SOUTHERN CALIFORNIA A. Edward Scherer Director VNuclear Regulatory Affairs An EDISON INTERNATIONAL Company June 19, 2008 U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555
Subject:
Docket No. 50-361 Special Report: Inspection of Steam Generator Tubes, Cycle 15 San Onofre Nuclear Generating Station, Unit 2
Dear Sir or Madam:
San Onofre Nuclear Generating Station Unit 2 entered Mode 4 on January 12, 2008 following the completion of an inspection of steam generator tubes during the Cycle 15 Refueling Outage. Technical Specification (TS) 5.7.2.c states "A report shall be submitted within 180 days after the initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.5.2.11, Steam Generator (SG) Program."
Accordingly we have attached the required report. The report contains no new commitments.
If you require any additional information, please contact Clay Williams at (949) 368-6707.
Sincerely, Attachment cc:
E. E. Collins, NRC Regional Administrator, Region IV A (- /
N. Kalyanam, NRC Project Manager, San Onofre Units 2, and 3 G. G. Warnick, NRC Senior Resident Inspector, San Onofre Units 2 & 3 P.O. Box 128 San Clemente, CA 92674
Inspection of Steam Generator Tubes Attachment Special Report Page 1 of 13 SPECIAL REPORT - INSPECTION OF STEAM GENERATOR TUBES Regulatory Reporting Requirements Reporting Requirement 5.7.2.c of Appendix A, Technical Specification to Facility Operating License NPF-10 requires a report of steam generator tube inspections to be submitted to the Nuclear Regulatory Commission within 180 days after the initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.5.2.11, Steam Generator (SG) Program.
The report shall include:
1. The scope of inspections performed on each SG,
- 2. Active degradation mechanisms found,
- 3. Nondestructive examination techniques utilized for each degradation mechanism,
- 4. Location, orientation (if linear), and measured sizes (if available) of service induced indications,
- 5. Number of tubes plugged or repaired during the inspection outage for each active degradation mechanism,
- 6. Total number and percentage of tubes plugged or repaired to date,
- 7. The results of condition monitoring, including the results of tube pulls and in-situ testing,
- 8. The effective plugging percentage for all plugging and tube repairs in each SG, and
- 9. Repair method utilized and the number of tubes repaired by each repair method.
Inspection Scope Table 1 summarizes the scope of inspections performed on each SG. Also, when indications by the bobbin probe were non-quantifiable or distorted, the inspection scope included inspection with the Plus Point Probe. There were no significant inspection scope expansions in response to inspection results.
Inspection of Steam Generator Tubes Special Report Attachment Page 2 of 13 TABLE I - Scope of Inspections Performed: Unit 2 Cycle 15 (U2C15) Refueling Outage Inspection Scope SG E-088 Tubes/Percent SG E-089 Tubes/Percent Full length of tube with the bobbin probe (excluding sleeved regions, tube section below sleeves and U-8093/100%
8224/100%
bends for Rows 1-3)
Hot leg expansion transition of unsleeved tubes at the top-of-tubesheet with the Plus Point Probe to an extent 7934/100%
8127/100%
of 4 inches above to 13 inches below the top-of-tubesheet Cold leg expansion transition at the top-of-tubesheet with the Plus Point Probe to an extent of 2 inches 8093/100%
8224/100%
above to 13 inches below the top-of-tubesheet U-bend regions of Rows 1, 2, and 3 with both mid-179/100%
171/100%
frequency and high-frequency Plus Point Probes U-bend regions of Rows 4 through 10 with the mid-90/22%
90/21%
frequency Plus Point Probe (Note 1)
Plus Point Probe examination of tube support intersections with dents greater than, or equal to, 2 2476/100%
1679/100%
volts Plus Point Probe examination of dings greater than, or 404/100%
309/100%
equal to, 4 volts Plus Point Probe examination of all tube support intersections with quantified wear indications by the 311/100%
387/100%
bobbin probe Full length of sleeves with the Plus Point Probe 159/100%
97/100%
Table 1 Note 1: No indications in a 100% inspection performed in 2004.
Inspection of Steam Generator Tubes Special Report Attachment Page 3 of 13 Results of the Inspection of Tubes Table 2 summarizes the degradation found and number of tubes plugged. Each tube is only counted once in this listing, although it may also have an eddy current indication of a type below the point in the listing where it appears. The Appendices provide detail.
No degradation was found in:
" the cold leg tubesheet region tubing bends dings in tubing freespan A robotic visual inspection of the untubed regions of the top of the tubesheet (i.e., tube bundle periphery and central blowdown lane) was performed on the secondary side of both Steam Generators.
One previously unretrievable analyzed object was again observed and re-verified unretrievable in the hot leg periphery of Steam Generator 88. Two previously unretrievable analyzed objects were again observed and re-verified unretrievable in the cold leg periphery and in the stay cavity region of Steam Generator 89. All three of these objects have an analysis for acceptability for tube integrity documented in the Corrective Action Process.
TABLE 2 - Degradation Found and Number of Tubes Plugged: U2C15 Refueling Outage Steam Generator E-088 E-089 Indication Orientation/Location Tubes with axially oriented ID (initiated on the inside-diameter of 1
2 the tubing wall) indications at tube support locations Tubes with axially oriented OD (initiated on the outside-diameter 28 47 of the tubing wall) indications at tube support locations Tubes with axially oriented OD indications not associated with a 2
2 tube support (freespan)
Tubes with circumferentially oriented ID indications near the 33 12 expansion transition at the top of the hot leg tubesheet Tubes with circumferentially oriented OD indications near the 15 22 expansion transition at the top of the hot leg tubesheet Tubes with axially oriented OD indications near the top of the hot 4
6 leg tubesheet Tubes with axially oriented ID indications in the hot leg tubesheet 34 10 region Tubes with circumferentially oriented ID indications in the hot leg 8
6 tubesheet region Tubes with indications of wear at tube support locations 7
17 Sleeved tubes with an eddy current signal indicative of the onset 1
1 of obstruction (Notes 1 and 2)
Total 133 125
Inspection of Steam Generator Tubes Special Report Attachment Page 4 of 13 Table 2 Note 1: These two sleeves were inspected full length with the rotating plus point probe.
They were not obstructed.
Table 2 Note 2: Overall, the rotating plus point probe inspection results for 100% of the sleeves indicated the effectiveness of previous significant preventive plugging. However, SCE Nuclear Fuel Management continues implementation of a conservative assumption (for accident analysis) that each remaining inservice sleeve may pose the potential for reactor coolant flow blockage, similar to that of a tube that is removed from service by plugging. The previous preventive plugging and the conservative assumption were described in the previous report (Letter from B. Katz (SCE) to Document Control Desk (NRC) dated February 7, 2006;
Subject:
Docket No. 50-361, Special Report: Inservice Inspection of Steam Generator Tubes, Cycle 14, San Onofre Nuclear Generating Station, Unit 2).
Examination Techniques Table 3 provides the list of Nondestructive Examination (NDE) techniques utilized for each degradation mechanism.
TABLE 3 - Nondestructive Examination (NDE) Techniques Utilized for Each Degradation Mechanism Indication Orientation/Location Probe Type for Detection Characterization Circumferentially oriented and axially oriented ID indications near or below the expansion transition at the top of the hot leg and cold leg Plus Point Plus Point tubesheets Axially oriented OD indications and Circumferentially oriented OD Plus Point Plus Point indications near the top of the hot and cold leg tubesheets Axially oriented OD indications not associated with a tube support Bobbin Plus Point (freespan)
Bobbin Plus Point Axially oriented OD indications at tube support locations PlsPin Plus Point Plus Point (Note 1)
Plus Point Bobbin Plus Point Axially oriented ID indications at tube support locations PlsP in Plus Point Plus Point (Note 1)
Plus Point Indications of wear at tube support locations Bobbin Plus Point Axially oriented ID indications and Circumferentially oriented ID Plus Point Plus Point indications in Low-Row U-bends Circumferentially oriented ID indications at the flanks of tubing bends Plus Point Plus Point Axially oriented OD indications at dings in tubing freespan (dings <5 Bobbin Plus Point volts)
Axially oriented OD indications at dings in tubing freespan Plus Point Plus Point Axially and Circumferentially oriented ID and OD indications and volumetric indications at sleeve in parent tubing below lower and Plus Point Plus Point above upper joints, and joints Table 3 Note 1: Plus Point technique is used at dents greater than, or equal to, two volts
Inspection of Steam Generator Tubes Special Report Attachment Page 5 of 13 Condition Monitoring Condition Monitoring demonstrated that performance criteria in Technical Specifications sections 5.5.2.11.b.1 (structural integrity) and 5.5.2.11.b.2 (accident induced leakage) were met during operation prior to this inspection.
In situ pressure testing was not needed for any eddy current indications. All indications were below screening criteria of the Electric Power Research Institute (EPRI) In Situ Pressure Testing Guidelines.
Table 4 contains all crack-like indications. SONGS Unit 2 Technical Specifications contain alternate repair criteria for a portion of the tube in the tubesheet region. However, all tubes with crack-like indications were removed from service. Voltage is the only size-related measurement for numerous indications in Table 4. This is consistent with industry guidance for tube integrity assessment. Industry guidance provides ranges of voltage measurement values for which voltage is the only needed size-related measurement. Table 4 addresses location, orientation and measured sizes of service-induced indications (except wear of tubing at tube supports). Appendices 3 and 4 address location and measured sizes of service-induced indications of wear of tubing at tube supports.
No tubes were removed (pulled) for destructive testing during this outage.
TABLE 4 - Measured Sizes of Service-Induced Indications: U2C15 SG Row Col Elev Inch Ind Origin PP Volts Depth PDA FLDA PP Length CA 88 6
138 07H
137 TSH
-1.95 SCI ID 0.57 68 N/A 27 88 7
143 TSH
-4.84 SCI ID 0.33 88 8
156 TSH
-0.15 SCI ID 0.57 72 N/A 27 88 9
51 03H
-0.32 SAI OD 0.27 88 10 40 TSH
-0.08 SCI ID 0.23 88 11 147 TSH
-0.07 SCI ID 0.57 65 N/A 23 88 12 24 06H
-0.13 SAI OD 0.27 88 13 47 TSH
-0.02 SCI ID 0.33 88 13 55 05H 0.64 SAI OD 0.26 88 14 126 TSH
-0.15 SCI ID 0.40 88 14 130 TSH
-0.06 SCI ID 0.45 88 15 141 TSH
-2.8 SCI ID 0.27 88 16 140 TSH
-8.44 SCI ID 0.51 36 N/A 23 88 17 15 TSH
-6.32 SAI ID 0.55 56 N/A 0.64 88 17 15 TSH
-6.03 SAI ID 0.55 44 N/A 0.13 88 17 57 01H 0.75 SAI OD 0.31 88 17 57 06H 0.58 SAI OD 0.22 88 17 59 TSH
-1.09 SAI ID 0.42 88 18 34 TSH 0.05 SCI ID 0.32 88 19 141 TSH
-6.13 SAI ID 0.50 88 20 120 TSH
-0.19 SCI ID 0.42
Inspection of Steam Generator Tubes Special Report Attachment Page 6 of 13 TABLE 4-Measured Sizes of Service-Induced Indications: U2C15 (continued)
SG Row Col Elev Inch Ind Origin PP Volts Depth PDA FLDA PP Length CA 88 21 31 TSH
-14.04 SCI ID 0.48 88 21 63 07C
-0.85 SAI OD 0.35 88 21 113 TSH
-2.37 SAI ID 0.52 54 N/A 0.15 88 21 127 04H 0.77 SAI OD 0.18 88 21 129 TSH
-0.09 SCI OD 0.31 88 22 52 03H
-0.7 SAI OD 0.31 88 23 109 TSH
-1.15 SAI ID 0.26 88 23 109 TSH
-0.79 SAI ID 0.51 49 N/A 0.12 88 23 109 TSH
-0.57 SAI ID 0.58 43 N/A 0.15 88 24 64 TSH
-0.81 SAI ID 0.95 36 N/A 0.15 88 24 160 06H
-0.06 SAI OD 0.20 88 25 117 TSH
-0.16 SCI ID 0.39 88 25 133 TSH
-0.14 SCI ID 0.70 53 N/A 27 88 25 133 TSH
-0.13 SCI ID 0.53 61 N/A 39 88 27 61 TSH
-4.41 SAI ID 0.87 39 N/A 0.15 88 27 61 TSH
-1.2 SAI ID 0.92 42 N/A 0.24 88 27 159 02H 0.03 SAI OD 0.23 88 27 159 02H 0.79 SAI OD 0.28 88 27 159 03H 0.87 SAI OD 0.49 88 28 120 TSH
-6.66 SAI ID 0.52 51 N/A 0.16 88 30 8
03H 0.85 SAI OD 0.24 88 30 38 TSH
-0.08 SCI ID 0.51 41 N/A 27 88 30 52 TSH 0.66 SAI OD 0.22 88 31 67 TSH
-0.06 SCI ID 0.61 73 N/A 27 88 31 69 TSH 0
SAI ID 0.57 32 N/A 0.12 88 31 107 TSH
-1.05 SAI ID 0.80 43 N/A 0.22 88 31 123 05H 0.66 SAI OD 0.28 88 31 165 05H
-0.34 SAI ID 0.76 66 N/A 0.18 88 31 165 05H 0.39 SAI ID 0.60 39 N/A 0.12 88 31 165 05H 0.54 SAI ID 0.39 88 32 112 TSH
-2.08 SAI ID 0.69 46 N/A 0.22 88 32 112 TSH
-1.63 SAI ID 0.81 46 N/A 0.18 88 32 122 TSH
-0.88 SAI ID 0.74 46 N/A 0.12 88 33 37 TSH
-0.1 SCI ID 0.42 88 34 108 TSH
-0.77 SAI ID 0.66 51 N/A 0.15 88 35 69 TSH
-1.07 SAI ID 0.47 88 36 70 TSH
-3.93 SAI ID 0.70 40 N/A 0.15 88 36 70 TSH
-3.11 SAI ID 0.51 34 N/A 0.12 88 36 70 TSH
-1.59 SAl ID 0.75 40 N/A 0.12 88 37 71 TSH
-2.58 SAI ID 0.66 43 N/A 0.12 88 38 28 01H 0.33 SAI OD 0.23
Inspection of Steam Generator Tubes Special Report Attachment Page 7 of 13 TABLE 4-Measured Sizes of Service-Induced Indications: U2C15 (continued)
SG Row Col Elev Inch Ind Origin PP Volts Depth PDA FLDA PP Length CA 88 38 28 05H
-0.67 SAI OD 0.44 88 38 110 TSH
-1.44 SAI ID 0.79 38 N/A 0.15 88 38 110 TSH
-0.65 SAI ID 0.55 35 N/A 0.18 88 40 58 TSH
-3.72 SAI ID 0.41 88 40 162 06H 0.25 SAI OD 0.31 88 41 39 TSH
-1.42 SCI ID 0.71 39 N/A 31 88 41 69 TSH
-2.14 SAI ID 0.69 32 N/A 0.12 88 42 14 DBH
-0.81 SAI OD 0.16 88 42 14 DBH
-0.11 SAI OD 0.20 88 42 106 TSH
-1.18 SAI ID 0.46 88 43 73 TSH
-3.9 SAI ID 0.65 43 N/A 0.12 88 46 148 01H
-0.16 SAI OD 0.24 88 47 111 TSH
-3.12 SAI ID 0.35 88 47 111 TSH
-0.87 SAI ID 0.84 54 N/A 0.33 88 47 143 01H
-0.03 SAI OD 0.15 88 48 124 TSH
-0.1 SCI ID 0.28 88 48 134 TSH
-0.07 SCI ID 0.57 50 N/A 23 88 49 47 08C
-1.17 SAI GD 0.14 88 50 102 TSH
-0.42 SAI ID 0.40 88 50 106 TSH
-0.07 SAI ID 0.41 88 50 148 08H 0.81 SAI OD 0.38 88 51 55 TSH 0.03 SCI OD 0.29 88 51 57 TSH 0.06 SCI OD 0.36 88 51 117 TSH
-0.1 SCI ID 0.69 53 N/A 27 88 51 155 04H 0.75 SAI OD 0.21 88 52 72 TSH 0.23 SAI OD 0.17 88 52 112 TSH
-3.67 SAI ID 0.45 88 52 112 TSH
-3.37 SAI ID 0.67 43 N/A 0.31 88 52 112 TSH
-2.57 SAI ID 0.51 34 N/A 0.21 88 52 112 TSH
-1.87 SAI ID 0.79 43 N/A 0.55 88 53 57 TSH 0.15 MCI OD 0.28 88 53 113 TSH
-3.74 SAI ID 0.43 88 53 113 TSH
-5.31 SAI ID 0.68 41 N/A 0.18 88 53 113 TSH
-1.74 SAI ID 0.74 41 N/A 0.18 88 54 38 TSH
-0.02 SCI ID 0.49 88 54 60 TSH 0.15 SAI OD 0.17 88 54 72 TSH 0.06 SCI OD 0.20 88 56 126 TSH
-0.17 SCI ID 0.39 88 56 154 TSH
-7.34 SAI ID 0.53 38 N/A 0.12 88 57 73 TSH 0.09 SCI OD 0.12
Inspection of Steam Generator Tubes Special Report Attachment Page 8 of 13 TABLE 4 - Measured Sizes of Service-Induced Indications: U2C15 (continued)
SG Row Col Elev Inch Ind Origin PP Volts Depth PDA FLDA PP Length CA 88 57 105 TSH
-2.35 SAI ID 0.41 88 57 161 06H
-0.41 SAI OD 0.41 42 N/A 0.61 88 58 70 TSH
-2.27 SAI ID 0.65 54 N/A 0.12 88 59 83 TSH
-1.4 SAI ID 0.56 58 N/A 0.14 88 59 83 TSH
-0.87 SAI ID 0.30 47 N/A 0.12 88 60 86 VC3 0.84 SAI OD 0.23 88 60 106 TSH 0
SCI ID 0.31 88 62 80 TSH 0.03 SCI OD 0.22 88 62 114 TSH
-2.04 SAI ID 0.58 49 N/A 0.12 88 64 120 TSH
-0.03 SCI ID 0.47 88 65 87 TSH 0.06 SCI OD 0.14 88 65 111 TSH
-1.11 SAI ID 0.75 46 N/A 0.17 88 65 111 TSH
-0.15 SCI ID 0.41 88 67 111 TSH 0.16 SCI OD 0.16 88 68 112 TSH
-9.88 SCI ID 0.30 88 68 112 TSH
-6.12 MCI ID 0.55 72 N/A 74 88 69 119 TSH
-0.03 SCI ID 0.51 66 N/A 39 88 69 119 TSH
-0.02 SCI ID 0.37 56 N/A 19 88 70 86 TSH
-2.15 SAI ID 0.50 88 70 86 TSH
-1.84 SAI ID 0.46 88 70 104 TSH 0.17 SAI OD 0.29 88 72 100 TSH 0.05 SCI OD 0.33 88 75 95 TSH
-0.19 SCI ID 0.63 74 N/A 62 88 75 99 TSH 0.08 SCI OD 0.24 88 76 18 06H 0.62 SAI OD 0.22 88 77 85 TSH
-1.92 SAI ID 0.68 44 N/A 0.16 88 78 74 TSH
-0.06 SCI ID 0.32 88 78 96 TSH 0.11 SCI OD 0.20 88 78 98 TSH
-0.1 SCI ID 0.38 88 78 102 TSH 0
SCI ID 0.53 78 N/A 27 88 78 120 TSH
-6 SCI ID 0.39 88 79 81 TSH
-0.05 SCI ID 0.17 88 79 97 TSH 0.03 SCI OD 0.37 88 80 84 TSH
-0.08 SCI ID 0.24 88 81 93 TSH
-2.6 SAI ID 0.61 44 N/A 0.21 88 83 49 02H 2.02 SAI 0D 0.32 88 83 87 TSH
-0.12 SCI ID 0.45 88 88 60 01H 2.27 SAI OD 0.20 88 90 42 08H 0.75 SAI OD 0.26 88 90 42 VC2 0.12 SAI OD 0.24
Inspection of Steam Generator Tubes Special Report Attachment Page 9 of 13 TABLE 4 - Measured Sizes of Service-Induced Indications: U2C15 (continued)
SG Row Col Elev Inch Ind Origin PP Volts Depth PDA FLDA PP Length CA 88 90 78 TSH
-0.11 SCI ID 0.27 88 94 48 01H 0.21 SAI OD 0.24 88 95 71 TSH
-0.08 SCI ID 0.30 88 98 94 TSH 0
SCI OD 0.22 88 100 102 TSH
-0.07 SCI ID 0.19 88 100 118 TSH 0
SCI ID 0.39 88 107 97 TSH 0.03 SCI OD 0.28 88 111 67 02H 1.06 SAI OD 0.46 88 143 109 03H
119 07H
-0.5 SAI OD 0.53 50 N/A 0.32 89 5
119 07H
58 TSH
-6.31 SCI ID 0.33 89 8
36 05H
122 07H
117 05H 0.91 SAI OD 0.26 89 10 44 05H
-0.83 SAI OD 0.31 89 10 44 05H 0.54 SAI OD 0.23 89 11 19 04H
-0.19 SAI OD 0.23 89 11 19 06H 0.22 SAI OD 0.30 89 11 55 05H 0.94 SAI OD 0.37 89 11 65 01H 0.54 SAI OD 0.30 89 11 119 04H
-0.25 SAI OD 0.31 89 11 121 TSH
-10.71 SCI ID 0.50 89 11 131 TSH
-13.59 SCI ID 0.72 38 N/A 28 89 12 114 06H
-0.16 SAI OD 0.40 89 12 128 01H 0.58 SAI OD 0.22 89 12 128 04H 0.5 SAI OD 0.34 89 14 18 05H 0.88 SAI OD 0.17 89 14 58 04H 1.07 SAI OD 0.41 89 15 131 TSH
-0.1 SCI ID 0.43 89 15 141 TSH
-0.08 SCI ID 0.54 47 N/A 27 89 16 56 06H
-1.39 SAI OD 0.12 89 16 60 TSH
-0.09 SCI ID 0.39 89 17 49 TSH 0.08 SCI OD 0.13 89 18 26 06H
Inspection of Steam Generator Tubes Special Report Attachment Page 10 of 13 TABLE 4 - Measured Sizes of Service-Induced Indications: U2C15 (continued)
SG Row Col Elev Inch Ind Origin PP Volts Depth PDA FLDA PP Length CA 89 18 34 TSH
-5.71 SAI ID 0.29 89 18 34 TSH
-5.26 SAI ID 0.48 46 N/A 0.18 89 20 120 04H 0.69 SAI OD 0.49 45 N/A 0.7 89 20 120 04H
-0.26 SAI OD 0.42 89 23 137 TSH
-0.14 SCI ID 0.32 89 24 50 TSH 0.12 SCI OD 0.23 89 24 130 TSH 0.08 SCI OD 0.19 89 25 49 TSH 0.09 SCI OD 0.16 89 25 51 07C
-0.6 SAI OD 0.32 89 25 149 06H
-0.38 SAI OD 0.26 89 28 54 TSH 0.35 SAI OD 0.37 89 28 122 TSH 0.12 MCI OD 0.19 89 29 47 07H 0.61 SAI OD 0.30 89 29 59 TSH
-3.59 SAI ID 0.32 89 30 134 TSH
-6.96 SCI ID 0.47 89 32 48 TSH
-0.09 SCI ID 0.45 89 33 67 04H 0.5 SAI OD 0.26 89 33 67 TSH 0.47 SAI OD 0.17 89 33 67 TSH 0.62 SAI OD 0.21 89 34 112 04H
-0.34 SAI OD 0.28 89 35 49 TSH 0.27 SAI OD 0.14 89 35 111 04H
-0.29 SAI OD 0.21 89 35 111 TSH
-0.98 SAI ID 0.72 44 N/A 0.17 89 36 128 TSH 0.05 MCI OD 0.34 89 38 8
06H 0.7 SAI OD 0.23 89 39 45 TSH 0.04 MCI OD 0.18 89 39 131 TSH
-8.54 SAI ID 0.47 38 N/A 0.15 89 39 131 TSH
-7.5 SAI ID 0.60 40 N/A 0.12 89 39 133 TSH
-7.28 SAI ID 0.73 60 N/A 0.17 89 39 133 TSH 0.03 SCI OD 0.24 89 40 46 TSH 0.05 SCI OD 0.25 89 40 60 TSH 0.31 SAI OD 0.33 89 40 136 TSH
-8.81 SCI ID 0.51 53 N/A 27 89 41 131 TSH
-0.16 SCI ID 0.57 53 N/A 50 89 42 38 TSH
-0.12 SCI ID 0.91 71 N/A 31 89 45 63 TSH 0.19 SAI OD 0.26 89 45 63 TSH
-3.16 SAI ID 0.76 57 N/A 0.16 89 45 63 TSH
-2.39 SAI ID 0.53 60 N/A 0.16 89 46 48 TSH 0.14 SCI OD 0.13 89 46 126 03H
Inspection of Steam Generator Tubes Special Report Attachment Page 11 of 13 TABLE 4-Measured Sizes of Service-Induced Indications: U2C15 (continued)
SG Row Col Elev Inch Ind Origin PP Volts Depth PDA FLDA PP Length CA 89 46 134 06H 0.16 SAI OD 0.47 46 30.43 0.87 89 48 12 04H 0.61 SAI OD 0.35 89 48 52 TSH 0.12 SCI OD 0.15 89 48 64 TSH
-1.43 SAI ID 0.37 89 48 64 TSH
-2.18 SAI ID 0.43 40 N/A 0.13 89 48 130 TSH
-0.13 SCI ID 0.36 89 49 51 TSH 0.07 MCI OD 0.15 89 49 53 TSH 0.09 SCI OD 0.17 89 49 57 08H 1.54 SAI OD 0.31 89 50 106 TSH 0.15 SCI OD 0.27 89 52 120 TSH
-0.13 SCI ID 0.62 63 N/A 28 89 54 52 TSH
-5.76 SCI ID 0.44 89 54 102 01H 13.43 SAI OD 0.27 89 55 45 TSH
-0.16 SCI ID 0.36 89 57 77 TSH 0.07 MCI OD 0.25 89 57 97 TSH
-4.39 SAI ID 0.50 46 N/A 0.13 89 58 54 TSH
-6.25 SAI ID 0.34 89 59 53 TSH
-0.17 SCI ID 0.25 89 59 89 06C
-0.69 SAI OD 0.30 89 59 89 VH3 0.08 SAI OD 0.31 89 62 74 TSH 1.36 SAI OD 0.22 89 62 92 TSH 0.13 SCI OD 0.20 94 N/A 51 89 64 76 05H 0.67 SAI OD 0.28 89 64 80 TSH
-2.87 SAI ID 0.35 89 64 84 TSH 0.09 SCI OD 0.19 89 65 37 VSM
-0.93 SAI OD 0.21 89 70 68 TSH 0.06 SCI OD 0.24 89 70 92 TSH
-2.27 SAI ID 0.29 89 71 57 08H 0.52 SAI OD 0.15 89 71 67 TSH 0.14 SCI OD 0.46 89 75 53 TSH
-0.03 SCI OD 0.12 89 79 53 TSH
-0.02 SCI ID 0.57 53 N/A 27 89 79 89 TSH 1
SCI OD 0.33 89 83 73 03H
-0.11 SAI OD 0.29 89 85 81 TSH 0.19 SCI OD 0.31 89 87 31 05H 0.33 SAI ID 0.82 51 N/A 0.15 89 87 47 03H
-0.21 SAI OD 0.18 89 89 93 TSH
-13 SAI ID 0.48 46 N/A 0.12 89 91 85 03H 0.2 SAI OD 0.33 1
Inspection of Steam Generator Tubes Special Report Attachment Page 12 of 13 TABLE 4-Measured Sizes of Service-Induced Indications: U2C15 (continued)
SG Row Col Elev Inch Ind Origin PP Volts Depth PDA FLDA PP Length CA 89 93 113 02H 0.84 SAI OD 0.35 89 98 62 TSH
-13.92 SAI ID 1.26 55 N/A 0.18 89 98 82 01H
-0.44 SAI OD 0.31 89 106 126 02H 0.24 MAI OD 0.44 89 108 52 06H 0.67 SAI ID 1.22 49 N/A 0.15 89 108 126 02H 0.66 SAI OD 0.33 89 110 122 02H 0.82 SAI OD 0.30 89 112 134 02H 0.5 SAI OD 0.54 51 N/A 0.74 89 118 62 01H 0.95 SAI OD 0.41 89 118 62 04H 0.95 SAI OD 0.25 89 118 124 02H 0.43 SAI OD 0.23 89 122 110 05H
-0.3 SAI OD 0.23 89 128 60 04H 0.75 SAI OD 0.42 89 130 82 01H
-0.27 SAI OD 0.67 55 N/A 0.61 Table 4 Notes:
SG 88 = SG E-088 SG 89 = SG E-089 PP = Plus Point Depth = Percent of Tube Wall Thickness PDA = Percent Degraded Area FLDA = Flaw-Length Degraded Area PP Length (units of measure are inches)
CA = Crack Angle (degrees)
Appendices 1 and 2 provide definitions for other terms
Inspection of Steam Generator Tubes Special Report Attachment Page 13 of 13 Repair Methods, Number of Tubes Repaired and Effective Plugging Percentage All tube plugging was performed using the design, materials, and installation methods of AREVA. A "roll" method was used for all tube plugs. Eighty-eight (88) tubes were "stabilized" in the vicinity of the top of the tubesheet using the design, materials, and installation methods of AREVA. Sleeving was not used for tube repair for the Cycle 15 outage. The design number of tubes in each SG is 9350 tubes and the sleeve-to-plug equivalency ratio is thirty-eight (38) sleeves per plug.
TABLE 5 - Number of Tubes Plugged or Repaired and Effective Plugging Percentage
- Tubes
- Tubes
- Sleeves Effective SG Plugged in Plugged To Remaining in Plugging 2C15 Date Service Percentage 88 133 1390 155 15.0%
89 125 1251 91 13.5%
Description of Appendices Appendix 1 -
Steam Generator Reference Information Appendix 2 -
Legend for Appendices 3 and 4 Appendix 3 -
Tube Inspection Summary, Steam Generator E-088 Appendix 4 -
Tube Inspection Summary, Steam Generator E-089
Inspection of Steam Generator Tubes Special Report Appendix 1 Page 1 of 4 Appendix 1 Steam Generator Reference Information
Inspection of Steam Generator Tubes Appendix 1 Special Report Page 2 of 4 Steam Generator CE Model 3410 Tube Support Drawing 1S" 16' 16' 16" 16' 16' 10H-10OC 30.75' 09H 09C 30.75' 08H 08C 30.7V 07H.
07C 38" 06H 06C 34" 05H 05C a5" 04H 04C 38" 03H 03C 36" 02H 02C 35.
O1H 0lC
________ J27.2S" TSH TSC 23' TEH TT-TEC
Inspection of Steam Generator Tubes Special Report Appendix 1 Page 3 of 4 STEAM GENERATOR TUBE SUPPORT INTERSECTIONS ABOVE THE 7 TH (FULL) EGGCRATE SUPPORT SUPPORT INTERSECTIONS ROW STRUCTURES 122-147 08H 09H 10H DBH VH1 VH2 VH3 VSM VC3 VC2 VC1 DBC 10C 09C 08C 120-121*
08H 09H 10H DBH VH1 VH2 VH3 VSM VC3 VC2 VC1 DBC 10C 09C 08C 115-119 08H 09H DBH VH1 VH2 VH3 VSM VC3 VC2 VC1 DBC 09C 08C 86-114 08H 09H DBH VH2 VH3 VSM VC3 VC2 DBC 09C 08C 84-85*
08H 09H DBH VH2 VH3 VSM VC3 VC2 DBC 09C 08C 83 08H DBH VH2 VH3 VSM VC3 VC2 DBC 08C 51-82 08H DBH VH3 VSM VC3 DBC 08C 49-50*
08H DBH VSM DBC 08C 19-48 DBH VSM DBC 1-18 DBH DBC
- Indicates those rows adjacent to scallop bars
Inspection of Steam Generator Tubes Special Report Appendix 1 Page 4 of 4 SOUTHERN CALIFORNIA EDISON, SAN ONOFRE CE MODEL 3410 STEAM GENERATOR 10 z0 V) 40 50 rO 70 so so 10 110 120 130 140 150 160 170 140 130 120 100 s0 80 70 149 00 0
0o 00 00 600006Q0 00 0000 0 010 0-0 0 0 0
0 0 o'o 009 i'90 01
- '001001 0
0 G 0 1
0-MMM, 59?mý-
Aq 200 130 0
a 06co 00 ý'ýa 430 P'6 &Q p
0 0 0ý0ý0ý0 080ý080ý0 0 00 00 10, 6 U616 16, 90 0
go 0
go jooso "v 0 9 0 0-0 a 6-0
' ' 2 0
00106100'0'00ý 200" 00 0 10-0220'0ý
?00 50040roo 0
9
-0 a,
69 o.
0 0-OX Mý.5'0iP5'.Q'0 ý26262528 62526262o -1
- '-6'-26-206-'26 6 6 11600600 041, 000 00 00 00 0 0 0 6-,6 0 0 10 696 9
'01 010 0
0
.'4'. 0 0.-.0 00 OR 0
0 0
0 I solo 0,00
ý-'00:'52'0;'o ERR-0, 0 0 CR, 0("
2-'0200 000 v
o.'-',o- `-N'.
2n'ý "I
B 0 0
9 MQ
-zo Qý on.
890ý Ito 060606060 060606060 0 01 0
01 0ý0 o 100ý0 0
1 0 0 'go8o 0
0,0 0,0 ON 0
0 "Q Q-?Ugo 6006000 6 go 01 10 10
ý0 000 00 0
0 0
'00 0 C 00000 0000009,0,00 8`1 0 r"00 09, 3g" 0
l'o.0,0,0"0, 0.,. Qo,.,
- 0.
0 0 0
00 0 0 000 o 0-0 01OX0
- 4) 9 09 0 0
ozol(ý
ý559ý0 10ýO X0 0
0 N
0606 U Q-I
ý80-0 ý,,'§ 06ýO'
ý.-q g
o 0106 0 0 0 0 010 0
0 01
- 0 0.9 1
'D 06 60100 01 10 0 0
00ý0 8 ý 0
0 6
0 10 0
100 0 91, 0 620 ". " -
0 060 0
00 og 0
01 0 0
0 0
0 go lp
'*008' 0,08-0,6868 0 0 g'3 1
00 0
O'S loý 0 0 o 13" 0
C
'Q Q
9 0
Sý 601-1go 0 0
-0 g 011) so 1
j 0
0 0 0 9 0 0
00 0 0 010 00 000 10 0
NO.
10 0
o S 00 0..
00 0,
- 9.
0 0 0 ZýZ 0.19 -
-0 a
02 R?
9.0 01ý.01 r'=6ý I
'ý-o 0
ý0608qv.06 -
0 00 0'Q'00
'O'Z)401 16 60 0
00 00, 1ý go 000 9
goo 0
0 0 0 0 0 0 0 0 0
0,00,0'ý)0,0 ON".,
010 0
6,000 "G 43 0 4D 0ý 0'gý 0-0 "(20" g-
.0-0. 0 11 MR
.0 O-P.-O 6
6v vo'ý'
0 16 'n 0 0 0
0 6
0 10 0 0
0ý0 Q Qýqý'
0 0 0
00 0ý0 10 0
0 00 0
0 0
0 lclý 00 0 0 0
ý0
-0 L.11ý1 lolol lo V
6ao;0-6 0 00 gg-XXX 0 0 ý211 "9ý2 N.
l'ý ý 9,
9ý'-
000 0,6,0,20_ 6, '6'
'0ý 0,0 0,
0'.'M 10go 01-0 v "- o 0
0 C 0 0' ' -
01 OYY--6 01010 0 0 0 0 0 0 0
0 0000000092 0000000,0 Q'00' ý'Q 0
'o 0
16 00 0 0
(5 0- -0 0
0 0
0, g 0 0, o 010 "o
O.-;o 90,0, "00 OR
ýqo
_6yoý'
262 2 116&
0 1
0 0 0 0 Mo 0 160 11610, '6ý 0
Qu "1'
0.0 62 06-0 OZO Q6Q 10 goo 0,10 E0600600610ý "I 1
0610 060
ýQ o 0ý0 41 0 0 0
0 0 010 0
0
-No Yolyol
. 1'0'voý'o ogv".go
.6 0 0 0
0o Q 0 11 0 600,0 0
010 ýW'0'0
'0
?vROK.W. 0-R 60 0--
192%0 5:05ya 0yo-06-00yo 0
-6 oo'ý 0 R -5 6'w
ý'Oýo 0o MS.
R, 40 g
3Q.6,6 6
Q 0
op 0
010 01,0'00,0 0,00,o 9 0 0
o OV 0 606
- 6,'&Q,6oQ48
6' ' 6('
Q6M6vp: 6
&o" v v 9
0" 6ý 51011.0 01 00 0
'000 0
0 Oý.
0
)0000 000. 00QP'Q8Qo 0 5-0.1 0 2-P.
ý'Vi R.
N.
0 '10-o 000 0
ýQ 00
-g 06 0 0
-0 oi.. 00.,,
OPP
.01v "M.
&OP 0
"-Q 0.19.
0
-'o 0 0-0 0-"
0 Nog 0
ý5?090yn
-Oyd-
-MISL 6
30 60;06 000 0
06 0":
0 0
0 Q6o'5Q6Q
- 00.
0 0
9 Y'0
ýfqyq o
010 q0' oyopýo 0
010900168 000 0
0 0 9
00 C' 0
0 0 0 0 0go 9,00 10 5 00 00, 010 0 0
.'0 0 0 0
0Q'00'0Q'0' 20 a'292.a'ý 6 6-20 101ý1.01-01 0 0
K i goý. 00 0 "R. '121" 1ýc ZU g
0 006 00600600600ý00 0 eý 1W ovq'Xq o
60,6,Z
-0 so 40 30 20 01O0%00c005 1
0 x 0
1 1;
0
.oo7 0
oqqggý Z.p
.'0 qrsýý'
0-ozo-q- -oza-ý-
1^0*
Q~V5?6V6V6A5V~
6 ~ jp~co~o~0. &~~5~5Thft'&'
3Q5Y6 taL?&~
1 1
+
10 0000' 0 0 0 0 0 o.
0 o
0 Oo 00 0oo o 00oto-o-00 0000000 00 r,
ooe~~-bv T,
0*'¢0
°>
04 000000
(.
0 ol" 0 -
o%
0
Inspection of Steam Generator Tubes Special Report Appendix 2 Page 1 of 2 Appendix 2 Legend for Appendices 3 and 4
Inspection of Steam Generator Tubes Special Report Appendix 2 Page 2 of 2 List of Abbreviations and Format Used to Describe Indications from Rotating Probe Testing Abbreviations Explanation of the Abbreviations SCI Single Circumferential Indication MCI Multiple Circumferential Indications SAI Single Axial Indication MAI Multiple Axial Indications MMI Mixed Mode Indications SVI Single Volumetric Indication (i.e. no special axial or circumferential aspect)
MVI Multiple Volumetric Indications (i.e. no special axial or circumferential aspect)
PCS Partially Collapsed Sleeve TWD Through Wall Depth (an indication of tubing wear used for volumetric wear indicated with a percent value shown in the next column)
Format In Appendices 3 and 4, a single line of data is associated with each individual indication. Below is a descriptive example of the format.
The example above displays the format of a Report line. The VOLTS field contains the voltage of the largest, most representative response. The DEG field contains the corresponding phase angle. The CHN field contains the reporting channel (e.g., the appropriate axially or circumferentially sensitive 300kHz Plus Point channel). The IND field contains the appropriate 3-letter code (see list above). The
%TW field indicates the percent wall loss for wear indications. The LOCATION field contains the abbreviation for the referenced landmark and the distance to the indication. The EXT fields contain the landmarks of the beginning and end of the test extent. The CAL# field identifies the calibration number associated with the acquired data. The LEG field identifies the Hot or Cold Leg as the location of the probe origination. The PROBE field contains the abbreviated identifier of the probe type used for the inspection. For the second column, the terms line and column are used interchangeably for Combustion Engineering designed steam generators.
Inspection of Steam Generator Tubes Special Report Appendix 3 Page 1 of 14 Appendix 3 Tube Inspection Summary Steam Generator E-088
AREVA NP InC Customer Name: San Onofre -
Unit 2 01/09/08 14:19:36 Component: S/G 88 Page 2 of 14 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMi[l]
ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 1
133 0.40 0
P2 TWD 18 04C
-0.17 07C TEC 6
COLD 600UL 6
138 0.15 87 2
SAI 07H
-0.98 07H 07H 156 HOT 580PP 6
168 0.37 130 P2 TWD 18 04H
-0.31 TEC TEH 23 HOT 600UL 7
55 0.32 110 2 SAI 07C
+0.97 07C DBC 109 COLD 5809P 7
137 0.57 27 P1 SCI TSH
-1.95 TSH TSH 86 HOT 580PP 7
143 0.33 20 P1 SCI TSH
-4.84 TSH TSH 85 HOT 580PP 8
156 0.57 24 Pl SCI TSH
-0.15 TSH TSH 85 HOT 580PP 9
51 0.27 77 2
SAI 03H
-0.32 03H 03H 212 HOT 520ET 10 40 0.23 22 P1 SCI TSH
-0.08 TSH TSH 76 HOT 580PP 11 147 0.57 22 P1 SCI TSH
-0.07 TSH TSH 83 HOT 580PP 12 24 0.27 104 2 SAI 06H
-0.13 06H 06H 169 HOT 580PP 13 9
0.34 98 P2 TWD 14 05H
-0.14 TEC TEH 25 HOT 60OUL 13 47 0.33 21 P1 SCI TSH
-0.02 TSH TSH 80 HOT 580PP 13 55 0.26 69 2
SAI 05H
+0.64 05H 05H 183 HOT 580PP 13 159 0.14 45 P3 TWD 8 DBH
-2.25 TEC TEH 19 HOT 600UL 14 126 0.40 17 P1 SCI TSH
-0.15 TSH TSH 70 HOT 580PP 14 130 0.45 24 P1 SCI TSH
-0.06 TSH TSH 74 HOT 58OPP 15 119 0.43 133 P2 TWD 19 07C
-0.96 TEH TEC 49 COLD 600UL 15 141 0.27 23 P1 SCI TSH
-2.80 TSH TSH 79 HOT 58022 16 140 0.51 17 P1 SCI TSH
-8.44 TSH TSH 78 HOT 580PP 17 15 0.55 16 2
SAI TSH
-6.03 TSH TSH 72 HOT 580PP 0.55 13 2
SAI TSH
-6.32 TSH TSH 72 HOT 58OPP 17 57 0.31 123 2 SAI 01H
+0.75 01H 01H 189 HOT 580PP 0.22 97 2
SAI 06H
+0.58 06H 06H 189 HOT 580P2 17 59 0.42 15 2
SAI TSH
-1.09 TSH TSH 87 HOT 5802P 18 34 0.32 19 P1 SCI TSH
+0.05 TSH TSH 49 HOT 5802P 18 44 0.23 113 P3 TWD 10 DBH
-2.00 TEC TEH 13 HOT 60OUL 19 47 0.52 18 P3 TWD 19 DBC
+1.66 TEH TEC 37 COLD 600UL 19 135 0.36 147 P3 TWD 18 DBH
+2.00 TEC TEH 11 HOT 600UL 19 141 0.50 14 2
SAI TSH
-6.13 TSH TSH 79 HOT 580PP 20 68 0.37 68 P3 TWD 13 DBH
-1.71 TEH TEC 39 COLD 600UL 20 108 0.14 43 P3 TWD 6 DBH
-1.54 TEH TEC 50 COLD 600UL 20 120 0.42 16 P1 SCI TSH
-0.19 TSH TSH 64 HOT 580PP 21 31 0.48 23 P1 SCI TSH
-14.04 TSH TSH 52 HOT 580PP 21 61 0.47 17 P3 TWD 17 DBC
+1.98 TEH TEC 38 COLD 600UL 21 63 0.35 105 2 SAI 07C
-0.85 07C 07C 113 COLD 58OPP 21 67 0.32 79 P3 TWD 12 DBH
+2.00 TEH TEC 38 COLD 600UL 0.34 141 P2 TWD 13 VSM
+0.76 TEH TEC 38 COLD 600UL 21 113 0.52 17 2
SAI TSH
-2.37 TSH TSH 65 HOT 58OPP 21 127 0.18 107 2
SAI 04H
+0.77 04N 04H 150 HOT 580P2 21 129 0.31 52 P1 SCI TSH
-0.09 TSH TSH 65 HOT 5802?
AREVA NP Inc Customer Name:
San Onofre -
Unit 2 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, NVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMI[1].qry 01/09/08 14:19:36 Component:
S/G 88 Page 3 of 14 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL 22 52 0.31 60 2
SAI 03H
-0.70 03H 03H 212 23 109 0.47 113 P2 TWD 20 VSM
+1.02 TEH TEC 50 0.51 15 2
SAI TSH
-0.79 TSH TSH 64 0.58 15 2
SAI TSH
-0.57 TSH TSH 64 0.26 14 2
SAI TSH
-1.15 TSH TSH 64 24 14 0.11 23 P2 TWD 7 VSM
+0.88 TEC TEH 22 24 64 0.95 13 2
SAI TSH
-0.81 TSH TSH 89 LEG PROBE HOT 520ET COLD 60OUL HOT 580PP HOT 580PP HOT 580PP HOT 60OUL HOT 580PP 24 156 0.38 101 P2 TWD 17 03H
+0.88 TEC TEH 20 HOT 60OUL 24 160 0.20 85 2
SAI 06H
-0.06 06H 06H 155 HOT 580?P 25 117 0.39 22 P1 SOI TSR
-0.16 TSH TSH 65 HOT 580PP 25 133 0.53 25 P1 SCI TSH
-0.13 TSH TSH 75 HOT 580PP 0.70 22 P1 SCI TSH
-0.14 TSH TSH 75 HOT 580PP 26 146 0.15 16 P3 TWD 5 DBH
+0.74 TEC TEH 16 HOT 60OUL 27 61 0.92 15 2
SAI TSH
-1.20 TSH TSH 89 HOT 580PP 0.87 14 2
SAI TSH
-4.41 TSH TSH 89 HOT 580PP 27 159 0.23 99 2
SAI 02H
+0.03 02H 02H 155 HOT 580PP 0.49 97 2
SAI 03H
+0.87 03H 03H 155 HOT 580PP 0.28 50 2
SAI 02H
+0.79 02H 02H 155 HOT 580PP 28 120 0.52 18 2
SAI TSH
-6.66 TSH TSR 64 HOT 580PP 30 8
0.24 96 2
SAI 03H
+0.85 03H 03H 169 HOT 580PP 30 38 0.51 18 P1 SCI TSH
-0.08 TSH TSH 102 HOT 580PP 30 52 0.22 73 2
SAI TSH
+0.66 TSH TSH 81 HOT 580PP 31 11 0.29 97 P3 TWD 11 DBH
+1.80 TEC TEH 25 HOT 600UL 31 65 0.54 10 P3 TWD 19 DBC
+2.00 TEH TEC 38 COLD 600UL 31 67 0.61 21 P1 SCI TSH
-0.06 TSH TSH 89 HOT 580PP 31 69 0.57 11 2
SAI TSH
+0.00 TSH TSH 93 HOT 5802P 31 107 0.80 15 2
SAI TSH
-1.05 TSH TSH 64 HOT 580PP 31 123 0.28 98 2
SAI 05H
+0.66 05H 05H 150 HOT 580PP 31 165 0.76 23 2
SAI 05H
-0.34 05H 05H 159 HOT 58OPP 0.60 14 2
SAI 05H
+0.39 05H 05H 159 HOT 5802P 0.39 16 2
SAI 05H
+0.54 05H 05H 159 HOT 580PP 32 4
0.31 131 P2 TWD 16 01C
-0.92 TEC TEH 26 HOT 60OUL 32 112 0.81 16 2
SAI TSH
-1.63 TSH TSH 65 HOT 580PP 0.69 15 2
SAI TSH
-2.08 TSH TSH 65 HOT 580PP 32 122 0.74 15 2
SAI TSH
-0.88 TSH TSH 71 HOT 58022 33 37 0.42 24 P1 SCI TSH
-0.10 TSH TSH 48 HOT 5802?
33 105 0.50 6
P3 TWD 21 DBC
+1.53 TEC TEH 36 HOT 600UL 0.31 144 P3 TWD 14 DBH
-1.69 TEC TEH 36 HOT 60OUL 0.20 82 P3 TWD 10 DBC
-1.59 TEC TEH 36 HOT 60OUL 34 108 0.66 19 2
SAI TSH
-0.77 TSH TSH 64 HOT 580PP 35 27 0.34 87 P2 TWD 14 VSR
+0.72 TEC TEH 17 HOT 600UL 0.37 77 22 TWD 15 VSM
-0.74 TEC TEH 17 HOT 600UL 35 69 0.47 15 2
SAT TSH 35 71 0.53 100 P3 TWD 19 DBC 36 70 0.75 14 2
SAI TSH 0.51 12 2
SAI TSH 0.70 14 2
SAI TSH
-1.07 TSH TSH 93 HOT 580PP
-1.90 TEH TEC 38 COLD 600UL
-1.59 TSH TSH 93 HOT 580PP
-3.11 TSH TSH 93 HOT 580PP
-3.93 TSH TSH 93 HOT 580PP 37 47 0.47 107 P2 TWD 20 VSM
+0.88 TEH TEC 317 COLD 600TUL
AREVA NP Inc Customer Name:
San Onofre -
Unit 2 01/09/08 14:19:36 Component:
S/G 88 Page 4 of 14 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[l].qry ROW LINE VOLTS DEG CHN IND %TW LOCA 37 61 0.36 154 P2 TWD 14 VSM 37 71 0.66 15 2
SAI TSH 37 103 0.54 23 P3 TWD 22 DBH 38 28 0.23 90 2
SAI 0H 0.44 68 2
SAI 05H 38 110 0.79 13 2
SAI TSH 0.55 12 2
SAI TSH TION EXT EXT CAL # LEG PROBE
+0.93 TEH TEC 38 COLD 60OUL
-2.58 TSH TSH 93 HOT 580PP
-2.10 TEC TEH 35 HOT 60OUL
+0.33 01H 01H 169 HOT 580PP
-0.67 05H 05H 169 HOT 580PP
-1.44 TSH TSH 64 HOT 580PP
-0.65 TSH TSH 64 HOT 58OPP 39 43 0.46 10 P3 TWD 17 DBC
+1.33 TEC TEH 13 HOT 60OUL 39 71 0.35 128 P3 TWD 13 DBC
-1.55 TEH TEC 38 COLD 60OUL 40 58 0.41 15 2
SAI TSH
-3.72 TSH TSH 88 HOT 58OPP 40 162 0.31 120 2 SAI 06H
+0.25 06H 06H 158 HOT 580PP 41 7
0.40 137 P2 TWD 16 VSM
-0.77 TEC TEH 25 HOT 60OUL 41 39 0.71 12 P1 SCI TSH
-1.42 TSH TSH 48 HOT 580PP 41 69 0.69 11 2
SAI TSH
-2.14 TSH TSH 93 HOT 58OPP 41 73 0.41 110 P2 TWD 17 VSM
+0.93 TEH TEC 39 COLD 60OUL 0.23 34 P3 TWD 9 DBC
+1.43 TEH TEC 39 COLD 60OUL 41 101 0.17 85 P3 TWD 6 DBH
-1.79 TEC TEH 28 HOT 60OUL 0.22 53 P3 TWD 8 DBC
+1.91 TEC TEH 28 HOT 60OUL 42 14 0.16 140 2 SAI DBH
-0.81 DBH DBH 130 COLD 560P2 0.20 122 2 SAI DBH
-0.11 DBH DBH 130 COLD 560P2 42 74 0.36 86 P3 TWD 13 DBC
+1.32 TEH TEC 39 COLD 600UL 0.32 34 P3 TWD 12 DBC
-1.68 TEH TEC 39 COLD 600UL 42 106 0.71 126 P2 TWD 30 VSM
-0.98 TEC TEH 35 HOT 60OUL 0.46 14 2
SAI TSH
-1.18 TSH TSH 64 HOT 580PP 42 158 0.21 152 P3 TWD 11 DBH
+1.72 TEC TEH 19 HOT 60OUL 43 19 0.59 95 P2 TWD 25 02H
+0.87 TEC TEH 22 HOT 60OUL 43 51 0.93 105 P2 TWD 31 VSM
+0.88 TEH TEC 37 COLD 600UL 43 57 0.37 57 P3 TWD 13 DBH
+1.68 STH TEC 41 COLD 60OUL 0.22 46 P3 TWD 8 DBC
+1.72 STH TEC 41 COLD 60OUL 43 73 0.27 82 P3 TWD 11 DBC
-1.89 TEH TEC 38 COLD 600UL 0.65 15 2
SAI TSH
-3.90 TSH TSH 93 HOT 58OPP 43 101 0.34 58 P3 TWD 12 DBC
-1.68 TEC TEH 27 HOT 600UL 0.55 176 P3 TWD 19 DBC
+1.66 TEC TEH 27 HOT 600UL 43 125 0.57 106 P2 TWD 23 VSM
-0.84 TEH TEC 50 COLD 60OUL 44 58 0.22 21 P2 TWD 10 VSM
-1.08 TEH TEC 39 COLD 600UL 0.47 109 P2 TWD 19 VSM
+0.86 TEH TEC 39 COLD 600UL 44 108 0.27 81 P2 TWD 13 VSM
+0.87 TEC TEH 36 HOT 60OUL 0.34 132 P2 TWD 16 VSM
-0.77 TEC TEH 36 HOT 60OUL 44 124 0.38 107 P2 TWD 17 VSM
-0.95 TEH TEC 50 COLD 60OUL 45 73 0.38 126 P3 TWD 13 DBC
-1.61 STH TEC 41 COLD 60OUL 45 145 0.24 80 P2 TWD 12 VSM
+0.88 TEC TEH 15 HOT 60OUL 46 6
0.26 141 P3 TWD 13 DBC
+1.63 TEC TEH 26 HOT 60OUL 0.41 39 P2 TWD 19 VSM
-0.75 TEC TEH 26 HOT 60OUL 46 148 0.24 122 2 SAI 01H
-0.16 0H 01H 155 HOT 58OPP 47 109 0.38 90 P2 TWD 14 VSM
-0.02 STH TEC 41 COLD 60OUL 0.45 107 P2 TWD 16 VSM
+0.88 STH TEC 41 COLD 600UL 47 111 0.35 11 2
SAI TSH
-3.12 TSH TSH 64 HOT 58OPP
AREVA NP Inc Customer Name: San Onofre -
Unit 2 01/09/08 14:19:36 Component:
S/G 88 Page 5 of 14 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[l].qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.84 19 2
SAI TSH
-0.87 TS1 TSH 64 HOT 58OPP 47 125 0.36 77 P2 TWD 16 VSM
+0.78 TEH TEC 50 COLD 600UL 47 143 0.15 78 2
SAI 01H
-0.03 01H 01H 155 HOT 580PP 48 76 0.58 90 P3 TWD 19 DBC
-1.75 TEC TEH 27 HOT 600UL 0.18 7
P3 TWD 6 DBH
+1.47 TEC TEN 27 HOT 60OUL 48 114 0.29 139 P3 TWD 14 DBH
-1.59 TEH TEC 49 COLD 60OUL 48 124 0.28 25 P1 SCI TSH
-0.10 TSH TSH 65 HOT 580PP 48 134 0.57 19 P1 SCI TSN
-0.07 TSH TSH 78 HOT 580PP 49 47 0.14 105 2 SAI 08C
-1.17 08C 08C 113 COLD 580PP 49 69 0.41 113 P2 TWD 16 08C
-1.22 TEH TEC 38 COLD 600UL 49 75 0.41 88 P3 TWD 17 DBH
-1.78 TEN TEC 36 COLD 600UL 50 8
0.28 131 P2 TWD 14 VSM
+0.77 TEC TEH 26 HOT 600UL 50 98 0.52 70 P2 TWD 22 VSM
-0.92 TEC TEH 28 HOT 60OUL 50 102 0.40 15 2
SAI 13W
-0.42 TSN TSN 127 NOT 580PP 50 106 0.41 13 2
SAI TSH
-0.07 TSH TSH 127 HOT 580PP 50 110 0.23 60 P2 TWD 12 08H
+0.87 TEC TEN 31 HOT 60OUL 50 148 0.38 101 2 SAI 08H
+0.81 08H 08H 155 HOT 58OPP 50 164 0.40 115 P2 TWD 18 VSM
+0.82 TEC TEH 20 HOT 600UL 51 55 0.29 114 P1 SCI TSH
+0.03 TSH TSH 87 HOT 58OPP 51 57 0.36 94 P1 SCI TSH
+0.06 TSH TSH 87 HOT 580PP 51 81 0.85 121 P3 TWD 26 DBC
-1.61 TEC TEH 27 HOT 600UL 0.46 169 P3 TWD 16 DBH
+1.43 TEC TEH 27 HOT 600UL 0.58 142 P3 TWD 19 DBH
-1.55 TEC TEH 27 HOT 60OUL 0.79 133 P3 TWD 25 DBC
+1.85 TEC TEH 27 HOT 600UL 51 117 0.69 21 P1 SCI TSH
-0.10 TSH TSH 64 HOT 58OPP 51 155 0.21 108 2 SAI 04H
+0.75 04H 04H 155 HOT 58OPP 51 163 0.39 41 P2 TWD 17 VH3
+0.90 TEC TEH 20 HOT 600UL 52 72 0.17 105 2 52 76 0.37 60 P3 52 112 0.79 15 2
0.51 12 2
0.67 15 2
0.45 13 2
SAI TSH TWD 13 DBC SAI TSH SAI TSH SAI TSH SAI TSH
+0.23 TSH TSH 94 HOT 580PP 53 57 0.28 98 P1 MCI TSH
+
53 113 0.68 14 2
SAI TSH 0.43 12 2
SAT TSH 0.74 14 2
SAi ISE 54 8
0.39 124 P2 TWD 18 01H
+
0.18 123 P2 TWD 10 01H 54 38 0.49 20 P1 SCI TSH 54 60 0.17 112 2 SAI TSH
+
54 72 0.20 79 P!
SCI TSH
+
54 76 0.41 48 P3 TWD 14 DBC 1.55 TEC TEN 27 HOT 60OUL 1.87 TSH TSH 65 HOT 580PP 2.57 TSH TSH 65 HOT 58OPP 3.37 TSH TSH 65 HOT 580PP 3.67 TSH TSH 65 HOT 580PP 0.15 1S3 TSH 88 HOT 580PP 5.31 TSH TSH 64 HOT 580PP 3.74 TSH TSH 64 HOT 58OPP 1.74 TSH TSH 64 HOT 58OPP 0.06 TEC TEN 26 HOT 600UL 1.06 TEC TEN 26 HOT 600UL 0.02 TSH TSH 49 HOT 580PP 0.15 TSH TSH 90 HOT 580PP 0.06 TSH TSH 93 HOT 580PP 1.65 TEC TEE 28 HOT 60OUL 1.84 TEC TEH 27 HOT 600UL 1.77 STH TEC 41 COLD 60OUL 54 92 0.10 44 P3 TWD 4 DBH 54 96 0.63 80 P3 TWD 20 DBH
AREVA NP Inc 01/09/08 14:19:36 Customer Name: San Onofre -
Unit 2 Component:
S/G 88 Page 6 of 14 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[l].qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 55 81 0.43 126 P3 TWD 15 DBH
-1.59 TEC TEH 27 HOT 600UL 55 91 0.61 128 P3 TWD 20 DBH
-1.67 TEC TEH 27 HOT 600UL 55 95 0.58 171 P3 TWD 19 DBC
+1.68 TEC TEH 27 HOT 60OUL 56 78 0.21 111 P3 TWD 8 DBH
-1.47 TEC TEH 28 HOT 600UL 56 80 0.92 141 P3 TWD 27 DBC
-2.00 TEC TEH 27 HOT 600UL 0.59 95 P3 TWD 20 DBH
-1.52 TEC TEH 27 HOT 600UL 0.27 11 P3 TWD 12 DBH
+1.75 TEC TEH 27 HOT 600UL 56 112 0.27 31 P3 TWD 12 DBH
-2.07 TEC TEH 31 HOT 60OUL 56 126 0.39 21 P!
SCI TSH
-0.17 TSH TSH 65 ROT 580PP 56 154 0.53 10 2
SAI TSH
-7.34 TSH TSH 85 HOT 580PP 57 73 0.12 103 21 SCI TSH
+0.09 TSH TSH 94 HOT 580PP 57 91 0.18 142 P3 TWD 8 DBC
-1.66 STH TEC 42 COLD 600UL 57 97 0.73 19 P3 TWD 23 DBH
+1.72 TEC TEH 28 HOT 60OUL 57 105 0.41 20 2
SAI TSH
-2.35 TSH TSH 59 HOT 580PP 57 109 0.37 78 P2 TWD 18 03H
-1.21 TEC TEH 31 HOT 600UL 57 161 0.41 114 2 SAI 06H
-0.41 06H 06H 155 HOT 580PP 57 167 0.52 147 P2 TWD 23 02C
+0.89 T.C TEH 23 HOT 600UL 58 70 0.65 19 2
SAI TSH
-2.27 TSH TSH 93 HOT 580PP 58 96 0.38 147 P3 TWD 15 DBH
-1.80 TEC TEH 27 HOT 600UL 58 100 0.40 57 P2 TWD 18 VSM
-0.80 TEC TEH 28 HOT 600UL 59 23 0.48 100 P2 TWD 19 VH3
-0.92 TEC TEH 21 HOT 600UL 59 25 0.41 155 P2 TWD 18 VH3
+0.84 TEC TEH 18 HOT 60OUL 0.35 138 P2 TWD 15 VH3
-0.82 TEC TEH 18 HOT 600UL 59 83 0.56 18 2
SAI TSH
-1.40 TSH TSH 50 HOT 58OPP 0.30 19 2
SAI TSH
-0.87 TSH TSH 50 HOT 580PP 59 95 0.28 22 P3 TWD 10 DBC
+1.58 TEC TEH 28 HOT 60OUL 59 161 0.41 80 P2 TWD 17 VH3
-0.90 TEC TEH 19 HOT 600UL 60 86 0.23 88 2
SAI VC3
+0.84 VC3 VC3 118 COLD 560P2 0.40 91 P2 TWD 16 VC3
+0.84 STH TEC 42 COLD 600UL 0.49 12 P3 TWD 17 DBH
+1.91 STH TEC 42 COLD 600UL 60 106 0.31 25 P1 SCI TSH
-0.00 TSH TSH 59 HOT 580PP 61 27 0.28 20 P2 TWD 12 VH3
-0.70 TEC TEH 18 HOT 60OUL 61 45 0.20 132 P3 TWD 9 DBC
+0.75 TEC TEH 13 HOT 600UL 61 85 0.27 160 P3 TWD 11 DBC
-1.58 TEC TEN 27 HOT 600UL 0.56 169 P3 TWD 20 DBC
+1.78 TEC TEH 27 HOT 600UL 61 87 0.32 154 23 TWD 11 DBC
-1.98 TEC TEH 27 HOT 60OUL 1.11 23 P3 TWD 31 DBH
+1.75 TEC TEH 27 HOT 600UL 61 125 0.27 143 P2 TWD 12 VC3
-0.10 TEC TEH 32 HOT 600UL 62 80 0.22 73 P1 SCI TSH
+0.03 TSH TSR 51 HOT 580PP 62 114 0.58 18 2
SAT TSH
-2.04 TSH TSH 60 HOT 58022 64 80 0.53 117 P3 TWD 18 DBH
+1.21 TEC TEH 27 HOT 60OUL 64 106 5.92 183 4
PCS SBH
+5.04 TO+13.33 STH SBH 101 HOT 500SP 64 120 0.47 26 P1 SCI TSH
-0.03 TSH TSH 59 HOT 580P2 65 81 0.22 108 P3 TWD 8 DBC
-1.22 TEC TEH 28 HOT 600UL 0.14 125 P3 TWD 6 DBC
+2.00 TEC TEH 28 HOT 600UL
AREVA NP Inc Customer Name: San Onofre -
Unit 2 01/09/08 14:19:36 Component:
S/G 88 Page 7 of 14 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAT, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[l].qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 65 87 0.14 78 P1 SCI TSH
+0.06 65 91 0.21 26 P2 TWD 8 VH3
+0.70 65 111 0.41 21 P1 SCI TSH
-0.15 0.75 17 2
SAI TSH
-1.11 66 48 0.41 130 P2 TWD 18 VC3
-0.85 0.31 136 P2 TWD 15 VSM
+0.90 0.56 103 92 TWD 23 VSM
-0.90 67 81 0.62 91 P3 TWD 21 DBC
-1.35 TSH TSH 51 HOT 580PP TEC TEH 27 HOT 600UL TSH TSH 59 HOT 58OPP TSH TSH 59 HOT 580PP TEC TEN 34 ROT 600UL TEC TEH 34 HOT 600UL TEC TEH 34 HOT 600UL TEC TEH 27 HOT 600UL 67 87 0.30 28 P3 TWD 11 DBH
+1.60 TEC TEH 27 HOT 600UL 0.36 148 P3 TWD 13 DBE
-1.36 TEC TEH 27 HOT 600UL 67 111 0.16 103 P1 SCI TSH
+0.16 TSH TSH 60 HOT 58OPP 67 165 0.78 119 P2 TWD 30 VH3
-0.86 TEC TEH 23 HOT 600UL 68 112 0.55 24 P1 MCI TSH
-6.12 TSH TSH 127 HOT 580PP 0.30 18 PT SCI TSH
-9.88 TSH TSH 127 HOT 580PP 68 146 0.53 73 P2 TWD 21 VC3
-0.84 TEC TEH 15 HOT 600UL 68 164 0.57 102 P2 TWD 23 VH3
+0.63 TEC TEH 20 HOT 600UL 69 85 0.24 132 P3 TWD 8 DBC
-1.73 TEC TEH 27 HOT 60OUL 69 87 0.41 134 P3 TWD 15 DBH
+2.00 STH TEC 42 COLD 600UL 69 119 0.51 21 P1 SCI TSH
-0.03 TSH TSH 59 HOT 58OPP 0.37 20 P1 SCI TSH
-0.02 TSH TSH 59 HOT 58OPP 70 82 0.31 159 P3 TWD 11 DBC
+1.88 TEC TEH 28 HOT 600UL 70 86 0.34 51 P3 TWD 13 DBH
-1.42 TEC TEH 27 HOT 60OUL 0.50 15 2
SAI TSH
-2.15 TSH TSH 50 HOT 580PP 0.46 11 2
SAI TSH
-1.84 TSH TSH 50 HOT 580PP 70 104 0.29 109 2 SAI TSH
+0.17 TSH TSH 60 HOT 58OPP 71 13 0.55 123 P2 TWD 21 VH3
-0.79 TEC TEH 21 HOT 60OUL 72 70 0.31 87 P2 TWD 15 VC3
-0.93 TEC TEH 38 HOT 600UL 72 90 0.56 126 P2 TWD 22 VSM
+0.74 TEC TEH 27 HOT 600UL 0.27 29 P2 TWD 11 VSM
-0.98 TEC TEH 27 HOT 600UL 72 100 0.33 132 P1 SCI TSH
+0.05 TSH TSH 50 HOT 580PP 73 17 0.59 98 P2 TWD 22 VH3
-0.82 TEC TEH 21 HOT 600UL 73 75 0.33 135 P2 TWD 15 VC3
+0.60 TEC TEH 38 HOT 60OUL 73 133 0.41 110 P2 TWD 18 VH3
+0.81 TEC TEH 12 HOT 600UL 73 161 0.46 128 P2 TWD 19 VH3
+1.21 TEC TEH 20 HOT 600UL 74 148 0.22 83 P2 TWD 10 VH3
-0.92 TEC TEH 16 HOT 600UL 75 95 0.63 28 P1 SCI TSH
-0.19 TSH TSH 51 HOT 580PP 75 99 0.24 97 P1 SCI TSH
+0.08 TSH TSH 51 HOT 58OPP 75 141 0.33 129 P2 TWD 75 157 0.28 116 P2 TWD 76 18 0.22 96 2
SAI 76 84 0.34 121 P2 TWD 0.35 55 P2 TWD 76 86 0.24 23 P3 TWD 77 31 0.36 131 P2 TWD 0.24 105 22 TWD 14 VH3
-0.93 TEC TEH 16 HOT 600UL 13 VH3
-0.79 TEC TEH 20 HOT 600UL 06H
+0.62 06H 06H 169 HOT 580PP 14 VH3
+0.76 TEC TEH 27 HOT 600UL 15 VH3
-0.84 TEC TEH 27 HOT 600UL 9
DBC
+2.25 TEC TEH 28 HOT 600UL 14 VSM
+0.88 TEC TEH 17 HOT 600UL 11 VSM
+0.33 TEC TEH 17 HOT 60OUL
AREVA NP Inc Customer Name:
San Onofre -
Unit 2 01/09/08 14:19:36 Component: S/G 88 Page 8 of 14 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[ll.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION 77 33 0.41 42 P2 TWD 18 VSM
+0.93 77 39 0.21 135 P3 TWD 11 DBC
+1.57 77 85 0.68 15 2
SAI TSH
-1.92 77 161 0.57 134 P2 TWD 22 VH3
-0.84 78 22 0.56 84 P2 TWD 24 VC3
-0.92 0.53 37 P3 TWD 23 DBC
-1.80 78 74 0.32 20 P1 SCI TSH
-0.06 78 96 0.20 114 P1 SCI TSH
+0.11 78 98 0.38 25 P1 SCI TSH
-0.10 EXT EXT CAL # LEG PROBE TEC TEH 18 HOT 600UL TEC TEH 14 HOT 600UL TSH TSH 50 HOT 580PP TEC TEH 20 HOT 60OUL TEC TEN 22 NOT 600UL TEC TEH 22 HOT 600UL TSN TSH 94 HOT 580PP TSN TSH 51 HOT 58OPP TSH TSH 51 HOT 58OPP 78 102 0.53 28 P1 SCI TSH
+0.00 TSH TSH 59 HOT 580PP 78 120 0.39 29 P1 SCI TSH
-6.00 TSH TSH 60 HOT 580PP 78 138 0.31 41 P3 TWD 14 DBC
+1.47 TEC TEH 12 HOT 60OUL 78 142 0.39 128 P2 TWD 16 VH3
+0.87 TEC TEH 16 HOT 600UL 78 144 0.66 47 P3 TWD 21 DBC
+1.65 TEC TEH 16 HOT 600UL 78 148 0.49 140 P2 TWD 20 08C
-0.92 TEC TEH 16 HOT 600UL 78 154 0.45 128 P2 TWD 19 VC3
+0.82 TEC TEH 20 HOT 60OUL 0.25 162 P2 TWD 12 VC3
-0.80 TEC TEH 20 HOT 600UL 79 15 0.41 19 P3 TWD 16 DBH
+1.45 TEC TEH 21 HOT 60OUL 79 19 0.23 40 P3 TWD 10 DBC
+1.84 TEC TEH 21 HOT 600UL 79 23 0.28 79 P3 TWD 12 DBC
+1.80 TEC TEH 21 HOT 600UL 79 81 0.17 22 P1 SCI TSH
-0.05 TSH TSH 50 HOT 580PP 79 97 0.37 120 P1 SCI TSH
+0.03 TSH TSH 50 HOT 580PP 79 143 0.18 111 P3 TWD 11 DBC
-1.50 TEC TEH 15 HOT 600UL 80 84 0.24 16 P1 SCI TSH
-0.08 TSH TSH 50 HOT 58OPP 80 112 0.32 81 23 0.37 81 93 0.61 81 151 0,35 0,12 82 54 0,74 0,13 82 160 0,25 83 49 0,32 83 87 0,45 115 54 P2 TWD 17 VSM
-0.84 TEC TEH 31 HOT 60OUL P3 TWD 15 DBC
+1.55 TEC TEH 7
HOT 600UL 15 2
SAI TSH
-2.60 TSH TSH 114 HOT 129 P2 TWD 16 VH3
+0.57 TEC TEH 11 HOT 29 P2 TWD 5 VH3
-0.21 TEC TEH 11 HOT 96 P2 TWD 25 VH3
-0.70 TEH TEC 16 COLI 170 P2 TWD 6 VH3
+0.91 TEH TEC 16 COLI 91 P3 TWD 13 DBH
+2.02 TEC TEN 11 HOT 104 2 SAI 02H
+2.02 02H 02H 173 HOT 580PP 600UL 600UL D
600UL D
600UL 600UL 580PP 25 PI SCI TSH 83 99 0,12 123 P3 TWD 5 DBH 84 48 0,64 92 P2 TWD 24 09C 85 43 0,56 131 P2 TWD 19 VH2 86 32 0,17 164 P3 TWD 7 DBC 86 54 0,24 119 P2 TWD 11 VH2 86 130 0.34 94 P2 TWD 17 VC2
-0.12
-1.75 TSH TSH 118 HOT 580PP TEN TEC 23 COLD 600UL TEH TEC 17 COLD 600UL TEC TEH 9
HOT 600UL
-1.50
-1.12
+1.75
-0.77
+--0-66 TEC TEH 7
TEH TEC 16 TEC TEH 6
HOT 600UL COLD HOT 600UL 600UL 87 37 0,36 131 P2 TWD 17 7H2
-0.94 0.38 133 P2 TWD 18 VH2
-1.06 87 63 0,42 116 P3 TWD 17 DBH
-0.25 TEC TEN 10 NOT 600Ut TEC TEN 10 HOT 600UL TEH TEC 19 COLD 600UL
AREVA NP Inc Customer Name: San Onofre -
Unit 2 01/09/08 14:19:36 Component:
S/G 88 Page 9 of 14 Post U2C15 Inspection Final Report MAT, MCI, MNT, NVI, SAT, SCI, EVI, 0-100%, PCS QUERY: QueryMlil].gry ROW LINE VOLTS DEG CHN IND
%TW LOCATION 88 60 0.20 91 2
SAI 01H 88 154 0.53 51 P2 TWD 22 VH2 89 35 0.43 94 P2 TWD 16 VH2 89 37 0.56 129 P2 TWD 19 VH2 89 51 0.32 73 P2 TWD 15 VH3 0.42 22 P3 TWD 17 DBH EXT EXT CAL # LEG PROBE
- ====::-=---=---- --
==
- =
==
-=====-===*===:
+2.27 01H 01H 178 HOT 580PP
-0.83 TEC TEH 12 HOT 600UL
-0.93 TEC TEH 7
HOT 60OUL
-0.96 TEC TEH 9
HOT 600UL
+0.80
-1.85 TEH TEC 17 TEH TEC 17 COLD 60OUL COLD 60OUL 89 157 0.18 145 P3 TWD 10 DBH
+1.90 TEC TEH 11 HOT 600UL 90 42 0.24 104 2 SAI VC2
+0.12 VC2 09C 114 COLD 560P2 0.26 118 2 SAI 08H
+0.75 08H 08H 173 HOT 580PP 90 78 0.27 17 P1 SCI TSH
-0.11 TSH TSH 120 HOT 580PP 91 55 0.35 63 P2 TWD 16 VH2
+0.84 TEH TEC 17 COLD 60OUL 91 125 0.36 125 P2 TWD 16 VH2
-0.86 TEH TEC 29 COLD 60OUL 92 26 0.64 86 P2 TWD 25 VH2
-0.79 TEC TEH 8
HOT 600UL 92 36 0.56 87 P2 TWD 23 VH2
-0.89 TEC TEH 10 HOT 600UL 92 56 0.23 102 P2 TWD 12 09H
-0.64 TEH TEC 17 COLD 600UL 93 65 0.35 122 P2 TWD 16 VH2
-0.70 TEH TEC 19 COLD 600UL 93 153 0.37 68 P2 TWD 17 03C
+0.95 TEC TEH 12 HOT 60OUL 0.47 66 P2 TWD 20 05C
-0.89 TEC TEH 12 HOT 600UL 0.19 84 P2 TWD 10 VC3
-0.96 TEC TEH 12 HOT 600UL 94 24 0.41 131 P2 TWD 15 VH2
+1.12 TEC TEH 7
HOT 60OUL 94 40 0.38 119 P2 TWD 15 VH2
+1.12 TEC TEH 9
HOT 600UL 94 48 0.24 106 2 SAI 01H
+0.21 01H 01H 172 HOT 580PP 95 71 0.30 19 P1 SCI TSH
-0.08 TSH TSH 111 HOT 580PP 97 35 0.49 145 P2 TWD 18 VH2
-0.98 TEC TEH 7
HOT 600UL 98 44 0.25 27 P3 TWD 13 DBH
-2.20 TEC TEH 10 HOT 600UL 0.41 70 P2 TWD 18 VSM
+0.75 TEC TEH 10 HOT 600UL 98 94 0.22 89 P1 SCI TSH
+0.00 TSH TSH 114 HOT 580PP 99 49 0.27 18 P3 TWD 11 DBH
-2.00 TEH TEC 17 COLD 600UL 99 131 0.23 150 P2 TWD 12 VH3
+0.67 0.41 102 P2 TWD 19 VH3
-1.01 99 149 0.59 114 P2 TWD 24 VH2
+0.00 TEC TEN 6
NOT 600UL TEC TEH 6
HOT 600UL TEC TEH 11 HOT 600UL 100 102 0.19 21 P1 SCI TSH
-0.07 TSH TSH 54 HOT 58OPP 100 118 0.39 32 P1 SCI TSH
+0.00 TSH TSH 57 HOT 58OPP 101 29 0.45 137 P2 TWD 20 VH2
+0.77 TEC TEH 8
HOT 600UL 101 77 0.49 95 P3 TWD 18 DBH
+1.15 TEH TEC 21 COLD 600UL 101 147 0.56 147 P2 TWD 24 VSE
-0.74 TEC TEH 5
HOT 600UL 102 26 0.33 112 P2 TWD 16 06H
+0.87 TEC TEH 8
HOT 600UL 104 40 0.35 49 P3 TWD 17 DBC
+2.03 TEC TEH 10 HOT 600UL 105 99 106 30 106 106 76 78 0.40 132 P2 TWD 17 03H
+0.74 TEH TEC 23 COLD 60OUL 0.34 122 P2 TWD 14 06H
+0.81 TEC TEH 7
HOT 600UL 0.36 54 P2 TWD 15 02H
-0.20 TEH TEC 21 COLD 600UL 0.21 149 P2 TWO 10 VC2
-0.78 TEN TEC 20 COLD 600UL 0.26 149 P2 TWD 11 VC2
+0.89 TEH TEC 20 COLD 60OUL
AREVA NP Inc 01/09/08 14:19:36 Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 10 of 14 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[13.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 107 29 0.55 9
P3 TWD 23 DBC
+1.29 TEC TEH 8
HOT 600UL 107 33 0.22 107 P2 TWD 12 09H
-0.37 TEC TEH 8
HOT 60OUL 107 75 0.34 66 P2 TWD 14 09C
-0.29 TEH TEC 7
COLD 60OUL 107 95 0.31 126 P2 TWD 13 VH2
+0.82 TEH TEC 23 COLD 60OUL 107 97 0.28 135 P1 SCI TSH
+0.03 TSH TSH 114 HOT 580PP 0.29 115 P2 TWD 12 VH3
-0.88 TEH TEC 22 COLD 600UL 107 125 0.46 111 P2 TWD 19 VN2
-0.69 TEN TEC 29 COLD 60OUL 0.22 101 23 TWD 9 DBH
-1.42 TEH TEC 29 COLD 600UL 108 36 0.32 79 P3 TWD 15 DBC
-1.80 TEC TEH 10 HOT 60OUL 108 142 0.16 151 P3 TWD 8 DBE
+1.66 TEC TEH 6
HOT 600UL 109 77 0.26 132 P2 TWD 11 VH2
+0.82 TEH TEC 21 COLD 600UL 1i0 52 0.19 97 P3 TWD 9 DBH
-1.33 TEH TEC 16 COLD 600UL 110 96 0.23 91 P3 TWD 9 DBH
+2.24 TEH TEC 23 COLD 600UL 110 138 0.37 116 P2 TWD 18 VC3
-0.90 TEC TEH 6
HOT 600UL I11 33 0.15 11 P3 TWD 8 DBH
+1.75 TEC TEN 8
HOT 600UL 111 37 0.29 20 P3 TWD 14 DBH
+1.85 TEC TEH 10 HOT 60OUL 111 67 0.46 115 2 SAI 02H
+1.06 02H 02H 178 HOT 580PP 11 81 0.23 142 P3 TWD 10 DBH
+2.24 TEN TEC 21 COLD 600UL il1 101 0.21 56 P3 TWD 8 DBH
-0.75 TEH TEC 23 COLD 600UL 112 92 0.35 32 P2 TWD 15 VH2
-0.70 TEH TEC 23 COLD 600UL 112 116 0.15 47 P2 TWD 7 VH3
-0.85 TEH TEC 30 COLD 600UL 112 144 0.86 158 P3 TWD 30 DBH
+2.13 TEC TEH 5
HOT 600UL 113 37 0.36 135 P2 TWD 14 VH2
-0.93 TEC TEN 9
HOT 600UL 0.17 138 P3 TWD 8 DBH
+1.84 TEC TEH 9
HOT 600UL 113 39 0.42 109 P3 TWD 17 DBH
+1.98 TEC TEH 9
HOT 600UL 113 41 0.47 94 P2 TWD 17 VH2
-0.68 TEC TEH 9
HOT 600UL 113 47 0.25 35 P3 TWD 11 DBH
-1.34 TEH TEC 17 COLD 600UL 113 87 0.16 144 P3 TWD 6 DBH
-1.52 TEH TEC 23 COLD 60OUL 114 38 0.30 138 P2 TWD 12 06C
-0.69 TEC TEH 9
HOT 600UL 114 86 0.12 164 P3 TWD 4 DBH
-1.37 TEH TEC 23 COLD 600UL 114 96 0.32 102 P2 TWD 13 VH3
-0.82 TEH TEC 24 COLD 600UL 114 110 0.31 44 P3 TWD 14 DBH
-1.57 TEH TEC 30 COLD 600UL 115 83 0.36 138 P3 TWD 14 DBH
-1.54 TEH TEC 21 COLD 600UL 115 93 0.25 121 P3 TWD 13 DBE
-1.23 TEN TEC 24 COLD 600UL 115 101 0.18 46 23 TWD 7 DBH
+2.15 TEH TEC 23 COLD 600UL 115 137 0.64 36 P2 TWD 26 VHN
-0.98 TEC TEH 5
HOT 600UL 116 64 0.20 104 P3 TWD 9 DBH
-1.13 TEH TEC 19 COLD 600UL 116 92 0.23 119 P2 TWD 10 04H
+0.86 TEH TEC 23 COLD 600UL 116 102 0.41 125 P3 TWD 15 DBH
+0.93 TEh TEC 33 COLD 600UL 117 55 0.66 124 P2 TWD 25 VHI
-0.72 TEH TEC 17 COLD 600UL 117 67 0.42 124 P2 TWD 18 VHI
-0.78 TEH TEC 19 COLD 60OUL 117 95 0.20 55 P3 TWD 10 DBH
+1.98 TEH TEC 24 COLD 60OUL
AREVA NP Inc 01/09/08 14:19:36 Customer Name: San Onofre -
Unit 2 Component:
S/G 88 Page 11 of 14 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryM!(1].qry ROW LINE VOLTS DEG CHN IND
%TW LOCATION EXT EXT CAL # LEG PROBE
- - - -----= --------------= ------
=
--= --= --=
=
-=
=-
== = = =-
=-
== = = = =-
-==
=-
=:
118 38 0.14 133 P3 TWD 6 DBC
+1.94 TEC TEH 9
NOT 600UL 118 68 0.23 77 P3 TWD 11 DBE
-1.69 TEH TEC 18 COLD 600UL 118 72 0.18 36 P3 TWD 7 DBH
+1.88 TEH TEC 20 COLD 60OUL 0.24 143 P3 TWD 11 DBH
-1.98 TEH TEC 20 COLD EODUL 118 88 0.42 149 P3 TWD 17 DBH
-1.64 TEH TEC 22 COLD 60OUL 118 90 0.20 37 P3 TWD 9 DBE
-1.98 TEH TEC 22 COLD 600UL 119 37 0.11 53 P3 TWD 6 DBC
-2.11 TEC TEH 10 HOT 60OUL 0.31 11 P3 TWD 15 DBC
+2.15 TEC TEH 10 HOT 60OUL 0.18 22 P2 TWD 10 10C
-1.33 TEC TEH 10 HOT 600UL 119 55 0.35 89 P3 TWD 15 DBH
+2.15 TEH TEC 16 COLD 600UL 119 79 0.49 119 P3 TWD 19 DBH
+2.02 TEH TEC 20 COLD 60OUL 119 95 0.49 103 P3 TWD 21 DBH
-1.83 TEH TEC 24 COLD 600UL 119 97 0.39 137 P3 TWD 15 DBH
-1.57 TEH TEC 25 COLD 60OUL 119 99 0.33 126 P3 TWD 16 DBH
-1.93 TEH TEC 24 COLD 60OUL 119 101 0.37 115 P3 TWD 14 DBH
-1.74 TEH TEC 23 COLD 60OUL 119 109 0.47 15 P3 TWD 20 DBH
+1.91 TEH TEC 30 COLD 60OUL 120 38 0.19 148 P3 TWD 10 DBC
-1.82 TEC TEH 10 HOT 600UL 0.22 117 P3 TWD 11 DBC
+2.25 TEC TEH 10 HOT 600UL 120 48 0.30 84 P2 TWD 14 VH2
-0.76 TEH TEC 17 COLD 60OUL 120 66 0.46 107 P3 TWD 19 DBH
-1.32 TEH TEC 18 COLD 60OUL 120 74 0.23 101 P2 TWD 10 10H
-1.19 TEH TEC 20 COLD 60OUL 120 78 0.30 135 P2 TWD 13 VHN
-0.73 TEH TEC 21 COLD 60OUL 120 80 0.27 63 P3 TWD 12 DBH
-1.96 TEH TEC 20 COLD 600UL 120 86 0.24 115 P3 TWD 11 DBH
-1.60 TEH TEC 22 COLD 600UL 0.35 103 P2 TWD 15 10H
+1.25 TEH TEC 22 COLD 60OUL 120 92 0.33 91 P3 TWD 13 DBH
-2.11 TEH TEC 23 COLD 600UL 120 94 0.11 135 P3 TWD 6 DBH
-1.95 TEH TEC 24 COLD 600UL 120 106 0.88 154 P3 TWD 24 DBH
+1.84 TEH TEC 32 COLD 60OUL 120 138 0.50 128 P3 TWD 21 DBH
-1.87 TEC TEH 5
HOT 600UL 121 39 0.41 72 P2 TWD 19 03C
-0.91 TEC TEH 10 HOT 600UL 121 67 0.25 94 P3 TWD 11 DBH
-1.75 TEH TEC 19 COLD 60OUL 121 69 0.30 17 P2 TWD 14 04H
+0.83 TEH TEC 19 COLD 600UL 121 71 0.22 137 P3 TWD 10 DBH
-1.60 TEH TEC 19 COLD 600UL 121 125 0.44 137 P2 TWD 17 10H
+0.73 TEH TEC 28 COLD 600UL 121 137 0.26 153 P3 TWD 13 DBH
-1.85 TEC TEH 5
NOT 60OUL 122 76 0.55 110 P2 TWD 21 VHl
+0.00 TEH TEC 21 COLD 600UL 122 94 0.32 145 P3 TWD 15 DBH
+1.92 TEH TEC 24 COLD 60OUL 122 96 0.46 141 P3 TWD 20 DBH
+1.93 TEH TEC 24 COLD 600UL 122 98 0.61 108 P2 TWD 22 l0H
+1.21 TEH TEC 24 COLD 600UL 0.24 140 P3 TWD 12 DBH
+1.95 TEH TEC 24 COLD 600UL 122 112 0.25 109 P2 TWD 11 10H
-1.16 TEN TEC 30 COLD 600UL 122 114 0.42 77 P2 TWD 17 10H
+0.95 TEH TEC 31 COLD 600UL 0.35 149 P3 TWD 13 DBH
+1.52 TEN TIC 31 COLD 600UL
AREVA NP Inc 01/09/08 14:19:37 Customer Name: San Onofre -
Unit 2 Component:
S/G 88 Page 12 of 14 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, EVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryM![l.qry ROW LINE VOLTS DEG CHN IND
%TW LOCATION EXT EXT CAL # LEG PROBE 122 124 0.46 128 P3 TWD 20 DBE
+1.84 TEH TEC 28 COLD 600UL 123 65 0.31 117 P3 TWD 14 DBH
-0.35 TEH TEC 18 COLD 600UL 124 64 0.54 107 P2 TWD 22 10H
-1.07 TEH TEC 19 COLD 60OUL 124 88 0.34 56 P3 TWD 13 DBH
+1.98 TEE TEC 23 COLD 600UL 125 91 0.33 140 P3 TWD 13 DBH
+1.87 TEN TEC 23 COLD 600UL 126 86 0.48 134 P3 TWD 18 DBH
+1.98 TEH TEC 23 COLD 60OUL 126 90 0.40 110 P3 TWD 16 DBH
+1.91 TEH TEC 22 COLD 60OUL 126 112 0.55 40 P3 TWD 22 DBH
+1.89 TEH TEC 30 COLD 600UL 127 53 0.60 100 P2 TWD 21 VHI
-0.85 TEH TEC 16 COLD 600UL 127 83 0.33 113 P3 TWD 14 DBH
-1.95 TEH TEC 20 COLD 60OUL 128 60 0.62 115 P2 TWD 22 10H
-1.19 TEH TEC 16 COLD 60OUL 0.40 64 P2 TWD 16 10H
+0.02 TEH TEC 16 COLD 60OUL 128 68 0.30 24 P3 TWD 12 DBH
+1.62 TEH TEC 19 COLD 600UL 129 47 0.77 129 P2 TWD 27 VH3
-0.90 TEH TEC 17 COLD 60OUL 129 63 0.37 100 P2 TWD 17 10H
-0.10 TEH TEC 19 COLD 600UL 129 67 0.49 79 P3 TWD 19 DBH
-2.00 TEH TEC 19 COLD 60OUL 130 74 0.41 66 P2 TWD 17 10H
+0.08 TEH TEC 21 COLD 60OUL 0.69 159 P2 TWD 24 10H
-1.07 TEH TEC 21 COLD 600UL 130 78 0.41 124 P2 TWD 16 VHl
+0.91 TEH TEC 20 COLD 600UL 130 128 0.46 67 P2 TWD 19 VH2
-0.48 TEH TEC 29 COLD 60OUL 131 83 0.20 111 P3 TWD 9
DBH
-1.74 TEH TEC 26 COLD 600UL 131 89 0.65 119 P2 TWD 25 10H
+0.94 TEH TEC 26 COLD 600UL 131 127 0.48 117 P2 TWD 17 03C
+0.82 TEH TEC 51 COLD 600UL 132 94 0.56 69 P2 TWD 22 10H
+0.95 TEH TEC 26 COLD 600UL 133 75 0.45 117 P3 TWD 17 DBH
+2.03 TEH TEC 25 COLD 600UL 133 83 0.51 158 P2 TWD 20 10H
-1.04 TEH TEC 27 COLD 600UL 133 115 0.42 114 P2 TWD 16 10H
+0.88 TEH TEC 28 COLD 600UL 134 66 0.18 113 P3 TWD 8 DBH
+0.98 TEH TEC 25 COLD 600UL 134 68 0.30 130 P2 TWD 13 10H
-0.71 TEH TEC 25 COLD 600UL 134 82 0.16 33 P3 TWD 7 DBH
+2.04 TEH TEC 27 COLD 600UL 134 84 0.78 136 P2 TWD 27 10H
-1.14 TEH TEC 27 COLD 600UL 134 86 1.14 141 P2 TWD 33 10H
-1.02 TEH TEC 27 COLD 600UL 134 100 0.41 154 P2 TWD 17 10H
+0.91 TEH TEC 27 COLD 600UL 135 67 0.08 25 P3 TWD 3 DBH
+2.25 TEH TEC 25 COLD 600UL 135 87 0.78 153 P2 TWD 28 10H
-1.04 TEH TEC 26 COLD 60OUL 135 91 0.41 109 P2 TWD 17 03H
-0.28 TEH TEC 27 COLD 60OUL 135 93 0.36 42 P2 TWD 15 10H
+0.98 TEH TEC 27 COLD 600UL 135 97 0.17 30 P2 TWD 8 10H
+0.92 TEH TEC 26 COLD 600UL 136 74 0.35 123 P2 TWD 15 10H
-1.02 TEH TEC 24 COLD 600UL 136 86 0.31 145 P2 TWD 14 10H
-0.96 TEH TEC 26 COLD 600UL 137 91 0.56 157 P2 TWD 22 10H
-1.08 TEH TEC 26 COLD 60OUL
AREVA NP Inc 01/09/08 14:19:37 Customer Name: San Onofre -
Unit 2 Component:
S/G 88 Page 13 of 14 Post U2C15 Inspection Final Report
- MAT, MCI,
- MMI, MVI,
- SAi, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[l].qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 137 119 0.41 80 P2 TWD 17 01C
-0.95 TEH TEC 29 COLD 60OUL 138 84 0.40 117 P2 TWD 17 VHi
+0.86 TEH TEC 27 COLD 600UL 139 61 0.46 120 P2 TWD 18 VHl
-0.93 TEH TEC 25 COLD 60OUL 139 105 0.56 75 P2 TWD 22 10H
+0.83 TEH TEC 29 COLD 60OUL 140 76 0.18 72 P3 TWD 8 DBH
-2.04 TEH TEC 26 COLD 600UL 140 88 0.25 140 P3 TWD 11 DBH
+1.86 TEH TEC 26 COLD 600UL 141 63 0.11 166 P3 TWD 5 DBC
-2.04 TEH TEC 25 COLD 600UL 0.40 17 P3 TWD 15 DBC
+1.63 TEH TEC 25 COLD 600UL 141 65 0.34 108 P2 TWD 15 08C
+0.77 TEH TEC 25 COLD 60OUL 141 67 0.69 108 P2 TWD 24 VC1
+0.86 TEH TEC 24 COLD 60OUL 141 77 0.25 121 P2 TWD 12 VC1
+0.90 TEH TEC 26 COLD 60OUL 0.30 71 P3 TWD 13 DBC
+1.61 TEH TEC 26 COLD 600UL 141 87 0.18 107 P2 TWD 9 VCt
+0.91 TEH TEC 27 COLD 600UL 142 66 0.44 172 P3 TWD 17 DBC
+1.49 TEH TEC 25 COLD 600UL 142 68 0.25 125 P2 TWD 11 10H
-0.24 TEH TEC 25 COLD 600UL 142 84 0.47 119 P3 TWD 17 DBC
+1.69 TEH TEC 27 COLD 600UL 142 86 0.20 116 P3 TWD 9 DBH
+1.90 TEH TEC 26 COLD 600UL 142 90 0.27 111 P3 TWD 11 DBH
+2.07 TEH TEC 27 COLD 600UL 142 98 0.29 15 P3 TWD 13 DBC
+1.44 TEH TEC 26 COLD 600UL 142 104 0.34 20 P3 TWD 13 DBH
+1.60 TEH TEC 29 COLD 60OUL 142 110 0.54 42 P3 TWD 19 DBH
+1.80 TEH TEC 29 COLD 600UL 143 83 0.49 38 P3 TWD 18 DBC
+1.57 TEH TEC 27 COLD 600UL 143 89 0.27 64 P3 TWD 11 DBH
-1.63 TEH TEC 26 COLD 600UL 143 109 0.23 126 P3 TWD 10 DBH
-1.57 TEH TEC 29 COLD 600UL 0.27 122 P2 TWD 13 VC2
+0.78 TEH TEC 29 COLD 600UL 0.46 73 2
SAT 03H
-0.85 03H 03H 152 HOT 580PP 144 76 0.19 48 P2 TWD 9 04H
-0.08 TEH TEC 26 COLD 600UL 0.38 130 P2 TWD 17 VC2
+0.92 TEN TEC 26 COLD 600UL 144 78 0.29 143 P2 TWD 13 VC2
+0.90 TEH TEC 26 COLD 600UL 0.43 122 P3 TWD 17 DBC
-1.53 TEH TEC 26 COLD 600UL 144 80 0.45 131 P3 TWD 18 DBH
+1.93 TEH TEC 26 COLD 600UL 144 86 0.31 139 P3 TWD 12 DBH
+1.97 TEH TEC 27 COLD 600UL 144 96 0.42 129 P3 TWD 17 DBH
+2.00 TEH TEC 26 COLD 60OUL 0.54 129 P3 TWD 20 DBC
+1.26 TEH TEC 26 COLD 600UL 145 79 0.59 100 P3 TWD 20 DBC
+1.69 TEH TEC 27 COLD 600UL 145 87 0.20 146 P3 TWD 8 DBC
-1.87 TEH TEC 26 COLD 600UL 0.19 34 P3 TWD 8 DBC
+1.81 TEH TEC 26 COLD 600UL 0.41 109 P2 TWD 18 VC1
+1.08 TEH TEC 26 COLD 60OUL 145 89 0.26 91 P3 TWD 10 DBH
-1.75 TEH TEC 27 COLD 600UL 0.34 48 P2 TWD 15 VC1
+0.85 TEh TEC 27 COLD 60OUL 146 82 0.32 151 P3 TWD 13 DBC
+1.69 TEH TEC 27 COLD 60OUL 0.20 56 P2 TWO 9 03H
-0.63 TEH TEC 27 COLD 600UL 146 86 0.17 95 P2 TWD 8 08C
+0.87 TEH TEC 27 COLD 60OUL 0.14 82 P3 TWD 6 DBH
+1.87 TEH TEC 27 COLD 60OUL 0.18 99 P3 TWD 7 DBC
+1.77 TEH TEC 27 COLD 600UL 146 94 0.23 78 P2 TWD 10 02H
+0.87 TEH TEC 27 COLD 600UL 0.58 61 P2 TWD 22 VHI
+1.22 TEH TEC 27 COLD 600UL
AREVA NP Inc Customer Name: San Onofre -
Unit 2 01/09/08 14:19:37 Component:
S/G 88 Page 14 of 14 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryM![11.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION 147 91 0.47 105 P2 TWD 19 VCl
-0.85 EXT EXT CAL # LEG TEH TEC 27 COLD PROBE 600UL Total Tubes
- 430 Total Records: 531
Inspection of Steam Generator Tubes Special Report Appendix 4 Page 1 of 16 Appendix 4 Tube Inspection Summary Steam Generator E-089
AREVA NP Inc 1/9/2008 2:18:16 PM Customer Name: San Onofre -
Unit 2 Component:
S/G 89 Page 2 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[2]
ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
=============================
======
2 122 0.30 95 2
SAI 01H
+0.74 01H 01H 170 HOT 58OPP 3
127 0.41 113 2 SAI 07C
+0.01 07C 07C 108 COLD 58OPP 5
119 0.53 89 2
SAI 07H
-0.50 07H 07H 169 HOT 580PP 0.33 86 2
SAI 07H
-0.30 07H 07H 169 HOT 580PP 0.33 85 2
SAI 07C
+0.61 07C 07C 108 COLD 580PP 6
58 0.33 16 P1 SCI TSH
-6.31 TSH TSH 107 HOT 580PP 8
36 0.35 73 2
SAI 05H
-0.71 05H 05H 148 HOT 580PP 8
122 0.27 72 2
SAI 07H
-0.62 07H 07H 169 HOT 580PP 9
65 0.32 90 2
SAI 07H
+0.73 07H DBH 193 HOT 58OPP 9
117 0.26 93 2
SAI 05H
+0.91 05H 05H 170 HOT 580PP 10 44 0.31 75 2
SAI 05H
-0.83 05H 05H 145 HOT 58OPP 0.23 77 2
SAI 05H
+0.54 05H 05H 145 HOT 580PP 11 19 0.30 135 2 SAI 06H
+0.22 06H 06H 145 HOT 580PP 0.23 104 2 SAI 04H
-0.19 04H 04H 145 HOT 58OPP 11 55 0.37 101 2 SAI 05H
+0.94 05H 05H 157 HOT 580PP 11 65 0.30 67 2
SAI 01H
+0.54 01H 01H 203 HOT 58OPP 11 119 0.31 55 2
SAI 04H
-0.25 04H 04H 164 HOT 580PP 11 121 0.50 22 P1 SCI TSH
-10.71 TSH TSH 82 HOT 580PP 11 131 0.72 14 P1 SCI TSH
-13.59 TSH TSH 52 HOT 58OPP 12 114 0.40 130 2 SAI 06H
-0.16 06H 06H 215 HOT 520ET 12 128 0.22 121 2 SAI 01H
+0.58 01H 01H 168 HOT 58OPP 0.34 114 2 SAI 04H
+0.50 04H 04H 168 HOT 58OPP 13 37 0.20 33 P3 TWD 16 DBC
-0.09 TEC TEH 27 HOT 600UL 13 123 0.58 103 P2 TWD 22 07H
+0.62 TEH TEC 31 COLD 600UL 14 18 0.17 83 2
SAI 05H
+0.88 05H 05H 148 HOT 580PP 14 58 0.41 125 2 SAI 04H
+1.07 04H 04H 157 HOT 58OPP 15 131 0.43 19 P1 SCI TSH
-0.10 TSH TSH 52 HOT 58OPP 15 141 0.54 21 P1 SCI TSH
-0.08 TSH TSH 99 HOT 580PP 16 52 0.18 100 P3 TWD 11 DBH
-2.12 TEH TEC 34 COLD 600UL 16 56 0.12 96 2
SAI 06H
-1.39 06H 06H 157 HOT 58OPP 16 60 0.39 19 P1 SCI TSH
-0.09 TSH TSH 66 HOT 58OPP 17 27 0.13 27 P3 TWD 11 DBC
+1.54 TEC TEH 19 HOT 600UL 17 43 0.13 20 P3 TWD 11 DBH
-1.90 TEC TEH 27 HOT 600UL 17 49 0.13 110 P1 SCI TSH
+0.08 TSH TSH 71 HOT 58OPP 18 26 0.20 98 2
SAI 06H
-0.15 06H 06H 148 HOT 580PP 18 34 0.29 13 2
SAI TSH
-5.71 TSH TSH 85 HOT 580PP 0.48 16 2
SAI TSH
-5.26 TSH TSH 85 HOT 580PP 18 44 0.13 147 P3 TWD 11 DBH
-1.81 TEC TEH 27 HOT 600UL 18 122 0.36 110 P3 TWD 15 DBE
-1.89 TEH TEC 29 COLD 600UL 18 144 0.44 11 P3 TWD 19 DBh
+1.15 TEC TEN 14 HOT 600UL 19 109 0.23 124 P3 TWD 10 DBC
+1.33 TEH TEC 29 COLD 600UL 19 173 0.21 157 P2 TWD 12 VSM
+0.81 TEC TEH 22 HOT 60OUL 20 18 0.71 125 P2 TWD 26 VSm
-0.16 TEC TEH 16 HOT 600UL
AREVA NP Inc 1/9/2008 2:18:16 PM Customer Name: San Onofre -
Unit 2 Component:
S/G 89 Page 3 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMi[2].qry ROW LINE VOLTS DEG CHN IND
%TW LOCATION EXT EXT CAL # LEG PROBE
======-----------------------=---------------=====---==-------=-=-=-===-======-=------==-=----
20 108 0.17 122 P3 TWD 10 DBC
+1.77 TEH TEC 30 COLD 600UL 20 120 0.49 120 2 SAI 04H
+0.69 04H 04H 215 HOT 520ET 0.42 132 2 SAI 04H
-0.26 04H 04H 215 HOT 520ET 21 67 0.49 98 P2 TWD 22 VSM
+0.78 TEH TEC 36 COLD 600UL 22 2
0.33 129 P2 TWD 23 VSM
-0.91 TEC TEH 11 HOT 60OUL 22 50 5.84 186 4 PCS SBH
+3.47 TO+10.13 STH SBH 128 HOT 500SP 22 118 0.43 126 P2 TWD 21 07H
+1.07 TEH TEC 30 COLD 600UL 23 23 0.27 50 P2 TWD 13 07H
+0.60 TEC TEH 20 HOT 60OUL 23 115 0.38 137 P2 TWD 16 VSM
+0.75 TEH TEC 29 COLD 600UL 23 137 0.32 22 P1 SCI TSH
-0.14 TSH TSH 42 HOT 580PP 24 18 0.27 109 P2 TWD 12 VSM
-0.92 TEC TEH 16 HOT 600UL 24 50 0.23 103 P1 SCI TSH
+0.12 TSH TSH 72 HOT 58OPP 24 130 0.19 120 P1 SCI TSH
+0.08 TSH TSH 50 HOT 58OPP 24 154 0.18 49 P2 TWD 11 VSM
+0.25 TEC TEH 17 HOT 60OUL 25 49 0.16 95 P1 SCI TSH
+0.09 TSH TSH 71 HOT 580PP 25 51 0.32 100 2 SAI 07C
-0.60 07C 07C 109 COLD 58OPP 25 149 0.26 73 2
SAI 06H
-0.38 06H 06H 169 HOT 580PP 28 54 0.37 111 2 SAI TSH
+0.35 TSH TSH 71 HOT 58OPP 28 122 0.19 107 P1 MCI TSH
+0.12 TSH TSH 81 HOT 58OPP 29 47 0.30 102 2 SAI 07H
+0.61 07H 07H 161 HOT 580PP 29 59 0.32 17 2
SAI TSH
-3.59 TSH TSH 65 HOT 580PP 29 113 0.20 53 P3 TWD 12 DBH
-1.77 TEH TEC 30 COLD 600UL 30 70 0.35 136 P3 TWD 17 DBC
-1.46 TEH TEC 36 COLD 600UL 30 106 0.17 149 P3 TWD 10 DBC
-1.90 TEH TEC 30 COLD 600UL 30 134 0.47 20 P1 SCI TSH
-6.96 TSH TSH 50 HOT 58OPP 31 45 0.36 51 P3 TWD 14 DBH
+1.64 TEC TEH 31 HOT 600UL 31 71 0.60 79 P3 TWD 27 DBH
-2.04 TEH TEC 36 COLD 600UL 0.26 129 P3 TWD 13 DBC
+1.79 TEH TEC 36 COLD 600UL 0.25 142 P3 TWD 12 DBC
-1.83 TEH TEC 36 COLD 600UL 32 48 0.45 23 P1 SCI TSH
-0.09 TSH TSH 72 HOT 58OPP 33 67 0.26 83 2
SAI 04H
+0.50 04H 04H 205 HOT 58OPP 0.17 114 2 SAI TSH
+0.47 TSH TSH 64 HOT 58OPP 0.21 100 2 SAI TSH
+0.62 TSH TSH 64 HOT 580PP 34 112 0.28 83 2
SAT 04H
-0.34 04H 04H 159 HOT 58OPP 35 49 0.14 116 2 SAI TSH
+0.27 TSH TSH 72 HOT 580PP 35 111 0.72 16 2
SAI TSH
-0.98 TSH TSH 83 HOT 580PP 0.21 46 2
SAI 04H
-0.29 04H 04H 159 HOT 580PP 36 104 0.19 31 P3 TWD 11 DBC
-2.10 TEH TEC 30 COLD 600UL 36 114 0.35 112 P2 TWD 15 02H
+0.90 TEH TEC 29 COLD 60OUL 36 128 0.34 104 P1 MCI TSH
+0.05 TSH TSH 75 HOT 58OPP 37 101 0.30 103 P3 TWD 17 DBC
+1.75 TEH TEC 24 COLD 600UL 0.26 136 P3 TWD 15 DBH
+1.75 TEH TEC 24 COLD 60OUL 37 103 0.52 78 P3 TWD 19 DBH
-1.87 TEH TEC 29 COLD 600UL 0.45 39 P3 TWD 17 DBC
+1.74 TEH TEC 29 COLD 600UL
AREVA NP Inc 1/9/2008 2:18:16 PM Customer Name: San Onofre -
Unit 2 Component:
S/G 89 Page 4 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[21.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
=-------------------=-====--------------==--===-------------==-==---------------=
38 4
0.20 45 P2 TWD 16 01C
+0.06 TEC TEN 11 HOT 60OUL 0.23 36 P2 TWD 18 02C
-0.92 TEC TEN 11 HOT 600UL 38 8
0.23 93 2
SAI 06H
+0.70 06H 06H 148 HOT 58OPP 38 20 0.19 130 P3 TWD 14 DBH
+0.56 TEC TEN 19 HOT 600UL 38 104 0.25 68 P3 TWD 11 DBC
-1.76 TEH TEC 29 COLD 60OUL 39 45 0.18 107 P1 MCI TSH
+0.04 TSH TSH 80 HOT 580PP 39 101 0.28 106 P3 TWO 11 DBC
-2.00 TEN TEC 23 COLD 60OUL 0.24 55 P3 TWD 10 DBC
+1.94 TEN TEC 23 COLD 60OUL 39 115 0.27 14 P3 TWD 15 DEN
+1.94 TEN TEC 30 COLD 60OUL 39 131 0.60 15 2
SAI TSH
-7.50 TSH TSH 52 HOT 58OPP 0.47 14 2
SAI TSH
-8.54 TSH TSH 52 HOT 580PP 39 133 0.24 86 P1 SCI TSH
+0.03 TSH TSH 52 HOT 58OPP 0.73 21 2
SAI TSH
-7.28 TSH TSH 52 HOT 58OPP 40 46 0.25 101 P1 SCI TSH
+0.05 TSH TSH 80 HOT 580PP 40 60 0.33 110 2 SAI TSH
+0.31 TSH TSH 65 HOT 58OPP 40 74 0.43 123 P3 TWD 20 DBC
-1.64 STH TEC 38 COLD 600UL 40 136 0.51 25 P1 SCI TSH
-8.81 TSH TSH 99 HOT 58OPP 41 57 0.34 27 P3 TWD 13 DBH
+1.84 TEN TEC 33 COLD 600UL 41 63 0.48 58 P2 TWD 20 02H
+0.93 TEN TEC 35 COLD 60OUL 41 73 0.27 49 P3 TWD 14 DBC
-1.29 TEN TEC 36 COLD 60OUL 41 75 0.67 106 P3 TWD 22 DBC
+1.83 TEN TEC 35 COLD 60OUL 0.13 113 P3 TWD 6 DBC
-1.71 TEN TEC 35 COLD 60OUL 41 101 0.77 110 P3 TWD 25 DBC
+2.10 TEN TEC 23 COLD 600UL 41 113 0.24 25 P3 TWD 14 DBH
-1.86 TEN TEC 30 COLD 60OUL 41 119 0.42 71 P3 TWD 22 DBH
+1.88 TEN TEC 30 COLD 60OUL 41 131 0.57 18 P1 SCI TSH
-0.16 TSH TSH 50 HOT 58OPP 41 143 0.24 50 P2 TWD 14 VSM
+0.78 TEC TEH 13 HOT 60OUL 42 38 0.91 27 P1 SCI TSH
-0.12 TSH TSH 80 HOT 58OPP 42 168 0.54 156 P2 TWD 23 VSM
+0.90 TEC TEN 21 HOT 600UL 42 170 0.67 117 P2 TWD 27 VSM
-0.35 TEC TEN 22 HOT 60OUL 44 18 0.16 50 P2 TWD 7 VSM
+0.55 TEC TEN 16 HOT 600UL 0.32 128 P2 TWD 14 VSM
-0.92 TEC TEN 16 HOT 60OUL 44 74 0.67 59 P3 TWD 23 DBC
-2.14 TEN TEC 35 COLD 60OUL 0.23 67 P3 TWD 10 DBC
+2.00 TEN TEC 35 COLD 600UL 44 104 0.23 136 P3 TWD 13 DBH
+2.02 TEN TEC 30 COLD 60OUL 0.57 80 P2 TWD 25 VSM
+0.74 TEN TEC 30 COLD 600UL 0.13 12 P2 TWD 7 VSN
-1.04 TEN TEC 30 COLD 600UL 0.21 74 P3 TWD 13 DBE
-1.67 TEN TEC 30 COLD 600UL 44 112 0.53 142 P2 TWD 20 VSM
-0.80 TEN TEC 29 COLD 60OUL 45 63 0.26 78 2
SAI TSH
+0.19 TSH TSH 63 HOT 580PP 0.76 20 2
SAT TSH
-3.16 TSH TSH 63 HOT 580PP 0.53 21 2
SAI TSH
-2.39 TSH TSH 63 HOT 580PP 45 103 0.90 130 P2 TWD 29 VSE
+0.86 TEH TEC 29 COLD 600UL 0.39 131 P2 TWD 16 VSM
-0.80 TEN TEC 29 COLD 60OUL 0.26 144 P2 TWD 12 VSM
+0.00 TEN TEC 29 COLD 600UL 45 145 0.25 76 P2 TWD 15 VSM
-0.88 TEC TEN 13 HOT 600UL 46 48 0.13 103 P!
SCI TSH
+0.14 TSH TSH 71 HOT 580PP
AREVA N? Inc Customer Name: San Onofre -
Unit 2 1/9/2008 2:18i16 PM Component: S/G 89 Page 5 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[2).qry ROW LTNE VOLTS DEG CHN IND %TW LOCATION
==
=== = = = = = = -
46 52 0.36 134 P2 TWD 15 VSM
-0.88 0.28 163 P2 TWD 12 VSM
+0.80 46 104 0.91 114 P2 TWD 29 VSM
-0.78 0.54 139 P2 TWD 21 VSM
+0.78 0.75 134 P2 TWD 26 VSM
+0.00 46 126 0.41 98 2
SAI 03H
-0.29 46 128 0.41 136 P2 TWD 17 VSM
-0.89 46 134 0.47 91 2
SAI 06H
+0.16 EXT EXT CAL # LEG PROBE TEN TEC 33 COLD 600UL TEH TEC 33 COLD 600UL TEH TEC 29 COLD 600UL TEN TEC 29 COLD 600UL TEH TEC 29 COLD 600UL 03H 03K 215 NOT 520ET TEH TEC 31 COLD 600UL 06H 06H 169 HOT 58OPP 46 156 0.66 115 P2 TWD 28 VSM
-0.87 TEC TEH 18 HOT 60OUL 0.13 152 P2 TWD 8 VSM
+0.77 TEC TEH 18 HOT 600UL 46 162 0.27 63 P2 TWD 15 VSM
+0.89 TEC TEH 22 HOT 60OUL 46 170 0.22 37 P3 TWD 13 DBC
+1.52 TEC TEH 22 HOT 600UL 47 29 0.32 16 P3 TWD 22 DBH
-1.78 TEC TEH 23 HOT 600UL 47 33 0.36 48 P3 TWD 23 DBH
+1.82 TEC TEH 23 HOT 600UL 47 53 0.23 93 P2 TWD 13 VSM
+0.83 STH TEC 38 COLD 600UL 47 117 0.30 51 P3 TWD 17 DBH
+1.93 TEH TEC 30 COLD 60OUL 47 121 0.21 159 P2 TWD 12 VSM
-0.86 TEH TEC 30 COLD 600UL 48 6
0.39 78 P2 TWD 25 08C
-1.72 TEC TEH 11 HOT 600UL 48 8
0.25 115 P2 TWD 12 02C
+0.89 TEC TEH 12 HOT 600UL 48 12 0.35 86 2
SAI 04H
+0.61 04H 04H 148 HOT 580PP 48 34 0.20 27 P2 TWD 9 VSM
-0.60 TEC TEH 24 HOT 600UL 48 52 0.15 131 P1 SCI TSH
+0.12 TSH TSH 71 HOT 580PP 48 64 0.43 14 2
SAI TSH
-2.18 TSH TSH 63 HOT 58OPP 0.37 13 2
SAI TSH
-1.43 TSH TSH 63 HOT 580PP 48 66 1.50 154 P2 TWD 38 VSM
-0.88 TEH TEC 35 COLD 600UL 48 100 0.63 24 P3 TWD 22 DBC
+1.90 TEH TEC 21 COLD 60OUL 48 118 0.47 40 P2 TWD 19 04H
-1.10 TEH TEC 29 COLD 600UL 48 130 0.36 18 P1 SCI TSH
-0.13 TSH TSH 50 HOT 580PP 48 158 0.55 167 P2 TWD 26 VSM
-0'.74 TEC TEH 17 HOT 600UL 0.09 160 P2 TWD 6 VSM
+0.97 TEC TEH 17 HOT 600UL 49 39 0.22 135 P2 TWD 10 VSM
-0.80 TEC TEH 28 HOT 600UL 49 51 0.15 66 P1 MCI TSH
+0.07 TSH TSH 71 HOT 58OPP 49 53 0.61 129 P2 TWD 23 08C
-1.51 TEH TEC 33 COLD 600UL 0.17 136 Pl SCI TSH
+0.09 TSH TSH 71 HOT 580PP 49 57 0.31 102 2 SAI 08H
+1.54 08H 08H 205 HOT 58OPP 49 65 0.31 135 P2 TWD 14 VSM
-0.71 TEH TEC 35 COLD 600UL 49 75 0.36 134 P3 TWD 14 DBC
-1.85 TEH TEC 35 COLD 600UL 49 103 0.41 153 P2 TWD 17 VSM
-0.80 TEH TEC 29 COLD 60OUL 49 145 0.54 49 159 0.58 0.27 0.12 50 16 0.15 50 44 0.20 102 P2 TWD 26 08H
-1.60 TEC TEH 133 P2 TWD 26 VSM
+0.76 TEC TEH 40 P2 TWD 15 VSM
+0.19 TEC TEH 92 P2 TWD 8 VSM
-1.05 TEC TEH
- 48. P2 TWD 7 08H
+1.23 TEC TEH 114 P2 TWD 15 VSM
-0.82 TEC TEH 13 HOT 600UL 18 NOT 600UL 18 HOT 600UL 18 HOT 60OUL 16 HOT 60OUL 27 HOT 600UL
AREVA NP inc 1/9/2008 2:18:16 PM Customer Name: San Onofre -
Unit 2 Component: S/G 89 Page 6 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[2].qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
=
====== = ----------
==
==
========
==
==
=
50 74 0.23 16 P3 TWD 9 DBC
+2.10 TEC TEH 45 HOT 600UL 0.21 75 P3 TWD 9 DBC
-2.00 TEC TEH 45 HOT 600UL 50 76 0.65 134 P3 TWD 23 DBC
-1.67 TEH TEC 23 COLD 600UL 50 100 0.38 121 P2 TWD 19 VSM
+0.12 TEH TEC 22 COLD 600UL 50 106 0.27 105 P1 SCI TSH
+0.15 TSH TSH 87 HOT 580PP 51 77 0.27 149 ?3 TWD 15 DBC
+1.93 TEH TEC 24 COLD 60OUL 51 153 0.40 68 P3 TWD 19 DBC
+0.62 TEC TEH 18 HOT 600UL 52 76 0.47 121 P3 TWD 23 DBC
-1.85 TEH TEC 24 COLD 60OUL 52 78 0.27 157 P3 TWD 11 DBC
-1.86 TEH TEC 23 COLD 600UL 52 80 0.80 92 P3 TWD 26 DBC
-1.86 TEH TEC 23 COLD 600UL 52 84 0.39 150 P3 TWD 15 DBC
-2.06 TEH TEC 23 COLD 600UL 0.64 126 P3 TWD 22 DBH
-1.45 TEH TEC 23 COLD 600UL 0.87 90 P3 TWD 27 DBH
+1.88 TEH TEC 23 COLD 60OUL 0.39 158 P3 TWD 15 DBC
+1.88 TEH TEC 23 COLD 600UL 52 96 0.25 164 P3 TWD 16 DBH
-1.69 TEH TEC 22 COLD 60OUL 52 120 0.62 24 P1 SCI TSH
-0.13 TSH TSH 82 HOT 580PP 52 158 0.50 91 P2 TWD 24 VH3
-0.96 TEC TEH 17 HOT 600UL 53 77 0.53 83 P3 TWD 19 DBC
-1.88 TEH TEC 23 COLD 60OUL 53 81 0.37 128 P3 TWD 15 DBC
-1.62 TEH TEC 23 COLD 60OUL 0.26 36 P3 TWD 10 DBH
-1.95 TEH TEC 23 COLD 600UL 53 91 0.38 90 P3 TWD 20 DBH
+1.79 TEH TEC 24 COLD 600UL 53 95 0.29 49 P3 TWD 17 DBH
+1.84 TEH TEC 22 COLD 60OUL 0.41 63 P3 TWD 22 DBC
+1.71 TEH TEC 22 COLD 600UL 53 155 0.34 46 P2 TWD 19 VH3
+0.47 TEC TEH 17 HOT 600UL 54 8
0.17 50 P2 TWD 14 01C
+0.10 TEC TEH 11 HOT 600UL 54 52 0.44 17 P1 SCI TSH
-5.76 TSH TSH 72 HOT 58OPP 54 102 0.27 90 2
SAI 01H
+13.43 01H 02H 215 HOT 520ET 54 148 0.41 93 P2 TWD 21 VH3
-0.82 TEC TEH 13 HOT 600UL 55 45 0.36 25 P1 SCI TSH
-0.16 TSH TSH 79 HOT 58OPP 55 79 0.37 29 P3 TWD 20 DEC
-2.00 TEH TEC 24 COLD 600UL 55 85 0.62 137 P3 TWD 22 DBH
+1.96 TEH TEC 23 COLD 60OUL 55 91 0.58 96 P3 TWD 21 DBC
+1.80 TEH TEC 23 COLD 60OUL 56 28 0.64 107 P2 TWD 24 VH3
-0.92 TEC TEH 24 HOT 600UL 56 92 0.37 122 P3 TWD 21 DBC
+1.92 TEH TEC 22 COLD 600UL 0.14 79 P3 TWD 10 DBC
-1.90 TEH TIC 22 COLD 600UL 56 150 0.41 105 P2 TWD 21 VH3
-0.91 TEC TEH 13 HOT 600UL 56 152 0.29
!!9 P3 TWD 18 DBH
+0.95 TEC TEH 13 HOT 600UL 56 158 0.48 90 P2 TWD 24 VH3
-0.76 TEC TEH 17 HOT 60OUL 57 77 0.25 92 Pl MCI TSH
+0.07 TSH TSH 53 HOT 580PP 57 79 0.46 29 P3 TWD 17 DBC
+1.80 TEH TEC 23 COLD 600UL 0.70 92 P3 TWD 24 DBC
-1.60 TEH TEC 23 COLD 600UL 57 97 0.50 15 2
SAI TSH
-4.39 TSH TSH 58 HOT 580PP 58 54 0.34 17 2
SAI TSH
-6.25 TSh TSH 71 HOT 58OPP 58 82 0.61 99 P3 TWD 22 DBH
+1.80 TEH TEC 23 COLD 600UL
AREVA NP Inc Customer Name:
San Onofre -
Unit 2 1/9/2608 2:18:16 PM Component:
S/G 89 Page 7 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[2].qry ROW 58 LINE VOLTS 92 0.30 DEG CHN IND %TW LOCATION 17 P3 TWD 12 DBH EXT EXT CAL # LEG
+2.04 TEN TEC 21 COLD PROBE 600UL 58 94 0.41 78 P3 TWD 22 DBC 58 96 0.25 28 P3 TWD 10 DBH 0.30 94 P3 TWD 12 DEC 59 25 0.51 79 P2 TWD 21 VH3 59 53 0.25 24 P1 SCI TSH
-1.96
-1.68
-1.68
-1.00
-0.17 TEN TEC 22 COLD 600UL TEN TEC 21 COLD E0OUL TEN TEC 21 COLD 600UL TEC TEN 20 HOT 60OUL TSH TSH 71 HOT 58OPP 59 89 0.86 100 P3 TWD 32 DBH
-1.56 STN TEC 40 COLD 600UL 0.35 133 P2 TWD 18 VH3
+0.00 STH TEC 40 COLD 600UL 0.21 140 P2 TWD 12 VH3
-0.71 STH TEC 40 COLD 600UL 0.30 93 2
SAI 06C
-0.69 06C 06C 108 COLD 580PP 0.31 110 2 SAT VN3
+0.08 DBH VH3 120 COLD 560P2 59 95 0.46 118 P3 TWD 17 DBH
-1.56 TEN TEC 21 COLD 600UL 0.24 122 P3 TWD 9 DBC
+0.74 TEN TEC 21 COLD 600UL 59 147 0.60 106 P2 TWD 25 VH3
+0.93 TEC TEN 14 HOT 600UL 0.38 149 P2 TWD 18 VH3
-0.93 TEC TEN 14 HOT 600UL 60 28 0.33 126 P2 TWD 15 VH3
-0.98 TEC TEN 24 HOT 600UL 60 30 0.36 81 P2 TWD 16 VH3
-1.04 TEC TEN 24 HOT 600UL 60 88 0.77 139 P3 TWD 25 DBH
+1.74 TEN TEC 23 COLD 600UL 60 94 0.46 103 P3 TWD 17 DBH
+1.68 TEN TEC 21 COLD 60OUL 0.60 138 P3 TWD 21 DBC
-1.72 TEN TEC 21 COLD 60OUL 60 146 0.43 111 P2 TWD 22 VH3
-1.05 TEC TEN 13 HOT 600UL 60 158 0.35 122 P2 TWD 19 VH3
-0.99 TEC TEN 17 HOT 600UL 61 89 0.41 95 P3 TWD 21 DBC
-2.08 TEN TEC 24 COLD 600UL 0.29 115 P3 TWD 17 DBH
-1.85 TEN TEC 24 COLD 60OUL 61 91 0.60 14 P3 TWD 21 DBH
+1.97 TEN TEC 23 COLD 600UL 62 74 0.22 95 2
SAI TSH
+1.36 TSH TSH 62 HOT 58OPP 62 92 0.20 96 P1 SCI TSH
+0.13 TSH TSH 53 HOT 58OPP 63 87 0.55 110 P3 TWD 24 DBH
-1.49 STH TEC 40 COLD 600UL 0.18 149 P3 TWD 10 DBC
-1.78 STH TEC 40 COLD 600UL 63 99 0.23 55 P3 TWD 10 DBC
-1.33 TEN TEC 21 COLD 600UL 63 145 0.33 116 P2 TWD 18 VH3
+0.84 TEC TEN 13 HOT 600UL 64 10 0.36 109 P2 TWD 23 03C
-0.94 TEC TEN 15 HOT 600UL 0.07 45 P3 TWD 6 DBH
+1.67 TEC TEN 15 HOT 600UL 64 12 0.42 101 P2 TWD 25 VH3 64 76 0.28 111 2 SAI 05H
+0.66
+0.67 TEC TEN 15 HOT 600UL 05H 05H 146 HOT 580PP 64 80 0.35 15 2
SAI TSH
-2.87 TSH TSH 54 HOT 580PP 64 82 0.56 113 P3 TWD 26 DBC
+2.01 TEN TEC 24 COLD 600UL 64 84 0.19 86 P1 SCI TSH
+0.09 TSH TSH 54 HOT 580PP 0.36 65 P3 TWD 19 DBH
+1.75 TEN TEC 24 COLD 600UL 64 86 0.30 66 P3 TWD 16 DBH
-1.70 STH TEC 40 COLD 600UL 64 92 0.19 136 P3 TWD 11 DBH
-1.72 STH TEC 40 COLD 600UL 0.15 68 P3 TWD 9 DBC
-1.79 STH TEC 40 COLD 600UL 64 94 0.34 85 P3 TWD 19 DBC
-1.88 TEN TEC 22 COLD 600UL 64 150 0.34 147 P2 TWD 19 VH3
-0.93 TEC TEN 13 HOT 60OUL 65 37 0.21 89 2
SAI VSM
-0.93 66 78 0.29 87 P3 TWD 16 DBH
+1.91 66 80 0.44 116 P3 TWD 17 DEC
+1.89 VSM VSM 189 HOT 560P2 TEN TEC 24 COLD 600UL TEH TEC 23 COLD 600UL
AREVA NP Inc Customer Name: San Onofre -
Unit 2 1/9/2008 2:18:17 PM Component:
S/G 89 Page 8 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMil[2].qry ROW LINE VOLTS DEG CNN IND %TW LOCATION EXT EXT CAL # LEG PROBE 66 84 0.24 21 P3 TWD 10 DBH
-1.80 TEH TEC 23 COLD 600UL 66 90 0.31 14 P3 TWD 17 DEC
-1.79 TEH TEC 24 COLD 60OUL 66 94 0.58 58 P3 TWD 20 DEC
+1.74 TEH TEC 21 COLD 60OUL 0.36 127 P3 TWD 14 DEC
-1.70 TEH TEC 21 COLD 60OUL 66 138 0.32 90 P2 TWD 16 08C
-0.90 TEC TEH 10 HOT 60OUL 67 83 0.79 74 P3 TWD 26 DEC
-1.76 TEH TEC 23 COLD 600UL 0.38 57 P3 TWD 15 DBH
-1.66 TEH TEC 23 COLD 60OUL 67 87 0.29 107 P2 TWD 11 VSM
+0.88 TEH TEC 23 COLD 600UL 0.30 161 P3 TWD 12 DBH
+1.53 TEH TEC 23 COLD 60OUL 68 40 0.22 151 P2 TWD 16 VC3
+0.87 TEC TEH 27 HOT 60OUL 68 90 0.66 121 P3 TWD 23 DEC
-2.00 0.39 41 P3 TWD 15 DBH
-1.92 0.36 16 P3 TWD 14 DEC
+2.25 69 91 0.32 97 P3 TWD 13 DEC
+2.17 69 163 0.28 148 P2 TWD 15 02C
+0.89 70 24 0.21 166 P3 TWD 8 DEC
+2.05 0.16 16 P3 TWD 6 DEC
-1.48 TEH TEC 23 COLD 600UL TEH TEC 23 COLD 600UL TEH TEC 23 COLD 600UL TEH TEC 23 COLD 600UL TEC TEH 22 HOT 600UL TEC TEH 20 HOT 600UL TEC TEH 20 HOT 600UL 70 52 0.37 153 P3 TWD 22 DEC
+1.29 TEC TEH 40 HOT 600UL 70 68 0.24 79 P1 SCI TSH
+0.06 TSH TSH 63 HOT 58OPP 70 90 0.21 146 P3 TWD 13 DBH
-1.88 TEH TEC 24 COLD 600UL 70 92 0.29 20 2
SAI TSH
-2.27 TSH TSH 54 HOT 58OPP 70 94 0.57 124 P3 TWD 20 DEC
-1.85 TEH TEC 21 COLD 600UL 70 144 0.39 119 P2 TWD 19 VC3
-0.86 TEC TEH 14 HOT 600UL 0.36 32 P2 TWD 17 VSM
-0.89 TEC TEH 14 HOT 60OUL 70 152 0.37 141 P2 TWD 18 VH3
-0.76 TEC TEH 14 HOT 600UL 70 156 0.46 135 P2 TWD 23 VH3
-1.01 TEC TEH 18 HOT 600UL 70 164 0.32 72 P2 TWD 16 02C
-0.94 TEC TEH 21 HOT 60OUL 71 57 0.15 78 2
SAI 08H
+0.52 08H 08H 156 HOT 580PP 71 67 0.46 109 P1 SCI TSH
+0.14 TSH TSH 64 HOT 58OPP 71 79 0.44 114 P3 TWD 22 DEC
-2.20 TEH TEC 24 COLD 600UL 71 91 0.27 143 P3 TWD 16 DEC
-1.85 TEN TEC 24 COLD 600UL 71 93 0.21 129 P3 TWD 13 DEC
-2.18 TEH TEC 22 COLD 600UL 71 143 0.23 58 P2 TWD 12 04C
-0.14 TEC TEN 14 NOT 600UL 0.22 159 P2 TWD 12 VC3
-0.88 TEC TEH 14 HOT 600UL 0.38 143 P2 TWD 18 VN3
-0.88 TEC TEH 14 HOT 600UL 0.42 134 P2 TWD 19 VSM
+0.70 TEC TEH 14 HOT 600UL 71 147 0.37 127 P2 TWD 18 VC3
-0.82 TEC TEH 14 HOT 60OUL 0.62 101 P2 TWD 25 VH3
-0.92 TEC TEH 14 HOT 600UL 72 26 0.46 101 P2 TWD 19 VC3
+0.80 TEC TEH 20 HOT 600UL 72 28 0.21 153 P3 TWD 10 DEC
+0.71 TEC TEH 24 HOT 600UL 72 36 0.18 9
P3 TWD 9 DEC
+1.46 TEC TEH 24 HOT 600UL 72 38 0.26 92 P3 TWD 19 DEC
+1.98 TEC TEH 27 HOT 600UL 72 78 0.27 77 P2 TWD 11 VC3
+0.88 TEH TEC 23 COLD 60OUL 0.33 134 P2 TWD 13 VH3
+0.80 TEH TEC 23 COLD 600UL 0.58 82 P2 TWD 20 VH3
-0.99 TEH TEC 23 COLD 60OUL 72 80 0.47 145 P2 TWD 17 VC3
+0.84 TEH TEC 23 COLD 600UL
AREVA NP Inc 1/9/2008 2:18:17 PM Customer Name: San Onofre -
Unit 2 Component:
S/G 89 Page 9 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAT, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[2].qry ROW LINE VOLTS DEG CNN TD %TW LOCATION EXT EXT CAL 4 LEG PROBE 72 84 0.39 130 P3 TWD 15 DEC
-1.78 TEH TEC 23 COLD 60OUL 0.37 130 P2 TWD 14 VH3
-0.84 TEH TEC 23 COLD 60OUL 72 90 0.39 94 P3 TWD 15 DEC
-2.22 TEN TEC 23 COLD 600UL 72 114 0.26 84 P2 TWD 14 VC3
+0.87 TEC TEH 32 HOT 60OUL 72 126 0.44 127 P2 TWD 22 VSM
-0.82 TEC TEH 33 HOT 600UL 0.42 104 P2 TWD 21 VH3
-0.12 TEC TEH 33 HOT 600UL 72 156 0.24 107 P2 TWD 14 VC3
-0.93 TEC TEH 17 HOT 600UL 73 13 0.25 85 P2 TWD 18 VH3
+0.80 TEC TEH 15 HOT 60OUL 73 51 0.30 142 P3 TWD 19 DBH
-1.10 TEC TEH 40 HOT 600UL 73 91 0.47 21 P3 TWD 18 DEC
+2.21 TEH TEC 23 COLD 60OUL 73 157 0.31 131 P2 TWD 17 VH3
+1.09 TEC TEH 17 HOT 600UL 73 163 0.13 44 P3 TWD 6 DEC
+1.54 TEC TEH 21 HOT 60OUL 74 18 0.13 152 P3 TWD 11 DEC
+2.06 TEC TEH 15 HOT 600UL 74 44 0.16 71 P2 TWD 12 VSM
+0.76 TEC TEH 27 HOT 600UL 0.50 133 P2 TWD 27 VH3
-0.80 TEC TEH 27 HOT 60OUL 74 50 0.32 161 P3 TWD 20 DBH
+1.89 TEC TEN 40 HOT 60OUL 74 56 0.23 49 P3 TWD 9 DBH
+0.97 TEC TEH 41 HOT 60OUL 74 90 0.41 123 P3 TWD 21 DEC
-1.75 TEH TEC 24 COLD 600UL 74 94 0.20 35 P3 TWD 12 DBH
-1.63 TEH TEC 22 COLD 60OUL 74 124 0.20 96 P3 TWD 9 DEC
-1.77 TEC TEH 33 HOT 600UL 74 132 0.28 103 P2 TWD 15 VC3
-0.99 TEC TEH 10 HOT 600UL 74 148 0.31 126 P2 TWD 18 VSM
-0.95 TEC TEH 13 HOT 600UL 0.44 55 P2 TWD 22 VH3
-0.93 TEC TEH 13 HOT 600UL 74 156 0.59 46 P2 TWD 26 VC3
-0.76 TEC TEH 18 HOT 600UL 0.41 87 P2 TWD 21 VSM
-0.85 TEC TEH 18 HOT 60OUL 0.57 95 P2 TWD 26 VH3
-0.87 TEC TEH 18 HOT 600UL 75 15 0.10 162 P3 TWD 8 DBH
+1.29 TEC TEH 11 HOT 600UL 75 23 0.14 46 P3 TWD 12 DEC
+1.69 TEC TEH 19 HOT 600UL 75 51 0.15 94 P3 TWD 6 DBH
-2.24 TEC TEH 41 HOT 60OUL 75 53 0.12 91 P1 SCI TSH
-0.03 TSH TSH 71 HOT 58OPP 75 83 0.51 54 P3 TWO 19 DEC
-2.01 TEN TIC 23 COLD 600UL 75 87 0.51 19 P3 TWD 19 DEC
+2.25 TEH TEC 23 COLD 600UL 0.70 119 P3 TWD 24 DEC
-2.23 TEH TEC 23 COLD 600UL 75 97 0.23 85 P2 TWD 13 VC3
-0.88 TEH TEC 22 COLD 600UL 0.34 105 P2 TWD 18 VC3
+0.90 TEH TEC 22 COLD 60OUL 75 103 0.19 139 P2 TWD 11 VC3
+0.91 TEC TEH 38 HOT 600UL 76 42 0.22 126 P3 TWD 16 DEC
-1.79 TEC TEH 27 HOT 600UL 76 56 0.32 21 P3 TWD 20 DBH
+1.18 TEC TEH 40 HOT 600UL 76 78 0.27 143 P2 TWD 15 VC3
-0.86 TEH TEC 24 COLD 600UL 0.55 125 P2 TWD 25 VC3
+0.86 TEH TEC 24 COLD 600UL 0.26 117 P2 TWD 15 VH3
+0.84 TEH TEC 24 COLD 600UL 76 84 0.37 5
P3 TWD 15 DEC
+2.15 TEI TEC 23 COLD 60OUL 76 90 0.42 118 P3 TWD 16 DEC
-2.00 TEH TEC 23 COLD 600UL 0.30 33 P3 TWD 12 DBC
+2.15 TEH TEC 23 COLD 600UL 76 114 0.38 78 P2 TWD 19 VH3
-0.87 TEC TEH 32 HOT 600UL 76 138 0.14 14 P3 TWD 8 DEC
+1.93 TEC TEH 9
HOT 600UL
AREVA NP Inc Customer Name: San Onofre -
Unit 2 1/9/2008 2:18:17 PM Component:
S/G 89 Page 10 of 16 Post U2C1S Inspection Final Report MAT, MCI, MMI, MVI, SAT, SCI, SVI, 0-100%, PCS QUERY: QueryMi [2[.ary ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 76 142 0.21 91 P2 TWD 13 08C
-0.49 TEC TEH 13 HOT 600UL 76 160 0.43 74 P2 TWD 22 VH3
+0.84 TEC TEH 17 HOT 600UL 77 27 0.24 80 P3 TWD 10 DBC
-1.69 TEC TEH 20 HOT 600UL 77 43 0.30 124 22 TWD 13 VH3
+0.78 TEC TEH 28 HOT 60OUL 77 113 0.18 103 P2 TWD 11 VH3
-1.04 TEC TEH 33 HOT 60OUL 77 137 0.64 98 P2 TWD 26 VSM
-0.90 TEC TEH 10 HOT 60OUL 77 139 0.60 132 P2 TWD 25 VC3
+0.77 TEC TEH 10 HOT 60OUL 0.25 99 P2 TWD 13 VC3
-0.90 TEC TEH 10 HOT 600UL 0.33 61 P2 TWD 17 VSM
-0.92 TEC TEH 10 HOT 600UL 0.31 105 P2 TWD 16 VH3
-1.03 TEC TEH 10 HOT 600UL 77 157 0.38 75 P2 TWD 20 VH3
-0.95 TEC TEH 17 HOT 60OUL 78 26 0.24 130 P2 TWD 18 07C
-0.14 TEC TEH 19 HOT 600UL 78 28 0.07 138 P3 TWD 6 DBC
-1.65 TEC TEH 23 HOT 600UL 78 44 0.33 127 P2 TWD 21 VSM
-0.78 TEC TEH 27 HOT 600UL 78 58 0.24 173 P3 TWD 16 DBH
+1.61 TEC TEH 40 HOT 60OUL 78 130 0.31 132 P2 TWD 15 VSM
-1.02 TEC TEH 10 HOT 60OUL 78 136 0.26 144 P2 TWD 14 VC3
-0.89 STH TEC 38 COLD 600UL 78 150 0.57 64 P2 TWD 24 VH3
-0.74 TEC TEH 14 HOT 60OUL 78 160 0.30 124 P3 TWD 15 DBC
-1.56 TEC TEH 18 HOT 60OUL 79 15 0.13 117 P3 TWD 10 DBH
+1.21 TEC TEN 11 HOT 600UL 79 43 0.23 45 P2 TWD 16 VH3
-0.62 TEC TEH 27 HOT 600UL 79 53 0.57 21 P1 SCI TSH
-0.02 TSH TSH 71 HOT 580PP 79 79 0.41 143 P2 TWD 16 VH3
-0.92 TEH TEC 23 COLD 600UL 79 89 0.17 108 2 SAI TSH
+1.00 TSH TSH 53 HOT 58OPP 79 99 0.33 125 P1 SCI TSH
-0.00 TSH TSH 57 HOT 580PP 80 72 0.20 88 P3 TWD 15 DBH
-2.24 TEC TEH 44 HOT 600UL 80 106 0.29 78 P2 TWD 16 VH3
+0.91 TEC TEH 32 HOT 600UL 80 152 0.59 108 P2 TWD 27 VC3
+0.86 0.67 105 P2 TWD 29 VC3
-0.80 0.33 123 P2 TWD 18 VSM
+0.86 0.52 137 P2 TWD 25 VSM
-0.82 80 160 0.63 117 P3 TWD 27 DBC
-1.59 81 21 0.15 87 P3 TWD 12 DBE
+0.78 81 25 0.13 158 P3 TWD 10 DBC
-1.38 81 75 0.34 125 22 TWD 17 VC3
+0.86 0.27 81 79 0.94 0.37 24 P3 TWD 13 100 P2 TWD 30 124 P2 TWD 15 DBH VH3 VC 3 TEC TEH 13 HOT 60OUL TEC TEH 13 HOT 600UL TEC TEH 13 HOT 600UL TEC TEH 13 HOT 600UL TEC TEH 17 HOT 600UL TEC TEN 11 NOT 600UL TEC TEH 11 HOT 600UL TEN TEC 17 COLD 600UL TEN TEC 17 COLD 600UL TEH TEC 13 COLD 60OUL TEH TEC 13 COLD 60OUL TEN TEC 9
COLD 6000L TEH TEC 9
COLD 600UL TEC TEN 5
NOT 600UL TEC TEN S
NOT D 60UL TEC TEH 9
HOT 60OUL TEC TEH 9
POT 600UL 81 105 0.55 148
?2 TWD 21 VH3
+0.99 0.29 114 P2 TWD 12 VSM
+0.87 81 135 0.41 123 P2 TWD 20 VH3
+0.92 0.24 157 P2 TWD 14 VH3
-0.73 81 159 0.33 72 P2 TWD 17 VH3
-0.87 0.26 87 P2 TWD 14 02H
-0.36 82 28 0.20 92 P2 TWD 16 VH3
-0.19 0.23 99 22 TWD 18 VH3
-0.68 TEC TEH 11 HOT TEC TEH 11 HOT 600UL - -- --
600UL
AREVA NP Inc 1/9/2008 2:18:17 PM Customer Name: San Onofre -
Unit 2 Component:
S/G 89 Page 11 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[2].qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 82 44 0.22 138 P2 TWD 13 VH3
+0.91 TEC TER 7
HOT 600UL 82 68 0.42 140 P2 TWD 20 VH3
+0.86 TEH TEC 17 COLD 600UL 0.89 127 P2 TWD 32 VH3
-0.86 TEM TEC 17 COLD 60OUL 82 148 0.61 125 P2 TWD 26 VH3
-0.89 TEC TEH 9
HOT 600UL 83 73 0.29 111 2 SAI 03H
-0.11 03H 03H 171 HOT 580PP 84 40 0.38 64 P2 TWD 22 VH2
-1.14 TEC TEH 8
HOT 600UL 84 100 0.47 66 P2 TWD 22 09H
-1.59 TEH TEC 12 COLD 60OUL 84 108 0.40 127 P2 TWD 19 09H
+0.39 TEH TEC 10 COLD 600UL 85 81 0.31 102 P1 SCI TSH
+0.19 TSH TSH 107 HOT 580PP 85 91 0.25 93 P3 TWD 9 DBC
-1.85 TEN TEC 11 COLD 60OUL 86 68 0.37 42 P2 TWD 19 VH2
+0.82 TEN TEC 17 COLD 60OUL 86 130 0.37 114 P2 TWD 19 VH2
-0.77 TEC TEH 5
HOT 600UL 87 31 0.82 19 2
SAI 05H
+0.33 05H 05H 143 HOT 580PP 87 47 0.18 105 2 SAT 03H
-0.21 03H 03H 165 HOT 58OPP 87 131 0.35 122 P2 TWD 18 VH2
+0.66 TEC TEH 5
HOT 600UL 88 40 0.23 76 P2 TWD 14 VSM
-0.93 TEC TEH 8
HOT 60OUL 89 25 0.14 36 P3 TWD 11 DBH
+0.04 TEC TEH 11 HOT 600UL 89 93 0.48 17 2
SAI TSH
-13.00 TSH TSH 113 HOT 580PP 90 122 0.38 140 P2 TWD 19 VH2
-0.78 TEN TEC 8
COLD 60OUL 91 85 0.33 104 2
SAI 03H
+0.20 03H 03H 176 HOT 580PP 93 113 0.35 67 2
SAT 02H
+0.84 02H 02H 174 HOT 580PP 94 22 0.23 93 P2 TWD 11 02C
+0.93 TEC TEN 12 HOT 60OUL 94 50 0.33 133 P2 TWD 14 05C
-0.12 TEN TEC 21 COLD 60OUL 94 146 0.23 124 P2 TWD 14 VH3
-0.96 TEC TER 5
HOT 600UL 97 37 0.50 115 P2 TWD 26 VC3
+0.95 TEC TEH 8
HOT 600UL 98 62 1.26 20 2
SAI TSH
-13.92 TSH TSH 101 HOT 580PP 98 82 0.31 100 2 SAI 01H
-0.44 01H 01H 176 HOT 58OPP 99 131 0.30 124 P2 TWD 16 VH2
+0.73 TEC TEH 5
HOT 600UL 101 25 0.33 118 P2 TWD 15 08H
+0.47 TEC TEN 12 HOT 600UL 101 33 0.20 20 P3 TWD 12 DBC
+2.00 TEC TEN 7
HOT 600UL 101 39 0.32 99 P2 TWD 19 VH2
+0.85 TEC TEH 8
HOT 600UL 101 143 0.24 121 P3 TWD 15 DBH
+1.84 TEC TEH 5
HOT 600UL 102 58 0.38 124 P2 TWD 16 VH3
+0.86 TEN TEC 19 COLD 600UL 0.25 109 P2 TWD 11 VC3
+0.86 TEN TEC 19 COLD 60OUL 0.21 150 P2 TWD 10 VC3
-0.82 TEH TEC 19 COLD 600UL 0.25 125 P2 TWD 11 VC2
-0.89 TEN TEC 19 COLD 60OUL 103 137 0.39 92 P2 TWD 20 VH3
-0.92 TEC TEH 6
HOT 60OUL 105 61 0.20 141 P2 TWD 11 VC3
-0.80 TEN TEC 20 COLD 600UL 105 141 0.19 148 P3 TWD 12 DBH
+1.78 TEC TEN 5
HOT 600UL 106 84 0.34 120 P2 TWD 15 VH3
+0.80 TEH TEC 13 COLD 600UL 106 126 0.44 94 2
MAI 02H
+0.24 02H 02H 174 HOT 580P?
107 33 0.21 38 P3 TWD 16 DBC
+1.65 TEC TER 7
HOT 60OUL
AREVA NP Inc 1/9/2008 2:18:17 PM Customer Name:
San Onofre -
Unit 2 Component:
S/G 89 Page 12 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: Querytl [2].qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 107 35 0.25 128 P3 TWD 16 DBC
+2.00 TEC TEH 7
HOT 600UL 107 59 0.32 60 P3 TWD 17 DBH
+1.77 TEH TEC 20 COLD 600UL 107 103 0.51 70 P2 TWD 23 VH2
-0.89 TEH TEC 12 COLD 60OUL 108 42 0.35 104 P3 TWD 13 DBH
+1.86 TEC TEH 8
HOT 60OUL 0.35 127 P3 TWD 13 DBH
-2.25 TEC TEH 8
HOT 60OUL 108 52 1.22 16 2
SAI 06H
+0.67 06H 06H 165 HOT 580PP 108 126 0.33 91 2
SAI 02H
+0.66 02H 02H 174 HOT 580PP 109 47 0.31 130 P2 TWD 17 VSM
-0.58 TEH TEC 22 COLD 600UL 0.29 47 P2 TWD 16 VC3
-0.70 TEH TEC 22 COLD 60OUL 109 55 0.25 133 P3 TWD 14 DBH
+1.48 TEH TEC 20 COLD 60OUL 110 34 0.28 140 P2 TWD 17 VH2
+0.76 TEC TEH 7
HOT 600UL 110 122 0.30 88 2
SAI 02H
+0.82 02H 02H 174 HOT 580PP 111 43 0.35 95 P2 TWD 21 VH3
-0.95 TEC TEH 8
HOT 60OUL 111 87 0.43 95 P2 TWD 17 VC2
+0.91 TEH TEC 13 COLD 60OUL 11 99 0.47 56 P2 TWD 17 09C
+0.51 TEH TEC 11 COLD 60OUL 112 32 0.32 122 P3 TWD 12 DBC
+1.80 TEC TEH 8
HOT 60OUL 112 134 0.54 97 2
SAI 02H
+0.50 02H 02H 174 HOT 580PP 112 144 0.46 51 P3 TWD 21 DBC
+2.05 TEC TEH 6
HOT 60OUL 113 53 0.24 78 P2 TWD 13 VC2
-0.52 TEH TEC 22 COLD 600UL 113 77 0.31 114 P2 TWO 13 VC3
+0.92 TEN TEC 13 COLD 6--UL 113 91 0.31 121 P2 TWD 16 VC3
-0.84 TEH TEC 12 COLD 600UL 113 105 0.40 79 P2 TWD 19 VN2
+0.79 TEH TEC 10 COLD 60OUL 0.33 73 P2 TWD 17 VH3
+0.81 TEH TEC 10 COLD 60OUL 113 125 0.23 23 P2 TWD 13 05H
-0.18 TEN TEC 8
COLD 600UL 114 36
- 0.22 76 P2 TWD 13 09C
-1.01 TEC TEH 7
HOT 600UL 0.12 21 P3 TWD 10 DBC
-1.98 TEC TEH 7
HOT 60OUL 114 40 0.35 67 P3 TWD 21 DBH
+1.51 TEC TEH 7
HOT 600UL 114 62 0.32 135 P3 TWD 13 DBH
-1.77 TEH TEC 19 COLD 60OUL 114 136 0.31 147 P2 TWD 17 VC3
+0.67 TEC TEH 6
HOT 60OUL 115 39 0.75 134 P2 TWD 28 VHI
+0.81 TEC TEH 8
HOT 60OUL 115 43 0.65 144 P2 TWD 26 VHI
+0.83 TEC TEH 8
HOT 60OUL 0.64 161 P2 TWD 25 VH1
-0.70 TEC TEH 8
HOT 60OUL 115 107 0.26 127 P3 TWD 11 DBH
-1.38 TEH TEC 9
COLD 600UL 116 50 0.25 61 P2 TWD 11 VH2
-1.15 TEH TEC 21 COLD 600UL 116 90 0.47 79 P2 TWD 21 VH1
-1.13 TEH TEC 14 COLD 600UL 116 102 0.64 38 P2 TWD 22 VHN
-0.69 TEH TEC 11 COLD 600UL 116 128 0.46 77 P3 TWD 22 DBH
-1.66 TEH TEC 8
COLD 600UL 116 140 0.24 104 P3 TWD 13 DBH
-1.50 TEC TEH 6
HOT 600UL 117 59 0.37 22 P3 TWD 19 DBH
-1.18 TEH TEC 20 COLD 600UL 117 129 0.42 131 P2 TWD 18 05H
-0.16 TEH TEC 7
COLD 60OUL 118 62 0.41 98 2
SAI 01H
+0.95 01H 01H 171 NOT 580PP 0.25 110 2
SAI 04H
+0.95 04H 04H 171 HOT 58OPP 118 124 0.23 78 2
SAI 02H
+0.43 02H 02H 174 HOT 580PP
AREVA NP Inc 1/9/2008 2:18:17 PM Customer Name: San Onofre -
Unit 2 Component:
S/G 89 Page 13 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[2].qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 118 128 0.29 101 P2 TWD 13 05H
+0.70 TEH TEC 7
COLD 600UL 119 79 0.68 132 P2 TWD 24 VH3
+0.86 TEH TEC 13 COLD 600UL 119 119 0.42 30 P2 TWD 18 10H
-1.08 TEH TEC 7
COLD 600UL 119 121 0.53 98 P2 TWD 21 10H
-1.20 TEH TEC 7
COLD 60OUL 120 38 0.23 66 P2 TWD 15 10H
+1.05 TEC TEH 8
HOT 600UL 120 72 0.23 61 P2 TWD 13 10H
-1.02 TEH TEC 17 COLD 600UL 120 98 0.48 80 P2 TWD 23 VHl
-0.80 TEH TEC 12 COLD 600UL 121 39 0.27 100 P2 TWD 17 10H
-1.44 TEC TEH 8
HOT 600UL 121 45 0.62 108 P2 TWD 29 VC2
-0.62 TEC TEH 8
HOT 60OUL 121 47 0.31 113 P2 TWD 16 10H
+0.76 TEH TEC 22 COLD 600UL 121 83 0.53 125 P2 TWD 23 VC3
-0.88 TEH TEC 14 COLD 60OUL 0.38 134 P2 TWD 18 VHl
+0.84 TEH TEC 14 COLD 60OUL 121 109 0.87 88 P2 TWD 31 10H
-1.50 TEH TEC 10 COLD 600UL 122 110 0.23 102 2 SAI 05H
-0.30 05H 05H 174 HOT 58OPP 123 45 0.29 17 P3 TWD 18 DBH
+2.02 TEC TEH 7
HOT 600UL 123 117 0.31 141 23 TWD 12 DBH
-1.90 TEH TEC 9
COLD 600UL 124 58 0.54 128 P2 TWD 24 VHl
-0.78 TEH TEC 20 COLD 600UL 124 98 0.26 7
P3 TWD 14 DBH
+1.86 TEH TEC 12 COLD 60OUL 125 53 0.31 133 P2 TWD 17 VHl
-0.79 TEH TEC 22 COLD 600UL 125 55 0.21 117 P3 TWD 12 DBH
+1.69 TEH TEC 20 COLD 600UL 125 77 0.42 128 P2 TWD 20 VHl
+0.92 TEH TEC 14 COLD 600UL 125 111 0.25 168 P3 TWD 14 DBH
+1.69 TEH TEC 10 COLD 600UL 125 119 0.30 109 P3 TWD 16 DBH
+1.62 TEH TEC 8
COLD 60OUL 126 74 0.31 84 P2 TWD 17 VHl
-1.06 TEH TEC 17 COLD 60OUL 126 86 0.24 110 P3 TWD 9 DBH
-1.90 TEH TEC 13 COLD 600UL 126 102 0.26 24 P3 TWD 14 DBH
-1.26 TEH TEC 12 COLD 600UL 126 108 0.27 162 P3 TWD 11 DBH
-1.64 TEH TEC 9
COLD 600UL 127 71 0.41 142 P2 TWD 20 04H
+0.89 TEH TEC 17 COLD 600UL 127 99 0.39 151 P2 TWD 15 VHl
+0.84 TEH TEC 11 COLD 600UL 127 111 0.33 25 P2 TWD 14 04H
+0.20 TEH TEC 9
COLD 600UL 127 123 0.34 97 P2 TWD 15 09C
-1.20 TEH TEC 7
COLD 60OUL 128 56 0.23 168 P3 TWD 10 DBH
+2.04 TEH TEC 19 COLD 600UL 128 60 0.42 95 2
SAI 04H
+0.75 04H 04H 166 HOT 580PP 128 72 0.32 92 P2 TWD 17 10H
+0.94 TEH TEC 17 COLD 600UL 0.61 120 P2 TWD 26 10H
+0.08 TEH TEC 17 COLD 600UL 0.69 144 P2 TWD 28 iOH
-1.19 TEH TEC 17 COLD 600UL 128 92 0.52 43 22 TWO 19 06H
+0.93 TEN TEC i1 COLD 60OUL 129 47 0.48 141 P2. TWD 23 10H
+0.83 TEH TEC 22 COLD 600UL 0.42 130 P3 TWD 22 DBH
+1.67 TEH TEC 22 COLD 600UL 0.39 47 P3 TWD 21 DBH
-1.32 TEH TEC 22 COLD 600UL 129 49 0.44 90 P2 TWD 21 VHI
-0.83 TEH TEC 22 COLD 600UL 0.32 90 P2 TWD 17 VHi
+0.91 TEH TEC 22 COLD 600UL 129 73 0.26 65 P3 TWO 16 DEN
+1.92 TEN TIC 18 COLD SOQUL--------------------
129 73 0.26 65 P3 TWD 16 DBE
+1.92 TEH TEC 18 COLD 600UL
AREVA NP Inc 1/9/2008 2:18:17 PM Customer Name:
San Onofre -
Unit 2 Component: S/G 89 Page 14 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MVI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMi[2].qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
==-------------------=--=----------------
129 89 0.27 60 P2 TWD 14 VH2
-0.88 TEH TEC 14 COLD 600UL 0.23 154 P2 TWD 12 VH3
-0.86 TEH TEC 14 COLD 600UL 0.24 87 P2 TWD 12 VC3
-1.07 TEH TEC 14 COLD 60OUL 0.23 76 P2 TWD 12 VC3
+0.82 TEH TEC 14 COLD 600UL 0.26 100 P2 TWD 14 VH2
+0.88 TEH TEC 14 COLD 600UL 129 109 0.43 139 P2 TWD 20 10H
-1.05 TEH TEC 10 COLD 60OUL 130 48 0.35 68 P2 TWD 18 02C
-0.18 TEH TEC 22 COLD 600UL 130 74 0.37 99 P2 TWD 19 10H
+0.96 TEH TEC 17 COLD 600UL 130 78 0.30 93 P2 TWD 12 10H
-1.22 TEH TEC 13 COLD 600UL 130 82 0.67 82 2
SAI 01H
-0.27 01H 01H 176 HOT 580PP 130 86 0.50 111 P2 TWD 20 VHN
+0.87 TEH TEC 13 COLD 60OUL 130 88 0.46 109 P2 TWD 22 VH1
-0.88 TEH TEC 14 COLD 600UL 132 56 0.62 131 P2 TWD 26 VHN
-1.02 TEH TEC 17 COLD 600UL 132 74 0.30 108 P3 TWD 14 DBH
+1.70 TEH TEC 17 COLD 600UL 132 106 0.71 125 P2 TWD 26 10H
-1.09 TEH TEC 15 COLD 60OUL 133 55 0.28 75 P2 TWD 15 02H
+0.22 TEH TEC 17 COLD 60OUL 133 81 0.58 130 P2 TWD 23 VHN
+0.90 TEH TEC 15 COLD 60OUL 133 119 0.57 114 P2 TWD 24 VHN
+0.92 TEH TEC 16 COLD 600UL 133 125 0.35 91 P2 TWD 17 01C
+0.88 TEH TEC 16 COLD 60OUL 134 64 0.31 98 P2 TWD 16 VH3
-0.90 TEH TEC 18 COLD 600UL 0.34 139 P2 TWD 17 VC3
-0.84 TEH TEC 18 COLD 600UL 134 76 0.39 78 P2 TWD 18 VHN
-0.86 TEH TEC 16 COLD 600UL 0.28 11 P3 TWD 14 DBH
+2.19 TEH TEC 16 COLD 600UL 134 80 0.29 6
P3 TWD 15 DBH
+2.04 TEH TEC 16 COLD 600UL 134 124 0.23 119 P2 TWD 12 VC3
+0.65 01C TEH 132 HOT 60OUL 135 67 0.34 84 P3 TWD 16 DBH
-1.62 TEH TEC 17 COLD 60OUL 135 71 0.23 161 P3 TWD 14 DBH
-1.80 TEH TEC 18 COLD 600UL 136 68 0.54 111 P2 TWD 24 VHN
-0.88 TEH TEC 17 COLD 600UL 0.33 95 P2 TWD 17 VH1
-1.13 TEH TEC 17 COLD 600UL 136 76 0.27 9
23 TWD 14 DBH
+1.85 TEH TEC 16 COLD 600UL 136 78 0.23 123 P3 TWD 12 DBH
+1.79 TEH TEC 16 COLD 600UL 0.31 48 P2 TWD 15 VH1
+0.72 TEH TEC 16 COLD 600UL 137 69 0.37 82 P2 TWD 19 VHN
+0.55 TEH TEC 17 COLD 600UL 137 71 0.45 48 P3 TWD 19 DBH
-1.64 TEH TEC 17 COLD 600UL 137 117 0.32 140 P3 TWD 16 DBH
+1.67 TEH TEC 16 COLD 600UL 0.40 115 P2 TWD 18 VHN
-0.82 TEN TEC 16 COLD 60OUL 138 58 0.44 69 P3 TWD 23 DBH
+1.87 TEH TEC 18 COLD 60OUL 138 64 0.27 101 P2 TWD 14 10H
+0.80 TEH TEC 18 COLD 600UL 138 80 0.40 70 P2 TWD 18 VHi
-0.86 TEH TEC 16 COLD 600UL 138 96 0.23 149 P3 TWD 12 DBC
+1.13 TEH TEC 16 COLD 600UL 138 102 0.44 97 P2 TWD 20 VHI
-0.86 TEH TEC 16 COLD 60OUL 139 61 0.24 104 P2 TWD 13 09C
-1.09 TEH TEC 18 COLD 600UL 139 65 0.31 95 P2 TWD 17 VH!
+0.88 TEH TEC 17 COLD 600UL 139 103 0.62 138 22 TWD 24 VH2
+0.84 TEH TEC 15 COLD 600UL
AREVA NP Inc 1/9/2008 2:18:17 PM Customer Name:
San Onofre -
Unit 2 Component: S/G 89 Page 15 of 16 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%,
PCS QUERY: QueryMl[2].qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
===========--
=== =--
-:===========================
- -----=======:==
= ------------
139 115 0.23 158 P3 TWD 12 DBH
+1.64 TEH TEC 16 COLD 60OUL 140 66 0.16 148 P3 TWD 8 DBH
+1.87 TEH TEC 17 COLD 60OUL 140 90 0.45 69 P2 TWD 20 VHl
-0.84 TEH TEC 16 COLD 60OUL 140 112 0.22 7
P3 TWD 12 DBC
+1.61 TEH TEC 16 COLD 60OUL 141 67 0.31 71 P2 TWD 16 09C
-1.07 TEH TEC 18 COLD 60OUL 141 83 0.24 136 P3 TWD 12 DBH
+1.80 TEH TEC 16 COLD 600UL 141 89 0.37 114 P2 TWD 18 VHl
-0.66 TEH TEC 16 COLD 600UL 141 103 0.23 31 P3 TWD 12 DBH
+2.02 TEH TEC 16 COLD 600UL 0.26 31 P2 TWD 13 VH3
-0.90 TEH TEC 16 COLD 600UL 0.26 83 P2 TWD 13 VH3
+0.88 TEH TEC 16 COLD 600UL 141 109 0.54 88 P2 TWD 22 VH3
+0.00 TEH TEC 15 COLD 60OUL 142 72 0.56 92 P3 TWD 27 DBC
+2.05 TEH TEC 18 COLD 600UL 142 92 0.51 106 P2 TWD 22 VHl
-0.88 TEH TEC 16 COLD 600UL 143 71 0.74 105 P2 TWD 29 VHl
-0.86 TEH TEC 18 COLD 60OUL 0.53 81 P2 TWD 24 VHl
+0.53 TEH TEC 18 COLD 600UL 0.45 126 P2 TWD 21 VHI
+0.86 TEH TEC 18 COLD 600UL 0.32 108 P2 TWD 16 VH2
-0.86 TEH TEC 18 COLD 600UL 0.57 108 P3 TWD 27 DOH
+2.17 TEH TEC 18 COLD 60OUL 143 75 0.30 151 P3 TWD 18 DBC
-1.68 TEH TEC 18 COLD 600UL 143 81 0.28 75 P2 TWD 14 VC1
-0.78 TEH TEC 16 COLD 600UL 143 85 0.24 99 P3 TWD 13 DBC
+1.32 TEH TEC 16 COLD 600UL 143 87 0.34 131 P2 TWD 15 10C
+0.88 TEH TEC 15 COLD 600UL 0.59 61 P3 TWD 21 DBC
+1.87 TEH TEC 15 COLD 600UL 0.26 53 P3 TWD 8 DBC
-1.99 TEH TEC 15 COLD 600UL 143 91 0.19 52 P3 TWD 11 DBH
+1.52 TEH TEC 16 COLD 600UL 143 105 0.22 166 P3 TWD 12 DBH
+1.81 TEH TEC 16 COLD 600UL 143 107 0.22 18 P3 TWD 12 DBH
-1.26 TEH TEC 16 COLD 60OUL 143 109 0.67 102 P3 TWD 27 DBC
-1.93 TEH TEC 16 COLD 600UL 144 78 0.25 148 P2 TWD 13 VC1
+0.82 TEH TEC 18 COLD 600UL 144 84 0.32 124 P3 TWD 13 DBC
-1.86 TEH TEC 15 COLD 60OUL 0.19 17 P3 TWD 8 DBC
+1.89 TEH TEC 15 COLD 60OUL 144 90 0.19 95 P2 TWD 10 VHI
-0.98 TEH TEC 16 COLD 600UL 144 102 0.26 71 P3 TWD 14 DBH
-1.64 TEH TEC 16 COLD 600UL 145 77 0.15 150 P3 TWD 10 DBH
-1.80 TEH TEC 18 COLD 60OUL 145 89 0.27 147 P3 TWD 14 DBH
+1.91 TEH TEC 16 COLD 600UL 0.44 84 P2 TWD 20 VC2
+0.90 TEH TEC 16 COLD 600UL 145 99 0.40 97 P3 TWD 19 DOH
+2.10 TEH TEC 16 COLD 60OUL 145 103 0.67 116 P3 TWD 27 DBH
+1.69 TEH TEC 16 COLD 600UL 146 76 0.28 78 P3 TWD 17 DBH
+2.17 TEH TEC 18 COLD 60OUL 146 78 0.50 96 P3 TWD 25 DBH
+1.84 TEE TEC 18 COLD 600UL 0.42 144 P3 TWD 23 DBC
+1.67 TEH TEC 18 COLD 60OUL 0.25 150 P3 TWD 15 DBC
-1.65 TEH TEC 18 COLD 600UL 146 80 0.26 145 P3 TWD 16 DBC
+1.62 TEH TEC 18 COLD 600UL 0.32 24 P3 TWD 19 DBH
+1.88 TEH TEC 18 COLD 600UL 146 88 0.51 55 P3 TWD 23 DBC
+1.64 TEH TEC 16 COLD 600UL Total Tubes
- 492 Total Records:
624
AREVA NP Inc Customer Name: San Onofre -
Unit 2 Post U2C15 Inspection Final Report
- MAI, MCI,
- MMI, MVIT, SAT,
- SCI, SVI, 0-100%,
PCS QUERY: QueryMl(2].qry ROW LINE VOLTS DEG CHN IND %TW LOCATION 1/9/2008 2:18:17 PM Component:
S/G 89 Page 16 of 16 EXT EXT CAL #
LEG PROBE