EMEflTS (conti rued)
SURVEI LLANCEE F
FRE OUEI C Y S1 3
1.3
. NOTES
- 1.
DG loadings may include gradual loading as recommended by the maniLITa*t
- rer.
- 2.
Momentary transients outside the load range do not invalidate this test.
- 3.
This Surveillance shall be conducted on only one DG at a time.
- 4.
This SR shall be preceded by, and immediately follow without shutdown, a successful performance of SR 3.8.1.2 or SR 3.8.1.7.
- 5.
To ensure Operability of an AVR, it must have been aligned to the DG during the performance of SR 3.8.1.2 and SR 3.8.1.3 within the last 60 days, plus any allowance per SR 3.0.2.
Verify each DG is synchronized and loaded, As specified in and operates for Ž 60 minutes at a load Table 3.8.1-1
> 4450 kW and ! 4700 kW.
SR 3.8.1.4 Verify each day tank contains > 31.5 inches 31 days of fuel oil.
SR 3.8.1.5 Check for and remove accumulated water from 31 days each day tank.
SR 3.8.1.6 Verify the fuel oil transfer system 31 days operates to transfer fuel oil from storage tank to the day tank.
(continued)
SAN ONOFRE--UNIT 2 3.8-6 Amendment No. 211
[iesel F1el ui Lube Fil, al d S:arti:I Ai L
8 ELECTRICAL POWER SYST TEMS 3,8.3 Diesel Fuel Oi1, Lube 01, and Starti nr-Air L0U G,
APPLICABILITY:
T stored diese fuel il lube oil
-and s ing i sLlbsYstem shall be within 1 imi tS for each required diesel generator (DG).
When associated DG is required to be OPERABLE.
ACTIONS NOTE--------------------------------
Separate Condition entry is allowed for each DG.
CONDITION REQUIRED ACTION, COMPLETION TIME A.
One or more DGs with A.I Restore fuel oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> fuel volume < 48,400 level to within gallons and > 41,800 limits.
gallons in storage tank during MODE 1,2,3 or 4.
B.
One or more DGs with B.1 Restore lube oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> lube o.il inventory inventory to within
< TS min and TS limits.
inop.
C.
One required DG with C.I Restore fuel oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> fuel volume in the level to within storage tank < 43,600 limits.
gallons and > 37,400 gallons during MODE 5 or 6.
D.
One or more DGs with D.1 Restore fuel oil 7 days stored fuel oil total total particulates to particulates not within limits.
within limits.
(continued)
SAN ONOFRE--UNIT 2 3.8-20 Amendment No. 211
Diesel Fuel Oil; Lube i
d
-I'd f-, ý4 ACTIONS 0
conFtiuel lPd)
COFN0DiTION REQUIRED ACTION COMPLETION TIME E.
One or hiore OGs G
ith E.1 Restore stored fuel 30 days ne,-1 V-1 oii oil propertieCs to properties not within w i thin limits.
limits.
F.
One or more DGs with F.I Restore starting air 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> starting air receiver receiver pressure to pressure < 175 psig L 175 psig.
and 136 psig.
G.
Required Action and G.I Declare associated DG immediately associated Completion inoperable.
Time of Condition A, B, C, D, E or F not met.
OR One or more DGs with diesel fuel oil, lube oil, or starting air subsystem not within limits for reasons other than Condition A, B, C, D, E, or F.
SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.3.1 Verify each fuel oil storage tank contains 31 days
> 48,400 gallons in MODE 1,2,3 or 4 and 21 43,600 gallons in MODE 5 or 6.
(continued)
SAN ONOFRE--UNIT 2 3.8-21 Amendment No. 211
M1 ~~Lir.:U
- 3:1.1 SiJi:\\-_I'LL-NCE FEOU REI EINTS (conti ued)
SURVEI LLAIiCE FREOUEN1Y S
3... I.
NOTES T
I.
DG loadings may include gradual loading as recommended by the manufacturer.
- 2.
Momentary transients outside the load range do not invalidate this test.
- 3.
This Surveillance shall be conducted on only one DG at a time.
- 4.
This SR shall be preceded by, and immediately follow without shutdown, a successful performance of SR 3.8.1.2 or SR 3.8.1.7.
- 5.
To ensure Operability of an AVR, it must have been aligned to the DG during the performance of SR 3.8.1.2 and SR 3.8.1.3 within the last 60 days, plus any allowance per SR 3.0.2.
Verify each DG is synchronized and loaded, As specified in and operates for -1 60 minutes at a load Table 3.8.1-1
> 4450 kW and < 4700 kW.
SR 3.8.1.4 Verify each day tank contains > 31.5 inches 31 days of fuel oil.
SR 3.8.1.5 Check for and remove accumulated water from 31 days each day tank.
SR 3.8.1.6 Verify the fuel oil transfer system 31 days operates to transfer fuel oil from storage tank to the day tank.
(continued)
SAN ONOFRE--UNIT 3 3.8-6 Amendment No. 203
['iecei Fuel vi-.
LI t-Li
- i-,
a
, LELCTRiL.RL POWEFP S"S STEI
- 5.3..*
Diesel Fuel OilI Lube 0il, and Starti0n1 LC0 3.8.3 The stored diesel fuel ciUG, lube oiI, and starting air subsystem shall be within limits for each required diesel generator (DG)
APPLICABILITY:
When associated DG is required to be OPERABLE.
ACTIONS NOTE -------------------------------------
Separate Condition entry is allowed for each DG.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more DGs with A.1 Restore fuel oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> fuel volume < 48,400 level to within gallons and > 41,800 limits.
gallons in storage tank during MODE 1,2,3 or 4.
B.
One or more DGs with B.1 Restore lube oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> lube oil inventory inventory to within
< TS min and Ž TS limits.
inop.
C.
One required DG with C.1 Restore fuel oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> fuel volume in the level to within storage tank < 43,600 limits.
gallons and > 37,400 gallons during MODE 5 or 6.
D.
One or more DGs with D.1 Restore fuel oil 7 days stored fuel oil total total particulates to particulates not within limits.
within limits.
(continued)
SAN ONOFRE--UNIT 3 3.8-20 Amendment No.
203
Di s L !
Iu L--
TC*-TI S (corti 11 ed)
C OND! T D
ON REOUIRED ACTION COMviPLETiO!
TINE E.
One or more DGs with new fuel oil properties not within limits.
E. I Rettore stored fuel oil properties to within limits.
30 days One or more DGs with starting air receiver pressure < 175 psig and 136 psig.
F.I Restore starting air receiver pressure to 175 psi g.
48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> 4
4 Required Action and associated Completion Time of Condition A, B, C, D, E or F not met.
OR One or more DGs with diesel fuel oil, lube oil, or starting air subsystem not within limits for reasons other than Condition A, B, C, D, E, or F.
G.I Declare associated DG inoperable.
Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.3.1 Verify each fuel oil storage tank contains 31 days 48,400 gallons in MODE 1,2,3 or 4 and a 43,600 gallons level in MODE 5 or 6.
(continued)
SH ONOFRE--UNIT 3 3.8-21 Amendment No.
203