Hqtrs. Morning Report - H-2005-0002 - Halon System Piping Incorrectly Connected
ML050450153
Person / Time
Site: Wolf Creek, Pilgrim, Limerick, Callaway, South Texas
Issue date: 01/21/2005
From: John Kramer
NRC/NRR/DIPM/IROB
To:
Gray, Kathy, NRR/DIPM/IROB, 301-415-1166
References
H-2005-0002
Download: ML050450153 (2)


Text

Morning Report Date: JAN 21, 2005 PRIORITY ATTENTION REQUIRED MORNING REPORT -HEADQUARTERS Licensee/Facility:

Notification:

H-2005-0002 01/12/2005 MR Number:

WOLF CREEK NUCLEAR OPERATING CORP.

[1] W-4-LP Fulton, Missouri Dockets:

[1] W-4-LP 05000483 Callaway Union Electric Co.

Plymouth, Massachusetts Dockets:

[1] GE-3 05000293 Pilgrim Entergy Nuclear Generation Company Philadelphia, Pennsylvania Dockets:

[2] GE-4 05000353 Limerick Exelon Generation Co., LLC Wadsworth, Texas Dockets:

[1] W-4-LP, [2] W-4-LP 05000498 05000499 South Texas Project STP Nuclear Operating Co.

Date:

Wolf Creek Call from ENS Burlington, Kansas 050-00482 Dockets:

Halon System Piping Incorrectly Connected

Subject:

On January 12, 2005, the Callaway and Wolf Creek licensees notified the NRC Operations Center (EN 41326 and EN 41327) of incorrectly connected piping in the halon fire suppression systems at both facilities. The actuation lines to the manual-pneumatic actuators in the halon systems in five of six fire areas were found to be reversed. The licensee contacted the vendor and confirmed that the halon banks may not have discharged as required with the lines reversed.

The actuation lines were reconnected in the proper configuration and all systems returned to a functional condition.

The regional offices are in the process of ensuring their respective licensees are aware of the issue and are assessing the extent of condition. As of January 19, similar incorrect halon piping issues have been identified at Limerick Unit 2, Pilgrim, and South Texas Project.