ML071550295
| ML071550295 | |
| Person / Time | |
|---|---|
| Site: | Fermi (NPF-043) |
| Issue date: | 06/05/2007 |
| From: | Adrian Muniz NRC/NRR/ADRO/DORL/LPLIII-1 |
| To: | Jennifer Davis Detroit Edison |
| muniz A, ADRO/DORL/415-4044 | |
| References | |
| TAC MD2618 | |
| Download: ML071550295 (4) | |
Text
June 5, 2007 Mr. Jack M. Davis Senior Vice President and Chief Nuclear Officer Detroit Edison Company Fermi 2 - 210 NOC 6400 North Dixie Highway Newport, MI 48166
SUBJECT:
FERMI UNIT 2 - REQUEST FOR ADDITIONAL INFORMATION REGARDING PROPOSED LICENSE AMENDMENT TO EXTEND THE COMPLETION TIME FOR TECHNICAL SPECIFICATION 3.8.1 FOR AN INOPERABLE DIESEL GENERATOR (TAC NO. MD2618)
Dear Mr. Cobb:
By letter to the Nuclear Regulatory Commission (NRC) dated July 12, 2006, as supplemented by letters date April 25, and May 23, 2007, Detroit Edison Company submitted a request to modify Conditions, required Actions and Completion Times associated with the inoperability of one or more emergency diesel generators in Technical Specification 3.8.1, for Fermi Unit 2.
The April 25, and May 23, 2007, letters, provided responses to NRC's requests for additional information regarding the risk-informed and deterministic portion of your submittal. The NRC staff is reviewing your submittal, and the supplemental information provided, and has determined that additional information is required to complete the review. The specific information requested is addressed in the enclosure to this letter. During a discussion with your staff on June 1, 2007, it was agreed that a response will be provided by June 15, 2007.
The NRC staff considers that timely responses to requests for additional information help ensure sufficient time is available for staff review and contribute toward the NRCs goal of efficient and effective use of staff resources. If circumstances result in the need to revise the requested response date, please contact me at (301) 415-4093.
Sincerely,
/RA/
Adrian Muniz, Project Manager Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-341
Enclosure:
Request for Additional Information cc w/encl: See next page
June 5, 2007 Mr. Jack M. Davis Senior Vice President and Chief Nuclear Officer Detroit Edison Company Fermi 2 - 210 NOC 6400 North Dixie Highway Newport, MI 48166
SUBJECT:
FERMI UNIT 2 - REQUEST FOR ADDITIONAL INFORMATION REGARDING PROPOSED LICENSE AMENDMENT TO EXTEND THE COMPLETION TIME FOR TECHNICAL SPECIFICATION 3.8.1 FOR AN INOPERABLE DIESEL GENERATOR (TAC NO. MD2618)
Dear Mr. Cobb:
By letter to the Nuclear Regulatory Commission (NRC) dated July 12, 2006, as supplemented by letters date April 25, and May 23, 2007, Detroit Edison Company submitted a request to modify Conditions, required Actions and Completion Times associated with the inoperability of one or more emergency diesel generators in Technical Specification 3.8.1, for Fermi Unit 2.
The April 25, and May 23, 2007, letters, provided responses to NRC's requests for additional information regarding the risk-informed and deterministic portion of your submittal. The NRC staff is reviewing your submittal, and the supplemental information provided, and has determined that additional information is required to complete the review. The specific information requested is addressed in the enclosure to this letter. During a discussion with your staff on June 1, 2007, it was agreed that a response will be provided by June 15, 2007.
The NRC staff considers that timely responses to requests for additional information help ensure sufficient time is available for staff review and contribute toward the NRCs goal of efficient and effective use of staff resources. If circumstances result in the need to revise the requested response date, please contact me at (301) 415-4093.
Sincerely,
/RA/
Adrian Muniz, Project Manager Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-341
Enclosure:
Request for Additional Information cc w/encl: See next page DISTRIBUTION:
PUBLIC LPL3-1 R/F RidsNrrDorlLpl3-1 RidsNRRPMAMuniz RidsNrrLATHarris RidsAcrsAcnwMailCenter RidsOgcRp RidsRgn3MailCenter RidsNrrDorlDpr RidsNrrDraApla TValentine Clark, NRO ADAMS Accession Number: ML071550295 *previously concurred **concurred w/comments OFFICE LPL3-1/PM LPL3-1/LA APLA/BC LPL3-1/BC(A)
NAME AMuniz THarris MRubin*
TTate**
DATE 06/05/07 06/05/07 6/5/07 6/5/07 OFFICIAL RECORD COPY
Fermi 2 cc:
David G. Pettinari Legal Department 688 WCB Detroit Edison Company 2000 2nd Avenue Detroit, MI 48226-1279 Michigan Department of Environmental Quality Waste and Hazardous Materials Division Radiological Protection and Medical Waste Section Nuclear Facilities Unit Constitution Hall, Lower-Level North 525 West Allegan Street P.O. Box 30241 Lansing, MI 48909-7741 U.S. Nuclear Regulatory Commission Resident Inspector's Office 6450 N Dixie Highway Newport, MI 48166 Mr. M. V. Yudasz, Jr., Director Monroe County Emergency Management Division 965 South Raisinville Road Monroe, MI 48161 Regional Administrator, Region III U.S. Nuclear Regulatory Commission Suite 210 2443 Warrenville Road Lisle, IL 60532-4351 Ronald W. Gaston Manager, Nuclear Licensing Detroit Edison Company Fermi 2 - 200 TAC 6400 North Dixie Highway Newport, MI 48166 Supervisor - Electric Operators Michigan Public Service Commission P.O. Box 30221 Lansing, MI 48909 Wayne County Emergency Management Division 10250 Middlebelt Road Detroit, MI 48242 Mr. Donald K. Cobb Assistant Vice President - Nuclear Generation Detroit Edison Company 6400 North Dixie Highway Newport, MI 48166
ENCLOSURE REQUEST FOR ADDITIONAL INFORMATION LICENSE AMENDMENT REQUEST EMERGENCY DIESEL GENERATORS COMPLETION TIME EXTENSION DETROIT EDISON COMPANY FERMI UNIT 2 DOCKET NO. 50-341 By letter dated July 12, 2006, as supplemented by letters dated April 25, and May 23, 2007 (Agencywide Documents Access and Management System Accession Nos. ML062000325, ML071210491 and ML071500114, respectively), Detroit Edison Companys (DeCo) submitted a proposed amendment to the Technical Specifications (TS) for Fermi Unit 2. The proposed changes would modify Conditions, required Actions and Completion Times associated with the inoperability of one or more emergency diesel generators (EDGs) in TS 3.8.1. The Nuclear Regulatory Commission staff has determined that the following information is needed in order to complete its review:
- 1.
Are the combustion turbine generators 11-2, 11-3, and 11-4 and the dedicated blackstart diesel generator included within the scope of the plant's implementation of the maintenance rule? If not, please describe how the plant tracks/monitors and maintains the reliability of these generators consistent with the values used in the plant-specific probabilistic risk assessment.
- 2.
Explain the numerical basis for the small (vs. negligible) challenge to the Division 1 switchgear fire area when the EDG 14 is out of service.
- 3.
Of the fire zones that were screened out of the individual plant examination of external events, fire analysis based on a fire core damage frequency less than 1E-6, could a fire in any of these zones cause both a loss of offsite power and damage to a train of equipment needed for safe shutdown? If so, please describe the impact of the extended EDG completion time on the fire risk assessment for these areas.