ML072890047

From kanterella
Jump to navigation Jump to search

D.C. Cook - Draft RAI Re. EDG Maximum Steady State Frequency
ML072890047
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 10/15/2007
From: Tam P
NRC/NRR/ADRO/DORL/LPLIII-1
To: Scarpello M, Simpson S, Steinmetz K
American Electric Power Co, Indiana Michigan Power Co
tam P, NRR/ADRO/DORL, 415-1451
References
TAC MD5899, TAC MD5900
Download: ML072890047 (3)


Text

From:

Peter Tam To:

Scarpello, Michael; Simpson, Sue; Steinmetz, Keith Date:

10/15/2007 7:59:09 AM

Subject:

D.C. Cook - Draft RAI re. EDG Maximum Steady State Frequency (TAC MD5899, MD5900)

Keith:

By letter dated 6/26/07 I&M requested an amendment to the D.C. CookTechnical Specifications (TS) surveillance requirement related to emergency diesel generator (EDG) testing. Our review of that submittal is ongoing, but we determined that additional information as outlined below is needed. We would like to discuss the information need in a conference call, but plan to formally issue the draft questions around 11/15/07 with or without a conference call:

(1) Clarify how the panel instrument errors are accounted for in the proposed EDG frequency values indicated in the TS.

(2) Provide the EDG manufacturer=s various ratings for the EDGs such as the continuous and the short-time ratings.

(3) State which NRC Regulatory Guides, IEEE Standards, or other guidance documents (and the revision numbers of those documents) to which D.C. Cook is committed for the purposes of EDG design and testing.

(4) Provide a summary of the latest EDG sizing calculation, including a copy of the purpose, assumptions, and conclusions section of the calculation.

(5) The NRC staff has identified an issue with D.C. Cook=s EDG voltage values in TS 3.8.1.

The voltage values indicated in the SRs of TS 3.8.1 are lower than the minimum degraded voltage function allowable value indicated in TS SR 3.3.5.3, which is not acceptable (see NRC Information Notice 2007-09, "Equipment Operability Under Degraded Voltage Conditions,"

ADAMS Accession Number ML070390066). Since the voltage values are contained within the same sentences in the TS that are affected by the proposed amendment to change the frequency values, the NRC staff cannot approve the amendment request knowing that there is a deficiency with the voltage values. Please propose how D.C. Cook plans to proceed regarding this issue and its effects on the proposed amendment.

The sole purpose of this e-mail is to prepare you and others for the proposed conference call.

This e-mail does not convey a formal NRC staff position, and does not formally request for additional information.

Peter S. Tam, Senior Project Manager Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation e-mail: pst@nrc.gov Tel.: 301-415-1451

CC:

Audrey Klett; Kemker, Brian; Lennartz, Jay Mail Envelope Properties (4713560D.BED : 12 : 35330)

Subject:

D.C. Cook - Draft RAI re. EDG Maximum Steady State Frequency (TAC MD5899, MD5900)

Creation Date 10/15/2007 7:59:09 AM From:

Peter Tam Created By:

PST@nrc.gov Recipients Action Date & Time aep.com Transferred 10/15/2007 7:59:23 AM kasteinmetz (Keith Steinmetz) mkscarpello (Michael Scarpello) sdsimpson (Sue Simpson) nrc.gov ch_po.CH_DO Delivered 10/15/2007 7:59:34 AM BJK1 CC (Brian Kemker)

Opened 10/15/2007 8:36:28 AM JAL3 CC (Jay Lennartz) nrc.gov OWGWPO04.HQGWDO01 Delivered 10/15/2007 7:59:15 AM ALK1 CC (Audrey Klett)

Opened 10/16/2007 7:21:38 AM Post Office Delivered Route aep.com ch_po.CH_DO 10/15/2007 7:59:34 AM nrc.gov OWGWPO04.HQGWDO01 10/15/2007 7:59:15 AM nrc.gov Files Size Date & Time MESSAGE 3179 10/15/2007 7:59:09 AM Options Auto Delete:

No Expiration Date:

None Notify Recipients:

Yes Priority:

Standard ReplyRequested:

No Return Notification:

None Concealed

Subject:

No

Security:

Standard To Be Delivered:

Immediate Status Tracking:

Delivered & Opened