Secondary Containment Isolation Instrumentation 3.3.6.2 Table 3.3.6.2-1 (page 1 of 1)

Secondary Containment Isolation Instrumentation APPUCABLE MODES OR REQUIRED OTHER CHANNELS SPECIFIED PER SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS TRIP SYSTEM REQUIREMENTS VALUE

1.

Reactor Vessel Water 1.2.3.

2 SR 3.3.6.2.1

>-42 Inches Level - Low Low (Level 2)

(a)

SR 3.3.62.2 SR 3.3.62.3 SR 3.3.62.4

2.

Drywell Pressure - High 1.2.3 2

SR 3.3.6.2.2 1.84 psIg SR 3.3.623 SR 3.3.62.4

3.

Reactor Building Ventilation 1.2.3.

2 SR 3.3.6.2.1 49 mRihr Exhaust Plenum (a),(b)

SR 3.3.6.2.2 Radiation - High SR 3.3.62.3 SR 3.3.6.2.4 I

I I

(a)

During operations with a potential for draining the reactor vessel.

(b)

During CORE ALTERATIONS and during movement of irradiated fuel assemblies in secondary contatnmenL Amendment 212 3.3-57

CREF System Instrumentation 3.3.7.1 Table 3.3.7.1-1 (page 1 of 1)

Control Room Emergency Filter System Instrumentation APPLICABLE MODES OR REQUIRED OTHER CHANNELS SPECIFIED PER TRIP SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS SYSTEM REQUIREMENTS VALUE

1. Reactor Vessel Water 1.2.3, 2

SR 3.3.7.1.1

>-42 Inches Level - Low Low (Level 2)

(a)

SR 3.3.7.1.2 SR 3.3.7.1.3 SR 3.3.7.1.4

2. Drywell Pressure - High 1,2.3 2

SR 3.3.7.12

<1.84 psig SR 3.3.7.1.3 SR 3.3.7.1.4

3. ReactorBuIldingVentilation 1.2,3.

2 SR 3.3.7.1.1 549 mR/hr Exhaust Plenum (a).(b)

SR 3.3.7.1.2 Radiation - High SR 3.3.7.1.3 SR 3.3.7.1A (a)

During operaUons wth a potenal for drainng the reactor vessel.

(b)

During CORE ALTERATIONS and durlng movement of hradiated fuel assembfles In the secondary containment I

I I

Amendment 212 3.3-63