EOC-24 Refueling Outage, Steam Generator Inservice Inspection Report
ML082490276
Person / Time
Site: Oconee 
Issue date: 08/28/2008
From: Baxter D
Duke Energy Carolinas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
EOC-24, IWA-6230, IWA-6240
Download: ML082490276 (178)


Text

Duke DAVE BAXTER Vice President

Energy, Oconee Nuclear Station Duke Energy Corporation ON01 VP17800 Rochester Highway Seneca, SC 29672 864-885-4460 864-885-4208 fax August 28, 2008 dabaxter@dukeenergy.com U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555

Subject:

Duke Energy Carolinas, LLC Oconee Nuclear Station, Unit 1 Docket No. 50-269 Unit 1 EOC-24 Refueling Outage, Steam Generator Inservice Inspection Report Per American Society of Mechanical Engineers Boiler and Pressure Vessel Code,Section XI, Subsubarticles IWA-6230 and IWA-6240, attached for your review is a summary report specific to the Steam Generator Tube Inservice Inspection activities conducted during Unit 1 EOC-24 Refueling Outage.

The Oconee Nuclear Station Technical Specification (TS) 5.5.10 establishes the Steam Generator (SG) tube surveillance program requirements for SGs. TS 5.6.8 requires the results of a SG Tube Inservice Inspection be reported to the NRC within 180 days following completion of the inspection. This report is included within the SG Tube Inservice Inspection summary report as an attachment to Form NIS-1.

An additional summary report which documents the remaining portions of the Unit 1 EOC-24 Refueling Outage Inservice Inspection will be transmitted separately.

Please address any questions to Corey A. Gray at 864-886-6325.

Sincerely, Dave Baxter, Site Vice President, Oconee Nuclear Station Attachment www. duke-energy. com

Nuclear Regulatory Commission August 28, 2008 Page 2 xc w/att:

Luis Reyes Region II Administrator U.S. Nuclear Regulatory Commission Atlanta Federal Center 61 Forsyth St., SWW, Suite 23T85 Atlanta, GA 30303 Leonard Olshan, Project Manager, Section.1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, DC 20555-0001 xc(w/o attch):

Andy Hutto Senior NRC Resident Inspector Oconee Nuclear Station Susan Jenkins, Section Manager, Division of Waste Management Bureau of Land and Waste Management SC Dept. of Health & Environmental Control 2600 Bull St.

Columbia, SC 29201

Steam Generator In-service Inspection Summary Report Oconee Nuclear Station Unit 1 EOC 24 Spring Outage 2008 Location: 7800 Rochester Highway, Seneca, South Carolina 29672 NRC Docket No. 50-269 National Board No. N/A Commercial Service Date: July 15, 1973 Owner: Duke Energy Carolinas, LLC 526 South Church St.

Charlotte, N.C. 28202 9

Revision 0 Prepared By:

Checked By:

Approved By:

LIZ A 6ti. 1)6 Date:

Date: i0Ls*LDL Date: 7 Document Completion Date:

O, L.

/-7&f,7w

/ C

-/

FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules

1. Owner: Duke Energy Carolinas, LLC, 526 S. Church St. Charlotte, NC 28202 (Name and Address of Owner)
2.

Plant:

Oconee Nuclear Station, 7800 Rochester Highway, Seneca, SC 29672 (Name and Address of Plant) 3.

4.

5.

6.

7.

Plant Unit:

1 Owner Certificate of Authorization (if required)

Commercial Service Date: July 15, 1973 National Board Number for Unit N/A Components Inspected:

N/A Component Steam Generator IA Steam Generator 1B Manufacturer Babcock & Wilcox-Canada Babcock & Wilcox-Canada Manufacturer Serial No.

006K01 006K02 State or Province No.

N/A N/A National Board No.

205 206 Note:

Supplemental sheets in form of lists, sketches, or drawings may be used provided (1) size is 81/2 in.

x 11 in., (2) information in items I through 6 on this data report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

FORM NIS-1 (Back)

8.

Examination Dates:

December 15, 2006 To June 1,2008

9.

Inspection Period Identification:

10.

Inspection Interval Identification:

11.

Applicable Edition of Section XI:

12.

Date/Revision of Inspection Plan:

Second Period Fourth Interval 1998 Addenda 2000 March 18, 2008 revision 01

13.

Abstract of Examinations and Test. Reference attached response to technical specification 5.6.8, Steam Generator Tube Inspection Report.

14.

Abstract of Results of Examination and Tests. Reference attached response to technical specification 5.6.8, Steam Generator Tube Inspection Report.

15.

Abstract of Corrective Measures. Reference attached response to technical specification 5.6.8, Steam Generator Tube Inspection Report.

We certify that a) the statements made in this report are correct b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. (if applicable)

Date.

)

20 08 Signed N/A Duke Energy Carolinas, LLC I

Owner Expiration Date N/A 3 y

)f,1-JZaW

-- 77-7ý CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Province of North Carolina employed by *The HSB CT., have inspected the components described in this Owner's Report during the period

/Z1 -/,S- - O L.

to

/-

, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in the Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, test, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection Commissions

$'IZ f-J/,4 L--

Inspector's Signature Date 20o8

  • The Hartford Steam Boiler of Connecticut 200 Ashford Center North Suite 205 Atlai National Board, State, Province, and Endorsements mta, GA. 30338

Attachment to Form NIS-1 Oconee 1 EOC 24 Steam Generator Tube Inspection Report Pursuant to Oconee technical specification 5.6.8 the following information is provided:

a. The scope of inspections performed on each SG The scope of the inspection performed on both ]A & 1B Steam Generators included 100% of the active tubes in each ROTSG composing of approximately 50% of the tubes each with the bobbin and x-probe. Special Interest was also performed on selected indications.
b. Active degradation mechanisms found Tube support plate wear is the only active degradation mechanism found.
c.

Non-destructive examination techniques utilized for each degradation mechanism The Non-destructive examination techniques utilized bobbin coil for the detection of tube support plate wear. The array probe was utilized to characterize selected wear indications.

d.

Location, orientation (if linear), and measured sizes (if available) of service induced indications The complete listing for service induced indications is attached.

e.

Number of tubes plugged during the inspection outage for each active degradation mechanism Twelve tubes were plugged in ]A ROTSG and nine tubes were plugged in 1B ROTSG, allfor tube support plate wear; no other tubes were plugged.

f. The total number and percentage of tubes plugged to date There are sixty-three tubes (0. 40 %) in the JA ROTSG plugged to date and forty-seven tubes (0.30%) plugged in 1B ROTSG.
g.

The results of condition monitoring, including the results of tube pulls and in-situ pressure testing Condition Monitoring was demonstrated. An NDE maximum depth call of 73%TW or less is sufficient to demonstrate a minimum degraded tube burst pressure of 3AP, 4050psi, at 0.95probability with 50% confidence. The worst case depth call observed during the Oconee 1EOC24 inspection was an NDE depth of 47% TW.

Thus, condition monitoring structural integrity was demonstrated. Therefore no in situ pressure testing was required. No tube pulls were performed.

h.

The effective plugging percentage for all plugging in each SG The effective plugging percentage'is 0. 40 % in the ]A ROTSG and 0. 30 % in the lB ROTSG.

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:18 AM Component: S/G A Page 1 of 97 ONSlAR-EOC24 Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 1

3 0.20 0.14 1

5 0.22 0.20 1

11 0.21 0.53 0.14 1

13 0.17 1

14 0.30 0.25 1

15 0.19 0.13 0.26 0.43 0.15 1

16 0.18 0.08 0.43 2

5 0.37 0.13 2

6 0.11 2

11 0.11 0.09 2

12 0.12 2

15 0.14 2

18 0.15.

2 20 0.22 0.20 2

21 0.24 2

22 0.12 0.14 2

27 0.10 3

6 0.10 3

7 0.11 3

13 0.21 3

15 0.10 3

17 0.10 3

18 0.10 3

19 0.20 3

20 0.18 3

22 0.24 3

23 0.20 3

24 0.16 0.18 0.15 3

25 0.31 3

26 0.16 0.21 3

27 0.09 3

30 0.23 3

32 0.18 4

10 0.27 0.13 0.08 4

16 0.11 0.26 4

17 0.19 4

18 0.17 4

19 0.13 0.26 0.10 4

20 0.11 4

21 0.13 0.11 0.11 4

22 0.24 0.18 4

23 0.23 0.13 0.11 4

24 0.11 4

25 0.17 0.17 4

26 0.25 4

27 0.14 0.12 4

28 0.10 0.16 4

29 0.21 0.20 DEG 133 143 133 147 143 132 142 156 113 127 146 145 144 131 119 153 144 145 135 140 132 146 88 131 139 130 141 142 133 124 137 154 126 141 133 138 122 114 134 145 149 107 148 147 147 141 155 149 57 154 124 134 152 129 143 131 139 147 134 129 127 149 148 140 151 149 141 134 146 143 124 130 140 137 142 144 144 141 144 157 CHN IND %TW LOCATION P2 TWD 11 011

-0.29 P2 TWD 8 011

+0.34 P2 TWD 12 011

-0.31 P2 TWD 11 011

+0.36 P2 TWD 12 010

-0.34 P2 TWD 24 011

-0.34 P2 TWD 8 011

+0.37 P2 TWD 10 011

-0.34 P2 TWD 15 010

+0.65 P2 TWD 13 011

-0.29 P2 TWD 11 009

+0.60 P2 TWD 8 010

-0.38 P2 TWD 14 011

-0.32 P2 TWD 21 011

+0.36 P2 TWD 9 010

+0.74 P2 TWD 10 011

-0.32 P2 TWD 5 012

-0.34 P2 TWD 21 015

+0.56 P2 TWD 19 011

-0.34 P2 TWD 8 011

+0.37 P2 TWD 7 011

-0.29 P2 TWD 7 010

+0.46 P2 TWD 6 010

-0.38 P2 TWD 7 010

-0.34 P2 TWD 8 010

-0.36 P2 TWD 8 010

-0.39 P2 TWD 11 010

-0.36 P2 TWD 11 011

+0.36 P2 TWD 13 011

+0.36 P2 TWD 7 010

-0.36 P2 TWD 8 011

+0.36 P2 TWO 6 010

-0.43 P2 TWD 6 011

-0.34 P2 TWD 7 011

-0.32 P2 TWD 12 011

+0.36 P2 TWD 6 011

+0.32 P2 TWD 6 010

-0.39 P2 TWD 6 010

+0.44 P2 TWD 11 011

+0.32 P2 TWD 10 011

+0.34 P2 TWD 14 011

+0.34 P2 TWD 10 010

+0.65 P2 TWD 9 010

-0.41 P2 TWD 10 011

-0.34 P2 TWD 9 011

+0.34 P2 TWD 15 011

-0.36 P2 TWD 10 011

-0.39 P2 TWD 12 011

+0.36 P2 TWD 5 010

+0.65 P2 TWD 13 011

-0.36 P2 TWD 10 010

+0.67 P2 TWD 15 011

-0.31 P2 TWD 8 011

+0.34 P2 TWD 5 012

-0.34 P2 TWD 7 010

-0.38 P2 TWD 14 013

+0.34 P2 TWD 11 011

+0.32 P2 TWD 10 013

-0.41 P2 TWD 8 011

-0.36 P2 TWD 14 011

+0.34 P2 TWO 6 009

-0.41 P2 TWD 7 010

-0.39 P2 TWD 7 010

-0.37 P2 TWD 6 011

-0.39 P2 TWD 6 011

+0.32 P2 TWD 13 010

-0.38 P2 TWD 10 011

+0.32 P2 TWD 13 010

-0.41 P2 TWD 7 011

-0.39 P2 TWD 7 011

+0.34 P2 TWD 6 010

-0.39 P2 TWD 10 010

-0.46 P2 TWD 10 011

+0.31 P2 TWD 13 010

-0.39 P2 TWO 8 010

-0.46 P2 TWD 7 011

+0.34 P2 TWD 6 010

-0.37 P2 TWD 9 011

+0.34 P2 TWD 12 010

-0.46 P2 TWD 11 011

-0.36 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1 UTIL 2

WAR WAR WAR WAR WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR 2

WAR 4

WAR 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR 5

WAR WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR CAL #

44 44 44 44 44 44 44 60 58 58 60 60 60 60 60 60 60 60 44 44 44 44 44 44 44 58 58 58 60 58 58 60 44 44 44 44 44 44 44 44 60 58 60 60 60 58 60 60 116 60 60 44 44 44 44 44 44 44 44 44 44 44 44 44 44 44 44 44 44 44 58 60 60 58 60 60 58 58 60 60 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:18 AM Component: S/G A Page 2 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 0.07 4

30 0.19 4

31 0.48 4

33 0.16 4

36 0.20 0.13 4

39 0.08 5

3 0.12 5

17 0.49 0.13 0.21 5

20 0.11 5

22 0.22 5

23 0.13 0.15 5

24 0.12 0.20 0.62 5

25 0.14 5

26 0.14 0.28 0.13 5

27 0.20 5

28 0.17 5

29 0.22 0.22 5

30 0.19 0.49 0.37 0.15 5

31 0.43 0.31 0.14 5

32 0.15 0.14 0.20 5

33 0.18 0.18 0.11 5

35 0.12 5

36 0.22 0.26 5

37 0.27 0.09 5

38 0.18 0.15 5

39 0.17 0.12 5

45 0.14 5

46 0.19 6

2 0.10 6

10 0.10 6

16 0.41 0.23 0.33 0.12 6

17 0.11 6

18 0.29 0.08 0.14 6

19 0.11 0.12 0.15 0.34 6

20 0.19 6

21 0.16 6

22 0.11 0.38 0.08 6

23 0.10 0.28 6

24 0.08 6

27 0.49 6

28 0.15 0.16 0.10 6

29 0.16 6

30 0.14 0.25 6

31 0.23 DEG CHN 155 P2 144 P2 139 P2 139 P2 120 P2.

154 P2 74 P2 66 P2 136 P2 148 P2 145 P2 148 P2 146 P2 140 P2 145 P2 140 P2

.138 P2 133 P2 143 P2 152 P2 "145 P2 151 P2 141 P2 151 P2 123 P2 143 P2 143 P2 141 P2 143 P2 142 P2 124 P2 144 P2 141 P2 145 P2 152 P2 139 P2 154 P2 136 P2 154 P2 144 P2 144 P2 150 P2 147 P2 157 P2 143 P2 152 P2 147 P2 133 P2 145 P2 146 P2 133 P2 145 P2 133 P2 151 P2 138 P2 119 P2 152 P2 131 P2 129 P2 143 P2 142 P2 146 P2 141 P2 143 P2 133 P2 139 P2 148 P2 136 P2 137 P2 150 P2 139 P2 146 P2 138 P2 145 P2 143 P2 147 P2 150 P2 149 P2 140 P2 147 P2 IND %TW TWD 4 TWD 10 TWD 23 TWD 10 TWD 11 TWO 7 TWD 5 TWD 7 TWD 22 TWD 7 TWD 11 TWD 6 TWD 12 TWD 7 TWD. 8 TWD 7 TWD 11 TWD 27 TWD 8 TWD 8 TWD 15 TWD 8 TWD 11 TWD 10 TWD 11 TWD 12 TWD 11 TWD 23 TWD 19 TWD 9 TWD 20 TWD 15 TWD 8

TWD 9 TWD 9 TWD 11 TWD 10 TWD 10 TWD 6

TWO 7 TWD 13 TWD 14 TWD 14 TWD 5

TWD 10 TWD 9 TWD 9 TWD 7 TWD 8 TWD 11 TWD 6 TWD 6 TWD 20 TWD 13 TWD 17 TWD 7 TWD 6 TWD 15 TWD 5 TWD 8 TWD 6 TWD 7 TWD 8 TWD 17 TWD 11 TWD 9 TWD 6 TWD 19 TWD 5 TWD 5 TWD 14 TWD 5 TWD 22 TWD 9 TWD 9 TWD 6 TWD 9 TWD 8 TWD 14 TWD 12 LOCATION 011

+0.31 011

+0.34 010

-0.43 009

+0.60 010

-0.39 011

+0.37 010

+0.69 010

+0.63 011

+0.34 012

-0.39 012

+0.32 013

-0.44 012

+0.29 010

-0.39 013

-0.41 009

-0.45 010

-0.41 012

-0.44 010

-0.41 009

-0.45 011

-0.36 013

-0.43 011

+0.32 011

-0.39 010

-0.42 011

-0.39 010

-0.46 011

-0.39 012

-0.41 009

+0.55 010

-0.39 011

-0.39 011

+0.34 010

-0.44 011

-0.36 011

+0.34 011

-0.39 011

+0.32 013

+0.29 011

-0.29 010

-0.43 011

-0.36 010

-0.41 011

-0.36 010

-0.43 011

+0.34 011

-0.36 010

-0.36 013

+0.32 011

-0.36 011

-0.32 008

+0.34 010

-0.39 011

+0.32 012

-0.41 011

-0.37 010

-0.41 010

-0.41 011

-0.36 012

-0.41 008

+0.29 009

-0.41 010

-0.41 013

-0.44 011

-0.41 009

+0.60 009

-0.46 011

-0.36 008

-0.38 012

-0.44 013

-0.41 012

-0.44 012

+0.29 009

+0.58 011

-0.36 012

+0.31 009

+0.58 009

+0.60 012

+0.29 011

-0.39 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

60 58 60 60 58 0

58 60 5

46 46

.46 46 44 44 46 46 44 44 44 46 44 44 44 58 4

60 58 58 60 60 60 60 58 58 58 60 60 60 58 58 58 58 60 60 58 58 60 5

60 58 6

58 58 60 3

44 98 44 44 44 5

44 46 98 98 5

98 46 46 46 46 44 46 44 44 4

44 46 46 1

44 46 44 44 4

44 8

58 60 60 58 LEG PROBE INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET

'510XB INLET 510XB INLET 510XB INLET 510XB INLET.

510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:45:18 Am Component:

S/G A Page 3 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l1 Support Wear ROW TUBE VOLTS 6

32 0.10 0.15 0.08 6

33 0.16 0.50 0.20 6

34 0.51 0.15 0.10 0.17 6

37 0.13 0.35 6

38 0.13 6

39 0.13 0.07 6

40 0.28 6

42 0.11 6

44 0.09 6

46 0.12 6

49 0.42 0.13 6

51 0.14 0.34 0.14 7

11 0.09 7

17 0.18 0.12 0.07 7

18 0.11 7

19 0.08 0.21 0.19 7

20 0.21 0.19 0.68 0.21 7

21 0.35 0.09 7

22 0.11 0.14 0.28 7

24 0.48 7

25 0.09 7

26 0.14 0.11 0.11 0.10 7

27 0.17 0.11 0.20 7

"28 0.16 7

29 0.14 7

32 0.46 0.25 0.13 7

33 0.26 0.17 0.11 7

34 0.25 7

35 0.22 0.20 0.18 0.35 0.14 7

36 0.73 0.34 0.16 7

39 0.13 0.10 7

40 0.08 7

41 0.33 0.12 0.10 7

42 0.14 7

45 0.23 7

46 0.08 7

47 0.32 7

48 0.30 7

52 0.13 8

2 0.47 DEG 158 149 119 146 141 129 136 154 149 139 150 135 150 157 158 136 129 118 150 148 148 141 140 146 137 149 153 151 147 144 139 147 136 141 133 150 139 152 150 138 140 135 152 147 144 147 123 142 149 149 141 147 112 140 152 149 147 138 145 145 139 151 131 150 135 148 115 139 148 146 128 137 130 149 148 112 135 145 149 126 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2.

P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P3 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 6 TWD 9 TWD 5 TWD 9 TWD 22 TWD 11 TWD 23 TWD 9 TWD 6 TWD 10 TWD 7 TWD 17 TWD 7 TWD 8 TWD 4 TWD 14 TWD 6 TWD 5 TWO 7 TWD 21 TWD 8 TWD 9 TWD 17 TWD 9 TWD 5 TWD 10 TWDO7 TWD 4 TWD 6 TWD 5 TWD 11 TWO 10 TWD 12 TWD 11 TWD 28 TWD 12 TWD 17 TWD 5 TWD 7 TWO 8 TWD 15 TWD 22 TWD 5 TWD 8 TWD 7 TWD 7 TWD 6 TWD 9 TWD 6 TWD 11 TWD 9 TWD 8 TWD 22 TWD 14 TWD 8 TWD 13 TWD 9 TWD 6 TWD 14 TWD 11 TWD 11 TWD 10 TWD 17 TWD 8 TWD 30 TWD 17 TWD 9 TWD 7 TWD 6 TWD 5 TWD 16 TWD 7 TWD 6 TWD 9 TWD 12 TWD 5 TWD 16 TWD 16 TWD 8 TWD 22 LOCATION 010

-0.53 011

-0.44 011

+0.29 010

-0.44 011

-0.41 011

+0.32 010

-0.49 011

-0.41 011

+0.31 009

+0.55 010

-0.41 011

+0.32 011

+0.34 010

-0.45 011

+0.26 010

-0.41 010

-0.39 010

+0.63 011

-0.34 011

-0.36 011

+0.34 010

-0.41 015

+0.56 014

+0.34 011

-0.32 010

-0.41 012

-0.41 011

-0.44 010

-0.44 010

-0.43 011

-0.41 012

-0.41 009

+0.58 Ol

-0.39 012

-0.41 012

+0.29 012

+0.32 011

-0.41 010

-0.41 011

-0.41 012

-0.41 012

-0.44 011

-0.41 011

-0.41 012

-0.41 013

-0.44 013

+0.27 009

+0.58 012

-0.46 012

+0.29 011

-0.39 011

-0.44 009

-0.48 010

+0.68 011

-0.41 009

+0.58 011

-0.41 012

-0.44 011

-0.44 009

-0.43 009

+0.58 011

-0.39 012

-0.46 014

-0.46 010

-0.48 011

-0.41 009

+0.60 010

-0.39 011

+0.32 010

-0.46 010

-0.42 011

+0.29 010

+0.41 010

-0.49 011

-0.36 011

+0.31 011

-0.39 011

-0.39 011

-0.36 011

-0.32 EXT EXT LTE UTE.

LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

60 60 60 58 58 58 60 60 60 60 58 58 58 60 60 58 58 58 58 60 60 60 60 60 46 46 46 46 44 46 46 46 44 44 44 44 46 4

46 44 44 44 44 46 44 44 44 44 46 46 46 44 46 60 60 60 58 58 58 60 58 58 58 58 4

58 60 60 60 58 58 60 58 58 0

58 60 58 60 58 60 60 44 LEG PROBE INLET 51OXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:18 AM Component: S/G A Page 4 of 97 ONSIAR-EOC24 Tube Support Wear QUERY: QueryMi[l]

ROW TUBE VOLTS 0.25 0.16 8

3 0.16 8

5 0.13 0.13 8

12 0.21 0.21 0.79 8

14 0.11 8

15 0.10 8

16 0.22 8

17 0.26 8

18 0.33 0.18 8

19 0.29 0.10 8

20 0.15 0.30 0.11 8

21 0.11 0.09 0.53 8

22 0.11 8

26 0.35 0.18 0.15 0.10 8

29 0.16 8

34 0.15 0.31 8

35 0.20 8

36 0.21 0.26 0.14 8

37 0.33 0.18 0.09 8

38 0.20 0.11 0.32 0.08 0.10 1.28 1.65 8

42 0.73 8

.43 0.13 0.19 8

44 0.21 8

45 0.18 8

46 0.25 8

48 0.11 8

50 0.66 8

52 0.26 8

53 0.14 0.06 0.06 9

13 0.14 9

15 0.24 0.10 0.14 9

16 0..20 9

17 0.24 9

18 0.16 0.70 0.29 0.19 9

19 0.12 0.11 0.28 0.45 0.12 0.16 9

20 0.28 0.91 0.12 0.26 9

21 0.22 0.27 0.18 0.28 DEG 128 139 110 135 43 145 142 132 148 126 129 146 142 134 137 159 142 139 151 130 125 132 131 141 147 149 152 142 142 145 152 145 152 150 143 143 157 149 141 145 144 117 129 123 130 147 150 139 144 135 138 133 143 146 149 160 94 139 143 144 142 144 142 134 145 129 140 141 143 139 141 115 145 132 150 152 137 131 147 132 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P3 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 14 TWD 9 TWD 9 TWD 8 TWO 8 TWD 12 TWD 12 TWD 31 TWD 7 TWD 6 TWD 12 TWD 14 TWD 17 TWD 10 TWO 15 TWD 6 TWO 9 TWD 16 TWD 7 TWD 7 TWD 6 TWD 24 TWD 7 TWD 17 TWO 10 TWD 8

TWD 6 TWD 9 TWD 9 TWO 16 TWD 10 TWD 12 TWD 14 TWD 8 TWD 16 TWD 10 TWD 5 TWD 11 TWD 7 TWD 17 TWD 5 TWD 6 TWD 40 PID TWD 28 TWD 8 TWD 11 TWO 11 TWO 11 TWO 13 TWD 6 TWD 26 TWD 13 TWD 9 TWD 4 TWD 4 TWO 8 TWD 12 TWD 5 TWD 8 TWD 11 TWD 12 TWD 9 TWD 29 TWD 15 TWO 11 TWD 7 TWO 6 TWD 14 TWD 21 TWD 7 TWO 9 TWO 15 TWO 33 TWO 7 TWD 14 TWD 12 TWD 14 TWD 10 TWD 14 LOCATION 012

-0.34 011

+0.34 010

+0.65 013

+0.34 010

+0.71 010

-0.41 011

-0.37 011

+0.34 010

-0.39 010

-0.42 010

-0.40 010

-0.42 010

-0.44 014

+0.29 010

-0.42 011

-0.41 008

+0.29 009

-0.46 011

-0.44 008

-0.43 008

+0.31 009

-0.46 008

-0.43 009

+0.55 011

-0.44 013

-0.51 011

+0.29 013

+0.32 009

+0.60 012

-0.48 009

+0.58 009

+0.60 011

-0;46 012

-0.48 009

+0.58 010

-0.44 013

-0.46 009

-0.43 009

+0.60 011

-0.44 011

+0.29 010

+0.68 010

-0.50 010

-0.50 010

-0.42 010

-0.49 014

-0.48 010

-0.42 010

-0.49 010

-0.41 010

-0.39 010

-0.39 010

-0.41 010

-0.46 011

+0.29 014

+0.61 010

+0.63 013

-0.44 013

+0.29 014

-0.46 010

-0.39 013

-0.46 010

-0.39 011

+0.29 012

-0.41 010

+0.61 010

-0.47 011

+0.29 012

-0.46 012

+0.27 009

-0.10 010

+0.61 010

-0.41 011

+0.29 012

-0.44 010

+0.61 009

+0.58 010

-0.44 011

-0.44 011

+0.27 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE -UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

44 5

44 40 40 40 40 40 40 44 3

44 44 44 44 44 44 5

44 44 44 44 44 44 44 44 46 46 46 4

46 44 60 60 58 60 60 60 58 58 58 60 60 60 60 60 LAR 60 116 58 60 60 58 60 58 58 58 58

.60 60 60 42 42 42 42 40 42 40 40 40 10 40 42 42 42 42 6

42 9

42 40 40 40 12 40 42 42 42 42 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:45:18 AM Component: S/G A Page 5 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl(l]

ROW TUBE VOLTS 0.68 0.36 0.06 0.12 9

23 0.26 9

24 0.09 9

25 0.09 0.30 0.10 0.28 9

26 0.20 9

27 0.14 9

29 0.25 0.08 0.11 9

30 0.17 9

33 0.07 0.19 9

34 0.14 9

35 0.34 9

37 0.11 9

38 0.10 0.15 9

39 0.20 0.43 0.29 9

40

.0.15 0.50 0.20 0.09 0.10 9

42 0.11 0.13 9

44 0.34 0.13 9

45 0.14 0.33 9

46 0.11 9

47 0.19 9

48 0.47 0.14 9

49 0.67 9

50 0.16 0.21 0.11 9

52 0.23 9

54 0.29 0.14 9

57 0.29 10 2

0.08 10 7,

0.09 10 12 0.11 10 14 0.09 0.20 0.12 0.06 0.18 10 i

0.13 0.13 0.67 0.36 10 16 0.10 0.30 10 17 0.19 0.13 10 18 0.21 10 19 0.30 0.15 0.82 0.28 0.19 10 20 0.11 0.20 0.27 0.07 10 21 0.15 0.32 0.14 10 22 0.13 0.13 DEG CHN IND %TW 141 P2 TWD 27 137 P2 TWD 17 153 P2 TWD 4 127 P2 TWD 7 142 P2 TWD 13 113 P2 TWD 5 147 P2 TWD 5 143 P2 TWD 15 144 P2 TWD 6 138 P2 TWD 14 152 P2 TWD 11 148 P2 TWD 8 146 P2 TWD 13 142 P2 TWD 5 142 P2 TWD 6 145 P2 TWD 10 146 P2 TWD 4 138 P2 TWD 10 144 P2 TWD 8 142 P2 TWD 16 161 P2 TWD 6 127 P2 TWD 6 154 P2 TWD 9 143 P2 TWD 11 136 P2 TWD 20 134 P2 TWD 14 144 P2 TWD 9 142 P2 TWD 23 154 P2 TWD 11 152 P2 TWD 6 153 P2 TWD 6 150 P2 TWD 6 141 P2 TWD 7 135 P2 TWD 16 144 P2 TWO 7 137 P2 TWD 8 138 P2 TWD 17 145 P2 TWD 6 146 P2 TWD 11 132 P2 TWD 21 147 P2 TWD 8 135 P2 TWD 28 146 P2 TWD 9 146 P2 TWD 11 150 P2 TWD 6 152 P2 TWD 12 136 P2 TWD 14 160 P2 TWD 8 130 P2 TWD 15 120 P2 TWD 5 128 P2 TWD 6 137 P2 TWD 6 150 P2 TWD 5 144 P2 TWO 11 147 P2 TWD 7 138 P2 TWD 4 129 P2 TWD 10 134 P2 TWD 8 149 P2 TWD 8 135 P2 TWD 28 148 P2 TWD 18 157 P2 TWD 6 142 P2 TWO 15 152 P2 TWD 11 153 P2 TWD 8 140 P2 TWD 11 146 P2 TWD 16 156 P2 TWD 9 130 P2 TWD 32 145 P2 TWD 15 151 P2 TWD 11 138 P2 TWD 6 139 P2 TWD 11 149 P2 TWO 14 152 P2 TWD 4 141 P2 TWD 9 137 P2 TWD 16 146 P2 TWD 8 150 P2 TWD 7 145 P2 TWD 7 LOCATION EXT EXT 012

-0.46 LTE UTE 012

+0.29 LTE UTE 008

+0.27 LTE UTE 010

+0.61 LTE UTE 012

+0.27 LTE UTE 012

+0.27 LTE UTE 008

+0.24 LTE UTE 011

-0.44 LTE UTE 011

+0.27 LTE UTE 013

+0.27 LTE UTE 009

+0.58 LTE UTE 009

+0.58 LTE UTE 009

+0.58 LTE UTE 011

-0.46 LTE UTE 013

+0.27 LTE UTE 013

+0.24 LTE UTE 013

+0.24 LTE UTE 009

+0.58 LTE UTE 013

+0.24 LTE UTE 011

+0.27 LTE UTE 011

-0.44 LTE UTE 008

+0.24 LTE UTE 013

-0.51 LTE UTE 009

-0.48 LTE UTE 011

-0.44 LTE UTE 012

-0.46 LTE UTE 009

+0.60 LTE UTE 010

-0.55 LTE UTE 011

-0.44 LTE UTE 011

+0.26 LTE UTE 008

-0.45 LTE UTE 009

+0.63 LTE UTE 010

-0.46 LTE UTE 010

-0.47 LTE UTE 011

+0.29 LTE UTE 009

+0.60 LTE UTE 010

-0.53 LTE UTE 011

-0.36 LTE UTE 009

-0.48 LTE UTE 010

-0.44 LTE UTE 014

-0.49 LTE UTE 010

-0.49 LTE UTE 010

-0.42 LTE UTE 011

-0.39 LTE UTE 014

+0.24 LTE UTE 010

-0.41 LTE UTE 010

-0.41 LTE UTE 011

-0.39 LTE UTE 010

-0.38 LTE UTE 009

-0.44 LTE UTE 012

-0.39 LTE UTE 011

-0.39 LTE UTE 011

+0.32 LTE UTE 013

-0.46 LTE UTE 013

+0.32 LTE UTE 009

-0.46 LTE UTE 010

+0.63 LTE UTE 009

-0.46 LTE UTE 011

-0.39 LTE UTE 011

+0.34 LTE UTE 012

-0.46 LTE UTE 011

-- 0.44 LTE UTE 013

+0.29 LTE UTE 009

-0.46 LTE UTE 011

+0.32 LTE UTE 010

-0.44 LTE UTE 010

-0.43 LTE UTE 011

-0.44 LTE UTE 011

+0.32 LTE UTE 012

-0.46 LTE UTE 013

-0.46 LTE UTE 009

-0.46 LTE UTE 011

+0.29 LTE UTE 013

-0.49 LTE UTE 013

+0.29 LTE UTE 009

-0.48 LTE UTE 011

+0.29 LTE UTE 013

-0.51 LTE UTE 009

-0.48 LTE UTE 011

-0.49 LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

42 42 42 4

42 42 40 42 42 42 42 7

40 7

42 42 42 42 40 42 7

42 40 58 58 60 60 58 58 58 60 60 60 60 60 58 58 58 58 60 60 58 60 58 58 60 58 58 58 58 58 58 116 42 40 42 42 42 42 42 10 42 40 40 40 40 42 42 40 40 42 40 40 40 40 40 42 42 42 42 40 40 40 42 42 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:19 AM Component:

S/G A Page 6 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 0.34 0.48 0.31 0.08 0.34 10 23 0.11 0.51 0.41 10 24 0.20 10 25 0.15 10 27 0.38 10 28 0.23 0.14 0.12 10 30 0.18 10 31 0.13 10 34 0.17 0.10 10 37 0.20 10 39 0.18 10 40 0.11 0.32 0.10 0.08 10 41 0.11 0.35 0.37 0.14 0.32 0.17 0.21 10 42 0.11 10 43 0.13 0.99 10 44 0.17 0.99 0.35 0.23 0.15 0.08 10 45 0.39 0.18 0.09 0.38 10 46 0.09 0.42 0.09 0.16 0.14 10 47 0.16 0.16 0.09 0.18 10 49 0.13 10 50 0.10 0.28 0.82 0.33 10 51 1.01 0.49 0.12 10 54 0.10 0.11 0.16 10 55 0.61 10 57 0.13 0.16 10 58 0.34 10 61 0.18 11 8

0.07 11 10 0.14 0.17 0.22 0.31 0.24 11 12 0.18 11 13 0.20 11 14 0.08 11 15 0.22 11 16 0.16 DEG CHN 142 P2 135 P2 143 P2 157 P2

.136 P2 147 P2 133 P2 140 P2 148 P2 148 P2 147 P2 146 P2 139 P2

.157 P2 148 P2 145 P2 151 P2 135 P2 147 P2 123 P2 149 P2 141 P2 151 P2 148 P2 146 P2 145 P2 137 P2 146 P2 148 P2 153 P2 148 P2 149 P2 151 P2 130 P2 129 P2 124 P2 140 P2 143 P2 122 P2 159 P2 139 P2 144 P2 148 P2 137 P2 145 P2 134 P2 157 P2 137 P2 146 P2 142 P2 146 P2 150 P2 138 P2 148 P2 151 P2 140 P2 135 P2 137 P2 129 P2 139 P2 150 P2 138 P2 144 P2 149 P2 130 P2 144 P2 153 P2 133 P2 140 P2 145 P2 143 P2 138 P2 140 P2 137 P2 133 P2 139 P2 147 P2 119 P2 144 P2 147 P2 IND %TW TWD 17 TWD 21 TWD 15 TWD 5 TWD 17 TWD 7 TWD 23 TWD 20 TWD 11 TWD 9 TWD 19 TWD 12 TWD 8 TWD 7 TWD 10 TWD 8 TWD 9 TWD 6 TWD 11 TWD 11 TWD 6 TWD 16 TWD 6 TWD 5 TWD 7 TWD 18 TWD 19 TWD 8 TWD 17 TWD 10 TWD 12 TWD 6 TWD 8 TWD 35 TWD 9 TWD 34 TWD 17 TWD 12 TWD 8 TWD 5 TWD 19 TWD 10 TWD 6 TWD 19 TWD 5 TWD 19 TWD 5 TWD 9 TWD 8 TWD 9 TWD 9 TWD 5 TWD 10 TWD 8 TWO 6 TWD 14 TWD 30 TWD 16 TWD 35 TWD 23 TWD 7 TWD 6 TWD 6 TWD 9 TWD 26 TWD 7 TWD 9 TWD 17 TWD 10 TWD 4 TWD 8 TWD 9 TWD 12 TWD 15 TWD 12 TWD 10 TWD 11 TWD 5 TWD 12 TWD 9 LOCATION 011

+0.27 012

-0.46 013

-0.51 013

+0.27 010

+0.61 011

-0.44 011

+0.29 013

-0.49 012

-0.51 012

-0.51 009

+0.58 013

-0.49 013

+0.24 009

+0.58 009

+0.58 009

-0.48 011

-0.48 008

+0.29 012

+0.22 009

+0.61 008

-0.46 012

+0.24 009

+0.59 012

-0.51 007

-0.39 009

-0.49 011

-0.46 013

+0.27 014

-0.49 010

+0.61 013

-0.51 010

-0.46 009

+0.58 010

-0.49 009

-0.49 010

-0.46 011

-0.44 012

-0.49 013

+0.24 009

+0.54 010

-0.49 011

-0.44 012

+0.17 013

-0.

46 008

-0.

44 010

-0. 44 011

-0.46 013

+0.24 010

+0.59 011

-0.46 011

+0.27 010

-0.46 010

+0.54 014

+0.24 009

-0.51 010

-0.45 011

-0.42 014

+0.24 010

-0.47 014

-0.49 014

+0.27 010

-0.44 011

+0.29 014

-0.49 010

-0.44 010

-0.41 013

-0.41 010

-0.39 010

-0.41 012

-0.39 010

+0.64 011

-0.39 012

-0.46 013

-0.41 1009

+0.56 010

+0.63 008

+0.29 011

-0.44 012

-0.43 009

+0.61 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

42 42 42 42 16 42 40 40 40 42 40 40 42 42 7

42 9

42 40 42 5

42 60 6

60 58 58 0

58 0

58 60 60 60 60 60 6

60 4

60 58

-60 60 58 58 58 58 58 3

58 60 60 60 60 58 58 58 58 7

58 60 60 60 7

60 60 58 58 58 58 60 60 60 58 58 58 60 58 58 58 60 42 42 42 42 42 42 42 40 42 40 42 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc 4/22/2008 9:45:19 AM Component: S/G A Customer Name: ONSI Repl Page 7 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl(l]

ROW TUBE VOLTS 0.24 0.11 11 17 0.38 0.20 0.27 0.14 11 18 0.15 0.06 11 19 0.15 0.31 11 20 0.08 11 21 0.18 0.22 0.14 11 22 0.12 0.15 11 23 0.11 11 26 0.12 11 28 0.18 0:22 0.07 11 31 0.08 11 38 0.14 11 42 0.24 0.17 0.09 0.14 11 43 0.11 11 44 0.30 0.13 11 45 0.09 0.13 11 46 0.23 0.23 0.09 0.08 11 47 0.31 0.22 0.14 11 48 0.55 0.22 0.06 11 50 0.21 0.42 11 52 0,49 0.36 0.11 11 53 0.25 11 55 0.72 0.12 0.07 0.07 11 56 0.54 0.12 0.09 0.12 11 58 0.16 11 60 1.01 11 61 0.18 11 62 0.76 11 66 0.10 12 3

0.10 12 5

0.10 12 8

0.08 12 9

0.14 12 10 0.15 0.08 0.09 0.11 12 12 0.12 0.12 12 13 0.21 0.12 12 14 0.30 0.34 12 15 0.10 0.20 0.16 0.32 12 16 0.24 DEG 134 143 123 149 145 146 142 155 134 148 148 149 143 154 147 147 136 150 146 145 129 134 136 151 139 148 139 150 148 152 157 137 152 141 136 136 144 146 134 141 136 147 132 134 134 139 151 143 128 144 160 124 135 152 155 145 140 121 151 129 134 152 128 145 121 145 153 142 134 156 139 139 144 138 137 151 143 143 141 141 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 92 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 D2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWO TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW LOCATION 13 010

+0.61 6

011

-0.44 19

'008

+0.29 11 011

-0.39 15 012

-0.44 8

012

+0.29 8

011

-0.41 4

012

-0.49 9

008

+0.27 16 013

-0.49 5

011

-0.44 11 009

+0.60 12 012

+0.29 8

012

-0.46 7

009

+0.56 8

012

-0.46 6

008

-0.46 7

012

-0.49 10 013

-0.53 12 013

+0.22 4

008

+0.24 5

013

+0.22 8

013

+0.22 12 012

-0.49 9

009

-0.49 5

009

+0.59 8

011

-0.47 7

011

-0.49 15 011

-0.46 7

010

-0.49 6

009

-0.51 8

011

-0.42 12 011

-0.44 12 010

-0.46 5

010

+0.64 5

012

-0.51 16 010

-0.49 12 011

+0.27 8

010

+0.61 23 011

-0.44 11 012

+0.27 4

009

-0.46 11 010

-0.49 19 011

+0.27 21 010

-0.46 17 014

+0.22 6

010

+0.61 14 010

-0.47 28 010

-0.45 7

011

+0.29 4

011

-0.42 4

007

-0.41 25 010

-0.50 8

011

+0.32 6

013

-0.49 8

013

+0.24 9

010

-0.44 34 010

-0.44 11 010

-0.41 29 010

-0.44 6

010

-0.41 6

011

-0.32 6

010

-0.39 5

012

-0.39 8

009

+0.58 9

008

+0.34 5

012

-0.44 5

012

+0.31 7

014

-0.44 7

011

-0.39 7

013

-0.46 11 010

+0.61 7

011

-0.41 16 012

-0.46 17 012

+0.32 5

009

+0.56 11 011

-0.44 9

012

-0.49 16 012

+0.27 13 011

-0.41 EXT LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE EXT UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

42 42 40 40 40 4

40 42 42 40 40 42 40 40 7

40 42 42 40 42 42 42 42 40 4

58 58 4

58 3

58 0

58 60 58 0

58 60 60 58 5

58 4

58 5

58 60 60 6

60 58 58 58 58 58 58 58 5

58 60 58 58 58 58 60 60 60 60 58 58 60 58 4

116 32 42 40 42 40 40 40 40 40 40 42 42 40 40 42 42 42 42 40 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

510XB, 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:19 AM Component: S/G A Page 8 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl~l]

ROW TUBE VOLTS 0.07 12 17 0.13 12 18 0.26 0.17 0.18 12 20 0.33 0.37 0.14 12 21 0.18 12 22 0.12 0.14 0.14 12 25 0.08 12 26 0.18 0.18 12 27 0.11 12 28 0.26 12 31 0.17 12 34 0.15 12 43 0.10 12 44 0.11 0.10 0.14 12 45 0.09 12 47 0.13 0.13 12 49 0.32 12 51 0.14 12 54 0.22 0.18 12 55 0.19 0.36 0.15 12 56 0.11 0.17 0.36 0.09 0.19 0.08 12 57 1.06 12 58 0.76 0.11 12 59 0.07 0.09 12 60 0.48 0.20 12 61 0.22 0.10 0.11 12 64 0.29 13 4

0.09 13 11 0.05 0.14 13 12 0.10 0.12 0.37 13 14 0.21 0.65 0.20 13 15 0.15 13 16 0.14 13 17 0.11 13 19 0.10 0.10 13 21 0.13 13 22 0.28 0.10 13 24 0.14 0.09 13 25 0.13 0.15 13 28 0.20 0.12 13 29 0.13 13 33 0.07 13 37 0.19 13 44 0.12 13 46 0.15 13 47 0.39 0.09 DEG CHN 147 P2 111 P2 141 P2 144 P2 150 P2 141 P2 134 P2 152 P2 145 P2 147 P2 151 P2 143 P2 149 P2 151 P2 145 P2 148 P2 145 P2 141 P2.

147 P2 157 P2 137 P2 148 P2 153 P2 139 P2 143 P2 152 P2 148 P2 152 P2 139 P2 148 P2 141 P2 141 P2 142 P2 140 P2 143 P2 146 P2 134 P2 149 P2 160 P2 131 P2 130 P2 133 P2 157 P2 117 P2 140 P2 126 P2 141 P2 159 P2 144 P2 139 P2 126 P2 154 P2 114 P2 153 P2 151 P2 138 P2 150 P2 136 P2 143 P2 139 P2 149 P2 138 P2 149 P2 153 P2 150 P2 135 P2 144 P2 144 P2 143 P2 145 P2 140 P2 150 P2 143 P2 148 P2 114 P2 139 P2 125 P2 150 P2 138 P2 159 P2 IND %TW TWD 5 TWD 7 TWD 14 TWD 10 TWD 10 TWD 17 TWD 18 TWD 8 TWD 10 TWD 7 TWD 8 TWD 8 TWD 5 TWD 11 TWD 10 TWD 6 TWD 14 TWD 9 TWD 9 TWD 6 TWD 7 TWD 6 TWD 8 TWD 5 TWD 7 TWD 7 TWD 16 TWD 8 TWD 11 TWD 10 TWD 11 TWD 19 TWD 9 TWD 6 TWD 9 TWD 17 TWD 5 TWD 10 TWD 5 TWD 36 TWD 29 TWD 6 TWD 5 TWD 6 TWD 21 TWD 10 TWD 12 TWD 6 TWD 7 TWD 15 TWD 5 TWD 3 TWD 8 TWD 6 TWD 7 TWD 18 TWD 12 TWD 27 TWD 11 TWD 8 TWD 8 TWD 6 TWD 6 TWD 6 TWD 7 TWD 15 TWD 6 TWD 8 TWD 5 TWD 8 TWD 8 TWD 11 TWD 7 TWD 8 TWD 4 TWD 10 TWD 7 TWD 9 TWD 18 TWD 5 LOCATION 012

-0.49 009

+0.58 008

+0.29 011

-0.41 012

+0.27 012

-0.46 013

+0.32 013

-0.58 013

-0*51 008

-0.46 013

-0.53 013

+0.22 009

-0.51 009

+0.53 013

+0.22 011

-0.49 012

-0.51 013

-0.56 008

-0.45 009

+0.46 008

+0.24 009

-0.49 012

-0.54 009

+0.59 012

-0.51 010

+0.61 011

-0.44 014

+0.20 014

+0.20 010

-0.46 010

-0.50 013

-0.51 014

+0.22 010

-0.45 011

+0.27 013

-0.49 013

+0.27 014

+0.22 009

+0.59 010

-0.47 010

-0,45 011

+0.29 010

-0.47 011

+0.27 010

-0.45 014

+0.24 010

-0.47 014

-0.46 014

+0.24 010

-0.42 010

-0.36 010

-0.44 010

+0.66 011

-0.39 012

-0.43 012

+0.29 012

-0.44 012

+0.29 009

+0.58 009

+0.58 011

-0.39 011

-0.44 012

-0.46 013

-0.44 012

+0.24 012

+0.27 012

-0.49 011

-0.41 012

-0.46 013

-0.53 013

+0.20 012

-0.51 012

+0.22 013

-0.56 008

+0.29 009

+0.55 011

-0.49 014

-0.56 011

-0.46 009

+0.59 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

40 42 40 40 40 40 40 4

40 42 40 40 40 42 40 40 42 40 42 40 0

58 60 60 0

60 4

58 58 6

58 58 4

58 58 3

58 60 60 60 58 58 58 58 58 58 60 58 58 60 60 58 58 60 60 60 58 30 42 6

42 40, 40 40 40 40 10 40 42 40 42 42 42 42 40 4"

40 40 40 42 42 40 40 6

42 42 42 60 2

60 58 0

58 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET

-PROBE 510XB 510X8 510XB 51OXB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XO 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XOx 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510X5 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXE 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510xB 510XB 510XB

AREVA NP Inc CUstomer Name: ONSr Repl 4/22/2008 9:45:19 AM Component:

S/G A Page 9 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: QueryMIl(1 ROW TUBE VOLTS 0.11 0.25 13 54 0.14 13 55 0.09 0.16 13 56 0.09 13 57 0.34 0.11 0.13 13 58 0.23 0.22 0.13 0.25 13 59 0.43 0.09 0.26 0.56 13 60 0.74 0.18 13 61 0.41 0.18 0.21 0.18 0.13 13 62 0.77 0.26 0.23 13 63 0.16 0.25 0.25 0.10 13 64 0.13 13 65 0.25 13 67 0.22 14 1

0.35 14 2

0.10 14 6

0.22 0.23 14 8

0.20 0.16 14 9

0.19 14 11 0.19 14 12 0.08 0.32 14 13 0.21 0.18 0.19 14 14 0.10 14 17 0.29 14 18 0.14 14 20 0.08 14 22 0.12 0.08 0.15 0.21 14 23 0.13 14 26 0.19 0.19 14 27 0.16 14 32 0.21 14 34 0.11 14 39 0.34 14 40 0.09 0.25 14 41 0.20 14 43 14 46 0.12 14 56 0.10 0.31 14 57 0.09 0.13 0.21 14 58 0.61 14 59 0.60 14 60 0.34 0.17 14 61 0.08 14 62 0.11 14 63 0.13 14 64 0.11 DEG CHN 155 P2 135 P2 133 P2 152 P2 151 P2 132 P2 142 P2 157 P2 158 P2 151 P2 132 P2 146 P2 151 P2 142 P2 128 P2 137 P2 131 P2 131 P2 141 P2 133 P2 144 P2 145 P2 142 P2 140 P2 133 P2 142 P2 140 P2 149 P2 156 P2 136 P2 152 P2 146 P2 150 P2 130 P2 125 P2 107 P2 135 P2 105 P2 143 P2 130 P2 133 P2 136 P2 136 P2 142 P2 135 P2 137 P2 150 P2 126 P2 136 P2 121 P2 148 P2 153 P2 140 P2 146 P2 146 P2 136 P2 151 P2 133 P2 143 P2 150 P2 152 P2 136 P2 144 P2 148 P2 144 P2 151 P2 105 P2 143 P2 148 P2 154 P2 138 P2 134 P2 133 P2 145 P2 140 P2 149 P2 156 P2 147 P2 122 P2 IND %TW LOCATION TWD 6 010

+0.59 TWD 13 012

-0.51 TWD 8 009.

+0.56 TWD 5 012

-0.51 TWD 9 011

-0.44 TWD 6 011

-0.42 TWD 17 011

-0.42 TWD 6 012

-0.46 TWD 7 013

-0.56 TWD 13 010

-0.46 TWD 12 011

-0.44 TWD 8 011

+0.29 TWD 14 012

-0.49 TWD 20 011

-0.39 TWD 5 012

-0.44 TWD 13 013

+0.24 TWD 24 010

-0.46 TWD 30 010

-0.47 TWD 10 012

+0.24 TWD 19 010

-0.47 TWD 10 011

-0.42 TWD 11 013

-0.46 TWD 10 013

+0.24 TWD 7 009

-0.42 TWD 30 010

-0.45 TWD 14 011

-0.42 TWD 13 014

-0.49 TWD 9 010

-0.42 TWD 13 014

-0.49 TWD 13 014

+0.22 TWD 6 011

+0.32 TWD 8 011

+0.27 TWD 13 014

+0.24 TWD 11 010

-0.42 TWD 18 010

+0.63 TWD 6 011

-0.34 TWD 12 011

-0.37 TWD 12 010

+0.64 TWD 11 013

-0.46 TWD 10 010

+0.64 TWD 10 010

+0.61 TWD 10 010

+0.63 TWD 5 011

-0.41 TWD 17 012

+0.29 TWD 11 008

+0.29 TWD 10 009

+0.56 TWD 10 012

+0.27 TWD 6 008

+0.27 TWD 15 008

+0.29 TWD 8 008

+0.29 TWD 5 009

-0.48 TWD 7 008

-0.46 TWD 5 008

+0.27 TWD 9 012

-0.51 TWD 12 009

+0.58 TWD 8 009

+0.56 TWD 11 012

-0.56 TWD 11 012

+0.22 TWD 9 013

-0.54 TWD 12 009

+0.55 TWD 6 009

-0.53 TWD 16 012

-0.58 TWD 6 009

-0.52 TWD 13 009

+0.53 TWD 11 013

+0.20 NDD TWD 7 013

-0.56 TWD 6 007

-0.46 TWD 15 011

-0.47 TWD 6 012

-0.49 TWD 8 010

+0.59 TWD 12 011

-0.44 TWD 25 011

-0.44 TWD 26 010

-0.49 TWD 16 011

-0.44 TWD 9 010

-0.49 TWD 5 010

-0.46 TWD 6 010

-0.46 TWD 8 014

+0.22 TWD 6 011

+0.29 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

0 58 0

58 0

60 58 0

58 60 58 58 58 60 60 60 60 58 58 58 0

58 60 60 58 58 58 58 58 60 60 60 58 58 58 0

58 60 58 58 32 30 30 9

30 40 10 40 7

42 42 40 40 42 42 42 40 42 40 40 40 40 40 40 6

42 40 40 42 40 40 42 40 40 58 60 6

58 58 58 60 4

60 4

60 58 60 58 5

58 60 4

58 60 0

58 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB" 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXB

AREVA NP Inc Customer Name: ONSl Repl 4/22/2008 9:45:19 Am Component: S/G A Page 10 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 14 65 0.09 14 66 0.09 0.31 14 67 0.13 14 68 0.14 0.12 15 4

0.09 0.20 0.22 15 5

0.07 15 7

0.16 15 10 0.11 0.09 15 11 0.20 0.21 15 12 0.18 15 13 0.15 15 14 0.12 0.13 15 17 0.16 0.23 15 18 0.18 15 19 0.08 0.20 0.10 15 21 0.11 15 22 0.15 15 25 0.11 15 27 0.14 15 29 0.27 15 32 0.17 15 40 0.16 15 43 0.11 0.16 15 44 0.11 15 48 0.07 15 52 0.10 15 54 0.13 15 56 15 57 0.10 0.08 15 58 15 61 0.13 0.97 0.41 0.46 0.09 0.12 0.18 15 62 0.10 0.28 0.14 15 66 0.12 15 67 0.62 0.14 15 69 0.09 0.13 15 72 0.15 16 5

0.08 16 7

0.13 0.16 0.18 0.14 16 8

0.19 0.38 16 9

0.47 0.14 16 10 0.10 0.18 0.23 16 11 0.19 16 12 0.21 0.17 16 14 0.09 16 18 0.08 0.15 16 24 0.15 0.11 16 25 0.18 16 26 0.07 DEG CHN IND

%TW LOCATION 155 P2 TWO 6 010

-0.47 126 P2 TWO 5 010

-0.45 137 P2 TWO 15 014

-0.46 139 P2 TWO 8 014

+0.24 160 P2 TWO 8 014

-0.46 142 P2 TWO 7 014

+0.24 135 P2 TWO 6 010

-0.39 112 P2 TWO 11 010

+0.63 151 P2 TWO 13 012

-0.36 139 P2 TWO 4 010

-0.36 121 P2 TWO 9 010

+0.61 147 P2 TWO 7 008

+0.31 143 P2 TWO 6 013

-0.46 132 P2 TWO 11 010

+0.64 134 P2 TWO 11 011

-0.39 140 P2 TWO 10 011

-0.37 148 P2 TWO 9 009

+0.61 151 P2 TWO 7 012

-0.46 138 P2 TWO 8 008

+0.29 143 P2 TWO 9 009

+0.56 148 P2 TWO 12 012

-0.49 148 P2 TWO 10 013

-0.56 125 P2 TWO 5 008

+0.27 143 P2 TWO 11 013

-0.54 152 P2 TWO 6 013

+0.22 146 P2 TWO 6 009

+0.54 143 P2 TWO 9 013

+0.22 141 P2 TWO 6 008

+0.24 141 P2. TWO 8 013

-0.56 140 P2 TWO 14 013

-0.54 154 P2 TWO 10 009

+0.53 147 P2 TWO 10 013

+0.19 144 P2 TWO 6 013

-0.56 132 P2 TWO 9 013

+0.17 134 P2 TWO 7 012

-0.59 158 P2 TWO 5 013

+0.17 153 P2 TWO 6 013

+0.17 147 P2 TWO 8 012

+0.17 NDD 158 P2 TWO 6 013

-0.54 146 P2 TWO 5 013

+0.15 NOD 159 P2 TWO 7 009

-0.46 131 P2 TWO 33 011

-0.44 143 P2 TWO 19 012

-0.49 138 P2 TWO 21 013

+0.22 162 P2 TWO 5 010

-0.51 157 P2 TWO 7 010

+0.54 146 P2 TWO 10 013

-0.51 151 P2 TWO 6 009

-0.46 134 P2 TWO 15 011

-0.44 146 P2 TWO 9 010

-0.51 151 P2 TWO 8 014

+0.22 134 P2 TWO 25 010

-0.47 157 P2 TWO 8 013

-0.46 145 P2 TWO 5 014

-0.49 143 P2 TWO 7 014

+0.22 135 P2 TWO 9 010

-0.44 135 P2 TWO 5 010

-0.39 125 P2 TWO 8 010

+0.63 133 P2 TWO 10 013

-0.39 150 P2 TWO 10 013

+0.32 75 P2 TWO 8 010

-0.A4 139 P2 TWO 10 008

+0.34 124 P2 TWO 18 010

+0.64 125 P2 TWO 21 010

+0.61 131 P2 TWO 8 011

-0.39 119 P2 TWO 6 008

+0.32 143 P2 TWO 10 010

+0.61 138 P2 TWO 12 011

-0.39 139 P2 TWO 10 010

+0.61 140 P2 TWO 11 010

+0.61 149 P2 TWO 10 011

-0.39 152 P2 TWO 6 011

-0.42 90 P2 TWO 5 008

+0.24 154 P2 TWO 9 013

-0.49 153 P2 TWO 8 009

+0.53 139 P2 TWO 7 013

-0.56 140 P2 TWO 10 013

-0.53 152 P2 TWO 5 008

+0.22 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG PROBE 60 58 58 60 58 58 32 32 32 30 7

30 40 40 42 42 40 42 40 4

40 42 42 40 42 42 42 42 40 42 42 42 40 5

40 58 58 60 60 60 60 60 4

58 3

58 60 58 58 58 0

58 0

58 0

58 0

58 6060 3

60 60 58 58 58 4

58 60 32 32 32 32 32 30 30 30 30 38 38 38 38 38 38 5

38 40 40 98 98 42 40 INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET 510XB 510XB 510Xx 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510X8 510XB 510XB 510xB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510Xl 510XB 510XB 510Xx 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OX8 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSr Rep1 4/22/2008 9:45:19 AM Component:

S/G A Page 11 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: Query~lih]

ROW TUBE VOLTS 16 27 0.38 0.14 16 29 0.11 0.17 16 34 0.14 16 35 0.14 16 36 0.13 16 38 0.31 16 41 0.28 16 42 0.10 0.14

0. 30 16 46 0.23 0.10 16 50 0.21 0.27 16 55 0.15 16 56 0.17 0.13 16 59 0.16 16 61 0.19 16 66 0.39 0.11 16' 68 0.10 16 69 0.64 0.31 0.47 16 70 0.16 17 1

0.27 17 2

0.24 17 5

0.16 17 6

0.20 17 8

0.15 0.11 0.20 17 9

0.52 0.17 0.13 17 10 0.12 17 12 0.23 17 14 0.17 0.21 17 16 0.08 0.22 17 18 0.22 0.09 0.45 17 25 0.12 0.14 17 28 0.16 17 30 0.15 17 33 0.13 17 34 0.38 17 37 0.18 17 38 0.11 17 41 0.13 17 44 0.16 0.13 17 48 0.06 17 49 0.15 0.20 0.10 17 51 0.11 17 55 0.12 17 56 0.14 17 58 0.11 17 59 0.10 17 60 0.16 0.14 17 67 0.20 17 69 0.32 17 70 0.34 0.19 0.15 17 71 0.27 0.11 17 76 0.31 0.11 0.12 17 77 0.11 DEG CHN IND 141 P2 TWD 147 P2 TWD 150 P2 TWD 131 P2 TWD 142 P2 TWD 145 P2 TWD 147 P2 TWO 134 P2 TWD 136 P2 TWD 146 P2 TWD 144 P2 TWD 135 P2 TWD 141 P2 TWD 149 P2 TWD 127 P2 TWD 125 P2 TWD 148 P2 TWD 149 P2 TWD 137 P2 TWD 142 P2 TWD 148 P2 TWD 138 P2 TWD 124 P2 TWD 141 P2 TWD 140 P2 TWD 142 P2 TWD 140 P2 TWD 144 P2 TWD 115 P2 TWD 103 P2 TWD 78 P2 TWD 112 P2 TWD 143 P2 TWD 150 P2 TWD 139 P2 TWD 138 P2 TWD 142 P2 TWD 122 P2 TWD 147 P2 TWD 146 P2 TWD 147 P2 TWD 148 P2 TWD 150 P2 TWD 148 P2 TWO 143 P2 TWD 136 P2 TWO 129 P2 TWD 123 P2 TWD 154 P2 TWO 140 P2 TWD 145 P2 TWD 126 P2 TWD 132 P2 TWD 148 P2 TWD 147 P2 TWD 159 P2 TWD 137 P2 TWD 96 P2 TWD 157 P2 TWD 152 P2 TWD 141 P2 TWD 140 P2 TWD 142 P2 TWD 149 P2 TWD 146 P2 TWD 147 P2 TWD 126 P2 TWD 139 P2 TWD 150 P2 TWD 130 P2 TWD 133 P2 TWD 145 P2 TWD 145 P2 TWD 151 P2 TWD 140 P2 TWD 134 P2 TWD 146 P2 TWD 146 P2 TWD 148 P2 TWD 152 P2 TWD

%TW LOCATION 18 013

-0.58 8

013

+0.07 6

010

+0.56 9

013

-0.58 8

012

-0.56 8

013

+0.12 8

009

-0.53 16 013

-0.58 14 012

-0.56 6

009

-0.50 8

009

+0.19 16 010

+0.19 12 013

-0.63 5

013

+0.15 11 013

+0.15 13 014

-0.61 8

012

+0.19 9

011

-0.51 7

013

+0.17 8

012

-0.54 9

011

-0.46 18 014

-0.51 6

014

+0.19 5

014

+0.19 25 010

-0.49 14 011

-0.42 20 014

-0.51 9

010

-0.44 15 010

+0.63 13 010

+0.66 10 010

+0.66 11 010

+0.64 8

010

-0.41 6

010

+0,61 11 011

-0.39 24 010

+0.58 10 011

-0.41 8

009

+0.65 7

009

+0.61 13 010

+0.62 10 012

-0.46 11 013

-0.56 5

012

-0.49 12 013

-0.56 12 012

-0.46 6

012

+0.22 21 013

+0.24 7

008

+0.24 8

009

+0.56 10 013

-0.55 9

013

-0.63 7

009

+0.10 18 009

+0.19 10 009

+0.19 7

009

-0.61 8

011

-0.56 9

013

+0.15 8

013

-0.52 4

013

+0.03 8

009

-0.54 10 011

-0.54 5

009

+0.19 6

013

+0.10 7

009

-0.56 7

012

-0.54 6

013

+0.15 5

012

-0.56 8

012

-0.59 7

012

+0.17 10 014

+0.19 15 011

-0.44 15 010

-0.49 10 011

+0.29 8

014

+0.22 13 010

-0.46 6

014

+0.22 15 010

-0.44 6

011

+0.32 6

014

+0.22 6

010

-0.44 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE.

LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

42 42 42 42 40 0

603 40 40 42 40 40 40 64 5

64 64 64 62 64 4

64 62 62 64 4

64 4

64 62 62 62 58 32 30 32 30 30 30 30 32 32 32 30 38 38 38 38 38 38 38 38 38 4

38 4

605 38 38 38 38 0

605 38 0

603 0

603 64 62 62 4

62 64 64 62 62 64 62 62 0

64 64 62 62 62 64 64 62 62 62 64 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

.510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510UL 510XL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 51OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:19 AM Component: S/G A Page 12 of 97 ONS1AR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS

1========

17 78 0.13 18 3

0.15 18 6

0.09 18 7

0.16 18 8

0.13 0.25 0.32 0.38 18 9

0.19 0.80 0.15 0.35 0.51 18 10 0.12 0.10 0.11 18 11 0.17 0.18 0.15 0.22 0.28 18 12 0.36 0.33 0.16 18 13 0.28 0.12 0.12 0.15 18 15 0.14 0.20 18 18 0.11 18 19 0.08 18 20 0.11 18 23 0.29 0.12 18 29 0.13 0.32 0.13 18 36 0.20 0.17 0.09 18 38 0.12 18 40 0.23 18 42 0.20 18 43 0.11 18 44 0.25 0.15 18 46 0.17 18 51 0.13 18 61 0.13 18 62 0.29 18 66 0.38 0.23 0.17 0.16 18 68 0.16 18 69 0.13 18 70 0.24 0.79 18 71 0.20 0.10 18 72 0.59 0.40 18 73 0.25 18 74 0.12 0.29 0.13 18 76 0.40 0.33 0.11 18 78 0.11 18 80 0.16 18 82 0.14 18 85 0.14 19 1

0.11 19 2

0.29 19 5

0.11 19 7

0.20 19 8

0.34 0.15 DEG 151 144 135 112 152 139 137 136 141 136 143 142 144 4145 140 139 148 125 141 145 131 136 134 133 132 145 134 144 146 152 135 154 130 140 120 115 126 144 146 140 144 148 140 130 134

.140 94 143 145 132 143 136 137 141 130 147 147 145 129 148 108 133 139 149 142 138 149 137 139 129 147 131 130 150 142 117 147 131 130 127 CHN P22 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 7 TWD 9 TWD 5 TWD 10 TWD 7 TWD 13 TWD 16 TWD 18 TWD 11 TWD 31 TWD 9 TWD 18 TWD 24 TWD 7 TWD 6 TWD 6 TWD 9 TWD 10 TWD 8 TWD 12 TWD 14 TWD 18 TWD 17 TWD 9 TWD 15 TWD 7 TWD 7 TWD 9 TWD 8 TWD 11 TWD 6 TWD 5 TWD 7 TWD 15 TWD 7 TWD 8 TWD 16 TWD 7 TWD 11 TWD 9 TWD 5 TWD 7 TWD 13 TWD 11 TWD 7 TWD 13 TWD 9 TWD 9 TWD 7 TWD 7 TWD 14 TWD 17 TWD 12 TWD 9 TWD 8 TWD 8 TWD 7 TWD 12 TWD 29 TWD 10 TWD 5 TWD 24 TWD 18 TWD 12 TWD 7 TWD 14 TWD 7 TWD 18 TWD 16 TWD 6 TWD 6 TWD 8 TWD 7 TWD 7 TWD 7 TWD 15 TWD 7 TWD 11 TWD 17 TWD 8 LOCATION 010

-0.41 010

+0.63 010

-0.39 010

+0.68 009

+0.61 012

-0.39 014

-0.41 014

+0.29 009

+0.61 010

+0.61 011

-0.41 012

-0.41 012

+0.34 009

+0.58 013

-0.46 011

-0.39 009

+0.58 010

+0.63 011

-0.41 013

-0.46 013

+0.32 012

-0.48 012

+0.29 013

-0.46 008

+0.31 009

+0.60 011

-0.42 010

+0.59 011

-0.42 009

+0.58 013

+0.20 013

+0.22 013

+0.22 012

-0.56 012

+0.17 009

+0.17 013

-0.61 013

+0.15 011

-0.56 011

+0.00 009

-0.55 009

+0.14 011

-0.58 009

+0.14 009

-0.53 008

-0.52 009

+0.19 011

-0.59 011

-0.56 012

-0.61 012

-0.56 011

-0.46 013

+0.19 014

-0.56 014

+0.15 009

-0.51 011

-0.44 012

-0.51 009

-0.49 009

-0.49 008

+0.27 013

-0.49 014

-0.54 010

-0.49 010

-0.49 014

+0.20 011

+0.27 010

-0.46 014

-0.49 014

+0.22 011

+0.29 010

-0.44 010

-0.41 015

-0.44 010

+0.63 010

+0.66 010

-0.41 010

+0.63 010

+0.66 011

-0.39 EXT EXT UTIL I

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL # LEG 62 INLET 32 INLET 30 INLET 32 INLET 30 INLET 30 INLET 30 INLET 30 INLET 32 INLET 32 INLET 32 INLET 32 INLET 32 INLET 30 INLET 30 INLET 6

30 INLET 30 INLET 30 INLET 30 INLET 30 INLET 30 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38, INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 0

.38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 38 INLET 64 INLET 64 INLET 0

62 INLET 64 INLET 64 INLET 64 INLET 64 INLET 64 INLET 64 INLET 62 INLET 64 INLET 64 INLET 62 INLET 0

62 INLET 64 INLET 64 INLET 62 INLET 64 INLET 64 INLET 5

64 INLET 64 INLET 64 INLET 6

64 INLET 4

64 INLET 64 INLET 64 INLET 62 INLET 32 INLET 30 INLET 32 INLET 32 INLET 30 INLET 30 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:19 AM Component: S/G A Page 13 of 97 ONSlAR-EOC24 7 Tube Support Wear QUERY: QueryMl[1]

ROW TUBE VOLTS 19 9

0.07 0.16 19 10 0.16 19 11 0.13 0.11 19 12 0.17 0.19 19 13 0.16 0.14 19 19 0.09 0.17 0.16 0.18 0.31 0.23 19 20 0.30 19 22 0.10 19 25 0.10 19 28 0.12 19 32 0.19 0.16 19 33 0.16 19 34 0.14 19 37 0.10 19 42 0.14 19 43 0.15 19 44 0.14 19 45 0.15 0.11 19 50 0.12 19 52 0.26 19 54 0.13 0.24 19 55 0.17 0.10 0.11 0.22 19 57 0.13 19 58 0.19 0.19 19 66 0.10 19 69 0.20 0.17 0.62 0.26 0.16 19 72 0.26 0.10 19 73 0.16 19 75 0.24 19 76 0.86 0.09 19 77 0.10 19 78 0.43 0.31 0.12 0.14 19 79 0.15 19 80 0.07 0.09 19 81 0.11 19 83 0.10 20 9

0.24 20 10 0.10 0.16 20 12 0.10 20 13 0.08 20 14 0.14 0.20 0.21 20 15 0.14 0.11 20 17 0.08 20 18 0.10 0.09 20 20 0.12 0.14 20 21 0.20 0.16 20 22 0.13 DEG CHN 87 P2 117 P2 133 P2 143 P2 138 P2 126 P2 137 P2 141 P2 155 P2 144 P2 149 P2 144 P2 146 P2 138 P2 140 P2 142 P2 145 P2 148 P2 132 P2 144 P2 136 P2 137 P2 152 P2 145 P2 128 P2 126 P2 131 P2 135 P2 143 P2 137 P2 142 P2 140 P2 139 P2 145 P2 143 P2 149 P2 140 P2 142 P2 138 P2 143 P2 143 P2 146 P2 136 P2 129 P2 147 P2 138 P2 150 P2 154 P2 155 P2 143 P2 137 P2 154 P2 150 P2 140 P2 140 P2 158 P2 143 P2 138 P2 136 P2 113 P2 144 P2 141 P2 139 P2 125 P2 134 P2 149 P2 143 P2 149 P2 142 P2 148 P2 152 P2 129 P2 160 P2 153 P2 136 P2 131 P2 149 P2 148 P2 136 P2 152 P2 IND %TW TWD 5 TWD 10 TWD 9 TWD 8 TWD 7 TWD 10 TWD 10 TWD 9 TWD 8 TWD 5 TWD 10 TWD 9 TWD 10 TWD 16 TWD 12 TWD 15 TWD 6 TWD 6 TWD 7 TWD 11 TWD 9 TWD 9 TWD 8 TWD 6 TWD 8 TWD 9 TWD 8 TWD 9 TWD 7 TWD 7 TWD 13 TWD 7 TWD 13 TWD 9 TWD 5 TWD 6 TWD 11 TWD 7 TWD 10 TWD 10 TWD 5 TWD 10 TWD 9 TWD 25 TWD 13 TWD 8 TWD 13 TWD 6 TWD 9 TWD 12 TWD 30 TWD 5 TWO 6 TWD 19 TWD 14 TWD 6 TWD 7 TWD 8 TWD 4 TWD 5 TWD 6 TWD 6 TWD 13 TWO 6 TWD 9 TWD 6 TWD 5 TWD 8 TWD 11 TWD 12 TWD 8 TWD 6 TWD 5 TWD 6 TWD 5 TWD 7 TWD 8 TWD 11 TWO 9 TWD 8 LOCATION 010

+0.63 009

+0.61 010

+0.61 010

+0.61 011

-0.44 010

+0.64 011

-0.42 013

-0.51 013

+0.29 009

-0.49 011

-0.46 011

+0.22 012

-0.53 013

-0.51 013

+0.22 009

+0.56 009

-0.51 012

-0.56 009

-0.51 013

-0.58 013

+0.15 009

+0.19 009

+0.17 008

+0.19 013

-0.65 010

+0.15 012

-0.63 009

+0.17 008

-0.48 013

+0.12 012

-0.60 010

+0.19 014

+0.07 011

-0.54 011

+0.17 013

-0.61 013

+0.12 013

+0.12 013

-0.61 013

+0.12 012

-0.59 011

-0.49 011

+0.24 013

+0.20 014

-0.59 013

-0.56 009

-0.49 012

-0.51 013

-0.51 010

-0.49 010

-0.49 014

+0.22 010

-0.46 010

-0.46 014

-0.46 014

+0.24 011

+0.29 011

+0.29 010

-0.46 011

+0.27 010

-0.44 010

-0.44 010

+0.61 009

+0.63 010

+0.63 009

+0.63 008

+0.29 008

+0.29 010

+0.59 011

-0.42 011

-0.46 009

-0.53 011

-0.47 013

+0.22 009

-0.51 009

-0.53 011

+0.24 012

-0.53 013

+0.20 009

-0.53 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

32 32 30 32 32 30 30 38 38 38 38 38 38 38 38 38 3

38 3

38 0

603 38 38 38 38 38 38 0

603 38 38 4

38 130 116 116 116 62 62 62 62 64 62 62 62 64 64 64 64 6

64 62 62 64 0

64 62 62 4

64 62 62 62 0

62 64 62 62 64 64 32 30 30 30 30 38 38 38 38 4

38 4

38 38 4

38 38 38 38 38 38 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repi 4/22/2008 9:45:19 AM Component:

S/G A Page 14 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: Query~l~l]

ROW TUBE VOLTS 0.11 0.24 20 27 0.21 20 30 0.17 20 31 0.20 0.09 20 32 0.18 20 36 0.11

20. 38 0.21 0.17 20 39 0.33 20 43 0.19 20 45 0.20 0.15 0.17 20 48 0.17 20 53 0.21 20 54 0.13 20 56 0.15 20 62 0.22 0.08 20 64 0.09 0.21 20 65 0.16 20 66 0.11 20 69 0.16 0.27 0.21 0.16 20 70 0.11 20 71 0.17 20 72 0.12 20 73 0.40

.0.11 0.10 20 76 0.20 0.12 20 77 0.56 0.47 20 78 0.46 20 79 0.88 20 80 0.38 0.11 20 81 0.27 20 82 0.29 20 83 0.10 20 84 0.13 20 85 0.11 20 89 0.17 21 2

0.15 21 5

0.07 21 7

0.23 21 8

0.20 21 9

0.11 0.26 0.10 21 10 0.15 21 12 0.17 0.15 0.16 0.11 21 13 0.12 0.14 21 14 0.12 0.10 21 15 0.21 0.15 21 17 0.30 21 20 0.23 21 22 0.15 0.30 0.17 21 23 0.16 0.12 21 27 0.14 21 28 0.24 21 29 0.11 0.14 21 31 0.26 21 34 0.18 DEG CHN 151 P2 144 P2 138 P2 143 P2 136 P2 140 P2 147 P2 144 P2 139 P2 132 P2 137 P2 133 P2 135 P2 137 P2 126 P2 137 P2 144 P2 119 P2 141 P2 136 P2 135 P2 128 P2 136 P2 152 P2 134 P2 145 P2 129 P2 145 P2 140 P2 143 P2 137 P2 154 P2 145 P2 151 P2 135 P2 144 P2 153 P2 141 P2 138 P2 135 P2 136 P2 135 P2 140 P2 144 P2 142 P2 153 P2 140 P2 155 P2 131 P2 71 P2 151 P2 141 P2 99 P2 148 P2 141 P2 150 P2 145 P2 139 P2 152 P2 126 P2 146 P2 156 P2 128 P2 130 P2 145 P2 149 P2 159 P2 147 P2 142 P2 146 P2 134 P2 134 P2 153 P2 150 P2 147 P2 145 P2 152 P2 129 P2 135 P2 140 P2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWDO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 6

13 11 10 11 6

10 6

11 10 17 10 11 8

9 9

11 7

8 11 55 11 8

6 8

13 11 8

6 9

6 18 6

5 10 6

23 20 20 30 18 6

13 14 5

7 6

9 8

5 13 11 7

14 6

9 9

9 9

6 7

9 7

6 11 8

15 13 9

16 9

9 7

8 13 6

8 14 10 LOCATION EXT EXT 011

. -0.49 LTE UTE 011

+0.17 LTE UTE 009

-0.53 LTE UTE 009

-0.54 LTE UTE 009

-0.53 LTE UTE 008

+0.24 LTE UTE 009

-0.56 LTE UTE 009

+0.19 LTE UTE 009

+0.17 LTE UTE 013

+0.12 LTE UTE 009

+0.17 LTE UTE 009

-0.53 LTE UTE 009

+0.14 LTE UTE 008

-0.53 LTE UTE 011

-0.61 LTE UTE 009

+0.15 LTE UTE 009

+0.17 LTE UTE 009

-0.56 LTE UTE 009

-0.56 LTE UTE 009

-0.56 LTE UTE 013

+0.12 LTE UTE 010

+0.22 LTE UTE 013

-0.61 LTE UTE 007

-0.46 LTE UTE 012

+0.17 LTE UTE 009

-0.56 LTE UTE 013

-0.56 LTE UTE 013

+0.15 LTE UTE 014

+0.12 LTE UTE 014

+0.15 LTE UTE 014

-0.59 LTE UTE 011

-0.46 LTE UTE 010

-0.54 LTE UTE 011

+0.24 LTE UTE 012

-0.54 LTE UTE 009

-0.49 LTE UTE 010

-0.51 LTE UTE 010

-0.51 LTE UTE 014

-0.51 LTE UTE 010

-0.46 LTE-UTE 010

-0.49 LTE UTE 010

-0.44 LTE UTE 011

+0.27 LTE UTE 010

-0.46 LTE UTE 010

-0.44 LTE UTE 010

-0.44 LTE UTE 010

-0.44 LTE UTE 010

-0.44 LTE UTE 015

+0.56 LTE UTE 010

+0.64 LTE UTE 012

-0.37 LTE UTE 010

+0.61 LTE UTE 010

+0.61 LTE UTE 008

+0.29 LTE UTE 010

+0.61 LTE UTE 011

-0.39 LTE UTE 009

+0.58 LTE UTE 010

+0.61 LTE UTE 013

-0.49 LTE UTE 013

+0.27 LTE UTE 011

-0.39 LTE UTE 008

+0.27 LTE UTE 009

+0.61 LTE UTE 008

+0.29 LTE UTE 012

+0.24 LTE UTE 012

-0.49 LTE UTE 013

-0.56 LTE UTE 012

-0.51 LTE UTE 011

+0.24 LTE UTE 011

-0.49 LTE UTE 011

+0.22 LTE UTE 013

-0.59 LTE UTE 011

-0.49 LTE UTE 013

-0.61 LTE UTE 011

-0.51 LTE UTE 012

-0.59 LTE UTE 009

-0.53 LTE UTE 013

+0.10 LTE UTE 009

+0.19 LTE UTE 009

+0.15 LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR' WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

38 38 38 38 3

38 38 38 38 38 38 38 38 38 4

38 6

38 64 64 62 64 64 64 64 64 62 64 62 62 62 62 4

64 62 64 62 62 62 64 4

64 62 62 64 62 64 64 62 64 62 64 62 62 30 32 32 30 32 32 32 30 30 30 30 5

30 32 32 30 30 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:19 AM Component: S/G A Page 15 of 97 ONS1AR-EOC24 -

Tube Support Wear QUERY: QueryMl[l)

ROW TUBE VOLTS

1========

21 35-0.13 21 38 0.28 0.11 0.11 21 40 0.11 21 43 0.20 21 46 0.12 21 47 0.13 21 49 0.15 21 62 0.16 21 63 0.27 21 64 0.13 0.25 21 73 0.17 21 77 0.10 21 78 0.09 21 79 0.33 0.26 21 80 0.11 21 81 0.11 0.25 21 82 0.16 0.17 21 83 0.40 21 84 0.09 0.25 21 85 0.16 22 2

0.11 22 4

0.12 22 7

0.08 22 8

0.18 22 9

0.27 22 10 0.14 0.12 22 11 0.22 22 12 0.09 0.10 22 16 0.1i 22 19 0.15 0.16 22 20 0.18 22 22 0.12 0.11 22 24 0.28 22 25 0.19 0.15 22 26 0.11 0.22 0.19 22 30 0.09 0.22 22 32 0.24 22 34 0.18 22 35 0.17 22 41 0.13 22 44 0.14 0.10 22 50 0.13 0.13 22 54 0.17 0.10 22 57 0.11 0.23 0.30 22 58 0.13 22 66 0.09 0.16 0.14 22 67 0.11 22 68 0.11 22 69 0.12 22 74 0.13 22 79 0.37(

0.09 0.10 22 80 0.21 22 82 0.17 0.21 22 83 0.13 0.15 DEG CHN 152 P2 133 P2 127 P2 148 P2 146 P2 138 P2 129 P2 120 P2 133 P2 113 P2 136 P2 140 P2 137 P2 143 P2 137 P2 142 P2 139 P2 142 P2 131 P2 153 P2 139 P2 151 P2 104 P2 135 P2 159 P2 147 P2 142 P2 128 P2 132 P2 77 P2 133 P2 143 P2 133 P2 147 P2 137 P2 148 P2 140 P2 149 P2 153 P2 138 P2 151 P2 156 P2 152 P2 128 P2 144 P2 134 P2 144 P2 152 P2 129 P2 125 P2 124 P2 140 P2 135 P2 142 P2 143 P2 138 P2 131 P2 122 P2 148 P2 142 P2 144 P2 151 P2 141 P2 127 P2 140 P2 107 P2 146 P2 126 P2 147 P2 141 P2 150 P2 137 P2 146 P2 147 P2 150 P2 138 P2 152 P2 147 P2 151 P2 149 P2 IND %TW TWD 8 TWD 14 TWD 6 TWD 6 TWD 6 TWD 11 TWD 7 TWD 8 TWD 8 TWD 9 TWD 13 TWD 7 TWD 12 TWD 9 TWD 5 TWD 5 TWD 16 TWD 13 TWD 6 TWD 6 TWD 12 TWD 8 TWD 9 TWD 18 TWD 5 TWD 12 TWD 9 TWD 6 TWD 7 TWD 5 TWD 10 TWD 15 TWD 8 TWD 7 TWD 12 TWD 5 TWD 6 TWO 6 TWO 8 TWD 9 TWD 10 TWD 7 TWD 6 TWD 14 TWD 10 TWD 8 TWD 6 TWD 12 TWD 11 TWD 5 TWD 12 TWD 13 TWD 10 TWD 10 TWD 8 TWD 8 TWD 6 TWD 7 TWD 7 TWD 9 TWD 6 TWD 6 TWD 12 TWD 14 TWD 7 TWD 5 TWD 8 TWD 8 TWD 6 TWD 6 TWD 6 TWD 7 TWD 17 TWD 5 TWD 6 TWD 11 TWD 9 TWD 11 TWD 7 TWD 8 LOCATION 011

-0.57 009

+0.14 013

-0.68 008

-0.58 013

+0.07 009

+0.15 009

+0.12 013

+0.07 011

-0.59 015

-0.68 012

-0.59 010

+0.20 013

+0.15 009

-0.51 014

+0.20 010

-0.54 009

-0.48 014

+0.20 014

+0.15 014

-0.51 014

+0.20 010

-0.46 011

+0.27 010

-0.45 010

-0.44 011

+0.29 010

-0.44 008

-0.39 010

-0.39 010

+0.63 010

+0.61 010

+0.61 008

+0.29 009

+0.58 010

+0.61 009

+0.61 010

+0.63.

013

-0.51 009

+0.56 013

+0.22 009

+0.54 009

+0.56 012

-0.56 010

+0.20 013

-0.61 013

+0.12 009

+0.17 011

-0.52 011

+0.15 008

+0.22 009

+0.15 009

+0.15 011

-0.59 008

-0.61 009

+0.15 009

-0.55 009

+0.15 009

+0.02 008

-0.53 009

-0.56 009

+0.02 010

-0.56 011

-0.56 013

-0.66 013

+0.07 008

+0.22 009

-0.53 013

+0.12 010

+0.20 012

+0.15 007

-0.46 014

+0.12 009

-0.51 010

-0.51 012

-0.49 009

-0.48 013

-0.54 014

+0.20 013

-0.49 013

+0.22 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE.

LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

605 38 38 38 0

603 38 38 38 64 64 62 64 64 64 64 62 64 64 62 64 64 62 62 64 62 62 64 30 30 32 30 32 30 30 32 30 30 7

38 38 38 3,8 38 6

38 38 38 38 38 38 38 38 38 38 38 4

605 38 38 38 64 3

64 64 4

64 64 64 64 62 64 64 64 62 64 62 64 62 62 62 64 64 64 62 62 LEG PROBE INLET 51OUL INLET 510XB INLET 510XB INLET 510XB INLET 51OUL INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB n INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name: ONSI Repi 4/22/2008 9:45:19 AM Component: S/G A Page 16 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW 22 22 22 22 22 22 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 24 TUBE VOLTS 0.16 84 0.19 85 0.44 0.14 86 0.30 87 0.35 88 0.15 0.07 90 0.09 2

0.14 3

0.21 0.13 6

0.25 7

0.25 8

0.21 0.50 10 0.12 11 0.18 12 0.12 0.20 0.17 15 0.20 0.14 16 0.08 18 0.13 19 0.11 23 0.13 0.12 24 0.12 0.09 25 0.09 0.17 30 0.22 0.12 0.15 0.11 33 0.16 0.24 34 0.17 38 0.23 39 0.25 0.15 40 0.16 42 0.29 45 0.24 0.11 48 0.24 0.14 59 0.14 61 0.17 66 0.16 0.18 68 0.13 73 0.10 0.14 74 0.17 0.13 77 0.10 79 0.12 80 0.14 0.23 0.17 0.22 0.07 83 0.08 84 0.23 85 0.18 0.10 0.07 86 0.17 0.22 87 0.24 0.21 88 0.11 0.25 89 0.17 0.18 91 0.09 92 0.14 2

0.14 DEG CHN 150 P2 143 P2 142 P2 152 P2 137 P2 145 P2 128 P2 128 P2 148 P2 72 P2 143 P2

.86 P2 109 P2.

124 P2 121 P2 139 P2 131 P2 136 P2 135 P2 144 P2 139 P2 153 P2 150 P2 132 P2 143 P2 151 P2 144 P2 138 P2 120 P2 143 P2 136 P2 141 P2 129 P2 135 P2 130 P2 154 P2 128 P2 124 P2 127 P2 137 P2 136 P2 112 P2 138 P2 131 P2 126 P2 153 P2 139 P2 134 P2 142 P2 137 P2 140 P2 127 P2 137 P2 138 P2 150 P2 151 P2 147 P2 154 P2 144 P2 146 P2 146 P2 149 P2 146 P2 159 P2 144 P2 149 P2 140 P2 138 P2 130 P2 136 P2 124 P2 142 P2 141 P2 157 P2 149 P2 127 P2 140 P2 135 P2 100 P2 97 P2 IND %TW TWD 8 TWD 10 TWD' 19 TWD 7 TWD 15 TWD 16 TWO 8 TWD 4 TWO 5 TWD 8 TWD 12 TWD 8 TWD 13 TWD 14 TWD 11 TWO 22 TWD 7 TWO 10 TWD 7 TWD 11 TWD 9

TWD 11 TWD 8 TWD 5 TWD 8 TWD 6

TWD 7 TWD 7 TWD 7 TWD 6 TWD 5 TWD 10 TWD 12 TWD 7 TWD 8 TWD 6 TWD 9 TWD 13 TWD 10 TWD 12 TWD 13 TWD 9 TWD 9 TWD 15 TWD 13 TWD 6 TWD 13 TWO 8 TWD 8 TWD 9

TWO 9 TWD 10 TWD 7 TWD 5 TWD 7

TWD 9 TWD 7 TWD 5 TWD 6 TWD 7 TWD 11 TWD 9

TWD 11 TWO 4 TWD 5 TWO 11 TWD 9 TWD 6

TWD 4

TWD 9 TWD 11 TWD 12 TWD 11 TWD 6 TWD 12 TWD 9 TWD 9 TWD 5 TWD 7

TWD 8 LOCATION 014

+0.20 014

-0.49 010

-0.46 014

-0.49 010

-0.46 010

-0.44 010

-0.44 008

+0.27 010

-0.41 010

+0.66 010

-0.37 010

+0.64 010

+0.64 010

+0.61 010

+0.61 014

-0.41 010

+0.64 010

+0.61 010

+0.64 012

-0.46 012

+0.27 011

-0.49 011

+0.22 008

+0.24 013

-0.56 011

-0.49 009

+0.17 012

-0.59 009

+0.17 008

-0.48 008

+0.24 009

+0.17 012

-0.64 013

-0.64 013

+0.07 012

+0.12 011

-0.59 012

-0.63 011

-0.61 012

-0.63 009

+0.15 013

-0.69 009

+0.14 012

-0.63 009

+0.12 008

-0.55 009

+0.14 013

+0.05 010

+0.12 009

-0.56 013

+0.07 013

-0.66 012

+0.12 011

+0.19 011

-0.54 009

-0.53 011

+0.20 010

-0.53 009

-0.51 009

-0.53 010

-0.51 011

+0.22 013

-0.54 012

-0.54 014

+0.19 014

+0.20 009

-0.48 011

-0.44 011

+0.29 010

-0.49 011

+0.29 010

-0.45 014

+0.24 010

-0.46 014

-0.46 010

-0.44 013

-0.44 010

-0.41 010

+0.66 010

+0.66 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG PROBE 62 64 62 62 64 62 64 64 64 30 32 32 30 32 30 30 30 6

32 30 30 30 32 32 30 38 6

38 38 38 38 3

38 38 38 38 38 38 2

38 38 38 38 38 38 38 38 38 38 5

38 38 38 64 64 64 6

64 64 64 6

64 62 62 5

64 6

64 62 62 62 62 62 5

64 62 64 64 64 62 62 64 64 62 62 64 64 64 0

62 30 INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:19 AM Component: S/G A Page 17 of 97 ONS1AR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 TUBE 5

6 7

8 9

11 12 13 14 19 20 22 27 28 29 32 33 34 37 43 45 46 48 49 58 69 70 72 73 76 79 80 84 85 86 87 88 89 90 91 92 4

5 7

8 11 13 14 16 19 21 28 30 31 33 35 36 37 40 43 50 VOLTS DEG CHN IND %TW LOCATION EXT EXT 0.18 143 P2 TWD 10 009

+0.58 LTE UTE 0.21 124 P2 TWD 11 010

+0.64 LTE UTE 0.14 127 P2 TWD 8 011

-0.39 LTE UTE 0.22 127 P2 TWD 12 010

+0.63 LTE UTE 0.16 124 P2 TWD 9 010

+0.61 LTE UTE 0.41 145 P2 TWD 20 014

+0.27 LTE UTE 0.24 142 P2 TWD 13 010

+0.58 LTE UTE 0.27 138 P2 TWD 14 010

+0.61 LTE UTE 0.15 150 P2 TWD 9 013

-0.51 LTE UTE 0.12 150 P2 TWD 7 010

.,+0.61 LTE UTE 0.29 145 P2 TWD 15 012

-0.56 LTE UTE 0.28 149 P2 TWD 14 009

+0.53 LTE UTE 0.12 144 P2 TWD 7 008

+0.24 LTE UTE 0.23 118 P2 TWD 12 013

-0.64 LTE UTE 0.08 150 P2 TWD 5 009

-0.53 LTE UTE 0.12 141 P2 TWO 7 009

+0.17 LTE UTE 0.28 133 P2 TWD 14 013

-0.64 LTE UTE 0.39 132 P2 TWD 18 013

-0.66 LTE UTE 0.12 131 P2 TWD 7 013

+0.05 LTE UTE 0.17 140 P2 TWD 9 009

+0.15 LTE UTE 0.20 138 P2 TWD 11 009

+0.15 LTE UTE 0.16 133 P2 TWD 9 013

+0.05 LTE UTE 0.15 134 P2 TWD 8 013

-0.66 LTE UTE 0.16 114 P2 TWD 9 009

+0.12 LTE UTE 0.08 134 P2 TWD 5 008

+0.22 LTE UTE 0.11 139 P2 TWD 6 009

+0.12 LTE UTE 0.18 136 P2 TWD 10 011

-0.61 LTE UTE 0.13 138 P2 TWD 8 009

-0.64 LTE UTE 0.15 108 P2 TWD 9 008

-0.51 LTE UTE 0.09 142 P2 TWD 6 009

+0.14 LTE UTE 0.17 141 P2 TWD 9 009

-0.58 LTE UTE 0.19 127 P2 TWD '10 013

-0.68 LTE UTE 0.40 132 P2 TWD 18 012

-0.61 LTE UTE 0.11 114 P2 TWD 6 010

+0.17 LTE UTE 0.13 130 P2 TWD 8

012

-0.59 LTE UTE 0.12 142 P2 TWD 7 009

-0.51 LTE UTE 0.12 140 P2 TWD 7 013

+0.15 LTE UTE 0.37 133 P2 TWD 17 013

-0.58 LTE UTE 0.17 143 P2 TWD 9 014

-0.59 LTE UTE 0.25 146 P2 TWD 13 010

-0.54 LTE UTE 0.15 149 P2 TWD 8 011

-0.51 LTE UTE 0.19 144 P2 TWD 10 012

-0.49 LTE UTE 0.35 139 P2 TWD 17 013

-0.54 LTE UTE 0.28 138 P2 TWD 14 013

+0.20 LTE UTE 0.17 141 P2 TWD 9

014

+0.17 LTE UTE 0.17 138 P2 TWD 9 011

-0.46 LTE UTE 0.12 153 P2 TWD 6 011

-0.44 LTE UTE 0.09 135 P2 TWD 5 009

-0.48 LTE UTE 0.09 151 P2 TWD 5 009

-0.46 LTE UTE 0.13 129 P2 TWD 7 011

+0.29 LTE UTE 0.37 135 P2 TWD 17 010

-0.46 LTE UTE 0.12 138 P2 TWD 6 010

-0.46 LTE UTE 0.13 133 P2 TWD 7 010

-0.44 LTE UTE 0.08 147 P2 TWD 4 010

-0.46 LTE UTE 0.12 138 P2 TWD 6 008

+0.31 LTE UTE 0.11 147 P2 TWD 6 010

-0.41 LTE UTE 0.21 129 P2 TWD 11 010

-0.39 LTE UTE 0.13

'146 P2 TWD 8 010

-0.39 LTE UTE 0.08 87 P2 TWD 5 010

+0.61 LTE UTE 0.14 154 P2 TWD 8 014

-0.44 LTE UTE 0.23 153 P2 TWD 13 014

+0.27 LTE UTE 0.13 142 P2 TWD 7 010

+0.64 LTE UTE 0.23 138 P2 TWD 13 010

+0.59 LTE UTE 0.35 145 P2 TWD 18 010

+0.56 LTE UTE 0.13 145 P2 TWD 7 010

+0.61 LTE UTE 0.17 140 P2 TWD 10 013

-0.56 LTE UTE 0.09 123 P2 TWD 5 008

+0.24 LTE UTE 0.20 150 P2 TWD 11 012

-0.56 LTE UTE 0.15 122 P2 TWD 8 009

+0.17 LTE UTE 0.15 142 P2 TWO 9 011

-0.59 LTE UTE 0.45 138 P2 TWD 20 009

+0.17 LTE UTE 0.13 145 P2 TWD 7 011

-0.59 LTE UTE 0.17 123 P2 TWD 9 011

-0.64 LTE UTE 0.12 143 P2 TWD 7 008

-0.51 LTE UTE 0.19 134 P2 TWD 10 009

+0.15 LTE UTE 0.14 137 P2 TWD 8 009

+0.12 LTE UTE 0.23 130 P2 TWD 12 009

+0.12 LTE UTE 0.30 135 P2 TWO 15 009

+0.15 LTE UTE 0.07 144 P2 TWD 4 008

+0.12 LTE UTE 0.14 137 P2 TWD 8 009

+0.10 LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 32 30 30 32 30 32 32 30 98 30 34 34 34 34 34 34 34 34 5

34 34 34 34 6

34 0

603 34 34 34 0

605 0

603 38 38 64 64 62 0

593 64 64 62 62 64 64 64 64 64 64 64 62 64 62 0

62 64 62 64 62 64 64 30 32 32 32 32 30 32 32 30 30 34 34 34 34 34 34 34 6

34 34 34 34 34 34 34 INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET

.INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510UL 51OUL 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:19 AM Component:

S/G A Page 18 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 26 TUBE VOLTS 51 0.13 0.11 53 0.10 54 0.14 58 0.16 60 0.11 69 0.17 0.20 75 0.25 0.21 0.38 0.18 81 0.09 82 0.11 83 0.25 84 0.15 0.27 85 0.12 0.13 86 0.17 87 0.10 88 0.08 89 0.16 0.21 90 0.14 0.11 0.15 0.09 91 0.17 0.19 93 0.13 0.08 95 0.12 96 0.15 2

0.33 4

0.16 6

0.20 7

0.29 9

0.23 0.10 12 0.15 0.19 13 0.38 15 0.14 17 0.33 0.11 0.13 18 0.11 0.09 19 0.09 20 0.19 21 0.10 25 0.25 26 0.15 0.12 27 0.13 29 0.27 35 0.12 36 0.21 38 0.09 41 0.19 42 0.15 46 0.12 0.16 48 0.08 52 0.13 53 0.23 55 0.11 56 0.20 57 0.11 61 0.08 69 0.22 0.14 72 0.11 76 0.14 77 0.22 0.16 78 0.18 0.26 85 0.24 DEG CHN 145 P2 137 P2 129 P2 142 P2 131 P2 120 P2 128 P2 146 P2 128 P2 141 P2 134 P2 140 P2 148 P2 143 P2 144 P2 149 P2 143 P2 147 P2 147 P2 153 P2 136 P2 161 P2 145 P2 147 P2 151 P2 156 P2 129 P2 160 P2 140 P2 143 P2 149 P2 132 P2 131 P2 141 P2 121 P2 120 P2 99 P2 128 P2 142 P2 152 P2 139 P2 143 P2 137 P2 145 P2 147 P2 151 P2 144 P2 133 P2 148 P2 150 P2 147 P2 150 P2 147 P2 144 P2 145 P2 150 P2 136 P2 146 P2 152 P2 143 P2 137 P2 126 P2 144 P2 142 P2 108 P2 132 P2 139 P2 135 P2 145 P2 136 P2 131 P2 131 P2 142 P2 142 P2 144 P2 134 P2 140 P2 136 P2 128 P2 145 P2 IND %TW TWD 7 TWD 6 TWD 6 TWD 7 TWD 8 TWD 6 TWO 9 TWD 10 TWD 13 TWD 11 TWD 17 TWO 10 TWO 5 TWD 6 TWD 13 TWD 8 TWD 13 TWD 7 TWD 7 TWD 9 TWD 6 TWD 4 TWO 8 TWD 11 TWO 7 TWD 6 TWO 8 TWD 5 TWD 9 TWO 10 TWO 7 TWO 4 TWD 6 TWD 8 TWD 16 TWD 9 TWD 11 TWO 16 TWO 13 TWO 6 TWD 9 TWD 10 TWD 19 TWD 9 TWD 17 TWD 7 TWD 8 TWD 6 TWD 5 TWO 5 TWD 10 TWO 6 TWO 14 TWO 8 TWD 7 TWD 7 TWD 14 TWO 8 TWD 12 TWO 5 TWO 10 TWD 8 TWD 7 TWD 9 TWD 5 TWO 8 TWD 12 TWO 6 TWD 10 TWD 6 TWD 5 TWD 11 TWD 8 TWO 6 TWO 8 TWD 11 TWD 8 TWD 10 TWD 13 TWD 12 LOCATION 009

+0.15 013

+0.05 009

+0.12 010

-0.22 009

+0.02 011

+0.10 012

-0.63 012

+0.10 012

-0.59 012

+0.12 013

-0.61 013

+0.12 013

+0.17 009

-0.54 014

-0.58 013

-0.54 014

-0.56 013

+0.17 014

+0.17 009

-0.49 014

+0.20 011

-0.46 013

+0.24 014

+0.22 010

-0.49 011

-0.42 011

+0.29 012

-0.47 010

-0.46 014

+0.22 010

-0.44 008

+0.29 010

-0.41 008

-0.39 010

+0.66 010

-0.39 010

+0.61 010

+0.63 010

+0.61 011

-0.44 011

-0.44 013

-0.51 010

+0.58 012

-0.51 009

+0.56 011

-0.51 013

-0.56 008

+0.22 011

-0.49 008

+0.22 009

+0.53 011

-0.56 012

-0.61 010

+0.17 008

-0.50 009

+0.15 009

+0.17 011

-0.59 009

+0.12 009

+0.12 009

+0.10 009

+0.12 008

+0.19 009

+0.10 009

+0.12 009

+0.12 009

+0.12 009

+0.10 009

+0.12 012

-0.66 008

+0.19 012

-0.63 012

+0.10 010

+0.17 009

-0.53 009

-0.54 014

+0.02 009

-0.53 013

-0.63 011

-0.46 EXT EXT UTIL LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 1

UTIL 2

CAL # LEG PROBE 34 INLET 510XB 34 INLET 510XB 64 INLET 510XB 5

62 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 62 INLET 510XB 64 INLET 510XB 62 INLET 510XB 62 INLET 510XB 64 INLET 510XB 64 INLET 510XB 62 INLET 510XB 4

64 INLET 510XB 62 INLET 510XB 64 INLET 510XB 64 INLET 510XB 62 INLET 510XB 62 INLET 510XB 62 INLET 510XB 62 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 62 INLET 510XB 30 INLET 510XB 30 INLET 510XB 7

30 INLET 510XB 12 32 INLET 510XB 32 INLET 510XB 32 INLET 510XB 30 INLET 510XB 30 INLET 510XB 32 INLET 510XB 32 INLET 510XB 32 INLET 510XB 32 INLET 510XB 32 INLET 510XB 30 INLET 510XB 30 INLET 510XB 36 INLET 510XB 34 INLET 510XB 36 INLET 510XB 36 INLET 510XB 34 INLET 510XB 5

34 INLET 510XB 34 INLET 510XB 34 INLET 510XB 0

605 INLET 51OUL 5

603 INLET 51OUL 34 INLET 510XB 34 INLET 510XB 34 INLET 510XB 34 INLET 510XB 34 INLET 510XB 34 INLET 510XB 34 INLET 510XB 64 INLET 510XB 62 INLET 510XB 64 INLET 510XB 62 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 64 INLET 510XB 62 INLET 510XB 62 INLET 510XB 64 INLET 510XB 64 INLET 510XB 62 INLET 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:19 AM Component: S/G A Page 19 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMi[l]

Support Wear ROW TUBE VOLTS 26 88 0.09 26 91 0.16 0.15 26 92 0.10 26 93 0.15 26 94 0.12 0.13 26 95 0.09 26 96 0.13 26 97 0.22 27 7

0.22 27 8

0.19 27 9

0.25 0.16 0.13 27 11 0.30 27 13 0.18 0.16 27 18 0.31 27 25 0.18 27 26 0.37 27 30 0.28 27 31 0.16 27 37 0.08 27 40 0.08 27 48 0.05 27 49 0.16 27 53 0.15 0.08 0.32 0.25 27 55 0.40 0.23 0.23 0.32 0.17 27 59 0.09 27 61 0.14 0.20 0.06 27 63

0. 17 27 64
0. 10 27 66 0.12 27 68
0. 13 0.14 0.08 27 75 0.24 27 78 0.22 27 79 0.34 27 80 0.09 27 88 0.24 0.16 0.22 27 93 0.12 27 95 0.10 0.09 27 96 0.12 27 97 0.13 0.07 28 3

0.16 28 4

0.18 28 6

0.12 28 7

0.13 28 8

0.29 0.17 0.12 0.39 0.11 28 9

0.24 28 10 0.23 28 11 0.12 28 12 0.35 0.10 28 13 0.16 28 19 0.19 28 20 0.08 28 21 0.08 0.08 0.10 28 23 0.08 DEG 151 142 141 148 154 148 132 152.

134 140 131 136 134 135 139 135 150 145 144 150*

134 133 137 145 143 117 136 150 150 131 140 135 123 131 130 141 134 134 130 139 134 148 138 141 106 140 129 144 138 144 140 139 141 154 148 161 128 133 156 133 103 142 137 133 143 142 135 134 148 137 152 139 151 148 134 155 145 101 153 141 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P3 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW

-L-

-=

TWD 5 TWD 8 TWD 8 TWD 6 TWD 8 TWD 7 TWO 7 TWD 5 TWD 7 TWD II TWD 11 TWD 11 TWD 13 TWD 9 TWD 7 TWD 15 TWD 10 TWD 9 TWD 16 TWD 11 TWD 18 TWD 14 TWD 10 TWD 5 TWD 5 TWD 3 TWD 9 TWD 9 TWD 6 TWD 17 TWD 14 TWD 18 TWD 12 TWD 12 TWD 15 TWD 9 TWD 5 TWD 8 TWD 10 TWD 3 TWD 9 TWD 5 TWD 7 TWD 7 TWD 7 TWD 4 TWD 12 TWD 11 TWD 16 TWD 5 TWD 12 TWD 8 TWD 11 TWD 6 TWD 5 TWD 5 TWD 6 TWD 7 TWD 4 TWD 10 TWD 10 TWO 7 TWO 8 TWD 15 TWD 10 TWD 7 TWD 18 TWD 6 TWD 13 TWD 12 TWD 7 TWD 17 TWD 6 TWD 10 TWD 10 TWO 5 TWD 5 TWD 4 TWD 6 TWD 5 LOCATION 011

-0.46 010

-0.49 012

+0.27 010

-0.46 010

-0.46 010

-0.44 011

+0.32 010

-0.44 010

-0.41 014

-0.46 010

+0.63 010

+0.66 010

+0.61 011

-0.44 009

+0.58 010

+0.63 012

-0.46 013

+0.24 013

-0.59 011

-0.58 011

+0.17 009

+0.15 009

-0.61 009

+0.10 009

+0.12 009

+0.10 009

+0.12 013

-0.05 012

-0.05 012

-0.74 009

+0.05 009

+0.12 011

-0.66 011

+0.02 013

-0.68 013

+0.00 009

+0.10 009

+0.12 012

-0.65 010

+0.15 012

-0.63 009

+0.02 009

+0.12 012

+0.02 013

-0.68 009

+0.12 012

-0.63 009

-0.53 009

-0.56 013

+0.15 012

+0.24 013

+0.20 014

+0.17 010

-0.49 012

-0.44 010

-0.49 010

-0.44 010

+0.68 010

-0.46 010

+0.64 010

+0.63 010

-0.41 009

+0.58 010

+0.61 013

-0.44 014

-0.41 014

+0.27 010

-0.44 012

-0.42 010

+0.63 014

-0.51 010

+0.58 012

-0.49 012

+0.22 013

-0.61 009

+0.19 009

+0.19 008

+0.24 011

-0.58 008

+0.19 EXT LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE EXT UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

64 62 0

62 64 62 64 64 62 64 9

62 30 5

32 30 30 6

30 30 30 5

30 32 36 34 34 0

605 34 44 44 44 34 34 34 34 66 66 66 66 66 66 66 66 66 64 62 64 64 64 64 64 64 62 5

64 64 64 64 62 62 62 64 62 62 32 30 30 32 30 30 30 30 4

30 32 30 0

32 30 30 32 30 36 34 34 0

34 34 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET

INLET, INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXB

AREVA NP Inc Customer Name: ONSl Rep]

4/22/2008 9:45:19 AM Component: S/G A Page 20 of 97 ONSIAR-E0C24 -

Tube Support Wear QUERY: Query~l[1I ROW TUBE VOLTS 28 29 0.12 28 31 0.17 28 35 0.14 28 38 0.12 28 40 0.22 28 52 0.17 0.09 28 53 0.13 28 54 0.07 28 55 0.12 28 56 0.21 28 57 0.13 28 59 0.23 28 60 0.14 28 72 0.06 28 73 0.12 28 75 0.38 0.12 28 83 0.16 28 85 0.14 28 86 0.13 28 90 0.15 28 91 0.09 28 94 0.27 28 95 0.15 28 96 0.19 28 97 0.46 28 99 0.09 28 100 0.28 28 101 0.08 29 1

0.33 0.51 29 4

0.10 29 5

0.17 29 6

0.11 0.20 29 8

0.09 29 9

0.15 0.11 0.28 0.21 29 10 0.12 0.20 0.13 29 11 0.18 0.12 29 16 0.22 29 19 0.28 0.09 29 20 0.10 29 21 0.11 29 24 0.26 0.15 29 25 0.14 0.10 29 28 0.12 29 29 0.17 29 32 0.39 0.15 29 34 0.09 29 36 0.14 29 37 0.37 29 43 0.15 29 49 0.10 29 52 0.12 29 57 0.17 0.09 29 62 0.18 29 63 0.11 29 76 0.08 29 77 0.22 29 85 0.14 29 90 0.08 29 91 0.14 29 92 0.13 29 96 0.24 0.11 0.27 29 97 0.17 0.15 DEG CHN 136 P2 143 P2 111 P2 139 P2 125 P2 116 P2 118 P2 127 P2 128 P2 133 P2 133 P2 118 P2 135 P2 146 P2 138 P2 144 P2 120 P2 142 P2 140 P2 129 P2 150 P2 147 P2 156 P2 139 P2 155 P2 139 P2 140 P2 150 P2 140 P2 154 P2 147 P2 135 P2 131 P2 85 P2 145 P2 152 P2 152 P2 152 P2 145 P2 133 P2 144 P2 150 P2 140 P2 138 P2 134 P2 148 P2 149 P2 139 P2 150 P2 154 P2 140 P2 137 P2 147 P2 148 P2 106 P2 92 P2 120 P2 127 P2 145 P2 135 P2 138 P2 138 P2 141 P2 141 P2 131 P2 130 P2 141 P2 124 P2 140 P2 139 P2 142 P2 122 P2 151 P2 149 P2 149 P2 135 P2 141 P2 143 P2 150 P2 153 P2 IND %TW TWD 7 TWD 9 TWD 8 TWD 7 TWD 12 TWD 9 TWD 5 TWD 7 TWD 4 TWD 7 TWD 11 TWD 7 TWD 12 TWD 8 TWD 4 TWD 7 TWD 17 TWD 6 TWD 8 TWD 7 TWD 7 TWD 8 TWD 5 TWD 13 TWD 8 TWD 10 TWD 20 TWD 5 TWD 14 TWD 4 TWD 17 TWD 24 TWO 6 TWD 9 TWD 7 TWD 11 TWD 6 TWD 8 TWD 6 TWD 14 TWD 11 TWO 7 TWD 11 TWD 8 TWD 10 TWD 7 TWD 12 TWD 14 TWD 5 TWD 6 TWD 6 TWD 14 TWD 8 TWD 9 TWD 6 TWD 7 TWD 9 TWD 18 TWO 9 TWD 5 TWD 8 TWD 18 TWD 10 TWD 8 TWD 6 TWD 9 TWD 5 TWD 10 TWD 6 TWD 5 TWD 10 TWO 7 TWD 5 TWD 7 TWD 7 TWD 12 TWD 6 TWD 13 TWD 9 TWD 8 LOCATION EXT EXT UTIL 1

009

+0.15 LTE UTE WAR 009

+0.15 LTE UTE WAR 011

-0.61 LTE UTE WAR 008

+0.17 LTE UTE WAR 012

-0.66 LTE UTE WAR 009

-0.60 LTE UTE WAR 013

+0.05 LTE UTE WAR 009

-0.60 LTE UTE WAR 008

+0.12 LTE UTE WAR 009

-0.58 LTE UTE WAR 009

-0.61 LTE UTE WAR 009

-0.52 LTE UTE WAR 014

-0.71 LTE UTE WAR 008

-0.54 LTE UTE WAR 010

+0.17 LTE UTE WAR 013

+0.02 LTE UTE WAR 014

-0.68 LTE UTE WAR 014

+0.02 LTE UTE WAR 013

-0.61 LTE UTE WAR 013

-0.58 LTE UTE WAR 011

-0.49 LTE UTE WAR 012

-0.51 LTE UTE WAR 008

-0.46 LTE UTE WAR 010

-0.46 LTE UTE WAR 010

-0.49 LTE UTE WAR 013

-0.46 LTE UTE WAR 010

-0.46 LTE UTE WAR 010

-0.41 LTE UTE WAR 011

-0.36 LTE UTE WAR 013

-0.39 LTE UTE WAR 015

-0.39 LTE UTE WAR 015

+0.63 LTE UTE WAR 010

-0.39 LTE UTE WAR 010

+0.66 LTE UTE WAR 014

-0.42 LTE UTE WAR 014

+0.27 LTE UTE WAR 010

-0.41 LTE UTE WAR 009

+0.58 LTE UTE WAR 010

-0.44 LTE UTE WAR 010

+0.64 LTE UTE WAR 011

-0.44 LTE UTE WAR 012

-0.44 LTE UTE WAR 010

+0.59 LTE UTE WAR 009

+0.66 LTE UTE WAR 010

+0.63 LTE UTE WAR 011

-0.44 LTE UTE WAR 010

+0.56 LTE UTE WAR 010

+0.56 LTE UTE WAR 011

-0.51 LTE UTE WAR 008

+0.19 LTE UTE WAR 009

+0.19 LTE UTE WAR 009

+0.17 LTE UTE WAR 011

-0.56 LTE UTE WAR 008

+0.22 LTE UTE WAR 013

-0.61 LTE UTE WAR 013

-0.69 LTE UTE WAR 013

-0.66 LTE UTE WAR 012

-0.66 LIE UTE WAR 012

+0.05 LTE UTE WAR 009

+0.10 LTE UTE WAR 009

+0.12 LTE UTE WAR 009

+0.12 LTE UTE WAR 009

-0.59 LTE UTE WAR 008

-0.67 LTE UTE WAR 009

+0.10 LTE UTE WAR 013 40.00 LTE UTE WAR 009

+0.10 LTE UTE WAR 010

+0.02 LTE UTE WAR 009

+0.02 LTE UTE WAR 009

+0.02 LTE UTE WAR 011

-0.59 LTE UTE WAR 013

-0.63 LTE UTE WAR

011,

-0.49 LTE UTE WAR 012

-0.56 LTE UTE WAR 011

-0.46 LTE UTE WAR 010

-0.46 LTE UTE WAR 011

-0.44 LTE UTE WAR 012

-0.46 LTE UTE WAR 010

-0.49 LTE UTE WAR 011

+0.27 LTE UTE WAR UTIL 2

CAL # LEG PROBE 34 34 34 44 48 52 52 52 66 66 66 0

567 66 0

567 64 62 64 4

64 9

62 0

62 64 64 62 64 6

62 64 62 62 64 62 32 32 32 7

30 32 32 32 30 30 30 30 32 32 32 30 30 32 30 30 32 30 34 34 36 36 36 34 34 34 34 34 48 5

597 6

589 52 66 3

66 66 66 64 0

591 7

62 64 62 64 64 64 64 62 62 INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB N*

AREVA NP Inc Customer Name: ONSl Rep]

4/22/2008 9:45:19 Am Component: S/G A Page 21 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: Queryil~l]

ROW TUBE VOLTS 29 98 0.12 29 102 0.15 0.14 29 104 0.21 30 1

0.24 30 2

0.25 30 5

0.09 30 7

0.36 30 9

0.32 30 10 0.18 0.12 30 11 0.20 30 14 0.12 30 16 0.18 30 21 0.09 0.11 30 27 0.13 30 28 0.13 30 30 0.12 30 31 0.12 30 32 0.26 0.11 30 35 0.09 30 39 0.07 30 45 0.22 30 52 0.30 30 53 0.18 30 57 0.10 0.09 30 58 0.13 0.08 30 59 0.16 30 61 0.13 30 67 0.10 30 85 0.23 30 88 0.08 30 93 0.11 0.12 30 94 0.38 30 97 0.14 0.22 0.38 0.21 0.21 0.36 0.17 0.13 30 98 0.16 0.23 0.18 0.07 30 102 0.11 0.13 0.10 30 104 0.08 31 1

0.17 31 7

0.23 0.11 31 8

0.09 0.11 31 9

0.14 0.24 31 10 0.14 0.14 0.19 31 16 0.21 31 21 0.09 31 22 0.06 31 24 0.12 31 27 0.20 0.26 31 28 0.16 31 30 0.12 31 31 0.14 31 40 0.11 31 44 0.15 31 48 0.13 31 49 0.14 31 50 0.10 31 51 0.18 DEG CHN 136 P2 121 P2 125 P2 132 P2 100 P2 121 P2 148 P2 145 P2 140 P2 141 P2 145 P2 151 P2 155 P2 142 P2 128 P2 129 P2 139 P2 122 P2 127 P2 125 P2 131 P2 133 P2 143 P2 147 P2 145 P2 144 P2 144 P2 140 P2 135 P2 130 P2 132 P2 135 P2 122 P2 129 P2 144 P2 147 P2 145 P2 137 P2 141 P2 136 P2 142 P2 134 P2 149 P2 135 P2 133 P2 137 P2 128 P2 148 P2 142 P2 142 P2 128 P2 147 P2 94 P2 132 P2 140 P2 137 P2 151 P2 155 P2 142 P2 139 P2 141 P2 143 P2 147 P2 136 P2 142 P2 140 P2 146 P2 151 P2 136 P2 137 P2 131 P2 142 P2 156 P2 137 P2 134 P2 123 P2 142 P2 137 P2 138 P2 143 P2 IND TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWD TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO

%TW LOCATION 7

010

-0.45 8

010

+0.63 7

013

-0.39 11 010

+0.68 13 010

+0.61 13 010

+0.66 6

010

-0.41 18 014

-0.42 17 010

+0.59 10 010

+0.59 7

011

-0.44 11 012

-0.46 7

009

+0.56 10 013

-0.59 5

008

+0.22 6

012

-0.58 8

013

+0.05 7

013

-0.66 8

009

-0.57 7

013

+0.07 13 009

+0.12 6

013

+0.05 6

009

-0.66 5

008

+0.17 11 009

+0.10 14 009

+0.10 10 009

+0.02 5

008

+0.15 5

009

+0.07 7

009

+0.10 4

010

+0.02 9

009

+0.10 8

008

-0.64 6

013

-0.74 14 011

-0.45 6

009

-0.60 7

014

-0.61 8

014

+0.16 21 012

-0.55 9

013

+0.21 13 013

-0.53 20 012

+0.18 13 012

-0.56 13 011

+0.24 19 011

-0.48 11 010

-0.51 8

009

-0.56 10 013

+0.26 14 013

-0.50 12 010

-0.50 5

011

+0.26 8

011

+0.29 9

010

+6.58 7

010

-0.50 6

010

-0.45 10 010

+0.64 13 014

-0.44 7

014

+0.27 5

012

-0.44 6

011

+0.29 8

009

+0.58 13 010

+0.59 8

011

-0.41 8

009

+0.58 10 010

+0.59 11 013

-0.56 6

008

+0.24 4

008

+0.17 7

011

-0.61 11 009

+0.17 13 014

-0.64 9

013

+0.05 7

011

+0.10 8

011

+0.10 7

009

-0.59 8

009

-0.60 7

009

+0.10 9

009

+0.08 5

009

+0.05 10 009

+0.02 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG PROBE 64 10 64 7

64 0

62 32 30 32 32 32 8

30 4

30 32 30 30 30 30 0

603 34 0

605 0

603 34 34 0

597 54 52 52 54 66 66 66 66 66 5

569 8

569 24 26 24 4

24 26 24 24 24 24 24 24 24 24 26 26 26 4

26 26 26 26 26 32 32 32 30 4

30 32 32 30 7

30 7

30 30 32 30 36 34 34 0

603 36 34 5

597 52 52 34 52 54 INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510UL 510UL 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

ONSI Reol 4/22/2008 9:45:19 AM Component: S/G A Page 22 of 97 Customer Name: ONS1 Repl ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 31 55 0.19 31 56 0.09 31 59 0.12 0.11 31 66 0.15 0.19 31 72 0.09 31 88 0.26 31 89 0.14 31 98 0.10 31 99 0.10 0.14 31 100 0.14 31 101 0.24 0.10 31 102 0.07 0.11 31 103 0.09 0.30 0.09 0.15 0.15 0.15 0.10 31 104 0.32 0.16 0.17 0.16 31 106 0.12 0.24 32 3

0.13 32 5

0.09 0.12 32 6

0.16 32 9

0.14 0.18 32 10 0.13 0.31 32 11 0.15 32 12 0.09 32 16 0.16 0.11 32 21 0.20 32 22 0.07 32 23 0.08 32 27 0.11 32 28 0.10 32 29 0.08 32 31 0.15 32 33 0.12 32 35 0.09 0.09 32 36 0.16 0.06 32 37 0.11 32 41 0.11 32 45 0.12 32 49 0.12 32 56 0.14 32 67 0.16 32 72 0.15 32 73 0.12 32 75 0.10 32 82 0.12 32 86 0.09 0.08 32 91 0.12 32 95 0.19 0.12 32 97 0.17 0.11 0.15 32 98 0.11 32 99 0.13 0.08 0.24 0.13 32 101 0.08 0.29 0.14 DEG CHN IND %TW LOCATION 144 P2 TWD 10 009

+0.10 135 P2 TWO 5 009

+0.02 128 P2 TWD 7 009

+0.02 146 P2 TWD 6 013

-0.02 133 P2 TWD 8 009

+0.10 132 P2 TWD 10 013

-0.02.

112 P2 TWD 6 009

-0.66 137 P2 TWD 16 009

-0.60 143 P2 TWD 9 012

-0.60 146 P2 TWD 7 010

-0.50 145 P2 TWD 7 012

+0.24 148 P2 TWD 9 010

-0.50 138 P2 TWD 9 010

-0.50 136 P2 TWD 14 012

-0.42 147 P2 TWD 7 010

-0.50 155 P2 TWO 5 012

+0.26 141 P2 TWD 8 010

-0.50 149 P2 TWD 6 013

+0.29 139 P2 TWD 17 012

+0.32 130 P2 TWD 6 012

-0.11 147 P2 TWD 10 011

+0.32 121 P2 TWD 9 011

-0.37 129 P2 TWD 10 010

-0.50 133 P2 TWD 6 012

-0.45 137 P2 TWD 18 013

-0.42 137 P2 TWD 10 012

+0.26 137 P2 TWO 11 011

+0.29 136 P2 TWD 11 010

-0.47 136 P2 TWD 8 013

-0.42 118 P2 TWD 14 010

+0.58 77 P2 TWD 7 010

+0.63 118 P2 TWD 5 010

-0.41 72 P2 TWD 7 010

+0.63 147 P2 TWD 10 010

-0.44 147 P2 TWD 8 009

+0.58 137 P2 TWD 10 011

-0.44 140 P2 TWO 8 009

+0.58 143 P2 TWD 16 010

+0.56 131 P2 TWD 8 010

+0.61 157 P2 TWD 6 011

-0.49 152 P2 TWD 10 013

-0.56 151 P2 TWD 7 013

+0.17 136 P2 TWD 11 014

-0.61

.148 P2 TWD 4 009

+0.12 156 P2 TWD 5 010

+0.17 147 P2 TWD 7 009

-0.54 22 P2 TWD 6 013

-0.66 150 P2 TWD 4 008

+0.17 137 P2 TWD 9 009

-0.56 90 P2 TWD 7 008

+0:17 149 P2 TWD 5 009

+0.10 150 P2 TWD 5 012

+0.05 140 P2 TWD 9 009

+0.12 94 P2 TWD 4 008

+0.10 134 P2 TWD 6 011

+0.07 148 P2 TWD 6 009

+0 12 148 P2 TWD 6 009

+0 10 94 P2 TWD 6 009

-0 60 140 P2 TWD 7 009

-0 60 106 P2 TWD 9 012

-0 71 143 P2 TWD 8 009

+0 12 132 P2 TWD 6 009

+0 02 138 P2 TWD 6 009

+0 05 135 P2 TWO 8 015

-0.75 149 P2 TWO 6 011

-0.56 155 P2 TWD 5 009

-0.64 138 P2 TWO 8 012

-0.58 138 P2 TWD 12 012

-0.60 147 P2 TWD 8 012

+0.16 144 P2 TWD 11 011

-0.45 152 P2 TWD 7 012

-0.53 150 P2 TWD 10.

010

+0.50 153 P2 TWD 7 013

+0.18 143 P2 TWO 8 012

+0.24 155 P2 TWO 6 012

-0.55 140 P2 TWD 14 011

-0.42 138 P2 TWD 8 009

-0.55 150 P2 TWD 5 011

+0.26 135 P2 TWD 16 010

-0.48 118 P2 TWD 9 010

+0.61 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE ATE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTIL 2

CAL # LEG 52 INLET 54 INLET 66 INLET 66 INLET 66 INLET 66 INLET 24 OUTLET 26 OUTLET 24 OUTLET 26 OUTLET 24 OUTLET 24 OUTLET 26 OUTLET 24 OUTLET 2

24 OUTLET 26 OUTLET 26 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 4

24 OUTLET 26 OUTLET 26 OUTLET 26 OUTLET 26 OUTLET 26 OUTLET 26 OUTLET 30 INLET 30 INLET 6

30 INLET 32 INLET 30 INLET 30 INLET 32 INLET 32 INLET 6

30 INLET 32 INLET 32 INLET 32 INLET 30 INLET 30 INLET 36 INLET 0

603 INLET 36 INLET 34 INLET 36 INLET 48 INLET 48 INLET 48 INLET 48 INLET 48

. INLET 52 INLET 52 INLET 52 INLET 52 INLET 52 INLET 0

567 INLET 66 INLET 66 INLET 24 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 0

24 OUTLET 24 OUTLET 8

24 OUTLET 6

24 OUTLET 26 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 7

24 OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB.

510XB 510XB 510XB 510XL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB

AREVA NP Inc Customer Name:

rNS1 Rep]

4/22/2008 9:45:20 AM Component: S/G A Page 23 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: Query~l[1]

ROW 32 32 32 32 32 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 34 34 34 34 34 34 34 34 34 34 34 TUBE VOLTS 102 0.08 0.21 104 0.10 0.09 0.67 105 0.12 106 0.10 0.16 107 0.21 1

0.08 3

0.16 0.09 4

0.14 5

0.25 10 0.18 0.12 12 0.16 17 0.09 18 0.10 19 0.09 0.26 0.10 21 0.08 22 0.09 23 0.12 26 0.12 27 0.09 0.13 29 0.21 0.08 31 0.11 37 0.09 40 0.09 42 0.17 49 0.12 50 0.07 0.13 51 0.41 52 0.24 0.07 55 0.22 59 0.10 74 0.11 86 0.11 87 0.13 91 0.10 96 0.06 0.09 97 0.11 98 0.12 99 0.10 100 0.11 0.17 0.20 101 0.47 102 0.26 0.24 103 0.10 0.29 0.24 0.13 104 0.14 0.07 105 0.12 106 0.17 1

ý0.25 4

0.16 5

0.19 7

0.08 8

0.23 10 0.15 0.20 0.15 0.07 11 0.18 0.11 12 0.14 15 0.10 16 0.11 18 0.10 DEG CHN 149 P2 141 P2 143 P2 146 P2 127 P2 141 P2 145 P2 133 P2 125 P2 132 P2 131 P2 138 P2 60 P2 122 P2 146 P2 148 P2 126 P2 153 P2 136 P2 152 P2 151 P2 149 P2 136 P2 128 P2 134 P2 157 P2 144 P2 111 P2 151 P2 160 P2 116 P2 154 P2 151 P2 141 P2 145 P2 150 P2 139 P2 138 P2 141 P2 161 P2 137 P2 116 P2 136 P2 139 P2 137 P2 150 P2 158 P2 136 P2 151 P2 150 P2 136 P2 154 P2 147 P2 146 P2 132 P2 140 P2 142 P2 141 P2 134 P2 135 P2 136 P2 145 P2 132 P2 132 P2 137 P2 123 P2 121 P2 116 P2 140 P2 139 P2 147 P2 141 P2 144 P2 152 P2 151 P2 145 P2 122 P2 150 P2 148 P2 145 P2 IND %TW LOCATION TWD 6 014

-0.53 TWD 13 010

-0.53 TWD 7 013

+0.29 TWD 6

'011

-0.37 TWD 30 010

-0.50 TWD 8 010

-0.51 TWD 7 011

+0.32 TWD 10 010

-0.42 TWD 13 010

+0.60 TWD 5 007

-0.41 TWD 9 010

+0.63 TWD 5 012

-0.34 TWD 8 010

+0.63 TWD 14 010

+0.61 TWD 10 010

+0.59 TWD 7 011

-0.44 TWD 9 012

+0.22 TWD 6 008

+0.22 TWD 6 008

+0.24 TWD 6 008

+0.17 TWD 14 010

+0.15 TWD 6 012

-0.61 TWD 5 008

+0.22 TWD 5 008

+0.22 TWD 7 010

+0.15 TWD 7 009

+0.15 TWD 5 009

+0.14 TWD 7 013

-0.69 TWD 12 009

+0.15 TWD 5 011

+0.07 TWD 7 008

-0.66 TWD 5 008

+0.12 TWO 5 009

+0.12 TWD 9 009

+0.10 TWD 6 009

+0.07 TWD 4 009

+0.05 TWD 8 008

-0.60 TWD 18 009

+0.10 TWD 13 009

+0.02 TWD 4 010

+0.02 TWD 11 009

+0.10 TWD 6 011

+0.02 TWD 6 009

+0.10 TWD 7 012

-0.69 TWD 8 014

-0.72 TWD 6 012

-0.72 TWD 4 009

-0.55 TWD 6 012

+0.03 TWD 7 012

-0.64 TWD 8 011

-0.47 TWD 7 012

+0.21 TWO 7 012

-0.53 TWD 11 011

+0.26 TWD 12 011

-0.45.

TWD 24 011

-0.43 TWD 15 013

-0.47 TWD 15 010

-0.50 TWD 6 014

+0.21 TWD 16 014

-0.50 TWD 14 010

-0.48 TWD 8 012

+0.29 TWD 9 014

-0.50 TWO 5 010

-0.52 TWO 8 013

-0.43 TWD 11 010

-0.50 TWO 14 010

+0.64 TWD 9 010

+0.66 TWD 11 010

+0.63 TWD 5 010

-0.44 TWD 12 010

-0.44 TWD 8 010

-0.46 TWD 11 010

+0.61 TWD 9 011

-0.44 TWD 4 009

-0.41 TWO 10 010

+0.58 TWD 7 011

-0.49 TWD 8 010

+0.58 TWD 6 012

-0.54 TWD 6 014

-0.56 TWD 6 008

+0.22 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL 26 26 26 26 26 24 26 26 26 4

4 98 98 30 32 30 5

30 30 32 30 32 32 32 32 30 30 36 34 34 36 36 0

605 52 52 52 52 54 4

54 52 54 54 52 66 66 24 24 24 26 4

26 24 26 24 26 26 26 24 26 26 24 24 24 4

24 26 2

26 3

24 26 4

30 32 32 30 30 30 30 30 10 98 6

98 5

30 32 30 30

  1. LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB

AREVA NP Inc Customer Name:

lNSl Repi 4/22/2008 9:45:20 AM Component: S/G A Page 24 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[1]

ROW TUBE VOLTS 0.22 0.14 0.13 34 19 0.08 34 22 0.12 34 23 0.06 34 24 0.11 34 25 0.14 0.15 34 26 0.14 34 30 0.16 0.15 0.12 34 37-0.11 0.11 34 38 0.11 34 40 0.30 0.21 34 43 0.46 34 44 0.10 34 48 0.13 34 52 0.09 34 53 0.18 34 58 0.21 34 69 0.14 0.12 34 72 0.15 34 75 0.11 34 82 0.11 34 88 0.09 34 91 0.13 34 96 0.09

,0.11 34 100 0.13 0.13 0.07 34 101 0.20 0.56 0.10 0.14 0.28 34 102 0.13 0.07 0.24 0.10 34 104 0.08 0.24 34 105 0.20 0.24 34 106 0.32 34 107 0.15 34 109 0.09 35 4

0.10 35 5

0.15 35 6

0.19 35 7

0.11 35 10 0.08 0.20 0.11 35 11 0.15 0.09 0.08 35 12 0.16 35 14 0.19 35 17 0.08 35 19 0.20 35 23 0.09 0.09 35 25 0.05 0.07 35 26 0.13 0.10 35 31 0.21 35 33 0.13 35 34 0.44 35 35 0.20 35 38 0.24 35 40 0.19 35 45 0.42 35 56 0.08 DEG CHN 140 P2 143 P2 146 P2 153 P2 122 P2 148 P2 58 P2 120 P2 112 P2 142 P2 136 P2 125 P2 122 P2 122 P2 149 P2 153 P2 132 P2 96 P2 133 P2 130 P2 141 P2 123 P2 147 P2 138 P2 137 P2 140 P2 128 P2 148 P2 132 P2 124 P2 123 P2 151 P2 150 P2 146 P2 139 P2 154 P2 143 P2 132 P2 160 P2 127 P2 140 P2 148 P2 158 P2 138 P2 139 P2 140 P2 140 P2 142 P2 137 P2 137 P2 139 P2 138 P2 139 P2 93 P2 118 P2 139 P2 154 P2 138 P2 146 P2 145 P2 147 P2 157 P2 149 P2 150 P2 153 P2 134 P2 152 P2 141 P2 158 P2 129 P2 141 P2 148 P2 126 P2 150 P2 139 P2 132 P2 147 P2 136 P2 135 P2 149 P2 IND %TW TWD 11 TWD 8 TWD 7 TWD 5 TWD 9 TWD 3 TWD 7 TWD 8 TWD 9 TWD 9 TWD 9 TWD 9 TWD 7 TWD 6 TWD 7 TWD 6 TWD 14 TWD 11 TWD 20 TWD 7 TWD 7 TWD 5 TWD 10 TWD 11 TWD 8 TWD 6 TWD 8 TWD 6 TWD 7 TWD 6 TWD 8 TWD 6 TWD 8 TWD 9 TWD 9 TWD 5 TWD 12 TWD 26 TWD 6 TWD 9 TWD 16 TWD 9 TWD 5 TWD 15 TWD 7 TWD 5 TWD 15 TWD 12 TWD 14 TWD 18 TWD 10 TWD 6 TWD 6 TWD 8 TWD 11 TWD 6 TWD 5 TWD 12 TWD 7 TWD 9 TWD 5 TWD 5 TWD 10 TWD 11 TWD 5 TWD 11 TWD 6 TWD 6 TWO 3 TWD 4 TWD 7 TWD 6 TWD 11 TWD 8 TWD 19 TWD 10 TWD 12 TWD 9 TWD 18 TWD 5 LOCATION 010

+0.19 012

-0.56 013

-0.63 011

-0.51 011

-0.57 009

+0.14 012

-0.66 012

-0.63 013

-0.61 012.

-0.63 010

+0.10 011

-0.61 013

-0.71 008

-0.55 013

-0.71 009

+0.10 009

+0.10 012

-0.71 009

+0.12 009

-0.67 007

+0.20 009

-0.60 009

+0.02 009

+0.07 009

+0.12 010

+0.02 008

-0.59 009

+0.12 008

+0.16 012

-0.68 012

-0.69 011

-0.50 009

-0.58 013

-0.55 011

-0.45 010

-0.47 011

+0.24 011

-0.45 013

-0.50 013

+0.21 010

+0.58 012

+0.21 012

-0.50 011

-0.45 014

+0.16 011

-0.42 010

-0.47 014

+0.24 010

-0.53 010

-0.52 010

-0.45 010

-0.40 011

-0.39 010

+0.63 010

+0.64 010

-0.44 009

-0.46 009

+0.56 010

-0.46 010

+0.61 011

-0.44 012

-0.46 010

+0.59 010

+0.56 012

-0.54 012

-0.56 008

+0.10 011

-0.61 008

+0.17 009

+0.12 009

+0,15 010

-0.58 012

-0.71 009

+0.02 009

+0.10 011

+0.07 009

+0.10 009

+0.10 009

+0.10 009

+0.02 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR 0

WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR 6

WAR 7

WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR CAL #

30 30 30 32 607 30 36 34 34 36 34 34 34 54 54 52 52 52 52 597 587 52 54 66 66 66 567 66 24 24 24 26 26 26 26 26 24 24 24 24 24 26 26 26 26 26 26 24 24 26 24 24 32 30 32 30 32 32 32 30 30 30 32 32 30 30 32 32 36 36 34 34 48 54 52 52 52 52 52 54 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB

AREVA NP Inc Customer Name:

rNSl Rep]

4/22/2008 9:45:20 AM Component: S/G A Page 25 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: Query~l(1]

ROW TUBE VOLTS 35 74 0.11 35 85 0.10 0.11 35 88 0.16 35 89 0.12 0.09 35 92 0.10 35 93 0.21 35 94 0.19 35 95 0.07 35 99 0.14 35 100 0.07 35 101 0.22 0.15 35 102 0.17 0.57 0.13 0.36 35 104 0.25 0.19 0.29 0.15 35 105 0.23 35 107 0.17 35 108 0.07 35 109 0.12 36 5

0.22 36 6

0.13 0.19 36 11 0.17 0.11 36 12 0.22 36 13 0.12 36 17 0.12 36 20 0.25 36 22 0.25 0.13 36 23 0.18 36 25 0.07 36 28 0.12 0.08 36 29 0.18 36 31 0.17 36 33 0.39 0.22 36 37 0.18 36 43 0.09 0.13 36 46 0.15 36 59 0.17 36 60 0.20 36 62 0.12 36 63 0.10 36 66 0.12 0.09 36 68 0.12 36 79 0.11 0.07 36 88 0.12 36 92 0.13 0.19 36 96 0.30 36 103 0.18 36 104 0.14 36 105 0.09 0.34 0.09 0.23 0.52 0.20 36 106 0.25 36 107 '0.23 36 108 0.13 0.20 36 109 0.18 36 110 0.26 36 112 0.16 36 113 0.29 0.13 0.16 DEG CHN 148 P2 151 P2 142 P2 134 P2 150 P2 150 P2 145 P2 146 P2 141 P2 142 P2 144 P2 157 P2 142 P2 145 P2 147 P2 132 P2 143 P2 140 P2 142 P2 138 P2 136 P2 144 P2 133 P2 136 P2 128 P2 138 P2 128 P2 106 P2 108 P2 143 P2 146 P2 135 P2 148 P2 155 P2 142 P2 138 P2 138 P2 147 P2 126 P2 114 P2 156 P2 131 P2 132 P2 136 P2 104 P2 134 P2 46 P2 150 P2 151 P2 139 P2 130 P2 125 P2 140 P2 128 P2 118 P2 145 P2 136 P2 96 P2 129 P2 150 P2 143 P2 132 P2 131 P2 140 P2 148 P2 139 P2 139 P2 145 P2 133 P2 143 P2 140 P2 138 P2 136 P2 140 P2 137 P2

'132 P2 141 P2 130 P2 138 P2 137 P2 IND %TW TWO 6 TWD 6 TWD 7 TWO 10 TWD 80 TWD 8 TWO 6 TWO 6 TWD 13 TWD 12 TWD 5 TWD 9 TWO 5 TWD 13 TWD 10 TWD 11 TWD 27 TWO 9 TWD 20 TWD 15 TWD 12 TWD 17 TWD 10 TWD 14 TWD 11 TWD 5 TWD 8 TWD 12 TWD 7 TWD 10 TWD 10 TWD 7 TWD 11 TWD 7 TWO 7 TWD 13 TWD 13 TWD 7 TWD 10 TWD 4 TWD 7 TWD 5 TWD 10 TWD 9 TWO 18 TWD 12 TWD 9 TWD 5 TWD 7 TWD 8 TWD 9 TWD 10 TWO 7 TWD 5 TWD 6 TWD 5 TWD 7 TWD 6 TWD 4 TWD 8 TWD 9 TWD 12 TWD 18 TWD 12 TWD 9 TWD 6 TWD 19 TWD 6 TWD 14 TWD 26 TWD 13 TWD 15 TWD 14 TWD 9 TWD 13 TWD 11 TWD 16 TWD 11 TWD 17 TWD 9 TWD 11 LOCATION 013

-0.02 011

-0.61 009

-0.66 012

-0.68 011

-0.53 009

-0.61 011

-0.53 009

-0.55 014

+0.03 009

-0.55 011

-0.45 011

-0.45 011

-0.45 010

+0.56 012

+0.18 011

-0.47 013

+0.03 010

+0.58 014

+0.03 012

+0.26 012

-0.47 011

+0.26 010

-0.48 010

-0.53 010

-0.45 010

+0.61 010

+0.63 010

-0.41 010

+0.59 010

+0.59 011

-0.46 010

+0.61 009

+0.56 012

-0.54 013

-0.58 012

-0.58 012

+0.15 011

+0.12 008

+0.17 010

-0.58 010

+0.10 009

+0.12) 012

-0.69 009

+0.15 012

-0.67 009

+0.10 008

+0.12 009

+0.10 009

+0.07 009

+0.10 009

+0.10 009

+0.02 009

+0.02 009

-0.63 009

+0.02 008

-0.69 009

-0.60 008

+0.10 012

-0.69 011

-0.58 009

-0.64 014

-0.72 011

-0.45 010

+0.61 013

+0.24 013

-0.53 012

+0.21 012

-0.51 011

-0.40 010

+0.56 010

-0.48 010

-0.56 013

-0.48 010

-0.50 010

-0.50 013

-0.45 013

-0.40 015

+0.58 013

+0.32 011

+0.32 EXT EXT LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL I

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

66 24 24 24 24 24 24 24 26 24 5

24 5

26 24 6

24 26 26 6

26 16 26 26 26

,26 26 24 24 4

26 8

24 32 30 30 32 32 30 32 32 30 30 5

30 98 30 36 36 34 48 48 48 52 52 52 52 52 66 66 66 66 0

66 5

569 66 66 22 22 22 22 22 6

22 22 22 22 22 22 9

22 22 22 22 22 22 22 22 22 22 22 LEG INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET' INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:20 AM Component: S/G A Page 26 of 97 ONSIAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 0.19 0.12 0.17 37 8

0.11 37 9

0.33 37 11 0.11 37 12 0.30 0.13 37 15 0.12 37 19 0.11 37 21 0.14 0.12 37 22 0.08 37 23 0.09 0.06 37 26 0;10 0.15 37 29 0.17 37 32 0.15 37 34 0.08 0.12 37 35 0.09 37 37 0.11 37 39 0.17 37 43 0.11 37 54 0.19 37 57 0.13 0.09 37 64 0.19 0.15 37 66 0.10 37 68 0.14 37 77 0.18 37 81 0.11 37 92 0.10 37 94 0.11 0.10 37 98 0.07 37 101 0.14 37 103 0.23 0.14 0.09 37 104 0.41 0.13 37 106 0.18 0.16 0.09 37 107 0.14 37 108 0.20 0.24 37 109 0.20 37 110 0.10 0.13 37 114 0.10 0.14 38 5

0.23 38 10 0.10 38 13 0.15 0.16 0.14 38 25 0.09 0.08 38 26 0.16 0.11 38 27 0.12 38 32 0.07 0.19 38 33 0.11 38 37 0.15 38 38 0.11 38 39 0.10 38 43 0.16 38 45 0.09 0.18 38 46 0.16 38 54 0.12 38 55 0.10 38 87 0.12 0.12 38 93 0.09 DEG 115 138 116 142 141 134 144 137 145 149 139 128 152 140 118 122 129 93 141 157 140 142 137 137 160 132 116 157 120 137 138 123 129 108 131 135 144 143 141 141 145 151 134 147 136 134 143 137 135 136 137 148 147 142 123 120 134 144 151 145 148 157 142 143 137 136 145 158 148

.128 121 107 139 138 121 142 123 117 117 133 CHN P2 P2 P3 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 12 TWD 8 TWD 12 TWD 7 TWD 16 TWD 6 TWD 15 TWD 8 TWD 7 TWD 6 TWD 8 TWD 7 TWD 5 TWD 5 TWD 4 TWD 6 TWD 8 TWD 10 TWD 9 TWD 5 TWD 7 TWD 5 TWD 6 TWD 9 TWD 5-TWD 9 TWD 7 TWD 5 TWD 10 TWD 8 TWD 5 TWD 8 TWD 10 TWD 6 TWD 7 TWD 7 TWD 7 TWD 5 TWD 10 TWD 14 TWD 10 TWD 6 TWD 22 TWD 9 TWD 12 TWD 11 TWD 6 TWD 10 TWD 13 TWD 15 TWD 13 TWD 7 TWD 9 TWD 7 TWD 10 TWD 11 TWD 6 TWD 8 TWD 9 TWD 8 TWO 6 TWD 5

-TWD 9 TWD 6 TWD 7 TWD 5 TWD 11 TWD 6 TWD 8 TWD 7 TWD 6 TWD 10 TWD 5 TWD 10 TWD 8 TWD 6 TWD 6 TWD 8 TWD 8 TWD 6 LOCATION 010

-0.42 001

+0.34 014

-0.43 010

-0.46 014

-0.47 011

-0.41 010

+0.58 011

-0.44 011

-0.49 011

-0.58 008

+0.22 013

-0.63 012

-0.58 013

-0.66 009

+0.15 008

+0.19 009

+0.15 013

+0.05 011

+0.02 010

+0.02 009

+0.10 009

+0.10 009

+0.10 009

+0.10 009

+0.07 009

+0.07 009

-0.65 009

+0.02 008

-0.58 009

+0.02 009

+0.07 009

+0.02 012

-0.68 012

-0.74 012

-0.64 011

+0.11 010

-0.64 009

-0.56 014

+0.13 013

-0.59 011

-0.43 010

-0.53 011

-0.40 010

+0.59 013

-0.53 010

-0.53 012

+0.24 010

-0.48 013

+0.24 010

-0.56 010

-0.53 013

-0.45 010

-0.51 013

+0.32 010

-0.42 010

+0.63 010

-0.46 009

-0.49 010

+0.61 012

-0.54 008

+0.17 009

+0.17 008

+0.19 009

+0.17 009

+0.17 008

+0.15 010

+0.02 009

+0.15 009

+0.12 009

+0.02 009

-0.68 009

-0.71 008

+0.12 009

+0.02 009

-0.61 009

+0.02 009

+0.07 010

+0.05 010

-0.03 013

-0.72 EXT EXT UTIL 1

UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE

  • WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTIL 2

CAL #

22 10 22 13 22 32 30 30 98 98 30 30 30 30 32 30 30 30 30 0

603 54 54 4

54 52 52 52 3

595 52 52 52 66 66 66 66 66 3

569 22 22 5

22 22 22 22 22 22 22 5

22 22 22 4

22 22 22 22 22 22 22 22 22 2

28 26 26 26 32 32 30 5

30 34 54 54 52 52 54 52 7

597 54 54 52 52 54 22 22 22 LEG OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET

'INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 5i0XB 510XB 51 OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXO 51OUL 510XB 510XB 510XB 510Xs 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSy Rep]

4/22/2008 9:45:20 AM Component: S/G A Page 27 of 97 ONSIAR-E0C24 -

Tube Support Wear QUERY: QueryMl[1]

ROW TUBE VOLTS 38 94 0.05 38 95 0.14 0.14 0.11 38 101 0.14 38 102 0.11 0.09 38 103 0.17 38 104 0.10 38 105 0.18 0.09 38 106 0.12 0.11 38 108 0.15 38 109 0.11 0.11 38 110 0.12 0.11 38 111 0.26 38 112 0.21 38 114 0.31 38 115 0.15 0.17 0.11 39 7

0.14 39 8

0.07 39 10 0.13 39 13 0.20 39 14 0.08 0.15 39 16 0.12 39 26 0.13 39 27 0.14 0.06 39 28 0.06 0.06 0.07 39 29 0.15 0.07 39 31 0.09 39 32 0.14 39 33 0.11 0.16 0.11 0.09 39 37 0.09 0.11 39 38 0.34 39 39 0.23 39 43 0.10 39 45 0.12 0.18 0.09 39 46

'0.11 39 49 0.12 39 58 0.11 39 60 0.12 39 67 0.13 39 69 0.11 39 71 0.11 39 73 0.08 39 78 0.28 39 92 0.06 0.08 39 94 0.12 39 98 0.11 39 99 0.16 0.12 0.38 0.10 0.11 0.16 39 103 0.20 0.10 39 104 0.08 0.34 0.18 39 105 0.10 0.10 39 106 0.11 DEG CHN 160 P2 133 P2 128 P2 140 P2 148 P2 150 P2 149 P2 146 P2 147 P2 150 P2 141 P2

.146 P2 133 P2 142 P2 133 P2 132 P2 151 P2 133 P2 134 P2 128 P2 136 P2 134 P2 128 P2 139 P2 100 P2 148 P2 143 P2 145 P2 150 P2 153 P2 152 P2 140 P2 127 P2 120 P2 126 P2 101 P2 150 P2 147 P2 152 P2 138 P2 123 P2 138 P2 144 P2 129 P2 43 P2 142 P2 107 P2 138 P2 134 P2 148 P2 152 P2 117 P2 144 P2 119 P2 143 P2 133 P2 127 P2 139 P2 134 P2 132 P2 126 P2 128 P2 148 P2 150 P2 131 P2 143 P2 138 P2 144 P2 132 P2 140 P2 139 P2 136 P2 127 P2 157 P2 153 P2 138 P2 144 P2 149 P2 144 P2 145 P2 IND %TW TWD 4 TWD 9 TWO 9 TWO 7 TWD 9 TWD 8 TWD 6 TWD 11 TWD 7 TWD 12 TWD 6 TWO 8 TWD 8 TWD 10 TWD 8 TWD 8 TWO 8 TWD 8 TWD 16 TWD 13 TWD 18 TWD 10 TWD 11 TWD 8 TWD 8 TWD 4 TWD 7 TWD 11 TWD 5 TWD 8 TWD 7 TWO 7 TWD 8 TWD 4 TWD 3 TWD 4 TWD 4 TWD 9 TWD 4 TWD 6 TWD 7 TWD 6 TWD 8 TWD 6 TWD 5 TWD 5 TWD 6 TWD 18 TWD 11 TWD 6 TWD 6 TWD 9 TWD 5 TWD 8 TWD 6 TWD 6 TWD 6 TWO 8 TWD 6 TWD 6 TWD 4 TWD 14 TWD 5 TWD 6 TWD 8 TWD 8 TWD 11 TWD 8 TWD 21 TWD 7 TWD 8 TWD 10 TWD 13 TWD 7 TWD 6 TWD 19 TWD 12 TWD 7 TWD 7 TWO 8 LOCATION 011

-0.56 013

+0.05 013

-0.72 011

-0.56 012

-0.58 012

-0.61 011

+0.19 012

-0.56 010

-0.56 012

-0.53 011

-0.43 010

-0.50 009

-0.58 010

-0.58 014

+0.21 011

+0.26 013

-0.48 010

-0.50 013

+0.29 010

+0.58 013

-0.37 013

-0.40 010

-0.40 007

-0.42 010

+0.64 014

+0.27 010

-0.49 010

+0.61 009

-0.49 010

+0.59 012

-0.54 008

+0.17 009

+0.15 008

+0.12 009

+0.17 008

+0.12 010

+0.05 010

+0.10 008

+0.12 012

-0.66 012

-0.69 008

+0.12 013

-0.71 013

+0.05 009

+0.02 008

+0.15 009

+0.12 009

+0.10 009

-0.61 009

+0.02 008

+0.15 009

-0.63 009

+0.10 008

-0.69 009

+0.10 009

+0.02 009

+0.07 008

-0.59 009

+0.10 009

+0.12 009

+0.07 008

-0.56 015

-0.75 013

-0.05 015

-0.75 007

-0.45 014

+0.05 013

+0.05 013

-0.69 010

-0.56 009

-0.61 012

+0.11 012

-0.58 010

+0.53 013

+0.16 013

-0.61 011

-0.48 012

-0.53 010

+0.53 011

-0.48 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 7

WAR WAR WAR WAR 5

WAR 6

WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 6

WAR WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 11 WAR WAR 4

WAR WAR WAR WAR 3

WAR 6

WAR CAL #

22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 28 26 26 28 26 26 26 26 30 30 34 34 34 54 54 54 52 52 52 52 52 52 52 54 52 52 52 52 52 597 52 52 52 571 66 66 66 66 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:20 Am Component: S/G A Page 28 of 97 ONSIAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 0.10 0.19 39 107 0.12 0.11 39 108 0.09 0.10 0.29 39 109 0.14 0.24 39 110 0.13 0.08 39 111 0.41 0.16 39 112 0.24 0.14 39, 114 0.25 0.13 39 116 0.22 0.18 40 1

0.13 40 9

0.20 0.09 40 10 0.31 0.13 40 12 0.22 0.14 0.30 0.15 0.09 40 24 0.13 40 26 0.09 0.11 40 27 0.11 40 28 0.21 40 29 0.24 40 32 0.17 40 33 0.08 40 35 0.12 40 36 0.14 40 37 0.11 0.10

40.

38 0.50 40 41 0.12 0.21 40 42 0.22 40 43 0.16 40 45 0.12 0.22 40 46 0.14 40 49 0.09 40 51 0.12 40 55 0.20 40 56 0.06 40 58 0.13 40 82 0.13 40 98 0.10 40 99 0.11 40 103 0.12 0.20 40 105 0.28 0.14 40 106 0.26 0.10 0.10 40 108 0.11 0.17 40 109 0.20 40 111 0.17 40 112 0.09 40 113 0.47 40 114 0.18 40 116 0.21 40 117 0.14 41 6

0.10 41 7

0.13 41 8

0.12 0.11 41 12 0.10 41 14 0.15 41 17 0.16 DEG CHN 144 P2 141 P2 154 P2 143 P2 141 P2 144 P2 140 P2 134 P2 137 P2 137 P2 148 P2 134 P2 139 P2 136 P2 124 P2 129 P2 124 P2 125 P2 135 P2 151 P2 151 P2 139 P2 140 P2 142 P2 140 P2 139 P2 144 P2 143 P2 140 P2 142 P2 142 P2 140 P2 144 P2 145 P2 128 P2 146 P2 149 P2 106 P2 141 P2 148 P2 145 P2 133 P2 139 P2 123 P2 138 P2 137 P2 120 P2 141 P2 152 P2 66 P2 106 P2 131 P2 138 P2 137 P2 137 P2 153 P2 150 P2 156 P2 146 P2 144 P2 148 P2 138 P2 137 P2 147 P2 148 P2 146 P2 139 P2 143 P2 152 P2 135 P2 145 P2 131 P2 138 P2 133 P2 159 P2 145 P2 149 P2 134 P2 144 P2 141 P2 IND %TW TWD 7 TWD 12 TWD 8 TWD 8 TWD 6 TWD 7 TWD 17 TWD 10 TWD 15 TWO 9 TWO 6 TWD 22 TWD 11 TWD 15 TWD 9 TWD 15 TWO 9 TWD 14 TWD 12 TWD 8 TWD 11 TWD 6 TWD 15 TWD 7 TWD 11 TWD 8 TWD 15 TWD 8 TWD 5 TWD 7 TWD 5 TWD 6 TWD 6 TWO 11 TWO 12 TWD 7 TWD 5 TWD 7 TWD 7 TWD 7 TWD 6 TWO 21 TWO 7 TWD 12 TWO 11 TWO 11 TWO 7 TWD 13 TWD 7 TWD 5 TWD 6 TWO 10 TWO 4 TWO 7 TWO 7 TWD 7 TWD 7 TWD 8 TWO 13 TWO 17 TWO 10 TWO 16 TWD 7 TWD 7 TWD 8 TWD 11 TWD 13 TWD 11 TWD 6 TWD 24 TWD 12 TWD 13 TWD 10 TWO 5 TWO 7 TWD 6 TWD 6 TWD 5 TWO 8 TWO 9 LOCATION 011

+0.24 010

+0.50 013

-0.53 009

-0.58 013

-0.53 011

-0.43 010

-0.50 013

+0.24 010

-0.53 014

-0.53 010

-0.50 013

-0.48 010

-0.50 013

-0.45 010

+0.61 013

-0.43 010

+0.61 010

+0.64 010

-0.40 008

+0.34 010

-0.46 012

-0.44 010

-0.46 012

-0.44 010

+0.61 011

-0.44 014

-0.49 014

+0.22 010

-0.51 010

+0.12 008

+0.19 009

+0.12 009

+0.15 009

+0.12 009

+0.15 009

+0.12 008

+0.17 009

+0.12 011

+0.05 008

+0.02 009

-0.58 009

+0.10 008

+0.10 009

+0.07 009

+0.07 009

+0.07 008

-0.60 009

+0.02 009

-0.63 008

+0.07 009

-0.68 009

+0.02 009

+0.05 009

+0.07 009

-0.62 012

-0.69 011

-0.58 012

-0.58 010

+0.51 011

-0.48 010

+0.53 009

-0.61 013

+0.19 010

+0.53 014

+0.13 010

-0.50 010

-0.48 010

-0.53 014

+0.21 013

-0.48 013

+0.27 010

+0.58 013

+0.35 010

-0.44 014

-0.47 012

-0.41 010

-0.46 012

-0.46 014

-0.56 010

+0.17 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE uTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE STE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE STE UTIL 1

UTIL 2

WAR 5

WAR 8

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 8

WAR WAR 6

WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR 2

WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR 5

WAR WAR 4

WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR CAL #

22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 4

28 28 26 26 26 26 26\\.

26 26 26 26 26 30 34 52 595 54 54 52 54 54 52 54 54 52 597 54 54 52 52 52 52 54 52 571 22 24 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 26 28 26 26' 26 26 28 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSr Rep]

4/22/2008 9:45:20 AM Component: S/G A Page 29 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: QueryMl~l)

ROW 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 TUBE 18 19 22 23 25 30 32 33 34 36 37 38 39 40 44 45 46 50 55 57 58 69 76 95 96 103 105 108 109 110 ill 113 116 1

5 8

9 10 11 13 17 18 21 23 26 28 29 31 32 34 36 37 38 40 42 43 46 73 VOLTS 0.19 0.05 0.14 0.16 0.08 0.20 0.15 0.24 0.11 0.11 0.06 0.09 0.09 0.18 0.12 0.10 0.16 0.10 0.22 0.14 0.24 0.11 0.11 0.13 0.12 0.09 0.09 0.10 0.12 0.09 0.07 0.09 0.15 0.10 0.11 0.08 0.11 0.14 0.24 0.12 0.16 0.04 0.23 0.25 0.10 0.33 0.13 0.29 0.19 0.10 0.24 0.10 0.28 0.25 0.13 0.34 0.28 0.20 0.15 0.20 0.10 0.08 0.10 0.09 0.07 0.08 0.08 0.06 0.12 0.09 0.20 0.09 0.23 0.13 0.11 0.17 0.19 0.18 0.17 0.08 DEG CHN 136 P2 146 P2 140 P2 141 P2 152 P2 143 P2 138 P2 138 P2 129 P2 136 P2 122 P2 140 P2 130 P2 96 P2 162 P2 51 P2 130 P2 111 P2 141 P2 136 P2 143 P2 100 P2 128 P2 132 P2 92 P2 128 P2 139 P2 110 P2 104 P2 151 P2 118 P2 115 P2 140 P2 147 P2 153 P2 154 P2 133 P2 142 P2 143 P2 136 P2 113 P2 161 P2 133 P2 141 P2 128 P2 130 P2 150 P2 145 P2 145 P2 148 P2 143 P2 146 P2 142 P2 135 P2 149 P2 142 P2 140 P2 143 P2 156 P2 139 P2 145 P2 124 P2 124 P2 104 P2 84 P2 140 P2 143 P2 51 P2 127 P2 145 P2 142 P2 124 P2 142 P2 137 P2 139 P2 136 P2 124 P2 139 P2 127 P2 127 P2 IND %TW TWD 10 TWD 3 TWD 8 TWD 9 TWD 5 TWD 11 TWD 8 TWD 12 TWD. 6 TWD 6 TWD 3 TWD 6 TWD 5 TWD 9 TWD 6 TWD 6 TWO 7 TWD 6 TWD 13 TWD 7 TWD 13 TWD 6 TWD 6 TWD 8 TWD 6 TWD 6 TWO 5 TWD 8 TWD 9 TWD 5 TWD 4 TWD 5 TWD 10 TWD 7 TWD 8 TWD 5 TWD 8 TWD 10 TWD 15 TWD 8 TWD 11 TWD 3 TWD 14 TWD 14 TWD 6 TWD 16 TWD 7 TWD 15 TWD 10 TWD 6 TWD 13 TWD 6 TWD 14 TWD 13 TWD 7 TWD 17 TWD 15 TWD 11 TWD 9 TWD 10 TWD 6 TWD 5 TWD 6 TWD 5 TWD 4 TWD 4 TWD 4 TWD 4 TWD 6 TWD 5 TWD 12 TWD 5 TWD 10 TWD 7 TWD 7 TWD 9 TWD 10 TWD 10 TWD 9 TWD 4 LOCATION 012

-0.59 008

+0.19 014

-0.61 014

+0.10 008

+0.19 010

-0.61 011

-0.56 011

+0.12 013

-0.66 009

+0.12 010

+0.10 009

+0.12 009

+0.05 009

+0.10 008

-0.56 009

+0.05

.009

+0.10 008

-0.58 009

+0.02 009

+0.10 009

+0.02 009

-0.63 009

-0.63 009

+0.07 009

+0.07 009

-0.62 009

-0.66 009

+0.00 009

+0.02 008

+0.10 009

+0.07 009

+0.07 010

+0.08 010

-0.66 010

+0.59 009

-0.53 012

+0.21 010

-0.50 010

-0.53 010

-0.53 010

+0.50 011

+0.29 010

+0.58 010

-0.37 010

-0.42 010

-0.46 012

-0.44 010

-0.46 010

+0.59 011

+0.27 012

-0.46 012

+0.25 009

-0.49 010

-0.49 013

-0.52 014

-0.56 014

+0.17 011

-0.56 011

+0.17 012

-0.61 010

-0.59 010

+0.15 011

+0.10 008

+0.15 009

+0.12 008

+0.15 009

+0.10 009

+0.02 009

+0.10 009

+0.10 009

+0.10 009

+0.10 009

+0.10 009

-0.59 009

-0.66 009

-0.63 009

+0.10 009

+0.02 009

-0.63 009

+0.02

  • EXT EXT LTE UTE LTE UTE*

LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR WAR 5

WAR WAR 3

WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR 4

WAR WAR WAR WAR WAR CAL #

26 26 28 28 28 26 26 26 26 26 26 54 54 52 52 52 595 54 54 52 54 52 54 54 52 597 52 589 589 52 66 66 22 22 22 22 22 22 22 22 22 22 22 4

4 26 26 28 28 28 28 28 26 26 28 28 28 28 28 26 26 26 26 26 26 26 26 54 52 52 54 54 595 52 597 52 52 54 52 66 LEG PROBE INLET 51OXB INLET 510XB INLET 51OXE INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL INLET 510LX INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL INLET 510XB INLET 51OUL INLET 51OUL INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL INLET 510LXB INLET 51OUL INLET 510LXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:20 AM Component: S/G A Page 30 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 42 89 0.09 42 93 0.10 42 97 0.11 42 98 0.10 42 99 0.17 0.27 0.12 0.12 0.12 42 103 0.18 42 104 0.12 42 106 0.09 0.11 0.15 0.10 0.12 42 107 0.19 0.23 0.13 42 108 0.54 0.16 0.22 0.18 0.35 0.18 0.22 0.10 0.11 0.09 42 109 0.16 0.16 0.34 0.16 0.26 0.15 0.31 0.10 42 110 0.35 42 111 0.10 42 112 0.23 42 113 0.15 42 114 0.14 0.10 42 116 0.13 42 117 0.14 43 1

0.14 43 3

0.30 43 7

0.12 43 9

0.19 43 10 0.35 0.19 0.17 0.22 0.15 43 11 0.17 0.18 43 12 0.13 43 13 0.12 43 15 0.19 43 16 0.11 43 17 0.11 43 25' 0.11 43 29 0.09 43 31 0.27 43 32 0.13 43 33 0.08 43 34 0.09 43 35 0.13 43 37 0.11 0.36 43 38 0.16 0.15 43 40 0.11 43 41 0.14 43 45 0.06 43 46 0.09 43 51 0.10 43 55 0.15 43 59 0.09 43 76 0.08 DEG CHN 128 P2 142 P2 137 P2 140 P2 143 P2 134 P2 122 P2 139 P2 141 P2 151 P2 151 P2 146 P2 150 P2 140 P2 140 P2 112 P2 139 P2 144 P2 148 P2 131 P2 145 P2 144 P2 143 P2 132 P2 144 P2 142 P2 147 P2 144 P2 151 P2 138 P2 140 P2 140 P2 135 P2 142 P2 144 P2 138 P2 144 P2 138 P2 152 P2 137 P2 129 P2 140 P2 138 P2 72 P2 126 P2 99 P2 111 P2 145 P2 146 P2 140 P2 137 P2 141 P2 150 P2 148 P2 155 P2 150 P2 145 P2 150 P2 143 P2 154 P2 145 P2 142 P2 109 P2 139 P2 82 P2 135 P2 147 P2 140 P2 100 P2 141 P2 148 P2 100 P2 145 P2 135 P2 160 P2 120 P2 147 P2 108 P2 121 P2 131 P2 IND TWD TWD TWO TWO TWD TWO TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 5

6 8

7 11 16 9

8 9

12 8

7 7

10 7

9 12 14 9

27 10 14 12 20 11 14 7

8 6

10 11 19 11 16 10 18 7

20 7

15 10 9

7 9

10 8

16 7

11 17 10 9

11 8

10 10 7

7 10 6

7 6

5 15 7

5 5

7 7

18 8

8 6

7 4

5 7

9 5

5 LOCATION EXT EXT 009

+0.07 LTE UTE 010

+0.22 LTE UTE 009

-0.61 UTE LTE 010

+0.11 UTE LTE 014

+0.00 UTE LTE 013

+0.05 UTE LTE 013

-0.69 UTE LTE 009

+0.16 UTE LTE 012

+0.11 UTE LTE 010

+0.42 UTE LTE 010

+0.56 UTE LTE 013

+0.16 UTE LTE 011

-0.48 UTE LTE 010

+0.51 UTE LTE 011

+0.19 UTE LTE 013

-0.64 UTE LTE 014

-0.59 UTE LTE 013

-0.61 UTE LTE 009

-0.48 UTE LTE 013

-0.56 UTE LTE 012

+0.21 UTE LTE 012

-0.58 UTE LTE 011

+0.24 UTE LTE 011

-0.48 UTE LTE 010

-0.53 UTE LTE 009

-0.58 UTE LTE 010

+0.61 UTE LTE 014

+0.13 UTE LTE 014

-0.56 UTE LTE 014

+0.19 UTE LTE 013

+0.21 UTE LTE 013

-0.58 UTE LTE 012

+0.24 UTE LTE 012

-0.50 UTE LTE 011

+0.24 UTE LTE 010

-0.56 UTE LTE 010

+0.58 UTE LTE 010

-0.58 UTE LTE 013

-0.51 UTE LTE 010

-0.53 UTE LTE 010

-0.50 UTE LTE 012

+0.29 UTE LTE 010

-0.42 UTE LTE 010

+0.67 UTE LTE 010

+0.61 UTE LTE 010

+0.64 LTE UTE 010

+0.64 LTE UTE 010

-0.44 LTE UTE 010

-0.49 LTE UTE 010

-0.46 LTE UTE 010

+0.62 LTE UTE 011

-0.44 LTE UTE 013

-0.49 LTE UTE 013

+0.27 LTE UTE 012

-0.49 LTE UTE 010

+0.59 LTE UTE 012

-0.49 LtE UTE 013

-0.54 LTE UTE 012

-0.54 LTE UTE 012

-0.59 LTE UTE 012

-0.56 LTE UTE 009

+0.12 LTE UTE 009

+0.10 LTE UTE 009

+0.12 LTE UTE 012

-0.71 LTE UTE 009

+0.07 LTE UTE 009

+0.12 LTE UTE 009

+0.07 LTE UTE 008

-0.60 LTE UTE 009

+0.12 LTE UTE 009

-0.58 LTE UTE 009

+0.10 LTE UTE 009

+0.07 LTE UTE 009

+0.10 LTE UTE 009

+0.07 LTE UTE 009

+0.05 LTE UTE 009

-0.02 LTE UTE 009

-0.62 LTE UTE 009

+0.02 LTE UTE 009

+0.02 LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

66 0

593 18 18 18 18 18 0

18 4

18 18 18 18 18 18 0

18 0

18 22 22 22 22 22 22 22 22 22 22 7

22 0

22 0

22 22 22 22 22 22 22 22 7

22 22 22 22 22 22 4

22 5

22 7

22 4

4 28 28 26 26 26 6

26 4

26 28 8

28 7

26 28 28 26 28 26 52 54 52 54 52 52 54 54 52 52 54 52 54 52 5

601 7

601, 52 66 LEG INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 51OUL 510XB 510XB

AREVA NP Inc Customer Name: ONSi Repi 4/22/2008 9:45:21 AM Component: S/G A Page 31 of 97 ONSIAR-EOC24 -

Tube QUERY: QueryMl(lJ Support Wear ROW TUBE VOLTS 43 78 0.08 43 96 0.12 43 99 0.10 43 102 0.13 0.17 43 103 0.18 43 106 0.31 43 108 0.10 0.10 0.16 0.16 0.09 43 109 0.09 0.11 0.07 0.11 0.13 43 110 0.24 43 111 0.12 43 112 0.18 43 114 0.09 0.31 43 115 0.13 43 116 0.12 0.22 43 117 0o11 44 4

0.23 0.11 44 6

0.17 44 7

0.10 0.28 44 8

0.22 44 10 0.18 0.25 0.10 44 11 0.17 44 12 0.26 0.36 0.21 44 13 0.24 44 15 0.10 44 21 0.20 44 23 0.09 44 24 0.11 44 25 0.11 44 26 0.08 0.06 44 27 0.13 44 28 0.24 44 31 0.10 44 34 0.12 0.12 44 35 0.10 44 36 0.14 44 37 0.43 44 38 0.12 0.07 44 39 0.29 44 40 0.14 44 41 0.24 44 43 0.11 0.14 44 45 0.13 44 47 0.12 44 49 0.10 44 59 0.19 44 73 0.07 44 79 0.08 44 104 0.12 44 108 0.07 44 109 0.15 44 111 0.18 44 112 0.11 0.09 44 113 0.21 44 114 0.24 0.16 0.18 44 115 0.14 44 116 0.21 DEG 142 139 146 131 139 133 145 135 144 149 144 154 144 142 139 142 144 141 138 135 153 135 144 143 128 143 107 130 138 145 113 134 144 145 146 147 139 141 144 142 142 137 139 138 142 142 137 132 128 86 140 135 123 125 130 136 90 134 122 145 146 109 140 83 143 124 142 113 141 143 143 142 148 154 131 144 148 143 139 140 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 4 TWD 8 TWD 7 TWD 9 TWD 11 TWD 12 TWD 18 TWD 7 TWD 7 TWD 11 TWO 11 TWD 7 TWD 6 TWD 7 TWD 5 TWD 7 TWD 9 TWD 15 TWD 8 TWD 12 TWD 6 TWD 18 TWD 9 TWD 8 TWD 14 TWD 8 TWD 13 TWD 7 TWD 10 TWD 5 TWD 13 TWD 12 TWD 10 TWD 14 TWD 6 TWD 9 TWD 14 TWD 18 TWD 12 TWD 12 TWD 5 TWD 10 TWD 6 TWD 6 TWD 7 TWD 4 TWD 3 TWD 8 TWD 12 TWD 6 TWD 7 TWD 7 TWD 5 TWO 8 TWD 19 TWD 7 TWD 5 TWD 14 TWD 8 TWD 12 TWD 6 TWD 8 TWD 7 TWD 7 TWD 5 TWD 9 TWD 4 TWD 4 TWD 8 TWD 5 TWD 11 TWD 12 TWD 8 TWD 6 TWD 14 TWD 15 TWD 11 TWD 12 TWD 10 TWD 13 LOCATION 009

+0.12 014

-0.03 010

+0.13 012

+0.11 009

-0.61 010

+0.13 010

+0.53 013

+0.19 011

+0.21 011

-0.48 013

-0.56 012

-0.56 014

+0.13 014

-0.61 013

+0.13 013

-0.58 010

+0.53 010

-0.56 010

-0.56 010

-0.56 014

-0.48 010

-0.53 010

-0.50 013

-0.48 010

-0.47 013

+0.29 010

+0.61 010

-0.42 010

-0.42 012

-0.41 010

-0.43 010

-0.44 009

+0.59 010

-0.46 012

-0.46 010

+0.61 012

+0.25 014

-0.56 014

+0.17 012

-0.49 012

+0.20 010

+0.12 010

+0.12 010

+0.10 008

+0.17 008

+0.12 009

+0.07 011

-0.66 009

+0.15 010

+0.05 009

+0.07 008

-0.58 009

+0.10 009

+0.02 009

+0.10 008

+0.12 009

+0.07 009

+0.10 009

+0.10 009

+0.07 009

+0.07 009

-0.61 008

-0.61 009

-0.66 009

+0.02 007

+0.17 009

+0.02 009

+0.07 010

+0.19 014

+0.08 011

-0.48 010

-0.50 012

-0.50 011

+0.26 010

-0.45 013

-0.53 012

+0.29 012

-0.47 010

-0.61 010

-0.50 EXT EXT UTIL 1

LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTIL 2

CAL #

66 18 18 18 18 18 18 18 18 18 7

18 7

18 18 18 18 18 7

18 18 18 18 18 18 5

18 18 18 184 7

4 4

5" 2

2 28 28 28 28 26 28 28 28 26 26 26 28 26 28 26 26 54 52 52 54 5

54 52 54 52 54 54 52 54 52 52 6

52 52 4

601 52 52 66 66 18 0

18 20 18 20 5

20 18 20 20 20 18 20 LEG INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51.0XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB

  • 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:45:21 AM Component: S/G A Page 32 of 97 ONS1AR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 44 117 0.11 0.27 44 118 0.07 44 119 0.14 0.13 0.07 0.09 45 7

0.50 0.22 0.36 45 8

0.22 45 9

0.16 0.12 45 10 0.19 0.12 45 15 0.15 45 23 0.06 45 26 0.16 0.16 0.13 45 29 0.07 45 31 0.09 45 32 0.15 45 34 Q.-10 45 39 0.10 45 40 0.19 45 41 0.11 45 43 0.16 45 44 0.15 45 47 0.13 45 50 0.10 45 52 0.12 45 56 0.13 45 83 0.09 45 102 0.10 45 104 0.09 45 107 0.41 45 108 0.19 0.17 45 109 0.14 0.08 45 112 0.14 0.07 45 113 0.12 0.31 45 114 0.09 45 116 0.08 45 117 0.20 0.66 0.11 0.46 45 118 0.08 0.16 0.08 45 119 0.09 45 120 0.10 46 1

0.13 0.17 46 5

0.13 46 6

0.19 46 7

0.10 46 8

0.33 0.38 46 9

0.12 46 12 0.14 46 13 0.27 46 19 0.14 46 23 0.11 46 25 0.07 46 26 0.07 46 33 0.17 46 35 0.11 46 37 0.13 0.09 0.10 46 40 0.14 46 42 0.23 46 43 0.10.

46 44 0.10 46 46 0.18 DEG 136 135 152 143 144 137 104 130 138 136 132 134 154 144 150 149 148 140 123 147 136 131 135 155 150 138 i43 143 140 155 140 140 85 147 143 142 139 1"42 138 145 150 147 156 146 140 154 144 134 132 147 133 122 148 143 140 142 133 133 142 132 151 137 121 147 155 143 145 131 137 133 129 137 131 142 116 140 145 143 151 148 CHN IND %TW LOCATION P2 TWD 7 011

-0.40 P2 TWD 16 010

-0.37 P2 TWD 5 010

-0.42 P2 TWD 10 012

+0.34 P2 TWD 9 013

+0.32 P2 TWD 5 011

-0.35 P2; TWD 6 010

+0.64 P2; TWD 21 010

-0.46 P2 TWD 11 012

-0.44 P2 TWD 17 012

+0.32 P2 TWD 11 010

-0.44 P2 TWD 9 010

-0.49 P2 TWD 7 012

-0.46 P2 TWD 10 008

+0.22 P2 TWD 7 010

-0.49 P2 TWD 9 012

-0.51 P2 TWD 4 008

+0.10 P2 TWD 8 009

+0.12 P2 TWD 9 010

-0.63 P2 TWD 7 011

-0.02 P2 TWD 5 009

+0.05 P2 TWD 5 009

+0.12 P2 TWD 9 012

-0.74 P2 TWD 6 009

+0.10 P2 TWD 6 009

+0.02 P2 TWD 10 009

+0.10 P2 TWD 6 008

-0.63 P2 TWD 9 009

+0.02 P2 TWD 8 009

+0.10 P2 TWD 7 009

+0.05 P2 TWD 7 009

+0.02 P2 TWD 8 009

+0.05 P2 TWD 9 009

-0.67 P2 TWD 5 009

+0.07 P2 TWD 7 010

+0.11 P2 TWD 7 010

+0.13 P2 TWb 22 010

+0.42 P2 TWD 13 014

-0.61 P2 TWD 12 012

-0.58 P2 TWD 9 011

-0.42 P2 TWD 6 012

+0.19 P2 TWD 10 013

-0.53 P2 TWD 5 009

-0.53 P2 TWD 8 013

+0.24 P2 TWD 18 010

-0.50 P2 TWD 7 010

-0.55 P2 TWD 6 010

-0.53 P2 TWD 13 013

+0.29 P2 TWD 30 012

+0.29 P2 TWD 8 011

+0.29 P2 TWD 24 010

-0.48 P2 TWD 6 013

+0.32 P2 TWD 11 013

-0.42 P2 TWD 6 010

-0.50 P2 TWD 6 008

+0.29 P2 TWD 7 013

-0.40 P2 TWD 7 009

+0.61 P2 TWD 10 010

-0.37 P2 TWD 7 010

-0.41 P2 TWD 10 010

-0.41 P2 TWD 6 010

-0.44 P2 TWD 15 010

-0.46 P2 TWD 17 010

+0.61 P2 TWD 7 012

-0.46 P2 TWD 8 011

-0.51 P2 TWD 14 010

+0.56 P2 TWD 8 012

-0.59 P2 TWD 6 012

-0.61 P2 TWD 4 009

+0.12 P2 TWD 4 009

+0.10 P2 TWD 9 010

+0.05 P2 TWD 6 009

+0.07 P2 TWD 7 009

-0.61 P2 TWO 5 009

+0.12 P2 TWD 6 012

-0.71 P2 TWD 8 009

+0.10 P2 TWD 13 009

+0.05 P2 TWD 6 009

+0.00 P2 TWD 7 009

+0.05 P2 TWD 10 009

+0.02 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

18 18 3

20 7

18 0

18 0

18 0

18 6

6 6

26 28 28 26 0

26 28 26 26 26 26 34 52 4

601 52 54 52 52 54 52 52 3

601 2

601 4

601 66 18 20 18 20 20 18 0

18 20 4

20 18 18 4

20 4

20 18 18 18 18 20 20 6

20 0

18 6

20 8

8 8

6 8

6 6

28 4

26 28 28 26 28 26 52 52 52 52 52 52 54 52 6

601 54 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL S10XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 51OUL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510UL 51OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:21 AM Component: S/G A Page 33 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 46 48 0.13 46 52 0.17 46 93 0.09 46 102 0.10 0.12 0.11 46 105 0.12 46 106 0.10.

46 109 0.14 46 110 0.08 0.08 0.11 46 111 0.08 0.09 46 112 0.28 0.22 0.14 0.12 46 113 0.13 0.20 0.55 0.20 0.24 0.14 0.61 0.11 46 114 0.16 0.17 0.21 46 117 0.13 46 119 0.16 46 120 0.12 46 121 0.07 47 5

0.13 0.18 47 6

0.15 0.29 0.14 0.14 47 7

0.21 47 8

0.21 47 9

0.15 0.10 47 10 0.17 47 12 0.14 0.11 47 15 0.13 0.13 47 16 0.11 0.19 47 21 0.06 47 22 0.10 0.11 47 23 0.11 47 24 0.10 0.07 40 25 0.12 47 26 0.08 47 27 0.12 47 30 0.13 47 33 0.16 0.08 0.09 47 35 0.10 47 37 0.20 47 38 0.13 47 39 0.14 47 40 0.16 47 41 0.19 47 42 0.11 47 43 0.13 47 44 0.10 47 4 5 0.17 47 46 0.17 0.09 47 50 0.12 47 52 0.16 47 72 0.12 47 78 0.08 47 86 0.05 DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL 8 LEG PROBE 139 P2 117 P2 141 P2 140 P2 151 P2 139 P2 150 P2 133 P2 137 P2 140 P2 148 P2 155 P2 149 P2 153 P2 135 P2 146 P2 137 P2 152 P2 147 P2 146 P2 138 P2 149 P2 142 P2 146 P2 131 P2 147 P2 138 P2 143 P2 137 P2 150 P2 109 P2 124 P2 136 P2 125 P2 89 P2 136 P2 142 P2 151 P2 128 P2 137 P2 153 P2 147 P2 152 P2 149 P2 145 P2 151 P2 139 P2 144 P2 151 P2 140 P2 140 P2 127 P2 113 P2 154 P2 115 P2 139 P2 142 P2 151 P2 148 P2 146 P2 133 P2 155 P2 142 P2 154 P2 152 P2 150 P2 140 P2 132 P2 144 P2 151 P2 151 P2 138 P2 127 P2 123 P2 154 P2 145 P2 149 P2 129 P2 140 P2 120 P2 TWD 9 TWD 11 TWD 6 TWD 7 TWO 9 TWD 7 TWD 9 TWD 7 TWD 10 TWD 6 TWD 6 TWO 8 TWD 6 TWD 7 TWD 17 TWD 14 TWD 9 TWD 8 TWD 9 TWD 13 TWD 27 TWD 13 TWD 15 TWD 10 TWD 29 TWD 8 TWD 10 TWD 11 TWD 13 TWD 9 TWD 11 TWD 8 TWD 5 TWD 8 TWD 10 TWD 8 TWD 14 TWD 7 TWD 7 TWO 12 TWD 10 TWD 8 TWD 6 TWD 10 TWD 8 TWD 7 TWD 7 TWD 7 TWD 7 TWD 10 TWD 3 TWD 8 TWO 8 TWD 7 TWD 5 TWD 4 TWD 7 TWD 4 TWD 7 TWD 7 TWD 9 TWD 5 TWD 6 TWD 6 TWO 12 TWD 7 TWD 7 TWD 7 TWD 11 TWD 6 TWD 8 TWO 5 TWO 10 TWD 9 TWD 5 TWD 6 TWD 8 TWD 7 TWO 4 TWD 3 009 009 012 015 010 014 010 010 011 013 011 010 012 011 013 013 010 015 014 013 013 012 012 011 011 009 010 013 014 010 010 010 010 010 010 010 012 014 012 010 010 010 012 012 013 010 012 012 009 013 009 009 008 010 009 008 009 009 009 009 009 009 010 009 009 009 009 009 009 009 009 009 009 009 009 009 009 008 009 010

+0.00

-0.71

-0.64

-0.03

+0.08

-0.69

+0.08

+0.13

-0.50

+0.16

-0.51

+0.56

-0.55

-0.48

+0.19

-0.56

+0.53

+0.45

+0.16

+0.18

-0.55

+0.18

-0.53

+0.24

-0.45

-0.58

-0.51

+0.24

+0.11

-0.53

+0.55

-0.37

-0.42

-0.41

+0.64

-0.41

+0.32

+0.29

-0.39

-0.44

-0.47

-0.46

+0.29

-0.47

-0.54

+0.61

+0.20

-0.56

-0.51

-0.56

+0.10

-0.52

-0.57

+0.10

+0.12

+0.15

+0.12

+0.07

+0.02

+0.10

-0.61

+0.02

+0.02

+0.10

+0.07

+0.07

-0.61

-0.62

+0.02

+0.05

+0.02

+0.07

-0.63

-0.66

+0.07

+0.05

+0.05

-0.59

-0.02

+0.05 LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 7

601 6

601 5

577 18 18 5

18 20 18 20 0

18 0

18 0

18 20 4

20 18 18 5

18 0

18 20 20 20 20 20 20 20 20 18 0

18 0

18 20 20 6

18 3

20 8

8 6

6 6

3 6

8 56 26 26 28 28 28 26 3

26 28 28 26 0

607 0

607 28 26 26 28 26 54 52 54 54 54 54 54 52 52 0

599 54 52 54 52 54 52 52 52 52 4

575 66 66 INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET 51OUL 510UL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 51OUL 510XB 510XB 510XB 510xB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:21 AM Component: S/G A Page 34 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 47 95 0.10 47 98 0.12 47 101 0,07 47 102 0.13 0.09 0.07 47 103 0.09 47 104 0.08 47 105 0.12 47 106 0.21 47 107 0.18 47 108 0.13 47 109 0.14 0.33 0.12 47 111 0.13 0.09 0.14 0.12 47 112 0.11 47 113 0.17 0.54 0.08 47 114 0.09 0.19 0.16 0.12 47 115 0.13 0.19 0.14 47 117 0.12 47 118 0.18 0.09 47 120 0.15 47 122 0.11 0.08" 0.07 48 8

0.10 48 9

0.16 48 11 0.16 48 14 0.19 48 16 0.40 0.19 48.19 0.17 48 21 0.11 48 22 0.12 48 23 0.08 0.10 48 25 0.10 48 26 0.10

48 28 0.09 48 30 0.25 48 33 0.09 48 34 0.10 48 36 0.12 48 37 0.10 48 39 0.09 0.10 48 40 0.43 0.27 0.12 48 41 0.20 48 43 0.20 48 45 0.14 0.16 0.08 48 46 0.15 0.09 48 49 0.18 0.09 48 50 0.13 48 67 0.06 48 84 0.11 48 102 0.10 48 104 0.09 48 106 0.12 0.08 48 108 0.12 0.12 48 110 0.10 DEG 153 138 138 138 144 129 143 150 127 143 140 151 140 142 147 145 142 144 150 150 132 134 142 149 146 144 151 147 142 148 141 138 148 107 132 140 146 154 126 154 142 142 151 136 148 136 145 149 143 146 135 149 142 141 147 135 143 119 142 134 102 143 139 127 133 147 125 141 133 141 ill 144 141 138 138 137 139 145 144 139 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 6

8 5

9 6

5 6

6 8

14 12 9

10 19 8

9 7

9 8

8 11 27 6

6 12 11 8

8 11 9

8 12 6

10 8

6 5

6 8

9 10 19 10 9

6 9

5 5

6 5

5 13 5

6 7

6 5

6 21 14 7

10 10 8

9 5

8 5

9 5

8 4

6 7

7 8

6 8

8 7

LOCATION 008

-0.52 011

-0.59 015

-0.03 013

-0.71 010

+0.08 012

+0.03 010

+0.08 007

-0.53 014

+0.03 010

-0.66 012

-0.64 011

-0.53 014

+0.03 010

+0.56 012

-0.61 015

-0.66 011

+0.19 011

-0.48 010

+0.53 011

+0.21 013

+0.19 010

+0.56 009

-0.58 011

+0.24 011

-0.47 010

-0.50 012

-0.55 012

-0.52 011

+0.21 010

-0.51 012

-0.48 010

-0.

5 0 013

+0.26 010

+0.55 010

-0.40 009

-0.42 008

+0.32 010

-0.44 010

-0.44 010

+0.59 012

-0.56 014

-0.61 012

-0.56 012

-0.61 010

-0.58 009

-0.54 009

-0.56 010

+0.12 009

+0.17 009

+0.15 009

+0.10 009

+0.12 009

+0.10 009

+0.05 009

+0.02 009

+0.07 010

+0.05 009

+0.00 009

-0.65 009

+0.02 008

-0.63 009

+0.07 009

+0.07 008

-0.60 009

-0.65 009

+0.02 009

-0.63 009

+0.05 009

-0.63 009

+0.05 008

-0.71 009

+0.00 009

+0.00 010

+0,08 010

+0.11 012

-0.69 010

+0.13 011

-0.56 010

+0.13 012

+0.16 EXT EXT LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

4 575 6

593 18 20 20 4

20 18 20 18 20 18 20 18 18 0

18 18 18 18 6

18 20 18 18 18 20 20 20 6

20 34 34 34 18 20 5

20 20 5

20 5

20 5

20 3

8 4

6 26 28 28 3

28 8

26 26 0

607 26 26 28 26 54 54 54 52 54 52 52 52 54 54 5

54 52 52 54 54 54 52 52 52 52 5

601 66 66 18 18 18 18 18 6

18 4

18 LEG INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB S5OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB I)

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:21 AM Component:

S/G A Page 35 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 0.10 48 112 0.13 48 114 0.08 48 116 0.23 48 117 0.20 0.17 0.50 0.17 0.46 0.13 0.23 0.11 48 118 0.13 0.11 48 121 0.11 48 122 0.07 49 2

0.15 49 8

0.25 49 9

0.24 49 10 0.14 49 12 0.13 49 14 0.23 49 16 0.07 49 17 0.12 49 22 0.10 0.13 0.07 49 24 0.10 0.15 49 25 0.08 49 26 0.13 49 27 0.07 0.23 0.11 49 28 0.12 49 33 0.10 49 34 0.13 49 35 0.18 49 37 0.16 49 39 0.16 49 40 0.31 49 42 0.18 0.16 49 45 0.08 0.14 49 46 0.26 49 47 0.15 49 49 0.18 0.11 49 51 0.09 49 56 0.13 49 58 0.10 49 62 0.10 49 66 0.11 49 102 0.14 0.13 49 105 0.11 49 108 0.12 49 109 0.12 0.09 49 111 0.21 49 112 0.08 49 113 0.13 0.08 49 115 0.12 49 117 0.18 0.12 0.10 0.17 49 118 0.18 49 119 0.31

-49 120 0.14 49 121 0.12 50 3

0.18 50 6

0.18 50 7

0.12 50 8

- 0.31 50 18 0.18 0.19 50 19 0.12 DEG CHN 129 P2 145 P2 146 P2 135 P2 145 P2 146 P2 136 P2 142 P2 137 P2 150 P2 137 P2 144 P2 146 P2 139 P2 154 P2 143 P2 99 P2 137 P2 131 P2 149 P2 154 P2 130 P2 110 P2 148 P2 134 P2 133 P2 126 P2 143 P2 142 P2 156 P2 137 P2 132 P2 138 P2 144 P2 135 P2 148 P2 130 P2 149 P2 141 P2 128 P2 133 P2 132 P2 120 P2 153 P2 134 P2 127 P2 149 P2 124 P2 138 P2 146 P2 150 P2 131 P2 147 P2 129 P2 153 P2 138 P2 134 P2 140 P2 129 P2 154 P2 148 P2 138 P2 150 P2 158 P2 148 P2 141 P2 134 P2 130 P2 127 P2 143 P2 137 P2 145 P2 137 P2 91 P2 143 P2 139 P2 143 P2 134 P2 143 P2 144 P2 IND %TW TWD 7 TWD 9 TWD 6 TWD 14 TWD 13 TWD 11 TWD 26 TWD 11 TWD 25 TWD. 9 TWD 15 TWD 8 TWD 9 TWD 7 TWD 8 TWD 5 TWD 9 TWD 13 TWD 12 TWD 7 TWD 7 TWD 12 TWD 4 TWD 7 TWD 6 TWD 7 TWD 4 TWD 8 TWD 10 TWD 5 TWD 7 TWD 5 TWD 13 TWD 7 TWO 6 TWD 6 TWD 7 TWD 11 TWD 8 TWD 10 TWD 15 TWD 9 TWD 8 TWD 5 TWD 8 TWD 13 TWD 8 TWD 9 TWD 6 TWD 5 TWD 8 TWD 7 TWD 6 TWD 6 TWD 10 TWD 9 TWD 8 TWD 9 TWD 8 TWD 6 TWD 13 TWD 6 TWD 9 TWD 6 TWD 8 TWD 12 TWD 8 TWD 7 TWD 11 TWD 12 TWD 18 TWD 10 TWD 8 TWD 9 TWO 10 TWD 6 TWD 16 TWD 10 TWD 11 TWD 7 LOCATION 014

+0.08 011

-0.48 010

-0.56 011

-0.45 014

+0.18 013

+0.24 013

-0.50 012

+0.26 012

-0.50 011

+0.26 011

-0.45 010

-0.50 012

-0.50 013

+0.24 013

-0.45 013

-0.42 009

+0.59 010

-0.44 010

-0.49 012

-0.46 012

-0.46 014

+0.12 010

+0.20 012

+0.12 010

+0.02 012

-0.63 008

+0.17 009

-0.57 011

-0.59 008

+0.17 009

+0.12 010

+0.05 009

-0.66 009

+0.05 009

+0.12 009

+0.02 009

+0.10 009

+0.10 009

+0.07 009

-0.65 009

+0.07 009

+0.05 009

-0.63 009

+0.02 009

-0.63 009

+0.05 009

+0.07 009

-0.63 009

+0.00 009

+0.07 009

+0.00 009

-0.69 009

-0.07 009

+0.02 012

+0.05 012

-0.72 011

-0.59 010

+0.11 015

-0.69 011

-0.53 010

+0.56 011

-0.50 012

-0.56 010

+0.53 010

+0.53 014

+0.19 013

+0.11 011

+0.26 010

+0.53 013

+0.21 013

-0.50 013

+0.26 010

-0.45 010

+0.61 010

-0.42 010

-0.44 010

-0.46 010

-0.56 012

+0.15 008

+0.15 EXT EXT UTIL UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 1

UTIL 2

CAL #

0 18 18 0

18 18 20 20 20 20 20 20 20 20 18 0

18 4

20 4

18 8

8 4

6 6

26 26 26 26 28 26 26 26 0

607 4

607 28 26 34 34 7

34 52 54 52 54 52 54 52 52 8

52 54 6

54 52 52 52 52 52 1

601 4

601 52 66 18 18 18 20 18 18 18 5

20 18 5

18 6

18 18 18 18 18 20 18 20 18 2

6 8

3 6

8 28 28 26 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510UX 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB*

510XB" 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:21 AM Component: S/G A Page 36 of 97 ONSlAR-EOC24 Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 50 24 0.15 50 25 0.09 50 26 0.08 50 27 0.20 0.09 50 28 0.11 50 29 0.13 50 31 0.09 50 34 0.19 0.09 50 39 0.11 50 40 0.25 0.09 50 41 0.13 50 42 0.14 50 44 0.12 50 45 0.26 0.15 50 46 0.24 50 48 0.09 50 49 0.16 0.10 50 50 0.11 50 66 0.11 50 103 0.10 50 105 0.11 50 107 0.21 50 109 0.12 0.15 50 110 0.10 50 113 0.11 50 115 0.09 50 117 0.13 0.07 0.07 50 118 0.20 0.10 0.08 50 119 0.12 50 121 0.11 51 3

0.26 51 5

0.33 51 8

0.32 0.27 0.18 51 9

0.35 51 10 0.25 51 12 0.16 0.25 51 14 0.19 51 16 0.15 0.11 51 20 0.15 51 21 0.13 51 22 0.15 51 25 0.09 51 28 0.19 0.16 51 29 0.13 51 31 0.10 51 33 0.10 51 36 0.10 51 37 0.11 51 38 0.14 51 40 0.18 51 41 0.48 51 42 0.26 51 43 0.11 51 45 0.09 51 46 0.07 51 49 0.08 0.14 51 50 0.12 51 58 0.12 51 62 0.09 51 67 0.08 51 70 0.09 51 102 0.08 0.12 51 106 0.10 DEG 147 145 141 145 142 140 130 140 118 125 137 142 149 147 127 140 134 120 142 143 144 144 145 140 138 139 147 133 131 144 144 145 127 143 140 142 150 148 135 105 141 140 140 134 140 148 152 141 138 153 135 153 144 141 143 139 145 139 129 146 150 144 144 137 134 145 141 143 113 152 120 141 104 152 136 118 141 151 144 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 11 TWD 5 TWO 5 TWO 10 TWO 5 TWO 7 TWO 7 TWO 5 TWD 10 TWO 5 TWO 8 TWO 12 TWO 5 TWD 8 TWO 8 TWO 9 TWO 14 TWO 9 TWO 12 TWD 5 TWO 9 TWO 6 TWO 6 TWO 6 TWD 7 TWD 8 TWO 13 TWO 8 TWO 10 TWO 7 TWO 8 TWD 7 TWO 9 TWD 5 TWO 5 TWO 13 TWO 7 TWO 6 TWO 9 TWD 7 TWO 13 TWO 17 TWO 15 TWO 13 TWO 9 TWD 16 TWD 13 TWO 9 TWD 12 TWO 10 TWO 8 TWO 6 TWO 8 TWO 9 TWO 11 TWO 5 TWO 11 TWO 9 TWO 7 TWO 5 TWD 6 TWD 6 TWO 6 TWO 7 TWO 10 TWO 20 TWO 14 TWO 6 TWO 7 TWO 4 TWO 5 TWO 7 TWO 9 TWO 8 TWD 5 TWO 5 TWO 5 TWO 6 TWD 8 TWO 7 LOCATION EXT EXT 011

-0.59 LTE UTE 008

+0.15 LTE UTE 008

+0.15 LTE UTE 009

-0.58 LTE UTE 009

+0.00 LTE UTE 009

+0.02 LTE UTE 009

+0.07 LTE UTE 009

+0.12 LTE UTE 009

-0.61 LTE UTE 009

+0.10 LTE UTE 009

-0.63 LTE UTE 009

-0.63 LTE UTE 010

+0.05 LTE UTE 009

+0.02 LTE UTE 009

+0.05 LTE UTE 009

-0.63 LTEUTE 009

+0.02 LTEUTE 008

-0.60 LTE UTE 009

-0.66 LTE UTE 009

+0.00 LTE UTE 009

-0.65 LTE UTE 009

+0.02 LTE UTE 009

+0.05 LTE UTE 009

+0.02 LTE UTE 013

+0.03 UTE LTE 010

+0.08 UTE LTE 010

+0.13 UTE LTE 011

-0.53 UTE LTE 010

+0.13 UTE LTE 014

+0.03 UTE LTE 012

-0.56 UTE LTE 014

+0.13 UTE LTE 010

-0.48 UTE LTE 011

+0.21 UTE LTE 014

+0.16 UTE LTE 012

-0.47 UTE LTE 011

+0.26 UTE LTE 014

+0.18 UTE LTE 013

+0.27 UTE LTE 010

-0.50 UTE'LTE 010

+0.64 LTE UTE 010

-0.42 LTE UTE 010

-0.46 LTE UTE 012

-0.44 LTE UTE 012

+0.27 LTE UTE 012

-0.49 LTE UTE 012

-0.49 LTE UTE 010

-0.53 LTE UTE 011

+0.22 LTE UTE 012

-0.54 LTE UTE 010

-0.56 LTE UTE 011

+0.15 LTE UTE 009

-0.56 LTE UTE 009

-0.59 LTE UTE 009

-0.57 LTE UTE 009

+0.12 LTE UTE 011

-0.66 LTE UTE 011

+0,02 LTE UTE 009

+0.10 LTE UTE 009

+0.10 LTE UTE 009

+0.07 LTE UTE 009

+0.02 LTE UTE 009

+0.07 LTE UTE 009

+0.07' LTE UTE 009

-0.63 LTE UTE 009

+0.07 LTE UTE 009

+0.02 LTE UTE 009

+0.05 LTE UTE 009

+0.00 LTE UTE 009

-0.02 LTE UTE 009

+0.05 LTE UTE 009

-0.65 LTE UTE 009

+0.00 LTE UTE 009

-0.69 LTE UTE 009

+0.05 LTE UTE 009

+0.02 LTE UTE 009

-0.07 LTE UTE 015

-0.05 UTE LTE 008

-0.53 UTE LTE 010

+0.11 UTE LTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR.

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL #

4 607 26 54 52 52 54 52 52 52 52 0

563 52 52 54 52 0

563 54 6

54 52 52 54 54 52 66 18 18 18 18 18 20 18 0

18 18 0

18 4

18 20 20 3

20 18 18 8

8 6

6 6

6 26 26 26 26 26 26 26 0

609 0

607 26 54 54 52 52 52 54 52 52 54 52 54 52 0

563 52 52 52 0

563 6

601 52 66 66 18 18 18 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET PROBE 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:22 AM Component: S/G A Page 37 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 51 110 0.11 51 113 0.15 0.10 0.17 51 114 0.14 51 115 0.14 51 116 0.16 0.23 51 117 0.07 51 118 0.13 0.08 51 119 0.16 0.09 0.20 51 120 0.10 0.12 51 121 0.25 51 122 0.08 51 123 0.13 52 1

0.16 52 3

0.08 52 5

0.13 0.10 52 6

0.21 52 7

0.25 52 8

0.46 0.46 52 9

0.18 52 12 0.23 52 16 0.08 52 20 0.10 52 31 0.13 52 32 0.11 52 33 0.14 52 37 0.14 52 38 0.12 0.06 52 41 0.26 52 42 0.36 52 43 0.44 0.35 0.18 52 46 0.12 52 49 0.22 0.11 0.20 52 50 0.16 52 98 0.10 52 99 0.11 5ý 103 0.13 52 104 0.11 52 105 0.12 52 113 0.12 0.25 52 114 0.27 0.32 52 115 0.14 0.15 0.10 52 116 0.15 0.14 52 117 0.23 52 118 0.07 0.08 52 119 0.14 0.38 0.09 0.10 0.20 52 120 0.05 0.07 52 122 0.09 52 125 0.29 0.09 53 3

0.17 53 5

0.20 53 7

0.21 53 8

0.47 0.31 53 9

0.39 DEG CHN 151 P2 136 P2 143 P2 149 P2 145 P2 156 P2 139 P2 142 P2 149 P2 143 P2 151 P2 142 P2 155 P2 140 P2 150 P2 141 P2 144 P2 144 P2 125 P2 133 P2 141 P2 143 P2 150 P2 124 P2 145 P2 134 P2 131 P2 109 P2 148 P2 153 P2 127 P2 138 P2 132 P2 135 P2 149 P2 142 P2 114 P2 142 P2 136 P2 128 P2 139 P2 108 P2 123 P2 134 P2 150 P2 134 P2 132 P2 140 P2 146 P2 139 P2 142 P2 135 P2 151 P2 147 P2 144 P2 142 P2 139 P2 134 P2 153 P2 154 P2 144 P2 141 P2 134 P2 144 P2 132 P2 138 P2 153 P2 143 P2 144 P2 148 P2 136 P2 147 P2 138 P2 78 P2 96 P2 139 P2 142 P2 138 P2 137 P2 134 P2 IND %TW TWD 8 TWD 10 TWD 7 TWD 11 TWD 10 TWD 9 TWD 11 TWD 14 TWD 5 TWD 9 TWD 6 TWD 11 TWD 6 TWD 13 TWD 7 TWD 8 TWD 16 TWD 6 TWD 9 TWD 9 TWD 5 TWD 7 TWD 6 TWD 11 TWD 13 TWD 20 TWD 20 TWD 10 TWD 12 TWD 5 TWD 6 TWD 7 TWD 8 TWD 7 TWD 8 TWD 7 TWD 4 TWD 14 TWD 17 TWD 20 TWD 17 TWD 10 TWD 9 TWD 11 TWD 6 TWD 10 TWD 9 TWD 6 TWD 7 TWD 9 TWD 8 TWD 8 TWD 8 TWD 15 TWD 17 TWD 19 TWD 10 TWD 10 TWD 7 TWD 10 TWD 10 TWD 13 TWD 5 TWD 6 TWD 10 TWD 21 TWD 7 TWD 7 TWD 13 TWD 4 TWD 5 TWD 6 TWD 17 TWD 6 TWD 9 TWD 11 TWD 11 TWD. 20 TWD 15 TWD 19 LOCATION 011

-0.58 013

+0.16 013

-0.58 012

-0.61 014

+0.11 010

+0.53 013

+0.18 011

-0.48 010

-0.53 013

-0.53 011

+0.27 014

+0.21 012

-0.48 011

+0.26 012

-0.45 011

+0.29 013

+0.29 010

-0.47 010

+0.51 009

+0.59 008

-0.39 010

-0.39 012

-0.42 010

-0.43 014

-0.47 010

-0.46 014

-0.49 010

+0.59 010

+0.58 010

+0.17 009

+0.15 009

+0.10 009

-0.60 009

+0.10 009

+0.02 009

+0.07 010

+0.00 009

+0.07 009

+0.02 009

-0.65 009

+0.07 008,.

-0.58 009

-0.65 009

-0.68 009

+0.02 008

-0.63 009

-0.65 010

+0.07 008

-0.62 015

-0.75 010

+0.08 015

-0.77 011

-0.53 010

+0.56 012

-0.58 010

+0.50 014

+0.16 011

-0.48 010

+0.56 011

-0.53 010

+0.55 011

-0.50 013

+0.21 011

-0.50 014

+0.24 012

-0.45 010

+0.61 012

+0.24 014

-0.48 011

+0.26 010

-0.47 010

-0.47 013

+0.29 010

+0.61

,010

+0.64 010

-0.39 010

-0.46 010

-0.48 014

-0.52 010

+0.61 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL I

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

5 20 18 18 18 20 5

18 20 20 0

18 20 20 18 18 18 4

20 5

20 18 20 18 8

8 8

8 6

8 6

6 8

98 26 26 52 0

563 52 50 48' 48 48 50 48 48 5

48 0

563 50 50 8

50 48 0

579 4

581 18 20 18 18 18 20 20 18 7

18 7

18 20 20 34 2

20 3

20 18 18 7

18 0

18 12 18 20 4

20 4

20 18 5

18 8

8 8

6 6

8 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:22 AM Component: S/G A Page 38 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW 53 53 53 53 53 53 53 53 53 53 53 53 53 53 53 53 53 53 53 53 53 53 53 53 53 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 TUBE VOLTS

1=

10 0.25 15 0.13 16 0.14 18 0.10 29 0.12 30 0.17 31 0.12 0.08 33 0.07 37 0.09 39 0.11 41 0.13 0.18 42 0.13 49 0.20 0.12 0.14 51 0.09 79 0.13 101 0.10 109 0.08 114 0.09 116 0.11 117 0.15 0.07 119 0.15 0.07 121 0.07 0.10 122 0.12 0.22 0.12 0.19 123 0.06 126 0.16 1

0.13 2

0.13 0.54 4

0.16 5

0.20 6

0.10 7

0.44 8

0.34 0.26 9

0.26 0.12 11 0.31 16 0.13 20 0.11 25 0.11 28 0.08 0.08 0.13 32 0.16 33 0.09 34 0.10 35 0.11 37 0.10 0.15 38 0.18 39 0.12 0.08 40 0.17 42 0.09 43 0.21

'44 0.30 0.13 0.14 0.13 45 0.24 0.14 49 0.12 50 0.10 0.18 0.09 0.09 51 0.14 52 0.15 0.08 63 0.15 DEG 130 149 144 144 152 126 142 144 147 142 146 144 128 140 143 125 126 146 147 123 135 94 154 145 147 145 155 153 136 138 139 147 138 139 117 138 145 135 135 140 Ill 134 141 138 137 146 137 139 141 133 144 96 138 140 150 149 147 138 144 141 145 122 131 142 141 139 93 104 125 141 106 117 125 123 131 103 129 140 148 138 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW LOCATION EXT EXT UTIL 1

TWD 12 TWD 7 TWD 8 TWD 6 TWD 6 TWD 10 TWD 7 TWD 4 TWD 4 TWD 5 TWD 6 TWD 7 TWD 10 TWD 7 TWD 11 TWD 7 TWD 8 TWD 5 TWD 7 TWD 5 TWD 6 TWD 7 TWD 8 TWO 10 TWD 5 TWD 10 TWD 5 TWO 5 TWD 7 TWD 8 TWD 14 TWD 8 TWO 12 TWD 5 TWD 11 TWO 7 TWO 7 TWO 24 TWD 9 TWD 10 TWO 6 TWO 19 TWD 17 TWD 14 TWD 13 TWD 6 TWO 14 TWD 8 TWD 7 TWD 6 TWO 5 TWD 4 TWD 7 TWD 8 TWO 5 TWD 6 TWD 6 TWD 6 TWD 8 TWD 9 TWD 7 TWD 5 TWD 9 TWD 5 TWD 11 TWD 14 TWD 7 TWD 7 TWO 7 TWD 12 TWD 8 TWD 6 TWD 6 TWD 10 TWD 5 TWD 5 TWO 8 TWD 8 TWD 5 TWD 8 010 009 010 010 009 009 009 008 008 009 009 009 009 009 009 008 009 009 007 010 012 008 Ol Ol 014 009 012 013 010 012 Ol 010 013 010 010 008 012 013 010 010 010 010 014 014 012 010 014 013 013 010 009 008 009 009 009 009 009 008 009 009 009 013 009 009 009 009 009 008 007 009 009 009 008 009 009 007 009 009 009 009

+0.61

-0.53

+0. 17

+0.15

+0.02

+0.12

+0.07

+0.12

+0.10

+0.07

+0.10

+0.02

-0.65

-0.63

+0.05

-0.63

-0.65

+0.02

-0.66

+0.02

-0. 66

+0.11

-0.50

-0.51

+0.08

-0.56

-0. 45

-0.48

-0.45

+0.29

+0.29

-0.50

+0.29

-0.43

+0.63

+0.32

-0.34

+0.37

-0.39

-0.41

-0.42

-0.44

-0.49

+0.25

-0.46

-0.53

-0.59

-0.61

+0.12

+0.07

+0.12

+0.12

-0.59

+0.02

+0.05

+0.02

+0.10

+0.12

+0.07

+0.02

+0.10

-0.15

-0.66

+0.02

+0.07

+0.02

-0. 63

-0.63

-0.63

+0.07

-0. 68

-0.65

-0. 65

-0.66

+0.07

-0. 65

-0.65

-0. 63

+0.07

+0.05 LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

6 6

6 26 28 28 50 48 48 48 48 48 48 5o 8

50 48 48 6

48 7

48 48 0

579 66 18 5

20 6

20 18 0

18 18 18 18 5

18 20 20 20 20 0

18 20 8

8 8

8 6

4 8

6 8

8 6

6 6

6 7

24 28 26 48 48 7

48 50 48 50 48 48 48 50 48 5

48 0

565 50 48 50 6

50 4

50 5

50 48 48

.5 50 48 48 48 48 2

50 48 48 48 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repi 4/22/2008 9:45:22 AM Component:

S/G A Page 39 of 97 ONSlAR-ZOC24 -

Tube Support Wear QUERY: Query~ifli ROW TUBE VOLTS 54 82 0.08 54 107 0.13 0.09 54 110 0.09 0.09 54 Il1 0.08 54 113 0.16 54 116 0.12 0.09 54 117 0.12 54 118 0.27 54 119 0.09 0.14 54 120 0.09 0.17 0.07 54 121 0.09 0.14 54 123 0,14 0.08 54 126 0.17 55 4

0.18

  • 55 5

0.26 55 6

0.41 0.16 55 7

0.23 55 8

0.20 55 14 0.17 55 17 0.12 55 24 0.14 55 27 0.10 0.10 0.15 0.11 55 29 0.09 55 32 0.15 55 35 0.15 55 39 0.09 55 40 0.11 55 41 0.33 0.19 55 42 0.15 55 43 0.09 55 45 0.13 0.14 55 46 0.12 55 47 0.12 0.11 0.09 55 49 0.13 55 50 0.11 0.16 55 53 0.15 55 60 0.05 55 62 0.15 0.03 0.09 55 66 0.10 55 68 0.12 55 115 0.19 0.24 55 116 0.06 55 118 0.13 0.14 55 119 0.14 0.07 55 120 0.10 0.15 0.07 55 121 0.22 0.09 0.07 55 126 0.17 0.18 0.17 0.38 0.14 56 1

0.38 0.12 56 2

0.23 DEG CHN 113 P2 144 P2 121 P2 155 P2 122 P2 153 P2 147 P2 150 P2 155 P2 145 P2 146 P2 151 P2 140 P2 145 P2 141 P2 143 P2 145 P2 141 P2 147 P2 154 P2 115 P2 141 P2 144 P2 137 P2 127 P2 144 P2 123 P2 140 P2 131 P2 142 P2 135 P2 1SO P2 132 P2 124 P2 145 P2 124 P2 103 P2 151 P2 127 P2 133 P2 142 P2 138 P2 92 P2 136 P2 111 P2 125 P2 115 P2 111 P2 134 P2 115 P2 142 P2 104 P2 140 P2 158 P2 130 P2 156 P2 142 P2 124 P2 122 P2 127 P2

.133 P2 153 P2 153 P2 147 P2 135 P2 136 P2 153 P2 142 P2 148 P2 137 P2 137 P2 139 P2 149 P2 145 P2 149 P2 121 P2 111 P2 131 P2 129 P2 137 P2 IND %TW TWD 4 TWD 9 TWD 6 TWD 6 TWD 6 TWD 6 TWD 11 TWD 8 TWD 7 TWD 8 TWD 16 TWD 7 TWD 10 TWD 6 TWD 11 TWD 5 TWD 7 TWD 10 TWD 10 TWD 6 TWDO 11 TWD 9 TWD 14 TWD 18 TWD 8 TWD 13 TWD 10 TWD 9 TWD 7 TWD 10 TWD 6 TWD 6 TWD 9 TWD 6 TWD 5 TWD 9 TWD 8 TWD 5 TWD 6 TWD 16 TWD 10 TWD 8 TWD 5 TWD 7 TWD 7 TWD 7 TWD 9 TWD 8 TWD 7 TWD 10 TWD 6 TWD 9 TWD 8 TWD 3 TWD 8 TWD 2 TWD 5 TWD 7 TWD 7 TWD 13 TWD 15 TWD 5 TWD 9 TWD 10 TWD 9 TWD 5 TWD 7 TWD 11 TWD 5 TWD 14 TWD 6 TWD 5 TWD 12 TWD 12 TWD 12 TWD 22 TWD 10 TWD 18 TWD 7 TWD 12 LOCATION 009

-0.02 010

+0.08 012

-0.69 011

-0.61 010

+0.13 011

-0.58 012

-0.61 012

-0.58 010

+0.56 011

-0.50 010

+0.56 012

-0.53 010

+0.55 013

+0.19 010

+0.61 010

-0.50 012

+0.26 011

-0.45 010

-0.50 012

+0.26 010

+0.64 010

-0.41 010

-0.44 010

-0.46 010

+0.66 010

-0.44 010

+0.61 012

-0.54 012

-0.61 012

-0.64 008

+0.15 009

+0.10 010

+0.07 011

-0.63 010

+0.05 009

+0.07 009

+0.02 009

+0.02 009

+0.05, 009

-0.63 009

+0.02 009

+0.05 009

+0.02 009

+0.02 008

-0.63 009

+0.02 008

-0.60 009

-0.68 009

-0.03 008

-0.69 009

+0.05 009

-0.63 009

+0.02 009

+0.05 008

-0.65 008

+0.05 007

+0.14 007

+0.17 009

-0.07 014

+0.03 014

-0.69 011

-0.50 012

-0.47 011

+0.24 010

+0.56 013

+0.16 012

-0.47 011

-0.47 011

+0.21 014

-0.53 010

+0.13 011

+0.24 013

-0.42 012

+0.32 011

+0.32 010

+0.61 009

+0.58 012

-0.34 009

+0.61 012

-0.34 EXT EXT LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

66 18 6

18 18 18 20 20 18 6

18 20 18 20 20 18 18 0

18 20 20 20 5

20 18 6

8 6

6 8

7 6

22 24 0

607 48 48 48 6

48 48 48 48 50 48 50 50 48 48 50 8

50 48 0

563 0

563 0

563 0

563 48 9

48 48 48 48 48 48 0

601 66 18 18 20 20 20 18 5

18 20 20 0

20 18 18 5

18 20 20 20 20 20 8

8 8

LEG INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:22 AM Component: S/G A Page 40 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 56 3

0.20 0.10 56 4

0.19 56 5

0.10 0.20 56 6

0.27 56 7

0.26 56 9

0.23 0.35 56 10 0.11 56 17 0.12 56 20 0.17 56 21 0.17 56 23 0.13 56 30 0.32 0.18 0.10 56 37 0.10 56 39 0.10 0.10 0.11 56 44 0.13 56 49 0.12 56 50 0.16 56 52 0.13 0.17 56 61 0.07 56 68 0.10 56 107 0.12 56 111 0.15 0.13 56 112 0.06 56 113 0.09 0.09 56 114 0.07 56 115 0.12 56 119 0.15 0.15 0.13 56 120 0.07 0.08 56 121 0.12 56 122 0.12 0.81 0.16 0.47 56 127 0.27 57 1

0.09 57 2

0.21 57 3

0.31 0.10 57 4

0.14 57 5

0.39 57 6

0.43 0.18 0.17 57 11 0.16 57 14 0.12 57 17 0.11 57 18 0.09 57 22 0.14 0.14 0.19 57 28 0.20 0.12 57 29 0.09 0.16 57 44 0.10 0.29 57 46 0.10 57 47 0.13 57 53 0.17 57 61 0.17 57 63 0.06 57 92 0.06 57 110 0.17 57 111 0.17 0.15 0.07 57 112 0.13 DEG CHN 139 P2 119 P2 131 P2 103 P2 114 P2 138 P2 143 P2 144 P2 131 P2 145 P2 145 P2 121 P2 139 P2 134 P2 129 P2 143 P2 129 P2 148 P2 147 P2 120 P2 140 P2 135 P2 147 P2 110 P2 146 P2 127 P2 1.48 P2 144 P2 125 P2 127 P2 153 P2 158 P2 145 P2 134 P2 153 P2 143 P2 138 P2 145 P2 142 P2 149 P2 153 P2 137 P2 146 P2 130 P2 143 P2 137 P2 135 P2 135 P2 94 P2 136 P2 152 P2 152 P2 134 P2 139 P2 1"36 P2 138 P2 150 P2 148 P2 148 P2 136 P2 144 P2 141 P2 131 P2 130 P2 142 P2 141 P2 131 P2 134 P2 131 P2 125 P2 136 P2 143 P2 132 P2 66 P2 90 P2 135 P2 133. P2 137 P2 151 P2 149 P2 IND TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD

%TW 10 5

10 5

10 14 13 11 16 6

7 12 12 9

16 10 6

6 6

6 6

7 6

9 7

9 4

6 8

10 9

4 6

6 5

8 10 10 9

5 6

8 9

34 11 25 17 5

11 16 6

7 19 18 9

9 9

7 7

58 8

10 10 6

5 9

6 14 6

10 10 9

4 3

11 11 10 5

9 LOCATION 010

-0.39 008

-0.39 010

-0.37 010

-0.41 010

+0.66 010

-0.44 010

-0.44 012

-0.47 010

+0.61 010

-0.49 010

+0.15 012

-0.62 012

-0.66 009

-0.66 011

-0.68 011

+0.05 010

+0.05 009

+0.05

.009

+0.07 009

-0.61 013

-0..76 009

+0.05 009

+0.02 009

-0.65 009

+0.02 008

-0.65 009

+0.00 008

-0.69 010

+0.05 015

-0.72 011

-0.59 011

-0.55 012

-0.59 010

+0.19 011

+0.13 011

+0.13 013

+0.19 011

-0.48 010

+0.59 012

-.0.50 010

-0.50 010

-0.45 012

-0.47 011

+0.26 010

+0.26 010

-0.47 013

-0.40 009

-0.42 010

+0.68 010

-0.39 012

-0.34 010

-0.38 010

-0.42 010

-0.44 010

+0.62 011

+0.29 014

-0.54 012

+0.20 012

-0.59 010

+0.17 009

-0.58 010

+0.10 011

-0.63 009

-0.63 011

+0.02 010

+0.07 009

-0.61 009

+0.02 008

-0.63 009

+0.05 009

+0.00 009

+0.02 009

+0.05 009

-0.05 007

+0.19 010

+0.08 014

-0.03 010

+0.11 015

+0.00 012

-0.66 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTIL 2

CAL #

6 4

6 8

6 6

4 8

6 6

7 6

4 8

22 8

607 9

609 0

609 48 48 2

48 48 48 5

48 48 48 50 48 48 9

48 50 5

517 18 18 18 20 18 18 5

20 18 18 18 18 20 20 18 20 20 20 20 18 8

6 8

8 56 8

56 56 56 6

22 5

24 22 22 22 22 50 2

50 48 6

48 50 13 50 48 0

563 48 48 48 66 18 18 18 0

18 20 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510UL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51DXB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSl Repl 4/22/2008 9:45:22 AM Component: S/G A Page 41 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 57 113 0.11 57 114 0.08 0.06 57 117 0.09 57 119 0.13 0.08 0.11 57 120 0.09 57 121 0.17 0.32 57 122 0.07 57 123 0.06 0.16 0.20 0.21 57 127 0.19 57 128 0.17 58 2

0.20 0.61 0.11 58 3

0.47 58 4

1.45 0.21 0.25 0.16 1.64 58 5

0.91 0.10 0.12 58 7

0.15 58 8

0.12 58 10 0.18 58 16 0.13 58 17 0.12 58 32 0.12 58 33 0.12 58 34 0.13 0.21 58 42 0.12 58 48 0.17 58 49 0.09 58 50 0.13 0.08 58 52 0.15 58 54 0.10 58 56 0.09 58 62 0.12 58 77 0.13 58 97 0.16 0.13 58 106 0.17 58 112 0.11 58 114 0.07 0.10 0.06 58 118 0.07 58 119 0.16 58 120 0.33 0.11 58 121 0.07 58 122 0.13 0.10 0.14 0.13 58 123 0.14 0.15 58 124 0.48 0.08 58 128 0.38 59 1

0.13 59 2

0.37 0.21 59 3

0.89 0.11 59 4

0.71 0.26 0.16 59 5

0.12 59 6

0.18 0.21 DEG CHN IND %TW 139 P2 TWD 7 160 P2 TWD 6 125 P2 TWD 5 152 P2 "TWD 6 151 P2 TWD 9 135 P2 TWDO6 140 P2 TWD 7 153 P2 TWD 7 140 P2 TWD 11 136 P2 TWD 18 156 P2 TWD 5 136 P2 TWD 5 140 P2 TWD 10 139 P2 TWD 13 135 P2 TWD 13 118 P2 TWD 12 107 P2 TWD 12 90 P2 TWD 10 132 P2 TWD 24 123 P2 TWD 6 135 P2 TWD 21 124 P2 PID 132 P2 TWD 10 141 P2 TWD 12 141 P2 TWD 8 119 P2 TWD 42 131 P2 TWD 33 136 P2 TWD 6

145 P2 TWD 7 129 P2 TWD 8 143 P2 TWD 6 136 P2 TWD 9 151 P2 TWD 7 145 P2 TWD 7 135 P2 TWD 7 154 P2 TWD 6 146 P2 TWD 7 124 P2 TWD 11 132 P2 TWD 9 146 P2 TWD 9 121 P2 TWD 5 123 P2 TWD 9 140 P2 TWD 6

129 P2 TWD 9

141P2 TWD 8 147 P2 TWD 5 141 P2 TWD 7 148 P2 TWD 8 149 P2 TWD 9

126 P2 TWD 7

139 P2 TWD 11 128 P2 TWD 7 147 P2 TWD 5 152 P2 TWD 7 123 P2 TWD 5 153 P2 TWD 5 149 P2 TWD 11 137 P2 TWD 19 152 P2 TWD 8 154 P2 TWD 5 145 P2 TWD 9 135 P2 TWD 7 143 P2 TWD 9 146 P2 TWD 9 152 P2 TWD 10 145 P2 TWD 11 129 P2 TWD 25 135 P2 TWD 6

128 P2 TWD 21 99 P2 TWD 7 131 P2 TWD 17 85 P2 TWD 11 130 P2 TWD 32 137 P2 TWD 6 130 P2 TWD 27 119 P2 TWD 13 129 P2 TWD 8 88 P2 TWD 7 141 P2 TWD 9 131 P2 TWD 11 LOCATION 010 012 010 012 010 014 012 013 012 011 013 014 012 011 010 010 010 010 011 011 010 010 010 014 014 010 010 011 014 010 009 010 012 012 009 009 009 009 008 009 009 009 009 009 009 009 009 007 012 015 014 014 010 Ol 008 012 Ol 013 Ol 013 014 Oill 011 010 014 011 010 010 010 010 010 010 010 010 010 010 Ol 010 009 010

+0.16

+0.08

+0.13

-0.58

+0.56

-0.67

+0.16

-0.58

+0.21

-0.45

+0.21

+0.21

-0.48

+0.24

-0.51

+0.61

+0.63

+0.71

+0.39

-0.37

-0.37

-0.39

+0.02

-0.42

+0.32

-0.39

-0.42

+0.32

-0.44

-0.44

-0.49

+0.61

-0.54

-o'.56

+0.07

+0.02

+0.07

-0.63

-0.69

+0.02

+0.02

-0.60

+0.10

-0.68

-0.02

+0.02

+0.05

-0.64

-0.75

-0.73

-0.03

-0.03

+0.13

-0.61

+0.11

-0.56

-0.53

-0.58

-0.45

+0.21

+0.21

+0.21

-0.45

+0.61

-0.55

+0.26

-0.45

+0.27

+0.64

+0.61

-0.37

+0.69

-0.37

+0.05

-0.39

+0.66

+0.34

+0.64

+0.58

+0.64 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE ELTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE

,UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LME UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR

'WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

5 18 20 4

20 18 18 18 4

18 20 18 18 20 18 18 18 18 18 20 6

6 3

6 8

56 6

6 6

LAR 6

8 8

8 8

6 6

7 6

22 24 48 50 48 8

48 5

563 50 48 4

563 0

563 48 0

563 48 48 517 66 66 18 18 4

18 18 18 0

18 20 18 0

18 3

20 18 18 18 18 20 20 18 3

18 18 8

6 6

8 8

6 6

6 8

6 6

LEG PROBE OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET

  • 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL INLET 510XB INLET 510XB INLET 510UL INLET 51OUL INLET 510XB INLET 51OUL INLET 510XB INLET 510XB OUTLET 51OUL INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name: ONSr Repl 4/22/2008 9:45:22 Am Component:

S/G A Page 42 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: Query~il]l ROW 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 TUBE 7

8 15 16 17 20 32 33 34 35 39 40 46 51 52 61 71 88 103 104 106 108 114 116 117 118 120 121 122 123 124 125 126 127 128 1

2 3

4 5

6 7

9 13 16 19 23 28 29 32 33 34 36 37 40 VOLTS 0.13 0.15 0.10 0.27 0.17 0.13 0.30 0.11 0.24 0.31 0.11 0.14 0.11 0.13 0.11 0.09 0.10 0.08 0.14 0.10 0.08 0.08 0.12 0.13 0.06 0.06 0.10 0.09 0.12 0.10 0.09 0.13 0.11 0.09 0.10 0.12 0.11 0.08 0.07 0.10 0.16 0.19 0.08 0.14 0.22 0.13 0.14 0.07 0.13 0.14 0.11 0.06 0.12 0.59 0.15 0.36 0.27 0.70 0.27 0.26 0.23 0.28 0.24 0.09 0.14 0.14 0.20-0.13 0.11 0.13 0.16 0.15 0.13 0.11 0.14 0.11 0.11 0.10 0.08 0.17 DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG 155 P2 145 P2 157 P2 140 P2 143 P2 151 P2 140 P2 155 P2 141 P2 137 P2 135 P2 139 P2 147 P2 128 P2 146 P2 150 P2 158 P2 142 P2 142 P2

'148 P2 90 P2 145 P2 99 P2 120 P2 125 P2 133 P2 150 P2 116 P2 143 P2 137 P2 141 P2 149 P2 146 P2 150 P2 147 P2 141 P2 127 P2 139 P2 152 P2 152 P2 144 P2 146 P2 153 P2 147 P2 142 P2 138 P2 135 P2 137 P2 134 P2 146 P2 131 P2 138 P2 94 P2 134 P2 81 P2 131 P2 111 P2 131 P2 98 P2 140 P2 140 P2 121 P2 147 P2 139 P2 123 P2 147 P2 131 P2 147 P2 144 P2 147 P2 151 P2 124 P2 148 P2 153 P2 151 P2 135 P2 136 P2 141 P2 149 P2 122 P2 TWD 7 TWD 8 TWD 5 TWD 14 TWD 10 TWD 8 TWD 16 TWD 7 TWD 12 TWD 15 TWD 6 TWD 8 TWD 7 TWD 7 TWD 6 TWD 5 TWD 5 TWD 5 TWD 8 TWD 5 TWD 5 TWD 6 TWD 7 TWD 7 TWD 4 TWD 4 TWD 5 TWD 5 TWD.7 TWD 7 TWD 7 TWD 9 TWD 8 TWD 7 TWD 7 TWD 8 TWD 8 TWD 6 TWD 5 TWD 7 TWD 10 TWD 13 TWD 6 TWD 10 TWD 14 TWD 9 TWD 9 TWD 5 TWD 9 TWD 10 TWD 7 TWD 5 TWD 7 TWD 25 TWD 9 TWD 16 TWD 13 TWD 28 TWD 14 TWD 12 TWD 11 TWD 14 TWD 13 TWD 5 TWD 8 TWD 7 TWD 10 TWD 7 TWD 7 TWD 7 TWD 11 TWD 10 TWD 7 TWD 6 TWD 8 TWD 6 TWD 6 TWD 6 TWD 5 TWD 10 010 014 014 009 009 012 014 014 009 014 010 009 009 009 009 009 009 009 009 009 009 009 009 009 009 009 010 009 014 010 Ol 012 010 Oil 012 Ol 008 008 Ol 010 010 o0l Ol 013 013 010 Ol 010 009 012 Ol 010 010 010 010 010 010 010 010 009 O11 010 Ol 012 009 009 010 012 010 012 009 009 009 011 009 009 009 009 009 009

-0.44

-0.52

+0.22

-0.54

-0.56

-0.56

-0.66

+0.07

-0.56

+0.07

+0.12

-0.53

+0.00

+0.05

+0.07

+0.05

+0.00

-0.05

+0.02

+0.00

-0.71

-0.05

-0.68

+0.02

-0.05

+0.00

+0.10

+0.12

-0.02

+0.08

-0.61

-0.61

+0.16

-0.58

-0.58

-0.53

+0.16

-0.47

+0.21

-0.50

+0.58

-0.50

+0.21

-0.53

-0.50

-0.50

+0.26

-0.48

+0.58

-0.40

+0.26

-0. 39

+0.64

-0.37

+0.64

-0.39

+0.68

-0.39

+0.66

+0.58

+0.32

+0.66

+0.32

-0.39

+0.61

+0.56

+0.61

-0.42

+0.59

-0.56

-0.57

-0.59

+0.02

+0.05

+0.07

+0.02

+0.05

+0.00

+0.00

-0.66 LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE.

UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

8 6

3 6

22 24 24 24 3

24 22 22 22 7

22 34 48 50 48 50 34 48 50 34 6

34 48 48 66 66 66 5

66 66 18 18 20 20 20 18 18 18 4

20 20 20 8

18 20 4

20 18 20 20 18 18 20 18 18 20 8

8 8

6 6

8 8

6 6

8 8

8 8

6 6

6.

6 3

6 24 8

22 4

607 0

607 50 48 48 50 48 34 34 48 INLET INLET INLET INLET INLET INLET

.INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET OUTLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET PROBE 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repy 4/22/2008 9:45:23 AM Component: S/G A Page 43 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: Query~l[1]

ROW TUBE VOLTS 60 44 0.14 60 50 0.08 60 52 0.13 0.09 60 55 0.08 60 61 0.10 60 62 0.08 60 110 0.11 60 111 0.07 0.12 0.07 60 114 0.14 60 115 0.10 60 116 0.08 0.08 60 119 0.22 0.12 0.11 60 120 0.11 60 121 0.15 0.09 0.10 60 122 0.11 0.11 0.27 0.26 0.28 60 123 0.12 60" 124 0.11 0.11 0 08 60 125 0.09 60 127 0.13 0.08 61 1

0.12 0.14 61 2

0.56 0.19 61 3

0.30 0.19 61 4

1.19 0.21 0.12 61 5

0.13 0.11 61 6

0.30 0.22 0.25 61 9

0.13 0.08 61 13 0.12 61 15 0.31 0.10 61 20 0.13 61 26 0.10 61 30 0.09 61 48 0.21 61 56 0.11 61 62 0.11 61 103 0.10 61 110 0.11 61 111 0.08 61 113 0.08 61 115 0.07 61 116 0.16 0.14 61 117 0.09 61 118 0.13 61 120 0.34 0.17 0.10 61 121 0.11 61 122 0.14 0.18 0.11 61 123 0.16 0.21 0.12 61 124 0.09 0.30 DEG CHN 126 P2 127 P2 122 P2 150 P2 143 P2 140 P2 113 P2 148 P2 137 P2 119 P2 136 P2 155 P2 149 P2 147 P2 152 P2 140 P2 150 P2 146 P2 150 P2 147 P2 138 P2 130 P2 145 P2 144 P2 140 P2 143 P2 140 P2 136 P2 150 P2 140 P2 146 P2 125 P2 137 P2 140 P2 140 P2 133 P2 132 P2 116 P2 142 P2 116 P2 125 P2 91 P2 134 P2 69 P2 154 P2 136 P2 124 P2 145 P2 145 P2 143 P2 157 P2 140 P2 128 P2 131 P2 149 P2 143 P2 146 P2 144 P2 120 P2 117 P2 138 P2 148 P2 140 P2 147 P2 141 P2 142 P2 157 P2 150 P2 145 P2 148 P2 142 P2 147 P2 146 P2 138 P2 148 P2 144 P2 134 P2 131 P2 156 P2 135 P2 IND %TW TWD 8 TWD 5 TWD 7 TWD 5 TWD 4 TWD 6 TWD 5 TWD 9 TWD 5 TWD 8 TWD 5 TWD 10 TWD 7 TWD 6 TWD 6 TWD 14 TWD 9 TWD 8 TWD 8 TWD 10 TWD 6 TWD 7 TWD 8 TWD 8 TWD 17 TWD 16 TWD 17 TWD 8 TWD 8 TWD 8 TWD 6 TWD 7 TWD 9 TWD 6 TWD 7 TWD 8 TWD 23 TWD 10 TWD 15 TWD 10 TWD 36 TWD 10 TWD 6 TWD 7 TWD 7 TWD 14 TWD 11 TWD 12 TWD 8 TWD 5 TWD 7 TWD 15 TWD 6 TWD 9 TWD 6 TWD 5 TWD 13 TWD 6 TWD 6 TWD 5 TWD 7 TWD 6 TWD 5 TWD 4 TWD 11 TWD 10 TWD 6 TWD 9 TWO 20 TWD 11 TWD 7 TWD 7 TWD 10 TWD 12 TWD 8 TWD 10 TWD 13 TWD 8 TWD 7 TWD 18 LOCATION 009

+0.05 009

-0.05 009

-0.68 009

+0.02 009

+0.00 009

+0.02 009

-0.65 012

-0.62 015

-0.72 013

-0.69 012

-0.61 011

-0.63 010

+0.16 012

-0.63 010

-0.58 013

+0.16 012

-0.53 O11

+0.16 010

-0.50 011

-0.51 010

-0.48 011

+0.21 014

+0.16 012

+0.26 012

-0.47 011

-0.50 010

+0.58 013

+0.21 012

-0.47 011

+0,26 010

-0.42 010

-0.51 011

+0.29 009

+0.51 008

-0.37 009

-0.39 010

-0.36 010

+0.66 010

-0.37 010

+0.66 010

-0.39 010 40.68 011

+0.34 010

+0.64 011

+0.32 009

+0.58 010

+0.64 011

+0.34 012

-0.47 012

+0.27 012

-0.54 009

-0.53 010

+0.17 010

+0.05 011

+0.05 009

+0.02 009

-0.03 009

-0.02 009

-0.70 010

+0.07 015

-0.77 011

-0.63 010

+0.11 009

-0.61 011

+0.11 011

-0.61 011

-0.56 011

-0.61 012

-0.55 011

+0.18 010

-0.58 011

-0.48 012

-0.53 010

+0.53 011

-0.50 011

+0.19 011

-0.51 010

-0.45 014

+0.16 011

+0.21 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

48 48 48 48 50 48 48 6

589 18 18 18 20 5

18 20 20 18 18 18 20 18 18 0

18 20 20 20 20 20 18 20 20 20 18 18 18 8

8 6

8 6

8 8

6 6

2 6

8 8

6 66 8

4 8

22 22 4

22 0

609 48 50 4

561 50 48 66 14 16 14 14 16 16 14 16 16 16 16 14 16 16 5

16 14 14 6

14 16 16 LEG PROBE INLET 51OXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL OUTLET 510LX OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL INLET 510XB INLET 510XB INLET 51OUL INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:23 AM Component: S/G A Page 44 of 97 ONSlAR-EOC24 - Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 0.18 0.18 61 125 0.07 61 126 0.32 0.29 61 127 0.15 0.22 61 128 0.09 61 129 0.16 62 2

0.97 62 3

0.94 0.10 62 4

0.16 0.18 0.25 62 5

0.27 0.11 0.09 62 6

0.25 0.16 62 8

0.10 62 9

0.23 62 13 0.16 62 27 0.17 62 31 0.15 62 49 0.13 62 51 0.14 62 56 0.34 0.14 62 60 0.08 0.10 62 68 0.07 62 72 0.05 62 109 0.06 62 111 0.10 62 113 0.09 62 114 0.09 62 115 0.20 0.11 62 116 0.06 0.18 0.12 62 117 0.08 62 118 0.10 62 119 0.19 0.10 62 121 0.19 0.11 0.11 62 122 0.32 0.17 0.15 62 124 0.08 0.07 0.08 62 125 0.07 0,59 0.17 0,10 0.18 62 126 0.72 62 128 0.10 0.07 62 129 0.13 63 2

0.64 0.23 63 3

0.82 63 4

0.16 0.86 63 5

0.10 63 6

0.14 63 7

0.11 63 11 0.13 63 13 0.12 63 15 0.46 0.13 0.10 63 16 0.14 0.19 63 19 0.11 DEG 137 136 129 140 138 141 132 152 122 125 128 152 131 139 138 140 146 145 130 139 123 142 147 145 141 120 126 137 137 141 129 117 152 140 116 147 145 146 127 147 142 152 147 151 142 146 147 150 130 142 147 145 147 147 137 150 131 138 148 130 130 150 147 154 131 99 129 144 126 148 141 143 144 152 140 133 141 146 133 138 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P 2 P2 IND %TW TWD 12 TWD 12 TWD 4 TWD 19 TWD 18 TWD 10 TWD 13 TWD 7 TWD 10 TWD 32 TWO 33 TWD 6 TWD 8 TWD 9 TWD 12 TWD 14 TWD 6 TWD 5 TWD 12 TWD 9 TWD 5 TWD 13 TWD 10 TWD 11 TWD 9 TWD 7 TWD 7 TWD 16 TWD 8 TWD 5 TWD 7 TWD 5 TWD 4 TWD 4 TWD 6 TWD 6 TWD 7 TWD 12 TWD 8 TWD 5 TWD 12 TWD 9 TWD 5 TWD 7 TWD 12 TWD 7 TWD 12 TWD 7 TWD 8 TWD 19 TWD 11 TWD 10 TWD 6 TWD 5 TWD 6 TWD 5 TWD 27 TWD II TWD 7 TWD 11 TWD 32 TWD 7 TWD 5 TWD 8 TWD 25 TWD 12 TWD 31 TWD 8 TWD 30 TWD 6 TWD 7 TWD 6 TWD 7 TWD 7 TWD 21 TWD 7 TWD 6 TWD 8 TWD 10 TWD 8 LOCATION EXT EXT 011

-0.48 UTE LTE 010

+0.55 UTE LTE 009

-0.48 UTE LTE 013

-0.50 UTE LTE 012

-0.42 UTE LTE 013

-0.45 UTE LTE 011

+0.29 UTE LTE 011

+0.26 UTE LTE 010

+0.56 UTE LTE 010

-0.34 LTE UTE 010

-0.39 LTE UTE 010

.+0.02 LTE UTE 009

-0.44 LTE UTE 011

+0.34 LTE UTE 009

+0.58 LTE UTE 009

+0.59 LTE UTE 011

+0.32 LTE UTE 010

-0.42 LTE UTE 010

+0.61 LTE UTE 010

-0.46 LTE UTE 010

-0.46 LTE UTE 011

-0.44 LTE UTE 012

-0.54 LTE UTE 009

-0.61 LTE UTE 009

+0.07 LTE UTE 008

-0.63 LTE UTE 008

-0.65 LTE UTE 009

-0.68 LTE UTE 009

+0.02 LTE UTE 009

-0.03 UTE LTE 007

+0,03 UTE LTE 009

+0.03 UTE LTD 009

-0.08 UTE LTE 010

+0.08 UTE LTE 011

-0.66 UTE LTE 011

-0.64 UTE LTE 011

-0.66 UTE LTE 011

-0.61 UTE LTE 012

-0.58 UTE LTE 012

+0.11 UTE LTE 012

-0.63 UTE LTE 010

+0.45 UTE LTE 009

-0.58 UTE LTE 010

+0.50 UTE LTE 012

+0.19 UTE LTE 011

-0,53 UTE LTE 012

-0.56 UTE LTE 011

-0.51 UTE LTE 008

+0.21 UTE LTE 012

-0.50 UTE LTE 011

-0.50 UTE LTE 010

+0.55 UTE LTE 013

+0.18 UTE LTE 009

-0.50 UTE LTE 011

-0.48 UTE LTE 014

-0.43 UTE LTE 012

+0.29 UTE LTE 011

+0.24 UTE LTE 011

-0.45 UTE LTE 009

-0.45 UTE LTE 011

+0.26 UTE LTE 013

+0.26 UTE LTE 011

-0.42 UTE LTE 007

+0.29 UTE LTE 010

-0.37 LTE UTE 010

+0.66 LTE UTE 010

-0.37 LTE UTE 009

+0.61 LTE UTE 010

-0.41 LTE UTE 009

+0.59 LTE UTE 014

+0.27 LTE UTE 009

+0.59 LTE UTE 012

-0.52 LTE UTE 012

-0.54 LTE UTE 009

-0.51 LTE UTE 010

+0.19 LTE UTE 009

-0.10 LTE UTE 010

+0.15 LTE UTE 009

-0.56 LTE UTE 009

-0.62 LTE UTE UTIL 1

UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 2

WAR WAR WAR WAR WAR WAR 5

WAR WAR 5

WAR 0

WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR 0

WAR 0

CAL #

16 16 14 16 16 14 14 16 14 6

8 8

6 6

6 8

88 6

6 6

8 24 561 48 50 50 50 50 26 26 24 24 14 14 14 16 14 14 16 16 16 14 16 14 14 14 14 14 16 16 16 16 16 16 14 14 14 14 14 16 16 16 14 6

6 8

6 6

8 6

8 8

24 98 98 98 98 98 609 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 51oXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XBE 510XB 510XB 510XB 510XB 510XB 51OUL

AREVA NP Inc Customer Name: ONSI Repl ONSlAR-EOC24 -

Tube Support Wear 4/22/2008 9:45:23 AM Component: S/G A Page 45 of 97 QUERY: QueryMl[l]

ROW TUBE VOLTS 63 24 0.17 63 25 0.10 63 32 0.29 63 33 0.12 63 35 0.11 63 48 0.12 63 49 0.12 63 55 0.11 63 107 0.08 63 108 0.10 63 115 0.16 0.09 63 116 0.13 0.18 0.22 63 118 0.22 0.15 0.08 63 121 0.16 0.18 0.12 63 122 0.11 0.10 0.07 63 123 0.22 0.47 0.75 0.14 0.17 0.09 63 124 0.16 0.27 63 125 0.16 0.09 0.13 0.07 0.12 0.07 63 126 0.09 0.06 63 127 0.20 0.17 63 128 0.08 0.13 63 129 0.11 63 130 0.11 0.13 0.13 64 2

0.51 64 3

0.67 64 4

0.52 64 5

0.19 0.10 64 7

0.13 0.18 64 8

0.10 0.16 0.11 64 1i 0.12 64 14 0.16 64 15 0.09 0.12 64 16 0.12 0.13 64 22 0.23 64 31 0.10 64 34 0.18 64 37 0.14 0.22 64 40 0.14 64 44 0.15 64 48 0.15 64 49 0.17 64 53 0.10 0.17 64 55 0.10 64 62 0.05 64 63 0.14 64 101 0.09 64 107 0.09 DEG CHN 147 P2 147 P2 136 P2 150 P2 151 P2 141 P2 132 P2 141 P2 142 P2 133 P2 145 P2 141 P2 133 P2 143 P2 145 P2 144 P2 152 P2 140 P2 148 P2 139 P2 132 P2 146 P2 147 P2 148 P2 132 P2 130 P2 128 P2 145 P2 141 P2 123 P2 152 P2 139 P2 144 P2 139 P2 139 P2 153 P2 124 P2 132 P2 126 P2 153 P2 135 P2 147 P2 148 P2 145 P2 122 P2 149 P2 104 P2 138 P2 131 P2 135 P2 128 P2 95 P2 143 P2 155 P2 111 P2 146 P2 141 P2 142 P2 142 P2 136 P2 101 P2 151 P2 150 P2 144 P2 138 P2 146 P2 142 P2 144 P2 140 P2 136 P2 125 P2 149 P2 140 P2 71 P2 141 P2 112 P2 144 P2 145 P2 139 P2 133 P2 IND %¶ TWD 9 TWD 8 TWD 1I TWD 7 TWD 6 TWD 6 TWD 7 TWD 6 TWD 5 TWD 7 TWD 1i TWD 6 TWD 9 TWD I1 TWD 1 TWD 1i TWD 1i TWD 6 TWD i1 TWD 1.

TWD 8 TWD 8 TWD 7 TWO 5 TWD 1:

TWD 2:

TWD 3:

TWD 9 TWD 1.

TWD 6 TWD 1:

TWD 1 TWD I1 TWD 6 TWD 8 TWD 5 TWD 8 TWD 5 TWD 6 TWD 4 TWD 1:

TWD I:

TWD 6 TWO 9 TWD 7 TWD 8 TWD 9 TWD 9 TWD 2ý TWD 2" TWD 2:

TWD 11 TWD 5 TWD 7 TWD 9 TWO 6 TWD 9 TWD 6 TWD 6 TWD 8 TWO 6 TWD 7 TWD 7 TWD 7 TWD i:

TWD 6 TWD 9 TWD 8 TWD i:

TWD 8 TWD 8 TWD 8 TWD 9 TWD 6 TWD 1(

TWD 7 TWD 4 TWD 9 TWD 5 TWO 5 TW 4

0 2

4 4

1 0

1 3

3 2

1.

70 LOCATION 009

-0.58 014

-0.76 009

-0.63 009

+0.07 009

+0.05 009

+0.02 009

+0.02 009

+0.00 010

+0.07 010

+0.08 011

-0.61 010

+0.16 014

+0.05 014

-0.69 012

-0.61 012

-0.58 010

+0.50 008

+0.21 010

-0.48 009

-0.56 008

,+0.21 011

-0.50 013

+0.16 012

+0.18 014

+0.16 012

+0.24 011

-0.48 010

+0.56 010

-0.45 008

+0.24 014

-0.55 011

-0.50 013

+0.21 012

-0.48 011

+0.24 011

-0.45 010

-0.40 009

-0.51 013

+0.21 011

+0.24 011

+0.26 009

+0.58 011

+0.29 009

+0.55 010

+0.56 011

+0.29 010

+0.58 009

+0.55 010

-0.37 010

-0.37 010

-0.34 010

+0.64 011

+0.37 009

+0.56 010

+0.64 009

+0.56 010

-0.44 012

+0.29 010

-0.51 014

-0.61 010

+0.17 012

-0.54 012

+0.15 012

-0.54 009

-0.56 009

+0.07 009

+0.02 009

+0.02 012

-0.02 009

+0.05 009

+0.05 009

+0.02 009

+0.05 009

-0.67 009

+0.00 009

-0.68 009

-0.05 009.

-0.05 010

+0.02 010

+0.12 EXT.EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LIE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL #

48 6

559 50 48 48 50 48 48 66 14 14 0

14 16 16 16 16 16 16 14 14 14 16 4

16 3

16 14 14 14 14 14 5

14 16 16 14 14 14 14 14 14 16 16 14 14 16 16 14 16 16 16 6

8 6

6 4

6 6

6 8

8 8

3 6

6 22 24 24 22 5

22 22 48 50 50 50 48 48 50 48 48 48 7

559 26 24 66 66 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET PROBE 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:23 AM Component: S/G A Page 46 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 64 112 0.09 64 113 0.10 0.10 0.09 64 114 0.11 0.07 64 116 0.12 0.12 0.09 64 117 0.08 0.13 64 119 0.18 0.13 0.49 0.17 0.13 0.11 64 120 0.18 64 122 0.13 0.24 64 123 0.51 0.14 64 124 0.49 0.14 0.18 0.24 64 125 0.13 64 126 0.13 0.14 64 127 0.66 0.08 64 128 0.21 0.17 64 129 0.22 0.08 64 131 0.31 65 1

0.08 0.12 0.12 65 2

0.26 65 3

0.18 0.32 65 4

0.40 0.18 65 5

0.21 0.14 65 6

0.14 65 7

0.16 65 8

0.21 65 10 0.13 0.15 65 29 0.13 65 30 0.14 65 33 0.27 0.20 65 48 0.16 65 51 0.12 65 115 0.23 0.21 0.11 65 116 0.15 65 117 0.12 0.11 65 118 0.10 0.15 65 119 0.17 0.16 65 121 0.13 0.18 0.12 65 122 0.19 65 123 0.29 65 124 0.08 0.17 0.13 65 125 0.19 0.08 0.11 0.21 65 126 0.22 DEG 135 128 138 151 139 151 135 135 147 150 149 147 144 134 145 146 145 141 127 141 137 137 134 144 146 147 135 138 144 132 145 138 127 135 147 140 73 126 54 131 141 141 132 90 139 104 135 60 136 148 100 146 141 133 141 137 143 135 135 137 145 137 150 153 151 144 135 139 144 153 146 137 145 140 136 136 140 144 135 144 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWO 6 TWD 7 TWD 7 TWD 6 TWO 7 TWD 5 TWO 8 TWO 8 TWD 6 TWD 6 TWO 9 TWO 12 TWD 9 TWD 26 TWD 11 TWD 9 TWD 8 TWD 11 TWD 8 TWD 14 TWD 26 TWO 10 TWD 24 TWO 9 TWD 11 TWO 14 TWO 9 TWO 8 TWO 9 TWO 31 TWO 6 TWD 13 TWO 11 TWO 14 TWD 6 TWD 19 TWD 5 TWD 7 TWD 7 TWD 13 TWD 10 TWD 16 TWD 18 TWD 9 TWD 11 TWD 8 TWD 7 TWO 9 TWD 10 TWD 7 TWO 8 TWO 7 TWD 8 TWO 13 TWO 10 TWD 9 TWD 6 TWD 14 TWO 13 TWD 7 TWD 11 TWO 8 TWD 7 TWD 7 TWD 10 TWO 11 TWO 10 TWO 9 TWD 11 TWO 8 TWO 13 TWD 17 TWD 6 TWO 11 TWD 9 TWD 12 TWO 5 TWO 7 TWO 13 TWD 14 LOCATION 015

-0.72 012

+0.05 012

-0.68 010

+0.08 011

-0.64 010

+0.13 012

+0.11 012

-0.03 011

-0.61 014

+0.05 011

-0.61 012

+0.16 012

-0.58 011

-0.58 010

+0.48 009

-0.58 013

+0.11 013

-0.61 014

+0.13 010

+0.56 011

-0.50 010

+0.53 011

-0.48 009

+0.48 013

-0.21 014

-0.16 010

+0.55 013

+0.24 013

-0.48 011

+0.29 008

+0.26 013

-0.48 011

+0.27 013

-0.45 011

+0.29 013

-0.40 009

+0,61 011

+0.39 010

+0.66 010

-0.31 010

-0.37 014

-0.44 010

-0.39 010

+0.64 010

-0.42 010

+0.64 010

-0.44 010

+0.64 009

+0.59 009

+0.56 010

+0.56 009

+0.02 009

+0.07 009

-0.63 009

+0.02 009

+0.05 009

-0.02 012

-0.66 011

-0.61 010

+0.13 011

-0.63 013

+0.11 010

+0.50 011

-0.58 010

+0.48 011

-0.56 014

-0. 69 013

+0.13 013

.- 0.61 010

+0.53 011

+0.16 013

-0.56 011

+0.21 011

-0.50 010

-0.47 014

+0.19 012

-0.45 01i

-0.45 009

-0.53 013

+0.21 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL I

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG PROBE 14 16 16 16 14 14 14 14 5

14 16 3

16 16 16 16 16 16 0

16 14 14 14 16 16 14 14 14 14 16 14 0

14 16 16 14 14 16 16 16 8

8 6

8 6

8 8

6 6

6 8

8 3

6 8

6 6

5 6

50 48 50 50 48 50 14 14 0

14 16 14 14 16 16 14 10 14 14 14 14 16 14 16 16 16 14 14 14 14 16 OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET(

OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:24 AM Component: S/G A Page 47 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS DEG 65 127 0.21 138 0.11 131 0.60 128 0.32 129 0.07 143 65 128 0.10 144 66 1

0.22 140 66 2

0.10 131 66 4

0.13 137 66 5

0.19 142 0.17 129 66 6

0.16 145 0.13 149 66 11 0.13 142 66 13 0.09 135 66 15 0.17 144 66 21 0.22 145 66 29 0.26 132 66 36 0.09 157 66 38 0.12 143 66 62 0.08 149 66 63 0.15 137 66 113 0.11 121 66 114 0.20 144 0.11 146 0.07 118 66 115 0.10 133 66 117 0.20 135 0.27 137 66 118 0.12 149 0.15 142 0.18 149 66 119 0.10 156 66 122 0.10 147 0.09 147 0.24 148 0.17 144 0.12 140 66 123 0.09 151 0.10 137 0.40 136 0.18 143 66 124 0.14 145 66 125 0.33 134 0.11 144 0.12 137 0.12 128 0.11 141 66 127 0.32 136 0.14 141 66 128 0.18 141 66 129 0.09 145 67 1

0.16 134 67 4

0.13 136 67 5

0.23 143 0.13 110 67 6

0.19 137 67 9

0.24 148 0.13 155 67 10 0.12 148 0.11 127 67 11 0.12 147 67 13 0.11 138 67 15 0.12 145 0.13 130 67 17 0.15 143 0.12 138 67 18 0.29 129 0.17 138 67 21 0.13 131 67 33 0.10 145 67 34 0.28 133 67 51 0.10 150 67 55 0.08 151 0.07 147 67 61 0.07 147 67 65 0.03 156 67 105 0.14 129 67 109 0.11 139 67 110 0.08 151 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2, P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 13 TWD 7 TWD 28 TWD 18 TWD 5 TWD 7 TWD 12 TWD 6 TWD 8 TWD 10 TWD 9 TWD 10 TWD 8 TWD 8 TWO 6 TWD 9 TWD 11 TWD 13 TWO 5 TWD 7 TWD 5 TWD 9 TWD 8 TWD 13 TWD 8 TWD 5 TWD 7 TWD 13 TWD 16 TWD 9 TWD 10 TWD 12 TWD 7 TWD 7 TWD 7 TWD 15 TWD 11 TWD 8 TWD 6 TWD 7 TWD 21 TWD 11 TWD 10 TWD 18 TWD 7 TWD 8 TWD 8 TWD 7 TWD 18 TWD 9 TWD 12 TWD 6 TWD 10 TWD 7 TWD 13 TWD 8 TWD 10 TWD 13 TWD 8 TWD 7 TWD 7 TWD 7 TWD 6 TWD 7 TWD 7 TWD 9 TWD 7 TWD 14 TWD 9 TWD 9 TWD '6 TWD 14 TWD 6 TWD 5 TWD 4 TWD 5 TWD 2 TWD 7 TWD 7 TWD 6 LOCATION 013

-0.48 012

-0.40 011

+0.27 010

-0.48 013

+0.27 011

+0.26 009

+0.56 011

-0.37 010

-0.39 010

-0.39 010

+0.66 010

+0.64 010

-0.44 009

-0.51 010

-0.54 014

-0.61 009

-0.58 009

-0.63 009

+0.02 009

-0.63 009

+0.03 009

-0.05 012

-0.66 012

-0.68 011

-0.63 015

-0.74 009

-0.61 011

+0,11 011

-0.64 012

-0.63 011

-0.61 010

+0.48 010

+0.51 014

+0.08 012

-0.55 011

-0.55 010

+0.50 010

-0.53 012

-0.53 011

-0.51 010

+0.56 009

-0.59 011

-0.53 012

+0.27 012

-0.48 011

+0.21 011

-0.48 010

+0.61 013

+0.27 011

+0.29 011

+0.26 013

+0.29 009

+0.61 010

-0.39 010

-0.42 010

+0.66 010

+0.61 014

-0.54 009

+0.56 013

+0.22 010

-0.49 010

-0.54 010

-0.56

.010

-0.54 012

+0.17 009

-0.56 012

-0.59 014

-0.66 009

-0.56 011

-0.64 009

+0.02 009

-0.63 009

+0.05 010

-0.78 009

-0.05 009

-0.05 009

-0.05 oil

-0.66 010

+0.08 010

+0.05 EXT EXT UTIL UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR UTE LTE WAR UTE'LTE WAR 1

UTIL 2

CAL # LEG 14 OUTLET 14 OUTLET 14 OUTLET 14 OUTLET 14 OUTLET 16 OUTLET 12 INLET 3

12 INLET 6

12 INLET 10 INLET 10 INLET 12 INLET 3

12 INLET 2

12 INLET 4

12 INLET 22 INLET 22 INLET 50 INLET 50 INLET 48 INLET 24 OUTLET 24 OUTLET 14 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 14 OUTLET 14 OUTLET 14 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 5

14 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 14 OUTLET 14 OUTLET 14 OUTLET 14 OUTLET 16 OUTLET 14 OUTLET 14 OUTLET 14 OUTLET 14 OUTLET 14 OUTLET 14 OUTLET 14 OUTLET 16 OUTLET 5

14 OUTLET 12 INLET 10 INLET 12 INLET 12 INLET 10 INLET 12 INLET 7

12 INLET 10 INLET 5

10 INLET 5

12 INLET 22 INLET 22 INLET 22 INLET 24 INLET 24 INLET 22 INLET 6

22 INLET 4

609 INLET 50 INLET 48 INLET 50 INLET 50 INLET 50 INLET 24 OUTLET 24 OUTLET 6

583 INLET 14 OUTLET 16 OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB

AREVA NP Inc Customer Name: ONSI RepI 4/22/2008 9:45:24 AM Component: S/G A Page 48 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 67 113 0.07 67 i14 0.10 0.09 0.07 67 115 0.12 0.10 67 116 0.11 0.19 67 117 0.23 67 118 0.09 0.12 0.15 67 119 0.15 0.27 67 120 0.12 0.10 67 121 0.45 67 122 0.11 0.27 0.27 67 123 0.20 67 124 0.11 0.08 67 125 0.13 0.11 67 126 0.09 67 127 0.44 0.28 0.12 67 129 0.16 0.08 0.08 68 2

0.10 68 5

0.16 0.20 68 6

0.14 0.11 68 7

0.19 0.16 68 9

0.19 68 11 0.16 0.16 68 13 0.12 0.11 68 14 0.10 0.09 68 16 0.20 68 19 0.18 68 20 0.19 0.19 68 24 0.17 68 26 0.13 68 29 0.09 68 31 0.10 68 32 0.12 68 33 0.14 68 35 0;08 0.11 68 53 0.19 68 59 0.10 68 61 0.11 0.16 68 110 0.10 68 I11 0.11 68 114 0.10 68 115 0.13 68 116 0.14 0.18 68 117 0.13 68 119 0.11 0.14 0.13 68 120 0.16 0.14 0.08 68 121 0.12 0.14 0.25 68 122 0.22 0.20 DEG 154 148 135 147 136 145 149 147 145 150 151 153 137 133 147 151 140 152 145 141 145 150 142 154 112 139 132 133 153 119 142 140 64 134 127 144 127 131 139 146 147 147 134 151 146 148 135 125 130 132 141 144 147 154 118 127 135 151 144 124 118 138 141 130 133 148 140 138 149 140 147 150 149 132 146 149 141 143 141 140 CHN IND %TW P2 TWD 5 P2 TWD 7 P2 TWD 6 P2 TWD 5 P2 TWD 8 P2 TWD 7 P2 TWD 8 P2 TWD 13 P2 TWD 14 P2 TWD 7 P2 TWD 8 P2 TWD 10 P2 TWD 9 P2 TWD 16 P2 TWD 9 P2 TWDO7 P2 TWD 23 P2 TWD 8 P2 TWD 17 P2 TWD 17 P2 TWD 13 P2 TWD 8 P2 TWD 6 P2 TWD 9 P2 TWD 7

P2 TWD 7 P2 TWD 22 P2 TWD 16 P2 TWD 8

P2 TWD 10 P2 TWO 6 P2 TWD 5 P2 TWD 7 P2 TWD 9 P2 TWD 11 P2 TWD 8 P2 TWD 7 P2 TWD 11 P2 TWD 9 P2 TWD 11 P2 TWD 9 P2 TWD 9

P2 TWD 7 P2 TWD 6

P2 TWD 6

P2 TWD 6 P2 TWD 14 P2 TWD 10 P2 TWD 10 P2 TWD 10 P2 TWD 9 P2 TWD 7 P2 TWD 5 P2 TWD 5

P2 TWD 9

P2 TWD 8 P2 TWD 5 P2 TWD 6 P2 TWD 10 P2 TWD 7 P2 TWO 7 P2 TWD 10 P2 TWD 7 P2 TWD 7 P2 TWD 6 P2 TWD 9 P2 TWO 9 P2 TWD 11 P2 TWO 9 P2 TWD 8 P2 TWD 10 P2 TWD 9 P2 TWD 10 P2 TWD 9 P2 TWD 6

P2 TWD 8 P2 TWD 10 P2 TWD 16 P2 TWD 13 P2 TWD 12 LOCATION 011

-0.64 012

-0.66 011

-0.66 010

+0.13 014

+0.03 012

-0.66 011

+0.08 011

-0.63 011

+0.00 012

-0.58 011

-0.58 010

+0.48 014

-0.67 012

+0.16 011

+0.16 011

-0.55 010

+0.53 011

-0.53 010

+0.53 009

-0.55 010

+0.58 012

+0.26 011

+0.21 013

+0.29 011

+0.24 011

+0.26 013

+0.27 011

+0.24 009

+0.61 010

+0.64 013

+0.27 011

+0.29 010

+0.64 010

+0.64 010

-0.42 010

-0.44 010

+0.61 010

-0,44 010

+0.64 012

-0.46 009

-0.49 013

+0.20 012

-0.51 010

-0.54 010

-0.54 012

-0.51 009

-0.54 010

-0.59 009

-0.56 014

-0.71 009

-0.58 009

-0.63 009

+0.02 009

+0.02 009

-0.63 009

-0.61 007

-0.63 009

+0.05 009

+0.02 007

-0.67 008

-0.72 009

-0.72 011

-0.63 010

+0.08 010

+0.13 009

-0.63 012

-0.58 011

-0.61 009

-0.60 012

-0.58 011

-0.61 009

+0.47 010

+0.58 013

+0.11 011

+0.13 013

+0.13 013

-0.61 011

+0.16 015

+0.42 013

-0.58 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 6

WAR 0

WAR WAR WAR 9

WAR WAR WAR WAR WAR WAR 5

WAR 6

WAR 5

WAR 0

WAR 4

WAR 4

WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR 7

WAR WAR WAR WAR WAR 4

WAR WAR 11 WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR WAR 6

WAR WAR 5

WAR 3

WAR WAR WAR WAR WAR-CAL #

14 16 16 16 14 14 16 16 14 16 16 16 14 14 16 16 14 16 16 16 14 16 16 14 14 16 14 14 14 14 14 14 12 10 10 12 12 10 10 10 10 10 10 10 24 24 607 24 22 22 50 50 50 50 555 48 48 48 48 509 24 24 553 14 14 16 14 14 16 16 16 16 14 14 14 16 16 16 14 14 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET' INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:24 AM Component: S/G A Page 49 of 97 ONS1AR-EOC24 -

Tube QUERY: QueryMl[l)

Support Wear ROW TUBE VOLTS 0.19 0.44' 68 123 0.32 68 124 0.22 68 126 0.15 0.11 0.10 68 128 0.10 0.07

.68 129 0.09 68 130 0.08 68 131 0.27 69 1

0.18 0.15 0.10 69 2

0.20 69 5

0.17 69 6

0.13 69 7

0.20 0.16 69 8

0.15 0.13 69 9

0.10 0.09 0.11 69 10 0.12 69 13 0.19 69 17 0.10 69 18 0.23 69 20 0.18 69 34 0.09 69 50 0.10 0.09 69 56 0.14 69 61 0.24 69 64 0.09 69 68 0.11 69 77 0.11 69 113 0.07 69 115 0.13 0.11 69 116 0.13 0.13 69 117 0.16 0.15 0.10 69 118 0.15 0.59 69 119 0.37 0.20 0.19 0.09 69 120 0.28 0.31 0.13 69 121 0.30 0.66 0.09 0.64 0.18 0.48 69 123 0.14 0.16 0.21 0.09 69 124 0.20 69 125 0.20 0.24 0.17 0.11 69 126 0.10 69 127 0.14 69 129 0.53 0.32 0.12 0.09 70 1

0.13 0.22 70 2

0.10 0.16 DEG 133 137 139 137 146 149 143 148 157 133 112 146 142 116 142 93 134 146 138 122 139 136 123 149 92 149 139 144 127 139 149 135 153 114 137 136 129 141 132 131 143 149 139 151 135 127 149 133 134 142 145 142 140 142 145 138 127 154 133 146 132 139 134 139 147 142 145 139 144 132 149 141 131 134 138 148 135 142 143 127 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P3 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 12 TWD 23 TWD 19 TWD 13 TWD 10 TWD 7 TWD 7 TWD 6 TWD 5 TWD 7 TWD 6 TWD 17 TWD 11 TWD 9 TWD 7 TWD 11 TWD 10 TWD 8 TWD 11 TWD 10 TWD 8 TWD 7 TWD 7 TWD 6 TWD 7 TWD 7 TWD 10 TWD 6 TWD 12 TWD 10 TWD 5 TWD 6 TWD 5 TWD 8 TWD 14 TWD 6 TWD 7 TWO 7 TWO 5 TWO 9 TWD 7 TWD 9 TWD 9 TWD 10 TWD 10 TWD 7 TWD 10 TWD 29 TWD 20 TWD 12 TWD 12 TWD 6 TWD 17 TWD 19 TWD 9 TWD 17 TWD 29 TWD 6 TWD 29 TWD 11 TWD 24 TWD 9 TWD 10 TWD 13 TWD 6 TWD 13 TWD 12 TWD 14 TWO 11 TWD 7 TWD 7 TWD 9 TWD 26 TWD 18 TWD 8 TWD 6 TWD 8 TWD 13 TWD 6 TWD 9 LOCATION 012

+0.19 010

+0.53 010

+0.55 011

+0.21 011

+0.24 009

+0.58 013

+0.24 011

+0.24 009

+0.58 008

-0.45 010

+0.61 011

+0.00 010

-0.34 010

+0.66 014

-0.47 010

+0.61 010

-0.42 010

-0.42 010

-0.44 010

+0.64 010

+0.61 010

-0.44 010

+0.64 010

-0.46 007

-0.59 012

-0.49 010

-0.56 009

-0.54 014

-0.66 009

-0.56 009

+0.02 007

-0.60 009

+0.00 009

-0.70 009

-0.05 009

-0.08 009

+0.03 008

-0.74 010

+0.05 014

-0.75 010

+0.13 012

-0.66 011

-0.66 012

-0.61 011

-0.58 010

+0.19 012

-0.61 011

+0.11 012

-0.61 011

-0.58 010

+0.48 011

+0.13 012

-0.61 011

-0.61 012

+0.16 014

-0.61 012

+0.19 011

-0.56 010

+0.53 009

+0.45 009

-0.61 011

+0.19 011

-0.51 010

+0.56 009

+0.58 013

+0'.16 013

-0.53 012

+0.24 011

+0.21 011

-0.48 013

+0.21 013

-0.50 013

+0.27 012

+0.32 012

-0.40 008

-0.43 009

+0.61 010

-0.34 009

+0.61 010

+0.66 EXT UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE EXT UTIL 1

LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTIL 2

CAL # LEG 14 14 16 14 14 14 0

14 14 14 16 14 16 12 12 5

12 10 6

12 0

10 12 12 10 0

10 12 4

12 7

12 10 6

10 24 22 22 50 48 48 50 24 24 24 24 14 14 14 16 16 14 14 4

14 16 16 14 14 14 4

14 16 16 10 16 14 14 14 14 14 14 14 14 14 14 16 14 14 14 14 4

16 14 14 14 14 14 12 12 10 10 OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET PROBE 51 0XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:24 AM Component: S/G A Page 50 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl(l]

ROW TUBE VOLTS 70 3

0.18 70 4

0.13 70 6

0.33 70 7

0.11 70 8

0.23 70 9

0.21 70 10 0.11 70 12 0.13 70 14 0.12 70 15 0.11 70 16 0.13 70 19 0.10 70 22 0.17 70 34 0.17 0.10 70 42 0.14 70 44 0.09 70 49 0.10 70 52 0.13 70 61 0.14 70 62 0.11 70 67 0.08 70 108 0.12 70 111 0.07 70 112 0.09 70 113 0.16 0.16 70 114 0.12 70 115 0.13 0.10 70 116 0.19 0.67 70 117 0.10 70 118 0.20 0.64 70 119 0.14 0.13 0.16 0.15 70 120 0.12 0.17 70 121 0.25 70 122 0.14 0.26 70 125 0.22 70 127 0.09 70 129 0.30 0.15 0.08 0.14 0.08 70 130 0.14 70 131 0.12 0.11 0.09 71 1

0.10 0.11 0.18 0.08 0.25 71 2

0.11 0.20 71 5

0.09 71 6

0.13 71 7

0.13 71 8

0.17 0.19 71 9

0.23 71 10 0.11 0.16 0.21 0.11 71 11 0.08 71 12 0.17 71 13 0.13 0.15 71 17 0.14 0.14 71 35 0.19 71 44 0.09 DEG CHN 151 P2 142 P2 138 P2 141 p2 146 P2 141 P2 152 P2 147 P2 148 P2 153 p2 145 P2 129 P2 143 p2 121 p2 137 P2 139 P2 128 P2 148 P2 123 P2 131 P2 130 P2 143 P2 150 P2 140 P2 136 F2 142 P2 141 F2 134 P2 117 P2 Il1 P2 139 P2 130 P2 147 P2 139 P2 133 P2 140 P2 147 P2 144 P2 151 P2 153 P2 139 P2 143 P2 148 P2 139 P2 140 P2 139 P2 135 P2 141 P2 123 P2 119 P2 152 P2 97 P2 110 P2 148 P2 127 P2 106 P2 125 P2 141 P2 138 P2 124 P2 102 P2 133 P2 142 P2 117 P2 55 P2 128 P2 141 P2 148 P2 123 P2 139 P2 141 P2 145 P2 151 P2 153 P2 147 P2 137 P2 148 P2 150 P2 138 P2 116 P2 IND TWD TWO TWD TWD TWD TWD TWD TWD TWD TWO TWO TWD TWD TWD TWO TWD TWD TWD TWD TWD TWO TWD TWO TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 9

8 17 7

13 11 7

8 7

6 7

6 9

10 6

8 7

6 7

9 7

5 8

5 8

10 10 8

9 6

13 31 6

13 30 9

9 10 10 8

11 15 10 16 13 6

17 10 5

9 6

10 8

7 6

7 7

11 5

14 6

11 6

78 9

10 13 6

9 11 6

5 9

7 8

8 8

10 5

LOCATION 011

+0.34 010

-0.39 010

-0.44 010

+0.66 010

-0.46 010

-0.49 010

-0.49 009

+0.59 009

-0.56 012

-0.58 012

-0.56 009

-0.54 009

-0.56 009

-0.61 009

+0.10 008

-0.63 009

-0.66 009

+0.02 009

-0.68 009

-0.05 009

-0.05 009

+0.03 008

-0.61 010

+0.05 011

-0.63 011

+0.05 011

-0.64 012

-0.66 012

-0.66 011

+0.08

-012

-0,63 011

-0.66 011

-0.61 013

-0.69 011

-0.63 012

-0.61 011

+0.08 011

-0.58 010

+0.53 012

-0.58 012

+0.18 010

+0.53 012

+0.18 011

+0.18 013

+0.19 013

+0.24 013

-0.45 011

+0.27 011

-0.42 010

+0.61 009

+0.53 010

+0.58 010

+0.61 013

+0.27 011

-0.37 001

-0.29 002

-0.32 009

+0.61 010

-0.34 010

+0.66 010

+0.64 009

+0.56 014

-0.47 010

+0.61 010

+0.61 014

+0.20 010

-0.46 010

-0.46 009

-0.51 010

-0.46 014

+0.20 010

+0.59 010

-0.51 011

-0.51 009

+0.56 010

-0.56 010

-0.58 009

-0.56 009

-0.63 009

+0.00 EXT EXT UTIL 1

UTIL 2

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 5

LTE UTE WAR 3

LTE UTE WAR LTE UTE WAR 4

LTE UTE WAR 5

LTE UTE WAR 4

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 5

LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR 6

UTE LTE WAR LTE UTE WAR 0

UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR 4

UTE LTE WAR UTE LTE WAR UTE LTE WAR 5

UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE.LTE WAR UTE LTE WAR UTE LTE WAR 9

UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR 6

UTE LTE WAR 0

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 4

LTE UTE WAR 6

LTE UTE WAR LTE UTE WAR LTE UTE WAR 4

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 6

LTE UTE WAR 2

LTE UTE WAR LTE UTE WAR LTE UTE WAR 6

LTE UTE WAR LTE UTE WAR 4

LTE UTE WAR LTE UTE WAR CAL #

56 12 12 10 12 10 12 12 24 22 22 22 22 48 48 48 555 48 48 24 24 24 585 14 551 14 14 16 14 14 16 16 14 16 16 14 14 14 14 16 16 14 16 16 14 14 14 14 14 14 14 16 14 14 14 12 12 12 12 12 10 10 12 10 12 10 10 12 10 10 10 10 12 10 10 10 22 22 48 48 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET OUTLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510TUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Reo1 4/22/2008 9:45:25 AM Component: S/G A Page 51 of 97 Customer Name: ONSI Renl ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 71 109 0.11 71 112 0.10 71 113 0.17 71 114 0.12 0.12 71 117 0.10 0.19 71 118 0.13 71 119 0.11 0.12 71 120 0.08 71 121 0.12 71 123 0.51 0.08 71 124 0.14 71 125 0.14 0.16 0.40 71 126 0.22 0.35 0.13 0.10 71 127 0.12 71 128 0.12 0.25 0.09 0.17 71 129 0.43 0.31 71 130 0.20 71 131 0.14 0.08 71 132 0.08 0.08 72 1

0.13 0.09 0.22 72 2

0.11 72 6

0.10 72 8

0.18 0.13 72 9

0.20 72 10 0.08 72 15 0.08 0.08 72 16 0.14 0.10 72 21 0.15 0.07 72 51 0.10 72 52 0.13 72 54 0.10 72 55 0.08 0.11 72 56 0.10 72 I1i 0.09 72 114 0.09 72 115 0.10 72 116 0.10 72 117 0.12 0.39 0.09 0.13 0.08 72 118 0.14 0.12 72 119 0.11 0.23 0.15 72 120 0.19 0.39 72 121 0.07 0.08 72 122 0.14 72 123 0.10

,72 126 0.09 72 127 0.29 0.11 0.12 0.18 DEG CHN 145 P2 143 P2 135 P2 128 P2 121 P2 144 P2 138 P2 141 P2 146 P2 141 P2 145 P2 152 P2 132 P2 146 P2 143 P2 143 P2 148 P2 135 P2 142 P2 138 P2 150 P2 147 P2 148 P2 147 P2 142 P2 148 P2 145 P2 132 P2 129 P2 127 P2 105 P2 124 P2 151 P2 149 P2 145 P2 129 P2 131 P2 73 P2 137 P2 148 P2 142 P2 145 P2 146 P2 123 P2 155 P2 139 P2 145 P2 138 P2 90 P2 106 P2 132 P2 113 P2 145 P2 125 P2 132 P2 146 P2 140 P2 145 P2 131 P2 126 P2 139 P2 154 P2 144 P2 154 P2 125 P2 150 'P2 142 P2 141 P2 150 P2 133 P2 138 P2 153 P2 151 P2 143 P2 147 P2 140 P2 139 P2 147 P2 143 P2

,143 P2 IND %TW TWO 6 TWD 6 TWD 11 TWD ii TWD 8 TWD 8 TWD 7 TWD 12 TWD 9 TWD 7 TWD 8 TWD 6 TWO 8 TWD 25 TWD 5 TWD 10 TWD 9 TWD 10 TWD 21 TWD 14 TWD 20 TWD 9 TWD 7 TWD 8 TWD 8 TWD 16 TWD 7 TWD 11 TWD 22 TWD 17 TWD 13 TWD 9 TWD 5 TWD 6 TWD 6 TWD 8 TWD 6 TWD 13 TWD 7 TWD 6 TWD 11 TWD 8 TWD 11 TWD 5 TWD 4 TWO 4 TWD 8 TWD 6 TWD 8 TWD 4 TWD 5 TWD 7 TWD 6 TWD 4 TWD 6 TWD 6 TWD 6 TWD 6 TWD 7 TWD 7 TWD 8 TWD 22 TWD 7 TWD 9 TWD 6 TWD 9 TWD 8 TWD 8 TWD 15 TWD 10 TWD 12 TWD 21 TWD 5 TWD 6 TWD 9 TWD 7 TWD 6 TWO 18 TWD 8 TWD 9 TWD 12 LOCATION 010

+0.10 010

+0.05 010

+0.08 015

-0.76 012

-0.71 012

-0.53 011

-0.64 009

-0.58 011

-0.58 012

+0.11 011

+0.11 010

+0.56 011

+0.19 010

-0.56 011

+0.18 013

+0.16 012

-0.48 011

+0.21 013

+0.18 011

+0.21 013

-0.50 010

-0.53 013

-0.50 013

+0.26 013

-0.53 011

+0.24 010

-0.45 012

-0.40 011

+0.27 010

+0.58 010

+0.66 007

-0.40 008

+0.26 005

+0.32 002

+0.37 010

-0.34 010

, +0.66 010

+0.64 010

-0.44 010

-0.46 010

+0.61 010

-0.49 010

-0.49 009

+0.15 009

-0.54 009

-0.56 010

+0.20 012

+0.05 010

-0.63 009

-0.68 009

-0.65 008

-0.62 009

+0.00 008

-0.68 009

+0.05 010

+0.05 010

+0.11 009

-0.63 014

+0.00 014

+0.03 012

-0.63 011

+0.11 011

-0.63 010

+0.16 011

+0.08 011

-0.56 011

+0.13 011

-0.58 010

+0.50 011

+0.11 010

+0.50 012

+0.18 011

+0.16 011

+0.19 011

+0.16 009

+0.58 013

+0.21 012

+0.26 012

-0.47 011

+0.24 EXT EXT UTIL LIE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTIL 2

CAL # LEG 66 INLET 14 OUTLET 14 OUTLET 16 OUTLET 16 OUTLET 14 OUTLET 14 OUTLET 16 OUTLET 14 OUTLET 14 OUTLET 4

16 OUTLET 0

14 OUTLET 14 OUTLET 4

14 OUTLET 16 OUTLET 14 OUTLET 14 OUTLET 14 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 5

16 OUTLET 14 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 14 OUTLET 14 OUTLET 16 OUTLET 14 OUTLET 14 OUTLET 16 OUTLET 5

16 OUTLET 12 INLET 12 INLET 12 INLET 12 INLET 3

12 INLET 12 INLET 12 INLET 10 INLET 0

12 INLET 22 INLET 22 INLET 22 INLET 4

22 INLET 22 INLET 22 INLET 50 INLET 48 INLET 48 INLET 50 INLET 50 INLET 48 INLET 14' OUTLET 14 OUTLET 16 OUTLET 5

14 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 14 OUTLET 14 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 14 OUTLET 14 OUTLET 16 OUTLET 16 OUTLET 14 OUTLET 16 OUTLET 14 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET 16 OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:25 AM Component:

S/G A Page 52 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMlil]

Support Wear ROW TUBE VOLTS 0.10 72 128 0.10 72 129 0.07 0.15 72 130 0.11 0.11 72 131 0.22 0.72 0.10 0.16 0.16 73 1

0.10 0.10 0.13 0.21 73 2

0.25 73 3

0.10 73 5

0.17 73 6

0.32 73 7

0.12 73 8

0.35 0.17 0.31 0.14 73 9

0.25 0.26 0.13 73 10 0.19 73 11 0.21 73 12 0.08 73 13 0.21 0.12 73 14 0.11 73 19 0.19 73 20 0.16 73 26 0.12 73 48 0.10 73 50 0.10 73 53 0.13 73 55 0.09 73 61 0.13 73 113 0.11 73 115 0.09 73 116 0.14 0.06 73 118 0.21 0.21 0.08 73 119 0.10 0.81 0.33 0.10 73 120 0.34 0.09 73 121 0.17 0.16 0.21 0.10 73 122 0.13 0.09 73 123 0.08 73 124 0.15 73 125 0.23 0.35 0.09 73 126 0.19 73 128 0.10 0.14 0.14 73 129 0.08 0.19 73 131 0.13 73 132 0.17 0.08 74 1

0.09 0.74 0.14 74 2

0.08 0.14 74 8

0.09 DEG CHN 145 P2 145 P2 144 P2 123 P2 151 P2 138 P2 130 P2 128 P2 133 P2 131 P2 139 P2 125 P2 154 P2 139 P2 132 P2 130 P2 153 P2 148 P2 128 P2 123 P2 128 P2 141 P2 138 P2 146 P2 130 P2 137 P2 140 P2 151 P2 147 P2 149 P2 142 P2 155 P2 129 P2 129 P2 135 P2 128 P2 138 P2 134 P2 125 P2 146 P2 126 P2 131 P2 143 P2 152 P2 159 P2 145 P2 146 P2 146 P2 138 P2 130 P2 144 P2 143 P2 133 P2 148 P2 145 P2 139 P2 135 P2 141 P2 143 P2 147 P2 130 P2 146 P2 134 P2 137 P2 142 P2 141 P2 148 P2 150 P2 139 P2 147 P2 135 P2 133 P2 136 P2 149 P2 132 P2 132 P2 140 P2 103 P2 111 P2 131 P2 IND %TW LOCATION EXT EXT UTIL 1

TWD 7 TWD 7 TWD 5 TWD 10 TWD 7 TWD 7 TWD 14 TWD 32 TWD 7 TWD 11 TWO 11 TWD 6 TWD 7 TWD 8 TWD 12 TWD 13 TWD 6 TWD 10 TWD 15 TWD 7 TWD 16 TWD 9 TWD 15 TWD 8 TWD 13 TWD 13 TWD 7 TWD 11 TWD 11 TWD 5 TWD 11 TWD 7 TWD 7 TWD 11 TWD 9 TWD 7 TWO 6 TWO 6 TWD 7 TWD S TWD 8 TWO 7 TWD 6 TWD 10 TWD 4 TWD 13 TWD 13 TWD 6 TWD 6 TWO 33 TWO 18 TWD 7 TWD 20 TWD 7 TWD 11 TWD 10 TWD 13 TWO 6 TWD 9 TWD 7 TWD 5 TWD 10 TWD 14 TWO 19 TWD 6 TWD 13 TWO 7 TWD 10 TWD 10 TWD 5 TWD 12 TWD 8 TWD 11 TWD 6 TWD 6 TWD 30 TWO 8 TWD 5 TWD 8 TWD 5 Ol 013 014 010 013 013 Oill Oil 005 003 001 002 007 008 010 010 014 014 010 010 010 010 014 014 010 014 010 010 010 010 010 010 010 009 009 012 009 009 008 009 008 010 010 Ol 008 012 Ol 009 012 Ol 010 009 013 Ol 012 Ol 013 010 013 Ol Ol Ol 014 Ol 013 013 010 014 013 Ol 013 003 005 013 002 010 010 009 010 010

-0.50

-0.45

-0.48

+0.58

+0.29

-0.42

-0.03

-0.42

-0.40

-0.37

-0.40

-0.27

+0.34

+0.32

-0.34

+0. 64

-0.42

-0.49

-0.41

+0. 64

-0.49

+0.61

-0.54

+0.17

-0.46

+0.20

+0.61

-0.49

-0.49

-0.51

-0.56

+0.61

-0.56

-0.56

-0.51

+0.05

+0.05

+0.00

-0.63

+0.00

-0.69

+0.05

+0.11

-0.63

-0.55

-0.63

+0.11

-0.61

-0.61

+0.11

+0.53

-0.64

-0.66

+0.13

-0.58

+0.16

'+0.11

-0.53

+0.11

+0.16

+0.19

+0.18

-0.53

+0.21

+0.16

+0.19

-0.45

-0.55

-0.48

+0.24

+0.27

+0.34

-0.39

+0.32

-0.39

-0.37

+0.02

+0.61

+0.66

-0.44 UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

16 14 16 16 5

14 0

14 16 16 16 16 16 12 12 12 12 10 4

12 16 14 16 14 14 14 4

14 14 14 14

-i6 0

14 4

16 0

14 0

14 4

24 24 22 48 48 4

48 50 50 24 14 14 16 16 16 16 16 14 14 14 14 16 16 14 14 5

14 5

14

  • 16 6

16 4

14 16 14 14 5

14 16 16 6

16 5

16 4

14 14 14 16 5

16 16 16 16 16 16 0

14 LEG PROBE OUTLET 51OXB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 51OXB OUTLET 50XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:25 AM Component: S/G A Page 53 of 97 ONSIAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 0.12 74 9

0.85 0.13 0.23 74 10 0.29 0.12 74 12 0.10 74 15 0.13 74 20 0.12 74 21 0.21 74 22 0.14 74 27 0.23 74 30 0.11 74 33 0.14 74 34 0.13 0.07 74 56 0.11 0.11 74 74 0.07 74 114 0.09 0.12 0.08 74 115 0.18 74 116 0.18 0.23 0.21 74 117 0.18 0.13 74 118 0.16 74 119 0.11 0.25 0.16 74 120 0.62 0.08 74 121 0.09 74 122 0.29 0.36 74 123 0.09 0.13 74 124 0.09 74 127 0.09 0.08 0.18 0.26 74 128 0.20 0.16 74 129 0.19 74 130 0.22 0.31 0.15 0.12 0.11 0.19 0.19 0.16 0.09 74 131 0.08 0.14 0.09 0.13 75 1

0.11 0.16 0.09 0.09 0.23 0.14 0.15 75 2

0.21 0.13 0.36 0.15 0.12 75 9

0.15 75 10 0.26 0.17 0.19 75 12 0.14 75 13 0.12 0.11 75 14 0.09 DEG 144 132 132 150 147 148 151 153 138 132 147 142 133 134 120 132 104 150 134 146 126 137 139 142 133 137 145 141 143 146 141 152 127 146 153 140 133 148 147 141 148 121 142 138 142 145 121 137 126 125 103 136 125 121 ill 149 156 147 142 136 147 143 131 153 146 132 115 125 147 129 92 121 149 128 133 143 149 156 148 152 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW LOCATION 7

010

+0.59 32 010

-0.49 8

010

-0.07 13 014

+0.17 14 010

-0.49 7

010

+0.59 6

012

+0.27 7

012

-0.56 7

009

-0.58 14 009

-0.59 10 012

-0.67 12 009

-0.60 6

01i

-0.70 8

009

-0.63 7

009

-0.65 4

010

-0.02 6

009

-0.65 6

009

+0.05 5

009

+0.00 6

011

+0.05 8

011

-0.64 5

010

+0.13 12 011

-0.69 11 012

-0.61 14 011

+0.08 13 011

-0.64 12 011

+0.08 9

011

-0.66 i0 011

+0.11 8

014

+0.05 16- 012

-0.58 11 010

+0.53 28 011

+0.16 5

012

+0.13 6

011

+0.13 17 013

+0.16 20 011

+0.16 7

014

-0.61 9

011

+0.18 6

011

+0.19 7

011

+0.24 6

011

-0.48 11 009

+0.58 16 013

+0.26 12 013

+0.24 10 010

+0.53 12 010

+0.61 13 013

+0.29 17 013

-0.45 10 010

+0.61 8

010

-0.40 8

008

-0.43 12 003

-0.31 12 002

-0.32 10 001

-0.32 6

005

-0.37 6

013

-0.42 10 011

+0.29 7

007

-0.45 9

003

-0.34 7

002

-0.29 10 005

-0.34 6

005

+0.10 6

007

+0.34 13 009

+0.59 8

010

-0.34 9

010

+0.64 11 002

-0.31 7

009

+0.61 17 010

-0.37 8

010

+0.66 6

002

+0.15 9

010

-0.46 13 010

-0.49 9

010

+0.61 10 014

-0.56 7

014

-0.61 6

010

-0.56 6

009

+0.56 6

010

-0.56 EXT LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE EXT UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE" UTE UTE UTE UTE UTE UTE UTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 5

14 16 16 16 14 14 0

14 22 22 5

607 4

609 50 48 50 48 48 48 48 24 10 10 10 12 10 10 10 12 12 6

10 12 12 5

12 10 3

10 12 10 10 12 12 5

10 12 12 12 12 14 14 16 14 14 14 14 14 14 14 14 6

14 16 16 16 16 16 16 16 16 16 16 16 14 14 14 0

14 4

14 16 14 14 14 14 0

14 0

14 24 INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET.

OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET.

OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE S10XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:26 AM Component: S/G A Page 54 of 97 ONSlAR-EOC24

- Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 75 20 0.07 75 27 0.16 75 52 0.11 0.08 75 111 0.09 75 114 0.10 75 115 0.13 75 116 0.14 75 117 0.37 0.12 0.34 0.08 75 118 0.28 1.12 0.32 0.17 0.15 75 119 0.12 75 120 0.11 0.11 75 123 1.04 0.14 75 125 0.09 0.07 75 126 0.11 0.07 75 128 0.14 75 130 0.19 0.10 0.19 0.07 0.09 75 131 0.13 75 132 0.14 0.13 0.09 76 1

0.09 0.10 0.25 0.17 76 2

0.11 0.13 76 5

0.10 0.15 76 6

0.12 76 7

0.25 76 8

0.16 76 9

0.44 0.14 0.34 0.09 76 10 0.27 0.19 76 12 0.16 76 13 0.24 0.24 0.10 76 14 0.17 76 16 0.42 0.13 76 17 0.13 0.54 0.16 76 18 0.12 0.41 0.29 76 19 0.19 76 20 0.19 76 23 0.11 0.14 0.10 76 33 0.10 76 34 0.11 76 36 0.16 76 110 0.12 76 111 0.11 76 112 0.11 0.14 76 114 0.11 76 115 0.40 DEG CHN 121 P2 134 P2 137 P2 148 P2 113 P2 129 P2 137 P2 140 P2 138 P2 150 P2 136 P2 152 P2 134 P2 123 P2 135 P2 134 P2 133 P2 152 P2 135 P2 137 P2 126 P2 132 P2 150 P2 145 P2 149 P2 147 P2 145 P2 143 P2 140 P2 135 P2 129 P2 139 P2 131 P2 131 P2 125 P2 122 P2 143 P2 134 P2 141 P2 104 P2 138 P2 132 P2 136 P2 134 P2 146 P2 139 P2 157 P2 133 P2 141 P2 133 P2 148 P2 150' P2 143 P2 139 P2 142 P2 135 P2 121 P2 126 P2 132 P2 152 P2 130 P2 132 P2 135 P2 128 P2 134 P2 149 P2 121 P2 131 P2 147 P2 96 P2 152 P2 123 P2 131 P2 107 P2 135 P2 140 P2 137 P2 135 P2 137 P2 135 P2 IND %TW TWD 4 TWD 9 TWD 6 TWD 5 TWD 6 TWD 7 TWD 9 TWD 9 TWD 21 TWD 8 TWD 19

'TWD 6

TWD 16 TWD 39 TWD 18 TWD 11 TWD 10 TWD 8 TWD 7 TWD 7 TWD 38 TWD 10 TWD 6 TWD 5 TWD 8 TWD 5 TWD 10 TWD 12 TWD 7 TWD 12 TWD 5 TWD 6 TWD 9 TWD 9 TWD 9 TWD 6 TWD 6 TWD 6 TWD 14 TWD 10 TWD 7 TWD 8 TWD 6 TWD 8 TWD 7 TWD 13 TWD 10 TWD 20 TWD 8 TWD 16.

TWD 5 TWD 15 TWD 11 TWD 10 TWD 12 TWD 12 TWD 5 TWD 10 TWD 21 TWD 8 TWD 7 TWD 23 TWD 9 TWD 7 TWD 20 TWD 15 TWD 10 TWD 10 TWD 6 TWD 8 TWD 6 TWD 6 TWD 6 TWD 9 TWD 8 TWD 10 TWD 7 TWD 9 TWD 7 TWD 21 LOCATION 009

-0.56 010

0 63 009

-0.68 009

+0.05 012

-0.69 012

-0.64 012

-0.71 010

+0.13 012

+0.08 012

-0.66 011

-0.63 010

+0.13 014

+0.03 010

+0.16 009

-0.66 011

+0.11 009

+0.11 010

+0.50 011

+0.13 008

+0.21

011,

+0.16 011

-0.29 013

-0.56 013

+0.19 013

-0.53 013

+0.21 013

+0.24 013

+0.29 011

+0.26 011

-0.37 005

-0.37 003

-0.34 005

0.35 005

-0.37 004

-0.39 002

-0.32 008

-0.39 009

-0.42 010

-0.37 010

+0.64 002

-0.32 005

-0.34 014

-0.49 014

+0.22 010

-0.44 O14

-0.54 014

+0.20 010

-0.51 014

-0.54 014

+0.17 011

+0.24 010

-0.51 014

+0.15 014

+0.07 014

-0.61 014

+0.12 011

+0.22 014

-0.61 014

-0.66 014

+0.02 012

-0.61 014

-0.68 014

+0.05 010

-0.58 014

-0.66 014

+0.02 010

-0.59 014

-0.71 012

-0.05 014

-0.71 014

-0.07 008

-0.58 008

-0.58 008

-0.60 010

+0.05 013

+0.05 011

-0.64 010

+0.03 013

+0.08 011

+0.08 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR UTE LTE WAR UTIL 2

CAL #

22 48 48 48 10 10 12 10 12 12 12 12 10 10 10 5

10 10 10 6

12 10 10 12 5

12 10 5

10 6

12 5

12 12 12 12 12 12 12 10 12 12 12 16 16 16 16 16 16 4

14 5

14 4

16 14 16 14 14 14 0

14 16 16 16 14 14 0

14 24 24 24 22 22 22 24 24 24 22 22 22 22 22 50 48 48 32 0

551 10 10 0

553 10 LEG INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET OUTLET OUTLET INLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 51OUL 510XB

AREVA NP Inc Customer Name: ONSI Renl 4/22/2008 9:45:26 AM Component: S/G A Page 55 of 97 Customer Name: ONS1 Repl ONSJAR-EOC24 -

Tube Support Wear QUERY: QueryMl[1]

ROW TUBE VOLTS 76 117 0.42 0.07 0.15 0.15 76 118 0.12 0.21 76 119 0.12 0.44 76 120 1.04 0.27 0.16 76 121 0.13 0.15 0.10 76 122 0.10 0.13 0.09 76 124 0.12 0.12 76 126 0.16 0.09 76 128 0.10 76 129 0.11 76 130 0.22 76 131 0.11 0.24 77 1

0.20 77 2

0.19 0.17 0.11 77 3

0.18 0.10 77 4

0.14 77 7

0.16 77 8

0.44 77 9

0.12 77 10 0.44 0.13 77 11 0.37 0.09 77 13 0.11 77 14 0.27 0.11 77 15 0.12 0.08 0.11 77 17 0.22 0.19 0.10 77 18 0.17 77 20 0.15 77 22 0.10 77 109 0.11 77 111 0.08 77 113 0.12 77 114 0.28 77 115 0.10 77 116 0.32 0.07 0.11 77 117 0.12 0.10 0.17 77 118 0.07 0.16 77 119 0.09 0.10 77 120 0.14 0.13 0.11 77 121 0.27 77 123 0.12 0.09 77 124 0.16 0.11 0.16 0.14 0.48 77 125 0.13 77 126 0.17 DEG CHN 133 P2 122 P2 142 P2 135 P2 147 P2 144 P2 141 P2 135 P2 126 P2 147 P2 136 P2 126 P2 140 P2 151 P2 158 P2 139 P2 152 P2 136 P2 135 P2 141 P2 146 P2 128 P2 143 P2 137 P2 108 P2 138 P2 137 P2 117 P2 85 P2 137 P2 136 P2 150 P2 130 P2 143 P2 134 P2 153 P2 121 P2 137 P2 139 P2 155 P2 144 P2 144 P2 144 P2 134 P2 134 P2 129 P2 126 P2 143 P2 141 P2 138 P2 143 P2 158 P2 130 P2 105 P2 139 P2 130 P2 141 P2 127 P2 158 P2 120 P2 138 P2 144 P2 134 P2 137 P2 136 P2 134 P2 156 P2 147 P2 142 P2 142 P2 133 P2 149 P2 148 P2 146 P2 143 P2 144 P2 148 P2 137 P2 138 P2 143 P2 IND %TW TWD 22 TWD 5 TWO 10 TWD 10 TWO 8 TWO 13 TWD 8 TWD 23 TWD 38 TWD 16 TWD 11 TWD 9 TWD 9 TWD 7 TWD 7 TWD 9 TWD 7 TWD 8 TWD 8 TWD 11 TWD 6 TWD 7 TWD 7 TWD 14 TWD 8 TWD 14 TWD 12 TWD 10 TWD 9 TWD 6 TWD 11 TWD 6 TWD 7 TWD 9 TWD 20 TWD 7 TWD 20 TWDO7 TWD 19 TWD 6 TWD 6 TWD 16 TWD 8 TWD 8 TWD 6 TWD 8 TWD 14 TWD 12 TWD 7 TWD 12 TWO 10 TWD 7 TWD 7 TWD 6 TWD 8 TWD 17 TWD 9 TWD 18 TWD 5 TWD 8 TWD 8 TWD 7 TWD 11 TWD 5 TWO 10 TWD 6 TWD 7 TWD 10 TWD 9 TWD 7 TWD 16 TWD 8 TWD 6 TWD 11 TWD 8 TWD 11 TWD 9 TWD 25 TWD 9 TWD 11 LOCATION 011

+0.11 008

+0.19 013

-0.01 012

-0.01 011

+0.ii 010

+0.16 013

+0.11 011

+0.11 011

+0.13 010

-0.61 011

-0.40 011

+0.11 012

+0.16 012

-0.56 013

-0.61 011

+0.13 010

-0.55 013

+0.16 009

+0.58 013

+0.21 011

+0.24 003

-0.37 013

-0.42 011

-0.40 003

-0.37 001

+0.77 010

-0.34 008

-0.

39 010

-0.37 005

-0.34 011

+0.37 014

+0.32 007

-0.39 010

-0.46 010

-0.46 014

+0.17 014

-0.56 014

+0.15 014

-0.59 014

+0.15 011

+0.22 009

-0.54 010

-0.56 010

-0.58 011

+0.20 013

-0.59 014

-0.64 014

+0.05 011

+0.20 011

-0.56 014

-0.71 011

+0.07 010

+0.05 012

-0.74 010

+0.08 012

-0.69 011

-0.56 014

-0.69 009

+0.13 012

-0.01 013

+0.05 012

-0.66 011

-0.64 011

+0.11 010

+0.16 011

+0.08 010

+0.51 012

+0.13 012

-0.61 011

+0.13 011

+0.13 012

-0.53 011

+0.16 013

+0.16 013

-0S58 012

+0.21 012

-0.48 011

+0.18 011

+0.19 013

+0.19 EXT EXT UTIL UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTIL 2

CAL # LEG 10 OUTLET 10 OUTLET 10 OUTLET 10 OUTLET 12 OUTLET 12 OUTLET 10 OUTLET 10 OUTLET 12 OUTLET 12 OUTLET 5

12 OUTLET 10 OUTLET 10 OUTLET 6

10 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 10 OUTLET 12 OUTLET 10 OUTLET 10 OUTLET 16 INLET 14 INLET 14 INLET 0

14 INLET 16 INLET 2

16 INLET 14 INLET 16 INLET 14 INLET 16 INLET 14 INLET 14 INLET 16 INLET 4

16 INLET 0

14 INLET 70 INLET 70 INLET 68 INLET 68 INLET 68 INLET 70 INLET 70 INLET 70 INLET 68 INLET 68 INLET 68 INLET 32 OUTLET 10 OUTLET 10 OUTLET 12 OUTLET 0

551 INLET 10 OUTLET 10 OUTLET 10 OUTLET 10 OUTLET 10 OUTLET 10 OUTLET 12 OUTLET 12 OUTLET 10 OUTLET 10 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 10 OUTLET 10 OUTLET 10 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 10 OUTLET 12 OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:26 AM Component: S/G A Page 56 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl(l]

ROW TUBE VOLTS 0.08

.0.12 0.19 0.14 77 127 0.23 77 128 0.37 0.09 77 129 0.09 77 130 0.07 77 131 0.12 0.09 0.09 0.08 0.08 77 132 0.30 0.15 78 7

0.19 78 8

1.12 0.16 78 9

0.18 0.17 0.16 0.16 78 10 0.45 0.27 0.14 78 12 0.11 0.26 78 13 0.27 0.09 78 16 0.27 0.21 78 110 0.16 78 112 0.11 78 113 0.09 78 114 0.26 78 115 0.11 78 116 0.11 78 119 0.08 78 120 0.15 0.13

0. 64 0.49 78 121 0.18 1.36 78 124 0.21 78 125 0.09 78 126 0.35 0.20 0.12 78 127 0.19 78 130 0.18 0.10 0.08 0.09 0.07 78 131 0.21 0.08 0.11 0.08 0.13 0.08 0.08 79 I

0.17 0.08 0.11 0.09 79 2

0.10 79 7

1.21 0.15 0.18 79 9

0.16 0.17 79 10 0.59 79 12 0.45 79 13 0.32 79 14 0.18 79 15 0.09 79 109 0.08 79 113 0.12 DEG CHN 151 P2 153 P2 143 P2 135 P2 136 P2 133 P2 149 P2 139 P2 147 P2 136 P2 128 P2 140 P2 135 P2 129 P2 141 P2 130 P2 127 P2 129 P2 140 P2 142 P2 134 P2 139 P2 87 P2 138 P2 145 P2 144 P2 146 P2 135 P2 138 P2 134 P2 143 P2 155 P2 129 P2 127 P2 126 P2 129 P2 121 P2 148 P2 147 P2 137 P2 142 P2 129 P2 134 P2 148 P2 130 P2 143 P2 150 P2 134 P2 137 P2 138 P2 139 P2 128 P2 131 P2 114 P2 61 P2 128 P2 141 P2 148 P2 143 P2 138 P2 133 P2 104 P2 143 P2 132 P2 139 P2 138 P2 140 P2 145 P2 122 P2 137 P2 133 P2 145 P2 150 P2 136 P2 131 P2 137 P2 147 P2 149 P2 147 P2 119 P2 IND %TW TWD 6 TWD 8 TWD 12 TWD 10 TWD 14 TWD 21 TWD 7 TWD 6 TWD 5 TWD 8 TWD 6 TWD 6 TWD 6 TWD 6 TWD 18 TWD 10 TWD 10 TWD 37 TWD 10 TWD 10 TWD 9 TWD 8 TWD 9 TWD 22 TWD 15 TWD 8 TWD 7 TWD 14 TWD 13 TWD 5 TWD 17 TWD 14 TWD 10 TWD 8 TWD 6 TWD 15 TWD 8 TWD 7 TWD 6

TWD 10 TWD 9

TWD 29 TWD 25 TWD 12 TWD 43 TWD 13 TWD 7 TWD 19 TWD 12 TWD 8

TWD 12 TWD 11 TWD 6 TWD 6 TWD 6 TWD 5

TWD 13 TWD 6 TWD 7 TWD 5 TWD 9 TWD 5 TWD 5 TWD 10 TWD 5 TWD 7 TWD 6 TWD 6 TWD 37 TWD 8 TWD 9 TWD 10 TWD 10 TWD 24 TWD 20 TWD 15 TWD 12 TWD 7 TWD 5 TWD 8 LOCATION 012

+0.21 012

-0.48 011

+0.18 010

-0.53 013

+0.19 013

-0.45 011

+0.26 011

-0.40 008

+0.29 011

-0.40 008

-0.37 005

-0.35 003

+0.08 003

-0.32 013

+0.32 005

-0.37 010

-0.49 010

-0.46 010

-0.07 010

-0.49 014

-0.56 014

+0.15 010

+0.66 010

-0.49 014

-0.59 014

+0.02 011

-0.51 012

-0.54 010

-0.56 013

+0.15 014

-0.68 014

+0.02 010

+0.03 012

-0.69 010

+0.08 014

+0.00 012

-0.69 010

+0.16 011

+0.13 013

+0.11 013

-0.61 012

+0.16 011

+0.16 012

-0.53 011

-0.08 012

+0.21 013

-0.53 013

+0.21 011

+0.24 010

-0.50 013

-0.48 013

-0.37 005

-0.37 002

-0.34 010

+0.64 006

+0.32 013.

+0.21 007

+0.32 005

-0.37 003

+0.08 003

-0.31 006

-0.37 001

+0.37 002

-0.29 002

+0.15 008

-0.39 009

-0.42 007

-0.39 010

-0.46 012

-0.41 010

-0.02 014

-0.59 014

+0.17 014

-0.59 014

-0.61 010

-0.58 010

-0.56 011

+0.17 010

+0.05 012

-0.66 EXT EXT UTIL UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR 1

UTIL 2

CAL #

12 12 12 12 10 12 12 4

10 12 10 10 10 10 10 12 12 14 16 16 14 14 14 0

14 16 16 16 16 16 14 14 68 68 10 10 12 10 12 6

10 5

12 10 10 10 10 12 LAR 12 10 12 10 10 10 12 10 10 10 10 5

10 12 12 12 12 12 12 7

12 16 16 16 16 14 14 14 0

14 16 16 14 14 14 70 68 32 10 LEG PROBE OUTLET 510XB OUTLET 510XB OUTLET 51OXB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB.

INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:27 AM Component: S/G A Page 57 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 0.05 79 114 0.20 0.15 79 115 0.27 0.32 0.15 0.16 0.20 0.09 79 116 0.11 79 117 0.17 0.31 0.29 0.19 79 118 0.29 0.20 0.17 0.18 79 120 0.12 79 121 0.13 0.19 79 123 0.16 0.29 0.09 0.08 0.07 79 124 0.16 79 125 0.42 0.23 0.17 79 126 0.10 79 127 0.10 0.10 79 128 0.13 79 129 0.20 0.21 0.15 0.09 79 131 0

16 0.10 0.09 0.12 0.12 0.08 0.06 0.06 79 132 0.42 0.17 0.11 0.08 0,09 0.14 0.09 0.25 80 4

0.14 0.17 80 5

0.42 0.12 80 8

0.32 0.16 80 9

0.49 0.13 80 10 0.10 0.35 0.16 80 11 0.10 80 13 0.30 80 15 0.07 80 104 0.07 80 107 0.15 80 111 0.08 80 112 0.14 0.14 0.06 80 113 0.17 80 114 0.16 0.31 0.19 80 115 0.12 80 116 0.14 DEG CHN 140 P2 135 P2 140 P2 135 P2 129 P2 134 P2 148 P2 131 P2 138 P2 151 P2 131 P2 136 P2 134 P2 139 P2 141 P2 141 P2 148 P2 141 P2 139 P2 150 P2 142 P2 137 P2 136 P2 139 P2 135 P2 147 P2 144 P2 133 P2 136 P2 141 P2 147 P2 144 P2 142 P2 134 P2 142 P2 136 P2 134 P2 139 P2 140 P2 119 P2 137 P2 118 P2 132 P2 117 P2 136 P2 138 P2 136 P2 143 P2 132 P2 137 P2 144 P2 132 P2 147 P2 146 P2 127 P2 138 P2 137 P2 140 P2 143 P2 144 P2 132 P2 142 P2 146 P2 141 P2 148 P2 112 P2 142 P2 108 P2 141 P2 142 P2 135 P2 135 P2.

127 P2 152 P2 131 P2 130 P2 136 P2 126 P2 152 P2 134 P2 IND %TW TWD 4 TWD 13 TWD 10 TWD 16 TWD 18 TWD 10 TWD 10 TWD 12 TWD 6 TWD 8 TWD 11 TWD 17 TWD 17 TWD 12 TWD 17 TWD 13 TWD 11 TWD 12 TWD 8 TWD 9 TWD 12 TWD 10 TWD 17 TWD 6 TWD 5 TWD 5 TWD 10 TWD '22 TWD 14 TWD 11 TWD 7 TWD 7 TWO 7 TWD 9 TWD 12 TWD 13 TWD 10 TWD 6 TWD 10 TWD 7 TWD 6 TWD 8 TWD 8 TWD 6 TWD 5 TWD 5 TWD 23 TWD 11 TWD 8 TWD 6 TWO 7 TWD 10 TWD 6 TWD 15 TWD 7 TWD 9 TWD 21 TWD 7 TWD 17 TWO 10 TWO 21 TWD 7 TWD. 6 TWD 18 TWD 10 TWD 5 TWD 15 TWD 5 TWD 5 TWD 9 TWD 8 TWD 9 TWD 9 TWD 5 TWD 11 TWD 10 TWO 18 TWD 12 TWD 8 TWD 9 LOCATION 008

+0.11 014

-0.03 014

-0.71 014

-0.03 013

+0.05 012

-0.66 011

-0.64 010

+0.13 012

+0.05 011

+0.03 014

-0.67 011

+0.11 010

+0.13 013

+0.05 014

+0.03 012

+0.11 012

-0.63 010

+0.16 012

+0.13 012

-0.56 012

+0.19 014

-0.56 011

+0.19 012

+0.21 012

-0.56 013

-0.56 012

-0.55 014

-0.59 013

+0.19 013

-0.53 013

+0.16 013

+0.21 013

-0.45 013

-0.45 012

+0.32 012

-0.43 011

+0.29 011

-0.37 013

+0.29 005

-0.37 003

+0.11 003

-0.31 002

-0.32 004

-0.32 001

+0.45 001

-0.27 013

+0.32 011

-0.32 005

-0.37 004

-0.34 003

+0.11 003

-0.29 002

-0.29 001

+0.08 010

-0.42 014

-0.44 010

-0.42 011

+0.34 010

-0.47 014

-0.54 014

-0.59 014

+0.15 011

+0.24 014

-0.59 014

+0.15 011

+0.12 010

-0.56 011

+0.19 010

-0.05 010

+0.05 008

+0.10 012

+0.05 008

+0.11 010

+0.08 014

-0.74 012

-0.69 011

+0.05 010

+0.08 010

+0.11 014

-0.67 EXT EXT UTIL 1

UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTIL 2

CAL #

10 12 12 10 10 10 10 10 4

10 6

12 10 10 10 2

10 12 12 12 12 12 10 10 10 10 O

10 0

10 0

10 12 10 10 10 12 10 4

10 12 10 10 10 4

10 10 10 10 10 10

5.

10 5

10 5

10 12 12 12 12 12 12

~12 12 14 14 16 16 16 16 14 0

14 16 16 16 0

14 14 68 32 32 0

551 10 10 3

10 12 10 10 10 12 10 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET

'INLET INLET INLET OUTLET OUTLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 51OXB 510XB

AREVA NP Inc Customer Name: ONSr Repl 4/22/2008 9:45:27 AM Component:

S/G A Page 58 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: Queryil~l]

ROW TUBE VOLTS 0.36 0.08 80 117 0.25 80 118 0.13 0.15 80 119 0.15 0.25 0.21 0.11 0.11 80 120 0.14 0.13 0.06 80 122 0.26 0.14 0.94 80 124 0.12 0.11 80 127 0.10 80 128 0.07 0.14 80 131 0.08 0.05 81 4

0.25 81 5

0.25 81 6

0.12 0.14 0.10 81 7

0.13 0.12 81 8

0.08 81 9

0.13 81 12 0.23 81 13 0.24 0.17 81 14 0.23 0.19 81 18 0.29 0.10 81 19 0.13 81 21 0.15 81 22 0.08 81 11 0.11 0.08 81 113 0.15 0.16 0.07 81 115 0.14 0.27 0.16 0.10 81 116 0.10 81 117 0.11 0.10 0.06 81 118 0.17 81 119 0.10 0.19 0.10 81 120 0.16 0.39 0.23 0.38 0.13 0.78 0.14 81 121 0.09 81 122 0.09 0.08 81 123 0.22 0.23 0.29 81 124 0.23 0.09 0.13 81 125 0.18 0.11 0.10 81 126 0.31 81 127 0.13 DEG CHN 134 P2 134 P2 142 P2 131 P2 146 P2 143 P2 141 P2 144 P2 151 P2 152 P2 139 P2 138 P2 132 P2 138 P2 148 P2 123 P2 138 P2 144 P2 145 P2 148 P2 139 P2 140 P2 142 P2 127 P2 141 P2 147 P2 132 P2 146 P2 142 P2 135 P2 145 P2 145 P2 137 P2 144 P2 134 P2 139 P2 147 P2 137 P2 133 P2 137 P2 90 P2 150 P2 113 P2 140 P2 138 P2 138 P2 133 P2 121 P2 138 P2 136 P2 153 P2 147 P2 150 P2 152 P2 118 P2 145 P2 142 P2 135 P2 151 P2 139 P2 137 P2 142 P2 138 P2 147 P2 129 P2 148 P2 131 P2 146 P2 153 P2 137 P2 138 P2 137 P2 144 P2 153 P2 143 P2 140 P2 144 P2 140 P2 139 P2 141 P2 IND %TW TWO 20 TWO 6 TWO 16 TWD 9 TWD 9 TWD 10 TWD 15 TWD 13 TWD 8 TWD 8 TWD 9 TWD 8 TWD 5 TWD 15 TWD 9 TWD 36 TWD 8 TWD 7 TWD 7 TWD 5 TWO 9 TWO 5 TWO 4 TWD 13 TWD 14 TWO 6 TWD 8 TWD 6 TWD 8 TWD 7 TWD 5 TWD 8 TWD 12 TWD 12 TWD 9 TWO 15 TWD 12 TWD 17 TWO 7 TWO 9 TWO 10 TWO 6 TWO 10 TWO 7 TWD 13 TWD 14 TWO 7 TWD 9 TWD 16 TWD 10 TWD 7 TWD 7 TWO 8 TWO 7 TWD 5 TWD 11 TWO 7 TWO 12 TWO 7 TWO 11 TWD 21 TWD 14

'TWD 21 TWD 9 TWD 33 TWD 10 TWD 6 TWD 6 TWD 6 TWD 14 TWD 14 TWD 17 TWD 14 TWO 6 TWO 9 TWD 11 TWD 7 TWD 7 TWD 18 TWD 9 LOCATION 012

+0.05 010

+0.13 010

+0.16 014

+0.03 011

+0.08 014

-0.69 013

+0.05 012

+0.13 011

+0.11 012

-0.55 014

-0.64 011

+0.11 008

+0.21 013

-0.58 012

-0.53 011

+0.19 013

+0.16 013

-0.50 013

-0.50 013

+0.27 013

-0.45 002

-0.32 003

+0.11 010

-0.42 010

-0.42 014

-0.51 011

+0.32 014

+0.22 010

-0.44 010

+0.61 011

+0.27 014

-0.59 014

-0.61 010

-0.54 011

+0.22 010

-0.56 011

+0.20 014

-0.66 011

+0.15 009

-0.56 011

-0.64 011

+0.10 012

-0.69 015

-0.03 014

+0.03 011

-0.61 010

+0.10 014

-0.72 013

+0.05 012

-0.64 011

-0.58 011

-0.61 012

-0.64 011

-0.64 010

+0.13 010

+0.13 014

+0.03 011

+0.11 011

-0.56 014

-0.69 013

+0.08 013

-0.66 012

+0.13 012

-0.58 011

+0.13 011

-0.55 013

+0.11 012

-0.53 011

+0.16 013

-0.58 012

+0.19 011

+0.16 013

+0.16 012

-0.53 011

+0.18 013

-0.56 012

-0.53 010

-0.53 013

+0.21 013

-0.48 EXT EXT UTE LTE' UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

10 10 12 10 10 12 12 12 12 4

12 10 10 10 10 10 10 10 10 12 10 10 12 12 14 16 14 0

14 0

14 16 16 0

14 4

16 14 14 14 70 70 70 70 70 70 70 0

551 0

551 5

551 5

551 0

551 10 10 10 6

10 12 10 10 10 12 10 6

10 5

10 12 12 12 12 12 12 12 4

10 12 12 10 10 10 12 12 12 10 10 4

10 12 10 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 51OUL 51OUL 51OUL 510XB 5IOXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB S1OXB C

AREVA NP Inc Customer Name: ONSI Repl ONSlAR-EOC24 -

Tube Support Wear 4/22/2008 9:45:28 AM Component: S/G A Page 59 of 97 QUERY: QueryMl[l]

ROW TUBE VOLTS 81 128 0.12 0.47 0.09 0.11 81 129 0.14 0.08 81 131 0.11 0.16 0.25 0.10 0.05 81 132 0.06 82 4

0.12 82 6

0.16 0.20 0.17 82 11 0.12 0.24 0.09 82 13 0.31 82 14 0.27 82 17 0.07 82 110 0.16 82 112 0.31 0.13 0.21 0.17 0.10 82 113 0.12 82 114 0.29 0.07 0.11 82 115 0.10 82 117 0.14 0.09 0.11 82 118 0.06 82 119 0.10 82 120 0.08 82 121 0.10 0.15 0.23 82 122 0.10 0.14 82 123 0.10 82 124 0.24 0.10 0.07 82 125 0.12 0.08 82 126 0.15 0.16 82 127 0.19 82 128 0.31 83 1

0.13 83 2

0.14 83 4

0.11 83 5

0.09 83 6

0.45 83 8

0.39 83 9

0.18 0.26 83 10 0.09 83 11 0.53 0.12 83 12 0.27 0.14 83 13 0.21 83 14 0.28 0.19 83 23 0.06 83 27 0.23 83 111 0.10 0.09 83 115 0.11 83 116 0.14 0.15 0.15 0.07 83 117 0.13 DEG 146 137 146 126 139 138 147 132 137 112 148 139 133 137 140 126 110 130 113 143 143 140 133 132 142 137 140 148 147 130 146 140 121 144 146 151 134 148 143 153 148 141 146 143 155 135 138 142 142 146 144 137 145 134 139 93 144 145 127 141 134 132 152 134 121 138 153 147 138 128 139 131 130 144 131 147 145 142 121 127 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 8 TWD 24 TWD 6 TWD 7 TWD 9 TWD 6 TWD 7 TWD 10 TWD 15 TWD 7 TWD 3 TWD 5 TWD 7 TWD 8

TWD 10 TWD 9 TWD 6 TWD 12 TWD 5 TWD 15 TWO 17 TWD 5 TWD 10 TWD 18 TWD 9 TWD 13 TWD 11 TWD 7 TWD 8 TWD 17 TWD 5 TWD 7 TWD 7 TWD 9 TWD 7 TWD 8 TWD 5 TWD 7 TWD 6 TWD 7 TWD 10 TWD 14 TWD 7 TWD 9

TWD 7

TWD 14 TWD 7 TWD 5 TWD 8 TWD 6 TWD 10 TWD 10 TWD 12 TWD 18 TWD 8

TWD 8 TWD 6 TWD 6

TWD 20 TWD 20 TWD 9 TWD 13 TWD 6 TWD 23 TWD 6 TWD 15 TWD 8

TWD 12 TWD 17 TWD 13 TWD 5 TWO 12 TWD 6 TWD 6 TWD 7 TWD 10 TWD 10 TWO 10 TWD 5 TWD 9 LOCATION 013

+0.24 012

+0.26 O012

+0.26 011

.+0.26 010

+0.56 013

-0.45 013

-0.05 013

+0.29 012

+0.34 011

-0.37 004

-0.37 002

+0.39 010

-0.40 010

-0.42 007

-0.44 010

-0.44 010

+0.64 014

-0.61 014

+0.12 011

+0.22 010

-0.54 010

-0.54 012

+0.12 010

+0.05 013

-0.69 011

-0.64 008

+0.05 008

-0.58 010

+0.11 008

+0.11 014

-0.03 011

+0.05 012

-0.67 011

-0.66 014

-0.74 011

+0.11 011

-0.61 011

+0.13 012

-0.58 011o

+0.16 012.

-0.56 011

+0.16 010

+0.55 012

+0.19 010

+0.58 013

+0.13 013

+0.19 011

+0.19 012

-0.53 011

+0.21 010

-0.50 012

+0.27 011

+0.24 013

-0.45 013

-0.43 010

-0.37 010

+0.64 007

-0.44 014

+0.27 010

-0.42 010

-0.44 014

-0.56 014

+0.15 014

+0.17 014

-0.61 014

+0.10 014

-0.64 014

+0.10 010

-0.54 010

-0.54 013

-0.59 011

+0.02 009

-0.61 011

+0.05 010

+0.05 010

+0.08 014

+0.05 014

-0.69 012

-0.63 010

+0.11 014

+0.00 EXT UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE OTE UTE EXT LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE tTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE UTIL I

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL 12 12 12 12 10 3

10 10 10 10 10 10 12 14 14 14 14 14 14 0

14 14 70 70 10 10 10 10 10 6

10 12 10 2

10 6

10 12 12 12 12 4

10 12 1o 12 12 12 10 10 12 10 10 4

10 12 12 10 10 12 10 16 5

14 0

14 16 14 16 14 14 16 14 0

14 16 16 16 70 70 72 100 10 10 10 12 12 12 12 10

  1. LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSr Repl 4/22/2008 9:45:29 AM Component: S/G A Page 60 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: QueryMl[1]

ROW TUBE VOLTS 0.18 0.77 0.16 83 118 0.26 83 119 0.23 0.05 83 120 0.18 83 121 0.23 0.08 83 122 0.14 0.21 0.08 83 123 0.15 0.15 0.10 83 124 0.10 83 125 0.28 0.15 0.19 83 126 0.11 83 127 0.21 83 128 0.14 83 129 0.15 83 130 0.20 83 131 0.15 0.11 83 132 0.15 84 3

0.17 84 4

0.54 0.14 84 7

0.20 0.17 0.22 0.15 84 8

0.08 84 10 0.36 84 11 0.12 84 12 0.13 84 13 0.27 0.22 84 14 0.26 0.10 84 103 0.07 84 106 0.06 84 112 0.13 84 114 0.11 84 115 0.07 84 117 0.10 0.08 84 118 0.11 0.16 0.12 0.12 84 120 0.31 0.14 84 121 0.09 0.10 0.15 84 123 0.21 0.19 84 124 0.19 0.19 0.13 0.14 84 126 0.44 84 127 0.09 84 128 0.43 0.20 0.23 84 129 0.11 84 130 0.16 84 131 0.11 85 3

0.16 0.09 85 4

0.58 0.08 85 5

0.08 85 12 0.15 0.11 85 13 0.16 DEG CHN 140 P2 128 P2 135 P2 139 P2 133 P2 131 P2 148 P2 140 P2 154 P2 140 P2 145 P2 147 P2 138 P2 148 P2 144 P2 148 P2 134 P2 135 P2 136 P2 150 P2 143 P2 138 P2 129 P2 119 P2 140 P2 122 P2 146 P2 140 P2 135 P2 142 P2 142 P2 143 P2 147 P2 147 P2 154 P2 136 P2 135 P2 143 P2 142 P2 141 P2 139 P2 147 P2 134 P2 152 P2 127 P2 140 P2 144 P2 142 P2 129 P2 147 P2 152 P2 149 P2 152 P2 140 P2 148 P2 144 P2 151 P2 145 P2 137 P2 138 P2 143 P2 143 P2 144 P2 143 P2 137 P2 147 P2 130 P2 145 P2 141 P2 135 P2 143 P2 126 P2 146 P2 150 P2 137 P2 141 P2 145 P2 136 P2 138 P2 148 P2 IND %TW TWD 11 TWD 32 TWD 10 TWD 16 TWD 14 TWD 3 TWD 12 TWD 14 TWD 5 TWD 9 TWD 13 TWD 6 TWD 10 TWD 10 TWD 7 TWO 7 TWD 16 TWD 10 TWD 12 TWD 8 TWD 13 TWO 9 TWD 10 TWO 13 TWD 9 TWD 7 TWD 10 TWD 10 TWD 25 TWD 9 TWD 11 TWD 10 TWD 12 TWD 9 TWD 5 TWD 18 TWO 7 TWD 8 TWD 15 TWD 12 TWD 16 TWD 7 TWD 5 TWD 4 TWD 8 TWD 10 TWD 5 TWD 7 TWD 6 TWD 8 TWD 10 TWD 8 TWD 8 TWD 18 TWD 10 TWD 6 TWD 7 TWD 10 TWD 13 TWD 12 TWD 12 TWD 12 TWD 9 TWD 10 TWD 23 TWD 6 TWD 23 TWD 13 TWD 14 TWD 7 TWD 11 TWD 7 TWD 10 TWD 6 TWD 26 TWD 5 TWD 5 TWD 9 TWD 7 TWD 11 LOCATION EXT EXT 014

-0.72 UTE LTE 013

+0.08 UTE LTE 010

+0.11 UTE LTE 011

-0.63 UTE LTE 012

+0.13 UTE LTE 008

+0.16 UTE LTE 010

+0.50 UTE LTE 012

+0.16 UTE LTE 011

-0.53 UTE LTE 014

-0.61 UTE LTE 012

+0.18 UTE LTE 012

-0.55 UTE LTE 014

+0.13 UTE LTE 012

-0.56 UTE LTE 011

+0.21 UTE LTE 013

+0.13 UTE LTE 013

+0.19 UTE LTE 012

+0.24 UTE LTE 011

+0.21 UTE LTE 013

+0.21 UTE LTE 013

-0.48 UTE LTE 013

-0.45 UTE LTE 013

-0.42 UTE LTE 010

+0.61 UTE LTE 013

+0.32 UTE LTE 011

-0.32 UTE LTE 011

+0.34 UTE LTE 010

-0.39, LTE UTE 010

-0.39 LTE UTE 014

+0.27 LTE UTE 011

+0.29 LTE UTE 013

+0.27 LTE UTE 014

-0.54 LTE UTE 014

+0.20 LTE UTE 011

+0.29 LTE UTE 014

-0.59 LTE UTE 014

-0.61 LTE UTE 014

+0.12 LTE UTE 010

-0.56 LTE UTE 013

-0.61 LTE UTE 010

-0.56 LTE UTE 011

+0.20 LTE UTE 010

-0.05 UTE LTE 010

+0.05 UTE LTE 008

+0.08 UTE LTE 012

-0.61 LTE UTE 009

+0.13 UTE LTE 012

-0.64 UTE LTE 010

+0.16 UTE LTE 014

-0.66 UTE LTE 012

+0.13 UTE LTE 011

-0.61 UTE LTE 010

+0.53 UTE LTE 012

+0.16 UTE LTE 010

+0.53 UTE LTE 011

+0.21 UTE LTE 011

-0.53 UTE LTE 010

+0.53 UTE LTE 013

+0.16 UTE LTE 011

+0.21 UTE LTE 013

-0.53 UTE LTE 012

+0.24 UTE LTE 012

-0.50 UTE LTE 011

+0.21 UTE LTE 011

+0.24 UTE LTE 013

+0.21

'UTE LTE 013

-0.47 UTE LTE 012

+0.29 UTE LTE 011

+0.29 UTE LTE 013

-0.42 UTE LTE 013

+0.29 UTE LTE 012

-0.37 UTE LTE 014

-0.47 LTE UTE 014

+0.27 LTE UTE 010

-0.42 LTE UTE 010

+0.00 LTE UTE 014

-0.52 LTE UTE 010

-0.51 LTE UTE 013

+0.20 LTE UTE 009

-0.56 LTE UTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR 7

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

CAL 10 10 10 12 10 10 12 10 10 12 12 12 10 10 10 12 10 10 10 12 10 12 10 12 10 10 12 16 16 16 16 16 16 16 16 16 16 16 16 16 70 70 32 32 10 551 10 10 10 12 12 12 12 12 12 10 10 10 10 10 12 12 12 12 12 10 12 12 12 10 12 10 16 16 16 16 16 16 16 70

  1. LEG PROBE OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET.

510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET' 510XB OUTLET 51OXB OUTLET 510XB INLET 51OUL OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name: ONSr Repl 4/22/2008 9:45:29 AM Component: S/G AK Page 61 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: Query~lih]

ROW TUBE VOLTS 85 14 0.07 85 17 0.08 85 27 0.19 85 49 0.10 85 100 0.05 85 110 0.12 85 11 0.15 0.11 0.11 85 112 0.13 85 113 0.13 85 114 0.11 0.18 0.16 0.12 85 115 0.23 0.15 0.10 0.12 85 116 0.13 85 117 0.09 0.13 85 118 0.14 0.17 85 119 0.22 85 120 0.14 85 121 0.16 0.10 0.09 %

0.26 85 122 0.20 0.09 0.06 85 123 0.26 85 124 0.22 0.22 0.13 85 125 0.10 0.17 85 126 0.16 0.07 85 127 0.15 0.14 85 128 0.14 85 129 0.10 85 130 0.35 0.18 86 3

0.24 86 7

0.17 0.17 0.15 86 8

0.23 0.49 86 9

0.20 0.15 86 13 0.22 0.15 0.08 86 14 0.12 0.11 86 15 0.10 86 19 0.05 86 21 0.14 86 28 0.14 86 31 0.12 86 47 0.08 86 48 0.08 86 66 0.08 86 102 0.08 86 110 0.07 0.04 86 111 0.10 0.05 86 112 0.12 0.13 86 114 0.09 0.09 0.12 86 115 0.16 86 116 0.27 DEG CHN 131 P2 147 P2 132 P2 101 P2 152 P2 127 P2 144 P2 147 P2 143 P2 117 P2 139 P2 133 P2 131 P2 140 P2 143 P2 131 P2 145 P2 147 P2 149 P2 144 P2 141 P2 143 P2 150 P2 148 P2 144 P2 149 P2 142 P2 146 P2 143 P2 137 P2 139 P2 147 P2 157 P2 132 P2 147 P2 145 P2 144 P2 147 P2 142 P2 146 P2 150 P2 140 P2 127 P2 142 P2 141 P2 132 P2 113 P2 140 P2 137 P2 146 P2 147 P2 138 P2 134 P2 142 P2 153 P2 147 P2 140 P2 152 P2 149 P2 130 P2 137 P2 152 P2 130 P2 122 P2 113 P2 152 P2 58 P2 139 P2 154 P2 135 P2 137 P2 149 P2 150 P2 147 P2 128 P2 134 P2 145 P2 121 P2 140 P2 136 P2 IND %TW TWD 6 TWD 7 TWD 10 TWD 6 TWD 3 TWD 8 TWD 10 TWD 8 TWD 8 TWD 11 TWD 8 TWD 7 TWD 11 TWD 10 TWD 8 TWD 14 TWD 10 TWD 7 TWD 8 TWD 9 TWD 6 TWD 9 TWD 9 TWD 11 TWD 13 TWD 10 TWD 10 TWD 7 TWD 6 TWD 15 TWD 13 TWD 7 TWD 4 TWD 15 TWD 14 TWD 14 TWD 9 TWD 7 TWD 11 TWD 11 TWD 5 TWD 10 TWD 9 TWD 10 TWD 7 TWD 20 TWD 12 TWD 14 TWD 10 TWD 10 TWD 9 TWD 13 TWD 23 TWD 12 TWD 9 TWD 12 TWD 9 TWD 5 TWD 9 TWD 8 TWD 9 TWD 5 TWD 11 TWD 10 TWD 7 TWD 5 TWD 5 TWD 5 TWD 5 TWD 5 TWD 3 TWD 7 TWD 4 TWD 9 TWD 10 TWD 7 TWD 7 TWD 9 TWD 11 TWD 17 LOCATION 010

+0.02 011

+0.15 014

-0.05 008

-0.65 010

+0.03 008

+0.13 011

+0.00 010

+0.08 008

+0.08 014

-0.72 014

+0.05 014

+0.00 014

-0.75 012

-0.61 010

+0.08 014

+0.00 012

-0.64 011

+0.11 009

+0.11 009

+0.08 010

+0.16 009

+0.08 011

-0.58 010

+0.50 010

+0.50 010

+0.55 013

+0.13 012

-0.53 011

+0.19 011

-0.51 013

+0.13 011

-0.50 011

+0.18 013

+0.19 014

-0.53 011

+0.21 013

-0.50 014

-0.51 013

-0.48 013

-0.48 011

+0.29 013

+0,21 011

-0.40 013

+0.24 011

+0.24 011

-0.34 010

+0.61 010

-0.39 010

+0.64 011

+0.29 012

+0.27 011

+0.29 012

-0.46 014

-0.54 014

+0.02 009

-0.54 010

-0.51 012

+0.20 010

-0.56 013

-0.59 011

+0.19 011

+0.12 Oil

-0.63 009

-0.56 009

-0.61 009

+0.07 009

-0.66 009

-0.05 010

+0.05 008

+0.08 010

+0.08 010

+0.05 008

+0.01 013

-0.05 010

+0.11 012 20.72 010

+0.13 014

-0.69 011

+0.08 012

-0.61 EXT LTE LTE LTE LTE UTE UTE UTE UTE UTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE EXT UTIL 1

UTIL 2

UTE WAR UTE WAR UTE WAR UTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR UTE WAR 0

UTE WAR 0

LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR 3

LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR 6

LTE WAR LTE WAR LTE WAR LTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR 4

UTE WAR 4

UTE WAR UTE WAR UTE WAR UTE WAR 0

UTE WAR UTE WAR UTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR 5

LTE WAR LTE WAR CAL #

72 72 100 100 32 10 12 12 12 551 553 10 10 10 10 10 10 10 10 12 10 10 12 12 10 12 10 10 10 10 12 12 12 10 12 12 12 10 10 12 12 10 10 12 10 12 12 16 16 16 16 16 16 16 16 16 16 16 70 70 72 72 72 535 100 100 100 24 32 6

6 8

8 6

6 6

6 6

8 6

LEG INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONS1 Repi ONSlAR-E0C24 -

Tube Supp QUERY: Query~l[1]

4/22/2008 9:45:30 AM Component: S/G A Page 62 of 97 ort Wear ROW TUBE VOLTS 0.09 86 118 0.12 0.17 86 121 0.17 0.16 0.12

.86 122 0.20 86 123 0.08 0.12 N'O0.16 86 124 0.08 0.07 86 125 0.24 0.16 0.11 0.19 0.11 0.14 0.10 86 127 0.15 0.13 86 128 0.15 86 129 0.12 86ý130 0.14 0.16 0.10 0.07 86 131 0.13 0.09 87 3

0.14 87 4

0.12 87 5

0.34 87 6

0.14 87 7

0.35 0.15 0.10 87 10 0.09 87 12 0.19 0.25 0.10 0.15 87 14 0.11 87 18 0.11 0.09 0.19 87 25 0.09 0.08 87 58 0.05 87 111 0.06 87 112 0.09 87 113 0.20 0.10 87 115 0.10 0.11 87 116 "0.24 0.10 0.10 87 117 0.23 0.09 87 118 0.09 0.15 87 120 0.09 0.12 87 121 0.19 0.12 87 122 0.07 0.13 0.11 87 125 0.25 0.23 87 126 0.36 87 127 0.13 87 128 0.24 0.10 0.07 87 129 0.27 0.10 87 130 0.44 0.59 0.11 DEG 131 149 139 148 146 143 138 151 147 138 136 141 143 147 144 140 147 142 146 147 136 130 92 139 136 60 136 145 144 138 139 138 136 136 143 147 160 141 138 150 148 142 144 110 134 137 145 112 115 131 143 121 148 139 140 135 129 144 149 150 141 153 140 142 153 139 145 141 137 144 137 146 135 151 126 142 130 135 131 133 CHN IND %TW LOCATION EXT EXT P2 TWO 7 013

-0.05 UTE LTE P2 TWD 8 012

-0.64 UTE LTE P2 TWD 1 011

-0.56 UTE LTE P2 TWD 11 013

-0.61 UTE LTE P2 TWD 11 012

-0.50 UTE LTE P2 TWD 8 013

+0.11 UTE LTE P2 TWD 12 010

+0.53 UTE LTE P2 TWD 5 013

+0.13 UTE LTE P2 TWD 8 011

-0.40 UTE LTE P2 TWD 11 010

+0.55 UTE LTE P2 TWD 6 013

+0.19 UTE LTE P2 TWD 5 012

-0.48 UTE LTE P2 TWD 15 013

+0.16 UTE LTE P2 TWD 10 012

+0.21 UTE LTE P2 TWD 8 012

-0.48 UTE LTE P2 TWD 12 011

+0.24 UTE LTE P2 TWD 7 011

-0.50 UTE LTE P2 TWD 9

010

-0.45 UTE LTE P2 TWD 7 009

+0.58 UTE LTE P2 TWD 10 013

+0.21 UTE LTE P2 TWD 9 011

+0.29 UTE LTE P2 TWD 10 013

-0.42 UTE LTE P2 TWD 8 010

+0.64 UTE LTE P2 TWD 9 012

+0.32 UTE LTE P2 TWD 10 011

-0.35 UTE LTE P2 TWD 6 010

+0.64 UTE LTE P2, TWD 5 008

-0.40 UTE LTE P2 TWD 9 012

+0.34 UTE LTE P2 TWD 7 008

-0.39 UTE LTE P2 TWD 8 010

-0.39 LTE UTE P2 TWD 7 010

-0.39 LTE UTE P2 TWD 18 010

-0.42 LTE UTE P2 TWD 9

011

+0.32 LTE UTE P2 TWD 18 010

-0.44 LTE UTE P2 TWD 9 011

+0.29 LTE UTE P2 TWD 6 013

-0.49 LTE UTE P2 TWD 6 010

-0.54 LTE UTE P2 TWD 11 010

-0.54 LTE UTE P2 TWD 14 011

+0.22 LTE UTE P2 TWD 6 012

+0.17 LTE UTE P2 TWD 9 013

-0.59 LTE UTE P2 TWD 10 012

-0.58 LTE UTE P2 TWD 9 009

-0.56 LTE UTE P2 TWD 7 010

+0.15 LTE UTE P2 TWD 15 011

-0.63 LTE UTE P2 TWD 5 010

-0.63 LTE UTE P2 TWD 5 011

+0.07 LTE UTE P2 TWD 4 008

-0.66 UTE LTE P2 TWD 5 008

+0.11 UTE LTE P2 TWD 9 014

+0.05 LTE UTE P2 TWD 13 011

+0.11 UTE LTE P2 TWD 8 010

+0.08 UTE LTE P2 TWD 8 008

+0.16 UTE LTE P2 TWD 8 011

+0.08 UTE LTE P2 TWD 16 011

-0.64 UTE LTE P2 TWD 8 010

+0.11 UTE LTE P2 TWD 7 011

+0.11 UTE LTE P2 TWD 15 011

+0.11 UTE LTE P2 TWD 7 008

+0.16 UTE LTE P2 TWD 6 012

-0.58 UTE LTE P2 TWD 9 011

+0.13 UTE LTE P2 TWD 6 009

-0.55 UTE LTE P2 TWD 8 011

+0.13 UTE LTE P2 TWD 13 014

+0.11 UTE LTE P2 TWD 8 010

+0.55 UTE LTE P2 TWD 5 014'

+0.16 UTE LTE P2 TWD 9 014

-0.61 UTE LTE P2 TWD 8 010

+0.45 UTE LTE P2 TWD 16 012

-0.45 UTE LTE P2 TWD 15 011

+0.26 UTE LTE P2 TWD 19 011

+0.26 UTE LTE P2 TWD 9 011

+0.32 UTE LTE P2 TWD 16 013

+0.27 UTE LTE P2 TWD 7 011

+0.29 UTE LTE P2 TWD 5 010

-0.42 UTE LTE P2 TWD 16 011

+0.34 UTE LTE P2 TWD 7 010

-0.39 UTE LTE P2 TWD 24 012

+0.35 UTE LTE P2 TWD 29 01I

+0.35 UTE LTE P2 TWD 8 011

-0.32 UTE LTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR.

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG PROBE 3

6 10 10 12 12 5

12 10 12 12 12 4

10 4

10 12 12 12 12 12 12 12 12 12 10 12 10 10 10 10 12 12 16 16 2

16 16 16 16 16 5

16 16 16 16 16 5

72 72 72 72 100 100 24 6

0 551 6

6 6

6 6

6 6

4 6

8 8

32 32 32 5

32 8

8 6

6 6

8 8

32

  • 8 6

6 6

8 8.

6 6

6 OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl ONSlAR-EOC24 -

Tube Support Wear 4/22/2008 9:45:31 AM Component: S/G A Page 63 of 97 Component: S/G A Page 63 of 97 QUERY: QueryMl[l]

ROW TUBE VOLTS DEG CHN IND %TW LOCATION EXT EXT 0.11 109 P2 TWD 8 010

+0.67 UTE LTE 0.10 133 P2 TWD 8 010

-0.37 UTE LTE 0.09 118 P2 TWD 7 008

-0.37 UTE LTE 0.11 148 P2 TWD 8 013

+0.35 UTE LTE 88 3

0.05 162 P2 TWD 3 010

-0.44 LTE UTE 88 5

0.48 134 P2 TWD 22 010

-0.42 LTE UTE 88 6

1.12 125 P2 TWD 36 010

-0.43 LTE UTE 0.15 146 P2 TWD 8 011

+0.32 LTE UTE 88 7

0.11 137 P2 TWD 7 011

+0.32 LTE UTE 88 9

0.14 137 P2 TWD 8 014

+0.20 LTE UTE 88 10 0.10 144 P2 TWD 6 010

-0.48 LTE UTE 0.16 138 P2 TWD 9 011

+0.27 LTE UTE 88 11 0.11 152 P2 TWO 7 010

-0.51 LTE UTE 0.11 143 P2 TWD 7 012

+0.22 LTE UTE 88 12 0.10 149 P2 TWD 6 010

-0.51 LTE UTE 88 13 0.15 150 P2 TWD 9 010

-0.54 LTE UTE 0;15 146 P2 TWD 9 011

+0.22 LTE UTE 88 16 0.07 150 P2 TWD 7 011

+0.17 LTE UTE 88 21 0.12 143 P2 TWD 10 009

-0.58 LTE UTE 88 24 0.11 135 P2 TWD 6 011

-0.66 LTE UTE 88 31 0.10 129 P2 TWD 6 011

-0.66 LTE UTE 88 106 0.12 141 P2 TWD 8 009

+0.08 UTE LTE 88 109 0.05 148 P2 TWD 4 010

+0.03 UTE LTE 88 112 0.19 133 P2 TWD 13 013

-0.69 UTE LTE 0.26 131 P2 TWD 17 012

+0.05 UTE LTE 0.17 140 P2 TWD 12 011

-0.67 UTE LTE 0.12 136 P2 TWD 9 008

+0.08 UTE LTE 0.16 137 P2 TWD 11 011

+0.03 UTE LTE 0.13 138 P2 TWD 9 012

-0.69 UTE LTE 88 113 0.17 142 P2 TWD 12 010

+0.11 UTE LTE 0.19 135 P2 TWD 12 008

+0.08 UTE LTE 88 116.0.20 139 P2 TWD 13 012

+0.08 UTE LTE 0.09 140 P2 TWO 6 012

-0.63 UTE LTE 88 118 0.19 141 P2 TWD 12 011

+0.11 UTE LTE 88 119 0.11 140 P2 TWD 8 012

+0.16 UTE LTE 0.34 139 P2 TWD 20 012

-0.56 UTE LTE 0.09 159 P2 TWD 7 009

+0.48 UTE LTE 88 120 0.18 144 P2 TWD 12 014

+0.11 UTE LTE 0.14 148 P2 TWD 10 012

-0.55 UTE LTE 0.23 141 P2 TWD 14 011

+0.16 UTE LTE 88 121 0.12 146 P2 TWD 8 011

-0.51 UTE LTE 88 122 0.14 140 P2 TWD 10 010

+0.56 UTE LTE 88 123 0.11 150 P2 TWD 8 010

+0.53 UTE LTE 88 125 0.09 143 P2 TWD 7 014

-0.53 UTE LTE 0.28 132 P2 TWD 18 013

+0.19 UTE LTE 0.23 143 P2 TWD 15 012

+0.24 UTE LTE 0.29 133 P2 TWD 18 012

-0.48 UTE LTE 0.27 137 P2 TWD 17 011

+0.24 UTE LTE 0.35 139 P2 TWD 21 011

-0.45 UTE LTE 88 126 0.26 142 P2 TWD 16 012

+0.24 UTE LTE 0.09 143 P2 TWD 6 011

+0.26 UTE LTE 88 127 0.14 137 P2 TWD 10 013

+0.21 UTE LTE 0.20 142 P2 TWD 14 011

+0.29 UTE LTE 88 128 0.26 138 P2 TWD 16 013

-0.47 UTE LTE 0.36 139 P2 TWD 21 012

+0.29 UTE LTE 0.62.

134 P2 TWD 30 011

+0.32 UTE LTE 0.13 141 P2 TWD 9 010

-0.45 UTE LTE 88 129 0.13 139 P2 TWD 9 012

-0.35 UTE LTE.

0.45 130 P2 TWD 25 011

+0.32 UTE LTE 0.21 133 P2 TWD 14 010

-0.40 UTE LTE 88 130 0.23 143 P2 TWD 15 011

+0.34 UTE LTE 0.16 147 P2 TWO 11 011

-0.37 UTE LTE 88 131 0.16 140 P2 TWD 11 013

+0,35 UTE LTE 0.08 139 P2 TWD 6

012

-0.40 UTE LTE 89 3

0.07 153 P2 TWD 4 010

-0.44 LTE UTE 89 5

0.09 145 P2

'TWD 5

011

+0.32 LTE UTE 89 6

0.25 141 P2 TWD 13 011

+0.17 LTE UTE 0.13 147 P2 TWD 7 012

-0.41 LTE UTE 89 7

0.10 142 P2 TWD 6 011

+0.29 LTE UTE 89 8

0.08 140 P2 TWO 5 011

+0.31 LTE'UTE 89 10 0.11 147 P2 TWD 6 010

-0.48 LTE UTE 89 11 0.09 140 P2 TWD 5 012

-0.54 LTE UTE 89 12 0.16 145 P2 TWD 9 010

-0.51 LTE UTE 0.15 142 P2 TWD 8 011

+0.24 LTE UTE 89 13 0.11 143 P2 TWD 8 012

-0.54 LTE UTE 0.10 140 P2 TWD 7 010

-0.56 LTE UTE 89 14 0.16 133 P2 TWO 13 011

+0.19 LTE UTE 89 16 0.14 139 P2 TWD 10 012

-0.59 LTE UTE 89 17 0.07 147 P2 TWD 6

010

+0.15 LTE UTE 0.11 141 P2 TWD 10 011

+0.17 LTE UTE UTIL 1

UTIL WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 8

WAR 7

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 5

WAR WAR 0

WAR WAR WAR WAR WAR S

WAR WAR WAR WAR 2

CAL # LEG 6

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 20 INLET 20 INLET 18 INLET 18 INLET 20 INLET 20 INLET 18 INLET 18 INLET 16 INLET 16 INLET 16 INLET 16 INLET 16 INLET 72 INLET 72 INLET 100 INLET 100 INLET 32 OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 8

OUTLET 8

OUTLET 8

OUTLET 8

OUTLET 8

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 8

OUTLET 8

OUTLET 8

OUTLET 6

OUTLET 8

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 8

OUTLET 8

OUTLET 6

OUTLET 6

OUTLET 8

OUTLET 8

OUTLET 8

OUTLET 8

OUTLET 6

OUTLET 6

OUTLET 6

OUTLET 8

OUTLET 8

OUTLET 6

OUTLET 6

OUTLET 24 INLET 24 INLET 22 INLET 22 INLET 24 INLET 22 INLET 22 INLET 24 INLET 22 INLET 22 INLET 70 INLET 70 INLET 72 INLET 70 INLET 72 INLET 72 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:32 AM Component:

S/G A Page 64 of 97 ONSIAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 89 38 0.12 89 102 0.11 89 113 0.08 89 114 0.08 89 115 0.16 0.14 89 116 0.10 0.07 89 119 0.14 89 120 0.11 0.07 0.10 89 122 0.13 89 124 0.30 0.21 0.13 0.22 89 125 0.15 0.25 89 126 0.09 0.20 0.11 89 127 0.30 0.33 0.64 0.15 0.30 0.15 0.09 89 128 0.12 0.15 0.06 89 129 0.19 89 130 0.29 0.15 90 3

0.16 90 5

1.00 0.09 0.07 90 6

0.51 0.12 0.18 90 7

0.16 90 8

0.11 90 13 0.08 0.13 90 15 0.07 0.14 0.16 90 22 0.07 90 26 0.08 90 104 0.08 90 107 0.07 90 112 0.11 90 114 0.07 90 115 0.16 0.10 0.22 0.09 0.10 0.11 0.12 90 118 0.14 0.13 0.11 0.09, 90 119 0.12ý 90 120 0.25 90 122 0.15 90 123 0.12 0.15 0.10 0.14 90 124 0.14 0.11 90 125 0.18 0.09 0.09 0.22 90 126 0.21 DEG 92 143 141 144 136 132 149 139 149 145 154 155 142 142 144 152 144 137 141 137 146 143 134 132 128 132 136 139 136 139 142 148 137 137 76 148 128 126 154 132 147 137 149 148 149 131 147 132 149 140 121 147 135 140 150 144 152 140 143 140 156 115 144 138 144 155 147 i46 141 150 143 140 139 148 140 146 141 148 137 140 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW LOCATION TWD 6 009

-0.61 TWD 7 010

-0.05 TWD 6 008

+0.11 TWD 6 012

-0.63 TWD 11 014

-0.69 TWD 10 012

+0.05 TWD 7 011

+0.11 TWD 5 009

+0.08 TWD 10 011

-0.56 TWD 8 014

-0.61 TWD 5 012

-0.53 TWD 7 010

-0.58 TWD 9 009

+0.48 TWD 18 012

+0.24 TWD 14 012

-0.48 TWD 9 011

+0.26 TWD 14 011

-0.45 TWD 10 011

+0.29 TWD 16 011

-0.37 TWD 6 012

-0.45 TWD 13 011

+0.26 TWD 8 011

-0.45 TWD 19 013

+0.24 TWD 20 012

-0.40 TWD 3I 011

+0.29 TWD 11 011

-0.40 TWD 19 010

-0.40 TWD 11 013

-0.45 TWD 7 012

+0.05 TWD 8 012

-0.40 TWD 11 010

-0.47 TWD 4 011

+0.29 TWD 13 010

-0.45 TWD 17 011

-0.34 TWD 10 010

+0.66 TWD 9 014

-0.42 TWD 35 010

-0.44 TWD 6 011

-0.44 TWO 5 011

+0.29 TWD 22 010

-0.46 TWD 7 011

+0.32 TWD 9 014

+0.22 TWD 10 014

-0.54 TWD 6 011

+0.22 TWD 7 011

+0.22 TWD 11 012

-0.56 TWD 6 011

+0.17 TWD 11 014

-0.64 TWD 13 014

+0.02 TWO 6 011

+0.10 TWD 4 009

-0.61 TWD 6 009

+0.13 TWO 5 010

+0.05 TWD 8 013

-0.05 TWD 5 008

+0.19 TWD 11 012

-0.63 TWD 7 011

+0.08 TWD 14 011

-0.63 TWD 6 010

+0.18 TWD 7 014

-0.64 TWD 8 013

.+0.05 TWD 9 013

-0.66 TWD 10 014

+0.13 TWD 10 014

-0.61 TWD 8 012

-0..53 TWD 7 011

-0.56 TWD 9 012

-0.53 TWO 16 012

-0.48 TWD 11 012

-0.45 TWDO8 014

-0.53 TWD 11 013

+0.16 TWD 7 011

-0.48 TWD 10 010

-0.48 TWD 10 014

-0.48 TWD 8 011

-0.42 TWD 12 013

+0.21 TWD 7 012

-0.48 TWD 7 011

+0.26 TWD 14 011

-0.42 TWD 14 013

+0.24 EXT EXT LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR 7

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR

'WAR WAR WAR WAR WAR 7

WAR 5

WAR WAR WAR WAR WAR WAR WAR 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR 4

WAR WAR WAR WAR WAR 5

WAR 4

WAR 5

WAR WAR 7

WAR 5

WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR WAR WAR WAR WAR CAL #

100 32 6

8 6

6 8

8 6

8 8

8 8

8 8

8 8

6 6

8 8

8 6

6 6

6 6

6 6

8 8

8 6

8 8

22 24 24 24 22 22 22 24 22 72 72 72 72 72 72 100 511 32 6

6 8

8 8

8 8

8 8

6 6

6 6

8 6*6 8

8 8

8 6

6 8

8 8

8 6

LEG INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 5100L 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

.510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB

AREVA NP Inc Customer Name:

rNSl Rep]

4/22/2008 9:45:32 AM Component: S/G A Page 65 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: Query~l(1]

ROW TUBE VOLTS DEG CHN 0.12 90 127 0.19 0.08 90 128 0.17 0.17 0.08 90 129 0.36 0.15 0.21 0.48 0.08 0.13 91 6

1.09 0.13 0.18 91 7

1.11 91 9

0.12 91 10 0.13 91 11 0.12 91 12 0.09 0.11 91 16 0.13 91 60 0.10 91 114 0.07 0.07 91 115 0.09 91 121 0.15 0.12 0.08 0.08 0.10 91 122 0.16 0.12 91 123 0.09 0.11 0.07 91 124 0.17 91 125 0.23 0.43 0.16 0.12 0.08 91 126 0.13 0.28 0.27 1.45 91 127 0.15 0.17 0.10 91 128 0.23 0.07 91 129 0.10 0.12 0.30 0.09 0.13 91 130 0.22 0.12 0.16 92 4

0.14 0.10 92 6

0.18 92 7

0.14 92 8

0.10 92 9

0.11 92 10 0.13 92 11 0.13 92 14 0.07 92 16 0.20 92 20 0.07 0.09 92 27 0.08 92 32 0.10 0.08 92 101 0.09 92 108 0.09 92 110 0.15 92 113 0.20 0.11 92 114 0.07 137 P2 145 P2 148 P2 137 P2 143 P2 129 P2 140 P2 134 P2 142 P2 135 P2 128 P2 86 P2 125 P2 135 P2 142 P2 127 P2 143 P2 148 P2 145 P2 144 P2 149 P2 136 P2 153 P2 142 P2 131 P2 146 P2 146 P2 151 P2 120 P2 149 P2 141 P2 147 P2 137 P2 133 P2 139 P2 153 P2 143 P2 139 P2 134 P2 142 P2 134 P2 146 P2 152 P2 136 P2 121 P2 122 P2 134 P2 141 P2 136 P2 138 P2 153 P2 150 P2 136 P2 136 P2 126 P2 137 P2-141 P2 107 P2 140 P2 141 P2 119 P2 152 P2 147 P2 146 P2 138 P2 144 P2 149 P2 147 P2 141 P2 129 P2 150 P2 117 P2 124 P2 140 P2 137 P2 135 P2 136 P2 137 P2 148 P2 142 P2 IND %TW TWD 9 TWD 13 TWD 6 TWD 12 TWD 12 TWD 6 TWD 21 TWD 10 TWD 13 TWD 25 TWD 6 TWD 9 TWD 35 TWD 7 TWD 10 TWD 37 TWD 7 TWD 7 TWD 7 TWD 5 TWD 6 TWD 11 TWD 6 TWD 6 TWD 6 TWD 7 TWD 10 TWD 9 TWD 6 TWD 6 TWO 8 TWD 11 TWD 9 TWD 7 TWD 8 TWD 5 TWD 11 TWD 15 TWD 24 TWD 11 TWD 9 TWD 6 TWD 9 TWD 17 TWD 17 TWD 45 TWD 11 TWD 12 TWD 7 TWD 14 TWD 5 TWD 7 TWD 9 TWD 19 TWD 7 TWD 9 TWD 14 TWD 9 TWD 11 TWD 8 TWD 5 TWD 9 TWD 8 TWD 5 TWD 7 TWD 7 TWD 8 TWD 6 TWD 15 TWD 6 TWD 8 TWD 5 TWD 6 TWD 5 TWD 7 TWD 7 TWD 10 TWD 14 TWD 8 TWD 5 LOCATION Ol

-0.37 013

+0.24 Ol

+0.32 013

+0.29 Ol

+0.32 010

-0.48 013

+0.32 012

-0.37 Ol

+0.29 011

-0.37 010

-0.45 010

+0.58 010

-0.41 011

+0.32 012

-0.41 010

-0.46 014

-0.56 010

-0.48 010

-0.51 012

+0.19 010

-0.51 011

-0.61 008

+0.02 010

+0.13 008

+0.08 012

-0.59 012

-0.53 011

-0.45 008

+0.24 011

-0.03 009

-0.53 014

+0.13 010

+0.58 008

+0.21 009

-0.50 008

-0.45 010

-0.48 013

+0.21 012

+0.26 011

-0.40 009

-0.48 011

+0.24 014

-0.48 013

-0.29 011

-0.16 011

+0.29 013

-0.42 011

+0.32 010

-0.42 010

-0.47 008

+0.29 013

+0.29 012

-0.40 011

+0.32 010

-0.48 009

+0.56 012

-0.37 010

+0.56 015

+0.57 010

-0.39 014

+0.27 010

-0.39 010

-0.44 011

+0.29 011

+0.27 010

-0.51 014

-0.61 011

+0.20 011

-0.59 011

+0.12 012

-0.61 012

-0.68 011

-0.68 011

+0.02 010

+0.07 010

+0.05 010

+0.11 013

-0.64 012

-0.64 010

+0.13 EXT EXT UTIL 1

UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR

UTIL, 2

CAL #

2 6

8 8

6 6

6 8

8 8

8 8

8 22 22 22 24 4

24 22 24 22 4

22 72 100 6

6 6

6 6

6 6

4 6

8 5

8 6

4 6

4 6

8 6

6 6

6 5

6 8

8 8

LAR 8

6 6

6 8

8 6

6 6

6 11 6

8 8

8 8

22 5

22 22 24 4

22 24 22 5

24 72 72 72 72 100 100 100 0

511 6

6 6

6 6

8 LEG/

PROBE OUTLET 51OXB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:32 AM Component: S/G A Page 66 of 97 ONSlAR-EOC24 Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 92 116 0.08 92 117 0.15 0.07 92 118 0.17 0.08 92 119 0.15 0.07 0.11 92 121 0.13 92 122 0.24 92 124 0.14 0.09 0.17 92 125 0.37 0.14 0.34 0.17 92 126 0.16 0.11 92 127 0.21 0.77 0.12 0.27 0.12 92 128 0.09 0.10 0.11 93 1

0.13-0.13 93 6

0.27 0.11 0.15 0.40 93 13 0.13 0.07.

93 15 0.13 0.15 93 16 0.05 93 20 0.05 93 24 0.15 93 26 0.19 93 105 0.07 93 107 0.11 93 108 0.15 93 109 0.17 93 111i 0.12 93 117 0.09 93 118 0.06 0.08 93 120 0.09 0.14 93 121 0.20 93 123 0.15 93 124 0.30 0.09 0.19 0.13 93 126 0.08 0.39 0.35 0.10 0.14 93 128 0.41 0.09 0.17 0.20 0.24 94 1

0.13 94 3

0.09 94 6

0.60 94 7

0.26 94 8

0.11 94 9

0.20 94 13 0.13 94 15 0.11 94 23 0.13 94 59 0.12 94 92 0.09 94 104 0.06 94 109 0.11 DEG 140 139 149 141 131 142 144 141 139 144 150 147 138 135 134 137 138 146 146 135 126 133 127 140 148 143 115 122 99 141 158 143 140 141 146 136 148 157 130 140 155 139 147 146 140 146 146 140 135 144 144 142 144 136 151 136 144 136 136 139 124 139 140 147 143 148 140 155 146 135 148 150 134 135 137 132 143 139 152 147 CHN IND %TW LOCATION P2 TWD 6 009

+0.53 P2 TWD 11 014

-0.67 P2 TWD 5 011

+0.13 P2 TWDO12 012

+0.13 P2 TWD 6 011

-0.16 P2 TWD 10 012

-0.56 P2 TWD 5 008

+0.13 P2 TWD 8 011

+0.16 P2 TWD 9 009

-0.50 P2 TWD 15 012

+0.21 P2 TWD 10 014

+0.18 P2 TWD 7 011

+0.26 P2 TWD 12 010

-0.45 P2 TWD 22 013

-0.45 P2 TWD 10 012

-0.48 P2 TWD 21, 011

+0.27 P2 TWD 12 011

-0.40 P2 TWD 11 013

+0.21 P2 TWD 8 009

-0.45 P2 TWD 14 013

+0.24 P2 TWD 34 011

+0.29 P2 TWD 8 011i

-0.13 P2 TWD 17 010

-0.45 P2 TWD 9 009

+0.56 P2 TWD 7 013

+0.26 P2 TWD 7 012

-0.40 P2 TWD 8 009

+0.58 P2 TWO 8 010

-0.37 P2 TWD 8 010

+0.64 P2 TWD 14 011

+0.32 P2 TWD 6

014,

-0.51 P2 TWD 8 014

+0.24 P2 TWD 18 010

-0.41 P2 TWD 11 011

+0.19 P2 TWD 7 012

+0.17 P2 TWO 11 011

-0.58 P2 TWD 12 009

-0.54 P2 TWD 5 008

-0.53 P2 TWO 5 011

+0.10 P2 TWD 8 014

-0.02 P2 TWD 10 011

+0.05 P2 TWO 5 010

+0.05 P2 TWO 8 010

+0.05 P2 TWD 11 010

+0.05 P2 TWD 12 010

+0.08 P2 TWO 9 011

+0.03 P2 TWD 7 011

+0.13 P2 TWD 5 014

-0.64 P2 TWD 6 009

+0.61 P2 TWD 6 014

+0.13 P2 TWD 10 011

+0.16 P2 TWD 13 012

+0.19 P2 TWD 10 011

-0.42 P2 TWD 18 013

+0.21 P2 TWD 7 011

+0.29 P2 TWD 12 010

+0.61 P2 TWD 9 011

-0.42 P2 TWD 6 011

-0.42 P2 TWD 22 010

-0.50 P2 TWD 20 011

+0.34 P2 TWD 7 009

+0.55 P2 TWD 10 013

+0.26 P2 TWD 23 013

+0.29 P2 TWD 7 012

+0.32 P2 TWD 11 012

-0.40 P2 TWD 13 011

+0.34 P2 TWD 15 011

-0.37, P2 TWD 8 011

+0.39 P2 TWD 5 011

+0.34 P2 TWD 25 010

-0.42 P2 TWD 14 010

-0.44 P2 TWD 6

011,

+0.29 P2 TWD 1 011

+0.25 P2, TWD 11 013

-0.61 P2 TWD 10 009

-0.56 P2 TWD 11 010

-0.61 P2 TWD 7 007

-0.62 P2 :TWD 6 009

-0.03 P2 TWD 4 010

+0.03 P2 TWD 8 010

+0.13 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

8 6

4 6

8 8

6 6

6 6

6 8

8 8

8 6

6 6

68 8

6 66 6

6 88

'7 8

24

.24 22 22 22 2

22 72 72 72 0

72 72 72 100 100 32 6

6 8

6 6

8 8

8 8

6 4

6 88 6

8 4

8 8

8 8

8 8

8 8

88 8

24 24 22 24 22 24 72 72 72 100 32 32 0

553 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET

INLET, INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB S1OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XBa 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:32 Am Component:

S/G A Page 67 of 97 Component: S/G A Pege 67 of 97 ONSlAR-EOC24 - Tube Support Wear QUERY: QueryMl(l]

ROW TUBE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 94 94 94 113 115 123 124 125 126 127 128 129 6

7 9

12 14 15 17 25 58 97 99 104 105 109 112 113 115 119 121 122 123 124 125 126 127 128 4

5 6

7 10 13 25 27 31 58 110 ill 112 113 115 119 0.11 0.11 0.13 0.15 0.07 0.11 0.18 0.08 0.07 0.10 0.15 0.45 0.49 0.63 0.13 0.12 0.06 0.28 0.08 0.06 0.11 0.40 0.53 0.15 0.08 0.12 0.37 0.15 0.19 0.16 0.22 0.10 0.13 0.16 0.10 0.06 0.05 0.09 0.13 0.15 0.09 0.07 0.10

0. 17 0.13
0. 12 0.10
0. 19
0. 12 0.07 0.15 0.13 0.40 0.44 0.22 0.61 1.06 0.48 0.13 0.16 0.11 0.11 0.18 0.11 0.27 0.13 0.12 0.06 0.05 0.09 0.10 0.07 0.09 0.11 0.11 0.08 0.09 0.11 0.32 0.13 139 P2 TWD 7 010 144 P2 140 P2 150 P2 143 P2 148 P2 148 P2 136 P2 142 P2 147 P2 147 P2 140 P2 136 P2 134 P2 136 P2 146 P2 135 P2 146 P2 149 P2 135 P2 147 P3 140 P2 138 P2 150 P2 158 P2 156 P2 139 P2 146 P2 144 P2 135 P2 141 P2 130 P2 137 P2 102 P2 110 P2 147 P2 126 P2 144 P2 124 P2 132 P2 120 P2 149 P2 149 P2 138 P2 133 P2 142 P2 142 P2 145 P2 86 P2 155 P2 140 P2 142 P2 134 P2 131 P2 126 P2 127 P2 123 P2 135 P2 141 P2 136 P2 131 P2 137 P2 145 P2 153 P2 137 P2 124 P2 143 P2 140 P2 144 P2 116 P2 97 P2 90 P2 109 P2 137 P2 129 P2 133 P2 157 P2 148 P2 145 P2 145 P2 TWD 7 TWD 9 TWD 10 TWD 5 TWD 8 TWD 12 TWD 6 TWD 6 TWD 7 TWD 10 TWO 24 TWD 25 TWD 30 TWD 9 TWD 9 TWD 5 TWD 17 TWD 6 TWD 5 TWD 8 TWO 18 TWD 24 TWD 9 TWD 5 TWD 7 TWD 19 TWD 10 TWD 12 TWD 11 TWD 16 TWD 8 TWD 11 TWD 9 TWD 5 TWD 4 TWD 3 TWD 6 TWD 9 TWD 11 TWD 7 TWD 7 TWD 7 TWD 12 TWD 9 TWD 9 TWD 7 TWD 12 TWD 9 TWD 5 TWD 11 TWD 9 TWD 23 TWD 24 TWD 15 TWD 30 TWD 40 TWD 25 TWD 9 TWD.11 TWD 8 TWD 8 TWD 10 TWD 6 TWD 15 TWD 7 TWD 7 TWD 5 TWD 5 TWD 5 TWD 6 TWD 4 TWD 5 TWD 8 TWD 8 TWD 6 TWD 6 TWD 8 TWD 19 TWD 9 Ol 014 010 012 Oili Oili Oili Oili 013 013 012 012 Ol Oili Oili 012 Ol Ol 012 014 010 010 Oili 012 Oili 014 Oili 012 Oili 009 009 009 008 009 010 010 010 012 Ol 012 010 014 014 Ol 009 012 Ol 009 012 013 013 012 012 Ol 010 Ol Ol 010 Ol Ol Ol 014 014 010 Ol Ol 012 013 Ol Ol Ol 008 010 014 010 009 010 012 009

+0.15

-0.58

-0.66

+0.50

-0.48

+0.24

-0.48

+0.24

-0.40

+0.21

-0.47

+0.24

-0.42

+0.29

-0.13

+0.29

-0.40

+0.32

+0.32

-0.37

+0.32

-0.42

-0.44

+0.29

+0.22

+0.25

-0.56

+0.22

-0.51

-0.56

-0.54

-0.63

-0.61

-0.67

-0.65

+0.00

+0.00

+0.05

-0.05

-0.69

-0.69

+0.13

+0.08

-0.69

+0.08

-0.53

-0.50

-0.48

-0.53

+0.24

+0.21

-0.48

+0.26

-0.45

-0.13

-0.50

+0.32

+0.32

-0.48

+0.32

-0.32

-0.32

-0.47

-0.47

-0.44

+0.29

+0.25

+0.02

+0.17

-0.70

-0.68

-0.60

-0.67

+0.13

-0.74

+0.13

-0.58

+0.53

-0.55

/ -0.58 LTE UTE WAR LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR' WAR WAR 0

553 4

553 8

8 8

8 86 4

6 8

8 8

8 8

7 8

6 8

86 8

8 22 24 24 24 24 24 70 70 70 72 0

545 128 100 100 32 32 32 6

5 6

4 6

0 551 0

553 6

6 6

6 8

6 8

6 6

6 6

6 6

LAR 6

8 8

6 6

8 24 2

22 24 22 24 72 0

72 100 100 100 100 6

8 4

6 8

8 8

8 INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:33 AM Component:

S/G A Page 68 of 97 ONSlAR-EOC24 - Tube Support Wear QUERY: QueryMl(l]

ROW TUBE VOLTS 0.11 96 121 0.14 96 122 0.37 0.08 0.08 0.10 96 123 0.24 0.70 1.17 96 124 0.16 96 126 0.19 96 127 0.23 97 5

0.12 97 6

0.42 97 7

0.12 97 16 0.07 97 17 0.08 0.12 97 18 0.09 97 19 0.06 0.16 97 29 0.08 97 99 0.05 97 104 0.10 97 105 0.13 0.11 97 106 0.08 97 108 0.21 97 114 0.08 97 115 0.10 97 118 0.20 0.16 0.16 97 120 0.15 0.34 97 122 0.11 0.34 0.11 0.16 0.13 97 125 0.10 0.22 0.11 97 126 0.12 0.15 98 7

0.16 0.11 98 8

0.09 98 9

0.10 98 12 0.07 0.13 98 14 0.11 98 15 0.25 0.14 98 17 0.12 98 22 0.04 98 25 0.11 98 86 0.16 98 96 0.11 0.08 98 97 0.11 98 99 0.11 98 101 0.12 98 107 0.09 98 109 0.09 98 ill 0.10 98 112 0.21 0.13 98 115 0.14 98 116 98 117 0.15 98 118 0.29 0.19 0.45 98 120 0.10 0.17 0.38 0.18 0.22 0.11 DEG 147 148 134 141 147 144 131 128 126 141 129 138 131 127 150 131 149 1.27 146 143 130 156 65 128 150 140 136 126 144 155 145 144 143 145 136 132 129 136 139 144 139 139 129 140 135 142 133 152 138 122 126 153 131 147 140 152 147 137 129 138 107 102 148 147 146 113 136 142 146 151 141 138 132 149 145 134 144 138 146 CHN IND %TW LOCATION EXT EXT UTIL 1

P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD 8 TWD 10 TWD 22 TWD 6 TWD 6 TWD 7 TWD 15 TWD 32 TWD 41 TWD 11 TWD 13 TWD 15 TWD 7 TWO 19 TWD 7 TWO 6 TWD 5 TWD 9 TWD 7 TWO 5 TWD 13 TWD 4 TWD 4 TWD 8 TWD 9 TWD 8 TWD 6 TWO 15 TWD 6 TWD 9 TWD 13 TWD 10 TWD 10 TWD 10 TWD 20 TWD 8

TWD 20 TWD 8 TWD 11 TWD 9

TWD 8 TWD 16 TWD 9 TWD 8

TWD 10 TWD 8

TWD 6

TWD 6 TWD 5 TWD 7 TWD 11 TWD 9

TWD 16 TWD 10 TWD 9 TWD 3

TWD 9 TWD 12 TWD 7 TWO 5 TWD 8 TWD 9 TWD 8 TWD 7 TWD 7 TWD 8 TWD 14 TWD 9 TWO 11 NDD TWD 12 TWD 17 TWD 12 TWD 24 TWO 7 TWO 11 TWD 21 TWD 12 TWD 14 TWD 8 012 010 011 Ol 012 014 011 010 011 010 010" Ol Ol 010 011 011 011 013 011 012 011 011 010 010 012 010 010 014 008 010 011 Ol 009 Ol 012 008 010 Ol 013 013 011 Ol 012 Ol 012 010 Ol Ol Ol 012 013 013 014 014 009 Ol 011 008 014 010 008 Ol 010 009 014 011 011 014 014 012 012 012 014 011 012 013 014 010 012

+0.21

-0.48

+0.27

-0.40

-0.45

-0.51

-0.16

-0.50

+0.29

-0.50

-0.40

-0.37

+0.32

-0.44

+0.27

-0.59

+0.15

-0.61

+0.15

+0.12

-0.63

+0.07

-0.05

-0.61

+0.02

+0.05

-0.63

-0.66

+0.22

+0.56

-0.49

+0.22

-0.50

+0.25

+0.27

+0.29

-0.42

+0.29

-0.44

+0.25

-0.34

+0.34

-0.39

-0.32

-0.37

-0.42

+0.29

+0.27

+0.24

+0.20

+0.20

+0.15

-0.64

+0.12

-0.61

+0.07

+0.10

-0.61

-0.80

-0.05

-0.68

-0.66

-0.75

-0.65

+0.05

+0.17

-0.56

-0.66

-0.59

-0.49

-0.49

+0.22

+0.17

+0.25

-0.47

+0.22

-0.49

-0.46

+0.25 UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

4 8

8 6

6 2

6 2

6 8

8 LAR 8

6 6

8 24 22 24 72 70 70 72 72 10 72 100 32 106 108 4

108 5

511 106 108 106 108 108 3

108 108 108 108 108 108 4

108 3

108 106 106 106 108 108 22 22 24

.5 22 72 72 72 70 70 0

545 72 72 112 32 3

32 0

507 0

505 0

507 0

511 106 106 108 108 106 108 106 108 108 108 108 108 108 108 5

108 3

108 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET

INLET, INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

rNSl Rep]

4/22/2008 9:45:33 AM Component: S/G A Page 69 of 97 ONSIAR-E0C24 -

Tube Support Wear QUERY: Query~l[1]

ROW TUBE VOLTS 0.12 98 123 0.22 98 124 0.17 0.38 0.10 98 126 0.11 98 127 99 7

0.52 99 16 0.13 99 19 0.13 99 21 0.07 99 23 0.07 99 28 0.11 99 84 0.13 99 86 0.10 99 88 0.15 99 98 0.12 99 102 0.10 99 104 0.10 0.15 99 107 0.10 99 109 0.09 99 110 99 111 0.12 99 112 99 114 0.15 0.11 99 119 0.24 0.39

99.

120 0.38 99 121 0.69 99 122 0.26 99 123 0.11 0.22 0.12 99 126 0.16 100 1 0.16 100 3 0.09 100 7 0.36 100 8 0.14 100 11 0.14 100 14 0.17 100 23 0.21 0.09 100 32 0.08 100 93 0.05 100 97 0.11 100 98 0.11 100 104 0.27 0.10 i00 105 0.11 100 109 0.10 100 110 0.23 100 113 0.11 0.13 100 114 0.12 100 116 0.31 100 118 0.16 0.13 0.13 100 120 0.80 0.17 0.16 0.14 100 121 0.10 100 122 0.12 0.15 DEG CHN 148 P2 134 P2 139 P2 130 P2 143 P'2 117 P2 133 P2 136 P2 135 P2 146 P2 148 P2 128 P2 118 P2 108 P2 119 P2 121 P2 137 P2 129 P2 130 P2 148 P2 145 P2 138 P2 134 P2 147 P2 142 P2 139 P2 137 P2 130 P2 133 P2 136 P2 145 P2 148 P2 124 P2 117 P2 150 P2 137 P2 138 P2 143 P2 142 P2 125 P2 135 P2 155 P2 146 P2 134 P2 129 P2 141 P2 129 P2 147 P2 144 P2 135 P2 146 P2 137 P2 144 P2 139 P2 142 P2 142 P2 150 P2 126 P2 143 P2 146 P2 132 P2 147 P2 137 P2 139 P2 IND %TW TWD 8 TWD 16 TWD 11 TWD 21 TWD 7 TWD 8 NDD TWD 24 TWD 11 TWD 10 TWD 6 TWD 6 TWD 6 TWD 9 TWD 8 TWD 10 TWD 8 TWD 8 TWD 8 TWD 12 TWD 7 TWD 8 NDD TWD 10 NDD TWD 10 TWD 8 TWD 17 TWD 25 TWD 21 TWD 34 TWD 16 TWD 9 TWD 16 TWD 10 TWD 11 TWD 10 TWD 6 TWD 18 TWD 8 TWD 10 TWD 13 TWD 16 TWD 8 TWD 5 TWD 3 TWD 7 TWD 8 TWD 16 TWD 7 TWD 9 TWD 8 TWD 14 TWD 9 TWD 10 TWO 8 TWD 18 TWD 10 TWD 9 TWD 9 TWD 34 TWD 11 TWD 10 TWD 9 TWD 8 TWD 8 TWD 10 NDD NDD TWD 6 TWD 19 TWD 12 TWD 7 TWD 8 TWD 8 TWD 5 TWD 6 TWD 7 TWD 4 TWD 5 LOCATION 013

-0.52 010

-0.41 010

-0.42 011

+0.34 012

-0.39 010

+0.61 010

-0.46 012

-0.51 010

-0.63 Ol

+0.12 Ol

+0.07 Ol

-0.68 008

-0.66 008

-0.63 009

-0.73 010

-0.75 Ol

-0.63 010

-0.61 Ol

-0.66 010

-0.59 010

+0.17 011

-0.59 014

-0.59 014

+0.15 010

-0.46 012

-0.47 010

-0.45 010

-0.45 010

-0.42 011

-0.39 011

+0.32 013

-0.42 010

-0.37 010

+0.66 010

-0.37 010

-0.44 010

-0.46 014

-0.57 014

+0.02 014

-0.73 014

+0.00 011

+0.00 011

+0.00 011

-0.05 011

-0.68 011

+0.05 011

-0.61 010

+0.10 015

+0.02 013

-0.64 014

+0.15 014

-0.59 014

-0.59 011

+0.25 009

-0.50 01

+0.25 010

-0.47 010

-0.42 011

+0.27 012

-0.42 012

+0.29 013

-0.44 011

+0.32 013

-0.44 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR.

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTIL 2

CAL #

5 108 106 108 108 108 8

108 108 24 72 0

545 72 72 100 0

521 0

505 5

507 0

507 0

511 106 106 108 106 108 3

106 108 108 108 106 106 108 106 108 106 106 106 108 24 24 24 2

22 2

70 72 72 72 100 32 32 0

507 108 0

108 106 106 108 106 0

106 108 108 108 108 3

108 108 108 108 6

108 106 108 108 108 108 22 22 24 24 22 70 0

72 128 0

507 32 32 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510UL 510UL 510UL 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 100 100 101 101 101 101 101 101 101 101 101 101 124 125 4

6 7

8 14 16 50 89 91 93 0.11 0.43 0.22 0.12 0.14 0.11 0.05 0.07 0.10 0.05 0.08 131 139 145 148 146 149 144 145 108 156 137 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 010 010 010 011 010 011 013 009 009 014 010

-0.42

-0.44

-0.44

+0.27

-0.44

+0.17

-0.61

+0,02

-0.71

-0.13

-0.05

AREVA NP Inc Customer Name:

rNSl Rep]

4/22/2008 9:45:33 AM Component: S/G A Page 70 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: QueryMl[1]

ROW TUBE VOLTS 0.08 101 103 0.09 101 104 0.09 0.13 101 111 0.22 101 113 0.18 0.09 101 116 0.18 101 117 0.33 0.34 0.16 101 118 0.12 0.63 0.22 0.20 0.30 101 119 0.35 0.12 101 120 0.13 101 124 102 3 0.11 102 5 0.17 102 7 0.38 102 8 0.16 102 13 0.12 102 17 0.10 102 18 0.19 102 21 0.08 102 29 0.17 102 32 0.13 102 40 0.13 102 85 0.10 102 89 0.13 102 98 0.12 102 99 0.17 102 102 0.15 102 105 0.18 102 106 0.10 102 108 102 110 102 112 102 113 0.10 102 116 0.47 DEG CHN 117 P2 143 P2 143 P2 146 P2 140 P2 140 P2 147 P2 142 P2 139 P2 136 P2 144 P2 145 P2 131 P2 144 P2 139 P2 140 P2 140 P2 151 P2 134 P2 149 P2 121 P2 133 P2 146 P2 148 P2 123 P2 134 P2 151 P2 134 P2 148 P2 148 P2 119 P2 137 P2 127 P2 143 P2 129 P2 138 P2 148 P2 150 P2 136 P2 141 P2 141 P2 139 P2 129 P2 138 P2 127 P2 148 P2 142 P2 141 P2 147 P2 134 P2 135 P2 141 P2 143 P2 119 P2 147 P2 133 P2 150 P2 136 P2 137 P2 145 P2 150 P2 137 P2 137 P2 130 P2 133 P2 127 P2 135 P2 132 P2 129 P2 128 P2 141 P2 IND %TW LOCATION EXT EXT UTIL 1

TWD 5 TWD 8 TWO 6 TWD 9 TWD 16 TWD 14 TWD 7 TWD 12 TWD 22 TWD 23 TWD 12 TWO 8 TWO 30 TWD 14 TWD 13 TWO 18 TWD 23 TWO 10 TWD 9 NDD TWD 6 TWO 9 TWD 18 TWD 10 TWD 8 TWO 7 TWO 15 TWO 6 TWD 9 TWD 7 TWD 7 TWD 7 TWO 9 TWD 8 TWD 13 TWD 12 TWO 12 TWO 8 NDD NDD NDD TWD 8 TWD 25 TWD 14 TWO 13 TWD 22 TWD 29 TWD 19 TWD 7 NDD NDD TWO 8 TWD 6 TWD 17 TWD 5 TWD 16 TWO 8 TWO 6 TWO 7 TWD 6 TWD 7 TWD 6 TWD 10 TWD 10 TWD 12 TWD 8 TWD 9 NDD TWD 12 TWD 14 NDD TWD 29 TWD 27 TWD 33 TWD 17 TWO 31 TWO 31 TWD 10 TWD 10 NDD 009 014 009 010 011 014 014 011 010 011 013 011 011 012 012 013 010 012 010 010 010 010 010 011 010 009 008 011 011 011 009 008 014 009 010 010 012 009 010 011 011 010 010 011 012 010 011 014 014 014 014 014 011 012 011 010 012 012 009 010 012 011 011 010 012 013 011 010 010 011 010

+0.05

+0.02

-0.59

+0.12

-0.56

-0.57

+0.12

-0.49

-0.49

+0.24

+0.20

-0.17

+0.27

-0.44

+0.27

+0.20

-0.47

+0.29

-0.42

-0.39

-0.42

-0.44

-0.44

-0.57

-0.56

-0.56

+0.10

+0.02

+0.05

-0.02

-0.66

-0.68

-0.74

+0.12

-0.61

+0.15

+0.13

-0.52

-0.50

-0.47

+0.25

-0.49

-0.45

+0.32

-0.42

-0.44

+0.27

-0.54

+0.17

-0.59

+0.17

+0.15

-0.54

+0.10

+0.00

-0.76

-0.61

+0.12

-0.54

+0.20

-0.59

+0.15

-0.54

-0.47

-0.47

+0.20

+0.22

-0.46

-0.45

+0.25

-0.44 UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

32 106 108 108 106 106

106, 108 106 106 106 108 108 108 108 108 106 106 108 108 22 22 22 24 70 70 72 0

545 100 100 100 0

507 0

507 32 106 106 108 0

509 108 108 108 106 108 108 108 106

'108 108 108 108 108 22 4

22 70 5

70 72 4

72 70 72 72 100 32 106 106 106 108 108 108 108 5

108 108 108 108 108 6

108 106 108 108 106 108 LEG OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 102 102 102 102 102 103 103 103 103 103 103 103 103 103 103 103 103 103 103 103 103 103 103 103 117 118 120 122 123 8

10 11 12 13 20 39 92 106 107 108 110 112 114 116 117 118 119 120 0.23 0.20 0.32 0.59 0.33 0.10 0.15 0.10 0.27 0.07 0.20 0.09 0.08 0.08 0.07 0.13 0.10 0.12 0.13 0.15 0.11 0.14 0.18 0.22' 0.59 0.54 0.75 0.28 0.58 0.66 0.14 0.12

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:34 AM Component: S/G A Page 71 of 97 ONSlAR-EOC24 Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 103 122 103 124 104 4 0.31 104 6 0.12 104 7 0.09 104 8 0.16 104 10 0.14 104 12 0.27 104 15 0.06 104 19 0.13 104 76 0.12 104 92 0.12 0.08 104 95 0.09 104 101 0.29 104 104 0.14 0.15 104 106 0.12 104 107 0.14 104 110 0.09 0.11 104 112 0.14 104 114 0.20 104 115 0.14 0.50 0.29 104 116 0.90 0.28 0.19 0.07 104 117 0.63 0.34 0.10 104 118 0.28 0.07 105 4 0.35 105 7 0.12 0.08 105 8 0.14 0.16 105 26 0.15 105 29 0.18 105 30 0.15 105 32 0.13 105 57 0.10 105 84 0.12 105 97 0.10 105 98 0.21 105 104 0.07 105 105 0.19 105 106& 0.09 105 107 0.18 105 108 0.13 105 110 0.12 105 113 0.08 105 114 0.39 0.11 105 115 0.76 0.34 0.06 0.25 105 116 0.83 105 117 0.24 105 119 0.08 105 120 0.11 105 121 0.12 106 7 0.08 106 8 0.23 106 11 0.17 106 13 0.12 106 24 0.07 106 28 0.15 106 84 0.11 106 91 0.09 106 97 0.10 106 103 0.15 0.08 106 104 0.15 0.15 106 106 0.12 DEG CHN 132 P2 142 P2 155 P2 147 P2 146 P2 133 P2 152 P2 122 P2 103 P2 134 P2 124 P2 142 P2 131 P2 131 P2 142 P2 144 P2 139 P2 142 P2 150 P2 141 P2 142 P2 142 P2 132 P2 140 P2 128 P2 140 P2 136 P2 156 P2 129 P2 136 P2 153 P2 133 P2 139 P2 129 P2 140 P2 150 P2 153 P2 136 P2 144 P2 138 P2 147 P2 134 P2 93 P2 128 P2 141 P2 126 P2 132 P2 129 P2 107 P2 140 P2 140 P2 141 P2 144 P2 135 P2 155 P2 132 P2 133 P2 161 P2 131 P2 128 P2 138 P2 144 P2 140 P2 148 P2 152 P2 142 P2 143 P2 150 P2 146 P2 121 P2 113 P2 107 P2 149 P2 138 P2 142 P2 134 P2 120 P2 146 P2 IND NOD NDD TWD TWD TWD TWO TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWO TWO TWO TWD TWD TWD TWO TWO TWD TWO TWO TWO TWD TWD TWD TWD TWD TWD TWD TWO TWD TWO TWO TWD TWD TWO TWD TWD TWD TWO TWO TWD TWO TWD TWD TWD TWD TWD TWO TWD TWO TWD TWO TWO TWD TWO TWO TWO TWO TWD TWD TWD TWD TWD TWD TWO TWD TWD TWO TWO TWD TWD TWD TWD

%TW LOCATION 16 7

5 10 9

17 5

8 8

5 6

18 10 11 9

10 7

8 10 13 10 27 18 38 18 13 5

31 21 7

18 6

17 7

010 010 010 010 011 014 011 014 009 009 009 012 010 010 010 014 010 008 009 013 011 009 010 014 010 011 012 012 010 011 013 010 011 010 010 011 010 011 011 011 011 011 009 008 009 014 010 014 014 009 009 012 009 010 012 010 011 011 013 010 010 011 011 011 010 010 014 012 011 011 009 009 009 012 012 009 014 009

-0.39

-0.34

-0.42

-0.44

-0.47

-0.59

+0.17

-0.66

-0.63

-0.70

+0.00

-0.05

-0.61

-0.59

+0.17

+0.02

+0.17

+0.24

-0.54

-0.56

-0.49

-0.49

-0.47

-0.54

-0.46

+0.25

+0.25

-0.47

-0.44

+0.27

-0.51

-0.44

+0.29

-0.39

-0.44

+0.29

-0.44

+0.29

+0.10

-0.

68

+0.02

+0.02

-0.61

-0.

68

-0.61

-0.76

+0.15

+0.05

-0.66

-0.54

-0.56

-0.54

-0.51

-0.49

-0.49

-0.44

+0.25

-0.46

+0.15

-0.44

-0.44

-0.39

-0.37

-0.34

-0.42

-0.44

+0.17

-0.51

+0.07

-0.69

-0.64

-0.61

-0.61

-0.61

+0.02

-0.54

-0.66

-0.54 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL #

108 108 24 5

24 22 24 7

70 70 72' 72 0

525 32 32 32 104 104 104 3

104 104 104 104 104 104 104 104 104 104 104 104 104 104 104 104 104 104 22 24 24 22 22 72 110 110 110 128 0

507 104 104 104 104 104 104

.4 104 104 104 104 3

104 104 104 104 104 104 104 104 104 104 24 22 72 7

72 72 4

527 7

505"

.0 507 0

511 102 3

i02 104 8

104 5

104 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510 XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB

.510XB

.510XB 510XB

.510XB

.510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510UL 510UL 510UL 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:34 AM Component: S/G A Page 72 of 97 ONSlAR-EOC24

- Tube Support Wear QUERY: QueryMl1l]

ROW TUBE VOLTS 106 107 0.09 106 109 0.12 106 110 0.18 106 111 0.12 0.12 106 112 0.19 0.11 0.15 106 113 0.15 106 115 0.36 0.15 0.27 0.10 106 116 0.34 0.10 106 119 0.12 106 121 0.10 107 7 0.13 107 8 0.15 0.13 0.08 107 10 0.11 0.14 0.07 0.12 107 16 0.11 0.10 107 21 0.17 107 88 0.16 107 96 0.12 107 98 0.13 107 105 0.20 0.12 107 108 0.14 107 110 0.19 107 112 0.13 0.13 107 114 0.44 0.37 107 118 0.09 108 4 0.07 108 6 0.12 108 7 0.14 0.15 108 12 0.10 108 17 0.12 0.07 108 80 0.12 108 88 0.12 108 92 0.09 0.09 108 94 0.15 0.08 108 96 0.15 108 97 0.09 108 98 0.30 0.26 108 99 0.13 108 103 0.11 0.08 108 104 0.16 108 105 0.24 108 107 0.12 108 108 0.17 108 109 0.09 0.15 108 110 0.09 108 112 0.10 108 113 0.48 0.18 108 115 0.30 109 7 0.14 0.13 109 18 0.16 109 25 0.08 0.07 109 26 0.11 109 41 0.09 109 95 0.12 0.10 DEG CHN 125 P2 150 P2 141 P2 149 P2 144 P2 141 P2 139 P2 137 P2 141 P2 130 P2 142 P2 138 P2 142 P2 136 P2 147 P2 142 P2 132 P2 137 P2 141 P2 144 P2 136 P2 143 P2 151 P2 121 P2 152 P2 140 P2 152 P2 144 P2*

141 P2 122 P2 137 P2 141 P2 134 P2 145 P2 146 P2 138 P2 137 P2 131 P2 140 P2 137 P2 138 P2 125 P2 152 P2 145 P2 150 P2 145 P2 147 P2 133 P2 102 P2 147 P2 124 P2 138 P2 134 P2 132 P2 127 P2 137 P2 135 P2 124 P2 156 P2 142 P2 134 P2 138 P2 146 P2 148 P2 147 P2 134 P2 147 P2 149 P2 131 P2 137 P2 142 P2 131 P2 135 P2 145 P2 116 P2 108 P2 145 P2 144 P2 146 P2 147 P2 IND %TW LOCATION EXT EXT UTIL 1

TWD 8 TWD 10 TWD 12 TWD 10 TWD 10 TWD 13 TWD 8 TWD 11 TWD 11 TWD 21 TWD 10 TWD 17 TWD 8 TWD 21 TWD 7 TWD 9 TWD 7 TWD 7 TWD 10 TWD 9 TWD 6 TWD 8 TWD 10 TWD 5 TWD 9,

TWD 8 TWD 7 TWD 14 TWD 12 TWD 8 TWD 9 TWD 16 TWD 10 TWD 10 TWD 13 TWD 10 TWD 10 TWD 25 TWD 22 TWD 7 TWD 5 TWD 7 TWD 8 TWD 8 TWD 7 TWD 10 TWD 6 TWD 9 TWD 8 TWD 6 TWD 6 TWD 11 TWD 6 TWD 11 TWD 7 TWD 19 TWD 17 TWD 10 TWD 8 TWD 6 TWD 11 TWD 16 TWD 9 TWD 14 TWD 7 TWD 11 TWD 8 TWD 9 TWD 26 TWD 12 TWD 19 TWD 10 TWD 9 TWD 13 TWD 6 TWD 5 TWD 9 TWD 7 TWD 9 TWD 7 012 009 011 011 011 011 011 012 011 010 011 014 013 010 011 011 010 010 011 010 011 010 011 011 012 011 012 011 009 010 009 009 014 011 011 011 012 010 014 012 010 010 010 011 011 011 012 009 009 010 010 011 015 009 010 009 010 010 009 015 011 011 012 012 011 014 011 011 010 011 011 010 011 014 012 008 011 009 014 014

-0.56

-0.53

-0.54

-0.49

+0.22

-0.49

+0.22

+0,.22

+0.25

-0.44

+0.27

-0.51

-0.49

-0.42

+0.29

-0.37

-0.34

-0.44

+0.29

-0.44

-0.47

+0.61

-0.47

-0.25

+0.27

-0.61

-0.52

+0.12

-0.64

-0.61

-0.59

-0.51

-0.64

-0.52

-0.52

+0.22

+0.25

-0.44

-0.49

-0.37

-0.39

-0.37

-0.44

+0.32

+0.22

-0.59

+0.17

-0.63

-0.

68

+0.05

-0.74

+0.02

-0.02

-0.59

+0.12

-0.59

-0.59

-0.59

-0.54

+0.05

+0.15

-0.56

-0.54

-0.54

+0.20

+0.15

+0.22

+0.24

-0.44

+0.25

+0.32

-0.42

+0.32

+0.02

+0.02

+0.15

+0.10

+0.08

-0.73

+0.05 LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

132 132 104 132 132 104 104 104 102 102 102 102 0

102 104 104 104 104 22 70 4

70 4

70 70 70 70 70 70 70 72 6

505 102 102 132 7

132 5

104 104 104 5

104 104 104 104 24 4

24 22 22 70 72 3

72 114 0

507 32 32 102 102 102 104 102 102 104 104 104 102 104 104 132 104 104 132 132 104 104 104 70 70 72 70 70 72 0

527 102 4

102 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:35 AM Component: S/G A Page 73 of 97 ONSIAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 109 97 0.09 109 102 0.17 109 103 0.14 0.18 109 105 0.24 0.15 0.09 109 108 0.20 0.15 109 109 0.15 0.17 109 110 0.15 109 111 0.41 109 112 0.29 109 113 0.17 109 115 0.06 110 4 0.10 110 7 0.13 0.16 110 8 0.19 0.14 110 17 0.18 110 34 0.22 110 47 0.09 110 91 0.07 110 92 0.08 110 93 0.11 0.12 110 94 0.10 110 95 0.10 110 98 0.15 0.15 0.08 110 101 0.22 110 102 0.14 110 103 0.20 110 104 0.08 110 105 0.30 110 106 0.16 0.17 0.11 110 107 0.12 110 108 0.44 0.21 0.21 0.12 0.11 0.58 110 109 0.42 0.15 110 110 0.30 110 111 0.25 110 112 0.17 110 113 0.11 110 114 0.10 110 115 0.06 111 5 0.09 111 7 0.11 0.06 il1 9 0.09 il1 11 0.07 111 27 0.10 111 65 0.12 111 73 0.09 0.11 111 74 0.13 111 86 0.12 11 88 0.11 111 93 0.22 111 96 0.08 111 97 0.10 11 99 0.12 111 103 0.30 111 104 0.30 0.76 0.11 I11 106 0.34 111 107 0.23 0.24 Il1 108 0.61 DEG CHN 147 P2 144 P2 137 P2 140 P2 141 P2 147 P2 147 P2 133 P2 152 P2 140 P2 134 P2 146 P2 139 P2 132 P2 138 P2 140 P2 144 P2 150 P2 141 P2 129 P2 138 P2 141 P2 133 P2 145 P2 151 P2 149 P2 134 P2 118 P2 147 P2 140 P2 146 P2 133 P2 144 P2 138 P2 136 P2 144 P2 148 P2 139 P2 147 P2 142 P2 154 P2 154 P2 131 P2 132 P2 140 P2 152 P2 133 P2 129 P2 134 P2 150 P2 134 P2 139 P2 140 P2 140 P2 103 P2 139 P2 147 P2 149 P2 154 P2 150 P2 150 P2 147 P2 137 P2 137 P2 149 P2 136 P2 140 P2 131 P2 135 P2 146 P2 157 P2 120 P2 138 P2 138 P2 134 P2 147 P2 139 P2 143 P2 139 P2 134 P2 IND %TW TWD 7 TWD 12 TWD 12 TWD 14 TWD 16 TWD 11 TWD 7 TWD 14 TWD 11 TWD 11 TWD 12 TWD 11 TWD 26 TWD 18 TWD 14 TWD 5 TWD 5 TWD 11 TWD 13 TWD 12 TWD 10 TWO 14 TWD 12 TWD 7 TWD 5 TWD 6 TWD 8 TWD 9 TWD 8 TWD 7.

TWO 10 TWD 10 TWD 6 TWD 15 TWD 12 TWD 14 TWD 6 TWD 19 TWO 13 TWD 14 TWD 10 TWD 9 TWD 27 TWD 16 TWD 17 TWD 11 TWD 9 TWD 32 TWO 24 TWD II TWD 21 TWD 16 TWD 14 TWD 8 TWD 9 TWD 5 TWD 5 TWD 9 TWD 6 TWO 8 TWO 6 TWO 8 TWD 9 TWD 8 TWD 9 TWD 9 TWD 8 TWD 8 TWD 14 TWD 6 TWD 8 TWD 9 TWD 21 TWD 19 TWO 34 TWD 8 TWD 21 TWD 18 TWD 18 TWO 31 LOCATION 011

+0.07 010

+0.17 009

-0.54 011

-0.58 009

-0.51 011

+0.20 011

-0.54 012

+0.22 011

-0.49 009

-0.46 012

+0.22 012

+0.22 010

-0.47 010

-0.42 010

-0.43 010

-0.42 010

-0.37 010

-0.41 011

+0.32 011

+0.29 012

+0.27 011

+0.15 011

-0.68 009

+0.10 009

-0.68 011

+0.02 010

-0.64 012

-0.64 009

-0.56 011

-0.64 011

+0.12 014

-0.69 014

+0.05 014

+0.10 009

-0.54 014

-0.61 009

-0.51 011

-70.52 009

-0.52 012

-0.37 011

-0.51 011

-0.52 011

-0.46 011

+0.24 013

+0.17 012

-0.53 012

+0.22 014

-0.59 010

-0.47

-011

-0.47 010

-0.46 010

-0.44 012

+0.29 010

-0.39 010

+0.61 010

-0.37 010

-0.39 010

-0.41 011

+0.29 011

-0.49 011

+0.22 011

+0.07 008

-0.63 014

-0.12 014

-0.74 010

-0.71 008

-0.66 008

-0.63 011

-0.64 010

+0.08 009

-0.56 010

+0.17 009

-0.54 009

-0.51 011

-0.52 011

+0.20 012

-0.52 012

-0.51 010

-0.49 010

-0.47 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE GTE LTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE GTE LTE GTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE GTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL #

102 104 132 132 102 5

102 4

102 104 4

104 102 102 104 132 104 132 102 22 72 72 70 70 72 110 112 32 102 104 104 0

509 102 102 102 102 104 132 104 0

102 104 132 132 0

132 5

104 132 132 132 132 132 132 104 104 132 104 132 104 132 104 22 72 4

72 72 72 72 7

501 112 9

112 7

503 0

503 0

.503 102 0

511 0

509 102 132 104 104 104 104 132 0

132 104 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

'510XB 510XB

'510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XL 510XL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510UL 510UL 510UL 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:35 AM Component: S/G A Page 74 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 0.15 111 109 0.44 il1 110 0.61 111 111 0.17 111 113 0.15 0.09 111 114 0.13 0.14 112 4 0.12 112 6 0.11 112 7 0.09 0.09 112 9 0.08 0.10 112 11 0.25 112 12 0.09 112 18 0.16 0.15 112 27 0.16 0.08 0.11 112 62 0.11 112 76 0.16 112 87 0.08 112 88 0.07 0.08 112 90 0.08 112 92 0.15 0.08 112 93 0.14 112 95 0.14 0.09 112 96 0.08 112 99 0.13 112 103 0.07 0.12 0.11 112 104 0.09 0.50 112 106 0.19 112 108 0.49 0.20 112 109 0.34 0.11 112 113 0.15 112 114 0.17 112 117 0.72 0.17 0.15 113 5 0.20 0.10 113 6 0.09 113 7 0.14 0.07 113 16 0.16 113 21 0.07 113 24 0.08 113 29 0.07 113 33 0.11 113 36 0.11 0.11 113 80

  • 0.09 0.13 113 84 0.12 113 88 0.11 113 94 0.15 0.12 113 101 0.15 0.19 113 102 0.07 0.22 113 103 0.08 0.24 113 104 0.10 0.16 0.10 113 105 0.19 0.46 113 106 0.63 0.14 DEG 141 136 129 140 141 145 146 143 119 143 150 143 156 152 143 151 137 142 138 149 149 140 138 145 139 152 153 120 151 123 120 149 152 128 128 141 136 148 136 127 134 139 136 140 145 139 129 134 142 134 140 146 143 146 131 123 155 143 125 144 148 141 146 138 130 145 129 132 139 135 139 135 134 142 142 141 138 136 133 138 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 11 TWD 27 TWD 30 TWD 14 TWD 12 TWD 8 TWD 10 TWD 10 TWD 7 TWD 6 TWD 7 TWD 7 TWD 6 TWD 7 TWD 16 TWD 8 TWD 13 TWD 12 TWD 13 TWD 7 TWD 9 TWD 7 TWD 11 TWD 6 TWD 4 TWD 5 TWD 6 TWD 10 TWD 6 TWD 10 TWD 10 TWD 7 TWD 7 TWD 9 TWD 5 TWD 8 TWD 8 TWD 7 TWD 27 TWD 13 TWD 27 TWD 13 TWD 23 TWD 10 TWD 13 TWD 12 TWD 33 TWD 12 TWD 11 TWD 10 TWD 6 TWD 6 TWD 11 TWD 6 TWD 11 TWD 6 TWD 7 TWD 6 TWD 9 TWD 9 TWD 8 TWD 6 TWD 8 TWD 8 TWD 8 TWD 11 TWD 9 TWD 11 TWD 13 TWD 5 TWD 15 TWD 6 TWD 16 TWD 7 TWD 11 TWD 7 TWD 13 TWD 25 TWD 31 TWD 10 LOCATION 012

+0.20 010

-0.47 010

-0.44 010

-0.44 010

-0.43 011

-0.39 011

-0.37 011

+0.37 011

+0.37 011

+0.34 010

-0.39 011

+0.32 014

-0.47 014

+0.25 014

-0.54 011

+0.24 011

-0.56 011

+0.15 011

-0.64 011

+0.07 010

+0.10 009

-0.68 009

-0.71 009

-0.61 010

-0.03 012

-0.05 010

-0.66 010

-0.61 010

+0.10 011

-0.64 010

-0.61 010

+0.15 009

-0.56 010

+0.17 006

-0.44 009

-0.49 014

+0.10 008

+0.22 009

-0.54 011

+0.25 010

-0.47 011

-0.47 010

-0.47 011

+0.27 012

+0.29 012

-0.39 011

-0.32 012

-0.37 013

+0.29 010

-0.37 011

+0.34 011

+0.34 010

-0.39 011

+0.32 011

-0.56 011

+0.12 011

+0.12 011

+0.02 014

-0.69 014

-0.71 014

-0.02 014

-0.10 010

-0.75 010

-0.70 014

-0.05 014

+0.05 012

-0.66 009

-0.54 011

+0.17 008

+0.27 009

-0.51 008

+0.22 009

-0.49 008

+0.25 010

-0.52 014

+0.15 009

-0.49 011

-0.49 010

-0.49 011

+0.25 EXT EXT LTE UTE LIE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE. UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL I

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

0 104 132 104 132 132 132 104 104 22 5

22 70 70 0

70 4

70 70 72 72 72 72 72 6

72 32 0

503 0

501 32 3

32 96 102 3

102 104 102 4

102 0

509 102 102 102 102 104 104 104 104 104 132 132 132 104 104 104 104 22 4

22 70 72 72 70 72 72 78 120

.120 4

120 32

.32 32 96 102 5

102 102 102 104 104 102 102 104 104 104 102 102 104 104 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE S10XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXB

AREVA NP Inc CUstomer Name:

rNSl Rep]

4/22/2008 9:45:36 AM Component:

S/G A Page 75 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 0.08 0.10 113 107 0.61 0.11 113 108 0.36 113 109 0.24 113 110 0.11 113 113 0.16 114 5.

0.13 0.14 114 6 0.11 114 13 0.17 114 23 0.14 114 28 0.13 114 33 0.11 114 72 0.12 114 78 0.09 114 83 0.10 114 84 0.09 114 86 0.10 114 89 0.10 114 92 0.12 0.14 114 93 0.29 114 94 0.16 114 97 0.15 114 99 0.22 114 100 0.19 114 101 0.07 0.27 0.37 0.09 114 102 0.34 0.24 0.14 114 103 0.25 114 104 0.13 0.18 114 105 0.20 114 106 0.82 0.14 114 107 0.36 0.12 115 4 0.22 115 7 0.08 115 8 0.11 115 22 0.06 115 27

.0.11 115 29 0.07 115 31 0.05 115 46 0.10 115 73 0.11 115 74 0.09 115 77 0.27 0.09 115 90 0.11 115 91 0.20 115 92 0.18 115 93 0.10 115 94 0.12 115 99 0.09 115 100 0.12 0.10 0.11 115 101 0.10 0.08 115 102 0.15 0.15 0.45 0.14 115 103 0.23 115 104 0.26 0.35 0.13 115 105 0.40 115 106 0.26 115 107 0.11 115 110 0.09 115 113 0.16 116 3 0.24 DEG CHN 154 P2 146 P2 124 P2 151 P2 135 P2 141 P2 143 P2 136 P2 140 P2 146 P2 142 P2 140 P2 124 P2 148 P2 136 P2 131 P2 132 P2 136 P2 137 P2 146 P2 140 P2 138 P2 143 P2 127 P2 122 P2 138 P2 150 P2 150 P2 154 P2 144 P2 137 P2 152 P2 137 P2 137 P2 141 P2 139 P2 145 P2 148 P2 147 P2 130 P2 146 P2 131 P2 125 P2 130 P2 140 P2 147 P2 141 P2 150 P2 146 P2 139 P2 147 P2 136 P2 136 P2 139 P2 148 P2 124 P2 137 P2 131 P2 157 P2 114 P2 142 P2 149 P2 149 P2 128 P2 149 P2 136 P2 141 P2 150 P2 137 P2 152 P2 137 P2 141 P2 138 P2 139 P2 139 P2 142 P2 147 P2 147 P2 133 P2 124 P2 IND %TW TWD 6 TWD 7 TWD 30 TWD 8 TWD 22 TWD 18 TWD 8 TWD 11 TWD 7 TWD 8 TWD 9 TWD 11 TWO 12 TWD 10 TWD 9 TWD 8 TWD 7 TWD 7 TWD 8 TWD 8 TWD 7 TWD 9 TWD 10 TWD 18 TWD 11 TWD 11 TWO 14 TWD 13 TWD 5 TWD 17 TWD 22 TWD 7 TWO 21 TWD 16 TWD 10 TWD 16 TWO 9 TWD 13 TWD 14 TWD 36 TWD 10 TWD 24 TWD 10 TWD 11 TWD 6 TWD 9 TWD 5 TWD 9 TWD 6 TWO 5 TWO 8 TWD 7 TWO 7 TWO 16 TWD 6 TWD 8 TWD 13 TWD 12 TWD 8 TWD 8 TWD 7 TWD 9 TWD 8 TWD 8 TWD 7 TWD 6 TWD 11 TWD 11

'TWD 25 TWD 10 TWD 15 TWD 17 TWD 21 TWD 9 TWD 26 TWO 17 TWD 10 TWD 7 TWD 11 TWD 13 LOCATION 012

-0.49 011

-0.49 010

-0.49 011

-0.44 010

-0.44 010

-0.46 010

-0.42 011

-0.37 010

-0.37 011

+0.37 011

+0.32 011

+0.22 014

-0.66 011

+0.10 011

-0.63 010

-0.76 008

-0.63 010

-0.69 010

-0.76 011

+0..02 010

-0.63 012

-0.61 012

+0.02 014

-0.69 014

-0.68 010

+0.17 011

-0.54 010

+0.54 008

+0.27 011

-0.51 011

+0.17 009

-0.49 009

-0.51 011

+0.20 014

-0.59 009

-0.46 012

+0.22 010

-0.51 011

-0.46 010

-0.49 011

+0.25 010

-0.43 012

+0.22 010

-0.34 011

+0.34 011

+0.29 012

+0.15 011

+0.10 014

-0.02 012

+0.07 009

+0.07 010

-0.69 010

-0.79 009

-0.73 010

-0.05 010

-0.63 010

-0.59 012

-0.62 012

+0.08 014

-0.66 009

-0.51 011

-0.52 012

-0.54 014

-0.61 009

+0.54 009

-0.51 009

-0.49 009

+0.56 012

-0.49 010

-0.49 014

<0.59 010

-0.49 012

-0.49 014

-0.54 010

-0.48 010

-0.44 010

-0.46 011

-0.37 011

-0.34 010

-0.34 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL #

104 4

104 102 4

102 104 132 104 102 22 22 72 70 72 78 6

120 32 0

501 0

503 0

501 96 96 102 102 104 102 102 102 104 102 102 102 0

102 104 6

104 3

104 102 104 3

104 102 104 4

104 132 132 22 70 72 72 78 78 78 112 3

503 4

501 32 4

32 4

509 102 104 4

509 102 5

102 4

104 4

104 5

104 5

102 0

102 104 104 104 4

104 102 0

104 104 104 132 104 132 104 102 24 LEG PROBE INLET 51OXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB INLET 51OUL INLET 51OUL INLET 51OUL INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL INLET 51OUL OUTLET 510XB OUTLET 51XO INLET 51OUL INLET 510xB INLET 510XB INLET 51OUL INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA N1P Inc Customer Name: ONSI Repl 4/22/2008 9:45:36 AM Component: S/G A Page 76 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 116 4 0.11 116 5 0.07 116 6 0.10 116 7 0.15 116 14 0.36 0.11 116 22 0.10 116 23 0.07 116 27 0.11 116 28 0.09 116 64 0.11 116 67 0.09 116 74 0.10 116 86 0.17 116 90 0.12 116 91 0.20 0.11 116 93 0.07 116 100 0.10 0.11 0.11 116 101 0.12 0.15 0.15 0.41 116 102 0.77 0.17 116 103 0.28 116 104 0.42 0.08 116 105 0.27 0.12 0.10 117 1 0.08 117 4 0.08 117 5 0.15 117 6 0.12 117 19 0.10 0.07 117 23 0.17 117 26 0.08 117 33 0.09 117 38 0.10 117 41 0.09 117 59 0.11 117 63 0.15 0.08 117 69 0.09 0.06 117 71 0.08 117 72 0.16 0.09 117 75 0.09 117 78 0.08 117 80 0.05 117 85 0.09 117 88 0.15 117 95 0.12 0.30 117 96 0.08 0.25 0.12 117 98 0.10 0.26 0.09 117 99 0.08 117 100 0.14 0.10 0.17 117 101 0.42 0.13 117 103 0.17 117 104 0.08 117 105 0.10 118 1 0.18 0.14 118 2 0.13 0.09 118 5 0.07 118 6 0.08 DEG CHN 125 P2 144 P2 150 P2 133 P2 136 P2 147 P2 142 P2 149 P2 148 P2 152 P2 121 P2 145 P2 132 P2 108 P2 144 P2 132 P2 152 P2 119 P2 150 P2 141 P2 132 P2 136 P2 138 P2 148 P2 131 P2 132 P2 139 P2 140 P2 136 P2 140 P2 140 P2 156 P2 142 P2 144 P2 149 P2 142 P2 140 P2 117 P2 150 P2 120 P2 144 P2 133 P2 143 P2 147 P2 141 P2 137 P2 139 P2 128 P2 129 P2 148 P2 133 P2 140 P2 129 P2 134 P2 87 P2 143 P2 133 P2 141 P2 138 P2 152 P2 146 P2 144 P2 139 P2 141 P2 148 P2 159 P2 143 P2 145 P2 133 P2 137 P2 140 P2 132 P2 159 P2 150 P2 89 P2 130 P2 151 P2 57 P2 139 P2 139 P2 IND %TW TWD 6 TWD 5 TWD 7 TWD 11 TWD 21 TWD 8 TWD 8 TWD 7 TWD 8 TWD 7 TWD 8 TWD 6 TWD 7 TWD 11 TWD 8 TWO 13 TWD 8 TWD 6 TWD 8 TWD 8 TWD 8 TWO 8 TWD 10 TWD 11 TWD 23 TWD 35 TWO 12 TWD 18 TWD 24 TWD 6 TWD 17 TWD 9 TWD 7 TWO 5 TWO 7 TWD 10 TWD 9 TWD 7 TWD 5 TWD 12 TWD 7 TWD 7 TWD 8 TWO 8 TWD 7 TWO 10 TWD 5 TWD 6 TWD 4 TWD 5 TWD 10 TWD 6 TWD 6 TWO 5 TWD 4 TWD 7 TWO 11 TWD 9 TWD 19 TWD 6 TWD 16 TWD 9 TWD 8 TWD 16 TWD 7 TWD 6 TWD 10 TWD 7 TWD 12 TWD 24 TWD 10 TWD 12 TWD 6 TWD 7 TWD 10 TWD 8 TWO 7 TWD 5 TWD 6 TWD 5 LOCATION 010

-0.34 011

+0.34 011

+0.34 011

+0.32 011

+0.22 012

-0.42 011

-0.61 011

+0.10 011

+0.10 011

+0.10 009

-0.61 008

-0.63 009

-0.61 014

-0.73 010

+0.12 010

-0.59 010

+0.10 012

+0.10 009

-0.51 014

-0.61 008

+0.24 008

+0.24 009

-0.46 011

-0.49 011

+0,.22 010

-0.51 012

+0.22 010

-0.49 010

-0.47 013

+0.12 010

-0.47 012

-0.47 013

+0.22 011

+0.42 011

+0.34 011

+0.32 011

+0.32 010

+0.17 011

+0.15 014

-0.66 011

+0.10 011

+0.02 011

+0.02 009

+0.10 009

-0.61 009

-0.65 009

+0.05 010

-0.68 010

-0.03 010

-0.05 011

-0.74 010

-0.05 010

-0.73 010

+0.05 010

+0.02 011

+0.02 011

-0.61 009

-0.51 010

-0.54 009

-0.51 010

+0.51 012

+0.15 009

-0.51 011

+0.22 008

.+0.24 009

-0.54 009

-0.51 012

-0.54 010

-0.51 010

-0.49 011

+0.27 010

-0.46 010

-0.44 010

-0.44 011

-0.29 011

+0.39 011

+0.34 010

-0.34 011

+0.34 011

+0.32 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTIE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR

WAR, WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL # LEG 22 INLET 74 INLET 76 INLET 74 INLET 76 INLET 76 INLET 0

543 INLET 72 INLET 80 INLET 78 INLET 1

503 INLET 32 OUTLET 4

503 INLET 96 INLET 102 INLET 104 INLET 104 INLET 0

511 INLET 104 INLET 6

104 INLET 0

104 INLET 102 INLET 102 INLET 102 INLET 102 INLET 104 INLET 104 INLET 102 INLET 104 INLET 104 INLET 104 INLET 104 INLET 0

104 INLET 24 INLET 74 INLET 76 INLET 74 INLET 76 INLET 76 INLET 74 INLET 78 INLET 120 INLET 112 INLET 112 INLET 0

503 INLET 32 OUTLET 4

32 OUTLET 32 OUTLET 32 OUTLET 32 OUTLET 32 OUTLET 32 OUTLET 32 OUTLET 32 OUTLET 96 INLET 96 INLET 102 INLET 104 INLET 104 INLET 102 INLET 102 INLET 102 INLET 102 INLET 102 INLET 7

102 INLET 104 INLET 102 INLET 102 INLET 0

102 INLET 104 INLET 104 INLET 102 INLET 104 INLET 102 INLET 24 INLET 24 INLET 22 INLET 5

22 INLET 74 INLET 76 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 51OUL 510XB 51OUL 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XBE.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Reol 4/22/2008 9:45:37 AM Component: S/G A Page 77 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l1 Support Wear ROW TUBE VOLTS 118 21 0.10 118 28 0.08 118 31 0.07 118 46 0.10 118 55 0.10 118 68 0.09 118 71 0.19 118 81 0.09 0.11 118 82 0.13 118 85 0.13 0.24 0.16 0.09 0.09 118 88 0.12 118 89 0.10 0.14 118 90 0.16 118 91 0.14 0.13 118 93 0.06 0.12 118 94 0.16 118 95 0.09 0.22 0.08 118 97 0.09 0.30 118 98 0.16 0.13 118 99 0.14 0.13 0.25 0.21 1.04 118 100 0.78 0.13 0.09 118 101 0.57 118 102 0.31 0.17 118 104 0.18 118 105 0.13 118 109 0.12 119 2 0.12 0.15 119 3 0.10 119 9 0.28 0.09 119 11 0.08 0.11 119 15 0.08 119 20 0.06 119 22 0.07 119 23 0.06 119 29 0.08 119 45 0.09 119 61 0.11 119 62 0.13 119 78 0.13 119 79 0.20 119 84 0.10 119 86 0.16 0.06 119 89 0.16 0.28 119 91 0.23 119 92 0.09 119 93 0.13 119 94 0.09 119 96 0.07 119 98 0.18 0.10 119 99 1.25 119 101 0.13 0.08 119 102 0.25 0.10 119 103 0.17 DEG CHN 141 P2 134 P2 152 P2 149 P2 115 P2 137 P2 135 P2 123 P2 134 P2 122 P2 126 P2 142 P2 143 P2 142 P2 128 P2 135 P2 140 P2 142 P2 138 P2 137 P2 141 P2 151 P2 130 P2 154 P2 139 P2 139 P2 136 P2 135 P2 140 P2 141 P2 141 P2 156 P2 151 P2 139 P2 134 P2 127 P2 130 P2 144 P2 152 P2 131 P2 128 P2 138 P2 130 P2 145 P2 139 P2 117 P2 144 P2 132 P2 139 P2 143 P2 142 P2 143 P2 151 P2 155 P2 154 P2 157 P2 134 P2 130 P2 111 P2 130 P2 149 P2 137 P2 144 P2 140 P2 139 P2 135 P2 131 P2 126 P2 144 P2 144 P2 150 P2 143 P2 147 P2 151 P2 124 P2 144 P2 151 P2 136 P2 145 P2 134 P2 IND %TW TWO 8 TWO 7 TWD 6 TWD 8 TWD 8 TWD 7 TWD 11 TWD 6 TWD 8 TWO 10 TWO 9 TWD 16 TWD 11 TWD 7 TWD 7 TWD 9 TWD 8 TWD 10 TWD 11 TWD 10 TWD 9 TWD 5 TWD 9 TWD 11 TWD 7 TWD 15 TWD 6 TWO 7 TWD 19 TWD 11 TWD 10 TWD 10 TWD 10 TWD 16 TWO 14 TWO 40 TWD 34 TWD 9 TWD 7 TWD 29 TWD 19 TWD 12 TWD 13 TWD 9 TWD 9 TWD 8 TWD 10 TWD 8 TWD 18 TWD 7 TWD 6 TWO 9 TWD 6 TWD 5 TWD 5 TWD 5 TWD 6 TWD 8 TWO 7 TWD 9 TWD 9 TWD 13 TWD 8 TWD 11 INR TWD13 TWD 20 TWD 15 TWD 8 TWD 10 TWD 8 TWD 5 TWD 12 TWD 8 TWO 44 TWD 9 TWD 6 TWD 16 TWD 8 TWD 12 LOCATION 011

+0.15 011

+0.07 011

+0.07 010

+0.05 010

-0.61 008

-0.66 009

-0.65 014

+0.02 014

.- 06.71 010

-0.66 012

-0.61 014

+0.02 015

+0.05 011

+0.12 012

+0.02 010

-0.59 010

-0.54 010

+0.17 010

-0.56 010

+0.17 012

+0.15 009

-0.54 011

-0.59 010

+0.51 009

-0.54 011

+0.17 012

-0.54 009

-0.54 011

-0.49 010

-0.51 011

+0.24 011

-0.47 012

-0.49 012

+0.22 011

+0.27 010

-0.49 010

-0.49 011

-0.44 014

-0.56 010

-0.47 010

-0.44 011

+0.27 010

-0.42 010

-0.42 011

+0.34 010

-0.34 011

+0.39 011

+0.34 011

+0.29 012

-0.42 012

+0.25 011

-0.46 011

+0.20 011

+0.15 011

+0.12 011

+0.15 011

+0.10 008

-0.59 010

-0.73 009

-0.61

012,

-0.74 010

-0.63 012

-0.63 010

-0.59 010

+0.11 012

-0.61 014

-0.66 014

-0.64 011

+0.17 012

-0.54 009

-0.60 009

-0.49 011

-0.49 012

+0.22 010

-0.49 010

-0.41 012

+0.22 010

-0.44 014

-0.49 010

-0.42 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

74 78 78 112 0

531 3

503 32 96 5

96 0

509 94 94 94 4

94 2

94 102 104 104 102 104 104 104 6

104 102 104 104 104 104 104 102 102 104 104 104 7

104 LAR 104 102 102 102 104 102 102 102 104 104 76 76 74 74 4

74 74 5

74 74 74 76 74 78 112 32 0

503 4

511 96 0

509 102 102 132 132 104 132 104 132 102 102 4

102 LAR 104 102 102 104 104 102 LEG INLET INLET INLET INLET INLET INLET OUTLET

'INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB j51OXB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:45:37 AM Component: S/G A Page 78 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl(l]

ROW TUBE VOLTS 119 104 0.07

'119 108 0.14 120 2 0.14 120 6 0.17 120 10 0.11 0.17 0.11 120 13 0.10 120 20 0.06 120 21 0.15 0.12 120 22 0.09 120 25 0.05 120 33 0.09 120 41 0.15 120 42 0.11 120 52 0.10 120 58 0.09 0.09 120 59 0.15 120 60 0.09 120 74 0.09 120 79 0.05 120 80 0.19 120 8?

0.07 120 88 0.15 120 90 0.08 120 92 0.11 120 94 0.13 0.10 0.13 120 96 0.08 120 97 0.10 120 98 0.42 0.45 0.15 120 99 0.65 0.08 120 100 0.21 0.11 0.11 120 101 0.11 0.12 0.09 120 102 0.10 120 103 0.12 121 6 0.08 0.21 121 12 0.05 121 15 0.12 121 22 0.10 121 33 0.09 121 63 0.13 121 67 0.13 0.06 121 79 0.13 121 84 0.17 0.17 121 85 0.15 121 87 0.15 0.12 0.12 121 90 0.08 0.17 121 92 0.14 0.12 121 93 0.10 121 94 0.15 0.08 121 96 0.15 121 97 0.14 121 98 0.76 0.24 0.24 0.09 0.11 121 99 0.31 121 100 0.20 0.14 121 101 0.16 DEG CHN 147 P2 148 P2 141 P2 148 P2 139 P2 144 P2 146 P2 137 P2 155 P2 118 P2 132 P2 148 P2 153 P2 131 P2 145 P2 148 P2 122 P2 136 P2 148 P2 116 P2 107 P2 99 P2 149 P2 126 P2 130 P2 142 P2 156 P2 152 P2 139 P2 153 P2 139 P2 153 P2 144 P2 135 P2 138 P2 151 P2 127 P2 157 P2 140 P2 149 P2 151 P2 127 P2 148 P2 131 P2 149 P2 143 P2 135 P2 145 P2 143 P2 146 P2 144 P2 147 P2 129 P2 128 P2 146 P2 147 P2 138 P2 143 P2 141 P2 152 P2 118 P2 148 P2 155 P2 147 P2 146 P2 145 P2 150 P2 142 P2 161 P2 150 P2 148 P2 127 P2 142 P2 145 P2 143 P2 142 P2 134 P2 139 P2 141 P2 130 P2 IND %TW LOCATION TWD 5 011

-0.42 TWD 10 013

+0.29 TWD 10 011

+0.39 TWD 12

'011

+0.32 TWD 8 011

+0,27 TWD 12 012

+0.27 TWD 8 011

-0.42 TWD 7 012

-0.44 TWD 5 011

+0.12 TWD 10 014

-0.64 TWO 8 014

+0.07 TWO 7 011

+0.12 TWO 4 011

+0.12 TWD 7 012

+0.02 TWD 12 009

+0.12 TWD 9 009

+0.12 TWD 8 011

-0.69 TWD 6 012

-0.78 TWD 6 010

-0.05 TWO 10 009

-0.58 TWD 7 010

-0.66 TWD 7 011

-0.66 TWD 4 010

+0.07 TWD 13 012

-0.66 TWD 6 010

+0.17 TWD 11 010

+0.17 TWD 6 009

-0.54 TWD 8 009

-0.54 TWD 10 009

-0.51 TWD 8 010

-0.51 TWD 10 012

-0.54 TWD 6 012

-0.52 TWD 8 011

-0.49 TWD 24 010

-0.47 TWD 25 014

-0.52 TWD 11 011

+0.27 TWD 31 010

-0.46 TWD 6 011

+0.27 TWD 14 010

-0.42 TWD 8 012

-0.47 TWD 8 014

-0.49 TWD 8 010

-0.44 TWD 9 012

+0.27 TWD 7 011

+0.27 TWD 7 014

-0.47 TWD 9 011

-0.39 TWD 6 010

+0.20 TWO 15 011

+0.34 TWD 4 011

+0.22 TWD 8 011

+0.20 TWD 8 014

+0.02 TWD 7 009

+0.10 TWD 9 010

-0.69 TWD 8 010

-0.70 TWD 4 010

+0.03 TWD 9 010

+0.15 TWD 12 012

-0.61 TWD 12 013

-0.64 TWD 10 014

+0.07 TWD 10 009

-0.54 TWD 9 012

-0.61 TWD 9 012

+0.12 TWD 6 009

-0.51 TWD 12 011

+0.15 TWD 10 009

-0.54 TWD 9 011

+0.22 TWD 7 011

-0.51 TWD 11 011

-0.47 TWD 6 009

-0.49 TWD 11 011

-0.47 TWD 10 012

+0.22 TWD 34 010

-0.45 TWD 15 011

-0.44 TWD 15.014

-0.52 TWD 7 011

+0.27 TWD 8 014

+0.22 TWD 19 010

-0.45 TWO 14 010

-0.42 TWO 10 014

+0.25 TWD 11 010

-0.41 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

104 104 74 74 74 74 8

74 5

76 74 7

76 5

76 74 76 78 112 112 112 32 32 0

503 6

501 0

515 96 94 3

102 104 104 104 104 104 104 104 102 104 104 5

104 102 6

102 104 104 104 102 102 4

102 104 102 74 74 74 76 74 0

517 0

503 32 32 94 94 94 102 102 102 102 104 104 104 104 0

102 104 104 94 96 94 94 94 2

94 3

94 96 94 94 96 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OL 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XE

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:38 AM Component: S/G A Page 79 of 97 ONSIAR-EOC24

- Tube Support Wear QUERY: QueryMl(l]

ROW TUBE VOLTS 0.21 121 102 0.10 0.12 122 10 0.06 122 12 0.09 0.08 122 22 0.07 122 74 0.17 122 78 0.19 0.15 122 85 0.08 122 86 0.06 122 92 0.15 0.16 122 93 0.30 0.28 0.15 0.32 122 94 0.23 0.08 122 95 0.11, 122 96 0.14 0.13 122 97 0.49 0.09 122 98 0.31 122 99 0.22 0.12 122 100 0.23 0.07 0.08 122 101 0.12 123 5 0.16 123 8 0.29 123 9 0.23 123 10 0.11 123 11 0.08 123 20 0.05 123 30 0.10 123 55 0.11 123 66 0.09 123 68 0.14 123 71 0.09 123 75 0.07 123 81 0.13 123 84 0.17 0.09 123 86 0.06 123 88 0.08 123 90 0.36 123 91 0.07 123 92 0.07 0.13 0.06 123 93 0.16 123 94 0.12 0.23 0.35 123 95 0.21 0.14 0.08 123 96 0.23 0.12 123 97' 0.47 0.21 123 98

ý0.39 0.15 0.15 123 99 0.26 0.13 0.27 123 101 0.07 124 10 0.14 124 11 0.12 124 18 0.10 0.18 0.09 124 63 0.21 0.12 124 72 0.09 DEG CHN 138 P2 133 P2 144 P2 141 P2 144 P2 138 P2 146 P2 132 P2 138 P2 140 P2 148 P2 148 P2 146 P2 142 P2 140 P2 140 P2 140 P2 140 P2 141 P2 154 P2 153 P2 147 P2 139 P2 129 P2 143 P2 141 P2 130 P2 147 P2 138 P2 152 P2 144 P2 128 P2 143 P2 138 P2 141 P2 144 P2 145 P2 153 P2 56 P2 137 P2 134 P2 138 P2 122 P2 120 P2 137 P2 14.7 P2 144 P2 155 P2 155 P2 134 P2 149 P2 159 P2 141 P2 155 P2 156 P2 148 P2 142 P2 138 P2 146 P2 148 P2 152 P2 137 P2 137 P2 130 P2 144 P2 138 P2 139 P2 145 P2 134 P2 132 P2 137 P2 150 P2 149 P2 153 P2 121 P2 136 P2 152 P2 141 P2 140 P2 136 P2 IND %TW TWO 14 TWD 8 TWD 8 TWD 5 TWD 8 TWD 6 TWD 6 TWD 12 TWD 13 TWD 10 TWD 6 TWD 5 TWD 11 TWD 11 TWD 18 TWD 17 TWD 10 TWD 19 TWD 15 TWD 6 TWD 8 TWO 10 TWD 9 TWD 26 TWD 7 TWD 19 TWO 14 TWD 9 TWD 15 TWD 5 TWD 6 TWD 8 TWD 11 TWD 19 TWD 15 TWD 8 TWD 5 TWD 4 TWD 8.

TWO 9 TWD 7 TWO 10 TWO 7 TWD 5 TWD 9 TWD 11 TWD 7 TWD 4 TWD 6 TWD 21 TWD 5 TWD 5 TWD 9 TWD 4 TWD 11 TWD 9 TWD 15 TWD 21 TWD 14 TWO 10 TWD 6 TWD 15 TWD 9 TWD 25 TWO 14 TWO 22 TWD 11 TWD 10 TWD 16 TWD 9 TWD 17 TWD 5 TWD 11 TWD 8 TWD 8 TWO 13 TWD 7 TWD 12 TWD 8 TWD 6 LOCATION 014

-0.46 010

-0.42 011

+0.32 012

+0.24 012

+0.24 011

+0.27 012

+0.17 010

-0.63 010

-0.63 014

+0.02 010

-0.59 007

-0.49 009

-0.51 011

+0.22 009

-0.46 011

+0.24 012

-0.51 014

-0.56 011

+0.25 009

-0.50 011

-0.49 010

-0.47 011

+0.25 010

-0.45 011

+0.27 010

-0.47 010

-0.42 014

-0.46 010

-0.42 011

+0.29 012

-0.42 010

-0.39 011

+0.34 011

+0.32 011

+0.29 012

+0.24 012

+0.27 012

+0.22 014

-0.71 009

-0.59 009

-0.59 011

-0.63 012

-0.63 010

+0.12 010

-0.56 012

-0.59 012

+0.02 010

-0.56 012

-0.57 014

-0.59 009

-0.49 009

-0.52 014

-0.54 010

-0.49 011

-0.46 009

-0.47 011

+0.27 014

-0.54 009

-0.46 011

-0.46 012

-0.46 010

-0.45 011

+0.29 010

-0.45 014

-0.51 010

-0.42 013

-0.44 012

+0.29 010

-0.42 011

+0.27 012

+0.29 011

+0.34 014

-0.49 011

+0.25 012

+0.20 014

-0.59 014

+0.10

.014

-0.08 012

-0.05 014

-0.68 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UT&

LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL # LEG 96 INLET 94 INLET 4

94 INLET 74 INLET 74 INLET 4

74 INLET 74 INLET 96 INLET 96 INLET 96 INLET 96 INLET 94 INLET 94 INLET 94 INLET 96 INLET 96 INLET 96 INLET 96 INLET 94 INLET 2

94 INLET 96 INLET 94 INLET 4

94 INLET 96 INLET 96 INLET 94 INLET 96 INLET 96 INLET 94 INLET 3

94 INLET 2

94 INLET 96 INLET 76 INLET 74 INLET 76 INLET 74 INLET 76 INLET 74 INLET 4

517 INLET.

112 INLET 3

501 INLET 92 INLET 96 INLET 96 INLET 96 INLET 96 INLET 4

96 INLET 94 INLET 94 INLET 94 INLET 96 INLET 94 INLET 94 INLET 94 INLET 96 INLET 94 INLET 94 INLET 94 INLET 96 INLET 96 INLET 96 INLET 94 INLET 3

94 INLET 96 INLET 96 INLET 94 INLET 94 INLET 2

94 INLET 96 INLET 96 INLET 96 INLET 96 INLET 74 INLET 76 INLET 74 INLET 74 INLET 74 INLET 32 OUTLET 6

32 OUTLET 96 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:39 AM Component:

S/G A Page 80 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[-l]

ROW TUBE VOLTS 124 75 0.14 124 84 0.09 124 85 0.17 124 88 0.07 0.15 124 89 0.07 0.06 0.11 0.11 124 90 0.14 124 91 0.10 124 92 0.19 0.10 124 93 0.10 124 94 0.21 0.14 124 95 0.30 0.12 124 96 0.46 0.16 124 97 0.32 124 98 0.38 125 21 0.15 125 46 0.15 125 48 0.10 125 57 0.06 125 75 0.24 125 76 0.21 125 84 0.23 125 85 0.25 125 87 0.09 125 88 0.20 0.28 0.15 125 89 0.10 125 90 0.13 125 91 0.21 0.12 0.23 0.08 125 92 0.15 0.11 125 93 0.15 0.16 125 94 0.08 125 95 0.22 125 96 0.54 0.59 125 97 0.28 125 98 0.10 125 99 0.12 0.10 125 100 0.35 126 9 0.11 126 15 0.07 126 36 0.12 0.05 126 38 0.09 126 47 0.10 126 53 0.13 126 58 0.08 0.08 126 67 0.14 126 71 0.27 0.08 126 73 0.11 126 74 0.13 126 80 0.17 126 83 0.12 126 85 0.06 0.15 126 87 0.22 0.22 0.27 126 88 0.15 126 89 0.12 126 90 0.10 126 92 0.27 126 93 0.12 126 94 0.48 DEG CHN 144 P2 146 P2 142 P2 154 P2 144 P2 146 P2 153 P2 125 P2 135 P2 149 P2 155 P2 136 P2 149 P2 152 P2 138 P2 148 P2 134 P2 140 P2 132 P2 134 P2 133 P2 131 P2 129 P2 136 P2 141 P2 153 P2 143 P2 146 P2 148 P2 138 P2 149 P2 138 P2 145 P2 143 P2 148 P2 150 P2 143 P2 148 P2 143 P2 150 P2 150 P2 147 P2 144 P2 148 P2 145 P2 117 P2 130 P2 135 P2 137 P2 141 P2 125 P2 143 P2 141 P2 143 P2 157 P2 124 P2 148 P2 146 P2 0

P2 101 P2 133 P2 128 P2 118 P2 132 P2 152 P2 129 P2 143 P2 140 P2 138 P2 155 P2 142 P2 143 P2 145 P2 144 P2 142 P2 150 P2 150 P2 136 P2 131 P2 129 P2 IND %TW TWD 10 TWD 7 TWD 12 TWD 6 TWD 11 TWD 5 TWD 5 TWD 8 TWD 8 TWD 10 TWD 7 TWD 13 TWD 8 TWD 7 TWD 14 TWD 10 TWD 18 TWD 8 TWD 25 TWD 11 TWD 19 TWO 22 TWD 11 TWD 9 TWD 8 TWD 4 TWD 15 TWD 14 TWD 15 TWD 16 TWD 6 TWD 14 TWD 18 TWD 10 TWD 7 TWD 9 TWD 14 TWD 9 TWD 15 TWD 6 TWD 11 TWD 8 TWD 10 TWD 11 TWD 6 TWD 14 TWD 28 TWD 29 TWD 17 TWD 7 TWD 9 TWD 7 TWD 21 TWD 9 TWD 6 TWD 10 TWD 5 TWD 7 TWD 8 TWD 9 TWD 6 TWD 6 TWD 10 TWD 17 TWD 6 TWD 8 TWD 9 TWD 12 TWD 9 TWD 5 TWD 11 TWD 15 TWD 15 TWD 17 TWD 10 TWD 9 TWD 7 TWD 17 TWD 9 TWD 25 LOCATION 015

-0.73 009

-0.54 011

+0.17 010

-0.51 014

+0.15 009

-0.46 011

+0.27 012

-0.51 012

+0.20 011

+0.25 011

-0.44 011

+0.29 011

-0.44 009

-0.49 010

-0.45 011

+0.29 010

-0.45 011

+0.32 010

-0.42 011

+0.32 010

-0.39 010

-0.42 014

-0.59 009

-0.58 009

-0.56 009

+0.13 010

-0.58 014

+0.05 010

-0.54 010

-0.54 010

-0.51 009

-0.52 012

-0.52 011

+0.22 011

+0.22 012

-0.49 010

-0.47 011

+0.27 012

-0.49 009

-0.49 009

-0.47 012

-0.47 010

-0.45 012

-0.46 010

-0.47 010

-0.42 010

-0.40 012

+0.29 010

-0.42 011

-0.37 011

-0.37 011

+0,37 011

+0.37 011

+0.29 011

+0.22 011

-0.64 011

+0.10 014

+0.05 009

-0.58 009

-0.63 008

-0.56 009

-0.61 014

-0.66 009

-0.58 011

+0.10 009

-0.53 010

-0.58 010

-0.56 012

+0.17 009

-0'.51 010

-0.51 010

-0.49 011

-0.49 011

+0.22 011

+0.27 009

-0.50 011

+0.24 010

-0.45 013

+0.22 010

-0.42 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE OTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR 8

WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR WAR 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR 0

WAR 0

WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 2

WAR CAL #

96 94 96 94 94 96 96 96 96 94 96 94 94 96 94 94 96 96 94 94 96 94 78 533 112 32 96 94 94 96 96 94 94 94 96 94 96 96 96 96 94 94 96 96 94 96 94 94 96 94 96 96 94 74 74 78 78 517 517 515 92 92 92 96 96 96 96 94 94 94 94 94 94 94 96 94 96 96 94 96 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510UL 510UL 510XB 510XB 510XB 510XB 510xB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB SlOWS

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:39 AM Component:

S/G A Page 81 of 97 ONS1AR-EOC24 -

Tube QUERY: QueryMljl]

Support Wear ROW TUBE VOLTS 126 95 0.54 0.19 126 96 0.39 0.06 126 97 0.12 126 98 0.37 127 6 0.14 127 10 0.11 127 21 0.08 127 35 0.07 127 36 6.07 127 38 0.05 127 41 0.12 127 48 0.09 127 49 0.05 127 54 0.17 0.10 0.18 127 56 0.15 127 57 0.10 0.06 127 69 0.06 127 77 0.08 0.06 127 78 0.12 127 79 0.14 0.08 127 81 0.12 127 83 0.14 0.11 127 84 0.07

ý0.05 127 85 0.17 127 86 0.07 0.08 0.08 127 87 0.24 0.23 127 88 0.06 0.11 0.11 127 89 0.26 0.12 127 90 0.23 127 91 0.21 127 93 0.23 0.14 127 94 0.45 127 95 0.34 0.10 127 96 0.20 127 97 0.26 0.15 0.17 127 98 0.26 0.17 128 2 0.12 128 6 0.14 128 7 0.17 0.12 0.11 128 22 0.12 128 34 0.17 128 39 0.10 128 50 0.09 128 53 0.17 128 56 0.08 0.11 128 59 0.23 0.09 128 63 0.09 128 67 0.14 128 68 0.07 128 72 0.08 128 73 0.59 128 74 0.13 0.14 0.06 128 79 0.09 0.10 DEG CHN 124 P2 141 P2 134 P2 157 P2 148 P2 136 P2 146 P2 150 P2 148 P2 143 P2 153 P2 144 P2 119 P2 112 P2 152 P2 131 P2 136 P2 139 P2 128 P2 128 P2 150 P2 96 P2 142 P2 146 P2 156 P2 144 P2 136 P2 147 P2 145 P2 148 P2 154 P2 155 P2 145 P2 148 P2 151 P2 155 P2 143 P2 146 P2 152 P2 139 P2 155 P2 135 P2 149 P2 145 P2 140 P2 140 P2 143 P2 134 P2 129 P2 142 P2 139 P2 138 P2 149 P2 138 P2 139 P2 138 P2 92 P2 141 P2 145 P2 139 P2 143 P2 147 P2 135 P2 153 P2 159 P2 129 P2 157 P2 133 P2 127 P2 127 P2 148 P2 130 P2 139 P2 104 P2 135 P2 154 P2 137 P2 119 P2 151 P2 138 P2 IND %TW TWD 28 TWO 13 TWO 22 TWD 5 TWD 9 TWD 21 TWO 10 TWD 9 TWO 6 TWD 6 TWD 6 TWD 5 TWD 10 TWD 8 TWD 4 TWO 12 TWD 7 TWD 12 TWD 11 TWD 7 TWO 4 TWO 5 TWD 6 TWD 4 TWD 9 TWD 10 TWD 6 TWD 8 TWD 10 TWD 8 TWD 6 TWD 4 TWD 12 TWD 5 TWD 6 TWD 6 TWD 15 TWD 15 TWD 5 TWD 8 TWD 8 TWD 17 TWD 8 TWD 15 TWD 14 TWD 15 TWO 10 TWD 25 TWO 20 TWD 7 TWD 13 TWD 17 TWD 10 TWD 12 TWD 16 TWD 12 TWD 8 TWD 9 TWD 13 TWD 9 TWD 9 TWO 10 TWO 13 TWO 8 TWO 7 TWD 12 TWD 5 TWD 8 TWD 15 TWO 7 TWD 6 TWO 10 TWD 5 TWD 6 TWD 29 TWD 9 TWD 10 TWO 5 TWD 7 TWD 7 LOCATION 010

-0.42 011

+0.34 010

-0.39 011

+0.34 011

+0.34 011

-0.37 011

+0.34 011

+0.27 012

+0.17 011

+0.12 012

+0.08 011

+0.12 014

-0.68 009

-0.58 011

+0.07 010

-0.61 010

+0.07 014

+0.00 010

-0.63 010

-0.61 010

+0.00 011

+0.12 012

-0.56 010

-0.63 012

-0.58 011

+0.02 013

-0.58 012

-0.56 009

-0.51 010

-0.51 010

-0.46 009

-0.52 010

-0.51 009

-0.50 010

-0.49 014

-0.59 009

-0.47 011

-0.49 009

-0.50 010

-0.46 011

+0.27 010

-0.47

'009

-0.49 010

-0.45 010

-0.42 010

-0.42 012

-0.42 010

-0.39 010

-0.39 011

+0.34 011

+0.37 011

-0.39 011

+0.34 012

-0.37 011

-0.34 011

+0.39 010

+0.64 011

+0.32 011

+0.32 012

-0.39 011

-0:39 011

+0.20 011

-0.61 009

-0.58 011

+0.15 010

-0.61 007

-0.53 009

-0.61 010

-0.63 012

-0.66 008

-0.60 010

-0.56 010

+0.17 015

-0.73 014

-0.63 009

-0.56 012

-0.58 012

+0.02 012

-0.56 014

+0.02 EXT LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE EXT UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTIL 1.

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 94 INLET 3

94 INLET 96 INLET 5

96 INLET 4

94 INLET 96 INLET 74' INLET 74 INLET 80 INLET 78 INLET 0

517 INLET 78 INLET 78 INLET 0

517 INLET 78 INLET 92 INLET 92 INLET 92 INLET 92 INLET 4

92 INLET 92 INLET 92 INLET 96 INLET 96 INLET 96 INLET 96 INLET 96 INLET 96 INLET 96 INLET 96 INLET 94 INLET 94 INLET 96 INLET 94 INLET 94 INLET 94 INLET 96 INLET 96 INLET 94 INLET 2

94 INLET 4

94 INLET 96 INLET 96 INLET 94 INLET 96 INLET 96 INLET 96 INLET 94 INLET 96 INLET 7

96 INLET 94 INLET 96 INLET 96 INLET 96 INLET 94 INLET 94 INLET 7

76 INLET 6

76 INLET 74 INLET 74 INLET.

74 INLET 120 INLET 78 INLET 0

517 INLET 0

517 INLET 92 INLET 0

515 INLET 0

515 INLET 92 INLET 92 INLET 0

515 INLET 92 INLET 92 INLET 5

92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 7

96 INLET 0

96 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

510XB, 510xB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XL 510UL 510XB 510UL 510UL 5i0XB 510XB 510UL 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:45:40 AM Component: S/G A Page 82 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS DEG CHN 128 83 0.14 141 P2 0.30 144 P2 0.17 139 P2 128 85 0.15 145 P2 0.21 141 P2 128 86 0.11 150 P2 0.24 123 P2 128 87 1.16 127 P2 128 88 0.28 135 P2 0.16 141 P2 128 90 0.19 141 P2 128 91 0.27 143 P2 128 92 0.32 138 P2 128 95 0.19 141 P2 129 7 0.14 133 P2 129 13 0.26 142 P2 129 24 0.11 147 P2 129 35 0.12 146 P2 0.21 127 P2 129 36 0.12 143 P2 129 46 0.03 152 P2 129 53 0.14 132 P2 129 57 0.09 150 P2 129 59 0.22 135 P2 129 60 0.07 126 P2 129 62 0.07 154 P2 129 64 0.09 129 P2 129 68 0.06 161 P2 129 70 0.14 149 P2 129 77 0.14 144 P2 129 78 0.19 142 P2 129 79 0.12 151 P2 0.08 153 P2 0.10 147 P2 129 80 0.16 145 P2 129 81 0.23 135 P2 129 82 0.23 140 P2 0.10 149 P2 0.52 134 P2 129 83 0.08 156 P2 0.35 139 P2 129 84 0.15 143 P2 129 85 0.27 142 P2 0.66 130 P2 0.20 144 P2 0.21 144 P2 129 87 0.18 144 P2 129 92 0.16 139 P2 129 94 0.14 140 P2 130 7 0.13 117 P2 130 11 0.09 148 P2 130 12 0.15 147 P2 130 13 0.21 145 P2 130 15 0.23 143 P2 130 41 0.12 134 P2 130 49 0.10 129 P2 130 55 0.09 146 P2 130 60 0.16 138 P2 130 69 0.06 153 P2 130 71 0.11 133 P2 130 74 0.11 148 P2 130 77 0.09 148 P2 130 78 0.09 150 P2 130 79 0.14 150 P2 130 80 0.39 143 P2 0.23 146 P2 130 81 0.41 141 P2 0.20 149 P2 0.25 145 P2 130 82 0.28 143 P2 0.20 148 P2 130 83 0.09 138 P2 0.26 145 P2 0.30 145 P2 130 84 0.16 148 P2 0.40 141 P2 130 85 1.17 126 P2 0.93 125 P2 130 87 0.39 133 P2 130 88 0.20 144 P2 IND %TW TWD 10 TWO 19 TWO 12 TWO 10 TWD 14 TWD 8 TWD 15 TWO 42 TWD 17 TWD 11 TWD 13 TWO 17 TWD 19 TWD 13 TWD 10 TWD 16 TWO 9 TWO 9 TWD 14 TWD 9 TWO 3 TWO 10 TWD 6 TWO 15 TWD 5 TWO 5 TWD 7 TWD 5 TWO 10 TWO 10 TWD 13 TWO 8 TWD 6 TWO 7 TWD 11 TWO 15 TWO 15 TWO 7 TWO 27 TWD 6 TWD 20 TWD 11 TWO 17 TWO 31 TWD 13 TWO 14 TWD 12 TWD 11 TWO 10 TWD 9 TWD 7 TWD 11 TWO 13 TWO 14 TWD 10 TWD 8 TWD 7 TWD II TWD 5 TWD 8 TWO 8 TWD 7 TWO 6 TWD II TWD 24 TWD 16 TWD 24 TWD 14 TWD 17 TWD 18 TWD 14 TWD 7

TWO 17 TWD 20 TWD 12 TWD 24 TWD 42 PID TWD 23 TWD 14 LOCATION 009

-0.52 014

-0.56 012

+0.20 009

-0.50 010

-0.46 009

-0.46 010

-0.49 010

-0.47 010

-0.45 012

-0.46 010

-0.42 010

-0.42 010

-0.42 013

+0.32 010

+0.61 011

+0.27 011

+0.15 013

+0.10 013

-0.61 011

+0.12 010

+0.15 010

-0.63 010

+0.12 010

-0.61 011

+0.10 011

+0.12 010

-0.61 011

+0.10 014

+0.10 011

-0.54 011

-0.54 010

-0.54 010

+0.54 012

+0.20 011

+0.20 011

-0.51 009

-0.50 010

-0.51 011

+0.22 009

-0.50 011

-0.49 009

-0.52 009

-0.49 010

-0.46 012

-0.46 012

+0.24 010

-0.47 011

-0.34 011

+0.34 010

+0.59 014

+0.22 011

+0.27 012

+0.32 011

+0.22 012

-0.66 010

-0.56 011

+0.12 010

-0.58 007

-0.51 011

+0.02 011

-0.51 012

-0.54 011

-0.51 011

-0.53 011

-0.56 009

-0.53 011

+0.18 011

-0.50 009

-0.50 0il

-0.56 009

-0.58 011

+0.19 010

-0.45 009

-0.56 012

-0.50 010

-0.45 010

-0.48 010

-0.48 010

-0.48 010

-0.40 EXT LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LEE LTE LEE LTE LTE LTE LTE LTE LEE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LEE UTE UTE EXT UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE LTE LTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL 94 94 5

9.4 94 5

94 96 96 LAR 94 96 96 96 94 96 94 8

76 76 78 80 10 80 120 78 92 92 92 0

515 92 92 92 92 92 2

92 96 3

96 5

96 2

94 0

96 94 94 94 96 96 94 96 96 96 96 96 94 94 5

76 5

76 74 76 76 78 0

517 92 92 92 92 6

92 92 4

92 3

30 30 30 30 30 30 30 30 30 30

.30 30 30 LAR 30 132 30 30

  1. LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB

AREVA NP Inc QUERY:tQueryNn~,

lNR1R]

4/22/2008 9:45:40 AM Component: S/G A Page 83 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: Query~lith ROW TUBE VOLTS 130 89 0.11 130 90 0.09 0.11 130 92 0.13 0.13 0.10 130 93 0.22 131 3 0.11 131 10 0.06 0.09 0.24 0.19 131 11 1.04 0.13 0.12 0.12 0.12 0.17 131 12 0.13 0.21 131 13 0.15 131 20 0.06 131 21 0.09 131 24 0.07 131 26 0.16 131 29 0.13 0.06 131 40 0.10 131 51 0.08 131 53 0.10 131 56 0.13 131 69 0.19 0.08 131 70 0.09 131 75 0.17 0.14 0.09 0.11 /

131 77 0.14 131 78 0.12 0.31 0.55 0.19 131 79 0.14 131 80 0.11 0.08 131 81 0.24 0.11 0.10 0.39 0.18 131 83 0.25 131 84 0.12 131 85 0.15 131 87 0.13 0.13 131 89 0.18 131 90 0.21 132 3 0.18 132 13 0.29 0.08 0.14 0.08 132 14 0.09 132 21 0.12 0.04 132 33 0.15 132 34 0.09 132 39 0.21 132 40 0.10 132 42 0.08 132 48 0.14 132 50 0.15 0.06 132 52 0.11 132 58 0.07 132 62 0.11 132 63 0.16 0.10 132 67 0.21 DEG C 148 P 144 P 148 P 146 P 139 P 129 P 139 P 129 F 152 F 154 P 141 F 140 P 125 F 142 142 P 141 146 148 155 141 143 149 148 126 140 146 155 127 142 148 146 131 159 155 148 138 153 150 156 159 148 140 133 146 153 149 148 145 148 143 143 147 151 150 144 147 144 143 133 137 153 150 153 148 146 151 150 147 142 149 153 125 141 147 140 150 152 142 142 140 HN

'2

'2

'2

'2

'2

'2

'2

'2

'2

'2

'2

'2

'2 P2 2

P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 9 TWD 7 TWD 8 TWD 10 TWD 10 TWD 8 TWD 17 TWD 8 TWO 5 TWO 7 TWD 16 TWD 14 TWO 39 TWD 9 TWD 8 TWD 8 TWD 8 TWD 11 TWD 10 TWD 15 TWO 10 TWD 5 TWD 7 TWD 6 TWD 12 TWO 10 TWD 5 TWD 8 TWD 6 TWD 7 TWD 9 TWO 13 TWO 6 TWO 6 TWO 12 TWD 10 TWD 7 TWD 8 TWD 10 TWD 9 TWD 20 TWD 29 TWD 14 TWO 11 TWD 8 TWD 7 TWD 17 TWD 9 TWD 8 TWD 23 TWD 13 TWD 17 TWD 9 TWD 11 TWD 10 TWD 10 TWD 13 TWD 15 TWD 12 TWO 17 TWD 5 TWD 9 TWD 6 TWD 8 TWD 9 TWD 4 TWD 11 TWD 7 TWD 15 TWO 8 TWD 6 TWD 10 TWD 11 TWD 5 TWD 7 TWD 5 TWD 8 TWD 11 TWD 8 TWD 14 LOCATION 010

-0.42 011

+0.34 011

-0.40 011

+0.42 011

-0.37 008

-0.40 011

-0.36 010

-0.34 010

-0.39 010

+0.61 011

+0.29 012

+0.32 011

+0.27 012

+0.32 009

-0.42 011

-0.44 012

-0.39 010

+0.59 010

+0.56 011

+0.27 010

+0.59 012

+0.22 011

+0.17 011

+0.15 010

+0.20 011

-0.56 011

+0.15 010

-0.66 011

+0.12 010

+0.15 010

-0.59 012

-0.59 012

+0.15 007

-0.48 011

-0.49 011

+0.22 012

+0.19 012

-0.51 011

+0.19.

014

+0.13 012

-0.53 011

+0.19 010

+0.50 011

-0.56 011

-0.50 011

+0.19 012

-0.48 011

+0.21 011

-0.50 010

-0.45 009

-0.55 010

-0.45 010

-0.48 010

-0.42 011

-0.40 010

-0.42 011

-0.37 011

-0.37 011

+0.37 011

+0.27 008

+0.29 010

+0.57 012

-0.42 011

+0.27 011

+0.22 012

+0.22 009

+0.17 009

+0.17 011

-0.59 012

-0.61 009

+0.19 014

+0.02 009

-0.54 011

+0.15 009

-0.56 010

+0.19 012

-0.58 012

-0.58 014

+0.02 011

-0.51 EXT EXT UTIL 1

UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE.

WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL # LEG 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 132 INLET 5

76 INLET 74 INLET 74 INLET 74 INLET 74 INLET 76 INLET 76 INLET 3

76 INLET 3

76 INLET 5

76 INLET 8

76 INLET 74 INLET 74 INLET 5

76 INLET 78 INLET 120 INLET 78 INLET 78 INLET 78 INLET 0

78 INLET 0

517 INLET 92 INLET 92 INLET 92 INLET 92 INLET 4

92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 4

92 INLET 0

30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 4

30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 30 OUTLET 76 INLET 76 INLET 0

76 INLET 5

76 INLET 3

76 INLET 74 INLET 78 INLET 78 INLET 120 INLET 78 INLET 120 INLET 78 INLET 78 INLET 88 INLET 92 INLET 92 INLET 0

515 INLET 92 INLET 5

92 INLET 92 INLET 4

92 INLET 92 INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:41 AM Component: S/G A Page 84 of 97 ONSlAR-EOC24

- Tube Support Wear QUERY: QueryMl(l]

ROW TUBE VOLTS 0.10 132 71 0.13 132 72 0.11 0.22 132 75 0.17 0.09 132 76 0.10 132 77 0.07 0.25 0.39 0.32 132 79 0.17 0.19 0.35 132 80 0.12 0.13 0.25 132 81 0.36 132 82.

0.10 132 84 0.08 132 85 0.63 133 6 0.06 133 12 0.15 0.16 133 18 0.10 133 29 0.11 133 30 0.08 133 31 0.05 133 32 0.07 133 34 0.07 133 39 0.09 133 42 0.20 133 43 0.18 0.09 0.06 133 48 0.23 133 49 0.14 133 52 0.16 0.12 0.08 133 54 0.14 133 65 0.14 133 68 0.12 133 70 0.22 0.09 0.15 133 72 0.19 133 73 0.30 0.33 133 74 0.46 0.14 133 76 0.11 0.12 133 79 0.99 133 80 0.14 133 82 0.26 133 84 0.30 133 85 0.09 133 86 0.12 134 15 0.13 0.12 0.39 0.05 134 22 0.07 134 23 0.15 134 42 0.10 0.12 134 43 0.11 134 46 0.15 134 53 0.16 0.08 134 55 0.15 0.06 134 56 0.12 134 57 0.14 134 65 0.11 134 66 0.13 134 67 0.39 0.14 134 68 0.35 DEG CHN 147 P2 153 P2 148 P2 138 P2 138 P2 140 P2 142 P2 141 P2 141 P2 142 P2 138 P2 135 P2 146 P2 144 P2 149 P2 151 P2 146 P2 143 P2 149 P2 152 P2 135 P2 153 P2 143 P2 139 P2 146 P2 143 P2 151 P2 148 P2 138 P2 143 P2 151 P2 136 P2 137 P2 146 P2 120 P2 132 P2 142 P2 150 P2 128 P2 159 P2 138 P2 132 P2 153 P2 147 P2 145 P2 149 P2 138 P2 145 P2 141 P2 138 P2 149 P2 146 P2 158 P2 129 P2 149 P2 142 P2 139 P2 152 P2 121 P2 152 P2 148 P2 137 P2 135 P2 145 P2 141 P2 145 P2 126 P2 152 P2 139 P2 143 P2 145 P2 149 P2 144 P2 136 P2 137 P2 137 P2 146 P2 142 P2 144 P2 138 P2 IND %TW LOCATION TWD 7

012

+0.12 TWD 9 009

-0.51 TWD 8 014

+0.15 TWD 15 012

-0.56 TWD 12 009

-0.49 TWD 6 011

-0.51 TWD 7 009

-0.49 TWD 6 014

+0.16 TWD 17 011

+0.19 TWD 23 011

-0.55 TWD 20 009

-0.48 TWD 13 011

+0.21 TWD 14 010

+0.61 TWD 22 010

-0.48 TWD 9

012

-0.50 TWD 10 010

-0.48 TWD 17 009

-0.55 TWD 22 010

-0.45 TWD 8 010

-0.45 TWD 6 011

+0.29 TWD 32 010

-0.42 TWD 5 011

+0.32 TWD 11 010

+0.56 TWD 12 014

-0.51 TWD 8 012

-0.49 TWD 9 011

+0.17 TWD 6 011

+0.17 TWD 4 012

+0.17 TWD 6 009

-0.54 TWD 6 009

-0.56 TWD 7 009

-0.56 TWD 14 009

-0.56 TWD 13 012

-0.61 TWD 7 012

+0.12 TWD 5 010

+0;07 TWD 15 012

-0.61 TWD 11 010

-0.58 TWD 11 009

-0.63 TWD 8 011

-0.58 TWD 6 011

+0.13 TWD 10 012

-0.59 TWD 10 011

-0.54 TWD 9 010

+0.56 TWD 14 012

-0.54 TWD 6 009

-0.51 TWD 11 011

+0.24 TWD 13 011

-0.49 TWD 19 009

-0.49 TWD 20 010

-0.49 TWD 25 009

-0.49 TWD 10 011

+0.22 TWD 8 014

-0.56 TWD 9 011

-0.53 TWD 40 010

-0.50 TWD 11 012

-0.45 TWD 18 010

-0.42 TWD 20 011

-0.40 TWD 7 011

+0.32 TWO 9 011

-0.40 TWO 10 011

+0.24 TWD 10 012

-0.46 TWD 24 014

-0.51 TWD 4 008

+0.24 TWD 6 012

+0.20 TWD 11 011

+0.20 TWD 8 009

-0.53 TWD 10 011

+0.17 TWD 9 009

-0.54 TWD 10 009

-0.56 TWD 11 010

-0.54 TWD 6 010

+0.15 TWD 10 010

-0.56 TWD 5 010

+0.17 TWD 9 012

-0.59 TWD 10 011

-0.51 TWD 8 014

-0.56 TWD 9 009

-0.53 TWD 23 011

-0.49 TWD 10 011

+0.22 TWD 21 009

-0.51 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

5 92 92 92 92 92 0

92 4

92 30 30 30 30 30 30 0

30 30 30 30 30 30 30 30 74 74 74 78 78 78 78 78 78 78 78 78 78 4

78 90 88 5

515 0

515 0

515 92 92 6

92 92 6

92 5

92 6

.92 92 92 92 5

92 30 30 LAR 30 30 30 30 30 30 78 78 78 78 4

78 78 78 78 78 90 92 92 92 92 92 92 92 92 92 92 92 LEG PROBE INLET S1OXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL INLET 51OUL INLET 51OUL INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:45:41 AM Component:

S/G A Page 85 of 97 ONSIAR-EOC24 -

Tube QUERY: QueryMl[1]

Support Wear ROW TUBE 134 70 134ý 71 134 72 134 73 134 75 134 76 134 78 134 80 134 81 134 82 134 83 134 84 135 1 135 3 135 7 135 8 135 10 135 21 135 33 135 38 135 40 135 41 135 42 135 44 135 52 135 53 135 55 135 56 135 58 135 59 135 62 135 64 135 65 135 67 135 69 135 70 135 71 135 74 135 75 135 76 135 77 135 79 135 80 135 81 135 82 136 2 136 7 136 14 136 15 136 31 136 40 136 46 136 51 136 55 136 56 136 60 136 61 136 62 VOLTS 0.11 0.14 0.09 0.13 0.17 0.12 0.12 0.23 0.40 0.39 0.07 0.10 0.09 0.26 0.09 0.26 0.10 0.11 0.10 0.08 0.16 0.27 0.07 0.08 0.13 0.09 0.11 0.12 0.07 0.10 0.09 0.12 0.07 0.12

0. 08 0.11 0.06 0.18 0.24 0.09 0.08 0.11 0.10 0.11 0.19 0.09 0.08 0.20 0.12 0.09 0.12 0.11 0.19 0.27 0.33 0.18 0.50 0.10 0.18 0.20 0.16 0.21 0.53 0.12 0.06 0.11 0.10 0.12 0.12 0.06 0.10 0.24 0.09 0.11 0.31 0.09 0.11 0.11 0.15 0.09 DEG CHN 150 P2 147 P2 146 P2 153 P2 137 P2 136 P2 149 P2 140 P2 135 P2 138 P2 150 P2 153 P2 145 P2 140 P2 145 P2 138 P2 128 P2 136 P3 57 P2 144 P2 136 P2 133 P2 145 P2 143 P2 144 P2 149 P2 146 P2 138 P2 146 P2 144 P2 150 P2 144 P2 137 P2 144 P2 140 P2 148 P2 149 P2 137 P2 135 P2 154 P2 153 P2 148 P2 132 P2 139 P2 140 P2 126 P2 135 P2 149 P2 143 P2 133 P2 141 P2 138 P2 138 P2 143 P2 134 P2 135 P2 136 P2 145 P2 144 P2 138 P2 126 P2 140 P2 130 P2 136 P2 67 P2 116 P3 146 P2 149 P2 144 P2 147 P2 145 P2 140 P2 149 P2 143 P2 132 P2 138 P2 149 P2 154 P2 141 P2 141 P2 IND %TW TWD 8 TWD 10 TWD 7 TWD 9 TWD 11 TWD 8 TWD 8 TWD 14 TWD 21 TWD 24 TWD 6 TWD 8 TWD 8 TWD 18 TWD 8*

TWD 18 TWD 8 TWD 8 TWD 7 TWD 5 TWD 12 TWD 18 TWD 6 TWD 7 TWD 10 TWD 7 TWD 9 TWD 10 TWD 6

TWD 7 TWD 7 TWD 9 TWD 5 TWD 9 TWD 6 TWD 8 TWD 5 TWD 12 TWD 16 TWD 7 TWD 6 TWD 8 TWD 7

TWD 8

TWD 13 TWD 7 TWD 6 TWD 13 TWD 8 TWD 6 TWD 8 TWD 7 TWD 12 TWD 16 TWD 18 TWD 11 TWD 30 TWD 9 TWD 11 TWD 12 TWD 11 TWD 13 TWD 26 TWD 10 TWD 5 TWD 8 TWD 8 TWD 10 TWD 10 TWD 5 TWD 8 TWD 16 TWD 7 TWD 8 TWD 19 TWD 7 TWD 8 TWD 8 TWD 11 TWD 7 LOCATION 009

-0.52 009

-0.49 009

-0.49 009

-0.49 011

+0.21 010

+0.58 010

-0.48 011

-0.53 010

-0.51 010

-0.42 011

+0.26 011

+0.32 011

-0.42 010

-0.45 011

+0.45 011

-0.37 011

-0.37 014

-0.44 010

-0.42 011

+0.34 011

+0.32 011

+0.29 012

+0.22 012

-0.58 009

-0.56 010

+0.20 010

-0.54 014

-0.66 009

-0.53 012

-0.59 011

+0.22

011,

-0.51 011

+0.17 012

+0.19 014

+0.12 009

-0.54 006

-0.41 011

-0.54 014

-0.59 012

-0.54 007

-0. 46 011

-0.46 011

+0.27 010

-0.49 011

-0.46 009

-0.49 009

-0.47 011

-0.44 011

+0.21 009

-0.53 011

-0.47 010

+0.63 010

-0.45 014

-0.50 010

-0.48 014

-0.48 010

-0.41 011

+0.32 011

+0.32 011

-0.40 011

+0.34 011

-0.37 011

-0.40 011

-0.34 010

+0.61 014

-0.05 011

+0.27 011

+0.27 012

-0.54 012

+0.17 011

+0.19 009

-0.54 012

-0.56 007

-0.49 014

-0.56 011

-0.51 011

+0.22 010

+0.54 011

-0.49 007

-0.44 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR

'WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL # LEG 92 INLS 92 INLI 92 INSI 92 INLS 24 OUT]

24 OUT]

0 24 OUT) 24 OUT]

0 24 OUT]

30 OUT]

30 OUT:

30 OUT 30 OUT.

30 OUT:

30 OUT:

30 OUT:

5 30 OUT:

5 76 INL]

76 INL]

4 76 INL 74 INL 74 INLS 4

78 INL 78 INLS 78 INLI 78 INL 78 INS 78 INL 78 INL 92 INL 4

92 INL 92 INL 92 INS 92 INL 92 INL 92 INL 92 INL 92 INL 92 INL 92 INL 92 INL 92 INL 92 INL 92 INS 92 INS 5

92 INS 92 INL 92 INL 24 OUT 24 OUT 0

24 OUT 0

24 OUT 0

24 OUT 24 OUT 24 OUT 24 OUT 132 INT 132 INT 24 OUT 24 OUT 26 OUT 26 OUT 24 OUT 132 INT 74 INT 76 INL 78 INT 78 INT 78 INT 78 INi 78 INT 92 INT 92 INT 92 INI 92 INI 6

92 INI 92 INI 6

92 INI 92 INI 92 INI ET ET ET ET LET LET LET LET LET LET LET LET LET LET LET LET LET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET ET LET SET SET SET

'LET LET LET

'LET LET LET

'LET

'LET SET

'ET

'LET LET LET LET LET ET ET ET ET ET iET iET iET LET ET LET LET LET LET LET LET LET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl ONSlAR-EOC24 Tube Support Wear QUERY: QueryMl[l]

4/22/2008 9:45:42 AM Component: S/G A Page 86 of 97 Component: S/G A Page 86 of 97 ROW TUBE VOLTS 0.09 136 64 0.40 0.14 136 65 0.11 0.11 136 66 0.23 0.15 0.11 136 67 0.14 136 68 0.11 136 69 0.18 136 70 0.10 0.24 136 71 0.14 136 72 0.21 0.09 136 73 0.16 0.14 136 74 0.21 136 75 0.30 136 77 0.11 0.20 0.23 0.97 136 78 0.19 0.34 0.42 136 79 0.61 0.13 136 80 0.27 0.09 136 81 0.62 0.10 137 3 0.16 137 7 0.24 137 11 0.09 0.12 0.22 0.11 137 12 0.24 137 14 0.17 0.09 137 17 0.10 137 18 0.05 137 19 0.07 137 26 0.08 0.23 137 28 0.05 137 29 0.08 137 44 0.11 0.06 137 45 0.06 137 46 0.26 0.11 137 47 0.07 0.13 0.17 137 53 0.12 137 58 0.21 137 59 0.14 137 60 0.16 0.10 0.11 0.11 137 63 0.32 0.10 137 64 0.17 0.55 137 65 0.11 0.26 137 66 0.09 0.09 137 67 0.20 137 68 0.60 0.14 137 69 0.20 0.08 137 70 0.11 137 73 0.10 137 74 0.09 DEG CHN 152 P2 139 P2 140 P2 145 P2 149 P2 142 P2 150 P2 137 P2 149 P2 143 P2 142 P2 151 P2 143 P2 148 P2 143 P2 147 P2 137 P2 137 P2 135 P2 139 P2 149 P2 140 P2 135 P2 126 P2 134 P2 134 P2 135 P2 128 P2 127 P2 139 P2 139 P2 135 P2 149 P2 142 P2 141 P2 150 P2 156 P2 141 P2 143 P2 140 P2 143 P2 150 P2 141 P2 162 P2 152 P2 153 P2 142 P2 146 P2 150 P2 151 P2 153 P2 158 P2 140 P2 144 P2 152 P2 134 P2 139 P2 141 P2 140 P2 145 P2 145 P2 153 P2 143 P2 147 P2 136 P2 124 P2 140 P2 137 P2 144 P2 143 P2 147 P2 149 P2 146 P2 130 P2 146 P2 143 P2 151 P2 153 P2 124 P2 137 P2 IND %TW TWD 7 TWD 23 TWO 10 TWD 8 TWD 8 TWD 15 TWD 10 TWD 8 TWD 10 TWD 8 TWD 12 TWD 7 TWD 16 TWD 10 TWD 14 TWD 7 TWD 10 TWD 9 TWD 13 TWD 17 TWD 7 TWD 12 TWD 14 TWD 36 TWD 12 TWD 19 TWD 22 TWD 28 TWD 8 TWD 16 TWD 6 TWD 28 TWD 6 TWD 10 TWD 15 TWD 7 TWD 10 TWD 15 TWD 9 TWD 17 TWD 13 TWD 7 TWD 8 TWD 4 TWD 6 TWD 7 TWD 16 TWD 4 TWD 7 TWD 9 TWD 5 TWD 4 TWD 17 TWD 8 TWD 5 TWD 10 TWD 12 TWD 9 TWD 14 TWD 10 TWDO 11 TWD 7 TWD 8 TWD 8 TWD 20 TWD 7 TWD 12 TWD 28 TWD 8 TWD 17 TWD 6 TWD 7 TWD 13 TWD 30 TWD 10 TWD 14 TWD 6 TWD 8 TWD 7 TWD 6 LOCATION 012

-0.51 010.

-0.51 011

+0.24 012

-0.49 011

+0.27 009

-0.49 010

-0.49 010

+0.54 009

-0.52 009

-0.49 009

-0.49 009

-0.49 010

-0.45 010

-0.44 009

-0.46 012

-0.46 012

-0.53 010

-0.45 010

-0.47 010

-0.48 013

+0.27 012

+0.26, 012

-0.45 010

-0.45 011

+0.34 011

-0.39 010

-0.42 011

-0.37 008

-0.42 011

-0.37 008

-0.39 015

+0.58 008

-0.42 011

+0.34 011

+0.34 010

-0.44 010

+0.56 011

+0.29 012

-0.39 011

+0.29 011

+0.27 012

-0.41 012

+0.27 010

+0.51 011 40.24 011

-0.51 014

-0.58 011

+0.19 011

-0.51 010

-0.56 012

+0.19 012

+0.15 011

-0.51 012

+0.17 007

-0.49 009

-0.56 012

-0.56 009

-0.54 012

-0.54 009

-0.54 009

-0.51 010

-0.49 011

+0.24 011

-0.49 009

-0.49 010

+0.54 009

-0.

4 7 011

-0.46 009

-0.49 010

-0.44 009

-0.49 013

+0.27 010

-0.45 010

-0.45 014

-0.49 010

-0.45 010

+0.59 010

-0.42 010

-0.50 010

-0.47 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

92 92 4

92 92 2

92 92 4

92 6

92 92 92 92 92 92 6

92 92 92 24 24 26 24 24 24 24 24 26 26 26 24 24 26 26 24 5

24 76 76 78 78 78 78 78

.78 78 78 78 78 78 78 78 78 88 3

88 92 92 5

92 92 92 92 92 92 92 92 92 92 7

92 92 92 92 92 92 92 92 0

92 92 92 92 92 92 8

92 24 26 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 5ioXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:42 AM Component: S/G A Page 87 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 0.11 137 76 0.40 0.09 137 77 0.29 0.15 0.17 137 78 0.34 0.05.

138 1 0.14 0.15 138 2 0.17 138 3 0.09 138 6 0.57 138 7 0.07 138 10 0.11 138 11 0.35 0.07 138 14 0.24 138 27 0.16 138 38 0.13 138 43 0.08 0.07 138 44 0.09 138 52 0.16 138 53 0.11 0.08 138 55 0.12 138 56 0.11 0.09 138 57 0.32 138 58 0.07 0.09 0.16 138 61 0.16 0.16 138 62 0.11 138 63 0.09 0.20 0.13 0.26 0.12 138 64 0.15 138 65 0.18 0.10 0.10 138 66 0.11 138 68 0.07 138 70 0.42 138 72 0.38 0.13 138 73 0.09 0.27 0.20 138 74 0.35 0.13 138 75 0.14 0.30 139 2 0.13 139 6 0.12 139 13 0.08 139 16 0.15 139 27 0.21 0.07 139 32 0.05 139 37 0.09 139 38 0.07 139 43 0.07 139 44 0.14 139 46 0.11 139 47 0.13 139 48 0.15 139 49 0.08 0.24 0.11 139 50 0.17 0.09 0.09 0.06 139 54 0.15 0.21 DEG 146 127 140 141 129 137 133 144 115 127 131 149 133 143 144 137 157 143 148 145 157 148 153 146 145 154 140 143 148 139 146 134 147 145 146 151 147 134 154 141 145 133 145 144 112 150 125 131 129 144 138 137 135 128 119 143 134 146 132 136 153 141 153 144 145 145 152 140 148 144 144 157 143 152 149 138 154 149 152 146 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 7 TWD 22' TWD 6 TWD 16 TWD 10 TWD 11 TWD 19 TWD 4 TWD 9 TWD 10 TWD 11 TWD 8 TWD 28 TWD 6 TWD 9 TWD 22 TWD 6 TWD 17 TWD 12 TWD 10 TWD 6 TWO 6 TWD 7 TWD 11 TWD 8 TWD 6 TWD 9 TWD 8 TWD 7 TWD 19 TWD 6 TWD 7 TWD 11 TWD 11 TWD 11 TWD 8 TWD 7 TWD 14 TWO 9 TWD 17 TWD 9 TWD 10 TWD 12 TWD 7

TWD 7 TWD 8 TWD 5 TWD 22 TWD 20 TWD 8 TWD 6 TWD 16 TWD 13 TWD 19 TWD 8 TWD 9

TWD 17 TWD 10 TWD 9 TWD 7 TWD 11 TWD 15 TWD 6

TWD 4 TWD 7 TWD 6

TWD 6 TWD 10 TWD 8 TWD 10 TWD 11 TWD 6 TWD 16 TWD 8 TWD 12 TWD 7 TWD 7 TWD 5 TWD 13 TWD 16 LOCATION 011

+0.34 010

-0.42 011

-0.42 011

+0.34 010

+0.63 010

-0.40 011

-0.42 008

-0.39 010

+0.64 011

-0.29 010

+0.64 011

+0.36 011

+0.34 011

+0.31 010

+0.59 011

+0.32 012

+0.32 011

+0.27 011

-0.51 009

-0.56 011

+0.24 012

+0.19 012

-0.56 009

-0.51 013

+0.22 012

+0.19 012

-0.49 011

+0.29 011

-0.49 009

-0.52 007

-0.41 010

-0.51 011

+0.27 009

-0.49 011

+0.27 009

-0.49 009

-0.49 010

-0.46 011

+0.29 012

-0.44 012

+0.27 010

-0.45 010

-0.45 011

+0.32 010

+0.63 012

-0.44 010

-0.44 010

-0.47 010

-0.47 011

+0.32 012

-0.'44 011

-0.42 010

-0.42 011

-0.34 009

-0.48 011

+0.39 011

-0.37 010

-0.34 011

+0.34 012

-0.42 010

+0.59 012

+0.22 012

-0.51 011

+0.22 012

+0.24 012

+0.19 011

+0.24 009

-0.54 009

-0.51 009

-0.53 011

-0.49 009

-0.51 010

+0.54 011

+0.24 011

-0.49 012

-0.49 010

+0.56 011

+0.24 010

+0.59 011

-0.46 EXT UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE EXT UTIL 1

LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE

-WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR LTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR' UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTIL 2

CAL # LEG 2

26 OUTLET 26 OUTLET 5

26 OUTLET 24 OUTLET 24 OUTLET 24 OUTLET 26 OUTLET 26 OUTLET 76 INLET 6

76 INLET 76 INLET 74 INLET 76 INLET 74 INLET 5

120 INLET 120 INLET 120 INLET 120 INLET 120 INLET 120 INLET 88 INLET 88 INLET 3

88 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 3

92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 92 INLET 5

92 INLET 92 INLET 92 INLET 24 OUTLET 24 OUTLET 5

24 OUTLET 26 OUTLET 26 OUTLET 26 OUTLET 24 OUTLET 24 OUTLET 26 OUTLET 26 OUTLET 74 INLET 74 INLET 82 INLET 82 INLET 82 INLET 1

82 INLET 82 INLET 5

82 INLET 82 INLET 4

88 INLET 88 INLET 88 INLET 88 INLET 88 INLET 88 INLET 88 INLET 88 INLET 88 INLET 88 INLET 0

88 INLET 3

88 INLET 124 INLET 124 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSr Repi 4/22/2008 9:45:43 AM Component: S/G A Page 88 of 97 ONSlAR-E0C24 -

Tube Support Wear QUERY: Query~l[1]

ROW TUBE VOLTS 0.21 139 55 0.13 0.09 139 56 0.15 0.10 0.06 139 57 0.13 0.13 0.10 139 58 0.15 139 59 0.24 0.18 0.11 0.27 139 60 0.13 0.13 0.15 139 61 0.17 139 62 0.12 139 63 0.15 139 66 0.07 139 67 0.11 139 70 0.12 0.13 0.50 139 71 0.20 0.11 0.07 139 72 0.28 139 73 0.24 0.12 0.17 0.16 140 2 0.16 140 10 0.09 140 13 0.14 0.14 0.28 0.10 140 14 0.09 140 16 0.12 140 17 0.07 140 18 0.12 140 19 0.15 140 25 0.06 0.12 140 32 0.09 140 33 0.12 140 34 0.06 140 35 0.11 140 36 0.05 140 41 0.29

.0.30 240 42 0.15 0.07 140 45 0.16 0.11 0.47 140 46 0.22 140 48 0.16 140 49 0.38 0.35 140 50 0.11 0.09 140 54 0.16 140 55 0.87 140 56 0.12 0.86 0.12 140 57 0.54 0.15 140 58 0.17 0.23 0.26 0.13 0.06 140 59 0.12 140 60 0.18 140 64 0.31 140 65 0.16 DEG 143 147 139 150 147 152 150 149 148 144 141 139 145 146 140 146 143 143 147 139 148 144 124 126 126 139 121 134 135 128 143 135 118 140 153 149 138 139 145 129 152 156 155 153 145 152 145 150 139 145 149 147 144 152 147 149 151 136 146 149 142 137 144 146 150 132 151 130 142 135 149 143 137 144 147 131 153 146 138 131 CHN P22 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWO TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 17 10 7

13 9

6 10 108 12 16 13 8

18 12 11 13 12 11 11 78 8

8 24 13 8

17 14 8

11 10 11 7

10 11 18 8

7 9

5 9

11 5

9 7

9 5

8 4

18 18 11 5

13 10 29 15 12 21 20 8

7 12 40 9

37 9

31 13 12 16 17 10 5

10 15 22 12 LOCATION 012

-0.49 010

-0.49 011

+0.29 010

-0.51 011

+0.29 012

-0.49 011

+0.29 013

+0.27 010

-0.49 010

+0.59 009

-0.46 010

-0.49 011

-0.46 011

+0.29 009

-0.49 012

-0.46 011

+0.29 010

-0.46 010

-0.45 010

-0.41 012

-0.44 010

-0.41 012.

-0.45 011

+0.32 010

-0.42 011

+0.31 010

-0.50 007

-0.44 011

-0.42 011

-0.34 010

-0.40 008

-0.42 010

+0.61 011

+0,37 011

+0.32 010

+0.61 011

-0.44 011

+0.29 012

+0.32 012

-0.42 010

+0.54 008

-0.39 009

+0.56 009

+0.54 011

+0.27 012

-0.51 012

-0.51 011

-0.51 009

-0.53 012

+0.24 011

+0.27 011

-0.52 012

-0.49 01l

-0.49 012

+0.22 009

-0.51 011

+0.24 014

-0.56 009

-0.51 009

-0.49 009

-0.52 010

-0.49 012

+0.22 012

-0.49 014

-0.51 011

-0.44 009

-0.49 010

-0.41 014

+0.20 009

-0.49 010

-0.46 010

-0.44 011

-0.42 011

+0.32 012

-0.46 009

-0.46 010

-0.44 010

-0.41 010

-0.41 010

-0.39 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 7

WAR WAR S

WAR WAR WAR WAR WAR WAR 7

WAR WAR 5

WAR WAR WAR WAR WAR 0

WAR WAR WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR LAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR 4

WAR 6

WAR WAR WAR CAL # LEG 124 88 88 124 124 124 88 88 88 124 88 88 88 88 124 124 124 88 124 88 124 88 24 24 24 26 26 26 26 24 24 24 24 76 82 82 82 82 82 82 82 82 82 82 82 82 82 82 82 82 82 90 90 88 88 124 124 124 88 88 90 90 88 88 88 124 88 88 88 124 124 88 88 88 88 88 124 124 124 88 INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:43 AM Component: S/G A Page 89 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMll]

Support Wear ROW TUBE VOLTS 140 66 0.10 0.09 0.09 140 67 0.23 0.16 140 68 0.21 0.10 140 69 0.12 140 70 0.09 0.18 140 71 0.31 0.37 141 3 0.07 141 8 0.09 0.06 0.08 141 10 0.07 141 11 0.30 0.13 141 13 0.17 0.07 141 14 0.06 141 15 0.09 0.05 141 16 0.23 0.07 141 17 0.06 0.06 141 21 0.07 141 24 0.09 0.08 141 32 0.09 141 40 0.08 141 42 0.10 0.25 0.14 141 43 0.14 0.10 141 44 0.24 141 46 0.27 141 47 0.13 0.22 141 48 0.22 0.22 0.18 0.08 0.11 141 49 0.14 0.07 0.08 141 50 0.27 0.24 0.12 0.28 0.15 141 51 0.10 0.43 0.13 0.07 141 53 0.32 0.14 141 55 0.23 0.29 141 56 0.48 141 57 0.25 0.13 141 58 0.13 0.10 141 59 0.16 141 60 0.10 141 61 0.08 141 62 0.17 141 63 0.19 141 64 0.30 141 65 0.24 0.11 141 67 0.14 141 68 0.27 142 2 0.10 142 4 0.12 DEG CHN 147 P2 147 P2 155 P2 131. P2 146 P2 132 P2 150 P2 140 P2 140 P2 140 P2 140 P2 132 P2 81 P2 152 P2 145 P2 141 P2 147 P2 138 P2 145 P2 142 P2 147 P2 148 P2 148 P2 153 P2 144 P2 144 P2 90 P2 163 P2 149 P2 149 P2 141 P2 154 P2 153 P2 150 P2 141 P2 148 P2 141 P2 143 P2 147 P2 142 P2 146 P2 139 P2 147 P2 146 P2 146 P2 152 P2 150 P2 144 P2 148 P2 151 P2 136 P2 143 P2 146 P2 146 P2 150 P2 146 P2 134 P2 143 P2 154 P2 141 P2 146 P2 144 P2 142 P2 138 P2 142 P2 153 P2 149 P2 135 P2 136 P2 139 P2 147 P2 144 P2 137 P2 142 P2 140 P2 148 P2 125 P2 133 P2 151 P2 151 P2 IND %TW TWD 9 TWO 8 TWD 8 TWO 16 TWD 11 TWD 13 TWD 6 TWD 8 TWD 6 TWD 11 TWD 18 TWD 20 TWD 6 TWD 7 TWD 5 TWD 6 TWD 6 TWD 19 TWD 10 TWD 12 TWD 5 TWD 5 TWO 7 TWD 4 TWD 16 TWD 6 TWD 5 TWD 5 TWD 6 TWO 7 TWD 6 TWD 7 TWD 8 TWD 9 TWD 19 TWD 12 TWD 10 TWD 8 TWD 18 TWD 20 TWD 10 TWD 15 TWD 17 TWD 17 TWD 15 TWD 7 TWD 10 TWD 10 TWD 6 TWD.6 TWD 20 TWD 19 TWD 11 TWD 21 TWD 13 TWD 8 TWD 25 TWD 10 TWD 5 TWD 20 TWD 10 TWD 16 TWO 19 TWD 25 TWD 17 TWD 10 TWD 11 TWD 9 TWD 12 TWD 9 TWD 6 TWD 14 TWD 13 TWD 22 TWD 16 TWD 9 TWD 9 TWD 16 TWO 8 TWD 8 LOCATION 010

-0.41 011

-0.39 011

+0.37 010

-0.41 011

+0.36 011

-0.40 011

+0.29 011

+0.31 013

+0.32 011

+0.34 011

+0.34 011

-0.37 010

-0.32 012

+0.34 010

-0.37 011

+0.32 011

+0.34 011

-0.42 011

+0.32 011

+0.29 014

-0.49 014

+0.22 012

-0.42 011

+0.22 010

+0.59 012

+0.29 009

-0.54 010

+0.56 009

-0.51 011

-0.49 011

+0.24 009

-0.54 010

+0.54 008

-0.41 009

-0.53 011

-0.49 011

+0,27 011

-0.49 010

-0.49 009

-0.49 011

+0.27 010

-0.44 010

-0.49 011

-0.46 012

-0.46 012

+0.24 010

+0.56 009

-0.49 012

-0.49 011

+0.29 009

-0.51 010

-0.46 010

+0.61 011

-0.44 011

+0.29 009

-0.46 010

-0.44 011

+0.32 012 r0.46 009

-0.49 010

-0.44 009

-0.49 010

-0.46 010

-0.47

  • 010

-0.41 012

-0.44 010

-0.41 010

+0.63 010

+0.61 010

+0.63 010

-0.41 010

-0.44 010

-0.39 010

-0.41 011

-0.34 011

+0.36 012

-0.44 011

-0.36 012

+0.37 011

+0.34 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR>

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

124 124 124 88 88 24 0

24 26 24 24 26 26 74 82 5

82 6

82 82 82 82 82 82 3

82 82 82 82 82 82 82 8

82 82 82 6

82 124 124 124 124 88 3

88 124 124 88 1

88 124 124 124 124 8

124 88 88 4

88 124 124 124 124 124 88 88 88 4

88 88 3

88 88 88 90 88 88 124 124 88 124 0

88 124 88 124 88

.88 26 26 74 84 LEG INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET PROBE

=5 OXB-------

510XB 510XB 510XB 510XB 510XB 51DXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XS 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:44 AM Component: S/G A Page 90 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 142 5 0.13 142 6 0.11 142 10 0.26 0.19 142 12 0.12 0.12 142 13 0.15 0.09 142 14 0.17 0.06 142 16 0.11 142 20 0.06 142 21 0.11 0.07 0.07 142 22 0.07 142 23 0.23 142 29 0.08 0.22 142 30 0.11 0.09 0.11 0.09 0.07 142 32 0.07 142 33 0.12 0.08 142 34 0.08 142 35 0.11 142 36 0.17 0.07 142 38 0.33 142 39 0.07 142 40 0.15 142 41 0.21 0.11 0.29 142 42 0.26 0.28 142 43 0.21 0.06 142 44 0.13 0.07 142 45 0.21 0.13 0.09 142 47 0.12 0.09 142 48 0.21 142 49 0.32 0.21 0.11 0.09 142 50 0.48 0.13 142 51 0.22 142 52 0.23 142 53 0.12 0.07 142 54 0.12 0.19 142 56 0.09 142 58 0:54 0.14 142 59 0.18 142 60 0.72 142 61 0.06 142 62 0.22 142 64 0.11 0.38 0.11 0.06 142 65 0.34 0.11 143 8 0.14 143 9 0.22 143 10 0.37 0.06 143 12 0.18 0.13 DEG CHN 138 P2 132 P2 139 P2 141 P2 137 P2 135 P2 149 P2 139 P2 149 P2 165 P2 155 P2 139 P2 143 P2 142 P2 150 P2 152 P2 141 P2 152 P2 138 P2 140 P2 148 P2 143 P2 160 P2 146 P2 163 P2 151 P2 152 P2 145 P2 142 P2 149 P2 149 P2 138 P2 149 P2 142 P2 142 P2 150 P2 141 P2 145 P2 143 P2 140 P2 151 P2 145 P2 156 P2 143 P2 147 P2 148 P2 148 P2 147 P2 141 P2 140 P2 145 P2 149 P2 149 P2 138 P2 149 P2 144 P2 140 P2 144 P2 148 P2 148 P2 142 P2 155 P2 137 P2 140 P2 143 P2 134 P2 140 P2 144 P2 128 P2 125 P2 152 P2 122 P2 137 P2 141 P2 144 P2 136 P2 138 P2 143 P2 132 P2 145 P2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW LOCATION 9

011

+0.34 8

011

+0.34 16 011

+0.34 13 012

-0.37 9

011

+0.29 8

010

+0.61 11 012

-0.41 7

012

+0.32 12 010

+0.61 4

012

-0.39 8

012

-0.44 5

008

-0.41 9

009

-0.49 6

008

-0.41 6

010

-0.41 6

008

-0.44 16 011

-0.46 6

007

-0.41 15 013

-0.49 8

010

-0.46 7

012

-0.49 8

012

+0.27 7

010

+0.59 6

011

-0.49 5

010

+0.56 9

009

-0.51 6

011

+0.27 6

008

-0.44 8

008

-0.41 14 012

-0. 46 6

011

+0.24 19 011

-0.47 6

009

-0.51 10 011

+0.27 15 009

-0.51 8

010

-0.49 19 014

-0.51 16 009

-0.51 17 012

-0.44 15 009

-0.49 5

012

+0.22 12 012

-0.46 7

012

+0.24 15 010

-0.41 10 011

+0.29 7

011

-0.44 9

010

-0.44 7

012

-0.49 17.010

-0.44 20 010

-0.41 14 012

-0.44 8

011

+0.29 7

011

-0. 44 25 010

-0.45 9

009

-0.58 15 010

-0.44 18 010

-0.42 9

010

-0.41 5

005

-0.41 11 012

-0.44 16 010

-0.44 8

012

-0.44 27 012

-0.44 10 010

-0.46 13 010

-0.41 32 010

-0.44 5

011

-0.37 14 011

+0.36 8

007

-0.39 23 010

-0.39 9

011

+0.36 5

009

-0.41 19 011

+0.37 8

010

-0.39 10 011

+0.34 14 010

+0.61 22 010

+0. 61 5

011

+0.32 13 010

+0.61 9

011

+0.29 EXT EXT UTIL I

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL # LEG 86 INLET 84 INLET 84 INLET 84 INLET 84 INLET 7

84 INLET 86 INLET 86 INLET 84 INLET 84 INLET 84 INLET 4

82 INLET 82 INLET 4

82 INLET 4

82 INLET 82 INLET 82 INLET 82 INLET 82 INLET 82 INLET 82 INLET 82 INLET 7

82 INLET 3

82 INLET 5

82 INLET 82 INLET 82 INLET 82 INLET 7

82 INLET 124 INLET 124 INLET 90 INLET 88 INLET 90 INLET 88 INLET 88 INLET 88 INLET 90 INLET 90 INLET 88 INLET 88 INLET 124 INLET 124 INLET 88 INLET 88 INLET 4

88 INLET 88 INLET 88 INLET 124 INLET 88 INLET 88 INLET 6

88 INLET 4

88 INLET 90 INLET 90 INLET 88 INLET 124 INLET 88 INLET 0

88 INLET 124 INLET 0

124 INLET 4

124 INLET 90 INLET 7

90 INLET 8

88 INLET 90 INLET 2

88 INLET 90 INLET 88 INLET 88 INLET 88 INLET 2

88 INLET 26 OUTLET 3

26 OUTLET 86 INLET 9

84 INLET 86 INLET 86 INLET 86 INLET 86 INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:45 AM Component: S/G A Page 91 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 143 13 0.33 0.15 143 14 0.16 0.14 0.06 143 20 0.23 0.07 143 21 0.41 0.20 0.08 0.13 143 22 0.15 0.11 143 23 0.10 0.21 0.26 0.21 143 24 0.10 143 26 0.09 143 29 0.11 143 30 0.06 143 31 0.16 143 34 0.12 0.20 0.06 143 35 0.12 143 39 0.07 0.18 143 40 0.13 0.16 0.07 143 41 0.10 0.40 0.08 143 42 0.15 143 44 0.09 143 45 0.12 143 46 0.11 143 47 0.49 143 49 0.14 143 50 0.09 143 51 0.06 143 53 0.12 143 54 0.24 143 55 0.12 143 56 0.32 0.06 143 57 0.23 0.20 143 58 0.06 0.06 143 59 0.12 0.07 143 60 0.19 0.09 143 61 0.15 0.12 143 62 0.09 0.17 144 2 0.08 144 6 0.16 144 8 0.16 0.11 144 12 0.16 144 14 0.10 144 15 0.16 0.28 144 16 0.11 0.16 0.31 0.09 144 17 0.15 0.25 0.15 0.09 144 18 0.19 0.18 0.51 0.19 144 19 0.09 DEG 137 150 140 136 147 139 143 138 147 153 155 150 133 148 148 144 133 150 153 148 146 154 149 147 149 151 153 146 149 147 149 157 137 134 141 99 150 153 138 147 144 151 149 144 145 143 151 137 146 146 98 152 159 141 ill 143 146 143 149 71 141 143 138 148 149 142 141 153 146 134 139 134 142 139 145 149 152 138 139 147 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 19 TWD 10 TWD 11 TWD 10 TWD 5 TWD 15 TWD 5 TWD 23 TWD 13 TWD 6 TWD 9 TWD 11 TWD 8 TWD 7 TWD 14 TWD 16 TWD 14 TWD 8 TWD 7 TWD 8 TWD 5 TWD 11 TWD 9 TWD 14 TWD 5 TWD 11 TWD 7 TWD 15 TWD 10 TWD 12 TWD 6 TWD 9 TWD 26 TWD 7 TWD II TWD 7 TWD 11 TWD 8 TWD 30 TWD 12 TWD 7 TWD 6 TWD 11 TWD 16 TWD 11 TWD 20 TWD 5 TWD 18 TWD 16 TWD 5 TWD 5 TWD 11 TWD 6 TWD 14 TWD 7 TWD 10 TWD 8 TWD 7 TWD 12 TWD 6 TWD 11 TWD 12 TWD 8 TWD 11 TWD 7 TWD 12 TWD 18 TWD 8 TWD 11 TWD 18 TWD 7 TWD 11 TWD 17 TWD 11 TWD 7 TWD 12 TWD 12 TWD 26 TWD 13 TWD 7 LOCATION EXT EXT 010

+0.59 LTE UTE 011

-0.42 LTE UTE 009

-0.49 LTE UTE 010

+0.61 LTE UTE 010

-0.44 LTE UTE 011

-0.42 LTE UTE 012

+0,29 LTE UTE 011

+0.27 LTE UTE 012

-0.42 LTE UTE 009

-0.51 LTE UTE 010

+0.59 LTE UTE 012

-0.49 LTE UTE 012

+0.29 LTE UTE 009

-0.49 LTE UTE 010

+0.59 LTE UTE 011

-0.47 LTE UTE 012

+0.27 LTE UTE 012

-0.46 LTE UTE 010

-0.49 LTE UTE 012

+0.27 LTE UTE 007

-0.41 LTE UTE 010

+0.57 LTE UTE 010

+0.59 LTE UTE 012

-0.44 LTE UTE 012

+0.24 LTE UTE 011

+0.27 LTE UTE 011

-0.46 LTE UTE 011

+0.29 LTE UTE 010

-0.46 LTE UTE 014

-0.51 LTE UTE 009

-0.49 LTE UTE 010

-0.46 LTE UTE 011

-0.44 LTE UTE 010

+0.56 LTE UTE 010

-0.44 LTE UTE 010

+0.64 LTE UTE 010

-0.44 LTE UTE 012

-0.44 LTE UTE 014

-0.49 LTE UTE 014

-0.51 LTE UTE 012

-0.44 LTE UTE 012

-0.44 LTE UTE 010

-0.41 LTE UTE 012

-0.44 LTE UTE 010

-0.39 LTE UTE 010

-0.39 LTE UTE 011

-0.42 LTE UTE 010

-0.39 LTE UTE 011

+0.39 LTE UTE 011

+0.34 LTE UTE 011

-0.34 LTE UTE 011

-0.36 LTE UTE 011

+0.34 LTE UTE 011

+0.36 LTE UTE 006

-0.36 LTE UTE 010

-0.41 LTE UTE 011

+0.36 LTE UTE 010

-0.36 LTE UTE 011

-0.34 LTE UTE 010

+0.66 LTE UTE 011

+0.34 LTE UTE 010

+0.64 LTE UTE 011

+0.34 LTE UTE 009

-0.44 LTE UTE 012

-0.42 LTE UTE 011

+0.29 LTE UTE 012

-0.44 LTE UTE 009

-0.47 LTE UTE 010

+0.59 LTE UTE 011

+0.32 LTE UTE 010

-0.39 LTE UTE 010

+0.61 LTE UTE 012

-0.42 LTE UTE 012

+0.32 LTE UTE 011

+0.32 LTE UTE 009

-0.47 LTE UTE 010

+0.59 LTE UTE 012

-0.42 LTE UTE 012

+0.29 LTE UTE 012

-0.42 LTE UTE UTIL 1

UTIL WAR WAR WAR WAR WAR 3

WAR WAR 5

WAR WAR WAR 4

WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 8

WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR WAR WAR WAR 4

WAR WAR WAR 4

WAR 1

WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR 5

WAR WAR WAR WAR WAR CAL #

84 84 86 86 86 86 86 84 84 84 84 86 86 84 84 84 84 86 86 84 86 84 86 86 86 124 124 124 88 88 88 124 124 124 88 88 124 88 124 124 88 124 124 88 124 88 88 124 124 88 88 124 124 88 88 90 90 88 88 86 86 86 86 84 84 86 86 84 84 84 84 86 86 86 86 84 84 84 84 86 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51DXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:45 AM Component:

S/G A Page 92 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 0.11 144 20 0.15 0.44 0.16 0.13 0.09 144 21 0.12 0.08 0.09 144 22 0.15 144 23 0.24 0.07 0.13 0.12 144 24 0.12 0.10 0.09 144 25 0.08 0.08 0.09 144 26 0.10 0.29 144 27 0.07 0.06 144 28 0.12 0.11 144 34 0.09 144 36 0.14 144 37 0.11 0.29 0.15 0.20 144 38 0.12 144 40 0.11 0.07 0.14 144 41 0.07 0.08 144 42 0.12 144 43 0.10 0.09 0.08 144 45 0.09 144 46 0.06 0.29 144 47 0.11 144 48 0.16 144 49 0.30 144 50 0.12 144 51 0.11 144 52 0.18 0.06 0.08 144 54 0.15 0.17 0.08 144 55 0.08 144.56 0.14 144 57 0.34 0.09 145 1 0.10 0.20 145 3 0.17 145 7 0.16 145 8 0.12 145 9 0.19 0.13 0.13 145 11 0.12 0.16 145 12 0.06 0.28 0.35 0.13 145 14 0.08 0.08 145 15 0.21 0.13 145 16 0.17 0.23 DEG CHN 146 P2 154 P2 139 P2 152 P2 126 P2 158 P2 144 P2 144 P2 144 P2 147 P2 149 P2 152 P2 147 P2 148 P2 142 P2 144 P2 156 P2 144 P2 147 P2 143 P2 148 P2 137 P2 153 P2 119 P2 157 P2 154 P2 144 P2 153 P2 148 P2 139 P2 148 P2 142 P2 134 P2 140 P2 56 P2 144 P2 151 P2 148 P2 127 P2 130 P2 152 P2 144 P2 142 P2 143 P2 133 P2 88 P2 84 P2 142 P2 139 P2 143 P2 139 P2 140 P2 81 P2 137 P2 146 P2 80 P2 125 P2 149 P2 139 P2 141 P2 140 P2 139 P2 149 P2 153 P2 141 P2 123 P2 146 P2 136 P2 149 P2 121 P2 138 P2 139 P2 136 P2 146 P2 141 P2 156 P2 140 P2 138 P2 145 P2 145 P2 IND %TW TWD 8 TWD 10 TWD 24 TWD 11 TWD 9 TWD 6 TWD 9 TWD 6 TWD 7 TWD 10 TWD 16 TWD 5 TWD 10 TWD 9 TWD 8 TWD 7 TWD 6 TWO 6 TWD 6 TWD 7 TWD 7 TWD 18 TWD 5 TWD 5 TWD 8 TWD 8 TWD 7 TWD 10 TWD 8 TWD 18 TWD 11 TWD 14 TWD 9 TWD 8 TWD 5 TWD 10 TWD 6 TWD 6 TWD 8 TWD 8 TWD 7 TWD 6 TWD 7 TWD 5 TWD 18 TWO 8 TWD II TWD 19 TWD 8 TWD 8 TWD 12 TWD 5 TWD 6 TWD 10 TWD 11 TWD 6 TWD 6 TWD 9 TWD 21 TWD 7 TWD 7 TWD 13 TWD 11 TWD 11 TWD 9 TWD 13 TWD 9 TWD 9 TWD 9 TWD 11 TWD 5 TWD 18 TWD 21 TWD 10 TWD 6 TWD 6 TWO 14 TWD 9 TWD 12 TWD 15 LOCATION 012

+0.29 010

+0.56 011

-0.47 012

-0.42 012

+0.27 009

-0.47 009

-0.46 010

-0.42 012

+0.32 008

-0.41 010

+0.59 011

-0.49 012

-0.44 012

+0.27 011

+0.29 010

-0.42 012

-0.44 011

-0.47 011

+0.27 010

+0.56 010

-0.44 011

+0.29 012

+0.29 008

+0.29 009

-0.52 010

+0.61 012

-0.44 009

-0.47 009

-0.49 011

-0.42 011

+0.32 012

+0.29 010

-0.39 011

+0.27 010

+0.62 010

-0.44 010

+0.61 010

-0.41 010

-0.42 010

+0.59 012

-0.41 010

-0.39 010

-0.39 011

+0.34 012

-0.44 010

+0.59 010

+0.64 012

-0.41 012

-0.41 010

-0.36 010

-0.39 011

+0.32 010

+0.66 011

-0.37 011

+0.39 010

+0.66 011

+0.36 011

+0.34 010

-0.37 011

+0.36 009

-0.42 010

-0.34 011

+0.34 011

+0.32 011

+0.34 010

+0.61 011

-0.42 011

+0.32 012

-0.39 010

+0.59 009

-0.41 010

+0.64 011

-0.42 011

+0.29 009

-0.46 010

+0.61 009

-0.47 010

+0.61 009

-0.44 010

+0.61 EXT LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE EXT UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR 4

WAR WAR.

WAR WAR WAR WAR WAR WAR 4

WAR 6

WAR 7

WAR 6

WAR WAR WAR WAR WAR 4

WAR WAR WAR 4

WAR WAR 4

WAR WAR WAR 0

WAR 3

WAR 6

WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 5

WAR 4

WAR 3

WAR 4

WAR 10 WAR WAR WAR WAR WAR WAR WAR WAR 8

WAR WAR CAL #

86 84 84 84 84 84 86 86 86 84 86 86 86 86 84 84 84 86 86 86

.84 84 86 86 84 84 84 84 86 86 86 86 84 84 84 84 86 86 84 86 86 86 86 84 84 86 84 86 84 86 84 84 84 84 84 84 86 84 86 86 84 84 84 84 86 84 84 84 84 84 86 86 86 86 86 86 84 84 86 86 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

-510XB

.510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

510XB, 510XB' 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:47 AM Component: S/G A Page 93 of 97 ONSlAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS DEG 0.13 151 0.31 140 0.16 146 0.38 136 145 17 0.24 146 0.15 144 0.12 155 0.76 128 0.44 139 0.07 160 145 18 0.15 140 0.10 143 0.09 144 0.11 142 0.19 141 0.27 140 0.30 137 0.21 143

'145 19 0.12 149 0.24 157 0.31 141 0.14 147 145 20 0.07 151 0.09 143 0.17 142 0.29 139 0.28 139 0.10 147 145 21 0.29 143 0.12 146 145 22 0.22 149 145 23 0.10 137 145 24 0.17 138 0.36 137 0.13 150 0.06 163 0.10 ii 145 25 0.16 139 0.28 147 145 26 0.08 150 0.08 53 0.10 144 0.21 143 145 27 0.20 142 0.15 142 145 28 0.18 144 0.23 139 145 29 0.16 144 145 30 0.08 160 0.15 141 0.14 136 0.07 138 145 31 0.19 143 145 32 0.06 153 145 33 0.09 132 145 34 0.08 153 0.14 145 0.11 146 145 36 0.10 140 0.12 119 145 37 0.13 149 0.27 144 145 38 0.13 89 0.07 140 145 39 0.70 137 145 44 0.11 96 145 46 0.06 146 145 47 0.15 138 0.10 141 145 49 0.27 139 0.11 148 0.18 137 145 50 0.13 143 145 51 0.16 145 0.10 146 145 53 0.09 144 145 54 0.13 136 0.10 141 0.15 140 146 2 0.16 122 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 9

19 12 22 15 10 8

33 24 5

11 8

7 8

13 18 19 14 8

15 18 9

5 7

12 18 18 8

18 9

15 7.

12 22 10 5

7 11 17 6

6 8

14 13 10 13 15 11 6

11 10 6

12 5

7 6

10 8

8 9

9 17 9

6 32 8

5 10 7

17 8

12 10 11 7

7 9

7 11 11 LOCATION 011

-0.44 011

+0.29 012

-0.41 012

+0.34 009

-0.50 010

-0.42 010

+0.59 011

+0.32 012

-0.39 012

+0.30 008

-0.41 009

+0.59 010

-0.44 010

+0.64 011

-0.42 011

+0.29 012

-0.44 012

+0.32 009

-0.50 010

+0.62 012

-0.42 012

+0.32 009

-0.49 010

-0.44 010

+0.61 011

-0.42 011

+0.29 012

-0.44 011

-0.44 009

-0.50 010

-0.44 012

-0.42 010

+0.59 011

-0.44 011

+0.27 009

-0.49 009

+0,56 010

+0,57 011

-0.42 010

-0.46 010

+0.64 011

+0.32 012

-0.46 009

-0.47 010

+0.61 010

+0.59 011

-0.44 012

-0.44 010

+0.64 011

-0.44 012

+0.32 009

-0.46 010

+0.59 010

+0.61 012

-0.42 009

-0.46 010

-0.44 009

+0.56 010

-0.44 010

+0.61 010

-0.44 012

-0.42 010

+0.59 010

-0.44 010

-0.42 010

+0.59 012

-0.41 007

-0.39 010

-0.42 011

-0.37 011

+0.37 012

+0.32 011

-0.34 011

-0.39 011

+0.34 007

-0.39 010

-0.36 010

+0.61 011

+0.34 010

+0.59 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 5

WAR WAR 4

WAR WAR WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR.

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR 10 WAR WAR WAR WAR WAR.

WAR WAR CAL # LEG 86 INLET 86 INLET 86 INLET 86 INLET 84 INLET 84 INLET 84 INLET 84 INLET 84 INLET 84 INLET 86 INLET 86 INLET 86 INLET 86 INLET 86 INLET 86 INLET 86 INLET 86 INLET 84 INLET 84 INLET 84 INLET 84 INLET 86 INLET 86 INLET 86 INLET 86 INLET 86 INLET 86 INLET 84 INLET 84 INLET 120 INLET 84 INLET 86 INLET 86 INLET 86 INLET 86 INLET 86 INLET 84 INLET 84 INLET 86 INLET 86 INLET 86 INLET 86 INLET 84 INLET 84 INLET 86 INLET 86 INLET

84.

INLET 86 INLET 86 INLET 86 INLET 86 INLET 84 INLET 86 INLET 84 INLET 86 INLET 86 INLET 86 INLET 86 INLET 86 INLET 84 INLET 84 INLET 86 INLET 86 INLET 84 INLET 86 INLET 86 INLET 84 INLET 84 INLET 84 INLET 84 INLET 84 INLET 86 INLET 84 INLET 84 INLET 84 INLET 86 INLET 86 INLET 86 INLET 84 INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:47 AM Component: S/G A Page 94 of 97 ONSIAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l]

ROW TUBE VOLTS 0.12 0.11 146 7 0.09 146 11 0.10 146 12 0.29 0.21 146 13 0.29 146 14 0.32 0.16 0.14 0.10 146 15 0.12 0.09 0.90 0.10 0.27 0.41 146 16 0..18 0.24 0.42 0.31 146 17 0.27 0.13 0.70

.0.17 0.32 0.13 146 18 0.15 0.12 0.26 0.27 0.10 146 19 0.10 0.13 0.13 0.53 0.08 146 20 0.15 0.08' 146 21 0.08 0.33 146 22 0.10 0.36 0.40 146 23 0.15 0.35 146 24 0.21 0.11 146 25 0.07 0.10 0.10 0.47 146 26 0.17 0.13 146 29 0.04 0.12 0.11 146 31 0.10 0.12 0.04 146 32 0.17 146 33 0.23 0.30 0.14 146 34 0.17 146 35 0.79 146 36 0.29 146 37 0.21 146 40 0.11 146 43 0.10 146 47 0.07 0.12 146 48 0.13 146 50 0.07 0.17 146 51 0.08 0.10 147 2 0.33 147 3 0.14 147 4 0.11 DEG CHN IND %TW 144 P2 TWD 9 110 P2 TWD 8 131 P2 TWD 7 142 P2 TWD 8 135 P2 TWD 18 144 P2 TWD 13 139 P2 TWD 18 139 P2 TWD 19 147 P2 TWD 11 133 P2 TWD 10 149 P2 TWD 7 146 P2 TWD 9 150 P2 TWD 7 128 P2 TWD 37 141 P2 TWD 8 143 P2 TWD 18 137 P2 TWD 23 145 P2 TWD 12 126 P2 TWD 15 133 P2 TWD 23 136 P2 TWD 18 138 P2 TWD 17 139 P2 TWD 9 132 P2 TWD 33 147 P2 TWD 12 140 P2 TWD 20 138 P2 TWD 10 129 P2 TWD 10 139 P2 TWD 8 143 P2 TWO 16 137 P2 TWD 17 146 P2 TWD 7 138 P2 TWD 8 144 P2 TWD 9 136 P2 TWD 10 135 P2 TWD 28 144 P2 TWD 6 143 P2 TWD 10 156 P2 TWD 6 126 P2 TWD 6 140 P2 TWD 20 145 P2 TWD 7 139 P2 TWD 21 143 P2 TWD 22 142 P2 TWD 11 143 P2 TWD 21 134 P2 TWD 14 134 P2 TWD 8 148 P2 TWD 5 135 P2 TWD 7 141 P2 TWD 8 131 P2 TWD 26 144 P2 TWD 11 143 P2 TWD 9 147 P2 TWD 3 139 P2 TWD 8 148 P2 TWD 8 149 P2 TWD 7 146 P2 TWD 9 160 P2 TWD 3 141 P2 TWD 12 137 P2 TWD 15 132 P2 TWD 18 148 P2 TWD 9 140 P2 TWD 12 132 P2 TWD 34 141 P2 TWD 19 144 P2 TWD 14 145 P2 TWD 8 104 P2 TWD 7 157 P2 TWD 5 152 P2 TWD 8 147 P2 TWD 9 143.P2 TWD 6 150 P2 TWD 12 143 P2 TWD 6 147 P2 TWD 7 148 P2 TWD 20 111 P2 TWD 10 104 P2 TWD 8 LOCATION 011

+0.34 010

-0.34 011

+0.37 009

-0.44 009

-0.44 010

-0.39 011

+0.34 011

+0.29 012

-0.37 010

+0.61 011

-0.42 012

+0.32 009

-0.44 010

+0.61 011

-0.39 011

+0.32 012

-0.39 009

-0.46 010

+0.61 011

+0.32 012

-0.37 009

-0.46 011

-0.42 011

+0.32 012

-0.42 012

+0.32 010

+0.56 009

-0.46 010

-0.42 012

-0.39 012

+0.32 011

+0.29 009

-0.46 010

-0.42 011

+0.32 012

-0.41 012

+0.34 010

-0.42 009

-0.49 009

-0.46 011

-0.42 009

-0.47 011

-0.42 012

-0.39 009

-0.44 011

+0.32 010

-0.42 009

+0.62 007

-0.39 008

+0.32 009

-0.46 011

+0.32 009

-0.47 010

+0.59 012

+0.32 010

+0.61 009

-0.44 009

-0.47 010

+0.57 012

+0.27 009

-0.46 010

-0.42 011

+0.34 009

-0.51 010

-0.42 010

-0.42 010

-0.41 010

-0.42 012

-0.39 010

+0.64 010

+0.64 011

+0.34 011

+0.39 011

-0.34 011

+0.39 010

+0.63 011

+0.41 010

-0.37 010

+0.66 010

+0.64 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL #

84 84 86 86 84 84 86 84 84 84 3

84 86 86 86 86 86 86 84 84 84 84 86 86 86 86 86 86 84 84 84 84 84 86 86 86 86 86 84 84 86 86 84 84 84 86 86 84 84 86 86 86 86 84 84 84 84 4

84 84 84 84 86 84 84 3

84 86 84 86 84 86 84 84 84 86 86 86 86 86 84 86 84 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

.510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXE

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:48 AM Component:

S/G A Page 95 of 97 ONSIAR-EOC24 -

Tube Support Wear QUERY: QueryMl[l1 ROW TUBE VOLTS 147 6 0.20 147 7 0.17 0.09 147 9 0.14 0.10 0.33 147 10 0.57 147 11 0.11 147 12 0.07 0.38 0.22 0.09 147 13 0.21 0.08 147 14 0.16 0.10 147 15 0.16 0.40 0.51 0.13 147 16 0.30 0.25 0.20 0.18 147 17 0.08 0.11 147 18 0.09 0.17 0.10 147 19 0.07 0.09 147 20 0.23 0.41 0.15 0.30 0.14 147 21 0.11 0.22 0.09 0.12 0.18 147 22 0.13 0.28 0.28 0.17 0.15 147 23 0.29 147 24 0.26 0.07 0.20 147 25 0.12 0.08 0.30 0.16 147 26 0.08 0.05 147 27 0.18 0.22 147 28 0.11 0.19 0.10 147 29 0.16 0.11 147 30 0.24 0.52 0.15 147 31 0.30 0.10 0.17 147 32 0.22 0.15 147.33 0.13 147 34 0.06 147 35 0.65 147 36 0.57 147 37 0.13 0.41 0.14 147 38 0.20 0.10 DEG CHN 137 P2 143 P2 147 P2 135 P2 136 P2 136 P2 132 P2 142 P2 151 P2 126 P2 145 P2 144 P2 141 P2 149 P2 140 P2 148 P2 138 P2 134 P2 131 P2 142 P2 139 P2 133 P2 125 P2 133 P2 149 P2 141 P2 147 P2 140 P2 129 P2 146 P2 117 P2 143 P2 138 P2 147 P2 144 P2 125 P2 147 P2 144 P2 155 P2 150 P2 147 P2 149 P2 145 P2 144 P2 123 P2 147 P2 140 P2 142 P2 138 P2 145 P2 147 P2 143 P2 138 P2 110 P2 146 P2 157 P2 140 P2 129 P2 138 P2 137 P2 146 P2 142 P2 153 P2 144 P2 133 P2 142 P2 144 P2 146 P2 145 P2 139 P2 124 P2 134 P2 159 P2 132 P2 134 P2 152 P2 136 P2 143 P2 144 P2 143 P2 IND %TW TWO 13 TWO 12 TWO 7 TWD 10 TWO 8 TWO 20 TWO 28 TWO 8 TWO 5 TWO 22 TWO 14 TWO 7 TWD 14 TWD 6 TWO 11 TWD 7 TWD 12 TWO 23 TWD 27 TWO 10 TWO 18 TWO 16 TWO 13 TWO 12 TWO 6 TWO 8 TWD 7 TWO 12 TWO 7 TWO 5 TWO 7 TWO 15 TWO 23 TWD 10 TWO 18 TWO 9 TWO 8 TWO 15 TWO 7 TWO 9 TWO 13 TWD 9 TWD 17 TWD 17 TWO 12 TWO 10 TWD 18 TWD 16 TWO 5 TWO 13 TWD 9 TWO 6 TWO 19 TWO 11 TWO 6 TWD 4 TWO 12 TWO 14 TWD 8..

TWO 13 TWO 7 TWO 11 TWO 8 TWO 16 TWO 28 TWD 11 TWD 18 TWO 7 TWD 11 TWD 15 TWO 11 TWD 9 TWO 5 TWD 30 TWO 29 TWD 9 TWO 23 TWO 9 TWO 14 TWD 8 LOCATION 011

+0.37 012

-0.37 012

+0.34 011

+0.34 012

-0.39 010

+0.64 011

+0.37 012

-0.37 009

-0.44 010

+0.61 011

+0.32 012

-0.39 011

+0.32 012

-0.39 009

-0.46 012

-0.39 009

-0.44 010

+0.64 012

-0.37 013

+0.32 011

-0.37 011

+0.34 012

-0.37 010

+0.61 010

-0.39 012

-0.39 009

-0.49 010

-0.39 010

+0.64 009

-0.46 010

-0.41 009

-0.46 011

-0.42 011

+0.34 012

-0.39 012

+0.30 009

-0.46 010

-0.41 011

+0.34 012

-0.39 012

+0.34 009

-0.49 010

-0.42 012

-0.39 010

+0.61 011

+0.29 010

-0.41 011

-0.42 011

+0.34 012

+0.32 010

-0.41 011

+0.34 012

-0.39 010

+0.64 009

-0.49 011

+0.32 009

-0.46 010

+0.61 009

-0.46 011

-0.39 012

+0.32 009

-0.46 011

+0.24 010

-0.41 011

-0.39 011

+0.34 010

-0.42 011

-0.42 012

-0.39 010

-0.41 010

+0.66 010

-0.42 012

+0.31 010

-0.39 010

-0.39 011

-0.37 012

-0.39 011

+0.32 011

-0.39 011

+0.34 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1 UTIL 2

WAR WAR WAR WAR WAR WAR 8

WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR 6

WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR 5

WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR 7

WAR WAR CAL #

84 86 86 86 86 86 84 86 84 84 84 84 86 86 84 84 86 86 86 86 84 84 84 84 86 86 84 84 84 86 86 84 84 84 84 84 86 86 86 86 86 84 84 84 84 84 86 84 84 84 86 86 86 86 86 86 84 84 86 86 86 84 84 86 86 86 84 84 84 86

.86 84 86 84 86 84 84 84 86 86 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB

510XB, 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:48 AM Component:

S/G A Page 96 of 97 ONSIAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 0.26 147 42 0.07 147 43 0.36 147 44 0.11 147 45 0.14 147 46 0.22 0.10 148 3 0.15 148 4 0.29 0.07 148 10 0.13 0.27 148 12 0.17 0.18 148 14 0.18 148 15 0.09 148 16 0.09 0.37 0.14 148 17 0.12 148 18 0.21 0.20 0.31 0.27 148 19 0.13 148 20 0.25 0.22 0.10 148 21 0.15 148 22 0.09 0.15 148 23 0.21 0.09 0.49 148 24 0.14 0.15 0.18 0.16 148 25 0.18 0.10 148 28 0.13 148 30 0.27 0.42 148 32 0.52 148 34 0.22 148 35 0.10 148 36 0.13 148 38 0.13 148 39 0.23 148 41 0.10 0.45 149 1 0.09 149 2 0.07 149 3 0.08 0.08 0.06 149 4 0.10 0.10 149 5 0.23 0.16 149 6 0.07 0.09 149 7 0.08 149 8 0.08 0.16 149 9 0.06 149 10 0.11 0.08 149 12 0.14 149 14, 0.13 149 16 0.11 149 17 0.09 149 19 0.06 149 20 0.12 149 21 0.14 149 25 0.47 149 26 0.06 149 28 0.10 0.10 0.12 DEG 142 148 143 138 136 143 148 137 141 75 145 138 142 138 135 137 146 129 138 141 147 134 142 127 143 148 147 90 107 121 125 141 148 135 142 142 141 145 144 116 156 141 137 134 135 149 131 126 145 143 140 103 142 149 129 140 128 147 136 135 144 128 145 144 142 127 141 138 149 134 154 146 154 89 121 131 149 137 146 139 CHN P2 P2 P2 P2 P3 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 17 TWD 5 TWD 21 TWD 8 TWD 10 TWD 15 TWD 8 TWD 11 TWD 18 TWD 5 TWD 9 TWD 17 TWD 11 TWD 12 TWD 12 TWD 7 TWD 7 TWD 21 TWD 10 TWD 9 TWD 14 TWD 13 TWO 18 TWD 17 TWD 9 TWD 16 TWD 14 TWD 7 TWD 11 TWD 7 TWD 10 TWD 14 TWD 7 TWD 26 TWD 10 TWD 10 TWD 12 TWD 11 TWD 13 TWD 8 TWD 9 TWD 17 TWD 23 TWD 27 TWD 14 TWD 8 TWD 9 TWD 9 TWD 15 TWD 8 TWD 25 TWD 7 TWD'5 TWD 6 TWD 6 TWD 5 TWD 7 TWD 7 TWD 15 TWD 11 TWD 5 TWD 6 TWD 6 TWD 6 TWD 11 TWD 5 TWD 8 TWD 6 TWD 10 TWD 9 TWD 8 TWD 7 TWD 5 TWD 9 TWD 10 TWD 25 TWD 5 TWD 8 TWD 8 TWD 9 LOCATION 012

-O.39 012

+0.34 011

+0.37 005

-0.36 014

-0.42 011

+0.39 012

+0.36 001

-0.27 011

+0.37 010

+0.61 009

-0.46 011

+0.37 011

+0.32 012

-0.37 010

+0.61 011

+0.32 009

-0.46 011

+0.34 012

-0.39 010

-0.39 011

-0.39 011

+0.32 012

-0.37 010

+0.59 012

-0.36 010

-0.39 012

-0.37 010

+0.61 010

+0.64 010

-0.39 010

+0.61 011

-0.39 011

+0.34 012

-0.37 009

-0.46 010

-0;39 011

+0.37 012

-0.37 010

-0.39 010

+0.61 011

-0.39 011

-0.37 012

-0.39 010

-0.37 011

-0.34 012

-0.39 010

-0.39 005

-0.39 011

+0.41 011

-0.37 011

+0.36 010

+0.64 008

-0.37 009

+0.63 010

+0.66 010

-0.37 009

+0.64 010

-0.34 011

+0.34 012

-0.37 011

+0.37 010

+0.62 010

-0.41 009

-0.44 010

-0.34 003

-0.34 010

-0.37 012

-0.37 010

-0.34 010

-0.39 010

+0.64 010

-0.37 012

-0.36 010

+0.68 010

+0.64 010

-0.37 011

-0.37 009

-0.41 010

-0.46 011

+0.39 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 86 INLET 86 INLET 84 INLET 86 INLET 10 84 INLET 86 INLET 86 INLET 86 INLET 84 INLET 84 INLET 84 INLET 84 INLET 84 INLET 84 INLET 10 84 INLET 86 INLET 84 INLET 84 INLET 84 INLET 86 INLET 84 INLET 84 INLET 84 INLET 84 INLET 86 INLET 84 INLET 84 INLET 84 INLET 86 INLET 4

84 INLET 84 INLET 86 INLET 86 INLET 86 INLET 84 INLET 84 INLET 84 INLET 3

84 INLET 86 INLET 86 INLET 4

84 INLET 84 INLET 84 INLET 84 INLET 84 INLET 3

86 INLET 4

84 INLET 84, INLET 86 INLET 86 INLET 86 INLET 84 INLET 84 INLET 86 INLET 86 INLET 0

86 INLET 84 INLET 7

84 INLET 86 INLET 86 INLET 84 INLET 84 INLET 86 INLET

84.

INLET 84 INLET 86 INLET 84 INLET 0

84 INLET 84 INLET 84 INLET 84 INLET 86 INLET 4

86 INLET 86 INLET 84 INLET 84 INLET 86 INLET 86 INLET 86 INLET 86 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

ý510XB 1510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:45:49 AM Component: S/G A Page 97 of 97 ONSlAR-EOC24 -

Tube QUERY: QueryMl[l]

Support Wear ROW TUBE VOLTS 149 29 0.11 149 32 0.10 0.33 149 33 0.14 150 1 0.16 150 2 0.08 150 3 0.16 0.20 150 4 0.07 0.09 150 6 0.06 150 7 0.14 0.19 150 8 0.12 150 10 0.14 150 11 0.10 0.15 150 13 0.13 150 15 0.18 0.15 0.13 0.14 0.22 150 16 0.20 150 17 0.10 150 20 0.09 150 23 0.12 0.19 0.09 0.22 150 24 0.07 0.06 0.06 150 27 0.13 0.16 0.22 151 1 0.14 151 2 0.07 0.30 0.08 151 3 0.29 0.10 151 4 0.15 0.14 0.14 151 5 0.36 0.09 0.16 151 6 0.22 0.28 0.61 151 7 0.32 0.23 0.18 0.12 151 8 0.18 0.18 151 9

0.17 0.78 0.13 0.11 151 10 0.23 0.21 151 12 0.12 151 13 0.14 0.11 151 14 0.43 0.29 151 16 0.12 0.06 DEG CHN 138 P2 142 P2 137 P2 147 P2 96 P2 127 P2 147 P2 118 P2 136 P2 147 P2 140 P2 133 P2 133 P2 139 P2 137 P2 129 P2 151 P2 133 P2 143 P2 144 P2 147 P2 141 P2 145 P2 135 P2 133 P2 137 P2 136 P2 143 P2 143 P2 146 P2 138 P2 101 P2 114 P2 135 P2 149 P2 143 P2 121 P2 136 P2 135 P2 98 P2 146 P2 128 P2 132 P2 137 P2 11 P2 140 P2 124 P2 108 P2 134 P2 137 P2 133 P2 142 P2 129 P2 139 P2 142 P2 141 P2 136 P2 146 P2 132 P2 147 P2 148 P2 138 P2 129 P2 144 P2 126 P2 105 P2 136 P2 134 P2 138 P2 139 P2 IND %TW TWD 8 TWD 7 TWO 20 TWO 9 TWO 11 TWO 6 TWO 11 TWO 13 TWD 5 TWD 7 TWD 5 TWO 10 TWO 13 TWO 9 TWD 10 TWD 7 TWD 10 TWO 9 TWO 12 TWD 10 TWD 9 TWO 10 TWO 14 TWO 14 TWD 7 TWD 7 TWD 8 TWD 13 TWD 6 TWO 14 TWO 6 TWO 5 TWD 5 TWD 9 TWO 11 TWO 15 TWO 10 TWD 5 TWD 19 TWD 6 TWD 18 TWD 7 TWD 11 TWD 10 TWD 10 TWD 21 TWO 7 TWO 11 TWD 15 TWD 18 TWD 30 TWD 19 TWD 15 TWD 12 TWO 9 TWD 13 TWO 13 TWO 11 TWD 34 TWD 9 TWD 8 TWD 15 TWD 14 TWD 9 TWO 9 TWD 8 TWD 24 TWD 18 TWD 9 TWO 4 LOCATION 012

-0.37 011

-0.34 012

-0.36 011

-0.37 010

+0*61 010

+0.68 010

-0.34 010

+0.59 004

-0.34 009

+0.61 008

-0.37 011

+0.37 012

-0.34 010

-0.37 010

-0.39 012

-0.37 013

+0.34 010

-0.34 008

-0.37 010

-0.39 011

-0.39 011

+0.34 012

-0.37 010

-0.39 010

-0.37 010

-0.37 008

-0.36 009

-0.41 011

+0.37 012

-0.37 009

-0.41 009

+0.61 005

-0.29 011

-0.37 011

+0.39 012

-0.36 010

+0.64 001

-0.26 011

+0.36 012

-0.34 010

-0.34 012

-0.34 009

-0.41 010

-0.34 010

+0.68 010

-0.37 009

-0.44 010

+0.59 011

-0.34 011

+0.39 012

-0.34 010

-0.34 010

+0.64 011

+0.39 012

-0.34 010

-0.37 010

+0.66 010

-0.44 011

-0.37 012

+0.36 012

-0.34 010

-0.39 010

+0.66 009

+0.61 011

+0.39 010

+0.64 011

-0.37 012

-0.32 008

-0.39 011

+0.34 EXT LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE EXT UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

84 86 86 84 84 86 84 84 86 86 86 84 84 86 86 5

84 6

84 84 84 84 84 84 84 86 84 86 84 84 84 84 86 86 86 86 86 86 84 86 86 86 84 84 86 86 86 84 5

84 84 86 86 86 84 84 84 84 86 86 84 84 84 3

84 86 86 4

86 84 84 86 86 86 86 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB S1OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB Total Tubes

4689 Total Records: 7750

AREVA NP Inc Customer Name: ONSi Repi 4/22/2008 9:48:01 AM Component: S/G B Page 1 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: Query~l[2]

ROW TUBE VOLTS 1

3 0.11 0.13 1

5 0.13 1

6 0.12 1

7 0.09 1

8 0.17 1

9 0.14 0.10 0.07 1

10 0.26 1

11 0.08 0.11 1

12 0.11 1

13 0.06 2

2 0.08.

2 6

0.13 2

12 0.09 2

16 0.11 2

17 0.11 3

1 0.18 3

2 0.09 0.10 3

8 0.12 0.10 3

18 0.09 3

19 0.13 3

20 0.12 3

21 0.16 3

22 0.16 3

23 0.13 3

24 0.10 3

26 0.16 3

28 0.17 4

1 0.10 4

2 0.08 4

6 0.08 4

13 0.08 4

15 0.10 4

16 0.18 0.13 4

17 0.10 4

18 0.17 0.14 0.13 4

19 0.14 4

20 0.16 0.13 4

22 0.14 4

25 0.11 4

29 0.17 4

31 0.13 4

32 0.20 0.11 4

33 0.18 0.06 4

36 0.13 4

37 0.12 5

1 0.11 5

8 0.10 5

13 0.13 5

16 0.08 5

17 0.09 0.11 5

18 0.09 0.10 5

19 0.09 5

20 0.13 5

21 0.10 5

23 0.10 0.10 0.09 5

24 0.28 0.14 0.14 5

25 0.11 5

26 0.21 0.12 0.08 5

27 0.47 0.09 DEG CHN 60 P2 146 P2 46 P2 119 P2 39 P2 128 P2 141 P2 53 P2 151 P2 133 P2 139 P2 48 P2 125 P2 158 P2 36 P2 59 P2 39 P2 53 P2 42 P2 140 P2 47 P2 147 P2 61 P2 145 P2 43 P2 63 P2 51 P2 68 P2 62 P2 55 P2 52 P2 69 P2 128 P2 51 P2 58 P2 43 P2 136 P2 131 P2 136 P2 74 P2 145 P2 142 P2 61 P2 148 P2 143 P2 153 P2 90 P2 60 P2 110 P2 109 P2 60 P2 137 P2 77 P2 134 P2 108 P2 92 P2 79 P2 77 P2 75 P2 87 P2 128 P2 140 P2 145 P2 144 P2 54 P2 130 P2 136 P2 139 P2 142 P2 140 P2 140 P2 133 P2 75 P2 135 P2 149 P2 126 P2 139 P2 137 P2 134 P2 144 P2 IND %TW TWD 7 TWD 8 TWD 8 TWD 6 TWD 6 TWD 8 TWD 9 TWD 7 TWD 5 TWD 11 TWD 6 TWD 7 TWD 5 TWD 4 TWD 5 TWD 8 TWD 6 TWD 7 TWD 7 TWD 9 TWD 6 TWD 7 TWD 7 TWD 6 TWD 6 TWD 7 TWD 7 TWD 7 TWD 10 TWD 8 TWD 7 TWD 10 TWD 10 TWD 5 TWD 5 TWD 5 TWD 4 TWD 5 TWD 11 TWD 8 TWD 5 TWD 10 TWD 9 TWD 8 TWD 7 TWD 10 TWD 8 TWD 9 TWD 7 TWD 10 TWD 8 TWD 9 TWD 6 TWD 11 TWD 4 TWD 6 TWD 8 TWD 6 TWD 6 TWD 7 TWD 5 TWD 5 TWD 6 TWD 6 TWD 6 TWD 5 TWD 8 TWD 5 TWD 5 TWD 5 TWD 5 TWD 16 TWD 9 TWD 9 TWD 6 TWD 12 TWD 8 TWD 5 TWD 19 TWD 5 LOCATION 010

+0.65 011

-0.31 010

+0.63 010

-0.27 010

+0.65 011

-0.32 011

-0.31 010

+0.65 011

+0.07 011

-0.34 011

-0.34 010

+0.67 011

-0.32 011

-0.34 010

+0.68 010

+0.68 010

+0.65 010

+0.67 010

+0.65 011

-0.29 010

+0.65 011

-0.31 010

+0.68 011

-0.31 010

+0.65 010

+0.68 010

+0.67 010

+0.67 010

+0.65 010

+0.65 010

+0.65 010

+0.65 010

-0.29 010

+0.71 010

+0.65 010

+0.65 010

-0.34 011

-0.34 009

-0.41 010

+0.63 009

-0.41 009

-0.41 010

+0.65 011

-0.39 009

-0.41 009

-0.43 010

+0.65 010

+0.68 010

+0.70 010

+0.68 010

+0.67 010

-0.33 010

+0.67 010

-0.33 011

-0.31 010

+0.65 010

+0.67 010

+0.69 010

+0.65 010

+0.66 011

-0.36 010

-0.31 011

-0.39 010

-0.34 010

+0.63 011

-0.34 010

+0.63 010

+0.66 009

+0.63 010

-0.34 013

+0.35 010

-0.34 010

+0.65 011

-0.36 010

-0.34 010

-0.34 010

+0.65 011

-0.36 010

-0.36 011

-0.36 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR WAR WAR WAR WAR 2

WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 7

WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR 3

WAR WAR WAR WAR 2

WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR WAR CAL #

36 36 36 38 36 38 36 36 36 38 36 36 38 36 32 36 36 36 36 34 32 32 32 32 32 34 32 38 36 36 36 36 40 34 32 32 34 34 32 32 34 32 32 32 34 32 32 32 40 40 40 42 42 40 40 42 40 34 32 34 32 34 34 32 32 34 32 34 34 34

.34 32 32 32 34 32 32 32 42 42 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXO 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 51OXE 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXS 510XB 510X3

AREVA NP Inc Customer Name: ONSi Repi 4/22/2008 9:48:01 AM Component: S/G B Page 2 of 74 ONSlBR-EOC24 -

Tube QUERY: QueryMl[2]

Support Wear ROW TUBE 5

28 5

30 5

31 5

33 5

34 5

35 5

36 6

1 6

4 6

5 6

6 6

7 6

8 6

10 6

15 6

18 6

19 6

20 6

21 6

23 6

24 6

25 6

26 6

27 6

28 6

29 6

30 6

31 6

34 6

35 6

36 6

37 6

38 6

39 6

41 6

51 7

15 7

18 7

19 7

20 7

21 7

25 7

28 7

30 7

31 7

32 VOLTS 0.19 0.09 0.09 0.11 0.09 0.22 0.13 0.13 0.10 0.11 0.13 0.09 0.14 0.11 0.09 0.11 0.10 0.07 0.09 0.15 0.11 0.15 0.09 0.15 0.18 0.09 0.14 0.12 0.08 0.08 0.09 0.07 0.20 0.14 0.13 0.20 0.21 0.16 0.32 0.45 0.33 0.21 0.10 0.12 0.14 0.16 0.19 0.16 0.13 0.16 0.12 0.96 0.52 0.28 0 14 0.11 0.13 0.16 0.13 0,12 0,12 0,28 0.11 0.09 0,16 0,09 0.10 0.11 0,12 0,13 0,13 0.15 0.31 0.13 0.09 0.17 0.11 0.14 0.09 0.13 DEG 133 50 49 133 140 127 142 116 78 127 56 52 72 59 49 56 53 141 81 137 135 142 59 147 120 97 136 115 104 72 47 142 149 137 144 137 141 129 141 139 142 115 148 146 142 134 136 135 147 141 127 129 132 138 103 133 85 146 137 141 92 144 128 134 145 129 80 141 152 143 128 132 133 87 140 139 102 132 133 148 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 11 TWD 6 TWD 6 TWD 7 TWD 5 TWD 10 TWD 8 TWD 6 TWD 6 TWD 7 TWD 7 TWD 6 TWD 7 TWD 7 TWD 5 TWD 7 TWD 7 TWD 5 TWD 5 TWD 9 TWD 6 TWD 8 TWD 5 TWD 9 TWD 11 TWD 5 TWD 7 TWD 6 TWD 5 TWD 5 TWD 6 TWD 5 TWD 12 TWD 7 TWD 7 TWD 12 TWD 10 TWD 8 TWD 15 TWD 19 TWD 18 TWD 12 TWD 7 TWD 7 TWD 9 TWD 10 TWD 9 TWD 10 TWD 7 TWD 8 TWD 6 TWD 34 TWD 20 TWD 16 TWD 7 TWD 5 TWD 6 TWD 8 TWD 7 TWD 8 TWO 6 TWD 15 TWD 7 TWD 5 TWD 8 TWD 6 TWD 6 TWD 9 TWD 8 TWD 8 TWD 8 TWD 9 TWD 14 TWD 6 TWD 5 TWD 10 TWD 7 TWD 7 TWD 6 TWD 8 LOCATION 010

-0.36 010

+0.67 010

+0.65 010

-0.36 010

-0.36 010

-0.36 010

-0.33 010

-0.33 010

+0.65 010

-0.33 010

+0.66 010

+0.66 010

+0.64 010

+0,63 010

+0.71 010

+0.66 010

+0.66 013

-0.37 010

+0.66 010

-0.34 010

-0.36 013

+0.35 010

+0.65 009

+0.63 010

+0.65 008

+0.31 010

-0.36 008

+0.31 008

+0.31 009

+0.63 010

+0.65 013

+0.36 014

-0.44 010

-0.36 010

+0.63 010

-0.34 009

-0.43 010

+0.61 013

+0.35 014

-0.47 010

-0.39 010

+0.63 011

-0.39 010

-0.34 010

-0.36 010

+0.63 010

-0.39 010

-0.36 009

+0.59 013

+0.34 010

+0.63 010

-0.36 010

-0.34 010

-0.34 010

+0.66 010

-0.37 010

+0.64 015

+0.59 010

-0.34 010

-0.36 010

+0.66 009

-0.41 010

-0.34 008

+0.26 010

+0.61 009

-0.43 009

+0.63 010

+0.63 013

+0.32 010

-0.36 010

-0.36 010

+0.60 010

-0.37 010

+0.66 009

+0.63 010

-0.36 010

+0.65 010

+0.63 008

+0.29 009

+0.63 EXT EXT UTIL 1

LTE==TE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL # LEG 40 INLET 40 INLET 40 INLET 4

40 INLET 4

42 INLET 42 INLET 40 INLET 42 INLET 40 INLET 4

40 INLET 34 INLET 32 INLET 34 INLET 32 INLET 34 INLET 32 INLET 32 INLET 32 INLET 34 INLET 32 INLET 34 INLET 34 INLET 5

34 INLET 32 INLET 32 INLET 3

34 INLET 3

34 INLET 34 INLET 32 INLET 32 INLET 32 INLET 32 INLET 32 INLET 34 INLET 34 INLET 32 INLET 34 INLET 34 INLET 34 INLET 34 INLET 32 INLET 32 INLET 40 INLET 4

40 INLET 40 INLET 40 INLET 42 INLET 40 INLET 42 INLET 42 INLET 6

42 INLET 40 INLET 42 INLET 40 INLET 42 INLET 3

42 INLET 42 INLET 42 INLET 34 INLET 32 INLET 34 INLET 32 INLET 32 INLET 34 INLET 34 INLET 32 INLET 32 INLET 32 INLET 32 INLET 0

32 INLET 40 INLET 40 INLET 42 INLET 42 INLET 42 INLET 40 INLET 40 INLET 42 INLET 40 INLET 40 INLET PROBE 510 XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

.510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

,510XB

.510XB 510XB 510XB 510XB 510XB 510XB

-510XB 510XB 51OXB 7

7 7

7 33 35 36 37

AREVA NP Inc Customer Name: ONSi Repi 4/22/2008 9:48:01 AM Component: S/G B Page 3 of 74 ONS1BR-80C24 -

Tube Support Wear QUERY: QueryMl(2]

ROW TUBE VOLTS 0.16 0.10 7

38 0.78 7

40 0.81 0.14 7

43 0.12 7

44 0.12 7

45 0.13 7

47 0.11 8

2 0.12 8

4 0.06 8

12 0.12 8

14 0.08 8

15 0.13 8

18 0.14

.8 19 0.21 8

20 0.12 0.10 0.16 8

21 0.09 0.18 0.11 0.16 0.23 0.06 8

22 0.08 0.13 0.13 8

23 0.11 0.11 0.13 8

25 0.15 8

29 0.11 8

30 0.10 8

32 0.24 8

33 0.11 0.12 0.08 8

34 0.07 0.10 8

35 0.11 8

36 0.15 0.41 8

37 0.16 0.09 8

39 0.24 0.16 0.08 8

41 0.12 0.14 0.14 8

42 0.20 8

43 0.10 8

44 0.12 8

45 0.14 8

46 0.13 8

47 0.10 8

48 0.14 8

49 0.09 8

50 0.09 0.10 8

51 0.08 8

52 0.10 8

53 0.09 9

4 0.10 9

10 0.09 9

11 0.09 9

13 0.09 9

14 0.15 9

15 0.15 9

16 0.12 9

19 0.21 9

20 0.11 9

21 0.24 0.12 9

22 0.15 0.20 0.10 9

23 0.10 0.13 DEG CHN 134 P2 154 P2 132 P2 128 P2 148 P2 133 P2 65 P2 67 P2 81 P2 46 P2 144 P2 130 P2 135 P2 140 P2 134 P2 136 P2 138 P2 61 P2 145 P2 136 P2 133 P2 142 P2 138 P2 121 P2 138 P2 137 P2 128 P2 149 P2 120 P2 148 P2 87 P2 132 P2 136 P2 110 P2 133 P2 141 P2 140 P2 103 P2 33 P2 147 P2 62 P2 145 P2 138 P2 134 P2 101 P2 137 P2 123 P2 102 P2 156 P2 89 P2 149 P2 142 P2 143 P2 141 P2 140 P2 124 P2 132 P2 72 P2 116 P2 130 P2 128 P2 56 P2 109 P2 51 P2 29 P2 130 P2 140 P2 127 P2 132 P2 139 P2 145 P2 137 P2 144 P2 137 P2 125 P2 143 P2 131 P2 144 P2 115 P2 140 P2 IND %TW TWD 10 TWD 6 TWD 27 TWD 32 TWD 9 TWD 5 TWD 8 TWD 6 TWD 5 TWD 7 TWD 4 TWD 7 TWD 5 TWD 7 TWD 9 TWD 10 TWD 8 TWD 6 TWD 10 TWD 5 TWD 9 TWD 6 TWD 8 TWD 11 TWD 3 TWD 5 TWD 8 TWD 8 TWD 6 TWD 6 TWD 7 TWD 8 TWD 6 TWD 6 TWD 14 TWD 6 TWD 6 TWD 4 TWD 5 TWD 7 TWD 5 TWD 9 TWD 21 TWD 8 TWD 5 TWD 11 TWD 8 TWD 4 TWD 8 TWD 9 TWD 9 TWD 12 TWD 5 TWD 8 TWD 7 TWD 8 TWD 5 TWD 9 TWD 5 TWD 6 TWD 6 TWD 4 TWD 6 TWD 5 TWD 6 TWD 6 TWD 5 TWD 5 TWD 9 TWD 8 TWO 8 TWD 10 TWD 7 TWD 11 TWD 6 TWD 9 TWD 12 TWD 7 TWD 5 TWD 7 LOCATION 010

+0.63 013

+0.34 010

-0.37 010

-0.36 013

+0.36 010

-0.34 010

+0.63 010

+0.63 010

+0.66 010

+0.66 013

-0.37 010

-0.32 010

-0.34 010

-0.37 010

+0.44 010

-0.36 010

-0.41 010

+0.63 011

+0.32 008

+0.31 009

-0.41 009

+0.61 010

-0.39 010

+0.63 011

+0.32 008

+0.29 010

-0.36 010

+0.53 008

+0.31 009

-0.43 010

+0.66 008

+0.29 010

-0.39 010

+0.63 010

+0.60 009

+0.59 010

+0.61 008

+0.27 009

+0.61 010

-0.41 010

+0.63 010

-0.39 014

-0.46 0n0

+0.61 008

-0.39 009

-0.44 010

+0.61 008

+0.27 009

-0.44 010

+0.65 010

-0.36 010

-0.39 010

-0.39 010

-0.36 010

-0.39 010

+0.63 010

-0.34 010

+0.65 010

+0.64 010

-0.36 010

+0.65 010

+0.71 010

-0.39 010

+0.64 010

+0.61 013

-0.44 010

-0.32 010

-0.29 010

-0.34 010

-0.34 010

-0.34 010

-0.36 010

-0.36 010

-0.39 010

+0.68 010

-0.39 010

+0.63 011

-0.36 008

+0.31 009

-0.43 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

40 3

40 42 40 40 4

42 40 42 42 32 32 32 0

32 34 32 34 32 32 32 34 34 34 34 34 34 32 32 32 34 34 34 34 3

34 32 40 42 42 42 40 40 42 40 40 42 0

42 42 42 42 40 40 3

40 40 3

42 40 42 40 0

42 40 42 40 40 42 40 42 32 32 34 34 32 34 32 34 32 34 34 32 32 32 34 34 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:01 AM Component: S/G B Page 4 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS DEG CHN 9

24 0.12 144 P2 9

26 0.09 148 P2 9

27 0.11 142 P2 9

30 0.10 144 P2 9

31 0.10 94 P2 9

34 0.08 60 P2 9

38 0.16 143 P2 9

39 0.08 135 P2 0.13 117 P2 9

40 0.11 122 P2 0.12 126 P2 0.10 126 P2 9

41 0.10 117 P2 0.11 140 P2 9

42 0.17 126 P2 0.16 141 P2 0.24 132 P2 9

43 0.13 143 P2 0.13 87 P2 9

44 0.25 139 P2 0.13 147 P2 9

45 0.16 142 P2 9

47 0.13 143 P2 9

48 0.30 135 P2 0.10 70 P2 0.09 113 P2 9

49 0.10 148 P2 0.13 97 P2 9

53 0.09 154 P2 9

54 0.14 96 P2 9

55 0.11 137 P2 9

57 0.13 115 P2 0.17 125 P2 9

58 0.12 133 P2 0.14 92 P2 9

61 0.06 27 P2 9

62 0.68

.136 P2 10 1

0.10 53 P2 10 4

0.10 52 P2 10 5

0.12 139 P2 0.12 56 P2 10 6

0.15 59 P2 0.09 139 P2 10 10 0.13 141 P2 10 12 0.08 136 P2 10 13 0.07 139 P2 10 14 0.09 63 P2 0.15 133 P2 10 15 0.10 145 P2 0.16 130 P2 0.12 144 P2 10 16 0.19 143 P2 0.28 126 P2 0.14 137 P2 10 19 0.19 146 P2 10 20 0.17 144 P2 10 21 0.16 131 P2 10 22 0.14 137 P2 0.08 149 P2 10 23 0.09 145 P2 0.20 121 P2 10 24 0.11 134 P2 0.46 133 P2 0.11 147 P2 0.14 145 P2 10 25 0.07 124 P2 10 26 0.10 147 P2 10 27 0.12 145 P2 10 30 0.11 147 P2 0.09 97 P2 10 33 0.09 53 P2 10 35 0.12 119 P2 10 37 0.14 142 P2 0.17 132 P2 10 41 0.11 134 P2 10 42 0.08 130 P2 10 43 0.10 107 P2 10 44 0.10 120 P2 0.11 144 P2 10 45 0.18 131 P2, IND %TW TWD 8 TWD 6 TWD 6 TWD 6 TWD 5 TWD 5 TWD 8 TWD 5 TWO 8 TWD 5 TWD 6 TWD 5 TWD 6 TWD 7 TWD 8 TWD 8 TWD 11 TWD 8 TWD 8 TWD 11 TWO 7 TWD 10 TWD 8 TWD 13 TWD 5 TWD 4 TWD 7 TWD 8 TWD 6 TWD 7 TWD 7 TWD 8 TWD 10 TWD 6 TWD 7 TWD 4 TWD 25 TWD 6 TWD 5 TWD 8 TWD 8 TWD 8 TWD 5 TWD 7 TWD 4 TWD 5 TWD 5 TWD 8 TWD 6 TWD 10 TWD 8 TWD 9 TWD 13 TWD 7 TWD 12 TWD 9 TWD 10 TWD 7 TWD 4 TWD 6 TWD 12 TWD 6 TWD 19 TWD 6 TWD 7 TWD 5 TWD 5 TWD 7 TWD 6 TWD 5 TWD 6 TWD 7 TWD 7 TWD 8 TWD 5 TWD 5 TWD 5 TWD 6 TWD 7 TWD 9 LOCATION 009

-0.44 010

+0.61 008

+0.31 008

-0.43 008

+0.26 009

+0.63 010

+0.61 008

+0.24 010

+0.58 008

+0.27

  • 010

+0.61 009

+0.64 008

+0.27 010

+0.61 008

+0.29 009

+0.61 010

-0.37 010

-0.39 010

+0.58 010

-0.39 010

+0.63 010

-0.39 010

+0.63 010

-0.37 010

+0.63 009

+0.59 010

-0.36 010

+0.63 010

-0.36 010

+0.66 010

-0.34 010

-0.34 010

+0.68 010

-0.32 010

+0.64 009

+0.65 015

+0.60 015

+0.67 010

+0.66 010

-0.32 010

+0.66 010

+0.66 011

-0.34 010

-0.34 013

-0.47 010

-0.34 010

+0.65 011

-0.39 010

-0.34 010

+0.65 011

-0.36 010

-0.36 010

+0.65 011

-0.36 010

-0.39 010

-0.41 010

-0.36 010

+0.60 011

+0.32 010

-0.38 010

+0.63 008

+0.29 009

-0.43 009

+0.60 010

-0.41 008

+0.24 008

+0.28 010

+0.63 014

-0.55 010

+0.60 010

+0.65 010

+0.63 010

-0.42 010

+0.63 010

+0.66 008

+0.29 008

+0.29 008

+0.29 010

+0.61 008

+0.27 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

UTIL 2

WAR WAR WAR WAR 4

WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR S

WAR WAR WAR WAR WAR 3

WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR S

WAR CAL # LEG 32--- INLET-32 INLET 32 INLET 34 INLET 32 INLET 34 INLET 32 INLET 42 INLET 40 INLET 40 INLET 42 INLET 42 INLET 42 INLET 40 INLET 40 INLET 42 INLET 42 INLET 42 INLET 40 INLET 40 INLET 42 INLET 42 INLET 40 INLET 40

'INLET 42 INLET 42 INLET 42 INLET 40 INLET 40 INLET 40 INLET 42 INLET 40 INLET 40 INLET 40 INLET 42 INLET 42 INLET 40 INLET 42 INLET 14 INLET 34 INLET 32 INLET 32 INLET 34 INLET 34 INLET 34 INLET 34 INLET 32 INLET 34 INLET 34 INLET 32 INLET 32 INLET 32 INLET 34 INLET 34 INLET 34 INLET 32 INLET 34 INLET 32 INLET 34 INLET 34 INLET 32 INLET 32 INLET 34 INLET 34 INLET 34 INLET 34 INLET 32 INLET 34 INLET 32 INLET 34 INLET 34 INLET 32 INLET 32 INLET 42 INLET 42 INLET 42 INLET 40 INLET 42 INLET

/

40 INLET 40 INLET 42 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:01 AM Component: S/G B Page 5 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 0.21 0.12 10 49 0.14 0.11 0.10 10 50 0.39 0.27 0.21 10 51 0.41 10 52 0.09 10 "53 0.13 0.11 10 56 0.07 0.13 10 57 0.14 10 58 0.10 0.15 10 59 0.17 0.08 10 61 0.10 0.12 11 6

0.09 11 9

0.16 0.09 11 10 0.17 11 11 0.13 11 12 0.12 11 13 0.16 11 15 0.12 0.12

-11 16 0.09 0.17 0.14 11 17 0.11 11 18 0.11 0.13 0.22 11 20 0.12 11 21 0.10 0.16 11 22 0.26 11 23 0.11 0.09 11 24 0.22 11 25 0.22 11 26 0.09 11 33 0.09 11 34 0.12 11 37 0.12 11 38 0.23 11 47 0.15 11 48 0.11 11 49 0.14 0.12 11 50 0.07 0.22 11 51 0.18 0.13 0.10 11 52 0.16 0.33 0.17 11 53 0.42 11 54 0.20 11 55 0.16 11 56 0.11 11 57 0.12 11 58 0.13 11 59 0:18 11 60 0.21 11 61 0.13 0.14 11 62 0.07 0.12 11 63 0.11 0.16 12 1

0.09 12 3

0.11 0.15 12 4

0.08 DEG CHN IND %TW 136 P2 TWD 10 144 P2 TWD 6 143 P2 TWD 7 134 P2 TWD 5 124 P2 TWD 5 138 P2 TWD 20 140 P2 TWD 15 124 P2 TWD 12 133 P2 TWD 17 149 P2 TWD 6 132 P2 TWD 7 96 P2 TWD 5 127 P2 TWD 5 107 P2 TWD 8 70 P2 TWD 7 117 P2 TWD 6 101 P2 TWD 9 132 P2 TWD 8 70 P2 TWD 4 80 P2 TWD 5 129 P2 TWD 6 133 P2 TWD 5 143 P2 TWD 10 50 P2 TWD 6 121 P2 TWD 9 85 P2 TWD 8 105 P2 TWD 6 133 P2 TWD 10 75 P2 TWD 7 153 P2 TWD 7 144 P2 TWD 5 137 P2 TWD 9 153 P2 TWD 7 112 P2 TWD 7 144 P2 TWD 6 90 P2 TWD 7 137 P2 TWD 11 134 P2 TWD 6 137 P2 TWD 6 147 P2 TWD 10 140 P2 TWD 12 145 P2 TWD 7 61 P2 TWD 6 138 P2 TWD 11 138 P2 TWD 13 120 P2 TWD 5 152 P2 TWD 6 147 P2 TWD 6 137 P2 TWD 8 142 P2 TWD 13 141 P2 TWD 7 152 P2 TWD 7 136 P2 TWD 7 151 P2 TWD 6 158 P2 TWD 5 142 P2 TWD 13 146 P2 TWD 9 132 P2 TWD 6 131 P2 TWD 5 145 P2 TWD 10 138 P2 TWD 17 140 P2 TWO 11 133 P2 TWD 17 141 P2 TWD 12 129 P2 TWD 8 138 P2 TWD 7 122 P2 TWD 6 93 P2 TWD 8 103 P2 TWO 9 101 P2 TWD 13 120 P2 TWD 6 96 P2 TWD 7 139 P2 TWD 5 46 P2 TWD 8 67 P2 TWD 6 137 P2 TWD 8 149 P2 TWD 5 113 P2 TWD 6 77 P2 TWD 8 54 P2 TWD 6 LOCATION 010

+0.61 013

-0.47 010

-0.39 008

+0.27 010

+0.64 009

-0.46 010

-0.41 010

+0.61 010

-0.39 010

-0.41 010

-0.39 010

+0.64 010

-0.36 010

+0.65 010

+0.66 010

-0.34 010

+0.65 010

-0.34 010

+0.71 010

+0.71 010

-0.37 010

-0.34 010

-0.36 010

+0.63 010

-0.37 010

+0.63 010

+0.68 010

+0.63 010

+0.63 011

-0.39 010

-0.36 010

+0.63 011

-0.46 010

+0.66 010

-0.36 010

+0.66 011

-0.44 010

-0.39 011

-0.41 014

-0.47 010

+0.65 010

-0.41 010

+0.63 009

-0.46 010

+0.61 008

+0.29 014

-0.49 010

-0.41 010

+0.63 010

+0.60 008

+0.29 008

+0.27 008

+0.24 010

+0.66 008

+0.29 010

-0.41 008

+0.27 010

+0.63 009

-0.46 009

-0.51 010

-0.41 010

+0.61 010

-0.39 010

-0.39 010

-0.41 010

-0.39 010

-0.37 010

+0.65 010

+0.63 010

+0.65 010

-0.34 010

+0.64 010

-0.34 010

+0.68 010

+0.66 010

-0.34 013

+0.39 003

-0.27 010

+0.66 010

+0.65 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL #

42 4

42 0

42 42 42 40 40 40 42 40 42 42 40 7

40 42 40 7

40 42 42 42 4

42 34 32 32 34 32 34 32 32 4

32 34 34 3

34 32 34 34 34 34 32 32 34 32 32 34 32 4

34 32 34 32 40 42 40 42 42 40 40 42 42 3

42 40 40 40 42 40 42 40 42 40 42 40 42 42 40 40 42 4

42 30 30 30 28 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB S1OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:01 AM Component: S/G B Page 6 of 74 ONSlBR-EOC24 -

Tube QUERY: QueryMl[2]

Support Wear ROW 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 TUBE 5

10 11 12 13 15 16 17 18 20 22 23 24 25 26 27 28 29 33 34 43 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 1

3 8

10 11 12 13 14 17 19 22 24 26 27 28 29 34 47 49 52 53 54 VOLTS DEG 0.16 80 0.09 148 0.18 140 0.10 79 0.14 112 0.10 154 0.12 132 0.10 52 0.11 132 0.09 137 0.09 127 0.10 122 0.09 143 0.12 137 0.10 149 0.10 148 0.13 129 0.23 140 0.10 133 0.09 130 0.07 51 0.17 146 0.08 134 0.10 155 0.18 142 0.11 145 0.11 148 0.13 147 0.11 146 0.12 147 0.12 128 0.07 142 0.09 139 0.07 129 0.12 139 0.09 131 0.15 151 0.13 138 0.12 142 0.22 134 0.14 138 0.16 136 0.12 137 0.16 120 0.11 113 0.10 142 0.16 130 0.19 129 0.17 84 0.24 105 0.13 102 0.11 147 0.17 142 0.10 136 0.10 138 0.09 126 0.15 149 0.12 124 0.09 /

53 0.16 il1 0.09 138 0.11 135 0.10 150 0.12 92 0.09 127 0.09 148 0.09 112 0.07 117 0.20 142 0.09 139 0.13 150 0.13 140 0.12 140 0.09 147 0.17 147 0.13 155 0.24 142 0.16 152 0.10 141 0.32 140 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWO 8 TWD 6 TWD 9 TWD 7 TWD 7 TWD 5 TWD 6 TWD 6 TWD 6 TWD 5 TWD 6 TWD 6 TWD 6 TWD 8 TWD 6 TWD 6 TWD 7 TWD 13 TWD 5 TWD 6 TWD 5 TWD 8 TWD 5 TWD 5 TWD 9 TWD 6 TWD 6 TWD 8 TWD 7 TWD 6 TWD 6 TWD 4 TWD 4 TWD 4 TWD 6 TWD 6 TWD 9 TWD 8 TWO 7 TWD 10 TWD 9 TWD 8 TWD 8 TWD 8 TWO 7 TWO 6 TWD 8 TWD 11 TWO 10 TWD II TWD 8 TWD 6 TWD 9 TWD 5 TWD 5 TWD 5 TWD 9 TWD 8 TWD 6 TWD 8 TWD 5 TWD 7 TWD 5 TWD 8 TWD 5 TWD 5 TWD 6 TWD 5 TWD 12 TWO 5 TWD 7 TWD 8 TWD 6 TWD 6 TWD 10 TWD 8 TWD 11 TWD 10 TWD 5 TWD 14 LOCATION 010

+0.66 013

-0.42 013

-0.47 010

+0.66 010

+0.65 011

-0.48 010

+0.63 010

.+0.61 010

+0.63 008

+0.26 008

+0.31 009

+0.61 008

+0.29 010

+0.63 009

-0.44 010

-0.39 009

-0.43 009

-0.46 008

+0.29 008

+0.29 010

+0.61 010

+0.61 008

+0.27 013

-0.49 014

+0.20 013

+0.25 010

-0.45 013

-0.52 014

+0.22 009

-0.51 010

+0.63 008

+0.24 008

+0.24 008

+0.27 008

+0.29 008

+0.27 009

-0.46 010

+0.63 010

-0.41 010

-0.42 010

-0.41 010

-0.42 010

-0.39 010

-0.39 010

+0.65 010

-0.36 010

-0.37 010

-0.34 010

+0.65 010

+0.66 010

+0.65 010

-0.34 002

-0.24 007

-0.39 007

-0.41 010

-0.34 01i

+0.32 009

+0.56 010

+0.66 010

+0.66 011

-0.42 009

+0.58 011

-0.39 010

+0.61 008

+0.34 008

-0.46 008

+0.31 008

+0.19 010

+0.58 008

+0.29 010

+0.58" 008

+0.24 008

+0.27 013

-0.52 014

-0.54 009

-0.46 014

-0.52 009

-0.46 008

+0.29 010

-0.44 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE'UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL # LEG 34 INLET 32 INLET 34 INLET 32 INLET 34 INLET 2

34 INLET 5

34 INLET 32 INLET 34 INLET 4

34 INLET 32 INLET 32 INLET 32 INLET 32 INLET 32 INLET 32 INLET 34 INLET 32 INLET 34 INLET 32 INLET 32 INLET 34 INLET 32 INLET 34 INLET 34 INLET 3

34 INLET 34 INLET 32 INLET 32 INLET 42 INLET 42 INLET 40 INLET 42 INLET 40 INLET 42 INLET 40 INLET 40 INLET 6

40 INLET 0

40 INLET 42 INLET 0

40 INLET 42 INLET

  • 3 40 INLET 42 INLET 40 INLET 3

40 INLET 42 INLET 40 INLET 40 INLET 42 INLET 40 INLET 42 INLET 30 INLET 30 INLET 30 INLET 30 INLET 32 INLET 32 INLET 32 INLET 34 INLET 34 INLET 32 INLET 4

34 INLET 32 INLET 34 INLET 34 INLET 32 INLET 32 INLET 32 INLET 34 INLET 34 INLET 32 INLET 34 INLET 32 INLET 40 INLET 40 INLET 42 INLET 40 INLET 42 INLET 42 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc.

Customer Name: ONSI Repl 4/22/2008 9:48:01 AM Component: S/G B Page 7 of 74 ONSIBR-EOC24 - Tube QUERY: QueryMl[2]

Support Wear ROW 13 13 13 13 13 13 13 13 13 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 TUBE 55 56 60 61 63 64 65 66 67 3

10 12 13 14 15 16 17 18 20 21 27 28 30 31 41 44 45 47 49 52 53 55 56 57 58 59 64 65 66 67 2

3 8

9 10 11 13 16 17 18 25 28 33 34 38 41 55 56 VOLTS 0.10 0.13 0.20 0.10 0.16 0.13 0.09 0.24 0.14 0.12 0.26 0.12 0.16 0.15 0.19 0.11 0.10 0.17 0.12 0.14 0.06 0.09 0.08 0.09 0.08 0.16 0.11 0.23 0.07 0.10 0.10 0.10 0.13 0.07 0.12 0.12 0.09 0.11 0.23 0.09 0.11 0.20 0.08 0.08 0.14 0.10 0.18 0.11 0.14 0.17 0.15 0.23 0.18 0.25 0.16 0.17 0.10 0.32 0.17 0.11 0.08 0.09 0.11 0.17 0.09 0.12 0.08 0.12 0.14 0.12 0.23 0.16 0.07 0.27 0.11 0.13 0.09 0.15 0.10 0.11 DEG 142 143 136 137 142 135 144 143 137 118 133 92 138 122 110 50 133 114 125 123 102 133 98 80 142 131 79 143 153 140 148 132 144 155 152 147 144 148 146 154 151 146 142 143 141 152 138 149 144 136 149 142 115 138 141 94 69 129 139 139 42 147 149 126 119 153 128 129 149 120 143 143 128 138 152 143 153 127 141 132 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 7 TWD 8 TWD 10 TWD 5 TWD 10 TWD 8 TWD 6 TWD 14 TWO 9 TWD 8 TWD 12 TWD 6 TWD 10 TWD 9 TWD 9 TWD 7 TWD 5 TWD 10 TWD 7 TWD 7 TWD 4 TWD 5 TWD 5 TWD 6 TWD 4 TWD 8 TWD 7 TWD 13 TWD 5 TWD 5 TWD 5 TWD 7 TWD 8 TWD 4 TWD 7 TWD 7 TWD 4 TWD 6 TWD 11 TWD 5 TWD 7 TWD 10 TWD 4 TWD 4 TWD 9 TWD 7 TWD 9 TWD 7 TWD 9 TWD 8 TWD 9 TWD 13 TWD 11 TWD 11 TWD 10 TWD 8 TWD 7 TWD 14 TWD 11 TWD 6 TWD 6 TWD 6 TWD 6 TWD 8 TWD 6 TWD 6 TWD 4 TWD 8 TWD 9 TWD 8 TWD 11 TWD 8 TWD 5 TWD 12 TWD 6 TWD 8 TWD 6 TWD 8 TWD 6 TWD 5 LOCATION 008

+0.29 010

-0.39 008

+0.29 010

+0.63 010

-0.39 013

+0.32 014

-0.46 014

+0.27 010

-0.36 010

+0.60 010

-0.37 010

+0.63 010

-0.34 010

+0.65 010

+0.66 010

+0.65 010

-0.34 010

+0.63 010

+0.63 010

+0.63 008

+0.27 008

+0.27 008

+0.29 010

+0.63 008

+0.32 010

+0.66 010

+0.63 014

-0.54 008

-0.48 008

-0.48 008

+0.26 008

+0.22 013

-0.52 009

-0.46 010

+0.58 009

-0.48 009

-0.49 009

-0.51 014.

-0.54 009

-0.51 009

-0.49 014

+0.24 008

+0.24 008

+0.22 008

+0.27 014

-0.49 008

+0.27 008

+0.29 010

-0.39 008

+0.27 009

-0.51 010

-0.36 010

+0.63 010

-0.37 010

-0.36 010

+0.63 010

+0.63 010

-0.32 013

+0.32 013

+0.30 010

+0.66 013

-0.47 013

+0.30 010

+0.64 013

+0.29 013

-0.49 008

-0.46 010

+0.61 014

-0.46 009

+0.63 014

-0.57 014

+0.15 008

+0.24 014

+0.17 013

+0.25 010

+0.53 010

+0.58 013

-0.60 010

+0.61 010

+0.63 EXT LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LIE EXT UTIL 1

UTIL 2

UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR 4

UTE WAR UTE WAR UTE WAR 4

UTE WAR 4

UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR 7

UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR 4

UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR 3

UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR 0

UTE WAR S

UTE WAR UTE WAR UTE WAR UTE WAR CAL 40 40 42 42 40 40 40 40 40 40 42 42 40 40 42 40 30 32 32 34 32 34 32 32 34 34 32 32 32 34 34 32 32 34 40 40 42 42 42 42 40 42 42 42 40 40 42 40 40 42 40 40 40 42 40 42 28 30 28 30 28 28 30 30 28 30 30 28 28 28 30 30 28 30 30 28 28 30 40 42

  1. LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 51*XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONS1 Repi 4/22/2008 9:48:01 AM Component: S/G B Page 8 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: Query~l[2]

ROW TUBE VOLTS 15 57 0.07.

15 58 0.11 15 60 0.10 15 61 0.26 15 64 0.20 0.15 15 66 0.12 15 67 0.36 15 68 0.28 15 69 0.11 0.18 15 70 0.14 15 73 0.09 15 78 0.33 16 3

0.15 16 5

0.08 16 7

0.10 16 8

0.15 0.17 0.11 16 11 0.11 0.16 0.07 16 13 0.14 16 15 0.19 16 16 0.12 16 17 0.07 16 18 0.13 16 21 0.47 0.31 16 24 0.09 0.19 16 25 0.15 0.19 0.12 16 28 0.17 16 37 0.12 16 39 0.26 0.10 0.18 16 42 0.11 16 45 0.09 0.11 0.27 16 47 0.10 16 50 0.15 16 51 0.15 16 52 0.16 16 54 0.14 16 55 0.15 16 58 0.53 16 60 0.17 0.13 16 61 0.10 16 62 0.11 16 66 0.08 0.39 0.18 0.18 16 67 0.10 0.11 0.19 16 68 0.09 16 69 0.36 0.06 0.14 16 70 0.23 16 71 0.20 0.10 16 73 0.12 16 81 0.52 17 3

0.12 17

.7 0.10 17 8

0.12 0.11 17 9

0.22 17 10 0.11 17 12 0.07 17 28 0.12 17 32 0.08 DEG 155 139 154 141 143 141 130 136 133 143 116 109 127 133 77 146 140 141 110 139 144 122 150 146 141 144 144 148 142 143 143 138 150 149 138 151 147 143 149 137 143 159 127 140 139 132 149 143 156 149 139 150 135 134 140 158 139 144 149 149 147 142 143 139 108 104 141 114 150 116 136 75 136 140 61 125 58 136 137 153 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWO 5 TWD 5 TWD 5 TWD 15 TWD 9 TWD 7 TWD 6 TWD 19 TWD 12 TWD 7 TWD 11 TWD 7 TWD 6 TWD 14 TWD 10 TWD 6 TWD 7 TWD 8 TWD 8 TWD 6 TWD 7 TWD 10 TWD 5 TWO 9 TWD 12 TWD 6 TWD 5 TWD 7 TWD 23 TWD 17 TWD 5 TWO 9 TWD 10 TWD 12 TWD 8 TWD 8 TWD 8 TWD 15 TWD 7 TWD 11 TWD 6 TWD 5 TWD 7 TWD 15 TWD 6 TWD 9 TWD 7 TWD 9 TWD 8 TWD 7 TWD 24 TWD 10 TWD 8 TWD 5 TWD 7 TWO 5 TWD 19 TWD 11 TWD 11 TWD 5 TWD 5 TWD 8 TWD 5 TWD 14 TWD 3 TWD 6 TWD 13 TWD 9 TWD 5 TWD 6 TWO 20 TWD 6 TWD 5 TWD 8 TWO 7 TWD 11 TWD 7 TWD 5 TWO 8 TWD 6 LOCATION 008

+0.29 008

+0.27 008

+0.29 009

-0.49 010

-0.41 010

+0.63 010

-0.41 010

-0.39 010

-0.39 010

-0.39 010

+0.63 010

+0.61 010

-0.36 015

-0.42 010

+0.63 013

-0.42 010

-0.37 009

+0.59 010

+0.68 011

-0.37 009

+0.63 010

+0.64 013

-0.47 010

+0.64 010

+0.61 010

+0.65 008

+0.29 010

+0.63 014

-0.51 014

+0.20 013

-0.57 014

-0.54 014

-0.54 014

+0.17 010

+0.58 010

+0.61 010

+0.24 010

+0.22 014

+0.12 014

-0.58 010

+0.27 009

-0.51 009

+0.22 010

-0.37 009

-0.51 014

-0.56 009

-0.53 009

-0.48 009

-0.46 009

-0.51 014

-0.56 010

-0.39 014

-0.51 008

+0.29 009

-0.46 008

+0.27 010

-0.36 014

+0.29 014

-0.49 008

+0.29 009

-0.48 010

-0.39 008

+0.29 010

-0.39 009

+0.65 010

+0.56 010

-0.32 010

+0.63 010

-0.36 010

+0.65 015

+0.57 010

+0.64 009

-0.41 009

+0.65 010

+0.63 010

+0.64 010

+0.65 008

+0.29 010

+0.58 011

-0.53 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE-LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 40 INLET 42 INLET 42 INLET 40 INLET 42 INLET 9

42 INLET 0

42 INLET 40 INLET 42 INLET 40 INLET 40 INLET 42 INLET 40 INLET 42 INLET 28 INLET 28 INLET 28 INLET 30 INLET 30 INLET 30 INLET 28 INLET 28 INLET 28 INLET 28 INLET 28 INLET 30 INLET 28 INLET 30 INLET 28 INLET 28 INLET 30 INLET 30 INLET 28 INLET 28 INLET 6

28 INLET 30 INLET 28 INLET 28 INLET 28 INLET 4

28 INLET 30 INLET 44 INLET 44 INLET 44 INLET 0

64 INLET 0

44 INLET 46 INLET 44 INLET 5

44 INLET 46 INLET 44 INLET 44 INLET 44 INLET 46 INLET 44 INLET 44 INLET 44 INLET 44 INLET 0

44 INLET 46 INLET 3

46 INLET 4

46 INLET 44 INLET 46 INLET 46 INLET 46 INLET' 44 INLET 46 INLET 0

46 INLET 42 INLET 42 INLET 24 INLET 24 INLET 26 INLET 26 INLET 24 INLET 26 INLET 28 INLET 28 INLET 28 INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB-510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:01 AM Component: S/G B Page 9 of 74 ONSIBR-EOC24 -

Tube QUERY: QueryMl[2]

Support Wear ROW TUBE VOLTS

1========

17 41 0.09 17 42 0.10 17 45 0.07 17 46 0.12 17 47 0.11 17 50 0.27 0.18 17 51 0.14 0.11 17 52 0.22 0.12 0.15 17 53 0.15 17 57 0.11 17 60 0.28 17 63 0.08 0.09 17 68 0.14 0.45 0.I0 17 69 0.10 0.29 17 70 0.18 17 71 0.20 17 72 0.10 0.17 17 73 0.16 17 74 0.12 0.13 17 75 0.09 0.13 17 76 0.10 0.10 17 77 0.19 17 79 0.16 18 4

0.10 0.16 18 8

0.10 0.12 0.11 0.14 0.12 18 9

0.13 0.14 0.15 0.07 18 10 0.22 18 17 0.17 18 19 0.24 0.18 18 23 0.11 18 24 0.16 18 27 0.17 18 30 0.17 18 34 0.10 18 35 0.10 18 36 0.10 18 39 0.10 0.12 18 40 0.09 18 42 0.17 18 44 0.13 18 47 0.23 18 48 0.14 18 54 0.14 18 56 0.15 18 57 0.13 18 58 0.18 0.15 18 60 0.07 18 63 0.12 18 68 0.15 18 70 0.14 18 71 0.14 18 72 0.17 0.11 18 73 0.22 0.16 18 74 0.10 0.16 DEG CHN 133 P2 155 P2 158 P2 156 P2 156 P2 142 P2 155 P2 154 P2 131 P2 143 P2 154 P2 131 P2 145 P2 152 P2 139 P2 149 P2 158 P2 153 P2 139 P2 137 P2 140 P2 142 P2 150 P2 137 P2 123 P2 108 P2 94 P2 141 P2 129 P2 139 P2 114 P2 148 P2 63 P2 106 P2 94 P2 127 P2 110 P2 136 P2 143 P2 81 P2 143 P2 143 P2 133 P2 148 P2 114 P2 141 P2 125 P2 142 P2 144 P2 145 P2 98 P2 148 P2 147 P2 141 P2 133 P2 154 P2 151 P2 150 P2 150 P2 136 P2 139 P2 145 P2 141 P2 138 P2 155 P2 142 P2 143 P2 150 P2 149 P2 124 P2 141 P2 140 P2 154 P2 150 P2 149 P2 119 P2 140 P2 88 P2 126 P2 112 P2 IND %TW TWD 5 TWD 7 TWD 4 TWD 6 TWD 7 TWD 11 TWD 8 TWD 8 TWD 7 TWD 9 TWD 6 TWD 7 TWD 9 TWD 7 TWD 12 TWD 5 TWD 5 TWD 6 TWO 17 TWD 5 TWD 6 TWD 15 TWD 8 TWD 11 TWD 5 TWD 8 TWD 10 TWD 6 TWD 6 TWD 6 TWO 8 TWO 5 TWO 5 TWD 11 TWD 9 TWO 7 TWD 10 TWD 7 TWD 8 TWO 7 TWD 9 TWD 8 TWD 7 TWD 7 TWD 8 TWO 4 TWD 13 TWD 11 TWD 14 TWD 11 TWO 8 TWD 8 TWD 11 TWD 8 TWD 5 TWD 7 TWD 5 TWO 7 TWO 8 TWO 5 TWO 8 TWD 6 TWD 10 TWO 8 TWD 8 TWD 9 TWD 8 TWD 11 TWD 9 TWD 5 TWD 7 TWO 9 TWO 8 TWO 8 TWO 10 TWD 7 TWD 13 TWD 9 TWD 6 TWD 10 LOCATION 009

-0.53 010

+0.22 009

-0.49 009

-0.54 009

-0.49 014

-0.59 014

+0.12 009

-0.49 010

-0.51 009

-0.54 010

+0.24 010

-0.44 009

-0.51 010

-0.44 014

-0.59 008

+0.22 009

-0.49 009

-0.49 014

-0.52 008

+0.29 008

+0.31 009

-0.44 010

-0.41 010

-0.34 010

-0.39 010

+0.63 010

+0.63 010

-0.36 010

+0.63 010

-0.41 010

+0.60 010

-0.39 010

+0.63 010

+0.67 010

+0.67 010

-0.36 010

+0.63 009

+0.60 010

-0.36 010

+0.63 011

-0.39 013

-0.44 009

+0.59 013

-0.44 010

+0.71 010

-0.32 010

+0.63 010

+0.58 014

-0.51 014

+0.17 010

+0.56 013

-0.54 010

+0.56 010

+0.19 010

+0.19 009

-0.51 010

+0.24 010

+0.22 010

-0.46 010

+0.19 010

+0.17 009

-0.52 009

-0.50 009

-0.49 009

-0.53 010

+0.26 014

-0.56 014

-0.56 014

+0.15 013

+0.17 010

-0.39 010

-0.41 014

-0.49 009

-0.46 010

-0.34 010

+0.65 010

-0.36 010

+0.65 010

-0.41 010

+0.58 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL I

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

30 28 44 46 44 46 46 44 4

44 46 46 3

46 44 2

44 46 44 44 46 46 46 44 44 2

46 44 46 46 44 46 46 44 44 46 46 44 44 5

26 26 26 26 26 26 26 24 24 24 24 26 28 28 28 28 30 28 30 30 28 30 28 3

28 30 30 30 48 44, 44 3

44 4

44 44 44 44 0

44 44 44 6

44 44 44 44 44 44 44 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB

,510XB

,510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510aXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:01 AM Component: S/G B Page 10 of 74 ONSlBR-EOC24 -

Tube QUERY: QueryMl[2]

Support Wear ROW 18 18 18 18 18 18 18 18 18 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 TUBE 75 76 77 78 79 80 82 83 84 8

9 i10 20 27 28 32 36 37 40 43 47 49 59 60 64 71 72 73 74 75 76 77 78 79 80 81 83 84 9

10 11 16 18 19 20 28 30 32 36 39 46 48 50 51 55 58 60 63 64 VOLTS DEG 0.15 118 0.10 123 0.13 133 0.17 112 0.10 140 0.13 125 0.15 114 0.14 54 0.14 108 0.18 138 0.13 148 0.17 105 0.09 144 0.14 150 0.11 120 0.07 155 0.08 145 0.08 139 0.21 139 0.12 147 0.17 140 0.06 105 0.08 152 0.12 144 0.11 146 0.21 139 0.36 138 0.07 139 0.08 140 0.12 138 0.12 148 0.29 137 0.17 142 0.23 141 0.22 150 0.09 137 0.14 153 0.14 142 0.26 138 0.08 157 0.29 139 0.09 133 0.15 134 0.18 130 0.19 132 0.11 45 0.16 106 0.13 103 0.07 149 0.11 128 0.10 116 0.14 106 0.14 69 0.13 132 0.16 120 0.11 131 0.10 149 0.08 135 0.09 149 0.18 129 0.17 144 0.22 151 0.13 151 0.26 147 0.12 144 0.07 151 0.18 131 0.07 144 0.12 140 0.07 154 0.23 144 0.12 154 0.10 156 0.12 139 0.24 131 0.20 143 0.07 163 0.42 139 0.28 137 0.13 148 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 9 TWD 6 TWD 8 TWD 10 TWD 6 TWD 8 TWD 9 TWD 8 TWD 6 TWD 10 TWD 9 TWD 11 TWD 5 TWD 7 TWD 6 TWD 4 TWD 4 TWD 4 TWD 13 TWD 6 TWD 11 TWD 4 TWD 5 TWD. 6 TWD 6 TWD 10 TWO 16 TWD 5 TWD 4 TWD 7 TWD 7 TWD 15 TWD 10 TWD 10 TWO 10 TWD 6 TWD 8 TWD 7 TWD 11 TWD 5 TWD 13 TWD 6 TWD 7 TWD 11 TWD 9 TWD 5 TWD 10 TWD 6 TWD 5 TWD 7 TWD 6 TWD 9 TWD 7 TWD 7 TWD 8 TWO 6 TWD 7 TWD 4 TWD 5 TWD 9 TWD 11 TWD 13 TWD 9 TWD 12 TWD 6 TWD 4 TWD 9 TWD 4 TWD 6 TWD 5 TWD 11 TWD 8 TWD 6 TWD 7 TWD 11 TWD 9 TWD 4 TWD 20 TWD 12 TWO 8 LOCATION EXT EXT 010

+0.58 LTE UTE 010

-0.41 LTE UTE 010

+0.60 LTE UTE 010

+0.60 LTE UTE 010

+0.67 LTE UTE 010

+0.60 LTE UTE 010

+0.60 LTE UTE 010

+0.70 LTE UTE 010

-0.36 LTE UTE 011

-0.34 LTE UTE 009

-0.53 LTE UTE 010

+0.60 LTE UTE 010

-0.37 LTE UTE 013

+0.15 LTE UTE 011

-0.39 LTE UTE 008

-0.39 LTE UTE 008

-0.46 LTE UTE 008

+0.24 LTE UTE 010

+0.58 LTE UTE 010

+0.24 LTE UTE 010

+0.22 LTE UTE 010

+0.24 LTE UTE 009

-0.51 LTE UTE

013,

-0.64 LTE UTE 013

+0.17 LTE UTE 014

-0.64 LTE UTE 014

+0.10 LTE UTE 008

+0.22 LTE UTE 010

+0.17 LTE UTE 009

-0.51 LTE UTE 009

-0.56 LTE UTE 014

-0.58 LTE UTE 014

+0.15 LTE UTE 010

-0.45 LTE UTE 009

-0.52 LTE UTE 008

+0.29 LTE UTE 009

-0.48 LTE UTE 008

+0.28 LTE UTE 010

-0.40 LTE UTE 010

-0.39 LTE UTE 010

-0.40 LTE UTE 010

-0.46 LTE UTE 010

+0.64 LTE UTE 010

+0.60 LTE UTE 010

-0.38 LTE UTE 010

+0.64 LTE UTE 010 i0.60 LTE UTE 010

+0.62 LTE UTE 010

-0.36 LTE UTE 010

+0.60 LTE UTE 010

-0.36 LTE UTE 010

+0.62 LTE UTE 010

+0.67 LTE UTE 010

-0.34 LTE UTE 010

+0.66 LTE UTE 011

-0.39 LTE UTE 010

-0.36 LTE UTE 009

-0.39 LTE UTE 014

-0.49 LTE UTE 010

+0.59 LTE UTE 013

+0.25 LTE UTE 014

-0:54 LTE UTE 014

+0.15 LTE UTE 014

-0.55 LTE UTE 010

+0.24 LTE UTE 010

+0.19 LTE UTE 014

-0.60 LTE UTE 010

+0.22 LTE UTE 010

+0.22 LTE UTE 010

+0.22 LTE UTE 014

-0.69 LTE UTE 009

-0.51 LTE UTE

.010

+0.19 LTE UTE 010

-0.46 LTE UTE 014

+0.07 LTE UTE 009

-0.55 LTE UTE 010

+0.19 LTE UTE 014

-0.68 LTE UTE 014

+0.15 LTE UTE 009

-0.51 LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG PROBE 44 44 44 44 44 44 4

44 44 46 44 26 26 24 24 3

24 26 24 24 28 30 28 28 28 30 30 30 30 28 30 44 44 44 44 48 5

48 44 44 48 48 44 48 44 48 44 48 48 44 48 44 44 44 44 48 24 24 24 26 24 30 8

30 28 28 28 30 30 30 30 30 2

30 3

28 30 5

44 44 0

44 48 48 44 44 48 4

44 INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

.510XB

AREVA NP Inc Customer Name: ONSI Reol 4/22/2008 9:48:01 AM Component: S/G B Page 11 of 74 ONSlBR-EOC24 -

Tube QUERY: QueryMl[2]

Support Wear ROW TUBE VOLTS 20 70 0.16 20 72 0.07 20 76 0.13 20 77 0.23 20 78 0.13 20 79 0.15 20 80 0.14 0.17 20 81 0.20 0.17 20 82 0.08 0.13 20 87 0.10 21 4

0.13 21 20 0.14 21 25 0.12 21 26 0.18 21 27 0.08 21 29 0.10 21 30 0.09 21 33 0.14 21 42 0.09 21 43 0.11 21 44 0.09 21 47 0.08 21 48 0.08 21 49 0.10 0.10 21 53 0.11 21 54 0.36 21 67 0.11 21 69 0.18 0.14 21 73 0.34 0.10 0.12 0.11 0.16 21 77 0.10 0.08 21 79 0.25 21 80 0.27 21 81 0.37 21 82 0.29 21 83 0.15 21 84 0.13 0.14 21 87 0.09 21 88 0.12 22 10 0.19 22 11 0.10 22 12 0.08 0.10 22 13 0.13 0.15 22 14 0.09 22 16 0.10 22 19 0.09 22 23 0.16 0.09 0.15 22 24 0.22 0.16 0.12 22 25 0.27 0.09 22 30 0.10 22 32 0.11 0.10 22 33 0.18 0.18 22 34 0.17 22 38 0.10 22 43 0.09 22 46 0.10 22 47 0.13 22 49 0.10 22 52 0.17 22 58 0.21 0.25 DEG CHN 147 P2 156 P2 136 P2 136 P2 144 P2 134 P2 139 P2 88 P2 117 P2 70 P2 148 P2 96 P2 51 P2 58 P2 102 P2 148 P2 143 P2 149 P2 138 P2 141 P2 148 P2 143 P2 145 P2 139 P2 137 P2 143 P2 146 P2 160 P2 134 P2 137 P2 157 P2 149 P2 154 P2 138 P2 150 P2 149 P2 152 P2 145 P2 145 P2 130 P2 132 P2 131 P2 132 P2 134 P2 133 P2 92 P2 136 P2 125 P2 92 P2 121 P2 72 P2 131 P2 148 P2 138 P2 134 P2 138 P2 116 P2 140 P2 148 P2 142 P2 150 P2 142 P2 135 P2 131 P2 143 P2 148 P2 117 P2 133 P2 138 P2 145 P2 142 P2 144 P2 138 P2 133 P2 143 P2 146 P2 141 P2 148 P2 139 P2 132 P2 IND %TW LOCATION TWD 9 009

-0.48 TWD 5 014

-0.54 TWD 8 010

-0.39 TWD 10 010

-0.40 TWD 8 010

-0.34 TWD 7 010

-0.41 TWD 8 010

-0.31 TWD 10 010

+0.65 TWD 9 010

-0.36 TWD 8 010 40.64 TWD 5 010

-0.41 TWD 8 010

+0.53 TWD 5 010

+0.67 TWD 8 010

+0.63 TWD 9 010

+0.58 TWD 6 014

+0.17 TWD 11 014

+0.17 TWD 4 010

+0.24 TWD 5 013

-0.64 TWD 6 010

+0.22 TWD 7 010

+0.19 TWD 6 009

-0.55 TWD 6 009

-0.55 TWD 6 009

-0.55 TWD 4 009

-0.62 TWD 6 009

-0.53 TWD 6 009

-0.56 TWD 6 010

-0.49 TWO 7 014

-0.61 TWD 15 014

-0.02 TWD 7 009

-0.51 TWD 11 009

-0.51 TWD 8 014

-0.54 TWD 18 009

-0.51 TWD 6 014

+0.19 TWD 7 010

-0.39 TWD 7 013

-0.54 TWD 10 014

-0.54 TWD 6 008

+0.29 TWD 5 011

+0.24 TWD 14 010

-0.36 TWD 12 010

-0.41 TWD 19 010

-0.36 TWD 13 010

-0.38 TWD 9 010

-0.34 TWD 6 010

+0.67 TWD 7 010

-0.38 TWD 5

-010

-0.36 TWD 5 010

+0.69 TWD 11 010

+0.63 TWD 5 010

+0.64 TWD 5 008

+0.27 TWD 6 013

-0.51 TWD 7 008

+0.29 TWD 8 010

+0.64 TWD 6 008

+0.29 TWD 5 013

-0.54 TWD 6 014

-0.54 TWD 10 013

-0.56 TWD 6 014

-0.56 TWD 10 014

+0.17 TWD 11 010

+0.24 TWD 8 013

-0.59 TWD 6 014

-0.57 TWD 16 014

-0.56 TWD 6 010

+0.24 TWO 5 010

+0.19 TWD 6 014

-0.59 TWO 5 010

+0.22 TWD 11 010

+0.19 TWD 11 013

-0.61 TWD 9 010

+0.19 TWD 5 013

-0.64 TWD 6 009

-0.55 TWD 5 008

-0.54 TWD 9 009

-0.53 TWD 7 010

-0.48 TWD 10 009

-0.56 TWD 12 014

-0.63 TWD 14 014

+0.07 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE'UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL # LEG PROBE 44 INLET 510XB 44 INLET 510XB 44 INLET 510XB 48 INLET 510XB 44 INLET 510XB 48 INLET 510XB 44 INLET 510XB 44 INLET 510XB 48 INLET 510XB 48 INLET 510XB 44 INLET 510XB 6

44 INLET 510XB 48 INLET 510XB 26 INLET 510XB 28 INLET 510XB 3

30 INLET 510XB 28 INLET 510XB 30 INLET 510XB 30 INLET 510XB 28 INLET 510XB 1

30 INLET 510XB 28 INLET 510XB 30 INLET 510XB 28 INLET 510XB 30 INLET 510XB 28 INLET 510XB 44 INLET 510XB 44 INLET 510XB 44 INLET 510XB 48 INLET 510XB 4

44 INLET 510XB 44 INLET 510XB 44 INLET 510XB 44 INLET 510XB 44 INLET 510XB 3

44 INLET 510XB 4

44 INLET 510XB 2

44 INLET 510XB 44 INLET 510XB 44 INLET 510XB 44 INLET 510XB 48 INLET 510XB 44 INLET 510XB 48 INLET 510XB 44 INLET 510XB 48 INLET 510XB 0

48 INLET 510XB 44 INLET 510XB 48 INLET 510XB 26 INLET 510XB 24 INLET 510XB 26 INLET 510XB 26 INLET 510XB 24 INLET 510XB 24 INLET 510XB 26 INLET 510XB 30 INLET 510XB 28 INLET 510XB 28 INLET 510XB 28 INLET 510XB 28 INLET 510XB 30 INLET 510XB 30 INLET 510XB 30 INLET 510XB 28 INLET 510XB 0

28 INLET 510XB 30 INLET 510XB 30 INLET 510XB 0

30 INLET 510XB 28 INLET 510XB 28 INLET 510XB 30 INLET 510XB 30 INLET 510XB 28 INLET 510XB 30 INLET 510XB 28 INLET 510XB 28 INLET 510XB 44 INLET 510XB 44 INLET 510XB 44 INLET 510XB

AREVA NP Inc Customer Name: 0NSI Repl 4/22/2008 9:48:01 Am Component:

S/G B Page 12 of 74 ONSlBR-EOC24 -

Tube QUERY: QueryMl[2]

Support Wear ROW TUBE VOLTS 22 65 0.27 22 66 0.31 22 72 0.20 22 73 0.40 0.24 22 77 0.18 0.41 0.08 22 80 0.08 0.45 22 81 0.10 0.43 22 82 0.11 22 83 0.06 22 84 0.10 22 85 0.31 0.10 22 86 0.17 22 87 0.13 0.14 22 88 0.10 22 89 0.10 0.08 22 90 0.08 0.13 23 3

0.11 23 9

0.19 0.11 23 10 0.12 0.12 23 13 0.09 23 16 0.10 23 18 0.13 0.08 23 19 0.12 23 23 0.13 23 25 0.10 23 26 0.15 23 27 0.15 23 31 0.17 0.14 23 32 0.08 23 36 0.12 0.10 23 40 0.10 23 47 0.11 23 48 0.28 23 52 0.12 23 54 0.15 23 56 0.07 0.16 23 61 0.23 23 67 0.21 0.11 23 68 0.32 23 69 0.13 23 77 0.07 23 79 0.10 23 80 0.35 0.15 0.10 23 81 0.09 0.16 0.12 23 82 0.18 0.72 23 83 0.15 0.16 0.27 23 85 0.07 0.09 23 86 0.26 23 87 0.18 23 88 0.24 0.10 23 89 0.10 23 90 0.09 24 2

0.10 24 8

0.10

.0.08 DEG CHN 136 P2 134 P2 145 P2 139 P2 141 P2 134 P2 141 P2 152 P2 154 P2 139 P2 135 P2 134 P2 146 P2 140 P2 134 P2 135 P2 60 P2 145 P2 57 P2 139 P2 74 P2 137 P2 59 P2 134 P2 72 P2 134 P2 147 P2 152 P2 136 P2 123 P2 130 P2 144 P2 155 P2 147 P2 140 P2 146 P2 147 P2 144 P2 137 P2 142 P2 150 P2 155 P2 147 P2 135 P2 142 P2 132 P2 137 P2 130 P2 148 P2 144 P2 145 P2 144 P2 148 P2 140 P2 142 P2 153 P2 138 P2 147 P2 136 P2 149 P2 139 P2 121 P2 151 P2 114 P2 144 P2 131 P2 134 P2 141 P2 136 P2 141 P2 133 P2 140 P2 136 P2 127 P2 100 P2 132 P2 133 P2 39 P2 150 P2 153 P2 IND %TW TWD 12 TWD 16 TWD 12 TWD 16 TWD 11 TWD 8 TWD 17 TWD 4 TWD 5 TWD 22 TWD 5 TWD 17 TWD 7 TWD 3 TWD 6 TWD 13 TWD 5 TWD 10 TWD 6 TWD 6 TWD 6 TWD 5 TWD 4 TWD 5 TWD 8 TWD 6 TWD 10 TWD 6 TWD 8 TWD 8 TWD 5 TWD 6 TWD 8 TWD 6 TWD 6 TWD 7 TWD 5 TWD 10 TWO 8 TWD 8 TWO 7 TWD 6 TWD 8 TWD 7 TWD 7 TWD 6 TWD 16 TWD 7 TWD 9 TWD 5 TWD 10 TWD 13 TWD 12 TWD 7 TWD 13 TWD 8 TWO 4 TWD 6 TWD 14 TWD 7 TWD 5 TWD 6 TWD 10 TWD 7 TWD 8 TWD 25 TWD 9 TWD 10 TWD 15 TWD 5 TWD 5 TWD 11 TWD 10 TWD 11 TWD 5 TWD 6 TWD 5 TWD 6 TWO 7 TWD 5 LOCATION EXT EXT 014

-0.02 LTE UTE 014

-0.58 LTE UTE 014

+0.17 LTE UTE 014

+0.17 LTE UTE 013

+0.17 LTE UTE 010

-0.45 LTE UTE 014

-0.51 LTE UTE 014

+0.24 LTE UTE 008

+0.29 LTE UTE 009

-0.43 LTE UTE 008

+0.24 LTE UTE 009

-0.48 LTE UTE 008

+0.29 LTE UTE 008

+0.26 LTE UTE 010

-0.36 LTE UTE 010

-0.40 LTE UTE 010

+0.64 LTE UTE 010

-0.31 LTE UTE 010

+0.66 LTE UTE 010

-0,36 LTE UTE 010

+0.62 LTE UTE 010

-0.36 LTE UTE 010

+0.64 LTE UTE 010

-0.31 LTE UTE 010

+0.62 LTE UTE 011

-0.42 LTE UTE 014

+0.27 LTE UTE 014

-0.44 LTE UTE 010

-0.36 LTE UTE 010

+0.63 LTE UTE 008

+0.27 LTE UTE 010

+0.60 LTE UTE 014

-0.51 LTE UTE 014

+0.20 LTE UTE 014.

-0.55 LTE UTE 013

-0.61 LTE UTE 010

+0.24 LTE UTE 010

+0.24 LTE UTE 013

-0:66 LTE UTE 010

+0.22 LTE UTE 013

-0.63 LTE UTE 009

-0.56 LTE UTE 009

-0.53 LTE UTE 014

-0.64 LTE UTE 009

'0.53 LTE UTE 009

-0.60 LTE UTE 014

+0.02 LTE UTE 008

+0.12 LTE UTE 014

-0.63 LTE UTE 014

+0.02 LTE UTE 014

-0.66 LTE UTE 014

-0.63 LTE UTE 010

-0.46 LTE UTE 010

+0.19 LTE UTE 009

-0.53 LTE UTE 009

-0.53 LTE UTE 008

+0.22 LTE UTE 009

-0.51 LTE UTE 010

-0.43 LTE UTE 014

-0.51 LTE UTE 009

-0.53 LTE UTE 008

+0.29 LTE UTE 009

-0.46 LTE UTE 010

-0.36 LTE UTE 013

+0.17 LTE UTE 014

-0.46 LTE UTE 008

+0.26 LTE UTE 009

-0.46 LTE UTE 010

-0.36 LTE UTE 008

+0.29 LTE UTE 010

+0.62 LTE UTE 010

-0.38 LTE UTE 010

-0.36 LTE UTE 010

-0.38 LTE CTE 010

+0.69 LTE UTE 010

+0.60 LTE UTE 010

-0.33 LTE UTE 010

+0.65 LTE UTE 011

-0.41 LTE UTE 013

-0.56 LTE UTE UTIL 1

UTIL 2

WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR 2

WAR WAR WAR WAR.

WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR 4

WAR 0

WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR CAL 48 44 44 48 48 48 48 48 44 44 48 48 44 48 44 48 48 44 48 48 44 48 48 44 44 24 24 24 26 26 24 26 28 28 30 30 30 28 30 30 30 28 28 28 28 30 28 44 44 44 44 44 44 44 48 44 44 44 48 48 48 44 44 44 48 48 44 44 44 44 44 48 44 48*

  • 48 44 48 26 26 26
  1. LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET

-INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONS1 Repi 4/22/2008 9:48:01 AM Component:

S/G B Page 13 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 0.08 0.16 24 9

0.13 0.14 0.11 24 11 0.10 24 13 0.10 24 15 0.12 24 17 0.28 0.15 0.17 0.26 0.09 24 18 0.09 0.10 24 23 0.16 24 24 0.17 24 25 0.13 24 28 0.10 24 30 0.11 24 35 0.07 24 39 0.15 24 43 0.13 24 44 0.12 0.10 24 46 0.13 24 47 0.13 24 49 0.10 24 52 0.09 0.09 24 62 0.10 24 68 0.20 24 69 0.25 24 72 0.11 0.10 24 73 0.15 24 76 0.26 24 79 0.12 24 80 0.10 24 81 0.29 24 82 0.10 24 83 0.22 24 85 0.10 24 86 0.08 24 88 0.16 24 89 0.26 0.09 24 90 0.08 25 3

0.13 0.14 25 9

0.10 0.10 0.11 25 10 0.09 0.12 25 12 0.16 25 17 0.15 25 18 0.10 0.13 0.12 25 23 0.08 25 24 0.17 0.20 0.12 25 25 0.21 0.20 25 33 0.10 25 34 0.05 25 38 0.07 25 50 0.25 25 59 0.12 25 64 0.18 25 66 0.13 0.19 25 69 0.62 25 70 0.24 0.15 25 71 0.11 0.08 25 74 0.13 DEG CHN 148 P2 115 P2 141 P2 123 P2 141 P2 147 P2 105 P2 137 P2 140 P2 142 P2 146 P2 145 P2 152 P2 141 P2 111 P2 150 P2 146 P2 130 P2 136 P2 145 P2 153 P2 153 P2 143 P2 146 P2 142 P2 127 P2 146 P2 149 P2 151 P2 153 P2 148 P2 140 P2 138 P2 155 P2 133 P2 143 P2 143 P2 150 P2 141 P2 129 P2 134 P2 140 P2 133 P2 132 P2 140 P2 142 P2 52 P2 155 P2 142 P2 65 P2 148 P2 139 P2 146 P2 134 P2 141 P2 94.

P2 150 P2 136 P2 151 P2 145 P2 157 P2 134 P2 140 P2 138 P2 143 P2 143 P2 146 P2 160 P2 153 P2 139 P2 149 P2 131 P2 150 P2 125 P2 135 P2 140 P2 153 P2 156 P2 132 P2 141 P2 IND %TW TWD 5 TWO 10 TWD I0 TWD 7 TWD 7 TWD 6 TWD 6 TWD 6 TWD 6 TWD 13 TWD 8 TWD 8 TWD 12 TWD 5 TWD 6 TWD 7 TWO 8 TWD 11 TWD 6 TWD 7 TWD 8 TWD 5 TWD 7 TWD 9 TWD 6 TWD 5 TWD 7 TWD 9 TWD 7 TWD 5 TWD 5 TWD 5 TWD 10 TWD 12 TWD 6 TWD 5 TWD 7 TWD 12 TWD 6 TWD 6 TWD 13 TWD 6 TWD 10 TWD 5 TWD 5 TWD 10 TWD 11 TWD 4 TWD 5 TWD 7 TWD 7 TWD 5 TWD 6 TWO 6 TWD 6 TWD 8 TWD 10 TWD 8 TWD 7 TWD 8 TWD 8 TWD 6 TWD 8 TWD 10 TWD 6 TWD 13 TWD 12 TWD 5 TWD 3 TWD 5 TWD 15 TWD 6 TWD 8 TWD 7 TWD 9 TWD 24 TWD 11 TWD 7 TWD 6 TWD 4 TWD 6 LOCATION 013

+0.32 010

+0.60 010

-0.39 010

+0.64 011

-0.39 008

+0.29 010

+0;64 010

+0.61 010

+0.58 013

-0.54 013

+0.17 014

-0.55 014

+0.17 013

-0.54 010

+0.46 010

+0.24 010

+0.24 013

-0.61 013

-0.64 013

-0.61 010

+0.19 014

+0.10 009

-0.56 013 70.66 009

-0.65 009

-0.55 009

-0.58 009

-0.58 010

-0.53 010

+0.02 010

-0.60 010

-0.48 010

-0.46 010

-0.46 010

+0.19 009

-0.53 014

-0.56 014

+0.22 010

-0.41 010

-0.43 010

-0.39 010

-0.40 008

+0.17 008

+0.29 010

-0.36 010

-0.38 010

+0.67 010

-0.38 011

-0.34 010

+0.66 009

-0.44 010

-0.39 012

-0.42 010

+0.61 011

-0.39 010

+0.58 014

-0.52 013

-0.59 014

-0.56 014

+0.15 010

+0.24 013

-0.61 014

-0.57 014

+0.12 010

+0.24 014

-0.56 010

+0.19 010

+0.19 010

+0,19 014

-0.68 009

-0.56 009

-0.63 014

+0.07 014

-0.63 009

-0.58 010

-0.48 010

+0.17 009

-0.55 010

+0.14 013

+0.19 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

26 6

26 24 24 24 24 24 24 30 30 30 30 30 28 28 30 28 30 28 28 28 0

573 28 0

573 4

573 30 28 28 50 50 0

573 50 50 1

50 3

50 4

50 50 50 44 0

48 44 48 48 44 44 48 48 44 24 24 24 24 24 26 26 26 3

24 26 26 26 28 30 30 30 28 28 30 28 28 28 50 4

573 50 3

50 50 50 50 50 50 50 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET.

INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB' 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Cuatomer Name: ONSI Repl 4/22/2008 9:48:01 AM Component: S/G B Page 14 of 74 ONSlBR-EOC24 -

Tube QUERY: QueryMl[2]

Support Wear ROW TUBE VOLTS 25 78 0,10 25 82 0.12 25 83 0.15 0.14 25 84 0.32 0.25 0.14 0.11 25 85 0.20 25 88 0.08 25 89 0.18 0.26 0.09 25 90 0.24 0.09 0.08 25 91 0.15 25 93 0.08 0.07 25 94 0.09 26 3

0.14 0.06 26 8

0.13 0.10 0.07 26 11 0.14 26 13 0.13 26 16 0.07 0.13 0.28 26 17 0.16 26 21 0.26 0.44 0.19 0.13 26 23 0.09 26 26 0.12 0.16 0.36 0.10 26 28 0.19 26 29 0.15 26 30 0.10 26 34 0.26 26 35 0.08 0.12 26 41 0.13 26 47 0.14 26 48 0.14 26 49 0.10 26 65 0.10 26 78 0.36 26 79 0.27 26 81 0.24 26 82 0.17 26 84 0.55 0.81 0.14 26 86 0.31 26 89 0.07 0.11 26 91 0.39 0.08 26 92 0.13 26 93 0.13 0.07 26 94 0.09 26 95 0.14 27 3

'0.08 0.12 27 6

0.10 27 7

0.09 27 8

0.19 27 10 0.15 27 11 0.15 0.10 27 12 0.09 27 17 0.10 0.15 0.18 DEG CHN 150 P2 146 P2 142 P2 135 P2 146 P2 144 P2 148 P2 142 P2 140 P2 147 P2 141 P2 145 P2 63 P2 140 P2 68 P2 100 P2 144 P2 148 P2 36 P2 58 P2 140 P2 142 P2 87 P2 147 P2 75 P2 148 P2 112 P2 143 P2 133 P2 140 P2 149 P2 142 P2 137 P2 151 P2 145 P2 141 P2 152 P2 151 P2 135 P2 150 P2 143 P2 148 P2 108 P2 137 P2 156 P2 141 P2 145 P2 137 P2 138 P2 140 P2 134 P2 142 P2 139 P2 143 P2 148 P2 135 P2 133 P2 141 P2 140 P2 142 P2 102 P2 129 P2 136.P2 142 P2 81 P2 132 P2 139 P2 75 P2 138 P2 98 P2 144 P2 150 P2 115 P2 146 P2 138 P2 139 P2 136 P2 50 P2 140 P2 147 P2 IND %TW TWD 5 TWD 6 TWD 7 TWD 7 TWD 14 TWD 12 TWD 7 TWD 5 TWD 10 TWD 4 TWD 9 TWD 12 TWD 5 TWD 11 TWD 5 TWD 4 TWD 7 TWD 4 TWD 4 TWD 5 TWD 7 TWD 3 TWD 8 TWD 7 TWD 4 TWO 7 TWD 7 TWD 5 TWD 8 TWD 16 TWD 8 TWO 12 TWD 18 TWD 9 TWD 7 TWD 4 TWD 8 TWD 10 TWD 20, TWD 7 TWD 9 TWD 10 TWD 5 TWD 12 TWO 5 TWD 8 TWD 9 TWD 7 TWD 9 TWD 5 TWD 5 TWD 16 TWD 12 TWD 14 TWD 8 TWD 21 TWD 28 TWD 7 TWD 14 TWD 5 TWD 7 TWD 20 TWD 5 TWD 7 TWD 8 TWD S TWD 5 TWD 9 TWD 5 TWD 8 TWD 5 TWD 6 TWD 10 TWO 8 TWD 9 TWD 7 TWD 5 TWD 7 TWD 10 TWD 11 LOCATION 014

-0.56 009

-0.50 010

-0.46 014

+0.22 013

+0.24 014

+0.22 009

-0.48 014

-0.51 010

-0.43 008

+0.26 010

-0.41 014

-0.44 010

+0.62 010

-0.38 010

+0.65 011

+0.24 010

-0.36 010

-0.36 010

+0.67 010

+0.64 011

-0.34 010

-0.34 010

+0.63 011

-0.41 010

-0.39 008

+0.27 010

+0.64 008

+0.27 013

-0.56 014

-0.56 013

-0.54 013

-0.59 014

-0.59 014

+0.12 013

+0.22 013

-0.59 010

+0.22 013

-0.61 014

-0.61 014

+0.02 010

+0.19 010

+0.17 013

-0.64 014

-0.67 010

-0.48 013

-0.61 009

-0.55 009

-0.60 009

-0.60 009

-0.58 014

-0.73 014

+0.15 014

-0.56 014

-0.55 014

-0.54 013

-0.54 014

-0.49 014

+0.22 009

-0.45 008

+0.28 010

+0.66 010

-0.40 011

+0.28 010

-0.45 010

+0.61 011

+0.26 010

-0.40 010

+0.66 010

-0.34 010

+0.65 010

-0.46 014

-0.42 010

+0.64 014

-0.49 010

+0.61 013

-0.49 010.

+0.61 010

+0.61 013

-0.59 014

-0.54 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE, UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL I

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 50 INLET 50

, INLET 50 INLET 50 INLET 50 INLET 50 INLET 0

50 INLET 4

50 INLET 50 INLET 50 INLET 50 INLET 50 INLET 50 INLET 50 INLET 50 INLET 50 INLET 50 INLET 50 INLET 50 INLET 50 INLET 24 INLET 24 INLET 26 INLET 26 INLET 26 INLET 24 INLET 24 INLET 26 INLET 26 INLET 26 INLET 24 INLET 30 INLET 30 INLET 30 INLET 0

30 INLET 30 INLET 28 INLET 28 INLET 28 INLET 4

28 INLET 30 INLET 28 INLET 5

573 INLET 30 INLET 28 INLET 28 INLET 28 INLET 30 INLET 28 INLET 4

573 INLET 3

573 INLET 50 INLET 50 INLET-52 INLET 54 INLET 54 INLET 54 INLET 54 INLET 54 INLET 52 INLET 52 INLET 52 INLET 52 INLET 54 INLET 52 INLET 52 INLET 54 INLET 52 INLET 26 INLET 26 INLET 24 INLET 26 INLET 24 INLET 24 INLET 26 INLET 26 INLET 24 INLET 26 INLET 26 INLET 26 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510OUL 51OUL 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51 0XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:01 AM Component: S/G B Page 15 of 74 ONSIBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW 27 27 27 27 2?

27 27 27 27 27 27 27 27 27 27 271 27; 27 27 27 27 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 29 29 29 29 29 29 29 29 29 29 29 TUBE 24 30 34 35 36 38 41 43 64 72 75 80 81 82 84 89 91 92 93 95 96 3

6 7

8 11 14 21 23 26 28 29 30 32 43 47 48 50 52 73 74 75 77 79 81 86 89 90 91 92 93 94 96 97 98 1

4 7

9 10 11 12 15 17 20 21 VOLTS 0.09 0.19 0.15 0.12 0.10 0.12 0.11 0.10 0.11 0.11 0.26 0.12 0.12 0.12 0.34 0.21 0.08 0.16 0.26 0.11 0.09 0.76 0.16 0.08 0.14

0. 17 0.11 0.16 0.13 0.15 0.14 0.12 0.11 0.14 0.07 0.11 0.07 0.34 0.19 0.09 0.12 0.16 0.24 0.20 0.15 0.14 0.14 0.12 0.15 0.08 0.13 0.12 0.12 0.17 0.49 0.13 0.15 0.11 0.11 0.49 0.07.
0. 14 0.27 0.16 0.08 0.11 0.24 0.17 0.64 0.16 0.11 0.14 o.10 0.16 0.11 0.10 0.15 0.11 0.08 0.12 DEG 142 136 143 144 140 140 129 145 150 152 143 150 146 144 138 142 101 142 141 144 43 133 121 119 138 135 140 96 148 129 142 146 152 138 146 138 154 137 123 149 149 127 127 143 132 138 134 130 147 145 149 146 147 146 138 143 138 151 149 139 87 136 140 134 145 66 137 143 128 133 142 142 144 147 154 151 148 142 127 122 CHN IND %TW LOCATION P2 TWO 5 009 P2 TWD 12 010 P2 TWD 10 013 P2 TWD 6 009 P2 TWD 7 010 P2 TWD 8 009 P2 TWO 7 009 P2 TWD 7 009 P2 TWD 5 014

+

P2 TWD 5 010 P2 TWD 15 009 P2 TWD 6 010 P2 TWD 6 010 P2 TWD 8 009 P2 TWD 15 014 P2 TWO 10 010 P2 TWD 6 010 P2 TWD 10 010 P2 TWD 12 010 P2 TWO 7 010 P2 TWD 6 010 P2 TWD 27 010 P2 TWD 8 010 P2 TWO 4 010 P2 TWO 7 010 P2 TWD 9.

010 P2 TWD 6 010 P2 TWD 8 010 P2 TWD 7 011 P2 TWD 8 010 P2 TWD 9 008 P2 TWD 6 013 P2 TWD 6 014 P2 TWD 9 013 P2 TWD 5 014 P2 TWD 5 014 P2 TWD 5 010 P2 TWD 17 014 P2 TWD 11 013 P2 TWD 5 009 P2 TWD 8 010 P2 TWD 10 009 P2 TWD 10 009 P2 TWD 9 014 P2 TWD 7 014 P2 TWD 9 009 P2 TWD 9 009 P2 TWD 8 009 P2 TWD 9 010 P2 TWD 5 010 P2 TWD 7 010 P2 TWD 6 013 P2 TWD 6 014 P2 TWD 10 014 P2 TWD 24 014 P2 TWD 8 014 P2 TWD 7 010 P2 TWD 7 009 P2 TWD 6 009 P2 TWD 24 014 P2 TWD 5 008 P2 TWO 7 010 P2 TWD 15 010 P2 TWD 9 010 P2 TWO 5 010 P2 TWD 7 010 P2 TWD 12 010 P2 TWD 9 015 P2 TWD 25 015 P2 TWD 8 010 P2 TWO 6 010 P2 TWD 7 011 P2 TWD 5 009 P2 TWD 8 014 P2 TWD 6 014 P2 TWD 5 013 P2 TWD 8 014 P2 TWD 6 014 P2 TWD 4 010 P2 TWD 8 013 0.53 0.19

-0.64

-0.56 0.17

-0.55 0.58

-0.58 0.00

-0.55

-0.55

-0.45

+0.19

-0.57

+0..17

-0.41

+0.66

-0.40

-0.36

-0.38

+0.66

-0.40

+0.66

-0.37

-0.39

-0.37

+0.05

+0.64

-0.39

+0. 64

+0.27

-0.56

-0.54

-0.61

+0.02

-0.68

+0.19

+0.00

-0.64

-0.60

+0.17

-0.60

-0.57

-0.73

+0.00

-0.60

-0.60

-0.63

-0.50

+0.14

-0.49

-0.54

+0.10

+0.12

-0.58

+0.15

-0.41

-0.52

-0.47

-0.46

+0.29

+0.60

-0.38

-0.37

-0.41

+0.66

-0.39

-0.37

+0.66

+0.53

-0.39

-0.39

-0.41

-0.49

+0.24

-0.53

-0.56

+0.17

-0.43

-0.61 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE OTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE OTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 30 INLET 28 INLET 28 INLET 30 INLET.

28 INLET 28 INLET 36 INLET 36 INLET 4

573 INLET 0

573 INLET 52 INLET 3

54 INLET 5

54 INLET 52 INLET 54 INLET 3

54 INLET 52 INLET 52 INLET 54 INLET 52 INLET 52 INLET 54 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24

INLET, 26 INLET 24 INLET 24 INLET 28 INLET 3

28 INLET 0

573 INLET 28 INLET 0

571 INLET 5

571 INLET 3

573 INLET 28 INLET 36 INLET 38 INLET 38 INLET 38 INLET 36 INLET 36 INLET 36 INLET 52 INLET 52 INLET 64 INLET 0

573 INLET 0

573 INLET 3

52 INLET 52 INLET 52 INLET 0

54 INLET 2

52 INLET 64 INLET 52 INLET 52 INLET 54 INLET 52 INLET 64 INLET 0

64 INLET 52 INLET 64 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24 INLET 24 INLET 26 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB "510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510UL 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:01 AM Component: S/G B Page 16 of 74 ONSIBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS DEG CHN 29 22 0.10 144 P2 29 23 0.24 130 P2 0.13 141 P2 0.33 135 P2 29 26 0.12 139 P2 29 28 0.12 145 P2 0;09 146 P2 29 29 0.25 121 P2 0.13 146 P2 29 30 0.13 144 P2 29 31 0.10 134 P2 29 32 0.12

\\ 147 P2 29 41 0.12 100 P2 29 42 0.11 120 P2 29 43 0.12 117 P2 29 44 0.16 138 P2 29 48 0.14 138 P2 29 54 0.09 113 P2 29 81 0.15 140 P2 29 82 0.12 137 P2 0.14 135 P2 0.08 150 P2 29 84 0.15 148 P2 0.31 138 P2 0.24 140 P2 29 85 0.17 145 P2 29 88 0.11 146 P2 29 91 0.13 144 P2 0.14 150 P2 0.06 65 P2 29 92 0.10 142 P2 0.10 141 P2 29 93 0.07 145 P2 29 95 0.13 147 P2 29 96 0.39 134 P2 29 102 0.12 132 P2 30 4

0.19 111 P2 30 6

0.08 130 P2 0.08 149 P2 30 7

0.09 146 P2 30 9

0.11 55 P2 0.13 147 P2 0.11 152 P2 30 14 0.09 143 P2 30 15 0.16 139 P2 0.31 142 P2 30 22 0.18 130 P2 0.08 156 P2 30 25 0.12 133 P2 30 36 0.19 127 P2 0.09 136 P2 30 39 0.08 146 P2 30 44 0.16 144 P2 30 46 0.11 143 P2 30 48 0.20 138 P2 30 52 0.10 142 P2 30 55 0.08 140 P2 0.10 153 P2 30 75 0.10 147 P2 30 78 0.22 142 P2 30 79 0.20 140 P2 30 82 0.09 151 P2 30 83 0.11 142 P2 30 84 0.12 140 P2 30 87 0.48 138 P2 0.11 155 P2 0.17 133 P2 30 88 0.18 146 P2 30 95 0.16 136 P2 0.12 152 P2 0.16 146 P2 30 97 0.33 139 P2 30 102 0.11 154 P2 30 105 0.25 149 P2 31 4

0.18 127 P2 31 7

0.22 137 P2 31 8

0.13 123 P2 31 9

0.17 126 P2 0.23

'145 P2 0.17 143 P2 IND %TW TWD 7 TWD 12 TWD 7 TWD 15 TWD 8 TWD 8 TWD 6 TWD 12 TWD 6 TWD 9 TWD 6 TWD 8 TWD 6 TWD 7 TWD 6 TWD 10 TWD 9 TWD 6 TWD 9 TWD 7 TWD 8 TWD 5 TWD 7 TWD 14 TWD 11 TWD 10 TWD 6 TWD 8 TWD 9 TWD 4 TWD 5 TWD 5 TWD 5 TWD 8 TWD 18 TWD 6 TWD 10 TWD 5 TWD 5 TWD 5 TWD 6 TWD 7 TWD 6 TWD 5 TWD 8 TWD 14 TWD 9 TWD 4 TWD 8 TWD 11 TWD 6 TWD 6 TWD 10 TWD 7 TWD 12 TWD 7 TWD 6 TWD 6 TWD 6 TWD 13 TWD 12 TWD 6 TWD 6 TWD 8 TWD 25 TWD 8 TWD 12 TWD 10 TWD 11 TWD 8 TWD 11 TWD 19 TWD 6 TWD 13 TWD 10 TWD 11 TWD 7 TWD 8 TWD 11 TWD 9 LOCATION 010

+0.24 013

-0.61 014

-0.62 014

+0.10 014

-0.61 013

-0.66 010

+0.17 014

-0.62 010

+0.20 010

+0.19 010

+0.10 009

-0.58 009

-0.58 009

-0.58 008

-0.57 009

-0.58 009

-0.62 009

-0.63 014

+0.12 009

-0.54 014

-0.54 014

+0.20 010

+0.24 014

-0.61 014

+0.10 014

+0.15 010

-0.42 010

+0.62 014

-0.50 008

+0.24 009

-0.47 014

+0.32 010

+0.62 010

-0.41 010

-0.37 010

-0.31 010

+0.68 010

-0.37 011

+0.32 010

-0.37 010

+0.65 011

-0.41 013

+0.29 008

+0.20 013

-0.56 014

-0.51 013

-0.61 009

-0.49 013

-0.62 009

-0.58 013

-0.64 008

+0.07 009

-0.63 009

-0.60 009

-0.60 009

-0.63 011

+0.07 014

-0.02 010

-0.48 010

-0.48 014

+0.05 010

+0.20 010

+0.25 010

+0.22 014

-0.48 014

+0.22 010

+0.62 014

-0.58 010

+0.64 011

-0.45 011.

+0.26 010

-0.36 010

-0.38 015

+0.65 010

+0.63 010

-0.39 010

+0.63 010

+0.63 011

+0.30 012

+0.29 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

28 30 30 30 28 28 4

28 30 0

30 28 0

571 28 38 36 38 36 36 36 52 64 64 64 54 54 54 52 2

64 52 52 52 64 0

64 52 52 64 54 64 64 0

64 24 24 24 24 64 20 20 30 30 28 36 5

36 3

561 36 36 36 36 36 4

36 52 52 52 5

599 6

601 0'

52 56 56 56 58 56 56 56 56 58 58 18 20 18 20 20 2

20 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510TUL 510XB 510XB 510XB 510XB 510XB/

510XB 510XB 510XB 510XB 51*0XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:01 AM Component: S/G B Page 17 of 74 ONSlBR-EOC24

- Tube Support Wear QUERY: QueryMl[2]

ROW 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 TUBE 11 12 14 15 19 20 22 25 28 29 32 37 38 40 42 44 46 47 48 49 52 70 73 82 84 85 86 87 89 90 93 96 97 98 99 105 106 1

3 4

7 8

9 10 13 14 15 20 22 23 24 29 34 35 41 43 45 46 47 VOLTS 0.14 0.11 0.14 0.24 0.14 0.19 0.10 0.13 0.16 0.10 0.11 0.12 0.10 0.14 0.12 0.11 0.17 0.15 0.09 0.07 0.12 0.06 0.18 0.18 0.27 0.10 0.09 0.13 0.07 0.14 0.14 0.11 0.11 0.26 0.08 0.51 0.20 0.17 0.15 0.36 0.09 0.13 0.12 0.13 0.07 0.10

0. 13 0.30 0.15 0.08 0.11 0.16 0.34 0.08 0.17 0.15 0.15 0.13 0.25 0.16 0.10 0.12 0.18 0.11 0.15 0.12 0.14 0.31 0.12 0.18 0.16 0.13 0.16 0.09 0.09 0.20 0.11 0.11 0.11 0.20 DEG 152 151 151 147 143 141 145 150 143 141 148 144 142 144 141 154 145 131 149 150 147 134 125 139 125 84 150 151 128 141 141 141 134 139 144 133 144 144 148 134 146 133 149 149 154 149 112 133 132 140 142 148 145 131 122 114 139 125 142 146 148 136 141 139 146 143 148 141 147 131 138 104 135 156 148 140 143 138 144 130 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWO 7 TWO 6 TWO 8 TWD 13 TWD 8 TWD 10 TWO 5 TWO 7 TWO 8 TWO 6.

TWO 6 TWO 8 TWO 5 TWO 9 TWD 6 TWO 8 TWO 8 TWO 7 TWO 6 TWO 5 TWO 8 TWO 5 TWO 8 TWD 11 TWD 12 TWD 5 TWO 6 TWO 9 TWO 5 TWO 9 TWO 9 TWO 7 TWD 7 TWO 15 TWO 5 TWO 24 TWO 12 TWO 11 TWO 10 TWO 19 TWO 6 TWO 8 TWO 8 TWD 8 TWD 5 TWO 6 TWO 8 TWO 17 TWO 9 TWO 5 TWO 7 TWO 9 TWO 17 TWO 5 TWO 9 TWD 8 TWO 7 TWD 7 TWO 13 TWO 9 TWO 5 TWD 7 TWO 10 TWO 6 TWO 8 TWO 6 TWO 8 TWO 15 TWD 6 TWO 9 TWO 10 TWO 6 TWO 7 TWO 6 TWO 6 TWO 12 TWO 7 TWO 5 TWO 7 TWO 9 LOCATION 013

-0.54 014

-0.54 013

-0.56 014

-0.51 014

-0.54 014

+0.22 010

-0.44 010

+0.58 010

+0.22 010

+0.24 013

-0.62 013

-0.64 013

-0.61 010

+0.19 013

-0.69 009

-0.58 014

-0.72 014

+0.02 010

+0.17 008

+0.17 008

+0.09 008

+0.07 009

-0.60 009

-0.60 009

-0.60 008

+0.12 014

-0.73 014

-0.05 008

+0.13 014

-0.70 014

+0.07 009

-0.53 013

-0.61 014

+0.15 009

-0.50 014

-0.60 010

-0.46 010

+0.19 013

+0.19 014

-0.56 014

+0.12 014

-0.53 009

-0.53 009

-0.50 009

-0.48 014

-0.48 010

+0.62 010

-0.38 010

-0.38 010

-0.33 011

+0.38 015

-0.39 015

+0.62 002

-0.41 010

+0.66 010

+0.66 010

-0.39 010

-0.36 014

-0.46 014

+0.27 009

-0.44 010

+0.61 011

-0.41 014

-0.54 010

+0.55 014

-0.56 010

+0.27 014

-0.61 010

+0.24 013

-0.64 013

-0.66 013

-0.56 009

-0.58 014

-0.71 013

-0.66 009

-0.65 009

-0.63 009

-0.60 009

-0.63 009

-0.60 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE.UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LIE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR-LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL #

20 20 18 18 18 18 20 20 20 18 18 26 4

573 28 6

573 28 38 38 36 36 7

561 3

561 38 36 38 3

38 36 4

559 12 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 6

52 52 52 52 52 58 58 12 20 18 20 18 18 18 20 18 18 3

20 7

18 20 64 18 30 30 28 5

573 38 36 5

36 36 36 38 36 38 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:48:02 AM Component: S/G B Page 18 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 0.13 32 48 0.13 32 54 0.10 32 59 0.12 32 60 0.11 0.11 32 76 0.13 0.09 32 77 0.09 32 81 0.19 32 85 0.23 0.21 32 86 0.19 32 89 0.10 32 91 0.28 0.08 32 92 0.10 0.15 32 93 0.14 32 94 0.16 32 95 0.07 0.21 0.14 0.12 32 96 0.08 32 98 0.10 32 99 0.30 32 100 0.27 0.10 32 101 0.30 32 102 0.10 32 106 0.12 33 3

0.19 33 4

0.23 33 7

0.12 0.27 33 9

0.09 33 10 0.24 0.10 33 12 0.10 33 13 0.26 0.24 0.32 33 19 0.14 33 22 0.21 33 38 0.11 33 39 0.14 33 40 0.10 0.12 33 41 0.10 0.07 0.11 33 44 0.11 0.14 33 48 0.08 33 50 0.13 33 51 0.11 33 52 0.13 33 75 0.15 0.07 33 80 0.12 33 82 0.10 33 85 0.15 33 88 0.09 33 90 0.09 0.09 33 93 0.20 0.10 0.19 33 94 0.12 0.13 0.14 33 96 0.09 33 97 0.13 33 98 0.08 33 99 0.11 33 101 0.18 33 102 0.32 33 103 0.22 33 107 0.31 DEG CHN 103 P2 141 P2 145 P2 149 P2 139 P2 138 P2 135 P2 145 P2 148 P2 143 P2 141 P2 149 P2 145 P2 155 P2 143 P2 155 P2 145 P2 143 P2 149 P2 142 P2.

152 P2 139 P2 142 P2 148 P2 143 P2 141 P2 141 P2 138 P2 143 P2 143 P2 117 P2 145 P2 143 P2 126 P2 131 P2 144 P2 47 P2 138 P2 144 P2 149 P2 146 P2 137 P2 139 P2 145 P2 137 P2 120 P2 136 P2 107 P2 135 P2 141 P2 139 P2 139 P2 129 P2 151 P2 161 P2 141 P2 101 P2 142 P2 101 P2 145 P2 138 P2 144 P2 147 P2 152 P2 153 P2 138 P2 148 P2 153 P2 139 P2 150 P2 142 P2 152 P2 143 P2 148 P2 126 P2 145 P2 146 P2 144 P2 148 P2 141 P2 IND %TW TWD 6 TWD 8 TWD 7 TWD 9 TWD 8 TWD 8 TWD 8 TWD 6 TWD 6 TWD 12 TWD 14 TWD 13 TWD 10 TWD 6 TWD 15 TWD 5 TWD 6 TWD 9 TWD 9 TWD 10 TWD 5 TWD 12 TWD 9 TWD 8 TWD 5 TWD 6 TWD 17 TWD 15 TWD 6 TWD 17 TWD 6 TWD 9 TWD 9 TWD 12 TWD 6 TWD 13 TWD 5 TWD 13 TWD 6 TWD 6 TWD 12 TWD 12 TWD 14 TWD 7 TWD 12 TWD 5 TWD 9 TWD 5 TWD 6 TWD 7 TWD 5 TWD 7 TWD 7 TWD 9 TWD 6 TWD 8 TWD 5 TWD 8 TWD 11 TWD 5 TWD 8 TWD 7 TWD 10 TWD 6 TWD 6 TWD 6 TWD 11 TWD 6 TWD 10 TWD 8 TWD 9 TWD 9 TWD 7 TWD 7 TWD 6 TWD 7 TWD 10 TWD 19 TWD 12 TWD 16 LOCATION 008

+0.14 009

-0.63 009

+0.10 009

-0.66 014

-0.10 010

+0.03 009

-0.58 010.

+0.14 009

-0.58 014

+0.07 014

-0.58 014

+0.12 010

-0.47 010

-0.47 014

-0.58 014

+0.17 010

-0.43 014

+0.19 009

-0.53 014

-0.53 009

-0.53 014

-0.48 014

+0.22 010

-0.43 008

+0.24 010

-0.40 010

-0.38 010

-0.38 011

+0.29 010

-0.36 010

-0.36 010

-0.31 011

-0.34 010

+0.63 010

-0.39 011

+0.30 010

+0.63 010

+0.60 014

+0.24 009

-0.46 013

-0.54 014

-0.54 014

+0.22 010

+0.22 014

-0.65 009

-0.58 009

-0.63 008

+0.15 009

-0.58 008

-0.55 008

+0.17 009

-0.63 009

-0.63 014

+0.00 008

+0.05 009

-0.63 008

+0.14 009

-0.62 014

-0.05 008

+0.13 014

-0.70 014

-0.58 014

+0.10 014

+0.15 010

-0.43 010

+0.21 013

+0.22 014

+0.19 010

+0.60 013

+0.24 014

+0.19 014

-0.53 009

-0.48 010

-0.38 008

+0.24 008

+0.26 010

-0.36 010

-0.36 010

-0.41 010

-0.29 EXT EXT LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR

'WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

3 38 36 36 6

8 8

52 52 52 52 56 56 58 0

58 58 58 52 52 52 52 52 52 52 4

52 52 3

52' 52 52 7

52 52 52 56' 20 18 20 20 20 18 18 18 20 20 20 20 18 38 36 38 38 36 4

36 6

36 36 36 3

561 36 38 36 10 10 52 56 56 56 56 4

56 58 58 6

58 56 56 0

56 56 58 56 58 58 56 58 58 LEG INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510xB 510XB 510XB 510XB 510XB 510XB 5'0OXB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:02 AM Component: S/G B Page 19 of 74 ONSIBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 34 2

0.09 34 3

0.10 34 4

0.14 34 8

0.34 0.18 34 10 0.32 0.21 0.13 34 11 0.15 0.16 0.20 34 12 0.12 34 13 0.15 34 14 0.17 0.25 0.21 0.29 34 23 0.28 34 30 0.08 34 33 0.13 34 36 0.14 34 41 0.11 34 42 0.11 0.10 0.09 0.20 34 44 0.19 34 45 0.13 34 46 0.12 34 48 0.23 0.11 34 49 0.09 34 50 0.12 0.12 34 53 0.08 34 55 0.08 34 56 0.15 34 63 0.09 34 74 0.09 34 85 0.09 34 89 0.06 0.11 34 90 0.35 34 92 0.08 34 98 0.08 34 102 0.11 34 103 0.19 34 105 0.06 34 106 0.15 34 108 0.16 35 4

0.21 0.17 35 5

0.17 35 6

0.25 0.13 35 8

0.15 35 10 0.10 0.28 0.12 35 11 0.11 35 34 0.10 35 40 0.11 35 41 0.23 35 42 0.12 0.19 35 43 0.16 35 45 0.12 35 47 0.08 35 49 0.15 0.12 35 50 0.08 0.13 35 64 0.09 35 66 0.08 35 67 0.08 35 71 0.08 35 72 0.07 35 76 0.07 35 100 0.09 0.09 137 P2 71 P2 118 P2 139 P2 144 P2 145 P2 141 P2 145 P2 147 P2 146 P2 147 P2 148 P2 138 P2 151 P2 130 P2 147 P2 137 P2 138 P2 137 P2 143 P2 132 P2 120 P2 149 P2 126 P2 148 P2 136 P2 128 P2 133 P2 138 P2 128 P2 94 P2 135 P2 125 P2 143 P2 117 P2 128 P2 127 P2 116 P2 137 P2 133 P2 153 P2 117 P2 138 P2 158 P2 147 P2 148 P2 148 P2 155 P2 142 P2 143 P2 127 P2 145 P2 137 P2 145 P2 142 P2 140 P2 143 P2 145 P2 137 P2 141 P2 157 P2 116 P2 128 P2 139 P2 126 P2 134 P2 145 P2 135 P2 120 P2 129 P2 149 P2 124 P2 131 P2 142 P2 131 P2 144 P2 137 P2 139 P2 147 P2 153 P2 TWD 6 TWO 5 TWO 8 TWO 17 TWD 10 TWD 16 TWD 11 TWD 8 TWD 8 TWD 8 TWD 10 TWO 7 TWO 7 TWD 9 TWO 13 TWO 12 TWO 15 TWD 14 TWD 6 TWD 8 TWD 9 TWD 5 TWO 7 TWD 6 TWD 6 TWD 12 TWD 9 TWD 8 TWO 8 TWO 10 TWO 5 TWD 6 TWD 8 TWD 8 TWD 6 TWD 5 TWD 9 TWO 7 TWD 8 TWO 6 TWO 5 TWO 8 TWD 20 TWD 6 TWD 5 TWO 8 TWO 10 TWD 4 TWD 10 TWO 11 TWO 10 TWO 8 TWO 10 TWO 12 TWO 6 TWD 7 TWD 5 TWD 13 TWD 6 TWD 6 TWD 7 TWD 5 TWD 14 TWO 6 TWO 9 TWD 10 TWD 8 TWD 5 TWD 7 TWD 6 TWD 6 TWD 8 TWD 7 TWO 7 TWO 6 TWO 7 TWO 5 TWO 6 TWO 6 TWD 6 008 010 010 010 011 014 014 011 013 014 014 013 014 013 013 014 014 014 008 009 009 008 011 008 009 009 009 009 009 009 008 009 008 009 008 008 009 008 008 011 008 014 014 010 010 010 010 010 010 010 010 011 011 014 014 010 013 014 014 008 014 009 009 008 009 009 009 008 009 008 008 009 008 008 008 009 009 008 008 009

+0.36

+0.64

+0.63

-0.39

+0.32

-0.46

+0.25

-0.44

-0.54

-0.51

+0.22

-0.42

-0.51

-0.54

+0.24

-0.56

+0.20

-0.63

-0.53

-0.60

-0.60

+0.14

-0.65

+0.14

+0.02

-0. 65

-0.65

-0. 63

-0.62

-0.62

+0.12

-0.63

+0.14

-0.62

+0.07

+0.07

-0.

63

+0.18

+0.10

-0.60

+0.15

-0.58

-0.65

-0.44

-0.36

-0.43

-0.36

-0.43

-0.38

-0.28

+0.64

-0.37

-0.41

-0.47

+0.25

-0.39

-0.54

-0.49

+0.22

+0.27

-0.71

-0.62

-0.65

-0.60

-0.62

-0.63

-0.62

+0.05

-0.64

+0.14

+0.14

-0.65

+0.10

+0.08

+0.08

+0.05

+0.03

+0.13

+0.29

-0.48 LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR

,WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 10 20 18 18 18 18 18 4

18 20 20 20 5

18 4

20 18 18 18 18 18 28 36 36 38 36 4

36 4

36 36 38 36 36 38 0

38 36 36 36 3

561 4

561 36 10 10 56 56 56 56 56 56 56 58 58 56 56 20 20 18 20 20 20 20 20 20 18 36 38 36 38 38 36 36 3

561 38 3

38 36 36 10 10 12 10 12 10 56 56 INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:02 AM Component: S/G B Page 20 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2)

ROW TUBE VOLTS 0.12 0.06 35 102 0.20 35 103 0.16 35 104 0.21 35 105 0.09 35 106 0.08 35 107 0.23 35 108 0.30 0.19 36 5

0.16 36 9

0.63 0.10 0.11 36 11 0.14 0.11 0.12 36 18 0.15 36 19 0.12 36 23 0.22 36 26 0.18 36 27 0.24 36 31 0.16 36 35 0.09 36 42 0.18 36 43 0.14 0.12 36 44 0.19 36 45 0.11 36 46 0.15 36 50 0.13 36 54 0.11 36 78 0.12 36 85 0.14 36 94 0.09 0.11 36 98 0.10 0.06 36 100 0.13 36 105 0.19 36 106 0.11 0.09 36 107 0.10 36 108 0.16 36 109 0.31 0.10 36 110 0.26 36 111 0.12 37 6

0.17 37 9

0.31 37 11 0.15 37 13 0.10 37 15 0.21 0.25 0.28 37 16 0.18 0.17 0.22 0.36 0.21 37 42 0.14 37 43 0.14 37 44 0.15 37 45 0.11 37 48 0.15 37 54 0.08 37 69 0.06 37 75 0.09 37 82 0.10 37 91 0.13 37 97 0.10 0.15 37 100 0.10 37 103 0.14 37 106 0.13 37 108 0.09 37 109 0.20 0.11 37 110 0.13 37 111 0.25 DEG CHN 153 P2 156 P2 135 P2 151 P2 141 P2 149 P2 130 P2 147 P2 141 P2 145 P2 113 P2 133 P2 128 P2 127 P2 146 P2 140 P2 142 P2 134 P2 147 P2 135 P2 144 P2 146 P2 140 P2 150 P2 129 P2 130 P2 131 P2 124 P2 145 P2 131 P2 131 P2 124 P2 153 P2 153 P2 153 P2 147 P2 130 P2 143 P2 140 P2 120 P2 152 P2 126 P2 137 P2 145 P2 139 P2 147 P2 146 P2 149 P2 140 P2 137 P2 147 P2 137 P2 136 P2 139 P2 142 P2 141 P2 138 P2 135 P2 140 P2 144 P2 121 P2 132 P2 115 P2 130 P2 136 P2 138 P2 138 P2 143 P2 150 P2 137 P2 150 P2 151 P2 144 P2 140 P2 147 P2 141 P2 146 P2 151 P2 145 P2 145 P2 IND %TW TWD 8 TWO 5 TWO 13 TWO 9 TWD 13 TWD 5 TWD 6 TWO 12 TWD 18 TWD 13 TWD 8 TWD 24 TWD 5 TWD 6 TWD 7 TWD 6 TWD 6 TWD 8 TWO 6 TWD 12 TWD 9 TWD 14 TWD 10 TWO 6 TWO 8 TWD 9 TWD 8 TWO 8 TWD 7 TWD 9 TWO 8 TWO 7 TWD 9 TWD 10 TWD 6 TWO 8 TWO 7 TWO 5 TWO 9 TWD 10 TWD 8 TWD 6 TWO 6 TWO 11 TWO 16 TWD 6 TWD 16 TWD 7 TWD 9 TWO 15 TWO 9 TWO 6 TWD 11 TWD 13 TWD 14 TWD 9 TWO 9 TWD 11 TWO 16 TWO 10 TWD 6 TWO 9 TWO 7 TWO 7 TWD 9 TWD 6 TWD 5 TWD 7 TWD 6 TWD 9 TWO 6 TWD 9 TWO 7 TWO 8 TWO 9 TWO 6 TWO 11 TWD 6 TWO 9 TWO 13 LOCATION 014

-0.46 014

+0.22 010

+0.62 013

-0.46 010

-0.34 010

-0.41 010

-0.38 010

-0.38 010

-0.31 01

+0.39 010

+0.63 010

-0.39 010

+0.00 011

+0.30 012

-0.47 010

-0.39 013

+0.24 010

+0.24 010

+0.22 014

-0.63 010

+0.20 014

-0.63 009

-0.58 008

+0.09 009

-0.60 009

-0.62 008

-0.60 009

-0.65 009

-0.62 009

-0.62 009

-0.65 009

-0.62 014

-0.79 014

+0.00 010

-0.46 010

+0.22 014

-0.56 014

+0.19 014

-0.51 010

+0.65 010

-0.36 011

+0.31 010

-0.33 010

-0.38 010

-0.38 011

+0.34 010

-0.31 011

+0.38 011

-0.46 010

-0.39 013

-0.56 011

-0.48 013

-0.56 014

-0.56 014

+0.17 010

-0.46 013

-0.61 013

+0.22 014

-0.58 014

+0.17 009

-0.62 009

-0.63 009

-0.62 009

-0.63 009

-0.65 008

+0.05 008

+0.05 009

+0.05 014

-0.05 013

-0.63 010

. +0.26 010

-0.46 009

-0.48 014

+0.24 010

-0.34 010

-0.41 010

-0.41 011

+0.34 010

-0.41 010

-0.31 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE CTE CTE LTE LTE CTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE CTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE CTE LTE UTE LTE LTE CTE LTE UTE LTE UTE LTE UTE LTE UTE LTE CTE LTE UTE LTE UTE LTE uTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 56 INLET

56.

INLET 56 INLET 58 INLET 56 INLET 58 INLET 56 INLET 58 INLET 56 INLET 56 INLET 20 INLET 20 INLET 20 INLET 5

20 INLET 20 INLET 4

20 INLET 3

20 INLET 18 INLET 20 INLET 18 INLET 30 INLET 28 INLET 36 INLET 3

561 INLET 38 INLET 36 INLET 4

36 INLET 38 INLET 36 INLET 36 INLET 36 INLET 36 INLET 10 OUTLET 56 INLET 56 INLET 56 INLET 56 INLET 56 INLET 56 INLET 58 INLET 56 INLET 4

56 INLET 58 INLET 56 INLET 58 INLET 58 INLET 56 INLET 58 INLET 20 INLET 18 INLET 18 INLET 18 INLET 18 INLET 18 INLET 0

18 INLET 20 INLET 20 INLET 20 INLET 20 INLET 20 INLET 38 INLET 36 INLET 38 INLET 36 INLET 36 INLET 4

561 INLET 10 OUTLET 10 OUTLET 6

571 INLET 56 INLET 58 INLET 0

58 INLET 56 INLET 58 INLET 56 INLET 56 INLET 58 INLET 58 INLET 56 INLET 58 INLET PROBE 510 XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510BL 510UX 510XB 510XB 510XB 510XB 510XB 510XB 5iOXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510CL 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:02 AM Component: S/G B Page 21 of 74 ONSIBR-EOC24 Tube QUERY: QueryMl[2]

Support Wear ROW TUBE VOLTS

=

1=====

38 1

0.15 38 5

0.18 0.09 38 9

0.15 38 14 0.24 38 16 0.15 0.13 38 19 0.13 0.13 38 30 0.08 38 41 0.08 38 45 0.18 38 49 0.09 0.08 38 51 0.06 38 56 0.14 38 76 0.07 38 98 0.06 38 99 0.12 0.10 0.09 38 100 0.15 38 104 0.09 0.19 38 106 0.16 38 107 0.16 0.09 0.13 38 108 0.25 38 109 0.22 38 110 0.24 38 I11 0.29 0.10 38 112 0.23 38 113 0.17 39 6

0.08 39 8

0.23 0.16 0.10 39 9

0.25 39 10 0.13 0.15 0.18 0.11 39 12 0.18 0.15 0.10 39 13 0.13 39 14 0.21 0.15 0.09 39 16 0.22 0.43 39 18 0.15 39 30 0.09 39 43 0.20 0.09 39 46 0.17 39 49 0.06 39 51 0.09 39 93 0.08 0.15 39 97 0.50 0.16 39 102 0.17 0.05 39 105 0.10 39 107 0.24 0.19 0.09 0.26 39 108 0.45 0.09 39 109 0.20 39 110 0.21 39 112 0.26 39 113 0.16 0.27 39 114 0.15 40 9

0.16 DEG CHN 118 P2 124 P2 125 P2 141 P2 141 P2 134 P2 144 P2 142 P2 137 P2 147 P2 122 P2 125 P2 141 P2 153 P2 126 P2 145 P2 144 P2 155' P2 120 P2 148 P2 152 P2 135 P2 119 P2 136 P2 133 P2 152 P2 155 P2 146 P2 144 P2 140 P2 141 P2 145 P2 147 P2 139 P2 146 P2 128 P2 142 P2 142 P2 137 P2 132 P2 137 P2 137 P2 142 P2 151 P2 131 P2 141 P2 150 P2 139 P2 147 P2 144 P2 137 P2 145ý P2 131 P2 134 P2 144 P2 130 P2 105 P2 134 P2 151 P2 121 P2 153 P2 148 P2 136 P2 145 P2 143 P2 158 P2 140 P2 139 P2 137 P2 157 P2 142 P2 138 P2 152 P2 143 P2 145 P2 142 P2 146 P2 141 P2 144 P2 138 P2 IND %TW TWD 9 TWD 10 TWD 6 TWD 8 TWD 11 TWD 8

TWD 6 TWD 7 TWD 7 TWD 6 TWD 5

TWD 11 TWD 6 TWD 5 TWD 4 TWD 9 TWD 5 TWD 5 TWD 7 TWD 6 TWD 5 TWD 10 TWD 7 TWD 13 TWD 11 TWD 9

TWD 5

TWD 8 TWD 15 TWD 12 TWD 15 TWD 15 TWD 6

TWD 14 TWD 10 TWD 5 TWD 12 TWD 9 TWD 6 TWD 12 TWD 7 TWD 9

TWD 10 TWD 6

TWD 10 TWD 8

TWD 6 TWD 7 TWD 12 TWD 8

TWD 5

TWD 12 TWD 20 TWD 9

TWD 6 TWD 12 TWD 6 TWD 11 TWD 4 TWD 6 TWD 5 TWD 10 TWD 25 TWD 11 TWD 10 TWD 3 TWD 7 TWD 15 TWD 12 TWD 6 TWD 16 TWD 21 TWD 5 TWD 13 TWD 11 TWD 16 TWD 9 TWD 14 TWD 10 TWD 8 LOCATION 015

+0.63 010

+0.65 011

-0.36 010

-0.39 014

-0.56 013

-0.59 014

-0.54 010

-0.48 013

-0.59 008

-0.55 008

+0.14 009

-0.62 008

+0.12 009

-0.65 008

+0.10 009

-0.64 009

+0.05 014

+0.15 013

-0.61 013

+0.17 014

+0.12 013

-0.58 008

+0.22 010

+0.60 010

+0.62 010

-0.36 011

+0.31 014

+0.24 010

-0.45 010

-0.43 010

-0.41 010

-0.40 011

+0.31 010

-0.31 011

+0.36 010

-0.34 010

-0.39 011

+0.29 014

-0.46 010

-0.39 010

-0.41 010

+0.00 011

+0.29 013

-0.49 012

+0.24 014

+0.22 014

-0.51 010

+0.58 010

+0.58 013

-0.54 013

+0.22 014

-0.53 014

+0.17 014

-0.61 008

-0.55 009

-0.65 008

-0.58 009

-0.67 008

+0.07 008

+0.10 010

+0.19 014

+0.07 014

-0.56 014

+0.19 014

-0.56 014

+0.19 008

+0.22 010

-0.36 010

+0.62 011

+0.29 014

-0.46 010

-0.46 011

+0.29 010

-0.34 010

-0.41 010

-0.41 010

-0.31 011

+0.34 010

-0.31 010

-0.39 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE'UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL #

4 12 10 4

10 18 7

20 20 6

20 3

18 4

18 36 36 36 36 36 36 36 10 56 58 58 58 56 56 56 56 58 58 2

58 56 58 56 58 58 56 58 18 18 18 18 20 18 18 18 5

18 18 18 4

18 20 18 5

18 3

18 18 18 18 36 36 3

36 36 36 36 56 56 56 56 58 58 56 56 56 56 56 58 58 56 58 56 58 58 56 20 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET*

INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XBI 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI RepS 4/22/2008 9:48:02 AM Component: S/G B Page 22 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: Query~l[2]

ROW TUBE VOLTS 40 10 0.46 0.20 0.12 40 11 0.15 40 13 0.10 40 14 0.13 40 15 0.13 40 18 0.12 40 20 0.12 40 21 0.11 40

.30 0.06 40 38 0.08 40 43 0.10 40 44 0.17 40 49 0.09 40 98 0.15 40 104 0.23 40 107 0.15 0.12 40 108 0.12 40 109 0.27 40 110 0.26 0.10 40 111 0.17 1

0.09 40 112 0.29 0.23 0.07 40 113 0.27 0.10 40 114 0.14 41 3

0.10 41 4

0.15 0.11 41 8

0.35 41 9

0.52 0.13 0.14 0.15 41 10 0.13 0.16 41 12 0.20 0.15 0.14 41 28 0.32 0.09 41 30 0.08 41 37 0.12 41 38 0.09 41 42 0.08 0.15 41 47 0.18.

41 48 0.07 41 83 0.12 41 98 0.34 41 99 0.14 0.46 0.11 41 100 0.09 41 104 0.20 41 108 0.32 0.20 41 109 0.13 0.08 41 110 0.40 0.09 0.55 0.07 41 111 0.54 0.15 41 112 0.41 0.23 0.15 41 113 0.17 41 114 0.07 42 7

0.12 42 8

0.31 42 9

0.13 0.19 0.12 DEG CHN 135 P2 142 P2 141 P2 145 P2 148 P2 155 P2 130 P2 135 P2 148 P2 157 P2 93 P2 134 P2 100 P2 140 P2 118 P2 149 P2 142 P2 152 P2 150 P2 144 P2 143 P2 143 P2 147 P2 152 P2 156 P2 140 P2 138 P2 153 P2 138 P2 143 P2 139 P2 153 P2 75 P2 138 P2 138 P2 132 P2 138 P2 141 P2 148 P2 139 P2 136 P2 138 P2 142 P2 147 P2 146 P2 153 P2 143 P2 124 P2 140 P2 125 P2 142 P2 131 P2 139 P2 131 P2 140 P2 148 P2 141 P2 152 P2 152 P2 141 P2 141 P2 127 P2 154 P2 145 P2 139 P2 149 P2 142 P2 148 P2 137 P2 150 P2 140 P2 143 P2 154 P2 147 P2 148 P2 144 P2 138 P2 145 P2 144 P2 151 P2 IND %TW LOCATION TWD 21 010

-0.41 TWD 11 011

-0ý44 TWD 7 011

+0.29 TWD 8 011

-0.41 TWD 5 010

-0.43 TWD 7 010

+0.60 TWD 6 014

-0.53 TWD 7 010

-0.48 TWD 7 010

-0.48 TWD 7 010

-0.54 TWD 4 008

+0.14 TWD 6 008

+0.11 TWD 5 008

+0.12 TWD 10 009

-0.65 TWD 7 008

+0.02 TWD 10 014

+0.17 TWD 14 010

+0.58 TWD 9 014

-0.48 TWD 7 014

+0.22 TWD 9 010

-0.36 TWD 14 010

-0.43 TWD 16 010

-0.43' TWD 7 011

+0.31 TWD 9 010

-0.40 TWD 5 011

+0.31 TWD 18 010

-0.41 TWD 15 011

+0.34 TWD 5 013

+0.36 TWD 14 010

-0.38 TWD 6 011

+0.34 TWD 10 010

-0.31 TWD 6 011

-0.36 TWD 9 010

+0.67 TWD 7 011

-0.39 TWD 16 010

-0.41 TWD 23 010

-0.41 TWD 7 010

-0.05 TWD 8 011

+0.27 TWD 8 013

-0.54 TWD 7 011

-0.41 TWD 8 010

-0.41 TWO 10 009

-0.48 TWD 8 014

-0.51 TWD 7 014

+0.20 TWD 17 014

-0.70 TWD 6 014

+0.00 TWD 5 008

+0.14 TWD 6 009

-0.62 TWD 6 009

-0.60 TWD 5 008

+0.12 TWD 9 009

-0.62 TWD 8 009

-0.63 TWD 5 008

+0.02 TWD 9 008

+0.08 TWD 20 014

-0.65 TWD 8 010

+0.22 TWD 21 014

-0.65 TWD 7 014

+0.07 TWD 6 010

+0.22 TWD 13 010

+0.60 TWD 16 010

-0.38 TWD 11 010

+0.64 TWD 7 010

-0.36 TWD 5 011

+0.29 TWD 19 010

-0.40 TWD 5 011

+0.31 TWD 24 014

-0.43 TWD 4 013

+0.31 TWD 24 010

-0.41 TWD 8 011

+0.31 TWD 19 010

-0.38 TWD 12 011

+0.33 TWD 8 013

+0.33 TWD 9 010

-0.38 TWD 4 010

-0.29 TWD 6 010

-0.39 TWD 15 010

-0.41 TWD 7 010

+0.05

.TWD 9

011

-0.41 TWD 6 011

+0.29 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

UTIL 2

WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR 0

WAR WAR 3

WAR WAR WAR 3

WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 6

WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR' WAR WAR WAR WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR 3

WAR WAR WAR WAR WAR CAL #

18 18 18 20 20 18 20 18 18 561 36 565 38 36 565 56 56 58 58 56 58 56 56 58 58 56 56 56 58 58 56 10 12 12 20 18 18 18 18 20 20 20 20 20 36 36 36 38 36 36 36 38 36 10 56 58 58 58 56 56 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 20 18 20 20 20 LEG PROBE INLET S1OXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL INLET 510XB INLET 51OUL INLET 510XB INLET 510XB INLET 51OUL INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:02 AM Component': S/G B Page 23 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS DEG CHN 0.17 146 P2 42 10 0.43 135 P2 0.20 144 P2 0.35 138 P2 0.26 143 P2 0.25 144 P2 0.11 141 P2 42 16 0.14 134 P2 42 17 0.12 151 P2 42 19 0.17 133 P2j 42 34 0.12 140 P2 42 41 0.15 127 P2 42 43 0.19 139 P2 42 49 0.12 134 P2 42 50 0.14 134 P2 42 87 0.11 136 P2 42 95 0.17 142 P2 0.05 146 P2 42 96 0.19 143 P2 42 105 0.16 148 P2 42 108 0.13 155 P2 42 109 0.18 151 P2 0.14 77 P2 42 110 0.10 143 P2 0.25 146 P2 0.13 144 P2 0.10 152 P2 42 111 0.22 147 P2 42 112 0.44 140 P2 0.15 144 P2 42 113 0.38 140 P2 42 116 0.09 148 P2 43 3

0.11 145 P2 43 8

0.42 131 P2 0.12 144 P2 0.22 140 P2 43 9

0.51 137 P2 0.11 138 P2 0.18 148 P2 43 10 0.24 141 P2 0.21 135 P2 43 15 0.13 136 P2 0.10 149 P2 0.20 146 P2 0.10 135 P2 43 30

.0.09 138 P2

.43 46 0.14 107 P2 43 47 0.13 140 P2 43 86 0.06 151 P2 43 98 0.32 139 P2 0.06 137 P2 43 99 0.69 135 P2 0.19 151 P2 43 101 0.12 147 P2 0.38 133 P2 0.07 150 P2 0.15 147 P2 43 104 0.10 157 P2 43 108 0.07 148 P2 43 109 0.19 148 P2 0.08 136 P2 43 110 0.35 142 P2 0.20 113 P2 0.09 148 P2 43 111 0.32 144 P2 0.08 157 P2' 43 112 0.14 151 P2 0.09 148 P2 43 113 0.28 142 P2 43 114 0.08 146 P2 44 4

0.13 144 P2 44 8

0.44 138 P2 0.09 147 P2 44 9

0.13 135 P2 0.20 135 P2 0.10 132 P2 44 10 0.08 143 P2 44 15 0.09 139 P2 44 16 0.24 145.P2 0.13 146 P2 IND %TW TWD 8 TWD 20 TWD 11 TWD 17 TWD 13 TWD 13 TWD 6 TWD 8 TWD 7 TWD 10 TWD 8 TWD 9 TWD 12 TWD 6 TWD 9 TWD 9 TWD 9 TWD 3 TWD 11 TWD 9 TWD 7 TWD 10 TWD 8 TWD 6 TWD 13 TWD 7 TWD 6 TWD 12 TWD 21 TWD 8 TWD 18 TWD 5 TWD 7 TWD 20 TWD 7 TWD 12 TWD 25 TWD 7 TWD 11 TWD 13 TWO 11 TWD 8 TWD 6 TWD 12 TWD 6 TWD 6 TWD 6 TWD 8 TWD 5 TWD 16 TWD,4 TWD 28 TWD 11 TWD 7 TWD 18 TWD 4 TWD 8 TWD 6 TWD 4 TWD 11 TWD 5 TWD 17 TWD 11 TWD 5 TWD 16 TWD 5 TWO 8 TWD 5 TWD 16 TWD 5 TWD 7 TWD 22 TWD 6 TWD.8 TWD 11 TWD 6 TWD 5 TWD 5 TWD 14 TWD 8 LOCATION 014

+0.22 010

-0.43 011

-0.41 011

+0.29 013

-0.53 014

-0.51 014

+0.22 014

+0.12 010

-0.46-014

-0.61' 008

-0.55 009

-0.64 009

-0.64 009

-0.65 009

-0.67 008

+0.10 014

-0.73 014

+0.07 014

-0;63 011

-0.50 010

-0.38 010

0.36 010

+0.62 009

-0.48 010

-0.45 011

+0.27 014

-0.46 010

-0.43 010

-0.43 011

+0.31 010

-0.41 011

+0.38 011

-0.35 010

-0.41 014

-0.45 014

+0.24 010

-0.47 010

-0.02 011

-0.50 011

-0.42 010

-0.44 014

-0.61 008

+0.25 014

+0.17 013

-0.63 008

-0.55 009

-0.65 009

-0.67 008

+0.10 014

-0.73 014

+0.00 014

-0.68 014

-0.05 010

+0.19 014

-0.61 014

+0.05 010

-0.46 014

+0.15 010

-0.41 010

-0.38 011

+0.24 010

-0.38 010

+0.67 011

+0,24 010

-0.46 011

+0.24 010

-0.43 011

+0.29 010

-0.38 010

-0.39 011

-0.39 010

-0.42 011

+0.30 010

+0.05 010

-0.39 013

-0.53 014

+0.20 008

+0.27 010

-0.48 013

-0.65 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE "UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE uTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTEUTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG PROBE 20 18 18 18 18 18 2

18, 18 18 18 36 36 36 38 36 10 58 58 58 58 58 58 58 58 58 58 5

58

'58 58 58 58 58 12 14 14 14 16 16 16 14 6

14 16 4

16 2

16 3

16 36 38 36 10 58 58 58 58 58 58 58 4

58 0

58 58 3

58 3

58 58 58 4

58 58 4

58 58 4

58 60 62 6

16 16 14 2

14 6

14 3

16 4

14 16 16 INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET.

OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:48:02 AM Component: S/G B Page 24 of 74 ONSlBR-EOC24 Tube QUERY:

QueryMl[2]

Support Wear ROW TUBE VOLTS

====4===0

44 43 0.12 44 46 0.10 44 50 0.07 44 97 0.12 44 102 0.16 0.09 44 103 0.11 44 105 0.24 44 107 0.23 44 109 0.08 0.09 44 110 0.36 0.16 0.15 44 111 0.42 0.20 0.15 44 112 0.33 0.15 0.08 44 113 0.10 44 114 0.09 44 118 0.10 45 3

0.32 45 6

0.16 45 7

0.11 45 9

0.08 0.17 45 11 0.08 45 16 0.11 0.23 0.31 45 17 0.14 0.09 45 18 0.14 45 22 0.12 45 25 0.08 45 78 0.08 45 93 0.07 45 102 0.33 0.08 45 108 0.19 45 111 0.22 45 112 0.32 45 113 0.12 46 5

0.16 46 6

0.15 46 7

0.12 46 8

0.31 46 9

0.10 0.15 0.08 46 10 0.37 0.20 0.15 0.22 0.09 0.10 46 12 0.12 46 13 0.14 46 14 0.24 0.08 46 15 0.08 0.12 0.16 46 17 0.14 0.11 0.10 46 20 0.22 0.30 46 22 0.14 46 23 0.10 46 58 0.07 46 101 0.10 46 111 0.08 46 112 0.13 0.10 46 113 0,16 0.11 46 114 0.08 DEG CHN 122 P2 113 P2 147 P2 141 P2 146 P2 147 P2 149 P2 132 P2 147 P2 154 P2 53 P2 140 P2 138 P2 146 P2 141 P2 141 P2 147 P2 143 P2 134 P2 139 P2 147 P2 127 P2 145 P2 139 P2 137 P2 142 P2 130 P2 142 P2 149 P2 144 P2 144 P2 141 P2 145 P2 134 P2 152 P2 134 P2 155 P2 132 P2 135 P2 137 P2 147 P2 133 P2 143 P2 145 P2 140 P2 143 P2 142 P2 122 P2 135 P2 143 P2 144 P2 141 P2 138 P2 143 P2 142 P2 148 P2 154 P2 142 P2 153 P2 146 P2 145 P2 150 P2 144 P2 137 P2 138 P2 146 P2 145 P2 144 P2 130 P2 137 P2 145 P2 147 P2 126 P2 144 P2 144 P2 136 P2 156 P2 145 P2 150 P2 149 P2 IND %TW TWD 8 TWD 7 TWD 5 TWD 8 TWD 10 TWD 6 TWD 7 TWO 14 TWO 13 TWD 5 TWD 6 TWD 19 TWD 10 TWD 9 TWD 21 TWD 12 TWD 9 TWD 18 TWD 9 TWD 5 TWD 6 TWD 6 TWD 6 TWD 16 TWD 9 TWD 7 TWD 5 TWD 9 TWD 5 TWD 7 TWD 13 TWD 17 TWO 8 TWD 5 TWD 8 TWD 8 TWD 5 TWD 6 TWD 6 TWD 18 TWO 5 TWD 12 TWD 13 TWD 17 TWD 8 TWD 9 TWD 8 TWD 7 TWD 16 TWD 6 TWD 9 TWD 5 TWD 20 TWD 12 TWD 10 TWD 13 TWD 6 TWD 7 TWD 7 TWD 8 TWD 14 TWD 6 TWD 5 TWD 7 TWD 9 TWD 8 TWD 7 TWD 6 TWD 12 TWD 15 TWD 10 TWD 6 TWD 5 TWD 6 TWD 6 TWD 8 TWD 6 TWD 10 TWD 7 TWD 5 LOCATION 009

-0.68 009

-0.65 009

+0.00 009

-0.53 014

+0.12 010

+0.22 014

+0.15 014

-0.58 014

-0.49 009

-0.54 010

+0.63 010

-0.39 010

+0.65 011

+0.27 010

-0.37 010

+0.66 011

+0.27 010

-0.36 011

+0.27 013

-0.46 011

+0.29 010

-0.39 011

+0.36 011

-0.34 010

-0.42 011

+0.31 010

+0.05 011

-0.42 014

-0.50 010

+0.22 014

-0.59 014

+0.12 009

-0.51 013

-0.61 010

-0.48 015

+0.00 015

-0.73 007

+0.10 014

-0.76 014

-0.58 014

+0.15 010

+0.63 010

-0.37 010

-0.36 010

-0.34 011

-0.37 011

-0.39 010

-0.39 010

-0.43 010

-0.05 014

-0.50 011

-0.40 010

-0.42 011

-0.43 011

+0.29 013

-0.54 014

-0.49 014

+0.22 011

-0.50 014

-0.52 014

+0.17 014

-0.56 008

+0.26 014

-0.55 014

+0.15 010

-0.46 010

+0.21 013

-0.62 014

-0.62 014

+0.07 010

-0.51 010

+0.16 008

+0.02 014

+0.10 009

-0.49 010

+0.65 010

-0.39 010

-0.37 011

+0.29 011

+0.29 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE U(TE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE' LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE rITE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 6

557 INLET 36 INLET 2

565 INLET 60 INLET 62 INLET 0

62 INLET 60 INLET 60 INLET 60 INLET 60 INLET 60 INLET 62 INLET 62 INLET 62 INLET 60 INLET 60 INLET 60 INLET 62 INLET 62 INLET 4

62 INLET 60 INLET 62 INLET 62 INLET 6

INLET 8

INLET 0

6 INLET 14 INLET 14 INLET 14 INLET 16 INLET 16 INLET 16 INLET 14 INLET 14 INLET 14 INLET 5

559 INLET 14 INLET 10 OUTLET 10 OUTLET 60 INLET 60 INLET 62 INLET 60 INLET 62 INLET 60 INLET 8

INLET 6

INLET 8

INLET 6

INLET 14 INLET 14 INLET 4

14 INLET 16 INLET 16 INLET 16 INLET 16 INLET 4

16 INLET 3

16 INLET 5

16 INLET 14 INLET 16 INLET 4

16 INLET 14 INLET 14 INLET 14 INLET 14 INLET 14 INLET 14 INLET 14 INLET 14 INLET 5

559 INLET 14 INLET 36 INLET 60 INLET 60 INLET 62 INLET 2

62 INLET 60 INLET 60 INLET 62 INLET PROBE 51OUL 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB "510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVAYNP Inc Customer Name: ONSi Repi 4/22/2008 9:48:02 AM Component: S/G B Page 25 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: Query~i [2]

ROW TUBE VOLTS 0.08 47 4

0.21 47 5

0.10 47 6

0.13 47 7

0.08 47 8

0.30 0.12 0.15 47 9

0.35 47 13 0.10 0.14 0.24 0.10 0.24 47 15 0.10 47 16 0.11 47 34 0.07 47 47 0.14 47 78 0.10 47 80 0.10 47 104 0.09 47 112 0.11 47 113 0.13 47 114 0.10 47 115 0.14 48 1

0.08 48 5

0.13 48

'6 0.15 48 7

0.20 48 8

0.28 48 9

0.32 0.09 48 10 0.17 0.14 48 13 0.15 0.07 48 16 0.10 48 17 0.23 0.35 48 18 0.16 48 26 0.09 48 46 0.13 48 48 0.13 48 79 0.12 48 95 0.09 48 100 0.14 48 111 0.11 48 112 0.10 48 114 0.19 48 115 0.18 0.11 48 116 0.10 48 117 0.10 48 121 0.08 49 4

0.18 0.13 49 7

0.10 49 8

0.26 49 10 0.12 0.14 49 15 0.11 49 16 0.24 49 18 0.21 49 81 0.08 49 89 0.09 49 113 0.08 49 119 0.10 50 6

0.10 50 7

0.18 50 8

0.17 50 13 0.09 50 18 0.15 50 19 0.14 0.10 50 20 0.11 50 46 0.07 50 69 0.07 50 84 0.07 50 111 0.11 50 115 0.08 DEG CHN IND 136 P2 TWO 145 P2 TWO 141 P2 TWO 147 P2 TWO 147 P2 TWO 137 P2 TWO 145 P2 TWO 144 P2 TWO 140 P2 TWO 155 P2 TWO 147 P2 TWO 140 P2 TWO 146 P2 TWO 143 P2 TWO 139 P2 TWO 141 P2 TWO 150 P2 TWO 144 P2 TWO 119 P2 TWO 131 P2 TWO 143 P2 TWO 58 P2 TWO 136 P2 TWO 152 P2 TWO 134 P2 TWO 136 P2 TWO 139 P2 TWO 132 P2 TWO 139 P2 TWO 135 P2 TWO 142 P2 TWO 158 P2 TWD 151 P2 TWO 133 P2 TWO 151 P2 TWO 155 P2 TWO 140 P2 TWO 143 P2 kTWD 137 P2 TWO 136 P2 TWO 122 P2 TWO 129 P2 TWD 143 P2 TWO 127 P2 TWO 146 P2 TWO 140 P2 TWO 137 P2 TWO 153 P2 TWO 137 P2 TWO 142 P2 TWO 132 P2 TWO 148 P2 TWO 137 P2 TWO 124 P2 TWO 139 P2 TWD 68 P2 TWO 136 P2 TWO 140 P2 TWO 136 P2 TWO 159 P2 TWO 137 P2 TWO 146 P2 TWO 141 P2 TWO 142 P2 TWD 143 P2 TWO 146 P2 TWD 125 P2 TWO 137 P2 TWO 142 P2 TWO 147 P2 TWO 149 P2 TWO 141 P2 TWO 141 P2 TWO 149 P2 TWO 143 P2 TWD 136 P2 TWO 139 P2 TWO 154 P2 TWO 148 P2 TWO 36 P2 TWO

%TW 5

11 6

7 5

15 7

9 19 7

9 14 6

14 6

6 5

10 8

8 6

7 8

6 9

5 8

9 11 15 16 5

10 8

10 5

6 13 19 9

6 8

8 10 7

7 7

6 11 11 7

6 7

5 10 8

6 14 8

9 6

14 11 6

7 5

7 6

10 9

6 9

9 6

6 5

6 5

7 6

LOCATION 010

-0.34 011

-0.34 011

-0.40 011

-0.41 011

+0.32 010

-0.43 011

-0.38 011

+0.31 011

-0.43 010

-0.47 010

+0.60 013

+0.22 014

-0.54 014

+0.17 014

-0.56 013

-0.64 009

+0.10 009

-0.69 007

+0.20 007

+0.13 010

+0.22 010

+0.66 010

+0.66 010

-0.39 010

-0.37 011

-0.32 011

-0.37 010

-0.41 010

-0.42 010

-0.45 011

-0.43 014

-0.48 011

-0.43 013

-0.60 010

-0.45 010

+0.60 014

-0.57 014

-0.63 014

+0.07 014

-0.62 015

-0.07 008

-0.60 009

-0.64 007

+0.13 008

+0.13 014

+0.03 014

-0.54 010

+0.63 010

+0.63 010

-0.37 010

+0.66 010

-0.37 011

+0.29 010

-0.29 011

-0.37 010

+0.64 010

-0.45 010

-0.42 013

-0.61 014

-0.52 014

-0.62 010

-0.45 014

-0.62 007

+0.10 008

+0.10 010

+0.66 010

-0.37 010

-0.38 010

-0.42 011

-0.43 010

-0.45 013

-0.64 010

-0.51 010

+0.19 010

-0.53 008

+0.10 007

+0.00 007

+0.10 014

+0.20 010

+0.66 EXT EXT UTIL 1

UTIL 2

LTE UTE WAR 4

LTE UTE WAR LTE UTE WAR LTE UTE WAR 0

LTE UTE WAR 0

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 6

LTE UTE WAR LTE UTE WAR 7

UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 3

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 0

LTE UTE WAR LTE UTE WAR 6

LTE UTE WAR LTE UTE WAR 5

LTE UTE WAR 4

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 3

LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR LTE LTE WAR 0

LTE UTE WAR 6

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 6

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 6

LTE UTE WAR 3

LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR 4

LTE UTE WAR CAL # LEG 62 INLET 6

INLET 8

INLET 6

INLET 8

INLET 6

INLET 6

INLET 6

INLET 16 INLET 16 INLET 16 INLET 16 INLET 16 INLET 16 INLET 16 INLET 14 INLET 36 INLET 557 INLET 10 OUTLET 10 OUTLET 60 INLET 62 INLET 60 INLET 62 INLET 60 INLET 8

INLET 8

INLET 6

INLET 8

INLET 6

INLET 6

INLET 6

INLET 14 INLET 14 INLET 16 INLET 16 INLET 14 INLET 16 INLET 16 INLET 14 INLET 559 INLET 36 INLET 36 INLET 10 OUTLET 10 OUTLET 601 INLET 60 INLET 62 INLET 62 INLET 60 INLET 60 INLET 62 INLET 60 INLET 60 INLET 8

INLET 8

INLET 6

INLET 8

INLET 16 INLET 16 INLET 14 INLET 16 INLET 14 INLET 10 OUTLET 10 OUTLET 60 INLET 60 INLET 6

INLET 8

INLET 6

INLET 16 INLET 14 INLET 16 INLET 16 INLET 14 INLET 36 INLET 10 OUTLET 10 OUTLET 60 INLET 60 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:02 AM Component: S/G B Page 26 of 74 ONSlBR-EOC24 Tube QUERY: QueryMl[2]

Support Wear ROW TUBE VOLTS 50 118 0.09 0.15 50 119 0.08 51 5

0.15 51 6

0.22 51 7

0.20 0.20 0.17 0.09 51 8

0.10 51 9

0.80 0.19 51 10 0.17 0.10 51 46 0.09 51 102 0.08 0.10 51 104 0.11 51 105 0.15 51 107 0.13 51 113 0.15 51 118 0.08 51 119 0.09 51 121 0.15 52 6

0.21 52 7

0.26 52 8

0.42 52 9

0.16 0.20 0.15 52 10 0.37 52 15 0.15 0.09 52 16 0,17 0.46 52 19 0.20 52 21 0.12 52 29 0.06 52 37 0.09 52 68 0.08 52 118 0.09 52 119 0.08 0.11 52 120 0.09 53 4

0.13 53 6

0.35 53 7

0.25 0.18 53 9

0.39 53 13 0.08 53 18 0.16 0.18 53 25 0.20 53 47 0.18 53 48 0.10 0.08 53 66 0.07 53 70 0.08 53 79 0.14 53 110 0.09 53 117 0.12 53 118 0.18 53 120 0.08 53 121 0.20 54 1

0.10 0.37 54 3

0.09 54 5

0.15 0.10 54 6

0.28 54 7

0.16 0.08 0.12 0.06 54 8

0.12 54 9

0.58 54 14 0.23 0.17 54 17 0.11 54 22 0.13 DEG 130 77 151 137 131 141 143 147 147 142 133 144 152 149 148 141 135 149 151 152 131 144 144 61 135 135 136 151 140 145 139 146 146 145 133 144 149 155 138 128 152 153 145 140 147 137 141 135 138 118 127 126 138 129 144 157 103 126 148 148 118.

123 153 143 142 138 130 135 138 134 134 143 143 106 137 135 145 147 151 150 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2:

P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 6 TWD 9 TWD 5 TWD 9 TWD 12 TWD 11 TWD 11 TWD 10 TWD 5 TWD 6 TWD 30 TWD 11 TWD II TWD 7 TWD 6 TWO 5 TWD 6 TWD 6 TWD 9 TWD 6 TWD 9 TWD 5 TWD 6 TWD 9 TWD 11 TWD 13 TWD 20 TWD 9 TWD 11 TWO 8 TWD 18 TWD 10 TWD 6 TWD 10 TWD 21 TWD II TWD 7 TWD 4 TWD 6 TWD 7 TWD 6 TWD 5 TWD 7 TWD 6 TWD 8 TWD 17 TWD 13 TWD 10 TWD 19 TWD 5 TWD 9 TWD 10 TWD II TWD 8 TWD 7 TWD 5 TWD 5 TWD 6 TWD 11 TWD 6 TWD 8 TWD 11 TWD 5 TWD 12 TWD 6 TWD 18 TWD 5 TWD 9 TWD 6 TWO 15 TWO 9 TWD 5 TWD 7 TWD 4 TWD 7 TWD 25 TWD 14 TWD 11 TWD 6 TWD 7 LOCATION 010

-0.39 010

+0.68 011

+0.32 011

-0.39 010

-0.39 010

-0.45 011

+0.31 014

-0.46 014

+0.29 010

-0.02 011

-0.45 013

-0.53 011

-0.41 013

-0.54 009

+0.02 008

+0.20 011

-0.56 014

+0.10 014

+0.15 014

+0.13 010

+0.63 010

-0.34 010

-0.34 010

+0.63 010

-0.43 010

-0.42 011

-0.43 011

-0.45 013

-0.52 013

+0.20 011

-0.45 010

-0.47 011

-0.57 014

-0.60 014

+0.12 010

-0.50 014

-0.64 008

+0.12 009

+0.10 007

+0.10 010

-0.36 010

-0.37 013

+0.34 010

-0.36 011

-0.36 010

-0.43 010

-0.42 011

+0.30 011

-0.42 008

+0.21 013

-0.64 014

-0.62 009

-0.58 009

-0.63 009

-0.64 009

+0.02 007

+0.17 007

+0.10 007

-0.66 014

+0.10 010

+0.64 010

+0.68 010

-0.34 010

-0.34 009

-0.42 011

-0.35 011

-0.40 010

-0.40 011

-0.40 010

-0.41 009

-0.49 009

-0.02 011

-0.45 009

+0.34 011

-0.43 011

-0.45 014

-0.57 014

+0.15 010

-0.46 010

-0.53 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

UTIL WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR 3

WAR WAR WAR WAR 4

WAR WAR 4

WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR 3

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 12 WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR 2

CAL #

62 62 60 6

8 6

6 6

6 8

6 6

16 16 36 60 60 601 60 601 62 60 62 62 6

8 6

8 8

81 6

16 16 14 14 14 14 36 36 6

62 60 60 62 6

6 8

8 8

16 14 14 14 38 36 36 36 10 22 62 60 62 62 60 8

8 8

8 8

6 8

8 8

8 6

8 16 16 14 14 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51 OUL 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc 4/22/2008 9:48:02 AM Customer Name:

ONSI Repl Component: S/G B Page 27 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 54 38 0.09 145 P2 TWD 6 009

+0.02 LTE UTE WAR 36 INLET 510XB 54 71 0.08 144 P2 TWD 7 007

+0.15 UTE LTE WAR 10 OUTLET 510XB 54 109 0.11 136 P2 TWD 7 010

+0.19 LTE UTE WAR 62 INLET 510XB 54 110 0.14 134 P2 TWD 9 014

-0.61 LTE UTE WAR 60 INLET 510XB 54 118 0.15 69 P2 TWD 9 010

+0.65 LTE UTE WAR 62 INLET 510XB 54 120 0.15 141 P2 TWD 9 010

-0.39 LTE UTE WAR 62 INLET 510XB 54 121 0.16 140 P2 TWD 10 010

-0.34 LTE UTE WAR 60 INLET 510XB 55 1

0.08 148 P2 TWD 5 008

+0.30 LTE UTE WAR 8

INLET 510XB 55 4

0.15 134 P2 TWD 8 010

-0.38 LTE UTE WAR 6

INLET 510XB 55 5

0.40 134 P2 TWD 19 010

-0.37 LTE UTE WAR 8

INLET 510XB 0.08 141 P2 TWD 5 011

-0.40 LTE UTE WAR 3

8 INLET 510XB 55 6

0.65 132 P2 TWD 26 010

-0.36 LTE UTE WAR 6

INLET 510XB 0.44 138 P2 TWD 20 011

-0.41 LTE UTE WAR 6

INLET 510XB 55 7

0.32 143 P2 TWD 16 011

-0.42 LTE UTE WAR 8

INLET 510XB 55 8

0.33 139 P2 TWD 16 011

-0.45 LTE UTE WAR 6

INLET 510XB 55 9

0.19 147 P2 TWD 10 011

-0.47 LTE UTE WAR 8

INLET 510XB 0.15 141 P2 TWD 9 014

-0.48 LTE UTE WAR 8

INLET 510XB 0.27 141 P2 TWD 14 014

+0.20 LTE UTE WAR 8

INLET 510XB 55 17 0.22 145 P2 TWD 12 014

+0.12 LTE UTE WAR 14 INLET 510XB 55 69 0.12 144 P2 TWD 9 007

+0.15 UTE LTE WAR 6

OUTLET 510XB 55 71 0.07 101 P2 TWD 6 007

+0.05 UTE LTE WAR 10 OUTLET 510XB 55 79 0.08 134 P2 TWD 7 007

+0.10 UTE LTE WAR 10 OUTLET 510XB 55 111 0.14 153 P2 TWD 9 010

+0.22 LTE UTE WAR 62 INLET 510XB 55 120 0.08 139 P2 TWD 5 010

-0.41 LTE UTE WAR 64 INLET 510XB 55 121 0.13 142 P2 TWD 8 010

-0.34 LTE UTE WAR 66 INLET 510XB 55 122 0.18 133 P2 TWD 10 010

-0.41 LTE UTE WAR 64 INLET 510XB 56 1

0.12 144 P2 TWO 7 011

-0.37 LTE UTE WAR 8

INLET 510XB 56 2

0.40 131 P2 TWD 19 011

-0.34 LTE UTE WAR 6

INLET 510XB 56 3

0.16 137 P2 TWO 9 010

-0.40 LTE UTE WAR 8

INLET 510XB 56 4

0.27 131 P2 TWD 14 010

-0.36 LTE UTE WAR 6

INLET 510XB 56 5

0.62 131 P2 TWD 26 010

-0.40 LTE UTE WAR 8

INLET 510XB 0.10 148 P2 TWD 6 013

-0.48 LTE UTE WAR 6

8 INLET 510XB 56 6

0.45 133 P2 TWD 21 010

-0.43 LTE UTE WAR 6

INLET 510XB 56 7

0.54 134 P2 TWD 24 011

-0.42 LTE UTE WAR 8

INLET 510XB 56 8

0.38 140 P2 TWD 18 011

-0.43 LTE UTE WAR 6

INLET 510XB 56 10 0.24 141 P2 TWD 13 014

-0.48 LTE UTE WAR 6

INLET 510XB 56 12 0.08 144 P2 TWD 5 010

-0.48 LTE UTE WAR 14 INLET 510XB 0.11 139 P2 TWD 6 013

-0.58 LTE UTE WAR 5

14 INLET 510XB 0.08 139 P2 TWD 5 008

+0.22 LTE UTE WAR 4

14.

INLET 510XB 56 19 0.16 143 P2 TWD 9 014

+0.10 LTE UTE WAR 14 INLET 510XB 0.10 126 P2 TWD 6 014

-0.66 LTE UTE WAR 4

14 INLET 510XB 56 71 0.08 130 P2 TWD 7 007

+0.10 UTE LTE WAR 10 OUTLET 510XB 56 72 0.07 119 P2 TWD 5 007

+0.10 UTE LTE WAR 12 OUTLET 510XB 56 111 0.11 133 P2 TWD 6 010

+0.27 LTE UTE WAR 64 INLET 510XB 56 112 0.16 146 P2 TWD 9 010

+0.22 LTE UTE WAR 66 INLET 510XB 0.19 146 P2 TWO 11 014

+0.10 LTE UTE WAR 66 INLET 510XB 56 113 0.14 140 P2 TWD 8 010

+0.22 LTE UTE WAR 6

64 INLET 510XB 56 115 0.13 141 P2 TWO 7 014

-0.54 LTE UTE WAR 64 INLET 510XB 56 120 0.13 153 P2 TWD 8 010

-0.41 LTE UTE WAR 66 INLET 510XB 0.08 156 P2 TWD 5 011

+0.24 LTE UTE WAR 4

66 INLET 510XB 56 121 0.16 144 P2 TWD 9 010

-0.37 LTE UTE WAR 64 INLET 510XB 56 122 0.21 141 P2 TWD 12 010

-0.39 LTE UTE WAR 66 INLET 510XB 56 123 0.13 121 P2 TWD 7 010

-0.39 LTE UTE WAR 64 INLET 510XB 57 1

0.82 124 P2 TWD 31 015

+0.60 LTE UTE WAR 8

INLET 510XB 57 2

0.59 133 P2 TWD 25 011

-0.34 LTE UTE WAR 6

INLET 510XB 57 3

0.16 137 P2 TWD 9 011

-0.37 LTE UTE WAR.

8 INLET 510XB 0.11 148 P2 TWD 6 013

-0.43 LTE UTE WAR 8

INLET 510XB 57 4

0.28 134 P2 TWD 14 010

-0.38 LTE UTE WAR 6

INLET 510XB 0.20 141 P2 TWD 11 011

-0.36 LTE UTE WAR 6

INLET 510XB 57 6

0.89 125 P2 TWD 32 011

-0.40 LTE UTE WAR 8

INLET 510XB 57 8

0.39 142 P2 TWD 19 011

-0.44 LTE UTE WAR 8

INLET 510XB 57 10 0.17 139 P2 TWD 10 014

-0.52 LTE UTE WAR 8

INLET 510XB 57 11 0.12 142 P2 TWD 7 014

-0.51 LTE UTE WAR 6

INLET 510XB 57 12 0.19 143 P2 TWD 10 010

-0.46 LTE UTE WAR 14 INLET 510XB 0.14 126 P2 TWD 8 013

-0.58 LTE UTE WAR 14 INLET 510XB 57 14 0.15 141 P2 TWD 9 014

-0.60 LTE UTE WAR 4

14 INLET 510XB 57 15 0.12 143 P2 TWD 7 010

-0.46 LTE UTE WAR 4

14 INLET 510XB 57 16 0.11 147 P2 TWD 6 010

-0.48 LTE UTE WAR 14 INLET 510XB 57 18 0.28 141 P2 TWO 14 010

-0.51 LTE UTE WAR 14 INLET 510XB 0.09 132 P2 TWD 5 014

-0.64 LTE UTE WAR 14 INLET 510XB 0.28 140 P2 TWD 14 014

+0.10 LTE UTE WAR 14 INLET 510XB 0.11 138 P2 TWD 7 010

+0.18 LTE UTE WAR 6

14 INLET 510XB 57 19 0.08 147 P2 TWO 5 010

+0.14 LTE UTE WAR 14 INLET 510XB 57 29 0.09 146 P2 TWD 6 009

+0.10 LTE UTE WAR 36 INLET 510XB 57 37 0.12 135 P2 TWD 5 009

+0.10 LTE UTE WAR 38 INLET 510XB 57 38 0.11 148 P2 TWD 7 009

+0.10 LTE UTE WAR 36 INLET 510XB 57 67 0.06 74 P2 TWD 4 007

+0.14 LTE UTE WAR 36 INLET 510XB 57 70 0.11 107 P2 TWD 9 007

+0.10 UTE LTE WAR 6

OUTLET 510XB 57 86 0.07 134 P2 TWD 6 007

+0.10 UTE LTE WAR 10 OUTLET 510XB 57 119 0.16 88 P2 TWD 10 010

+0.63 LTE UTE WAR 7

66 INLET 510XB

AREVA NP Inc Customer Name: ONS1 Repi 4/22/2008 9:48:02 AM Component: S/G B Page 28 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: Query~l(2]

ROW 57 57 57 57 57 57 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 58 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 59 TUBE VOLTS 120 0.09 121 0.13 0.23 0.08 122 0.16 123 0.09 124 0.15 125 0.06 2

0..09 0.18 0.12 0.20 0.17 3

0.29 0.26 4

0.50 0.42 5

0.64 0.12 6

0.17 7

0.14 0.48 0.12 8

0.30 9

0.14 10 0.12 11 0.11 0.15 15 0.16 16 0.45 0.35 0.16 0.11 17 0.16 0.11 24 0.11 38 0.06 42 0.09 69 0.12 70 0.06 75 0.11 78 0.10 91 0.13 117 0.13 0.14 118 0.17 120 0.06 121 0.08 0.10 0.06 0.12 123 0.19 124 0.10 125 0.13 129 0.12 2

0.20 4

0.53 0.46 7

0.86 10 0.30 11 0.13 0.08 0.08 12 0.09 15 0.10 16 0.11 0.12 43 0.10 79 0.13 83 0.13 91 0,15 105 0.08 113 0.22 114 0.30 0.12 119 0.07 121 0.08 0.13 123 0.14 124 0.27 DEG CHN IND 143 P2 TWD 139 P2 TWD 137 P2 TWO 155 P2 TWD 136 P2 TWD 151 P2 TWD 135 P2 TWD 76 P2 TWO 126 P2 TWO 117 P2 TWD 127 P2 TWD 142 P2 TWD 138 P2 TWO 137 P2 TWD 140 P2 TWD 132 P2 TWO 136 P2 TWO 130 P2 TWD 145 P2 TWO 143 P2 TWD 73 P2 TWD 133 P2 TWO 145 P2 TWD 143 P2 TWD 140 P2 TWO 146 P2 TWD 129 P2 TWD 152 P2 TWO 131 P2 TWO 137 P2 TWD 133 P2 TWD 144 P2 TWO 136 P2 TWD 145 P2 TWO 144 P2 TWD 127 P2 TWO 154 P2 TWO 103 P2 TWD 107 P2 TWD 134 P2 TWO 112 P2 TWD 125 P2 TWD 127 P2 TWO 138 P2 TWD 150 P2 TWO 104 P2 TWD 149 P2 TWD 148 P2 TWO 126 P2 TWD 139 P2 TWD 82 P2 TWO 134 P2 TWO 141 P2 TWD 139 P2 TWD 135 P2 TWO 112 P2 TWD 134 P2 TWD 131 P2 TWO 126 P2 TWO 137 P2 TWD 143 P2 TWD 143 P2 TWO 151 P2 TWD 131 P2 TWO 133 P2 TWO 120 P2 TWD 139 P2 TWD 144 P2 TWO 115 P2 TWO 130 P2 TWD 140 P2 TWO 130 P2 TWO 142 P2 TWD 137 P2 TWO 136 P2 TWO 155 P2 TWD 153 P2 TWO 151 P2 TWO 143 P2 TWD 133 P2 TWO

%TW LOCATION 5

013

+0.27 8

009

-0.46 13 010

+0.58 5

011

+0.24 9

010

-0.37 6

010

-0.36 8

010

-0. 37 4

010

-0.32 5

010

-0.31 10 010

+0.69 7

011

-0.33 11 011

+0.39 10 013

+0.36 15 010

-0.37 14 011

+0.35 22 010

-0.41 20 011

-0.36 26 010

-0.39 7

011

-0.37 9

010

-0.36 8

010

+0.64 22 011

-0.42 7

013

+0.'25 15 011

-0.43 8

011

-0.44 7

014

-0.48 6

014

-0.52 8

014

+0.20 8

013

-0.62 20 010

-0.48 17 014

-0.61 9

014

+0.14 6

010

+0.21 8

009

-0.50 6

010

-0.52 6

014

-0.69 4

009

+0.10 6

009

+0.14 9

007

+0.08 5

007

+0.10 8

007

+0.10 6

007

+0.10 8

007

+0.08 7

013

+0.27 8

014

+0.22 10 010

+0.63 4

010

-0.39 5

009

-0.44 6

010

-0.37 4

008

+0.24 7

010

+0.68 10 010

-0'.

37 6

010

-0.36 7

010

-0.37 7

011

+0.39 11 010

+0.62 23 010

-0.42 21 011

-0.41 31 011

-0.43 15 014

+0.20 7

014

-0.53 5

014

+0.22 5

010

-0.43 5

014

-0.62 6

008

+0.21 6

013

-0.61 6

013

+0.14 7

009

+0.02 10 007

+0.10 10 007

+0.10 11 007

+0.13 7

008

+0.07 12 014

-0.61 15 010

+0.24 7

013

-0.57 4

010

-0.39 5

010

-0.39 8

013

-0.49 8

010

-0.39 14 010

-0.37 EXT EXT LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE, LTE UTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE GTE LTE UTE LTE UTE LTE LTE GTE LTE UTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE GTE LTE UTE LTE UTE LTE UTE LTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL

  • I WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 64 66 66 66 6

64 66 64 66 6

6 6

6 6

8 8

6 6

8 8

5 6

8 8

4 8

6 2

8 5

6 8

0 8

4 20 18 18 18 3

18 20 20 18 36 36 6

8 10 4

591 4

585 64 64 66 66 64 64 64 6

64 64 66 64 64 6

6 6

6 8

6 6

0 6

20 18 20 4

20 36 10 10 10 2

519 66 64 64 66 66 66 66 64 INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET" INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:02 AM Component: S/G B Page 29 of 74 ONSIBR-E0C24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS DEG CHN IND 0.12 59 125 0.13 60 2

0.18 60 3

0.44 0.17 0.22 0.28 60 4

0.28 0.31 60 6

0.33 0.30 0.14 60 7

0.27 60 8

0.26 60 9

0.30 60 12 0.11 60 15 0.17 60 16 0.11 60 31 0.07 60 39 0.08 60 70 0.13 60 71 0.08 60 81 0.08 60 83 0.08 0.12 60 93 0.10 60 107 0.06 60 114 0.26 60 115 0.32 60 116 0.17 60 120 0.08 60 121 0.07 60 122 0.07 60 123 0.09 60 124 0.06 61 1

0.12

  • 0.15 0.07 61 3

0.59 0.22 0.28 0.22 61 6

0.33 0.18 0.45 61 7

0.17 0.09 0.10 61 8

0.12 0.15 61 9

0.14 0.09 0.33 61 10 0.23 0.13 61 11 0.22 0.16 61 12 0.13 61 13 0..09 0.22 61 17 0.20 0.20 61 19 0.12 0.15 61 31 0.07 61 39 0.11 61 53 0.11 61 67 0.08 61 79 0.17 61 81 0.11 61 84 0.08 61 87 0.11 61 92 0.13 61 114 0.19 61 119 0.13 61 120 0.15 61 121 0.06 0.11 61 123 0.09 61 125 0.32 147 P2 145 P2 95 P2 134 P2 118 P2 142 P2 136 P2 132 P2 136 P2 142 P2 134 P2 144 P2 138 P2 137 P2 140 P2 150 P2 144 P2 148 P2 146 P2 155 P2 115 P2 130 P2 135 P2 136 P2 137 P2 140 P2 139 P2 138 P2 134 P2 149 P2 156 P2 140 P2 157 P2 135 P2 156 P2 132 P2 142 P2 155 P2 133 P2 122 P2 137 P2 142 P2 138 P2 144 P2 131 P2 143 P2 151 P2 140 P2 138 P2 137 P2 133 P2 144 P2 138 P2 140 P2 125 P2 141 P2 141 P2 133 P2 151 P2 141 P2 144 P2 139 P2 151 P2 142 P2 151 P2 148 P2 127 P2 112 P2 125 P2 138 P2 135 P2 145 P2 146 P2 132 P2 143 P2 139 P2 152 P2 139 P2 127 P2 136 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TwO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO

%TW 78 10 20 9

12 15 15 16 16 15 8

14 13 15 6

9 6

5 6

10 6

6 6

10 8

6 14 16 10 5

4 5

5 4

7 9

4 25 12 15 12 16 10 21 10 5

6 7

9 8

6 17 12 8

12 9

7 5

11 10 10 7

8 5

7 7

6 12 9

7 9

10 14 9

11 5

8 7

20 LOCATION 013

+0.34 010

-0.34 010

+0.63 010

-0.35 010

+0.65 011

-0.35 011

+0.37 011

-0.36 011

+0.36 010

-0.39 011

-0.40 014

+0.28 011

-0.41 011

-0.42 011

-0.43 010

-0.40 010

-0.48 010

-0.49 009

+0.02 009

+0.02 007

+0.13 007

+0.13 007

+0.13 008

-0.69 007

+0.15 007

+0.15 008

+0.07 010

+0.19 010

+0.24 011

+0.19 010

-0.44 010

-0.42 009

-0.46 011

-0.42 013

+0.29 009

-0.42 015

-0.38 003

+0.39 010

-0.36 010

+0.65 012

+0.34 011

+0.00 011

-0.36 013

-0.46 010

-0.41 011

-0.40 010

-0.42 013

+0.28 010

-0.41 011

-0.41 010

-0.42 013

-0.53 011

-0.42 011

-0.43 010

-0.41 010

-0.47 013

-0.55 008

+0.21 010

-0. 48 014

-0.59 010

-0.49 011

-0.52 009

-0.52 010

-0.52 009

-0.02 009

+0.12 009

-0.64 007

+0.18 007

+0.10 007

+0.13 007

+0.13 007

+0.13 007

+0.15 010

+0.13 010

+0.59 010

+0.53 011

+0.18 010

-0.48 010

+0.58 010

-0.46 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR

  • UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTIL 2

CAL #

64 66 6

8 8

8 8

6 6

8 88 6

8 0

6 6

20 4

18 36 36 6

8 10 10 10 10 3

519 66 64 66 3

66 64 66 64 66 8

8 8

6 6

6 6

6 6

8 6

8 0

8 4

8 5

6 6

6 8

8 4

8 0

6 6

8 8

6 20 20 20 20 18 18 36 36 36 4

565 10 10 10 10 10 10 12 10 12 12 12 12 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSi Rep1 4/22/2008 9:48:02 AM Component: S/G B Page 30 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: Query~l(2]

ROW TUBE VOLTS 62 2

0.66 0.22 1.96 62 5

0.81 0.25 0.21 62 6

0.33 0.16 62 7

0.89 0.13 62 8

0.11 0.10 0.14 62 9

0.15 0.21 62 10 0.09 0.13 62 12 0.17 0.19 0.05 0.12 62 13 0.10 62 16 0.14 62 17 0.16 62 28 0.12 62 47 0.14 62 69 0.20 62 71 0.13 62 80 0.11 62 113 0.24 62 115 0.39 62 116 0.09 0.08 62 117 0.07 0.09 62 118 0.12 62 119 0.15 0.07 0.07 62 121 0.11 0.08 62 123 0.12 0.09 62 124 0.12 62 126 0.25 62 127 0.07 63 1

1.03 63 2

0.27 0.18 0.51 63 3

0.64 0.21 0.18 0.38 63 5

0.32 0.09 0.16 0.26 63 6

0.10 0.65 0.45 0.18 63 7

0.98 0.25 0.08 0.13 63 9

0.13 63 10 0.17 63 11 0.17 0.31 63 12 0.10 0.24 63 13 0.24 0.31 63 14 0.13 63 15 0.07 63 17 0.10 63 18 0.20 0.23 0.17 DEG CHN 131 P2 111 P2 119 P2 127 P2 132 P2 143 P2 139 P2 150 P2 129 P2 141 P2 147 P2 150 P2 147 P2 149 P2 139 P2 148 P2 136 P2 144 P2 134 P2 141 P2 152 P2 153 P2 137 P2 146 P2 151 P2 136 P2 127 P2 133 P2 140 P2 134 P2 134 P2 143 P2 124 P2 152 P2 149 P2 138 P2 138 P2 156 P2 154 P2 129 P2 148 P2 137 P2 140 P2 144 P2 134 P2 107 P2 121 P2 134 P2 92 P2 132 P2 129 P2 107 P2 143 P2 139 P2 137 P2 143 P2 "129 P2 139 P2 127 P2 131 P2 137 P2 138 P2 127 P2 137 P2 118 P2 145 P2 137 P2 132 P2 139 P2 141 P2 125 P2 138 P2 140 P2 139 P2 141 P2 147 P2 142 P2 139 P2 135 P2 147 P2 IND TWD TWD TWD TWD TWD TWD TWD TWO TWO TWD TWD TWD TWD TWD TWO TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWO TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWO TWO TWO TWD TWO TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWO TWD TWO TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 27 12 47 31 13 11 17 9

32 7

6 6

8 9

11 5

7 10 11 3

7 5

88 8

9 14 10 9

17 23 7

7 6

7 9

11-6 5

8 6

9 7

9 17 5

35 14 10 23 26 11 10 18 16 5

9 14 6

27 21 10 34 13 5

7 7

10 10 16 6

13 11 14 8

4 5

11 12 9

LOCATION 010

-0.35 010

+0.65 011

-0.35 010

-0.39 011

-0.37 014

+0.25 011

-0.40 013

-0.48 011

-0.41 010

-0.43 010

-0.47 011

-0.42 014

-0.48 011

-0.43 010

-0.38 010

-0.49 014

-0.55 010

-0.43 013

-0.60 013

+0.14 011

-0.45 010

-0.46 014

+0.10 010

-0.50 009

+0.12 009

-0.69 007

+0.15 007

+0.10 007

+0.13 010

+0.13 010

+0.15 009

-0.64 008

-0.45 010

-0.54 010

+0.53 010

+0.56 010

+0.53 010

-0.51 009

-0.61 010

+0.54 008

+0.20 010

+0.56 013

+0.23 011

+0.20 010

-0.41 010

-0.41 015

+0.57 010

-0.35 010

+0.67 011

-0.32 010

-0.35 010

+0.65 011

+0.37 011

-0.32 011

-0.37 011

+0.32 013

-0.45 014

-0.45 008

+0.25 010

-0.42 011

-0.40 011

+0.32 012

-0.40 013

+0.28 008

+0.22 010

-0.42 010

-0.44 010

-0.44 010

-0.44 011

-0.45 008

+0.20 010

-0.49 010

-0.49 011

-0.51 010

-0.45 010

-0.46 008

+0.16 014

-0.66 014

+0.10 015

+0.05 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG PROBE 8

INLET 51*XB 8

INLET 510XB LAR 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 6

INLET 510XB 4

6 INLET 510XB 8

INLET 510XB 4

8 INLET 510XB 0

8 INLET 510XB 0

6 INLET 510XB 6

INLET 510XB 8

INLET 510XB 6

8 INLET 510XB 6

INLET 510XB 6

INLET 510XB 6

INLET 510XB 0

6 INLET 510XB 3

20 INLET 510XB 18 INLET 510XB 4

20 INLET 510XB 36 INLET 510XB 36 INLET 510XB 6

OUTLET 510XB 6

OUTLET 510XB 2

OUTLET 510XB 10 OUTLET 510XB 12 OUTLET 510XB 6

10 OUTLET 510XB 5

10 OUTLET 510XB 12 OUTLET 510XB 6

12 OUTLET 510XB 10 OUTLET 510XB 12 OUTLET 510XB 12 OUTLET 510XB 12 OUTLET 510XB 12 OUTLET 510XB 12 OUTLET 510XB 12 OUTLET 510XB 4

12 OUTLET 510XB 10 OUTLET 510XB 10 OUTLET 510XB 12 OUTLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 3

8 INLET 510XB 8

INLET 510XB 8

INLET 510XB.

8 INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 4

8 INLET 510XB 4

8 INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 8

INLET 510XB 20 INLET 510XB 3

20 INLET 510XB 18 INLET 510XB 20 INLET 510XB 20 INLET 510XB 18 INLET 510XB 18 INLET 510XB 18 INLET 510XB

AREVA NP Inc Customer Name: ONSI Reol 4/22/2008 9:48:03 AM Component: S/G B Page 31 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 63 70 0.07 63 81 0.13 63 95 0.14 63 97 0.11 63 106 0.06 63 109 0.12 0.11 63 112 0.11 63 113 0.18 63 114 0.30 63 115 0.23 63 116 0.38 63 117 0.11 63 118 0.13 0.08 0.11 63 119 0.08 0.15 0.13 0.11 63 120 0.15 63 121 0.10 0.04 0.13 63 122 0.28 63 123 0.11 63 124 0.12 63 125 0.15 63 129 0.11 63 130 0.15 64 1

0.14 0.08 64 2

0.15 0.18 64 3

0.35 0.19 64 4

0.77 0.14 64 5

0.26 64 6

0.53 0.70 0.09 64 7

0.08 0.35 0,22 0.12 64 8

0.37 0.14 0.09 64 9

0.27 64 10 0.14 64 11 0.09 0.17 64 12 0.09 0.31 64 13 0.16 0.28 0.31 0.19 0.17 64 14 0.23 64 15 0.18 0.11 64 16 0.21 64 17 0.12 0.16

.64 18 0.09 0.12 0.32 0.21 0.12 64 20 0.08 64 71 0.21 64 72 0.10 64 79 0.08 0.11 64 81 0.08 64 94 0.08 64 98 0.11 64 114 0.18 DEG CHN IND %TW LOCATION 149 P2 TWO 6 007

+0.10 129 P2 TWD 11 007

+0.18 118 P2 TWD 11 007

+0.10 123 P2 TWO 9 007

+0.13 140 P2 TWD 5 011

-0.69 142 P2 TWO 9 014

-0.05 136 P2 TWD 8 014

-0.74 144 P2 TWO 9 014

+0.05 133 P2 TWO 13 010

+0.13 138 P2 TWO 20 010

+0.13 138 P2 TWD 15 010

+0.13 136 P2 TWD 23 010

+0.15 150 P2 TWD 8 010

-0.56 148 P2 TWD 10 010

+0.54 142 P2 TWD 7 009

-0.62 138 P2 TWD 9 008

-0.42 144 P2 TWO 6 014

+0.08 141 P2 TWD 11 014

-0.56 147 P2 TWO 9 010

-0.51 136 P2 TWO 8 010

+0.53 139 P2 TWD 11 010

-0.51 144 P2 TWO 7 010

-0.46 151 P2 TWD 3 009

-0.52 127 P2 TWD 10 010

+0.56 140 P2 TWD 19 010

+0.54 141 P2 TWD 8 010

+0.53 145 P2 TWD 9 010

-0.46 145 P2 TWD 11 011

+0.23 145 P2 TWD 8 011

+0.28 145 P2 TWO 11 008

+0.25 66 P2 TWO 8 010

+0.67 95 P2 TWO 5 010

-0.35 140 P2 TWO 9 008

-0.37 80 P2 TWD'10 010

+0.65 129 P2 TWD 17 010

-0.35 107 P2 TWD 11 010

+0.67 126 P2 TWD 30 010

-0.37 130 P2 TWD 8 011

-0.37 137 P2 TWD 14 011

-0.37 129 P2 TWD 23 010

-0.42 130 P2 TWD 28 011

-0.40 143 P2 TWD 5 008

+0.25 136 P2 TWD 5 008

+0.22 134 P2 TWD 17 011

-0.40 138 P2 TWO 12 011

+0.32 142 P2 TWD 7 014

-0.45 135 P2 TWO 18 011

-0.42 149 P2 TWO 8 011

+0.30 147 P2 TWO 5 010

-0.42 138 P2 TWO 14 011

-0.42 143 P2 TWO 8 011

-0.42 140 P2 TWD 6 008

+0.17 134 P2 TWO 9 013

+0.18 114 P2 TWO 5 010

-0.49 141 P2 TWD 16 011

-0.47 143 P2 TWO 9 010

-0.47 144 P2 TWO 14 011

-0.50 137 P2 TWD 16 014

-0.58 142 P2 TWD 10 013

+0.15 141 P2 TWD 9 014

+0.13 148 P2 TWD 12 010

-0.47 143 P2 TWD 9 010

-0.51 82 P2 TWD 6 013

-0.65 143 P2 TWD 11 011

-0.53 135 P2 TWO 6 008

+0.18 142 P2 TWO 8 010

-0.46 133 P2 TWO 5 008

+0.21 145 P2 TWO 7 010

-0.50 134 P2 TWD 16 014

-0.65 145 P2 TWD 12' 014

+0.09 137 P2 TWD 7 015

+0.05 134 P2 TWD 5 008

+0.15 132 P2 TWD 15 007

+0.10 109 P2 TWD 8 007

+0.10 121 P2 TWO 7 006

+0.18 119 P2 TWD 9 007

+0.13 130 P2 TWO 7 007

+0.10 137 P2 TWO 7 007

+0.20 116 P2 TWD 9 007

+0.'13 129 P2 TWD 13 010

+0.13 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL I

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR

.WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 6

OUTLET 2

OUTLET 10 OUTLET 10 OUTLET 10 OUTLET 10 OUTLET 0

10 OUTLET 10 OUTLET 12 OUTLET 10 OUTLET 12 OUTLET 10 OUTLET 12 OUTLET 10 OUTLET 10 OUTLET 7

10 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 8

12 OUTLET 10 OUTLET 12 OUTLET 12 OUTLET 9

12 OUTLET 10 OUTLET 6

12 OUTLET 4

10 OUTLET 12 OUTLET 12 OUTLET 12 OUTLET 8

INLET 8

INLET 8

INLET 8

INLET 8

INLET 8

INLET 8

INLET 8

INLET 8

INLET 8

INLET 8

INLET 4

8 INLET 8

INLET 8

INLET 8

INLET 3

8 INLET 8

INLET 8

INLET 2

8 INLET 8

INLET 4

8 INLET 8

INLET 8

INLET 8

INLET 3

8 INLET 8

INLET 8

INLET 8

'INLET 0

8 INLET 0

8 INLET 18 INLET 20 INLET 20 INLET 3

18 INLET 20 INLET 20 INLET 18 INLET 18 INLET 18 INLET 3

18 INLET 2

18 INLET 18 INLET 6

OUTLET 6

OUTLET 2

OUTLET 4

2 OUTLET 2

OUTLET 10 OUTLET 10 OUTLET 10 OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 5i0XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONS1 Repi 4/22/2008 9:48:03 Am Component: S/G B Page 32 of 74 ONSIBR-E0C24 -

Tube Support Wear QUERY: QueryMi (21 ROW TUBE VOLTS 64 115 0.07 64 116 0.86 64 117 0.10 0.08 64 118 0.12 0.13 0.13 0.10 64 121 0.15 0.06 64 122 0.31 0.67 0.17 0.21 0.13 0.09 0.09 64 123 0.12 0.17 0.12 64 125 0.37 64 127 0.10 64 129 0.09 64 130 0.22 65 1

0:66 65 2

0.17 65 3

0.17 0.16 65 4

0.42 0.18 0.20 65 5

0.46 65 6

0.51 0.33 65 7

0.28 0.16 0.17 0.12 65 8

0.18 0.11 0.20 0.43 0.17 65 9

0.10 0.17 65 10 0.24 65 11 0.26 65 12 0.17 0.33 65 13 0.13 65 14 0.20 65 15 0.13 0.49 0.12 65 16 0.12 0.11 65 17 0.09 0.10 65 18 0.12 0.19 65 19 0.19 65 36 0.07 65 38 0.07 65 68 0.13 65 69 0.14 65 70 0.12 65 71 0.13 65 81 0.09 65 95 0.08 65 97 0.14 65 98 0.08 65 114 0.11 65 115 0.24 0.09 65 116 0.15 0.15 0.09 65 117 0.08 0.06 65 118 0.08 DEG CHN 155 P2 130 P2 149 P2 127 P2 141 P2 138 P2 148 P2 126 P2 140 P2 139 P2 139 P2 130 P2 114 P2 129 P2 127 P2 121 P2 144 P2 139 P2 135 P2 132 P2 138 P2 120 P2 151 P2 138 P2 133 P2 89 P2 134 P2 142 P2 130 P2 143 P2 142 P2 131 P2 136 P2 141 P2 136 P2 141 P2 144 P2 140 P2 147 P2 57 P2 136 P2 134 P2 148 P2 132 P2 144 P2 142 P2 138 P2 139 P2 139 P2 141 P2 147 P2 140 P2 137 P2 113 P2 149 P2 114 P2 146 P2 152 P2 128 P2 143 P2 144 P2 152 P2 145 P2 118 P2 127 P2 133 P2 135 P2 143 P2 134 P2 130 P2 116 P2 140 P2 141 P2 147 P2 144 P2 137 P2 144 P2 143 P2 139 P2 143 P2 IND %TW LOCATION TWD 5 009

-0.61 TWD 37 010

+0.15 TWD 8 013

-0.64 TWD 6 010

+0.13 TWD 9 014

-0.66 TWD 10 011

+0.10 TWD 10 009

+0.53 TWD 8 008

-0.45 TWD 11 010

-0.51 TWD 5 007

-0.43 TWD 20 011

+0.18 TWD 32 010

+0.54 TWD 13 010

+0.20 TWD 15 010

-0.48 TWD 10 008

-0.37 TWD 7 007

+0.30 TWD 7 011

-0.54 TWD 9 014

+0.13 TWD 12 010

-0.48 TWD 9 010

+0.56 TWD 22 013

+0.23 TWO 8 010

-0.41 TWD 7 011

+0.28 TWD 15 011

+0.31 TWD 27 011

-0.32 TWD 9 010

+0.62 TWD 9 010

-0.40 TWD 9 011

-0.37 TWD 20 010

-0.37 TWD 10 011

-0.37 TWD 11 014

+0.28 TWD 21 011

-0.40 TWD 23 011

-0.40 TWD 17 014

+0.25 TWD 14 011

-0.40 TWD 9 014

-0.48 TWD 10 014

+0.23 TWD 7 009

+0.59 TWD 10 009

+0.57 TWD 6 010

+0.62 TWD 11 011

-0.42 TWD 20 014

-0.50 TWD 10 014

+0.23 TWD 6 010

-0.42 TWD 9 011

-0.45 TWD 13 011

-0.47 TWD 14 010

-0.47 TWD 10 010

-0.47 TWD 16 011

-0.'47 TWD 6 010

-0.49 TWD 11 010

-0.48 TWD 6 010

-0.49 TWD 20 011

-0.51 TWD 6 014

-0.59 TWD 7 010

-0.45 TWD 6 013

-0.66 TWD 5 008

+0.18 TWD 5 010

-0.53 TWD 7 008

+0.19 TWD 10 010

-0.48 TWD 10 011

+0.14 TWD 5 009

-0.10 TWD 5 009

+0.02 TWD '10 007

+0.10 TWD 11 007

+0.13 TWD 11 007

+0.07 TWD 10 007

+0.13 TWD 8 007

+0.13 TWD 7 007

+0.13 TWD 11 007

+0.13 TWD 7 007

+0.13 TWD 9 010

+0.13 TWD 16 010

+0.10 TWD 7 010

-0.54 TWD 12 014

-0.66 TWD 12 010

+0.13 TWD 7 008

-0.42 TWD 6 008

+0.20 TWO 4 009

-0.61 TWD 7 010

-0.53 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR I

UTIL 2

CAL #

12 10 12 12 10 10 5

10 6

10 12 12 10 10 10 10 10 10 4

10 12 12 8

12 12 12 3

12 10 8

8 8

8 8

8 8

8 8

8 8

8 8

8 8

8 8

8 8

8 8

O 8

88 8

2018 20 2

20 0

20 18

,18 20 20 18 18 18 36 36 6

6 8

509 6

2 10 6

10 4

10 12 12 10 10 6

10 12 12 10 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB/

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:48:03 AM Component:

S/G B Page 33 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 0.14 65 119 0.08 65 121 0.12 65 122 0.23 65 i25 0.19 65 128 0.09 65 129 0.06 66 1

0.10 0.77 0.13 66 2

0.72 66 3

0.34 66 4

0.72 0.29 66 5

0.22 66 6

0.45 0.37 0.36 0.23 66 7

0.45 0.14 0.10 66 8

0.24 0.10 66 11 0.11 66 12 0.11 0.20 66 14 0.21 0.58 66 15 0.39 66 16 0.17 66 17 0.19 0.21 66 19 0.12 0.09 66 70 0.10 66 82 0.09 66 84 0.08 66 112 0.15 0.11 66 113 0.37 66 114 0.32 66 117 0.22 0.20 0.11 0.08 66 118 0.16 66 119 0.10 0.12 0.13 66 120 0.11 66 121 0.14 66 122 0.26 0.10 66 123 0.07 0.24 0.18 66 126 0.09 66 128 0.12 67 2

0.25 67 3

0.39 67 5

0.16 67 6

0.24 0.12 0.15 67 7

0.20 0.10 67 8

0.22 0.09 0.11 67 9

0.14 0.10 67 11 0.14 0.10 67 12 0.26 0.16 0.08 67 13 0.39 0.14 0.13 DEG CHN 134 P2 138 P2 147 P2 135 P2 145 P2 129 P2 145 P2 145 P2 131 P2 142 P2 130 P2 140 P2 132 P2 139 P2 138 P2 131 P2 138 P2 144 P2 142 P2 137 P2 140 P2 146 P2 133 P2 136 P2 148 P2 55 P2 141 P2 146 P2 133 P2 140 P2 142 P2 138 P2 151 P2 147 P2 144. P2 126 P2 90 P2 143 P2 141 P2 152 P2 136 P2 136 P2 140 P2 140 P2 144 P2 130 P2 139 P2 134 P2 147 P2 152 P2 132 P2 148 P2 136 P2 131 P2 144 P2 146 P2 136 P2 142 P2 148 P2 137 P2 131 P2 141 P2 141 P2 140 P2 148 P2 146 P2 146 P2 145 P2 149 P2 153 P2 145 P2 140 P2 144 P2 156 P2 146 P2 142 P2 156 P2 140 P2 149 P2 148 P2 IND %TW LOCATION EXT EXT UTIL 1

TWD 10 TWD 6 TWD 9 TWD 16 TWD 14 TWD 7 TWD 5 TWD 5 TWD 28 TWD 7 TWD. 29 TWD 16 TWD 29 TWD 15 TWD 12 TWD 21 TWD 18 TWD 18 TWD 12 TWD 21 TWD 8 TWD 6 TWD 13 TWD 6 TWD 6 TWD 6 TWD 11 TWD 10 TWD 23 TWD 18 TWD 9 TWD 11 TWD 11 TWO 7 TWD 5 TWD 8 TWD 8 TWD 7 TWD 12 TWD 9 TWD 22 TWD 20 TWD 15 TWD 14 TWD 9 TWD 7 TWD 12 TWD 7 TWD 9 TWD 10 TWD 9 TWD 10 TWD 18 TWD 8 TWD 6 TWD 16 TWD 13 TWD 7 TWD' 10 TWD 13 TWD 19 TWD 9 TWD 12 TWD 7 TWD 8 TWD.11 TWD 6

'TWD 11 TWD 5 TWD 6 TWD 8 TWD 6 TWD 8 TWD 5 TWD 14 TWD 9 TWD 5 TWD 17 TWD 7 TWD 7 008 010 010 010 011 010 008 009 011 015 011 011 011 014 011 011 013 014 014 011 011 013 011 011 011 010 010 010 011 011 010 010 011 010 013 007 007 007 014 010 010 010 011 010 010 009 010 014 009 010 010 010 010 008 014 014 010 010 011 011 011 011 011 014 013 011 011 011 011 014 010 013 014 014 010 013 011 010 010 014

-0.45

-0.51

+0.53

+0.54

+0.23

-0.43

+0.25

-0.40

-0.32

-0.38

-0.36

-0.35

-0.36

+0.30

-0.40

-0.40

-0.45

-0.45

+0.28

-0.42

+0.30

-0.50

-0.40

+0.32

-0.45

+0.60

-0.49

-0.46

-0.47

-0.51

-0.51

-0.49

-0.55

-0.51

+0.05

+0.13

+0.08

+0.10

`0. 05

+0.10

+0.13

+0.13

+0.10

+0.15

-0.53

+0.15

+0.51

+0.08

+0.54

+0.53

+0.56

+0.53

+0.53

+0.23

+0.15

-0.51

-0.46

-0.43

+0.28

-0.35

-0.36

-0.38

-0.42

+0.28

+0.20

-0.43

+0.29

-0.45

+0.30

-0.48

-0.48

-0.53

-0.57

+0.15

-0.47

+0.14

-0.50

-0.47

+0.57

0. 55 UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

8 10 12 7

12 10 24 4

10 12 4

4 0

4 2

4 2

2 8

8 8

8 8

8 8

6 8

4 8

0 8

0 8

8 8

20 20 0

18 20 18 0

18 18 18 6

2 2

10 4

10 12 10 10 10 10 4

10 10 12 8

12 7

12 10

.8 12 10 3

10 12 12 12 3

10 24 4

2 2

4 0

4 0

4 2

2 4

0 4

2 2

4 0

4 2

2 0

2 20 6

20 2

20 LEG PROBE OUTLET 51OXB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51oXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 51OXB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:03 AM Component: S/G B Page 34 of 74 ONSlBR-EOC24 Tube Support Wear QUERY:

QueryMl[2]

ROW TUBE VOLTS DEG CHN IND 67 14 0.16 0.12 67 15 0.38 0.30 67 16 0.14 67 17 0.13 67 19 0.18 67 20 0.08 67 21 0.15 67 38 0.06 67 41 0.08 67 68 0.08 67 70 0.09 67 76 0.09 67 77 0.10 67 79 0.09 67 84 0.14 67 87 0.08 67 93 0.07 67 112 0.36 67 114 0.07 67 115 0.22 0.05 67 116 0.24 0.30 0.10 0.15 67 117 0.09 67 119 0.08 67 120 0.11 67 121 0.11 0.17 67 122 0.15 67 123 0.31 0.34 0.10 67 126 0.13 0.36 67 127 0.10 68 1

0.07 0.09 68 3

0.12 68 4

0.20 68 5

0.09 68 6

0.77 0.17 0.39 0.10 68 7

0.26 0 :24 68 8

0.13 0.30 68 9

0.81 0.11 0.11 0.15 68 10 0.63 0.11 0.12 68 11 0.13 0.54 0.08 68 12 0.13 68 13 0.12 0.11 68 14 0.28 68 15 0.11 68 17 0.22 68 18 0.12 0.14 68 19 0.09 68 20 0.09 68 38 0.06 68 83 0.17 68 112 0.22 68 113 0.17 68 114 0.12 68 116 0.16 0.11 0.10 134 P2 146 P2 133 P2 141 P2 143 P2 139 P2 144 P2 148 P2 143 P2 149 P2 151 P2 108 P2 143 P2 134 P2 113 P2 92 P2 130 P2 132 P2 103 P2 138 P2 152 P2 145 P2 142 P2 141 P2 133 P2 140 P2 143 P2 152 P2 150 P2 146 P2 139 P2 141 P2 128 P2 134 P2 135 P2 137 P2 136 P2 141 P2 152 P2 157 P2 153 P2 143 P2 136 P2 153 P2 134 P2 147 P2 136 P2 147 P2 139 P2 141 P2 127 P2 135 P2 133 P2 147 P2 150 P2 141 P2 134 P2 143 P2 139 P2 151 P2 136 P2 143 P2 150 P2 139 P2 153 P2 143 P2 118 P2 129 P2 144 P2 144 P2 137 P2 124 P2 147 P2 128 P2 141 P2 136 P2 133 P2 137 P2 156 P2 122 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWO TWO TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWO TWD TWD TWO TWD TWD TWO TWO TWO TWD TWD TWD

%TW 9

7 17 14 8

7 9

5 10 4

6 6

7 7

9 8

11 6

6 22 6

16 5

16 20 8

12 7,

6 8

8 12 11 19 21 8

10 22 8

4 5

6 11 5

30 10 19 6

13 12 8

16 29 6

6 8

27 7

7 7

23 4

8 7

6 14 6

11 7

8 5

5 4

13 15 12 10 12 9

8 LOCATION 014

-0.61 008

+0.15 014

-0.59 011

-0.53 010

-0.49 010

-0.48 010

-0.53 008

+0.11 014

-0.73 009

+0.05 009

+0.00 007

+0.13 007

+0.13 007

+0.15 007

+0.20 007

+0.13 007

+0.15 007

+0.10 007

+0.13 010

+0.10 010

-0. 46 010

+0.15 008

+0.18 014

+0.05 010

+0.13 009

+0.18 011

+0.10 010

-0.48 010

-0.51 010

-0.48 010

+0.56 010

-0.48 010

+0.51 014

+0.15 010

-0.48 006

+0.23 010

-0.41 009

+0.51 013

+0.28 008

+0.28 013

+0.36 011

-0.36 010

-0.38 013

+0.23 011

-0.39 013

-0.48 014

-0.46 014

+0.30 011

-0.40 011

+0.33 009

-0.50 011

-0.43 011

-0.42 011

+0.27 013

+0.18 014

+0.23 011

-0.48 011

+0.24 014

-0.53 009

-0.47 011

-0.45 008

+0. 12 011

-0.45 010

-0.50 011

-0.50 011

-0.51 008

+0. 16 013

-0. 67 010

-0.49 011

-0.56 008

+0.16 008

+0.14 009

+0.17 007

+0. 13 010

+0.16 010

+0.13 010

+0.13 010

+0.13 010

-0.53 008

-0.45 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL #

18 4

18 20 2

20 18 20, 20 18 4

557 36 36 6

6 6

5 509 2

2 10 10 10 4

24 24 4

24 10 10 10 0

10 12 12 3

10 8

12 8

12 10 12 12 6

12 10 10 6

12 4

0 4

5 4

2 0

4 2

2 2

2 2

4 4

2 2

4 4

3 4

2 4

2 2

0 2

4 4

4 0

2 4

2 4

2 2

18 20 20 18 0

18 20 18 36 2

7 517 10 0

10 10 10 8

10 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510OXB 510XB 510XB 510XB 510XB 510XB 51OUL 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONS1 Repi 4/22/2008 9:48:03 AM Component: S/G B Page 35 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 68 117 0.13 68 118 0.11 68 119 0.09 68 121 0.25 68 122 0.29 0.12 68 123 0.13 68 124 0.18 68 125 0.15 0.37 68 126 0.16 68 128 0.11 68 131 0.22 69 1

0.43 69 4

0.32 69 5

0.22 0.09 69 6

0.26 0.15 0.20 69 7

0.35 0.31 69 8

0.68 0.18 0.27 69 9

0.19 0.35 0.13 0.14 69 10 0,78 0.10 69 11 0.50 0.22 69 13 0.26 0.11 69 14 0.18 0.27 0.14 69 15 0.24 0.36 0.12 0.11 69 16 0.11 69 17 0.20 69 18 0,10 0.21 69 20 0.10 69 38 0.07 69 40 0:07 69 54 0.08 0.09 69 73 0.09 69 78 0.11 69 80 0.09 69 84 0.12 69 85 0.10 69 114 0.17 69 115 0.14 0.07 69 116 0.16 69 117 0.20 0.12 69 118 0.21 69 121 0.10 0.10 0.12 0.13 69 122 0.20 69 124 0.25 69 125 0.28 0.22 69 129 0.17 69 132 0.15 70 2

0.36 70 3

0.'18 0.13 0.13 70 5

0.12 70 6

0.19 0.12 DEG CHN IND 143 P2 TWO 149 P2 TWD 144 P2 TWD 140 P2 TWD 128 P2 TWD 127 P2 TWO 139 P2 TWD 144 P2 TWD 146 P2 TWD 137 P2 TWD 137 P2 TWD 138 P2 TWD 137 P2 TWD 137 P2 TWD 139 P2 TWD 141 P2 TWO 150 P2 TWD 144 P2 TWO 105 P2 TWO 147 P2 TWD 136 P2 TWO 140 P2 TWD 133 P2 TWD 153 P2 TWO 138 P2 TWO 145 P2 TWD 139 P2 TWD 144 P2 TWD 147 P2 TWO 135 P2 TWO 146 P2 TWD 135 P2 TWD 142 P2 TWD 143 P2 TWO 145 P2 TWO 141 P2 TWD 147 P2 TWD 140 P2 TWD 141 P2 TWD 137 P2 TWO 127 P2 TWD 144 P2 TWD 127 P2 TWD 138 P2 TWD 146 P2 TWD 135 P2 TWO 133 P2 TWO 140 P2 TWO 142 P2 TWO 131 P2 TWD 124 P2 TWD 129 P2 TWD 123 P2 TWD 131 P2 TWD 120 P2 TWO 136 P2 TWD 136 P2 TWD 138 P2 TWD 151 P2 TWD 132 P2 TWD 139 P2 TWO 140 P2 TWO 139 P2 TWD 143 P2 TWD 148 P2 TWD 147 P2 TWO 144 P2 TWO 137 P2 TWO 139 P2 TWD 144 P2 TWD 144 P2 TWD 137 P2 TWO 134 P2 TWO 137 P2 TWD 144 P2 TWD 148 P2 TWO 103 P2 TWO 77 P2 TWD 143 P2 TWD 144 P2 TWD

%TW LOCATIOI 10 010 8

010 7

009 17 010 19 010 9

010 10 008 14 010 12 011 24 010 12 010 9

011 15 013 19 011 15 011 12 010 6

011 13 010 8

010 10 013 18 010 16 014 26 010 10 014 13 014 11 011 18 014 8

012 8

014 29 011 5

011 23 011 12 014 14 010 6

011 9

010 13 011 7

013 13 010 17 014 7

014 6

015 6

008 11 010 5

010 10 013 6

008 5

009 5

009 6

008 6

007 8

007 9

007 8

007 10 007 9

007 13 010 10 010 6

010 12 010 14 010 9

010 15 010 8

014 8

014 9

013 10 010 15 010 18 010 18 014 16 010 12 011 11 008 18 011 10 011 7

014 7

010 7

010 11 010 7

011 N

EXT EXT

+0.15 UTE LTE

-0.51 UTE LTE

-0.59 UTE LTE

-0.48 UTE LTE

-0.46 UTE LTE

+0.54 UTE LTE

-0.48 UTE LTE

-0.43 UTE LTE

+0.18 UTE LTE

-0.46 UTE LTE

-0.43 UTE LTE

+0.28 UTE LTE

+0.31 UTE LTE

-0.33 LTE UTE

-0.36 LTE UTE

-0.39 LTE UTE

-0.39 LTE UTE

-0.41 LTE UTE

+0.64 LTE UTE

-0.44 LTE UTE

-0.41 LTE UTE

+0.30 LTE UTE

-0.41 LTE UTE

-0.49 LTE UTE

+0.23 LTE UTE

+0.27 LTE UTE

-0.53 LTE UTE

+0.22 LTE UTE

+0.20 LTE UTE

-0.46 LTE UTE

-0.03 LTE UTE

-0.46 LTE UTE

+0.20 LTE UTE

-0.48 LTE UTE

+0.22 LTE UTE

-0.45 LTE UTE

-0.50 LTE UTE

-0.62 LTE UTE

-0.46 LTE UTE

+0.12 LTE UTE

-0.61 LTE UTE

+0.07 LTE UTE

+0.14 LTE UTE

-0.49 LTE UTE

-0.46 LTE UTE

-0.62 LTE UTE

+0.13 LTE UTE

+0.02 LTE UTE

+0.12 LTE UTE

+0.02 LTE UTE

+0.14 LTE UTE.

+0.08 UTE LTE

+0.08 UTE LTE

+0.10 UTE LTE

+0.13 UTE LTE

+0.02 UTE LTE

+0.15 UTE LTE

+0.13 UTE LTE

-0.51 UTE LTE

+0.15 UTE LTE

+0.13 UTE LTE

-0.51 UTE LTE

+0.15 UTE LTE

+0.10 UTE LTE

-0.56 UTE LTE

+0.15 UTE LTE

-0.51 UTE LTE

-0.48 UTE LTE

-0.48 UTE LTE

-0.51 UTE LTE

-0.43 UTE LTE

+0.28 UTE LTE

-0.43 UTE LTE

-0.37 LTE UTE

-0.36 LTE UTE

+0.31 LTE UTE

+0.64 LTE UTE

+0.64 LTE UTE

-0.39 LTE UTE

-0.41 LTEUTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL 12 0

10 12 12 10 8

10 12 24 24 24 10 4

10 12 4

4 2

0 2

4 4

4 2

2 4

4 4

2 2

0 2

6 2

4 0

4 2

5 2

2 2

3 20 3

20 4

20 18 18 18 4

18 20 18 20 20 18 36 36 36 5

36 6

6 2

2 4

509 10 12 6

12 10 12 12 10 12 7

12 0

12 0

12 2

14 14 16 16 16 16 2

4 4

44 2

0 2

  1. LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510UL 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 5lOWS

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:03 AM Component: S/G B Page 36 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 70 7

0.41 0.11 0.11 70 8

0.15 0.11 70 9

0.34 0.16 0.11 0.59 0.15 70 10 0.40 0.14 0.23 0.15 0.08 70 11 0.15 0.17 70 13 0.74 0.29 0.31 0.17 0.07 70 14 0.29 70 15 0.12 0.15 70 17 0.20 70 18 0.18 0.25 0.39 0.09 70 19 0.12 70 20 0.08 70 21 0.15 70 26 0.09 70 30 0.07 70 40 0.08 70 70 0.16 70 71 0.11 70 73 0.12 70 77 0.11 70 81 0.25 70 84 0.12 70 113 0.14 0.08 70 115 0.10 0.18 70 116 0.23 0.06 70 117 0.12 70 118 0.12 70 120 0.14 70 121 0.26 70 122 0.14 0.12 70 123 0.26 70 124 0.26 70 125 0.10 0.17 0.08 70 129 0.13 0.10 70 131 0.09 71 1

0.10 0.14 0.08 0.33 0.22 71 2

0.47 71 3

0.43 71 4

0.14 0.18 71 5

0.20 0.11 71 6

0.31 71 7

0.50 71 8

0.40 0.25 0.12 0.09 71 9

0.35 DEG CHN 137 P2 148 P2 153 P2 142 P2 143 P2 139 P2 138 P2 151 P2 136 P2 106 P2 140 P2 143 P2 135 P2 118 P2 149 P2 141 P2 148 P2 133 P2 134 P2 136 P2 143 P2 151 P2 146 P2 135 P2 148 P2 147 P2 138 P2 130 P2 141 P2 153 P2 153 P2 126 P2 150 P2 138 P2 143 P2 134 P2 123 P2 131 P2 131 P2 124 P2 131 P2 108 P2 139 P2 122 P2 147 P2 139 P2 139 P2 124 P2 147 P2 145 P2 145 P2 139 P2 133 P2 124 P2 137 P2 134 P2 153 P2 148 P2 140 P2 138 P2 150 P2 145 P2 135 P2 141 P2 147 P2 142 P2 137 P2 135 P2 136 P2 121 P2 148 P2 145 P2 155 P2 141 P2 134 P2 136 P2 140 P2 140 P2 142 P2 139 P2 IND %TW TWD 18 TWD 6 TWD 6 TWD 9 TWD 7 TWD 16 TWD 8 TWD 6 TWD 24 TWD 8 TWD 20 TWD 8 TWD 13 TWD 9 TWD 5 TWD 8 TWD 9 TWD 29 TWD 15 TWD 16 TWD 10 TWD 5 TWD 13 TWD 7 TWD 8 TWD 11 TWD 9 TWD 12 TWD 17 TWD 5 TWD 7 TWD 4 TWD 8 TWD 6 TWD 5 TWD 5 TWD 12 TWD 8 TWD 9 TWD 8 TWD 18 TWD 10 TWD 11 TWD 7 TWD 8 TWD 13 TWD 17 TWD 6 TWD 9 TWD 10 TWD 11 TWD 17 TWD 11 TWD 10 TWD 18 TWD 18 TWD 8 TWD 12 TWD 7 TWD 10 TWD 8 TWD 7 TWD 6 TWD 7 TWD 5 TWD 16 TWD 11 TWD 20 TWD 21 TWD 7 TWD 9 TWD 11 TWD 7 TWD 15 TWD 23 TWD 18 TWD 13 TWD 6 TWD 5 TWD 18 LOCATION 010

-0.43 n11

+0.31 014

-0.49 011

-0.41 011

+0.29 010

-0.43 011

-0.43 013

+0.18 014

+0.21 010

+0.59 011

-0.46 013

+0.17 014

+0.22 010

+0.61 011

+0.27 014

-0.54 011

-0.46 011

-0.48 014

-0.61 014

+0.15 010

-0.46 011

+0.22 011

-0.50 009

+0.23 011

-0.54 011

-0.56 010

-0.52 013

-0.69 011

-0.54 013

+0.02 010

-0.48 008

+0.16 010

-0.49 015

-0.05 009

+0.12 009

+0.02 007

+0.13 007

+0.13 007

+0.10 007

+0.13 007

+0.13 007

+0.10 010

+0.13 013

+0.03 014

+0.03 010

+0.15 010

+0.13 014

+0.05 010

+0.13 010

+0.51 010

-0.51 010

+0.54 010

-0.50 010

+0.58 010

-0.49 010

-0.46 014

-0.51 011

+0.20 009

+0.54 012

-0.46 011

+0.28 001

+0.31 002

-0.28 003

+0.38 009

-0.43 "011

-0.31 015

+0.60 011

-0.33 011

-0.37 010

+0.69 014

+0.28 011

-0.39 014

-0.44 011

-0.41 010

-0:41 011

-0.41 014

+0.23 011

+0.28 014

-0.51 014

+0.22 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

4 4

4 2

2 4

4 4

4 4

2 2

2 2

5 2

5 4

4 2

2 2

0 2

0 2

20 18 3

18 18 20 20 5

20 0

20 18 20 18 36 36 36 6

8 6

8 2

2 14 5

14 16 16 14 3

14 16 7

14 14 16 14 7

14 16 14 16 16 0

16 16 16 16 4

4 4

4 4

4 2

4 4

2 4

2 4

2 4

4 4

4 2

LEG PROBE INLET 51OXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET

.510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name: ONSi Repi 4/22/2008 9:48:03 AM Component: S/G B Page 37 of 74 ON1S1R-E0C24 -

Tube Support Wear QUERY: Query~l[2]

ROW TUBE VOLTS

1========

71 10 0.30 0.33 0.10 0.10 71 11 0.90 0.20 0.15 0.43 71 12 0.37 0.18 0.10 0.23 71 13 0.21 0.25 0.13 71 14 0.13 71 15 1.29 0.27 71 16 0.14 0.52 0.48 0.17 0.20 0.10 71 17 0.21 0.12 0.14 0.11 0.44 0.13 71 18 0.09 0.83 0.15 71 30 0.08 71 77 0.11 71 83 0.09 71 84 0.15 71 85 0.09 71 98 0.08 71 113 0.14 71 115 0.27 71 116 0.09 0.07

'71 117 0.47 71 118 0.22 71 119 0.12 0.12 0.08 71 120 0.18 71 121 0.08 71 122 0.22 71 123 0.11 71 124 0.39 0.38 71 125 0.34 0.28 0.16 0.08 0.08 0.98 71 132 0.11 72 1

0.17 0.13 0.17 0.47 0.07 72 2

0.15 72 3

0.12 0.52 0.21 72 4

0.58 72 5

0.22 0.11 0.11 72 6

0.30 72 7

0.11 72 8

0.26 72 9

0.34 0.16 0.19 DEG CHN 139 P2 145 P2 107 P2 138 P2 130 P2 143 P2 145 P2 138 P2 138 P2 148 P2 149 P2

.145 P2 135 P2 144 P2 145 P2 142 P2 126 P2 140 P2 149 P2 139 P2 133 P2 140 P2 139 P2 143 P2 148 P2 137 P2 136 P2 135 P2 136 P2 139 P2 150 P2 131 P2 134 P2 150 P2 141 P2 137 P2 131 P2 131 P2 122 P2 142 P2 139 P2 140 P2 158 P2 135 P2 139 P2 144 P2 147 P2 142 P2 150 P2 149 P2 135 P2 125 P2 137 P2 137 P2 132 P2 137 P2 137 P2 153 P2 155 P2 126 P2 133 P2 131 P2 138 P2 141 P2 135 P2 124 P2 139 P2 48 P2 132 P2 145 P2 133 P2 146 P2 145 P2 144 P2 142 P2 146 P2 144 P2 139 P2 142 P2 145 P2 IND %TW TWO 15 TWO 15 TWO 5 TWO 6 TWO 33 TWO 11 TWO 9 TWO 21 TWO 17 TWO 9 TWO 5 TWO 12 TWO 12 TWO 14 TWO 8 TWO 7 TWD 38 TWO 14 TWO 7 TWO 21 TWO 20 TWO 8 TWO 10 TWO 5 TWO 11 TWO 7 TWO 8 TWO 6 TWO 20 TWO 7 TWO 5 TWO 29 TWO 7 TWO 5 TWO 9 TWO 8 TWO 12 TWO 6 TWO 7 TWO 10 TWO 19 TWO 7 TWO 6 TWO 27 TWO 15 TWO 10 TWO 10 TWO 7 TWO 13 TWO 6 TWO 15 TWO 9 TWO 24 TWO 23 TWO 22 TWO 19 TWO 13 TWO 6 TWO 7 TWO 40 TWO 9 TWO 9 TWO 7 TWO 9 TWO 20 TWO 4 TWO 9 TWO 7 TWO 22 TWO 11 TWD 25 TWO 11 TWO 6 TWO 6 TWO 15 TWO 6 TWO 14 TWO 16 TWO 8 TWO 10 LOCATION 011

-0.46 014

-0.51 013

-0.54 014

+0.20

'010

-0.46 011

-0.46 011

+0.24 014

+0.17 010

-0.46 011

-0.46 011

+0.20 013

-0.61 010

-0.48 011

-0.49 011

+0.22 011

-0.50 011

-0.52 014

+0.12 010

-0.47 011

-0.53 014

-0.60 014

+0.10 013

-0.65 013

+0.02 011

-0.56 011

+0.14 013

-0.69 014

-0.62 014

+0.10 010

-0.48 010

-0.45 011

-0.57 013

-0.68 009

+0.12 007

+0.13 007

+0.10 007

+0.13 007

+0.10 007

+0.10 010

+0.16 010

+0.15 010

+0.15 010

-0.54 010

+0.15 010

+0.13 010

+0.51 009

+0.53 013

+0.13 010

+0.51 010

-0.48 010

+0.54 010

-0.46 011

+0.20 010

-0.46 011

-0.25 010

-0.46 009

+0.51 012

-0.53 013

-0.54 011

+0.18 005

-0.40 002

-0.28 003

-0.28 004

+0.38 011

-0.33 003

+0.41 011

-0.34 010

+0.66 011

-0.36 014

+0.28 011

-0.39 014

+0.28 011

-0.41 014

-0.43 011

-0.39 011

-0.41 010

-0.44 011

-0.41 014

-0.51 014

+0.20 EXT LTEI LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE EXT UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE LTE LTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL #

4 4

0 4

0 4

2 2

2 2

4 4

4 4

2 2

2 0

20 18 18 20 20 20 1

20 3

20 0

20 18 18 18 18 18 4

18 20 20 20 36 6

2 2

4 10 7

519 14 16 16 14 16 14 14 0

14 16 3

14 16 14 16 16 14 14 14 6

14 3

14 LAR 14 16 4

4 4

4 4

2 4

4 4

2 4

0 4

3 4

2 4

2 4

4 0

4 LEG PROBE INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 51OUL OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET' 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510xB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name:

TNSI Repp 4/22/2008 9:48:03 Am Component: S/G B Page 38 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: Query~l[2]

ROW TUBE VOLTS 72 10 0.89 0.17 72 11 0.09 0.24 72 12 0.17 72 13 0.40 0.57 0.17 72 14 1.13 72 15 0.16 72 16 0.18 72 17 0.17 0.08 72 18 0.22 72 19 0.08 72 26 0.14 72 31 0.08 72 72 0.10 72 81 0.06 0.10 72 84 0.08 72 86 0.08 72 96 0.11 72 112 0.24 72 113 0.10 72 115 0.09 72 116 0.33 0.76 0.13 72 117 0.08 0.17 0.09 72 118 0.29 0.17 0.09 72 119 0.18 0.11 72 120 0.12 72 121 0.23 72 123 0.14 72 125 0.09 0.12 72 127 0.09 0.09 72 131 0.16 0.12 0.09 0.09 0.08 73 1

0.24 0.16 0.13 0.09 0.17 73 2

0.20 0.37 73 4

0.14 73 5

0.09 0.44 0.09 73 6

0.45 73 7

0.21 0.26 73 8

0.36 73 10 0.34 0.16 0.38 0.26 0.27 0.17 73 12 0.95 0.18 0.17 0.44 73 13 0.09 0.48 0.62 0.40 0.21 73 14 0.56 DEG CHN 131 P2 135 P2 158 P2 145 P2 147 P2 140 P2 135 P2 140 P2 130 P2 138 P2 140 P2 140 P2 143 P2 142 P2 134 P2 144 P2 145 P2 135 P2 138 P2 137 P2 148 P2 103 P2 110 P2 141 P2 145 P2 149 P2 143 P2 129 P2 138 P2 142 P2 144 P2 149 P2 137 P2 137 P2 147 P2 146 P2 156 P2 137 P2 146 P2 147 P2 151 P2 147 P2 125 P2 146 P2 143 P2 141 P2 147 P2 147 P2 144 P2 139 P2 134 P2 152 P2 141 P2 143 P2 135 P2 129 P2 65 P2 143 P2 136 P2 141 P2 133 P2 143 P2 146 P2 135 P2 138 P2 148 P2 134 P2 140 P2 133 P2 145 P2 131 P2 145 P2 146 P2 141 P2 145 P2 137 P2 131 P2 136 P2 139 P2 140 P2 IND %TW TWD 32 TWD 10 TWD 5 TWD 12 TWD 10 TWD 19 TWD 25 TWD 10 TWD 35 TWD 9 TWD 9 TWD 9

TWO 5 TWD 11 TWD 5

TWD 9 TWD 6

TWD 9

TWD 6

TWD 9 TWD 7 TWD 6 TWD 8

TWD 17 TWO 8 TWD 7 TWD 22 TWD 36 TWD 11 TWD 6 TWD 12 TWD 7

TWD 20 TWD 13 TWD 7

TWD 13 TWD 9

TWD 10 TWD 16 TWD 10 TWD 7 TWD 9 TWD 7 TWD 7 TWD 12 TWD 9 TWD 7 TWD 7

TWD 6 TWD 12 TWD 9

TWD 7.

TWD 5

TWD 9 TWD II TWD 18 TWD 8

TWD 5 TWD 19 TWD 5

TWD 21 TWD 11 TWD 13 TWD 18 TWD 17 TWD 9 TWD 19 TWD 14 TWD 14 TWD 10 TWD 32 TWD 10 TWD 9 TWD 19 TWD 6 TWD 22 TWD 26 TWD 19 TWO 12 TWD 22 LOCATION 010

-0.46 014

-0.56 011

-0.48 014

-0.54 011

-0.49 010

-0.48 011

-0.51 013

-0.63 011

-0.50 010

-0.48 013

-0.68 010

-0.49 007

-0.59 010

-0.49 010

-0.49 009

-0.59 009

+0.00 007

+0.07 008

-0.69 007

+0.13 007

+0.13 007

+0.13 007

+0.10 010

+0.10 010

+0.10 010

+0.13 014

-0.69 010

+0.13 014

+0.05 013

+0.10 010

+0.15 010

-0.54 014

-0.64 010

+0.18 009

+0.15 010

+0.51 009

+0.51 010

-0.51 010

-0.49 010

-0.46 011

+0.20 009

+0.54 010

-0.43 011

+0.26 008

+0.23 008

-0.46 003

+0.35 002

+0.38 002

+0.08 001

+0.43 003

-0.28 004

+0.38 005

+0.35 008

-0.38 004

+0.39 011

-0.32 010

+0.66 009

-0.46 011

-0.38 014

+0.28 011

-0.39 010

-0.41 014

+0.26 014

+0.22 010

-0.46 011

+0.29 013

-0.56 014

-0.54 014

+0.20 011

-0.44 010

-0.46 011

-0.48 014

-0.59 014

+0.15 009

-0.53 011

-0.49 014

-0.59 010

-0.48 013

-0.61 011

-0.51 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

2 0

2 0

4 0

4 2

2 2

2 20 18 20 18 18 20 18 36 36 5

509 2

5 2

2 10 10 14 16 5

16 14 14 7

14 16 16 0

16 14 14 4

14 16 9

16 2

14 16 16 16 9

16 16 4

16 16 16 16 16 16 4

4 4

4 4

2 2

6 2

4 4

0 4

2 4

4 2

2 2

2 2

2 0

2 4

4 4

4 2

2 2

5 2

5 2

20 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET

.OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:04 AM Component: S/G B Page 39 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl(2]

ROW TUBE VOLTS 0.47 0.23 0.11 73 15 0.14 0.20 0.16 0.15 73 16 0.73 73 18 0.16 73 70 0.15 73 71 0.13 73 73 0.19 73 77 0.12 73 82 0.13 73 84 0.12 0.10 73 96 0.10 73 114 0.16 73 115 0.17 73 116 0.09 73 117 0.84 73 118 0.18 0.14 0.08 73 120 0.15 0.11 73 121 0.13 0.10 73 122 0.32 0.08 73 123 0.12 73 124 0.11 73 127 0.13 73 130 0.09 0.11 0.09 73 132 0.19 0.30 0.20 0.23 0.12 0.59 74 1

0.18 0.16 0.07 74 2

0.40 74 3

0.21 74 4

0.17 0.48 74 5

0.43 0.20 74 6

0.32 74 7

0.30 74 8

0.65 0.23 0.25 74 10 0.47 74 12 0.47 0.19 74 13 0.90 0.16 74 14 0.25 0.29 0.24 0.10 74 15 0.24 0.33 0.12 0.14 74 16 0.11 0.85 74 17 0.44 0.44 0.10 0.20 0.37 0.28 74 18 0.17 74 19 0.20 0.13 DEG 136 139 144 126 136 139 149 137 130 129 127 133 136 131 136 123 105 142 141 139 130 146 142 139 148 144 147 149 141 137 146 138 141 143 139 129 143 138 141 132 141 134 130 128 147.

132 138 98 134 135 148 135 140 131 146 142 135 135 146 131 136 148 135 145 151 132 140 147 129 149 135 133 138 136 147 138 143 143 139 131 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW LOCATION TWD 20 014

-0.58 TWD 11 010

-0.45 TWD 6 011

+0.19 TWD 8 008

+0.16 TWD 11 013

-0.65 TWD 9 014

-0.60 TWD 9 011

-0.50 TWD 27 011

-0.55 TWD 8 008

+0.14 TWD 12 007

+0.13 TWO 11 007

-0.67 TWD 16 007

-0.77 TWD 10 007

+0.10 TWD 11 007

+0.13 TWD 10 007

-0.68 TWD 8 007

+0.10 TWD 6 007

+0.15 TWD 12 010

+0.13 TWD 12,010

+0.13 TWO 7 010

+0.15 TWD 37 010

+0.15 TWD 14 013

-0.69 TWD 11 010

+0.15 TWD 7 009

+0.18 TWD 12 010

-0.51 TWD 9 009

+0.53

/

TWD 10 010

-0.49 TWD 8 013

+0.13 TWD 21 010

-0.48 TWD 7 011

+0.13 TWD 9 010

-0.46 TWD 9 010

-0.46 TWD 10 009

+0.54 TWO 8

002

+0.38 TWO 9 002

+0.03 TWD 8 002

-0.33 TWD 14 015

+0.53 TWD 19 013

+0.26 TWD 14 005

-0.38 TWD 16 003

-0.36 TWD 9 002

-0.31 TWD 31 001

+0.00 TWD 9 003

-0.28 TWD 8 004

-0.30 TWD 4 005

+0.35 TWD 19 011

-0.34 TWD 11 011

-0.36 TWD 10 010

+0.66 TWD 22 011

-0.39 TWD 19 011

-0.38 TWD 10 014

-0.46 TWD 17 010

-0.39 TWD 14 011

-0.41 TWD 27 010

-0.44 TWD 13 014

-0.49 TWD 14 014

+0.25 TWO 22 010

-0.46 TWO 22 010

-0.46 TWD 11i 011

-0.51 TWO 32 011

-0.51 TWD 9 013

-0.63 TWO 12 011

-0.49 TWD 13 014

-0.59 TWD 11 014

+0.12 TWD 5 011

+0.22 TWD 13 014

-0.61 TWD 16 014

+0.12 TWO 7 015

+0.05 TWO 8 008

+0.15 TWD 6 010

-0.49 TWD 29 011

-0.51 TWD 20 010

-0.49 TWD 20 011

-0.56 TWD 6 013

-0.64 TWD 11 013

+0.07 TWD 18 014

-0.63 TWD 14 014

+0.07 TWD 8 013

-0.66 TWD 11 011

-0.57 TWD 8 013

-0.69 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE

  • LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE

- UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE -LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR.

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL #

20 0

20 3

20 18 18 18 4

18 20 20 6

8 509 8

509 6

2 2

3 2

4 589 14 16 7

14 16 14 14 14 14 14 16 0

16 14 0

14 16 14 16 5

14 0

14 3

14 16 16 16 16 16 16 4

4 4

2 4

4 2

2 4

4 2

4 2

2 2

2 2

2 2

2 20 20 20 3

20 18 18 18 18 20 20 18 18 18 18 18 18 20 18 18 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB S1OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

ONSI Reol 4/22/2008 9:48:04 AM Component: S/G B Page 40 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 74 24 0.07 0.13 74 32 0,08 74 42 0.08 74 65 0,10 74 70 0.20 74 80 0.10 74 82 0,11 74 83 0.12 74 93 0.10 74 113 0,11 74 114 0,15 74 115 0.16 74 116 0,25 74 117 0.31 74 118 0.20 0.09 0.06 74 120 0.20 74 121 0,16 0.06 74 122 0.25 74 124 0,06 74 125 0.18 74 126 0,11 74 128 0.11 74 130 0,19 0.12 75 1

0.24 0.20 0.17 0o09 0.10 0.10 0.17 0.06 0.12 0.11 0.09 0.73 0.11 75 2

0.22 0.29 0.47 75 3

0.09 75 5

0.44 75 6

0.19 0.12 75 7

0.32 75 8

0.16 75 10 0.78 0.12 75 11 0.14 1.04 0.14 0.32 75 12 0.21 75 13 0.32 0.22 0.19 75 14 0.39 0.25 75 15 0.23 75 16 0.14 0.12 0.36 0.14 75 17 0.15 75 18 0.19 0.16 75 20 0.23 0.19 75 21 0.14 75 40 0.08 75 69 0.12 75 71 0.18 0.21 75 72 0.10 75 78 0.16 75 81 0.15 DEG CHN 156 P2 152 P2 143 P2 130 P2 121 P2 133 P2 139 P2 125 P2 132 P2 121 P2 147 P2 145 P2 145 P2 142 P2 142 P2 144 P2 133 P2 160 P2 146 P2 148 P2 144 P2 140 P2 143 P2 145 P2 100 P2 140 P2 128 P2 137 P2 132 P2 145 P2 137 P2 145 P2 127 P2 123 P2 131 P2 153 P2 131 P2 49 P2 149 P2 132 P2 68 P2 142 P2 133 P2 134 P2 133 P2 136 P2 146 P2 145 P2 141 P2 140 P2 132 P2 150 P2 138 P2 125 P2 142 P2 140 P2 146 P2 140 P2 130 P2 150 P2 139 P2 143 P2 145 P2 133 P2 149 P2 137 P2 142 P2 146 P2 148 P2 134 P2 135 P2 141 P2 145 P2 143 P2 84 P2 141 P2 107 P2 130 P2 127 P2 138 P2 IND %TW TWD 5 TWD 8 TWD 5 TWO 6 TWD 9 TWD 14 TWD 7 TWD 9 TWD 9 TWD 6 TWD 9 TWO 12 TWD 12 TWD 18 TWD 20 TWD 15 TWO 7 TWD 6 TWO 15 TWD 12 TWO 5 TWD 18 TWD 5 TWD 13 TWD 9 TWD 9 TWD 14 TWD 10 TWD 12 TWD 10 TWD 9 TWD 5 TWD 5 TWD 6 TWD 9 TWD 4 TWD 7 TWD 6 TWD 5 TWD 28 TWD 6 TWD 12 TWD 15 TWD 22 TWD 5 TWD 19 TWD 11 TWD 7 TWD 15 TWD 9 TWD 29 TWD 7 TWD 8 TWO 35 TWD 8 TWD 16 TWD 11 TWD 17 TWD 12 TWD 11 TWD 17 TWD 12 TWD 12 TWD 7 TWD 6 TWD 16 TWD 7 TWD 8 TWO 9 TWD 8 TWD 11 TWD 9 TWD 8 TWD 5 TWD 11 TWD 13 TWD 9 TWD 9 TWD 12 TWD 12 LOCATION EXT EXT UTIL 1

009

+0.02 LTE UTE WAR 010

-0.50 LTE UTE WAR 009

+0.02 LTE UTE WAR 009

+0.02 LTE UTE WAR 007

+0.07 UTE LTE WAR 007

+0.13 UTE LTE WAR 007

+0.10 UTE LTE WAR 007

+0.13-UTE LTE WAR 007

+0.13 UTE LTE WAR 007

+0.15 LTE UTE WAR 0o0

+0.10 UTE LTE WAR 010

+0.13 UTE LTE WAR 010

+0.15 UTE LTE WAR 010

+0.13 UTE LTE WAR 010

+0.15 UTE LTE WAR 013

+0.15 UTE LTE WAR 009

+0.18 UTE LTE WAR 008

-0.48 UTE LTE WAR 010

-0.48 UTE LTE WAR 010

-0.49 UTE LTE WAR 008

+0.18 UTE LTE WAR 010

-0.46 UTE LTE WAR 010

-0.43 UTE LTE WAR 010

-0.46 UTE LTE WAR 009

+0.51 UTE LTE WAR 009

+0.56 UTE LTE WAR 005

-0.38 UTE LTE WAR 011

+0.25 UTELTE WAR 003

-0.30 LTE UTE WAR 004

+0.41 LTE UTE WAR 005

-0.30 LTE UTE WAR 008

-0.41 LTE UTE WAR 003

+0.41 LTE UTE*

WAR 004

-0.08 LTE UTE WAR 005

+0.28 LTE UTE WAR 008

+0.33 LTE UTE

  • WAR 001

+0.43 LTE UTE WAR 010

+0.66 LTE UTE WAR 009

-0.41 LTE UTE WAR 002

+0.10 LTE UTE WAR 009

+0.08 LTE UTE WAR 003

-0.31 LTE UTE WAR 004

-0.29 LTE UTE WAR 011

-0.34 LTE UTE WAR 009

-0.38 LTE UTE WAR 011

-0.41 LTE UTE WAR 011

-0.39 LTE UTE WAR 013

-0.47 LTE UTE WAR 014

-0.46 LTE UTE WAR 010

-0.41 LTE UTE WAR 010

-0.43 LTE UTE WAR 011

-0.48 LTE UTE WAR 009

-0.46 LTE UTE WAR 010

-0.44 LTE UTE WAR 011

+0.27 LTE UTE WAR 014

+0.22 LTE UTE WAR 011

-0.48 LTE UTE WAR 011

-0.51 LTE UTE WAR 013

-0.59 LTE UTE WAR 010

-0.46 LTE UTE WAR 011

-0.51 LTE UTE WAR 010

-0.46 LTE UTE WAR 011

-0.54 LTE UTE WAR 010

-0.46 LTE UTE WAR 013

+0.10 LTE UTE WAR 014

+0.10 LTE UTE WAR 014

-0.61 LTE UTE WAR 011

-0.56 LTE UTE WAR 010

-0.46 LTE UTE WAR 013

-0.66 LTE UTE WAR 011

-0.56 LTE UTE WAR 014

-0.66 LTE UTE WAR 010

-0.49 LTE UTE WAR 009

+0.02 LTE UTE WAR 007

+0.05 UTE LTE WAR 008

-0.76 UTE LTE WAR 007

+0.13 UTE LTE WAR 007

+0.10 UTE LTE WAR 007

+0.10 UTE LTE WAR 007

+0.13 UTE LTE WAR UTIL 2

CAL #

36 4

36 36 36 6

509 6

7 511 2

4 5

589 16 4

14 12 16 14 16 14 7

14 14 14 16 16 14 4

14 16 7

14 8

14 14 5

14 4

4 4

4 4

4 4

4 0

4 0

4 4

17 4

0 4

2 2

2 4

4 2

0 2

4 2

4 0

4 2

2 2

2 4

2 2

0 2

20 3

20 18 20 20 20 20 18 20 20 20 20 18 36 5

505 6

6 6

505 6

2 LEG PROBE INLET 510XB INLET 510XB INLET 50XB INLET 510XB OUTLET 51OUL OUTLET 510XB OUTLET 51OUL OUTLET 510XB OUTLET 510XB INLET 51OUL OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB.

OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 5IOXB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 51OUL OUTLET 510XB OUTLET 510XB OUTLET 51OUL OUTLET 510XB OUTLET 510XB

AREVA NP Inc Customer Name: ONSI Reol 4/22/2008 9:48:04 AM Component:

S/G B Page 41 of 74 Customer Name: ONS1 Repl ONSlBR-EOC24 Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS

7====

1=====

75 82 0.10 75 84 0.14 75 112 0.09 75 113 0.12 75 116 0.10 75 117 0.75 75 118 0.23 75 120 0.06 75 121 0.15 75 122 0.27 75 123 0.20 75 127 0,08 75 129 0.07 75 130 0.20 0.14 0.78 0.11 75 131 0.14 0.07 0.18 75 132 0.13 0.14 76 1

0.11 0.51 0.16 76 2

0.33 0.14 0.13 0.22 0.19 0.20 0.08

0. 63 76 3

0.14 0.13 76 4

0.10 0.21 0.17 76 5

0.11 0.56 76 6

0.19 76 7

0.31 76 8

0.22 76 9

0.32 0.23 0.15 0.09 76 10 0.80 0.30 0.17 0.13 0.11 76 11 0.17 76 13 0.15 1.32 0.55 76 14 0.63 76 15 0.09 0.10 0.46 76 16 0.09 0.22 76 17 0.12 76 18 0.10 76 62 0.10 76 69 0.13 76 71 0.13 76 113 0.14 76 115 0.08 76 116 0.11 76 117 0.27 76 118 0.14 0.10 76 119 0.09 76 120 0.09 76 121 0.16 76 122 0.22 76 123 0.21 76 124 0.30 76 129 0.18 DEG C 130 P 139 P 136 P 128 P 134 P 130 P 140 P 139 P 144 P 142 P 139 P 145 P 133 P 141 P 135 P 131 P 148 F 134 P 124 F 135 P 131 F 137 F 125 F 136 F 139 P 134 P 132 P 133 P 143 138 134 1 147 135 93 143 142 120 144 127 133 144 142 148 134 146 133 139 131 142 140 144 136 150 147 126 134 135 117 142 138 151 132 128 110 124 121 145 146 151 141 139 147 146 149 139 136 138 140 139 141 HN 2

2 2

2 2

2 2

2 2

2 2

2

'2

'2 2

'2

'2

'2

'2

'2

'2

'2

'2

'2

'2 2

2 2

P2 P2 2

P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW LOCATION TWD 7 007

-0.66 TWD 11 007

+0.10 TWD 7 010

+0.16 TWD 9 014

-0.74 TWD 8 010

-0.54 TWD 35 010

+0.13 TWD 16 010

+0.15 TWD 5 006

+0.23 TWD 11 010

-0.49 TWD 18 010

-0.49 TWD 14 010

-0.46 TWD 7 011

+0.26 TWD 6 003

-0.38 TWD 14 013

+0.28 TWD 11 012

-0.44 TWD 36 011

+0.28 TWD 9 011

-0.15 TWD 11 005

-0.41 TWD 5 003

-0.38 TWD 13 001

-0.33 TWD 10 009

+0.53 TWD 11 005

-0.38 TWD 6 004

-0.40 TWD 22 011

-0.33 TWD 8 013

-0.38 TWD 15 003

-0.28 TWD 8 005

-0.20 TWD 7 006

-0.35 TWD 11 001

+0.10 TWD 10 002

-0.28 TWD 10 002

+0.38 TWD 5 003

+0.38 TWD 25 004

+0.08 TWD 8 010

+0.66 TWD 8 014

+0.30 TWD 5 009

-0.45 TWD 11 010

+0.65 TWD 9

014

+0.29 TWD 6 009

-0.44 TWD 25 011

-0.41 TWD 10 010

-0.39 TWD 16 011

-0.41 TWD 11 011

-0.44 TWD 16 010

-0.44 TWD 13 011

-0.44 TWD 9 014

+0.24 TWD 6 011

+0.23 TWD 29 010

-0.44 TWD 15 011

-0.45 TWD 9 013

-0.58 TWD 7 014

+0.21 TWD 6 010

-0.03 TWD 10 011

-0.47 TWD 9

010

+0.57 TWD 39 011

-0.47 TWD 24 010

-0.46 TWD 24 011

-0.46 TWD 5 007

-0.51 TWD 6 010

-0.46 TWD 21 011

-0.54 TWD 5 008

+0.17 TWD 11 013

-0.66 TWD 7 013

-0.71 TWD 5 007

-0.54 TWD 8 007

+0.05 TWD 10 007

+0.13 TWD 10 007

+0.13 TWD 11 010

+0.10 TWD 7 010

+0.13 TWD 9 010

+0.13 TWD 18 010

+0.15 TWO 11 013

+0.13 TWD 8

014

-0.56 TWD 7 006

+0.23 TWD 7 010

-0.51 TWD 12 010

-0.46 TWD 16 010

-0.49 TWD 15 010

-0.46 TWD 19 011

+0.20 TWO 13 012

-0.46 EXT EXT UTIL UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR 1

UTIL 2

CAL #

4 2

4 517 5

519 8

16 16 16 16 16 16.

16 4

16 16 16 16 16 16 16 16 16 16 16 4

4 4

4 4

4 4

4 4

4 14 4

2 2

4 4

4 2

2 4.

2 4

2 2

2 4

2 4

4 4

4 0

4 2

2 2

4 2

20 18 18 18 20 20 18 20 6

6 6

16 5

16 6

16 16 16 7

16 16 16 16 16 16 16 16 LEG OUTLET OUTLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510XB 510MB 51OUL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510MB 510XB 510XB 510XB 510MB 510XB 510XB 510XB 510MB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:04 AM Component: S/G B Page 42 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 0.72 76 130 0.09 76 131 0.17 0.12 77 1

0.11 0.13 0.11 0.23 0.54 0.13 0.10 77 2

0.24 0.14 0.08 0.13 0.26 77 3

0.21 0.16 77 4

0.31 77 5

0.10 0.29 77 6

0.39 77 7

0.35 77 8

0.50 0.29 77 9

0.16 77 10 0.25 0.12 77 11 0.18 77 12 1.20 0.10 77 13 0.42 77 14 0.16 77 16 0.20 0.15 0.35 0.43 0.09 77 17 0.11 0.14 0.12 77 18 0.21 0.11 0.19 77 40 0.05 77 44 0.08 77 50 0.05 77 52 0.09 0.06 0.06 77 67 0.11 77 68 0.12 77 71 0.11 77 73 0.09 77 74 0.09 77 82 0.09 77 115 0.16 0.20 0.27 77 117 0.17 77 118 0.24 77 120 0.09 77 121 0.18 0.06 0.12 77 122 0.12 0.12 77 123 0.08 77 128 0.13 77 130 0.10 77 132 0.12 78 4

0.27 78 5

0.22 78 6

0.31 78 7

0.16 0.36 78 9

0.39 0.10 78 12 0.86 78 13 1.16 DEG CHN 131 P2 149 P2 128 P2 131 P2 139 P2 132 P2 132 P2 142 P2 134 P2 133 P2 118 P2 124 P2 124 P2 104 P2 135 P2 132 P2 141 P2 140 P2 133 P2 66 P2 139 P2 136 P2 140 P2 135 P2 140 P2 151 P2 135 P2 142 P2 147 P2 124 P2 147 P2 138 P2 144 P2 133 P2 150 P2 132 P2 141 P2 152 P2 145 P2 143 P2 152 P2 139 P2 126 P2 131 P2 119 P2 144 P2 143 P2 117 P2 132 P2 156 P2 97 P2 110 P2 113 P2 110 P2 144 P2 120 P2 144 P2 136 P2 137 P2 147 P2 137 P2 149 P2 144 P2 150 P2 120 P2 148 P2 139 P2 142 P2 139 P2 136 P2 149 P2 142 P2 139 P2 138 P2 139 P2 135 P2 136 P2 150 P2 131 P2 128 P2 IND %TW TWD 34 TWD 7 TWD 12 TWD 9 TWD 7 TWD 7 TWD 7 TWD 13 TWD 24 TWD 8 TWD 6 TWD 13 TWD 8 TWD 5 TWD 8 TWD 14 TWD 12 TWD 10 TWO 16 TWD 6 TWD 15 TWD 19 TWD 18 TWD 22 TWD 15 TWD 9 TWD 13 TWD '7 TWO 10 TWD 37 TWD 6 TWD 20 TWO 9 TWD II TWD 8 TWD 17 TWD 20 TWD 5 TWD 7 TWD 8 TWD 7 TWD 11 TWO 6 TWD 10 TWD 5 TWD 7 TWD 4 TWD 8 TWD 5 TWO 5 TWO 9 TWO 11 TWD 8 TWD 8 TWD 9 TWD 8 TWD 12 TWO 14 TWO 18 TWO 12 TWD 17 TWD 7 TWO 13 TWO 5 TWD 9 TWD 9 TWD 9 TWO 7 TWD 10 TWD 8 TWD 9 TWD 14 TWD 12 TWO 16 TWO 9 TWO 18 TWD 19 TWO 6 TWD 32 TWO 36 LOCATION 011

+0.28 003

+0.30 003

-0.33 001

+0.36 002

-0.27 005

-0.34 005

+0.39 011

-0.35 012

+0.35 013

-0.40 004

-0.27 002

+0.38 005

-0.14 002

-0.26 001

+0.38 004

+0.07 001

+0.44 002

+0.41 011

-0.36 010

+0.66 011

-0.42 011

-0.39 011

-0.39 010

-0.41 011

-0.43 011

-0.42 010

-0.43 011

-0.43 011

-0.44 010

-0.43 011

+0.24 011

-0.50 011

-0.53 013

-0.68 013

+0.10 014

-0.61 014

+0.10 010

-0.46 014

-0.63 014

+0.10 011

-0.58 007

-0.53 013

-0.68 014

-0.63 008

+0.03 007

-0.69 007

+0.13 009

-0.74 008

+0.03 007

+0.10 007

+0.13 007

+0.12 007

+0.13 007

+0.13 007

+0.07 007

+0.13 014

+0.00 014

-0.61 013

-0.69 010

+0.15 010

+0.18 011

+0.13 011

+0.13 010

-0.49 010

+0.59 013

-0.59 010

+0.56 010

-0.46 009

+0.54 011

-0.41 011

+0.33 011

-0.37 011

-0.39 011

-0.42 010

-0.38 011

-0.41 010

-0.43 011

-0.46 011

-0.51.

011

-0.53 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE OTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

16 16 16 16 12 12 12 12 12 12 0

12 10 10 10 4

10 0

10 12 12 10 12 12 10 12 10 10 12 10 3

10 12 10 0

10 10 98 98 98 98 98 6

98 96 96 5

96 98 98 98 0

22 22 22 22 22 22 6

5 505 6

6 5

505 2

16 16 16 16 16 16 16 16 16 16 16 16 16 3

16 16 12 10 12 10 10 10 0

10 12 10 LEG OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSi Repi 4/22/2008 9:48:04 AM Component: S/G B Page 43 of 74 ONSIBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 78 14 0.25 0.12 78 15 1.12 78 16 0.14 0.61 0.17 78 19 0.14 0.26 0.27 0.20 78 20 0.10 78 51 0.10 78 52 0.08 0.05 78 58 0.06 78 67 0.11 78 72 0.12 78 74 0.15 78 76 0.11 78 78 0.10 78 80 0.11 78 82 0.08 78 83 0.10 78 84 0.12 78 114 0.10 78 120 0.17 78 121 0.08 78 123 0.14 78 125 0.73 78 131 0.13 0.09 79 1

0.40 0.13 0.08 0.11 0.11 0.19 0.14 0.13 0.25 79 2

0.14 0.18 0.13 0.11 0.43 0.40 0.38 79 3

0.20 79 4

"0.76 79 6

0.20 79 7

0.16 0.24 79 8

0.22 0.36 79 9

0.18 79 12 0.11 79 13 0.18 79 14 0.82 79 15 0.31 0.17 0.11 0.43 79 16 0.23 0.10 0.13 0.05 79 17 0.35 79 18 0.07 79 19 0.09 79 51 0.07 79 53 0.05 79 71 0.12 79 74 0.10 79 76 0.12 79 81 0.22 0.10 79 84 0.10 79 86 0.08 79 94 0.10 79 96 0.09 DEG CHN 141 P2 143 P2 128 P2 145 P2 133 P2 143 P2 133 P2 145 P2 141 P2 147 P2 146 P2 136 P2 129 P2 129 P2 139 P2 123 P2 126 P2 130 P2 137 P2 141. P2 116 P2 141 P2 146 P2 120 P2 145 P2 147 P2 137 P2 144 P2 133 P2 140.P2 113 P2 136 P2 128 P2 154 P2 134 P2 131 P2 141 P2 141 P2 140 P2 133 P2 137 P2 123 P2 127 P2 130 P2 134 P2 135 P2 130 P2 139 P2 128 P2 141 P2 137 P2 145 P2 131 P2 133 P2 144 P2 147 P2 148 P2 134 P2 144 P2 143 P2 137 P2 140 P2 145 P2 133 P2 147 P2 153 P2 137 P2 99 P2 151 P2 110 P2 144 P2 117 P2 128 P2 134 P2 130 P2 141 P2 105 P2 122 P2 118 P2 126 P2 IND %TW TWD 14 TWD 7 TWD 36 TWD 8 TWD 26 TWD 10 TWD 7 TWD 13 TWD 13 TWD 11 TWD 6 TWD 8 TWD 7 TWD 4 TWD 5 TWD 9 TWD 9 TWD 11 TWD 8 TWD 8 TWD 9 TWD 7 TWD 9 TWO 10 TWD 8 TWD 12 TWD 6 TWD 11 TWD 35 TWD 10 TWD 7 TWD 19 TWD 8 TWD 5 TWD 7 TWD 7 TWD 11 TWD 8 TWD 7 TWD 14 TWD 8 TWO 10 TWD 8 TWD 7 TWD 20 TWD 19 TWD 18 TWD 11 TWD 29 TWD 11 TWD 9 TWD 13 TWD 12 TWD 18 TWD 10 TWD 6 TWD 10 TWD 30 TWD 16 TWD 10 TWD 7 TWD 21 TWD 12 TWD 6 TWD 7 TWD 3 TWD 18 TWD 4 TWD 6 TWD 6 TWD 4 TWD 9 TWD 8 TWD 10 TWD 15 TWD 8 TWD 9 TWD 6 TWD 8 TWD 7 LOCATION Ol

-0.55 014

+0.15 Ol

-0.55 010

-0.46 oil

-0.58 014

-0.61 007

-0.53 011

-0.58 014

-0.68 014

+0.02 007

-0.53 007

+0.13 007

+0.13 008

+0.08 007

+0.10 007

+0.13 007

+0.15 007

+0.13 007

+0.13 007

+0.13 007

+0.10 007

+0.13 007

+0.10 007

+0.13 010

+0.13 010

+0.54 010

-0.46 010

-0.43 011

+0.23 002

+0.38 002

-0.33 001

+0.42 002

-0.29 002

+0.15 002

+0.44 003

-0.29 004

+0.37 008

+0.32 009

-0.39 005

+0.00 002

+0.28 003

-0.28 005

-0.10 008

+0.31 011

-0.36 001

+0.12 004

+0.00 011

-0.35 011

-0.39 011

-0.38 010

-0.39 011

-0.44 010

-0.41 011

-0.43 010

-0.42 011

-0.48 011

-0.50 011

-0.53 011

-0.53 013

-0.63 014

-0.58 014

+0.15 011

-0.53 013

-0.63 014

+0.05 010

-0.43 011

-0.55 007

-0.53 013

-0.68 007

+0.10 007

+0.13 007

+0.13 007

+0.15 007

+0.13 007

+0.13 008

+0.03 007

+0.10 007

+0.10 007

+0.13 007

+0.13 EXT EXT LIE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LIE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL 1

UTIL 2

WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR CAL #

96 96 98 96 96 96 98 98 98 98 96 22 22 22 22 6

6 6

6 6

6 2

505 2

16 16 16 16 16 16 16 12 12 12 12 12 12 12 12 12 10 10 10 10 10 10 10 12 10 10 12 12 10 10 12 10 10 98 96 96 96 96 98 98 98 98 96 98 96 22 22 6

6 6

6 6

2 10 10 10 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

.510XB

.510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB

AREVA NP Inc Customer Name: ONSi Repi 4/22/2008 9:48:04 AM Component:

S/G B Page 44 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[23 ROW TUBE VOLTS 79 97 0.05 79 111 0.14 79 116 0.17 79 117 0.19 0.28 0.08 79 118 0.11 79 121 0.22 79 131 0.18 80 1

0.14 0.22 0.10 80 4

0.20 80 5

0.32 80 6

0.26 80 7

0.18 80 8

0.14 80 9

0.12 0.11 80 10 0.18 80 11 0.13 80 12 0.19 80 13 0.57 0.19 0.15 0.32 0.23 0.10 80 14 0.19 80 15 0.56 80 16 0.21 0.56 0.14 0.15 80 17 0.16 80 18 0.15 80 26 0.10 80 58 0.07 80 67 0.12 80 69 0.14 80 71 0.15 80 75 0.08 80 81 0.11 80 82 0.13 80 88 0.07 80 90 0.08 80 94 0.08 80 96 0.09 80 99 0.08 80 100 0.06 80 101 0.07 80 115 0.18 0.10 80 116 0.24 0.11 80 117 0.38 0.24 0.12 0.32 80 118 0.16 80 119 0.21 0.18 80 120 0.29 80 121 0.14 80 122 0.13 80 123 0.25 80 127 0.08.

80 129 0.08 80 131 0.12 81 1

0.09 0.10 0.31 0.15 81 2

0.11 0.25 81 5

0.18 81 6

0.32 81 7

0.10 0.19 81 8

0.44 DEG CHN 104 P2 143 P2 136 P2 138 P2 139 P2 145 P2 141 P2 147 P2 139 P2 138 P2 138 P2 139 P2 141 P2 140 P2 140 P2 144 P2 150 P2 142 P2 142 P2 148 P2 151 P2 143 P2 135 P2 136 P2 146 P2 135 P2 145 P2 145 P2 150 P2 134 P2 139 P2 135 P2 133 P2 142 P2 140 P2 139 P2 150 P2 135 P2 120 P2 141 P2 114 P2 139 P2 127 P2 141 P2 124 P2 139 P2 102 P2 110 P2 137 P2 131 P2 133 P2 138 P2 132 P2 139 P2 146 P2 137 P2 142 P2 143 P2 137 P2 142 P2 141 P2 147 P2 143 P2 143 P2 135 P2 135 P2 150 P2 153 P2

,142 P2 122 P2 146 P2 142 P2 147 P2 128 P2 142 P2 141 P2 136 P2 134 P2 150 P2 134 P2 IND %TW TWD 4 TWD 10 TWD 12 TWD 14 TWD 19 TWD 7 TWD 9 TWD 15 TWD 13 TWD 8 TWD 12 TWD 6 TWD 11 TWD 16 TWD 14 TWD 10 TWD 8 TWD 7 TWD 6 TWD 10 TWD 8 TWD 11 TWD 24 TWD 11 TWD 9 TWD 16 TWD 12 TWD 6 TWD 10 TWD 25 TWD 11 TWD 24 TWD 8 TWD 8 TWD 10 TWD 8 TWD 8 TWD 6 TWD 9 TWD 10 TWD 12 TWD 7 TWD 8 TWD 11 TWD 5 TWD 6 TWD 7 TWD 7 TWD 7 TWD 5 TWD 6 TWD 14 TWD 8 TWD 17 TWD 9 TWD 24 TWD 17 TWD 10 TWD 21 TWD 12 TWD 15 TWD 13 TWD 20 TWD 11 TWD 10 TWD 17 TWD 6 TWD 6 TWD 9 TWD 6 TWD 6 TWD 16 TWD 9 TWD 7 TWD 13 TWD 10 TWD 16 TWD 6 TWD 11 TWD 21 LOCATION 007

+0.10 010

+0.10 014

+0.08 014

-0.64 010

+0.18 014

+0.10 010

+0.20 010

+0.51 011

+0.31 001

+0.44 011

-0.37 009

-0.39 011

-0.42 011

-0.41 011

-0.42 011

-0.41 011

-0.44 011

-0.41 010

-0.43 011

-0.46 011

-0.48 011

-0.49 011

-0.50 012

+0.19 014

-0.60 014

+0.15 010

-0.43 011

+0.22 014

+0.15 011

-0.53 010

-0.46 011

-0.53 014

-0.63 014

+0.10 011

-0.56 007

-0.53 014

-0.10 007

+0.13 007

+0.13 007

+0.15 007

+0.13 007

-0.69 007

+0.13 007

+0.10 007

+0.13 007

+0.13 007

+0.15 007

+0.13 007

+0.13 007

+0.15 007

+0.15 014

-0.61 010

+0.13 014

-0.59 011

+0.10 014

+0.05 014

-0.59 011

+0.10 010

+0.15 010

+0.20 011

+0.15 010

+0.56 010

+0.56 010

+0.59 010

-0.51 010

-0.51 011

+0.26 011

+0.28.

011

+0.31 002

-0.27 009

-0.39 011

-0.35 012

+0.40 003

-0.30 011

-0.34 011

-0.37 011

-0.38 010

-0.39 011

-0.42 010

-0.40 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR

.WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL #

12 16 16 16 16 16 16 16 16 12 12 6

12 12 10 12 0

10 0

12 3

10 0

10 12 4

10 12 10 10 10 10 0

10 0

10 98 96 98 98 98 0

98 4

96 98 22 22 6

6 6

6 4

507 2

10 10 10 10 10 10 12 20 20 20 5

20 20 20 20 20 20 20 20 20 20 7

20 20 16 16 16 12 12 12 12 10 10 12 10 12 12 10 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

510XB, 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB

AREVA NP Inc Customer Name: ONSi Repi 4/22/2008 9:48:05 AM Component: S/G B Page 45 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: QueryNJ.[2]

ROW TUBE VOLTS 81 9

0.25.

81 11 0.il 81 12 0.18 81 15 0.13 0.10 81 16 0.19 0.10 0.09 0.20 81 17 0.82 0.17 0.39 81 52 0.05 81 58 0.06 81 67 0.09 81 70 0.22 81 71 0.08 81 72 0.11 81 73 0.09 81 80 0.14 81 82 0.11 81 83 0.09 81 84 0.11 81 85 0.11 81 87 0.09 81 96 0.08 81 115 0.14 0.21 0.12 81 117 0.14 81 118 0.06 0.13 0.23 0.11 0.13 81 120 0.15 81 121 0.26 0.11 81 122 0.14 0.11 81 123 0.15 0.14 81 124 0.08 0.10 81 126 0.09 82 3

0.24 82 4

0.10 82 5

0.11 0.15 82 6

0.13 82 7

0.27 0.39 82 8

0.61 0.24 82 9

0.17 0.23 0.29 82 10 0.25 0.28 0.24 0.10 82 11 0.34 0.13 82 12 0.25 0.12 82 13

'0.37 82 14 0.12 0.21 0.09 0.25 0.16 82 18 0.11 82 50 0.15 82 51 0.08 0.12 82 52 0.08 0.05 82 70 0.10 82 72 0.11 82 79 0.18 DEG CHN 144 P2 146 P2 143 P2 143 P2 148 P2 144 P2 124 P2 150 P2 147 P2 132 P2 135 P2 140 P2 135 P2 117 P2 134 P2 132 P2 129 P2 121 P2 136 P2 117 P2 124 P2 142 P2 121 P2 127 P2 158 P2 143 P2 130 P2 141 P2 146 P2 144 P2 147 P2 146 P2 139 P2 141 P2 142 P2 141 P2 143 P2 149 P2 139 P2 149 P2 138 P2 145 P2 145 P2 147 P2 147 P2 142 P2 140 P2 140 P2 137 P2 145 P2 138 P2 136 P2 134 P2 142 P2 125 P2 133 P2 140 P2 141 P2 139 P2 143 P2 135 P2 139 P2 149 P2 144 P2 144 P2 137 P2 140 P2 146 P2 111 P2 139 P2 143 P2 149 P2 121 P2 138 P2 135 P2 137 P2 153 P2 126 P2 125 P2 137 P2 IND %TW LOCATION EXT EXT UTIL 1

TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD Ol 012 Oili 010 Oil 015 014 013 Oili 014 010 007 007 007 007 007 007 007 007 007 007 007 007 007 007 014 010 014 010 014 013 010 014 Ol 010 014 013 010 Oili Oil 010 013 Oili Oili Oil 010 011 Ol Oili 010 Ol 010 Oili 010 014 Ol Ol 013 014 014 Ol 013 Ol 014 Oil 011 Oil 013 014 014 011 007 007 017 007 008 007 007 007

-0.44

+0.12

-0.48

-0.46

+0.05

-0.56

-0. 63

+0.07

-0.46

-0.56

-0.63

-0.48

+0.10

+0.13

+0.13

+0.13

+0.15

+0.13

+0.12

+0.15

+0.10

+0.02

+0.10

-0.65

+0.02

+ 0.13

-0.64

+0.13

+0. 00

+0.18

+0.08

-0.64

+0.18

-0.59

+0.13

+0.53

+0.53

-0.59

+0.53

+0.

18

+0.18

-0.46

+0.23

+0.20

+0.23

-0.38

-0.39

-0.38

-0.41

-0.42

-0.40

-0.43

-0.44

-0.44

-0.43

+0.10

-0.45

-0.47

-0.57

-0.52

+0.23

-0.45

-0.56

-0.52

-0.46

-0.50

-0.49

-0.51

-0.63

-0.58

+0.15

-0.51

+0.10

+0.10

-0.69

+0.10

+0.03

+0.13

+0.13

-0.69 LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

12 0

12 10 98 98 96 96 96 0

96 98 98 3

98 22 22 6

6 4

515 6

5 505 6

2 4

505 2

3 505 4

515 10 20 20 5

20 20 20 20 20 7

20 6

20 20 20 7

20 20 8

20 8

20 6

20 20 20 20 10 12 10 0

10 12 10 10 12 12 10 10 0

10 12 12 12 0

12 10 10 12 4

12 10 96 96 96 96 96 0

98 22 22 4

22 22 22 6

6 6

LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510UL 510XB 510XB 510UL 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51PXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 51DXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB' 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Namne: ONSI Repi 4/22/2008 9:48:05 AM Component: S/G B Page 46 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: QueryMl(2J ROW TUBE VOLTS 0.09 82 80 0.10 82 82 0.12 82 86 0.07 82 87 0.09 82 110 0.11 82 112 0.21 0.12 82 114 0.31 82 115 0.11 0.21 82 116 0.13 82 118 0.13 0.12 0..11 82 119 0.10 82 120 0.21 82 121 0.17 82 122 0.19 82 123 0.15 82 124 0.15 82 127 0.74 82 128 0.15 82 129 0.10 83 1

0.13 0.26 0.09 0.29 83 2

0.10 83 3

0.31 0.16 83 5

0.12 83 6

0.18 0.17 83 7

0.19 0.12 83 8

0.21 83 9

0.16 83 10 0.16 83 11 0.11 0.11 83 12 0.22 83 13 0.10 0.52 0.24 0.34 0.10 0.16 0.24 83 14 0.17 83 16 0.22 0.10 83 19 0.15 0.08 83 20 0.23 0.09 0.09 83 71 0.11 83 72 0.12 83 74 0.09 83 76 0.11 83 80 0.16 83 81 0.14 83 84 0.09 83 116 0.44 83 120 0.14 0.09 83 121 0.14 83 122 0.15 0.11 0.21 0.16 83 123 0.14 83 125 0.16 83 127 0.20 83 129 0.17 83 132 0.11 84 7

0.14 0.14 84 8

0.22 DEG CHN 110 P2 133 P2 134 P2 142 P2 130 P2 130 P2 140 P2 142 P2 135 P2 145 P2 141 P2 136 P2 141 P2 143 P2 151 P2 151 P2 144 P2 147 P2 142 P2 144 P2 143 P2 129 P2 138 P2 150 P2 117 P2 138 P2 147 P2 144 P2 144 P2 140 P2 151 P2 150 P2 144 P2 134 P2 136 P2 145 P2 141 P2 145 P2 142 P2 144 P2 140 P2 140 P2 138 P2 132 P2 133 P2 140 P2 138 P2 143 P2 140 P2 146 P2 148 P2 146 P2 137 P2 133 P2 145 P2 156 P2 145 P2 108 P2 140 P2 122 P2 139 P2 133 P2 128 P2 123 P2 134 P2 142 P2 146 P2 142 P2 145 P2 154 P2 138 P2 150 P2 136 P2 139 P2 137 P2 147 P2 145 P2 137 P2 147 P2 144 P2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 8

8 10 7

7 9

15 10 20 9

16 10 10 9

9 8

15 13 14 12 12 36 12 8

8 14 5

15 6

16 10 7

10 10 11 7

12 9

9 7

7 12 6

23 13 17 6

9 13 10 11 5

9 5

13 5

6 8

10 7

8 12 11 8

26 11 7

12 12 9

16 12 12 13 16 14 9

8 8

12 LOCATION 007

+0.08 007

+0.20 007

+0.10 007

+0.12 007

+0.08 014

-0.66 010

+0.10 014

+0.00 010

+0.13 014

+0.03 010

+0.15 010

+0.15 014

-0.56 013

-0.62 010

+0.53 010

+0.56 010

+0.51 010

+0.53 010

+0.53 010

-0.46 010

-0.46 011

+0.26 013

-0.46 013

+0.31 003

-0.29 011

-0.32 013

-0.37 015

-0.40 009

-0.40 011

-0.34 015

+0.60 011

-0.37 011

-0.41 014

+0.27 010

-0.42 011

-0.42 010

-0.43 011

-0.44 011

-0.45 011

-0.47 014

+0.18 011

-0.47 010

-0.45 011

-0.50 013

-0.55 014

-0.55 012

+0.17 011

+0.21 014

+0.19 011

-0.51 010

-0.46 011

-0.53 014

-0.68 014

+0.02 010

-0.51 014

-0.68 014

+0.02 007

+0.13 007

+0.13 007

+0.13 007

+0.13 007

+0.13 007

+0.13 007

+0.13 010

+0.15 010

+0.53 010

-0.51 010

+0.53 013

+0.20 013

-0.58 010

+0.56 009

+0.53 010

-0.45 010

-0.43 010

-0.41 011

+0.25 011

+0.33 010

-0.42 011

-0.40 010

-0.44 EXT EXT UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE.LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE UTIL 1

UTIL WAR 4

WAR WAR WAR 4

WAR WAR WAR WAR 7

WAR WAR WAR WAR 6

WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR 3

WAR 0

WAR WAR 2

WAR 3

WAR WAR 5

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 5

WAR 5

WAR WAR WAR WAR WAR 0

WAR 2

CAL #

6 8

2 515 10 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 12 12 12 12 10 12 12 12 10 10 12 12 10 12 10 12 12 10 10 10 10 10 10 10 10 96 98 98 96 96 96 96 96 6

6 6

6 6

2 2

20 20 20 18 20 20 20 20 18 18 18 18 18 10 10 12 LEG OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET PROBE 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

.510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:48:05 AM Component: S/G B Page 46 of 74 ONSlBR-EOC24 - Tube Support Wear QUERY: QueryMl[2]

ROW TUBE 82 80 82 82 82 86 82 87 82 110 82 112 82 114 82 115 82 116 82 118 82 82 82 82 82 82 82 82 82 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 83 84 84 119 120 121 122 123 124 127 128 129 1

2 3

5 6

7 8

9 10 11 12 13 14 16 19 20 71 72 74 76 80 81 84 116 120 121 122 123 125 127 129 132 7

8 VOLTS 0.09 0.10 0.12 0.07 0.09 0.11 0:21 0.12 0.31 0.11 0.21 0.13 0.13 0.12 0.11 0.10 0.21 0.17 0.19 0.15 0.15 0.74 0.15 0.10 0.13 0.26 0.09 0.29 0.10 0.31 0.16 0.12 0.18 0.17 0.19

.0.12 0.21 0.16 0.16 0.11 0.11 0.22 0.10 0.52 0.24 0.34 0.10 0.16 0.24 0.17 0.22 0.10 0.15 0.08 0.23 0.09 0.09 0.11 0.12 0.09 0.11 0.16 0.14 0.09 0.44 0.14 0.09 0.14 0.15 0.11 0.21 0.16 0.14 0.16 0.20 0.17 0.11 0.14 0.14 0.22 DEG CHN 110 P2 133 P2 134 P2 142 P2 130 P2 130 P2 140 P2 142 P2 135 P2 145 P2 141 P2 136 P2 141 P2 143 P2 151 P2 151 P2 144 P2 147 P2 142 P2 144 P2 143 P2 129 P2 138 P2 150 P2 117 P2 138 P2 147 P2 144 P2 144 P2 140 P2 151 P2 150 P2 144 P2 134 P2 136 P2 145 P2 141 P2 145 P2 142 P2 144 P2 140 P2 140 P2 138 P2 132 P2 133 P2 140 P2 138 P2 143 P2 140 P2 146 P2 148 P2 146 P2 137 P2 133 P2 145 P2 156 P2 145 P2 108 P2 140 P2 122 P2 139 P2 133 P2 128 P2 123 P2 134 P2 142 P2 146 P2 142 P2 145 P2 154 P2 138 P2 150 P2 136 P2 139 P2 137 P2 147 P2 145 P2 137 P2 147 P2 144 P2 IND %TW LOCATION TWO 8 007

+0.08 TWD 8 007

+0.20 TWD 10 007

+0.10 TWD 7 007

+0.12 TWD 7 007

+0,08 TWD 9 014

-0.66 TWD 15 010

+0.10 TWD 10 014

+0.00 TWD 20 010

+0.13 TWD 9 014

+0.03 TWD 16 010

+0.15 TWD 10 010

+0.15 TWD 10 014

-0.56 TWD 9 013

-0.62 TWD 9 010

+0.53 TWD 8 010

+0.56 TWD 15 010

+0.51 TWD 13 010

+0.53 TWD 14 010

+0.53 TWD 12 010

-0.46 TWD 12 010

-0.46 TWD 36 011

+0.26 TWD 12 013

-0.46 TWD 8 013

+0.31 TWD 8 003

-0.29 TWD 14 011

-0.32 TWD 5 013

-0.37 TWD 15 015

-0.40 TWD 6 009

-0.40 TWD 16 011

-0.34 TWD 10 015

+0.60 TWD 7 011

-0.37 TWD 10 011

-0.41 TWO 10 014

+0.27 TWD 11 010

-0.42 TWD 7 011

-0.42 TWD 12 010

-0.43 TWD 9 011

-0.44 TWD 9 011

-0.45 TWD 7 011

-0.47 TWD 7 014

+0.18 TWD 12 011

-0.47 TWD 6 010

-0.45 TWD 23 011

-0.50 TWD 13 013

-0.55 TWD 17 014

-0.55 TWD 6 012

+0.17 TWD 9 011

+0.21 TWD 13 014

+0.19 TWD 10 011

-0.51 TWD 11 010

-0.46 TWD 5 011

-0.53 TWD 9 014

-0.68 TWD 5 014

+0.02 TWD 13 010

-0.51 TWD 5 014

-0.68 TWD 6 014

+0.02 TWD 8 007

+0.13 TWD 10 007

+0.13 TWD 7 007

+0.13 TWD 8 007

+0.13 TWD 12 007

+0.13 TWD 11 007

+0.13 TWD 8 007

+0.13 TWD 26 010

+0.15 TWD 11 010

+0.53 TWD 7 010

-0.51 TWD 12 010

+0.53 TWD 12 013

+0,20 TWD 9 013

-0.58 TWD 16 010

+0.56 TWD 12 009

+0.53 TWD 12 010

-0.45 TWD 13 010

-0.43 TWD 16 010

-0.41 TWD 14 011

+0.25 TWD 9 011

+0.33 TWD 8 010

-0.42 TWD 8 011

-0.40 TWD 12 010

-0.44 EXT EXT GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE GTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 4

6 8

2 4

515 10 20 20 7

20 20 20 20 6

20 20 20 6

20 20 20 20 20 20 20 20 20 20 12 12 12 12 10 12 12 12 10 10 12 12 10 4

12 10 12 12 10 10 10 10 10 0

10 3

10 0

10 96 2

98 3

98 96 5

96 96 96 96 6

6 6

6 6

2 2

20 20 20 18 20 20 20 20 5

18 5

18 18 18 18 10 0

10 12 OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET UTIL 2

CAL # LEG PROBE 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:05 AM Component: S/G B Page 47 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

0.21 0.10 0.10 84 9

0.09 0.18 84 10 0.54 0.19 0.25 0.14 84 11 0.25 0.43 0.14 84 12 0.32 0.16 0.17 84 13 0.34 0.17 84 14 0.15 0.55 0.38 0.27 84 15 0.43 0.04 84 18 0.32 0.19 84 29 0.05 84 39 0.08 84 51 0.09 84 69 0.10 84 72 0.11 84 80 0.12 84 84 0.24 0.18 84 114 0.24 0.08 84 118 0.31 84 120 0.19 0.24 0.09 84 121 0.16 0.22 84 124 0.35 0.23 84 129 0.14 85 1

0.29 0.14 85 3

0.22 85 7

0.13 85 8

0.22 0.24 0.38 0.13 85 9

0.18 0.16 85 10 0.16 0.80 0.32 0.18 0.35 0.13 85 11 0.25 0.17 85 12 0.59 85 13 0.17 0.12 0.16 85 14 0.13 85 15 0.10 0.13 0.63 85 16 0.36 0.09 85 17 0.36 0.11 85 19 0.20 0.10 85 66 0.12 85 73 0.15 85 74 0.10 85 75 0.10 148 140 148 144 139 136 146 137 142 142 132 133 143 134 145 140 141 145 140 136 142 139 153 135 146 143 145 139 144 125 130 124 138 141 142 135 143 140 161 143 145 138 139 141 144 137 144 128 137 145 142 149 149 139 137 129 140 145 137 137 149 149 131 150 150 143 149 132 152 139 139 140 144 152 139 144 130 130 135 107 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 TWD 12 TWD 6 TWD 6 TWD 6 TWD 10 TWD 24 TWD 11 TWD 13 TWD 8 TWD 13 TWD 20 TWD 8-'

TWD 16 TWD 9 TWD 10 TWD 17 TWD 10 TWD 8 TWD 23 TWD 18 TWD 14 TWD 21 TWD 3 TWD 16 TWD 10 TWD 5 TWD 7 TWD 8 TWD 9 TWD 8 TWD 9 TWD 18 TWD 14 TWD 18 TWD 7 TWO 22 TWD 15 TWD 18 TWD 8 TWD 13 TWD 17 TWD 23 TWD 17 TWD 12 TWD 15 TWD 8 TWD 12 TWD 8 TWD 12 TWD 13 TWD 18 TWD 7 TWD 10 TWD 9 TWD 9 TWD 30 TWD 16 TWD 10 TWD 17 TWD 7 TWD 13 TWD 10 TWD 25 TWD 9 TWD 7 TWD 9 TWD 8 TWD 6 TWD 7 TWD 25 TWD 18 TWD 5 TWD 17 TWO 6 TWD 11 TWD 6, TWD 10 TWD 10 TWD 9 TWD 9 014

+0.25 LTE UTE 011

+0.27 LTE UTE 013

-0.50 LTE.UTE 014

+0.24 LTE UTE 013

-0.53 LTE UTE 011

-0.47 LTE UTE 014

-0.50 LTE UTE 014

+0.20 LTE UTE 013

-0.55 LTE UTE 011

-0.45 LTE UTE 014

-0.51 LTE UTE 010

-0.43 LTE UTE 011

-0.52 LTE UTE 013

-0.57 LTE UTE 014

+0.20 LTE UTE 011

-0.50 LTE UTE 014

+0.17 LTE UTE 010

-0.48 LTE UTE O1l

-0.51 LTE UTE 014

-0.61 LTE UTE 014

+0.15 LTE UTE 011

-0.53 LTE UTE 010

-0.44 LTE UTE 011

-0.58 LTE UTE 010

-0.51 LTE UTE 009

+0.05 UTE LTE 007

-0.66 UTE LTE 007

-0.69 UTE LTE 007

+0.07 UTE LTE 007

+0.15 UTE LTE 007

+0.15 UTE LTE 007

+0.13 UTE LTE 007

-0.66 UTE LTE 010

+0.15 UTE LTE 014

+0.03 UTE LTE 014

-0.66 UTE LTE 013

+0.18 UTE LTE 010

+0.53 UTE LTE 009

+0.53 UTE LTE 010

+0.53 UTE LTE 009

+0.53 UTE LTE 011

+0.20 UTE LTE 010

-0.46 UTE LTE 011

+0.25 UTE LTE 011

-0.34 LTE UTE 012

+0.37 LTE UTE 011

-0.37 LTE UTE 010

-0.39 LTE UTE 010

-0.40 LTE UTE 013

-0.53 LTE UTE 014

-0.48 LTE UTE 011

-0.45 LTE UTE 011

-0.44 LTE UTE 013

-0.55 LTE UTE 010

-0.42 LTE UTE 011

-0.47 LTE UTE 013

-0.55 LTE UTE 014

-0.53 LTE UTE 014

+0.19 LTE UTE 013

+0.21 LTE UTE 011

-0.47 LTE UTE 014

-0.55 LTE UTE 011

-0.49 LTE UTE 011

-0.51 LTE UTE 014

-0.58 LTE UTE 014

+0.15 LTE UTE 011

-0.53 LTE UTE 008

+0.17 LTE UTE 010

-0.46 LTE UTE 011

-0.56 LTE UTE 011

-0.56 LTE UTE 014

+0.12 LTE UTE 011

-0.56 LTE UTE 014

+0.07 LTE UTE 010

-0.49 LTE UTE 014

-0.68 LTE UTE 007

+0.15 UTE LTE 007

+0.16 UTE LTE 007

+0.05 UTE LTE 007

+0.10 UTE LTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

12 5

12 0

12 10 7

10 12 12 12 6

12 10 10 0

10 12 12 12 10 10 98 98 98 98 96 96 98 4

98 22 22 22 4

505 3

6 6

2 2

18 0

18 18 18 18 18 18 18 18 18 18 12 12 12 12 10 10 10 5

10 12 12 10 10 10 10 10 0

10 12 0

12 10" 98 98 98 0

96 98 98 98 96 96 98 2

98 96 0

96 6

9 507 5

505 5

505 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 51OUL 51OUL

AREVA NP Inc Customet Name: ONSI Repl 4/22/2008 9:48:05 Am Component: S/G B Page 48 of 74 ONSlBR-EOC24 Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 85 79 0.22 85 83 0.15 85 94 0.11 85 113 0.15 85 114 0.27 0.11 85 115 0.13 85 120 0.14 85 122 0.13 0.10 85 124 0.13 0.09 85 125 0.12 85 126 0.11 85 128 0.17 85 129 0.19 86 1

0.15 0.18 0.28 86 2

0.26 86 3

0.16 86 6

0.11 86 7

0.08 86 8

0.09 0.19 86 9

0.61 0.20 0.17 86 10 0.34 86 11 0.20 86 12 0.25 0.11 0.15 86 13 0.76 0.09 0.12 86 14 0.12 86 15 0.17 86 16 0.08 0.22 86 18 0.11 0.15 86 19 0.09 86 52 0.12 86 53 0.10 86 78 0.08 86 83 0.13 86 87 0.15 86 115 0.21 0.38 86 116 0.30 0.19 0.67 86 117 0.11 86 121 0.20 0.09 86 123 0.13 0.15 0.08 86 124 0.19 86 125 0.12 86 126 0.16 86 128 0.27 0.09 86 129 0.22 0.13 87 1

0.10 0.19 87 2

0.18 87 3

0.14 87 4

0.13 87 5

0.18 87 8

0.16 87 9

0.46 0.16 87 10 0.52 0*17 87 Ii 0.68 87 12 0.78 0.08 DEG CHN IND %TW 124 P2 TWD 15 121 P2 TWD 12 125 P2 TWD 9

138 P2 TWD 11 138 P2 TWD 19 128 P2 TWD 10 139 P2 TWD 11 154 P2 TWD 12 149 P2 TWD 11 128 P2 TWD 9 150 P2 TWD 10 156 P2 TWD 7 139 P2 TWD 10 125 P2 TWD 9

141 P2 TWD 13 139 P2 TWD 15 139 P2 TWD 9

140 P2 TWD 10 141 P2 TWD 15 137 P2 TWD 14 145 P2 TWD 9

146 P2 TWD 6

153 P2 TWD 5

145 P2 TWD 6 145 P2 TWD 11 131 P2 TWD 26 138 P2 TWD 11 142 P2 TWD 10 141 P2 TWD 17 143 P2 TWD 11 143 P2 TWD 14 132 P2 TWD 6 147 P2 TWD 9 130 P2 TWD 29 145 P2 TWD 6

131 P2 TWD 7

147 P2 TWD 7 142 P2 TWD 10 144 P2 TWD 5 145 P2 TWD 11 143 P2 TWD 6 130 P2 TWD 8 117 P2 TWD 6 144 P2 TWD 9 128 P2 TWD 8 135 P2 TWD 7 138 P2 TWD 10 116 P2 TWD 11 138 P2 TWD 16 140 P2 TWD 24 138 P2 TWD 21 141 P2 TWD 15 129 P2 TWD 34 145 P2 TWD 9 138 P2 TWD 14 155 P2 TWD 8 138 P2 TWD 10 138 P2 TWD 12 153 P2 TWD 7 140 P2 TWD 15 144 P2 TWD 9 137 P2 TWD 13 135 P2 TWD 19 128 P2 TWD 8 145 P2 TWD 16 123 P2 TWD 10 127 P2 TWD 6 145 P2 TWD 11 142 P2 TWD 10 151 P2 TWD 8 116 P2 TWD 8 146 P2 TWD 10 139 P2 TWD 9 138 P2 TWD 22 142 P2 TWD 10 134 P2 TWD 23 137 P2 TWD 9 138 P2 TWD 28 127 P2 TWD 30 123 P2 TWD 5 LOCATION 007

+0.15 007

+0.10 007

+0.13 014

-0.67 014

-0.71 010

+0.13 010

+0.15 009

+0.51 010

-0.53 011

+0.20 013

+0.31 011

+0.20 010

-0.48 010

-0.48 011

+0.28 011

+0.28 002

-0.05 002

+0.38 011

-0.32 011

-0.35 011

-0.36 010

-0.36 010

-0.40 009

-0.46 011

-0.42 011

-0.45 014

+0.24 013

-0.55 011

-0.47 011

-0.49 011

-0.49 013

-0.57 014

+0.20 011

-0.49 013

+0.14 014

-0.59 011

-0.48 011

-0.53 010

-0.46 011

-0.53 007

-0.51 013

-0.66 007

-0.51 007

+0.16 007

+0.13 007

+0.15 007

+0.13 007

+0.15 014

+0.05 010

+0.15 014

+0.03 014

-0.69 010

+0.15 010

+0.18 010

+0.56 009

+0.51 012

-0.54 010

+0.56 009

-0.53 009

-0.53 009

-0.48 010

-0.43 013

-0.46 010

-0.40 011

+0.28 010

-0.38 002

+0.39 011

-0.32 011

-0.36 011

-0.39 009

-0.40 014

-0.42 011

-0.45 011

-0.44 013

-0.55 011

-0.47 013

-0.55 011

-0.49 011

-0.50 014

+0.17 EXT EXT UTE LTE UTE LTE UTE LTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE tTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1 UTIL 2

WAR WAR WAR WAR 7

WAR WAR WAR 6

WAR WAR WAR 7

WAR WAR 6

WAR 5

WAR 9

WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR 7

WAR WAR WAR WAR WAR 5

WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR S

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 10 WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 7

WAR WAR WAR CAL #

6 2

10 517 18 18 18 18 18 18 20 20 18 20 20 18 12 12 12 12 10 12 10 12 12 10 10 10 12 10 12 12 12 10 10 10 98 96 98 98 98 98 96 527 22 6

2 10 20 20 18 18 18 20 20 20 20 20 20 18 20 18 18 18 20 20 12 12 10 12 10 12 10 12 12 10 10 12 10 10 LEG OUTLET OUTLET OUTLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 51OXB 510XB 510XB 51OUL 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:06 AM Component: S/G B Page 49 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMlE2]

ROW TUBE VOLTS 87 13 0.09 0.31 0.18 87 14 1.20 0.11 87 16 0.20 87 17 0.32 0.25 87 28 0.12 87 69 0.11 87 77 0.09 87 79 0.19 87 80 0.10 87 83 0.08 87 91 0.11 87 94 0.09 87 106 0.14 87 112 0.24 87 116 0.10 87 120 0.15 0.08 87 121 0.20 0.20 0.12 87 122 0.09 0.16 0.11 0.09 0.10 0.13 87 123 0.18 87 124 0.16 0.10 0.10 87 126 0.10 87 127 0.54 0.21 87 128 0.11 87 130 0.16 88 1

0.09 0.09 88 4

0.12 88 6

0.34 88 7

0.16 0.09 0.19 0.19 88 8

0.10 88 9

0.45 88 10 0.37 88 11 0.45 88 13 0.08 88 14 0.09 88 15 0.08 0.07 0.44 0.15 0.13 88 21 0.05 88 51 0.07 88 53 0.05 88 73 0.09 88 74 0.10 88 80 0.14 88 83 0.12 88 103 0.08 88 113 0.13 88 115 0.19 88 117 0.10 88 120 0.16 88 122 0.12 88 124 0.18 88 125 0.11 88 126 0.11 88 127 0.11 88 128 0.16 0.31 88 129 0.16 89 1

0.11 0.23 DEG CHN 134 P2 145 P2 146 P2 127 P2 133 P2 135 P2 138 P2 144 P2 149 P2 125 P2 130 P2 136 P2 141 P2 147 P2 138 P2 83 P2 132 P2 132 P2 144 P2 143 P2 146 P2 148 P2 137 P2 147 P2 153 P2 150 P2 144 P2 150 P2 144 P2 141 P2 136 P2 151 P2 145 P2 149 P2 107 P2 132 P2 133 P2 146 P2 134 P2 126 P2 148 P2 125 P2 132 P2 145 P2 143 P2 138 P2 142 P2 157 P2 134 P2 143 P2 137 P2 137 P2 133 P2 128 P2 148 P2 138 P2 136 P2 137 P2 159 P2 128 P2 108 P2 112 P2 131 P2 105 P2 124 P2 136 P2 138 P2 140 P2 146 P2 148 P2 140 P2 138 P2 116 P2 144 P2 149 P2 144 P2 135 P2 142 P2 141 P2 149 P2 IND %TW TWD 5 TWD 15 TWD 9 TWD 38 TWD 7 TWD 11 TWD 16 TWD 13 TWD 10 TWD 8 TWD 7 TWD 14 TWO 9 TWO 7 TWD 9 TWD 7 TWD 10 TWD 18 TWD 8 TWD 12 TWD 6 TWD 16 TWD 16 TWD 10 TWD 8 TWD 12 TWO 9 TWD 8 TWD 8 TWD 10 TWD 15 TWD 12 TWD 8 TWO 8 TWD 8 TWD 30 TWD 16 TWD 9 TWD 12 TWD 6 TWD 5 TWD 7 TWO 17 TWD 9 TWD 6 TWD 11 TWD 11 TWD 6 TWD 21 TWD 18 TWD 21 TWD 5 TWD 5 TWD 5 TWD 5 TWD 21 TWD 9 TWD 8 TWD 4 TWD 6 TWD 5 TWD 8 TWD 8 TWD 11 TWD 9 TWD 7 TWD 11 TWD 15 TWD 9 TWD 12 TWD 10 TWD 13 TWD 10 TWO 9 TWO 10 TWD 12 TWD 21 TWD 13 TWD 7 TWD 12 LOCATION 010

-0.44 011

-0.51 014

+0.17 011

-0.54 013

-0.61 014

-0.63 014

-0.66 014

+0.05 009

-0.64 007

-0.73 007

+0.15 007

+0.15 007

+0.10 007

+0.13 007

+0.13 007

+0.13 014

-0.08 010

+0.13 010

+0.20 010

+0.54 009

+0.56 014

-0.61 011

+0.18 011

-0.48 014.

+0.15 014

-0.59 013

-0.54 012

+0.18 009

-0.56 008

-0.50 010

+0.56 014

-0.54 011

+0.23 009

-0.51 010

-0.43 011

+0.23 010

-0.40 010

-0.41 010

-0.36 009

-0.42 011

-0.37 010

-0.34 010

-0.39 011

-0.41 011

+0.27 013

-0.49 014

+0.27 011

-0.44 011

-0.46 011

-0.47 011

-0.48 008

+0.19 014

-0.61 007

-0.51 010

-0.41 011

-0.53 014

-0.61 013

-0.59 015

-0.02 007

+0.10 007

+0.10 007

+0.08 007

+0.13 007

+0.13 007

+0.13 007

+0.13 014

-0.71 010.

+0.15 011

+0.13 010

+0.54 010

-0.43 010

+0.59 009

-0.48 011

+0.26 009

+0.51 011

+0.28 010

-0.38 011

+0.28 015

-0.41 015

+0.61 EXT EXT UTIL LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTELTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR 1

UTIL 2

CAL # LEG 98 INLET 98 INLET 98 INLET 96 INLET 4

96 INLET 96 INLET 98 INLET 98 INLET 22 OUTLET 7

503 OUTLET 6

OUTLET 6

OUTLET 4

505 OUTLET 2

OUTLET 10 OUTLET 10 OUTLET 10 OUTLET 18 OUTLET 5

20 OUTLET 20 OUTLET 20 OUTLET 18 OUTLET 18 OUTLET 18 OUTLET 20 OUTLET 20 OUTLET 20 OUTLET 20 OUTLET 20 OUTLET 20 OUTLET 18 OUTLET 20 OUTLET 20 OUTLET 9

20 OUTLET 20 OUTLET 18 OUTLET 18 OUTLET 20 OUTLET 20 OUTLET 12 INLET 12 INLET 12 INLET 12 INLET 10 INLET 10 INLET 10 INLET 10 INLET 12 INLET 10 INLET 12 INLET 10 INLET 10 INLET 98 INLET 96 INLET 96 INLET 96 INLET 96 INLET 5

96 INLET 96 INLET 22 OUTLET 22 OUTLET 4

501 OUTLET 6

OUTLET 6

OUTLET 4

503 OUTLET 10 OUTLET 18 OUTLET 6

18 OUTLET 7

18 OUTLET 9

20 OUTLET 6

20 OUTLET 9

20 OUTLET 18 OUTLET 7

20 OUTLET 18 OUTLET 20 OUTLET 20 OUTLET 18 OUTLET 12 INLET 12 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51 OXB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

  • 510XB 51OUL 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:06 AM Component: S/G B Page 50 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 89 2

0.22 89 5

0.12 89 7

0.13 0.16 89 8

0.15 89 9

0.51 0.18 0.24 89 10 0.21 89 12 0.22 89 13 0.81 0.16 0.47 0.13 89 15 0.10 0.75 0.21 89 16 0.12 89 18 0.13 0.25 89 80 0.13 89 112 0.09 89 115 0.17 89 116 0.13 89 121 0.14 89 122 0.16 89 123 0.16 0.16 89 124 0.09 89 125 0.30 0.27 0.21 0.14 89 126 0.10 0.11 89 127 0.57 0.97 89 128 0.08 0.23 90 2

0.14 90 3

0.16 90 4

0.11 90 6

0.09 90 7

0.63 0.21 0.26 0.15 90 9

0.55 0.11 90 10 1.10 0.10 90 11 0.44 0.13 90 13 0.48 0.22 0.08 90 15 0.11 0.11 90 16 0.14 90 18 0.08 90 52 0.06 90 69 0.10 90 70 0.10 90 81 0.08 90 86 0.09 90 90 0.10 90 115 0.19 0.12 0.08 90 117 0.12 90 119 0.10 90 120 0.10 90 123 0.09 90 125 0.22 0.15 90 126 0.75 0.09 0.06 90 127 0.23 1.12 DEG CHN IND %TW LOCATION EXT EXT UTIL 1

136 P2 139 P2 151 P2 134 P2 148 P2 138 P2 139 P2 142 P2 143 P2 142 P2 134 P2 145 P2 137 P2 138 P2 143 P2 133 P2 139 P2 142 P2 147 P2 142 P2 132 P2 138 P2 142 P2 142 P2 150 P2 142 P2 133 P2 139 P2 136 P2 138 P2 141 P2 139 P2 147 P2 149 P2 127 P2 128 P2 124 P2 142 P2 142 P2 144 P2 140 P2 124 P2 146 P2 133 P2 145 P2 142 P2 147 P2 139 P2 152 P2 124 P2 143 P2 137 P2 133 P2 138 P2 145 P2 147 P2 145 P2 150 P2 139 P2 151 P2 140 P2 134 P2 133 P2 124 P2 146 P2 144 P2 140 P2 148 P2 140 P2 142 P2 137 P2 143 P2 84 P2 141 P2 142 P2 130 P2 133 P2 145 P2 131 P2 125 P2 TWD 12 TWD 7 TWD 8 TWD 9 TWD 8 TWD 23 TWD 10 TWD 13 TWD 12 TWO 12 TWD 30 TWD 9 TWD 21 TWD 7 TWD 6 TWD 29 TWD 11 TWD 7 TWD 8 TWD 14 TWD 10 TWD 7 TWD 14 TWD 11 TWD 12 TWD 12 TWD 13 TWD 13 TWD 7 TWD 21 TWD 20 TWD 16 TWD 12 TWO 8 TWD 9 TWD 32 TWD 41 TWD 7 TWD 16 TWD 8 TWD 9 TWD 7 TWD 5 TWD 26 TWD 12 TWD 14 TWD 9 TWD 25 TWD 7 TWD 36 TWD 6 TWD 21 TWD 8 TWD 21 TWD 11 TWD 5 TWD 6 TWD 6 TWD 8 TWD 5 TWD 5 TWD 8 TWD 8 TWD 7 TWD 7 TWD 8 TWD 15 TWD 10 TWD 7 TWD 10 TWD 9 TWD 8 TWD 8 TWD 17 TWD 13 TWD 36 TWD 8 TWD 5 TWD 17 TWD 43 011 014 011 013 011 011 013 014 011 011 011 013 014 014 007 Ol 014 014 011 009 007 010 010 014 011 011 010 009 010 013 013 011 009 Ol 010 013 011 012 010 011 011 010 011 011 013 014 014 011 013 011 013 011 013 014 014 011 014 011 014 007 007 007 007 007 007 008 014 010 014 011 011 011 010 009 013 011 011 010 010 011

-0.34

+0.28

-0.42

-0.50

-0.43

-0.44

-0.55

-0.50

-0.45

-0,48

-0.48

-0.61

-0.58

+0.17

-0.51

-0.53

+0.17

-0.61

-0.58

-0.15

+0.15

+0.17

+0.15

+0.08

+0.18

+0.18

+0.56

-0.51

-0.43

+0.25

-0.48

+0.23

+0.53

+0.23

-0.38

+0.28

+0.25

-0.43

-0.38

-0.37

-0.38

-0.34

-0.42

-0.41

-0.46

-0.46

+0.25

-0.47

-0.55

-0.46

+0.17

-0.49

-0.57

-0.58

+0.15

-0.51

+0.07

-0.53

+0.12

-0.53

+0.10

+0.15

+0.15

+0.13

+0.10

-0.61

-0.66

+0.18

+0.03

+0.15

+0.13

+0.18

+0.56

+0.53

+0.25

+0.28

-0.46

+0.59

-0.38

+0.28 LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL.

2 CAL #

10 0

12 12 12 10 12 12 12 10 10 98 98 98 5

98 98 98 98 5

96 4

96 11 96 6

7 517 18 20 18 20 18 18 8

20 18 18 18 18 5

20 6

20 18 LAR 18 20 20 12 10 12 12 10 10 10 10 12 12 10 5

10 12 12 98 98 0

98 98 4

98 96 96 22 6

6 6

10 3

513 18 18 3

18 6

24 5

18 4

20 18 18 7

18 20 20 20 18 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXB UTE LTE WAR LAR 18 OUTLET 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:48:07 AM Component: S/G B Page 51 of 74 ONSlBR-EOC24 -

Tube QUERY: QueryMl[2]

Support Wear ROW TUBE VOLTS 91 6

0.31 0.28 0.20 91 7

0.11 91 8

0.36 91 9

0.16 91 10 0.66 91 11 0.28 0.14 91 12 0.11 0.11 91 13 0.41 91 14 0.19 0.11 0.04 0.06 0.13 91 16 0.14 0.12 91 18 0.19 0.11 91 19 0.11 0.14 91 22 0.12 91 52 0.09 91 75 0.10 91 114 0.09 91 116 0.19 91 122 0.18 91 123 0.17 0.24 0.20 91 126 0.18 0.28 0.10 0.13 91 127 0.14 0.21 91 128 0.11-91 129 0.27 0.11 92 3

0.32 92 4

0.14 92 5

0.14 92 6

0.85 0.13 92 7

0.42 0.15 92 8

0.14 92 9

0.66 92 10 0.21 92 11 0.13 0.12 0.11 92 12 0.36 92 13 0.13 0.09 92 14 0.18 92 15 0.17 92 16 0.20 0.28 0.35 92 19 0.08 92 25 0.16 92 77 0.10 0.08 92 106 0.09 92 114 0.19 92 117 0.08 92 123 0.10 92 126 0.21 92 127 0.17 0.11 92 128 0.29 0.13 92 129 0.10 93 4

0.15 93 5

0.17 0.10 93 7

0.33 DEG 128 141 139 152 137 147 131 134 133 137 149 139 141 146 108 140 129 130 148 144 149 148 135 150 127 1.43 137 134 144 138 140 141 136 141 121 144 145 133 125 136 94 142 125 140 128 143 141 140 144 139 143 154 145 129 139 141 141 141 145 140 139 142 151 139 142 105 153 138 145 149 142 129 142 141 128 140 127 132 146 142 CHN P22 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 16 TWD 14 TWD 11 TWD 6 TWD 18 TWD 9 TWD 27 TWD 15 TWD 8 TWD 6 TWD 6 TWD 19 TWD 11 TWD 7 TWD 3 TWD 4 TWD 8 TWD 9 TWD 7 TWD 11 TWD 7 TWD 7 TWD 8 TWD 7 TWD 7 TWD 8 TWD 8 TWD 14 TWD 14 TWD 14 TWD 18 TWD 16 TWD 13 TWD 19 TWD 8 TWD 10 TWD 11 TWD 16 TWD 9 TWD 20 TWD 10 TWD 16 TWD 8 TWD 8 TWD 31 TWD 7 TWD 20 TWD 9 TWD 8 TWD 28 TWD 11 TWD 8 TWD 7 TWD 7 TWD 18 TWD 8 TWD 6 TWD 10 TWD 10 TWO 10 TWD 14 TWD 17 TWD 5 TWD 12 TWD 8 TWD 6 TWD 7 TWD 14 TWO 7 TWD 9 TWD 16 TWD 14 TWD 10 TWD 20 TWD 10 TWD 8 TWD 9 TWD 10 TWD 6 TWD 17 LOCATION 010

-0.38 011

-0.41 014

+0.27 014

+0.28 011

-0.43 011

-0.44 011

-0.45 014

-0.52 013

-0.55 007

-0.43 011

-0.50 011

-0.51 010

-0.44 014

+0.15 007

-0.44 011

+0.20 014

-0.58 014

-0.61 014

+0.12 014

-0.66 014

+0.07 010

-0.49 014

-0.68 014

+0.00 007

+0.10 007

-0.61 010

+0.18 014

-0.64 011

+0.20 014

+0.18 014

-0.53 011

+0.20 013

-0.46 011

+0.26 012

-0.49 011

-0.46 011

+0.25 010

-0.36 010

-0.38 011

+0.30 010

-0.38 011

-0.39 010

-0.31 010

-0.34 011

-0.38 014

+0.27 011

-0.42 013

-0.50 011

-0.43 011

-0.44 011

-0.46 014

+0.20 015

-0.58 007

-0.43 011

-0.48 011

-0.51 014

+0.17 011

-0.53 014

+0.12 009

-0.48 014

-0.63 014

+0.10 015

-0.66 009

-0.64 007

-0.56 008

-0.61 014

+0.02 010

+0.20 014

-0.63 010

-0.43 011

+0.28 010

-0.39 011

+0.25 011

+0.31 010

-0.43 011

+0.33 010

-0.33 010

-0.37 011

-0.39 011

-0.42 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE STE STE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE STE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

10 10 10 4

12 10 12 10 12 6

12 0

10 0

10 98 96 96 96 96 0

96 96 96 96 96 96 3

96 96 22 5

505 0

18 20 20 18 18 18 20 20 3

20 10 20 18 18 20 18 18 12 10 12 10 10 12 12 10 12 10 12 12 4

12 10 4

96 3

96 98 96 98 98 98 96 22 5

505 4

505 4

513 20 18 18 20 18 4

18 20 20 4

20 10 12 12 12 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 5i0XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510UL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB

AREVA NP Inc Customer Name:

ONSX Repl 4/22/2008 9:48:07 AM Component:

S/G B Page 52 of 74 ONSIBR-EOC24 Tube QUERY: QueryMl[2]

Support Wear ROW TUBE VOLTS 0.10 93 8

0.40 93 9

0.29 93 10 0.15 93 11 0.14 93 12 0.11 93 15 0.18 0.12 93 72 0.08 93 78 0.07 93 82 0.09 93 84 0.09 93 112 0.18 0.10 93 116 0.09 93 122 0.11 93 126 0.42 0.22 93 127 0.18 0.19 0.32 93 128 0.08 94 2

0.13 94 4

0.19 94 5

0.17 94 7

0.54 0.24 0.10 94 8

0.14 0.99 0.18 0.61 0.16 94 12 0.20 0.21 94 14 0.08 94 16 0.08 0.08 94 17 0.10 94 19 0.07 94 65 0.05 94 113 0.13 94 115 0.11 0..11 94 125 0.09 94 126 0.16 94 128 0.14 94 129 0.06 95 1

0.23 0.11 95 2

0.16 95 3

0.11 95 5

0.49 95 6

0.12 95 7

0.18 95 9

0.12 0.14 95 10 0.13 95 12 0.15 95 16 0.16 0.15 0.14 95 18 0.11 95 19 0.12 0.12 0.08 95 28 0.16 0.08 95

72.

0.09 95 73 0.09 95 78 0.11 95 116 0.09 95 118 0.12 95 121 0.09 95 122 0.15 95 123 0.08 0.13 95 125 0.20 95 126 0.13 0.10 DEG CHN 149 P2 137 P2 142 P2 146 P2 146 P2 153 P2 142 P2 143 P2 133 P2 133 P2 144 P2 138 P2 136 P2 145 P2 151 P2 135 P2 138 P2 131 P2 141 P2 130 P2 139 P2 124 P2 131 P2 137 P2 136 P2 132 P2 145 P2 146 P2 131 P2 127 P2 131 P2 134 P2 144 P2 143 P2 137 P2 140 P2 152 P2 141 P2 142 P2 153 P2 97 P2 146 P2 149 P2 149 P2 129 P2 134 P2 133 P2 145 P2 140 P2 139 P2 140 P2 158 P2 132 P2 132 P2 143 P2 156 P2 134 P2 141 P2 1461 P2 145 P2 150 P2 139 P2 137 P2 145 P2 137 P2 136 P2 141 P2 139 P2 135 P2 120 P2 121 P2 147 P2 148 P2 153 P2 129 P2 152 P2 125 P2 135 P2 146 P2 130 P2 IND %TW TWD 6 TWD 19 TWD 15 TWD 9 TWD 8 TWD 6 TWD 11 TWD 7 TWD 6 TWD 6 TWD 7 TWD 7 TWD 14 TWD 9 TWD 7 TWD 9 TWD 25 TWD 16 TWD 14 TWD 15 TWD 22 TWD 7 TWD 8 TWD 10 TWD 10 TWD 24 TWD 13 TWD 6

TWD 8 TWD 34 TWD 10 TWD 26 TWD 9 TWD 11 TWD 12 TWD 4 TWD 5 TWD 5 TWD 6

TWD 4

TWD 4

TWD 11 TWD 10 TWD 10 TWD 8 TWD 12 TWD 11 TWD 5 TWD 13 TWD 6 TWD 9 TWD 6 TWD 23 TWO 7 TWO 10 TWD 7 TWD 8 TWD 8 TWD 8 TWD 9 TWD 8 TWD 7 TWD 6 TWD 7 TWD 7 TWD 5 TWD 13 TWD 7 TWD 8 TWD 8 TWD 8 TWD 7 TWO 10 TWD 8 TWD 12 TWD 7 TWD 11 TWD 16 TWD 10 TWD 8 LOCATION 009

-0.46 011

-0.43 011

-0.47 011

-0.45 011

-0.45 011

-0.51 014

-0.61 014

+0.12 007

-0.57 007

+0.19 007

-0.56 007

-0.58 014

-0.66 014

+0.03 014

-0.64 011

+0.20 011

+0.28 010

-0.38 011

+0.30 010

-0.37 009

+0.57 010

-0.38 011

-0.36 011

-0.38 010

-0.37 010

-0.36 014

+0.28 011

-0.42 010

-0.38 011

-0.43 013

+0.27 014

-0.46 014

+0.25 014

-0.53 014

+0.20 014

+0.15 009

-0.51 010

-0.44 014

+0.10 010

-0.46 007

+0.13 010

+0.18 014

-0.66 014

+0.03 010

-0.38 010

-0.38 010

-0.38 009

+0.56 015

+0.58 013

+0.32 011

-0.34 011

-0.37 010

-0.32 010

-0.33 014

+0.28 011

-0.44 013

-0.52 013

-0.55 014

-0.56 011

-0.56 014

-0.61 014

+0.12 014

-0.66 014

-0.68 011

-0.61 0*14

+0.02 009

-0.66 009

+0.10 007

+0.21 007

+0.18 007

-0.61 014

+0.15 010

+0.54 013

+0.20 010

+0.56 009

+0.52 010

-0.40 010

-0.38 011

+0.28 010

-0.41 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTIL 1

UTIL 2

WAR 0

WAR WAR WAR 0

WAR 0

WAR 2

WAR WAR WAR 0

WAR 4

WAR 3

WAR 5

WAR WAR 6

WAR WAR S

WAR WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR WAR 5

WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR 6

WAR 6

WAR WAR 13 WAR WAR WAR 0

WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR 4

WAR WAR WAR 0

WAR WAR WAR 3

WAR 4

WAR WAR 3

WAR WAR WAR 5

WAR 0

WAR 9

WAR 6

WAR WAR WAR 6

WAR WAR WAR CAL #

12 10 12 10 10 98 96 96 505 505 505 505 18 18 20 20 20 20 18 18 18 20 10 10 12 12 12 12 10 10 10 10 10 10 10 98 98 98 96 96 22 18 18 18 18 20 20 20 12 12 10 12 12 10 12 12 12 10 98 98 98 98 98 96 96 96 22 22 112 112 505 20 20 18 20 18 18 18 20 20 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET PROBE S1OXB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 51OUL 51OUL 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:07 AM Component:

S/G B Page 53 of 74 ONSlBR-EOC24

- Tube QUERY: QueryMl[2]

Support Wear ROW TUBE VOLTS 95 127 0.10 96 3

0.20 96 5

0.11 96 6

0.13 96 8

0.22 96 9

0.18 0.15 0.10 96 11 0.12 96 13 0.17 96 15 0.09 96 16 0.11 96 17 0.07 0.12 96 25 0.12 96

26. 0.06 96 28 0.09 96 50 0.08 96 62 0.06 96 71 0.10 96 72 0.10 96 77 0.11 96 81 0.09 96 111 0.08 96 112 0.08 96 113 0.13 96 114 0.10 96 115 0.06 0.08 96 122 0.15 0.19 0.12 96 123 0.12 96 124 0.12 0.10 0.10 96 125 0.43 97 1

0.14 97 2

0.17 97 3

0.21 97 4

0.14 97 5

0.22 97 6

0.11 0.10 0.11 97 7

0.56 0.18 97 9

0.29 0.15 97 13 0.07 97 15 0.19 0.26 97 16 0.11 0.16 0.22 97 21 0.05 97 49 0.07 97 57 0.05 97 68 0.07 97 71 0.08 97 73 0.09 97 82 0.08 97 108 0.11 97 118 0.21 97 120 0.18 0.09 97 123 0.14 0.22 97 124 0.17 97 126 0.09 98 1

0.15 0.12 98 2

0.18 98 4

0.12 98 6

0.14 0.11 98 7

1.15 0.21 0.25 0.26 DEG 110 146 150 141 139 148 146 144 149 133 151 150 122 152 148 132 112 130 134 101 140 136 131 147 157 132 142 161 139 146 144 132 144 140 112 143 139 150 141 146 124 145 144 103 142 133 142 141 147 144 134 137 149 142 149 152 il1 137 134 129 138 122 133 102 95 143 134 142 124 141 138 151 143 146 142 150 122 144 139 139 CHN IND %TW P2 TWD 9 P2 TWD 11 P2 TWD 7 P2 TWD 7 P2 TWD 12 P2 TWD 10 P2 TWD 9 P2 TWD 6 P2 TWD 7 P2 TWD 10 P2 TWD 5 P2 TWD 6 P2 TWD 5 P2 TWD 7 P2 TWD 10 P2 TWD 5 P2 TWD 8 P2 TWD 6 P2 TWD 5 P2 TWD 9 P2 TWD 9 P2 TWD 9 P2 TWD 7 P2 TWD 7 P2 TWD 7 P2 TWD 11 P2 TWD 8.-

P2 TWD 6 P2 TWD 7 P2 TWD 11 P2 TWD 14 P2 TWD 10 P2 TWD 10 P2 TWD 10 P2 TWO 8 P2 TWD 8 P2 TWD 27 P2 TWD 8 P2 TWD 10 P2 TWD 12 P2 TWD 8 P2 TWD 12 P2 TWD 6 P2 TWD 6 P2 TWD 6 P2 TWD 25 P2 TWD 10 P2 TWD 15 P2 TWD 9 P2 TWD 4 P2 TWD 10 P2 TWD 13 P2 TWD 7 P2 TWO 9 P2 TWD 12 P2 TWD 3 P2 TWD 6 P2 TWD 4 P2 TWD 6 P2 TWD 7 P2 TWD 7 P2 TWD 7 P2 TWD 9 P2 "TWD 16 P2 TWD 14 P2 TWD 7 P2, TWD 12 P2 TWD 17 P2 TWD 13 P2 TWD 8 P2 TWD 9 P2 TWD 7 P2 TWD 10 P2 TWD 7 P2 TWD 8 P2 TWD 6 P2 TWD 36 P2 TWD 11 P2 TWD 13 P2 TWD 14 LOCATION 010

-0.38 011

-0.37 011

-0.42 011

-0.41 010

-0.39 014

-0.48 014

+0.22 011

-0.46 014

-0.53 014

-0.56 009

-0.54 014

+0.10 014

-0.63 014

+0.10 009

-0.64 014

-0.08 009

-0.67 007

+0.10 007

+0.10 007

+0.18 007

+0.18 008

-0.62 008

-0.66 013

+0.03 009

-0.59 014

+0.03 014

+0.10 013

-0.59 013

+0.15 014

-0.51 011

+0.26 009

+0.61 009

+0.45 009

+0.54 010

-0.41 013

-0.44 011

+0.33 011

-0.37 011

-0.36 011

-0.37 010

-0.29 011

-0.39 014

+0.25 010

-0.31 011

+0.29 010

-0.36 014

-0.45 011

-0.44 014

+0.23 014

+0.17 013

-0.61 014

-0.61 009

-0.54 014

-0.63 014

+0.10 015

+0.00

.007

+0.08 007

+0.15 007

+0.25 007

+0.18 007

+0.21 008

-0.62 014

-0.65 010

+0.54 010

+0.67 011

+0.28 010

-0.33 011

+0.31 011

+0.31 011

+0.42 011

-0.35 013

+0.32 011

-0.35 011

-0.37 010

-0.32 014

+0.28 010

-0.33 013

-0.51 013

+0.27 014

-0.43 EXT EXT UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

18 12 0

12 10 0

12 10 4

10 0

10 96 96 98 96 0

96 22 22 3

533 22 22 112 112 S503 0

507 7

18 20 6

18 3

20 18 0

18 20 8

20 11 20 18 20 8

20 8

20 18 12 10 12 10 0

12 10 0

10 10 12 12 512 5

12 3

98 98 98 96 96 96 96 22 22 3

503 0

503 3

503 0

503 68 9

68 68 68 70 70 24 70 12 12 12 12 6

12 4

12 10 10 10 10 LEG OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET OUTLET OUTLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510OXB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:08 AM Component: S/G B Page 54 of 74 ONSlBR-EOC24 -

Tube QUERY: QueryMl[2]

Support Wear ROW TUBE VOLTS 0.23 0.10 0.11 0.11 98 8

0.16 98 9

0.60 0.26 98 12 0.20 98 14 0.17 98 58 0.11 98 72 0.08 98 79 0.07 98 81 0.08 98 116 0.20 98 118 0.10 0.16 98 120 0.08 0.40 98 122 0.09 98 126 0.27 99 2

0.12 99 3

0.16 0.13 99 4

0.20 99 6

0.27 0.12 99 7

0.21 0.18 0.15 0.10 0.18 99 8

0.46 99 12 0.16 99 18 0.15 99 19 0.12 99 39 0.06 99 57 0.06 99 59 0.06 99 64 0.07 99 66 0.10 99 72 0.08 99 78 0.07 99 80 0.09 99 112 0.12 0.09 99 118 0.15 99 120 0.06 99 121 0.17 0.09 0.13 99 122 0.13 0.16 99 124 0.08 100 6 0.22 100 7 0.39 100 8 0.38 0.17 100 9 0.40 0.20 100 12 0.12 0.21 100 16 0.14 100 18 0.19 100 23 0.17 0.17 100 57 0.09 100 62 0.07 100 65 0.09 100 68 0.07 100 71 0.07 100 78 0.09 100 80 0.11 100 84 0.07 100 114 0.13 100 117 0.11 100 121 0.08 0.07 100 123 0.10 100 124 0.09 101 4 0.13 DEG 140 140 144 130 148 132 141 140 135 140 133 126 132 115 154 113 138 135 145 140 132 147 133 135 140 146 147 147 151 149 148 134 150 141 148 81 125 125 100 115 138 127 120 134 140 137 147 100 120 142 128 137 148 125 134 136 144 136 149 139 146 143 136 147 139 122 77 126 110 127 100 132 143 137 151 135 146 149 141 127 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW TWD 12 TWD 6 TWD 6 TWD 6 TWD 9 TWD 25 TWD 14 TWD 12 TWD 10 TWD 9 TWD 7 TWD 6 TWD 7 TWD 15 TWD 8 TWD 13 TWD 7 TWD 26 TWD 8 TWD 19 TWD 7 TWD 9 TWD 8 TWD 11 TWD 14 TWD 7 TWD 12 TWD 10 TWD 9 TWD 6 TWD 10 TWD 21 TWD 10 TWD 9 TWD 7 TWD 5 TWD 5 TWD 5 TWD 6 TWD 8 TWD 6 TWD 6 TWD 8 TWD 10 TWD 8 TWD 12 TWD 5 TWD 13 TWD 8 TWD II TWD 11 TWD 12 TWD 7 TWD 12 TWD 19 TWD 19 TWD 10 TWD 19 TWD II TWD 7 TWD 12 TWD 8 TWD 11 TWD 10 TWD 10 TWD 8 TWD 6 TWD 7 TWD 5 TWD 6 TWD 8 TWD 9 TWD 6 TWD 11 TWD 9 TWD 7 TWO 7

TWD 8 TWD 8 TWD 7 LOCATION 014

+0.27 Ol

+0.31 012

-0.46 012

+0.29 011

-0.44 Ol

-0.43 014

-0.48 014

-0.56 014

-0.58 007

+0.16 007

+0.18 007

+0.09 008

-0.62 010

+0.59 013

-0.47 010

+0.62 009

-0.41 014

-0.47 011

+0.31 011

+0.42 011

-0.36 011

-0.37 012

+0.35 011

-0.36 010

-0.33 014

+0.30 011

-0.42 011

+0.32 013

-0.47 014

-0.45 012

+0.32 011

-0.43 014

+0.17 014

-0.63 014

+0.07 009

+0.03 007

+0.10 007

+0.10 007

+0.18 007

+0.15 007

+0.16 007

+0.21 007

+0.18 013

-0.60 013

+0.18 013

-0.45 011

+0.29 009

+0.62 010

-0.36 011

+0.31 010

-0.34 011

+0,31 011

+0.34 010

-0.31 010

-0.34 014

-0.46 013

-0.51 011

-0.44 014

-0.47 014

-0.56 014

+0.20 015

-0.61 014

-0.63 014

-0.73 014

+0.02 007

+0.10 007

+0.10 007

+0.10 007

+0.12 007

+0.18 007

+0.11 008

-0.62 007

+0.23 014

-0.52 013

-0.47 010

-0.31 009

+0.57 011

+0.34 011

+0.37 010

-0.31 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE STE UTE LTE UTE LTE STE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

10 0

10 6

10 4

10 12 10 10 96 96 5

531 4

503 0

503 5

503 68 68 8

68 68 68 68 68 10 12 0

12 10 10 6

10 12 12 12 5

12 4

12 10 96 6

96 96 22 22 22 22 22 4

503 0

503 112 70 70 70 70 68 68 68 70 70 70 10 12 10 5

10 12 12 96 96 6

96 96 96 96 22 22 22 0

501 0

503 0

503 4

112 112 68 70 70 70 70 68 10 LEG INSET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510US 51OUL 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XS

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:08 AM Component: S/G B Page 55 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 101 6 0.17 0.13 101 7 0.23 0.20 101 11 0.15 101 13 0.13 101 16 0.13 0.12 0.38 0.18 101 17 0.08 101 41 0.10 101 70 0.06 101 106 0.10 101 110 0.15 101 118 0.11 101 119 0.25 102 2 0.17 102 4 0.14 102 5 0.11 102 6 0.44 0.13 102 8 0.30 102 12 0.21 102 16 0.21 0.31 102 48 0.09 102 56 0.15 102 59 0.07 102 61 0.08 102 72 0.17 102 80 0.08 0.10 102 92 0.16 102 107 0.09 102 115 0.10 0.10 0.08 102 116 0.12 102 117 0.26 0.20 0.13 102 118 0.19 102 119 0.08 102 122 0.13 103 1 0.23 103 3 0.16 103 4 0.11 103 5 0.32 0.16 103 6 0.34 0.18 0.17 103 7 0.16 103 8 0.25 0.22 0.13 103 9 0.15 103 12 0.25 103 16 0.09 103 18 0.13 0.11 103 57 0.06 103 110 0.09 103 116 0.13 103 117 0.11 0.14 103 118 0.32 0.10 103 119 0.08 103 121 0.09 103 124 0.14 104 2 0.08 104 6 0.14 104 7 0.27 104 9 0.13 104 11 0.11 0.07 104 15 0.23 104 49 0.07 DEG CHN 129 P2 123 P2 139 P2 145 P2 145 P2 145 P2 144 P2 132 P2 138 P2 146 P2 152 P2 152 P2 133 P2 149 P2 144 P2 145 P2 129 P2 139 P2 144 P2 137 P2 133 P2 145 P2 141 P2 127 P2 137 P2 134 P2 134 P2 139 P2 144 P2 88 P2 130 P2 134 P2 137 P2 138 P2 105 P2 146 P2 143 P2 140 P2 147 P2 133 P2 140 P2 149 P2 133 P2 127 P2 141 P2 145 P2 145 P2 142 P2 139 P2 145 P2 131 P2 130 P2 134 P2 134 P2 133 P2 132 P2 140 P2 137 P2 145 P2 139 P2 134 P2 134 P2 113 P2 141 P2 142 P2 135 P2 140 P2 135 P2 139 P2 90 P2 135 P2 141 P2 134 P2 124 P2 128 P2 145 P2 147 P2 152 P2 138 P2 134 P2 IND %TW LOCATION EXT EXT UTIL 1

TWO 9 TWO 8 TWO 13 TWO 11 TWO 9 TWO 8 TWO 7 TWO 7 TWO 18 TWD 10 TWO 5 TWO 9 TWO 5 TWO 8 TWO 12 TWO 9 TWO 18 TWO 10 TWO 8 TWO 7 TWO 21 TWO 8 TWO 16 TWO 12 TWO 12 TWD 16 TWO 8 TWO 12 TWO 6 TWO 6 TWO 14 TWO 7 TWO 9 TWO 12 TWO 8 TWO 8 TWO 8 TWO 7 TWO 10 TWO 19 TWO 15 TWO 11 TWO 15 TWO 7 TWO 11 TWO 12 TWO 9 TWO 7 TWO 16 TWO 9 TWO 17 TWO 10 TWO 10 TWO 9 TWO 13 TWO 12 TWO 8 TWO 9 TWO 13 TWO 5 TWO 7 TWO 6 TWO 5 TWO 8 TWO 11 TWO 9 TWO 11 TWO 22, TWO 8 TWO 7 TWO 8 TWO 11 TWO 5 TWO 8 TWO 14 TWO 8 TWO 7*

TWD 5 TWO 13 TWO 6 011

-0.41 010

-0;31 010

-0.36 011

-0.42 014

-0.56 014

-0.58 009

-0.51 013

-0.63 014

-0.61 014

+0.10 015

+0.02 009

-0.62 007

+0.19 010

+0.18 010

+0.26 010

-0.34 010

-0.34 011

-0.32 010

-0.29 010

-0.33 010

-0.34 011

-0.42 011

-0.39 014

-0.56 014

-0.63 014

+0.10 009

-0.62 007

+0.13 007

+0.13 007

+0.13 008

-0.65 007

+0.18 008

-0.59 009

-0.66 013

-0.63 010

-0.36 011

+0.26 014

-0.53 011

+0.29 010

-0.36 011

+0.26 013

-0.47 010

-0.34 010

-0.34 011

+0.39 015

-0.38 011

-0.39 011

-0.43 010

-0.32 014

+0,30 010

-0.33 012

-0.41 014

+0.30 010

-0.34 011

-0.41 010

-0.35 014

+0.27 014

+0.27 014

-0.53 015

+0.07 013

-0.63 015

-0.63 007

+0.13 014

-0.55 010

-0.42 010

-0.36 011

+0.29 010

-0.34 011

+0.31 010

-0.36 015

+0.59 011

+0.42 011

-0.39 010

-- 0.31 010

-0.33 011'

-0.43 014

+0.22 014

-0.53 014

-0.63 007

+0.13 LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

10 0

10 12 12 0

96 96 98 98 98 5

98 96 0

537 3

501 68 68 68 70 12 12 0

10 12 12 12 96 96 96 0

537 22 22 22 112 112 4

112 10 5

70 70 70 70 68 70 70 70 68 70 68 12 12 10 12 12 10 10 10 12 10 7

10 5

10 10 98 3

98 98 98 22 68 2

68 70 70 68 68 70 70 70 12

  • 6 12 10 0

10 96 5

96 96 22 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET.

INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:09 AM Component:

S/G B Page 56 of 74 ONSIBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 104 108 0.07 104 109 0.06 104 115 0.10 104 116 0.13 104 117 0.30 104 118 0.26 104 122 0.07 104 123 0.08 0.25 105 4 0.27 105 6 0.11 0.14 105 7 0.15 0.32 0.10 0.18 105 9 0.16 105 12 0.13 105 14 0.12 105 27 0.09 105 69 0.08 105 70 0.10 105 103 0.14 105 105 0.10 105 106 0.17 105 112 0.06 0.12 105 113 0.17 105 114 0.15 105 115 0.25 105 116 0.43 105 117 0.10 0.13 106 5 0.16 0.10 106 7 0.30 106 8 0.18 106 11 0.25 0.21 106 13 0.10 0.13 0.15 106 16 0.11 0.16 106 22 0.14 0.13 0.08 0.18 106 36 0.03 106 61 0.07 106 64 0.07 106 105 0.10 0.13 106 106 0.13 106 107 0.08 0.17 106 109 0.15 106 110 0.,17 0.14.

106 112 0.18 106 113 0.12 0.11 106 114 0.14 106 115 0.18 0.07 106 116 0.12 0.30 107 6 0.15 107 7 0.15 0.12 107 8 0.18 107 13 0.10 107 44 0.05 107 45 0.08 107 46 0.07 107 56 0.09 107 97 0.14 107 103 0.10 107 111 0.12 107 112 0.10 DEG 145 154 144 129 135 130 141 146 136 135 137 141 143 134 158 151 139 147 130 154 132 143 138 146 141 153 149 142 135 131 129 132 148 119 137 141 143 139 148 141 146 142 133 148 144 133 123 143 145 126 136 139 147 147 153 149 137 82 118 90 138 143 130 132 148 57 133 142 127 149 147 140 138 116 119 126 130 136 136 144 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND %TW LOCATION TWD 6 010

+0.26 TWD 5 009

-0.49 TWD 8 011

+0.24 TWO 11 010

-0.34 TWO 21 010

-0.34 TWD 19 010

-0.31 TWD 6 011

+0.37 TWD 7 015

-0.37 TWD 18 015

+0.62 TWD 14 010

-0.31 TWO 6 010

-0.28 TWO 8 014

+0.32 TWO 9 010

-0.34 TWD 16 011

-0.42 TWD 6 014

-0.47 TWD 10 014

+0.28 TWD 9 011

-0.46 TWO 8 014

-0.56 TWO 7 014

-0.58 TWO 7 007

-0.61 TWD 7 007

+0.21 TWD 8 007

+0.21 TWD 11 009

-0.52 TWO 9 010

+0.21 TWD 13 010

+0.23 TWD 6 009

-0.49 TWD 10 010

+0.60 TWD 14 009

-0.49 TWO 12 010

-0.39 TWO 18 010

-0.36 TWD 26 010

-0.36 TWD 8 010

-0.34 TWD 10 011

+0.31 TWD 10 010

-0.31 TWO 6 013

-0.42 TWO 16 011

-0.42 TWO 10 011

-0.41 TWO 14 014

-0.53 TWO 12 014

+0.22 TWO 6 009

-0.56 TWO 8 013

-0.59 TWO 9 013

+0.19 TWO 6 014

-0.61 TWO 9 014

+0.10 TWD 9 014

-0.66 TWD 8 014

+0.05 TWD 5 015

-0.68 TWO 10 015

+0.02 TWO 3 015

-0.13 TWO 6 007

+0.15 TWD 6 007

+0.21 TWD 8 010

-0.42 TWD 11 010

+0.23 TWD 10 010

+0.26 TWD 7 011

+0.18 TWO 13 014

+0.18 TWO 12 014

-0.55 TWO 13,010

+0.60 TWO 12 009

+0.57 TWD 14 010

+0.65 TWD 10 010

-0.37 TWD 9

011

+0.24 TWO 11 010

-0.36 TWO 14 010

-0.34 TWD 7 011

+0.26 TWD 10 009

+0.65 TWD 21 010

-0.31 TWO 8 011

+0.32 TWO 9 010

-0.31 TWO 7 011

-0.44 TWD 10 011

-0.44 TWO 6 013

+0.19 TWD 4 007

+0.10 TWD 6 007

+0.10 TWO 6 007

+0.13 TWO 7 007

+0.10 TWO 11 009

-0.57 TWD 9 010

+0.26 TWD 10 009

-0.47 TWO 8 009

-0.44 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE GTE LTE LTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE GTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE LTE GTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG 68 INLET 70 INLET 70 INLET 68 INLET 70 INLET 68 INLET 68 INLET 70 INLET 70 INLET 10 INLET 10 INLET 10 INLET 12 INLET 12 INLET 12 INLET 12 INLET 98 INLET 6

96 INLET 96 INLET 22 OUTLET 0

501 INLET 4

503 INLET 68 INLET 68 INLET 70 INLET 70 INLET 70 INLET 68 INLET 2

70 INLET 68 INLET 70 INLET 68 INLET 68 INLET 12 INLET 12 INLET 12 INLET 10 INLET 96 INLET 96 INLET

96.

INLET 96 INLET 96, INLET.

98 INLET 98 INLET 96 INLET 2

96 INLET 0

96 INLET 0

96 INLET 22 OUTLET 22 OUTLET 0

503 INLET 70 INLET 70 INLET 68 INLET 70 INLET 70 INLET 70 INLET 68 INLET 6

68 INLET 68 INLET 70 INLET 70 INLET 68 INLET 70 INLET 70 INLET 68 INLET 68 INLET 14 INLET 14 INLET 14 INLET 98 INLET 96 INLET 22 OUTLET 22 OUTLET 1

22 OUTLET 22 OUTLET 68 INLET 3

70 INLET 70 INLET

-68 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:09 AM Component:

S/G B Page 57 of 74 ONSIBR-EOC24 -

Tube QUERY: QueryMl[2]

Support Wear ROW 107 107 107 108 108 108 108 108 108 108 108 108 108 108 108 108 108 108 108 108 108 108 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 109 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 TUBE 113 114 115 4

5 6

7 8

14 15 20 21 47 86 88 95 97 110 ill 112 113 114 3

4 5

8 9

17 21 33 39 43 44 67 68 69 70 78 80 97 101 109 110 ill 112 113 117 4

5 6

8 10 11 12 19 43 58 87 91 93 101 102 103 106 107 108 109 110 ill VOLTS 0.39 0.29 0.57 0.11 0.08 0.09 0.28 0.09 0.10 0.11 0.11 0.14 0.16 0.06 0.14 0.06 0.06 0.11 0.23 0.08 0.09 0.17 0.13 0.31 0.25 0.15 0.16 0.15 0.09 0.30 0.09 0.12 0.12 0.14 0.08 0.06 0.10 0.10 0.09 0.09 0.10 0.22 0.12 0.17 0.08 0.12 0.06 0.06 0.14 0.12 0.41 0.52 0.52 0.12 0.09 0.15 0.27 0.11 0.09 0.08 0.10 0.24 0.21 0.16 0.09 0.06 0.12 0.05 0.11 0.08 0.12 0.10 0.20 0.11 0.17 0.14 0.26 0.14 0.50 0.28 DEG CHN 131 P2 137 P2 129 P2 118 P2 140 P2 110 P2 136 P2 134 P2 133 P2 144 P2 138 P2 150 P2 152 P2 155 P2 139 P2 132 P2 136 P2 137 P2 142 P2 149 P2 116 P2 134 P2 129 P2 134 P2 131 P2 123 P2 134 P2 139 P2 137 P2 142 P2 134 P2 152 P2 133 P2 141 P2 136 P2 145 P2 134 P2 148 P2 150 P2 134 P2 136 P2 139 P2 134 P2 130 P2 136 P2 136 P2 149 P2 145 P2 125 P2 143 P2 140 P2 131 P2 139 P2 126 P2 149 P2 135 P2 142 P2 142 P2 134 P2 69 P2 94 P2 140 P2 143 P2 133 P2 111 P2 145 P2 139 P2 160 P2 151 P2 153 P2 150 P2 149 P2 118 P2 127 P2 132 P2 141 P2 132 P2 153 P2 135 P2 135 P2 IND %TW TWD 25 TWD 20 TWD 31 TWD 9 TWD 7 TWD 8 TWD 16 TWD 6 TWD 7 TWD 6 TWD 6 TWD 7 TWD 9 TWD 4 TWD 9 TWD 4 TWD 5 TWD 8 TWD 16 TWD 6 TWD 7 TWD 14 TWD 11 TWD 21 TWD 18 TWD 12 TWD 13 TWD 9 TWD 5 TWD 17 TWD 6 TWD 7 TWD 7 TWD 7 TWD 5 TWD 5 TWD 8 TWD 8 TWD 7 TWD 7 TWD 7 TWD 15 TWD 10 TWD 12 TWD 6 TWD 10 TWD 5 TWD 5 TWD 10 TWD 9 TWD 26 TWD 27 TWD 30 TWD 9 TWD 7 TWD 9 TWD 15 TWD 6 TWD 5 TWD 5 TWD 5 TWD 13 TWD 11 TWD 9 TWD 8 TWD 5 TWD 10 TWD 4 TWD 8 TWD 7 TWD 8 TWD 7 TWD 15 TWD 8 TWD 12 TWD 11 TWD 17 TWD 11 TWD 29 TWD 18 LOCATION 010

-0.36 009

-0.44 010

-0.36 010

-0.34 011

+0,31 010

-0.31 010

-0.31 010

-0.29 010

-0.31 011

-0.43 011

-0.41 014

+0.12 014

+0.15 007

-0.51 014

+0.07 010

+0.15 007

+0.10 009

-0.61 009

-0.63 009

-0.58 013

-0.67 009

-0.55 010

-0.34 010

-0.43 010

-0.36 010

-0.38 010

-0.31 011

-0.37 010

-0.29 011

+0.30 012

+0.32 011

-0.44 015

-0.63 015

+0.07 013

+0.12 009

-0.64 009

-0.57 009

-0.64 009

-0.60 007

+0.15 007

+0.15 007

+0.13 008

-0.66 007

+0.15 009

+0.03 008

-0.59 010

+0.20 014

+0.02 014

-0.58 010

-0.36 010

-0.34 010

-0.36 010

-0.34 010

-0.34 011

+0.34 011

-0.36 011

+0.35 013

-0.44 010

-0.29 010

+0.63 010

+0.61 014

-0.56 014

+0.20 014

-0.63 009

-0.62 007

+0.13 008

-0.58 008

+0.18 010

+0.16 010

+0.23 010

+0.23 010

+0.60 009

+0.60 009

-0.49 010

-0.36 010

-0.34 010

-0.36 009

-0.47 010

-0.34 010

-0.34 EXT EXT UTIL LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 1

UTIL 2

CAL # LEG 68 INLET 70 INLET 70 INLET 68 INLET 68 INLET 70 INLET 16 INLET 14 INLET 6

16 INLET 14 INLET 98 INLET 4

98 INLET 96 INLET 98 INLET 96 INLET 96 INLET 22 OUTLET 7

511 INLET 10 OUTLET 0

505 INLET 3

505 INLET 68 INLET 3

68 INLET 24 OUTLET 68 INLET 24 OUTLET 68 INLET 16 INLET 5

14 INLET 16 INLET 96 INLET 98 INLET 98 INLET 98 INLET 96 INLET 22 OUTLET 6

543 INLET 22 OUTLET 8

545 INLET 22 OUTLET 12 OUTLET 10 OUTLET 6

10 OUTLET 10 OUTLET 12 OUTLET 0

509 INLET 0

505 INLET 0

505 INLET 74 INLET 0

74 INLET 72 INLET 74 INLET 72 INLET 74 INLET 74 INLET 14 INLET 16 INLET 14 INLET 5

14 INLET 98 INLET 98 INLET 96 INLET 98 INLET 0

96 INLET 7

543 INLET 22 OUTLET 5

509 INLET 10 OUTLET 74 INLET 72 INLET 74 INLET 6

74 INLET 72 INLET 74 INLET 74 INLET 72 INLET 74 INLET 72 INLET 72 INLET 74 INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 51OUL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 51OUL 510LX 510XB 510XB 510XB 510XB 510XB 51OUL 51OUL 510UL 510XB 510XB 510UX 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 51OUL 510XB 510XB 510XB 510UX 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510OXB 510OXB

AREVA NP Inc Customer Name: ONSI Repi 4/22/2008 9:48:10 AM Component: S/G B Page 58 of 74 ONSlBR-EOC24 -

Tube QUERY: QueryMl[2]

Support Wear ROW TUBE VOLTS Ill 2 0.10 0.16 0.24 111 4 0.18 111 8 0.09 0.08 0.12 111 15 0.17 0.22 I11 19 0.21 0.14 I11 39 0.09 111 42 0.13 111 68 0.15 11 89 0.10 111 92 0.12 111 93 0.12 i11 106 0.10 I11 107 0.27 111 109 0.31 0.10 111 110 0.12 0.20 111 111 0.15 111 112 0.08 112 4 0.16 112 7 0.21 112 8 0.08 0.06 0.14 112 9 0.14 0.20 112 10 0.09 112 15 0.16 112 19 0.14 0.11 112 20 0.14 0.08 112 21 0.07 0.14 112 40 0.10 112 41 0.09 112 42 0.09 112 68 0.07 112 89 0.12 112 93 0.09 112 100 0.14 112 105 0.15 112 107 0.16 112 108, 0.62 0.07 112 109 0.25 112 110 0.18 112 111 0.09 112 112 0.09 112 114 0.15 112 115 0.12 113 1 0.10 113 2 0.18 113 6 0.08 113 7 0.14 0.10 113 8 0.12 113 9 0.21 0.09 113 11 0.09 113 66 0.05 113 68 0.09 113 96 0.15 113 104 0.08 113 105 0.12 113 106 0.14 0.11 113 107 0.23 113 108 0.23 113 113 0.17 114 1 0.21 114 3 0.15 114 4 0.25 0.10 DEG 134 96 140 137 47 152 150 134 140 139 142 142 134 139 130 138 140 142 137 135 147 135 135 122 156 128 134 59 123 152 146 142 69 135 134 149 148 140 150 141 144 150 146 118 149 117 146 149 140 127 146 142 132 129 115 142 144 147 108 148 134 146 151 140 137 145 104 137 136 157 147 142 149 134 143 139 136 132 143 154 CHN IND P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD

%TW 6

9 12 10 5

5 7

10 12 12 8

7 11 11 8

9 9

7 17 19 7

9 13 11 6

9 12 5

4 8

8 11 5

10 8

7 8

4 5

8 8

8 7

6 9

8 11 12 13 31 5

19 13 7

7 11 9

7 10 5

8 6

7 12 6

6 4

7 12 8

9 11 10 16 18 12 13 9

14 7

LOCATION 011

-0.31 010

+0.65 015

+0.58 011

+0.34 010

+0.63 Oil j0. 4 1 013

-0.49 014

-0.59 014

+0.15 014

-0.63 014

+0.10 009

-0.69 009

-0.66 007

+0.13 014

-0.77 009

-0.55 009

-0.57 010

-0.42 010

-0.36 010

-0.34 013

+0.29 009

-0.44 010

-0.34 010

-0.34 011

+0.31 011

-0.34 011

+0.32 010

+0.61 011

+0.29 014

-0.49 011

-0.44 014

+0,27 010

+0.63 014

-0.59 014

-0.59 014

+0.10 015

+0.07 015

-0.58 015

-0.63 015

+0.02 009

-0.64 009

-0.66 009

-0.66 007

+0.20 008

-0.61 014

-0.66 010

+0.26 014

-0.52 010

-0.36 010

-0.36 011

+0.29 010

-0.36 010

-0.34 010

-0.31 010

-0.31 015

+0.61 011

+0.36 011

-0.32 010

+0.65 011

+0.32 010

-0.29 011

+0.29 011

-0.41 014

-0.49 014

+0.24 014

-0.54 007

+0.05 007

+0.16 014

-0.63 009

-0.47 009

-0.47 010

-0.39 013

-0.52 010

-0.34 010

-0.34 010

-0.31 011

-0.34 011

-0.34 010

-0.29 015

+0.61 EXT LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE UTE UTE UTE LTE UTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE LTE EXT UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE LTE LTE LTE UTE LTE UTE UTE.

UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTE UTIL 1

UTIL 2

WAR WAR 7

WAR WAR WAR WAR 2

WAR 3

WAR WAR WAR WAR 3

WAR 8

WAR WAR WAR 5

WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR 0

WAR WAR WAR WAR WAR WAR WAR WAR 6

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 0

WAR WAR 10 WAR WAR WAR WAR 2

WAR WAR WAR WAR WAR WAR 3

WAR 3

WAR 4

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR CAL # LEG 14 INLET 14 INLET 14 INLET 14 INLET 98 INLET 98 INLET 98 INLET 96 INLET 96 INLET 96 INLET 96 INLET 545 INLET 22 OUTLET 10 OUTLET 511 INLET 74 INLET 74 INLET 74 INLET 74 INLET 74 INLET 74 INLET 74 INLET 74 INLET 74 INLET 74 INLET 14 INLET 96 INLET 98 INLET 98 INLET 98 INLET 96 INLET 96 INLET 98 INLET 96 INLET 96 INLET 96 INLET 98 INLET 98 INLET 96 INLET 96 INLET.

22 OUTLET 22 OUTLET 22 OUTLET 511 INLET 10 OUTLET 76 INLET 78 INLET 76 INLET 76 INLET 78 INLET 78 INLET 76 INLET 78 INLET 74 INLET 74 INLET 74 INLET 74 INLET 16

INLET, 14 INLET 98 INLET 96 INLET 96 INLET 98 INLET 96 INLET 96 INLET 96 INLET 511 INLET 511 INLET 76 INLET 76 INLET 78 INLET 76 INLET 76 INLET 78 INLET 76 INLET 78 INLET 16 INLET 14 INLET 16 INLET 16 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB
  • 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name; ONSi Repi 4/22/2008 9:48:10 AM Component: S/G B Page 59 of 74 ONSlBR-EOC24 -,Tube Support Wear QUERY: Query~l[2]

ROW TUBE VOLTS 114 5 0.32 114 7 0.16 114 13 0.16 114 18 0.13 114 41* 0.08 114 101 0.12 114 103 0..10 114 105 0.21 114 106 0.18 0.10 114 107 0.32 114 108 0.12 114 109 0.13 114 110 0.19 115 1 0.15 115 2 0.32 115 3 0.11 115 4 0.61 0.12 0.14 115 5 0.17 0.13 115 6 0.14 0.43 0.10 115 7 0.14 115 8 0.13 115 10

'0.15 115 12 0.10 115 15 0.12 115 45 0.10 115 94 0.10 115 102 0'.12 115 104 0.27 115 105 0.52 115 106 0.11 0.11 115 109 0.13 115 110 0.10 116 3 0.15 116 4 0.11 116 5 0.08 0.09 116 6 0.14 116 10 0.13 0.10 116 38 0.11 116 41 0.09 116 42 0.09 116 88 0.08 116 90 0.16 116 94 0.11 0.07 116 100 0.08 116 102 0.11 0.10 0.06 0.09 116 103 0.33 116 104 0.44 116 105 0.45 116 106 0.08 116 109 0.21 116 110 0.10 117 1 0.12 117 2 0.30 117 3 0.15 0.11 0.11 117 12 0.15 117 40 0.10 117 43 0.15 117 44 0.13 117 89 0.08 117 93 0.08 117 100 0.10 117 101 0.23 117 102 0.34 117 103 0.17 117 104 0.20 DEG CHN 124 P2 147 P2 136 P2 147 P2 141 P2 144 P2 147 P2 142 P2 136 P2 155 P2 137 P2, 137 P2 146 P2 136 P2 133 P2 135 P2 145 P2 130 P2 141 P2 135 P2 144 P2 139 P2 133 P2 135 P2 139 P2 141 P2 139 P2 134 P2 135 P2 135 P2 152 P2 149 P2 143 P2 142 P2 131 P2 133 P2 130 P2 109 P2 145 P2 138 P2 143 P2 137 P2 142 P2 133 P2 95 P2 140 P2 155 P2 153 P2 155 P2 132 P2 143 P2 146 P2 156 P2 149 P2 143 P2 143 P2 148 P2 156 P2 139 P2 136 P2 131 P2 142 P2 141 P2 150 P2 149 P2 136 P2 133 P2 127 P2 142 P2 148 P2 155 P2 146 P2 136 P2 144 P2 155 P2 136 P2 144 P2 131 P2 142 P2 139 P2 IND %TW TWD 16 TWD 9 TWD 9 TWD 8 TWD 7 TWD 10 TWD 9

.TWD 16 TWD 13 TWD 8 TWD 22 TWD 9 TWD 11 TWD 14 TWD 9 TWD 16 TWD 7 TWD 25 TWD 7 TWD 8 TWD 9 TWD 7 TWD 9 TWD 21 TWD 6 TWD 7 TWD 8 TWD 9 TWD 6 TWD 7 TWD 9 TWD 8 TWD 11 TWD 20 TWD 28 TWD 10 TWD 9 TWD 9 TWD 9 TWD 10 TWD 6 TWD 5 TWD 6 TWD 7 TWD 7 TWD 6 TWD 9 TWD.7 TWD 8 TWD 6 TWD 13 TWD 10 TWD 6 TWD 8 TWD 10 TWD 9 TWD 5 TWD 8 TWD 21 TWD 28 TWD 26 TWD 7 TWD 15 TWD 9 TWD 7 TWD 15 TWD 8 TWD 6 TWD 6 TWD 9 TWD 9 TWD 12 TWD 9 TWD 7 TWD 7 TWD 8 TWD 17 TWDO 21 TWD 14 TWD 14 LOCATION 010

-0.26 011

-0.41 014

-0.58 011

-0.53 009

-0.66 010

+0.60 010

+0.60 010

-0.39 010

-0.34 010

+0.52 010

-0.36 010

-0.36 010

-0.34 010'

-0.31 011

-0.32 011

-0.36 010

-0.27 010.

-0.31 011

-0.34 011

+0.34 011

+0.37 010

-0.27 010

-0.32 011

+0.32 012

+0.32 011

+0.29 011

-0.41 010

+0.54 014

+0.22 014

+0.17 009

-0.66 009

-0.52 010

+0.62 010

-0.39 010

-0.36 010

-0.34 010

+0.60 010

-0.31 010

-0.29 010

-0.27 011

-0.36 011

-0.37 011

+0.32 010

+0.07 010

+0.58 013

-0.51 009

-0.64 009

-0.61 009

-0.66 009

-0.54 009

-0.55 009

-0.52 010

+0.21 011

+0.23 009

-0.47 010

+0.65 013

-0.50 013

+0.26 010

-0.36 010

-0.36 010

-0.34 010

-0.31 010

-0.31 011

-0.34 011

-0.34 011

-0.33 011

-0.36 011

+0.32 015

+0.60 014

+0.20 009

-0.66 009

-0.64 009

-0.60 009

-0.57.

009

-0.52 009

-0.47 010

-0.39 010

-0.36 010

-0.36 010

-0.34 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL I

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

14 98 9

98 5

96 22 7

76 76 76 78 78 76 78 76 78 16 14 16 14 14 14 98 7

98 96 96 96 5

98 5

96 9

96 4

96 4

98 22 76 76 76 78 76 76 78 76 16 4

14 3

104 3

104 106 106 0

106 22 22 22 4

505 76 76 76 76 76 76 76 76 78 76 78 76 78 76 16 14 106 4

106 6

106 104 22 22 9

545 76 76 78 0

76 78 76 78 LEG INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 5 1OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:10 Am Component:

S/G B Page 60 of 74 ONSlBR-EOC24 - Tube Support Wear QUERY: QueryMl[2]

ROW TUBE 117 107 118 1 118 4 118 7 118 8 118 14 118 16 118 43 118 44 118 46 118 85 118 91 118 96 118 99 118 100 118 102 118 103 118 104 119 4 119 7 119 13 119 37 119 38 119 40 119 42 119 44 119 72 119 76 119 87 119 91 119 97 119 99 119 100 119 101 119 102 120 2 120 3 120 4 120 7 120 8 120 14 120 37 120 39 120 40 120 42 120 43 120 46 120 47 120 98 120 100 120 101 120 102 120 103 120 107 121 1 121 2 121 5 121 8 121 9 121 10 121 12 121 27 121 34 121 35 121 41 121 42 121 86 121 87 VOLTS 0.10 0.12 0.24 0.14 0.11 0.12 0.12 0.13 0.13 0.10 0.15 0.14 0.05 0.20 0.13 0.10 0.15 0.12 0.17 0.07 0.33 0.22 0.09 0.11 0.12 0.19 0.16 0.12 0.06 0.08 0.07 0.10 0.09 0.07 0.08 0.12 0.08 0.10 0.19 0.08 0.38 0.16 0.19 0.25 0.09 0.12 0.12 0.07 0.12 0.10 0.18 0.10 0.07 0.09 0.09 0.09 0.08 0.09 0.11 0.15 0.19 0.23 0.11 0.11 0.10 0.14 0.13 0.18 0.16 0.10 0.12 0.06 0.06 0.15 0.09 0.09 0.12 0.10 0.13 0.18 DEG 146 129 142 139 141 151 135 142 144 147 140 138 145 132 143 139 130 146 141 150 134 132 148 140 141 141 142 142 156 150 154 155 153 90 148 137 146 152 145 150 134 145 142 138 149 145 120 148 145 155 144 150 150 146 148 154 155 143 139 144 136 143 140 136 135 125 144 136 127 146 148 154 153 139 146 140 146 150 148 145 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2.

P2 P2 P2 IND TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 9

8 13 9

7 8

7 7

7 6

12 11 4

17 10 9

11 9

14 6

23 15 8

6 8

11 10 7

5 7

6 8

7 6

6 9

7 9

15 7

23 13 14 14 6

7 7

5 7

6 11 9

6 7

7 8

7 7

10 12 14 18 10 8

8 8

8 10 10 6

7 4

4 13 9

8 9

9 10 15 LOCATION 010

-0.34 011

-0.34 011

+0.34 011

-0.41 013

-0.42 012

+0.32 011

+0.32 011

-0.41 014

-0.56 014

+0.17 009

-0.64 009

-0.64 010

+0.05 014

-0.63 010

+0.24 010

+0.60 010

-0.37 010 40.63 010

-0:39 011

+0.26 010

-0.36 010

-0.34 010

-0.31 013

-0.42 011

-0.41 014

+0.17 014

-0.51 013

-0.51 007

+0.15 009

-0.64 009

-0.64 009

-0.61 009

-0.64 010

+0.08 010

+0.14 008

-0.56 009

-0.52 014

+0.13 014

-0.50 009

-0.47 010

-0.37 010

-0.37 010

-0.37 011

-0.35 012

+0.34 011

-0.34 013

-0.39 013

-0.39 011

+0.29 011

-0.44 014

-0.56 009

-0.64 009

-0.64 009

-0.64 009

-0.64 009

-0.61 009

-0.64 009

-0.64 010

-0.39 010

-0.39 010

-0.34 010

-0.34 010

+0.65 010

-0.31 010

-0.29 013

-0.34 011

-0.37 013

-0.42 011

+0.29 011

-0.41 013

-0.46 011

-0.44 011

-0.46 014

-0.63 009

-0.52 009

-0.52 009

-0.64 009

-0.61 014

+0.13 014

-0.58 EXT EXT UTIL 1

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTE LTE WAR UTE LTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL # LEG 76 INLET 16 INLET 106 INLET 104 INLET 3

104 INLET 5

104 INLET 5

104 INLET 0

106 INLET 3

106 INLET 4

106 INLET 22 OUTLET 22 OUTLET 22 OUTLET 80 INLET 4

78 INLET 4

76 INLET 78 INLET 78 INLET 76 INLET 76 INLET 76 INLET 78 INLET 76 INLET 5

106 INLET 5

104 INLET 3

104 INLET 6

104 INLET 3

104 INLET 22 OUTLET 22 OUTLET 22 OUTLET 22 OUTLET 22 OUTLET 4

22 OUTLET 4

509 INLET 7

505 INLET 76 INLET 76 INLET 76 INLET 76 INLET 78 INLET 76 INLET 78 INLET 104 INLET 0

104 INLET 5

106 INLET 6

106 INLET 3

104 INLET 106 INLET 104 INLET 104 INLET 22 OUTLET 22 OUTLET 22 OUTLET 22 OUTLET 22 OUTLET 22 OUTLET 22 OUTLET 76 INLET 76 INLET 78 INLET 76 INLET 76 INLET 78 INLET 78 INLET 6

106 INLET 104 INLET 106 INLET 104 INLET 4

106 INLET 4

106 INLET 0

104 INLET 0

104 INLET 88 INLET 88 INLET 90 INLET 22 OUTLET 22 OUTLET 78 INLET 76 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc 4/22/2008 9:48:11 AM Customer Name: ONSI Repl Component: S/G B Page 61 of 74 ONSlBR-EOC24 - Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 0.12 121 88 0.18 0.14 0.17 121 93 0.06 121 98 0.31 121 99 0.14 121 100 0.23 121 101 0.13 121 103 0.05 122 1 0.13 122 4 0.09 122 10 0.12 122 13 0.13 122 16 0.14 0.08 122 17 0.10 122 20 0.11 0.13 122 41 0.14 122 42 0.15 122 44 0.08 0.08 122 64 0.07 122 74 0.11 122 75 0.12 0.11 122 78 0.09 0.13 122 87 0.14 122 88 0.09 122 89 0.11 122 90 0.09 0.12 122 93 0.08 122 97 0.37 122 98 0.20 122 99 0.29 122 100 0.13 123 1 0.12 123 3 0.13 123 9 0.08 123 15 0.17 123 19 0.23 0.31 123 40 0.09 123 41 0.12 123 44 0.12 123 69 0.13 123 71 0.10 123 88 0.11 123 94 0.14 123 95 0.11 123 96 0.18 123 97 0.17 123 98 0.22 123 99 0.25 123 100 0.14 124 7, 0.09 124 '14 0.10 124 39 0.10 124 40 0.11 124 41 0.06 124 42 0.08 124 43 0.12 124 44 0.08 124 45 0.12 124 56 0.17 124 77 0.07 124 85 0.11 124 87 0.11 124 88 0.20 124 89 0.07 124 90 0.09 124 92 0.13 124 93 0.09 124 94 0.10 124 95 0.13 124 96 0.16 124 97 0.12 DEG 153 142 142 147 156 129 146 135 143 155 143 146 140 146 143 132 148 128 135 145 149 133 149 150 139 126 155 140 156 146 154 141 155 94 144 132 135 128 144 130 146 153 150 141 142 148 151 140 137 157 145 118 152 139 138 137 136 128 152 136 152 154 135 153 145 149 152 138 145 133 89 145 156 150 148 126 131 138 142 143 CHN IND P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWO P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD

%TW LOCATION 10 014

+0.13 13 010

-0.44 11 010

+0.24 12 014

+0.16 6

014

+0.24 20 010

-0.34 12 010

-0.37 17 010

-0.41 11 010

-0.34 4

010

-0.34 7

011

-0.34 6

011

-0.35 7

014

+0.27 7

014

+0.19 9

014

-0.53 5

014

+0.19 6

008

+0.24.

7 010

+0.22 8

014

-0.61 11 009

-0.54 12 009

-0.64 7

010

+0.08 7

009

-0.61 5

009

+0.14 10 014

+0.05 10 013

-0.66 9

014

+0.03 8

014

-0.63 12 014

-0.03 11 009

-0.59 8

014

+0.18 8

013

-0.55 8

014

+0.16 10 010

+0.60 7

010

-0.43 22 010

-0.34 15 010

-0.34 19 010

-0.37 11 010

-0.31 7

011

-0.34 7

011

-0.32 5

011

-0.41 9

014

-0.54 12 014

-0.56 15 014

+0.12 8

009

-0.66 10 009

-0.61 10 009

-0.64 12 009

-0.58 9

014

+0.05 10 014

-0.58 11 010

+0.63 9

010

-0.41 15 010

-0.34 12 010

-0.34 17 010

-0.34 17 010

-0.31 11 010

-0.31 5

014

-0.44 6

014

+0.17 8

009

-0.61 9

009

-0.64 5

009

+0.08 7

009

-0.61 10 009

-0.64 6

009

-0.64 9

009

-0.61 12 009

-0.64 6

010

+0.18 9

010

+0.55 9

010

+0.63 16 014

-0.52 6

014

+0.21 8

009

-0.50 11 014

-0.50 8

010

-0.39 8

010

-0.34 11 010

-0.37 13 010

-0.34 10 010

-0.34 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL I

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL # LEG PROBE 76 78 78 78 76 78 76 24 76 76 106 3

104 104 106 5

104 2

104 4

106 3

104 5

104 22 22 22 22 4

511 80 82 82 80 80 24 76 7

78 76 7

76 6

24 78 76 78 76 6

106 106 106 106 106 7

106 22 22 22 80 80 76 8

76 5

24 2

76 78 76 78 76 0

106 5

104 22 22 22 22 22 22 22 12 3

505 4

76 4

76 76 76 76 76 4

76 4

76 76 76 76 INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OUL 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:11 AM Component: S/G B Page 62 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: Query~l[2]

ROW TUBE VOLTS DEG CHN IND 124 98 124 99 125 13 125 16 125 27 125 37 125 38 125 39 125 40 125 41 125 44 125 53 125 54 125 73 125 90 125 91 125 92 125 93 125 94 125 95 125 96 125 97 126 17 126 18 126 22 126 26 126 38 126 39 126 40 126 41 126 45 126 47 126 51 126 53 126 55 126 57 126 66 126 68 126 70 126 84 126 85 126 86 126 90 126 91 126 92 126 93 126 94 126 95 126 96 126 97 127 4 127 9 127 14 127 22 127 38 127 42 127 50 127 51 127 67 127 87 127 88 127 89 127 91 127 92 127 93 127 94 127 95 127 96 127 98 128 11 128 15 0.14 0.08 0.16 0.14 0.14 0.10 0.08 0.12 0.10 0.09 0.09 0.10 0.11 0.12 0.16 0.13 0.10 0.10 0.22 0.14 0.08 0.25 0.15 0.36 0.06 0.13 0.13 0.08 0.07 0.14 0.08 0.10 0.08 0.12 0.12 0.11 0.14 0.11 0.12 0.07 0.11 0.06 0.08 0.08 0.11 0.19 0.07 0.14 0.08 0.12 0.12 0.09 0.22 0.14 0.12 0.10 0.12 0.12 0.09 0.07 0.14 0.10 0.05 0.10 0.07 0.12 0.16 0.11 0.17 0.09 0.09 0.14 0.12 0.09 0.09 0.13 0.13 0.10 0.24 0.11 134 P2 144 P2 146 P2 152 P2 142 P2 135 P2 146 P2 135 P2 150 P2 144 P2 144 P2 148 P2 154 P2 146 P2 132 P2 131 P2 136 P2 160 P2 149 P2 128 P2 152 P2 128 P2 146 P2 127 P2 136 P2 142 P2 144 P2 137 P2 151 P2 141 P2 146 P2 139 P2 131 P2 148 P2 129 P2 134 P2 140 P2 148 P2 142 P2 142 P2 143 P2 148 P2 153 P2 153 P2 135 P2 144 P2 156 P2 139 P2 143 P2 150 P2 137 P2 146 P2 128 P2 145 P2 145 P2 130 P2 152 P2 131 P2 144 P2 148 P2 144 P2 145 P2 144 P2 152 P2 147 P2 121 P2 130 P2 115 P2 140 P2 149 P2 146 P2 144 P2 127 P2 135 P2 127 P2 150 P2 138 P2 149 P2 146 P2 135 P2 TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW LOCATION 12 010

-0.31 8

010

-0.31 9

014

+0.19 8

013

-0.51 9

014

+0.15 7

009

+0.19 8

009

-0.57 10 009

-0.55 9

009

-0.54 8

009

+0.10 8

009

-0.64 9

009

-0.64 9

009

-0.66 9

009

-0.60 12 009

-0.64 9

014

-0.61 8

009

-0.54 9

010

-0.34 18 014

-0.50 11 010

-0.36 8

010

-0.34 18 010

-0.36 13 010

-0,31 23 010

-0.33 6

010

-0.42 8

014

-0.51 7

014

-0.54 5

014

+0.15 7

010

+0.21 13 014

-0.60 8

009

-0.55 9

009

-0.55 8

009

-0.57 10 009

-0.57 10 013

-0.71 10 008

-0.57 12 009

-0.57 9

009

-0.57 11 009

-0.57 7

010

+0.13 10 009

-0.55 5

009

-0.57 6

009

-0.56 7

014

+0.08 9

013

-0.66 16 014

-0.65 7

010

-0.39 11 014

+0.21 8

013

-0.55 11 010

-0.36 9

010

-0.36 8

010

-0.36 16 010

-0.36 13 010

-0.34 11 010

+0.65 8

010

-0.33 11 010

-0.31 10 010

-0.31 6

011

-0.47 4

013

-0.44 9

014

-0.51 7

014

+0.19 5

010

+0.26 9

009

-0.57 7

009

-0.57 11 009

-0.57 13 009

-0.57 11 013

-0.63 15 010

+0.63 7

010

-0.36 8

010

-0.37 12 010

-0.37 9

010

-0.36 8

010

-0.34 8

010

-0.31 12 010

-0.31 11 010

-0.31 8

011

+0.39 14 010

+0.68 7

014

+0.19 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE UTE LTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

76 76 106 0

106 104 4

523 88 90 88 22 22 22 22 4

547 22 0

505 24 80 80 6

82 80 82 80 82 80 104 6

106 2

106 2

88 88 88 90 88 90 90 88 88 90 88 88 80 3

505 4

505 80 5

505 80 80 82 80 80 3

82 80 82 80 7

80 82 80 82 4

104 106 104 104 0

90 88 88 88 90 80 10 80 82 80 80 82 80 82 80 82 82 104 104 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET OUTLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 51OXB 510XB 510XB 510XB 510XB 510UL 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510UL 51OXB 510UL 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510UL 51OUL 51OXB 510UL 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repi 4/22/2008 9:48:11 AM Component: S/G B Page 63 of 74 ONSlBR-EOC24 -

Tube QUERY: QueryMl(2]

Support Wear ROW TUBE 128 32 128 33 128 34 128 37 128 39 128 40 128 41 128 51 128 55 128 56 128 61 128 73 128 78 128 81 128 83 128 86 128 87 128 88 128 89 128 90 128 92 128 93 128 94 129 10 129 129 129 129 129 129 129 129 129 129 129 129 129 229 129 129 129 129 129 129 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 130 VOLTS 0.09 0.09 0.11 0.10 0.10 0.07 0.12 0.13 0.16 0.08 0.11 0.08 0.13 0.10 0.12 0.14 0.06 0.14 0.14 0.09 0.06 0.13 0.09 0.10 0.08 0.06 0.14 0.21 0.12 0.07 0.14 0.13 0.06 0.08 0.11 0.08 0.07 0.09 0.07 0.11 0.11 0.12 0.09 0.05 0.13 0.10 0.07 0.15 0.10 0.22 0.07 0.15 0.11 0.08 0.21 0.17 0.17 0.08 0.10 0.11 0.07 0.13 0.10 0.08 0.12 0.09 0.07 0.10 0.05 0.05 0.05 0.10 0.18 0.05 0.04 0.06 0.05 0.07 0.26 0.16 DEG 152 140 112 138 146 140 144 136 143 153 134 130 144 145 142 148 155 147 139 152 152 143 141 138 141 159 148 142 129 144 153 143 138 151 147 152 150 141 151 107 141 140 117 140 147 130 153 136 137 131 159 132 140 136 147 148 143 145 143 150 160 147 109 138 140 135 122 146 131 139 163 145 141 145 148 152 153 149 134 147 CHN IND P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD

%TW LOCATION EXT 8

009

-0.55 LTE 9

009

-0.55 LTE 10 013

-0.68 LTE 8

009

-0.52 LTE 9

009

-0.55 LTE 7

009

-0.57 LTE 11 009

-0.55 LTE 11 009

-0.55 LTE 15 009

-0.55 LTE 6

011

+0.17 LTE 8

008

-0.52 LTE 7

009

-0.58 LTE 11 009

-0.55 LTE 10 009

-0.52 LTE 10 013

-0.52 LTE 11 014

-0.52 LTE 6

009

-0.47 LTE 13 010

-0.37 LTE 11 010

-0.36 LTE 9

010

-0.37 LTE 6

011

+0.29 LTE 11 010

-0.34 LTE 9

010

-0.34 LTE 10 010

-0.31 LTE 6

010

-0.31 LTE 6

010

-0.31 LTE 9

011

-0.42 LTE 12 011

+0.29 LTE 8

010

-0.27 LTE 5

008

+0.27 LTE 7

010

+0.48 LTE 8

008

+0.38 LTE 5

013

+0.18 LTE 7

009

-0.55 LTE 10 009

-0.52 LTE 7

009

-0.52 LTE 6

008

-0.54 LTE 9

009

-0.57 LTE 7

014

+0.05 LTE 9

009

-0.57 LTE 9

009

-0.57 LTE 10 009

-0.55 LTE 8

013

-0.66 LTE 6

008

+0.18 LTE 10 009

-0.55 LTE 8

014

-0.58 LTE 6

014

-0.52 LTE 12 010

-0.36 LTE 8

009

-0.47 LTE 16 010

-0:36 LTE 7

010

-0.37 LTE 11 010

-0.34 LTE 9

010

-0.31 LTE 8

010

-0.34 LTE 12 010

+0.58 LTE 9

010

+0.58 LTE 9

014

-0.49 LTE

5.

014

+0.15 LTE 9

014

-0.52 LTE 9

010

+0.26 LTE 5

010

+0.21 LTE 10 009

-0.55 LTE 9

013

-0.65 LTE 7

009

-0.54 LTE 9

009

-0,54 LTE 8

009

-0.57 LTE 6

009

-0,57 LTE 9

009

-0.54 LTE 5

008

+0.24 LTE 6

008

+0.24 LTE 5

014

+0.13 LTE 8

014

-0.58 LTE 14 014

+0.18 LTE 6

010

+0.26 LTE 4

014

+0.26 LTE 6

010

-0.42 LTE 5

010

-0.42 LTE 7

010

-0.37 LTE 18 010

-0.34 LTE 14 010

-0.37 LTE EXT UTIL UTE WAR UTE WAR' UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE.

WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR OTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR UTE WAR I

UTIL 2

CAL #

90 88 88 90 88 90 88 90 84 6

505 6

507 80 82 80 82 0

82 80 80 82 80 80 82 80 80 82 80 104 104 104 104 106 104 2

90 90 88 90 88 88 88 90 90 90 90 3

84 86 0

86 82 5

82 82 82 80 82 82 80 104 7

106 5

106 0

104 6

110 4

110 4

94 94 92 92 94 92 92 92 84 84 84 86 86 0'

84 84 5

84 80 80 82 80 LEG PROBE INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OUL INLET 51OUL INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET

/ 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET

)510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:12 Am Component:

S/G B Page 64 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl(2]

ROW TUBE 130 87 131 9 131 12 131 13 131 18 131 27 131 32 131 33 131 34 131 37 131 40 131 41 131 42 131 43 131 44 131 45 131 46 131 47 131 49 131 63 131 75 131 83 131 84 132 11 132 14 132 18 132 132 132 132 132 132 132 132 132 132 132 132 132 132 132 132 132 132 132 132 132 132 132 133 133 133 133 133 133 133 133 133 133 133 133 133 133 133 133 133 133 133 VOLTS 0.24 0.10 0.08 0.13 0.16 0.09 0.07 0.07 0.13 0.11 0.08 0.11 0.14 0.12 0.16 0.09 0.14 0.16 0.09 0.14 0.09 0.05 Q.07 0.11 0.12 0.11 0.11 0.22 0.12 0.16 0.07 0.07 0.15 0.08 0.08 0.11 0.10 0.09 0.11 0.09 0.13 0.14 0.13 0.05 0.09 0.12 0.08 0.07 0.09 0.14 0.12 0.12 0.11 0.11 0.07 0.10 0.15 0.09 0.11 0.07 0.09 0.13 0.45 0.14 0.10 0.12 0.11 0.07 0.11 0.11 0.07 0.17 0.09 0.11 0.12 0.12 0.10 0.06 0.08 0.06 DEG CHN 133 P2 148 P2 155 P2 133 P2 155 P2 152 P2 140 P2 153 P2 143 P2 123 P2 147 P2 143 P2 140 P2 141 P2 134 P2 135 P2 135 P2 148 P2 121 P2 132 P2 150 P2 143 P2 157 P2 151 P2 126 P2 145 P2 149 P2 142 P2 132 P2 144 P2 157 P2 153 P2 128 P2 154 P2 145 P2 150 P2 143 P2 148 P2 155 P2 138 P2 136 P2 145 P2 148 P2 90 P2 143 P2 144 P2 149 P2 157 P2 145 P2 146 P2 143 P2 141 P2 141 P2 152 P2 153 P2 147 P2 129 P2 150 P2 142 P2 143 P2 136 P2 141 P2 135 P2 138 P2 145 P2 135 P2 146 P2 147 P2 148 P2 148 P2 139 P2 144 P2 145 P2 129 P2 128 P2 147 P2 139 P2 155 P2 139 P2 150 P2 IND %TW TWD 17 TWD 6 TWD 5 TWD 8 TWD 9 TWD 8 TWD 6 TWD 7 TWD 10 TWD 10 TWD 6 TWD 9 TWO 11 TWD 10 TWD 12 TWD 8 TWD 11 TWD 13 TWD 8 TWD 11 TWD 9 TWD 5 TWD 7 TWD 10 TWD 10 TWD 6 TWD 7 TWD 17 TWD 10 TWD 13 TWD 7 TWD 7 TWD II TWD 7 TWD 7 TWD 10 TWD 8 TWD 8 TWD 9 TWD 7 TWD 11 TWD 13 TWD 10 TWD 5 TWD 8 TWO 10 TWD 8 TWD 6 TWD 7 TWD 11 TWD 10 TWD 9 TWD 9 TWD 11 TWD 7 TWD 8 TWD 12 TWD 9 TWD 9 TWD 6 TWD 7 TWD 11 TWD 28 TWD 12 TWD 8 TWO 10 TWD 10 TWD 6 TWD 8 TWD 10 TWD 5 TWD 14 TWD 8 TWD 8 TWD 12 TWD 12 TWD 8 TWD 6 TWD 7 TWD 6 LOCATION 010

-0.37 010

+0.61 014

-0.49 014

+0.22 010

+0.58 014

+0.18 009

+0.23

.009

-0.54 009

-0.49 013

-0.63 009

-0.57 009

-0.54 009

-0.60 009

-0.60 009

-0.57 009

-0.57 009

-0.54 009

-0.59 013

-0.62 013

-0.63 009

-0.58 008

+0.26 009

-0.52 010

-0.37 010

-0.34 013

+0.29 010

+0.56 013

-0.55 013

+0.21 014

+0.16 014

+0.16 009

-0.52 009

-0.52 009

-0.52 009

-0.54 009

-0.55 009

-0.52 009

-0.54 010

+0.21 013

-0.63 009

-0.52 009

-0.55 009

-0.55 008

+0.26 009

-0.52 010

+0.24 009

-0.52 009

-0.55 010

+0.26 014

-0.58 014

+0.21 013

-0.53 013

+0.21 014

+0.18 009

-0.50 009

-0.42 010

-0.34 010

-0.34 010

-0.34 010

-0.31 011

+0.20 014

+0.26 010

+0.55 014

-0.55 009

-0.47 014

+0.13 013

-0.58 014

+0.16 009

-0.55 009

-0.55 008

+0.16 009

-0.55 009

-0.55 013

-0.63 009

-0.55 009

-0.52 013

-0.61 008

+0.21 008

+0.24 008

-0.52 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE -UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

82 106 104 104 7

106 108 3

94 92 94 92 94 92 94 92 94 92 94 92 92 94 84 3

84 84 80 82 106 104 110 110 110 108 92 94 92 94 92 94 92 94 94 92 84 86 84 86 86 84 86 86 86 86 5

86 4

86 84 80 82 0

82 80 82 80 0

26 110 110 108 3

108 110 3

108 0

108 94 92 94 92 92 94 84 84 7

86 84 86 84 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET

-INLET INLET INLET INLET INLET INLET INLET INLET INLET.

INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI RepS 4/22/2008 9:48:12 AM Component: S/G B Page 65 of 74 ONSlBR-E0C24 Tube Support Near QUERY: QueryMl[2]

ROW

'33 133 133 133 133 133 133 133 133 133 134 134 134 134 134 134 134 134 134

'134 134 134 134 134 134 134 134 134 134 134 134 1 3.4 134 134 134 134 134 134 134 134 134 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 135 TUBE VOLTS 60 0.12 67 0.08 71 0.05 72 0.24 0.11 0.11 75 0.15 78 0.14 79 0.17 80 0.21 81 0.08 82 1.28 10 0.07 12 0.26 13 0.77 0.08 0.31 0.09 14 0.09 0.82 15 0.09 16 0.10 22 0.19 28 0.22 32 0.06 34 0.06 38 0.10 39 0.10 40 0.11 41 0.12 44 0.13 45 0.08 46 0.08 0.05 47 0.07 48 0.07 49 0.08 50 0.10 52 0.08 0.08 53 0.05 55 0.05 63 0.24 65 0.13 70 0.27 75 0.16 77 0.09 0.13 79 0.13 82 0.08 5

0.09 7

0.14 9

0.18 11 0.35 0.17 13 0.20 27 0.11 28 0.17 31 0.09 32 0.10 33 0.07 35 0.06 36 0.08 37 0.10 39 0.12 40 0.09 42 0.09 43 0.12 44 0.11 46 0.12 47 0.07 48 0.07 0.20 50 0.07 0.14 0,10 52 0.09 54 0.09 63 0.07 72 0.08 DEG CHN 139 P2 123 P2 146 P2 138 P2 151 P2 135 P2 151 P2 141 P2 150 P2 132 P2 151 P2 123 P2 139 P2 131 P2 131 P2

.152 P2 139 P2 152 P2 139 P2 127 P2 153 P2 131 P2 115 P2 137 P2 141 P2 139 P2 143 P2 151 P2 147 P2 149 P2 147 P2 144 P2 152 P2 157 P2 152 P2 148 P2 158 P2 137 P2 146 P2 144 P2 143 P2 100 P2 142 P2 150 P2 143 P2 136 P2 146 P2 140 P2 133 P2 149 P2 72 P2 116 P2 122 P2 137 P2 137 P2 138 P2 140 P2 139 P2 147 P2 135 P2 125 P2 143 P2 153 P2 143 P2 141 P2 151 P2 131 P2 142 P2 145 P2 149 P2 135 P2 122 P2 140 P2 128 P2 143 P2 148 P2 126 P2 122 P2 153 P2 143 P2 IND %TW TWD 9 TWD 8 TWD 5 TWD 17 TWD 9 TWD 9

TWD 14 TWD 11 TWD 14 TWD 15 TWD 7 TWD 45 TWD 6 TWD 17 TWD 38 TWD 7 TWD 22 TWD 8 TWD 8 TWD 39 TWD 8

TWD 9

TWD 15 TWD 16 TWD 5 TWD 5 TWD 8

TWD 9

TWD 8 TWD 10 TWD 10 TWD 7 TWD 8

TWD 5 TWD 7 TWD 6

TWD 8 TWD 8 TWD 7 TWD 7 TWD 5

TWD 5

TWD 20 TWD 12 TWD 19 TWD 14 TWD 7 TWD 11 TWD 11 TWD 7 TWD 7 TWD II TWD 13 TWD 24 TWD 14 TWD 16 TWD 8

TWD 14 TWD 7 TWD 9

TWD 6

TWD 5

TWD 7 TWD 8 TWD 9 TWD 8 TWD 8 TWD 9

TWD 8

TWD 10 TWD 7 TWD 6

TWD 15 TWD 6

TWD 11 TWD 8 TWD 8 TWD 8

TWD 8

TWD 7 LOCATION 008

+0.24 013

-0.66 008

+0.26 010

-0.37 013

-0.50 010

+0.63 010

-0.37 010

-0.37 010

-0.37 010

-0.37 010

-0.34 010

-0.31 014

+0.20 011

+0.23 011

+0.26 012

-0.44 012

+0.31 013

-0.47 010

+0.63 011

+0.26 014

+0.21 014

-0.50 014

-0.55 014

-0.58 009

-0.52 010

+0.26 009

-0.49 009

-0.52 009

-0.52 009

-0.52 009

-0.55 009

-0.52 009

-0.52 008

+0.21 008

-0.62 009

-0.55 009

-0.55 013

-0.60 008

-0.52 008

+0.21 008

+0.26 008

+0.28 009

-0.55 009

-0.52 014

-0.53 010

+0.60 009

-0.50 010

-0.34 010

-0.34 010

-0.34 010

+0.64 010

+0.56 010

+0.59 011

+0.29 012

+0.32 011

+0.26 014

+0.13 014

-0.65 010

+0.24 014

-0.58 008

-0.52 010

+0.26 009

-0.52 009

-0.52 009

-0.57 009

-0.55 009

-0.59 009

-0.55 009

-0.54 009

-0.57 009

-0.55 008

+0.23 009

-0.55 008

+0.23 009

-0.52 013

-0.58 008

+0.26 008

+0.26 009

-0.55 009

-0.47 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LýTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE OTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL #

86 84 84 86 86 6

86 80 82 80 82 80 LAR 82 4

26 26 108 108 108 108 110 110 108 110 110 94 4

94 0

94 94 92 94 92 94 92 84 3

84 5

84 86 84 7

86 0

86 0

86 84 84 84 84 86 80 82 82 82 80 26 26 26 110 110 110 94 92 94 92 94 0

94 92 94 94 92 116 94 94 86 84 86 86 86 86 86 86 86 84 86 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB' 510XB

'510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB SlOXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name:

ONSI Repl 4/22/2008 9:48:13 AM Component: S/G B Page 66 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW 135 135 135 135 135 135 135 136 136 i36 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 136 137 137 137 137 137 137 137 137 137 137 137 137 137 137 137 137 137 137 137 137 TUBE VOLTS DEG 73 0.07 148 74 0.13 146 0.44 132 75 0.07 156 0.05 148 76 0.16 128 77 0.09 149 78 0.08 140 80 0.11 130 9

0.24 133 0.09 141 13 0.08 143 1.24 121 14 0.13 133 0.10 145 17 0.09 140 18 0.13 134 20 0.15 143 21 0.11 137 26 0.11 146 0.27 135 29 0.07 152 30 0.18 137 31 0.07 149 33 0.18 131 34 0.08 132 36 0.12 144 37 0.09 151 38 0.06 150 0.09 150 40 0.08 145 41 0.17 141 0.06 151 42 0.10 147 43 0.07 142 44 0.09 142 47 0.07 149 49 0.06 151 0.10 148 50 0.12 133 51 0.08 159 0.11 131 0.04 152 53 0.04 94 62 0.24 139 0.12 148 63 0.21 152 64 0.06 147 0.10 152 69 0.16 143 70 0.25 137 0.13 98 71 0,.04 135 72 0.10 140 0.63 132 73 0.07 155 0.17 144 75 0.14 146 76 0.08 149 81 0.26 131 10 0.42 139 11 0,13 131 13 0.18 122 16 0.14 147 24 0.16 136 25 0.06 159 26 0.11 132 27 0.07 154 29 0.11 142 33 0.12 147 35 0.06 152 37 0.08 139 40 0.08 155 43 0.07 151 44 0.08 141 45 0.07 156 51 0.06

- 153 58 0.13 138 60 0.06 148 61 0.07 151 CHN P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 IND TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW LOCATION 6

009

-0.52 11 009

-0.47 26 010

-0.37 6

009

-0.50 5

013

+0.29 12 010

-0.37 8

010

-0.34 6

010

-0.34 9

010

-0.34 16 011

+0.23 7

012

+0.28 7

009

-0.45 46 011

+0.26 11 010

+0.62 8

009

-0.44 8

009

-0.44 11 010

+0.60 12 014

-0.52 9

014

-0.55 9

010

+0.57 18 014

-0.58 5

008

-0.47 13 013

-0.55 6

014

+0.03 13 014

-0.58 7

014

-0.60 9

009

-0.52 7

009

-0.52 5

009

-0.52 7

008

-0.47 7

009

-0.52 12 009

-0.49 5

010

+0.26 8

009

-0.52 6

009

-0.57 9

009

-0.55 8

009

-0.55 6

009

-0.49 10 013

-0.60 10 009

-0.52 8

009

-0.52 11 013

-0.60 4

008

+0.26 5

008

+0.26 17 014

-0.52 9

014

+0.26 15 014

-0.51 5

009

-0.52 8

013

-0.50 14 010

-0.39 18 010

-0.42 10 010

+0.62 4

009

-0.49 8

009

-0.47 33 010

-0.39 7

009

-0.47 14, 010

-0.37 13 010

-0.39 8

010

-0.37 18 010

-0.31 27 011

+0.26 11 011

+0.24 14 010

+0.63 11 010

+0.60 12 014

-0.60 5

008

-0.46 8

013

-0.58 6

008

-0.49 8

008

-0.49 10 008

-0.49 5

009

-0.51 7

013

-0.60 7

009

-0.55 7

009

-0.55 7

008

+0.21 7

009

-0.55 6

008

-0.52 11 010

-0.42 5

009

-0.52 8

009

-0.52 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

80 82 82 80 80 82 80 82 82 26 3

26 110 LAR 110 108 4

108 110 108 108 110 94 94 94 94 4

94 94 94 94 94 94 2

94 94 94 0

94 94 94 84 84 84 84 86 84 84 84 84 86 86 28 86 4

86 84 0

86 6

86 84 86 86 80 80 80 80 82 108 4

110 4

110 108 94 94 94 94 94 100 100 100 102 84 86 84 84 5

86 86 84 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:13 AM Component: S/G B Page 67 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW 137 137 137 137 137 137 137 137 137 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 138 139 139 139 139 139 139 139 139 139 139 139 139 139 TUBE VOLTS 0.05 62 0.12 65 0.13 0.07 67 0.27 0.04 0.11 68 0.15 69 0.06 0.05 71 0.14 0.07 72 0.07 0.19 73 0.12 74 0.23 7

0.16 9

0.24 10 0.09 0.52 11 0.57 13 0.07 14 0.12 15 0.23 21 0.11 27 0.09 28 0.10 35 0.07 37 0.10 39 0.08 40 0.24 41 0.06 0.12 45 0.07 46 0.07 52 0.40 53 0.08 54 0.10 0.07 0.06 55 0.16 0.16 56 0.10 0.13 58 0.06 0.02 59 0.10 60 0.08 63 0.12 0.26 0.07 65 0.10 66 0.11 67 0.14 68 0.12 69 0.22 70 0.16 71 0.12 72 0.05.

74 0.17 0.10 1

0.14 0.12 9

0.29 11 0.08 0.25 0.07 0.20 15 0.0.

0.28 16 0.15 21 0.07 34 0.09 36 0.09 40 0.10 42 0.12 0.05 45 0.04 47 0.11 48 0.11 DEG 166 142 151 58 145 153 75 139 156 148 153 154 129 141 150 139 133 130 138 137 130 148 121 137 151 152 115 156 148 146 138 145 145 143 159 138 150 152 153 149 143 149 158 152 149 172 148 154 147 140 152 137 154 137 156 135 149 138 159 152 151 144 124 138 143 138 135 137 148 125 148 153 153 140 148 141 123 160 150 152 CHN IND %TW LOCATION P2 TWD 5 010

-(

P2 TWD 9 014

+(

P2 TWD 12 010

-(

P2 TWD 8 010

+1 P2 TWD 22 010

-(

P2 TWD 4 009 P2 TWD 11 010

+

P2 TWD 12 010 P2 TWD 6 010

-I P2 TWD 5 009 P2 TWD 13 010 P2 TWD 6 009 P2 TWD 6 009 P2 TWD 14 010 P2 TWD 11 010 P2 TWD 16 010 P2 TWD 12 011

+

P2 TWD 18 011

+

P2 TWD 8 010

+

P2 TWD 31 011

+

P2 TWD'32 011

+

P2 TWD 6 009 P2 TWO 10 010

+

P2 TWD 17 010

+

P2 TWD 9 014 P2 TWD 8 008 P2 TWD 9 010

+

P2 TWD 6 009 P2 TWD 8 009 P2 TWO 7 009 P2 TWD 17 014 P2 TWD 6 009 P2 TWD 12 013 P2 TWD 6 008 P2 TWO 7 009 P2 TWD 28 009 P2 TWD 7 009 P2 TWD 10 009 P2 TWD 7 014 P2 TWD 6 014

+

P2 TWD 12 009 P2 TWD 12 014 P2 TWD 10 009 P2 TWD 12 014 P2 TWD 6 009 P2 TWO 2 010 P2 TWD 8 010 P2 TWD 8 009 P2 TWD 9 013 P2 TWD 19 014 P2 TWD 6 014

+

P2 TWD 8 010 P2 TWD 11 010 P2 TWD 11 010 P2 TWD 12 010 P2 TWD 16 010 P2 TWO 14 010 P2 TWD 10 010 P2 TWD 5 010 P2 TWD 14 011 P2 TWD 9 011

+

P2 TWD 10 011

+

P2 TWD 9 011 P2 TWD 21 011

+

P2 TWD 7 011 P2 TWD 19 011 4

P2 TWD 6 012 P2 TWD 16 012

+

P2 TWO 6 009 P2 TWD 20 010

+

P2 TWD 12 010 P2 TWD 6 008 P2 TWD 8 008 P2 TWD 8 013 P2 TWD 8 009 P2 TWD 10 009 P2 TWD 5 008 P2 TWD 5 009 P2 TWD 11 009 P2 TWD 9 009 0.39 0.26 0.42 0.65 0.39 0.47 0.68 0.39 0.39 0.52 0.39 0.42 0.44 0.37 0.34 0.37 0.26 0.32 0.62 0.29 0.29 0.42 0.60 0.60 0.52 0.47 0.59 0.52 0.52 0.52 0.57 0.52 0.55 0.44 0.52 0.49 0.49 0.52 0.50 0.26 0.49 0.50 0.47 0.52 0.49 0.36 0.39 0.49 0.45 0.47 0.26 0.37 0.36 0.36 0.36 0.36 0.37

-0.37 0.37 0.31 0.39 0.31 0.33 0.32 0.39 0.29

-0.42 0.34 0.44 0.57

-0.60 0.47 0.49

-0.57

-0.51

-052 0.29

-0.52 0.49

-0.52 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE DTE LTE LTE DTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE DTE LTE UTE LTE LTE DTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

84 5

86 84 84 84 84 4

84 86 84 84 80 80 82 82 80 3

82 26 110 108 108 110 110 108 110 3

102 102 100 102 102 102 100 84 84 86 5

84 84 86 84 84 84 86 0

86 84 84 84 84 2

86 84 86 86 86 86 84 86 84 86 80 82 0

80 80 80 26 26 110 110 110 110 110 110 7

110 108 110 100 100 100 86 86 4

84 84 3

86 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUILET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE S1OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:13 Am Component: S/G B Page 68 of 74 ONSlBR-EOC24 -

Tube QUERY: QueryMl[21 Support Wear ROW TUBE VOLTS 0.07 139 49 0.20 0.11 139 50 0.06 0.14 0.40 0.07 0.16 139 51 0.43 0.12 139 52 0.07 0.25 139 S3 0.06 139 55 0.07 139 56 0.11 139 58 0.08 139 60 0.08 0.09 139 62 0.28 139 64 0.12 0.07 0.10 139 65 0.09 139 66 0.18 139 67 0.06 139 68 0.13 139 69 0.11 139 71 0.06 139 72 0.12.

140 5 0.09 140 8 0.43 140 14 0.10 140 15 0.18 0.09 140 16 0.12 140 18 0.07 0.06 140 19 0.26 140 26 0.09 140 28 0.09 0.08 140 32 0.11 140 34 0.09 140 39 0.09 140 41 0.09 140 43 0.18 140 44 0.17 140 45 0.24 140 46 0.20 0.08 140 47 0.15 0.09 140 48 0.17 0.17 140 49 0.47 0.12 0.21 140 50 0.09 0.37 0.05 0.13 140,51 0.10 0.54 0.10 0.30 140 52 0.05

  • 140 53 0.11 140 55 0.04 140 58 0.04 0.13 140 59 0.09 140 60 0.14 0.03 140 61 0.17 140 62 0.07 140 63 0.11 140 64 0.05 140 66 0.04 140 68 0.05 141 12 0.09 DEG 142 149 71 139 139 134 42 143 142 141 142 139 156 159 145 152 147 124 147 141 126 148 149 132 162 139 146 159 142 147 134 146 143 150 121 145 154 136 148 148 150 130 151 154 157 133 152 143 151 153 146 147 155 156 134 143 143 155 145 154 141 151 133 153 139 160 144 161 151 139 137 149 156 144 157 140 136 163 148 60 CHN IND P2 TWO P2 TWD P2 TWD P2 TWD P2 TWO P2 TWO P2 TWD P2 TWD P2 TWO P2 TWD P2 TWO P2 TWO P2 TWO P2 TWO P2 TWD P2 TWD P2 TWD P2 TWO P2 TWO P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWO P2 TWO P2 TWO P2 TWO P2 TWO P2 TWD P2 TWD P2 TWO P2 TWO P2 TWO P2 TWO P2 TWD P2 TWD P2 TWD P2 TWO P2 TWO P2 TWO P2 TWO P2 TWD P2 TWD P2 TWO P2 TWO P2 TWO P2 TWD P2 TWD P2 TWO P2 TWO P2 TWO P2 TWO P2 TWO P2 TWO P2 TWO P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWO P2 TWO P2 TWO P2 TWD P2 TWD P2 TWO P2 TWO P2 TWD P2 TWD P2 TWD P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWO P2 TWD P2 TWD P2 TWO

%TW LOCATION 6

010

-0.44 17 009

-0.49 10 010

+0.68 5

008

+0.21 11 009

-0.47 25 010

-0.42 6

010

+0.63 12 013

-0.50 30 009

-0.49 12 010

+0.57 6

008

+0.26 18 009

-0.49 6

009

-0.49 7

009

-0.49 9

009

-0.47 7

008

-0.47 7

014

-0.47 8

014

+0.29 19 014

-0.44 10 010

-0.37 6

009

+0.63 8

011

+0.34 9

010

-0.36 14 010

-0.34 6

010

-0.34 10 010

-0.37 10 010

-0.34 6

010

-0.34 10 010

-0.34 7

011

+0.26 27 011

+0.31 9

009

-0.44 15 009

-0.42 8

010

+0.63 10 010

+0.60 6

008

-0.44 5

014

+0.24 19 010

+0.60 8

009 0.49 7

008

-0.46 7

009

-0.49 9

010

+0.56 8

009

-0.54 9

009

-0.52 7

009

-0.52 14 009

-0.49 15 009

-0.52 17 009

-0.47 18 009

-0.49 8

013

-0.53 12 010

-0.50 8

010

+0.60 16 009

-0.44 16 010

-0.49 27 009

-0.44 10 010

+0.63 16 010

-0.50 9

009

-0.47 27 010

-0.49 5

008

+0.29 12 010

+0.62 8

008

-0.44 30 009

-0.47 8

009

+0.63 20 010

-0.50 5

008

-0.44 9

009

-0.47 4

008

-0.44 5

009

-0.47 12 009

+0.63 7

009

-0.47 13 010

-0.36 3

009

-0.52 13 010

-0.39 7

010

-0.36 9

010

-0.34 6

010

-0.34 4

010

-0.34 5

010

-0.37 8

010

+0.63 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

3 86 84 0

84 86 86 86 3

86 3

86 84 5

84 86 86 84 84 86 86 86 86 86 86 86 4

86 84 86 84 86 80 80 82 26 108 108 110 110 6

108 108 108 110 100 100 100 100 100 84 86 86 84 86 84 84 2

86 5

86 84 2

84 86 86 4

86 84 84 84 9

84 86 86 6

86 3

86 84 86 86 84 84 86 84 84 86 84 86 84 84 80 110 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:14 AM Component: S/G B Page 69 of 74 ONSlBR-EOC24 Tube Support Wear QUERY:

QueryMI[2]

ROW TUBE VOLTS 141 14 0.11 0.12 141 15 0.05 0.15 141 16 0.11 141 17 0.13 141 18 0.18 0.17 141 19 0.11 141 21 0.07 141 22 0.11 141 24 0.12 141 25 0.10 141 26 0.08 0.09 141 27 0.09 141 29 0.07 0.06 141 31 0.13 141 32 0.10 141 33 0.07 141 34 0.10 0.08 141 36 0.12 141 37 0.11 141 38 0.09 141 39 0.06 0.09 141 41 0.05 141 42 0.10 0.13 0.09 141 43 0.10 0.29 0.17 141 44 0.18 0.14 141 45 0.16 0.46 141 46 0.07 1.11 141 47 0.11 0.85 141 48 0.25 0.59 141 49 0.11 0.68 0.06 0.17 141 50 0.71 141 51 0.54 141 53 0.35 0.15 0.08 141 55 0.11 0.11 141 56 0.11 0.46 141 57 0.13 141 58 0.11 141 59 0.13 141 60 0.08 141 61 0.12 142 4 0.08 142 5 0.11 142 16 0.18 142 17 0.11 0.35 0.11 142 23 0.07 0.06 0.12

.142 24 0.07 142 25 0.10 142 29 0.12 142 30 0.11 142 31 0.10 0.06 142 32 0.12 142 33 0.10 DEG CHN 143 P2 135 P2 158 P2 149 P2 150 P2 144 P2 145 P2 134 P2 137 P2 154 P2 150 P2 152 P2 144 P2 151 P2 149 P2 149 P2 150 P2 49 P2 146 P2 155 P2 146 P2 152 P2 152 P2 145 P2 146 P2 150 P2 160 P2

.151 P2 143 P2 151 P2 154 P2 161 P2 136 P2 139 P2 139 P2 142 P2 152 P2 149 P2 133 P2 151 P2 130 P2 151 P2 128 P2 148 P2 140 P2 146 P2 132 P2 152 P2 144 P2 135 P2 128 P2 139 P2 128 P2 139 P2 146 P2 143 P2 150 P2 143 P2 143 P2 155 P2 138 P2 157 P2 125 P2 59 P2 78 P2 131 P2 148 P2 143 P2 148 P2 153 P2 155 P2 134 P2 153 P2 152 P2 149 P2 153 P2 148 P2 152 P2 145 P2 153 P2 IND TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 9

10 5

12 9

11 15 14 10 6

9 10 8

7 8

7 6

6 11 8

6 8

7 10 9

8 5

8 5

9 12 9

9 21 13 15 12 13 28 6

46 9

39 20 34 10 35 6

14 37 31 23 12 7

9 9

10 29 11 10 11 8

10 8

9 14 10 24 9

6 5

10 6

8 10 9

9 6

10 8

LOCATION 009

-0.44 010

+0.63 009

-0.49 010

+0.60 009

-0.52 009

-0.44 010

+0.60 014

-0.52 010 t0.54 008

-0.49 008

-0.47 008

-0.47 010

+0.62 009

-0.50 008

-0.47 008

-0.49 010

-0.44 010

+0.59 014

-0.54 009

-0.52 009

-0.52 009

-0.52 013

-0.55 009

-0.49 009

-0.52 008

-0.47 008

-0.47 009

-0.52 008

+0.29 008

+0.26 009

-0.55 010

-0.42 008

+0.26 009

-0;52 014

+0.26 009

-0.54 010

-0.42 009

-0.47 010

-0.42 009

-0.47 010

-0.44 009

-0.47 010

-0.42 009

-0.47 010

-0.44 009

-0.47 010

-0.42 011

+0.26 013

-0.47 010

-0.44 010

-0.39 010

-0.36 010

+0.65 009

-0.47 009

-0.47 010

-0.39 009

-0.49 010

-0.39 010

-0.39 010

-0.39 010

-0.36 010

-0.39 010

-0.36 010

+0.63 010

+0.63 010

+0.63 009

-0.47 014

-0.47.

009

+0.57 008

-0.47 009

-0.47 010

+0.62 008

-0.44 008

-0.44 008

-0.44 014

-0.52 008

-0.46 009

-0.49 008

-0.47 008

-0.46 EXT EXT UTIL 1

LTE OTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR.

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR UTIL 2

CAL # LEG 110 INLET 110 INLET 108 INLET 108 INLET 4

110 INLET 108 INLET 110 INLET 110 INLET 108 INLET 100 INLET 3

102 INLET 4

102 INLET 100 INLET 102 INLET 3

102 INLET 100 INLET 100 INLET 100 INLET 4

100 INLET 102 INLET 100 INLET 102 INLET 102 INLET 102 INLET 100 INLET 88 INLET 0

90 INLET 5

90 INLET 90 INLET 88 INLET 88 INLET 88 INLET 90 INLET 90 INLET 4

90 INLET 88 INLET 88 INLET 90 INLET 90 INLET 88 INLET LAR 88 INLET 90 INLET 90 INLET 88 INLET 88 INLET 90 INLET 90 INLET 90 INLET 90 INLET 88 INLET 90 INLET 90 INLET 90 INLET 3

90 INLET 90 INLET 90 INLET 88 INLET 88 INLET 90 INLET 88 INLET 90 INLET 88 INLET 90 INLET 110 INLET 108 INLET 110 INLET 108 INLET 108 INLET 7

108 INLET 100 INLET 100

-INLET 100 INLET 102 INLET 100 INLET 100 INLET 4

102 INLET 100 INLET 100 INLET 102 INLET 100 INLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 51OXE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB S1OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSi Repi 4/22/2008 9:48:14 AM Component: S/G B Page 70 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: Query~l[2]

ROW TUBE VOLTS 0.09 142 34 0.09 142 35 0.09 142 38 0.05 142 39 0.10 142 40 0.17 0.13 0.05 0.09 142 41 0.14 0.18 0.08 0.15 0.21 0.14 0.19 142 42 0.12 0.08 142 43 0.23 142 44 0.78 142 46 0.75 142 47 0.81 142 48 0.33 142 49 0.08 0.19 142 50 0.07 0.29 142 51 0.09 142 52 0.13 0.07 142 53 0.06 0.08 142 55 0.07 142 57 0.10 142"58 0.25 142 59 0.10 143 16 0.13 0.36 143 17 0.13 0.08 143 19 0.10 0.09 143 21 0.18 0.07 143 22 0.11 0.08 0.14 143 23 0.16 143 24 0.17 143 25 0.10 143 27 0.06 0.13 143 28 0.12 143 29 0.09 143 31 0.11 143 32 0.21 0.09 143 33 0.13 143 34 0.14 0.15 143 35 0.11 143 36 0.09 143 37 0.07 143 38 0.06 0.07 143 39 0.07 0.57 143 40 0.12 0.68 0.09 0.09 143 41 0.13 0.31 143 42 0.29 143 43 0.32 143 44 0.92 143 45 0.11 143 46 0.18 143 47 0.10 143 48 0.34 DEG CHN 151 P2 152 P2 153 P2 159 P2 152 P2 147 P2 144 P2 148 P2 142 P2 155 P2 151 P2 152 P2 151 P2 147 P2 158 P2 151 P2 157 P2 136 P2 154 P2 129 P2 135 P2 131 P2 136 P2 152 P2 151 P2 153 P2 141 P2 160 P2 142 P2 152 P2 158 P2 150 P2 154 P2 145 P2 137 P2 51 P2 148 P2 136 P2 134 P2 137 P2 152 P2 144 P2 136 P2 118 P2 149 P2 130 P2 148 P2 140 P2 148 P2 149 P2 146 P2 128 P2 147 P2 149 P2 146 P2 143 P2 149 P2 149 P2 149 P2 151 P2 153 P2 139 P2 153 P2 155 P2 146 P2 155 P2 137 P2 143 P2 130 P2 142 P2 142 P2 152 P2 144 P2 138 P2 142 P2 128 P2 151 P2 135 P2 157 P2 135 P2 IND %TW TWD 8 TWO 7 TWO 8 TWO 5 TWD 9 TWD 14 TWO 11 TWO 5 TWO 8 TWD 12 TWD 15 TWD 8 TWD 13 TWO 17 TWD 12 TWD 16 TWD 10 TWO 7 TWO 18 TWO 37 TWD 39 TWD 40 TWO 22 TWO 7 TWO 16 TWO 6 TWO 20 TWD 8 TWO 11 TWO 6 TWD 6 TWD 8 TWO 7 TWO 9 TWO 18 TWO 10 TWD 11 TWO 24 TWO 11 TWO 8 TWO 9 TWO 8 TWO 13 TWO 6 TWO 9 TWO 7 TWO 11 TWO 13 TWD 13 TWD 9 TWO 5 TWb 10 TWO 9 TWO 8 TWO 9 TWO 15 TWD 8 TWD 10 TWO 12 TWD 12 TWO 10 TWD 8 TWD 7 TWD 6 TWD 6 TWO 6 TWO 34 TWD 10 TWD 35 TWO 8 TWO 8 TWD 12 TWD 23 TWD 20 TWD 24 TWO 40 TWO 10 TWD 14 TWO 9 TWO 23 LOCATION 009

-0.52 008

-0.47 008

-0.44 010

-0.50 009

-0.52 009

-0.52 013

-0.53 008

-0.47 008

+0.29 008

-0.44 009

-0.55 011

-0.42 012

-0.47 012

+0.32 014

-0.47 014

+0.29 010

-0.47 013

+0.24 010

-0.49 010

-0.47 010

-0.49 010

-0.52 010

-0.47 009

-0.47 010

-0.47 009

-0.44 010

-0.47 010

-0.49 009

+0.63 010

-0.42 009

-0.49 010

-0.47 010

-0.47 010

-0.39 010

-0.34 010

+0.62 009

-0.49 010

+0.60 008

+0.29 009

-0.47 008

-0.44 009

-0.47 010

+0.56 008

+0.20 008

-0.47 008

+0.26 009

-0.49 008

-0.44 008

-0.47 008

-0.46 008

-0.46 010

+0.62 010

+0.60 009

-0.49 013

-0.55 008

-0.44 009

-0.52 013

-0.52 009

-0.49 013

-0.52 008

-0.47 008

-0.44 008

-0.42 009

-0.47 008

-0.44 008

+0.26 009

-0.55 009

-0.44 010

-0.39 013

+0.26 008

+0.26 009

-0.49 010

-0.42 010

-0.36 010

-0.42 010

-0.37 010

-0.39 010

-0.34 010

-0.42 010

-0.37 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE'UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL 1

WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

100 4

102 100 4

90 88 90 90 4

90 3

90 88 88 88 88 88 88 88 4

90 4

90 88 90 88 LAR 88 90 88 88 90 90 88 90 5

90 88 6

88 88 88 90 4

88 108 108 110 110 110 110 26 26 162 102 102 100 102 100 100 5

100 102 100 100 102 102 100 100 100 88 90 88 90 3

90 88 88 90 90 90 4

90 88.

88 90 88 LAR 90 88 90 88 90 LEG PROBE INLET 510XB INLET 510XB INLET S1OXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB.

INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XBý INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB OUTLET 510XB OUTLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 51OXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:15 AM Component:

S/G B Page 71 of 74 ONSlBR-EOC24 -

Tube Support Wear QUERY: QueryMl[2]

ROW TUBE 143 49 143 50 143 51 143 52 143 53 143 54 143 55 143 56 143 59 143 62 144 4 144 6 144 15 144 16 144 18 144 19 144 20 144 21 144 22 144 23 144 25 144 27 144 28 144 29 144 30 144 31 144 32 144 33 144 35 144 36 144 37 144 39 144 40 144 41 144 42 144 43 144 44 144 45 144 46 144 47 144 55 145 2 145 11 145 14 145 15 145 16 145 17 145 18 145 20 145 21 145 22 145 23 145 24 VOLTS 0.23 0.21 0.12 0.07 0.06 0.18 0.07 0.07 0.18 0.08 0.09 0.24 0.25 0.24 0.25 0.22 0.12 0.07 0.14 0.12 0.28 0.13 0.09 0.13 0.08 0.08 0.15 0.10 0.08 0.10 0.10 0.17 0.15 0.09 0.14 0.10 0.09 0.25 0.09 0.24 0.09 0.09 0.12 0.17 0.36 0.17 0.22 0.13 0.37 0.09 0.53 0.21 0.24 0.06 0.05 0.06 0.10 0.10 0.07 0.09 0.12 0.09 0.12 0.11 0.08 0.11 0.10 0.16 0.10 0.12 0.17 0.09 0.15 0.10 0.09 0.10 0.19 0.11 0.11 0.11 DEG CHN 149 P2 142 P2 146 P2 125 P2 153 P2 135 P2 148 P2 134 P2 147 P2 140 P2 72 P2 136 P2 140 P2 136 P2 139 P2 144 P2 143 P2 152 P2 142 P2 150 P2 142 P2 136 P2 152 P2 147 P2 155, P2 156 P2 148 P2 152 P2 41 P2 155 P2 143 P2 140 P2 146 P2 149 P2 92 P2 146 P2 151 P2 143 P2 159 P2 153 P2 156 P2 151 P2 157 P2 153 P2 139 P2 145 P2 146 P2 147 P2 146 P2 155 P2 133 P2 148 P2 138 P2 154 P2 155 P2 160 P2 148 P2 147 P2 144 P2 62 P2 127 P2 149 P2 114 P2 142 P2 135 P2 139 P2 159 P2 148 P2 149 P2 60 P2 141 P2 155 P2 145 P2 58 P2 142 P2 148 P2 136 P2 144 P2 142 P2 58 P2 IND %TW TWD 19 TWD 16 TWO 11 TWD 6 TWD 6 TWD 14 TWD 7 TWO 7 TWD 15 TWD 7 TWD 8 TWD 18 TWD 18 TWD 18 TWD 19 TWD 16 TWD 10 TWD 6 TWD 11 TWD 10 TWD 20 TWD 11 TWD 8 TWD 10 TWD 7 TWD 7 TWD 12 TWD 8 TWD 7 TWD 8 TWD 8 TWD 13 TWD 12 TWD 8 TWD 11 TWO 8 TWD 8 TWD 18 TWD 9 TWD 19 TWD 8 TWD 8 TWD 11 TWD 14 TWD 24 TWD 13 TWD 16 TWD 11 TWD 26 TWD 9 TWD 30 TWD 17 TWD 18 TWD 6 TWD 5 TWD 6 TWD 9 TWD 9 TWD 6 TWD 8 TWD 10 TWD 8 TWD 10 TWD 10 TWD 7 TWD 9 TWD 9 TWO 12 TWO 8 TWD 10 TWD 13 TWD 8 TWD 11 TWD 8 TWD 8 TWD 8 TWD 14 TWD 9 TWD 9 TWD 9 LOCATION 010

-0.39 010

-0.37 010

-0.39 010

-0.37 010

-0.39 010

-0.36 010

-0.39 010

-0.34 011

-0.34 011

+0.39 010

+0.65 011

+0.34 009

-0.42 010

+0.60 009

-0.44 009

-0.44 010

+0.63 010

-0.47 009

-0.49 008

-0.44 009

-0.49 009

+0.62 012

-0.50 010

+0.65 010

-0.47 009

-0.46 010

-0.44 009

-0.49 010

+0.64 008

-0.44 010

+0.62 009

-0.49 010

+0.65 009

-0.49 010

+0.64 009

+0.60 008

-0.44 009

-0.49 009

-0.52 010

-.0.50 009

-0.50 013

-0.47 008

-0.44 013

-0.47 009

-0.44 009

+0.63 010

-0.47 011

+0.34 010

-0.49 010

-0.44 010

-0.47 010

-0.47 010

-0.44 010

-0.44 010

-0.44 010

-0.47 010

-0.42 011

+0.42 012

+0.39 010

+0.65 011

+0.31 009

-0.47 010

+0.65 009

-0.50 010

-0.37 010

+0.65 009

-0.47 010

+0.63 009

-0.46 010

+0.62 010

+0.59 009

-0.47 010

-0.39 010

+0.65 010

-0.36 009

-0.47 010

+0.65 009

-0.49 010

-0.36 010

+0.65 EXT EXT LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE. UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTIL WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR 1

UTIL 2

CAL #

88 90 88 90 88 90 88 90 88 90 110 110 108 108 110 102 102 100 102 100 100 100 100 102 4

102 100 100 100 100 100 6

100 102 102 100 4

100 102 100 100 88 88 90 90 88 88 90 90 90 90 88 88 90 88 90 88 5

90 88 90 4

90 3

90 108 4

110 3

108 108 110 110 108 4

108 102 100 7

100 100 102 102 100 3

100 102 102 100 100 100 LEG PROBE INLET 51OXB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB INLET 510XB LTE UTE WAR

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:15 AM Component:

S/G B Page 72 of 74 ONSlBR-EOC24 - Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS 145 27 0.11 0.17 145 28 0.22 0.33 0.22 0.26 0.22 0.12 0.13 0.12 145 29 0.41 0.17 0.06 145 30 0.07 0.36 0.09 0.15 145 31 0.20 0.05 145 32 0.14 0.11 0.08 145 33 0.10 0.09 145 34 0.25 0.08 145 35 0.22 0.06 145 36 0.44 0.07 145 37 0.26 145 39 0.13 145 41 0.10 145 42 0.13 145 43 0.12 145 44 0.10 145 45 0.13 145 46 0.23 145 48 0.12 0.07 145 50 0.06 146 13 0.07 0.10 146 15 0.05 0.21 146 16 0.09 0.16 146 17 0.13 146 18 0.19 0.13 146 19 0.08 146 20 0.17 146 21 0.24 146 22 0.13 0.14 0.09 146 23 0.17 0.09 146 24 0.13 0.21 0.07 0.11 146 25 0.19 146 26 0.08 0.22 146 28 0.14 0.29 0.13 0.06 146 29 0.08 146 30 0.12 0.16 146 31 0.07 0.15 146 32 0.07 146 33 0.14 0.74 146 34 0.31 146 35 0.25 146 37 0.10 DEG CHN 152 P2 145 P2 144 P2 140 P2 130 P2 146 P2 146 P2 144 P2 146 P2 139 P2 142 P2 143 P2 132 P2 143 P2 139 P2 148 P2 115 P2 146 P2 165 P2 143 P2 147 P2 153 P2 150 P2 148 P2 135 P2 151 P2 143 P2 159 P2 133 P2 156 P2 147 P2 156 P2 157 P2 146 P2 151 P2 141 P2 149 P2 136 P2 65 P2 127 P2 148 P2 128 P2 144 P2 156 P2 141 P2 149 P2 136 P2 141 P2 145 P2 112 P2 143 P2 140 P2 145 P2 145 P2 136 P2 55 P2 143 P2 144 P2 145 P2 143 P2 154 P2 78 P2 145 P2 152 P2 141 P2 140 P2 141 P2 124 P2 146 P2 157 P2 156 P2 148 P2 153 P2 136 P2 158 P2 150 P2 129 P2 146 P2 138 P2 143 P2 IND TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD TWO TWD TWD TWD TWD TWD TWD TWD TWD TWD TWD

%TW 9

13 16 22 16 19 16 10 11 10 25 13 5

6 24 7

12 16 5

12 10 7

9 9

18 7

18 6

27 6

20 12 9

11 11 9

12 17 10 6

6 7

9 5

16 8

13 10 15 10 7

13 17 11 11 8

13 8

11 16 6

9 14 7

16 11 21 10 6

8 11 13 7

12 6

11 36 23 18 9

LOCATION 009

-0.44 010

+0.65 009

-0.49 010

-0.42 010

+0.62 011

+0.31 012

-0.47 012

+0.34 013

+0.29 009

+0.62 010

-0.39 010

+0.62 011

+0.29 006

+0.34 009

-0.49 009

+0.65 010

+0.57 009

-0.52 008

-0.44 009

-0.47 012

+0.34 013

+0.26 008

+0.29 010

-0.39 010

-0.39 008

+0.29 010

-0.39 011

+0.31 010

-0.37 011

+0.34 010

-0.39 010

-0.39 010

-0.39 010

-0.36 010

-0.36 010

-0.34 010

-0.39 010

-0.34

.010

+0.68 010

-0.42 010

-0.34 010

-0.36 012

-0.44 009

-0.49 010

+0.62 009

-0.47 010

+0.62 010

+0.65 010

-0.39 010

+0.62 010

-0.36 010

-0.36 010

-0.37 010

-0.36 009

+0.65 010

+0.64 009

+0.60 010

-0.34 009

-0.46 010

-0.39 009

+0.70 010

+0.62 010

-0.39 009

-0.52 010

-0.36 009

-0.52 010

-0.36 010

+0.62 011

+0.34 010

-0.39 009

-0.52 010

+0.65 009

-0.44 010

-0.37 011

-0.44 009

-0.55 010

-0.37 010

-0.36 010

-0.34 010

-0.37 EXT EXT UTIL 1

UTIL 2

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 7

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 6

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 4

LTE UTE WAR 6

LTE UTE WAR 2

LTE UTE WAR LTE UTE WAR 3

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 3

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 8

LTE UTE WAR 7

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR 6

LTE UTE WAR 7

LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR LTE UTE WAR CAL # LEG 102 INLET 102 INLET 100 INLET 100 INLET 100 INLET 100 INLET 100 INLET 100 INLET 100 INLET 100 INLET 102 INLET 102 INLET 102 INLET 100 INLET 100 INLET 100 INLET 100 INLET 88 INLET 88 INLET 90 INLET 90 INLET 90 INLET 88 INLET 88 INLET 90 INLET 90 INLET 88 INLET 88 INLET 90 INLET 90 INLET 88 INLET 88 INLET 88 INLET 90 INLET 88 INLET 90 INLET 88 INLET 90 INLET 90 INLET 90 INLET 90 INLET 108 INLET 108 INLET 108 INLET 108 INLET 108 INLET 108 INLET 102 INLET 100 INLET 100 INLET 102 INLET 100 INLET 102 INLET 100 INLET 100 INLET 100 INLET 102 INLET 102 INLET 100 INLET 100 INLET 100 INLET 100 INLET 102 INLET 100 INLET 100 INLET 100 INLET 100 INLET 100 INLET 100 INLET 88 INLET 88 INLET 88 INLET 90 INLET 90 INLET 88 INLET 90 INLET 90 INLET 88 INLET 90 INLET 90 INLET PROBE 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: TNSI Repp 4/22/2008 9:48:16 AM Component: S/G B Page 73 of 74 ONSlBR-E0C24 -

Tube Support Wear QUERY: Query~l[2]

ROW TUBE VOLTS DEG CHN 146 38 0.03 153 P2 146 43 0.08 149 P2 146 44 0.36 144 P2 146 47 0.06 93 P2 147 6 0.07 77 P2 147 9 0.07 153 P2 147 14 0.12 143 P2 147 15 0.10 149 P2 0.10 141 P2 147 16 0.12 147 P2 147 17 0.18 141 P2 0.08 69 P2 147 18 0.10 139 P2 147 19 0.08 139 P2 0.10 61 P2 147 20 0.12 135 P2 0.10 154 P2 0.07 148 P2 147 21 0.08 150 P2 0.11 147 P2 0.13 119 P2 147 22 0.08 153 P2 147 23 0.11 143 P2 147 24 0.23 148 P2 0.20 140 P2 0.10 147 P2 147 25 0.11 61 P2 0.29 143 P2 147 26 0.38 140 P2 0.09 152 P2 0.11 60 P2 147 27 0.06 156 P2 147 28 0.11 156 P2 0.13 136 P2 147 29 0.07 152 P2 147 30 0.13 151 P2 0.04 163 P2 147 31 0.12 156 P2 147 32 0.16 141 P2 148 14 0.17 143 P2 148 16 0.10 141 P2 148 17 0.06 134 P2 148 19 0.10 142 P2 0.11 46 P2 148 21 0.10 139 P2 148 22 0.24 139 P2 148 23 0.18 141 P2 148 24 0.14 151 P2 0.05 164 P2 148 25 0.17 123 P2 148 26 0.12 147 P2 148 27 0.07 121 P2 148 29 0.08 136 P2 149 3 0.09 146 P2 149 7 0.10 141 P2 149 8 0.07 138 P2 149 9 0.11 147 P2 149 10 0.24 135 P2 149 11 0.17 142 P2 149 12 0.20 135 P2 149 16 0.12 43 P2 149 17 0.07 147 P2 149 18 0.14 145 P2 149 19 0.29 136 P2 149 20 0.19 112 P2 149 21 0.21 122 P2 149 24 0.19 94 P2 149 25 0.07 157 P2 149 26 0.10 61 P2 149 33 0.11 157 P2 150 7 0.12 145 P2 150 9 0.11 64 P2 150 11 0.13 131 P2 150 12 0.16 128 P2 150 15 0.28 140 P2 150 16 0.21 138 P2 150 19 0.08 119 P2 150 21 0.27

.128 P2 151 8 0.20 141 P2 IND %TW LOCATION EXT EXT UTIL 1

TWD 3 TWD 8 TWO 25 TWO 6 TWO 6 TWO 6 TWD 10 TWD 9 TWD 9 TWD 10 TWD 14 TWD 7 TWD 8 TWD 7 TWD' 9 TWD 10 TWD 8 TWD 6 TWD 7 TWD 9 TWD 11 TWD 7 TWD 10 TWD 16 TWD 15 TWD 8 TWD 9 TWD 20 TWD 25 TWD 8 TWD 9 TWD 6 TWD 10 TWD 11 TWD 7 TWD 11 TWO 3 TWO 11 TWD 13 TWD 14 TWD 8 TWO 6 TWD 9 TWO 9 TWO 8 TWO 17 TWD 14 TWD 13 TWD 5 TWD 13 TWD 11 TWD 6 TWD 7 TWD 7 TWD 8 TWD 6 TWD 9 TWD 17 TWD 13 TWD 14 TWD 10 TWD 6 TWD 11 TWD 20 TWD 15 TWD 17 TWD 15 TWD 7 TWD 8 TWD 10 TWD 9 TWD 8 TWD 10 TWD 12 TWD 19 TWD 16 TWD 7 TWD 19 TWD 14 010 010 010 010 010 010 010 009 010 010 010 010 010 010 010 010 014 014 009 010 010 010 010 010 010 Ol 010 010 010 Ol 010 009 009 OilO 011 009 010 008 010 010 010 010 010 010 010 010 010 010 010 009 010 009 010 010 008

.010 010 010 010 010 010 010 010 010 010 010 010 010 010 010 010 010 010 010 010 010 010 010 010 002

-0.42

-0.36

-0.39

-0.34

+0.65

-0.36

-0.36

-0.47

-0.34

-0.37

-0.36

+0.62

-0.37

-0.36

+0.62

-0.37

-0.44

+0.29

-0.49

-0.36

+0.65

-0.36

-0.36

-0.36

+0.65

+0.31

+0.62

-0.36

-0.36

+0.31

+0.65

-0.49

+0.

63

-0.39

-0.49

-0.37

-0.42

-0.36

-0.37

-0.36

-0.36

+0.41

-0.36

+0.64

-0.36

-0.34

-0.36

-0.36

-0.49

-0.39

-0.47

-0.34.

-0.34

-0.43

-0.41

-0.43

-0.41

-0.41

-0.41

-0.38

+0.67

-0.31

-0.36

-0.36

+0.67

+0.65

+0.68

-0.36

+0. 65

-0.36

-0.38

+0.56

-0.

38

-0.41

-0.34

-0.34

-0.37

-0.34

-0.33 LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE UTE LTE UTE LTE UTE LTE LTE UTE LTE UTE LTE UTE LTE UTE UTE LTE WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR UTIL 2

CAL #

88 88 88 90 110 108 110 108 108 102 100 6

100 3

102 100 2

100 102 102 102 100 100 100 4

102 100 102 102 102 4

100 100 100 100 6

100 88 90 2

90 88 90 90 88 90 108 102 100 100 4

100 3

100 102 100 88 88 90 88 3

90 90 26 26 2

26 26 26 26 26 100 102 100 102 100 9

88 90 88 90 88 26 26 4

26 26 102 100 90 90 26 LEG INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET INLET INLET INLET INLET INLET INLET OUTLET OUTLET OUTLET OUTLET INLET INLET INLET INLET OUTLET PROBE 510OXB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB.

510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB 510XB

AREVA NP Inc Customer Name: ONSI Repl 4/22/2008 9:48:16 AM Component: S/G B Page 74 of 74 ONSlBR-EOC24

- Tube Support Wear QUERY: QueryMl[2]

ROW TUBE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE Total Tubes

3991 Total Records: 5839