TAC Nos. MD4068 and MD4069 Docket 50-445 and 50-446 From:

Mohan Thadani To:

Internet:fred.madden@txu.com Date:

2/22/2007 9:43:08 AM

Subject:

Re: COMANCHE PEAK 01/18, 2007 REQUEST TO EXTEND AOT FOR OFFSITE CIRCUITS TO 30 DAYS Fred:

While performing an acceptance review of the revised LAR 06-007, the NRC review staff noted in FSAR Section 8.2.1 that CPSES has a SPARE STARTUP TRANSFORMER, which can be placed into service by operation of a single switch. This was not discussed in LAR 06-007.

Instead, TXU stated that to do transformer maintenance required a dual unit outage of 30 days.

The NRC staff has a question. Why can't this transformer be used during the 10-year maintenance?

Your response will be appreciated.

Thanks.

Mohan CC:

Howe, Andrew; Rubin, Mark; Terao, David; Wilson, George Mail Envelope Properties (45DDABFC.961 : 23 : 35106)

Subject:

Re: COMANCHE PEAK 01/18, 2007 REQUEST TO EXTEND AOT FOR OFFSITE CIRCUITS TO 30 DAYS Creation Date 2/22/2007 9:43:08 AM From:

Mohan Thadani Created By:

MCT@nrc.gov Recipients fred madden (Internet:fred.madden@txu.com) nrc.gov OWGWPO04.HQGWDO01 AJH1 CC (Andrew Howe) nrc.gov TWGWPO02.HQGWDO01 DXT CC (David Terao) nrc.gov TWGWPO03.HQGWDO01 MPR CC (Mark Rubin) nrc.gov TWGWPO04.HQGWDO01 GAW1 CC (George Wilson)

Post Office Route fred Internet:txu.com OWGWPO04.HQGWDO01 nrc.gov TWGWPO02.HQGWDO01 nrc.gov TWGWPO03.HQGWDO01 nrc.gov TWGWPO04.HQGWDO01 nrc.gov Files Size Date & Time MESSAGE 1625 2/22/2007 9:43:08 AM Options Expiration Date:

None Priority:

Standard ReplyRequested:

No Return Notification:

None Concealed

Subject:

No Security:

Standard