Refueling Equipment Interlocks 3.9.1 3.9 REFUELING OPERATIONS 3.9.1 Refueling Equipment Interlocks LCO 3.9.1 APPLICABILITY:
The refueling equipment interlocks associated with the reactor mode switch refuel position shall be OPERABLE.
During in-vessel fuel movement with equipment associated with the interlocks when the reactor mode switch is in the refuel position.
ACTIONS CONDITION REQUIRED ACTION TIME A.
One or more required A.1 Suspend in-vessel fuel Immediately refueling equipment movement with equipment interlocks inoperable.
associated with the inoperable interlocks(s).