SUBJECT:
EDWIN I. HATCH NUCLEAR PLANT - RESPONSE TO INSPECTION REPORT
NOS. 05000321/2003006 AND 05000366/2003006
Dear Mr. Sumner:
In your letter dated October 1, 2003, in response to our Triennial Fire Protection Inspection
Report 05000321/2003006 and 05000366/2003006, you made several requests. One of those
requests was that the NRC withdraw Non-Cited Violation (NCV) 50-366/03-06-04, Unapproved
Manual Operator Actions for Post-Fire SSD. In our letter to you dated November 18, 2003, we
stated that we were still reviewing additional information that you had provided in response to
that NCV. We have now completed our review of your information related to that NCV and are
advising you of our decision. Details of our review are in the enclosure to this letter, titled
"Evaluation of Licensee Information."
Based on our review of your additional information, we are withdrawing the examples of the
NCV related to a high pressure coolant injection (HPCI) pump runaway. Your information has
substantiated that the HPCI pump is not vulnerable to cable failures that could cause a runaway
condition due to fires in III.G.2 areas, where plant shutdown would be from the control room.
Since this information differs from your Safe Shutdown Analysis (SSA) and Fire Procedure, we
expect that you will consider updating those documents accordingly.
However, we have concluded that your information did not provide a valid basis for withdrawing
the example of the NCV related to the local manual operator action for repowering the battery
chargers. Also, as explained in the enclosure, you may need to perform additional reviews to
verify that this operator action can be performed (will not be affected by the fire) for fires in all
fire areas where the action may be needed.
In accordance with 10 CFR 2.790 of the NRC's "Rules of Practice," a copy of this letter will be
available electronically for public inspection in the NRC Public Document Room or from the
Publically Available Records (PARS) component of the NRC's document system (ADAMS).
xL4
3
unresolved item. After further team in-office review of the NRC policy for documenting
such issues as Green findings, as stated in NRC Inspection Procedure 71111.05, Fire
Protection, this issue was recharacterized as a Green finding and NCV. However, the
fact that the issue was recharacterized as an NCV after the inspection team left the site
does not constitute a basis for the NRC to withdraw the NCV.
2.
The NRC does not agree with this licensee statement. The concern is not an assumed
loss of offsite power concurrent with a fire. Instead, the concern is that fires in certain
areas of the Hatch plant can cause a loss of offsite power. The Hatch SSA
conservatively assumes that a fire in any fire area can cause a loss of offsite power. A
more detailed NRC review after receipt of your October 1, 2003, letter indicated that
fires in two of the four focus areas for the inspection (4KV switchgear rooms 2E and 2F)
could cause fire damage to cables that could result in a loss of offsite power to
additional safety-related alternating current (AC) busses and consequently a loss of
power to battery chargers that are required to maintain hot shutdown conditions. The
Hatch design is such that following such a loss of offsite power, the emergency diesel
generators would automatically start but the battery chargers would not be automatically
repowered. The station batteries are designed to provide vital direct current (DC)
electrical power for two hours, and the battery chargers would have to be locally
manually reenergized within that time to maintain the vital DC electrical power that is
needed for instrumentation and control that is required to maintain the reactor in a hot
shutdown condition.
10 CFR 50, Appendix R, Section III.G.2 requires that, where fire damage to cables could
prevent operation of redundant trains of equipment necessary to maintain hot shutdown
conditions, the cables must be physically protected from such fire damage by one of
three specified methods. Local manual operation of equipment is not one of the three
specified methods. Further, the licensee had received no NRC exemption from this
requirement for power to the battery chargers. Consequently, this licensee statement
does not constitute a basis for the NRC to withdraw the NCV.
3.
The NRC agrees with this licensee statement. In the referenced documents, the
licensee requested an exemption from the requirements of Appendix R,Section III.J for
8-hour battery-powered emergency lights in the control room and the NRC granted that
exemption. However, a review of the referenced documents by the Region II Counsel
determined that they do not constitute an NRC approval to deviate from the Section
III.G.2 requirement for physical protection of cables from fire damage that could result in
a loss of power to the battery chargers and consequently the instrumentation and
controls that are required to maintain hot'shutdown conditions. Consequently, this
licensee statement does not constitute a basis for the NRC to withdraw the NCV.
4.
The NRC agrees that the Hatch abnormal procedures that would be used following a
loss of offsite power, without a fire, would include locally manually repowering the
battery chargers. However, the specific procedure step that is addressed in this NCV is
in the Fire Procedure, which would only be used in the event of a fire. As described
above, 10 CFR 50, Appendix R, Section III.G.2 requires that, where fire damage to
cables could prevent operation of redundant trains of equipment necessary to maintain
hot shutdown conditions, the cables must be physically protected from such fire damage
by one of three specified methods. Local manual operation of equipment is not one of