PDuke EEnergy BRUCE H HAMILTON Vice President McGuire Nuclear Station Duke Energy Corporation MG01VP / 12700 Hagers Ferry Road Huntersville, NC 28078 704-875-5333 704-875-4809 fax bhhamilton@duke-energy. com February, 2, 2009 U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C. 20555-0001
SUBJECT:
Duke Energy Carolinas, LLC McGuire Nuclear Station Docket No. 50-369 Steam Generator In-Service Inspection Report Unit 1, End of Cycle (EOC) 19 Pursuant to ASME Section XI and McGuire Technical Specification 5.6.8, Duke Energy hereby submits the attached Steam Generator In-Service Inspection Summary Report for the McGuire Unit 1 EOC-19 refueling outage.
Questions regarding the attached report should be directed to Mitch Hatley at (704) 875-5456 or Kay Crane at (704) 875-4306.
Bruce Hamilton www. duke-energy. corn
U. S. Nuclear Regulatory Commission February 2, 2009 Page 2 Mr. L. A. Reyes, Regional Administrator U.S. Nuclear Regulatory Commission, Region II Atlanta Federal Center 61 Forsyth St., SWW, Suite 23T85 Atlanta, GA 30303 Mr. Jon H. Thompson NRC Project Manager U. S. Nuclear Regulatory Commission Mail Stop 8G9A.
Washington, DC 20555-0001 Joe Brady NRC Senior Resident Inspector McGuire Nuclear Station
Steam Generator In-service Inspection Summary Report McGuire Nuclear Station Unit I EOC 19 Fall Outage 2008 Location: McGuire Nuclear Station, 12700 Hagers Ferry Road Huntersville, N.C. 28078-9340 NRC Docket No. 50-369 National Board No. 44 Commercial Service Date: December 1, 1981 Owner: Duke Energy Carolinas, LLC 526 South Church St.
Charlotte, N.C. 28202 Revision 0 Prepared By:
Checked By:
Approved By:
iJ~
4 1
u Date: L2*
/oL Date:
QXo c Date:
7 Document Completion Date:
/
~2-~7~e~9 I
Copy No Controlled Assigned To:
Uncontrolled:
Controlled Distribution Copy No.
Assigned To Original McGuire Nuclear Station Document Control Master File MC 1201.35 NRC Document Control Uncontrolled Distribution 2
Hartford Steam Boiler Inspection and Insurance Corporation (AlA) 3 State of North Carolina Department of Labor C/o J. M. Givens, II
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules
- 1. Owner: Duke Energy Corporation, 526 S. Church St.. Charlotte, NC 28201-1006 (Name and Address of Owner)
- 2.
Plant:
McGuire Nuclear Station, 12700 Hagers Ferry Rd, Huntersville, NC 28078-9340 (Name and Address of Plant) 3:
4.
5.
6.
7.
Plant Unit:
1 Owner Certificate of Authorization (if required)
Commercial Service Date: December 1, 1981 National Board Number for Unit 44 Components Inspected:
N/A Component Steam Generator 1A Steam Generator lB Steam Generator IC Steam Generator ID Manufacturer BWI BWI
- Manufacturer Serial No.
7701-04 7693-01 State or Province No.
NC-302668 NC-302669 NC-302670 NC-302671 National Board No.
157 146 BWI BWI 7701-03 7701-02 155 154 Note:
Supplemental sheets in form of lists, sketches, or drawings may beused provided (1) size is 81/2 in. x 11 in., (2) information in items I through 6 on this data report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
FORM NIS-1 (Back)
- 8.
Examination Dates May 2 8th 2007 to November 1 2th 2008
- 9.
Inspection Period Identification:
- 10.
Inspection Interval Identification:
- 11.
Applicable Edition of Section XI
- 12.
Date/Revision of Inspection Plan:
- 13. Abstract of Examinations and Test.
P Steam Generator Tube Inspection Report.
Second Period Third Interval 1998 Addenda 2000 August 19, 2008 Revision 2
- eference attached response to technical specification 5.6.8
- 14. Abstract of Results of Examination and Tests. Reference attached response to technical specification 5.6.8 Steam Generator Tube Inspection Report.
- 15. Abstract of Corrective Measures. Reference attached response to technical specification 5.6.8 Steam Generator Tube Inspection Report.
We certify that a) the statements made in this report are correct b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.
Certificate of Authorization No. (if applicable)
Date
/-
_?
20 Z I Signed NA Expiration Date NA Duke Energy Corp.
Owner CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Province of NC employed by *The Hartford Steam Boiler Inspection & Insurance Company of Connecticut have inspected the components described in this Owner's Report durifig the period.
dS Y-
-ýC>C, '7" to
//
-/
R
.ootr
, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in the Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, test, and corrective measures described in this Owner's Report.
Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage oya loss of any kind arising from or connected with this inspection Commissions AV-_//"
V AJ).
61 lDatector's Signature Date
/'-*'
National Board, State, 7rovince, and Endorsements 200-7
- The Hartford Steam Boiler Inspection & Insurance Company of Connecticut 200 Ashford Center North Suite 205 Atlanta, GA. 30338
Attachment to Form NIS-1 McGuire 1 EOC 19 Steam Generator Tube Inspection Report Pursuant to ASME Section XI and McGuire Technical Specification 5.6.8 the following information is provided:
- a.
The scope of inspections performed on each SG Iinspection scope included full length data acquisition and bobbin coil data analysis on allfour (4) steam generators as follows.
- 1) 100% of all tubes in each SG.
Special interest inspection scope included data acquisition and array data analysis asfollows:
- 1) Special interest based on new bobbin calls (new wear indications, all bobbin "I" codes, and some miscellaneous codes)
- 2) Periphery tubes 5 rows deep (Top of Tube Sheet both Hot Leg and Cold Leg to first support) in all four (4) steam generators (Outer perimeter and open lane)
- 3) New dent indications
- 4) Bounding inspections one tube around all PLP indications confirmed with array
- 5) All tubes with previous loose part indications or locations with loose parts left in-service.
Plug inspection scope was as follows:
- 1)
Visual inspection of all plugs,
- b. Active degradation mechanisms found Active degradation found in allfour (4) steam generators include wear at support structures and wear from loose parts.
- c.
Non-destructive examination techniques utilized for each degradation mechanism Bobbin was used to detect wear at support structures. Bobbin and array were used to detect wear from loose objects.
- d. Location, orientation (if linear), and measured sizes (if available) of service induced indications The complete listing for service induced indications is referenced in attachment
- 1.
- e. Number of tubes plugged during the inspection outage for each. active degradation mechanism In the 1B SG, tube R 104-C107 was preventively plugged due to the presence of a foreign object and tube R 116-C75 was plugged due to a 27% through wall wear indication due to fan bar wear.
- f.
The total number and percentage of tubes plugged to date Tubes Plugged Steam Generator A
B C
D Total Prior to 1EOC 19 2
2 5
4 12 lEOC19 0
2 0
0 2
Total 2
4 5
4 15
% Plugged 0.03%
0.06%
0.075%
0.06%
0.056%
- g. The results of condition monitoring, including the results of tube pulls and in-situ pressure testing An NDE maximum depth call of 54% TW or less is sufficient to demonstrate a minimum degraded tube burst pressure of 3AP at 0.95 probability with 50%
confidence. The worst case depth call observed during the McGuire JEOC19 inspection for wear at structures was 27% TW. The worst case depth call observed during the McGuire 1EOC19 inspection for general volumetric degradation was 33% TW. Therefore, condition monitoring structural integrity has been demonstrated. Since the burst pressure equation treats though-wall tearing as coincident with burst, demonstration of structural integrity also demonstrates leakage integrity at the lower differential pressure of a postulated steam line break accident. No in-situ testing was required or performed. No tube pulls were performed.
- h. The effective plugging percentage for all plugging in each SG The effective plugging percentagefor each of the McGuire Unit 1 Steam Generators is identical to those shown in section () above.
Attachment #1 Location, orientation, and measured sizes of service induced indications
AREVA NP Inc Customer Name: McGuire -
Unit 1 Replacement 01/22/09 00:47:15 Component: S/G A Page 1 of 5 QUERY: QueryM ROW 37 43 45 47 49 50 50 50 50 53 55 55 56 58 58 60 60 61 63 64 69 70 70 72 72 72 72 74 74 77 77 77 COL 68 68 60 78 60 87 91 93 95 84 64 88 89 71 101 83 89 54 110 97 72 63 73' 53 63 75 101 71 103 20 68 74 VOLTS 0.74 0.23 0.24 0.31 0.28 0.19 0.43 0.51 0.14 0.83 0.11 0.40
- 0.
07 0.28 0 08 0.32 0.22 0.08 0.42 0.12 0.37 0.16 0.27, 0.85 0.27 0.12 0.26 0.09 0.85 0.15 0.08 0.19 0.46 0.09 0.26 0.07 0.27 0.81 0.10 0.19 0.89 0.19 0.19 0.32 0.26 0.31 0.07 0.13 0.14 0.11 1.33 0.48 0.24 0.25
.051 DEG 99 101 92 79 92 84 92 113 127 82 72 106 39 106 82 82 93 62 112 59 151 103 87 98 102 83 96 117 105 68 115 96 128 117 118 122 103 112 61 89 110 108 110 84 97 105 117 113 122 79 164 114 110 62 CHN 22 P2 P2 P2 P2 P2 190 18 P2 82 P2 186 P2 18 P2 174 P2 P2 10 P2 6
P2 P2 174 6
P2 178 P2 190 P2 P2 190 6
P2 174 P2 P2 170 P2 P2 190 P2 P2 22 P2 178 P2 P2i P2 P2 174 P2 P2 Q16 IND %TW LOCATION VOL FB5
-1.18 TWD 12 FB5
-0.63 TWD 13 FB5
-1.04 TWD 11 FB4
+1.10 TWD 11 FB5
-0.96 TWD 7 03H
-1.57 VOL 03H
-1.51 VOL FB6
+0.85 TWD 6 FB6
+1.44 VOL FB2
+1.40 TWD 5 FB2
+0.75 VOL FB4
+0.77 TWD 3 FB4
+0.93 VOL FB4
+1.29 TWD 3 FB4
+1.20 VOL FB5
,+0.82 TWD 11 FB5
+1.40 TWD 5 FB3
+0.96 VOL FB3
+0.93 TWD 5 FB3
-1.87 VOL FB4
-0.69 TWD 8 FB4
-1.20 TWD 13 FB6
+1.03 VOL FB6
+0.90 VOL FB4
-1.02 TWD 5 FB4
-1.25 VOL FB4
-0.85 TWD 5 FB4
-1.29 VOL FB5
+1.31 TWD 8 FB5
+1.44 TWD 4 FB4
+1.41 VOL FB4
+0.93 VOL FB4
+1.21 TWD 5 FB4
+0.92 VOL FB4
-0.99 TWD 4 FB4
-1.02 TWD 10 FB4
-0.63 VOL FB4
-0.76 TWD 6 FB3
+0.44 TWD 8 FB4
+1.40 VOL FB4
+1.34 TWD 9 FB5
+1.51 TWD 9 FB5
+1.24 VOL FB5
+1.37 TWD 10 FB4
+1.61 VOL FB4
-1.16 TWD 3 FB4
-1.26 TWD 7 FB5
+0.63 TWD 7 FB4
+1.55 TWD 5 FB5
+0.57 VOL TSC
+0.24 TWD 11 TSC
-0.00 TO+0.27 TWd 9 FB4
+1.66 TWD 10 FB5
-1.16 VOL FB5
-1.34 EXT FB5 TEC TEC TEC TEC TEC 03H FB6 TEC FB2 TEC FB4 TEC FB4 TEC FB5 TEC TEC FB3 TEC FB4 TEC TEC FB6 FB4 TEC FB4 TEC FB5 TEC TEC FB4 FB4 TEC FB4 TEC TEC FB4 TEC TEC FB4 TEC TEC FB5 TEC FB4 TEC TEC TEC TEC 01C 01C
- TEC TEC FB5 EXT UTIL 1
FB5 WAR TEH WAR TEH WAR TEH WAR TEH WAR TEH WAR 03H WAR FB6 WAR TEH WAR FB2 WAR TEH WAR FB4 WAR TEH WAR FB4 WAR TEH WAR FB5 WAR TEH WAR TEH WAR FB3 WAR TEH WAR FB4 WAR TEH WAR TEH WAR FB6 WAR FB4-WAR TEH WAR FB4 WAR TEH WAR FB5 WAR TEH WAR TEH WAR FB4 WAR FB4 WAR TEH WAR FB4 WAR TEH WAR TEH WAR FB4 WAR TEH WAR TEH WAR FB4 WAR TEH WAR TEH WAR FB5 WAR TEH WAR FB4 WAR TEH WAR TEH WAR TEH WAR TEH WAR TSC LPI TSC 0.28 TEH WAR TEH WAR FB5 WAR UTIL 2
CAL #
802 507 501 502 523 502 801 802 523 801 523 801 523 801 523 802 522 501 801 523 801 522 540 802 801 525 801 522 802 522 503 801 801 526 801 524 502 801 536 514 801 509 511 801 514 801 518 513 513 520 3
0.27 3
512 514 801 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT
-HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD HOT HOT HOT PROBE 560XP 560UL 560UL 56OUL 560UL 560UL 560XP 560XP 560UL 560XP 560UL 560XP 560UL 560XP 560UL 560XP 560UL 56OUL 560XP 56OUL 560XP 56OUL 560UL 560XP 560XP 560UL 560XP 56OUL 560XP 560UL 560UL 560XP 560XP 560UL 560XP 56OUL 560UL 560XP 560UL 560UL 560XP 560UL 560UL 560XP 560UL 560XP 560UL 560UL 560UL 560UL 560XP 560XP 560UL 560UL 560XP SCOPE Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Special Interest E
Bobbin Exam Special Interest E Bobbin Exam Special Interest E Bobbin Exam Special Interest E Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Special Interest E Bobbin Exam Bobbin.Exam Special Interest E Special Interest E Bobbin Exam Special Interest E
.Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Special Interest E Special Interest E Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam TTS Array Exam TTS Array Exam Bobbin Exam Bobbin Exam Special Interest E
AREVA NP Inc Customer Name: McGuire -
Unit 1 Replacement 01/22/09 00:47:15 Component: S/G A Page-2 of 5 QUERY: QueryMl ROW COL VOLTS 77 84 0.41 0.09 78 19 0.27 0.31 0.27 79 20 0.33 0.63 79 60 0.23 79 62 0.23 0.23 80 21 0.65 0.64 1.05 80 67 0.12 0.20 80 91 0.25 0.08 81 20 0.:30 0.53 0.48 81 58 0.45 81 60 0.49 81 84
-0.63 0.28 82 21 0.24 0.09 0.17 0.36 0.39 0.16 0.20 0.20 0.14 82 73 0.16 0.34 83 60 0.37 85 72 0.11 85 74 0.36 85 82 0.24 85 84 0.77 0.38 0.28 0.17 86 67 0.29 86 73 0.25 86 119 0.85 0.68 1.04 87 120 0.12 0.12 88 73 0.40 0.28 0.63 88 119 0.74 0.90 DEG 113 53 79 90 127 35 32 91 91 126 95 94 89 146 106 122 60 81 81 119 86 69 123 96 97 74 102 89 93 99 98 88 110 88 89 80 123 96 98 98 97 94 82 87 80 105 94 90 83 83 77 81 90 96 85 CHN 186 P2 174 174 3
190 190 P2 P2 P2 3
22 46 P2 6
174 P2 174 178 3
P2 P2 146 P2 3
3 3
190 190 190 190 190 190 P2 190 P2 P2 P2 P2 166 18 P2 P2 P2 P2 3
130 126 142 142 190 P2 P2 3
6 IND %T*
VOL TWD 4 TWD 6 VOL NQI TWD 7 VOL TWD 11 TWD 11 TWD 11 NQI TWD 13 VOL TWD 6 VOL VOL TWD 5 TWD 7 VOL NQI TWD 18 TWD 19 VOL TWD 12 NQI NQI NQI TWD 8 VOL TWD 4 TWD 5 VOL VOL TWD 7 VOL TWD 16 TWD 6 TWD 14 TWD 10 VOL VOL TWD 12 TWD 7 TWD 11 TWD 10 NQI TWD 12 VOL TWD 2 VOL VOL TWD 14 TWD 25 NQI TWD 15 W LOCATION FB4 FB4 TSC TSC TSC TSC TSC FB4 FB4 FB4 TSC TSC TSC FB3 FB3 FB4 FB4 TSC TSC TSC FB4 FB4 FB5 FB5 TSC TSC.
TSC TSC TSC TSC TSC TSC TSC FB7 FB7 FB4 FB5 FB5 FB3 FB5 FB4 FB5 FB4 FB4 FB5 01C 01C 01C 01C 01C FB7 FB7 FB5 01C 01C
-1.21
-1.25
+0.76
+0.92
+0.80
+0.19
+0.37
-0.45
+0.95
-0.71
+1.09
+0..99
+1.17
+0.92
+0.96
-0.96
-1.10
+1.25
+1.42
+1.49
-0.56
-0.62
-0.69
-0.54
+0.72
+1.94
+2.30
+0.80
+1.01
+1.84
+2.13
+2.26
+1.92
+1.96
+1.88
-0.51
-0.59
-1.69
-0.60
-0.69
-1.88
-0.5-4
-1.85
+1.55
+1.81
-1.87
-1.93
-1.74
-1.87
-1.71
+1.53
+1.84
+1.67
-1.96
-1.98 TO+0.98 TO+0.43 TO+1.28 TO+1.47 TO+1.07 TO+2.05 TO+2.34 TO-1. 63 TO-1.66 TO-1.71 EXT FB4 TEC 01C 01C TEC 01C 01C TEC TEC TEC TEC 01C 01C TEC FB3 FB4 TEC 01C 01C TEC TEC TEC FB5 TEC TEC TEC TEC 01C 01C OIC 01C 01C 01C TEC FB7 TEC TEC TEC TEC FB5 FB4 TEC TEC TEC TEC TEC 01C 01C 01C 01C FB7 TEC TEC TEC 01C EXT FB4 TEH TSC TSC TEH TSC TSC TEH TEH TEH TEH TSC TSC TEH FB3 FB4 TEH TSC TSC TEH TEH TEH FB5 TEH TEH TEH TEH TSC TSC TSC TSC TSC TSC TEH FB7 TEH TEH TEH TEH FB5 FB4 TEH TEH TEH TEH TEH TSC TSC TSC TSC FB7 TEH TEH TEH TSC UTIL 1
WAR WAR 0.35 LPI 0.21 LPI WAR WAR WAR 0.35 LPI WAR WAR WAR WAR 0.35 LPI WAR WAR WAR WAR 0.35 LPI 0.21 0.21 LPI LPI WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0.28 LPI 0.21 LPI WAR WAR WAR 0.28 UTIL 2
CAL #
801 516 0.22 3
3 507 0.24 3
3 509 511 511 534 0.29 3
3 511 801 801 515 0.21 3
3 507 510 510 802 516 535 535 535 0.27
.3 3
0.21 3
0.21 3
3 3
514 802 509 536 514 514 801 801 516 516 512 514 521 0.29 5
5 0.21 5
5 802 513 513 521 0.27 5
LEG HOT HOT COLD COLD HOT COLD COLD HOT HOT HOT HOT COLD COLD HOT HOT HOT HOT COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD COLD COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT COLD COLD COLD COLD HOT HOT HOT.
HOT COLD PROBE SCOPE 560XP Special Interest E
56OUL Bobbin Exam 560XP TTS Array Exam 560XP TTS Array Exam 560UL Bobbin Exam 560XP TTS Array Exam 560XP TTS Array Exam 560UL Bobbin Exam 56OUL Bobbin Exam 560UL Bobbin Exam 560UL Bobbin Exam 560XP TTS Array Exam 560XP TTS Array Exam 560UL Bobbin Exam 560XP Special Interest E 560XP Special Interest E
560UL Bobbin Exam 560XP TTS Array Exam 560XP TTS Array Exam 56OUL Bobbin Exam 560UL Bobbin Exam 560UL Bobbin Exam 560XP Special Interest E
560UL Bobbin Exam 560UL Bobbin Exam 56OUL Bobbin Exam 560UL Bobbin Exam 560XP TTS Array Exam 560XP TTS Array Exam 560XP TTS Array Exam 560XP TTS Array Exam 560XP TTS Array Exam 560XP TTS Array Exam 560UL Bobbin Exam 560XP Special Interest E 56OUL Bobbin Exam 560UL Bobbin Exam 560UL Bobbin Exam 560UL Bobbin Exam 560XP Special Interest E 560XP Special Interest E 560UL Bobbin Exam 560UL Bobbin Exam 560UL Bobbin Exam 560UL Bobbin Exam 560UL Bobbin Exam 560XP TTS Array Exam 560XP TTS Array Exam 560XP TTS Array Exam 560XP TTS Array Exam 560XP Special Interest E 56OUL Bobbin Exam 560UL Bobbin Exam 560UL
-Bobbin Exam 560XP TTS Array Exam
AREVA NP Inc Customer Name: McGuire -
Unit 1 Replacement 01/22/09 00:47:15 Component: S/G A Page 3 of 5 QUERY: QueryMl ROW COL VOLTS 0.90 90 69 0.47 92 69 0.17 0.21 93 72 0.46 0.13 93 84 0.60 0.13 94 61 0.40 94 73 0.32 94 77 0.16 95 60 0.26 0.39 0.69 0.49 95 64 0.24 0.19 95 70 0.26 0.31 0.37 0.35 96 75 0.40 0.31 97 64 0.21 97 68 0.26 98 33 0.28 0.27 0.27 0.24 0.14 0.24 98 59 0.38 99 64 0.28 0.38 0.27 0.31 99 76 0.50 100 59 0.11 100 65 0.23 0.60 100 79 0.36 0.43 101 84 0.26 102 67 0.18 0.10 0.44 102 77 0.38 0.23 0.27 0.19 103 68 0.36 0.23 0.73 104 69 0.16 104 73 0.24 DEG 85 94 55 76 100 98 103 82 97 94 101 105 98 81 58 107 112 86 88 47 61 100 105 100 103 85 88 88 90 98 127 63 80 73 101 93 95 36 62 118 91 97 88 63 90 59 113 152 84 125 75 97 124 78 106 CHN 6
P2 P2 158 P2 178 166 P2 P2 P2 P2 P2 P2 158 158 P2 P2 P2 P2 122 158 P2 P2 P2 P2 46 46 46 46 3
3 P2 P2 P2 P2 154 P2 P2 P2 154 P2 P2 P2 P2 P2 Q8 186 146 P2 P2 P2 P2 174 P2 P2 IND %TW LOCATION VOL 01C
-1.87 TWD 20 FB4
+1.01 TWD 9 FB4
+1.68 VOL FB4
+1.68 TWD 17 FB5
+0.06 VOL FB5
+0.08 VOL FB4
-1.02 TWD 6 FB4
-0.95 TWD 16 FB5
-1.76 TWD 13 FB5
+0.61 TWD 8 FB4
+0.66 TWD 12 FB5
-1.84 TWD 17 FB4
-0.53 VOL FB4
-1.13 VOL FB5
-1.00 TWD 11 FB5
-1.25 TWD 9 FB3
-1.22 TWD 12 FB5
-1.69 TWD 14 FB4
-0.80 VOL FB4
-1.49 VOL FB5
-1.06 TWD 15 FB5
+0.57 TWD 12 FB3
-1.79 TWD 8 FB2
+0.76 TWD 10 FB6
+1.04 VOL TSC
+3.40 TWD 6 TSC
+0.66 TO+0.90 VOL TSC
+0.82 TWD 6 TSC
+3.21 TO+3.48 NQI TSC
+3.26 NQI TSC
+0.70 TWD 17 FB4
-1.63 TWD 13 FB5
-1.15 TWD 17 FB4
-1.03.
TWD 13 FB3
-1.15 VOL FB4
-1.02 TWD 21 FB4
+0.60 TWD 6 FB4
-1.66 TWD 12 FB5
+0.56 VOL FB5
+0.52 TWD 17 FB4
+1.79 TWD 19 FB5
+1.67 TWD 11 FB5
-0.54 TWD 10 FB5
+0.62 TWD 6 FB3
+0.71 VOL FB5
+1.23 VOL FB4
+1.23 VOL FB5
+1.34 TWD 13 FB4
+1.79 TWD 10 FB5
+0.77 TWD 16 FB4
-0.95 TWD 11 FB3
-1.31 VOL FB4
-0.08 TWD 9 FB4
+1.68 TWD 10 FB7
+1.78 EXT 01C TEC TEC FB4 TEC FB5 FB4 TEC TEC TEC TEC TEC TEC FB4 FB5 TEC TEC TEC TEC FB4 FB5 TEC TEC TEC TEC 01C 01C 01C 01C TEC TEC TEC TEC TEC TEC FB4 TEC TEC TEC FB5 TEC TEC TEC TEC TEC FB5 FB4 FB5 TEC TEC TEC TEC FB4 TEC TEC EXT UTIL TSC LPI TEH WAR TEH WAR FB4 WAR TEH WAR FB5 WAR FB4 WAR TEH WAR TEH WAR TEH WAR TEH WAR TEH WAR TEH WAR FB4 WAR FB5 WAR TEH WAR TEH WAR TEH WAR TEH WAR FB4 WAR FB5 WAR TEH WAR TEH WAR TEH WAR TEH WAR TSC LPI TSC 0.21 TSC LPI TSC 0.21 TEH TEH TEH WAR TEH WAR TEH WAR TEH WAR FB4 WAR TEH WAR TEH WAR TEH WAR FB5 WAR TEH WAR TEH WAR TEH WAR TEH WAR TEH WAR FB5 WAR FB4 WAR FB5 WAR TEH WAR TEH WAR TEH WAR TEH WAR FB4 WAR TEH WAR TEH WAR 1
UTIL 2
CAL # LEG 5
COLD 511 HOT 536 HOT 801 HOT 514 HOT 801 HOT 801 HOT 516 HOT 510 HOT 514 HOT 513 HOT 509 HOT 509 HOT 802 HOT 802 HOT 511 HOT 511 HOT 511 HOT 511 HOT 802 HOT 802 HOT 514 HOT 514 HOT 512 HOT 512 HOT 3
COLD 0.24 3
COLD 3
COLD 0.26 3
COLD 507 HOT 507 HOT 509 HOT 511 HOT 511 HOT 511 HOT 801 HOT 513 HOT 536 HOT 536 HOT 801 HOT 513 HOT 513 HOT 516 HOT 536 HOT 536 HOT 801 HOT 801 HOT 801 HOT 513 HOT 513 HOT 511 HOT 511 HOT 801 HOT 536 HOT 514 HOT PROBE 560XP 560UL 560UL 560XP 560UL 560XP 560XP 56OUL 560UL 56OUL 56OUL 560UL 560UL 560XP 560XP 560UL 560UL 56OUL 56OUL 560XP 560XP 560UL 56OUL 560UL 560UL 560XP 560XP 560XP 560XP 560UL 560UL 560UL 560UL 560UL 560UL 560XP 560UL 560UL 560UL 560XP 560UL 560UL 560UL 560UL 560UL 560XP 560XP 560XP 560UL 560UL 560UL 560UL 560XP 560UL 560UL SCOPE TTS Array Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam TTS Array Exam TTS Array Exam TTS Array Exam TTS Array Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Special Interest E Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam
AREVA NP Inc Customer Name: McGuire -
Unit 1 Replacement 01/22/09 00:47:15 Component: S/G A Page 4 of 5 QUERY: QueryMl ROW COL VOLTS 104 77 0.10 105 66 0.36 105 82 0.16 106 67 0.37 106 69 0.44 0.52 0.14 0.-16 106 77 0.25 108 57 0.23 0.56 108 69 0.21 0.71 109 70 0.34 0.07 109 72 0.31 110 57 0.19 0.57 110 67 0.23 111 58 0.05 0.25 111 66 0.46 0.26 0.28 0.19 0.43 0.71 111 68 0.22 111 74 0.14 112 65 0.30 0.34 0.19 0.16 0.26 112 69 0.14 0.20 112 73 0.10 0.47 113 62 0.26 0.61 113 68 0.37 113 76 0.35 113 80 0.35 0.23 0.16 0.55 0.58 114 67 0.67 0.27 114 71 0.32 0.75 115 66 0.17 0.29 116 67 0.15 0.48 DEG 54 68 95 106 89 92 108 100 91 85 77 66 96 90 139 104 56 87 84 73 78 86 121 92 125 137 87 92 106 87 87 100 62 97 80 91 94 103 77 156 67 91 83 98 115 128 38 86 95 78 101 107 98 102 90 CHN P2 P2 P2 P2 P2 P2 178 154 P2 P2 154 P2 174 166 P2 P2 P2 154 P2 P2 162 P2 P2 P2 190 154 178 P2 P2 P2 P2 P2 122 154 P2 P2 P2 190 P2 166 P2 P2 P2 P2 P2 186 146 P2 P2 P2 174 P2 166 P2 186 IND %T*
TWD 6 TWD 13 TWD 7 TWD 14 TWD 16 TWD 19 VOL VOL TWD 12 TWD 9 VOL TWD 11 VOL VOL TWD 4 TWD 12 TWD 10 VOL TWD 12 TWD 3 VOL TWD 20 TWD 12 TWD 13 VOL VOL VOL TWD 11 TWD 7 TWD 15 TWD 16 TWD 10 VOL VOL TWD 8 TWD 11 TWD 4 VOL TWD 10 VOL TWD 14 TWD 14 TWD 14 TWD 9 TWD 7 VOL VOL TWD 22 TWD 10 TWD 13 VOL TWD 8 VOL TWD 8 VOL W LOCATION EXT EXT UTIL 1
UTIL 2
CAL # LEG PROBE FB7 FB4 FB4 FB4 FB6 FB5 FB5 FB6 FB4 FB5 FB5 FB4 FB4 FB4 FB4 FB5 FB5 FB5 FB5 FB5 FB5 FB6 FB4 FB4 FB4 FB6 FB4 FB4 FB4 FB6 FB5 FB2 FB5 FB6 FB3 FB2 FB4 FB4 FB7 FB7 FB4 FB4 FB4 FB3 FB5 FB3 FB4 FB4 FB3 FB4 FB4 FB4 FB4 FB3 FB3
+0.62
-0.51
-1.64
-1.61
+1.56
+0.63
+1.21
+1.02
+1.60
+1.62
+1.45
+1.68
+1.20
+0.79
+0.83
+0.03
+1.77
+1.48
-1.68
+1.04
+1.04
-1.12
+1.12
-1.27
+1.12
-1.12
-0.98
+0.51
+1.61
+1.68
+0.59
-1.30
+1.07
+1.40
+0.68
-1.39
+1.07
+1.18
+0.60
+0.63
-0.50
-1.48
-1.66
+0.15
-1.69
-0.44
-1.76
-1.16
-0.54
+1.40
+1.78
+0.80
+0.93
-0.68
-0.63 TEC TEC TEC TEC TEC TEC FB5 FB6 TEC TEC FB5 TEC FB4 FB4 TEC TEC TEC FB5 TEC TEC FB5 TEC TEC TEC FB4 FB6 FB4 TEC TEC TEC TEC TEC FB5 FB6 TEC TEC TEC FB4 TEC FB7 TEC TEC TEC TEC TEC FB3 FB4 TEC TEC TEC FB4 TEC FB4 TEC FB3 TEH TEH TEH TEH TEH TEH FB5 FB6 TEH TEH FB5 TEH FB4 FB4 TEH TEH TEH FB5 TEH TEH FB5 TEH TEH TEH FB4 FB6 FB4 TEH TEH TEH TEH TEH FB5 FB6 TEH TEH TEH FB4 TEH FB7 TEH TEH TEH TEH TEH FB3 FB4 TEH TEH TEH FB4 TEH FB4 TEH FB3 WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 536 512 514 512 537 537 802 802 513 537 801 536 801 801 513 514 536 801 540 509 801 511 511 511 801 801 801 511 513 536 536 536 801 801 536 536 514 801 512 802 512 514 514 514 514 801 801 512 512 537 801 511 801 511 801 HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT 560UL 560UL 560UL 560UL 560UL 560UL 560XP 560XP 56OUL 560UL 560XP 56OUL 560XP 560XP 56OUL 56OUL 560UL 560XP 56OUL 56OUL 560XP 56OUL 560UL 560UL 560XP 560XP 560XP 560UL 56OUL 560UL 560UL 560UL 560XP 560XP 560UL 560UL 56OUL 560XP 56OUL 560XP 560UL 560UL 560UL 560UL 560UL 560XP 560XP 560UL 56OUL 560UL 56OXP 560UL 560XP 56OUL 560XP SCOPE Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Special Interest E
Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
AREVA NP Inc Customer Name: McGuire -
Unit 1 Replacement 01/22/09 00:47:15 Component: S/G A Page 5 of 5 QUERY: QueryMl ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1
UTIL 2
CAL # LEG PROBE SCOPE Total Tubes
- 110 Total Records: 220
AREVA NP Inc Customer Name: McGuire Nuclear Station - Unit One 01/22/09 02:25:54 Component: S/G B Page 1 of 3 QUERY: QueryMl ROW 5
39 45 46 49 51 57 58 61 62 64 65 68 69 76 77 77 78 80 81 81 81 82 86 88 88 89 89 91 92 94 94 94 94 95 COL VOLTS 72 0.18 88 0.15 52 0.15 0.10 57 0.14 82 0.29 78 0.32 76 0.65 0.22 75 0.23 0.07 52 0.24 43 2.36 0.27 0.25 73 0.49 0.11 88 0.79 0.33 51 0.24 64 0.46 0.12 79 0.36 0.83 64 0.28 0.32 66 0.37 71 0.56 67 0.13 0.38 64 0.42 66 0.44 80 0.24 65 0.36 83 0.24 31 0.47 0.13 71 0.36 0.12 70 0.33 0.13 72 0.84 68 0.37 0.25 77 0.58 65 0.12 73 0.35 0.22 0.47 0.45 75 0.54 1.00 77 0.38 0.45 72 0.51 DEG 103 116 86 106 84 103 99 86 120 101 87 91 79 77 75 ill 68 95 91 78 89 102 117 128 46 27 72 103 93 112 53 110 72 105 101 75 103 131 272 1il 103 87 110 77 81 115 100 97 35 115 97 223 90 96 102 CHN IND %TW P2 TWD 7 P2 TWD 5 P2 TWD 5 P2 TWD 3 P2 TWD 5 P2 TWD 11 P2 TWD 10 18 VOL P2 TWD 9 178 VOL P2 TWD 3 P2 TWD 8 22 VOL P2 TWD 9 P2 TWD 9 174 VOL P2 TWD 4 190 VOL P2 TWD 12 P2 TWD 8 178 VOL P2 TWD 5 P2 TWD 13 P30 VOL P2 TWD 9 190 VOL P2 TWD 11 P2 TWD 16 P2 TWD 5 186 VOL P2 TWD 13 P2 TWD 13 P2 TWD 9 P2 TWD 11 P2 TWD 9 150 VOL P2 TWD 5 P2 TWD 13 178 VOL P2 TWD 10 178 VOL P2 TWD 25 P2 TWD 13 190 VOL P2 TWD 18 P2 TWD 4 P2 TWD 14 P2 TWD 10 190 VOL 186 VOL P2 TWD 20 190 VOL 166 VOL P2 TWD 16 P2 TWD 15 LOCATION 07H
+1.57 FB4
-0.68 FB4
-0.86 06H
+0.41 FB3
-1.99 FB5
+0.86 FB4
-0.95 FB5
+1.44 FB5
+1.39 FB7
+1.24 FB7
+0.59 FB5
+1.51 07H
-1.56 07H
-1.50 07H
-1.50 FB5
+1.15 FB5
+1.20 FB4
+1.40 FB4
+1.47 FB5
-1.32 FB4
+1.55 FB4
+1.63 FB4
-0..68 FB4
+1.09 FB4
-1.36 FB4
-0.75 FB4
-1.63 FB5
-1.01 FB4
+1.21 FB4
+1.38 FB4
-1.30 FB5
+1.09 FB2
-1.92 FB5
-1.42 FB4
-1.74 08H
+0.39 08H
+0.38 FB5
-1.66 FB5
-0.63 FB5
+1.13 FB5
+1.30 FB5
-0.06 FB5
-1.65 FB5
-1.60 FB5
-1.60 FB4
-0.89 FB4
-1.21 FB2
-1.80 FB4
-1.26 FB2
-1.82 FB5
-1.12 FB5
-1.63 FB5
-1.18 FB5
-1.06 FB5
+0.15 EXT 09C TEC TEC TEC TEC TEC TEC FB5 TEC FB7 TEC TEC 07H TEC TEC FB5 TEC FB4 TEC TEC FB4 TEC TEC FB4 TEC FB4 TEC TEC TEC FB4 TEC TEC TEC TEC TEC 08H TEC TEC FB5 TEC FB5 TEC TEC FB5 TEC TEC-TEC TEC FB4 FB2 TEC FB5 FB5 TEC TEC EXT TEW TEH TEH TEH TEH TEH TEH FB5 TEH FB7 TEH TEH 07H TEH TEH FB5 TEH FB4 TEH TEH FB4 TEH TEH FB4 TEH FB4 TEH TEH TEH FB4 TEH TEH TEH TEH TEH 08H TEH TEH FB5 TEH FB5 TEH TEH FB5 TEH TEH TEH TEH FB4 FB2 TEH FB5 FB5 TEH TEH UTIL 1
WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2
CAL #
557 521 538 538 539 520 521 801 520 801 553 538 801 541 IDOK 544 801 552 801 520 538 801 537 506 801 525 801 525 525 524 801 525 525 505 525 505 801 535 524 801 525 801 524 524 801 506 525 507 507 801 801 507 801 801 505 525 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 560UL 56OUL 560UL 560UL 560UL 560UL 560UL 560XP 56OUL 560XP 560UL 56OUL 560XP 560UL 560UL 560XP 560UL 560XP 560UL 56OUL 560XP 560UL 56OUL 560XP 56OUL 560XP 560UL 560UL 560UL 560XP 560UL 560UL 560UL 56OUL 560UL 560XP 560UL 56OUL 560XP 560UL 560XP 560UL 560UL 560XP 560UL 560UL 560UL 560UL 560XP 560XP 560UL 560XP 560XP 56OUL 56OUL SCOPE Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
-Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Bobbin Exam
AREVA NP Inc Customer Name: McGuire Nuclear Station - Unit One 01/22/09 02:25:54 Component: S/G B Page 2 of 3 QUERY: QueryMl ROW COL VOLTS 0.42 95 80 0.39 96 35 0.35 0.38 0.27 96 75 0.61 0.73 97 36 0.22 0.17 0.14 97 68 0.34 0.38 97 72 0.94 0.90 99 72 0.53 0.46 100 35 0.19 0.17 0.13 101 78 0.28 102 73 0.23 105 74 0.24 0.21 106 73 0.19 106 77 0.33 0.38 106 89 0.83 0.25 108 75 0.28 0.24 108 87 0.20 0.36 110 75 0.20 0.55 110 83 0.46 0.17 111 78 0.30 112 77 0.22 0.51 0.68 114 75 0.20 0.40 0.22 0.40 0.47 0.36 116 73 0.23 0.63 116 75 0.91 0.44 0.24 1.17 0.67 1.26 DEG 94 93 96 101 98 87 95 107 110 86 91 54 89 87 110 237 91 93 87 102 102 118 ill 114 92 93 127 92 107 76 91 271 84 116 92 74 83 1il 99 74 ill 89 106 327 80 141 ill 106 74 79 112 108 126 230 CHN 166 P2 18 18 3
P2 166 14 46 3
P2 190 P2 P2 P2 174 10 10 3
P2 P2 P2 190 P2 166 P2 P30 P2 P2 190 P2 186 P2 P14 154 P2 P2 P2 P2 166 P2 P2 P2 178 166 178 P2 154 P2 P2 P2 190 190 190 IND %T*
VOL TWD 13 VOL TWD 6 NQI TWD 21 VOL VOL TWD 3 NQI TWD 11 VOL TWD 27 TWD 26 TWD 18 VOL VOL TWD 3 NQI TWD 11 TWD 10 TWD 10 VOL TWD 8 VOL TWD 14 VOL TWD 10 TWD 10 VOL TWD 7 VOL TWD 9 VOL VOL TWD 6 TWD 11 TWD 8 TWD 17 VOL TWD 9 TWD 16 TWD 10 VOL VOL VOL TWD 9 VOL TWD 27 TWD 16 TWD 9 VOL VOL VOL W LOCATION FB5 FB4 TSH TSH TSH FB5 FB5 TSH TSH TSH FB5 FB5 FB4 FB5 FB5 FB5 TSH TSH TSH FB4 FB4 FB5 FB5 FB4 FB5 FB5 FB5 FB5 FB4 FB4 FB4 FB4 FB6 FB6 FB4 FB4 FB5 FB5 FB4 FB4 FB7 FB5 FB3 FB7 FB5 FB3 FB4 FB4 FB5 FB4 FB3 FB5 FB4 FB3
-0.14
+0.62
+3.47
+3.23
+3.22
-1.21
-1.20
+3.24
+3.20
+3.13
-1.22
-1.65
+0.03
+0.03
-0.44
-0.42
+2.11
+1.98
+1.90
+1.12
-1.18
+1.24
+0.82
+1.47
-1.01
-1.06
-1.21
-1.68
-1.07
-1.07
-0.56
-0.82
+0.56
+0.66
+1.01
+1.15
-1.60
+1.12
-0.59
-0.91
+1.56
-1.18
+0.83
+1.70
-1.18
+0.88
+1.48
+1.48
-1.21
-1.07
-1.15
-1.84
-0.49
-0.49 TO+3 TO+3 TO+2 EXT FBS TEC 01H
.58 01H TEC TEC FB5 01H
.44 01H TEC TEC FB5 TEC TEC TEC FB5 01H
.22 01H TEC TEC TEC TEC FB5 TEC FB5 TEC FB5 TEC TEC FB4 TEC FB4 TEC FB6 FB4 TEC TEC TEC TEC FB4 TEC TEC TEC FB7 FB5 FB3 TEC FB4 TEC TEC TEC FB5 FB4 FB3 EXT UTIL I
FB5 WAR TEH WAR TSH TSH 0.28 TEH TEH WAR FB5 WAR TSH TSH 0.28 TEH TEH WAR FB5 WAR TEH WAR TEH WAR TEH WAR FB5 WAR TSH TSH 0.21 TEH TEH WAR TEH WAR TEH WAR FB5 WAR TEH WAR FB5 WAR TEH WAR FB5 WAR TEH WAR TEH WAR FB4 WAR TEH WAR FB4 WAR TEH WAR FB6 WAR FB4 WAR TEH WAR TEH WAR TEH WAR TEH WAR FB4 WAR TEH WAR TEH WAR TEH WAR FB7 WAR FB5 WAR FB3 WAR TEH WAR FB4 WAR TEH WAR TEH WAR TEH WAR FB5 WAR FB4 WAR FB3 WAR UTIL 2
CAL #
801 506 7
0.35 7
532 508 801 7
0.24 7
531 525 801 524 524 524 801 7
0.24 7
532 505 507 507 801 507 801 505 801 505 508 801 506 801 507 801 801 5O5 506 506 506 801 507 507 507 801 801 801 508 801 508 508 508 801 801 801 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 560XP 560UL 560XP 560XP 560UL 56OUL 560XP 560XP 560XP 56OUL 560UL 560XP 560UL 560UL 560UL 560XP 560XP 560XP 56OUL 560UL 56OUL 560UL 560XP 56OUL 560XP 560UL 560XP 560UL 560UL 560XP 560UL 560XP 560UL 560XP 560XP 560UL 560UL 56OUL 560UL 560XP 560UL 560UL 560UL 560XP 560XP 560XP 560UL 560XP 560UL 560UL 560UL 560XP 560XP 560XP SCOPE Special Interest E
Bobbin Exam TTS Array Exam TTS Array Exam Bobbin Exam Bobbin Exam Special Interest E
TTS Array Exam TTS Array Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
TTS Array Exam TTS Array Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Special Interest E
Special Interest E
Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Special Interest E
Special Interest E
AREVA NP Inc Customer Name: McGuire Nuclear Station - Unit One 01/22/09 02:25:54 Component: S/G B Page 3 of 3 QUERY: QueryMl ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1
UTIL 2
CAL # LEG PROBE SCOPE Total Tubes
- 58 Total Records: 109
AREVA NP Inc Customer Name: McGuire - Unit 1 Replacement 01/22/09 02:28:50 Component: S/G C Page 1 of 3 QUERY: QueryMl ROW 29 33 33 61 62 63 63 65 66 68 69 69 73 75 75 75 76 77 77 78 79 80 82 82 82 83 84 84 85 85 86 86 86 87 90 90 COL 124
.66 104 68 77 58 88 64 93 53 60 64 60 54 60 66 61 60 72 69 60 61 59 63 73 60 65 67 60 62 59 61 73 70 59 67 VOLTS 0.99 0.17 0.18 1.79 0.77 0.62 0.22 0.30 0.50 0.50 0.33 0.15 0.40 0.13 0.11 0.88 0.20 0.24 0.46 0.15 0.33 0.19 0.25 0.22 0.10 0.38 0.31 0.56 0.45 0.33 0.19 0.19 0.24 0.36 0.17 0.16 0.22 0.37 0.25 0.32 0.41 0.64 0.69 0.26 0.31 0.22 0.21 0.34 0.33 0.40 0.30 0.92 0.30 0.14 0.49 DEG 60 115 97 83 63 112 79 83 83 73 80 58 89 93 59 125 90 78 143 79 87 101 82 112 102 99 78 60 123 91 104 102 95 133 106 106 47 80 102 92 98 85 220 99 106 62 90 98 97 76 92 71 ill 80 102 CHN 70 P2 P2 150 Q7 P1 P2 Q6 P2 P2 Q6 P2 Q5 P2 P2 Plo P2 P2 P26 P2 P2 P2 P2 138 P2 P2 P2 118 P2 P2 106 P2 P2 106 P2 P2 P2 P2 106 P2 P2 P2 118 P2 106 142 P2 P2 P2 P2 P2 P9 142 P2 106 IND VOL TWD TWD VOL TWD NQI TWD VOL TWD TWD VOL TWD VOL
- TWD, TWD VOL TWD TWD VOL TWD TWD TWD TWD VOL TWD TWD TWD VOL TWD TWD VOL TWD TWD VOL TWD TWD TWD TWD VOL TWD TWD TWD VOL TWD VOL VOL TWD TWD TWD TWD TWD VOL VOL TWD VOL
%TW LOCATION 04H 7
04H 8
FB5 04H 20 04H 04H 9
FB5 FB5 19 FB5 17 FB5 FB4 6
FB4 FB4 6
FB4 4
05H FB4 9
FB4 10 FB4 FB4 6
FB4 10 FB4 6
FB4 11 FB4 FB4 4
FB4 11 FB5 9
FB4 FB4 17 FB4 10 FB5 FB5 9
FB4 7
FB6 FB5 8
FB5 8
FB5 8
FB5 15 FB4 FB5 14 FB5 12 FB5 17 FB4 FB6 8
FB6 FB5 FB3 10 FB3 14 FB5 14 FB5 13 FB5 9
FB5 FB5 FB3 7
FB3 FB6
-1.68
-1.52
+1.91
-1.42
-1.75 TO-1.42
-1.58
+0.78
+0.94
-0.95
+1.01
-0.74
-1.10
+1.49
+1.65
+0.48
-1.02
-1.79
-0.51*
+1.72
+1.26
-0.62
-1.09
-0.57
-1.08
-1.07
-1.18
-0.59
-0.38
-0.59
-1.28
-1.34
-0.63
-1.12
-1.21
-0.62
-1.64
+1.61
-0.57
-1.35
-1.64
-1.30
-0.98
-1.62
-1.74
-0.97
+0.75,
+0. 62
-1.16
-1.67
+1.74
+1.19
+1. 63
+1.32
+0.66
-0.69 EXT 04H TEC TEC 04H 04H TEC TEC FB5 TEC TEC FB4 TEC FB4 TEC TEC FB4 TEC TEC FB4 TEC TEC TEC TEC FB4 TEC TEC TEC FB4 TEC TEC FB5 TEC TEC FB5 TEC TEC TEC TEC FB5 TEC TEC TEC FB6 TEC FB5 FB3 TEC TEC TEC TEC TEC PB5 FB3 TEC FB6 EXT 04H TEH TEH 04H 04H TEH TEH FB5 TEH TEH FB4 TEH FB4 TEH TEH FB4 TEH TEH FB4 TEH TEH TEH TEH FB4 TEH TEH TEH FB4 TEH TEH FB5 TEH TEH FB5 TEH TEH TEH TEH FB5 TEH TEH TEH FB6 TEH FB5 FB3 TEH TEH TEH TEH TEH FB5 FB3 TEH FB6 UTIL 1
WAR WAR WAR LPI 46.00 WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2
CAL #
801 549 506 801 0.33 801 545 506 801 542 509 801 543 801 506 543 801 508 506 801 506 525 527 524 801 522 525 525 801 552 523 801 524 525 801 524 524 531 524 801 522 523 525 801 525 801 801 524 524 524 531 523 801 801 524 801 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT
-HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 560XP 560UL 560UL 560XP 560XP 560UL 560UL 560XP 560UL 560UL 560XP 560UL 560XP 560UL 560UL 560XP 560UL 560UL 560XP 560UL 560UL 560UL 560UL 560XP 560UL 560UL 560UL 560XP 560UL 560UL 560XP 560UL 560UL 560XP 560UL 560UL 560UL 560UL 560XP 560UL 560UL 560UL 560XP 56OUL 560XP 560XP 56OUL 560UL 560UL 560UL 560UL 560XP 560XP 560UL 560XP SCOPE Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Special Interest E
AREVA NP Inc Customer Name: McGuire - Unit 1 Replacement 01/22/09 02:28:50 Component: S/G C Page 2, of 3 QUERY: QueryMl ROW COL VOLTS 0.21 90 71 0.11 90 73 0.30 93 68 0.28 0.24 93 70 0.25 0.32 93 74 0.22 94 61 0.44 0.18 0.25 95 54 0.13 95 60 0.40 95 64 0.14 0.42 96 59 0.41 96 61 0.36 96 67 0.66 0.22 98-61 0.26 99 62 0.16 100 59 0.33 0.18 0.16 100 61 0.70 0.41 101 64 0.16 0.50 102 63 0.16 104 65 0.28 104 73 0.13 105 68 0.20 0.32 107 68 0.46 0.29 108 65 0.48 0.22 0.26 0.31 109 68 0.27 0.30 110 61 0.64 110 63 0.24 0.23 110 67 0.33 114 61 0.23 0.23 DEG 102 52 70 115 112 101 103 75 120 87 102 65 92 44 97 93 90 100 84 94 113 110 126 73 158 83 257 98 127 109 110 105 83 77 81 148 115 103 ill 107 96 81 116 105 97 123 83 CHN IND P2 TWD P2 TWD P2 TWD 118 VOL P2 TWD 118 VOL P2 TWD P2 TWD 130 VOL P2 TWD P2 TWD P2 TWD P2 TWD 118 VOL P2 TWD P2 TWD P2 TWD 142 VOL P2 TWD P2 TWD P2 TWD 130 VOL P2 TWD P2 TWD 118 VOL P2 TWD 118 VOL P2 TWD P2 TWD P2 TWD P2 TWD 142 VOL P2 TWD Q14 VOL P2 TWD 106 VOL 106 VOL P2 TWD P2 TWD 106 VOL P2 TWD P2 TWD 142 VOL P2 TWD P2 TWD 118 VOL P2 TWD
%TW LOCATION 10 FB6
-0.69 5
FB4
-1.56 10 FB5
+1.71 FB5
-1.24 11 FB5
-1.73 FB5
-1.16 14 FB5
-0.59 8
FB4
-1.12 FB6
-0.83 8
FB6
-0.60 11 FB5
-1.58 4
FB4
+1.45 16 FB4
-0.60 FB5
-1.16 12 FB5
-1.24 17 FB4
+1.19 10 FB5
-1.65 FB4
+1.42 7
FB4
+1.38 11 FB6
-0.60 8
FB7
+0.78 FB4
-1.13 9
FB4
-1.16 7
FB6
+1.73 FB6
+0.57 12 FB6
+0.45 FB5
-1.10 19 FB5
-1.10 8
FB7
+1.22 8
FB4
+1.19 6
FB4
+1.22 FB6
-1.60 14 FB6
-1.79 FB5
-0.96 9
FB5
-0.93 FB5
-1.87 FB4
-1.07 8
FB5
-1.35 9
FB4
-1.13 FB5
+0.77 13 FB5
+0.66 23 FB4
-0.93 FB7
+1.52 10 FB7.
+1.67 14 FB4
-0.60 FB6
+1.13 10 FB6
+1.19 EXT TEC TEC TEC FB5 TEC FB5 TEC TEC FB6 TEC TEC TEC TEC FB5 TEC TEC TEC FB4 TEC TEC TEC FB4 TEC TEC FB6 TEC FB5 TEC TEC TEC TEC FB6 TEC FB5 TEC FB5 FB4 TEC TEC FB5 TEC TEC FB7 TEC TEC FB6 TEC EXT TEH TEH TEH FB5 TEH FB5 TEH TEH FB6 TEH TEH TEH TEH FB5 TEH TEH TEH FB4 TEH TEH TEH FB4 TEH TEH FB6 TEH FB5 TEH TEH TEH TEH FB6 TEH FB5 TEH FB5 FB4 TEH TEH FB5 TEH TEH FB7 TEH TEH FB6 TEH UTIL 1
UTIL 2
WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR CAL #
522 520 531 801 522 801 522 531 801 524 524 527 524 801 525 524 525 801 523 524 524 801 524 524 801 525 801 524 524 525 530 801 522 801 523 801 801 525 525 801 522 524 801 524 522 801 524 LEG HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 560UL 560UL 560UL 560XP 56OUL 560XP 560UL 56OUL 560XP 560UL 56OUL 56OUL 56OUL 560XP 560UL 560UL 56OUL 560XP 560UL 560UL 560UL 560XP 560UL 560UL 560XP 560UL 560XP 56OUL 560UL 560UL 560UL 560XP 560UL 560XP 56OUL 560XP 560XP 560UL 560UL 560XP 560UL 560UL 560XP 560UL 560UL S60XP 560UL SCOPE Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Special Interest E Bobbin Exam Special Interest E Special Interest E Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Total Tubes
- 64 Total Records: 102
AREVA NP Inc Customer Name: McGuire - Unit 1 Replacement 01/22/09 02:28:50 Component: S/G C Page 3 of 3 QUERY: QueryMl ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1
UTIL 2
CAL # LEG PROBE SCOPE
AREVA NP Inc 01/22/09 02:32:36 Component: S/G D Page 1 of 2 TJ J Re lacement customer Name: mc u re n
L, QUERY: QueryMl ROW COL VOLTS 6
61 0.19 0.33 0.41 15 142 0.18 31 8
1.08 1.79 2.03 32 7
0.60 0.36 0.39 33 8
0.12 0.16 0.13 0.11 34 7
0.52 0.59 0.85 45 98 0.18 0.35 51 60 0.13 0.64 56 75 0.43 0.23 59 92 0.26 67 80 0.12 68 55 0.19 0.53 72 57 0.64 0.11 76 85 0.10 77 86 0.32 0.81 85 86 0.18 87 74 0.22 87 90 0.15 89 78 0.26 91 82 0.21 92 65 0.43 0.08 93 80 0.25 96 81 0.30 97 72 0.40 0.48 0.24 0.28 98 73 0.17 99 80 0.35 0.25 100 79 0.12 0.58 103 56 0.08 107 80 0.25 112 83 0.31 0.28 DEG 127 100 96 112 110 105 46 155 166 39 48 116 95 123 146 145 106 125 116 77 102 107 93 98 102 119 107 100 70 99 105 66 98 132 88 122 108 96 73 102 61 39 36 121 119 80 60 91 89 108 74 85 103 101 CHN P1 82 82 P2 178 26 Q3 54 178 Q8 138 62 90 3
70 166 Q15 P2 10 P2 18 46 P2 P2 P2 P2 6
186 P2 P2 P2 Q1 P2 P2 P2 P2 P2 186 P2 P2 P2 Q8 Q8 P2 P2 P2 P2 P2 P2 170 P2 P2 P2 P2 IND %TW NQI VOL TWD 8 TWD 7 VOL VOL TWD 33 VOL VOL TWD 10 VOL VOL TWD 3 NQI VOL VOL TWD 19 TWD 8 VOL TWD 6 VOL VOL TWD 11 TWD 12 TWD 7 TWD 10 VOL VOL TWD 5.
TWD 4 TWD 14 VOL TWD 8 TWD 11 TWD 8 TWD 12 TWD 11 VOL TWD 4 TWD 11 TWD 15 VOL VOL TWD 11 TWD 12 TWD 6 TWD 17 TWD 13 TWD 7 VOL TWD 4 TWD 13 TWD 14 TWD 13 LOCATION 07C 07C 07C 07H TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH FB5 FB5 FB5 FB5 FB5 FB5 FB4 FB7 FB6 FB6 FB4 FB4 FB4 FB5 FB5 FB5 FB4 FB4 FB5 FB4 FB4 FB4 FB6 FB5 FB5 FB4 FB5 FB4 FB4 FB4 FB7 FB7 FB7 FB4 FB6 FB4 FB5
-1.72
-1.87
-2.01 TO-1.71
+0.36
+0.16
+0.08
-0.13 TO+0.11
+0.19
+0.19
-0.11 TO+0.05
+17.78
+17.67
+17.56 TO+17.91
+17.53
+0.18
+0.19
-0.19 TO+0.08
-1.40
-1.48
+0.82
+1.08
-1.14
-1.59
+1.59
+1.88
+0.80
+0.85
-1.07
-1.22
+0.98
-1.69
-1.15
-1.54
+1.81
-0.57
-1.66
+1.69
-0.82
-0.98
-0.56
+0.83
+0.09
-0.17
+0.12
+0.00
+1.04
-0.62
+1.77
+0.62
+0.79
-0.86
-0.56
+1.16
+0.80 EXT EXT 09C TEC 07C 06C 07C 06C TEC TEH TSH 01H 01H TSH 01H TSH TSH 01H 01H TSH 01H TSH TSH 01H 01H TSH 01H TSH TEC TEH TSH 01H 01H TSH 01H TSH TEC TEH FB5 FB5 TEC TEH FB5 FB5 FB5 FB5 TEC TEH TEC TEH TEC TEH TEC TEH FB6 FB6 FB4 FB4 TEC TEH TEC TEH TEC TEH FB5 FB5 TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH FB4 FB4 TEC TEH TEC TEH TEC TEH FB5 FB5 FB4 FB4 TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH FB7 FB7 TEC TEH TEC TEH TEC TEH TEC TEH UTIL 1
UTIL 2
CAL #
501 801 0.28 0.30 801 WAR 502 LAR IDOK 800 LAR 8
0.42 0.24 8
0.35 0.16 8
0.28 0.35 8
0.35 0.27 8
WAR 507 WAR 11 WAR 536 WAR 11 WAR 11 WAR 525 WAR 505 WAR 508 WAR 537 WAR 11 WAR 11 WAR 530 WAR 519 WAR 519 WAR 11 WAR 519 WAR 520 WAR 518 WAR 519 WAR 518 WAR 11 WAR 528 WAR 519 WAR 518 WAR 11 WAR 11 WAR 526 WAR 526 WAR 512 WAR 518 WAR 518 WAR 518 WAR 11 WAR 530 WAR 518 WAR 514 WAR 514 LEG COLD COLD COLD HOT COLD HOT HOT COLD HOT HOT COLD HOT HOT HOT COLD HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT HOT PROBE 560UL 560XP 560XP 560UL 560XP 560XP 560XP 560XP 560XP 560XP 560XP 560XP 560XP 560UL 560XP 560XP 560XP 560UL 560XP 560UL 560XP 560XP 560UL 560UL 560UL 560UL 560XP 560XP 560UL 56OUL 560UL 560XP 560UL 560UL 560UL 560UL 56OUL 560XP 560UL 56OUL 560UL 560XP 560XP 560UL 560UL 560UL 560UL 56OUL 560UL 560XP 56OUL 560UL 560UL 56OUL SCOPE Bobbin Exam Special Interest E
Special Interest E
Bobbin Exam Post SSI LP Boundi TTS Exam TTS Exam Post SSI LP Boundi TTS Exam TTS Exam Post SSI LP Boundi TTS Exam TTS Exam Bobbin Exam Post SSI LP Boundi TTS Exam TTS Exam Bobbin Exam Special Interest E Bobbin Exam Special Interest E Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam Special Interest E Bobbin Exam Bobbin Exam Bobbin Exam Bobbin Exam
AREVA NP Inc Customer Name: McGuire - Unit 1 Replacement 01/22/09 02:32:36 Component: S/G D Page 2 of 2 QUERY: QueryMl ROW COL VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1
UTIL 2
CAL # LEG PROBE SCOPE Total Tubes
- 30 Total Records: 54