ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 3 of 5)

Engineered Safety Feature Actuation System Instrumentation APPLICABLE MODES OR OTHER NOMINAL SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE TRIP FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE SETPOINT

4.

Steam Line Isolation (continued)

(2) Negative Rate - High 3(b)(c) 3 per steam line D

SR 3.3.2.1 SR 3.3.2.5 SR 3.3.2.8 SR 3.3.2.9

< 120(d) psi 100(d) psi

5.

Turbine Trip and Feedwater Isolation

a.

Turbine Trip (1) Automatic Actuation Logic and Actuation Relays (2) SGWater Level-High High (P-1 4) 1,2 1,2 2 trains 3 per SG I

SR 3.3.2.2 SR 3.3.2.4 SR 3.3.2.6 J

SR 3.3.2.1 SR 3.3.2.2 SR 3.3.2.4 SR 3.3.2.5 SR 3.3.2.6 SR 3.3.2.8 SR 3.3.2.9 NA

< 85.6%

NA 83.9%

(3) Safety Refer to Function 1 (Safety Inlectlon) for all Initiation functions and requirements. See Item Injection 5.a.(1) for Applicable MODES.

b.

Feedwater Isolation (1) Automatic Actuation Logic and Actuation Relays (2) SGWater Level-High High (P-14) 1,2 (e), 3(e) 1,2 (e), 3(e) 2 trains 3 per SG H

SR 3.3.2.2 SR 3.3.2.4 SR 3.3.2.6 D

SR 3.3.2.1 SR 3.3.2.2 SR 3.3.2.4 SR 3.3.2.5 SR 3.3.2.6 SR 3.3.2.8 SR 3.3.2.9 NA

< 85.6 NA 83.9%

(continued)

(b)

Except when all MSIVs are closed and de-activated.

(c)

Trip function automatically blocked above P-11 (Pressurizer Pressure) Interlock and may be blocked below P-i1 when Steam Line Isolation Steam Line Pressure-Low Is not blocked.

(d)

Time constant utilized In the rate/lag controller Is > 50 seconds.

(e)

Except when all MFIVs, MFCVs, and associated bypass valves are closed and de-activated or Isolated by a closed manual valve.

McGuire Units 1 and 2 3.3.2-12 Amendment Nos. 224 and 206

ESFAS Instrumentation B 3.3.2 BASES APPLICABLE SAFETY ANALYSES, LCO, and APPLICABILITY (continued)

Steam Line Pressure-Low Function must be OPERABLE in MODES 1, 2, and 3 (above P-1 1), with any main steam valve open, when a secondary side break or stuck open valve could result in the rapid depressurization of the steam lines. This signal may be manually blocked by the operator below the P-11 setpoint. Below P-1 1, an inside containment SLB will be terminated by automatic actuation via Containment Pressure-High High. Stuck valve transients and outside containment SLBs will be terminated by the Steam Line Pressure-Negative Rate-High signal for Steam Line Isolation below P-i1 when Steam Line Isolation Steam Line Pressure-Low has been manually blocked. The Steam Line Isolation Function is required in MODES 2 and 3 unless all MSIVs are closed and de-activated. This Function is not required to be OPERABLE in MODES 4, 5, and 6 because there is insufficient energy in the secondary side of the unit to have an accident.

(2)

Steam Line Pressure-Negative Rate-High Steam Line Pressure-Negative Rate-High provides closure of the MSIVs for an SLB when less than the P-1 1 setpoint, to maintain at least one unfaulted SG as a heat sink for the reactor, and to limit the mass and energy release to containment. When the operator manually blocks the Steam Line Pressure-Low main steam isolation signal when less than the P-1 1 setpoint, the Steam Line Pressure-Negative Rate-High signal is automatically enabled. Steam Line Pressure-Negative Rate-High provides no input to any control functions.

Thus, three OPERABLE channels are sufficient to satisfy requirements with a two-out-of-three logic on each steam line.

Steam Line Pressure-Negative Rate-High must be OPERABLE in MODE 3 when less than the P-11 setpoint, when a secondary side break or stuck open valve could result in the rapid depressurization of the steam line(s). In MODES I and 2, and in MODE 3, when above the P-1I setpoint, this signal is automatically disabled and the Steam Line Pressure-Low signal is automatically enabled. The Steam Line Isolation Function is required to be OPERABLE in McGuire Units 1 and 2 B 3.3.2-1 7 Revision No. 62