From:
Ed Miller Sent:
Tuesday, October 28, 2008 1:16 PM To:
'michael_okeefe@fpl.com' Cc:
'gary_kilby@fpl.com'
Subject:
Acceptance Review for Alternate Depth Sizing Qualification (MD9785)
Mike, The following are the draft versions of the information insufficiencies to be discussed during a conference call on October 30, 2008. They are being provided in advance so that you can ensure that the appropriate technical staff are included in the call.
1.) The root-mean-square error (RMSE) values proposed greatly exceed the precedence provided in the submittal and the submittal does not provide an appropriate justification for the large RMSE values.
2.) The submittal does not provide a description of the surface condition at each subject weld.
3.) The submittal does not provide a discussion of the bounding surface conditions where the vendor could demonstrate appropriate, ASME Code required, RMSE value results.
4.) The submittal does not provide a discussion on planned activities to create an inspectable surface condition conducive to the vendors capabilities.
Please contact me if you have any questions prior to the call.
G. Edward Miller Project Manager Plant Licensing Branch I-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation E-mail Properties Mail Envelope Properties ()
Subject:
Acceptance Review for Alternate Depth Sizing Qualification (MD9785)
Sent Date: 10/27/2008 3:47:03 PM Received Date: 10/28/2008 1:15:00 PM From: Ed Miller Created By: Ed.Miller@nrc.gov Recipients:
michael_okeefe@fpl.com ('michael_okeefe@fpl.com')
Tracking Status: None gary_kilby@fpl.com ('gary_kilby@fpl.com')
Tracking Status: None
Post Office:
Files Size Date & Time MESSAGE 10002 10/27/2008 Options Expiration Date:
Priority: olImportanceNormal ReplyRequested: False Return Notification: False Sensitivity: olNormal Recipients received: