PAM Instrumentation 3.3.3 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME RCS Cold Leg Temperature (Wide Range) channel inoperable and no OPERABLE SG Pressure channel for the associated SG.
D. Required Action and D.1 Enter the Condition Immediately associated Completion referenced in Table 3.3.3-1 Time of Condition C not for the channel or train.
met.
E. As required by Required E.1 Be in MODE 3.
6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Action D.1 and referenced in AND Table 3.3.3-1.
E.2 Be in MODE 4.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> F. As required by Required F.1 Initiate action in Immediately Action D.1 and accordance with referenced in Specification 5.6.6.
Table 3.3.3-1.
SURVEILLANCE REQUIREMENTS
- NOTE -
SR 3.3.3.1 and SR 3.3.3.3 apply to each PAM instrumentation Function in Table 3.3.3-1.
SURVEILLANCE FREQUENCY SR 3.3.3.1 Perform CHANNEL CHECK for each required 31 days instrumentation channel that is normally energized.
SR 3.3.3.2 Perform CHANNEL CALIBRATION of the following:
92 days
- a.
Function 22, RWST Level Instruments.
INDIAN POINT 2 3.3.3 - 2 Amendment No. 243
PAM Instrumentation 3.3.3 Table 3.3.3-1 (page 1 of 1)
Post Accident Monitoring Instrumentation CONDITION FUNCTION REQUIRED CHANNELS REFERENCED FROM REQUIRED ACTION D.1
- 1.
Reactor Coolant System (RCS) Hot Leg Temperature (Wide Range)
- 2.
RCS Cold Leg Temperature (Wide Range)
- 3.
RCS Pressure (Wide Range)
- 4.
Reactor Vessel Level Indication System (RVLIS)
- 5.
Containment Sump Water Level (Recirculation Sump)
- 6.
Containment Water Level (Containment Sump)
- 7.
Containment Pressure
- 8.
Containment Pressure (High Range)
- 9.
Containment Area Radiation (High Range)
- 10.
NOT USED
- 11.
Pressurizer Level
- 12.
Steam Generator (SG) Water Level (Narrow Range)
- 13.
Steam Generator Water Level (Wide Range)
- 14.
Condensate Storage Tank level
- 15.
Core Exit Temperature - Quadrant 1
- 16.
Core Exit Temperature - Quadrant 2
- 17.
Core Exit Temperature - Quadrant 3
- 18.
Core Exit Temperature - Quadrant 4
- 19.
Auxiliary Feedwater Flow
- 20.
Steam Generator Pressure
- 21.
RCS Subcooling Margin Monitor
- 22.
RWST Level 1 per loop (a) 1 per loop (b) 2 2
2 3
2 2
2 2
2 per steam generator 4
2 2 trains(c) 2 trains(c) 2 trains(c) 2 trains(C) 4 2 per steam line 2
2 E
E E
F E
E E
E F
I E
E E
F E
E E
E E
E E
E (a)
The required redundant channel for each of the four loops of RCS hot leg temperature is a qualified Core Exit Temperature train in the quadrant associated with that loop.
(b)
The required redundant channel for each of the four loops of RCS cold leg temperature is any channel of steam generator pressure for that loop.
(c)
A CET train consists of two core exit thermocouples (CETs).
INDIAN POINT 2 3.3.3 - 4 Amendment No. 243
Hydrogen Recombiners 3.6.8 3.6 CONTAINMENT SYSTEMS 3.6.8 Not Used INDIAN POINT 2 3.6.8 - I Amendment No. 243
PAM Instrumentation 3.3.3 Table 3.3.3-1 (page 1 of 2)
Post Accident Monitoring Instrumentation FUNCTION 1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
Neutron Flux RCS Hot Leg Temperature (Wide Range)
(TM )
RCS Cold Leg Temperature (Wide Range)
(Tcold)
RCS Pressure (Wide Range)
Reactor Vessel Water Level Containment Water Level (Wide Range)
Containment Water Level (Recirculation Sump)
Containment Pressure Automatic Containment Isolation Valve.
Position Containment Area Radiation (High Range)
NOT USED Pressurizer Level SG Water Level (Narrow Range)
SG Water Level (Wide Range) and Auxiliary Feedwater Flow NOT USED Steam Generator Pressure Condensate Storage Tank Level Core Exit Thermocouples-Quadrant 1 Core Exit Thermocouples-Quadrant 2 Core Exit Thermocouples-Quadrant 3 Core Exit Thermocouples-Quadrant 4 Main Steam Line Radiation Gross Failed Fuel Detector RCS Subcooling Margin REQUIRED CHANNELS 2
1 per loop 1 per loop 2
2 2
2 2
2 per penetration flow path(axb) 2 2
2 per SG 1 each per SG 2 per SG 2
2 (d) 2 (d) 2 (d) 2 (d) 1 per steam line 2
2 CONDITION REFERENCED FROM REQUIRED ACTION D.1 F
E E
E E
E E
E F
F E
E E
E F
E E
E E
F F
E SR 3.3.3.2 FREQUENCY 24 months 24 months 24 months 24 months 24 months 24 months 24 months 18 months 24 months 24 months 24 months 24 months 24 months, SGL 18 months, AFF 24 months 24 months 24 months 24 months 24 months 24 months 24 months 24 months 24 months I
See NOTES, next page.
INDIAN POINT 3 3.3.3-4 Amendment 228
PAM Instrumentation 3.3.3 TABLE 3.3.3-1 (page 2 of 2)
Post Accident Monitoring Instrumentation NOTES:
(a) Not required for isolation valves whose associated penetration is isolated by at least one closed and deactivated automatic valve, closed manual valve, blind flange, or check valve with flow through the valve secured.
(b) Only one position indication channel is required for penetration flow paths with only one installed control room indication channel.
(c) A channel consists of two core exit thermocouples (CETs).
INDIAN POINT 3 3.3.3-5 Amendment 228
Hydrogen Recombiners 3.6.8 3.6 CONTAINMENT SYSTEMS 3.6.8 Not Used INDIAN POINT 3 3.6.8-1 Amendment 22P