Final Status Survey Summary Report, March 3, 2008, Carbon Dioxide System Piping Survey Unit F8990511
ML081580597
Person / Time
Site: Rancho Seco
Issue date: 04/08/2008
From: Ellen Brown
Sacramento Municipal Utility District (SMUD)
To:
NRC/FSME
References
F8990511
Download: ML081580597 (17)


Text

Rancho Seco Final Status Survey Summary Report March 3, 2008 Carbon Dioxide System Piping Survey Unit F8990511 Prepared-By:

{

/

FSS Enqjnmee Date: 3*i1/3o, 2:

Date" Reviewed By:.

Approved By:

Date:

Dismantlement Superintendent, Radiological

FINAL STATUS SURVEY

SUMMARY

REPORT Survey Unit:

F899051 1, Carbon Dioxide System Piping Survey Unit

Description:

Operating History: This system transported liquid carbon dioxide for fire protection in areas of the site in which water could not be used. This system was designed to be clean.

Operating records and the HSA document no occurrences of radioactive contamination associated with this system piping. In addition, the system was maintained at or above atmospheric pressure which prevented any contamination from entering the system.

Site Characterization: Direct measurements were made of the interior surfaces of the system piping which confirmed the absence of plant-derived radionuclides. Direct measurements of the interior showed a mean gross activity level of 8,585 dpm/l100 cm 2 and a maximum value of 23,654 dpm/100 cm2. Based on the classification procedure (DSIP-0020) and levels of gross activity reported, the system was determined to be a Class 2 system.

HSA Events: None Survey Unit Design Information:

The Survey Unit Design Parameters are presented in Table 1 below. The survey unit and measurement locations are depicted on the maps in Attachment-1. Direct measurement locations were spaced at 15cm intervals and 1.8 m2 were scanned for approximately 72%

coverage. The instrumentation used for the survey along with the MDC values are listed in Tables 2-1 and 2-2 in Attachment 2.

Page 2 of 8 FSS Summary Report F8990511

Table 1. Survey Unit Design Parameters Survey Design Value Comment Parameter Survey Area:

Survey Unit:

Class:

SU Area (m2):

Evaluator:

DCGL (dpm/100 cm 2):

Area Factor:

Design DCGLemc (dpm/100 cm 2):

LBGR (dpm/100 cm 2):

Design Sigma (dpm/100 cm 2):

Type I Error:

Type II Error:

Predominant Nuclide:

Sample Area (m):

Scan Area (m 2):

Scan Coverage (%):

ZI-.

Sign P:

Calculated Relative Shift:

Relative Shift Used:

N-Value:

Design N-Value + 20%:

Design Min Samples N:

Grid Spacine L:

F899 0511 2

2.5 Erin L. Brown 100000 N/A N/A 50000

.8930 0.05 0.05 Cs-137 3

1.8 72%

1.645 1.645 0.99865 5.6 3

11 14 14 0.4 Carbon Dioxide System Piping Structure Surface LTP Table 5-4 Gross Activity DCGL Class 2 Class 2 Default 50% DCGL Class 2 Class 2 Uses 3.0 if Relative Shift is

>3 NUREG-1575 Table 5-5 Class 2 Class 2 A

Page 3 of 8 FSS Summary Report F8990511

Survey Results:

A total of 40 direct measurements were made in F89905 11. The results including mean, median, standard deviation and range are shown in Table 2. All direct measurements were less than the DCGL. None of the scan measurements indicated areas of elevated activity. Scan activity ranged from 1655 to 2275 dpm/1 00 cm 2, based on the pipe detector efficiency.

Table 2. Direct Measurement Results Measurement ID Gross Activity (dpm/100 cm F8990511-MOO01GI 1925 F8990511-MOO02GI 1742 F8990511-MOO03GI 1858 F8990511-MOO04GI 1963 F8990511-MOO05GI 1854 F8990511-MOO06GI-1767 F8990511-MOO07GI 1796 F8990511-MOO08GI 1655 F8990511-MOO09GI 1714 F8990511-MOOlOGI 1944 F8990511-MOOIIGI 1957 F8990511-MOO12GI 1897 F8990511-MOO13GI 2050 F8990511-MOO14GI 1882 F8990511-MOO15GI 1925 F8990511-MOO16GI 1828 F8990511-MOO17GJ 2196 F8990511-MOO18GI 1981 F8990511-MOO19GI 1888 F8990511-MOO20GI 1834 F8990511-MOO21GI 1740 F8990511-M0022GI 1908 F8990511-M0023GI 1852 F8990511-M0024GI 1866 F8990511-M0025GI 1912 F8990511-M0026GI 1796 F8990511-M0027GI 1712 F8990511-M0028GI 1838 F8990511-M0029GI 2043 F8990511-MOO30GI 1761 F8990511-MOO31GI 1716 F8990511-M0032GI 2024 F8990511-M0033GI 2011 F8990511-M0034GI 2131 F8990511-M0035GI 2097 F8990511-M0036GI 2103 F8990511-M0037GI 2248 F8990511-M0038GI 2275 F8990511-M0039GI 2254 F8940511-MOO40GI 2207 Page 4 of 8 FSS Summary Report F8990511

Mean:

1929 Median:

1903 Standard Deviation:

164 Range:

1655-2275 Page 5 of 8 FSS Summary Report F8990511

Survey Unit Data Assessment:

The survey design required 40 direct measurements for the Sign Test. The critical value and the results of the Sign Test are presented in Table 4. The sample mean and median values were less than the DCGL. The sample standard deviation was less than the design standard deviation so no additional samples were required.

Page 6 of 8 FSS Summary Report F8990511-

Table 4. Data Assessment Results Survey Results Parameter Value Comment Material Background Used (dpmlO00 cm 2):

N/A Ambient Background Used (dpm/100 cm2):

N/A Average Ambient BKG 0

Actual Direct Measurements (N):

40 Median (dpm/100 cm2):

1903 Mean (dpm/100 cm 2):

1929 Direct Measurement Standard Deviation 164 (dpm/100 cm2):

Total Standard Deviation (dpm/100 cm 2):

164 Based on samples and backgrounds.

Maximum (dpm/100 cm2):

2275 Material Type:

N/A Background Subtract Not Applied Sign Test Final N Value:

40 S+ Value:

40 Critical Value:

25 Sufficient Samples Collected:

Yes Maximum Value < DCGL:

Yes Median Value < DCGL:

Yes Mean Value < DCGL:

Yes Maximum Value < DCGLemc:

N/A Class 2 Total Standard Deviation <= Sigma:

Yes Pass the Sign Test?

Yes Reject the Null Hypothesis?

Yes Does the Survey Unit Pass All Criteria?

Yes Page 7 of 8 FSS Summary Report F8990511

Survey Unit Investigations and Results:

No investigations were required and no investigation results are reported.

ALARA Statement:

As stated in Chapter 4 of the LTP, as long as the residual activity within the survey unit is less than the DCGL (i.e. the survey unit average activity is less than the DCGL), the ALARA criterion has been met.

Changes in Initial Survey Unit Assumptions:

The survey unit was designed as a Class 2 structure survey and the sample results are consistent with that classification. The variability of the survey results was less than the characterization data used for survey design. No potential areas of elevated activity were detected.

==

Conclusion:==

The FSS of this survey unit was properly designed as a Class 2 survey based on Table 5-4 of the LTP. The required number of direct measurements was made and the scan coverage met the requirement of Table 5-6 of the LTP. No direct measurements exceeded the DCGL of 100000 dpm/100 cm 2 or the grout limit of 21,000dpm/100cm 2. No investigations were required.

The direct measurement data support rejection of the null hypothesis, providing high confidence that the survey unit satisfied the release criteria and that the data quality objectives were met.

It is concluded that survey unit F899051 1 meets the release criteria of I0CFR20.1402.

Page 8 of 8 FSS Summary Report F8990511 Maps March 3, 2008 Survey Unit F8990511

CD rtQ 0

E081360 E0513877 N1883624 NI 8S674 KEY PLAN LEGENP

.REMAINING UNDERGROUND RMVDPPINd CONTNNMFT 00 PIPING SIJMK%4AJI 32 LENG 6EA 4*'0 20 LF. I2SM 1-0 201Y

.5SSI CARBRON DIOXIDE GAS U ND ERG. ROU ND PIPING F899,051 1 -M 1 Sir-OF I RC Il I ~3 Instrumentation March 3, 2008 Survey Unit F8990511

Table 2-1. Survey Unit Instrumentation Instrument Detector MDC Static MDC Scan Model; Serial No.

Model; Serial No.

(dpm/100 cm2)

(dpm/100 cm2 )

M2350; 189081 44-159; 199736 2860 N/A Table 2-2. Investigation Criteria and DCGL Value P a r a m e t e r 'V

.a u C M (dpm/100 cm2)

Investigation Criteria - Direct 100000 Investigation Criteria - Scan N/A DCGLw 100000 DCGLEMC N/A Page 2 of 2 Att. 2 Instrumentation F8990511 Investigation March 3, 2008 Survey Unit F8990511 (none required)

Data Assessment March 3, 2008 Survey Unit F8990511

0 CD~

F8990511 Gross Activity Sample Results Quantile Plot DCGL = 100000 dpm/lOOcm 2 2,500 2,000 1903 I.

3m 1,500 1,000 500 0

0 20 40 60 80 100 It0 Percentile Direct Measurements (dpm/1 00cm2)

-median

- 75th Percentile

- 50th Percentile

ct~

0 F8990511 Gross Activity Sample Results Scatter Plot DCGL = 100000 dpm/1OOcm 2 Cl)

Cl)

(1) 00 3.000 p'2500-E 2000 EL 1500 S1000 500 0

0000000000 0

0 00 0lll 0

I 1

.0 mm

.Q.0

=.

0",

0O0 0

0 0

0 00 00 2421 1929 1436

-i I

I II I

II liii II I

0000000000000000000000000000000000000000 Measurement Locations 0 0 Gross Activity Average -

"+3StDev" -

"-3StDev"l

0 F899051 1 Gross Activity Frequency Plot DCGL = 100000 dpm/1 00cmr 00 I'D 0

a)

Ci 9

8 7

6 5

4 3

2 1

0

-4.

-4.

Bins -

~1~

~1~

Value

~1~

~1~

ZIZIELI Upper End N.

(dpm/1 00cm2)

ILO