Core Operating Limits Report, Revision 1, for Cycle 14 Operation
ML061520490
Person / Time
Site: Browns Ferry 
Issue date: 05/19/2006
From: Crouch W
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
TVA-COLR-BF2C14, Rev 1
Download: ML061520490 (47)


Text

Tennessee Valley Authority, Post Office Box 2000, Decatur, Alabama 35609-2000 May 19, 2006 U.S. Nuclear Regulatory Commission ATTN:

Document Control Desk Mail Stop:

OWFN, Pl-35 Washington, D.C. 20555-0001 Gentlemen:

In the Matter of

)

Docket No.

50-260 Tennessee Valley Authority

)

BROWNS FERRY NUCLEAR PLANT (BFN)

UNIT 2 -

CORE OPERATING LIMITS REPORT (COLR),

REVISION 1, FOR CYCLE 14 OPERATION In accordance with the requirements of Technical Specification 5.6.5.d, enclosed is Revision 1 of the Unit 2, Cycle 14, Core Operating Limits Report.

Revision 1 of the Unit 2, Cycle 14 COLR adds Power Load Unbalance Out-Of-Service limits.

There are no new commitments contained in this letter.

If you have any questions, please contact me at (256) 729-2636.

Sincerely, William D. Crouch Manager of Licensing and Industry Affairs Enclosure cc:

See page 2

U.S. Nuclear Regulatory Commission Page 2 May 19, 2006 Enclosure cc (Enclosure):

Mr. Malcolm T.

Widmann, Branch Chief U.S. Nuclear Regulatory Commission Region II Sam Nunn Atlanta Federal Center 61 Forsyth Street, S.W., Suite 23T85 Atlanta, Georgia 30303-8931 NRC Resident Inspector Browns Ferry Nuclear Plant 10833 Shaw Road Athens, Alabama 35611-6970 Ms. Eva A. Brown, Project Manager U.S. Nuclear Regulatory Commission One White Flint, North (MS 08G9) 11555 Rockville Pike Rockville, Maryland 20852-2739 Ms. Margaret Chernoff, Project Manager U.S. Nuclear Regulatory Commission One White Flint, North (MS 08G9) 11555 Rockville Pike Rockville, Maryland 20852-2739

ENCLOSURE

.':TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT (BFN)

UNIT 2' CORE OPERATING LIMITS REPORT (COLR),

REVISION 1, FOR CYCLE 14 OPERATION (SEE ATTACHED)

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1, Page 1 r -

Browns Ferry Nuclear Plant Unit 2 Cycle 14 CORE OPERATING LIMITS REPORT (COLR) -

TENNESSEE VALLEY AUTHORITY Nuclear Fuel Division BWR Fuel Engineering Department Prepared By:

Verified By:

Approved By:

Earl E. Riley, " Sr. Engineering Specialist BWR Fuel Engineering, BeC. Mitchell, Nuclear Engineer BWR Fuel Engineering BWRFuel ngineenng------- -.

Date:

.9-/Q-ot.

Date:

4_,__/o Date:

4Ito /06~

Reviewed By:

Approved By:

Date:

d(//,/6 Date:______

P C -Chaiifian Revision 1 (4/10/2006)

Pages Affected:

1, 2, 6, 8, 11, and 20-44 Revision 1 (4/1012006)

Pages Affected:

1, 2, 6, 8, 11, and 2044

TVA Nuclear Fuel Corm Operating Limits Report TVA-COLR-BF2CI4 Revision 1, Page 2 Revision Log Revision Date Description Affected Pages 0

3/10/2004 1

4/10/2006 Initial Release for New Cycle Added PLUOOS Limits Note: Added pages affected pagination after page 20.

All 1,2, 6, 8, 11, and 20-44 Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel TVA-COLR-BF2Cl4 Core Operating Limits Report Revision 1, Page 3

1. INTRODUCTION This Core Operating Limits Report for Browns Ferry Nuclear Plant Unit 2 Cycle 14 is prepared in accordance with the requirements of Browns Ferry Technical Specification 5.6.5.

The core operating limits presented here were developed using NRC-approved methods (References 2 and 3).

One exception to this is an issue with the assumed uncertainty for the GEXLI4 CPR correlation. The NRC has identified that the correlation lacked top-peaked axial power shape data in its formulation and in the calculation of the overall correlation uncertainty. As an interim action, an increased GEXLI4 uncertainty that incorporates a significant penalty has been calculated and applied to the MCPR Safety Limit (SLMCPR) for this cycle.

Results from the reload analyses for Browns Ferry Nuclear Plant Unit 2 Cycle 14 are documented in Reference 1.

The following core operating and Technical Specification limits are included in this report:

a. Average Planar Linear Heat Generation Rate (APLHGR) Limit (Technical Specifications 3.2.1 and 3.7.5)
b. Linear Heat Generation Rate (LHGR) Limit (Technical Specification 3.2.3, 3.3.4.1, and 3.7.5)
c. Minimum Critical Power Ratio Operating Limit (OLMCPR)

(Technical Specification's 3.2.2, 3.3.4.1, and 3.7.5)

d. Average Power Range Monitor (APRM) Flow Biased Rod Block Trip Setting (Technical Requirements Manual Section 5.3.1 and Table 3.3.4-1)
e. Rod Block Monitor (RBM) Trip Setpoints and Operability (Technical Specification Table 3.3.2.1-1)

The Unit 2 Cycle 14 core is composed of Framatome-ANP ATRIUMTM-10, Global Nuclear Fuel GE-14TM, and Global Nuclear Fuel GE-13TM assemblies. Throughout this document these are referred to as A10, GEl4, and GE13 with the trademark implied.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2CI4 Revision I, Page 4

2. APLHGR LIMIT (TECHNICAL SPECIFICATIONS 3.2.1 AND 3.7.5)

The APLHGR limit is determined by adjusting the rated power APLHGR limit for off-rated power, off-rated flow, and SLO conditions. The most limiting of these is*then used as follows:

APLHGR limit = MIN (APLHGRp, APLHGRF, APLHGRsLo) where:

APLHGRp APLHGRF APLHGRsLo off-rated power APLHGR limit off-rated flow APLHGR limit SLO APLHGR limit

[APLHGRRATED

  • MAPFAC(P)]

[APLHGRRATED

  • MAPFAC(F)]

[ALPHGR RATED

  • SLOMultiplier]

The off-rated power and flow corrections to the APLHGR limit only apply to the GEl3 and GEl4 fuel in the Browns Ferry Unit 2 Cycle 14 core. For that reason, this multiplier is set to 1.0 as shown below for the Al 0 fuel.

Rated Power and Flow Limits: APLHGRRATED The APLHGR limits for full power and flow conditions for each type of fuel as a function of exposure are shown in Figures 1-8. The APLHGR limits provided in the COLR figures for the GEl3 and GE14 assemblies are for the most limiting lattice (excluding natural uranium) at each exposure point. The specific values for each GEl3 and GE14 lattice are given in Reference 4. The ATRIUM-10 values are provided in Reference 1.

Bundle Type Rated Power APLHGR Limit GE13-P9DTB391-I3GZ (EDB 2430)

Figure 1 GE 13-P9DTB412-2G7.0/ 11G5.0 (EDB 2431)

Figure 2 GE14-P1ODNAB416-16GZ (EDB2600)

Figure 3 GE 14-P 10DNAB416-16GZ (EDB2601)

Figure 4 GE14-PIODNAB367-14GZ (EDB2602)

Figure 5 GE14-PIODNAB416-18GZ (EDB2627)

Figure 6 GE14-PODNAB417-18GZ (EDB2628)

Figure 7 A10-3920B-14GV70 Figure 8 Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C14 Revision 1, Page 5 Off-Rated Power Corrections: APLHGRp The APLHGR limits for the GEl3 and GEl4 fuel lattices are adjusted for off-rated power conditions using the ARTS multiplier, MAPFAC(P). The reduced power multiplier, MAPFAC(P), for both the GEl3 and GEl4 fuel is provided in Reference 1. No off-rated power correction is required for the Al 0 rated APLHGR limits.

Product Line MAPFAC(P)

GE13 Figure 9 GE14 Figure 10 A10 1.0 Off-Rated Flow Corrections: APLHGRF The APLHGR limits for the GEl3 and GE14 fuel lattices are adjusted for off-rated flow conditions using the ARTS multiplier, MAPFAC(F). The reduced flow multiplier, MAPFAC(F) is provided in Reference 1. No off-rated flow correction is required for the A 10 rated APLHGR limits.

Product Line MAPFAC(F)

GEl3 Figure II GE14 Figure 12 A10

  • 1.0 SLO Corrections: APLHGRsLo Single Recirculation Loop Operation (SLO) requires that the rated power APLHGR limit (APLHGRrated) be reduced by applying the following multipliers. The GE13 and GE14 multipliers are provided in Reference 5. The A10 multiplier is provided in Reference 1.

-Product Line -

-SLO Multiplier.

GE13 0.87 GE14 0.93 A10 0.85 Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2CI4 Revision 1, Page 6 Equipment Out-Of-Service (EOOS) Corrections:

The rated APLHGR limits in Figures 1-8 are applicable for operation with all equipment In-Service as well as the following Equipment Out-Of-Service (EOOS) options. This includes combinations of these EOOS options.

In-Service RPTOOS TBVOOS PLUOOS FHOOS (or FFTR)

All equipment In-Service (includes I SRVOOS)

EOC-Recirculation Pump Trip Out-Of-Service Turbine Bypass Valve(s) Out-Of-Service Power Load Unbalance Out-Of-Service Feedwater Heaters Out-Of-Service (or Final Feedwater Temperature Reduction)

Single Recirculation Loop Operation (SLO) requires the application of the SLO multipliers to the rated APLHGR limits as described previously.

The off-rated power corrections [MAPFAC(P)] in Figures 9 and 10 are dependent upon operation of the Turbine Bypass Valve system. For this reason, separate limits are supplied in these figures to be applied for TBVIS or TBVOOS operation. The MAPFAC(P) limits have no dependency on RPTOOS, SLO, FHOOS/FFTR, or PLUOOS.

The off-rated flow corrections [MAPFAC(F)] in Figures II and 12 bound both equipment In-Service or EOOS operation.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1, Page 7

3. LHGR LIMIT (TECHNICAL SPECIFICATION 3.2.3,3.3.4.1, and 3.7.5)

The LHGR limit is determined by adjusting the rated power LHGR limit for off-rated power and off-rated flow conditions. The most limiting of these is then used, as follows:

LHGR limit = MIN ( LHGRp, LHGRF) where:

LHGRp LHGRF off-rated power LHGR limit off-rated flow LHGR limit

[LHGRRATED

  • LHGRFAC(P)]

[LHGRRATED

  • LHGRFAC(F)]

The off-rated power and flow corrections to the LHGR limit only apply to the A10 fuel in the Browns Ferry Unit 2 Cycle 14 core. For that reason, these multipliers for the GE13 and GEl4 fuel are set to 1.0 as shown below.

Rated Power and Flow Limits: LHGRRATED The LHGR limit is fuel type dependent. The limits for these types are given below:

.Fuel Type LHGR Limit GE13 14.4 kw/ft GE14 13.4 kw/ft A10 Figure 13 The A10 LHGR limit is provided in Reference 6. The GEl3 and GE14 LHGR limits are provided in Reference 7.

Off-Rated Power Corrections: LHGRp The LHGR limits for the A10 fuel are adjusted for off-rated power conditions using.the LHGRFAC(P) multiplier which is provided in Reference 1. The LHGRFAC(P) multiplier is dependent on whether the Turbine Bypass system is in-service (TBVIS) or out-of-service (TBVOOS). No off-rated power correction is required for the GEl3 or GE14 rated LHGR limits.

Product Line LHGRFAC(P)

GEl3 & GEl4 1.0 A10 I *~..

Figure 14

  • . [

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1, Page 8 Off-Rated Flow Coirre'tions: LHGRF The LHGR limits for the A10 fuel are adjusted for off-rated flow conditions using the LHGRFAC(F) multiplier which is provided in Reference 1. No off-rated flow correction is required for the GEI3 and GE14 rated LHGR limits.

Product Line GE13 & GE14 LHGRFAC(F) 1.0 Figure 15 I

A1O Equipment Out-Of-Service (EOOS) Corrections:

The rated LHGR limits are applicable for operation with all equipment In-Service as well as the following Equipment Out-Of-Service (EOOS) options. This includes combinations of these EOOS options.

In-Service RPTOOS TBVOOS PLUOOS SLO FHOOS (or FFTR)

All equipment In-Service (includes 1 SRVOOS)

EOC-Recirculation Pump Trip Out-Of-Service Turbine Bypass Valve(s) Out-Of-Service Power Load Unbalance Out-Of-Service Single Recirculation Loop Operation Feedwater Heaters Out-Of-Service (or Final Feedwater Temperature Reduction)

The off-rated power corrections [LHGRFAC(P)] in Figure 14 are dependent upon operation of the Turbine Bypass Valve system. For this reason, separate limits are supplied in this figure to be applied for TBVIS or TBVOOS operation. The LHGRFAC(P) limits have no dependency on RPTOOS, PLUOOS, SLO, or FHOOS/FFTR.

The off-rated flow corrections [LHGRFAC(F)] in Figure 15 bound both equipment In-Service or EOOS operation.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel TVA-COLR-BF2CI4 Core Operating Limits Report Revision 1, Page 9

4. OLMCPR (TECHMNICAL SPECIFICATIONS 3.2.2, 3.3.4.1, AND 3.7.5)

The MCPR Operating Limit (OLMCPR) is calculated to be the most limiting of the flow-dependent MCPR (MCPRF) and power-dependent MCPR (MCPRp).

OLMCPR limit = MAX ( MCPRF, MCPRp) where:

MCPRF core flow-dependent MCPR limit MCPRp power-dependent MCPR limit MCPRF limits are provided by fuel type in Figures 16 through 18. MCPRp limits are provided in Tables 1 through 6.

Flow-Dependent MCPR Limits: MCPRF The MCPRF limits are dependent upon:

.0 Core Flow (% of Rated)

  • Max Core Flow Limit (Rated or Increased Core Flow, ICF)
  • FuelType (GE13, GEl4, or A10)

The MCPRF limits are provided by fuel type in Figure 16 (GEI3), Figure 17 (GEl4), and Figure 18 (A10). These limits are valid for all EOOS combinations. No adjustment is required to the MCPRF limits for SLO. The MCPRF limits are found in Reference 1.

Power-Dependent MCPR Limits: MCPRp The MCPRp limits are dependent upon:

  • Core Power Level (% of Rated)

Technical Specification Scram Speed (TSSS) or Nominal Scram Speed (NSS)

" FuelType (GEl3, GEl4, or A10)

  • Cycle Operating Exposure (NEOC, EOC, and CD - as defined in this section)
  • Equipment Out-Of-Service Options
  • Two or Single recirculation Loop Operation (TLO vs. SLO)......

The MCPRp limits (Ref. 1) are provided in the following tables, where each table contains the limits for all fuel types and EOOS options (for a specified scram speed and exposure range). The MCPRp limits are determined from these tables using linear interpolation between the specified powers.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

IV.A Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C14 Revision 1, Page 10 Exposure Range Scram Speed MCPRp BOC to NEOC NSS Table 1 TSSS Table 2 BOC to EOC NSS Table 3 TSSS Table 4 BOC to CD NSS Table 5 TSSS Table 6

a. Scram Speed Dependent Limits (TSSS vs. NSS)

MCPRp limits are provided for two different sets of assumed scram speeds. The Technical Specification Scram Speed (TSSS) MCPRp limits are applicable at all times as long as the scram time surveillance demonstrates that the times in Technical Specification table 3.1.4-1 have been met. Nominal Scram Speeds (NSS) may be used as long as the scram time surveillance demonstrates that the times in the following table are met (Ref. 8).

Notch Nominal Scram Speed Position (seconds) 46 0.42 36 0.98 26 1.60 06 2.90

-lii-dEm-finstrating compliance with this table, the same surveillance requirements from Technical Specification 3.1.4 apply, except that the definition of SLOW rods should conform to the scram speeds in the table above. If conformance to this table is not demonstrated, TSSS MCPRp limits shall be used.

On initial cycle startup, TSSS limits are used until the successful completion of scram timing confirms that NSS limits may be used.

b. Fuel Type Dependent Limits Separate MCPRp limits are provided for the GEl3, GE14, and A10 fuel types.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TV.A Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1, Page 11

c. Exposure Depende'lni Limits Exposures are tracked on a Core Average Exposure basis (not Cycle Exposure). The higher exposure MCPRp limits are always more limiting and may be used for any Core Average Exposure up to the ending exposure.

MCPRp limits are provided for the following exposure ranges (Ref. 1):

BOC to NEOC BOC to EOC BOC to CD NEOC corresponds to EOC corresponds to CD corresponds to 30,755 MWd / MTU 32,798 MWd / MTU 33,871 MIVd / MTU NEOC refers to a Near EOC exposure point.

The EOC exposure point is not the true End-Of-Cycle exposure. Instead it corresponds to a licensing exposure window that exceeds expected end-of-full-power-life.

The CD (CoastDown) exposure point represents a licensing exposure point that exceeds the expected end-of-cycle exposure including cycle extension options.

d. Equipment Out-Of-Service (EOOS) Options EOOS options included in the MCPRp limits are:

In-Service RPTOOS TBVOOS RPTOOS+TBVOOS PLUOOS+RPTOOS PLUOOS+TBVOOS+RPTOOS FHOOS (or FFTR)

All equipment In-Service (includes 1 SRVOOS)

EOC-Recirculation Pump Trip Out-Of-Service Turbine Bypass Valve(s) Out-Of-Service Combined RPTOOS and TBVOOS Combined PLUOOS and RPTOOS Combined PLUOOS, RPTOOS, and TBVOOS Feedwater Heaters Out-Of-Service (or Final Feedwater Temperature Reduction)---

PLUOOS refers to Power Load Unbalance and is only provided for TSSS Insertion Times in combination with the indicated EOOS options. PLUOOS.is not provided as a stand-alone EOOS option for Unit 2 Cycle 14.

For.exposure ranges up to_NEOC and EOC, additional combinations of MCPRp limits are also provided that include FHOOS. The CD exposure range assumes application of FFTR, so the CD based MCPRp limits already include FHOOS.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report 5

TVA-COLR-BF2C 14 Revision 1, Page 12

e. Single-Loop-Operation (SLO) Limits The MCPRp limits for SLO are to be increased by 0.02 (Ref. 1).
f. Below Pbypass Limits Below Pbypass (30% rated power), the MCPRp limits are dependent upon core flow.

One set of MCPRp limits applies if the core flow is above 50% of rated with a second set that applies if the core flow is less than or equal to 50% rated.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report

-:r...

F.

TVA-COLR-BF2CI4 Revision 1, Page 13

5. APRM FLOW BIASED ROD BLOCK TRIP SETTING (TECHNICAL REQUIREMENTS MANUAL SECTION 5.3.1 AND TABLE 3.3.4-1)

The APRM Rod Block trip setting shall be (Ref. 9):

SRB _< (0.66(W-AW) + 61%)

SRB _* (0.66(W-AW) + 59%)

Allowable Value Nominal Trip Setpoint (NTSP) where:

SRB=

W=

AW=

Rod Block setting in percent of rated thermal power (3458 MWt)

Loop recirculation flow rate in percent of rated Difference between two-loop and single-loop effective recirculation flow at the same core flow (AW=0.0 for two-loop operation)

The APRM Rod Block trip setting is clamped at a maximum allowable value of 115%

(corresponding to a NTSP of 113%).

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C14 Revision 1, Page 14

6. ROD BLOCK MONITOR (RBM) TRIP SETPOINTS AND OPERABILITY (TECHNICAL SPECIFICATION TABLE 3.3.2.1-1)

The RBM trip setpoints and applicable power ranges shall be as follows (refs. 9 & 10):

RBM Trip Setpoint Allowable Value Nominal Trip Setpoint (AV)

(NTSP)

LPSP 27%

25%

IPSP 62%

60%

HPSP 82%

80%

LTSP - unfiltered 121.7%

120.0%

- filtered 120.7%

119.0%

ITSP - unfiltered 116.7%

115.0%

- filtered 115.7%

114.0%

HTSP - unfiltered 111.7%

110.0%

- filtered 110.9%

109.2%

DTSP 90%

92%

(1),(2)

(1),(2)

(1),(2)

Notes: (1) These setpoints are based upon an Analytical Limit HTSP of 114% (w/o filter) which corresponds to a MCPR operating limit of 1.35(A10) / 1.33 (GE13/GE14), as reported in section 5.5 of Reference 1. Unit 2 Cycle 14 has had a cycle specific CRWE analysis performed and the table provided in section 5.5 of Reference 1 supercedes the OLMCPR values of references 9 and 11.

(2) The unfiltered setpoints are consistent with a nominal RBM filter setting of 0.0 seconds (reference 9.b)). The filtered setpoints are consistent with a nominal RBM filter setting < 0.5 seconds (reference 9.a)).

The RBM setpoints in Technical Specification Table 3.3.2.1-1 are applicable when:

THERMAL POWER Applicable Notes from

(% Rated)

MCPR O Table 3.3.2.1-1

> 27% and <90%'

< 1.72 (a), (b), (0, (h)

<1.75 (a), (b), (f), (h)

> 90%

< 1.42 (g) dual loop operation single loop operation dual loop operation (2)

Notes: (1) The MCPR values shown correspond to a SLMCPR of 1.08 for dual recirculation loop operation and 1.10 for single loop operation. (Ref. 1).

(2)

Greater than 90% rated power is not attainable in single loop operation.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C14 Revision 1, Page 15

7. SHUTDOWN MARGIN (SDM) LIMIT (TECHNICAL SPECIFICATION 3.1.1)

The core shall be subcritical with the following margin with the strongest OPERABLE control rod fully withdrawn and all other OPERABLE control rods fully inserted (Ref. 7).

SDM > 0.38% dklk Browns Ferry Nuclear Plant Unit 2 Cycle 14

,w TVA Nuclear Fuel TVA-COLR-BF2C14 Core Operating Limits Report Revision 1, Page 16

8. REFERENCES
1. EMF-3139 Rev. 2, "Browns Ferry Unit 2 Cycle 14 Reload Analysis", dated August 2005.
2. Framatome-ANP Analytical Methodology

References:

a) XN-NF-81-58(P)(A) Revision 2 and Supplements 1 and 2, RODEX2 Fuel Rod Thermal-Mechanical Response Evaluation Model, Exxon Nuclear Company, March 1984.

b) XN-NF-85-67(P)(A) Revision 1, Generic Mechanical Design for Exxon Nuclear Jet Pump B WR Reload Fuel, Exxon Nuclear Company, September 1986.

c): EMF-85-74(P) Revision 0 Supplement I (P)(A) and Supplement 2(P)(A), RODEX2A (BWR) Fuel Rod Thermal-Mechanical Evaluation Model, Siemens Power Corporation, February 1998.

d) ANF-89-98(P)(A) Revision I and Supplement 1, Generic Mechanical Design Criteria for BWR Fuel Designs, Advanced Nuclear Fuels Corporation, May 1995.

e) XN-NF-80-19(P)(A) Volume 1 and Supplements 1 and 2, Exxon Nuclear Methodology for Boiling Water Reactors - Neutronic Methods for Design and Analysis, Exxon Nuclear Company, March 1983.

f) XN-NF-80-19(P)(A) Volume 4 Revision 1, Exxon Nuclear Methodology for Boiling Water Reactors: Application of the ENC Methodology to BTWR Reloads, Exxon Nuclear Company, June 1986.

g) EMF-2158(P)(A) Revision 0, Siemens Power Corporation Methodology for Boiling Water Reactors: Evaluation and Validation of CASMO-4/MICROBURN-B2, Siemens Power Corporation, October 1999.

h) XN-NF-80-19(P)(A) Volume 3 Revision 2, Exxon Nuclear Methodology for Boiling Water Reactors, THERMEX: Thermal Limits Methodology Summary Description, Exxon Nuclear Company, January 1987.

i) XN-NF-84-105(P)(A) Volume I and Volume 1 Supplements I and 2, XCOBRA-T: A Computer Code for BWR Transient Thermal-Hydraulic Core Analysis, Exxon Nuclear Company, February 1987.

j) ANF-524(P)(A)

Revision 2 and Supplements 1 and 2, ANF Critical Power Methodology for. Boiling Water Reactors, Advanced Nuclear Fuels Corporation, November 1990.

k) ANF-913(P)(A) Volume I Revision 1 and Volume 1 Supplements 2, 3 and 4, COTRANSA2: A Computer Program for Boiling Water Reactor Transient Analyses, Advanced Nuclear Fuels Corporation, August 1990.

1) ANF-1358(P)(A) Revision 1, The Loss of Feedwater Heating Transient in Boiling Water Reactors, Advanced Nuclear Fuels Corporation, September 1992.

m) EMF-2209(P)(A) Revision 2, SPCB. Critical Power Correlation, Siemens Power Corporation, September 2003.

ni) EMF-2245(P)(A) Revision 0, Applic-ation 6fSieinns-P*-*-Cbi'tibn 'sCritical...

Power Correlations to Co-Resident Fuel, Siemens Power Corporation, August 2000.

o) EMF-2361(P)(A) Revision 0, EXFM BWR-2000 ECCS Evaluation Model, Framatome ANP, May 2001.

p) EMF-2292(P)(A) Revision 0, ATRIUMTM-1O" Appendix K Spray Heat Transfer Coefficients, Siemens Power Corporation, September 2000.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel TVA-COLR-BF2C 14 Core Operating Limits Report Revision 1, Page 17

3. Global Nuclear Fuel Analytical Methodology

References:

a) NEDE-2401 1-P-A-14, "General Electric Standard Application for Reactor Fuel", June 2000.

b) NEDE-24011-P-A-14-US, "General Electric Standard Application for Reactor Fuel (Supplement for United States)", June 2000.

4. 0000-0006-1355-MAPL Rev. 0, "Lattice-Dependent MAPLHGR Report for Browns Ferry Unit 2 Reload 12 Cycle 13", February 2003.
5. NEDC-32484P Rev. 6, "Browns Ferry Nuclear Plant Units 1, 2, and 3 - SAFER/GESTR-LOCA Loss-Of-Coolant Accident Analysis", dated February 2005.
6. EMF-3114(P) Rev. 0, "Mechanical Design Report for Browns Ferry Unit 2 Batches BFE2-14 ATRIUMTM-10 Fuel Assemblies", dated September 2004.
7. TVA-COLR-BF2Cl3 Rev. 0, "Browns Ferry Nuclear Plant Unit 2, Cycle 13 Core Operating Limits Report (COLR)", dated February 26, 2003.
8. EMF-3061(P) Rev. 2, "Browns Ferry Unit 2 Cycle 14 Plant Parameters Document", dated January 2005.

9.. PRNM Setpoint Calculation:

a) Filtered Setpoints - EDE-28-0990 Rev. 3 Supplement E, "PRNM (APRM, RBM, and RFM) Setpoint Calculations [ARTS/MELLL (NUMAC) - Power-Uprate Condition] for Tennessee Valley Authority Browns Ferry Nuclear Plant", dated October 1997.

b) Unfiltered Setpoints - EDE-28-0990 Rev. 2 Supplement E, "PRNM (APRM, RBM, and RFM) Setpoint Calculations [ARTS/MELLL (NUMAC) - Power-Uprate Condition] for Tennessee Valley Authority Browns Ferry Nuclear Plant", dated October 1997.

10. GE Letter LB#: 262-97-133, "Browns Ferry Nuclear Plant Rod Block Monitor Setpoint Clarification - GE Proprietary Information", dated Sepiember 12, 1997.
11. NEDC-32433P, "Maximum Extended Load Line Limit and ARTS Improvement Program Analyses for Browns Ferry Nuclear Plant Unit 1, 2, and 3", dated April 1995.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1, Page 18 Table 1: MCPRp Limits for BOC to NEOC Exposures - NSS Scram Times (Applicable up to Core Average Exposure of 30,755 MWd / MTU)

MCPRp Limit MCPRp Limit EOOS Power AID GE13 GE14 Option

(% Rated) 100 1.36 1.33 1.37 60 1.52 1.60 1.60 50 1.63 50 1.77 1.72 1.78 30 1.96 2.00 2.10 30 (> 5o%F) 2.21 2.23 2.36 25 (> 50%F) 2.37 2.41 2.52 30 (5.50%F) 2.18 2.06 2.35 25 L 50%F) 2.33 2.21 2.52 100 1.37 1.34 1.39 60 1.52 1.60 1.60 50 1.63 50 1.77 1.72 1.78 RPTOOS 30 1.96 2.00 2.10 30 (> 50%F) 2.21 2.23 2.36 25 (> 50%F) 2.37 2.41 2.52 30 (5L50%1) 2.18 2.06 2.35 25 (1 50%F) 2.33 2.21 2.52 100 1.39 1.36 1.41 60 1.55 1.60 1.63 50 1.65

.50 1.77 1.72 1.78 TBVOOS 30 1.99 2.02 2.12 30 (> 50%!)

2.73 2.65 2.82 25 (> 50%1)

.3.02 2.96 3.09 30 550o%1) 2.47 2.22 2.61 25 U 50%1) 2.78 2.50 2.93 100 1.40 1.37 1.42 60 1.55 1.60 1.63

50.

1.65 50 1.77 1.72 1.78 TOOS 30 1.99 2.02 2.12 30 (> 50%F) 2.73 2.65 2.82 25 (>50%F) 3.02

- 2.96

- 3.09-30 L 50%1) 2.47 2.22 2.61 25 (550o%!)

2.78 2.50 2.93 EOOS Power Option

(% Rated) 100 1.36 1.33 1.37 60 1.57 1.60 1.66 50 1.69 50 1.77 1.72 1.80 FHOOS 30 2.05 2.08 2.20 30 (> 50%F) 2.30 2.31 2.45 25 (> 50%F:)

2.48 2.51 2.64 30 (5 50%F) 2.25 2.12 2.44 25 (5 5o%1) 2.43 2.30 2.63 100 1.37 1.34 1.39 60 1.57 1.60 1.66 50 1.69 50 1.77 1.72 1.80 MOOS 30 2.05 2.08 2.20 30 (> 50%!)

2.30 2.31 2.45 25 (> 50%!)

2.48 2.51 2.64 30 (<-5o%)

2.25 2.12 2.44 25 L< 50%F) 2.43 2.30 2.63 100 1.39 1.36 1.41 60 1.59 1.60 1.68 50 1.71 50 1.77 1.72 1.81 TBVOOS 30 2.06 2.10 2.21 FHOOS 30 (> 50%1) 2.79 2.71 2.90 25 (> 50%!)

3.09

.3.04 3.18 30 (5 50%1) 2.53 2.27 2.68

---25 (-550O%!)

2.86 2.56 3.02 100 1.40 1.37 1.42 60 1.59 1.60 1.68 5 0 1.7 1 RPTOOS 50 1.77 1.72 1.81 TBVOOS 30 2.06 2.10 2.21 FHOOS 30 (> 5o%1) 2.79 2.71 2.90 25 (> so%1)0- -3.09

-.- 3.04.

-.3.18 30 (5. 50%)

2.53 2.27 2.68 25 (5 50%!)

2.86 2.56 3.02 Add 0.02 to the above MCPRp limits for SLO.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating LUits Report TVA-COLR-BF2C 14 Revision 1, Page 19 Table 2: MCPRp Limits for BOC to NEOC Exposures - TSSS Scram Times (Applicable up to Core Average Exposure of 30,755 MWd / MTU)

MCPRr Limit MCPRp Limit EOOS Power Option

(% Rated) 100 1.37 1.34 1.39 60 1.54 1.60 1.62 50 1.65 50 1.78 1.73 1.79 30 1.98 2.01 2.12 Serce 30 (> so%F 2.21 2.23 2.36 25 (> so%F) 2.37 2.41 2.52 30 (.50%F) 2.18 2.06 2.35 25 (5sO%F) 2.33 2.21 2.52 100 1.38 1.36 1.41 60 1.54 1.60 1.62 50 1.65 50 1.78 1.73 1.79 RPTOOS 30 1.98 2.01 2.12 30 (> 50%F) 2.21 2.23 2.36 25 (> 50%F) 2.37 2.41 2.52 30 (L.50%F) 2.18 2.06 2.35 25 (- 50%F) 2.33 2.21 2.52 100 1.41 1.37 1.42 60 1.57 1.60 1.66 50 1.67 50 1.78 1.73 1.79 TBVOOS 30 2.01 2.04 2.14 30 (> 50%F) 2.73 2.65 2.82 25 (> 50%F)

.3.02 2.96 3.09 30 (- 50%F) 2.47 2.22 2.61 25 L< 50%F) 2.78 2.50 2.94 100 1.41 1.38 1.44 60 1.57 1.60 1.66 50 1.67 50 1.78 1.73 1.79 TOOS 30 2.01 2.04 2.14 30 (> 50%F) 2.73 2.65 2.82 25 (> 5o%F) 3.02.. -2.96 3.09.-

30 (. 50%F) 2.47 2.22 2.61 25 (L 50%F) 2.78 2.50 2.94 EOOS Power OptonAI0 GE13 GE14 Option

(% Rated) 100 1.37 1.34 1.39 60 1.59 1.60 1.67 50 1.71 50 1.78 1.73 1.81 FHOOS 30 2.06 2.10 2.22 30 (> 5o%F) 2.30 2.31 2.45 25 (> 50%F) 2.48 2.51 2.64 30 (. 5o%F) 2.25 2.12 2.44 25 (L. 5o%F) 2.43 2.30 2.63 100 1.38 1.36 1.41 60 1.59 1.60 1.67 50 1.71 50 1.78 1.73 1.81 RPOOS 30 2.06 2.10 2.22 30 (> 5o%F) 2.30 2.31 2.45 25 (> 50%F) 2.48 2.51 2.64 30 (S 5o%F) 2.25 2.12 2.44 25 (- 50%F) 2.43 2.30 2.63 100 1.41 1.37 1.43 60 1.61 1.60 1.70 5 0 1.7 3 50 1.78 1.73 1.83 TBOOS 30 2.09 2.12 2.23 30 ( 50./ooF) 2.79 2.72 2.90 25 (. 5o%F) 3.09 3.04 3.18 30(

50%F) 2.53 2.27 2.68 25 ( 50%F) 2.86 2.56 3.02 100 1.41 1.38 1.44 60 1.61 1.60 1.70 50 1.73 RPTOOS 50 1.78 1.73 1.83 TBVOOS 30 2.09 2.12 2.23 FHOOS 30 (> 50%F) 2.79 2.72 2.90 25 (>50%F) 3.09 --

3.04-

.-3.18 30 505o%F) 2.53 2.27 2.68 25 5o%F) 2.86 2.56 3.02 Add 0.02 to the above MCPRp limits for SLO.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Corc Operating Limits Report TVA-COLR-BF2C14 Revision 1, Page 20 Table 2 (Continued): MCPRp Limits for BOC to NEOC Exposures - TSSS Scram Times (Applicableup to Core Average Exposure of 30,755 MWd / MTU)

MCPRr Limit EOOS Power A10 GE13 GE14 Option

(% Rated) 100 1.39 1.36 1.41 65 1.52 1.57 1.60 60 1.74 1.69 1.74 PLUOOS 50 1.78 1.73 1.79 RPTOOS 30 1.98 2.01 2.12 30 (> 50%F) 2.21 2.23 2.36 25 (> 50%F) 2.37 2.41 2.52 30 L 50%F) 2.18 2.06 2.35 25 (. 50%F) 2.33 2.21 2.52 100 1.39 1.36 1.41 65 1.57 1.57 1.64 60 1.74 1.69 1.74 PLUOOS 50 1.78 1.73 1.81 RPTOOS 30 2.06 2.10 2.22 FHOOS 30 (> 50%F) 2.30 2.31 2.45 25 (> 50%F) 2.48 2.51 2.64 30 50%F) 2.25 2.12 2.44 25 (5 5o%F) 2.43 2.30 2.63 100 1.41 1.38 1.44 65 1.55 1.58 1.64 60 1.74 1.69 1.74 PLUOOS 50 1.78 1.73 1.79 RPTOOS 30 2.01 2.04 2.14 TBVOOS 30 (> 5O%F) 2.73 2.65 2.82 25 (> 50%F) 3.02 2.96 3.09 30 (5. so%F) 2.47 2.22 2.61

--25 (-50%F)--

  • 2.78 2.50 2.94

.100 1.41 1.38 1.44 65 1.59 1.58 1.67 60 1.74 1.69 1.74 PLOOS 50 1.78 1.73 1.83 RPTOOS TBVOOS 30 2.09 2.12 2.23

.FHOOS 30 (> 5O%F) 2.79 2.72 2.90 25 (> 50%F) ---

3.09

- 3.04.-. 3.18-30 (L 5o%F) 2.53 2.27

'2.68 25 (L 5o%F) 2.86 2.56 3.02 Add 0.02 to the above MCPRp limits for SLO.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Curc Operating Limits Report TVA-COLR-BF2CI4 Revision 1. Page 21 Table 3: MCPRp Limits for BOC to EOC Exposures - NSS Scram Times (Applicable up to Core Average Exposure of 32,798 MWd / MTU)

MCPRp Limit MCPRp Limit EOOS Power Option

(% Rated) 100 1.37 1.33 1.37 60 1.52 1.60 1.60 50 1.63 50 1.77 1.72 1.78 ic 30 1.96 2.00 2.10 30 (> 50%F) 2.21 2.23 2.36 25 (> 5O%F) 2.37 2.41 2.52 30 (55o%F) 2.18 2.06 2.35 25 (5 5o%F) 2.33 2.21 2.52 100 1.38 1.35 1.39 60 1.52 1.60 1.60 50 1.63 50 1.77 1.72 1.78 RPTOOS 30 1.96 2.00 2.10 30 (> 50%F) 2.21 2.23 2.36 25 (> SO%F) 2.37 2.41 2.52 30 (- 50%F) 2.18 2.06 2.35 25 ( 50%F) 2.33 2.21 2.52 100 1.40 1.36 1.41 60 1.55 1.60 1.63 50 1.65 so 1.77 1.72 1.78 TBVOOS 30 1.99 2.02 2.12 30 (> so%F) 2.73 2.65 2.82 25 (> 50%F) 3.02 2.96 3.09 30 (L 50%F) 2.47 2.22 2.61 25 (L 50%F) 2.78 2.50 2.93 100 1.41 1.37 1.42 60 1.55 1.60 1.63 50 1.65 RPTOOS 50 1.77 1.72 1.78 30 1.99 2.02 2.12 30 (> 5o%F) 2.73 2.65 2.82 25 (> 5o%F) 3.02 2.96 3.09 30 (L 5o%F) 2.47 2.22 2.61 25 (LS o%F) 2.78 2.50 2.93 EOOS Power A10 GE13 GE14 Option

(% Rated) 100 1.37 1.33.

1.37 60 1.57 1.60 1.66 5 0 1.69 50 1.77 1.72 1.80 FHOOS 30 2.05 2.08 2.20 30 (> 50%F) 2.30 2.31 2.45 25 (> 50%F) 2.48 2.51 2.64 30 (_5 0%F) 2.25 2.12 2.44 25 ( 5O%F) 2.43 2.30 2.63 100 1.38 1.35 1.39 60 1.57 1.60 1.66 50 1.69 RPTOOS 50 1.77 1.72 1.80 RPOOS 30 2.05 2.08 2.20 30 (> 50%F) 2.30 2.31 2.45 25 (> 50%F) 2.48 2.51 2.64 30 (55o%F) 2.25 2.12 2.44 25 (- 5o%F) 2.43 2.30 2.63 100 1.40 1.36 1.41 60 1.59 1.60 1.68 50 1.71 50 1.77 1.72 1.81 FHOOS 30 2.06 2.10 2.21 30 (> 50%F) 2.79 2.71 2.90 25 (> 50%F) 3.09 3.04 3.18 30 (- 5o%F) 2.53 2.27 2.68 25 (5 50%F) 2.86 2.56-- -- 3.02-100 1.41 1.37 1.42 60 1.59 1.60 i.68 50 1.71 RPTOOS 50 1.77 1.72 1.81 TBVOOS 30 2.06 2.10 2.21 FHOOS 30 (> 50%F) 2.79 2.71 2.90 25 (> 50%F) -- 3.09 -- -3.04

- 3.18-30 (< 50%F) 2.53 2.27 2.68 25 (55o%F) 2.86 2.56 3.02 Add 0.02 to the above MCPRp limits for SLO.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2CI4 Revision 1, Page 22 Table 4: MCPRp Limits for BOC to EOC Exposures - TSSS Scram Times (Applicable up to Core Average Exposure of 32,798 MWd / MTU)

MCPRp Limit MCPRp Limit EOOS Power Option

(% Rated) 100 1.38 1.34 1.39 60 1.54 1.60 1.62 50 1.65 50 1.78 1.73 1.79 30 1.98 2.01 2.12 30 (> 50%F) 2.21 2.23 2.36 25 (> 50%F) 2.37 2.41 2.52 30 (< so%F) 2.18 2.06 2.35 25 (5. o%F) 2.33 2.21

  • 2.52 100 1.41 1.39 1.41 60 1.54 1.60 1.62 50 1.65 50 1.78 1.73 1.79 RPTOOS 30 1.98 2.01 2.12 30 (> 50%F) 2.21 2.23 2.36 25 (> 5o%F) 2.37 2.41 2.52 30 L< 0%F) 2.18 2.06 2.35 25 (s 50%F) 2.33 2.21 2.52 100 1.41 1.37 1.42 60 1.57 1.60 1.66 50 1.67 50 1.78 1.73 1.79 TBVOOS 30 2.01 2.04 2.14 30 (> 5o%F) 2.73 2.65 2.82 25 (> 50%F) 3.02 2.96

-3.09 30 L 5o%F) 2.47 2.22 2.61 25 ( 50%F)-

2.78 2.50 2.94 100 1.45 1.42 1.44 60 1.57 1.60 1.66 50 1.67 50 1.78 1.73 1.79 TBVOOS 30 2.01 2.04 2.14 30 (> 5o%F) 2.73 2.65 2.82 25(> 50%F) - --3.02

  • 2.96--... 3.09 30 so%F) 2.47 2.22 2.61 25 (L so%F) 2.78 2.50 2.94 EOOS Power Option

(% Rated)

A10 GE13 GE14 100 1.38 1.34 1.39 60 1.59 1.60 1.67 50 1.71 50 1.78 1.73 1.81 FIIOOS 30 2.06 2.10 2.22 30 (> 50%F) 2.30 2.31 2.45 25 (> 50%F) 2.48 2.51 2.64 30 L 50%F) 2.25 2.12 2.44 25 (L 50%F) 2.43 2.30 2.63 100 1.41 1.39 1.41 60 1.59 1.60 1.67 5 0 1.7 1 50 1.78 1.73 1.81 MOOS 30 2.06 2.10 2.22 30 (> 50%F) 2.30 2.31 2.45 25 (> 5o%F) 2.48 2.51 2.64 30 < 50%oF) 2.25 2.12 2.44 25 (-. 50%F) 2.43 2.30 2.63 100 1.41 1.37 1.43 60 1.61 1.60 1.70 5 0 1.7 3 50 1.78 1.73 1.83 TBOOS 30 2.09 2.12 2.23 30 (> so%F) 2.79 2.72 2.90 25 (> 50%F) 3.09 3.04 3.18

-30 (_< 50%F) 2.53 -

2.27 2.68 25 (L. SOF) 2.86 2.56 3.02 100 1.45 1.42 1.44 60 1.61 1.60

  • 1.70 50 1.73 RPTOOS 50 1.78 1.73 1.83 TBVOOS 30 2.09 2.12 2.23 FHOOS 30 (> 50%F) 2.79 2.72 2.90 25 (> 50%F)

.3.09 3.04 3.18 30 (L 50%F) 2.53 2.27 2.68 25 (L 50%F) 2.86 2.56 3.02 Add 0.02 to the above MCPRp limits for SLO.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1. Pare 23 Table 4 (Continued): MCPRp Limits for BOC to EOC Exposures - TSSS Scram Times (Applicable up to Core Average Exposure of 32,798 MWd / MTU)

MCPRp Limit EOOS Power Option

(% Rated) 100 1.42.

1.39 1.41 65 1.54 1.58 1.60 60 1.75 1.69 1.74 PLUOOS 50 1.78 1.73 1.79 RPTOOS 30 1.98 2.01 2.12 30 (> 5O%!)

2.21 2.23 2.36 25 (> 50%M) 2.37

.2.41 2.52 30 (55o%!)

2.18 2.06 2.35 25 ( 50%:F) 2.33 2.21 2.52 100 1.42

.1.39 1.41 65 1.57 1.58 1.64 60 1.75 1.69 1.74 PLUOOS 50 1.78 1.73 1.81 RPTOOS 30 2.06 2.10 2.22 FHOOS 30 (> 50%r) 2.30 2.31.

2.45 25 (> 50%!:)

2.48 2.51 2.64 30 (50%F) 2.25 2.12 2.44 25 (s50%F) 2.43 2.30 2.63 100 1.45

.1.42 1.44 65 1.56 1.58 1.64 60 1.75 1.69 1.74 PLUOOS 50 1.78 1.73 1.79 RPTOOS 30 2.01 2.04 2.14 TBVOOS 30 (> 50%1) 2.73 2.65 2.82 25 (> 50%F) 3.02 2.96 3.09 30 (50%F) 2.47 2.22-

--2.61---

25 so%F) 2.78 2.50 2.94 100 1.45 1.42 1.44 65 1.59 1.58 1.67 PLUOOS 60 1.75 1.69 1.74 50 1.78 1.73 1.83

.mvOOS 30 2.09 2.12 2.23 FHOOS 30 (> 50%!)

2.79-- ---2.72 2.90 25 (> 50%F!)

3.09 3.04 3.18 30 (L 50%/F) 2.53 2.27 2.68 25 (L 50%F) 2.86 2.56 3.02 Add 0.02 to the above MCPRp limits for SLO.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2CI4 Revision 1, Page 24 Table 5: MCPRp Limits for BOC to CD Exposures - NSS Scram Times (Applicable up to Core Average Exposure of 33,871 MWd / MTU)

All Values Include FFTRJFHOOS and Bound Heaters In-Service MCPRp Limit EOOS Power Option

(% Rated) 100 1.37 1.33 1.37 60 1.57 1.60 1.66 50 1.69 In-50 1.77 1.72 1.80 Service 30 2.05 2.08 2.20 30 (> 50%F) 2.30 2.31 2.45 25 (> 50%F) 2.48 2.51 2.64 30(

50%F) 2.25 2.12 2.44 25 ( 50%F) 2.43 2.30 2.63 100 1.38

1.35 1.39 60 1.57 1.60 1.66 50 1.69 50 1.77 1.72 1.80 RPTOOS 30 2.05 2.08 2.20 30 (> 50%F) 2.30 2.31 2.45 25 (> 50%F) 2.48 2.51 2.64 30 (.. 5o%F) 2.25 2.12 2.44 25 (L 50%F) 2.43 2.30 2.63 100 1.40 1.37 1.41 60 1.59 1.60 1.68 50 1.71 50 1.77 1.72 1.81 TBVOOS 30 2.06 2.10 2.21 30 (> 50%F) 2.79 2.71 2.90 25 (> 50%F) 3.09 3.04 3.18 30 L< 50%F) 2.53 2.27 2.68 25 L 50%F) 2.86 2.56 3.02 100 1.41 1.39 1.43 60 1.59 1.60 1.68 50 1.7 1 50 1.77 1.72 1.81 TOOS 30 2.06 2.10 2.21 30 (> 5o%F) 2.79-" ---2.71 2.90 25 (> 5o%F) 3.09 3.04 3.18 30 L< 5o%F) 2.53 2.27 2.68 25 (.5 50%F) 2.86 2.56 3.02 Add 0.02 to the above MCPRp limits for SLO.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1, Page 25 Table 6: MCPRp Limits for BOC to CD Exposures - TSSS Scram Times (Applicable up to Core Average Exposure of 33,871 MWd / MTU)

All Values Include FFTR/FHOOS and Bound Heaters In-Service F

MCPRp Limit EOOS Power Option

(% Rated) 100 1.38 1.34 1.39 60 1.59 1.60 1.67 50 1.71 50 1.78 1.73 1.81 ine 30 2.06 2.10 2.22 30 (> 50%F)-

2.30 2.31 2.45 25 (> 5o%F) 2.48 2.51 2.64 30 (5 5o%F) 2.25 2.12 2.44 25 (-. So%F) 2.43

.2.30 2.63 100 1.41 1.39 1.41 60 1.59 1.60 1.67 50 1.71 50 1.78 1.73 1.81 RPTOOS 30 2.06 2.10 2.22 30 (> so%F) 2.30 2.31 2.45 25 (> 50%F) 2.48 2.51 2.64 30( 5o%F) 2.25 2.12 2.44 25 (.50%F) 2.43 2.30 2.63 100 1.41 1.37 1.43 60 1.61 1.60 1.70 50 1.73 50 1.78 1.73 1.83 TBVOOS 30 2.09

.2.12 2.23 30 (> 50%F) 2.79 2.72 2.90 25 (>5o%F) 3.09 3.04 3.18 30 &5o.m).

-2.53'-- -2.27 2.68 25 (55oF) 2.86 2.56 3.02 100 1.47 1.45 1.47 60 1.61 1.60 1.70 50 1.73 50 1.78 1.73 1.83 TOOS 30 2.09 2.12 2.23 B30 (>; 5o0%F) 2.79

-2.72-

"2.90 25 (> 5o%F) 3.09 3.04 3.18 30 ( 5o%F) 2.53 2.27 2.68 25 50oF) 2.86 2.56 3.02 Add 0.02 to the above MCPRp limits for SLO.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Cdre Operating Limits Report TVA-COLR-BF2C14 Revision 1, Page 26 Table 6 (Continued)i MCPRp Limits for DOC to CD,Eposures - TSSS Scram Times (Applicable up to Core Average Exposure of 33,871 MWd / MTU)

All Values Include FFTR/FHOOS and Bound Heaters In-Service MCPRp Limit EOOS Power Option

(% Rated)

A10 GE13 GE14 100 1.42 1.39 1.41 65 1.57 1.58 1.64 60 1.76 1.69 1.75 50 1.78 1.73 1.81 PLUOS 30 2.06 2.10 2.22 30 (> 5o%F) 2.30 2.31 2.45 25 (> SO%F) 2.48 2.51 2.64 30 (.. 50%F) 2.25 2.12 2.44 25 (L 50%F) 2.43 2.30 2.63 100 1.47 1.45 1.47 65 1.60 1.59 1.68 60 1.76 1.69 1.75 PLUOOS 50 1.78 1.73 1.83 RPTOOS 30 2.09 2.12 2.23 TBVOOS 30 (> 50%F) 2.79

.2.72 2.90 25 (> so%F) 3.09 3.04 3.18 30 L<so%r) 2.53

.2.27 2.68 25 (50%F) 2.86

-2.56 3.02 Add 0.02 to the above MCPRp limits for SLO.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

T%.A Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2CI4 Revision 1, Page 27 Figure 1 APLHGR Limits for Bundle-Type GE13-P9DTB391-13GZ (GE13 EDB# 2430) 15.00 14.00 13.00 12.00 I j.

[UNACCEPTABE PERATION)

I E

3

-J a-IMVV 0.00-9.00 -i

-* --e.

7.00-ACCEPTABLE OPERATION I 6.00 5.00 4.0oo__

_ I I

4.00 3.00 -

2.00 1.00 0.0 10.0 20.0 30.0 40.0.

Average Planar Exposure (GWD/MTU) 50.0 60.0 Most Limiting Lattice for Each Exposure Point Average Planar LHGR Average Planar LHGR Average Planar LHGR

-Exposure---- --

L Limit Exposure Limit Exposure Limit (GWD/MTU)

(kw/ft)

(GWD/MTU)

(kw/ft)

(GWDIMTU)

(kwlft) 0.00 10.75 7.72 11.45 27.56 10.79 0.22 10.80 8.82 11.55 33.07 10.24 1.10 10.87 9.92 11.66 38.58 9.85 2.20 10.96 11.02 11.77 44.09 9.49 3.31 11.06 13.78 11.71 49.60 9.15 4.41 11.15 16.53 11.63 55.12 8.78 5.51 11.25 19.29 11.55 60.63 8.45 6.61 1135......

22.05.

. 11.39-63.74......8.27 These values apply to both Turbine Bypass In-Service and Out-Of-Service.

These values apply to both Recirculation Pump Trip In-Service and Out-Of-Service.

These limits are for dual recirculation loop operation. Single Loop Operation (SLO) adjustments are performed as described in Section 2 Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report 4'

TVA-COLR-BF2C 14 Revision 1, Page 28 Figure2 APLHGR Limits for Bundle Type GE13-P9DTB412-2G7.0/11G5.0 (GEI3 EDB# 2431) 15.00-14.00 13.00-12.00-UNACCEPTABLE OPERATION 11.00.

10.00 S8.00, 7.00 ACCEPTABLE OPERATION 6 7.00-6.00 0.00 10.00 20.00 30.00 40.00 50.00 60.00 Average Planar Exposure (GWD/MTU)

Most Limiting Lattice for Each Exposure Point Average Planar LHGR Average Planar LHGR Average Planar LHGR Exposure Limit Exposure Limit

- Exposure----

-Limit (GWD/MTU)

(kw/ft)

(GWDIMTU)

(kw/ft)

(GWD/MTU)

(kw/ft) 0.00 10.38 7.72 11.58 27.56 11.12 0.22 10.45 8.82 11.73 33.07 10.78 1.10 10.57 9.92 11.86 38.58 10.46 2.20 10.72 11.02 12.00 44.09 10.01 3.31 10.88 13.78 12.03 49.60 9.49 4.41 11.05 16.53 11.96 55.12 9.04 5.51 11.22 19.29 11.80 60.63 8.66 6.61 11.40 22.05 T

11.59

-63.92-..

.8;45--

These values apply to both Turbine Bypass In-Service and Out-Of-Service.

These values apply to both Recirculation Pump Trip In-Service and Out-Of-Service.

These limits are for dual recirculation loop operation. Single Loop Operation (SLO) adjustments are performed as described in Section 2 Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1, Page 29 Figure 3 APLHGR Limits for Bundle Type GE14-P1ODNAB416-16GZ (GE14 EDB#2600) 14.00 13.00 12.00 11.00 10.00 9.00 8.00

]

7.00 x.0 5.00 4.00 3.00 2.00 1.00 UNACCEPTABLE OPERAT ION ACCEPTABLE OPERAT

_ _ 1_

i

_ _ _ _ _I_ _ _ _ _ _ _ _ _ _ _

_ 1.

__ I___

0.00 0.00 10.00 20.00 30.00 40.00 50.00 60.00 Average Planar Exposure (GWDIMTU)

Most Umiting Lattice for Each Exposure Point Average Planar LHGR Average Planar LHGR Average Planar LHGR Exposure Limit Exposure Limit Exposure Limit (GWD/MTU)

(kwlft)

(GWD/MTU)

(kw/ft)

(GWD/MTU)

(kw/ft) 0.00 9.41 8.82 10.56 22.05 10.85 0.22 9.51 9.92 10.65 27.56 10.50 1.10 9.61 11.02 10.74 33.07 10.10 2.20 9.73 12.13 10.85 38.58 9.63 3.31 9.86 13.23 10.85 44.09 9.10 4.41 10.00 14.33 10.86 49.60 8.57 5.51 10.14 15.43 10.88 55.12 8.02 6.61 10.28 16.53 10.91 60.63 6.24 7.72 10.42 18.74 10.94 63.50 4.93 These values apply to both Turbine Bypass In-Service and Out-Of-Service.

These values apply to both Recirculation Pump Trip In-Service and Out-Of-Service.

These limits are for dual recirculatlon loop operation. Single Loop Operation (SLO) adjustments are performed as described In Section 2 Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel C6re Operating Limits Report TVA-COLR-BF2C14 Revision 1, Page 30 Figure 4 APLHGR Limits for Bundle Type GE14-P1ODNAB416-16GZ (GE14 EDB#2601)

IQ.UUY I 13.00 41.-

"I 11.00 10.00 9.00 8.00 IL.. -- 4 E

C,

_J 7.001 PBLE OPERATION E O I

_*I I

I I

%I).VV 6.00 4.00 a.O0 2.00 I

0.00 0.00 10.00 20.00 30.00 40.00 50.00 60.00 Average Planar Exposure (GWD/MTU)

Most Limiting Lattice for Each Exposure Point Average Planar LHGR Average Planar LHGR Average Planar LHGR Exposure Limit Exposure Limit Exposure Limit (GWD/MTU)

(kw/ft)

(GWD/MTU)

(kw/tft)

(GWD/MTU)

(kw/ft) 0.00 9.43 8.82 10.76 22.05 10.88 0.22 9.47 9.92 10.83 27.56 10.50 1.10 9.54 11.02 10.91 33.07 10.10 2.20 9.67 12.13 10.99 38.58 9.66 3.31 9.83 13.23 11.03 44.09 9.13 4.41

.10.02 14.33 11.02 49.60 8.59 5.51 10.21 15.43 11.02 55.12 8.03 6.61 10.43 16.53 11.03 60.63 6.38 7.72 10.62-..

18.74 11.02

-63.82

-4..92 These values apply to both Turbine Bypass In-Service and Out-Of-Service.

These values apply to both Recirculation Pump Trip In-Service and Out-Of-Service.

These limits are for dual recirculatlon loop operation. Single Loop Operation (SLO) adjustments are performed as described In Section 2 Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2CI4 Revision 1, Page 31 Figure 5 APLHGR Limits for Bundle Type GE14-P1ODNAB367-14GZ (GE14 EDB# 2602)

E, 14.UU I_

13.00, 12.00

{UNACCEPTABLE OPERATION J 11.00I 10.00 9.00-8.00 I CCEPTABLE OPEATION 6.00-5.00.

I I

4.00-1 2.00 1

.00 I Q*V 0.001 0.0)0 10.00 20.00 30.00 40.00 Average Planar Exposure (GWD/MTU) 50.00 60.00 Most Limiting Lattice for Each Exposure Point Average Planar LHGR Average Planar LHGR Average Planar LHGR Exposure Limit Exposure Limit Exposure Limit (GWDIMTU)

(kwlft)

(GWD/MTU)

(kw/tt)

(GWD/MTU)

(kwlft) 0.00 9.80 8.82 10.99 22.05 10.94 0.22 9.86 9.92 11.14 27.56 10.38 1.10 9.96 11.02 11.29 33.07 9.83 2.20 10.09 12.13 11.45 38.58 9.29 3.31 10.24 13.23 11.54 44.09 8.76 4.41 10.40 14.33 11.53 49.60 8.23

.5.51 10.56 15.43 11.49 55.12 7.67 6.61 10.71 16.53 11.43 60.63 5.66 7.72 10.85 18.74 11.26 62.56

--4.79 These values apply to both Turbine Bypass In-Service and Out-Of-Service.

These values apply to both Recirculation Pump Trip In-Service and Out-Of-Service.

These limits are for dual recirculation loop operation. Single Loop Operation (SLO) adjustments are performed as described in Section 2 Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2CI4 Revision 1, Page 32 Figure 6 APLHGR Limits for Bundle Type GE14-P1ODNAB416-18GZ (GE14 EDB# 2627) 14.00 13.00 12.00 11.00 10.00 9.00 8.00 7.00 6.00

.J 5.00 4.00 3.00 2.00 1.00 0.00 1L 0.00 10.00 20.00 30.00

.40.00 50.00 60.00 Average Planar Exposure (GWDIMTU)

Most Limiting Latitice for Each Exposure Point Average Planar LHGR Average Planar LHGR Average Planar LHGR Exposure Limit Exposure Limit Exposure Limit (GWD/MTU)

(kwlft)

(GWD/MTU)

(kw/ft)

(GWD/MTU)

(kw/ft) 0.00

.9.26 8.82 10.54 22.05 10.85 0.22 9.34 9.92 10.65 27.56 10.49 1.10 9.47 11.02 10.75 33.07 10.09 2.20 9.62 12.13 10.85 38.58 9.60 3.31 9.77 13.23 10.85 44.09 9.09 4.41 9.93 14.33 10.86 49.60 8.56 5.51 10.09 15.43 10.88 55.12 8.01 6.61 10.25 16.53 10.91 60.63 6.21 7.72 10.41 18.74 10.93 63.42 4.93 These values apply to both Turbine Bypass In-Service and Out-Of-Service.

These values apply to both Recirculation Pump Trip In-Service and Out-Of-Service.

These limits are for dual recirculation loop operation. Single Loop Operation (SLO) adjustments are performed as described In Section 2 Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1, Page 33 Figure 7 APLHGR Limits for Bundle Type GE14-P1ODNAB417-I8GZ (GE14 EDB# 2628)

_J 14.UU 13,00 12.00-10,00.

9.00 8.00-ACCEPTABLE OPEA1N 6.00.

5.00._

4.00-3.00-

___KI_______

f I

1.00 0.00 0.0 I

I-0 10.00 20.00 30.00 40.00 Average Planar Exposure (GWD/MTU) 50.00 60.00 Most Limiting Lattice for Each Exposure Point Average Planar LHGR Average Planar LHGR Average Planar LHGR Exposure Limit Exposure Limit Exposure_...

Limit (GWD/MTU)

(kw/ft)

(GWD/MTU)

(kw/ft)

(GWD/MTU)

(kwlft) 0.00 9.39 8.82 10.74 22.05 10.88 0.22 9.43 9.92 10.83 27.56 10.50 1.10 9.50 11.02 10.91 33.07 10.10 2.20 9.63 12.13 11.00 38.58 9.62 3.31 9.80 13.23 11.02 44.09 9.12 4.41 9.99 14.33 11.02 49.60 8.58 5.51 10.19 15.43 11.02 55.12 8.02 6.61 10.41 16.53 11.03 60.63 6.35 7.72 10.64 18.74 11.02 63.74 4.92 These values apply to both Turbine Bypass In-Service and Out-Of-Service.

These values apply to both Recirculatlon Pump Trip In-Service and Out-Of-Service.

These limits are for dual recirculation loop operation. Single Loop Operation (SLO) adjustments are performed as described In Section 2 Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1, Page 34 Figure 8 APLHGR Limits for A10-3920B-14GV70 (A10)

E

_J 0.00 1 1

1_11 0.00 10.00 20.00 30.00 40.00 50.00 60.00 Average Planar Exposure (GWD/MTU)

Average Planar LHGR Exposure Limit (GWDIMTU)

(kwlft) 0.00 12.50 15.00 12.50 67.00 7.30 These values apply to both Turbine Bypass In-Service and Out-Of-Service.

These values apply to both Recirculation Pump Trip In-Service and Out-Of-Service.

These limits are for dual recirculation loop operation. Single Loop Operation (SLO) adjustments are performed as described in Section 2 Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2CI4 Revision 1. Page 35 Figure 9 GE13 Power Dependent MAPLHGR Multiplier - MAPFAC(P)

NSS/TSSS Insertion Times - All Exposures

.L eL 0.

1.1I II I

Turbine Bypass In-Servlce(TBVIS 0.9

,AD

[

0.8-0.7 TrieBypass Out-Of-Service (TBVOOS) 0.7 S

I I__ _

0.5 I

I 0 TBVIS: 150%Core Flw, 4 TBVOS: S W/.Core I

TBVOOS: 3.

/. Core Flow, 0.3 1

25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Power (% Rated)

Turbine Bypass In-Service Turbine Bypass Out-Of-Service Core Power M%

rated)

MAPFAC(P) 100 1

30 0.51 Core Flow > 50% rated 30 0.39 25 0.36 Core Flow < 50% rated 30 0.43 Core Power 50%rated M% rated)

MAFCP 100 0.91 30 0.51 Core Flow > 50% rated 30 0.33 25 1

0.31 Core Flow < 50% rated 30 0.37 25 1

0.42 25 1

0.34 MAPFAC(P) Is not dependent upon any Equipment.Out-Of-Service except Turbine Bypass.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report

~*

TVA-COLR-BF2C14 Revision 1, Page 36 Figure 10 GE14 Power Dependent MAPLHGR Multiplier - MAPFAC(P)

NSS/TSSS Insertion Times - All Exposures 1.1 0.9 0.8 0.7 t

Turbine Bypass In-Service (TBVIS)

"I"

_j,ý,ýý Turbine Bypass Out-Of-Service (TBVOOS) 2

° I

! I I

0.5 ~-----,

BvIS:.50%*Core Flow I

TBVOOS: 5 MY. Core 04 I TBvIS:,S0.co,.

I

[ I I__

I 0.4 TBVOOS:3.1 W/.0 Core Rlow I

0_

  • I 02

~**

~___

v.-

25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 PoweS (% Rated)

Turbine Bypass In-Service Turbine Bypass Out-Of-Service Core Power AFCP M rated) 100 1

30 0.55 Core Flow > 50% rated 30 0.44 25 0.42 Core" Flow < 50% rated 30 1

0.50 Care Power MAPFAC(P)

%rated) 100 0.96 30 0.54 Core Flow > 50% rated 30 0.39 25 0.37 Core Flow < 50% rated 30 J

0.43 25 0.41 25 0.49 MAPFAC(P) Is not dependent upon any Equipment Out-Of-Service except Turbine Bypass.

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Linits Report TVA-COLR-BF2C14 Revision 1, Page 37 Figure 11 Flow Dependent MAPLHGR Factor - MAPFAC(F)

(GEl3) r.

30 40 50 60 70 80 90 100 Core Flow (% Rated)

Max Core Flow 102.5% Rated Core Flow MAPFAC(F)

(% rated) 30 0.55 80 1.00 102.5 1.00 Max Core Flow 107% Rated Core Flow

(% rated).

MAPFAC(F) 30 0.52 85 1.00 107 1.00 These values bound both Turbine Bypass In-Service and Out-Of-Service.

These values bound both Recirculation Pump Trip In-Service and Out-Of-Service.

The 102.5% maximum flow line is used for operation up to 100% rated flow.

The 107% maximum flow line is used for operation up to 105% rated flow (ICF).

Browns Ferry Nuclear Plant Unit 2 Cycle 14 I

TWA Nuclear Fuel Core Operatinig Linmits Report TVA-COLR-BF2CI4 Revision 1, Page 38 Figure 12 Flow Dependent MAPLHGR Factor - MAPFAC(F)

(GE14) 1.00 0.90 0.80 0.70 0.60 0.50 30 40 50 60

_70 80 90 100 Core Flow (% Rated)

Max Core Flow 102.5% Rated Core Flow MAPFAC(F)

(% rated) 30 0.55' 78 1.00 102.5 1.00 Max Core Flow 107% Rated Core Flow MAPFAC(F)

(% rated) 30 0.55 81 1.00 107 1.00 These values bound both Turbine Bypass In-Service and Out-Of-Service.

These values bound both Recirculation Pump Trip In-Service and Out-Of-Service.

The 102.5% maximum flow line Is used for operation up to 100% rated flow.

The 107% maximum flow line is used for operation up to 105% rated flow (ICF).

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2CI4 Revision 1, Page 39 Figure 13 LHGR Limits for all ATRIUM-10 Fuel (AIO) 14.00" 13.00-12.00 1 UKNACCEPTABLE OPERATION 11.00 10.00 9.00,Ii 8nn*

E 7.00-6.00

-J I

I t

IACCEPTABLE OPERATION I

[ ACCEPTABLE OPERATION l i

5.00 4.00 3.00 2.00 1.00 0.00 0.0

__ I I ________

I ________________________________

It

___________ I.

___________ I

. F 0

10.00 20.00 30.00

.40.00 50.00 Pellet Exposure (GWD/MTU) 60.00 70.00 Pellet LHGR Exposure Limit (GWD/MTU)

(kw/ft) 0.00 13.40 18.90 13.40 74.40 7.10 These values applyto both Turbine Bypass In-Service and Out-Of-Service..

These values apply to both Recirculation Pump Trip In-Service and Out-Of-Service.

These limits apply to both Two Loop Operation (TLO) and Single Loop Operation (SLO).

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1, Page 40 Figure 14 A10 Power Dependent LHGR Multiplier - LHGRFAC(P)

NSS/rSSS Insertion Tim~s -All Exposures 1.10 1.00 0.90 0.80 a.

0.70 0.60 0.50 0.40 0.30 Turbine Bypass In-Service (TBVIS)

I S I I

I i

I l1Turbine Bypass Out-Of-Service (TB VOOS)

TBVIS: S 50% Core Flow TBVLS:

,50% Core TOVOOS: ASO% Core I_____

TOVOOS. 3, 50% Core Flow

_ _ _ _ _ I_

~1~

~1____________

25 30 35 40 45 50 55 60 65 70 Power (1/ Rated) 75 80 85 90 95 100 Turbine Bypass In-Service Turbine Bypass Out-Of-Service Core Power [LHGRFAC(P)

V/ rated) 100 i

1.00 30 0.69 Core Flow > 50% rated 230 0.49 25 0.44 Core Flow;< 50% rated 30 0.58 25 0.52 LHGRFAC(P) is not dependent upon any Equipment Out-Of-Service except Turbine Bypass.

Browns Ferry Nuclear Plant Unit 2 Cycle14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C14 Revision 1, Page 41 Figure 15 Flow Dependent LHGR Multiplie - LHGRFAC(F)

(AlO Fuel)

-J 40 50 60 70" 80 90 100 Core Flow (% Rated)

Max Core Flow 102.5% Rated Core Flow LHGRFAC(F)

(% rated) 30 0.84 55 1.00 102.5 1.00 Max Core Flow 107% Rated Core Flow LHGRFAC(F)

(% rated) 30 0.82 60 1.00 107 1.00 These values bound both Turbine Bypass In-Service and Out-Of-Service.

T*hese vaiues bound booth JRecirculati-on Pumip Trip In-Service and Out-Of-Service.

The 102.5% maximum flow line Is used for operation up to 100% rated flow.

The 107% maximum flow line is used for operation up to 105% rated flow (ICF).

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report

',J TVA-COLR-BF2C14 Revision 1. Page 42 Figure 16 Flowi Dependent MCPR Limit - MCPR(F)

(GE 13 Fuel) c-Ue 1.78 1.73 1.68 1.63 1.58 1.53 1.48 1.43 1.38 1.33 1.28 1.23 1.18

_ I I

MAX FLOW 107%

i I _

30 40 50 60 70 Core Flow (% Rated) 80 90 100 Max Core Flow 102.5% Rated Core Flow MCPR(F)

(% rated).

30 1.73 88 1.21 102.5 1.21 Max Core Flow 107% Rated Core Flow MCPR(F)

(% rated) 30 1.77 88 1.21 107 1.21 These values bound both Turbine Bypass In-Service and Out-Of-Service.

- " These values bound both Recirculation Pump Tripln-Service and Out-Of-Service.

The 102.5% maximum flow line is used for operation up to 100% rated flow.

The 107% maximum flow line is used for operation up to 105% rated flow (ICF).

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2C 14 Revision 1, Page 43 Figure 17 Flow Dependent MCPR Limit - MCPR(F)

(GE14 Fuel) 1.68 1.63 1.58 1.53 1.48 m 1.43 Ia.

U 1.38 1.33 1.28 1.23 1.18 1

.30 40 50 60 70 80 90 100 Core Flow (% Rated)

Max Core Flow 102.5% Rated Core Flow

(% rated)

MCPR(F) 30 1.63 88 1.21 102.5 1.21 Max Core Flow 107% Rated Core Flow

(% rated)

MCPR(F) 30 1.65 88 1.21 107 1.21 These values bound both Turbine Bypass In-Service and Out-Of-Service.

These values bound both Recirculation Pump Trip In-Service and Out-Of-Service.

The 102.5% maximum flow line is used for operation up to 100% rated flow.

The 107% maximum flow line is used for operation up to 105% rated flow (ICF).

Browns Ferry Nuclear Plant Unit 2 Cycle 14

TVA Nuclear Fuel Core Operating Limits Report TVA-COLR-BF2CI4 Revision 1, Page 44 (Final)

Figure 18 Flow Dependent MCPR Limit - MCPR(F)

(AlO Fuel) 1.73 1.68 1.63 1.58 1.53 1.48 o 1.43 1.38 1.33 1.28 1.23 1.18 30 40 50 60 70 80 90 100 Core Flow (% Rated)

Max Core Flow 102.5% Rated Core Flow MCPR(F)

(% rated) 30 1.66 88 1.21 102.5.

1.21 Max Core Flow 107% Rated Core Flow

.(% rated)

MCPR(F) 30 1.71 88 1.21 107 1.21 These values bound both Turbine Bypass In-Service and Out-Of-Service.

These values bound both Recirculation Pump Trip In-Service and Out-Of-Service.

The 102.5% maximum flow line is used for operation up to 100% rated flow.

The 107% maximum flow line is used for operation up to 105% rated flow (ICF).

Browns Ferry Nuclear Plant Unit 2 Cycle 14