February 2005 Monthly Operating Reports for San Onofre Nuclear Generating Station Units 2 and 3
ML050810489
Person / Time
Site: San Onofre  
Issue date: 03/15/2005
From: Scherer A
Southern California Edison Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML050810489 (9)


Text

SOUTHERN CALIFORNIA EDISON1 An EDISON INTERNATIONALS Company A. Edward Scherer Manager of Nuclear Regulatory Affairs March 15, 2005 U. S. Nuclear Regulatory Commission Document Control Desk Washington, D.C. 20555

Subject:

Docket Nos. 50-361 and 50-362 Monthly Operating Reports for February 2005 San Onofre Nuclear Generating Station, Units 2 and 3 Gentlemen:

As required by Technical Specification 5.7.1.4 of Facility Operating Licenses NPF-10 and NPF-15, this letter provides the Monthly Operating Reports for February 2005 for San Onofre Nuclear Generating Station, Units 2 and 3, Attachments 1 and 2, respectively.

If you have any questions, please contact Mr. C. E. Williams at (949) 368-6707.

Sincerely, Attachments 1 & 2 cc:

B. S. Mallett, Regional Administrator, NRC Region IV B. M. Pham, NRC Project Manager, San Onofre Units 2 & 3 C. C. Osterholtz, NRC Senior Resident Inspector, San Onofre Units 2 & 3 P.O. Box 128 San Clemente, CA 92674-0128 949-368-7501 Fax 949-368-7575

'A4' Monthly Operating Report, February 2005 San Onofre Nuclear Generating Station, Unit 2

MONTHLY OPERATING REPORT SAN ONOFRE NUCLEAR GENERATING STATION UNIT 2 February 2005 Docket No:

Unit Name:

Date:

Completed by:

Telephone:

50-361 SONGS - 2 March 15, 2005 C. E. Williams (949) 368-6707 Page 2 of 4 OPERATING DATA REPORT I I Design Electrical Rating (Net MWe) 1070 2 l Maximum Dependable Capacity (Net MWe) l 1070 1

This Month Yr-to-Date Cumulative 3

Number of Hours in Period 672 1,416 188,785 4

Numberof Hours Reactor Was Critical*

261 1,005 154,236 5

Hours Generator On-line*

229 973 152,166 6

Unit Reserve Shutdown Hours*

0 0

0 7

Net Electrical Energy Generated (MWh)*

231,691 1,015,634 163,199,614

  • Rounded

MONTHLY OPERATING REPORT SAN ONOFRE NUCLEAR GENERATING STATION UNIT 2 February 2005 Docket No:

Unit Name:

Date:

Completed by:

Telephone:

50-361 SONGS - 2 March 15, 2005 C. E. Williams (949) 368-6707 Page 3 of 4 UNIT SHUTDOWNS Number 2005-01 Date (YY/MMWDD) 05102103 Type (1)

F Duration (Hours)*

109.7 Reason (2)

H Method of Shutting Down the Reactor (3) 3 Cause/Corrective Actions/Comments Automatic Reactor trip following Unit (Include LER number, if any)

Auxiliary Transformer differential relay trip. This event resulted from an invalid actuation during Digital Fault Recorder testing and was reported in LER 2-2005-001, dated March 4, 2005.

Number 2005-02 Date (YY/MMIDD) 05102/15 Type (1)

F Duration (Hours)*

333.5 Reason (2)

A Method of Shutting Down the Reactor (3) 1 Cause/Corrective Actions/Comments Reactor manually shut down to allow (Include LER number, if any) repair of Component Cooling Water System valve 2HV6500. This event will be reported in LER 2-2005-002 on or before April 15, 2005.

  • Rounded (1) F-Forced S-Scheduled (2) Reason:

A-Equipment Failure (Explain)

B-Maintenance or Test C-Refueling D-Reguiatory Restriction E-Operator Training & Ucense Examination F-Administrative G-Operational Error (Explain)

H-Other (Explain)

(3) Method:

1-Manual 2-Manual Trip/Scram 3-Automatic Trip/Scram 4-Continuation from Previous Month (Explain) 5-Other (Explain)

MONTHLY OPERATING REPORT SAN ONOFRE NUCLEAR GENERATING STATION UNIT 2 February 2005 Docket No:

Unit Name:

Date:

Completed by:

Telephone:

50-361 SONGS - 2 March 15, 2005 C. E. Williams (949) 368-6707 Page 4 of 4

SUMMARY

OF OPERATING EXPERIENCE FOR THE MONTH Date Time 02/01/05 0000 Unit in Mode 1.

02/03105 1223 Automatic Reactor trip following Unit Auxiliary Transformer differential relay trip. Unit entered Mode 3.

02/06/05 1711 Unit entered Mode 2.

02/06/05 1750 Reactor critical.

02/07/05 0345 Unit entered Mode 1.

02108/05 0209 Turbine and Main Generator synchronized to the grid.

02/08/05 2317 Unit reaches essentially full power.

02/10/05 2315 Train "B" Containment Spray System declared inoperable due to Component Cooling Water valve 2HV6500 not fully opening or closing.

Entered 7-day shutdown action in accordance with plant Technical Specifications.

02/14/05 2155 Unit shutdown commenced to repair 2HV6500.

02/15/05 0231 Manually tripped Turbine and Main Generator. Unit offline.

02/15/05 0241 Manually tripped Reactor from approximately 9% power. Unit entered Mode 3.

02/15/05 0902 Unit entered Mode 4.

02/15/05 1804 Unit entered Mode 5.

02/28/05 2400 Unit in Mode 5.

Note: There were no challenges to the pressurizer safety valves during the month.

Monthly Operating Report, February 2005 San Onofre Nuclear Generating Station, Unit 3

MONTHLY OPERATING REPORT SAN ONOFRE NUCLEAR GENERATING STATION UNIT 3 February 2005 Docket No:

Unit Name:

Date:

Completed by:

Telephone:

50-362 SONGS - 3 March 15, 2005 C. E. Williams (949) 368-6707 Page 2 of 4 OPERATING DATA REPORT I 1 Design Electrical Rating (Net MWe) 1 1080 2

Maximum Dependable Capacity (Net MWe) 1080 This Month Yr-to-Date Cumulative 3

Number of Hours in Period 672 1,416 I

183,336 4

Number of Hours Reactor Was Critical*

672 1,416 151,206 5

Hours Generator On-line*

672 1,416 148,980 6

Unit Reserve Shutdown Hours*

0 0

0 7

Net Electrical Energy Generated (MWh)*

753,859 1,431,728 1 157,949,573

  • Rounded

MONTHLY OPERATING REPORT SAN ONOFRE NUCLEAR GENERATING STATION UNIT 3 February 2005 Docket No:

Unit Name:

Date:

Completed by:

Telephone:

50-362 SONGS - 3 March 15, 2005 C. E. Williams (949) 368-6707 Page 3 of 4 UNIT SHUTDOWNS Number N/A Date (YY/MM/DD)

N/A Type (1)

N/A Duration (Hours)*

N/A Reason (2)

N/A Method of Shutting Down the Reactor (3)

N/A Cause/Corrective Actions/Comments N/A (Include LER number, if any)

I Rounded (1) F-Forced S-Scheduled (2) Reason:

A-Equlpment Failure (Explain)

B-Maintenanoe or Test C-Refueling D-Regulatory Restriction E-Operator Training & Lcense Examination F-Administrative G-Operational Error (Explain)

H-Other (Explain)

(3) Method:

1-Manual 2-Manual Trip/Scram 3-Automatic Trip/Scram 4-Continuation from Previous Month (Explain) 5-Other (Explain)

MONTHLY OPERATING REPORT SAN ONOFRE NUCLEAR GENERATING STATION UNIT 3 February 2005 Docket No:

Unit Name:

Date:

Completed by:

Telephone:

50-362 SONGS - 3 March 15, 2005 C. E. Williams (949) 368-6707 Page 4 of 4

SUMMARY

OF OPERATING EXPERIENCE FOR THE MONTH Date Time 02/01/05 l 0000 I Unit in Mode 1.

02/28/05 l 2400 l Unit in Mode 1.

Note: There were no challenges to the pressurizer safety valves during the month.