Text

_

Exelkn.

Exelon Nuctar www.exeloncorp.com Nuclear Limerick Geierating Station P.O. Box 2300 Pottstown, PA 19464 NPDES PA 00051926 January 20, 2006 Ms. Jennifer Fields, P.E.

Chief, Permits Section Water Management Program Department of Environmental Protection 2 East Main St.

Norristown, PA 19401

Subject:

Spray Pond Additive for Antimicrobial Control

Reference:

LGS Industrial Waste NPDES Permit # PA00051926

Dear Ms. Fields:

Limerick Generating Station is requesting the addition of GE Betz Spectrus NX1 103, an EPA approved broad spectrum antimicrobial agent, to the list of approved chemicals. It would replace GE Betz Spectrus CT 1300, a material used for periodic biocide treatment of Spray Pond cooled equipment. Testing has shown that the CT1 300 material, which has been used for over ten years, is no longer an effective biocide unless applied at a concentration of >75 ppm.

NX1 103 would be applied at 30 ppm during a 75-minute biocide treatment twice per week.

Each treatment, consisting of 11.25 pounds of product, would combine with 375,000 gallons of the spray pond inventory of 29,000,000 gallons, or 1.29% of the Spray Pond total volume.

NX1 103 would also be applied, on average, 1.5 times per week at 30 ppm, for a 75-minute biocide treatment of the RHR Service Water system. Each treatment, consisting of 22.5 pounds of product, would combine the biocide with 750,000 gallons of the Spray Pond inventory, or 2.57% of the Spray Pond total volume. This would yield an addition rate of about 45 pounds of NX1 103 to the spray pond per week. Total usage rates for NX1 103 applications would be as follows maximum daily - 120 lbs/day, based on both ESW and all four RHR systems requiring treatment on the same day; and average monthly -20 lbs/day, based on weekly ESW treatments and twice per month treatment of all RHR heat exchangers.

The treatments return to the spray pond and mix with the water inventory of 29 million gallons.

The average overflow from the spray pond is approximately 20 gallons per minute, which combines with average Cooling tower blowdown of 6000 gpm.

After implementing NX1 103 usage, two applications per year of CT1 300 would still be required to treat for Asiatic clams in the ESW/RHRSW systems. Each application lasts for 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, and typically injects 25 pounds of CT1 300 into the Spray Pond.

Should you have any questions regarding this information, please contact Bob Alejnikov at 61 0-718-2513. Thank you for your cooperation in this matter.

C&oo'

Sincerely, Christopher H. Mudrick Plant Manager-LGS Exelon Generation Company, LLC

Attachment:

Material Safety Data Sheet-GE Betz Spectrus NX1 103 cc:

S. Collins, Region 1 Administrator, USNRC S. Hansell, Resident Inspector, USNRC Document Control Desk, USNRC, Wash. DC

A bcc:

R. DeGregorio - GML 5-1 C. Mudrick - GML 5-1 T. Tierney - SSB 2-3 M. Audette - SSB 2-3 R. Alejikov - SSB 2-3 T. Siglin - KSA 3N R. Kreider - SSB 2-4 N. Chand - SSB 3-2

0 GE Betz GE Betz, Inc.

4636 Somerton Road Trevose, PA 19053 Business telephone: (215) 355-3300 Material Safety Data Sheet Issue Date: 22-MAR-2002 EMERGENCY TELEPHONE (Health/Accident): (800) 877-1940 1 PRODUCT IDENTIFICATION PRODUCT NAME:

SPECTRUS NX1103 PRODUCT APPLICATION AREA:

WATER-BASED MICROBLAL CONTROL AGENT.

2 COMPOSITION / INFORMATION ON INGREDIENTS Information for specific product ingredients as required by the U.S. OSHA HAZARD COMMUNICATION STANDARD is listed. Refer to additional sections of this MSDS for our assessment of the potential hazards of this formulation. This product is subject to the Pennsylvania and New Jersey Worker and Community Right to Know Law.

HAZARDOUS INREDIENTS:

CASt CHEMICAL NAME 13590-97-1 6317-18-6 67-63-0 DODECYLGUANIDINE HYDROCHLORIDE (DGH)

Corrosive METHYLENE BIS(THIOCYANATE)

Corrosive (eyes); toxic (by ingestion); irritant (skin); potential sensitizer (skin)

ISOPROPYL ALCOHOL (IPA)

Flammable liquid; chronic overexposure may cause liver and kidney toxicity No component is considered to be a carcinogen by the National Toxicology Program, the International Agency for Research on Cancer, or the Occupational Safety and Health Administration at Pennsylvania thresholds for carcinogens.

NON-HZARDOUS INGREDIENTS:

CAS#

CHEMICAL NAME htps://remoteoffice.ge.com/ge-betz-msds/BetzHTMIPRODUCTS/PANJ/SPECTRUSL...

4/21/2004

7732-18-5 WATER 25 32 7A-68 -3 POLYETHYLENE GLYCOL 3 HAZARDS IDENTIFICATION E2ERGENCY OVERVIEW Severe irritant to the skin. Skin sensitizer. Corrosive to the eyes. Vapors, gases, mists and/or aerosols cause irritation to the upper respiratory tract.

DOT hazard: Combustible liquid Emergency Response Guide #27 Odor: Slight Pungent; Appearance: Yellow, Liquid Fire fighters should wear positive pressure self-contained breathing apparatus(full face-piece type). Proper fire-extinguishing media:

dry chemical/C02/foam or water--slippery condition; use sand/grit.

i************************************** *****************************************

POTENTIAL BEALTH EFFECTS ACUTE SKIN EFFECTS:

Primary route of exposure; Severe irritant to the skin. Skin sensitizer.

ACUTE EYE EFFECTS:

Corrosive to the eyes.

ACUTE RESPIRATORY EFFECTS:

Primary route of exposure;Vapors, gases, mists and/or aerosols cause irritation to the upper respiratory tract.

INGESTION EFFECTS:

May cause severe gastrointestinal irritation.

TARGET ORGANS:

Prolonged or repeated exposures may cause primary irritant dermatitis and/or skin sensitization.

MEDICAL CONDITIONS AGGRA'VATED:

Not known.

SYMPTONS OF EXPOSURE:

Inhalation of vapors/mists/aerosols cause eye, nose, throat and lung irritation. Skin contact may cause redness, itching, dermatitis, or skin sensitization.

4 FIRST AID MEASURES SKIN CONTACT:

Wash thoroughly with soap and water. Remove contaminated clothing.

Thoroughly wash clothing before reuse. Get medical attention if https://remoteoffice.ge.com/gebetz_nsds/BetzHTML/PRODUCTS/PA_NJ/SPECTRUSI...

4/21/2004

irritation develops or persists.

EYE CONTACT:

URGENT! Immediately flush eyes with plenty of low-pressure water for at least 20 minutes while removing contact lenses. Hold eyelids apart. Get immediate medical attention.

INEALATION:

Remove to fresh air. If breathing is difficult, give oxygen. If breathing has stopped, give artificial respiration. Get immediate medical attention.

INGESTION:

Do not feed anything by mouth to an unconscious or convulsive victim. Do not induce vomiting. Immediately contact physician.

Dilute contents of stomach using 3-4 glasses milk or water.

NOTES TO PHYSICIANS:

No special instructions 5 FIRE FIGHTING MEASURES FIRE FIGHTNG INSTRUCTIONS:

Fire fighters should wear positive pressure self-contained breathing apparatus (full face-piece type).

EXTINGUISHING MEDIA:

dry chemical/CO2/foam or water--slippery condition; use sand/grit.

HAZARDOUS DECOMPOSITION PRODUCTS:

Thermal decomposition (destructive fires) yields elemental oxides.

FLASH POINT:

120F 49C SETA(CC)

MISCELLANEOUS:

Combustible liquid NA1993;Emergency Response Guide #27 6 ACCIDENTAL RELEASE MEASURES PROTECTION AND SPILL CONTAINMENT:

Ventilate area. Use specified protective equipment. Contain and absorb on absorbent material. Place in waste disposal container.

Remove ignition sources. Flush area with water. Spread sand/grit.

DISPOSAL INSTRUCTIONS:

Water contaminated with this product may be sent to a sanitary sewer treatment facility,in accordance with any local agreementa permitted waste treatment facility or discharged under a permit. Product as is -

Dispose of in approved pesticide facility or according to label instructions.

7 HANDLING & STORAGE HANDLING:

Combustible. Corrosive to skin and/or eyes.

STORAGE:

Keep containers closed when not in use. Keep away from flames or sparks. Bond containers during filling or discharge when performed at temperatures at or above the product flash point.

8 EXPOSURE CONTROLS / PERSONAL PROTECTION EXPOSUIE LIMTS https://remoteoffice.ge.com/gebetz-msds/BetzHTIML/PRODUCTS/PANJ/SPECTRUSR..

4t2l/2004

I r

I CHENUCAL NAME DODECYLGUANIDINE HYDROCHLORIDE (DGH)

PEL (OSHA):

NOT DETERMINED TLV (ACGIH): NOT DETERMINED METHYLENE BIS(THIOCYANATE)

PEL (OSHA):

NOT DETERMINED TLV (ACGIH): NOT DETERMINED ISOPROPYL ALCOHOL (IPA)

PEL (OSHA):

400 PPM(500PPM-STEL)

TLV (ACGIH): 400 PPM(500PPM-STEL)

ENGINEERING CONTROLS:

Adequate ventilation to maintain air contaminants limits.

PERSONAL PROTECTIVE EQUIPMENT:

Use protective equipment in accordance with 29CFR

. RESPIRAORY PROTECTION:

A RESPIRATORY PROTECTION PROGRAM THAT MEETS below exposure 1910 Subpart I OSHA'S 29 CFR 1910.134 AND ANSI Z88.2 REQUIREMENTS MUST BE FOLLOWED WHENEVER WORKPLACE CONDITIONS WARRANT A RESPIRATOR'S USE.

USE AIR PURIFYING RESPIRATORS WITHIN USE LIMITATIONS ASSOCIATED WITH THE EQUIPMENT OR ELSE USE SUPPLIED AIR-RESPIRATORS.

If air-purifying respirator use is appropriate, use a respirator with organic vapor and HEPA cartridges.

SKIN PROTECTION:

gauntlet-type neoprene gloves, chemical resistant apron--

Wash off after each use. Replace as necessary.

EYE PROTECTION:

splash proof chemical goggles, face shield 9 PHYSICAL & CHEMICAL PROPERTIES SpedifiE Gra,.'

47j0F;21Cl:)-

1.o95 I Freeze Point (F)

< -30 Freeze Point (C)

< -34 Viscosity(cps 70F,21C) 64 Vapor Pressure (mmHG)

Vapor Density (air=1)

% Solubility (water) 24.0

> 1.00 100 0 Odor Appearance Physical State Flash Point SETA(CC) pH As Is (approx.)

Evaporation Rate (Water=l)

Slight Pungent Yellow Liquid 120F 48C 3.2

< 1.00 NA = not applicable ND = not deterained 10 STABILITY & REACTIVITY STABILITY:

Stable under normal storage conditions.

HAZARDOUS POLYMERIZATION:

Will not occur.

INCONPATIBILITIES:

https://remoteoffice.ge.com/ge_betzmsdsfBetz_HTML/PRODUCTS/PANJ/SPECTRUSI...

4/21/2004

May react with strong oxidizers.

DECCX4POSITION PRODUCTS:

v Thermal decomposition (destructive fires) yields elemental oxides.

INTER11AL PUMPOUT/CLEANOUT CATEGORIES:

WBW 11 TOXICOLOGICAL INFORMATION Oral LD50 RAT:

668 mg/kg NOTE -

Rat oral LD50: 520 mg/kg in an earlier study Dermal LD50 RABBIT:

>2,000 mg/kg NOTE -

Rabbit Dermal LD50: >16,000 mg/kg in an earlier study Inhalation LC50 RAT:

>2.90 mg/L/hr NOTE - Maximum achievable concentration Skin Irritation Score RABBIT:

4.9 NOTE -

Skin Irritation Score: 2.46 in an earlier study Eye Irritation Score RABBIT:

102 NOTE -

Irreversible; 21 day test, max.ave. score day 2 Skin Sensitization G.PIG:

POSITIVE NOTE - Magnusson & Kligman method 12 ECOLOGICAL INFORMATION AQUAIC TOXICOLOGY Bluegill Sunfish 96 Hour Static Acute Bioassay LC50= 2.7; No Effect Level= 1.5 mg/L Daphnia magna 48 Hour Static Renewal Bioassay LC50=.26; No Effect Level=.14 mg/L Fathead Minnow 96 Hour Static Renewal Bioassay LC50= 1.1; No Effect Level=.36 mg/L Rainbow Trout 96 Hour Static Acute Bioassay LC50= 2.7; No Effect Level= 1.33 mg/L BIODEGRADATION BOD-28 (mg/g):

518 BOD-5 (mg/g):

93 COD (mg/g):

1424 TOC (mg/g):

418 13 DISPOSAL CONSIDERATIONS If this undiluted product is discarded as a waste, hazardous waste identification number is :

D001=Ignitable.

the US RCRA Please be advised; however, that state and local requirements for waste disposal may be more restrictive or otherwise different from federal regulations. Consult state and local regulations regarding the proper disposal of this material.

14 TRANSPORT INFORMATION DOT HAZARD:

UN / NA NUMBER:

DOT EMERGENCY RESPONSE GUIDE #:

Combustible liquid NA1993 27 httpsi/moteoffice.ge.com/gebetzmsds/BetzHTML/PRODUCTSPANJ/SPECTRUSI..

4t21t2004

15 REGULATORY INFORMATION TSCA:

This is an EPA registered biocide and is exempt from TSCA inventory requirements.

CERCLh AND/OR SARA REPORTABLE QUANTITY (RQ):

No regulated constituent present at OSHA thresholds FIFRA REGISTRATION NIMIER:

3876-121 FOOD AND DRUG AD3INISTRATION:

The ingredients in this product are approved by FDA under 21 CFR 176.300.

USDA FEDERALLY INSPECTED MEAT AND POULTRY PLANTS:

SEC.G5,G7 SARA SECTION 312 HAZARD CIASS:

Immediate(acute);Delayed(Chronic);Fire SARA SECTION 302 CHEMICALS:

No regulated constituent present at OSHA thresholds SARA SECTION 313 CHEMICALS:

.No-xegulated constituent present at OSHA thresholds CALIEFORNIA REGULATORY INFORMATION CALIFORNIA SAFE DRINKING WATER. AND TOXIC ENFORCEMENT ACT (PROPOSITION 65) CHEMILS PRESENT:

No regulated constituent present at OSHA thresholds MICHIGAN REGULATORY INFRXQOTION No regulated constituent present at OSHA thresholds 16 OTHER INFORMATION NFPA/HMIS CODE TRANSLATION Health Fire Reactivity Special (1) Protective Equipment 3

2 0

NONE D

Serious Hazard Moderate Hazard Minimal Hazard No special Hazard Goggles, Face Shield, Gloves,Apron (1) refer to section 8 of MSDS for additional protective equipment recommendations.

CHANGE LOG EFFECTIVE DATE REVISIONS TO SECTION:

MSDS status:

22-JAN-1998 01-JUN-1998 12-JAN-1999 06-APR-1999 22-MAR-2002 8

3,7 1

4 SUPERCEDES

    • NEW **

22-JAN-1998 01-JUN-1998 12-JAN-1999 06-APR-1999 https://remoteoffice.ge.com/ge_betzmsds/BetzHTML/PRODUCTS/PANJ/SPECTRUSR..

421/2004

Spectrusw NX1103 Microbiological Control Agent Broad spectrum antimicrobial Proprietary blend minimizes microbial resistance FDA Approved (CFR 176.180 and 176.300)

USDA Approved (G5, G-7)

Approved for sale in California DESCRIPTION AND USE Spectrusu NX1103 is EPA approved for control of bacteria, algae, and fungi in a variety of industrial water-based systems. Specrus NX1 103 consists of a proprietary blend of 10% dodecylguanidine hydrochloride (DGH) and 5% methylene bis (thio-cyanate) [MBT].

Spectrus NXI 103 is approved for use in open recircu-lating cooling systems, heat exchange systems and evaporative condensers.

Control of microbiological populations in industrial water systems is essential to prevent biofouling. In cooling systems, biofouling of heat exchange equip-ment and tower fill reduces heat transfer efficiency and can force unscheduled shutdowns and extended turnarounds, leading to lost production. Equipment can also be damaged as a result of microbiologically influenced corrosion (MIC) associated with biofouling.

Consequently, biofouling must be prevented in order for operating units to avoid such events and achieve profitability goals.

Compared to single active biocide products (see Chart), the combination of surface active agent (DGH) and metabolic inhibitor (MBT) in Spectrus NX1103 work together to provide faster microbial control at lower dosages. The blend of actives in Spectrus NXI 103 also limits development of resistant microbial populations and reduces the need to alter-nate products to maintain effectiveness.

In addition to cooling systems, Spectrus NXI103 can be used to control microbes in influent water systems, air washers, pasteurizers, and water-based scrub-bers. See the Spectrus NX1 103 product label for a complete listing of approved end uses.

TREATMENT AND FEEDING REQUIREMENTS Correct treatment levels and frequency of Spectrus NXII03 addition depend on many factors. These indude, but are not limited to, system cleanliness, types of microbes, nutrient concentrations, tempera-ture, p1-, retention time, and other system operating characteristics. Consult the product label for general dosage guidelines. Microbiological monitoring is rec-ommended to evaluate product requirements.

Consult your GE Betz representative for technical advice on your specific application.

In all cases, this product must be applied in accor-dance with use instructions on the Spectrus NXI103 label.

Feed point - Apply Spectrus NXI 103 to a point in the system where turbulence and flow patterns assure good mixing with the water being treated.

Dosage Reqdrd 1o Adgeve 90%

Inhibition of Vious Microbes*

1X _

120-i 40-20Od~

us I

s s

I w

w I

Bade&a ftm a

  • NXl103 [] D8NA O3Gk~mkbdelid Fungi

(>Based on b studes uskig pure ai s; bwest dosage Idicates superior perbranoe.)

wv w.gebev.com wCme21w

Dilution s'. This blended product is best fed neat (undi-luted) from the storage container.

Compatible Materials - Spectrus NX1 103 is compati-ble with the following materials of construction: 316L Stainless; Hastalloy 825; High Density Cross-linked Polyethylene; Teflon; PVC; Buna N; Buna S; Ethylene Propylene Resin.

Avoid: 304 and 316, Stainless; High Density Polypropylene; Litharge Viton.

This product may be fed using the PaceSetterTM Control system.

GENERAL PROPERTIES Physical properties of Spectrus NXII03 are shown on the Material Safety Data Sheet, a copy of which is available on request PACKAGING INFORMATION Spectrus NX1103 is a liquid blend available in a wide-variety of containers and delivery methods, induding GE Betzs ChemSureTm Drumless Delivery Services.

STORAGE Protect from extreme temperatures. Store in a cool, ventilated location. Keep containers dosed when not in use. Store away from oxidizers.

SAFETY PRECAUTIONS Use of eye protection (goggles and face shield) and gauntlet-type rubber gloves is required when handling this product. See section 7 of the MSDS for additional information on recommended personal protective equipment.

GENERAL INFORMATION EPA Registration Number 3876-121 www.gebetz com PKC 7Z 0211 C= W O WEd, loc. All lights ramer.