ML052270342

From kanterella
Jump to navigation Jump to search

Technical Specifications, Emergency Specification Change Request, Lake Water Maximum Temperature Limit
ML052270342
Person / Time
Site: Nine Mile Point 
Issue date: 08/12/2005
From: Colburn T
NRC/NRR/DLPM/LPD1
To: Spina J
Nine Mile Point
References
TAC MC8061
Download: ML052270342 (1)


Text

LIMITING CONDITION FOR OPERATION SURVEILLANCr= REQUIREMENT LIMITIN CONDITION FOR OPERATION SURVEILLANCE flFOUIRFMFNT t

I

f.

The containment spray system shall be considered operable by verifying that lake water temperature does not exceed 830F.

g.

If specification Tf" cannot be met commence shutdown within one hour and be in hot shutdown within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> and cold shutdown within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

f.

Lake Water Temperature Record at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> when latest recorded water temperature is greater than or equal to 75TF and at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> when the latest recorded water temperature Is greater than or equal to 790F.

AMENDMENT NO. 442, 190 161