensure circulation of LD and KD for at least 20 minutes.

Engine covers must remain in place during this cooling period, since engine vapors may ignite.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

2009 Systems - Control Room JPM F NUREG 1021, Revision 9

(

(

Appendix C STEPS ELEMENTS Page 11 of 13 PERFORMANCE INFORMATION STANDARD Form ES-C-1 SIU COMMENTS REQUIRED FOR UNSAT

  • 20 (Precaution 6.7) IF a The operator places the 1 B sudden loss of crankcase DIG normal stop switch to vacuum is indicated, STOP.

together with an unusual knock or sudden decrease of speed, stop engine with normal stop switch to ensure circulation of LD and KD for at least 20 minutes.

Engine covers must remain in place during this cooling period, since engine vapors may ignite.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

2009 Systems - Control Room JPM F NUREG 1021 J Revision 9

(

(

Appendix C Page 12 of 13 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM F Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

(

Appendix C Page 12 of 13 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM F Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM F NUREG 1021, Revision 9

Appendix C INITIAL CONDITIONS:

INITIATING CUE:

Form ES-C-1 JPM CUE SHEET Unit 1 is operating at 100% power.

A monthly test of the 1 B Emergency Diesel Generator is required.

The A Train is the operating Train.

The System Engineer wants to start and stop the Diesel from the Control Room.

PT/11A143501002B Enclosure 13.1 is complete through Step 2.6.

Two NEOs, Bob and Carol are standing by at the 1 B DIG to assist. They have a copy of the PT.

The CRSRO has directed you to conduct a Slow Start of the 1 B Emergency Diesel Generator starting with Step 2.7 of Enclosure 13.1 of PT/11A143501002B, "Diesel Generator 1 B Operability Test."

NUREG 1021, Revision 9 Appendix C INITIAL CONDITIONS:

INITIATING CUE:

(

(

Form ES-C-1 JPM CUE SHEET Unit 1 is operating at 100% power.

A monthly test of the 1 B Emergency Diesel Generator is required.

The A Train is the operating Train.

The System Engineer wants to start and stop the Diesel from the Control Room.

PT/1/A/43501002B Enclosure 13.1 is complete through Step 2.6.

Two NEOs, Bob and Carol are standing by at the 1 B DIG to assist. They have a copy of the PT.

The CRSRO has directed you to conduct a Slow Start of the 1 B Emergency Diesel Generator starting with Step 2.7 of Enclosure 13.1 of PT/1/A/43501002B, "Diesel Generator 1 B Operability Test."

NUREG 1021, Revision 9

Appendix C Job Performance Measure Worksheet Form ES-C-1 81M JPM G 2009 Systems - Control Room JPM G NUREG 1021, Revision 9

(

Appendix C Job Performance Measure Worksheet Form ES-C-1 81M JPM G 2009 Systems - Control Room JPM G NUREG 1021, Revision 9

Appendix C Facility:

McGuire Job Performance Measure Worksheet Task No.:

Form ES-C-1 Task

Title:

Restore Repaired Power Range Channel to Service JPM No.:

2009 Systems - Control Room JPM G KIA

Reference:

015 A2.01 3.5/3.9 Examinee:

Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

Complete a restoration of a previously failed Power Range Channel and recognize that the instrument has failed again during the restoration. All critical tasks evaluated as satisfactory.

Required Materials:

N43 Control Power Fuses General

References:

AP/1/Al5500/16, Malfunction of Nuclear Instrumentation Handouts:

AP/1/Al5500/16, Malfunction of Nuclear Instrumentation, Case III, marked up for place-keeping through Step 21.

2009 Systems - Control Room JPM G NUREG 1021, Revision 9

(

Appendix C Facility:

Task

Title:

KIA

Reference:

Examinee:

Facility Evaluator:

Method of testing:

Job Performance Measure Worksheet Form ES-C-1 McGuire Restore Repaired Power Range Channel to Service 015 A2.01 3.5/3.9 Task No.:

JPM No.:

2009 Systems - Control Room JPM G Examiner:

Date:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Initial Conditions:

With Unitfat100% po\\.ver, Power Rang~ ChannelN43 failed high.

TheControl Room crew removed Power Range Channel N43 from service in accordance with AP16, "Malfunction of Nuclear Instrumentation," Case III.

T\\1sinstrument has been out of service for 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br />.

... 'IAE has iRdlcatedthatthe,channel!1a'sbeen repaired and can now be restored to service.

Task Standard:

Complete a restoration of a previously failed Power Range Channel and recognize that the instrument has failed again during the restoration. All critical tasks evaluated as satisfactory.

Required Materials:

N43 Control Power Fuses General

References:

AP/1/A/5500/16, Malfunction of Nuclear Instrumentation Handouts:

AP/1/A/5500/16, Malfunction of Nuclear Instrumentation, Case III, marked up for place-keeping through Step 21.

Initiating Cue:The'CRS~O ha~':direCt~d yoU t'o'.~~store Pow$r Range Channel N43 to service irraccordance with Step 22ofAP16, "Malfunction of Nuclear Instrumentation," Case III, "Power Range Malfunction."

2009 Systems - Control Room JPM G NUREG 1021, Revision 9

Appendix C Time Critical Task:

NO Validation Time:

5 minutes 2009 Systems - Control Room JPM G Job Performance Measure Worksheet Form ES-C-1 NUREG 1021, Revision 9 Appendix C Time Critical Task:

NO Validation Time:

5 minutes

(

2009 Systems - Control Room JPM G Job Performance Measure Worksheet Form ES-C-1 NUREG 1021, Revision 9

Appendix C Job Performance Measure Worksheet Form ES-C-1 SIMULATOR OPERATIONAL GUIDELINES

1. Reset simulator to IC-39, 100% Power
2. Place in RUN and allow time to stabilize
3. Insert Malfunction ENB13F, Power Range Channel Failure, N43
4. Perform the actions of AP/1 IA/5500/16 up through step 21.
5. Run CAEPZZPR43BS
6. Remove Malfunction.
7. Freeze the Simulator.
1. Reset to IC-129.

NOTE: The Simulator Instructor will need to insert Malfunction ENB013F just prior to Step 13 of JPM.

2009 Systems - Control Room JPM G NUREG 1021, Revision 9

(

(

Appendix C Job Performance Measure Worksheet Form ES-C-1 SIMULATOR OPERATIONAL GUIDELINES

1. Reset simulator to IC-39, 100% Power
2. Place in RUN and allow time to stabilize
3. Insert Malfunction ENB13F, Power Range Channel Failure, N43
4. Perform the actions of AP/1 IA/5500/16 up through step 21.
5. Run CAEPZZPR43BS
6. Remove Malfunction.
7. Freeze the Simulator.

OR

1. Reset to IC-129.

NOTE: The Simulator Instructor will need to insert Malfunction ENB013F just prior to Step 13 of JPM.

2009 Systems - Control Room JPM G NUREG 1021, Revision 9

Appendix C Page 5 of 10 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout AP/1/A/5500/16, with Case III marked up for place-keeping through step 21.

START TIME:

STEPS ELEMENTS STANDARD StU COMMENTS REQUIRED FOR UNSAT

  • 1 (Step 22) WHEN malfunctioning PtR channel repaired, THEN perform the following:

(Step 22.a) Ensure Operator checks fuses installed in Power Range B instrument power fuses in Drawer.

"POWER RANGE B" drawer installed.

  • 2 (Step 22.b) Install control Operator inserts fuses into power fuses in "POWER Power Range A Drawer.

RANGE A" drawer.

The operator observes the Drawer lights come back on.

  • 3 (Step 22.c) Select "RESET" Operator selects RESET on on the "RATE MODE the Rate Mode Switch and SWITCH".

allows spring-return to NORMAL.

The operator observes the Positive Rate Trip light extinguishes.

4 (Step 22.d) Check reactor Operator observes other power-GREATER THAN Power Range Channels and 25%.

determines that the plant is at 100% power.

2009 Systems - Control Room JPM G NUREG 1021, Revision 9

(,

Appendix C Page 5 of 10 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout AP/1/A/5500/16, with Case III marked up for place-keeping through step 21.

START TIME:

STEPS ELEMENTS STANDARD StU COMMENTS REQUIRED FOR UNSAT

  • 1 (Step 22) WHEN malfunctioning PtR channel repaired, THEN perform the following:

(Step 22.a) Ensure Operator checks fuses installed in Power Range B instrument power fuses in Drawer.

"POWER RANGE B" drawer installed.

  • 2 (Step 22.b) Install control Operator inserts fuses into power fuses in "POWER Power Range A Drawer.

RANGE A" drawer.

The operator observes the Drawer lights come back on.

  • 3 (Step 22.c) Select "RESET" Operator selects RESET on on the "RATE MODE the Rate Mode Switch and SWITCH".

allows spring-return to NORMAL.

The operator observes the Positive Rate Trip light extinguishes.

4 (Step 22.d) Check reactor Operator observes other power - GREATER THAN Power Range Channels and 25%.

determines that the plant is at 100% power.

2009 Systems - Control Room JPM G NUREG 1021, Revision 9

Appendix C STEPS 5

6

  • 7
  • 8
  • 9 Page 6 of 10 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 22.e) Check the Operator observes that the following bistable - LIT:

P/R HI FLUX LO STPT Bistable light is LIT (1 S12-

"P/R HI FLUX LO STPT" C12).

(1 SI-2).

(Step 22.f) Check the Operator observes that the following bistables - DARK:

P/R HI FLUX HI STPT "P/R HI FLUX HI STPT" Bistable light is DARK (1 SI2-C13).

(1SI-2)

"P/R HI FLUX RATE" (1SI-Operator observes that the P/R HI FLUX HI RATE 3).

Bistable light is DARK (1SI3-C1).

(Step 22.g) Place At Comparator and Rate "COMPARATOR Drawer, Operator places CHANNEL DEFEAT" switch the COMPARATOR to "NORMAL".

CHANNEL DEFEAT switch to NORMAL.

The operator observes the Comparator Defeat light extinguishes.

(Step 22.h) Place "POWER At Detector Current MISMATCH BYPASS" Comparator Drawer, switch to "OPERATE".

Operator places the POWER MISMATCH BYPASS switch to OPERATE.

(Step 22.i) Place "UPPER At Detector Current SECTION" switch to Comparator Drawer, "NORMAL".

Operator places the UPPER SECTION switch to NORMAL.

The operator observes the Channel Defeat light extinguishes.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM G NUREG 1021, Revision 9

(

(

Appendix C STEPS 5

6

  • 7
  • 8
  • 9 Page 6 of 10 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 22.e) Check the Operator observes that the following bistable - LIT:

P/R HI FLUX LO STPT Bistable light is LIT (1 S12-

"P/R HI FLUX LO STPT" C12).

(1SI-2).

(Step 22.f) Check the Operator observes that the following bistables - DARK:

P/R HI FLUX HI STPT "P/R HI FLUX HI STPT" Bistable light is DARK (1 SI2-C13).

(1SI-2)

"P/R HI FLUX RATE" (1SI-Operator observes that the P/R HI FLUX HI RATE 3).

Bistable light is DARK (1SI3-C1).

(Step 22.g) Place At Comparator and Rate "COMPARA TOR Drawer, Operator places CHANNEL DEFEAT" switch the COMPARATOR to "NORMAL".

CHANNEL DEFEAT switch to NORMAL.

The operator observes the Comparator Defeat light extinguishes.

(Step 22.h) Place "POWER At Detector Current MISMA TCH BYPASS" Comparator Drawer, switch to "OPERATE".

Operator places the POWER MISMATCH BYPASS switch to OPERATE.

(Step 22.i) Place "UPPER At Detector Current SECTION" switch to Comparator Drawer, "NORMAL".

Operator places the UPPER SECTION switch to NORMAL.

The operator observes the Channel Defeat light extinguishes.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM G NUREG 1021, Revision 9

Appendix C STEPS

  • 10
  • 11
  • 12 Page 7 of 10 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 22.j) Place "LOWER At Detector Current SECTION" switch to Comparator Drawer, "NORMAL".

Operator places the LOWER SECTION switch to NORMAL.

The operator observes the Channel Defeat light extinguishes.

(Step 22.k) Place "ROD At Detector Current STOP BYPASS" switch to Comparator Drawer, "OPERATE".

Operator places the ROD STOP BYPASS switch to OPERATE.

(Step 22.1) Place "P/R TO At 1 MC2, Operator places S/G PROGRAM LEVEL the P/R TO S/G PROGRAM CHANNEL DEFEAT" switch LEVEL CHANNEL DEFEAT to "NORM".

switch to NORM.

  • SimuJaitOr.jh$'.ro'tltor:

Upon completion of Step 22Jinsert.Malfunction EtfSlJ1Gf jFaUiureo.n. f't43.

~:~ttf:* +his will~a'Use AD-

.2tF~*'~*~fI~.HI 'Yott.,e..'

  • F.Ji~*~"'il:1h":tfP~ta~r

.",;' :': '!,.~.

", '\\ i ~

rinlyaddress ARP1 AD*

.~F-3*or go directly to AP-1<1 I*,*.;::i. ;.... ;...

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM G NUREG 1021, Revision 9

(

(

Appendix C STEPS

  • 10
  • 11
  • 12 Page 7 of 10 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 22.j) Place "LOWER At Detector Current SECTION" switch to Comparator Drawer, "NORMAL".

Operator places the LOWER SECTION switch to NORMAL.

The operator observes the Channel Defeat light extinguishes.

(Step 22.k) Place "ROD At Detector Current STOP BYPASS" switch to Comparator Drawer, "OPERATE".

Operator places the ROD STOP BYPASS switch to OPERATE.

(Step 22.1) Place "P/R TO At 1 MC2, Operator places S/G PROGRAM LEVEL the P/R TO S/G PROGRAM CHANNEL DEFEAT" switch LEVEL CHANNEL DEFEAT to "NORM".

switch to NORM.

Simulator Instructor:

Upon completion of Step 22.1 insert Malfunction ENB013F, Failure on N43.

Note: This will cause AD-2/F3, "P/R HI Voltage Failure." The operator may address ARP1AD-2/F-3 or go directly to AP-

16.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM G NUREG 1021, Revision 9

Appendix C STEPS

  • 13 ELEMENTS Page 8 of 10 PERFORMANCE INFORMATION STANDARD (Immediate Action) Go to Operator addresses the Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT APt1tAl5500t16, beginning of the procedure Malfunction of Nuclear for Case III.

Instrumentation.

  • 14 (Step 1) Place control rods Operator places Rods in in manual.

MANUAL.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

2009 Systems - Control Room JPM G NUREG 1021, Revision 9

(

(

Appendix C STEPS

  • 13 ELEMENTS Page 8 of 10 PERFORMANCE INFORMATION STANDARD (Immediate Action) Go to Operator addresses the Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT AP/1/A/5500/16, beginning of the procedure Malfunction of Nuclear for Case III.

Instrumentation.

  • 14 (Step 1) Place control rods Operator places Rods in in manual.

MANUAL.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

2009 Systems - Control Room JPM G NUREG 1021, Revision 9

Appendix C Page 9 of 10 VERIFICATION OF COMPLETION Job Performance Measure No.:

2008 Audit JPM G Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Form ES-C-1 Examiner's Signature:

Date:

2009 Systems - Control Room JPM G NUREG 1021, Revision 9

(

(

(

Appendix C Page 9 of 10 VERIFICATION OF COMPLETION Job Performance Measure No.:

2008 Audit JPM G Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Form ES-C-1 Examiner's Signature:

Date:

2009 Systems - Control Room JPM G NUREG 1021, Revision 9

Appendix C INITIAL CONDITIONS:

INITIATING CUE:

Form ES-C-1 JPM CUE SHEET With Unit 1 at 100% power, Power Range Channel N43 failed high.

The Control Room crew removed Power Range Channel N43 from service in accordance with AP16, "Malfunction of Nuclear Instrumentation," Case III.

The instrument has been out of service for 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br />.

IAE has indicated that the channel has been repaired and can now be restored to service.

The CRSRO has directed you to restore Power Range Channel N43 to service in accordance with Step 22 of AP16, "Malfunction of Nuclear Instrumentation," Case III, "Power Range Malfunction."

NUREG 1021, Revision 9 Appendix C

(

INITIAL CONDITIONS:

INITIATING CUE:

(

Form ES-C-1 JPM CUE SHEET With Unit 1 at 100% power, Power Range Channel N43 failed high.

The Control Room crew removed Power Range Channel N43 from service in accordance with AP16, "Malfunction of Nuclear Instrumentation," Case III.

The instrument has been out of service for 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br />.

IAE has indicated that the channel has been repaired and can now be restored to service.

The CRSRO has directed you to restore Power Range Channel N43 to service in accordance with Step 22 of AP16, "Malfunction of Nuclear Instrumentation," Case III, "Power Range Malfunction."

NUREG 1021, Revision 9

Appendix C Page 1 of 14 PERFORMANCE INFORMATION Form ES-C-1 81M JPM H R

2009 Systems - Control Room JPM H NUREG 1021, Revision 9

(

I

\\

Appendix C Page 1 of 14 PERFORMANCE INFORMATION Form ES-C-1 SIM JPM H 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

Appendix C Page 2 of 14 PERFORMANCE INFORMATION Form ES-C-1 Facility:

McGuire Task No.:

MO-7319, MO-3331.3 Task

Title:

Place Standby Component Cooling JPM No.:

2009 Systems - Control Train in Operation Room JPM H KIA

Reference:

008, A4.01, 3.3/3.1 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The '8' Train Component Cooling pumps are started in accordance with AP/1/A15500/21, Loss of Component Cooling Water.

Required Materials:

None General

References:

AP/1/A15500/21, Loss of Component Cooling Water Handouts:

Time Critical Task:

AP/1/A15500/21, Loss of Component Cooling Water, marked up for place-keeping through Step 8.

NO 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

(

Appendix C Page 2 of 14 PERFORMANCE INFORMATION Form ES-C-1 Facility:

McGuire Task No.:

MO-7319, MO-3331.3 Task

Title:

Place Standby Component Cooling JPM No.:

2009 Systems - Control Train in Operation Room JPM H KIA

Reference:

008, A4.01, 3.3/3.1 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

Actual Performance:

X Classroom Simulator X

Plant READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The '8' Train Component Cooling pumps are started in accordance with AP/1/A/5500/21, Loss of Component Cooling Water.

Required Materials:

None General

References:

AP/1/A/5500/21, Loss of Component Cooling Water Handouts:

AP/1/A/5500/21, Loss of Component Cooling Water, marked up for place-keeping through Step 8.

Time Critical Task:

NO 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

(

Appendix C Validation Time:

15 minutes Page 3 of 14 PERFORMANCE INFORMATION 2009 Systems - Control Room JPM H Form ES-C-1 NUREG 1021, Revision 9

(

(

Appendix C Validation Time:

15 minutes Page 3 of 14 PERFORMANCE INFORMATION 2009 Systems - Control Room JPM H Form ES-C-1 NUREG 1021, Revision 9

Appendix C Page 4 of 14 PERFORMANCE INFORMATION Form ES-C-1 SIMULATOR OPERATIONAL GUIDELINES

1. Reset to IC-20, 100% BOC
2. Insert MAL-KC010A (1A1 KC Pump trips due to over current)
3. Set 1KC-149 (A KF Hx Outlet Flow Control) to 400 gpm to prevent runout of 1A2 KC Pump
4. Freeze Simulator
1. Reset Simulator to Temporary Snap IC-130 (December, 2008).
2. Momentarily go to run and acknowledge alarms.

2009 Systems - Control Room JPM H NUREG 1021, Revision 9

(

\\

(

(

Appendix C Page 4 of 14 PERFORMANCE INFORMATION Form ES-C-1 SIMULATOR OPERATIONAL GUIDELINES

1. Reset to IC-20, 100% BOC
2. Insert MAL-KC01 OA (1A 1 KC Pump trips due to over current)
3. Set 1 KC-149 (A KF Hx Outlet Flow Control) to 400 gpm to prevent runout of 1 A2 KC Pump
4. Freeze Simulator
1. Reset Simulator to Temporary Snap IC-130 (December, 2008).
2. Momentarily go to run and acknowledge alarms.

2009 Systems - Control Room JPM H NUREG 1021, Revision 9

Appendix C Page 5 of 14 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout AP/1/A15500/21, Loss of Component Cooling Water, marked up for place-keeping through step 8.

START TIME:

STEPS ELEMENTS STANDARD StU COMMENTS REQUIRED FOR UNSAT 1

(Step 9) Start standby KC The operator observes B train as follows:

Train KC components as available.

(Step 9.a) Check standby KC train - AVAILABLE TO If the operator asks the START.

CRSRO whether or not Train B of KC is available, provide the following cue:

Cue:

"S*' tra'in ofKC is

. a,.,aU8'IJle to start.

2 (Step 9.b) Check standby The operator observes KC Surge Tank Level-1 KCP-5640 and determines GREATER THAN 2 FT.

B Train KC Surge Tank level to be ::::6.6 ft.

3 (Step 9.c) Start the standby KC train PER one of the The operator proceeds to following:.

To start A train, GO TO To start B train, GOTO 4

(Enclosure 5, Step 1) Check The operator observes the 1 KC-81 B (KC to B NO HX) 1 KC-81 B Green status light CLOSED.

LIT, Red status light OFF.

2009 Systems - Control Room JPM H NUREG 1021, Revision 9

(

\\

(

Appendix C Page 5 of 14 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout AP/1/A/5500/21, Loss of Component Cooling Water, marked up for place-keeping through step 8.

START TIME:

STEPS ELEMENTS STANDARD S/U COMMENTS REQUIRED FOR UNSAT 1

(Step 9) Start standby KC The operator observes B train as follows:

Train KC components as available.

(Step 9.a) Check standby KC train - AVAILABLE TO If the operator asks the START.

CRSRO whether or not Train B of KC is available, provide the following cue:

Cue:

"8" train of KC is available to start.

2 (Step 9.b) Check standby The operator observes KC Surge Tank Level -

1 KCP-5640 and determines GREATER THAN 2 FT.

B Train KC Surge Tank level to be==6.6 ft.

3 (Step 9.c) Start the standby KC train PER one of the The operator proceeds to following:.

To start A train, GO TO To start B train, GO TO 4

(Enclosure 5, Step 1) Check The operator observes the 1 KC-81 B (KC to B NO HX) 1 KC-81 B Green status light CLOSED.

LIT, Red status light OFF.

2009 Systems - Control Room JPM H NUREG 1021, Revision 9

Appendix C STEPS 5

6 7

8 9

10

  • 11 Page 6 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2) Check 1 KC-56A The operator observes the (KC to A ND HX) CLOSED.

1 KC-56A Green status light LIT, Red status light OFF.

(Step 3) Check 1A Train KC The operator observes the pumps - OFF.

Red status light LIT, and the Green status light OFF for the 1A2 KC Pump and proceeds to the Step 3 RNO.

(Step 3 RNO) GO TO Step The operator proceeds to

5.

Step 5.

(Step 5) Check 1 B Train KC The operator observes the pumps -OFF.

Green status light LIT, and the Red status light OFF for the 1 B1 and 1 B2 KC Pump.

(Notes prior to Step 6)

The operator reads the Voiding of 1 B train KC may Notes and proceeds to Step be suspected if any of the

6.

following have occurred:

1 B train KC pumps were CUE:

tripped due to cavitation or air entrainment.

There W8sno indication 1A train KC pumps were of air e'ntrsl'n'ment or tripped due to cavitation or eavftationp't:iG:tto the 1A1 air entrainment while B train KC Pump trip.

was still cross-tied to A train.

(Step 6) IF voiding of 1 B The operator determines train KC is suspected, that loss of KC is not due to THEN........

voiding or air entrainment.

(Step 7) Close the following:

The operator presses the (Step 7.a) 1 KC-53B (Trn B 1 KC-53B CLOSE pushbutton and observes Aux Bldg Non Ess Sup Isol) the Green status light LIT, Red status light OFF.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

(

(

(

Appendix C STEPS 5

6 7

8 9

10

  • 11 Page 6 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2) Check 1 KC-56A The operator observes the (KC to A ND HX) CLOSED.

1 KC-56A Green status light LIT, Red status light OFF.

(Step 3) Check 1A Train KC The operator observes the pumps - OFF.

Red status light LIT, and the Green status light OFF for the 1A2 KC Pump and proceeds to the Step 3 RNO.

(Step 3 RNO) GO TO Step The operator proceeds to

5.

Step 5.

(Step 5) Check 18 Train KC The operator observes the pumps - OFF.

Green status light LIT, and the Red status light OFF for the 181 and 182 KC Pump.

(Notes prior to Step 6)

The operator reads the Voiding of 18 train KC may Notes and proceeds to Step be suspected if any of the following have occurred:

6.

18 train KC pumps were CUE:

tripped due to cavitation or air entrainment.

There was no indication 1A train KC pumps were of air entrainment or tripped due to cavitation or cavitation prior to the 1A1 air entrainment while 8 train KC Pump trip.

was still cross-tied to A train.

(Step 6) IF voiding of 18 The operator determines train KC is suspected, that loss of KC is not due to THEN........

voiding or air entrainment.

(Step 7) Close the following:

The operator presses the (Step 7.a) 1 KC-538 (Trn 8 1 KC-538 CLOSE pushbutton and observes Aux 81dg Non Ess Sup Isol) the Green status light LIT, Red status light OFF.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

Appendix t STEPS

  • 12 13 14
  • 15 16
  • 17 18 Page 7 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 7) Close the following:

The operator presses the (Step 7.b) 1 KC-2B (Trn B 1 KC-2B CLOSE pushbutton and observes the Green Aux Bldg Non Ess Ret Isol) status light LIT, Red status light OFF.

(Step 7) Close the following:

The operator observes the (Step 7.c) 1 KC-228B (Trn B 1 KC-228B Green status light LIT, Red status light Rx Bldg Non Ess Sup Isol)

OFF.

(Step 7) Close the following:

The operator observes the (Step 7.d) 1 KC-18B (Trn B 1 KC-18B Green status light Rx Bldg Non Ess Ret Isol)

LIT, Red status light OFF.

(Step 8) Start 1 B RN pump.

The operator presses the 1 B RN Pump START pushbutton and observes the Red status light LIT, Green status light OFF.

The operator observes pump motor amps, discharge pressure and flow increase.

(Step 9) Ensure 1 RN-187B The operator observes the (B KC HX Inlet Isol) opens.

1 RN-187B Red status light LIT, Green status light OFF.

(Step 10) Place control The operator places the switch for 1 KC-54B (Train B 1 KC-54B control switch in Recirc Isol.) in "AUTO" the vertical (Auto) position.

position.

(Step 11) Ensure 1 KC-54B The operator observes the (Train B Recirc Isol) opens.

1 KC-54B Red status light LIT, Green status light OFF.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

(

(

(

Appendix C STEPS

  • 12 13 14
  • 15 16
  • 17 18 Page 7 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 7) Close the following:

The operator presses the (Step 7.b) 1 KC-2B (Trn B 1 KC-2B CLOSE pushbutton and observes the Green Aux Bldg Non Ess Ret Isol) status light LIT, Red status light OFF.

(Step 7) Close the following:

The operator observes the (Step 7.c) 1 KC-228B (Trn B 1 KC-228B Green status light LIT, Red status light Rx Bldg Non Ess Sup Isol)

OFF.

(Step 7) Close the following:

The operator observes the (Step 7.d) 1 KC-18B (Trn B 1 KC-18B Green status light Rx Bldg Non Ess Ret Isol)

LIT, Red status light OFF.

(Step 8) Start 1 B RN pump.

The operator presses the 1 B RN Pump START pushbutton and observes the Red status light LIT, Green status light OFF.

The operator observes pump motor amps, discharge pressure and flow increase.

(Step 9) Ensure 1 RN-187B The operator observes the (B KC HX Inlet Isol) opens.

1 RN-187B Red status light LIT, Green status light OFF.

(Step 10) Place control The operator places the switch for 1 KC-54B (Train B 1 KC-54B control switch in Recirc Isol.) in "AUTO" the vertical (Auto) position.

position.

(Step 11) Ensure 1 KC-54B The operator observes the (Train B Recirc Isol) opens.

1 KC-54B Red status light LIT, Green status light OFF.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

Appendix C STEPS

  • 19 20
  • 21 22 23 24 Page 8 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 12) Start 181 KC The operator presses the Pump 181 KC Pump START pushbutton and observes the Red status light LIT, Green status light OFF.

The operator observes pump motor amps, discharge pressure and flow increase.

(Step 13) Check 1KC-12 Operator determines that (181 KC Pump Discharge) -

1 KC-12 was not throttled LOCALLY THROTTLED IN initially and proceeds to the STEP 6.

RNO.

(Step 13 RNO a-b) Perform The operator presses the the following:

182 KC Pump START pushbutton and observes Start 182 KC Pump the Red status light LIT, Green status light OFF.

The operator observes pump motor amps, discharge pressure and flow increase.

GO TO Step 17.

The operator proceeds to Step 17.

(Step 17) Check ND pumps The operator determines

- ANY ON PRIOR TO from the Initial Conditions ENTERING THIS that the ND pumps are not PROCEDURE.

on and proceeds to the RNO.

(Step 17 RNO) GO TO step The operator proceeds to

20.

Step 20.

(Step 20) Check KC leak -

Operator determines that HAS OCCURRED.

KC leak has not occurred and proceeds to the RNO.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

(

(

Appendix C STEPS

  • 19 20
  • 21 22 23 24 Page 8 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 12) Start 1 B1 KC The operator presses the Pump 1 B1 KC Pump START pushbutton and observes the Red status light LIT, Green status light OFF.

The operator observes pump motor amps, discharge pressure and flow increase.

(Step 13) Check 1 KC-12 Operator determines that (1 B1 KC Pump Discharge) -

1 KC-12 was not throttled LOCALL Y THROTTLED IN initially and proceeds to the STEP 6.

RNO.

(Step 13 RNO a-b) Perform The operator presses the the following:

1B2 KC Pump START pushbutton and observes Start 1 B2 KC Pump the Red status light LIT, Green status light OFF.

The operator observes pump motor amps, discharge pressure and flow increase.

GO TO Step 17.

The operator proceeds to Step 17.

(Step 17) Check NO pumps The operator determines

- ANY ON PRIOR TO from the Initial Conditions ENTERING THIS that the NO pumps are not PROCEDURE.

on and proceeds to the RNO.

(Step 17 RNO) GO TO step The operator proceeds to

20.

Step 20.

(Step 20) Check KC leak -

Operator determines that HAS OCCURRED.

KC leak has not occurred and proceeds to the RNO.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

Appendix C STEPS 25

  • 26 Page 9 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 20 RNO) Perform the The operator reads the Step following:

and proceeds to Step 20 (Step 20 RNO a) Limit KC RNOb.

pump flow to 4000 gpm per operating KC pump in next step.

(Step 20 RNa) Perform the following:

(Step 20 RNa b) Open the following valves:

The operator presses the 1 KC-18B (Trn B Rx Bldg 1 KC-18B OPEN pushbutton Non Ess Ret Isol) and observes the Red status light LIT, Green status light OFF.

The operator observes MCB Annunciator 1 AD-10tA-1 alarm.

1 KC-228B (Trn B Rx Bldg The operator presses the Non Ess Sup Isol) 1 KC-228B OPEN pushbutton and observes the Red status light LIT, Green status light OFF.

The operator observes MCB Annunciator 1AD-10tA-2 alarm.

The operator observes Train B flow increase to

==1600 gpm.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

(

(

(

Appendix C STEPS 25

  • 26 Page 9 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 20 RNO) Perform the The operator reads the Step following:

and proceeds to Step 20 (Step 20 RNO a) Limit KC RNO b.

pump flow to 4000 gpm per operating KC pump in next step.

(Step 20 RNO) Perform the following:

(Step 20 RNO b) Open the following valves:

The operator presses the 1 KC-18B (Trn B Rx Bldg 1 KC-18B OPEN pushbutton Non Ess Ret Isol) and observes the Red status light LIT, Green status light OFF.

The operator observes MCB Annunciator 1AD-10/A-1 alarm.

1 KC-228B (Trn B Rx Bldg The operator presses the Non Ess Sup Isol) 1 KC-228B OPEN pushbutton and observes the Red status light LIT, Green status light OFF.

The operator observes MCB Annunciator 1AD-10/A-2 alarm.

The operator observes Train B flow increase to

==1600 gpm.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

Appendix C STEPS

  • 27
  • 28 Page 10 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 20 RNO) Perform the following:

(Step 20 RNO c) Close the following valves:

The operator presses the 1 KC-230A (Trn A Rx Bldg 1 KC-230A CLOSE Non Ess Sup Isol) pushbutton and observes the Green status light LIT, Red status light OFF.

The operator observes MCB Annunciators 1AD-16/A-1 through A-4 alarm.

The operator presses the 1 KC-3A (Trn A Rx Bldg Non 1 KC-3A CLOSE pushbutton Ess Ret Isol) and observes the Green status light LIT, Red status light OFF.

The operator observes MCB Annunciators 1AD-16/D-1 through D-4 alarm intermittently.

(Step 20 RNO) Perform the following:

(Step 20 RNO d) Open the The operator presses the following valves 1 KC-2B OPEN pushbutton 1 KC-2B (Trn B Aux Bldg and observes the Red Non Ess Ret Isol.

status light LIT, Green status light OFF.

The operator presses the 1 KC-53B (Trn B Aux Bldg 1 KC-53B OPEN pushbutton Non Ess Sup Isol).

and observes the Red status light LIT, Green status light OFF.

The operator observes Train B flow increase to

==3500 gpm.

(Step 20 RNO e) GO TO The operator proceeds to Step 25.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

(

Appendix C STEPS

  • 27
  • 28 Page 10 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 20 RNO) Perform the following:

(Step 20 RNO c) Close the following valves:

The operator presses the 1 KC-230A (Trn A Rx Bldg 1 KC-230A CLOSE Non Ess Sup Isol) pushbutton and observes the Green status light LIT, Red status light OFF.

The operator observes MCB Annunciators 1AD-16/A-1 through A-4 alarm.

The operator presses the 1 KC-3A (Trn A Rx Bldg Non 1 KC-3A CLOSE pushbutton Ess Ret Isol) and observes the Green status light LIT, Red status light OFF.

The operator observes MCB Annunciators 1AD-16/0-1 through 0-4 alarm intermittently.

(Step 20 RNO) Perform the following:

(Step 20 RNO d) Open the The operator presses the following valves 1 KC-2B OPEN pushbutton 1 KC-2B (Trn B Aux Bldg and observes the Red Non Ess Ret Isol.

status light LIT, Green status light OFF.

The operator presses the 1 KC-53B (Trn B Aux Bldg 1 KC-53B OPEN pushbutton Non Ess Sup Isol).

and observes the Red status light LIT, Green status light OFF.

The operator observes Train B flow increase to

3500 gpm.

(Step 20 RNO e) GO TO The operator proceeds to Step 25.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

Appendix C STEPS 29 30

  • 31 32
  • 33 34 35 Page 11 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD Step 25.

(Step 25) Check 1A ND The operator observes the pump - OFF 1A ND Pump Green status light LIT, Red status light OFF.

(Step 26) Check 1 KC-56A The operator observes the (KC to ND HX) - CLOSED 1 KC-56A Green status light LIT, Red status light OFF.

(Step 27) Place control The operator rotates the switch for 1 KC-51A (Train A 1 KC-51A control switch Recirc Isol) in the "CLOSE" counter-clockwise to position.

CLOSE.

(Step 28) Ensure 1 KC-51A The operator observes the (Train A Recirc Isol) closes.

1 KC-51A Green status light LIT, Red status light OFF.

(Step 29) Stop 1 A 1 and 1 A2 The operator observes the pumps.

1 A 1 KC Green status light LIT, Red status light OFF.

The operator presses the 1A2 KC Pump STOP pushbutton and observes the Green status light LIT, Red status light OFF.

(Step 30) Check KC flow -

The operator observes LESS THAN 4000 GPM Train B flow to be 4900 gpm PER OPERATING KC and determines flow to be <

PUMP.

4000 gpm per KC Pump.

(Step 31) Check ND pumps The operator determines

- ANY ON PRIOR TO ND Train A is not in ENTERING THIS operation and goes to the PROCEDURE.

RNO.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

{

\\

(

(

Appendix C STEPS 29 30

  • 31 32
  • 33 34 35 Page 11 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD Step 25.

(Step 25) Check 1A NO The operator observes the pump - OFF 1A NO Pump Green status light LIT, Red status light OFF.

(Step 26) Check 1 KC-56A The operator observes the (KC to NO HX) - CLOSED 1 KC-56A Green status light LIT, Red status light OFF.

(Step 27) Place control The operator rotates the switch for 1 KC-51A (Train A 1 KC-51A control switch Recirc Isol) in the "CLOSE" counter-clockwise to position.

CLOSE.

(Step 28) Ensure 1 KC-51A The operator observes the (Train A Recirc Isol) closes.

1 KC-51A Green status light LIT, Red status light OFF.

(Step 29) Stop 1A 1 and 1A2 The operator observes the pumps.

1A1 KC Green status light LIT, Red status light OFF.

The operator presses the 1A2 KC Pump STOP pushbutton and observes the Green status light LIT, Red status light OFF.

(Step 30) Check KC flow -

The operator observes LESS THAN 4000 GPM Train B flow to be 4900 gpm PER OPERATING KC and determines flow to be <

PUMP.

4000 gpm per KC Pump.

(Step 31) Check NO pumps The operator determines

- ANY ON PRIOR TO NO Train A is not in ENTERING THIS operation and goes to the PROCEDURE.

RNO.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

Appendix C STEPS 36 37 38 Page 12 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 31 RNO) GO TO Step The operator proceeds to

37.

Step 37.

(Step 37) Check KC System The operator determines leak - HAS OCCURRED.

KC leak has not occurred and proceeds to the RNO.

(Step 37 RNO) GO TO Step The operator informs the 41 in body of this CRSRO that Enclosure 5 procedure.

has been completed.

CUE:

Anotl1er operator will e9ntiiifiIYCII:8With, :this

';;~f1iil'i(lbt~h ' '

~,~~~IM!,~)'(;, "

'/ '"

,t,

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

2009 Systems - Control Room JPM H Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT NUREG 1021, Revision 9

(

(

(

Appendix C STEPS 36 37 38 Page 12 of 14 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 31 RNO) GO TO Step The operator proceeds to

37.

Step 37.

(Step 37) Check KC System The operator determines leak - HAS OCCURRED.

KC leak has not occurred and proceeds to the RNO.

(Step 37 RNO) GO TO Step The operator informs the 41 in body of this CRSRO that Enclosure 5 procedure.

has been completed.

CUE:

Another operator will continue with this procedure.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

2009 Systems - Control Room JPM H Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT NUREG 1021, Revision 9

Appendix C Page 13 of 14 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM H Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

(

(

(

Appendix C Page 13 of 14 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems - Control Room JPM H Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

Form ES-C-1 2009 Systems - Control Room JPM H NUREG 1021, Revision 9

Appendix C INITIAL CONDITIONS:

INITIATING CUE:

Form ES-C-1 JPM CUE SHEET Unit 1 is operating at 100% power with "A" train RN and KC in service.

1 A 1 KC pump has tripped on overcurrent and will not restart.

The crew has completed AP/11A15500/21 (Loss of KC or KC System Leakage) through subsequent step 8.

The CRSRO has directed you to start the standby KC train starting with Step 9 of AP/1/A/5500/21.

NUREG 1021, Revision 9 Appendix C INITIAL CONDITIONS:

INITIATING CUE:

(

Form ES-C-1 JPM CUE SHEET Unit 1 is operating at 100% power with "A" train RN and KC in service.

1A 1 KC pump has tripped on overcurrent and will not restart.

The crew has completed AP/1/N5500/21 (Loss of KC or KC System Leakage) through subsequent step 8.

The CRSRO has directed you to start the standby KC train starting with Step 9 of AP/1/A/5500/21.

NUREG 1021, Revision 9

Appendix C Page 1 of 7 PERFORMANCE INFORMATION Form ES-C-1 In-Plant JPM I To be run in conjunction with JPM_

2009 Systems -In-Plant JPM I NUREG 1021, Revision 9

(

Appendix C Page 1 of 7 PERFORMANCE INFORMATION Form ES-C-1 In-Plant JPM I To be run in conjunction with JPM _

2009 Systems - In-Plant JPM I NUREG 1021, Revision 9

Appendix C Facility:

McGuire Page 2 of 7 PERFORMANCE INFORMATION Task No.:

MO-S022 Form ES-C-1 Task

Title:

Reset Unit 2 Turbine Driven CA Pump Stop Valve per Generic 4 JPM No.:

2009 Systems - In-Plant JPM I KIA

Reference:

APE OS4, EA2.0S, 3.S/3.7 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

x Actual Performance:

Classroom Simulator Plant x

READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The 2SA-3 (Unit 2 TO CA Pump Turb Stop Valve) is reset and open.

Required Materials:

PPE (Hardhat, Safety Glasses, Hearing Protection, etc.)

General

References:

EP/2/A/SOOO/G-1, Generic Enclosures, Enclosure 24, Resetting TO CA Stop Valve.

Handouts:

EP/2/A/SOOO/G-1, Generic Enclosures, Enclosure 24, Resetting TO CA Stop Valve.

2009 Systems - In-Plant JPM I NUREG 1021, Revision 9

(

(

Appendix C Facility:

McGuire Page 2 of 7 PERFORMANCE INFORMATION Task No.:

MO-5022 Form ES-C-1 Task

Title:

Reset Unit 2 Turbine Driven CA Pump Stop Valve per Generic 4 JPM No.:

2009 Systems - In-Plant JPM I KIA

Reference:

APE 054, EA2.05, 3.5/3.7 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

x Actual Performance:

Classroom Simulator Plant x

READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The 2SA-3 (Unit 2 TO CA Pump Turb Stop Valve) is reset and open.

Required Materials:

PPE (Hardhat, Safety Glasses, Hearing Protection, etc.)

General

References:

EP/2/A/5000/G-1, Generic Enclosures, Enclosure 24, Resetting TO CA Stop Valve.

Handouts:

EP/2/A/5000/G-1, Generic Enclosures, Enclosure 24, Resetting TO CA Stop Valve.

2009 Systems - In-Plant JPM I NUREG 1021, Revision 9

Appendix C Time Critical Task:

NO Validation Time:

10 minutes 2009 Systems -In-Plant JPM I Page 3 of 7 PERFORMANCE INFORMATION Form ES-C-1 NUREG 1021, Revision 9 Appendix C Time Critical Task:

NO Validation Time:

10 minutes

(

2009 Systems -In-Plant JPM I Page 3 of 7 PERFORMANCE INFORMATION Form ES-C-1 NUREG 1021, Revision 9

Appendix C Page 4 of 7 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout EP/2/A15000/G-1, Generic Enclosures, Enclosure 24, Resetting TO CA Stop Valve.

START TIME:

STEPS ELEMENTS STANDARD S/U COMMENTS REQUIRED FOR UNSAT

  • 1 (Step 1) Turn handwheel The operator turns clockwise to allow handwheel clockwise.

mechanical linkage to reconnect.

Cue:

H~ndwheel rotated clockwise,stem is in.

  • 2 (Step 2) Reconnect The operator looks at the mechanical linkage by mechanical Linkage.

pulling mechanical linkage toward Valve Trip Cue:

Mechanism and slowly release while ensuring The Linkage i$NOT the following connections:

connected.

The operator pulls the mechanical linkage toward the Valve Trip Mechanism and slowly releases.

Cue:

The mechanical linkage p.lIHedt9wardValve.Trip Mechanism and is slowly released.

The operator observes the (Step 2.a) At Valve Trip Valve Trip Mechanism figure.

Mechanism: (See Figure below)

Cue:

Trip Hook is fully engaged Trip H()ok is fully engaged with Latch-up Lever.

I with Latch-up Lever..

2009 Systems -In-Plant JPM I NUREG 1021, Revision 9

(

(

Appendix C Page 4 of 7 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout EP/2/A15000/G-1, Generic Enclosures, Enclosure 24, Resetting TO CA Stop Valve.

START TIME:

STEPS ELEMENTS STANDARD StU COMMENTS REQUIRED FOR UNSAT

  • 1 (Step 1) Turn handwheel The operator turns clockwise to allow handwheel clockwise.

mechanical linkage to reconnect.

Cue:

Handwheel rotated clockwise, stem is in.

  • 2 (Step 2) Reconnect The operator looks at the mechanical linkage by mechanical Linkage.

pulling mechanical linkage toward Valve Trip Cue:

Mechanism and slowly release while ensuring The Linkage is NOT the following connections:

connected.

The operator pulls the mechanical linkage toward the Valve Trip Mechanism and slowly releases.

Cue:

The mechanical linkage pulled toward Valve Trip Mechanism and is slowly released.

The operator observes the (Step 2.a) At Valve Trip Valve Trip Mechanism figure.

Mechanism: (See Figure below)

Cue:

Trip Hook is fully engaged Trip Hook is fully engaged with Latch-up Lever.

with Latch-up Lever.

2009 Systems -In-Plant JPM I NUREG 1021, Revision 9

(

Appendix C STEPS

  • 3
  • 4
  • 5 Page 5 of 7 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.b) At Overspeed The operator observes the Trip Mechanism: (See Overspeed Trip Mechanism Figure below) figure.

Tappet nut lays flat against Cue:

Overspeed Trip Mechanism housing.

Tappetnut is laying flat Head Lever is vertical.

aQ,ainstOverspeed Trip Mechanism housing, AND the Head lever is vertical.

(Step 3) Slowly turn The operator rotates the handwheel handwheel in the counter-counterclockwise to open clockwise direction.

stop valve while it is reset.

Cue:

The handwh.eelrotates,.and then stops.

{Step 4) WHEN handwheel The operator rotates the reaches full open, position handwheel in the clockwise valve 114 turn direction % turn.

from open backseat to prevent thermal binding.

Cue:

Thehandwheel* rotates until stopped.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM I NUREG 1021, Revision 9

(

Appendix C STEPS

  • 3
  • 4
  • 5 Page 5 of 7 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.b) At Overspeed The operator observes the Trip Mechanism: (See Overspeed Trip Mechanism Figure below) figure.

Tappet nut lays flat against Cue:

Overspeed Trip Mechanism housing.

Tappet nut is laying flat against Overs peed Trip Head Lever is vertical.

Mechanism housing, AND the Head lever is vertical.

(Step 3) Slowly turn The operator rotates the handwheel handwheel in the counter-counterclockwise to open clockwise direction.

stop valve while it is reset.

Cue:

The handwheel rotates, and then stops.

(Step 4) WHEN handwheel The operator rotates the reaches full open, position handwheel in the clockwise valve 1/4 turn direction % turn.

from open backseat to prevent thermal binding.

Cue:

The handwheel rotates until stopped.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

Form ES-C-1 SIU COMMENTS REQUIRED FOR UNSAT 2009 Systems - In-Plant JPM I NUREG 1021, Revision 9

Appendix C Page 6 of 7 VERIFICATION OF COMPLETION Form ES-C-1 Job Performance Measure No.:

2009 Systems -In-Plant JPM I Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

2009 Systems -In-Plant JPM I NUREG 1021, Revision 9

(

(

Appendix C Page 6 of 7 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems -In-Plant JPM I Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Form ES-C-1 Examiner's Signature:

Date:

2009 Systems -In-Plant JPM I NUREG 1021, Revision 9

Appendix C INITIAL CONDITIONS:

INITIATING CUE:

Form ES-C-1 JPM CUE SHEET The Unit 2 reactor has tripped due to a loss of all offsite power.

2ETA and 2ETB are deenergized.

The crew has entered EP/2/A/SOOO/ECA-0.0, "LOSS OF ALL AC POWER."

While performing Step 7, the RO notices the "TD CA PUMP STOP VLV NOT OPEN" alarm (2AD-S, F-3) is lit.

The CRSRO dispatches you to reset the U-2 TD CA stop valve PER EP/2/A/SOOO/G-1, "Generic Enclosures," Enclosure 24, "Resetting TD CA Stop Valve."

NOTE: No plant equipment should be operated during the performance of this JPM. All actions must be SIMULATED.

NUREG 1021, Revision 9 Appendix C INITIAL CONDITIONS:

INITIATING CUE:

(

(

Form ES-C-1 JPM CUE SHEET The Unit 2 reactor has tripped due to a loss of all offsite power.

2ETA and 2ETB are deenergized.

The crew has entered EP/2/A/SOOO/ECA-0.0, "LOSS OF ALL AC POWER."

While performing Step 7, the RO notices the "TO CA PUMP STOP VLV NOT OPEN" alarm (2AD-S, F-3) is lit.

The CRSRO dispatches you to reset the U-2 TO CA stop valve PER EP/2/A/SOOO/G-1, "Generic Enclosures," Enclosure 24, "Resetting TO CA Stop Valve."

NOTE: No plant equipment should be operated during the performance of this JPM. All actions must be SIMULATED.

NUREG 1021, Revision 9

Appendix C Page 1 of 12 PERFORMANCE INFORMATION DR FT Form ES-C-1 In-Plant JPM J DR fT To be run in conjunction with JPM _

2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

(

Appendix C Page1of12 PERFORMANCE INFORMATION R fT Form ES-C-1 In-Plant JPM J To be run in conjunction with JPM _

2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

Appendix C Facility:

McGuire Page 2 of 12 PERFORMANCE INFORMATION Task No.:

Form ES-C-1 Task

Title:

Aligning Nitrogen To Supply Control JPM No.:

2009 Systems -In-Air to D. E and F VI Compressors Plant JPM J KIA

Reference:

APE 065, AK3.08, 3.7/3.9 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

x Actual Performance:

Classroom Simulator Plant X

READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The operator aligns Nitrogen from backup cylinders to D, E, and F VI compressors with pressure set between 90-100 psig.

Required Materials:

PPE (Hardhat, Safety Glasses, Hearing Protection, etc.)

General

References:

AP/1/A/5500/22, Loss of VI 2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

(

Appendix C Facility:

McGuire Page 2 of 12 PERFORMANCE INFORMATION Task No.:

Form ES-C-1 Task

Title:

Aligning Nitrogen To Supply Control JPM No.:

2009 Systems -In-Air to D, E and F VI Compressors Plant JPM J KIA

Reference:

APE 065, AK3.08, 3.7/3.9 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

x Actual Performance:

Classroom Simulator Plant X

READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The operator aligns Nitrogen from backup cylinders to D, E, and F VI compressors with pressure set between 90-100 psig.

Required Materials:

PPE (Hardhat, Safety Glasses, Hearing Protection, etc.)

General

References:

AP/1/A/5500/22, Loss of VI 2009 Systems -In-Plant JPM J NUREG 1021, Revision 9

Appendix C Handouts:

Time Critical Task:

Validation Time:

Notes:

Page 3 of 12 PERFORMANCE INFORMATION Form ES-C-1 AP/1/A/5500/22, Loss of VI, Enclosure 6, D, E and F VI Compressor Operation With Low Control Air.

NO 15 minutes Several valves that need to be operated during this JPM require the use of a ladder. If asked, cue the operator that they may assume ladders are available; however, they should not climb during performance of the JPM.

2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

(

Appendix C Handouts:

Time Critical Task:

Validation Time:

Notes:

Page 3 of 12 PERFORMANCE INFORMATION Form ES-C-1 AP/1/A/5500/22, Loss of VI, Enclosure 6, D, E and F VI Compressor Operation With Low Control Air.

NO 15 minutes Several valves that need to be operated during this JPM require the use of a ladder. If asked, cue the operator that they may assume ladders are available; however, they should not climb during performance of the JPM.

2009 Systems -In-Plant JPM J NUREG 1021, Revision 9

Appendix C Page 4 of 12 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout AP/1/A/5500/22, Loss of VI, Enclosure 6 after operator identifies enclosure satellite copy in Service Bldg. Basement at Station Lube Oil House.

NOTE: If operator requests copy of enclosure 6, inform them to use satellite copy.

START TIME:

STEPS ELEMENTS STANDARD S/U COMMENTS REQUIRED FOR UNSAT 1

(Step 1) Check VI pressure After the cue, the operator as read on OVI PT5090 (VI observes VI Header Dryer Outlet Hdr Press)

Pressure on OVIPT5090 to (Unit 2 TB, 739, column 2N-be 15 psig.

32) - LESS THAN 70 PSIG.

Cue:.........

"Gagelsifldicath1g16 psig......

2 (Step 2) Check KR in The operator checks local service as follows:

KR pump indications.

Any KR pump - RUNNING Cue:

Band CKR pumps are I*.

I****rt.mnlng.

KR pump discharge Cue:

pressure - GREATER THAN 50 PSIG.

Both gauges read 75 psig.

3 (Step 3) Check D, E, and F The operator determines VI compressors - ALL OFF from initial conditions that D, E and F VI compressors are NOT running.

2009 Systems -In-Plant JPM J NUREG 1021, Revision 9

(

Appendix C Page 4 of 12 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout AP/1/A/5500/22, Loss of VI, Enclosure 6 after operator identifies enclosure satellite copy in Service Bldg. Basement at Station Lube Oil House.

NOTE: If operator requests copy of enclosure 6, inform them to use satellite copy.

START TIME:

STEPS ELEMENTS STANDARD S/U COMMENTS REQUIRED FOR UNSAT 1

(Step 1) Check VI pressure After the cue, the operator as read on OVI PT5090 (VI observes VI Header Dryer Outlet Hdr Press)

Pressure on OVIPT5090 to (Unit 2 T8, 739, column 2N-be 15 psig.

32) - LESS THAN 70 PSIG.

Cue:

Gage is indicating 15 psig.

2 (Step 2) Check KR in The operator checks local service as follows:

KR pump indications.

Any KR pump - RUNNING Cue:

Band C KR pumps are running.

KR pump discharge Cue:

pressure - GREATER THAN 50 PSIG.

Both gauges read 75 psig.

3 (Step 3) Check D, E, and F The operator determines VI compressors - ALL OFF from initial conditions that D, E and F VI compressors are NOT running.

2009 Systems -In-Plant JPM J NUREG 1021, Revision 9

Appendix C STEPS 4

5

  • 6 Page 5 of 12 PERFORMANCE INFORMATION ELEMENTS STANDARD (Note prior to Step 4) Steps The operator reads the 4 through 19 align VB to the Note and proceeds to Step control air header for 0, E,
4.

and F VI compressors to ensure proper operation.

(Step 4) Check VB The operator observes that compressor - RUNNING neither VB compressor is running.

Cue:

Both Breathing Air (VB)

Compressors are OFF.

(Step 4 RNO a/b) Perform the following:

The operator presses the Depress "START" on both START pushbutton for the VB compressors A VB Compressor.

Cue:

The A VB Compressor rernains.OFF.

The operator presses the START pushbutton for the B VB Compressor.

Cue:

The B VB Compressor remains OFF.

IF both VB compressors still The operator proceeds to off, THEN GO TO Step 20.

step 20.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM J NUREG 1021, Revision 9

(

(

Appendix C STEPS 4

5

  • 6 Page 5 of 12 PERFORMANCE INFORMATION ELEMENTS STANDARD (Note prior to Step 4) Steps The operator reads the 4 through 19 align VB to the Note and proceeds to Step control air header for 0, E,
4.

and F VI compressors to ensure proper operation.

(Step 4) Check VB The operator observes that compressor - RUNNING neither VB compressor is running.

Cue:

Both Breathing Air (VB)

Compressors are OFF.

(Step 4 RNO a/b) Perform the following:

The operator presses the Depress "START" on both START pushbutton for the VB compressors A VB Compressor.

Cue:

The A VB Compressor remains OFF, The operator presses the START pushbutton for the B VB Compressor.

Cue:

The B VB Compressor remains OFF.

IF both VB compressors still The operator proceeds to off, THEN GO TO Step 20.

step 20.

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

Appendix C STEPS 7

8 9

10

  • 11 Page 6 of 12 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 20) Check D, E, and The operator determines F VI compressors - ALL from initial conditions that OFF.

D, E and F VI compressors are NOT running.

(Step 21) Observe notes The operator proceeds to prior to Step 26 and GO TO Notes prior to Step 26.

Step 26.

(Notes prior to Step 26)

The operator reads the Subsequent steps use Notes and proceeds to Step nitrogen cylinders as control

26.

air for VI compressors.

Two nitrogen cylinders are installed in the service bldg, 739, column U-30.

(Step 26) Dispatch The operator contacts maintenance personnel or maintenance to obtain another operator to bring additional Nitrogen.

two additional 225 cubic feet nitrogen cylinders to Cue:

service bldg, 739, column U-30 in case extra cylinders Maintenance has been are needed.

dispatched.

(Step 27/27.a) Align The operator rotates the "F nitrogen cylinders (located COOLER ISOLATION" in service bldg, 739, column valve handle clockwise 90°.

U-30) to supply control air to D, E, and FVI Cue:

compressors as follows:

T~;e

    • 11~9d.lels **

Close "F VI COMPRESSOR perpEJlidicUlar.t() pipe VORTEX COOLER flow.

ISOLATION" valve (located on top of F VI compressor microcontroller panel).

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

(

(

Appendix C STEPS 7

8 9

10

  • 11 Page 6 of 12 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 20) Check D, E, and The operator determines F VI compressors - ALL from initial conditions that OFF.

D, E and F VI compressors are NOT running.

(Step 21) Observe notes The operator proceeds to prior to Step 26 and GO TO Notes prior to Step 26.

Step 26.

(Notes prior to Step 26)

The operator reads the Subsequent steps use Notes and proceeds to Step nitrogen cylinders as control

26.

air for VI compressors.

Two nitrogen cylinders are installed in the service bldg, 739, column U-30.

(Step 26) Dispatch The operator contacts maintenance personnel or maintenance to obtain another operator to bring additional Nitrogen.

two additional 225 cubic feet nitrogen cylinders to Cue:

service bldg, 739, column U-30 in case extra cylinders Maintenance has been are needed.

dispatched.

(Step 27/27.a) Align The operator rotates the "F nitrogen cylinders (located COOLER ISOLATION" in service bldg, 739, column valve handle clockwise 90°.

U-30) to supply control air to D, E, and F VI Cue:

compressors as follows:

The handle is Close "F VI COMPRESSOR perpendicular to pipe VORTEX COOLER flow.

ISOLATION" valve (located on top of F VI compressor microcontroller panel).

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

Appendix C STEPS

  • 12
  • 13
  • 14
  • 15 Page 7 of 12 PERFORMANCE INFORMATION ELEMENTS (Step 27.b) Close 1VI-837 (Alternate VI Control Air Supply to D/E/F VI STANDARD The operator rotates 1 VI-837 valve handwheel clockwise.

Compressors) (service bldg, I:-=-:-~"..,..,--,-,-----,-.-~----------cl 739+8, between col Q-30 and F VI Compressor).

(Step 27.c) Close "D VI COMPRESSOR VORTEX COOLER ISOLATION" valve (located on top of D VI compressor microcontroller panel).

(Step 27.d) Close "E VI COMPRESSOR VORTEX COOLER ISOLATION" The operator rotates the "D COOLER ISOLATION" valve handle clockwise 90°.

~i;<
'

'Fh~hanCfte <i$'>

\\p:.el1diGul~rtQ* pipe ft'Q¥1:

The operator rotates the "E COOLER ISOLATION" valve handle clockwise 90°.

valve (located on top of E VI I:-=-:--:-~-:--:--:--:-~~

compressor microcontroller panel).

(Step 7.e) Unlock and close 1VI-842 (Normal VI Control Air Supply to VI Compressors D, E, and F)

(service bldg, 739, U-30, west side of column).

The operator removes the lock and rotates 1VI-842 valve handwheel clockwise.

S/U Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

(

(

Appendix C STEPS

  • 12
  • 13
  • 14
  • 15 Page 7 of 12 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 27.b) Close 1VI-837 The operator rotates 1 VI-(Alternate VI Control Air 837 valve handwheel Supply to D/E/F VI clockwise.

Compressors) (service bldg, 739+8, between col Q-30 Cue:

and F VI Compressor).

The hal1dwheel rotates clockwise, and THEN stops.

(Step 27.c) Close "0 VI The operator rotates the "0 COMPRESSOR VORTEX COOLER ISOLATION" COOLER ISOLATION" valve handle clockwise 90°.

valve (located on top of 0 VI compressor Cue:

microcontroller panel).

The handle is perpendicular to pipe flow.

(Step 27.d) Close "E VI The operator rotates the "E COMPRESSOR VORTEX COOLER ISOLATION" COOLER ISOLATION" valve handle clockwise 90°.

valve (located on top of E VI compressor microcontroller Cue:

panel).

The handle is perpendicular to pipe flow.

(Step 7.e) Unlock and close The operator removes the 1 VI-842 (Normal VI Control lock and rotates 1 VI-842 Air Supply to VI valve handwheel clockwise.

Compressors 0, E, and F)

(service bldg, 739, U-30, Cue:

west side of column).

The handwheel rotates clockwise, and THEN stops.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM J NUREG 1021, Revision 9

Appendix C STEPS ELEMENTS Page 8 of 12 PERFORMANCE INFORMATION STANDARD

  • 16 (Step 7.f) Open 1VI-843 (VI The operator rotates 1VI-
  • 17
  • 18 Backup Compressed 843 valve handwheel Nitrogen Cylinders Isol) counter-clockwise.

(service bldg, 739, U-30, west side of column).

(Step 7.g) Ensure pressure regulating knob on 1VI-574 (VI Nitrogen Cylinder Pressure Regulator)

(service bldg, 739, at column U-30) turned fully counterclockwise.

(Step 7.h) Open isolation valve on top of each nitrogen cylinder.

The_ndwl1e~t,rotates'

(;o~nWr,;;cloekfiiSe,and THE~tslops.

The operator rotates the 1VI-574 regulator knob fully counter-clockwise.

The operator rotates the Nitrogen Cylinder valve handwheel fully counter-clockwise.

StU Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

(

(

Appendix C STEPS

  • 16
  • 17
  • 18 Page 8 of 12 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 7.f) Open 1VI-843 (VI The operator rotates 1 VI-Backup Compressed 843 valve handwheel Nitrogen Cylinders Isol) counter-clockwise.

(service bldg, 739, U-30, west side of column).

Cue:

The handwheel rotates counter-clockwise, and THEN stops.

(Step 7.g) Ensure pressure The operator rotates the regulating knob on 1 VI-574 1VI-574 regulator knob fully (VI Nitrogen Cylinder counter-clockwise.

Pressure Regulator)

(service bldg, 739, at Cue:

column U-30) turned fully counterclockwise.

The knob rotates counter-clockwise, and THEN stops.

(Step 7.h) Open isolation The operator rotates the valve on top of each Nitrogen Cylinder valve nitrogen cylinder.

handwheel fully counter-clockwise.

Cue:

The valve handwheel rotates counter-clockwise, and THEN stops.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

Appendix C STEPS

  • 19
  • 20 21 Page 9 of 12 PERFORMANCE INFORMATION ELEMENTS (Step 7.i) Open the following:

1VI-572 (VI Nitrogen Cylinder Isolation) (service bldg, 739, at column U-30).

1VI-573 (VI Nitrogen Cylinder Isolation) (service bldg, 739, at column U-30).

(Step 7.j) Turn regulating knob on 1VI-574 (VI Nitrogen Cylinder Pressure Regulator) (service bldg, 739, at column U-30) clockwise to obtain 90-100 PSIG outlet pressure.

(Caution prior to Step 7.k)

Compressor trip may occur if 1 VI-57 4 outlet pressure goes below 70 PSIG.

STANDARD The operator rotates the "1VI-572" valve handle counter-clockwise 90°.

The operator rotates the "1VI-573" valve handle counter-clockwise 90°.

The operator rotates the 1VI-574 regulator knob clockwise.

The operator observes pressure between 90-100 psig and stops rotating the 1VI-574 regulator knob.

Cue:

outlet pressure is 98 The operator reads the Caution and proceeds to Step 27.k.

StU Form ES-C-1 COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM J NUREG 1021, Revision 9

(

Appendix C STEPS

  • 19
  • 20 21 Page90f12 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 7.i) Open the The operator rotates the following:

"1 VI-572" valve handle counter-clockwise 90°.

1 VI-572 (VI Nitrogen Cylinder Isolation) (service Cue:

bldg, 739, at column U-30).

The handle is in-line with pipe flow.

1VI-573 (VI Nitrogen The operator rotates the Cylinder Isolation) (service "1VI-573" valve handle bldg, 739, at column U-30).

counter-clockwise 90°.

Cue:

The handle is in-line with pipe flow.

(Step 7.j) Turn regulating The operator rotates the knob on 1 VI-57 4 (VI 1VI-574 regulator knob Nitrogen Cylinder Pressure clockwise.

Regulator) (service bldg, 739, at column U-30)

Cue:

clockwise to obtain 90-100 PSIG outlet pressure.

The knob rotates clockwise.

The operator observes pressure between 90-100 psig and stops rotating the 1 VI-57 4 regulator knob.

Cue:

The outlet pressure is 98 psig.

(Caution prior to Step 7.k)

The operator reads the Compressor trip may occur Caution and proceeds to if 1 VI-57 4 outlet pressure Step 27.k.

goes below 70 PSIG.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM J NUREG 1021, Revision 9

(

Appendix C STEPS 22 23 Page 10 of 12 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 27.k) Periodically The operator ensures 1VI-ensure 1VI-574 is 574 is maintaining 90-100 maintaining 90-100 PSIG PSIG outlet pressure.

outlet pressure.

Cue:

The outlet pressure is 98 pSig.

(Step 28)Check D VI CUE:

compressor - AVAILABLE TO START.

Another Operator will complete this enclosure.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

(

(

(

Appendix C STEPS 22 23 Page 10 of 12 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 27.k) Periodically The operator ensures 1VI-ensure 1 VI-57 4 is 574 is maintaining 90-100 maintaining 90-100 PSIG PSIG outlet pressure.

outlet pressure.

Cue:

The outlet pressure is 98 psig.

(Step 28)Check D VI CUE:

compressor - AVAILABLE TO START.

Another Operator will complete this enclosure.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems - In-Plant JPM J NUREG 1021, Revision 9

Appendix C Page 11 of 12 VERIFICATION OF COMPLETION Job Performance Measure No.:

2009 Systems -In-Plant JPM J Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Form ES-C-1 Examiner's Signature:

Date:

2009 Systems -In-Plant JPM J NUREG 1021, Revision 9

(

(

Appendix C Page 11 of 12 VERIFICATION OF COMPLETION Form ES-C-1 Job Performance Measure No.:

2009 Systems -In-Plant JPM J Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

2009 Systems -In-Plant JPM J NUREG 1021, Revision 9

Appendix C INITIAL CONDITIONS:

INITIATING CUE:

Form ES-C-1 JPM CUE SHEET A flexible coupling rupture on the Instrument Air System Header has caused all Instrument Air Compressors previously in service to trip.

AP/1/A/5500/22 (Loss of VI) has been implemented.

The C/R SRO has dispatched you to locally check the Air Compressors.

You discover that D, E, and F Compressors have all tripped off and report this to the Control Room.

The C/R SRO checks Instrument Air header pressure and discovers that pressure is less that 20 PSIG.

A, B, and C VI Compressors are all out of service for a major modification.

The CRSRO directs you to perform AP/1/A/5500/22, Loss of VI,, D, E, and F VI Compressor Operation With Low Control Air.

NOTE: No plant equipment should be operated during the performance of this JPM. All actions must be SIMULATED.

NUREG 1021, Revision 9 Appendix C INITIAL CONDITIONS:

INITIATING CUE:

(

(

Form ES-C-1 JPM CUE SHEET A flexible coupling rupture on the Instrument Air System Header has caused all Instrument Air Compressors previously in service to trip.

AP/1/A/5500/22 (Loss of VI) has been implemented.

The C/R SRO has dispatched you to locally check the Air Compressors.

You discover that D, E, and F Compressors have all tripped off and report this to the Control Room.

The C/R SRO checks Instrument Air header pressure and discovers that pressure is less that 20 PSIG.

A, 8, and C VI Compressors are all out of service for a major modification.

The CRSRO directs you to perform AP/1/A/5500/22, Loss of VI,, D, E, and F VI Compressor Operation With Low Control Air.

NOTE: No plant equipment should be operated during the performance of this JPM. All actions must be SIMULATED.

NUREG 1021, Revision 9

Appendix C Page 1 of 11 PERFORMANCE INFORMATION R FT Form ES-C-1 In-Plant JPM K R FT To be run in conjunction with JPM _

2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

(

Appendix C Page 1 of 11 PERFORMANCE INFORMATION Form ES-C-1 In-Plant JPM K To be run in conjunction with JPM _

2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

Appendix C Facility:

McGuire Page 2 of 11 PERFORMANCE INFORMATION Task No.:

Form ES-C-1 Task

Title:

Swap Battery Charger EVCA Power JPM No.:

2009 Systems - In-Supply from Unit 1 to Unit 2 Plant JPM K KIA

Reference:

APE 058, AK3.02, 4.0/4.2 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Simulated Performance:

x Actual Performance:

Classroom Simulator Plant x

READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The operator aligns power to Battery Charger EVCA from Unit 2 within 20 minutes of dispatch.

Required Materials:

PPE (Hardhat, Safety Glasses, Hearing Protection, etc.)

General

References:

AP/11A15500107, Loss of Electrical Power Handouts:

AP/11A15500107, Loss of Electrical Power, Enclosure 22, Swapping Battery Charger Power Supplies.

2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

(

(

Appendix C Facility:

Task

Title:

McGuire Page 2 of 11 PERFORMANCE INFORMATION Task No.:

Swap Battery Charger EVCA Power JPM No.:

Supply from Unit 1 to Unit 2 KJA

Reference:

APE 058, AK3.02, 4.0/4.2 Examinee:

NRC Examiner:

Facility Evaluator:

Date:

Method of testing:

Form ES-C-1 2009 Systems -In-Plant JPM K Simulated Performance:

x Actual Performance:

Classroom Simulator Plant X

READ TO THE EXAMINEE I will explain the initial conditions, which steps to simulate or discuss, and provide initiating cues. When you complete the task successfully, the objective for this Job Performance Measure will be satisfied.

Task Standard:

The operator aligns power to Battery Charger EVCA from Unit 2 within 20 minutes of dispatch.

Required Materials:

PPE (Hardhat, Safety Glasses, Hearing Protection, etc.)

General

References:

AP/1/A/5500107, Loss of Electrical Power Handouts:

AP/1/A/5500107, Loss of Electrical Power, Enclosure 22, Swapping Battery Charger Power Supplies.

2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

Appendix C Time Critical Task:

Validation Time:

Notes:

Page 3 of 11 PERFORMANCE INFORMATION YES-20 Minutes 15 minutes Form ES-C-1 Start this JPM from the hallway outside of the Ops kitchen area.

Record the Time Critical Completion Time (in step number 13) when the Charger "DC Output" Breaker is closed in.

2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

(

(

\\

\\

Appendix C Time Critical Task:

Validation Time:

Notes:

Page 3 of 11 PERFORMANCE INFORMATION YES-20 Minutes 15 minutes Form ES-C-1 Start this JPM from the hallway outside of the Ops kitchen area.

Record the Time Critical Completion Time (in step number 13) when the Charger "DC Output" Breaker is closed in.

2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

Appendix C Page 4 of 11 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout AP/1/A15500/7, Loss of Electrical Power, Enclosure 22.

START TIME:

STEPS ELEMENTS STANDARD StU COMMENTS REQUIRED FOR UNSAT 1

(Caution prior to Step 1) This enclosure should be performed without delay to limit time battery is supplying DC bus.

2 (Step 1) Perform applicable section(s) as specified in The operator determines (DC Bus from initial conditions that Alignment):

Battery Charger EVCA is the desired charger and To swap power supplies to proceeds to step 2.

EVCA Battery Charger, perform Step 2.

To swap power supplies to EVCB Battery Charger, perform Step 3.

To swap power supplies to EVCC Battery Charger, perform Step 4.

To swap power supplies to EVCD Battery Charger, perform Step 5.

To swap power supplies to EVCS Battery Charger, perform one of the following:

IF 1 EMXH is aligned to EVCS, THEN swap power supplies to 1 EMXH PER Step 6.

OR IF 2EMXH is aligned to EVCS, THEN swap power supplies to 2EMXH PER Step 7.

2009 Systems - In-Plant JPM K NUREG 1021, Revision 9

(

(

Appendix C Page 4 of 11 PERFORMANCE INFORMATION (Denote Critical Steps with an asterisk*)

Form ES-C-1 Provide Candidate with Initial Conditions/Cue (Last Page of this JPM), and Handout AP/1/Al5500/7, Loss of Electrical Power, Enclosure 22.

START TIME:

STEPS ELEMENTS STANDARD S/U COMMENTS REQUIRED FOR UNSAT 1

(Caution prior to Step 1) This enclosure should be performed without delay to limit time battery is supplying DC bus.

2 (Step 1) Perform applicable section(s) as specified in The operator determines (DC Bus from initial conditions that Alignment):

Battery Charger EVCA is the desired charger and To swap power supplies to proceeds to step 2.

EVCA Battery Charger, perform Step 2.

To swap power supplies to EVCB Battery Charger, perform Step 3.

To swap power supplies to EVCC Battery Charger, perform Step 4.

To swap power supplies to EVCD Battery Charger, perform Step 5.

To swap power supplies to EVCS Battery Charger, perform one of the following:

IF 1 EMXH is aligned to EVCS, THEN swap power supplies to 1 EMXH PER Step 6.

OR IF 2EMXH is aligned to EVCS, THEN swap power supplies to 2EMXH PER Step 7.

2009 Systems - In-Plant JPM K NUREG 1021, Revision 9

Appendix C STEPS 3

4 Page 5 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2/2.a) To swap power The operator determines supplies to EVCA Battery from initial conditions that Charger, perform the following:

it is desired to supply Battery Charger EVCA Determine which unit is from Unit 2, and places a desired to supply EVCA:

check mark in front of Unit

2.

Unit 1 OR Unit 2 (Steps 2. b. 1-2) Have Control The operator determines Room perform the following:

from initial conditions that 1 ETA is NOT energized IF Unit I ETA is energized, and proceeds to step THEN.......

2.b.2.

IF Unit 2 ETA is energized, The operator contacts to THEN:

Control Room and asks if 2ETA is energized.

Cue:

2ETAi~ energizecl, Ensure 2A DIG load The operator contacts the sequencer reset.

Control Room and directs RO to ensure 2A DIG Sequencer is reset and EVCA stop button on 2MC-8 is depressed.

Depress "STOP" for "EVCA Batt Charger" on 2MC-8.

Cue:

~AO/G seque~cer is r~s~t,AND$T()P PushbuUQn has,been depressed.

Form ES-C-1 SIU COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

(

(

(

Appendix C STEPS 3

4 Page 5 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2/2.a) To swap power The operator determines supplies to EVCA Battery from initial conditions that Charger, perform the following:

it is desired to supply Battery Charger EVCA Determine which unit is from Unit 2, and places a desired to supply EVCA:

check mark in front of Unit

2.

Unit 1 OR Unit 2 (Steps 2.b.1-2) Have Control The operator determines Room perform the following:

from initial conditions that 1 ETA is NOT energized IF Unit I ETA is energized, and proceeds to step THEN.......

2.b.2.

IF Unit 2 ETA is energized, The operator contacts to THEN:

Control Room and asks if 2ETA is energized.

Cue:

2ETA is energized.

Ensure 2A DIG load The operator contacts the sequencer reset.

Control Room and directs RO to ensure 2A DIG Sequencer is reset and EVCA stop button on 2MC-S is depressed.

Depress "STOP" for "EVCA Batt Charger" on 2MC-S.

Cue:

2A DIG sequencer is reset, AND STOP Pushbutton has been depressed.

Form ES-C-1 SIU COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

Appendix C STEPS

  • 5 6
  • 7 Page 6 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.c) Open EVCA Battery The operator places the Charger "DC OUTPUT" EVCA Battery Charger breaker breaker in down direction.

Cue:

Switch is mpved in the down direction and br~aker indicates. OfF.

(Caution prior to Step 2.d) It The operator reads the may be necessary to apply Caution and proceeds to pressure on the breaker rotary Step 2.d switch in the counterclockwise direction while operating kirk key devices.

(Step 2.d) Open the following breakers:

ECB1-1B (Normal Inc Supply The operator opens the From MCC 1 EMXA)

Normal breaker.

Cue:

"Normal ~lJPply" breaker handle rotated counter clockwise to the "OFF" position.

ECB1-1C (Alt Inc Supply From The operator observes the MCC 2EMXA)

Alternate breaker.

Cue:

Breakerhandle***is indicating "OFP'.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - In-Plant JPM K NUREG 1021, Revision 9

(

(,

Appendix C STEPS

  • 5 6
  • 7 Page 6 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.c) Open EVCA Battery The operator places the Charger "DC OUTPUT" EVCA Battery Charger breaker breaker in down direction.

Cue:

Switch is moved in the down direction and breaker indicates OFF.

(Caution prior to Step 2.d) It The operator reads the may be necessary to apply Caution and proceeds to pressure on the breaker rotary Step 2.d switch in the counterclockwise direction while operating kirk key devices.

(Step 2.d) Open the following breakers:

ECB 1-1 B (Normal I nc Supply The operator opens the From MCC 1 EMXA)

Normal breaker.

Cue:

"Normal Supply" breaker handle rotated counter clockwise to the "OFF" position.

ECB1-1C (Alt Inc Supply From The operator observes the MCC 2EMXA)

Alternate breaker.

Cue:

Breaker handle is indicating "OFF".

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems - In-Plant JPM K NUREG 1021, Revision 9

Appendix C STEPS

  • 8 9
  • 10 Page 7 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.e) Remove kirk key The operator rotates and from breaker in step above.

removes the kirk key from breaker ECB1-1 B.

Cue:

Kiri( key rotated and removed.

(Step 2.f) IF Unit 1 to supply The operator determines EVCA, THEN perform the from initial conditions that following......

it is NOT desired to supply power to EVCA from Unit 1 and proceeds to step 2.g.

(Step 2.g) IF Unit 2 to supply The operator inserts key EVCA, THEN perform the into the Unit 2 supply following:

breaker and closes it.

Use kirk key and close ECB1-Cue:

1C (Alt Inc Supply From MCC 2EMXA).

Kirk Keyin~ert~d.

"AlternCite*Supply" breaker handlel"otCited clockwise to the "O.N" position.

Have Unit 2 Control Room The operator contacts the operator start Battery Charger Control Room and EVCA on 2MC-8.

requests that they start the Battery Charger EVCA on 2MC-8.

Cue:

Unit2.RO has started EVCA Batt.* Charger from 2MC.,S..

Form ES-C-1 StU COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM K NUREG 1021, ReVISIon 9

(

Appendix C STEPS

  • S 9
  • 10 Page 7 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.e) Remove kirk key The operator rotates and from breaker in step above.

removes the kirk key from breaker ECB1-1 B.

Cue:

Kirk key rotated and removed.

(Step 2.D IF Unit 1 to supply The operator determines EVCA, THEN perform the from initial conditions that following......

it is NOT desired to supply power to EVCA from Unit 1 and proceeds to step 2.g.

(Step 2.g) IF Unit 2 to supply The operator inserts key EVCA, THEN perform the into the Unit 2 supply following:

breaker and closes it.

Use kirk key and close ECB1-Cue:

1 C (Alt Inc Supply From MCC 2EMXA).

Kirk Key inserted.

"Alternate Supply" breaker handle rotated clockwise to the "ON" position.

Have Unit 2 Control Room The operator contacts the operator start Battery Charger Control Room and EVCA on 2MC-S.

requests that they start the Battery Charger EVCA on 2MC-S.

Cue:

Unit 2 RO has started EVCA Batt. Charger from 2MC-S.

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM K NUREG 1021, ReVISion 9

Appendix C STEPS 11 12

  • 13 Page 8 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.h) IF EVCA battery The operator checks charger DC volts are greater EVCA battery charger DC than or equal to 115 volts, output voltage.

THEN GO TO Step 2.j.

Cue:

Charg~rDC outPllt voltag~is 132 v()lt$~

The operator proceeds to Step 2.j.

(Step 2.j) Ensure EVCA The operator places the Battery Charger Battery Charger "FLOAT/EQUALIZE" switch "FLOAT/EQUALIZE" in "FLOAT" position.

switch in "FLOAT" position.

Cue:

Switcil in l'FLO~T" pO$'tion. Tile green "F40AT"light.is iIIuminat~d; (Step 2.k) Close EVCA Battery The operator places the Charger "DC OUTPUT" EVCA Battery Charger breaker "DC OUTPUT" breaker to the UP position.

Cue:

ar~akertlClnE1le. hCls~een pull~dir;ltothelJP pOsition.

$~(~ptinjefo(fI~~;~f~~l~~I',.

1iask:c

........ ". i\\.i.....

"l

,}~.;,.,.*.* :,.'.,>

.'\\.~j

  • (*i:*:".

.1;***.***7 >::

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

(

(,

Appendix C STEPS 11 12

  • 13 Page 8 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.h) IF EVCA battery The operator checks charger DC volts are greater EVCA battery charger DC than or equal to 115 volts, output voltage.

THEN GO TO Step 2.j.

Cue:

Charger DC output voltage is 132 volts.

The operator proceeds to Step 2.j.

(Step 2.j) Ensure EVCA The operator places the Battery Charger Battery Charger "FLOAT/EQUALIZE" switch "FLOAT/EQUALIZE" in "FLOAT" position.

switch in "FLOAT" position.

Cue:

Switch in "FLOAT" position. The green "FLOAT" light is illuminated.

(Step 2.k) Close EVCA Battery The operator places the Charger "DC OUTPUT" EVCA Battery Charger breaker "DC OUTPUT" breaker to the UP position.

Cue:

Breaker handle has been pulled into the up position.

Stop Time for Time Critical Task:

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

Appendix C STEPS 14 15 16 Page 9 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.1) Notify Control The operator contacts Room that EVCA Battery the Control Room and Charger is running.

informs the RO that the EVCA Battery Charger is running.

Cue:

The RO acknowledges.

(Step 2.m) IF another battery The operator recognizes charger needs to be swapped, that no other battery THEN perform the applicable Chargers need to be re-step as directed in Step 1.

energized.

Cue:

.No.otb~r chargers need to be swapped.

(Step 2.n) Exit this enclosure.

The operator exits the procedure.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

(

(,

Appendix C STEPS 14 15 16 Page 9 of 11 PERFORMANCE INFORMATION ELEMENTS STANDARD (Step 2.1) Notify Control The operator contacts Room that EVCA Battery the Control Room and Charger is running.

informs the RO that the EVCA Battery Charger is running.

Cue:

The RO acknowledges.

(Step 2.m) IF another battery The operator recognizes charger needs to be swapped, that no other battery THEN perform the applicable Chargers need to be re-step as directed in Step 1.

energized.

Cue:

No other chargers need to be swapped.

(Step 2.n) Exit this enclosure.

The operator exits the procedure.

Terminating Cue:

Evaluation on this JPM is complete.

STOP TIME:

Form ES-C-1 S/U COMMENTS REQUIRED FOR UNSAT 2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

Appendix C Page 10of11 VERIFICATION OF COMPLETION Form ES-C-1 Job Performance Measure No.:

2009 Systems -In-Plant JPM K Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

2009 Systems -In-Plant JPM K NUREG 1021, Revision 9

(

(

Appendix C Page 10 of 11 VERIFICATION OF COMPLETION Form ES-C-1 Job Performance Measure No.:

2009 Systems -In-Plant JPM K Examinee's Name:

Date Performed:

Facility Evaluator:

Number of Attempts:

Time to Complete:

Question Documentation:

Result:

SAT UNSAT Examiner's Signature:

Date:

2009 Systems - In-Plant JPM K NUREG 1021, Revision 9

Appendix C INITIAL CONDITIONS:

INITIATING CUE:

Form ES-C-1 JPM CUE SHEET Unit 1 has just experienced a LOOP (Loss of Offsite Power).

The 1 A DIG will not start.

1 ETA is de-energized.

AP/1/A/5500107 (Loss of Electrical Power), Case 1 has been entered.

While performing Enclosure 7 (DC Bus Alignment), the RO notices that Vital Battery Charger EVCA is de-energized.

The CRSRO directs you to swap power supplies to the EVCA Battery Charger from Unit 1 to Unit 2 in accordance with AP/1/A/5500107 (Loss of Electrical Power), Enclosure 22 (Swapping Battery Charger Power Supplies).

NOTE: No plant equipment should be operated during the performance of this JPM. All actions must be SIMULATED.

NOTE: THIS IS A TIME CRITICAL TASK NUREG 1021, Revision 9 Appendix C INITIAL CONDITIONS:

INITIATING CUE:

(

(

Form ES-C-1 JPM CUE SHEET Unit 1 has just experienced a LOOP (Loss of Offsite Power).

The 1 A DIG will not start.

1 ETA is de-energized.

AP/1/A/5500107 (Loss of Electrical Power), Case 1 has been entered.

While performing Enclosure 7 (DC Bus Alignment), the RO notices that Vital Battery Charger EVCA is de-energized.

The CRSRO directs you to swap power supplies to the EVCA Battery Charger from Unit 1 to Unit 2 in accordance with AP/1/A/5500107 (Loss of Electrical Power), Enclosure 22 (Swapping Battery Charger Power Supplies).

NOTE: No plant equipment should be operated during the performance of this JPM. All actions must be SIMULATED.

NOTE: THIS IS A TIME CRITICAL TASK NUREG 1021, Revision 9