Summary of May 14, 2007 Meeting to Discuss the Use of Fiber-Reinforced Polymer at Oconee
ML071370500
Person / Time
Site: Oconee  
Issue date: 05/22/2007
From: Olshan L
NRC/NRR/ADRO/DORL/LPLII-1
To:
Duke Power Co
Olshan L N, NRR/DORL, 415-1419
References
Download: ML071370500 (5)


Text

May 22, 2007 LICENSEE:

DUKE POWER COMPANY LLC (DUKE)

FACILITY:

OCONEE NUCLEAR STATION, UNITS 1, 2, AND 3 (OCONEE)

SUBJECT:

SUMMARY

OF MAY 14, 2007, MEETING TO DISCUSS THE USE OF FIBER-REINFORCED POLYMER (FRP) AT OCONEE On May 14, 2007, the U.S. Nuclear Regulatory Commission (NRC) met with Duke to discuss the use of FRP at Oconee to protect masonry walls from tornado-induced differential pressure.

At the beginning of the meeting, Duke provided a handout (available in the Agencywide Documents Access and Management System under accession number ML071360356). The handout was modified to reflect comments and agreements made during the meeting (ML071360351). Enclosed is a list of the attendees.

Duke stated that if the FRP license amendment request is not approved by July 2, 2007, it will impact the schedule for implementing the tornado-mitigation modifications. Duke stated that it will inform the NRC within 2 weeks as to when Duke can provide the additional information that the NRC requested.

/RA/

Leonard N. Olshan, Project Manager Plant Licensing Branch II-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-269, 50-270, and 50-287

Enclosure:

List of Attendees cc w/encl: See next page

LICENSEE:

DUKE POWER COMPANY LLC (DUKE)

FACILITY:

OCONEE NUCLEAR STATION, UNITS 1, 2, AND 3 (OCONEE)

SUBJECT:

SUMMARY

OF MAY 14, 2007, MEETING TO DISCUSS THE USE OF FIBER-REINFORCED POLYMER (FRP) AT OCONEE On May 14, 2007, the U.S. Nuclear Regulatory Commission (NRC) met with Duke to discuss the use of FRP at Oconee to protect masonry walls from tornado-induced differential pressure.

At the beginning of the meeting, Duke provided a handout (available in the Agencywide Documents Access and Management System under accession number ML071360356). The handout was modified to reflect comments and agreements made during the meeting (ML071360351). Enclosed is a list of the attendees.

Duke stated that if the FRP license amendment request is not approved by July 2, 2007, it will impact the schedule for implementing the tornado-mitigation modifications. Duke stated that it will inform the NRC within 2 weeks as to when Duke can provide the additional information that the NRC requested.

/RA/

Leonard N. Olshan, Project Manager Plant Licensing Branch II-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-269, 50-270, and 50-287

Enclosure:

List of Attendees cc w/encl: See next page Distribution:

PUBLIC T. Liu, NRR T. Quay, NRR LPL2-1 R/F P. Hiland, NRR S. Campbell, EDO Rgn II RidsNrrDorlLpl2-1 (EMarinos)

G. Wilson, NRR RidsRgn2MailCenter (JMoorman)

RidsNrrPMLOlshan (hard copy)

K. Manoly, NRR RidsNrrOd(Tech Comm Assist)

RidsNrrLAMOBrien (hard copy)

T. MCGinty, NRR RidsOgcRp J. Ma, NRR RidsAcrsAcnwmailCenter Accession Number: ML071370500 OFFICE NRR/LPL2-1/PM NRR/LPL2-1/LA NRR/LPL2-1/BC NAME LOlshan:nc MOBrien EMarinos DATE 05 / 22 /07 05 / 21 /07 05 / 22 /07 OFFICIAL RECORD COPY

Enclosure MEETING ATTENDEES FROM MAY 14, 2007, MEETING WITH DUKE POWER COMPANY LLC (DUKE)

TO DISCUSS THE MAY 14, 2007, USE OF FIBER-REINFORCED POLYMER AT OCONEE NRC DUKE P. Hiland T. Mills G. Wilson L. Llibre K. Manoly C. Davis T. McGinty L. Nicholson J. Ma S. Newman T. Quay J. Sumpter L. Olshan R. Freudenberger

Oconee Nuclear Station, Units 1, 2, and 3 cc:

Mr. Bruce H. Hamilton Vice President, Oconee Site Duke Power Company LLC 7800 Rochester Highway Seneca, SC 29672 Ms. Lisa F. Vaughn Associate General Counsel and Managing Attorney Duke Energy Carolinas, LLC 526 South Church Street - EC07H Charlotte, North Carolina 28202 Manager, LIS NUS Corporation 2650 McCormick Dr., 3rd Floor Clearwater, FL 34619-1035 Senior Resident Inspector U.S. Nuclear Regulatory Commission 7812B Rochester Highway Seneca, SC 29672 Mr. Henry Porter, Director Division of Radioactive Waste Management Bureau of Land and Waste Management Dept. of Health and Env. Control 2600 Bull St.

Columbia, SC 29201-1708 Mr. Michael A. Schoppman Framatome ANP 1911 North Ft. Myer Dr.

Suite 705 Rosslyn, VA 22209 Mr. B. G. Davenport Regulatory Compliance Manager Oconee Nuclear Site Duke Energy Corporation ON03RC 7800 Rochester Highway Seneca, SC 29672 Mr. Leonard G. Green Assistant Attorney General NC Department of Justice P.O. Box 629 Raleigh, NC 27602 Mr. R. L. Gill, Jr.

Manager - Nuclear Regulatory Issues and Industry Affairs Duke Power Company LLC 526 S. Church St.

Mail Stop EC05P Charlotte, NC 28202 Division of Radiation Protection NC Dept of Environment, Health, & Natural Resources 3825 Barrett Dr.

Raleigh, NC 27609-7721 Mr. Peter R. Harden, IV VP-Customer Relations and Sales Westinghouse Electric Company 6000 Fairview Road 12th Floor Charlotte, NC 28210 Mr. Henry Barron Group Vice President, Nuclear Generation and Chief Nuclear Officer P.O. Box 1006-EC07H Charlotte, NC 28201-1006 Mr. Charles Brinkman Director, Washington Operations Westinghouse Electric Company 12300 Twinbrook Parkway, Suite 330 Rockville, MD 20852 Ms. Kathryn B. Nolan Senior Counsel Duke Energy Carolinas, LLC 526 South Church Street - EC07H Charlotte, NC 28202